![Page 1: Nexans, screened connector...Medium voltage separable connectors and bushings- Interface B -covers_DEFINITIEF.indd 1 16-03-2006 10:25:09 10/2011 • Nexans Network Solutions N.V. Div](https://reader034.vdocuments.us/reader034/viewer/2022051806/5ffb0f57b8342274b45ec3d3/html5/thumbnails/1.jpg)
![Page 2: Nexans, screened connector...Medium voltage separable connectors and bushings- Interface B -covers_DEFINITIEF.indd 1 16-03-2006 10:25:09 10/2011 • Nexans Network Solutions N.V. Div](https://reader034.vdocuments.us/reader034/viewer/2022051806/5ffb0f57b8342274b45ec3d3/html5/thumbnails/2.jpg)
• Salesin90+ countries• 600 employeesworldwide• Morethan50 years of experience in cable accessories• Nexansprovides installer training andcablepreparationtools• Committedtoquality:ISO9001 certifiedand5electricallaboratories• TheleadingEuropeandesignerand manufacturerofpoweraccessories
Nexans,global leader in cables
• Totalsalesof6 billion eurosin2010• The most complete rangeofcablesandcablingsystems• Plantsin40 countries• 23,700 employeesworldwide• Completeoffersfor every market segment
Expert inpower cable accessories
![Page 3: Nexans, screened connector...Medium voltage separable connectors and bushings- Interface B -covers_DEFINITIEF.indd 1 16-03-2006 10:25:09 10/2011 • Nexans Network Solutions N.V. Div](https://reader034.vdocuments.us/reader034/viewer/2022051806/5ffb0f57b8342274b45ec3d3/html5/thumbnails/3.jpg)
Globalexpert
Track record of more than 50 years in power accessories
![Page 4: Nexans, screened connector...Medium voltage separable connectors and bushings- Interface B -covers_DEFINITIEF.indd 1 16-03-2006 10:25:09 10/2011 • Nexans Network Solutions N.V. Div](https://reader034.vdocuments.us/reader034/viewer/2022051806/5ffb0f57b8342274b45ec3d3/html5/thumbnails/4.jpg)
Expert in separable, screened connectors
100 %
80 %
60 %
80 %
60 %
20 % 20 %
40 % 40 %
elbowconnector
equipmentbushing
equipment
cable
Ascreenedconnectorisanencapsulated,safetotouchterminationusedtoconnectMVcablestotheepoxybushingsofequipment(suchastransformers,switchgear,motors...).
Stress distribution inatypicalcombination.Thisfigureshowshowtheelectricalfieldremainssafely inside the cable, accessory, bushing andequipmentwhenusingscreenedconnectors.
![Page 5: Nexans, screened connector...Medium voltage separable connectors and bushings- Interface B -covers_DEFINITIEF.indd 1 16-03-2006 10:25:09 10/2011 • Nexans Network Solutions N.V. Div](https://reader034.vdocuments.us/reader034/viewer/2022051806/5ffb0f57b8342274b45ec3d3/html5/thumbnails/5.jpg)
Compact, safe & secure
Safety provided by a 3 mm
thick conductive
rubber layer
![Page 6: Nexans, screened connector...Medium voltage separable connectors and bushings- Interface B -covers_DEFINITIEF.indd 1 16-03-2006 10:25:09 10/2011 • Nexans Network Solutions N.V. Div](https://reader034.vdocuments.us/reader034/viewer/2022051806/5ffb0f57b8342274b45ec3d3/html5/thumbnails/6.jpg)
Interface type Current 12 kV 24 kV 36 kV
A 250A
B 400A
C 630A1250A
Overviewoftheproductfamily
• Nominimumdistancesrequired: canbeinstalledincompactsubstations• Safe totouchaccidentallywhenenergized• Maintenancefree• Quick and easytoinstallwithoutspecialtools• Easytodisconnect• Fullywatertight• DegreeofprotectionIP67: dusttight&immersioninwater• ResistanttoUV,ozone,chemicals,mechanicalabuse• Temperaturerangefrom-30°Cto+110°C• Offersmanytestoptions:capacitivetestpoint,cabletests...• Acompleterangefor12 to 42 kV• Canbeusedoutdoorswithoutcablebox
Advantages of screened connector systems
152SR 158LR
400LB 430TB 440TB
400LR 400TE
K152SR K158LR
K400LB K430TB K440TB
K400LR K400TE
M400TB M430TB M440TB
M400LR M400TE
![Page 7: Nexans, screened connector...Medium voltage separable connectors and bushings- Interface B -covers_DEFINITIEF.indd 1 16-03-2006 10:25:09 10/2011 • Nexans Network Solutions N.V. Div](https://reader034.vdocuments.us/reader034/viewer/2022051806/5ffb0f57b8342274b45ec3d3/html5/thumbnails/7.jpg)
A complete line of accessories
with possibilities for voltage detection,cable testing andmultiple arrangement
![Page 8: Nexans, screened connector...Medium voltage separable connectors and bushings- Interface B -covers_DEFINITIEF.indd 1 16-03-2006 10:25:09 10/2011 • Nexans Network Solutions N.V. Div](https://reader034.vdocuments.us/reader034/viewer/2022051806/5ffb0f57b8342274b45ec3d3/html5/thumbnails/8.jpg)
Up to 24 kV - 250 A
158LRINTERFACEA
ELBOWCONNECTOR
Separable connector
type
VoltageUm(kV)
CurrentIr
(A)
Conductor sizes (mm2)(for information only)
min max
158LR/G
158LR
K158LR/G
K158LR
12
12
24
24
250
250
250
250
16
70
16
25
70
95
25
95
Design
Separableconnectorcomprising:
1.ConductiveEPDMinsert.
2.ConductiveEPDMjacket.
3.InsulatingEPDMlayermouldedbetween
theinsertandthejacket.
4.TypeA-250Ainterfaceasdescribed
byCENELECEN50180and50181.
5.Conductorconnector.
6.Earthinglead(-/Gversiononly).
1
3
221 mm
160 mm
2
4
5
6
![Page 9: Nexans, screened connector...Medium voltage separable connectors and bushings- Interface B -covers_DEFINITIEF.indd 1 16-03-2006 10:25:09 10/2011 • Nexans Network Solutions N.V. Div](https://reader034.vdocuments.us/reader034/viewer/2022051806/5ffb0f57b8342274b45ec3d3/html5/thumbnails/9.jpg)
Reliability guaranteed by the factorytesting of every part on partial discharges and industrial power frequency
![Page 10: Nexans, screened connector...Medium voltage separable connectors and bushings- Interface B -covers_DEFINITIEF.indd 1 16-03-2006 10:25:09 10/2011 • Nexans Network Solutions N.V. Div](https://reader034.vdocuments.us/reader034/viewer/2022051806/5ffb0f57b8342274b45ec3d3/html5/thumbnails/10.jpg)
Equipmentbushing
type
VoltageUr
(kV)
CurrentIr
(A)
Dimensions (mm)
A B
180AR-1
K180AR-1
180AR-2
K180AR-2
180AR-3
K180AR-3
12
24
12
24
12
24
250
250
250
250
250
250
222
222
284
284
171
171
106
106
168
168
55
55
Up to 24 kV - 250 A
180AR-1 /-2 /-3INTERFACEA
EQUIPMENTBUSHING
B
A
28
8
19
Dia. 110
Dia. 75
Minimum oil level:- 12 kV: 40 mm- 24 kV: 50 mm
M10
Dia.16Epoxybushingforuseinequipment
insulatedwithoilfluid,typicallyfortransformers,switchgear,capacitors...
![Page 11: Nexans, screened connector...Medium voltage separable connectors and bushings- Interface B -covers_DEFINITIEF.indd 1 16-03-2006 10:25:09 10/2011 • Nexans Network Solutions N.V. Div](https://reader034.vdocuments.us/reader034/viewer/2022051806/5ffb0f57b8342274b45ec3d3/html5/thumbnails/11.jpg)
Zero maintenance
![Page 12: Nexans, screened connector...Medium voltage separable connectors and bushings- Interface B -covers_DEFINITIEF.indd 1 16-03-2006 10:25:09 10/2011 • Nexans Network Solutions N.V. Div](https://reader034.vdocuments.us/reader034/viewer/2022051806/5ffb0f57b8342274b45ec3d3/html5/thumbnails/12.jpg)
Up to 36 kV630 A (800 A)
430TBINTERFACEC
TEECONNECTOR
Design
1.ConductiveEPDMinsert.
2.ConductiveEPDMjacket.
3.InsulatingEPDMlayermoulded
betweentheinsertandthejacket.
4.TypeCinterfaceasdescribedby
CENELECEN50180and50181.
5.Conductorconnector.
6.Basicinsulatingplug(withVDpoint).
7.Cablereducer.
8.Conductiverubbercap.
9.Clampingscrew.
10.Earthinglead.
Thescreenbreakdesignenablescableoutersheathtestingwithoutremovingordismantlingtheconnector.
Separable connector
type
VoltageUm(kV)
CurrentIr
(A)
CurrentIr (A)
Wheninstalledonanappropriateequipmentbushing
Conductor sizes(mm2)
min max
430TBK430TBM430TB
122436
630630630
800800800
353550
300300240
185 mm
290 mm
(350 mmfor 36 kV)
4 9
6
1
2
3
10
7
5
8
![Page 13: Nexans, screened connector...Medium voltage separable connectors and bushings- Interface B -covers_DEFINITIEF.indd 1 16-03-2006 10:25:09 10/2011 • Nexans Network Solutions N.V. Div](https://reader034.vdocuments.us/reader034/viewer/2022051806/5ffb0f57b8342274b45ec3d3/html5/thumbnails/13.jpg)
Simplicityspeed
and ease of installation
offered by the premoulded slip-on technology
![Page 14: Nexans, screened connector...Medium voltage separable connectors and bushings- Interface B -covers_DEFINITIEF.indd 1 16-03-2006 10:25:09 10/2011 • Nexans Network Solutions N.V. Div](https://reader034.vdocuments.us/reader034/viewer/2022051806/5ffb0f57b8342274b45ec3d3/html5/thumbnails/14.jpg)
Up to 36 kV630 A (1250 A)
430TBM-P2/P3DUAL/TRIPLECABLEARRANGEMENT
FOR430TB
Design
1.TypeCinterfaceasdescribedby
CENELECEN50180and50181.
2. Busfor300PB.
3. ConductiveEPDMinsert.
4. InsulatingEPDMlayermoulded
betweentheinsertandthejacket.
5.ConductiveEPDMjacket.
6. ConductiveEPDMcap.
7. Basicinsulatingplug(withVDpoint).
8.Conductorconnector.
9. Cablereducer.
10. Earthinglead.
Separable connector
type
VoltageUm(kV)
CurrentIr
(A)
CurrentIr (A)
Wheninstalledonanappropriateequipmentbushing
Conductor sizes(mm2)
min max
430TBM-P2/P3K430TBM-P2/P3M430TBM-P2/P3
122436
630630630
125012501250
353550
300300240
Non-sizesensitive:290 mm
Sizesensitive:350 mm
105 mm
430TBMconnector
300PBMcouplingconnector
290 mm
1 2
8
3
4
5
9
7
6
10
![Page 15: Nexans, screened connector...Medium voltage separable connectors and bushings- Interface B -covers_DEFINITIEF.indd 1 16-03-2006 10:25:09 10/2011 • Nexans Network Solutions N.V. Div](https://reader034.vdocuments.us/reader034/viewer/2022051806/5ffb0f57b8342274b45ec3d3/html5/thumbnails/15.jpg)
The most
modern and automated
production facilities
in the accessories
world
![Page 16: Nexans, screened connector...Medium voltage separable connectors and bushings- Interface B -covers_DEFINITIEF.indd 1 16-03-2006 10:25:09 10/2011 • Nexans Network Solutions N.V. Div](https://reader034.vdocuments.us/reader034/viewer/2022051806/5ffb0f57b8342274b45ec3d3/html5/thumbnails/16.jpg)
Up to 36 kV - 630 A
400AR-3INTERFACEC
EQUIPMENTBUSHING
Equipmentbushing
type
VoltageUr
(kV)
CurrentIr
(A)
400AR-3
K400AR-3
M400AR-3
12
24
36
630
630
630
Epoxybushingforuseinequipmentinsulatedwithoilfluid,typicallyfortransformers,switchgear,capacitors...
Minimum oil level:-12 kV: 40 mm-24 kV: 50 mm-36 kV: 70 mm
40
Dia. 128
133
144
330
Dia. 88
Dia.25
Dia. 70M16
10
30
![Page 17: Nexans, screened connector...Medium voltage separable connectors and bushings- Interface B -covers_DEFINITIEF.indd 1 16-03-2006 10:25:09 10/2011 • Nexans Network Solutions N.V. Div](https://reader034.vdocuments.us/reader034/viewer/2022051806/5ffb0f57b8342274b45ec3d3/html5/thumbnails/17.jpg)
Resistance to the environment:
heavy pollution,humidity and condensation,extreme
temperatures,radiation, ozone,chemicals
![Page 18: Nexans, screened connector...Medium voltage separable connectors and bushings- Interface B -covers_DEFINITIEF.indd 1 16-03-2006 10:25:09 10/2011 • Nexans Network Solutions N.V. Div](https://reader034.vdocuments.us/reader034/viewer/2022051806/5ffb0f57b8342274b45ec3d3/html5/thumbnails/18.jpg)
Full catalogue
Thisdocumentisaselectionofourextendedproductrange.
We are also producer of cold and heat-shrinkable joints
andterminationsandalltypesofferrulesandlugs.Inorder
to get a full catalogue of our complete medium voltage
accessoriesrange,pleasesendusane-mail.
![Page 19: Nexans, screened connector...Medium voltage separable connectors and bushings- Interface B -covers_DEFINITIEF.indd 1 16-03-2006 10:25:09 10/2011 • Nexans Network Solutions N.V. Div](https://reader034.vdocuments.us/reader034/viewer/2022051806/5ffb0f57b8342274b45ec3d3/html5/thumbnails/19.jpg)
a Nexans company
Catalogue 2006
Medium�voltage�separable�
connectors�and�bushings
-�Interface�A�-
covers_DEFINITIEF.indd 4 16-03-2006 10:25:41
a Nexans company
Catalogue 2006
Medium�voltage�separable�
connectors�and�bushings
-�Interface�B�-
covers_DEFINITIEF.indd 1 16-03-2006 10:25:09
![Page 20: Nexans, screened connector...Medium voltage separable connectors and bushings- Interface B -covers_DEFINITIEF.indd 1 16-03-2006 10:25:09 10/2011 • Nexans Network Solutions N.V. Div](https://reader034.vdocuments.us/reader034/viewer/2022051806/5ffb0f57b8342274b45ec3d3/html5/thumbnails/20.jpg)
10/2011•NexansNetworkSolutionsN.V.Div.Euromold
poweraccessories
Germany
NEXANSPOWERACCESSORIESGERMANYGmbH
+49(0)928183060•[email protected]
Belgium
NEXANSNETWORKSOLUTIONSNV-div.EUROMOLD
+32(0)53850211•[email protected]
UnitedKingdom
NEXANSPOWERACCESSORIESLtd
+44(0)1977669966•[email protected]
France
NEXANSPOWERACCESSORIESFRANCESAS
+33(0)324277850•[email protected]
Italy
NEXANSITALIASpA
+390396434512•[email protected]