430tb - nexans · 6 01/2011 application. separable tee shape connector (bolted type) designed to...

2
6 01/2011 Application Separable tee shape connector (bolted type) designed to connect polymeric insulated cable to equipment (transformers, switchgear, motors, ...). Also connects cable to cable when using the appropriate mating parts. Technical characteristics • A thick conductive EPDM jacket provides a total safe to touch screen. • Each separable connector is tested for AC withstand and partial discharge prior to leaving the factory. Specifications and standards The 430TB separable connector meets the requirements of CENELEC HD 629.1. Up to 36 kV 630 A (800 A) 430TB INTERFACE C TEE CONNECTOR 6/10 (12) kV 6.35/11 (12) kV 8.7/15 (17.5) kV 12/20 (24) kV 12.7/22 (24) kV 18/30 (36) kV 19/33 (36) kV Design Separable connector comprising: 1. Conductive EPDM insert. 2. Conductive EPDM jacket. 3. Insulating EPDM layer moulded between the insert and the jacket. 4. Type C interface as described by CENELEC EN 50180 and 50181. 5. Conductor connector. 6. Basic insulating plug (with VD point). 7. Cable reducer. 8. Conductive rubber cap. 9. Clamping screw. 10. Earthing lead. The screen break design enables cable outer sheath testing without removing or dismantling the connector. 185 mm 290 mm (350 mm for 36 kV) 4 9 6 1 2 3 10 7 5 8 Separable connector type Voltage Um (kV) Current Ir (A) Current Ir (A) Conductor sizes (mm 2 ) When installed on an appropriate equipment bushing and when using a copper (-11-2) or a bolted (-12-5 or -14-5) conductor contact min max 430TB/G K430TB/G M430TB/G 12 24 36 630 630 630 800 800 800 35 35 50 300 300 240

Upload: hoangdang

Post on 17-Feb-2019

214 views

Category:

Documents


0 download

TRANSCRIPT

6

01/2

011

ApplicationSeparable tee shape connector (bolted type) designed to connect polymeric insulated cable to equipment (transformers, switchgear, motors, ...).Also connects cable to cable when using the appropriate mating parts.

Technical characteristics•AthickconductiveEPDM

jacket provides a total safe to touch screen.

•Eachseparableconnectoristested for AC withstand and partial discharge prior to leaving the factory.

Specifications and standardsThe 430TB separable connector meets the requirements of CENELEC HD 629.1.

Up to 36 kV630 A (800 A)

430TBINTERFACE C

TEE CONNECTOR

6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV

12/20 (24) kV12.7/22 (24) kV

18/30 (36) kV19/33 (36) kV

DesignSeparable connector comprising: 1. Conductive EPDM insert. 2. Conductive EPDM jacket. 3. Insulating EPDM layer moulded between the insert and the jacket. 4. Type C interface as described by CENELEC EN 50180 and 50181. 5. Conductor connector. 6. Basic insulating plug (with VD point). 7. Cable reducer. 8. Conductive rubber cap. 9. Clamping screw. 10. Earthing lead.

The screen break designenables cable outer sheathtesting without removing ordismantling the connector.

185 mm

290 mm

(350 mmfor 36 kV)

4 9

6

1

2

3

10

7

5

8

Separable connector

type

VoltageUm(kV)

CurrentIr

(A)

Current Ir (A)Conductor sizes (mm2)

When installed on an appropriate equipment bushing and when using a copper (-11-2) or a

bolted (-12-5 or -14-5) conductor contact min max

430TB/GK430TB/GM430TB/G

122436

630630630

800800800

353550

300300240

7

3 x (K)(M)430TB/G-W-X connector kit

When installed on an appropriate equipment

bushing: 800 A continuously

Kit contentsThe complete (K)(M)430TB/G tee connector kit comprises 3 x the following components:

The kit also comprises silicone grease, field control mastic, installation rod, installation instructions and crimp chart.

Table W

Table X

Connector housing(K)(M)430BT/G

Cable reducer430CA-W

(411CA-Wfor 36 kV)

Clamping screw

430TCS

For use withcopper tape

screened cables. Order: Kit MT.

Orderingpart number

Voltage(Um)(kV)

Dia. over core insulation (mm)

min max

3 x 430TB/G-11-X3 x 430TB/G-16-X3 x 430TB/G-18-X

3 x K430TB/G-11-X3 x K430TB/G-16-X3 x K430TB/G-18-X

3 x M430TB/G-11-X3 x M430TB/G-15-X3 x M430TB/G-19-X3 x M430TB/G-22-X3 x M430TB/G-25-X3 x M430TB/G-27-X

121212

242424

363636363636

12.017.019.0

12.017.019.0

12.016.020.023.526.528.5

17.523.532.6

17.523.532.6

17.522.026.531.032.537.5

Ordering instructionsTo order the tee connector, select the ordering part number which gives you the best centring of your core insula-tion diameter and substitute X using table X, according to your conductor size and type.

Example:The cable is 24 kV, 150 mm2 compact stranded copper with a diameter over core insulation of 27.5 mm.Order 3 x K430TB/G-18-95.240-14-5 tee connector kit.

Conductorcontact TMBC-X

Conductor contact TBC-X

For use with Alupe orC 33-226 cables.

Please contact our representative.

For use withother cable types.

Please contact our representative.

For applicationsoutdoors and in humid climate.

Order: +MWS.

For use witheasy strip semi-conductive screened cables. Order: Field control mastic

(type MFC).

Conduc-tor sizes (mm2)

Aluminium conductor Copper conductor

DINhexagonal

Deepindent

BoltedDIN

hexagonalBolted

35 35(K)M-10-2 35KM-10-1 35(K)M-11-250 50(K)M-10-2 50(K)M-10-1 50(K)M-11-270 70(K)M-10-2 70(K)M-10-1 70(K)M-11-295 95(K)M-10-2 95(K)M-10-1 95(K)M-11-2

120 120(K)M-10-2 120(K)M-10-1 120(K)M-11-2150 150(K)M-10-2 150(K)M-10-1 150(K)M-11-2185 185(K)M-10-2 185(K)M-10-1 185(K)M-11-2240 240(K)M-10-2 240(K)M-10-1 240(K)M-11-2300 300(K)M-10-2 – 300(K)M-11-2

16.9

5-14

-5

95.2

40-1

4-5

50.1

50-1

4-5

120.

300-

12-5

16.9

5-14

-5

50.1

50-1

4-5

95.2

40-1

4-5

120.

300-

12-5

Basic insulatingplug

(K)(M)300BIPA +rubber cap