emai l : [email protected] www.moxa.com 5-5-25
Industrial Networking Solutions
Flexible remote I/O with a variety of I/O modules
emai l : [email protected] www.moxa.com 5-25
5
Rem
ote I/O >
ioLogik 4000 Modular R
emote I/O
ioLogik 4000 Modular Remote I/O
ioLogik remote I/O products from Moxa are used to connect a variety of sensors and actuators to computers and applications over standard Ethernet networks and the Internet. Sensors could be used for taking temperature, humidity, and light intensity readings, and actuators could include devices that apply pressure actuators and motor drives. Moxa also offers a line of RS-485 remote I/O servers that can be used with existing applications. By using one of Moxa’s NPort wireless device servers, you can even connect to sensors and devices over a wireless LAN network.
Slice Type I/O Modules Removable Terminal Block Module Coding TagSpring Type Terminal Block
ioLogik 4000 servers provide spring type, removable terminal blocks (RTB) that allow you to preserve field wiring before replacing I/O expansion modules. Each I/O expansion module can be replaced quickly and easily.
Easy Maintenance
www.moxa.com emai l : [email protected] 5-5-26 www.moxa.com emai l : [email protected]
Remote Monitoring Solutions
5-26
5
Rem
ote I/O >
ioLogik 4000 Modular R
emote I/O
ioAdmin allows you to configure and monitor ioLogik 4000 modular I/O servers remotely. ioAdmin automatically detects the installed ioLogik Ethernet I/O server and presents the installation sequence of the I/O modules. ioAdmin also detects and generates a Modbus address table, which can be printed or stored on a computer for SCADA software configuration.
The utility also allows you to:
1. Automatically search for installations
2. Look for help using online documentation
3. Generate reports of I/O combinations
What You See Is What You Install !!
Easy-to-Use Windows Utility
Self-diagnostic Function for Digital Output Channels
Remote Confi guration
ioAdmin is a powerful, Windows-based configuration and management tool. You can use ioAdmin to modify the IP address, update communication parameters, and configure all other settings easily. In addition, ioAdmin can be used to configure ioLogik modular I/O servers from a remote host. This means that ioLogik modular I/O servers can be configured from anywhere over the Ethernet, which can help reduce your operating expense.
The M-2402, M-2403, M-2404, and M-2405 modules include a self-diagnostic function to guarantee that the digital output signal is monitored electronically. The hardware-monitored status is written to
the logic system, and you can obtain the actual digital output status over the network when the software sends a command to the module. This is all done internally, and configuration is not required.
Although ioAdmin is the main configuration interface for ioLogik servers, you can also check the following information using the ioLogik server’s web console:
• Network configuration
• Modular I/O
• Status of each channel
Although ioAdmin is the main configuration interface for ioLogik
Check Remote I/O Status with a Web Browser
emai l : [email protected] www.moxa.com 5-5-27
Industrial Networking Solutions
Dimensions (unit = mm)
emai l : [email protected] www.moxa.com 5-27
5
Rem
ote I/O >
ioLogik 4000 Modular R
emote I/O
Supports Various SCADA Software Packages
Versatile Software Support
Modular Remote I/O
SCADA DAQ Software
SCADA SoftPLC
OPC Client
Modbus SpecificDriver
3rd PartyOPC Server
Visual BasicC-Applications
Programming ToolsProgramming Tools
MXIO DLL
Utility & DiagnosticsUtility & Diagnostics
ioAdminWindows Utility
RS-232/485 Ethernet
Host ComputerHost Computer
SCADA Software PackagesSCADA Software Packages
Modbus/TCPModbus/RTU
I/O Module DimensionsI/O Network Adaptor15 (0.60")
99 (3.90")
30 (1.18")
70 (2.75")
12 70 (2.75")
35 (1.38")
99 (3.90")
60 (2.36")
30 (1.18")
36 (1.42")28 (1.10")
Modular Remote I/O
ioLogik 4000 servers support the standard Modbus protocol and are compatible with most SCADA software. In addition, Moxa provides an easy-to-use MXIO DLL library that helps programmers develop application software with Visual Basic or C language under Windows.
The ioLogik 4000 line was designed for the standard Modbus protocol and can be used with most SCADA systems. The following SCADA software is compatible with ioLogik 4000 servers: Modicon Driver, Wonderware Intouch, GE Fanuc iFix and CIMPLICITY, Broadwin, kingview, and Citect. In addition, we successfully tested the OPC Server “Kepware,” which means that ioLogik 4000 servers can be accessed either from a SCADA system or through an OPC Server.
Note: The installation guides for different SCADA software packages can be downloaded from Moxa’s download center.
Side ViewSide View Side View Front ViewFront View Removable View
70 (2.75") 42 (1.65")
99 (3.90")
36 (1.42")35 (1.38")
28 (1.10")
99 (3.90")
60 (2.36")
70 (2.75")
99 (3.90")
36 (1.42")35 (1.38")
28 (1.10") 60 (2.36")
www.moxa.com emai l : [email protected] 5-5-28 www.moxa.com emai l : [email protected]
Remote Monitoring Solutions
5-28
5
Rem
ote I/O >
ioLogik 4000 Modular R
emote I/O
Digital Input Modules
Specs
Model M-1400 M-1401 M-1410 M-1411 M-1800 M-1801 M-1600 M-1601 M-1450 M-1451
Channels 4 4 4 4 8 8 16 16 4 4
Sink/Source Sink Source Sink Source Sink Source Sink Source – –
Connector RTB RTB RTB RTB RTB RTB 20-pin 20-pin RTB RTB
Voltage 24 VDC 24 VDC 48 VDC 48 VDC 24 VDC 24 VDC 24 VDC 24 VDC 110 VAC 220 VAC
Isolation Optical isolation
Digital Output Modules
Specs
Model M-2400 M-2401 M-2800 M-2801 M-2600 M-2601 M-2402 M-2403 M-2404 M-2405 M-2250 M-2254
Channels 4 4 8 8 16 16 4 4 4 4 2 2
Sink/Source Sink Source Sink Source Sink Source Sink Source Sink Source Relay Triac
Connector RTB RTB RTB RTB 20-pin 20-pin RTB RTB RTB RTB RTB RTB
Voltage 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 230 VAC/ 24 VDC
12 to 125 VDC
Current 0.5A 0.5A 0.5A 0.5A 0.3A 0.3A 0.5A 0.5A 2.0A 2.0A 2.0A 0.5A
Isolation Optical isolation
Diagnostics – – – – – – Yes Yes Yes Yes – –
Analog Input Modules
Specs
Model M-3400 M-3402 M-3410 M-3412 M-3414 M-3401 M-3403 M-3411 M-3413 M-3415 M-6200 M-6201
Channels 4 4 4 4 4 4 4 4 4 4 2 2
Current 0 to 20 mA
4 to 20 mA – – – 0 to 20
mA4 to 20
mA – – – – –
Voltage – – 0 to 10V -10 to 10V 0 to 5V – – 0 to 10V -10 to
10V 0 to 5V – –
Connector RTB RTB RTB RTB RTB RTB RTB RTB RTB RTB RTB RTB
Resolution 12-bit 12-bit 12-bit 12-bit 12-bit 14-bit 14-bit 14-bit 14-bit 14-bit – –
Isolation Optical isolation
SensorInput – – – – – – – – – – RTD
(Ohm)
Thermo-couple(µV)
Analog Output Modules
Specs
Model M-4201 M-4202 M-4210 M-4211 M-4212
Channels 2 2 2 2 2
Current 0 to 20 mA 4 to 20 mA – – –
Voltage – – 0 to 10V -10 to 10V 0 to 5V
Resolution 12-bit 12-bit 12-bit 12-bit 12-bit
Connector RTB RTB RTB RTB RTB
Isolation 1K VDC galvanic isolation
Modular Remote I/O Selection Guide
I/O Modules
Power Modules
Specs
Model M-7001 M-7002 M-7803 M-7804 M-7805 M-7806
Channels 0 0 8 8 8 8
Voltage 24 VDC DC: 5, 24, 48 VDCAC: 110/220 VAC - 0 V 24 VDC 4 for 0 VDC
4 for 24 VDC
Purpose System power Field power Shield signal Field power Field power Field power
emai l : [email protected] www.moxa.com 5-5-29
Industrial Networking Solutions
Ethernet network adaptor module
emai l : [email protected] www.moxa.com 5-29
5
Rem
ote I/O >
NA-4010
NA-4010
0 1
2 3
4 5
6 7
CH0 CH0
CH0 CH0
CH0 CH0
CH0 CH0
ioLogik 4000Modbus TCP/IPNA-4010
SYSLINKACTIVEI/O
FieldPower
0 1
2 3
4 5
6 7
SG
Field Power (0 VDC)Field Power (24 VDC)
SG
24V 0V
0V 0V
24V 24V
System Power (0 VDC)
System Power (24 VDC)
Field Power (0 VDC)
Field Power (24 VDC)
Shielding Ground
System Power (5 VDC)System Power (GND)
System Bus
Non-isolationSwitchingPower
Specifi cations
NetworkEthernet: 10/100 Mbps, RJ45
Software Features Protocols: Modbus/TCP, HTTP, BootpIP Settings: ARP, Bootp, static IPUtility: ioAdminProgramming Library: MXIO DLL library for Windows supporting Visual Basic, Visual C++, Borland C++ BuilderNumber of I/O Modules: Max. of 32 I/O expansion modules
Power Requirements Power Input: 11 to 28.8 VDC, 24 VDC typicalPower Consumption: 60 mA typical @ 24 VDCCurrent for I/O Modules: Max. 1.5A @ 5 VDC
Field Power Rated Voltage: 11 to 28.8 VDC, 24 VDC typicalCurrent in Field Power Contact: Max. 10A
IsolationSystem Power to I/O Driver: Optical isolation
Environmental LimitsOperating Temperature: -20 to 60°C, 5 to 90%RHStorage Temperature: -45 to 85°CVibration: IEC-68-2-6, 2G in operation
Regulatory ApprovalsEMC: CE EN-55082, EN-55081Safety: UL 508
WeightNet Weight: 150 g
Ordering Information
NA-4000 Series M-1000/2000/3000/4000/6000 Series M-7000 Series
Step 1: Select a Network Adaptor Module Step 2: Select I/O Modules Step 3: Select Power Modules (optional)
NA-4010: Ethernet Network Adaptor (Modbus/TCP)
*The NA-4010 Ethernet Network Adaptor is expandable with up to 32 I/O modules. Please refer to pages 5-31 to 5-44 to select the M-series modules that you need for your own application.
The certifi cation logos shown here apply to some or all of the products in this section. Please see the Specifi cations section or Moxa’s website for details.
www.moxa.com emai l : [email protected] 5-5-30
RS-485 or RS-232 network adaptor modules
www.moxa.com emai l : [email protected]
Remote Monitoring Solutions
5-30
5
Rem
ote I/O >
NA-4020/4021
NA-4020/4021
Specifi cationsSerial CommunicationBaudrate: 1200 to 115200 bpsData Bits: 7, 8Parity Bits: None, Even, OddStop Bits: 1, 2Signals:NA-4020: Data+, Data-, Gnd, DIRNA-4021: TxD, RxD, Gnd
Software FeaturesProtocols: Modbus/RTU, Modbus/ASCIIModbus Address: 00 to 99 by rotary switchesUtility: ioAdminProgramming Library: MXIO DLL library for Windows supporting Visual Basic, Visual C++, Borland C++ BuilderNumber of I/O Modules: Max. of 32 I/O expansion modules
Ordering Information
0 1
2 3
4 5
6 7
CH0
CH0
CH0 CH0
ioLogik 4000Modbus RS-485NA-4020
SYSTxDRxDI/O
FieldPower
0 1
2 3
4 5
6 7
SG
Field Power (0 VDC)Field Power (24 VDC)
SG
24V 0V
0V 0V
24V 24V
System Power (0 VDC)
System Power (24 VDC)
Field Power (0 VDC)
Field Power (24 VDC)
Shielding Ground
System Power (5 VDC)System Power (GND)
System Bus
Non-isolationSwitchingPower
NA-4000 Series M-1000/2000/3000/4000/6000 Series M-7000 Series
Step 1: Select a Network Adaptor Module Step 2: Select I/O Modules Step 3: Select Power Modules (optional)
NA-4020: RS-485 Network Adaptor (Modbus)
NA-4021: RS-232 Network Adaptor (Modbus)
*The NA-4020/4021 RS-485/RS-232 Adaptors are expandable with up to 32 I/O modules. Please refer to pages 5-31 to 5-34 to select the M-series modules that you need for your own application.
Power RequirementsPower Input: 11 to 28.8 VDC, 24 VDC typicalPower Consumption: 70 mA typical @ 24 VDCCurrent for I/O Modules: Max. 1.5A @ 5 VDC
Field PowerRated Voltage: 11 to 28.8 VDC, 24 VDC typicalCurrent in Field Power Contact: Max. 10A
IsolationSystem Power to I/O Driver: Optical isolation
Environmental LimitsOperating Temperature: -20 to 60°C, 5 to 90%RHStorage Temperature: -45 to 85°CVibration: IEC-68-2-6, 2G in operation
Regulatory ApprovalsEMC: CE EN-55082, EN-55081Safety: UL 508
WeightNet Weight: 150 g
The certifi cation logos shown here apply to some or all of the products in this section. Please see the Specifi cations section or Moxa’s website for details.
emai l : [email protected] www.moxa.com 5-5-31
Industrial Networking Solutions
emai l : [email protected] www.moxa.com 5-31
5
Rem
ote I/O >
Digital Input M
odules
M-1800 8 digital inputs, sink, 24 VDCInputs per Module: 8 points, sink typeOn-state Voltage: 24 VDC nominal, min. 11 VDC to max. 28.8 VDCMin. Off-state Voltage: Max. 5 VDCOn-state Current: Max. 6 mA / point @ 28.8 VDCInput Impedance: Typ. 5.1K ohmsFiltering Time: Typ. 1.5 msCommon Type: External commonPower Consumption: Max. 35 mA @ 5 VDC
M-1401 4 digital inputs, source, 24 VDCInputs per Module: 4 points, source typeOn-state Voltage: 24 VDC nominal, min. 11 VDC to max. 28.8 VDCMin. Off-state Voltage: Max. 5 VDCOn-state Current: Max. 6 mA / point @ 28.8 VDCInput Impedance: Typ. 5.1K ohmsFiltering Time: Typ. 1.5 msCommon Type: 4 points/2 COMPower Consumption: Max. 35 mA @ 5 VDC
0 1
2 3
4 5
6 7
CH0 CH1
CH2 CH3
0V 0V
24V 24V
0 1
2 3
System Power (5 VDC)System Power (GND)
System Bus
Field Power (0 VDC)Field Power (24 VDC)
M-1400
Status
0
1
23
M-1400 4 digital inputs, sink, 24 VDCInputs per Module: 4 points, sink typeOn-state Voltage: 24 VDC nominal, min. 11 VDC to max. 28.8 VDCMin. Off-state Voltage: Max. 5 VDCOn-state Current: Max. 6 mA / point @ 28.8 VDCInput Impedance: Typ. 5.1K ohmsFiltering Time: Typ. 1.5 msCommon Type: 4 points/2 COMPower Consumption: Max. 35 mA @ 5 VDC
0 1
2 3
4 5
6 7
CH0 CH1
CH2 CH3
0V 0V
24V 24V
0 1
2 3
System Power (5 VDC)System Power (GND)
System Bus
Field Power (0 VDC)Field Power (24 VDC)
M-1401
Status
0
1
23
0 1
2 3
4 5
6 7
CH0 CH1
CH2 CH3
CH4 CH5
CH6 CH7
0 1
2 3
System Power (5 VDC)System Power (GND)
System Bus
Field Power (0 VDC)Field Power (24 VDC)
Field Power (24 VDC)Field Power (0 VDC)
M-1800
Status
0
1
23
4
5
6
7
Digital Input Modules4 or 8-channel 24 VDC digital input modules4 or 8-channel 24 VDC digital input modules
M-1801 8 digital inputs, source, 24 VDCInputs per Module: 8 points, source typeOn-state Voltage: 24 VDC nominal, min. 11 VDC to max. 28.8 VDCMin. Off-state Voltage: Max. 5 VDCOn-state Current: Max. 6 mA / point @ 28.8 VDCInput Impedance: Typ. 5.1K ohmsFiltering Time: Typ 1.5 ms
Common Type: External commonPower Consumption: Max. 35 mA @ 5 VDC
0 1
2 3
4 5
6 7
CH0 CH1
CH2 CH3
CH4 CH5
CH6 CH7
0 1
2 3
System Power (5 VDC)System Power (GND)
System Bus
Field Power (0 VDC)Field Power (24 VDC)
Field Power (24 VDC)Field Power (0 VDC)
M-1801
Status
0
1
23
4
5
6
7
www.moxa.com emai l : [email protected] 5-5-32 www.moxa.com emai l : [email protected]
Remote Monitoring Solutions
5-32
5
Rem
ote I/O >
Digital Input M
odules
M-1411 4 digital inputs, source, 48 VDCInputs per Module: 4 points, source typeOn-state Voltage: 48 VDC nominal, min. 34 VDC to max. 60 VDCMin. Off-state Voltage: Max. 10 VDCOn-state Current: Max. 4 mA / point @ 48 VDCInput Impedance: Typ. 12K ohmsCommon Type: 4 points/2 COMPower Consumption: Max. 35 mA @ 5 VDC
M-1410 4 digital inputs, sink, 48 VDCInputs per Module: 4 points, sink typeOn-state Voltage: 48 VDC nominal, min. 34 VDC to max. 60 VDCMin. Off-state Voltage: Max. 10 VDCOn-state Current: Max. 4 mA / point @ 48 VDCInput Impedance: Typ. 12K ohmsCommon Type: 4 points/2 COMPower Consumption: Max. 35 mA @ 5 VDC
16-channel 24 VDC digital input modules
0 1
2 3
4 5
6 7
CH0 CH1
CH2 CH3
0V 0V
48V 48V
0 1
2 3
System Power (5 VDC)System Power (GND)
System Bus
Field Power (0 VDC)Field Power (48 VDC)
* Field Power distributor required.
M-1410
Status
0
1
23
0 1
2 3
4 5
6 7
CH0 CH1
CH2 CH3
0V 0V
48V 48V
0 1
2 3
System Power (5 VDC)System Power (GND)
System Bus
Field Power (0 VDC)Field Power (48 VDC)
* Field Power distributor required.
M-1411
Status
0
1
23
M-1600 16 digital inputs, sink, 24 VDC Inputs per Module: 16 points, sink typeOn-state Voltage: 24 VDC nominal, min. 11 VDC to max. 28.8 VDCMin. Off-state Voltage: Max. 5 VDCOn-state Current: Max. 6 mA / point @ 28.8 VDCInput Impedance: Typ. 5.1K ohmsFiltering Time: Typ. 1.5 msCommon Type: 16 points/2 COM Power Consumption: Max. 40 mA @ 5 VDC
M-1601 16 digital inputs, source, 24 VDCInputs per Module: 16 points, source typeOn-state Voltage: 24 VDC nominal, min. 11 VDC to max. 28.8 VDCMin. Off-state Voltage: Max. 5 VDCOn-state Current: Max. 6 mA / point @ 28.8 VDCInput Impedance: Typ. 5.1K ohmsFiltering Time: Typ. 1.5 ms
Common Type: 16 points/2 COM Power Consumption: Max. 40 mA @ 5 VDC
24V24V
0V0V
1514
1312
1110
98
76
54
32
1Ch0
0 1
18 19
System Power (5 VDC)System Power (GND)
System Bus
Field Power (0 VDC)Field Power (24 VDC)
M-1600
Status
3 71115
2 61014
1 5 9 13
0 4 8 12
24V24V
0V0V
1514
1312
1110
98
76
54
32
1Ch0
0 1
18 19
System Power (5 VDC)System Power (GND)
System Bus
Field Power (0 VDC)Field Power (24 VDC)
M-1601
Status
3 71115
2 61014
1 5 9 13
0 4 8 12
4-channel 48 VDC digital input modules
emai l : [email protected] www.moxa.com 5-5-33
Industrial Networking Solutions
emai l : [email protected] www.moxa.com 5-33
5
Rem
ote I/O >
Digital Input M
odules
4-channel 110/220 VAC digital input modules
M-1451 4 digital inputs, 220 VACInputs per Module: 4 pointsOn-state Voltage: 240 VAC nominal, min. 170 VAC to max. 264 VACMin. Off-state Voltage: Max. 45 VACOn-state Current: Max. 12 mA / point @ 264 VACInput Impedance: Typ. 22K ohmsCommon Type: 4 points/2 COM (single common)Power Consumption: Max. 35 mA @ 5 VDC
M-1450 4 digital inputs, 110 VACInputs per Module: 4 pointsOn-state Voltage: 120 VAC nominal, min. 85 VAC to max. 132 VACMin. Off-state Voltage: Max. 45 VACOn-state Current: Max. 8 mA / point @ 132 VACInput Impedance: Typ. 11K ohmsCommon Type: 4 points/2 COM (single common)Power Consumption: Max. 35 mA @ 5 VDC
0 1
2 3
4 5
6 7
CH0 CH1
CH2 CH3
N N
L L
0 1
2 3
System Power (5 VDC)System Power (GND)
System Bus
Field Power (110 VAC N)Field Power (110 VAC L)
* Field Power distributor required.
M-1450
Status
0
1
23
0 1
2 3
4 5
6 7
CH0 CH1
CH2 CH3
N N
L L
0 1
2 3
System Power (5 VDC)System Power (GND)
System Bus
Field Power (220 VAC N)Field Power (220 VAC L)
* Field Power distributor required.
Field Power (220 VAC)
M-1451
Status
0
1
23
Ordering Information
Digital Input Modules
Specs
Model M-1400 M-1401 M-1410 M-1411 M-1800 M-1801 M-1600 M-1601 M-1450 M-1451
Channels 4 4 4 4 8 8 16 16 4 4
Sink/Source Sink Source Sink Source Sink Source Sink Source – –
Connector RTB RTB RTB RTB RTB RTB 20-pin 20-pin RTB RTB
Voltage 24 VDC 24 VDC 48 VDC 48 VDC 24 VDC 24 VDC 24 VDC 24 VDC 110 VAC 220 VAC
Isolation Optical isolation
www.moxa.com emai l : [email protected] 5-5-34 www.moxa.com emai l : [email protected]
Remote Monitoring Solutions
5-34
5
Rem
ote I/O >
Digital O
utput Modules
M-2400 4 digital outputs, sink, 24 VDC, 0.5AOutputs per Module: 4 points, sink typeOutput Voltage Range: 24 VDC nominal, min. 11 VDC to max. 28.8 VDCOn-state Voltage Drop: Max. 0.3 VDC @ 25°COn-state Current: Min. 1 mA per channelOff Leakage Current: Max. 50 µAOutput Current Rating: Max. 0.5A per channel Common Type: 4 points /4 COM (single common)Power consumption: Max. 45 mA @ 5 VDC
Digital Output Modules
4 or 8-channel 24 VDC digital output modules4 or 8-channel 24 VDC digital output modules
System Power (5 VDC)System Power (GND)
System Bus
Field Power (0 VDC)Field Power (24 VDC)
L
L
0 1
2 3
4 5
6 7
CH0 CH1
CH2 CH3
24V
24V 24V
0 1
2 3
24V
M-2400
Status
0
1
23
0 1
2 3
4 5
6 7
CH0 CH1
CH2 CH3
0V 0V
0 1
2 3
System Power (5 VDC)System Power (GND)
System Bus
Field Power (0 VDC)Field Power (24 VDC)
L
L
0V 0V
M-2401
Status
0
1
23
M-2401 4 digital outputs, source, 24 VDC, 0.5AOutputs per Module: 4 points, source typeOutput Voltage Range: 24 VDC nominal, min. 11 VDC to max. 28.8 VDCOn-state Voltage Drop: Max. 0.3 VDC @ 25°COn-state Current: Min. 1 mA per channelOff Leakage Current: Max. 50 µAOutput Current Rating: Max. 0.5A per channel Common Type: 4 points/4 COM (single common)Power Consumption: Max. 45 mA @ 5 VDC
0 1
2 3
4 5
6 7
CH0 CH1
CH2 CH3
CH4 CH5
CH6 CH7
0 1
2 3
System Power (5 VDC)System Power (GND)
System Bus
Field Power (0 VDC)Field Power (24 VDC)
Field Power (24 VDC)Field Power (0 VDC)
L
L
L
L
M-2800
Status
0
1
23
4
5
6
7
M-2800 8 digital outputs, sink, 24 VDC, 0.5AOutputs per Module: 8 points, sink typeOutput Voltage Range: 24 VDC nominal, min.11 VDC to max. 28.8 VDCOn-state Voltage Drop: Max. 0.3 VDC @ 25°COn-state Current: Min. 1 mA per channelOff Leakage Current: Max. 50 µAOutput Current Rating: Max. 0.5A per channel Common Type: 8 points/External common (single common)Power Consumption: Max. 60 mA @ 5 VDC
0 1
2 3
4 5
6 7
CH0 CH1
CH2 CH3
CH4 CH5
CH6 CH7
0 1
2 3
System Power (5 VDC)System Power (GND)
System Bus
Field Power (0 VDC)Field Power (24 VDC)
Field Power (24 VDC)Field Power (0 VDC)
L
L
L
L
M-2801
Status
0
1
23
4
5
6
7
M-2801 8 digital outputs, source, 24 VDC, 0.5AOutputs per Module: 8 points, source typeOutput Voltage Range: 24 VDC nominal, min. 11 VDC to max. 28.8 VDCOn-state Voltage Drop: Max. 0.3 VDC @ 25°COn-state Current: Min. 1 mA per channelOff Leakage Current: Max. 50 µAOutput Current Rating: Max. 0.5A per channel Common Type: 8 points/external common (single common)Power Consumption: Max. 60 mA @ 5 VDC
emai l : [email protected] www.moxa.com 5-5-35
Industrial Networking Solutions
emai l : [email protected] www.moxa.com 5-35
5
Rem
ote I/O >
Digital O
utput Modules
M-2403 4 digital outputs, diagnostics, source, 24 VDC, 0.5AOutputs per Module: 4 points, source typeOutput Voltage Range: 24 VDC nominal, min. 11 VDC to max. 28.8 VDCOn-state Voltage Drop: Max. 0.3 VDC @ 25°COn-state Current: Min. 1 mA per channelOff Leakage Current: Max. 50 µAOutput Current Rating: Max. 0.5A per channel Common Type: 4 points /4 COM (single common)Self Diagnostics: YesPower Consumption: Max. 45 mA @ 5 VDC
M-2402 4 digital outputs, diagnostics, sink, 24 VDC, 0.5AOutputs per Module: 4 points, sink typeOutput Voltage Range: 24 VDC nominal, min. 11 VDC to max. 28.8 VDCOn-state Voltage Drop: Max. 0.3 VDC @ 25°COn-state Current: Min. 1 mA per channelOff Leakage Current: Max. 50 µAOutput Current Rating: Max. 0.5A per channel Common Type: 4 points/4 COM (single common)Self Diagnostics: YesPower Consumption: Max. 45 mA @ 5 VDC
4-channel digital output modules with diagnostics
System Power (5 VDC)System Power (GND)
System Bus
Field Power (0 VDC)Field Power (24 VDC)
L
L
0 1
2 3
4 5
6 7
CH0 CH1
CH2 CH3
24V
24V 24V
0 1
2 3
24V
M-2402
Status
0
1
23
0 1
2 3
4 5
6 7
CH0 CH1
CH2 CH3
0V 0V
0 1
2 3
System Power (5 VDC)System Power (GND)
System Bus
Field Power (0 VDC)Field Power (24 VDC)
L
L
0V 0V
M-2403
Status
0
1
23
M-2405 4 digital outputs, diagnostics, source, 24 VDC, 2AOutputs per Module: 4 points, source typeOutput Voltage Range: 24 VDC nominal, min. 11 VDC to max. 28.8 VDCOn-state Voltage Drop: Max. 0.3 VDC @ 25°COn-state Current: Min. 1 mA per channelOff Leakage Current: Max. 50 µAOutput Current Rating: Max. 2A per channel Common Type: 4 points/4 COM (single common)Self Diagnostics: YesPower Consumption: Max. 45 mA @ 5 VDC
M-2404 4 digital outputs, diagnostics, sink, 24 VDC, 2AOutputs per Module: 4 points, sink typeOutput Voltage Range: 24 VDC nominal, min. 11 VDC to max. 28.8 VDCOn-state Voltage Drop: Max. 0.3 VDC @ 25°COn-state Current: Min. 1 mA per channelOff leakage Current: Max. 50 µAOutput Current Rating: Max. 2A per channel Common Type: 4 points/4 COM (single common)
Self Diagnostics: YesPower Consumption: Max. 45 mA @ 5 VDC
System Power (5 VDC)System Power (GND)
System Bus
Field Power (0 VDC)Field Power (24 VDC)
L
L
0 1
2 3
4 5
6 7
CH0 CH1
CH2 CH3
24V
24V 24V
0 1
2 3
24V
M-2404
Status
0
1
23
0 1
2 3
4 5
6 7
CH0 CH1
CH2 CH3
0V 0V
0 1
2 3
System Power (5 VDC)System Power (GND)
System Bus
Field Power (0 VDC)Field Power (24 VDC)
L
L
0V 0V
M-2405
Status
0
1
23
www.moxa.com emai l : [email protected] 5-5-36 www.moxa.com emai l : [email protected]
Remote Monitoring Solutions
5-36
5
Rem
ote I/O >
Digital O
utput Modules
M-2600 16 digital outputs, sink, 24 VDC, 0.3AOutputs per Module: 16 points, sink typeOutput Voltage Range: 24 VDC nominal, min. 11 VDC to max. 28.8 VDCOn-state Voltage Drop: Max. 0.3 VDC @ 25°COn-state Current: Min. 1 mA per channelOff Leakage Current: Max. 50 µAOutput Current Rating: Max. 0.3A per channel
Max. 4A per commonCommon Type: 16 points / 2 COM (single common)Power Consumption: Max. 80 mA @ 5 VDC
16-channel digital output modules
24V24V
0V0V
1514
1312
1110
98
76
54
32
1Ch0
0 1
18 19
System Power (5 VDC)System Power (GND)
System Bus
Field Power (0 VDC)Field Power (24 VDC)
L
L
LLLLLL
M-2600
Status
3 71115
2 61014
1 5 9 13
0 4 8 12
24V24V
0V0V
1514
1312
1110
98
76
54
32
1Ch0
0 1
18 19
System Power (5 VDC)System Power (GND)
System Bus
Field Power (0 VDC)Field Power (24 VDC)
L
L
LLLLLL
M-2601
Status
7111561014
1 5 9 13
0 4 8 12
M-2601 16 digital outputs, source, 24 VDC, 0.3AOutputs per Module: 16 points, source typeOutput Voltage Range: 24 VDC nominal, min. 11 VDC to max. 28.8 VDCOn-state Voltage Drop: Max. 0.3 VDC @ 25°COn-state Current: Min. 1 mA per channelOff Leakage Current: Max. 50 µAOutput Current Rating: Max. 0.3A per channel
Max. 4A per common
Common Type: 16 points / 2 COM (single common)Power Consumption: Max. 80 mA @ 5 VDC
emai l : [email protected] www.moxa.com 5-5-37
Industrial Networking Solutions
emai l : [email protected] www.moxa.com 5-37
5
Rem
ote I/O >
Digital O
utput Modules
0 1
2 3
4 5
6 7
CH0 CH1
Ch0 Ch1
L1 L1
L2 L2
0 1
2 3
System Power (5 VDC) System Power (GND)
System Bus
Field Power (N or 0 VDC) Field Power (230 VAC or 24 VDC)
* Field power distributor required when the field power is not 24 VDC.
L
L
COM (to N or 0 VDC)
M-2250
Status
0
1
0 1
2 3
4 5
6 7
CH0 CH1
NC NC
N N
L L
0 1
2 3
System Power (5 VDC)System Power (GND)
System Bus
Field Power (110 VAC N)Field Power (110 VAC L)
* Field Power distributor required when the field power is not 24 VDC.
L
L
to 125 VAC
M-2254
Status
0
1
NC: No Connection
2-channel relay output module
M-2254 2 digital outputs, Triac, 12 to 125 VAC, 0.5AOutputs per Module: 2 pointsSwitch Type: Zero crossingRated Load Voltage: 15 to 132 VACOutput Current Rating: 0.05 to 0.5AFrequency Range: 47 to 63 HzSurge Current: 40A (16 ms) /4A (30S)On-state Voltage Drop: 1.3 Vrms (max. load)Off-state Leakage Current: Max. 1.5 mACommon Type: 2 points / 2 COMPower Consumption: Max. 35 mA @ 5 VDC
M-2250 2 digital outputs, relay, 24 VDC/230 VAC, 2AOutputs per Module: 2 points, relay Relay Type: Form A, Normally Open (N.O.) Single Pole, Single Throw (SPST)Output Voltage Range: Load dependent 5 to 28.8 VDC / 2A resistive 48 VDC / 0.8A resistive 110 VAC / 0.3A resistive 250 VAC / 2A resistiveMin. Load: 100 µA, 100 m VDC per pointMax. On-state Voltage Drop: 0.5V @ 2A, resistive load, 24 VDCOff-state Leakage Current: Max. 1.5 mACommon Type: 1 point/1 COMPower Consumption: Max. 65 mA @ 5 VDC
Ordering Information
Digital Output Modules
Specs
Model M-2400 M-2401 M-2800 M-2801 M-2600 M-2601 M-2402 M-2403 M-2404 M-2405 M-2250 M-2254
Channels 4 4 8 8 16 16 4 4 4 4 2 2
Sink/Source Sink Source Sink Source Sink Source Sink Source Sink Source Relay Triac
Connector RTB RTB RTB RTB 20-pin 20-pin RTB RTB RTB RTB RTB RTB
Voltage 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 230 VAC/ 24 VDC
12 to 125 VDC
Current 0.5A 0.5A 0.5A 0.5A 0.3A 0.3A 0.5A 0.5A 2.0A 2.0A 2.0A 0.5A
Isolation Optical isolation
Diagnostics – – – – – – Yes Yes Yes Yes – –
www.moxa.com emai l : [email protected] 5-5-38 www.moxa.com emai l : [email protected]
Remote Monitoring Solutions
5-38
5
Rem
ote I/O >
Analog Input Modules M-3410 4 analog inputs, 0 to 10V, 12 bits
M-3412 4 analog inputs, -10 to 10V, 12 bitsM-3414 4 analog inputs, 0 to 5V, 12 bitsInput SpecificationsResolution in Ranges: 12 bits, 2.44 mV/bit (M-3410) 12 bits, 4.88 mV/bit (M-3412) 12 bits, 1.22 mV/bit (M-3414)Input Current Range: 0 to 10 VDC (M-3410) -10 to 10 VDC (M-3412) 0 to 5 VDC (M-3414)Data Format: 16-bit integer (2’s complement)Accuracy: ±0.1%, FSR @ 25°C ±0.3%, FSR @ 0°C, 60°CInput Impedance: 500K ohmsConversion Time: 4 ms / all channels
General SpecificationsPower Consumption: Max. 150 mA @ 5 VDCIsolation: I/O to logic: Photocoupler isolationWiring: I/O cable max. AWG14
M-3400 4 analog inputs, 0 to 20 mA, 12 bitsM-3402 4 analog inputs, 4 to 20 mA, 12 bitsInput SpecificationsResolution in Ranges: 12 bits, 4.88 µA/bit (M-3400) 12 bits, 3.91 µA/bit (M-3402)Input Current Range: 0 to 20 mA (M-3400) 4 to 20 mA (M-3402)Data Format: 16-bit integer (2’s complement)Accuracy: ±0.1%, FSR @ 25°C ±0.3%, FSR @ 0°C, 60°CInput Impedance: 120 ohmsConversion Time: 4 ms / all channels
General SpecificationsPower Consumption: Max. 150 mA @ 5 VDCIsolation: I/O to logic: Photocoupler isolationWiring: I/O cable max. AWG14
Analog Input Modules
4-channel analog input modules, 12-bit resolution4-channel analog input modules, 12-bit resolution
4-channel analog input modules, 12-bit resolution Power (GND)System Bus
Field Power (0 VDC) Field Power (24 VDC)
0 1
2 3
4 5
6 7
CH0 CH1
CH2 CH3
G
CG CG
0 1
2 3
G
Voltage 0 to 10V (M-3410/3411) Voltage -10 to 10V (M-3412/3413) Voltage 0 to 5V (M-3414/3415)
Shielding Ground
M-34xx
Status
0
1
23
4-channel analog input modules, 12-bit resolution Power (5 VDC)
System Power (5 VDC)System Power (GND)
System Bus
Field Power (0 VDC)Field Power (24 VDC)
0 1
2 3
4 5
6 7
CH0 CH1
CH2 CH3
G
CG CG
0 1
2 3
G
Current 0 to 20mA (M-3400/3401)
Shielding Ground
Current 4 to 20mA (M-3402/3403)
M-34xx
Status
0
1
23