![Page 1: 2.4 Modeling on reactive power or voltage controlweb.eecs.utk.edu/~kaisun/ECE522/ECE522_2.4-Modelin… · · 2018-03-30Reactive Capacity of a Generator ... that the capability limits](https://reader034.vdocuments.us/reader034/viewer/2022051802/5aef47fa7f8b9aa17b8d8797/html5/thumbnails/1.jpg)
1
2.4 Modeling on reactive power or voltage control
Saadat’s Chapters 12.6‐12.7Kundur’s Chapters 5.4, 8 and 11.2EPRI Tutorial’s Chapter 5
![Page 2: 2.4 Modeling on reactive power or voltage controlweb.eecs.utk.edu/~kaisun/ECE522/ECE522_2.4-Modelin… · · 2018-03-30Reactive Capacity of a Generator ... that the capability limits](https://reader034.vdocuments.us/reader034/viewer/2022051802/5aef47fa7f8b9aa17b8d8797/html5/thumbnails/2.jpg)
2
Objectives of Reactive Power and Voltage Control
•Equipment security:– Voltages at terminals of all equipment (of either utility and customers) in the system are within acceptable limits to avoid damage
•System stability:– System stability is enhanced to maximize utilization of the transmission system. (Voltage and reactive power control have a significant impact on system stability.)
•Transmission efficiency:– The reactive power flow is minimized so as to reduce RI2 and XI2 losses to improve transmission system efficiency, i.e. leaving the room mainly for real power transfer
![Page 3: 2.4 Modeling on reactive power or voltage controlweb.eecs.utk.edu/~kaisun/ECE522/ECE522_2.4-Modelin… · · 2018-03-30Reactive Capacity of a Generator ... that the capability limits](https://reader034.vdocuments.us/reader034/viewer/2022051802/5aef47fa7f8b9aa17b8d8797/html5/thumbnails/3.jpg)
3
Methods of Reactive Power and Voltage Control
Equipment Supply Q Absorb Q
Synchronous generator
Overhead lines
Underground cables
Transformers
Loads
Compensating devices
Y(Over‐excited)
Y (Under‐excited)
Y Y
Mostly
Y
Mostly
Y Y
• Generators: – Excitation control systems with automatic voltage regulators (AVRs)
• Other control devices– Sources or sinks of var, e.g.
• shunt capacitors, • shunt reactors, • synchronous condensers, • static var compensators (SVC)
– Line reactance compensators, e.g. series capacitors
– Regulating transformers, e.g. tap‐changing transformers and boosters.
![Page 4: 2.4 Modeling on reactive power or voltage controlweb.eecs.utk.edu/~kaisun/ECE522/ECE522_2.4-Modelin… · · 2018-03-30Reactive Capacity of a Generator ... that the capability limits](https://reader034.vdocuments.us/reader034/viewer/2022051802/5aef47fa7f8b9aa17b8d8797/html5/thumbnails/4.jpg)
4
Excitation Systems of Generators
•The basic function of an excitation system is to provide direct current to the synchronous machine field winding.
•In addition, the automatic voltage regulator (AVR) with an excitation system performs control and protective functions essential to the satisfactory performance of the power system by controlling the field voltage and thereby the field current
Field current
![Page 5: 2.4 Modeling on reactive power or voltage controlweb.eecs.utk.edu/~kaisun/ECE522/ECE522_2.4-Modelin… · · 2018-03-30Reactive Capacity of a Generator ... that the capability limits](https://reader034.vdocuments.us/reader034/viewer/2022051802/5aef47fa7f8b9aa17b8d8797/html5/thumbnails/5.jpg)
5
Performance Requirements of Excitation Systems•Generator considerations:
– Under steady‐state conditions, the excitation system should supply and automatically adjust the field current of the synchronous generator to maintain the terminal voltage as the output varies continuously within the capacity of the generator
– Under disturbances, the excitation system must be able to respond to transient disturbances with field forcing consistent with the generator instantaneous and short‐term capacities
– In either case, heating limits (e.g. due to resistances that carry It or ifd) should be concerned
•Power system considerations– The excitation system should contribute to effective control of voltage and enhancement of system stability under both large and small disturbances
![Page 6: 2.4 Modeling on reactive power or voltage controlweb.eecs.utk.edu/~kaisun/ECE522/ECE522_2.4-Modelin… · · 2018-03-30Reactive Capacity of a Generator ... that the capability limits](https://reader034.vdocuments.us/reader034/viewer/2022051802/5aef47fa7f8b9aa17b8d8797/html5/thumbnails/6.jpg)
6
End region heating limit (due to heating caused by end-turn flux in under-excited conditions)
Over-excited
(Supplying Q, Lagging p.f.)
Under-excited
(Absorbing Q, Leading p.f.)
Under-excited Limit
2
It<It,max : Armature current heating limit
ifd<ifd, max: Field current heating limit
1
2
Always >0
>0 (over-excited)
or <0 (under-excited)
1
Reactive Capacity of a Generator
Ignore Ra
![Page 7: 2.4 Modeling on reactive power or voltage controlweb.eecs.utk.edu/~kaisun/ECE522/ECE522_2.4-Modelin… · · 2018-03-30Reactive Capacity of a Generator ... that the capability limits](https://reader034.vdocuments.us/reader034/viewer/2022051802/5aef47fa7f8b9aa17b8d8797/html5/thumbnails/7.jpg)
7
Elements of an Excitation Control System1. Exciter provides dc power to the
generator field winding2. Regulator (AVR) processes and
amplifies input control signals for control of the exciter
3. Terminal voltage transducer and load compensator helps maintain the terminal voltage and the voltage at a remote point at desired levels
4. Power system stabilizer (PSS) provides an additional input signal to the regulator to damp system oscillations
5. Limiters and protective circuits ensure that the capability limits of the exciter and generator are not exceeded.
![Page 8: 2.4 Modeling on reactive power or voltage controlweb.eecs.utk.edu/~kaisun/ECE522/ECE522_2.4-Modelin… · · 2018-03-30Reactive Capacity of a Generator ... that the capability limits](https://reader034.vdocuments.us/reader034/viewer/2022051802/5aef47fa7f8b9aa17b8d8797/html5/thumbnails/8.jpg)
8
Simplified linear model (ignoring saturations with the amplifier and exciter and other nonlinearities• Rectifier/Sensor model:
– R is very small, e.g. 0.01 to 0.06s • Amplifier model:
– KA=10 to 400, A=0.02 to 0.1s• Exciter model:
– E is very small for modern exciters• Generator model:
– KG=0.7 to 1.0, G=1.0 to 2.0s from full load to no‐load
Excitation Control System/AVR Model
What is G?
( )( )
d
fd
se s
~
![Page 9: 2.4 Modeling on reactive power or voltage controlweb.eecs.utk.edu/~kaisun/ECE522/ECE522_2.4-Modelin… · · 2018-03-30Reactive Capacity of a Generator ... that the capability limits](https://reader034.vdocuments.us/reader034/viewer/2022051802/5aef47fa7f8b9aa17b8d8797/html5/thumbnails/9.jpg)
9
•Open‐ and closed‐loop transfer functions:
Simplified Linear Model
( ) ( )(1 )(1 )(1 )(1 )
A E G R
A E G R
K K K KKG s H ss s s st t t t
=+ + + +
( ) (1 )( ) (1 )(1 )(1 )(1 )
t A E G R
ref A E G R A E G R
V s K K K sV s s s s s K K K K
tt t t t
+=
+ + + + +
0lim ( )
1 1A E G A
tss tsA E G R A
K K K KV sV sK K K K K
= = »+ +
1( )refV ss
For a step input , using the final value theorem, the steady-state response is
(KEKGKR1)
If KA, Vtss=Vref
![Page 10: 2.4 Modeling on reactive power or voltage controlweb.eecs.utk.edu/~kaisun/ECE522/ECE522_2.4-Modelin… · · 2018-03-30Reactive Capacity of a Generator ... that the capability limits](https://reader034.vdocuments.us/reader034/viewer/2022051802/5aef47fa7f8b9aa17b8d8797/html5/thumbnails/10.jpg)
10
Saadat’s Example 12.6
![Page 11: 2.4 Modeling on reactive power or voltage controlweb.eecs.utk.edu/~kaisun/ECE522/ECE522_2.4-Modelin… · · 2018-03-30Reactive Capacity of a Generator ... that the capability limits](https://reader034.vdocuments.us/reader034/viewer/2022051802/5aef47fa7f8b9aa17b8d8797/html5/thumbnails/11.jpg)
11
-20 -15 -10 -5 0-10
-8
-6
-4
-2
0
2
4
6
8
10Root Locus
Real Axis (seconds-1)
Imag
inar
y A
xis
(sec
onds
-1)
• KA=10, Vtss=0.909Vref
• KA=12.16, Vtss=0.924Vref
0 5 10 15 200
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
t, s
Terminal voltage step response
0 5 10 15 200
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
t, s
Terminal voltage step response
• KA=5, Vtss=0.833Vref
0 5 10 15 200
0.2
0.4
0.6
0.8
1
1.2
1.4
t, s
Terminal voltage step response
-1/A-1/R -1/E -1/G
KA=12.16
![Page 12: 2.4 Modeling on reactive power or voltage controlweb.eecs.utk.edu/~kaisun/ECE522/ECE522_2.4-Modelin… · · 2018-03-30Reactive Capacity of a Generator ... that the capability limits](https://reader034.vdocuments.us/reader034/viewer/2022051802/5aef47fa7f8b9aa17b8d8797/html5/thumbnails/12.jpg)
12
Excitation System Stabilizers
• Rate feedback
• PID control (sim12ex8.mdl)
t, s
Terminal voltage step response
KA=10
KF=0.2 TF=0.02
KP=1 KI=0.25 KD=0.28
![Page 13: 2.4 Modeling on reactive power or voltage controlweb.eecs.utk.edu/~kaisun/ECE522/ECE522_2.4-Modelin… · · 2018-03-30Reactive Capacity of a Generator ... that the capability limits](https://reader034.vdocuments.us/reader034/viewer/2022051802/5aef47fa7f8b9aa17b8d8797/html5/thumbnails/13.jpg)
13
Stability Analysis on AVRSee Example 7.8 in Anderson’s “Power System Control and Stability” for details on choosing KF and F
![Page 14: 2.4 Modeling on reactive power or voltage controlweb.eecs.utk.edu/~kaisun/ECE522/ECE522_2.4-Modelin… · · 2018-03-30Reactive Capacity of a Generator ... that the capability limits](https://reader034.vdocuments.us/reader034/viewer/2022051802/5aef47fa7f8b9aa17b8d8797/html5/thumbnails/14.jpg)
14
F>1
0.05<F<1
F< 0.05
![Page 15: 2.4 Modeling on reactive power or voltage controlweb.eecs.utk.edu/~kaisun/ECE522/ECE522_2.4-Modelin… · · 2018-03-30Reactive Capacity of a Generator ... that the capability limits](https://reader034.vdocuments.us/reader034/viewer/2022051802/5aef47fa7f8b9aa17b8d8797/html5/thumbnails/15.jpg)
15
Non‐reciprocal per unit system• Lad-base Reciprocal per unit system: armature
terminal voltage Et is around 1.0 pu under normal operating conditions, but exciter output voltage efd(i.e. field voltage) in pu is very small (~0.001 pu)
• Non-reciprocal per unit system: – 1 pu field voltage Efd produces rated armature
terminal voltage Et on the air-gap line– 1 pu field current Ifd corresponds to rated field
current ifd
See Example 8.1:
Rfd=0.0006 pu, Ladu=1.66 pu
ifd=1.565 pu, efd= 0.000939 pu
Ifd=2.598 pu, Efd=2.598 pu
![Page 16: 2.4 Modeling on reactive power or voltage controlweb.eecs.utk.edu/~kaisun/ECE522/ECE522_2.4-Modelin… · · 2018-03-30Reactive Capacity of a Generator ... that the capability limits](https://reader034.vdocuments.us/reader034/viewer/2022051802/5aef47fa7f8b9aa17b8d8797/html5/thumbnails/16.jpg)
16
Detailed excitation system model with load compensation
With positive (or negative) RC and XC, the voltage at a point within (or outside)
the generator is regulated.
VR Efd
![Page 17: 2.4 Modeling on reactive power or voltage controlweb.eecs.utk.edu/~kaisun/ECE522/ECE522_2.4-Modelin… · · 2018-03-30Reactive Capacity of a Generator ... that the capability limits](https://reader034.vdocuments.us/reader034/viewer/2022051802/5aef47fa7f8b9aa17b8d8797/html5/thumbnails/17.jpg)
17
Separately excited DC Exciter (DC generator)
Main generatorDC Exciter
VR=Eef
VR=Eef -EX
![Page 18: 2.4 Modeling on reactive power or voltage controlweb.eecs.utk.edu/~kaisun/ECE522/ECE522_2.4-Modelin… · · 2018-03-30Reactive Capacity of a Generator ... that the capability limits](https://reader034.vdocuments.us/reader034/viewer/2022051802/5aef47fa7f8b9aa17b8d8797/html5/thumbnails/18.jpg)
18
IEEE Type DC2A Excitation System Model: ESDC2A
From PSS
(VUEL - Under-excitation limiter output)
(Taking the bigger input)
Voltage transducer
![Page 19: 2.4 Modeling on reactive power or voltage controlweb.eecs.utk.edu/~kaisun/ECE522/ECE522_2.4-Modelin… · · 2018-03-30Reactive Capacity of a Generator ... that the capability limits](https://reader034.vdocuments.us/reader034/viewer/2022051802/5aef47fa7f8b9aa17b8d8797/html5/thumbnails/19.jpg)
19
AC Exciter (Brushless Excitation)
• Electronic rectifiers replace the commutator, slip‐rings and brushes
AC exciter Main generator
![Page 20: 2.4 Modeling on reactive power or voltage controlweb.eecs.utk.edu/~kaisun/ECE522/ECE522_2.4-Modelin… · · 2018-03-30Reactive Capacity of a Generator ... that the capability limits](https://reader034.vdocuments.us/reader034/viewer/2022051802/5aef47fa7f8b9aa17b8d8797/html5/thumbnails/20.jpg)
20
IEEE Type AC2A Excitation System Model: ESAC2A
Rectifier regulation
model