Download - 01 capm software introduction
CAPM Software
The CAPM Evolution
First Generation
CAPM1 CAPM2 CAPM3
Second Generation
CAPM4 CAPM5
CAPM2 Software version naming scheme
Major Version Number Minor Version Number Protocol Variant Functional Variant
V9. 71 zz aa
Software version naming scheme for CAPM4/5
Version 21 Version 22 Version 23 Version 24
CAPM4
CAPM5
Version 26 Version 27 Version 28
Version 26 Version 27 Version 28
Version 25
Exclusive CAPM5 Features
Frequency Measurement Under/Over Frequency Protection
Fast Trip Input Module
19.2K Baud Rate on RS-232 Port P8
Auxiliary Panel Support
CAPM4/5 Software version naming scheme
The Software Version XXX-XX.XX
The Configuration Number 2XXXX
Examples
Software 028-07.00Configuration 21186
Software 528-07.00Configuration 21187
CAPM4 CAPM5
Software Version Details on Operator Panel
CAPM Software Version via WSOS On-Line
Compatibility of CAPM and WSOS Software
Each CAPM software version released is supported by a Windows Switchgear Operating System (WSOS) update.
Always ensure that you have the latest release WSOS and that it is compatible with the release version of CAPM software being installed.
http://www.nulec.com.au/
http://www.nulec.com.au/service/
STAR
*****
Searching for Controller Software
Filtering the Search Conditions
Searching for N Series CAPM5 Software
Search Results
Filtering on Search Description
DNP3
CAPM4/5 Software Upgrade
OBJECTIVE:
To Install the latest revision software over an existing version of CAPM4/5 software, whilst retaining all previous control and protection settings.
Equipment Required
Nu-Lec Industries Serial Cable Part No: N05-902
Laptop Personal Computer (32 bit system) with the latest version of WSOS installed.
The replacement software file.
(i.e. 21728528.13a)
The cap5load.exe file.
CAPM Software and Executable Files
CAPM4/5 Software Upgrade Procedure
Save the existing Switchgear Configuration Settings.
Download the CAPM software file to the controller using cap5load.exe.
Confirm new software is installed.
Reload Switchgear Configuration Settings.
Compare On-Line and Off-Line files.
Restore the Switchgear to Service.
Saving the Existing Switchgear Configuration
Using cap5load to load Software
Trip and Close must be isolated
Download Completed OK
Confirm New Software is Installed
Reloading Switchgear Configuration Settings
Compare Switchgear Settings
Restore ACR to Service
View the Event Log on the Operator Control Panel to confirm that a Pickup event has not been generated.
Enable the Trip and Close solenoids by returning both switches to the Enable position.
Go off-line with WSOS, disconnect and store the PC and serial cable.
CAPM Software Summary
The latest release of CAPM4/5 software is version 28.
Under/Over Frequency Protection is available on CAPM5 but not CAPM4.
CAPM4 CAPM5Software 028-07.00 Software 528-07.00
Configuration 21186 Configuration 21187
Each CAPM4/5 software release is supported by a release of WSOS Ver 4.
CAPM4/5 software is loaded using cap5load.exe from the Command Prompt.
The WSOS Compare command can be used to check that the configuration has been correctly restored following a CAPM software upgrade.