dimensionality reduction and early event detection using...
TRANSCRIPT
1
Dimensionality Reduction and Early Event
Detection Using Online Synchrophasor DataYang Chen, Student Member, IEEE, Le Xie, Member, IEEE, and P. R. Kumar, Fellow, IEEE
Abstract—This paper proposes a novel approach to utilizinglarge online synchrophasor data for early event detection inpower systems. Based on principal component analysis (PCA),a linear basis of the massive online phasor measurement unit(PMU) data can be extracted to reduce the dimensionality. Usingthe linear basis with much reduced dimensionality, an earlyevent detection algorithm is proposed. This algorithm is capableof predicting the changes of system operating conditions bycomparing the error between PCA-projected and actual valuesfrom a few selected locations. Numerical case studies basedon both PSS/E simulation and actual PMU data from ElectricReliability Council of Texas are conducted to demonstrate theefficacy of this algorithm.
Index Terms—Dimensionality reduction, principal componentanalysis, early event detection, phasor measurement unit.
I. INTRODUCTION
THIS paper focuses on the new paradigm of improving
power system online monitoring by using massively
deployed synchrophasor data. While the synchrophasor data
offer many opportunities to improve the situational awareness
[1]–[4], it also becomes a major challenge for large-scale
power system operators to utilize the data in a timely manner.
As an example, with only 120 PMUs installed, the Tennessee
Valley Authority needs to manage 36 GB data per day [5]. It
becomes very difficult for the system operators to directly use
the raw data for real-time decision making.
Complementary to conventional model-based monitoring
and decision making tools available in the control room, the
deployment of PMUs offers opportunities for real-time data-
driven analytics for the system operators. As a first step, this
paper assesses the potential of dimensionality reduction using
the classic PCA methods. Preliminary results indicate that
for a large power system, the measurements obtained from
PMUs lie in a much reduced lower-order space. Starting from
this observation, we further propose an online algorithm for
early event detection. This algorithm uses only a very small
set of PMU measurements as base vectors and predicts the
measurements from other PMUs. The deterioration of the
quality of the prediction will then indicate the change of
system conditions, i.e., for event detection. Such an algorithm
requires no knowledge of system fundamental model, and
is shown to be effective with several different case studies.
These preliminary results show the great potential to explore
This work is supported in part by NSF ECCS Grant #1150944, CNS-1239116, CNS-1035340, and CNS-1035378.
The authors are with Department of Electrical and Computer Engineer-ing, Texas A&M University, College Station, TX, 77843 USA. Email:[email protected], [email protected], [email protected].
the fundamental connection between large systems theory and
data-driven computational sciences. In summary, this work
serves the following purposes: (1) it provides a significantly
lower dimensional “signature” of the states of the overall
power system; (2) it greatly simplifies the data analysis, by
getting rid of the inherent redundancy as well as the noise
in the data; (3) it thereby proves a capability for a very
rapid detection of events, within a few samples of their
occurrence; (4) it greatly reduces the need for and amount of
data storage; (5) it can be more readily and quickly digested by
system operators and thus potentially improve their situational
awareness.
The rest of the paper is organized as follows. Section II
presents a linear PCA-based dimensionality reduction tech-
nique. This is a prerequisite for the early event detection al-
gorithm proposed in Section III. In Section IV, two numerical
case studies are conducted to evaluate the efficacy of this
algorithm. Conclusions and remarks are given in Section V.
II. DIMENSIONALITY REDUCTION OF ONLINE PMU DATA
As the synchrophasor measurement technology exhibits
great superiority in enhancing system situational awareness,
more PMUs and similar functional devices, such as frequency
monitoring network (FNET) [6] and frequency disturbance
recorder (FDR) [7], are being brought online. Correspondingly,
the availability of massive data is increasing significantly [5].
It is therefore an urgent need to leverage inherent correlations
among the PMU data for dimensionality reduction.
The dimensionality reduction method has been recognized
recently in power systems for its adaptive machine learning
features. PCA, as one of the premier linear dimensionality
reduction methods, reduces dimensionality by preserving the
most variance of the original data [8], [9]. Its fast compu-
tation feature itself provides much attraction in the areas of
coherency identification [10], extraction of fault features [11],
and fault location [12]. In a very recent paper [5], PCA is
performed on synchrophasor data for dimensionality reduction.
Using the participation weights and principal components
(PCs), the reconstruction errors are utilized in [5] to extract
correlations of different variables and therefore reduce the
dimensionality. The reconstruction accuracy will be very high
for the global variables like bus frequency, due to the globally
similar profiles. However, for some local variables, such as
voltage magnitude or reactive power, the reconstructions may
not exhibit high accuracy, under which condition, a new
algorithm for dimensionality reduction is of great need.
In this paper, we propose a PCA-based linear dimensionality
reduction algorithm using online PMU data. Instead of using
2
reconstruction as [5], we utilize only the first few PCs to form
a new space. The original PMU data are projected into the
new space to determine the basis matrix, which contains the
much reduced linear basis of the original data, and therefore
reduces the dimensionality.
Let p denote the number of available PMUs, each providing
ℓ measurements. p is expected to be of the order of 103 in the
near future [13], indicating the massiveness of the real-time
data handling problem. Typically, and as is true for the data
in this paper, ℓ = 3, corresponding to bus frequency, phase
angle, and voltage magnitude. At each time sample, therefore,
a total of N := pℓ measurements is collected. Consider a
set of n such samples, each taken a different time instant.
Define Yn×N = [y(1), . . . , y(N)] as the matrix containing N
measurements from PMUs. Each measurement, as noted, has n
samples constituting a time history, i.e., y(i) = [y(i)1 , . . . , y
(i)n ]T ,
i= 1, . . . , N. The procedure for the PCA-based dimensionality
analysis can be described as follows:
1) Calculate the covariance matrix of Y : C = Y Tn×NYn×N .
2) Calculate the N eigenvalues and eigenvectors of C.
3) Reorder the N eigenvalues of C from the highest to the
lowest, and the corresponding eigenvectors are the PCs.
4) Select the highest m out of N PCs based on a predefined
variance threshold, where m ≪ N.
5) Use the m PCs to form a new m-dimensional space, in
which the N original variables are projected.
6) Decide m′ out of the original N variables to keep, where
the m′ variables are selected as nearly orthogonal to each other
in the m-dimensional space as possible, and m′ ≤ m. This
step is a key to the utilization of the PCA method for power
systems, since it makes possible the notion of “pilot PMUs,”
as we detail in the sequel.
7) Define the basis matrix formed by the m′ variables as
YB := [y(1)b , . . . , y
(m′)b ] ∈ R
n×m′, where YB ⊆ Y .
The basis matrix YB contains the basis vectors, which can
form a linear basis for each of the original measurements.
Let v(i) = [v(i)1 , . . . , v
(i)m′ ]
T be the vector containing the linear
regression coefficients for approximating column y(i) ⊆ Y in
terms of YB, i.e.,
y(i) ≈m′
∑j=1
v(i)j y
( j)b = YBv(i). (1)
To solve the over-determined problem (1), v(i) is defined as
[14]
v(i) := (Y TB YB)
−1Y TB y(i), (2)
which aims to minimize the squared approximation error
‖y(i)−YB · v(i)‖2.
Using (2), each measurement in Y can be represented
in terms of the linear basis in YB. The dimensionality can
therefore be reduced from N to m′, where m′ ≪ N. More
importantly, the system operators can regard the PMUs whose
measurements are featured in YB as the “pilot PMUs” for pre-
dicting other non-pilot measurements and detecting changes of
system operating conditions in an online fashion. In the next
section, we propose an early event detection algorithm based
on these “pilot PMUs.”
III. EARLY EVENT DETECTION ALGORITHM
If massive PMU data indeed lie in a much reduced dimen-
sional space, system operators can leverage the low dimen-
sionality of PMU data for early event detection (EED). In
this section, we propose such an algorithm with the following
features: (a) only a reduced number m′ of PMUs are needed;
(b) it is implementable; (c) it can detect events at a very early
stage. A system event is defined in this paper as either a change
of model or a change of control inputs. The EED algorithm
is described as follows.
i) Offline Training: The training aims at computing the linear
representation (2). Assume an n-time-sample N-measurement
matrix Y is obtained from historical PMU data. Y can be bus
frequency, phase angle, or voltage magnitude. After perform-
ing the PCA-based dimensionality reduction algorithm, the
corresponding v(i) can be obtained for each y(i).
ii) Online Prediction: The prediction uses the recent mea-
surements at time t of the pilot PMUs and the predictor
coefficients v(i)’s to predict the measurements of all the
other PMUs at that time sample t. If a significant prediction
error is identified, an event alert will be declared. Under
normal conditions, the predictor coefficients v(i)’s are good
for predicting y(i), therefore, the prediction has high accuracy.
When events occur, the spatial dependencies inside the power
system change, and so the v(i)’s are not anymore good for
predicting the other PMU measurements, and this leads to a
large prediction error.
Now we precisely state the algorithm used. The real-time
prediction of the ith measurement is defined as
y(t)(i) := Y measB (t) · v(i), (3)
where Y measB (t) is the real-time measurement of the pilot
PMUs, and v(i) is directly from the training without timely
update.
Define the prediction error as
e(t)(i) :=
∣
∣
∣
∣
∣
y(t)(i)
y(t)(i),meas
∣
∣
∣
∣
∣
×100%, (4)
where
∣
∣
∣y(t)(i)
∣
∣
∣:=
∣
∣
∣y(t)(i)− y(t)(i),meas
∣
∣
∣is the absolute predic-
tion error, and y(t)(i),meas is the real-time measurement of
the ith PMU. The system/regional operators can monitor the
occurrence of events by using e(t) of selected non-pilot PMUs.
Numerically, due to the per unit scale of power system
variables, the prediction error can be very small and difficult
identify. We therefore define the performance index PI of the
ith variable for EED as
PI(t)(i) :=e(t)(i)
enormal, (5)
where enormal is the prediction error calculated when the
system is under normal operating conditions. Whenever PI
becomes larger than a pre-specified threshold, an event alert
will be issued. Given the fact that PMU samples at a rate of
30 Hz or higher, theoretically speaking, an alert can be issued
only two samples after the occurrence of an event. Such a swift
alert allows the system operators to quickly identify events in
real-time situations.
The flowchart of EED algorithm is shown in Fig. 1.
3
m PI
n NY
C
BY
!iv
N
m m N
! !
ˆi
y t
! !i
e t
! !i
PI t
YES
1t t !
NOY
Fig. 1. Implementation of EED algorithm.
IV. CASE STUDY
In this section, two cases are employed to illustrate the
proposed algorithm. Siemens PSS/E is utilized in Case A
to generate PMU data, with three events simulated. Case B
uses realistic data from the Electricity Reliability Council of
Texas (ERCOT). The algorithms in both cases are conducted in
Matlab. Due to the page limit, only bus frequency is analyzed
in this paper.
A. Simulation in PSS/E
A 23-bus 6-generator system in Siemens PSS/E is utilized
to generate PMU data with the system topology shown in Fig.
2. Assume each bus has one PMU, and only the bus frequency
ω is analyzed with the sampling rate of 30 Hz.
Three events, line tripping, unit tripping, and input change,
respectively, are simulated with details shown in Fig. 3.
1) Offline Training: The training contains PMU data of 250
seconds. The cumulative variance preserved by the number of
PCs for ω is shown in Fig. 4, which indicates that the first two
PCs preserve a high amount of variance (99.99%). According
to Section II, we select m = m′ = 2. The basis matrix is Y ωB =
[ω1, ω12], which stays unchanged for the three events.
2) Line Tripping Event: As shown in Fig. 3(a), two trans-
mission lines connecting buses 154 and 203, 152 and 153, are
assumed to have a line tripping event and followed by a line
closure event. The frequency profile for bus 154 is shown in
Fig. 5. Using equation (2), PIω s in (5) for bus frequencies are
depicted in Figs. 6 and 7.
Fig. 6 illustrates PIω of bus 154, near which the first line
tripping event happens. As one can observe, the PI proposed
in Section III can detect all the four line tripping events.
The zoomed-in figure is an illustration of the early detection
for the first event. The line between buses 154 and 203 is
tripped at t = 100 sec, with PIω154 > 500 at the same time
indicating a large prediction error of the linear representation.
However, using frequency profile in Fig. 5, only a 0.0001 pu
frequency deviation happens at t = 100.033 sec. This indicates
the advantage of the PIω for a quick detection of an event.
Fig. 7 shows PIω205 and PIω
3011, which are for a nearby bus
205 and a remote bus 3011 in the line tripping event. It can
101NUC-A
1
102NUC-B
1.020
22.0
16.5
1
81.2R
465.9
-168.0
-460.4
-94.6
465.9
-168.0
-460.4
-94.6
201HYDRO
1.040
520.0
6.2
1
740.0
-740.0
1.009
504.4
-1.3
3004WEST
154DOWNTN
1
600.0
450.0
2
350.0
251.6
100.4
-247.9
209.7
80.4
-206.6
14.1
1
300.0
150.0
123.2
52.7
205SUB230
1
354.9
1
75.0
-88.4
69.3
64.0
555.8
12.9
-549.8
-148.0
592.4
26.1
-83.3
-29.7
83.8
-83.3
-29.7
1.024
18.4
-3.0
1
3001MINE
3002E. MINE
3003S. MINE
202.5
84.8
-202.5
-81.2
11.6
3005WEST
0.995
228.8
-5.2
1
100.0
50.0
40.6
-100.6
-43.4
101.3
40.6
-100.6
-43.4
-78.4
81.2R
- 472. 8
600. 0
600.0H
-134.5
-251.5
0.993
228.4
-3.2
-590.7
1.016
508.2
-3.4
100.0
101.3
78.6
81.2
138.2
-137.7
-114.6
152MID500
81.2
3008CATDOG
1.023
235.4
-2.3
56.0
-55.8
1
600.0
3011MINE_G
1
258.7
104.0R
1
100.0
80.0H
17.7R
211HYDRO_G
1.040
20.8
12.9
53.0
17.7
-258.5
-96.9
258.7
104.0
56.0
12.0
-56.0
-11.6
133.8
-193.2
-125.1
-100.0
100.0
80.0
54.0
135.9
-54.4
-78.6
-138.3
1.012
505.9
10.9
203EAST230
0.939
216.0
-9.9
- 797. 5
200.0
250.5
800.0
0.994
228.6
-3.8
-66.6
1.030
236.9
-1.4
0.959
220.5
-9.0
9.1
-69.0
400.0
0.967
222.3
-6.9
-19.2
193.4
151NUCPANT
750.0
1200.0
1.022
14.1
-4.1
3018CATDOG_G
3006UPTOWN -1
4.1
1.028
514.0
-1.8
200.0
78.7
-66.1
1.020
22.0
16.5
-6.8
-748.4
1.017
508.5
-1.1
-6.8
-264.5
295.8
-354.2
206URBGEN
700.0
-42.6
600.0
0.949
218.3
-9.2
26.1
83.8
-208.3
276.5
-122.4
-53.9
-75.8
750.0
-264.8
-128.5
800. 0
31.8
42.7
AREA 1 (FLAPCO) AREA 2 (LIGHTCO)AREA 5 (WORLD)
564.8
130.9 MW
-538.3 Mvar
358.7 MW
184.0 Mvar
1000.0 MW
800.0 Mvar
Area 1 to 2 Interchange
Area 5 Generation
Bus 154 Load
PSS(R)E PROGRAM APPLICATION GUIDE EXAMPLE
153MID230
750.0
-748.4
750.0
191.2
-561.3
202EAST500
-16.3
1.040
14.4
0.0
1
0.0
614.4
1
0.0
-324.5
-597.7
1
0.0
-46.7
1
0.0
-270.2
603.2
67.3
-590.7
-148.2
236.8
98.8
-34.8
-18.0
1
0.0
-264.5
Bus - VOLTAGE (kV/PU)/ANGLE
Fig. 2. Topology of PSS/E 23-bus system [15].
time / sec250 0 100 200 300 450
Line tripping
154-203Training
Stage
Line closure
154-203
Line tripping
152-153
Line closure
152-153
(a) Line Tripping Event
time / sec250 0 100
Unit tripping
102Training
Stage
(b) Unit Tripping Event
time / sec250 0 100 200
Training
Stage
(c) Input Change Event
102
ref 0.01V !211
ref 0.01V ! "
Fig. 3. Timeline of three simulated system events.
0 5 10 15 20 2599.96
99.97
99.98
99.99
100
100.01
Number of PCs
%
Cumulative Variance for Bus Frequency
Fig. 4. Cumulative variance preserved by PCs of ω in Case A.
0 100 200 300 400 500 600
0.999
1
1.001
1.002
1.003
Time (s)
Bus F
requency (
p.u
.)
ω154
Profile During Line Tripping Event
Fig. 5. Frequency profile for ω154 during line tripping event.
99 99.5 100 100.5 101 101.5 102−500
0
500
Time (s)
PI
Zoomed−in PI of ω154
0 100 200 300 400 500 600−500
0
500
Time (s)
PI
PI of ω154
Fig. 6. PIω of line tripping event.
be observed that both PIω205 and PIω
3011 are capable to detect
4
0 100 200 300 400 500 600−500
0
500
Time (s)
PI
PI of ω3011
0 100 200 300 400 500 600−500
0
500
Time (s)
PI
PI of ω205
Fig. 7. PIω of nearby and remote buses in line tripping event.
the event at an early stage.
In summary the proposed PIω of any bus is shown to be
capable of detecting the line tripping event efficiently.
3) Unit Tripping Event: Generator 102 is assumed to be
tripped at time t = 100 sec, as shown in Fig. 3(b). The
frequency profile of bus 102 is depicted in Fig. 8, with the
PIω s shown in Figs. 9 and 10.
From Fig. 9, generator 102 tripped at t = 100 sec yields
PIω102 > 3000. From the frequency profile in Fig. 8, the
deviation of ω102 is only about 0.002 pu at t = 100 sec whereas
it is difficult to use ω102 directly to indicate a unit tripping
event. The proposed PI however is capable of magnifying
the difference between normal condition and contingency
quantities.
Fig. 10 shows PIω of buses which are nearby (bus 151) and
remote (bus 3018) to the unit tripping bus. The large values of
PIω s during the event suggest that PIω of any bus can detect
the unit tripping event quickly.
4) Control Input Change Event: As shown in Fig. 3(c), the
voltage regular set points of buses 102 and 211 are changed
by 0.01 pu at t = 100 sec and −0.01 pu at t = 200 sec,
respectively. The frequency profile of bus 211 is shown in
Fig. 11, with the PIω depicted in Figs. 12 and 13.
From Fig. 12, PIω211 provides a clear indication of both input
change events. From the zoomed-in figure, one can observe
that the first event is detected at time t = 100.033 sec, while
the frequency profile in Fig. 11 cannot provide such a clear
detection until t = 100.5 sec.
Fig. 13 shows PIω s of a nearby bus 201 and a remote bus
3018, and both events can be detected by either PIω201 or PIω
3018.
This again illustrates that PIω of any bus can detect control
input changes at an early stage.
B. Realistic PMU Data From ERCOT
In this case, we will demonstrate the proposed algorith-
m using the realistic PMU data from ERCOT, without the
knowledge of system topology. We note that the usability of
our method even without knowing the system topology is a
potentially very important capability of our EED algorithm.
Data of 7 PMUs on two separate days are utilized as the offline
training data and the online prediction data, respectively.
Fig. 14 indicates that there are 2 events in the real-time
system, happening around t = 354 sec and t = 1113 sec.
i) Offline Training: We perform PCA on the 7 bus frequency
data on the first day. The cumulative variance is shown in
0 50 100 150 200 250 300 3500.9
0.92
0.94
0.96
0.98
1
Time (s)
Bus F
requency (
p.u
.)
ω102
Profile During Unit Tripping Event
99 99.5 100 100.5 101 101.5 1020.96
0.97
0.98
0.99
1
1.01
Time (s)
Bus F
requency (
p.u
.)
Zoomed−in ω102
Profile
Fig. 8. Frequency profile for ω102 during unit tripping event.
0 50 100 150 200 250 300 350−5000
0
5000
Time (s)
PI
PI of ω102
99 99.5 100 100.5 101 101.5 102−5000
0
5000
Time (s)
PI
Zoomed−in PI of ω102
Fig. 9. PIω of unit tripping event.
0 50 100 150 200 250 300 350−5000
0
5000
Time (s)
PI
PI of ω3018
0 50 100 150 200 250 300 350−5000
0
5000
Time (s)
PI
PI of ω151
Fig. 10. PIω of nearby and remote buses in unit tripping event.
0 50 100 150 200 250 3000.9998
0.9999
1
1.0001
Time (s)
Bus F
requency (
p.u
.)
ω211
Profile During Input Change Event
99 99.5 100 100.5 101 101.5 1020.9998
0.9999
1
1.0001
Time (s)
Bus F
requency (
p.u
.)
Zoomed−in ω211
Profile
Fig. 11. Frequency profile for ω211 during input change event.
Fig. 15. We select m = m′ = 2, and the basis matrix is Y ωB =
[ω3, ω5].ii) Online Prediction: Using equation (2), PIω for the non-
pilot frequencies can be calculated. For illustration, PIω4 is
shown in Fig. 16. In the zoomed-in figures, the detection of
changes of system operating conditions can be achieved at
t = 354 sec and t = 1113 sec, respectively. However, from the
frequency profile in Fig. 14, the frequency deviation at t = 354
sec is only 0.0005 pu, which is too small to be detected. Again,
5
0 50 100 150 200 250 300−1000
−500
0
500
1000
Time (s)
PI
PI of ω211
99 99.5 100 100.5 101 101.5 102−1000
−500
0
500
1000
Time (s)
PI
Zoomed−in PI of ω211
Fig. 12. PIω of input change event.
0 50 100 150 200 250 300−1000
−500
0
500
1000
Time (s)
PI
PI of ω3018
0 50 100 150 200 250 300−1000
−500
0
500
1000
Time (s)
PI
PI of ω201
Fig. 13. PIω of nearby and remote buses in input change event.
0 200 400 600 800 1000 1200
0.996
0.998
1
Time (s)
Bus F
requency (
p.u
.)
ω1 Profile
Fig. 14. Frequency profile for ω1.
1 2 3 4 5 6 799.994
99.996
99.998
100
100.002
Number of PCs
Cumulative Variance for Bus Frequency
%
Fig. 15. Cumulative variance preserved by PCs of ω in Case B.
0 200 400 600 800 1000 1200
−500
0
500
Time (s)
PI
PI of ω4
353 353.5 354 354.5 355 355.5 356 356.5 357−500
0
500
Time (s)
PI
Zoomed−in PI of ω4 for 1
st Event
1112 1112.5 1113 1113.5 1114 1114.5 1115 1115.5 1116
−500
0
500
Time (s)
PI
Zoomed−in PI of ω4 for 2
nd Event
Fig. 16. PIω for ω4.
the efficacy of using PIω rather than ω itself is demonstrated.
V. CONCLUSION
In this paper, we present a PCA-based dimensionality reduc-
tion method for online PMU data. A linear representation of
the basis is first obtained by PCA in the offline training using
historical data. The pilot PMUs are then applied in the online
prediction. We propose a performance index PI based on the
prediction error to detect system events at an early stage.
Two simulated examples illustrate the efficacy of the pro-
posed EED algorithm. It has been shown that based on the
prediction error, the defined PIω ’s are capable to detect system
events at an early stage. Although only bus frequency is
analyzed in this paper due to page limitation, the phase angle
and voltage magnitude are also under analysis and results will
be included in our future work.
Further work will focus on the theoretical justifications of
the connection between the early detection of system events
and the prediction error from PCA-based learning. More realis-
tic data will be used to test the proposed algorithms. Nonlinear
methods such as embedding will be used and applied for
higher accuracy of early detection [16], [17].
REFERENCES
[1] J. Thorp, A. Abur, M. Begovic, J. Giri, and R. Avila-Rosales, “Gaininga wider perspective,” Power and Energy Magazine, IEEE, vol. 6, no. 5,pp. 43–51, 2008.
[2] J. Jiang, J. Yang, Y. Lin, C. Liu, and J. Ma, “An adaptive PMU basedfault detection/location technique for transmission lines: I. theory andalgorithms,” Power Delivery, IEEE Transactions on, vol. 15, no. 2, pp.486–493, 2000.
[3] R. Diao, K. Sun, V. Vittal, R. O’Keefe, M. Richardson, N. Bhatt,D. Stradford, and S. Sarawgi, “Decision tree-based online voltagesecurity assessment using PMU measurements,” Power Systems, IEEE
Transactions on, vol. 24, no. 2, pp. 832–839, 2009.[4] Y. Makarov, P. Du, S. Lu, T. Nguyen, X. Guo, J. Burns, J. Gronquist, and
M. Pai, “PMU-based wide-area security assessment: Concept, method,and implementation,” Smart Grid, IEEE Transactions on, vol. 3, no. 3,pp. 1325–1332, 2012.
[5] N. Dahal, R. King, and V. Madani, “Online dimension reduction ofsynchrophasor data,” in Transmission and Distribution Conference and
Exposition (T&D), 2012 IEEE PES. IEEE, 2012, pp. 1–7.[6] Z. Zhong, C. Xu, B. Billian, L. Zhang, S. Tsai, R. Conners, V. Centeno,
A. Phadke, and Y. Liu, “Power system frequency monitoring network(FNET) implementation,” Power Systems, IEEE Transactions on, vol. 20,no. 4, pp. 1914–1921, 2005.
[7] L. Wang, J. Burgett, J. Zuo, C. Xu, B. Billian, R. Conners, and Y. Liu,“Frequency disturbance recorder design and developments,” in Power
Engineering Society General Meeting, 2007. IEEE. IEEE, 2007, pp.1–7.
[8] I. Fodor, “A survey of dimension reduction techniques,” Center for
Applied Scientific Computing, Lawrence Livermore National Laboratory,vol. 9, pp. 1–18, 2002.
[9] L. Van der Maaten, E. Postma, and H. Van Den Herik, “Dimension-ality reduction: A comparative review,” Journal of Machine Learning
Research (submited), 2009.[10] K. Anaparthi, B. Chaudhuri, N. Thornhill, and B. Pal, “Coherency
identification in power systems through principal component analysis,”Power Systems, IEEE Transactions on, vol. 20, no. 3, pp. 1658–1660,2005.
[11] Y. Zhang, Z. Wang, J. Zhang, and J. Ma, “PCA fault feature extraction incomplex electric power systems,” Advances in Electrical and Computer
Engineering, vol. 10, no. 3, pp. 102–107, 2010.[12] Z. Wang, Y. Zhang, and J. Zhang, “Principal components fault location
based on WAMS/PMU measure system,” in Power and Energy Society
General Meeting, 2011 IEEE. IEEE, 2011, pp. 1–5.[13] Mar. 2012. [Online]. Available:
http://www.eia.gov/todayinenergy/detail.cfm?id=5630[14] S. Van De Geer, “Estimating a regression function,” The Annals of
Statistics, pp. 907–924, 1990.[15] P. Siemens, “PSS,” E 30.2 Program Operational Manual, 2009.[16] J. Tenenbaum, V. De Silva, and J. Langford, “A global geometric
framework for nonlinear dimensionality reduction,” Science, vol. 290,no. 5500, pp. 2319–2323, 2000.
[17] S. Roweis and L. Saul, “Nonlinear dimensionality reduction by locallylinear embedding,” Science, vol. 290, no. 5500, pp. 2323–2326, 2000.