digital generator protection system

25
1 Industrial Systems Digital Generator Protection System Microprocessor Based Protection, Control and Monitoring System Waveform Sampling User Friendly GE/Hydro Quebec Joint Development

Upload: laurie

Post on 30-Jan-2016

62 views

Category:

Documents


1 download

DESCRIPTION

Digital Generator Protection System. Microprocessor Based Protection, Control and Monitoring System Waveform Sampling User Friendly GE/Hydro Quebec Joint Development. System Overview. Multiple Microprocessors Sampling Rate = 12 Samples/Cycle 20 MHz Operation - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Digital Generator  Protection System

1

Industrial Systems

Digital Generator Protection System

• Microprocessor Based Protection, Control and Monitoring System

• Waveform Sampling• User Friendly• GE/Hydro Quebec Joint

Development

Page 2: Digital Generator  Protection System

2

Industrial Systems

Page 3: Digital Generator  Protection System

3

Industrial Systems

System Overview

• Multiple Microprocessors• Sampling Rate = 12 Samples/Cycle• 20 MHz Operation• Auto Gain Change A/D Converter

TIME SYNCH(IRIG-B)

6 CONTACTINPUTS

11 AUXILIARYRELAYS

4 TRIPRELAYS

8 CURRENTS

4 VOLTAGES

FILTERANDMUX

ANALOGTO

DIGITALCONVERTER

DSP’S3-TMS320

MMI

MICROPROCESSORS2-80C186

REMOTEPC

DIGITALINPUTS/

OUTPUTS

Page 4: Digital Generator  Protection System

4

Industrial Systems

Applications

• For Small, Medium and Large Generator Protection

• Suitable for Variety of Prime-Movers - Gas, Steam, Hydro Turbines

• Most Commonly Used Protection Functions Packaged in a Standard Modular Case

Page 5: Digital Generator  Protection System

5

Industrial Systems

Protective Functions

• Stator Differential (87G)– Variable Slope Characteristic

• 100% Stator Ground Fault (64G)– Two Overlapping Zones– 95% with Fundamental Neutral OV– 15% with 3rd Harmonic Comparator– or 15% with 27TN Function (Special)

• Time Overcurrent with Voltage Restraint (51V)

• Current Unbalance (46)– Negative Sequence Overcurrent - I22t– Linear Reset Characteristic

• Loss of Excitation (40)– Two Zones of Off-Set Mho

R

X

Offset = X’d 2

Diameter = 1.0 pu

Diameter = Xd

(87G)

(40)

Page 6: Digital Generator  Protection System

6

Industrial Systems

Protective Functions (Cont.)

• Overexcitation or V/Hz (24)– Inverse Characteristic– Instantaneous with Time Delay

• Reverse Power (32)– Two Levels

• Under/Over Frequency (81)– Multiple Steps (2-4)– Undervoltage Cutoff Feature

• Overvoltage (59)– Inverse Characteristic

• Undervoltage (27)• Neutral Overcurrent (51GN)

Relay Characteristic

Transformer Limit Curve onGenerator Voltage Base

Generator Manufacturer’sRecommended Protection Curve

VOLTS/HERTZ (%)

TIME (MINUTES)

140

130

120

110

100

.01 0.1 1.0 10 100

(24)

Page 7: Digital Generator  Protection System

7

Industrial Systems

Additional Protective Features• Voltage Transformer Fuse Failure (VTFF)

– Internal or External– Block 40 and 51V functions

VTFF+DI6

FD

Overcurrent(voltage restraint) 51VAND

Loss of ExcitationZone 1 40-1TL12AND

Loss of ExcitationZone 2 40-2TL13AND

DI6

Ext. VTFF OR

V 2 > 15VSELV2SUP

PUDO

PU=3 SamplesDO=5 Samples

ENA

DIS

Page 8: Digital Generator  Protection System

8

Industrial Systems

Adaptive Sampling Interval - 30.5 - 79.5 Hz

Frequency vs SensitivityDGP Relay System

0

1

2

3

4

5

6

7

8

9

10

11

12

0 10 20 30 40 50 60 70 80 90 100 110

System Frequency (Hz)

Rel

ativ

e S

ensi

tivi

ty

Fixed Sampling Rate of 12 Samples/ Cycle

64G1

32

24

4659

32

Page 9: Digital Generator  Protection System

9

Industrial Systems

Additional Protective Features• Accidental Energization Logic

• Sequential Trip Logic

AE

AND

DI1 - GEN.OFF-LINE

AE ARM

AND50 (51V Pickup Flag) AND AND

VTFF

PUDO

V1 < 30VOR

OR PU=5 secDO=0.25 sec

AND

Reverse Pwr.No. 1

Seq. Trip Enabled

SELBKDI1

AND ANDOR TL1 32-1

DI1 - GEN.OFF-LINE

INLET VALVECLOSED

Page 10: Digital Generator  Protection System

10

Industrial Systems

Inputs

• (8) Currents– Ia, Ib, Ic, In

(Neutral Side)– Ia, Ib, Ic, In

(System Side)• (4) Voltages

– Va, Vb, Vc(Wye or Open Delta)

– Vng(Neutral Ground Xfmr)

• IRIG-B Time Synchronization• (6) Digital Inputs

– Two External Trip (DI3, DI4)

– Generator Off-Line Indication (AE)

– Turbine Inlet Valve Close Indication (Sequential Trip)

– Oscillography Trigger– External VT Fuse Failure

Page 11: Digital Generator  Protection System

11

Industrial Systems

Outputs

• (4) Trip Relays– Two From A Contacts Each– Configurable

• (11) Auxiliary Relays– One Form C Contact Each– Four Configurable Alarm Contacts (74A, 74B, 74C, 74D)– Pre-defined Alarm Contacts

• Critical Self-Test Alarm• Non Critical Self-Test Alarm• VT Fuse Failure Alarm• Test Pickup Indication• Test Trip Indication• Loss of Power Supply No. 1• Loss of Power Supply No. 2

Page 12: Digital Generator  Protection System

12

Industrial Systems

Simplified Logic Diagram

CO

NF

IGU

RA

BL

E L

OG

IC

TRIP A94G

Overvoltage (59)

Accidental Energization (AE)

Stator Differential (87G)

Reverse Pwr.(32-1, 32-2)

Undervoltage (27)

Overcurrent with voltage restraint (51V)

Current Unbalance - Trip, Alarm (46T, 46A)

Loss of Excitation (40-1, 40-2)

Stator Ground - Zone 1, 2 (64G1, 64-2)

Neutral Overcurrent (51GN)

Overexcitation, Trip (24T)Generator On-Line

Overexcitation, Trip (24T)Generator Off-Line

Under Frequency (81-1U, 2U,3U,4U)

OR

TRIP B94G1

OR

TRIP C94G2

OR

TRIP D94G3

OR

ALARM74A

OR

ALARM74B

OR

ALARM74C

OR

ALARM74D

OROver Frequency (81-1O, 2O,3O,4O)

Page 13: Digital Generator  Protection System

13

Industrial Systems

Monitoring

• Present Values• Trip Circuit Monitor• Fault Reports (Last 3 Faults)• Sequence of Events

(Last 100 Events)• Self Tests

Page 14: Digital Generator  Protection System

14

Industrial Systems

Present Value Monitoring

• Currents– System and Neutral Side (Ia, Ib, Ic, In)– Negative Sequence

• Voltages– Va, Vb, Vc– % 3rd Harmonic Voltage (Phase and Neutral)

• Megawatts• Mvars• Frequency• Status of Digital InputsScroll on Command or Display Selected Parameters

Page 15: Digital Generator  Protection System

15

Industrial Systems

Trip Circuit Monitor

• Trip Voltage Monitor– Normal Condition– Four Trip Circuits (94G, 94G1, 94G2,

94G3)• Trip Current Monitor

– Trip Condition– Four Trip Circuits (94G, 94G1, 94G2,

94G3)– Seal-in of Output Relay

• Disable/Enable Feature

Page 16: Digital Generator  Protection System

16

Industrial Systems

Communications

• Local MMI (Standard)

– 2 Level Password Protection

– 16 LED Alphanumeric Display

– Keypad with 20 Keys

– Separate Function Keys for

• Settings

• Action

• Information

– 19 LED Targets

– Status LED

– Local Printer Port (AA, CA models)

Page 17: Digital Generator  Protection System

17

Industrial Systems

Communications

• Remote Access

– Via RS232 & “DGP-LINK” Software

– Front and Rear RS232 Ports

– 3 Level Password Protection

• Access to:

– Present Values

– Fault Report

– Sequence of Events

– Oscillography

– Manual Control

– Relay Settings

Local Functions Setup Help

[ - ] DGP COMMUNICATIONS 1.35

Logout Change access level Hang up phone

Actions . . . Information . . . Settings . . .

Relay Functions

Login

Phone disconnected

Page 18: Digital Generator  Protection System

18

Industrial Systems

Present Values

• Currents• Voltages• Watts• Vars• Frequency• Negative Sequence

Current• 3rd Harmonic Voltage• Status of Digital Inputs

GEN Simulator DGP 0000PRESENT VALUES

Station ID:MALVERN

Generator ID:MODEL GENERATOR

10/28/9314:37:23:446

IAS: 5696.0 A -014 DEGS VAN: 008.5 KV 000 DEGSIBS: 5488.0 A -142 DEGS VBN: 008.1 KV -118 DEGSICS: 4864.0 A 104 DEGS VCN: 008.2 KV 122 DEGSIAR: 5680.0 A -014 DEGSIBR: 5456.0 A -142 DEGSICR: 4880.0 A 104 DEGSNEGATIVE SEQ CURRENT: 08.1 %3RD HARM PH: 00.1 % 3RD HARM N: 03.7%

WATTS: +126.33 MWATT VARS: +041.95 MVAR

GEN OFF-LIN: OPEN INLET VLV: OPENDIG IN 3: OPEN DIG IN 4: OPENOSC TRIG: OPEN EXT VTFF: OPEN

FREQ: 60.00 SAMPLING FREQ: 720.0

Page 19: Digital Generator  Protection System

19

Industrial Systems

Fault ReportFault Report

Prefault– Currents

– Voltages

– Watts

– Vars

– Frequency

Post Fault– Currents

– Voltages

– Trip Targets

– Operating Time

Selected Events Last 3 Faults Stored

Gen Simulator DGP 0000

FAULT REPORT

Station ID:MALVERNGenerator ID:MODEL GENERATOR

FAULT#: 02

FAULT DATE: 08/09/93 TRIP TIME: 05:10:37:829FAULT TYPE: ABCTRIP TYPE: 87G SYSTEM OPERATING TIME: 000008

PREFAULT FAULT-------------------------------------- ------------------------------------------------------IAS: 0128.0 A IAS: 014672 A IAR: 015664 AIBS: 0208.0 A IBS: 015264 A IBR: 016704 AICS: 0080.0 A ICS: 013600 A ICR: 014960 A

INS: 0048.0 A INR: 0384.0 AVAN: 010.2 KVVBN: 010.2 KV VAN: 693.0 VVCN: 010.0 KV VBN: 693.0 V

VCN: 679.4 VFREQ: 60.00 VN: 047.0 V

WATTS: +1888.5 KWATTVARS: +3777.0 KVAR

05:10:37.834 87G PHASE A ON05:10:37.834 87G PHASE B ON

Page 20: Digital Generator  Protection System

20

Industrial Systems

Sequence of Events

• Operational Events– Setting Changes– Fault Data– Status

• Diagnostic Self-Test Events– Warning (Non-Critical

Alarm)– Failure (Critical Alarm)

• Time Tagged to 1ms Resolution

• Last 100 Events Stored• Available at Communication

Port or at Printer Port

GEN Simulator DGP 0000Events

Station ID:MALVERN

Generator ID:MODEL GENERATOR

10/29/93 14:39:54:971 94G TRIP CIRCUIT OPEN ALARM ON10/29/93 14:33:35:661 94G2 TRIP SIGNAL RESET

10/29/93 14:33:35:660 32-1 OFF10/29/93 14:33:35:639 32-2 OFF10/29/93 14:33:34:396 32-1 ON

10/29/93 14:33:31:997 TURBINE INLET VALUE CLOSED10/29/93 14:33:28:423 GENERATOR OFF-LINE10/29/93 14:33:26:452 94G2 TRIP SIGNAL ON

10/29/93 14:33:26:451 32-2 ON10/29/93 14:27:09:878 GENERATOR ON-LINE

10/29/93 14:27:04:968 TURBINE INLET VALUE OPEN10/29/93 14:26:54:263 94G3 TRIP SIGNAL RESET

10/29/93 14:26:54:262 64G1 OFF10/29/93 14:26:50:911 TURBINE INLET VALUE CLOSED

10/29/93 14:26:47:584 GENERATOR OFF-LINE10/29/93 14:26:42:604 94G3 TRIP SIGNAL ON

10/29/93 14:26:42:603 64G1 ON10/29/93 14:25:44:444 GENERATOR ON-LINE

10/29/93 14:25:38:202 TURBINE INLET VALUE OPEN10/28/93 16:32:31:642 REMOTE - SETTINGS CHANGE DONE

10/28/93 16:32:30:882 REMOTE - SETTINGS CHANGE STARTED

Page 21: Digital Generator  Protection System

21

Industrial Systems

Sequence of Events

• Events Include:– Trip Signal ON / RESET– Protection Function ON / OFF– Digital Input Status– VT Fuse Failure Alarm ON / OFF– Trip Circuit Open Alarm ON / OFF– Trip Circuit ENERGIZED / NOT ENERGIZED– Password Changed– ENABLE / DISABLE Outputs– Setting Change START / DONE– Failure Messages (Critical Self-Test Alarm)– Warning Messages (Non-Critical Self-Test Alarm)

Page 22: Digital Generator  Protection System

22

Industrial Systems

Oscillography Data

Currents and Voltages Digital Flags Internal and External

Oscillography Triggering 120 Cycles of Storage

Capability Up to 20 Cycles Prefault

Data Up to 3 Trip Event Captures ASCII File Format

(Readable by EXCEL/LOTUS/DGP-DATA)

Fault Report and Settings Saved for Each Fault

Page 23: Digital Generator  Protection System

23

Industrial Systems

Hardware and Packaging

• Testing and Trouble Shooting– Optional MOD-10 Modular Test and Connection Plugs

for Current/Voltage Injection

• Draw-Out Modular Construction– Plug-In Modules for Test and Maintenance– Removable Door– Target Clearing Through Door

• Self-Test Diagnostics– Critical Alarm– Non-Critical Alarm

Page 24: Digital Generator  Protection System

24

Industrial Systems

Nomenclature Selection Guide

DGP * * * A * * 1 1 AMP Rated5 5 AMP Rated

0 One power supply, 48 Vdc1 One power supply, 110/125 Vdc2 One power supply, 220/250 Vdc3 Two power supplies, 48 Vdc4 Two power supplies, 110/125 Vdc5 Two power supplies, 220/250 Vdc

A With Test BlocksB Without Test Blocks

A Future UseA Function Group A See B Function Group B DGP SelectionC Function Group C Guide

A Revision Level

Page 25: Digital Generator  Protection System

25

Industrial Systems

DGP Selection GuideFUNCTIONS & FEATURES A B CStator Differential 87G X X XCurrent Unbalance 46 X X XLoss of Excitation 40-1, 40-2 X X XAnti-motoring 32 2 Setpoints 1 Setpoint 2 SetpointsOC - voltage restraint 51V X X XStator Ground 64G1 (Fundamental OV) X X XStator Ground 64G2 (3rd Harm. Comparator) X - XNeutral OC 51GN - X XOver Excitation 24 (Volts/Hz) X X XOver Voltage 59 X X XUnder Voltage 27 - X XUnder Frequency 81-U 4 Setpoints 2 Setpoints 4 SetpointsOver Frequency 81-O 4 Setpoints 2 Setpoints 4 SetpointsAccidental Energization Logic X X XSequential Trip Logic X X XVoltage Transformer Fuse Failure VTFF X X XOscillography Data Capture X - XCommunication Ports 2-RS232 2-RS232 2-RS232Printer Output X - XIRIG-B InputX - X

Example: DGP54BACA - DGP rated 5 amperes, 50/60 Hz, 110/125 VDC redundant powersupplies, no built-in test blocks, function group A, revision A.