alstom - digital integrated generator protection relay

Upload: ninh-quoc-trung

Post on 14-Apr-2018

247 views

Category:

Documents


5 download

TRANSCRIPT

  • 7/29/2019 Alstom - Digital Integrated Generator Protection Relay

    1/24

    Type LGPG111Digital Integrated Generator Protection Relay

  • 7/29/2019 Alstom - Digital Integrated Generator Protection Relay

    2/242

    Features

    An optimum mix of generatorprotection functions

    Applicable to a wide range ofgenerators

    User configurable scheme logic

    An alternative setting group

    Wide operative frequency range

    Display of measured values

    Fault, event and disturbancerecording

    Integral testing to aidcommissioning

    Remote serial communications

    Power-on diagnostics and self-monitoring

    Eight optically isolated logicinputs for monitoring externalplant.

    Type LGPG111Digital Integrated Generator Protection Relay

    Figure 1: Relay Type LGPG111

    Introduction

    The LGPG111 is a multi-functionrelay which integrates a number ofcommon generator protectionfunctions and associated schemelogic into a single relay case.

    Models Available

    LGPG111Incorporating 14 separategenerator protection functions

    (see Figure 2).

    Application

    The LGPG111 can be applied to awide range of generators. Each ofits protection functions can beenabled or disabled to suitindividual requirements.This approach avoids the need forapplication-specific relay versions,and simplifies the tasks of relayspecification, evaluation and projectplanning. The integrated schemelogic eliminates much panelengineering work by reducing theneed for auxiliary relays andassociated external wiring.

    Contacts from external protection

    and plant monitoring equipment canbe connected to any of the eightoptically-isolated inputs. This allowsexternal information to beincorporated into the relays user-configurable scheme logic.The optically-isolated inputs andrelay outputs may be labelled in thesoftware for local or remotemonitoring.These functions can be recorded inthe alarm and event recording

    facilities.

    The protection functions provided bythe LGPG111 relay are as shown inFigure 2.

    Functions

    Generator differential (87G)

    The generator differential function isfor the protection of phase to phaseor three-phase stator windings faults

    which normally involve high faultcurrents, so that fast fault clearanceis required. This function works on aper phase basis and has a dualslope bias characteristic as shown

  • 7/29/2019 Alstom - Digital Integrated Generator Protection Relay

    3/243

    in Figure 3: the lower slopeprovides sensitivity for internalfaults, whereas the higher slopeprovides stability under through faultconditions, especially if thegenerator CTs saturate.

    Stator earth fault (51N)

    The stator earth fault function iscurrent operated and can betypically set to cover up to 95% ofthe stator windings. It is generallyused on resistively earthedgenerators, but can also be used torespond to current in the secondarycircuit of an earthing transformerloaded with a resistor. A time-delayed low set element and aninstantaneous high set element areprovided.

    Neutral displacement (59N)

    The neutral displacement function isvoltage operated and is used fordetecting stator winding earth faultson generators which are earthed viaa distribution transformer. Two timeroutput elements are provided.

    Sensitive directional earthfault (67N)

    When two or more generators are

    connected in parallel directly to abusbar, the sensitive directionalearth fault function is used todiscriminate between internal andexternal earth faults. A dedicatedsingle-phase CT input is availablefor the operating current, which canaccept the residual current fromthree line CTs or current from adedicated core-balance CT.The polarising signal for thedirectional decision is either the

    voltage signal applied to the neutralvoltage VT input or the currentsignal applied to the stator earthfault current input.

    The stator earth fault, neutraldisplacement and sensitivedirectional earth fault functions allhave third harmonic rejection builtin by means of a software filter.

    Voltage dependent

    overcurrent (51V)The voltage dependent overcurrentfunction is used for system backupprotection and can trip thegenerator circuit breaker, if a fault

    Figure 2: Protection functions provided by LGPG111

    Figure 3: Generator differential bias characteristic

    Figure 4: Voltage dependent overcurrent functions

    Currentpick-uplevel

    Currentpick-uplevel

    I>

    KI>

    Vs Voltage

    levelVoltage controlled mode Voltage restrained mode

    I>

    KI>

    Vs2 Vs1 Voltage

    level

    Trip

    Differentialcurrent

    No TripIs1

    Percentagebias K2

    Percentagebias K1

    Maximum mean bias currentIs2

    has not been cleared by otherprotection after a certain period oftime. The voltage dependentfunction can be either voltagecontrolled or voltage restrained.

    When voltage controlled, the timingcharacteristic is changed from aload to a fault characteristic whenthe voltage drops below a set level.

    It is mainly used for generatorsconnected directly to the busbar.

    When voltage restrained, thecurrent pick-up level is

    proportionally lowered as thevoltage falls below a set value,producing a continuous variation oftiming characteristics. This isapplicable to generators connected

    87G Generator dif ferent ia l

    51N Stator earth fault

    59N Neutral displacement

    67N Sensitive directional earth fault

    51V Voltage dependent overcurrent

    32R Reve rse powe r

    32L Low forward power

    46 Negat ive phase sequence40 F iel d f ailu re

    27 Unde rvol tage

    59 Over voltage

    81U Under frequency

    81O Overf requency

    60 Voltage balance

    67N 51N

    59N

    51V 32R32L

    40 46

    2759

    81U81O

    60

    87G

  • 7/29/2019 Alstom - Digital Integrated Generator Protection Relay

    4/244

    to the busbar, each via a step-uptransformer.A voltage vector compensationfeature is also available todetermine the HV phase-phasevoltage signals where a Yd1 or aYd11 step-up transformer is used.

    The timing characteristic can either

    be definite time or IDMT.

    The effects of the voltage level onthe current pick-up level for bothfunctions are shown in Figure 4.

    Reverse power (32R) and lowforward power (32L)

    Reverse power protection is used todetect loss of the prime mover.Low forward power protection canbe applied to steam turbine

    generators where sequentialshutdown is preferable, under lessurgent operations, to avoid over-speeding. Both are balancedconditions, therefore a single phasemeasurement is sufficient. For thisfunction, the relay calculates VIcosfor the A-phase.

    In order to provide the requiredsensitivity, a special current input isused for both of these functions.A compensation angle setting is alsoavailable to compensate for phaseerror of the generators CT and VTsignals. A delayed drop-off timer isincluded in the timing logic whichacts as an integrating timer. Thisallows the relay to trip within thepre-determined time delay, underpulsating power conditions.

    Negative phase sequence (46)

    Negative phase sequence function

    is for the detection of sustainedunbalanced load conditions.Under such circumstances doublefrequency eddy currents are inducedin the rotor of a generator and cancause rapid overheating.The function has a thermal replicacurve which simulates the effects ofpre-fault heating due to low levels ofstanding negative phase sequencecurrent I2. When the I2 value is wellabove threshold, the thermal replica

    approximates to a t = K/I22

    characteristic, where K is thegenerators per-unit current thermalcapacity constant in seconds.

    Figure 5: Negative phase sequence tripping characteristic

    tMAX

    t

    tmin

    I2>> I2

    K

    Figure 6: Field failure protection characteristic

    The tripping characteristic is shownin Figure 5.

    When high values of K are selectedand the negative phase sequencecurrents measured are near to thethreshold, the operating time maybe too slow. In this case, amaximum time setting tMAX isavailable to provide a safe trip time.

    When I2 is high, the operating timemay become too fast and cause lossof discrimination with other powersystem protection under faultconditions. To reduce this risk, the

    inverse characteristic is providedwith an adjustable minimumoperating time setting tMIN.

    A separate thermal capacityconstant setting Kreset is alsoprovided for use when the generator

    is cooling, due to a reduction in I2.This is to cater for rotor componentswith differing cooling time constants.

    An independent alarm element witha definite time output is available forpre-trip warning purposes.

    Field failure (40)

    Severe loss of excitation caused byfield failure can cause a high valueof reactive current to be drawn from

    the power system which canendanger the generator. The fieldfailure protection provided by thisrelay is a single phase impedancemeasuring element with an offset

    Xa

    Xb

    X

    R

  • 7/29/2019 Alstom - Digital Integrated Generator Protection Relay

    5/245

    mho characteristic, as shown inFigure 6. An integrating timingarrangement, identical to that for thepower functions, is also provided.This allows the relay to trip withinthe pre-determined time delay eventhough the impedance measurementmay temporarily fall outside the mho

    characteristic, eg. under pole-slipping conditions.

    Undervoltage (27) andovervoltage (59)

    An undervoltage element and a2-stage overvoltage element areprovided. They are primarily usedfor backing up the speed controlgovernor and the automatic voltageregulator. When severe overvoltageoccurs, the high set of the

    overvoltage element can be set toprovide fast operation.Both elements are three-phasedevices.

    Underfrequency (81U) andoverfrequency (81O)

    Two underfrequency elements andone overfrequency element areprovided. The underfrequencyelements are used to detectoverloading of the generator caused

    by various system disturbances oroperating conditions.The overfrequency element is usedto back-up the speed controlgovernor if overspeeding occurs.

    Voltage balance (60)

    The voltage balance function isprovided to detect VT fuse failure.It compares the secondary voltagesof two sets of VTs (or from twoseparately fused circuits of a singleVT) and can be used to blockpossible incorrect tripping of thoseprotection functions whoseperformance may be affected by theapparent loss of voltage such aswhen a VT fuse ruptures.

    Timer held facility

    Both the overcurrent function, thelow set element of the stator earthfault function and the neutraldisplacement function are providedwith a timer held facility.The purpose is to enable fasterclearance of recurrent intermittentfaults, for example, self-sealinginsulation faults. This facility allows

    the relay timer to hold its valuewhen the current drops off, providedthat the drop-off period is less thanthe tRESET timer setting.This adjustable reset facility alsoenables closer co-ordination withelectromechanical induction discrelays.

    Integrating timer facility

    Time integration is required for thepower function to allow forreciprocating load conditions wherethe measuring element may pick upbriefly and periodically. The samefeature is also provided for the fieldfailure function for pole-slippingconditions. Time integration allowsthe function to operate within its pre-determined operating time.

    To implement timing integration, anadditional delayed drop-off timer isprovided. Once the protectionmeasurement element has pickedup, the relay will operate after theset time delay, provided that thetime interval when the elementdrops off is within the setting of thedelayed drop-off timer tDO.

    Frequency tracking

    The relay tracks the power systemfrequency and continuously adjustsits internal sampling clock to exactmultiples of the system frequency.This provides correct measurementsand operation of the protectionfunctions during start-up and run-down of the generator set when thegenerator unit is operated at

    abnormal frequency. The operatingfrequency range is from 25Hz to70Hz for the differential functionand from 5Hz to 70Hz for the otherprotection functions.

    Configuration

    Scheme logicThe protection scheme logic for agenerator set normally involves alarge number of protection functionscombined together to drive a fewcommon trip outputs. Some blockingand interlocking logic may also berequired. In order to accommodatedifferent generator applications, thescheme logic is flexible andreconfigureable.

    The LGPG111 scheme logic is in theform of logic arrays with anarchitecture commonly found inprogrammable logic array devices,having an internal AND-ORstructure shown in Figure 7.

    The OR functions allow one or moreof the AND function outputs tocontrol each output relay, whilst theAND functions provide blocking orinterlocking for two or more inputs,or just a through connection for one

    input. There are 32 inputs to thescheme logic: 19 from theprotection functions, 8 optically-isolated inputs and a selection ofinverted inputs to allow blockinglogic to be created. The schemelogic controls a total of 15 outputrelays and has 32 selectable ANDfunctions.

    Figure 7: Block diagram of the scheme logic

    From protection elementsand status inputs

    Output matrix

    Input matrix

    AND

    AND

    AND

    OR OR OR

    To output relays

  • 7/29/2019 Alstom - Digital Integrated Generator Protection Relay

    6/246

    20ms. Thus the duration of a recordvaries with the data type. For rawdata, the duration is 64 electricalcycles, but for magnitude and phasedata, the duration is 7.68s.The latter set-up allows longduration events such as pole-slipping to be captured. In either

    case, each data entry is timestamped. This is particularly usefulfor the raw data recording, sincethe sampling interval varies with thepower system frequency, due to thefrequency tracking.

    The disturbance recorder can betriggered from selected relay outputsand status inputs. A maximum oftwo records can be stored in volatilememory. A record remains in thebuffer area until it is uploaded to a

    PC, after which the buffer isreleased. If the two buffers are full,no further recording can be made.

    Time synchronisation

    The clock for event record timetagging has a resolution of 1ms.To provide time synchronisation withother equipment in the generatorstation, the clock can besynchronised by external clockpulses (0.5, 1, 5, 10, 15, 30 or 60minute period) from an optically-isolated input.

    Print functions

    Several print functions are providedto allow the relay to provide hard-copy documentation, via the frontpanel parallel port. This consists ofthe system settings, protectionsettings, scheme logic settings, eventrecords and fault records.

    The scheme logic print-out isformatted so that it can becompared directly with the schemelogic diagram.

    Test features

    A number of features are providedto enable the relay to be thoroughlytested during commissioning, routinemaintenance and fault findingoperations:

    The measurement functions allow

    the analogue input and itsassociated wiring to be checked.

    Display the on/off states of thestatus inputs and relay outputs.

    The input and output matrices allowthe desired connections to becreated. Each intersection of thematrix represents a programmableinterconnection. By designing theappropriate interconnections andthen entering the information intothe relay, through the scheme logic

    settings, the required tripping logiccan be configured.

    The presence of the optically-isolated inputs to the scheme allowsexternal devices such as rotor earthfault relay, temperature sensingdevices and mechanical relays to beconnected to the scheme, so that thetripping facilities, together with thealarm and remote communicationfacilities, can be utilised.

    The optically-isolated inputs andrelay outputs used in a scheme maybe allocated to any functionrequired by the application.The relay has a facility to label eachof these by providing an identifier.The identifiers are used during theconfiguration of the scheme logic,by the input and output statusdisplays and by the event, fault anddisturbance recording systems.

    Alternative setting groupThe relay provides an alternativesetting group which consists of allthe protection and scheme logicsettings. It can be used during start-up or run-down of generators orduring changes in power systemconfiguration. This setting group canbe selected by either energising theappropriate optically-isolated inputs,or via the relay settings menu.

    Ancillary Functions

    Measurements

    The magnitudes of all 17 analogueinputs to the relay are available fordisplay. Other derived quantities arealso available. This provides suchinformation as the three-phase,

    residual and earth currents, thephase to phase voltages, differentialand bias currents, negative phasesequence current, phase A activeand reactive power plus the phaseangle and power system frequency.All measurements can be displayedin either primary or secondaryquantities, selectable by the user.Primary display quantities are basedon the settings for the CT and VTratios used by the relay.

    Event and fault records

    Up to 100 event records areavailable, all of them stored in non-volatile memory. The latest recordwill automatically overwrite theoldest one. Event records aregenerated whenever there is aprotection function operation,energisation of a status input,operation of an output relay or anyhardware failure.

    Fault records are also stored asevents. Out of the 100 eventrecords, up to 50 fault records canbe accommodated. Fault recordsare initiated when user selectedrelay outputs operate. The recordconsists of the date and time of thefault, the state of the optically-isolated inputs, relay outputs andprotection functions, together withthe measurement values during the

    fault.

    Disturbance records

    The internal disturbance recordercan store up to eight analoguechannels, together with all the statusinput and relay output information.The analogue channels are userselectable from the relays 17inputs.

    The data in the analogue channels

    can be stored as either raw data oras magnitude and phase data.The raw data is sampled at 12samples per electrical cycle,whereas the magnitude and phasedata are calculated once every

  • 7/29/2019 Alstom - Digital Integrated Generator Protection Relay

    7/247

    Testing the four indicating LEDs.

    Testing the relay outputs and theirassociated circuits by operatingthe relay output contacts.

    Display the operation of eachprotection function as apercentage of the time-to-trip.

    This allows the pick-up, progressand operation of each protectionfunction to be checked.

    Testing the set-up of the schemelogic settings by manuallyentering an input pattern to thescheme, and then examining itslogical output. This test can beperformed at any time withoutinterfering with the relaysoperation.

    Power-on diagnostics and selfmonitoring

    Power-on diagnostic tests arecarried out by the relay when it isenergised. These tests includechecks on the timer, microprocessor,memory and the analogue inputmodule. Continuous self-monitoring,in the form of watchdog circuitry,memory checks and analogue inputmodule tests, is also performed. Inthe event of a failure, the relay willeither lock-out or attempt a recovery,depending on the type of failuredetected.

    Hardware Description

    The relay is housed in a 4U(178mm) high case suitable foreither rack or panel mounting.Internally, it consists of a number ofplug-in modules which areindividually tested and calibrated.The modular hardware architectureis shown in Figure 8.

    The microcomputer module consistsof a powerful 16-bit microcomputerwhich controls all of the subsidiarymodules through a 64-way ribboncable called the I/O Bus.The processor performs all of themajor software functions such asinput signal processing, protectionalgorithms, scheme logic, relayoutput controls and handling of the

    operator interface.The analogue input module consistsof 12 CTs, 5 VTs and 6 optically-isolated inputs. The CTs and VTs areused to isolate and condition theanalogue inputs from the maintransformers connected to thegenerator. Their output signals arethen converted into digital data forfurther processing.

    In addition to the 6 optically-isolated

    inputs on the analogue module, afurther 8 are provided by the statusinput module, making a total of 14optically-isolated inputs available tothe relay. Six of these have pre-defined functions, such as clocksynchronisation, setting groupselection, etc., which leaves 8 inputsto be fed into the scheme logic.

    All of the optically-isolated inputsoperate from an auxiliary supplyVx(2), which is independent of themain auxiliary supply Vx(1).The ratings of Vx(1) and Vx(2) maybe different (see Technical Data).

    Two relay output modules areprovided; each module contains 8

    miniature relays. All relays are self-reset. However, a software functionis available which allows the user toselect outputs to be latched whenoperated.

    The front panel consists of a 2 x 16character alphanumeric liquidcrystal display (LCD) and a 7 push-button keypad. It provides localaccess to all of the relays features.There are also 4 light emitting

    diodes for visual indication of therelays status, a non-isolatedIEC 60870 serial port forconnection to a PC, and a parallelport for connection to a printer.

    At the rear of the relay, apart fromthe normal dc supply and plantconnections, there is an isolatedIEC 60870 port and a K-Bus portfor permanent connection to aremote PC.

    The remote communications moduleis responsible for handling thecommunications protocol and forcontrolling the three communicationports.

    Figure 8: Hardware architecture

    Relay

    outputs

    Remote

    comms

    Status

    input

    Analogue

    inputs

    Front

    panel

    Microcomputer

    Powersupply

    I/O bus

  • 7/29/2019 Alstom - Digital Integrated Generator Protection Relay

    8/248

    User Interface

    Front panel user interface

    The features of the relay can beaccessed through a user-friendlymenu system. The menu is arrangedso that related items (menu cells) aregrouped into individual sections,

    each of which is identified by a title.The user navigates around the menuby using the arrow keys, first toselect a particular section title andthen to select an item within it.The front panel liquid crystal displayis limited to displaying one menucell at a time.

    Remote access user interface

    The menu can be accessed via theremote communications facility.

    This allows all of the menu cells in asection to be displayed on thescreen of a PC. Changes to themenu cell can be made from the PCkeyboard.

    Relay interconnection

    Three communication ports areavailable: the front panel, non-isolated IEC 60870 port; the rear,isolated IEC 60870 port; and theK-Bus port. The IEC 60870 ports useRS232 signal levels and allow point-to-point connection. It is applicablewhen networking is not required orduring commissioning.

    Alternatively, the relays can beconnected via a shielded, twistedpair called K-Bus. Up to 32 relaysmay be connected in parallel to thebus.K-Bus can be connected through aprotocol converter, type KITZ, either

    directly or via a modem, to theRS232 port of a PC. K-Bus is RS485based and runs at 64kbits/s.The K-Bus connection is shown inFigure 9.

    Software is available with each KITZto provide access to the relays, toread and change settings.Additional software entitledProtection Access Software andToolkit is available to give access tothe event recorder, together withother additional functions.

    Each relay is directly addressablevia the bus to allow communicationwith the PC. It should be noted thatprotection tripping and blockingsignals are not routed via the K-Bus.Separate conventional wiring isused for these functions.

    Figure 9: K-Bus terminals connection arrangement

    SK1

  • 7/29/2019 Alstom - Digital Integrated Generator Protection Relay

    9/24

  • 7/29/2019 Alstom - Digital Integrated Generator Protection Relay

    10/24

    10

    Figure 11: Type LGPG111 scheme logic

    Relay14

    Relay15

    Logic 0Logic 1Logic 2Logic 3

    &&&&

    Logic 4Logic 5Logic 6Logic 7

    &&&&

    Logic 8Logic 9Logic 10Logic 11

    &&&&

    Logic 12Logic 13Logic 14Logic 15

    &&&&

    Logic 16Logic 17

    Logic 18Logic 19

    &&

    &&

    Logic 20Logic 21Logic 22Logic 23

    &&&&

    Logic 24Logic 25Logic 26Logic 27

    &&&&

    Logic 28Logic 29Logic 30Logic 31

    &&&&

    Input13

    Input12

    Input11

    Input10

    Input9

    Input9

    Input8

    Input8

    Input7

    Input7

    Input6

    Input6

    60VBProt(Blocking)

    60VBComp

    60VBProt

    40FieldFailure

    67NSensitiveDirEF

    59N2NeutralDisp

    59N1NeutralDisp

    51N>>StatorEF

    51N>StatorEF

    46>>NPSTrip

    46>NPSAlarm

    59OverVoltage

    27Undervoltage

    81U2Underfreq

    81U1Underfreq

    81OOverfreq

    32LLow

    ForwardPower

    32RReversePower

    51VOverCurrent

    87GGeneratorDiff

    Input Matrix

    Output Inhibited

    EN

    Note: Speed of the relay outputs are:

    Relays 1, 2, 8, 9, 10 8ms pick-up, 8 ms drop-off

    Relays 3, 11 2ms pick-up, 2ms drop-off

    Relays 4, 5, 6, 7,

    12, 13, 14, 152ms pick-up, 8ms drop-off

  • 7/29/2019 Alstom - Digital Integrated Generator Protection Relay

    11/2411

    Technical Data

    Ratings

    Inputs

    AC current In 1A or 5A

    AC voltage Vn 100V to 120V

    Nominal dc Operative range(V) (V)

    Auxiliary voltage Vx(1) 24/27 19.2 32.4(Relay power supply) 30/34 24 40.8

    48/54 38.4 64.8110/125 88 150220/250 176 300

    Auxiliary voltage Vx(2) 24/27 19.2 32.4(Optically isolated status input supply) 30/34 24 40.8

    48/54 38.4 64.8110/125 88 150220/250 176 300

    Note: Vx(2) may be different fromVx(1)

    Frequency Fn 50/60Hz

    Burdens

    AC current

    Generator differential

  • 7/29/2019 Alstom - Digital Integrated Generator Protection Relay

    12/2412

    CT requirements

    Generator differential

    Biased differential Vk 50In (Rct + 2RL + Rr) where maximumsettings at Is1=0.05In, through fault currentk1=0%, Is2=1.2In, = 10 x In andk2=150% maximum X/R = 120

    Vk 30In (Rct + 2RL + Rr) where maximum

    through fault current= 10 x In andmaximum X/R = 60

    Note: Minimum knee point voltage = 34V

    Earth fault protection functions

    Sensitive directional Vk 6In (Rct + 2RL + Rr) where maximumearth fault, using three X/R = 5 andresidually connected maximum earth faultline CTs current = 1 x In

    Sensitive directional Vk 6NI

    n(R

    ct+ 2R

    L+ R

    r) where maximum

    earth fault, using core X/R = 5 andbalance CT maximum earth fault

    current = 2 x In

    Stator earth fault Vk 6NIn (Rct + 2RL + Rr)

    Ancillary protection functions

    Voltage dependent Vk 20In (Rct + 2RL + Rr)overcurrent, field failureand negative phasesequence

    where Vk = Minimum current transformer knee-point voltage for stabilityIn = Relay rated current (1A or 5A)

    Rct = Resistance of current transformer secondary winding ()

    RL = Resistance of a single lead from relay to current transformer ()

    Rr = Resistance of any other protection functions sharing the currenttransformer ()

    N =Maximum earth fault current

    Core balanced CT or earth CT rated primary current

    Note: N should not be greater than 2. The core balance CT or earth CT

    ratio must be selected accordingly.

    Power function

    For settings >3% Pn Use correctly loaded class 5P protection CT

    For settings 3% Pn Use metering class CT. See table below.

  • 7/29/2019 Alstom - Digital Integrated Generator Protection Relay

    13/2413

    Metering CT class recommended forpower setting less than 3%Pn

    Reverse/low forward Power Setting Metering CT Class(%Pn)

    0.20.1

    0.4

    0.6

    0.80.2

    1.0

    1.2

    1.4

    1.6

    1.8

    2.0 0.5

    2.2

    2.4

    2.62.8

    1.03.0

    Thermal withstand

    Continuous withstand CT input 4 x InVT input 400V

    Short time withstand CT input 100A for 1s (In = 1A)400A for 1s (In = 5A)

    Setting ranges

    Generator differential

    Basic differential current setting Is1 0.05In to 0.1In in 0.01In steps

    Threshold for increase bias Is2 1In to 5In in 0.1In steps

    Bias K1 (Ibias < Is2) 0% to 20% in 5% steps

    Bias K2 (Ibias > Is2) 10% to 150% in 10% steps

    Stator earth fault

    Low set element:

    Characteristic Standard inverse/Definite time

    Current setting Ie> 0.005In to 0.5In in 0.005In steps

    Time multiplier setting TMS 0.05 to 1.2 in 0.05 steps

    IDMT Operating characteristic t =0.14

    (I/Ie>)0.021x TMS

    Definite time setting t> 0.1s to 10s in 0.1s steps

    Reset timer setting tRESET 0s to 60s in 1s steps

    High set element:

    Current setting Ie>> 0.005In to 2In in 0.005In steps

    Time setting t>> 0s to 5s in 0.1s steps

  • 7/29/2019 Alstom - Digital Integrated Generator Protection Relay

    14/2414

    Neutral displacement

    Voltage setting Ve> 1V to 25V in 1V steps

    Timer 1 setting t1 0.5s to 5s in 0.5s steps

    Timer 2 setting t2 1s to 10s in 1s steps

    Timer 2s reset timer t2RESET 0s to 60s in 1s steps

    Sensitive directional earth fault

    Operating current Ires> 0.005In to 0.02In in 0.005In steps

    Polarising voltage Vp> 1V to 10V in 1V steps

    Polarising current Ip> 0.005In to 0.02In in 0.005In steps

    Relay characteristic angle RCA 95 to 95 in 1 steps

    Voltage dependent overcurrent

    Functions Voltage controlled/Voltagerestrained/Simple

    Characteristic Standard Inverse/Definite Time

    Current setting I> 0.5In to 2.4In in 0.05In steps

    Time multiplier TMS 0.05 to 1.2 in 0.05 steps

    IDMT Operating characteristic t = 0.14(I/I>)0.021

    x TMS

    Definite time setting t 0s to 10s in 0.1s steps

    Reset timer setting tRESET 0s to 60s in 1s steps

    Voltage settings:

    Vs (for voltage controlled) 20V to 120V in 1V steps

    Vs1 (for voltage restrained) 80V to 120V in 1V stepsVs2 (for voltage restrainted) 20V to 80V in 1V steps

    K factor 0.25 to 1.00 in 0.05 steps

    Voltage vector rotate None or Yd

    Current pick-up level

    Voltage Controlled Voltage Restrained

    I> for V> Vs I> for V > Vs1

    KI> for V Vs KI>I> KI>

    VS1 VS2+ (V V

    S2)for Vs1 V Vs2

    KI> for V < Vs2

    Reverse power

    Power setting P> 0.2W to 8W in 0.05W steps(for 1A relay)

    1W to 40W in 0.25W steps(for 5A relay)

    Delayed pick-up timer t 0.5s to 10s in 0.5s steps

    Delayed drop-off timer tDO

    0s to 5s in 0.1s steps

  • 7/29/2019 Alstom - Digital Integrated Generator Protection Relay

    15/2415

    Low forward power

    Power setting P< 0.2W to 8W in 0.05W steps(for 1A relay)

    1W to 40W in 0.25W steps(for 5A relay)

    Delayed pick-up timer t 0.5s to 10s in 0.5s steps

    Delayed drop-off timer tDO 0s to 5s in 0.1s stepsCompensation angle comp 5 to +5 in 0.1 steps(for both reverse andlow forward power)

    Note: The power settings are single phase quantities.

    Negative phase sequence trip element

    Trip threshold setting I2>> 0.05In to 0.5In in 0.01In steps

    Thermal capacity constant (heating) K 2s to 40s in 1s steps

    Thermal capacity constant (cooling)

    Kreset 2s to 60s in 1s stepsOperating characteristic K

    I2>>2t = 1loge

    I2>>I2

    2

    (under no pre-heating condition)

    Maximum operating time tmax 500s to 2000s in 10s steps

    Minimum operating time tmin 0.25s to 40s in 0.25s steps

    Negative phase sequence alarm element

    Alarm threshold I2> 0.03In to 0.5In in 0.01In steps

    Alarm timer setting t> 2s to 60s in 1s steps

    Field failure

    Mho offset Xa 2.5 to 25 in 0.5 steps(for 1A relays)0.5 to 5 in 0.1 steps(for 5A relays)

    Mho diameter Xb 25 to 250 in 1 steps(for 1A relays)5 to 50 in 0.2 steps(for 5A relays)

    Delayed pick-up timer t 0s to 25s in 0.1s steps

    Delayed drop-off timer tDO 0s to 5s in 0.1s steps

    Undervoltage

    Voltage setting V< 30V to 110V in 1V steps

    Timer setting t 0.1s to 10s in 0.1s steps

    Overvoltage

    Voltage settings V> ,V>> 105V to 185V in 1V steps

    Timer settings t>, t>> 0s to 10s in 0.1s steps

  • 7/29/2019 Alstom - Digital Integrated Generator Protection Relay

    16/2416

    Underfrequency

    Frequency settings F1< ,F2< 40Hz to 65Hz in 0.05Hz steps

    Timer settings t1, t2 0.1s to 25s in 0.1s steps

    Overfrequency

    Frequency settings F> 40Hz to 65Hz in 0.05Hz steps

    Timer settings t 0.1s to 25s in 0.1s steps

    Voltage balance

    Voltage setting Vs 5V to 20V in 1V steps

    Digital inputs

    Optically isolated inputs 14 (6 dedicated, 8 available to thescheme logic)

    Contacts

    Output relays 10 dual make

    2 single make3 change-over

    Power supply failure alarm 1 single make1 single break

    Relay inoperative alarm 1 change-over

    Contact rating Make: 30A and carry for 0.2sCarry: 5A continuousBreak: dc 50W resistive

    25W inductive(L/R = 0.4s)

    ac 1250VA

    Subject to maxima of 5A and 300V

    Durability

    Loaded contact 10,000 operations

    Unloaded contact 100,000 operations

  • 7/29/2019 Alstom - Digital Integrated Generator Protection Relay

    17/2417

    Communications

    Language Courier

    IEC 60870 port (front/rear)

    Transmission mode Asynchronous

    Signal levels RS232

    Message format IEC 60870 FT1.2

    Data rate 600 19200 bits/s

    Connection Single-ended

    Cable type Screened multi-core

    Cable length 15m

    Connector 25-way D-type female

    Isolation Front (non-isolated)

    Rear (1kV rms for 1 minute to case

    earth and other circuits)

    K-Bus portTransmission mode Synchronous

    Signal levels RS485

    Message format HDLC

    Data rate 64 kbits/s

    Connection Multidrop (32 units)

    Cable type Screened twisted pair

    Cable length 1000m

    Connector Screw terminals

    Isolation 2kV rms for 1 minute

    Voltage withstand

    Dielectric withstandIEC 60255-5: 1977 2.0kVrms for 1 minute between all

    terminals and case earth

    2.0kVrms for 1 minute betweenterminals of independent circuits,including contact circuits

    1.0kVrms for 1 minute acrossopen contacts of output relays

    1.0kVrms for 1 minute betweenIEC 60870 rear port and earth

    High voltage impulseIEC 60255-5: 1977 Three positive and three negative

    impulses of 5kV peak, 1.2/50s,0.5J between all terminals of thesame circuit (except outputcontacts), between independentcircuits and between all terminalsconnected together and case earth

    Insulation resistanceIEC 60255-5: 1977 >100M

  • 7/29/2019 Alstom - Digital Integrated Generator Protection Relay

    18/2418

    Electrical environment

    DC supply interruptionsIEC 60255-11: 1979 The relay will withstand a 10ms

    interrupt in the auxiliary supply,under normal operating conditions,without de-energising

    AC ripple on dc supply

    IEC 60255-11: 1979 The unit will withstand 12% acripple on the dc supply

    High frequency disturbanceIEC 60255-22-1: 1988 Class III 2.5kV peak between

    independent circuits and betweenindependent circuits and case earth

    1.0kV peak across terminals ofthe same circuit (except metalliccontacts)

    Electrostatic dischargeIEC 60255-22-2: 1996 Class 2 4.0kV discharge in air with cover

    in place.

    4.0kV contact discharge with coverremoved.

    Fast transient disturbanceIEC 60255-22-4: 1992 Class III 2.0kV, 5kHz applied directly to

    auxiliary supply2.0kV, 5kHz applied directly toall inputs

    Class IV 4.0kV, 2.5kHz applied directly toauxiliary supply

    4.0kV, 2.5kHz applied directly toall inputs

    Radio frequency interference

    Radiated immunityIEC 60255-22-3: 1989 Class III field strength 10V/m

    Extended frequency range 20MHzto 1000MHz

    Conducted immunityIEC 60801-6: 1994 10V rms, 0.15MHz to 80MHz

    Radiated emissionsEN55022: 1994 Class A

    Conducted emissionsEN55022: 1994 Class A

    EMC compliance89/336/EEC Compliance with the EuropeanEN50081-2: 1994 Commission Directive on EMC isEN50082-2: 1995 claimed via the Technical

    Construction File route.Generic Standards were used toestablish conformity

  • 7/29/2019 Alstom - Digital Integrated Generator Protection Relay

    19/2419

    Product safety73/23/EEC Compliance with the European

    Commission Low Voltage Directive.

    EN 61010-1: 1993/A2: 1995 Compliance is demonstrated byEN 60950: 1992/A11: 1997 reference to generic safety

    standards.

    Atmospheric environment

    TemperatureIEC 60255-6: 1988 Storage and transit

    -25C to +70C

    Operating25C to +55C

    HumidityIEC 60068-2-3: 1969 56 days at 93% relative humidity

    at 40C.

    Enclosure protectionIEC 60529: 1989 IP50 (dust protected)

    Mechanical environment

    VibrationIEC 60255-21-1: 1988 Vibration response Class 2

    Vibration endurance Class 2

    Shock and bumpIEC 60255-21-2: 1988 Shock response Class 2

    Shock withstand Class 2

    Bump Class 1

    SeismicIEC 60255-21-3: 1993 Class 2

  • 7/29/2019 Alstom - Digital Integrated Generator Protection Relay

    20/2420

    Case

    The relay is housed in a multi-module Midos case as shown inFigure 12.

    Additional Information

    LGPG111 Service Manual R5942

    Courier Communications leaflet R4113

    Figure 12: Case outlines

    432

    438

    Removablecover

    Hinged frontpanel

    465483

    178 101.6

    Front

    252

    10

    Push buttonprojection 10mm max.

    10

    450 min.

    465.1 1.6

    7 max.

    31.750.4

    12.70.4

    Tolerance betweenany two holeswithin a distance

    of 1mm 0.4

    10.67

    Fixing hole detail

    U ScaleU = 44.45

    Allow a minimum of50mm for terminal blockand wiringSide

    Rack mounting

    Panel mounting

    483mm Rack detailsDimensions to IEC 297

    432

    438

    Removablecover

    Hinged frontpanel

    443

    201

    Front

    252

    10

    Push buttonprojection

    10mm max.

    10

    440

    Allow a minimum of 50mm forterminal block and wiring

    Side

    Panel cut-out detail

    37

    178

    400

    200

    191180.5

    Fixing holes5.4

    All dimensions in mm

    Mounting screws are not provided

    Terminal screws:M4 x 8 brass Cheese Head withLockwashers are provided

    37

  • 7/29/2019 Alstom - Digital Integrated Generator Protection Relay

    21/2421

    Unit type: L G P G 1 1 1 0 1

    Case mounting

    Flush panel PRack R

    Vx(1) auxiliary voltage

    24 27V dc 1

    30 34V dc 2

    48 54V dc 3

    110 125V dc 4

    220 250V dc 5

    Vx(2) auxiliary voltage

    24 27V dc 130 34V dc 2

    48 54V dc 3

    110 125V dc 4

    220 250V dc 5

    VT and CT rating

    100/120V 1A L

    100/120V 5A M

    Language

    English E

    French F

    German G

    Spanish S

    Information Requiredwith Order

  • 7/29/2019 Alstom - Digital Integrated Generator Protection Relay

    22/2422

  • 7/29/2019 Alstom - Digital Integrated Generator Protection Relay

    23/2423

  • 7/29/2019 Alstom - Digital Integrated Generator Protection Relay

    24/24

    St Leonards Works, Stafford, ST17 4LX England

    Tel: 44 (0) 1785 223251 Fax: 44 (0) 1785 212232 Email: [email protected] Internet: www.alstom.com

    1999 ALSTOM T&D Protection & Control Ltd

    ALSTOM T&D Protec tion & Control Ltd