detecting synchrophasors computed over fault/switching transients
DESCRIPTION
TRANSCRIPT
![Page 1: Detecting Synchrophasors Computed Over Fault/Switching Transients](https://reader031.vdocuments.us/reader031/viewer/2022020217/547e958b5806b5d65e8b469e/html5/thumbnails/1.jpg)
Dr. Sarasij Das
1
![Page 2: Detecting Synchrophasors Computed Over Fault/Switching Transients](https://reader031.vdocuments.us/reader031/viewer/2022020217/547e958b5806b5d65e8b469e/html5/thumbnails/2.jpg)
This Presentation is based on the paper
Sarasij Das, and Tarlochan Sidhu, "Detecting Synchrophasors
Computed Over Fault/Switching Transients", IET Generation,
Transmission & Distribution,
http://digital-library.theiet.org/content/journals/10.1049/iet-gtd.2013.0493
2
![Page 3: Detecting Synchrophasors Computed Over Fault/Switching Transients](https://reader031.vdocuments.us/reader031/viewer/2022020217/547e958b5806b5d65e8b469e/html5/thumbnails/3.jpg)
Brief overview of Wide Area Measurement
Systems (WAMS)
Proposed algorithm
Conclusions
3
![Page 4: Detecting Synchrophasors Computed Over Fault/Switching Transients](https://reader031.vdocuments.us/reader031/viewer/2022020217/547e958b5806b5d65e8b469e/html5/thumbnails/4.jpg)
4
![Page 5: Detecting Synchrophasors Computed Over Fault/Switching Transients](https://reader031.vdocuments.us/reader031/viewer/2022020217/547e958b5806b5d65e8b469e/html5/thumbnails/5.jpg)
Voltage/current waveforms sinusoid in nature
Phasor = representation of sinusoid in complex
plane
Phasors estimated by measuring
- magnitudes
- phase angles
![Page 6: Detecting Synchrophasors Computed Over Fault/Switching Transients](https://reader031.vdocuments.us/reader031/viewer/2022020217/547e958b5806b5d65e8b469e/html5/thumbnails/6.jpg)
![Page 7: Detecting Synchrophasors Computed Over Fault/Switching Transients](https://reader031.vdocuments.us/reader031/viewer/2022020217/547e958b5806b5d65e8b469e/html5/thumbnails/7.jpg)
Traditional SCADA monitoring slow
One complete SCADA polling may take 2-10 s
Measurements are not time synchronized
Phase angle measurement no possible
Not suitable for system dynamics monitoring
7
![Page 8: Detecting Synchrophasors Computed Over Fault/Switching Transients](https://reader031.vdocuments.us/reader031/viewer/2022020217/547e958b5806b5d65e8b469e/html5/thumbnails/8.jpg)
WAMS = PMU based monitoring systems
Synchrophasor = phasor + GPS time tagging
Synchrophasor = magnitude & phase angles
Synchrophasors used in system dynamics
monitoring
8
![Page 9: Detecting Synchrophasors Computed Over Fault/Switching Transients](https://reader031.vdocuments.us/reader031/viewer/2022020217/547e958b5806b5d65e8b469e/html5/thumbnails/9.jpg)
Control Center
Voltage, Current Synchrophasors
9
![Page 10: Detecting Synchrophasors Computed Over Fault/Switching Transients](https://reader031.vdocuments.us/reader031/viewer/2022020217/547e958b5806b5d65e8b469e/html5/thumbnails/10.jpg)
IEEE standard C37.118.1-2011[2] specifies
accuracy requirements for synchrophasors
IEEE standard C37.118.2-2011[3] specifies
message formats for communication data packets
IEEE standard C37.244-2013 [4] describes functional requirements for PDCs
10
![Page 11: Detecting Synchrophasors Computed Over Fault/Switching Transients](https://reader031.vdocuments.us/reader031/viewer/2022020217/547e958b5806b5d65e8b469e/html5/thumbnails/11.jpg)
11
![Page 12: Detecting Synchrophasors Computed Over Fault/Switching Transients](https://reader031.vdocuments.us/reader031/viewer/2022020217/547e958b5806b5d65e8b469e/html5/thumbnails/12.jpg)
12
![Page 13: Detecting Synchrophasors Computed Over Fault/Switching Transients](https://reader031.vdocuments.us/reader031/viewer/2022020217/547e958b5806b5d65e8b469e/html5/thumbnails/13.jpg)
Context Synchrophasor validations mostly happen in
PDCs
Validation often offline and time consuming
Lack of samples makes validation difficult in PDCs
Lack of algorithms to compute synchrophasor quality at PMU
13
![Page 14: Detecting Synchrophasors Computed Over Fault/Switching Transients](https://reader031.vdocuments.us/reader031/viewer/2022020217/547e958b5806b5d65e8b469e/html5/thumbnails/14.jpg)
Motivation
Fault/switching transient synchrophasors
computed over pre and post fault/switching
samples
Unusable in applications
Not easy to detect from values
1( ) 89.998
2
1.0045( 1) 90.1340
2
X k
X k
14
![Page 15: Detecting Synchrophasors Computed Over Fault/Switching Transients](https://reader031.vdocuments.us/reader031/viewer/2022020217/547e958b5806b5d65e8b469e/html5/thumbnails/15.jpg)
Motivation
No existing Algorithm
However, Algorithms [1][5] can be used
Existing Algorithms [1][5] make wrong detections in
presence of harmonics, decaying dc
15
![Page 16: Detecting Synchrophasors Computed Over Fault/Switching Transients](https://reader031.vdocuments.us/reader031/viewer/2022020217/547e958b5806b5d65e8b469e/html5/thumbnails/16.jpg)
Proposed low complexity algorithm to detect
fault/switching transient synchrophasor
16
![Page 17: Detecting Synchrophasors Computed Over Fault/Switching Transients](https://reader031.vdocuments.us/reader031/viewer/2022020217/547e958b5806b5d65e8b469e/html5/thumbnails/17.jpg)
17
![Page 18: Detecting Synchrophasors Computed Over Fault/Switching Transients](https://reader031.vdocuments.us/reader031/viewer/2022020217/547e958b5806b5d65e8b469e/html5/thumbnails/18.jpg)
Suggested to apply on current signals
Success Rate
18
X=Xm [1+ksx u(t-ts)]cos(ωot +ksa u(t-ts))
![Page 19: Detecting Synchrophasors Computed Over Fault/Switching Transients](https://reader031.vdocuments.us/reader031/viewer/2022020217/547e958b5806b5d65e8b469e/html5/thumbnails/19.jpg)
19
Performance
during
Oscillations
![Page 20: Detecting Synchrophasors Computed Over Fault/Switching Transients](https://reader031.vdocuments.us/reader031/viewer/2022020217/547e958b5806b5d65e8b469e/html5/thumbnails/20.jpg)
20
Performance
in presence of
missing samples
![Page 21: Detecting Synchrophasors Computed Over Fault/Switching Transients](https://reader031.vdocuments.us/reader031/viewer/2022020217/547e958b5806b5d65e8b469e/html5/thumbnails/21.jpg)
21
![Page 22: Detecting Synchrophasors Computed Over Fault/Switching Transients](https://reader031.vdocuments.us/reader031/viewer/2022020217/547e958b5806b5d65e8b469e/html5/thumbnails/22.jpg)
22
![Page 23: Detecting Synchrophasors Computed Over Fault/Switching Transients](https://reader031.vdocuments.us/reader031/viewer/2022020217/547e958b5806b5d65e8b469e/html5/thumbnails/23.jpg)
23
![Page 24: Detecting Synchrophasors Computed Over Fault/Switching Transients](https://reader031.vdocuments.us/reader031/viewer/2022020217/547e958b5806b5d65e8b469e/html5/thumbnails/24.jpg)
Proposed algorithm performs satisfactorily
- during nominal and off-nominal frequencies
- in presence of harmonics, decaying DC
- in presence of oscillations, ramping
- in presence of a number of missing samples
- for estimation windows 2.5 cycles or
greaterPlease see the paper for additional results
24
![Page 25: Detecting Synchrophasors Computed Over Fault/Switching Transients](https://reader031.vdocuments.us/reader031/viewer/2022020217/547e958b5806b5d65e8b469e/html5/thumbnails/25.jpg)
Algorithm has been proposed to tag fault/switching
transient synchrophasors
Proposed algorithm performs satisfactorily in various
scenarios
25
![Page 26: Detecting Synchrophasors Computed Over Fault/Switching Transients](https://reader031.vdocuments.us/reader031/viewer/2022020217/547e958b5806b5d65e8b469e/html5/thumbnails/26.jpg)
1. “Synchronized phasor measurements and their applications”, by Arun G. Phadke, John Samuel Thorp
2. “IEEE Standard for Synchrophasor Measurements for Power Systems”, IEEE C37.118.1-2011, (Revision of IEEE Std. C37.118-2005)
3. “IEEE Standard for Synchrophasor Data Transfer for Power Systems”, IEEE C37.118.2-2011
4. “IEEE Guide for Phasor Data Concentrator Requirements for Power System Protection, Control, and Monitoring”, IEEE Std C37.244-2013
5. Sodhi, Ranjana, S. C. Srivastava, and S. N. Singh. "A transient monitor to reflect the quality of synchrophasors." Power and Energy Society General Meeting, 2010 IEEE. IEEE, 2010.
26