design of axial members - wood

Upload: ryan5443

Post on 05-Feb-2018

226 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/21/2019 Design of Axial Members - Wood

    1/41

    1

    www.sgh.com

    Axial Forces and Combined

    Axial and Bending Forces

    Axial Forces and Combined Bending and

    Axial Forces Four Types of Applications:

    Axial Tension Axial Compression

    Combined Bending and Tension

    Combined Bending and Compression

    Most common axial load members are columns

    Most common combined stress member is beam-

    column

    Magnitude of lateral force in wall elements depends

    on design load and how the wall is framed

    (horizontally or vertically).

  • 7/21/2019 Design of Axial Members - Wood

    2/41

    2

    Examples of

    Axial and Axial

    plus Bending

    Elements

    Axial Tension Members

    Number of structural applications:

    Trusseshave numerous axial force members;

    about in tension

    Chordsof shearwalls and diaphragms

    Collector or drag strut members (when length of

    diaphragm is greater than shearwall).

    Axial members allow for direct solution in design

    Parallel to grain applications avoid cross grain

    tension General formula:

    ft= P/An Ft

  • 7/21/2019 Design of Axial Members - Wood

    3/41

    3

    Capacity of

    tension

    members is

    affected by

    connections

    Axial Tension Members

    Gross area vs. Net area(projected fastener area is

    subtracted - nails usually disregarded)

    Avoid tight-fitting installations that require forcible

    driving of the bolt

    Perfect installations are difficult may have to drill

    from both sides

    Hole diameter can be taken to be bolt diameter

    plus 1/16 in., as specified in NDS

  • 7/21/2019 Design of Axial Members - Wood

    4/41

    4

    Axial Tension Members

    General formula:

    ft= P/An Ft

    Where Ft= Ft(CD)(CM)(Ct)(CF)(Ci)

    DEAD + LIVE LOADS 44 psf

    Determine required size

    of truss bottom chord

    Loads only applied to

    top chord (convert to

    point loads)

    Use method of joints

    truss joints assumed

    pinned

    Connections made with

    a single row of 1/2 in.

    bolts

    Trusses 4 ft o.c., lumber

    No. 1 SPF South MC < 19%, normal

    temperatures

    16 ft 12 ft 12 ft

    2.5 ft

    8 ft

    125

    44 psf

    Example Size truss bottom chord

  • 7/21/2019 Design of Axial Members - Wood

    5/41

    5

    Example Size truss bottom chord

    44 psf (4 ft o.c.) = 176 plf

    4(6) = 24

    5

    5P/2 = 528 lb

    528 lb

    P = 176(6) =1056 lb1056 lb

    1056 lb

    2,112 lb 2,112 lb

    Example Size truss bottom chord cont.

    Find forces by method of joints;T = 3.8k

    FromTable 4Afor No.1 SPF South:Ft= 400 psi

    FactorscD = 1.15, andassume cF = 1.3

    DetermineFt init.= Ft(cD) (cF)= 400(1.15)(1.3) =598 psi

    Find required An= P/Ft= 3,802/598 = 6.36 in.2

    Consider bolt holes:

    Reqd Ag= An+Ah= 6.36+1.5(1/2 + 1/16) = 7.2 in.2

    Try 2 x 6: A = 8.25 in.2 > 7.2 in.2 OK

    Backchecksize factorfor 2x8: cF = 1.3 - same as assumed.

    44 psf (4 ft o.c.) = 176 plf

    4(6) = 24

    5

    5P/2 = 528 lb

    528 lb

    P = 1056 lb 1056 lb

    1056 lb

    2,112 lb 2,112 lb

    FBD

    RA= 2,112 lb

    528 lb

    2,112 528 = 1,584 lb

    1,584(12)/5 = 3,802 lb

    F

    TAC=3,802 lbA

  • 7/21/2019 Design of Axial Members - Wood

    6/41

    6

    Columns

    Columns are generally sufficiently long thatbuckling

    needs to be considered

    Direct design is not feasible (trial size,iteration)

    General formula:

    fc = P/A Fc

    Where Fc= Fc(CD)(CM)(Ct)(Cp)(CF)

    Cross sectional area to be used (gross or net) should

    be considered along the length of member, together

    withtendency of member at that point to buckle

    laterally

    Column Design Considerations

    Size factor applies only to dimension lumber

    Column stability factor CPtakes buckling into

    consideration slenderness ratio is a measure ofbuckling propensity

    Slenderness ratiois generally expressed in terms of

    effective (unbraced, corrected for end condition)

    length, divided with least radius of gyration: (le/r).

    For rectangular columns, slenderness ratio can be

    expressed as le/d (radius of gyration is a direct

    function of the width)

    For non-rectangular columns, r 12 can be substituted

    for d

  • 7/21/2019 Design of Axial Members - Wood

    7/41

    7

    Column Design Considerations

    Behavior of wood columns is the result of

    interaction between two modes of failure:

    buckling and crushing

    For use in design, theEuler critical buckling stress

    is expressed in NDS as:

    Crushingis measured by compressive design value

    multiplied byall factors except CP:

    F*c= Fc(CD)(CM)(Ct)(Ci)(CF)

    Column Stability Factor

    Takes into consideration Euler critical stress and

    crushing strength:

    where buckling and crushing interaction factor

    for columns c:

    = 0.8 for sawn lumber= 0.85 for timber poles and piles

    = 0.9 for SCL columns

  • 7/21/2019 Design of Axial Members - Wood

    8/41

    8

    Slenderness can really affect column strength

    Slenderness Considerations

    By inspection the slenderness ratio about the y axis is

    larger and therefore critical

  • 7/21/2019 Design of Axial Members - Wood

    9/41

    9

    In this case, (l/d)xmay govern

    Slenderness Considerations

    Conditions can exist under which the column may

    buckle about the strong axis

    In Stud walls, weak axis is

    braced, but strong is not

  • 7/21/2019 Design of Axial Members - Wood

    10/41

    10

    Slenderness Considerations

    End conditions are important

    Theeffective length eused in slenderness ratiosis

    theoretically the unbraced length of a pinned-end

    column

    For other column-end conditions, the effective

    length is taken as the distance between inflection

    points (point of reverse curvature and zeromoment)

    For purposes of column analysis, the inflection

    point is considered as pinned end

    Effectivelength

    factor: ke

  • 7/21/2019 Design of Axial Members - Wood

    11/41

    11

    Sidesway means

    that top of column

    is relatively free to

    displace laterally:

    In braced

    situations or in

    shearwalls,

    sidesway is

    prevented)

    In rigid frames,

    system is

    flexible, and

    sidesway can

    occur

    Slenderness Considerations

    Effective length = effective length factor x unbraced

    length:Le= Kex L

  • 7/21/2019 Design of Axial Members - Wood

    12/41

    12

    16 ft 12 ft 12 ft

    125

    44 psf

    17 psf

    750 plf

    330 plf

    8 ft

    45 psf72 plf

    7 ft

    55 psf

    96 plf

    96 plf

    Example: Interior Bearing Wall Capacity

    No bending although on

    exterior walls there could

    be wind loads

    Continuous lateral support

    provided in y direction

    Need to consider bearing

    capacity of top and bottom

    plates

    Load is D + L, disregard self

    weight of wall See if Standard grade Hem-

    Fir, 2 x 4 studs at 16 in. o.c.

    are adequate

    No special temperature

    and moisture requirements

    Total load: 17(12) + 45(12) + 72 = 816 lb/ft

    Total wall height, including top and bottom plates, is 8 ft

    Total load per stud, assuming 16 in. o.c.:

    P =816 lb/ft (16/12) =1,088 lbs From Table 4A, for Standard grade Hem-Fir:

    Fc= 1300 psi, Fc= 405 psi, Emin= 440,000 psi

    Example: Interior Bearing Wall Capacity

  • 7/21/2019 Design of Axial Members - Wood

    13/41

    13

    Example Continued

    CF= 1.0 for compression standard grade,

    A = 5.25 in2; le= 8(12) 3(1.5) = 91.5 in.

    (le/d)x= 1(91.5)/3.5 = 31.3 (about y axis studs are braced)

    Emin = Emin = 440,000psi

    c = 0.8 for visually graded lumber

    = 369 psi; Fc* = 1300(1.0) = 1,300 psi

    = 0.265 ;

    Fc= 1,300(.265) = 344 psi;

    P = Fc A = 344(5.25) = 1,806 lb > 1,088 lb OK

    Fc= Fc= 405 psi > 344 psi; so column capacity governs

    x

    x

    P = 1,088 lb

    Fc= 1300 psi,Fc= 405 psi,

    Emin= 440,000 psi

    16 ft 12 ft 12 ft

    3

    1

    5

    125

    44 psf

    17 psf

    750 plf

    330 plf

    8 ft

    96 plf

    72 plf

    72 plf

    7 ft

    45 psf

    55 psf

    96 plf

    96 plf

    BASEMENT COLUMN

    Column height 7 ft

    From before, load on beam

    due to D+L: w = 1,583 plf

    2

    4

    Example Design of a Column

    W

    Trib. L = 12 ft

    Trib. length for column = 12 ft

    Column load:

    PD+L = 12(1,583) = 18,996 lb

  • 7/21/2019 Design of Axial Members - Wood

    14/41

    14

    Example Design Sawn Lumber Column

    Design column, No. 1 Douglas Fir - Larch

    Bracing the same for buckling about x and y axes

    (non existent)

    Dead and live load apply

    Temperature, moisture, incision do not apply

    P = 19k D + L

    L

    =

    7

    Try 4x6 (dimension lumber):

    Example Design Sawn Lumber ColumnFrom Table 4A for No 1 DFL:

    Fc= 1500 psi, Emin= 620,000 psi; A = 19.25 in2, CF= 1.1

    (le/d)max=kle/dy=1(84)/3.5 = 24; Emin = Emin = 620,000psi

    c = 0.8 for visually graded lumber

    = 885 psi; Fc* = 1500(1.0)(1.1) = 1,650 psi

    = 0.46 ;

    Fc= 1650(.46) = 757 psi

    Pallow.= Fc A = .757(19.25) = 14.57k < 19k NG P = 19k D + L

    L

    =

    7

  • 7/21/2019 Design of Axial Members - Wood

    15/41

    15

    Trial 2: Try 6x6 (P&T); From Table4Dfor No 1 DFL:

    Fc= 1000 psi, Emin= 580,000 psi, CF= 1.0, A = 30.25 in2

    (le/d)max=kle/dy=1(84)/5.5 = 15.3; Emin=Emin=580,000psi

    c = 0.8 for visually graded lumber

    = 2037 psi; Fc* = 1000(1.0)(1.0) = 1,000 psi

    = 0.87 ;

    Fc= 1000(.87) = 870 psi

    Allow. P = Fc A = .87(30.25) = 26.3 k > 19 kOK,

    Use 6x6 column, No. 1 DF-L

    P = 19k D + L

    L

    =

    7

    Example Design Sawn Lumber Column

    Example: Axial Capacity of Glulam

    Determine if a 3-1/8x6 axial-

    load glulam combination 2 DF

    works for the previous

    example.

    MC less than 16%, normal

    temp.

    Loads are D+L assumed to

    govern

    Different unbraced lengths

    about x and y axes (due to

    installed kickers).

    5

    5

    3

    1

    5

  • 7/21/2019 Design of Axial Members - Wood

    16/41

    16

    Example: Axial Capacity of Glulam

    A = 18.75 in2, and from Table 5B: Fc= 1,950 psi;

    Exmin = 830,000psi

    Eymin= 830,000psi

    (le/d)x=1(7)(12)/6 =14; Governs

    (le/d)y=1(3.5)(12)/3.125 =13.44

    c = 0.9 for glulam; Emin= Emin

    = 3,481 psi; Fc* = 1,950(1.0) = 1,950 psi

    = 0.91;

    Fc= Fc* (CP) = 1,950(0.91) = 1,767 psi

    P = Fc A = 1.767(18.75) = 33.1 k > 19 k OK

    In this case, same Emin properties

    apply for x and y axes, but could

    be different in glulam.

    Built-Up Columns

    Constructed from several parallel wood members

    that arenailed or bolted togetherto function as a

    composite column NDS Section 15.2

    Connectingfasteners do not fully transfer the shear

    between the various pieces, and capacity of a built-

    up column is less than that of a solid sawn or glulam

    column of same size and grade

    Capacity of an equivalent solid column is reduced by

    anadjustment factor Kf(only applies to the columnslenderness ratio for the axis parallel to the weak

    axis of individual laminations)

  • 7/21/2019 Design of Axial Members - Wood

    17/41

    17

    Built-Up Columns

    Questions?

  • 7/21/2019 Design of Axial Members - Wood

    18/41

    18

    www.sgh.com

    Combined Axial and Bending

    Forces

    Combined Bending and Tension

    Effects ofsimultaneousbending and tensile stresses

    must be considered

    On one face, axial stressesaddto bending stresses, on

    other face theycanceleach other

    Therefore, capacity of member is either governed by

    combined tension criterion or by net compression

    criterion

  • 7/21/2019 Design of Axial Members - Wood

    19/41

    19

    Combined Bending and Tension

    Interaction equation:

    Because actual bending stress fbis a bending tensile

    stress, F*bis used (does not include CL)

    If combined stress is compressive, bending analysis

    must be performed (CLis included but Cvis not):

    Fb** = Fb CLapplies, but CVdoes not

    Combined Bending and Tension

    Designer should be cautious about net compressive

    stress:maximum bending compressive stress may occur

    with or without tensile stress to cancel it.

    Truss bottom chords are good example (tensile force

    may or may not be present)

    Conservative approach is toignore reduction in bending

    stress due to tension:

    Fb** = Fb CLapplies, but CVdoes not

  • 7/21/2019 Design of Axial Members - Wood

    20/41

    20

    Combined Biaxial Bending and Tension

    Axial tension and bending tension:

    Net Compressive stress

    Example: Combined Bending and Tension

    Truss example similar to

    earlier example

    additional uniform load

    applied to bottom chord

    Use Select Structural DFL

    with MC

  • 7/21/2019 Design of Axial Members - Wood

    21/41

    21

    44 psf (4 ft o.c.) = 176 plf

    4(6) = 24

    5

    5

    P/2=528+408 = 936 lb

    6(176) = 1056 lb

    1056 lb

    RA= 2,928 lb

    2,928 lb

    W = 17 psf (4 ft o.c.) = 68 plf

    P = 1056 lb

    P = 68(12)= 816 lb

    936 lb

    Example: Combined Bending and Tension

    Trial and error procedure try a nominal 2x8:

    Ag=10.88 in.2; S=13.14 in.3; An=1.5(7.25 9/16) = 10.03 in

    2

    Fb= 1500 psi, Ft= 1000 psi; cF=1.2 for tension & bending

    Check axial tension at An: ft= T/An= 4.78/10.03 = 476 psi

    Ft= Ft(cD)(cF) = 1000(1.15)(1.2) = 1380 psi > 476 psi OK

    Check Bending: M=wl2/8= 14,688 in-lb; fb= M/S= 1118 psi

    Fb= Fb(cD)(cF) = 1,500(1.0)(1.2) = 1800 psi > 1118 psi OK

    RA= 2,928 lb

    936 lb

    2,928 938 = 1,990 l b

    1,990(12)/5 = 4,776 lb

    F

    TAC= 4,776 lbA

    176 plf

    24

    5

    5

    P/2 = 936 lb

    1056 lb

    1056 lb

    RA= 2,928lb

    2,928lb

    W = 68 plf

    P = 10 56 lb

    P = 816 lb

    936 lb

    FBDW = 68 plf

    12

    4,776 k

    Example: Combined Bending and Tension

  • 7/21/2019 Design of Axial Members - Wood

    22/41

    22

    Combined Stresses:

    Fb= 1500 psi, Ft= 1000 psi;

    cF= 1.2 for tension & bending

    Ag =10.88 in.2; S = 13.14 in.3;

    ft=T/Ag= 4,776/10.88 = 439 psi

    F*b= Fb(cD)(cF) = 1500(1.15)(1.2) = 2,070 psi

    ft/Ft+ fbx/F*bx= 439/1380+1118/2070 = 0.86 < 1 OK

    (D+S governs; typically would need to check D alone too)

    Net bending compressive stress: automatically ok, since we already

    checked it.

    Also, since combined stress index is0.86, we theoretically could find

    a smaller size that would work (likely wont).

    In general, CSI values of 1.02 or 1.03 could be acceptable.

    W = 68 plf

    12

    4,776 k

    Example: Combined Bending and Tension

    Combined Bending and Compression

    NDS interaction formula considers column buckling,

    lateral torsional buckling of beams, and beam-column

    interaction In a beam-column, additional bending stress is created

    due to P- effect

    To analyze combined stresses, following convention

    used:

    Column buckling isgoverned by whichever the

    larger slenderness ratio is(Fcincludes CP)

    When bending momentabout x axis, the value of

    FCEfor use in amplification factor is to bebased on

    (le/d)x

  • 7/21/2019 Design of Axial Members - Wood

    23/41

    23

    Combined Bending and Compression

    General formula:

    Where

    Combined Bending and Compression

    Effect of column buckling, lateral torsional buckling,

    and P-D effect is demonstrated on the following

    interaction diagrams:

  • 7/21/2019 Design of Axial Members - Wood

    24/41

    24

    Biaxial Bending and Compression

    General formula:

    where:

    Truss T.C. Example: Beam-Column

    Determine required size of truss top chord

    D + S loads, effects of roof slope already

    accounted for

    Connections made with a single row of in.

    bolts

    Trusses 4 ft o.c., lumber is No. 1 Dense

    Southern Pine

    MC < 19%, normal temperatures, top chord

    laterally bracedL =6 f t

    5

    RA= 2,928 lb

    936 lb

    2,928 938 = 1,990 lb

    1,990(12)/5 = 4,776 lb

    F

    TAC= 4,776 lbA

    5,174 lb

  • 7/21/2019 Design of Axial Members - Wood

    25/41

    25

    Example Beam-Column cont.

    Try 2x8:A = 10.88 in.2; S = 13.14 in.3 CF= 1 for both C & BFc= 1,800 psi, Fb= 1,650 psi, Emin= 620,000 psi

    Axial check: fc= P/A = 5174/10.88 = 476 psi;

    Stability: (le/d)x=kle/dx=1(6.5)(12)/7.25 = 10.75;

    Emin= Emin = 620,000 psi; c = 0.8 for visually graded lumber

    = 4,410 psi; Fc* = 1,800(1.15)(1.0) = 2,070 psi

    = 0.88; Fc= 2,070(.88) = 1,822 psi

    Fc= 1,822 > fc= 476 OK

    x

    x

    L =6 f t

    5

    Example Beam-Column cont.

    From before:Fc= 1,800 psi, Fb=1,650 psi, Emin= 620,000 psi

    2x8: A = 10.88 in.2; S = 13.14 in.3 CF= 1 for both C & B

    Net section compression check (not really needed here):An=1.5(7.25 (9/16)) = 10.03 in

    2

    fc= P/A = 5,174/10.03 = 516 psi

    Fc= Fc* = 1,650(1.15)(1.0) = 1,898 psi > 516OK

    Bending Check:

    M = wl2/8 = 176(6)2/8 = 792 ft-lb; fb= M/S = 723 psi

    Fb= 1800(1.15)(1.0) = 2,070psi > 723 psiOK

    L =6 f t

    5

  • 7/21/2019 Design of Axial Members - Wood

    26/41

    26

    Example Beam-Column cont.

    From before:Fc= 1,800 psi, Fb=1,650 psi, Emin= 620,000 psi

    2x8: A = 10.88 in.2; S = 13.14 in.3 CF= 1 for both C & B

    Combined Stress check :

    CDbased on shortest duration of load in combination

    FcEx= FcE= 4,410 psi (coincidence that le/dx= le/dmax)

    fb= 849 psi; Fbx= 2,070 psi; fc= 476 psi ; Fc= 1,822 psi(476/1822)2 + (1/(1 476/4410))(723/2070) = 0.46 < 1 OK

    Can use 2 x 8 No. 1 SP, but

    perhaps another, weaker

    grade or a smaller size works.

    L =6 f t

    5

    Beam Columns with Transverse and

    Eccentric Loads

    In most cases with square-cut column ends, effects of

    eccentricity are ignored by designers

    Minimum recommended eccentricity to consider is 1 in.

    or one tenth of column width.

    No code requirement to design for minimum eccentricload left to thejudgment of engineer

  • 7/21/2019 Design of Axial Members - Wood

    27/41

    27

    Example Exterior Wall Beam-Column Check column in

    exterior wall that

    supports gravity and

    wind loads

    Consider two L.C.:L.C.1: D+.75(L)+.75(S)

    L.C. 2: D + W(there are others that may govern:D+L; D+S; D+.75W+.75L+.75 S)

    Try 4x4 SPF#2 column,disregard self weight.

    8 ft

    8 ft

    125

    Large double windows

    on either side

    D + L = 7 +10 = 17 psf

    D+S =14+30 = 44 psf

    W

    =20psf

    6 6

    85

    1

    2

    1260 lb

    360lb

    4 x 4

    5.524

    Example Exterior Wall Beam-Column

    Gravity Loads:

    PD= 14(6)(12)+7(6)(6)

    PD = 1260 lb

    PL= 10(6)(6) = 360 lb

    PS= 30(6)(12) = 2160 lb

    PT= PD+.75PL+.75PS =

    = 1260+.75(360+2160)

    PT = 3,150 lb

    8 ft

    8 ft

    125

    TA 2 Attic

    TA 1 Roof

    PS = 2160 lb

    20 psf

  • 7/21/2019 Design of Axial Members - Wood

    28/41

    28

    L.C. 1, Gravity loads: PD+ 0.75 (PL+S) = 3.15 k; cD= 1.15;

    Neglect column fixity @ ends, assume k=1:

    (le/d)x= 1(8)(12)/3.5 = 27. 4

    (le/d)y= 1(5)(12)/3.5 = 17.14; 27.4 governs

    Emin= 510,000 psi, c = 0.8 for sawn lumber

    = 558 psi; Fc* = 1150(1.15) = 1,322 psi

    = 0.38;Fc= 1,322(0.38) = 502 psi

    fc = P/A=3,150/12.25 = 257 psi OK

    OK

    From Table 4A:Fc = 1150 psi;

    Fb = 875 psi;

    Emin= 510,000 psi

    A =12.25 in2;

    S = 7.15 in3

    xx

    Example Exterior Wall Beam-Column

    8

    5

    1

    2

    PT= 3.15k

    840lb

    20 psf

    L.C. 2: (D + W)

    Axial alone (dead load): PD= 1260 lb

    (le/d)max= (le/d)x= 27.4 from beforeEmin= 510,000 psi, c = 0.8 for sawn lumber

    = 558 psi; Fc* = 1150(1.6) = 1,840 psi

    1.6 taken throughout combined stress check

    = 0.28;

    Fc= 1840(0.28) = 517 psi

    fc = P/A = 1260/12.25 = 103 psi

    fc/Fc=0.2

    xx

    Example Exterior Wall Beam-ColumnFc = 1150 psi;

    Fb = 875 psi;

    Emin= 510,000 psi

    A =12.25 in2;

    S = 7.15 in3

    8

    5

    1

    2

    PD= 1.26k

    840lb

    20 psf

  • 7/21/2019 Design of Axial Members - Wood

    29/41

    29

    L.C. 2 (D +W):Bending alone (wind)

    Wind on header: w1= 20(3) = 60 lb/ft

    Wind on sill: w2= 20(3.5) = 70 lb/ft

    Reaction on column from headers: P1= 60(6) = 360 lb

    Reaction on column from sills: P2= 70(6) = 420 lb

    Mx= 720(12) = 8640 in-k; f b= M/S = 8,640/7.15 = 1208 psi

    Fb=Fb(cD)(cL)

    Load & shear & momentWall Framing and Tributary heights

    Example Exterior Wall Beam-Column

    1260 lb

    .5

    3

    1

    3.5

    P=1.26k

    5

    P=1.26k P=1.26k

    P=1.26k

    8

    P1=.36k

    P2=.42k

    2

    1

    420

    360

    60

    420

    720

    Fc = 1150 psi;Fb = 875 psi;

    Emin= 510,000 psi

    A =12.25 in2;

    S = 7.15 in3

    L.C. 2Bending alone (wind) - continued:

    Find cL: Lu= 5 ft (window height); Lu/d=60/3.5=17.1

    14.3 17.1: Le

    = 1.84Lu

    = 110.4 (Table 3.3.3)** formula applies conservatively for all cases

    = 5.6; = 19,402; Fb*= 875(1.6) = 1400 psi

    = 0.996;

    Fb= 1400(.996) = 1,395 psi

    Stress ratio:

    fb/Fb= 1208/1395 =0.866

    Example Exterior Wall Beam-ColumnFc = 1150 psi;

    Fb = 875 psi;

    Emin= 510,000 psi

    A =12.25 in2;

    S = 7.15 in3

  • 7/21/2019 Design of Axial Members - Wood

    30/41

    30

    L.C. 2Combined Stresses D+W:

    (le/d)bending= (le/d)x= 27.4

    = 558; From before:

    fc= 103 psi; fc/Fc= 0.2; fb/Fb= 0.866

    Amplification factor: 1/(1-fc/FcE) = 1/(1-103/558) = 1.226;

    = (0.2)2 + 1.226(0.866) = 1.1 NG

    NOTE:4x6 would work for sure, but more effective to use better grade

    NOTE:D+L; D+S; D+.75W+.75L+.75 S should also be checked

    NOTE: Shear, deflection, and bearing perpendicular to grain need checking too

    also need to be checked.

    xx

    Example Exterior Wall Beam-ColumnFc = 1150 psi;Fb = 875 psi;

    Emin= 510,000 psi

    A =12.25 in2;

    S = 7.15 in3

    QUESTIONS?

  • 7/21/2019 Design of Axial Members - Wood

    31/41

    31

    Example 7.2 Size truss bottom chord

    Determine required size of truss bottom chord Loads only applied to top chord

    Loads assumed to be applied to T.C. joints

    Use method of joints truss joints assumed pinned

    D + S loads, effects of roof slope already accounted for

    Connections made with a single row of in. bolts

    Trusses 4 ft o.c., lumber No. 1 SPF South

    MC < 19%, normal temperatures

    Example 7.2 Size truss bottom chord

    Find forces by method of joints; T = 3.96k

    Factors cD = 1.15, and assume cF = 1.3

    Determine Ft= Ft(cD) (cF) = 400 (1.15)(1.3) = 598 psi

    Find required An= P/Ft= 3960/598 = 6.62 in.2 Consider bolt holes:

    Reqd Ag= An+Ah= 6.62+1.5(3/4 + 1/16) = 7.84 in.2

    Try 2 x 6: A = 8.25 in.2 > 7.84 in.2 OK

    Backcheck size factor cF = 1.3 - same as assumed.

    FBD

  • 7/21/2019 Design of Axial Members - Wood

    32/41

    32

    Example 7.7 Design Sawn Lumber Column

    Design column, No. 1 Douglas Fir - Larch Bracing the same for buckling about x and y axes

    Dead and roof live load apply

    Temperature, moisture, incision do not apply

    Example 7.7 Design Sawn Lumber Column

    Try 4x6 (dimension lumber); From Table 4A for No 1 DFL:

    Fc= 1500 psi, Emin= 620,000 psi, CF= 1.1, A = 19.25 in2

    (le/d)max=kle/dy=1(120)/3.5 = 34.3; Emin=Emin=620,000psi

    c = 0.8 for visually graded lumber

    = 433 psi; Fc* = 1500(1.25)(1.1) = 2062 psi

    S = 0.2 ;

    Fc= 2062(.2) = 412 psi

    Allow. P = Fc A = .412(19.25) = 7.94 k < 15 kNG

  • 7/21/2019 Design of Axial Members - Wood

    33/41

    33

    Example 7.7 Design Sawn Lumber Column

    Trial 2: 6x6 (P&T); From Table 4D for No 1 DFL:Fc= 1000 psi, Emin= 580,000 psi, CF= 1.0, A = 30.25 in

    2

    (le/d)max=kle/dy=1(120)/5.5 = 21.8; Emin=Emin=580,000psi

    c = 0.8 for visually graded lumber

    = 1003 psi; Fc* = 1000(1.25)(1.0) = 1250 psi

    S = 0.611 ;

    Fc= 1250(.611) = 764 psi

    Allow. P = Fc A = .764(30.25) = 23.1 k > 15 k

    OK, use 6x6 column, No. 1 DF-L

    Example 7.9 Axial Capacity of Glulam

    Determine axial compression capacity of 6-3/4 x 11

    24F-1.7E Southern Pine glulam

    MC will exceed 16% (consider treatment), normal temp

    Loads are D+S assumed to govern Different unbraced lengths about x and y axes,

    different material properties for x and y axes

    A = 74.25 in2

  • 7/21/2019 Design of Axial Members - Wood

    34/41

    34

    Example 7.9 Axial Capacity of Glulam

    Table 5A: Fc= 1000 psi (CM= 0.73),Exmin= 880,000 psi (CM= 0.833)

    Eymin= 670,000 psi (CM= 0.833)

    (le/d)x=1(22)(12)/11 = 24; Exmin= 860,000(.833) = 733000 psi

    (le/d)y=1(11)(12)/6.75 = 19.6; Eymin= 670,000(.83) = 558000 psi

    c = 0.9 for glulam

    = 1046 psi; Fc* = 1000(1.15)(0.73) = 840 psi

    =1200 psi; Fc* is the same;

    cPx= .832; cPy= .867; Fc= 1000(1.15)(.73)(.832) = 699 psi

    P = Fc A = .699(74.25) = 51.9 k

    y

    y

    y

    x

    x

    Example 7.11 Capacity of a Bearing Wall

    No bending although on exterior walls there could be

    wind loads

    Continuous lateral support provided in x direction

    Need to consider bearing capacity of top and bottom plates Load is D + S

    Lumber is Standard grade Hem-Fir, 2 x 4 studs

    No special temperature and moisture requirements

  • 7/21/2019 Design of Axial Members - Wood

    35/41

    35

    Example 7.11 Capacity of a Bearing Wall

    Table 4A: Fc= 1300 psi, Fc= 405 psi, Emin= 440,000 psi,CF= 1.0 for compression, A = 5.25 in

    2

    le= 9.5(12) 3(1.5) = 109.5 in.

    (le/d)x= 1(109.5)/3.5 = 31.3; Emin = Emin = 440,000psi

    c = 0.8 for visually graded lumber

    = 370 psi; Fc* = 1300(1.15) = 1495 psi

    = 0.233 ;

    Fc= 1495(.233) = 348 psi;

    P = Fc A = 348(5.25) = 1829 lb ; max w = 1829/1.33 = 1371 lb/ft

    Fc= Fc= 405 psi > 348 psi; column capacity

    governs

    x

    x

    Example 7.15 Combined Bending and Tension

    Truss example similar to truss in example 7.2

    additional uniform load applied to bottom chord

    Use No.1 and Better Hem-Fir with MC

  • 7/21/2019 Design of Axial Members - Wood

    36/41

    36

    Example 7.15 Combined Bending and Tension

    Trial and error procedure try a nominal 2x8 first: Fb= 1100 psi, Ft= 725 psi; cF= 1.2 for tension & bending

    Ag=10.875 in.2; S=13.14 in.3; An=1.5(7.25 (13/16)=9.66 in

    2

    Check axial tension at An: ft= T/An= 4.44/9.66 = 460 psi

    Ft= Ft(cD)(cF) = 725 (1.15)(1.2) = 1000 psi > 460 psi OK

    Check Bending: M = wl2/8=10,800 in-lb; fb= M/S = 822 psi

    Fb= Fb(cD)(cF) = 1100(0.9)(1.2) = 1188 psi > 822 psi OK

    Example 7.15 Combined Bending and Tension

    Combined Stresses:

    Fb= 1100 psi, Ft= 725 psi; cF= 1.2 for tension & bending

    Ag=10.875 in.2; S=13.14 in.3; ft=T/Ag=4440/10.875= 408psi

    F*b= Fb(cD)(cF) = 1100(1.15)(1.2) = 1518 psift/Ft+ fbx/F*bx= 408/1000+822/1518 = 0.95 < 1 OK

    (D+S governs, but D alone is close)

    Net bending compressive stress: automatically ok, since

    we already checked it.

    Also, since combined stress index is 0.95, we are likely

    not going to find a smaller size that would work.

    In general, CSI values of 1.02 or 1.03 could be

    acceptable.

  • 7/21/2019 Design of Axial Members - Wood

    37/41

    37

    Example 7.18 Beam-Column

    Determine required size of truss top chord (example 7.15)

    D + S loads, effects of roof slope already accounted for

    Connections made with a single row of in. bolts

    Trusses 4 ft o.c., lumber is No. 1 Southern Pine

    MC < 19%, normal temperatures, top chord laterally braced

    Example 7.18 Beam-Column Try 2x8: A = 10.875 in.2; S = 13.14 in.3 CF= 1 for both C & B

    Fc= 1650 psi, Fb= 1500 psi, Emin= 620,000 psi

    Axial: Stability check: fc= P/A = 4960/10.875 = 456 psi

    (le/d)x=kle/dx=1(8.39)(12)/7.25 = 13.9;Emin=Emin= 620,000psi c = 0.8 for visually graded lumber

    = 2638 psi; Fc* = 1650(1.15)(1.0) = 1898 psi

    S = 0.791; Fc= 1898(.791)=1501 psi

    1501 > 456 OK

    x

    x

  • 7/21/2019 Design of Axial Members - Wood

    38/41

    38

    Example 7.18 Beam-Column

    Try 2x8: A = 10.875 in.2; S = 13.14 in.3 CF= 1 for both C & B

    Fc= 1650 psi, Fb= 1500 psi, Emin= 620,000 psi

    Net section check:

    An=1.5(7.25 (13/16)) = 9.66 in2

    fc= P/A = 4960/9.66 = 514 psi

    Fc= Fc* = 1650(1.15)(1.0) = 1898 psi > 514 OK

    Bending Check:

    M = wl2

    /8 = 0.176(7.5)2

    /8 = 1.24 ft-k; fb= M/S = 1130 psiFb= 1500(1.15)(1.0) = 1725 psi > 1130 psi OK

    Example 7.18 Beam-Column

    Try 2x8: A = 10.875 in.2; S = 13.14 in.3 CF= 1 for both C & B

    Fc= 1650 psi, Fb= 1500 psi, Emin= 620,000 psi

    Combined Stress check :

    CDbased on shortest duration of load in combination

    FcEx= FcE= 2638 psi (coincidence that le/dx= le/dmax)

    Fb= 1130 psi; Fbx= 1725 psi; fc= 456 psi; ; Fc= 1501 psi

    (456/1501)2 + (1/(1 456/2638)(1130/1725) = 0.884 < 1 OK

    Use 2 x 8 No. 1 SP

  • 7/21/2019 Design of Axial Members - Wood

    39/41

    39

    Example 7.20 Glulam Beam-Column

    Check glulam column that supports gravity and wind loads L.C. 1: D +LR ; L.C. 2: D + W

    Axial-load glulam combination: 5-1/8x7-1/2; 2 DF glulam

    Example 7.20 Glulam Beam-Column

    L.C. 1: Gravity loads: D + LR = 5+4 = 9k; cD= 1.25;

    (D alone should be checked as well)

    neglect column fixity @ ends, assume k=1:

    (le/d)x= 1(16)(12)/7.5 = 25.6(le/d)y= 1(8)(12)/5.125 = 18.7 < 25.6

    Exmin= Eymin= Emin= 830,000 psi, c = 0.9 for glulam

    = 1041 psi; Fc* = 1950(1.25) = 2438 psi

    = 0.4; Fc= 2438(0.4) = 975 psi

    fc = P/A = 9000/38.4 = 234 psi;

    OK

    Table 5B:

    Fc=1950 psi;

    Fbx=1700 psi;

    Exmin= 830,000psi

    Eymin = 830,000psi

    A = 38.4 in2;

    S = 48 in3

    xx

  • 7/21/2019 Design of Axial Members - Wood

    40/41

    40

    Example 7.20 Glulam Beam-Column

    L.C. 2: Could be (D +W) or (D + 0.75(W + Lr))(predetermined that D+W governs)

    Axial (dead load):

    (le/d)max= (le/d)x= 25.6 from before

    Emin= 830,000 psi, c = 0.9 for glulam

    = 1041 psi; Fc* = 1950(1.6) = 3120 psi

    1.6taken throughout combined stress check

    = 0.319; Fc= 3120(0.319) = 995 psi

    fc = P/A = 5000/38.4 = 130 psi

    fc/Fc= 0.131

    Table 5B:Fc=1950 psi;

    Fbx=1700 psi;

    Exmin= 830,000psi

    Eymin = 830,000psi

    A = 38.4 in2;

    S = 48 in3

    xx

    Example 7.20 Glulam Beam-Column

    L.C. 2(D +W): Bending (wind)

    Wind on header: w1

    = 22.2(6.5) = 144 lb/ft

    Wind on sill: w2= 22.2(5.5) = 122 lb/ft

    Reaction on column from headers: P1= 144(12) = 1728 lb

    Reaction on column from sills: P2= 122(12) = 1463 lb

    Mx= 87.8 in-k; f b= M/S = 87.8/48 = 1830 psi

    Fb=Fb(cD)(cL) or Fb=Fb(cD)(cV); determine which governs

    Load & shear & moment

    Table 5B:

    Fc=1950 psi;

    Fbx=1700 psi;

    Exmin= 830,000psi

    Eymin = 830,000psi

    A = 38.4 in2;

    S = 48 in3

    Wall Framing and Tributary heights

  • 7/21/2019 Design of Axial Members - Wood

    41/41

    Example 7.20 Glulam Beam-Column

    L.C. 2Bending (wind):

    FindcL: lu= 8 ft (window height); lu/d=96/7.5=12.8.

    7 12.8 14.3: le= 1.63lu+3d = 179 (Table 3.3.3)*

    * formula applies conservatively for all cases

    = 7.15; = 19,483; Fb*= 1700(1.6)=2720 psi

    = 0.993

    FindcV: (21/L)1/x(12/d)1/x(5.125/b)1/x x for DF glulam = 10

    Cv= (21/16).1(12/7.5).1(5.125/5.125).1 =

    Cv= 1.007 > 1 : Cv= 1, CLgoverns:

    Fb= 1700(1.6)(.993) = 2700 psi

    Stress ratio: fb/Fb= 1830/2700 = 0.678

    Table 5B:

    Fc=1950 psi;

    Fbx=1700 psi;

    Exmin= 830,000psi

    Eymin = 830,000psi

    A = 38.4 in2;

    S = 48 in3

    Example 7.20 Glulam Beam-Column

    L.C. 2Combined Stresses:

    (le/d)bending= (le/d)x= 25.6 coincidence, could differ

    = 1041; From before:

    fc= 130 psi; fc/Fc= 0.131; fb/Fb= 0.678

    Amplification factor: 1/(1-fc/FcE) = 1/(1-130/1041) = 1.14;

    = (0.131)2 + 1.14(0.678) = 0.79OK

    Note: if D + 0.75(W + LR) was used, the interaction valuewould be considerably less.

    NOTE: shear, deflection, and bearing perpendicular to

    grain also need to be checked

    Table 5B:

    Fc=1950 psi;

    Fbx=1700 psi;

    Exmin= 830,000psi

    Eymin = 830,000psi

    A = 38.4 in2;

    S = 48 in3

    xx