INCH-POUND

MIL-STD-1653B(AS) 30 May 1997

SUPERSEDING MIL-STD-1653A(AS)

12 March 1980

DEPARTMENT OF DEFENSEINTERFACE STANDARD

POWER CABLE ASSEMBLIES

AMSC N/A FSC 6150

Downloaded from http://www.everyspec.com

MIL-STD-1653B(AS)

FOREWORD

1. This standard is approved for use by the Naval Air System Command, Department of theNavy, and is available for use by all Departments and Agencies of the Department of Defense.

2. Beneficial comments (recommendations, additions, deletions) and any pertinent data whichmay be of use in improving this document should be addressed to Commander, Naval Air WarfareCenter Aircraft Division, Code 4.1.4.2B120-3, Highway 547, Lakehurst, NJ 08733-5100, byusing the self-addressed Standardization Document Improvement Proposal (DD Form 1426)appearing at the end of this document or by letter.

ii

Downloaded from http://www.everyspec.com

MIL-STD-1653B(AS)

CONTENTSPARAGRAPH PAGE

FOREWORD...................................................................................................ii

1. SCOPE.............................................................................................................11.1 Scope...........................................................................................................1

2. APPLICABLE DOCUMENTS.........................................................................12.1 General........................................................................................................12.2 Government Documents...............................................................................12.2.1 Specifications, standards, and handbooks.....................................................1

3. DEFINITIONS.................................................................................................23.1 Organizational (flightline) equipment............................................................23.2 Intermediate (shop) equipment.....................................................................23.3 Type I..........................................................................................................2

4. GENERAL REQUIREMENTS ........................................................................24.1 Electrical power source................................................................................24.2 Cable assembly construction.........................................................................2

5. DETAILED REQUIREMENTS.......................................................................35.1 Connections.................................................................................................35.2 Power cable assemblies................................................................................3

6. NOTES ............................................................................................................46.1 Intended use.................................................................................................46.2 Cross-reference............................................................................................46.2.1 Replacement Series......................................................................................46.3 Subject term (keyword) listing......................................................................56.4 Changes from previous issue........................................................................5

TABLE

I Test Equipment Power Cables, Connectors and Connections........................4

FIGURE

1. Power cable (detachable) 60 Hz 1∅ 115 volts..............................................62. Test equipment receptacle 60 Hz 1∅ 115 volts............................................63. Bench power receptacle Wiring 60 Hz 1∅ 115 volts....................................6

iii

Downloaded from http://www.everyspec.com

MIL-STD-1653B(AS)

CONTENTSFIGURE PAGE

4. Power cable (detachable) 400 Hz 1∅ and 3∅ (line to neutral) 115/200V .....75. Test equipment receptacle 400 Hz 1∅ 115 volts............................................... 76. Test equipment receptacle 400 Hz 3∅ (line to neutral) 115/200V...................... 87. Bench power receptacle wiring 400 Hz 1∅ to 3∅ (line to neutral) ...................

115/200V.......................................................................................................... 88. Power cable (detachable) 28 volts D.C. ............................................................ 99. Test equipment receptacle 28 volts D.C. .......................................................... 910. Bench power receptacle wiring 28 volts D.C. ................................................... 911. Power cable (attached) 60 Hz 1∅ 115 volts...................................................... 1012. Power cable (attached) 400 Hz 1∅ 115 volts.................................................... 1013. Power cable (attached) 400 Hz 3∅ (line to neutral)

115/200 volt...................................................................................................... 1114. Power cable (attached) 28 volts D.C. ............................................................... 1115. 60 Hz to 400 Hz power plug adapter................................................................. 12

iv

Downloaded from http://www.everyspec.com

MIL-STD-1653B(AS)

1. SCOPE

1.1 Scope. This standard specifies the configuration requirements of input power cableassemblies for Organizational (flightline) and Intermediate (shop) electronic test equipment,classified as Type I in MIL-T-28800, and rated up to 10 amperes. It also shows the relevantconnections for the test equipment and power source receptacles.

2. APPLICABLE DOCUMENTS

2.1 General. The documents listed in this section are specified in sections 3, 4, and 5 of thisstandard. This section does not include documents cited in other sections of this standard orrecommended for additional information as examples. While every effort has been made to ensurethe completeness of this list, document users are cautioned that they must meet all specifiedrequirements of documents cited in sections 3, 4, and 5 of this standard, whether or not they arelisted.

2.2 Government Documents.

2.2.1 Specifications, standards, and handbooks. The following specifications, standards andhandbooks form a part of this document to the extent specified herein. Unless otherwisespecified, the issues of these documents are those listed in the latest issue of the Department ofDefense Index of Specifications and Standards (DoDISS) and supplement thereto, cited in thesolicitation.

FEDERAL SPECIFICATIONS

W-C-596 - Connector, Electrical, Power

DEPARTMENT OF DEFENSE SPECIFICATIONS

MIL-C-3432 - Cable and Wire, Electrical (Power and Control, Flexible and Extra Flexible, 300 and 600 Volts)

MIL-C-28777/5 - Cable Assembly, Electronic Test Equipment, (3 wire, 3 prong, 125 volt, molded) Grounding Plug Connector

MIL-T-28800 - Test Equipment for use with Electrical and Electronic Equipment, General Specification for

DEPARTMENT OF DEFENSE STANDARDS

MS2548 - Cable Assemblies, Electric Power, for Portable Ground Support Equipment

MS3102 - Connector, Receptacle, Electric, Box Mounting

1

Downloaded from http://www.everyspec.com

MIL-STD-1653B(AS)

MS3106 - Connector, Plug, Electric, StraightMS3107 - Connector, Plug, Electric, Quick DisconnectMS3436 - Connector, Plug, Electric, Solder Contact, UtilityMS3507 - Connector, Plug, Electric, Solder Contact, Quick

Disconnect, UtilityMS90384 - Cables, Electric Power, Permanently Wired, for

Portable Ground Support Test Equipment

(Unless otherwise indicated, copies of the above specifications, standards, and handbooks areavailable from the Standardization Document Order Desk, 700 Robbins Avenue, Building 4D,Philadelphia, PA 19111-5094.)

3. DEFINITIONS

3.1 Organizational (flightline) equipment. Test equipment used in the vicinity of the aircrafton land or on board ship. It includes test equipment used on the flight line or flight deck, and inthe hangar or hangar deck. This class of test equipment is for use in areas where theenvironmental conditions are uncontrolled.

3.2 Intermediate (shop) equipment. Test equipment used in the shop at land facilities or onboard ship where the service area is protected and environmentally controlled for humanoccupancy. It includes test equipment used in field shops, fixed or mobile.

3.3 Type I. Test equipment designed specifically for military use.

4. GENERAL REQUIREMENTS

4.1 Electrical power source. Equipment not powered from aircraft or system under test shalloperate from power sources specified by the acquiring activity. The nominal power sources shallbe selected from the following voltages that are readily available to the maintenance technician:

a. 60 and 400 Hz, single phase, 115V

b. 400 Hz (only), single phase, 115V

c. 400 Hz (only), 3 phase wye (line to neutral), 115/200V

d. DC, 28V

4.2 Cable assembly construction. This standard specifies the type of connectors, cables,color codes and pin connections required for each voltage source. Other items needed tocomplete the cable assemblies are to be consistent with good construction practices.

2

Downloaded from http://www.everyspec.com

MIL-STD-1653B(AS)

5. DETAILED REQUIREMENTS

5.1 Connections.

a. The cable assembly connections for equipment rated up to 10 amperes shall be asspecified in Table I, column 1 or 2 as applicable for the voltage source.

b. Connections for the equipment receptacles and power source receptacles listed in TableI, columns 3 and 4 are shown for informational purposes.

c. Connections for other power source requirements or current ratings higher than 10amperes shall be as specified by the acquiring activity.

5.2 Power cable assemblies.

a. Detachable power cable assemblies shall be as specified in Table I, column 1 asapplicable for the voltage source. They are furnished with equipment having a combination caseenclosure with a removable front cover and input power connection on the front panel. Thecables shall be stowed in the enclosure cover.

b. Permanently attached power cable assemblies shall be as specified in Table I, column 2and shall be furnished with other style enclosures. A strain relief shall be provided.

c. Equipment operating from multiphase sources (60 and 400 Hz) shall be furnished witha cable assembly as specified in figures 1 or 11 and an adapter as in figure 15.

d. No branched power cable assemblies shall be furnished.

e. Power cable assemblies for other power sources or current ratingshigher than 10 amperes shall be as specified by the acquiring activity.

3

Downloaded from http://www.everyspec.com

MIL-STD-1653B(AS)

TABLE I. Test equipment power cables, connectors and connections

1 2 3 4EQUIPMENT

POWERREQUIREMENT

DETACHABLEPOWERCABLE

ASSEMBLY

ATTACHEDPOWERCABLE

ASSEMBLY

EQUIPMENTRECEPTACLE

POWERSOURCE

RECEPTACLE

60 and 400 HZ1 Phase115V

Figs. 1 & 15 Figs. 11 & 15 Fig. 2 Figs. 3 & 7

60 HZ1 Phase115V

Fig. 1 Fig. 11 Fig. 2 Fig. 3

400 HZ1 Phase115V

Fig. 4 Fig. 12 Fig. 5 Fig. 7

400 HZ3 Phase Wye115/200V

Fig. 4 Fig. 13 Fig. 6 Fig. 7

DC28V Fig. 8 Fig. 14 Fig. 9 Fig. 10

6. NOTES

(This section contains information of a general or explanatory nature that may be helpful, but isnot mandatory.)

6.1 Intended use. The cable assemblies described by this standard are intended for use withtest equipment aboard carriers and on shore.

6.2 Cross-reference. This interface standard replaces MIL-STD-1653A(AS).

6.2.1 Replacement series. For replacement of MS3102, MS3106 and MS3107 connectors,see the applicable MS3400 and MS3450 series documents.

4

Downloaded from http://www.everyspec.com

MIL-STD-1653B(AS)

6.3 Subject term (keyword) listing.

connectorsflightlineground supportintermediateorganizationalplugreceptaclestest equipment

6.4 Changes from previous issue. Marginal notations are not used in this revision to identifychanges with respect to the previous issue. There are no technical changes in the power cableassemblies resulting from the transition from a MILITARY to an INTERFACE STANDARD.

5

Downloaded from http://www.everyspec.com

MIL-STD-1653B(AS)

6

Downloaded from http://www.everyspec.com

.-

MIL-STD-1653B(AS)

BLACK +AA A

6REO + B

B

cORANGE+C

cWHITE NEUTRAL

QGREEN SAFETY GROUNO

D

CONNECTEOTO SHELL

MS3507A- 20-4P MS3436A-20-4SPOWER PLUG EQUIPMENT PLUG

CABLE NO: CO-05MGF[5/16) 0455 (MIL-C-3432)LENGTH I 96*21NCHESPOWER CABLE P/NI M$2548-4 f

FIGURE 4. PO wercable (detachable) 400Hz lb and 3b(linc to neutral) 115/200v.

r)● d

wMS3102A-20-4PMATES WITH MS3436A-20-4S

A

B

c

Dl=:’ ~‘BLACK

NO CONNECTION HI

NO CONNECTION LOAD

WHITE LO

SHELL CONNECTED TOEQUIPMENT CASE

MS3102A-20-4P (CLEANED AND f30NDEo)

(SCc6.2.1) ‘A-BLACK,LOAD(HI SIOE)6-NO CONNECTIONC-NO CONNECTIOND- WHITE,CIRCUIT RETURN LINE(LO SIDE)

SHELL-EQUIPMENT CASE (CLEANED AND BONDED)

FIGURE 5.~estequipment receptacle400Hzl $115 volts.

7

Downloaded from http://www.everyspec.com

. .

MIL-STD-1653B(AS)

9P

o0, ●A

C, ,B

MS3102A-20-4PMATES WITH tvtS3436~-20-4S

A-BLACK, +A LOAD(HI SIDE)B- REO, +B LOAO (H IstDE)C- ORAN GE, +C LOAD (HI SIDE)D- WHITE, SYSTEM RETURN LINE

SHELL-EQUIPMENT CASE (CLEANED

- ~SHELL CONNECTEDTO

MS3102A-20- 4P EQUIPMENT CASE

(scc6.2.1) (CLEANED AND BONDED)

(LO SIDE)

AND BONDED)

FIGURE 6. Test equipment receptacle 400 Hz 3+ (line to”neutral)l15/200V.

9 Q

o+A ~~e A

‘o 0°+a~ Q B

+ c —--+ii* cBO oc AC GROUND NEUTRAL

MS3102A-20-4S

MATES WITH MS3507A-20-4P-L

STRUCTURE~ =

/ -MS3102A-20-4S

:-#A oR SINGLE+ “CONNECTION TO SHELL~ (see6.2. 1)

+B .C-+cD- AC GROUND ATTACHED TO STRUCTURE ,

SHELL -GROUND ATTACHED TO STRUCTURE

FIGURE 7. ench DOwerrecc~ taclewiring400Hz ]dand36 (line to neutral) 115/200V.●

8

Downloaded from http://www.everyspec.com

$,?

MIL-sTD-16i3B(As)

BBLACK

WHITEB

A

MS3107A-16-IIP MS3106A-16-IISPOWER PLUG EQUIPMENT PLUG

(SCC 6.2.]) (scc6.2.1)CABLE NO. ICO-02MGF(2/14) 0400 (MI L-c-3432)

LENGTH t 96&2 INCHES

POWER CABLE P/N~ MS2648-6

FIGURE 8. Power cable (detachable) 28 volts DC.

‘o -~~‘=- ‘~B@

‘+

+ B8LACK

LOAD

AWHITE

‘o

MS3102A-16-IIPEQUIPMENT CASE+ =

LA-w

MS3102A-16-IIPMATES WITH MS3106A-16-ll S

A-B-

WHITE, NEGATIVE GROUND8LACK, POSITIVE, LOAD (HI

(S026.2. I )

SIDE)

FIGURE 9. Test eauitment receD tacle 28 volts DC.

oBo

Ao

+lt+

MS3102A-16- I ISMATES WITH MS3107A-16- 11P

‘428 VOLTS DC POSITIVE ~

NEGATIVE ATTACHED TO ASTRUCTURE

-LSTRUCTURE ~= MS3102A-16-IIS

(see6.2. 1)

A- NEGATIVE, GROUNDB- POSITIVE, 28 VOLTS DC

FIGURE 10. J3ench power rece~taclc wiri~ 28 volts DC.●

b

-—>--..—-

9

- L—--..— — L- -----.1— -.. L-X.. ---.. :--2 >-&-

Downloaded from http://www.everyspec.com

.,... -

MIL-STD-1653B(AS)

r—.. —EQUIPMENT

CAE3LE STRAIN RELIEF A

I HI

ILOAD

HOTI

NEUTRALWHITE I

LO

SAFETY GROUND -,GREEN

EQUIPMENT CASEMOLDED POWER PLUG

MATES WITH W-C-596/12-4 1- —— —

.

POWER PLUG VIEWEO FROM THEI ENGAGING ENO

‘OT=@=:::::Lv,NALCABLE NO: M28777\5-1 (MIL-c-28777)

LENGTH: 96*21NCHES1 CABLE STRAIN RELIEF SHALL BE PROVIOEO

POWER CABLE P/N:M28777/5-l

FIGURE 11. Power cable [attached) 60 HZl$ llsvolts.

CABLE STRAIN RELIEF

-1 r’=p= –

A BLACK -w

BNO CONNECTION w I HI

NO CONNECTION I I LOADc

WHITE NEUTRAL I Loo

GREEN SAFETY GROUND

CONNECTED TO SHELL

L =~EQUIPMENT CASE

MS3507A-20-4PPOWER PLUG

— ..

CABLE NO: CO-03MGF(3/16)0365(MlU&C -3432)LENGTH: 96t2 INCHES, CA~LE STRAIN RELIEF SHALL BE PROVIDED

POWER CABLE P/N: MS90384-2

FIGURE 12. power cable (attached)400Hz lbll 5 volts. ,

10

--- . ..- 1 “, .# _yr–:— — , c - ——-—. --- -.--, --—- S [ -...”

Downloaded from http://www.everyspec.com

,. -

MIL-STD-1653B(AS)

r—————I

EQUIPMENT

CABLE ‘TRA’N ‘EL’EFl I HI LO

13LACK +AA ‘

B )REO #B Y- ,=

LcD

>coNNEcTED To SHELL IIMS3507A-20- 4PPOWER PLUG 1-

——— - -EQUIPMENT CASE

ORANGE+C

WHITE NEUTRALr * b~GREEN SAFETY GROUND I 1

#

CABLE NO: CO-05MGF(6/16)0455(hilL-C-3432)LENGTH : 96 ~ 21NCHES,CABLE STRAIN RELIEF SHALL BE pRovloEO

POWER CABLE P/NJ MS90384-I

FIGURE 13. Power cable (attached), 400 Hz 3$ (lln.

etoncutral) 115/200volL

r———”CABLE STRAIN RELIEF—\ I EQUIPMENT

LO

BBLACK LOAD 1

AWHITE f)

.

MS3107A-16-IIP I EQUIPMENT CASE~~POWER PLUG

(see6.2. 1)l—————

,.

CABLE NO’ CO-02MFG(2/14)0400(MlL~C-3432)LENGTHI 96~21NcHESt cABLE STRAIN RELIEF SHALL BE pRovlDED

POWER CABLE P/NI MS90384-4

FIGURE 14.●

PO er cable (at ached) 28w t volts DC.~

11

Downloaded from http://www.everyspec.com

MIL-STD-1653B(AS)

At

BLACK 1.

BNO CONNECTION

co WHITE

GREEN●

HOT

43

HOT

NEUTRAL “GROUND

‘ CONNECTED TO SHELL

MS3!307A-20-4P WC596-14-2 OR MOLDEDPOWER RECEPTACLEMATES WITH W-C-596/13

CABLE NO: CO-03MGF(3/16)0360 (MIL-C-3432jLENGTH : 8*2 lNcHESADAPTER P/N: MS2548-6

FIGURE 15.60 Hz to 400 Hz t)Ower Dlufzadanter.

CONCLUDINGMATER.IAL ,

Custodian:Navy - AS

Review activities:Navy - EC

Preparing activity:Navy - AS(Project 6150-N269)

12

Downloaded from http://www.everyspec.com

STANDARDIZATION DOCUMENT IMPROVEMENT PROPOSALINSTRUCTIONS

1. The preparing activity must complete blocks 1, 2, 3, and 8. In block 1, both the document number and revision letter should begiven.

2. The submitter of this form must complete blocks 4, 5, 6, and 7.

3. The preparing activity must provide a reply within 30 days from receipt of the form.

NOTE: This form may not be used to request copies of documents, nor to request waivers, or clarification of requirements on currentcontracts. Comments submitted on this form do not constitute or imply authorization to waive any portion of the referenceddocument(s) or to amend contractual requirements.

I RECOMMEND A CHANGE: 1. DOCUMENT NUMBERMIL-STD-1653B (AS)

2. DOCUMENT DATE (YYMMDD)970530

3. DOCUMENT TITLE POWER CABLE ASSEMBLIES

5. REASON FOR RECOMMENDATION

6. SUBMITTERa. NAME (Last, First, Middle Initial) b. ORGANIZATION

c. ADDRESS (Include Zip Code) d. TELEPHONE (Include Area Code)(1) Commercial

(2) AUTOVON(if applicable)

7.DATE SUBMITTED(YYMMDD)

8. PREPARING ACTIVITY

a. NAME

COMMANDER, NAVAL AIR WARFARE CENTERAIRCRAFT DIVISION

b. TELEPHONE Include Area Code)(1) Commercial (2) AUTOVON(908) 323-7488 624-7488

c. ADDRESS (Include Zip Code) CODE 414100B120-3 HIGHWAY 547 LAKEHURST, NJ 08733-5100

IF YOU DO NOT RECEIVE A REPLY WITHIN 45 DAYS, CONTACT:DEFENSE QUALITY AND STANDARDIZATION OFFICE5203 Leesburg Pike, Suite 1403, Falls Church, VA 22401-3466Telephone (703) 756-2340 AUTOVON 289-2340

DD Form 1426, OCT 89 Previous editions are obsolete. 198/290

Downloaded from http://www.everyspec.com