Definition of initiating events including protection misoperation for dynamic studies of cascading outages E. Ciapessoni, D. Cirio, A. Pitto Ricerca sul Sistema Energetico RSE S.p.A. Milan, Italy 1

Upload: lamhuong

Post on 05-May-2018

217 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Definition of initiating events including protection misoperation …sites.ieee.org/pes-cascading/files/2016/07/9-Ciapessoni_v2-CFWG... · Definition of initiating events including

Definitionofinitiatingeventsincludingprotection

misoperation fordynamicstudiesofcascadingoutages

E.Ciapessoni,D.Cirio,A.PittoRicerca sul Sistema Energetico RSES.p.A.

Milan,Italy

1

Page 2: Definition of initiating events including protection misoperation …sites.ieee.org/pes-cascading/files/2016/07/9-Ciapessoni_v2-CFWG... · Definition of initiating events including

Overview

• Challengesinmodelingcontingenciesfordynamicstudies

• Probabilisticmodelingapproach• Examples• Conclusions

2

Page 3: Definition of initiating events including protection misoperation …sites.ieee.org/pes-cascading/files/2016/07/9-Ciapessoni_v2-CFWG... · Definition of initiating events including

Modeling initating contingencies fordynamicstudies:stateofartandchallenges

• Nowadays’timedomain-based cascading simulators– Dynamicmodels formost commonprotectionrelays (overcurrent,distance,

under/overvoltage)areincluded,tosimulatecascadingevolution (+)– little attentiondevoted tothedefinitionoftheinitiatingevent (-)

• Dependence inN-kevents (kusually <3)is not considered• Simplified representation ofsubstation configuration («bus-branch»model)

• However,thefollowing factors areimportant toevaluate thefinalimpactofadisturbance inadynamic simulation:– Linking contingencieswithroot causes

• Starting fromthreats todrivetheselection ofmost dangerous N-kcontingencies

– Substationconfiguration• Simplebusbar,doublebusbar

– Primaryandback-upprotection response inearly faultstages• Correct operation,stuck breaker,communication failure• Timesequence ofprotection intervention is important:same«static»contingency canbe

translated into different «dynamic»ctgs

3

Page 4: Definition of initiating events including protection misoperation …sites.ieee.org/pes-cascading/files/2016/07/9-Ciapessoni_v2-CFWG... · Definition of initiating events including

Modeling theinitiating contingencies inRSE’sProbabilistic Risk Assessment tool

4

Herecontingencymodels aredefined

fordynamicsimulations!

Page 5: Definition of initiating events including protection misoperation …sites.ieee.org/pes-cascading/files/2016/07/9-Ciapessoni_v2-CFWG... · Definition of initiating events including

Approach forcontingencymodeling indynamics

• Aninitiatingcontingency isdefined intermsof:– Fault(type,impedance andlocation)– Outaged components– Timesequence ofprotection interventions inthevery early instants after thefault– Its probability ofoccurrence

• Accountingforprimaryandback-upprotections inearly faultstage– Busdifferential protections– Backupprotections (IIzonedistance relays forlines,overcurrent protections fortrafos)– Breaker failure devices

5

Outaged elements

Timesequence ofprot.interventions

Probability ofoccurrence

Hazard model

Substationconfiguration

Protection responsetype C

TG F

EATU

RES

… used to evaluate …

Page 6: Definition of initiating events including protection misoperation …sites.ieee.org/pes-cascading/files/2016/07/9-Ciapessoni_v2-CFWG... · Definition of initiating events including

Hazardmodeltheroot causes ofcontingencies

6

Probabilistic models ofhazardspThr(s,t,x)

Probabilistic models ofcomponentvulnerability

PV(t|s,t,x)

DATAinputs (user,onlinemonitoringsystems, historical dataseries,etc.)

Tuning of models

Component failure probability

Forany component,located at x

Contingency probability

Combining component failure probs

SHORT TERMLONG TERM

Selection of«critical»components

( ) ( ) ( )∫ ∫ ⋅=

t

t SThrVF ddsxspxstPtxP

0

,,,,|, τττ

Page 7: Definition of initiating events including protection misoperation …sites.ieee.org/pes-cascading/files/2016/07/9-Ciapessoni_v2-CFWG... · Definition of initiating events including

Substation configuration:themodel• «Bus-branch»representation usually available for

substationsmodeling incurrent tools– Lack ofdataonactual substation configuration

• «Bus-branch»modelconverted into «node-breaker»model

– using reasonable assumptions based onbaypower flows

7

Half-busbar

sets

1 Odd elements of LE & TUEven elements of LU & TE

2 Odd elements of LO & TEEven elements of LE & TU

Defining four bay sets:LU (lines with outgoing power flow), TU (transformers with outgoing

power flow), LE (lines with injected power flow), TE (transformers with injected

power flow)Applying the rules in the table above

Page 8: Definition of initiating events including protection misoperation …sites.ieee.org/pes-cascading/files/2016/07/9-Ciapessoni_v2-CFWG... · Definition of initiating events including

Contingency Enumeration fromhazard modelsTheinitial setofctgs (tobefurther screened)is given by:- All N-1ctgs- multipleN-kcontingencies

- power plant andbusbarctgs,considering possiblemalfunctioning ofprotection systems

- Multiplebranchcontingencies duetoextensive effect ofacommonthreat (e.g. astorm)

Risk based ctg screening is thenperformed using topological(geodesic length,net-ability)metrics toassess impact

8

Hazard modeling Vulnerabilitymodeling

Calculating probability offailure forpower/ICTcomponents

Identifying setofindividual critical components

Defining N-1,N-kcontingencies(including componentdependencies)

Calculating contingencyprobability

Calculating ex-anteimpact

Calculating «ex-ante»risk

Contingency screeningbased onex-anterisk

Page 9: Definition of initiating events including protection misoperation …sites.ieee.org/pes-cascading/files/2016/07/9-Ciapessoni_v2-CFWG... · Definition of initiating events including

Multiplecontingencies:selection criteria

• AnextensiveN-kanalysisis unfeasible– Combinatorial explosion!

• Need forcriteria todrivethesearch

• Selecting componentsmorepronetofail(«critical components»)using cumulativescreeningmethod

9

Criticalcomponents allowidentifying:

– Thecritical branches– Criticalsubstations:if theirbusbars orat least one ofconnectedbranch arelistedinthecritical componentset

– Criticalpower plants:iftheir busbars orgeneratorsarelisted inthecriticalcomponentset

Page 10: Definition of initiating events including protection misoperation …sites.ieee.org/pes-cascading/files/2016/07/9-Ciapessoni_v2-CFWG... · Definition of initiating events including

Which dependencies?• Geographical dependency among components inN-kmultiplebranch contingencies– All components affected bythesame root cause

• Functional dependencies in:– Doublecircuit outages– Power Plant (PP)outages

• AFaultonEHVbusbarmaydisconnectedthewholePPconnectedtothebusbar

– Busbar outages• Anincorrectoperationofprotectionsmay tripmorecomponentsthan expected

• Afailureonameasurement transformers andcircuitbreakersmaylead totheoutageofthebusbar theyareconnectedto

10

Page 11: Definition of initiating events including protection misoperation …sites.ieee.org/pes-cascading/files/2016/07/9-Ciapessoni_v2-CFWG... · Definition of initiating events including

Protection SystemResponsemodelMultiplecontingencies onbusbars

• Busbar contingencies– different assumptions onprotectionsystem responses:B1)correctfaultclearingwithbusdifferentialprotectionsB2)Acircuitbreakeronabayisstuck.B3)Busbar couplerdoesn’topen

• onlyfortheseparable busbarB4)missedinterventionofbusbardifferentialprotection

• Specifications ofcontingenciesB1andB2arerequired accordingtothesubstation configuration (singleordoublebusbar)

• Probability oftheN-kcontingency is evaluated bycombiningfailure probabilities ofthedifferent involveddevices (branches,relays,circuit breakers,etc.)

11

Page 12: Definition of initiating events including protection misoperation …sites.ieee.org/pes-cascading/files/2016/07/9-Ciapessoni_v2-CFWG... · Definition of initiating events including

Protection SystemResponsemodelMultiplecontingencies onpower plants

• Power plant contingencies cansignificantly threatenpower system securityduetothepowermismatch theymay cause

• Tripping ofmany units at atimeis possible incaseof:– Stressed operating conditions– Problems totherelated thermal process (incaseofthermalunits)

– Faultonthebusbars oftheEHVsubstation which connectsthePPtothegrid

12

Page 13: Definition of initiating events including protection misoperation …sites.ieee.org/pes-cascading/files/2016/07/9-Ciapessoni_v2-CFWG... · Definition of initiating events including

Assessing theprobability ofoccurrence:Commonmodeevents

• Importantexampleofcommonmodeoutages– E.g.Storm affecting aportion ofthegrid

• Usingthesame threat modeltodetermine failure probs ofinvolvedcomponents is theintrinsic causeofdependenceamongPFj(t)– Thehigher thehazard magnitude,thehigher theprobabilities ofall affected

components• N-kbranchoutages probalso is given by

PCTG(t)=Pj=1…TR PFj(t)*Pk=TR+1…N (1-PFk(t))

TR=nroftripped components, N=total nrofcomps• Incaseofdoublecircuit lines (circuits AandB)theapproachallows toestimate

failureprobability ofthedoublecircuitp(AOUT&BOUT)=C([PA PB],rho)

C is thecorrelationmodel(copula),rhomaybederivedfromanalysisofhistoricaldata(rho=0incaseoftwo lineswithsameterminals but nocommonpathway)

13

From samehazard model!

Page 14: Definition of initiating events including protection misoperation …sites.ieee.org/pes-cascading/files/2016/07/9-Ciapessoni_v2-CFWG... · Definition of initiating events including

( )( ) ( )( )

( ) ( ) ( )[ ]( )( )( )

( )( )⎥⎥⎥⎥⎥⎥⎥⎥⎥⎥

⎢⎢⎢⎢⎢⎢⎢⎢⎢⎢

⋅−×

×⋅−−×

×⋅−×−

⎭⎬⎫

⎩⎨⎧=

⎪⎭

⎪⎬⎫

⎪⎩

⎪⎨⎧=

⎭⎬⎫

⎩⎨⎧=

Xbusbar -half on theconnectedstrasformer

,

Xbusbar -half on theconnected linescircuit double

ofcircuit singletripping,,,,

Xbusbar -half on theconnectedlinescircuit single

,

1

,,1

11

1

jocCBtrafo

k

ocCBkBkAkAk

iocCBiHB

jj

k

iX

ptp

ptptpCtp

ptptp

ρ

Assessing theprobability ofoccurrence:busbar contingencies

14

OK

Line breaker doesn’t open

F

F

Busbar doesn’t open

F

F

N-k all the

section

N-k faulted half

busbar

N-k faulted half

busbar

Busbar Differential doesn’t trip

N-k all the

section

Initial Condition

Final Condition

Resulting Contingency

Conditions

Tripping the remote end of the lines

C = correlation model; pk,A = failure prob. of circuit A of k-th double circuit

Example (only for substations with separable busbars)Opening bays of half-busbar X (X = 1, 2) of busbar v

Busbar fail. prob increased by including PT’s and CB’sphalf-busbar system = 1 – (1-phalf-bus)*Õi: all CBs (1-pCBi) Õj: all PTs (1-pPTj).

Page 15: Definition of initiating events including protection misoperation …sites.ieee.org/pes-cascading/files/2016/07/9-Ciapessoni_v2-CFWG... · Definition of initiating events including

Assessing theprobability ofoccurrence:power plant (PP)outages

• Possible loss ofaPPgiven afaultonEHVside• Similar tobusbar outages but increased failureprobability ofstep-up transformers toaccountforgenerators’failure probability

15

tr_2

~

Set T_G_tr_1

tr_1

HV 1

G1

ptr1’ = 1- (1-ptr1)*(1-ptr2)*(1-pG1)

NO CB’s!

EXAMPLE

Page 16: Definition of initiating events including protection misoperation …sites.ieee.org/pes-cascading/files/2016/07/9-Ciapessoni_v2-CFWG... · Definition of initiating events including

Timesequence ofprotection interventionstheadditional protection device models

• Timesequence ofprotection interventionsplayanessential rule toassess ctg impactonpower systemdynamics– Same «static»contingency is translated into different

«dynamic»ctgs• Dynamic studies requiresadditionalmodels toaccount

forfurther protectionresponse types anddeviceswhichmayaffect timesequence

– Missing signal fromprotection relays– Breaker failure device (BFD)operation

• possible toassess theprobabilityofoccurrencealso for«dynamic»ctgs

– see tables innext slides

• IncludesP4andP5multiplecontingencies reported inTable1ofNERCStandardTPL-001-4—“TransmissionSystemPlanningPerformanceRequirements”,lastrev.Nov2014

16

87

21

BFD

KCB

Page 17: Definition of initiating events including protection misoperation …sites.ieee.org/pes-cascading/files/2016/07/9-Ciapessoni_v2-CFWG... · Definition of initiating events including

Dynamic definition ofcontingencies

17

CTGID

Description Probability ICT failure/stuckbreaker

Action

1 Busbar fault withcorrect operationof all CBs and BDP

psb/2*prod(1-pCBj)*(1-pK)*prod(1-p_bdpj)*(1-p_bdpK)*(1-pBDP)

NO Intervention of BDP

2a Busbar fault withmalfunction ofone signal to a CB

Psb/2*p_bdpj*(1-pCBj) *(1-pBDP)(forany j)

YES, missing signalto a CB

Intervention of BDP and breaker failuredevice on one CB

2b Busbar fault withone stuck breaker

Psb/2*pCBj*(1-pBDP)(forany j)

YES, one CB stuck Intervention of BDP and back up protectionfor one CB

3a Busbar fault withmissing signal to K

Psb/2*(1-pK)*p_bdpK*(1-pBDP)For any half-busbar

YES, missing signalto K

Intervention of BDP for faulty half-busbar +back-up protections for components of safehalf-busbar

3b Busbar fault withstuck K

Psb/2*pK*(1-pBDP)For any half-busbar

YES, stuck K Intervention of BDP for faulty half-busbar +breaker failure device for components ofsafe half-busbar

3c Busbar fault withBDP out of service

Psb/2*pBDPFor any half-busbar

YES, BDP out ofservice

Intervention of all backup protections forall components at two half-busbars

Source: TERNA (Italian TSO)

K = bus couplerpsb = failure probability (f.p.) at a busbarptr2 = transformer failure probabilitypl = line failure probabilityp_bdpj = BDP signal f.p. at component jp_dsj = distance protection signal f.p.p_ptj = Transformer protection signal f.p.p_BDP = probability of failure of Bus Differential Protection (BDP)

LEGEND

P4 and P5 outagesfrom TPL 001-4

P5

P4

P4

P5

P5

Page 18: Definition of initiating events including protection misoperation …sites.ieee.org/pes-cascading/files/2016/07/9-Ciapessoni_v2-CFWG... · Definition of initiating events including

18

CTGID

Description Probability ICTfailure/stuckbreaker

Action

4 Line fault Pl* (1-pCBj)*(1-p_dsj) NO Opening of faulty line with distanceprotections + telepiloting

5 Transfo fault Ptr2* (1-pCBj)* (1-p_ptj)

NO Opening of faulty transformer withovercurrent/differential protections

6 Line fault with stuckbreaker

Plj*pCBjFor any line j

YES, stuckbreaker

Intervention of breaker failure devicefor all safe CBs and backup protectionintervention for faulty CB

6b Line fault with missingtripping signal fromdistance protection(telepiloting)

Plj*(1-pCBj)*p_dsjFor any line j

YES, missingsignal

Intervention of back-up protections forcomponents of the whole substationconnected the faulty component

7 transfo fault with stuckbreaker

Ptr2j*pCBjFor any transfo j

YES, stuckbreaker

Intervention of breaker failure devicefor all safe CBs and backup protectionintervention for faulty CB

7b transfo fault withmissing signal fromovercurrent/differentialprotection

Ptr2j*(1-pCBj)*p_ptjFor any transfo j

YES, missingsignal

Intervention of back-up protections forcomponents of the whole substationconnected the faulty component

K = bus couplerpsb = failure probability (f.p.) at a busbarptr2 = transformer failure probabilitypl = line failure probabilityp_bdpj = BDP signal f.p. at component jp_dsj = distance protection signal f.p.p_ptj = Transformer protection signal f.p.p_BDP = probability of failure of Bus Differential Protection (BDP)

LEGENDDynamic definition of

contingencies

P4

P4

Page 19: Definition of initiating events including protection misoperation …sites.ieee.org/pes-cascading/files/2016/07/9-Ciapessoni_v2-CFWG... · Definition of initiating events including

Applicationexamples onrealistic EHVPS

• EHVgrid undertest:220/400kVSicily network

• Contingency setdefinedstartingfroma«storm»scenarioaffectingNorth-Westofisland– Includes 253ctgs (N-1,N-2and

multiple dependent N-kbusbarandpower plant ctgs)

• Two cases:– ScenarioA:telepiloting of

distance relays ON(IIzone=140ms)

– ScenarioB:Telepiloting OFF(IIzone=400ms)

19

0 0.002 0.004 0.006 0.008 0.01 0.012

N-1_CORP211_CRCP211N-1_CORP211_CRCP211SSB1_PRRP211SSB2_PRRP211N-1_BLLP211_CRCP211N-1_BLLP211_CRCP211N-1_CMRP211_PRRP211N-1_CMRP211_PRRP211N-1_PNAP211_PRRP211N-1_PNAP211_PRRP211N-2_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211N-2_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211N-2_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211N-2_Ln_BLLP211-CRCP211_Ln_CORP211-CRCP211N-2_Ln_BLLP211-CRCP211_Ln_CORP211-CRCP211N-2_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211N-2_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211N-2_Ln_BLLP211-CRCP211_Ln_CORP211-CRCP211N-2_Ln_BLLP211-CRCP211_Ln_CORP211-CRCP211N-1_BLLP211_PRRP211N-1_BLLP211_PRRP211N-1_CMRP211_CRCP211N-1_CMRP211_CRCP211N-2_Ln_CMRP211-CRCP211_CMRP211-CRCP211N-2_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211N-2_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-2_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-2_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-2_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211SSB1_PRRP211_BUSFAULT_MSig_CB_L_PP2250SSB2_PRRP211_BUSFAULT_MSig_CB_L_PP2251N-1_CORP211_SRGP211N-1_CORP211_SRGP211N-2_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211SSB1_PRRP211_BUSFAULT_MSig_CB_L_PP2225SSB2_PRRP211_BUSFAULT_MSig_CB_L_PP2224SSB1_PRRP211_BUSFAULT_MSig_CB_L_PP2223SSB2_PRRP211_BUSFAULT_MSig_CB_L_PP2222SB_CRCP211_BDP_OOSSB_CRCP211_BDP_OOSSB_CRCP211_HB2_stuck_BusCouplSB_CRCP211_HB1_stuck_BusCouplSSB1_PRRP211_BUSFAULT_stuckCB_L_PP2250SSB2_PRRP211_BUSFAULT_stuckCB_L_PP2251SSB1_PRRP211_BUSFAULT_stuckCB_L_PP2225SSB2_PRRP211_BUSFAULT_stuckCB_L_PP2224SSB2_CRCP211_BUSFAULT_stuckCB_L_PP2210SSB2_CRCP211_BUSFAULT_MSig_CB_L_PP2210SSB2_CRCP211SSB2_CRCP211_BUSFAULT_stuckCB_T_CRCP211A1SSB2_CRCP211_BUSFAULT_stuckCB_T_CRCP211A3SSB2_CRCP211_BUSFAULT_MSig_CB_T_CRCP211A1SSB2_CRCP211_BUSFAULT_MSig_CB_T_CRCP211A3SSB1+DT_PRRP211_L_251 _stuckCBSSB2+DT_PRRP211_L_250 _stuckCBSSB1_PRRP211_BUSFAULT_stuckCB_L_PP2223SSB2_PRRP211_BUSFAULT_stuckCB_L_PP2222SSB1+DT_CRCP211_L_210 _stuckCBSSB1_PRRP211_stuckCB_FAULT_ON_L_PP2250SSB2_PRRP211_stuckCB_FAULT_ON_L_PP2251SSB2_CRCP211_BUSFAULT_MSig_CB_L_PP2211SSB1_PRRP211_stuckCB_FAULT_ON_L_PP2225SSB2_PRRP211_stuckCB_FAULT_ON_L_PP2224SSB2_CRCP211_BUSFAULT_MSig_CB_L_PP2248SSB2_CRCP211_stuckCB_FAULT_ON_T_CRCP211A1SSB2_CRCP211_stuckCB_FAULT_ON_T_CRCP211A3SSB2_CMRP211SSB2_CMRP211_BUSFAULT_stuckCB_T_CMRP211A2SSB2_CMRP211_BUSFAULT_MSig_CB_T_CMRP211A2SSB1_PRRP211_stuckCB_FAULT_ON_L_PP2223SSB2_PRRP211_stuckCB_FAULT_ON_L_PP2222SSB2_CRCP211_stuckCB_FAULT_ON_L_PP2210N-3_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CORP211-CRCP211N-3_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CORP211-CRCP211N-3_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211N-3_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211N-3_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-3_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211SB_CRCP211_HB2_MSig_2_BusCouplSB_CRCP211_HB1_MSig_2_BusCouplN-3_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211N-3_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211SSB1_CORP211_BUSFAULT_stuckCB_T_CORP211A2SSB1_CORP211_BUSFAULT_MSig_CB_T_CORP211A2SSB1_CORP211_BUSFAULT_MSig_CB_L_PP2205SSB1_CORP211SSB1_CORP211_BUSFAULT_stuckCB_L_PP2205SSB2+DT_CRCP211_L_209 _stuckCBSSB2_CMRP211_BUSFAULT_MSig_CB_L_PP2250SSB1_CMRP211SSB1_CMRP211_BUSFAULT_stuckCB_T_CMRP211A1SSB1_CMRP211_BUSFAULT_MSig_CB_T_CMRP211A1SSB2_CRCP211_BUSFAULT_stuckCB_L_PP2211SSB2_CMRP211_BUSFAULT_MSig_CB_L_PP2249N-3_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-3_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-3_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-3_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-3_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-3_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-3_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-3_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211SSB1_PRRP211_no_signal_to_one_CBSSB1_PRRP211_no_signal_to_one_CBSSB1_PRRP211_no_signal_to_one_CBSSB2_PRRP211_no_signal_to_one_CBSSB2_PRRP211_no_signal_to_one_CBSSB2_PRRP211_no_signal_to_one_CBSSB1_CORP211_BUSFAULT_MSig_CB_L_PP2210N-4_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-4_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-4_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-4_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211SSB2_CMRP211_stuckCB_FAULT_ON_T_CMRP211A2N-4_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-4_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-4_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-4_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211SSB1_CMRP211_BUSFAULT_MSig_CB_L_PP2251SSB2_CRCP211_BUSFAULT_stuckCB_L_PP2248SSB1_CMRP211_BUSFAULT_MSig_CB_L_PP2248N-3_Ln_BLLP211-CRCP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211N-3_Ln_BLLP211-CRCP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211N-3_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211N-3_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211SSB1_CORP211_BUSFAULT_MSig_CB_L_PP2231SSB2_CRCP211_stuckCB_FAULT_ON_L_PP2211SSB2+DT_CRCP211_L_212 _stuckCBSSB2_CMRP211_BUSFAULT_stuckCB_L_PP2250SSB1_CMRP211_stuckCB_FAULT_ON_T_CMRP211A1SSB2+DT_CRCP211_L_249 _stuckCBSSB1_CORP211_stuckCB_FAULT_ON_L_PP2205N-4_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211SSB1_CORP211_BUSFAULT_stuckCB_L_PP2210SSB1_CORP211_stuckCB_FAULT_ON_T_CORP211A2N-4_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211SSB2_CRCP211_stuckCB_FAULT_ON_L_PP2248SSB2+DT_CMRP211_L_251 _stuckCBSSB2_CMRP211_BUSFAULT_stuckCB_L_PP2249SSB2_CRCP211_no_signal_to_one_CBSSB2_CRCP211_no_signal_to_one_CBSSB2_CRCP211_no_signal_to_one_CBSSB2_CRCP211_no_signal_to_one_CBSSB2_CRCP211_no_signal_to_one_CBSSB2+DT_CMRP211_L_248 _stuckCBSSB2_CMRP211_stuckCB_FAULT_ON_L_PP2250SSB1_BLLP211SSB1_BLLP211_BUSFAULT_stuckCB_T_BLLP211A2SSB1_BLLP211_BUSFAULT_MSig_CB_T_BLLP211A2SSB1_CMRP211_BUSFAULT_stuckCB_L_PP2251N-5_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-5_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211SSB2_CMRP211_no_signal_to_one_CBSSB2_CMRP211_no_signal_to_one_CBSSB2_CMRP211_no_signal_to_one_CBN-4_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211SSB2_CMRP211_stuckCB_FAULT_ON_L_PP2249SSB1+DT_CORP211_L_209 _stuckCBSSB1+DT_CMRP211_L_250 _stuckCBSSB1_CMRP211_BUSFAULT_stuckCB_L_PP2248SSB1_BLLP211_BUSFAULT_MSig_CB_L_PP2211SSB1+DT_CMRP211_L_249 _stuckCBSSB1_CORP211_stuckCB_FAULT_ON_L_PP2210N-4_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211N-4_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211N-4_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211N-4_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211SSB1_CMRP211_stuckCB_FAULT_ON_L_PP2251SSB1_CMRP211_no_signal_to_one_CBSSB1_CMRP211_no_signal_to_one_CBSSB1_CMRP211_no_signal_to_one_CBN-5_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211N-5_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211N-6_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211SSB1_BLLP211_BUSFAULT_MSig_CB_L_PP2222SSB2_BLLP211SSB2_BLLP211_BUSFAULT_stuckCB_T_BLLP211A3SSB2_BLLP211_BUSFAULT_MSig_CB_T_BLLP211A3SSB1_CMRP211_stuckCB_FAULT_ON_L_PP2248SSB1_BLLP211_stuckCB_FAULT_ON_T_BLLP211A2N-5_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211N-5_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211SSB1_BLLP211_BUSFAULT_stuckCB_L_PP2211SSB2_BLLP211_BUSFAULT_MSig_CB_L_PP2212SSB1+DT_BLLP211_L_212 _stuckCBSSB2_BLLP211_BUSFAULT_MSig_CB_L_PP2223SSB2_BLLP211_stuckCB_FAULT_ON_T_BLLP211A3SSB1_BLLP211_stuckCB_FAULT_ON_L_PP2211SSB2_BLLP211_BUSFAULT_stuckCB_L_PP2212SSB1_BLLP211_BUSFAULT_stuckCB_L_PP2222SSB1_BLLP211_no_signal_to_one_CBSSB1_BLLP211_no_signal_to_one_CBSSB1_BLLP211_no_signal_to_one_CBSSB1_BLLP211_stuckCB_FAULT_ON_L_PP2222SSB2+DT_BLLP211_L_211 _stuckCBSSB2_BLLP211_stuckCB_FAULT_ON_L_PP2212SSB2_BLLP211_BUSFAULT_stuckCB_L_PP2223SSB2_BLLP211_no_signal_to_one_CBSSB2_BLLP211_no_signal_to_one_CBSSB2_BLLP211_no_signal_to_one_CBSSB2_BLLP211_stuckCB_FAULT_ON_L_PP2223SSB1_CORP211_BUSFAULT_stuckCB_L_PP2231SSB1_CRCP211SSB1_CRCP211_BUSFAULT_stuckCB_T_CRCP211A2SSB1_CRCP211_BUSFAULT_MSig_CB_T_CRCP211A2SSB1_CRCP211_BUSFAULT_MSig_CB_L_PP2226SSB1_CRCP211_BUSFAULT_stuckCB_L_PP2226SSB1_CORP211_no_signal_to_one_CBSSB1_CORP211_no_signal_to_one_CBSSB1_CORP211_no_signal_to_one_CBSSB1_CORP211_no_signal_to_one_CBSSB1_CORP211_stuckCB_FAULT_ON_L_PP2231SSB1_CRCP211_BUSFAULT_MSig_CB_L_PP2209SSB1_CRCP211_BUSFAULT_stuckCB_L_PP2209SSB2_CORP211_BUSFAULT_MSig_CB_L_PP2204SSB2_CORP211SSB2_CORP211_BUSFAULT_stuckCB_L_PP2204SSB1_CRCP211_BUSFAULT_MSig_CB_L_PP2249SSB1_CRCP211_BUSFAULT_MSig_CB_L_PP2212SSB1_CRCP211_stuckCB_FAULT_ON_L_PP2226N-1_CORP211_SFMP231SSB2_CORP211_BUSFAULT_MSig_CB_L_PP2209SSB1_CRCP211_BUSFAULT_stuckCB_L_PP2212SSB1_CRCP211_stuckCB_FAULT_ON_T_CRCP211A2SSB1_CRCP211_stuckCB_FAULT_ON_L_PP2209SB_CMRP211_HB2_stuck_BusCouplSB_CMRP211_HB1_stuck_BusCouplSSB1_CRCP211_BUSFAULT_stuckCB_L_PP2249SSB1+DT_CRCP211_L_248 _stuckCBN-1_CORP211_SFMP221SSB1_CRCP211_stuckCB_FAULT_ON_L_PP2212SSB1+DT_CRCP211_L_211 _stuckCBSSB1_CRCP211_stuckCB_FAULT_ON_L_PP2249SSB2_CORP211_BUSFAULT_MSig_CB_L_PP2232SSB2_CORP211_BUSFAULT_stuckCB_L_PP2209SSB2_CORP211_stuckCB_FAULT_ON_L_PP2204SSB1_CRCP211_no_signal_to_one_CBSSB1_CRCP211_no_signal_to_one_CBSSB1_CRCP211_no_signal_to_one_CBSSB1_CRCP211_no_signal_to_one_CBSSB1_CRCP211_no_signal_to_one_CBSSB2+DT_CORP211_L_210 _stuckCBSSB2_CORP211_stuckCB_FAULT_ON_L_PP2209SB_CMRP211_HB1_MSig_2_BusCouplSB_CMRP211_HB2_MSig_2_BusCouplSB_CMRP211_BDP_OOSSB_CMRP211_BDP_OOSN-1_CRCP211_TIMP211SSB2_CORP211_BUSFAULT_stuckCB_L_PP2232SSB2_CORP211_stuckCB_FAULT_ON_L_PP2232SSB2_CORP211_no_signal_to_one_CBSSB2_CORP211_no_signal_to_one_CBSSB2_CORP211_no_signal_to_one_CB

Angle based Instability Impact Index (dt = 10 minutes)Impact value

Con

tinge

ncy

ID

0 0.002 0.004 0.006 0.008 0.01 0.012

N-1_CORP211_CRCP211N-1_CORP211_CRCP211SSB1_PRRP211SSB2_PRRP211N-1_BLLP211_CRCP211N-1_BLLP211_CRCP211N-1_CMRP211_PRRP211N-1_CMRP211_PRRP211N-1_PNAP211_PRRP211N-1_PNAP211_PRRP211N-2_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211N-2_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211N-2_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211N-2_Ln_BLLP211-CRCP211_Ln_CORP211-CRCP211N-2_Ln_BLLP211-CRCP211_Ln_CORP211-CRCP211N-2_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211N-2_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211N-2_Ln_BLLP211-CRCP211_Ln_CORP211-CRCP211N-2_Ln_BLLP211-CRCP211_Ln_CORP211-CRCP211N-1_BLLP211_PRRP211N-1_BLLP211_PRRP211N-1_CMRP211_CRCP211N-1_CMRP211_CRCP211N-2_Ln_CMRP211-CRCP211_CMRP211-CRCP211N-2_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211N-2_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-2_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-2_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-2_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211SSB1_PRRP211_BUSFAULT_stuckCB_L_PP2250SSB2_PRRP211_BUSFAULT_stuckCB_L_PP2251SSB1_PRRP211_BUSFAULT_stuckCB_L_PP2225SSB2_PRRP211_BUSFAULT_stuckCB_L_PP2224SSB1_PRRP211_BUSFAULT_stuckCB_L_PP2223SSB2_PRRP211_BUSFAULT_stuckCB_L_PP2222SSB1_PRRP211_no_signal_to_one_CBSSB1_PRRP211_no_signal_to_one_CBSSB1_PRRP211_no_signal_to_one_CBSSB2_PRRP211_no_signal_to_one_CBSSB2_PRRP211_no_signal_to_one_CBSSB2_PRRP211_no_signal_to_one_CBN-3_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211N-3_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211N-3_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211N-3_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211SSB1_PRRP211_BUSFAULT_MSig_CB_L_PP2250SSB2_PRRP211_BUSFAULT_MSig_CB_L_PP2251N-1_CORP211_SRGP211N-1_CORP211_SRGP211N-2_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211N-3_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CORP211-CRCP211N-3_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CORP211-CRCP211SSB1_PRRP211_BUSFAULT_MSig_CB_L_PP2225SSB2_PRRP211_BUSFAULT_MSig_CB_L_PP2224N-3_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-3_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-3_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-3_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-3_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-3_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-3_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-3_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-3_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-3_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-4_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-4_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-4_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-4_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-4_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-4_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-4_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-4_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211SSB1_PRRP211_BUSFAULT_MSig_CB_L_PP2223SSB2_PRRP211_BUSFAULT_MSig_CB_L_PP2222SB_CRCP211_BDP_OOSSB_CRCP211_BDP_OOSSSB1+DT_PRRP211_L_251 _stuckCBSSB2+DT_PRRP211_L_250 _stuckCBSSB1_PRRP211_stuckCB_FAULT_ON_L_PP2223SSB2_PRRP211_stuckCB_FAULT_ON_L_PP2222SSB1_PRRP211_stuckCB_FAULT_ON_L_PP2225SSB2_PRRP211_stuckCB_FAULT_ON_L_PP2224SSB1_PRRP211_stuckCB_FAULT_ON_L_PP2250SSB2_PRRP211_stuckCB_FAULT_ON_L_PP2251SB_CRCP211_HB2_MSig_2_BusCouplSB_CRCP211_HB1_MSig_2_BusCouplN-3_Ln_BLLP211-CRCP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211N-3_Ln_BLLP211-CRCP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211N-3_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211N-3_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211N-4_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211N-4_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211N-4_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211N-4_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211N-4_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211N-4_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211N-5_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211N-5_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211N-5_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211N-5_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211SB_CRCP211_HB2_stuck_BusCouplSB_CRCP211_HB1_stuck_BusCouplSSB2_CRCP211_BUSFAULT_stuckCB_L_PP2210SSB2_CRCP211_BUSFAULT_MSig_CB_L_PP2210SSB2_CRCP211SSB2_CRCP211_BUSFAULT_stuckCB_T_CRCP211A1SSB2_CRCP211_BUSFAULT_stuckCB_T_CRCP211A3SSB2_CRCP211_BUSFAULT_MSig_CB_T_CRCP211A1SSB2_CRCP211_BUSFAULT_MSig_CB_T_CRCP211A3SSB2_CRCP211_BUSFAULT_stuckCB_L_PP2211SSB2_CRCP211_BUSFAULT_stuckCB_L_PP2248SSB1+DT_CRCP211_L_210 _stuckCBSSB2_CRCP211_no_signal_to_one_CBSSB2_CRCP211_no_signal_to_one_CBSSB2_CRCP211_no_signal_to_one_CBSSB2_CRCP211_no_signal_to_one_CBSSB2_CRCP211_no_signal_to_one_CBSSB2_CRCP211_BUSFAULT_MSig_CB_L_PP2211N-5_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211N-5_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211SSB2_CRCP211_stuckCB_FAULT_ON_L_PP2248N-4_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211SSB2_CRCP211_BUSFAULT_MSig_CB_L_PP2248SSB2_CRCP211_stuckCB_FAULT_ON_T_CRCP211A1SSB2_CRCP211_stuckCB_FAULT_ON_T_CRCP211A3SSB2_CRCP211_stuckCB_FAULT_ON_L_PP2211SSB2+DT_CRCP211_L_249 _stuckCBSSB2_CRCP211_stuckCB_FAULT_ON_L_PP2210SSB2_CMRP211SSB2_CMRP211_BUSFAULT_stuckCB_T_CMRP211A2SSB2_CMRP211_BUSFAULT_MSig_CB_T_CMRP211A2SSB2+DT_CRCP211_L_212 _stuckCBSSB2_CMRP211_BUSFAULT_stuckCB_L_PP2250SSB2_CMRP211_BUSFAULT_stuckCB_L_PP2249SSB1_CORP211_BUSFAULT_stuckCB_T_CORP211A2SSB1_CORP211_BUSFAULT_stuckCB_L_PP2205SSB1_CORP211_BUSFAULT_MSig_CB_T_CORP211A2SSB1_CORP211_BUSFAULT_MSig_CB_L_PP2205SSB1_CORP211SSB2+DT_CRCP211_L_209 _stuckCBSSB2_CMRP211_BUSFAULT_MSig_CB_L_PP2250SSB1_CMRP211SSB1_CMRP211_BUSFAULT_stuckCB_T_CMRP211A1SSB1_CMRP211_BUSFAULT_MSig_CB_T_CMRP211A1SSB1+DT_CORP211_L_209 _stuckCBSSB2_CMRP211_no_signal_to_one_CBSSB2_CMRP211_no_signal_to_one_CBSSB2_CMRP211_no_signal_to_one_CBSSB2+DT_CMRP211_L_248 _stuckCBSSB1_CORP211_BUSFAULT_stuckCB_L_PP2210SSB2_CMRP211_BUSFAULT_MSig_CB_L_PP2249N-6_Ln_BLLP211-CRCP211_Ln_BLLP211-CRCP211_Ln_CMRP211-PRRP211_Ln_CMRP211-PRRP211_Ln_CORP211-CRCP211_Ln_CORP211-CRCP211SSB2+DT_CMRP211_L_251 _stuckCBSSB1_CMRP211_BUSFAULT_stuckCB_L_PP2251SSB2_CMRP211_stuckCB_FAULT_ON_L_PP2249SSB1_CORP211_BUSFAULT_stuckCB_L_PP2231SSB1_CORP211_BUSFAULT_MSig_CB_L_PP2210SSB1_CMRP211_BUSFAULT_stuckCB_L_PP2248SSB2_CMRP211_stuckCB_FAULT_ON_L_PP2250SSB1_CORP211_no_signal_to_one_CBSSB1_CORP211_no_signal_to_one_CBSSB1_CORP211_no_signal_to_one_CBSSB1_CORP211_no_signal_to_one_CBSSB2_CMRP211_stuckCB_FAULT_ON_T_CMRP211A2SSB1_CMRP211_BUSFAULT_MSig_CB_L_PP2251SSB1+DT_CMRP211_L_249 _stuckCBSSB1_CMRP211_no_signal_to_one_CBSSB1_CMRP211_no_signal_to_one_CBSSB1_CMRP211_no_signal_to_one_CBSSB1_CORP211_stuckCB_FAULT_ON_L_PP2231SSB1_CMRP211_BUSFAULT_MSig_CB_L_PP2248SSB1_CMRP211_stuckCB_FAULT_ON_L_PP2248SSB1+DT_CMRP211_L_250 _stuckCBSSB1_CORP211_BUSFAULT_MSig_CB_L_PP2231SSB1_CORP211_stuckCB_FAULT_ON_L_PP2210SSB1_CMRP211_stuckCB_FAULT_ON_L_PP2251SSB1_CMRP211_stuckCB_FAULT_ON_T_CMRP211A1SSB1_CORP211_stuckCB_FAULT_ON_L_PP2205SSB1_CORP211_stuckCB_FAULT_ON_T_CORP211A2SSB1_BLLP211SSB1_BLLP211_BUSFAULT_stuckCB_T_BLLP211A2SSB1_BLLP211_BUSFAULT_MSig_CB_T_BLLP211A2SSB1_BLLP211_BUSFAULT_stuckCB_L_PP2211SSB1_BLLP211_BUSFAULT_stuckCB_L_PP2222SSB1_BLLP211_BUSFAULT_MSig_CB_L_PP2211SSB1_BLLP211_no_signal_to_one_CBSSB1_BLLP211_no_signal_to_one_CBSSB1_BLLP211_no_signal_to_one_CBSSB1_BLLP211_stuckCB_FAULT_ON_L_PP2222SSB1+DT_BLLP211_L_212 _stuckCBSSB1_BLLP211_BUSFAULT_MSig_CB_L_PP2222SSB2_BLLP211SSB2_BLLP211_BUSFAULT_stuckCB_T_BLLP211A3SSB2_BLLP211_BUSFAULT_MSig_CB_T_BLLP211A3SSB1_BLLP211_stuckCB_FAULT_ON_L_PP2211SSB1_BLLP211_stuckCB_FAULT_ON_T_BLLP211A2SSB2_BLLP211_BUSFAULT_stuckCB_L_PP2212SSB2_BLLP211_BUSFAULT_stuckCB_L_PP2223SSB2_BLLP211_BUSFAULT_MSig_CB_L_PP2212SSB2_BLLP211_no_signal_to_one_CBSSB2_BLLP211_no_signal_to_one_CBSSB2_BLLP211_no_signal_to_one_CBSSB2_BLLP211_stuckCB_FAULT_ON_L_PP2223SSB2_BLLP211_BUSFAULT_MSig_CB_L_PP2223SSB2_BLLP211_stuckCB_FAULT_ON_L_PP2212SSB2_BLLP211_stuckCB_FAULT_ON_T_BLLP211A3SSB2+DT_BLLP211_L_211 _stuckCBSSB1_CRCP211SSB1_CRCP211_BUSFAULT_stuckCB_L_PP2226SSB1_CRCP211_BUSFAULT_stuckCB_T_CRCP211A2SSB1_CRCP211_BUSFAULT_MSig_CB_T_CRCP211A2SSB1_CRCP211_BUSFAULT_MSig_CB_L_PP2226SSB1_CRCP211_BUSFAULT_stuckCB_L_PP2209SSB1_CRCP211_no_signal_to_one_CBSSB1_CRCP211_no_signal_to_one_CBSSB1_CRCP211_no_signal_to_one_CBSSB1_CRCP211_no_signal_to_one_CBSSB1_CRCP211_no_signal_to_one_CBSSB1_CRCP211_BUSFAULT_stuckCB_L_PP2249SSB1_CRCP211_BUSFAULT_MSig_CB_L_PP2209SSB1_CRCP211_BUSFAULT_stuckCB_L_PP2212SB_CMRP211_HB1_MSig_2_BusCouplSB_CMRP211_HB2_MSig_2_BusCouplSSB2_CORP211_BUSFAULT_stuckCB_L_PP2204SSB2_CORP211_BUSFAULT_MSig_CB_L_PP2204SSB2_CORP211SSB1_CRCP211_BUSFAULT_MSig_CB_L_PP2249SSB1_CRCP211_BUSFAULT_MSig_CB_L_PP2212SSB2+DT_CORP211_L_210 _stuckCBSB_CMRP211_BDP_OOSSB_CMRP211_BDP_OOSSSB1_CRCP211_stuckCB_FAULT_ON_L_PP2212SSB2_CORP211_BUSFAULT_stuckCB_L_PP2209SSB1_CRCP211_stuckCB_FAULT_ON_L_PP2209SSB1_CRCP211_stuckCB_FAULT_ON_L_PP2249SSB1+DT_CRCP211_L_211 _stuckCBSSB1+DT_CRCP211_L_248 _stuckCBN-1_CORP211_SFMP231SSB2_CORP211_BUSFAULT_stuckCB_L_PP2232SSB2_CORP211_no_signal_to_one_CBSSB2_CORP211_no_signal_to_one_CBSSB2_CORP211_no_signal_to_one_CBSSB2_CORP211_BUSFAULT_MSig_CB_L_PP2209SSB1_CRCP211_stuckCB_FAULT_ON_L_PP2226SSB1_CRCP211_stuckCB_FAULT_ON_T_CRCP211A2SB_CMRP211_HB2_stuck_BusCouplSB_CMRP211_HB1_stuck_BusCouplN-1_CORP211_SFMP221SSB2_CORP211_stuckCB_FAULT_ON_L_PP2232SSB2_CORP211_BUSFAULT_MSig_CB_L_PP2232SSB2_CORP211_stuckCB_FAULT_ON_L_PP2209SSB2_CORP211_stuckCB_FAULT_ON_L_PP2204N-1_CRCP211_TIMP211

Angle based Instability Impact Index (dt = 10 minutes)Impact value

Conti

ngen

cy ID

…Telepiloting OFF

… Telepiloting ON to …

Detect the change in top 10 most severe contingencies passing from …

Page 20: Definition of initiating events including protection misoperation …sites.ieee.org/pes-cascading/files/2016/07/9-Ciapessoni_v2-CFWG... · Definition of initiating events including

Conclusions• Need foramoredetaileddefinitionofinitiatingevents forcascadingdynamic

simulations• ApproachdevelopedbyRSEdefines contingencies fordynamicstudiesstarting

from:– Current root causes acting onthesystem– Substation configuration– Different protection response types

• Each initiatingcontingency is characterisedby threeelements:(1)outagedcomponents,(2)probabilityofoccurrence,(3)timesequenceofprotectioninterventions

• Tool able toidentifymostdangerousmultiplecontingencies– Avoiding combinatorial explosion

• Useful tool toinvestigatemultipleevents reported inNERCstandardTPL001-4.