Rotor DC Current Measurement by Using Current Transformers
Authors:Z. Gajić, ABB SwedenD. Trišić, Drinsko-Limske HE, SerbiaS.Roxenborg, ABB Sweden
Presented by Roger Hedding
![Page 2: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/2.jpg)
Objectives
Information about typical excitation systems
Static excitation What is the role of an excitation
system New measurement principle for
rotor DC current Information about the trial
installation Show some captured recordings DC current use for the protection Conclusions
![Page 3: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/3.jpg)
Power Station
CONTROL ROOM
CONTROL SYSTEMS
STEP UP TRANSFORMER
HV SYSTEM
STARPOINTCUBICLE
HV- SUBSTATION
TURBINEGOVERNOR
STATIC STARTER
SYNCHRONIZATION
1
1
Power Island
GEXCITATIONTRANS-FORMERTURBINE
MV SWITCHGEAR
PT’sCT’sSA’s
AUXILIARYTRANS-FORMER
MVDRIVES
LV SWITCHGEAR
EXCITATION SYSTEM
UNITPROTECTION
![Page 4: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/4.jpg)
Two main types of excitation system
![Page 5: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/5.jpg)
AVR
Regulation & Control Electronics
Excitation transformer
Converter
De-excitation
DC-breaker*
Field flashing
AC-breaker*
*AC- or DC breaker
Main Components Static Excitation Systems
![Page 6: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/6.jpg)
Static Excitation System “Inside View”
ULVPh-Ph
![Page 7: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/7.jpg)
Thyristor Controlled Rectifier
Note that phases are marked with letters R, S, T instead of A, B, C
![Page 8: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/8.jpg)
Static excitation System
AVR
Excitation Transformer
Converter
ACCB
PT
CTController
Field Discharge
Provide variable DC current with short time overload capability
Control terminal voltage with suitable accuracy
Ensure stable operation with network and / or other machines
Contribute to transient stability subsequent to a fault
Communicate with the power plant control system
Keep machine within allowed operating range on P-Q diagram
![Page 9: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/9.jpg)
HPP Bajina Bašta (Low Lake)
![Page 10: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/10.jpg)
View of RHE from the dam
![Page 11: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/11.jpg)
HPP Bajina Bašta (Upper Lake)
![Page 12: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/12.jpg)
Overall Single Line Diagram of the Plant
315MVA11kV
100MVA15,75kV
0,2km 220kV OHL
Hydro Power Plant
220kV S/S Zaugline
8km, 220kV OHL (4 off)
![Page 13: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/13.jpg)
Generator/Pump Unit Data
Turbine Francis 428.6rpm
Synchronous Machine 315MW pf=0.95 11kV; 50Hz
Unit Transformer 2*160MVA 242kV/11kV Yd5
![Page 14: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/14.jpg)
Special Things about this Installation
Operating Modes Generator Motor (Pump) Electrical braking Synchronous start
(i.e. Back-to-Back)
![Page 15: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/15.jpg)
Single Line Diagram of Machine Used in Trial Installation
![Page 16: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/16.jpg)
Excitation System Three-Line-Diagram
![Page 17: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/17.jpg)
Traditional Possibilities to measure DC current
Resistive Shunt Hall-effect sensor
Typically not possible to be used by the numerical protection relays
Primary connections
Connections to transducer
![Page 18: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/18.jpg)
Required CT Connections for DC Current Measurement
100/5
1500/5
1400kVA11kV/0,55kV
Yd1
![Page 19: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/19.jpg)
How the DC Current is Calculated ?
When HV CTs are used: IA, IB, IC are measured By using properties of
excitation transformer re-calculate Ia, Ib, Ic first
Then use formulas to the right
When LV CTs are used: Ia, Ib, Ic are measured Calculate instantaneous
DC current by using the following formula:
Calculate equivalent RMS value of the DC current by using the following formula:
![Page 20: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/20.jpg)
Recordings from the Trial Installation
100/5
1500/5
1400kVA11kV/0,55kV
Yd1
IR_HV, IS_HV, IT_HV
IR_LV, IS_LV, IT_LV
HV_DC_I
LV_DC_I
R, S, T <=> A, B, C
![Page 21: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/21.jpg)
Filed Record No 1
![Page 22: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/22.jpg)
Filed Record No 2
![Page 23: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/23.jpg)
Filed Record No 3
![Page 24: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/24.jpg)
Filed Record No 4
![Page 25: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/25.jpg)
Filed Record No 5
![Page 26: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/26.jpg)
DC Current Value on the built-in HMI, via Comms, etc.
![Page 27: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/27.jpg)
Conclusion
Patented DC current measurement in the numerical IED will improve the synchronous generator protection and monitoring.
Current based protection for the rotor winding can be done in an easy way (e.g. thermal overload).
Possible to record and monitor the rotor winding DC current together with Stator U and I in the same COMTRADE file!
![Page 28: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/28.jpg)
Practical Advise
When more than one power source is used for the excitation equipment supply, use the CT located just in front of the six-pulse rectifier bridge in order to measure DC current under all operating conditions of the machine
5
2
3
6
4
1
7
89
220kV Transmission Network
![Page 29: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/29.jpg)
Questions
![Page 30: DC Current Measurement](https://reader035.vdocuments.us/reader035/viewer/2022062218/5695d42b1a28ab9b02a08866/html5/thumbnails/30.jpg)
Recording from Another Machine
8 10 12 1440-
20-
0
20
40 IAIBIC
W1 Current Waveforms
Time [cycles]
Cur
rent
[Am
ps P
rimar
y]
8 10 12 14
200
400
600
800HV_side
DC Current Integrated Value
Time [cycles]
DC
Cur
rent
[Am
pere
s]