VRF Air Conditioning System

8HP / 10HP

22.4kW / 28kW

3.5HP / 4HP

5HP / 6HPR410A

Condition:

Model Cooling Only FVI-T032CA-A21N FVI-T036CA-A21N FVI-T040CA-A21N FVI-T045CA-A21N FVI-T050CA-A21N

Cool / Heat FVI-T032HA-A21N FVI-T036HA-A21N FVI-T040HA-A21N FVI-T045HA-A21N FVI-T050HA-A21N

FUJIAIRE (M) SDN. BHD.

Model Cooling Only FVI-T008CB-A21N FVI-T010CB-A21N FVI-T013CB-A21N FVI-T016CB-A21N

Cool / Heat FVI-T008HB-A21N FVI-T010HB-A21N FVI-T013HB-A21N FVI-T016HB-A21N

Model Cooling Only FVI-E010CA-A21N FVI-E013CA-A21N FVI-E018CA-A21N FVI-E025CA-A21N FVI-E032CA-A21N FVI-E040CA-A21N FVI-E045CA-A21N

Cool / Heat FVI-E010HA-A21N FVI-E013HA-A21N FVI-E018HA-A21N FVI-E025HA-A21N FVI-E032HA-A21N FVI-E040HA-A21N FVI-E045HA-A21N

Model Cooling Only FVI-C008CA-A21N FVI-C010CA-A21N FVI-C013CA-A21N FVI-C016CA-A21N FVI-C020CA-A21N FVI-C025CA-A21N

Cool / Heat FVI-C008HA-A21N FVI-C010HA-A21N FVI-C013HA-A21N FVI-C016HA-A21N FVI-C020HA-A21N FVI-C025HA-A21N

Model Cooling Only FVI-D008CA-A21N FVI-D010CA-A21N FVI-D013CA-A21N FVI-D016CA-A21N FVI-D020CA-A21N FVI-D025CA-A21N FVI-D032CA-A21N FVI-D040CA-A21N FVI-D050CA-A21N

Cool / Heat FVI-D008HA-A21N FVI-D010HA-A21N FVI-D013HA-A21N FVI-D016HA-A21N FVI-D020HA-A21N FVI-D025HA-A21N FVI-D032HA-A21N FVI-D040HA-A21N FVI-D050HA-A21N

Model FVI-D080CA-E21N

FVI-D080HA-E21N

FVI-D100CA-E21N

FVI-D100HA-E21N

Model FVI-L080A-E21G FVI-L100A-E21G FVI-L120A-E21G FVI-L140A-E21G FVI-L160A-E21G

Model Cooling Only FVI-W008CA-A21N FVI-W010CA-A21N FVI-W013CA-A21N FVI-W016CA-A21N FVI-W018CA-A21N FVI-W020CA-A21N FVI-W022CA-A21N FVI-W025CA-A21N

Cool / Heat FVI-W008HA-A21N FVI-W010HA-A21N FVI-W013HA-A21N FVI-W016HA-A21N FVI-W018HA-A21N FVI-W020HA-A21N FVI-W022HA-A21N FVI-W025HA-A21N

Model Cooling Only FVI-T010CA-A21N FVI-T013CA-A21N FVI-T016CA-A21N FVI-T018CA-A21N FVI-T020CA-A21N FVI-T022CA-A21N FVI-T025CA-A21N FVI-T028CA-A21N

Cool / Heat FVI-T010HA-A21N FVI-T013HA-A21N FVI-T016HA-A21N FVI-T018HA-A21N FVI-T020HA-A21N FVI-T022HA-A21N FVI-T025HA-A21N FVI-T028HA-A21N

12HP / 14HP / 16HP

33.5kW / 40kW / 45kW

REMOTE CONTROL

FUJIAIRE DC INVERTER TECHNOLOGY SAVES ENERGY BY 40%WITH PROVIDING OPTIMUM COMFORT

Comparison ofPower Consumption

High efficiency is realized by the use of DC Inverter Hermetic Scroll Compressors with high pressure chamber design and improved DC Inverter driving technology, and large heat exchanger.

Note:

The unit can operate in wide range, greatly reducing the ambient temperature limitation.Note:

cooling range may be up to -5 C.

loading changes of indoor environment, continually adjusts the flow rate of the refrigerant.

Meanwhile, the outdoor unit with DC Inverter compressor provides the capacity with certain amount of refrigerant exactly according to the total demands of indoor units.

fluctuation that occurs with a conventional ON/OFF control system.

Quiet operation Quiet operation during night time

Intelligently adjustment of outdoor fan control can reduce the operation noise up to 8dB(A) during night time and it can be lowered to 50dB(A)

2.0

3.0

3.5

4.04.07EER

COP4.37

structure can raise the high

and middle

performance NewDC motor

raises the low

performance

the DC Inverter Scroll Compressor can save up to 40% of energy consumption in a year.

concentrated winding.

technology, the DC Inverter compressor achieves stepless output regulation between 20Hz – 120Hz.

20 40 60 80 100

Com

pres

sor e

ffici

ency

7%

Distributed winding Concentrated winding

40%SAVINGS

Intelligent Defrost Technology

reliability

system pressure is too low, that can obviously lengthen the time gap between two defrost operations, hence reduce the time of defrosting.

75% with highly comfortable heating operation

High Efficiency Compressor

Heating

Defrosting starts if frost isdetected by the unit

Defrosting stopsafter completion

Hea

ting

Cap

acity

Defrosting

Time

270C

-200C

480C

-100C

HEATING COOLING

High Efficiency Oil-balanced TechnologyHigh pressure chamber compressor with

oil-balanced pipe can automatically drain out the excess oil which can prevent oil-unbalance between the compressors.

New patented oil separator allows the oil separating efficiency up to 99%.

outside of the modules allows high reliability.

Before Oil-balanced After Oil-balanced

EFFICIENT High EER/COP Rating

VERSATILE

MODEL FVI-L035A-A21G

3.5

10

FVI-L040A-A21G

4.0

12

FVI-L050A-A21G

5.0

14

FVI-L060A-A21G

6.0

16

High Static Pressure of Outdoor Fan

The outdoor unit can be installed in the

re-selection is necessary.

Modular Outdoor Unit Design8HP 64HP with 2HP

increments

Maximum capacity of outdoor unit is 64HP

Note:This value is based on the outdoor unit is located above the indoor unit.If the outdoor unit is located underneath the indoor unit, the value is 25m.

Flexible designLong piping design

– 150m– 70m

– 80m

indoor units – 10m

outdoor and indoor unit – 30m*

branch and the farthest indoor unit – 25m

FVI Mini

Floor area: 0.323m!

Note:This value is based on the outdoor unit which is located above the indoor unit.If the outdoor unit is located underneath the indoor unit, the value is 40m.

Long Piping DesignMaximum total piping length – 500mMaximum actual piping length – 150m

– 175mMaximum height difference between

indoor units – 15mMaximum height difference between

outdoor and indoor unit – 50m*Maximum piping length from first indoor

branch to the farthest indoor unit – 40m

No Module(s) Capacity Model Description Outdoor Max. Connection

HP kW Indoor Unit Combination (HP)

Model FVI-L035A-A21G FVI-L040A-A21G FVI-L050A-A21G FVI-L060A-A21G

12 HoursRotation

12 HoursRotation

12 HoursRotation

12 HoursRotation

Suction pipe

Discharge pipe

Auto-oil pipe

Compressors

Oil storage tanks

Oil equalizing pipe Oil equalizing pipe

Compact Design

Easy Installation

50m

Note:From the standard model that 4 modules connect in parallel, up to 64

connected, please contact us.

Various Combination110

12 types and 69 modelsMaximum diversity is 135%

Emergency OperationEach module is an independent sub-system, and the

of any one of the modules emergency operation can be performed after simple manual set up on the outdoor

modules will be changed without restart when the system accumulatively operates for 12 hours whichcan maximize the service life of the system.

RELIABLEModular Operating

1250mm

950mm340mm

COMFORTComfortable Precise Temperature Control

Wide Operation Range

Capacity

FUJIAIRE DC INVERTER TECHNOLOGY SAVES ENERGY BY 40%WITH PROVIDING OPTIMUM COMFORT

Comparison ofPower Consumption

High efficiency is realized by the use of DC Inverter Hermetic Scroll Compressors with high pressure chamber design and improved DC Inverter driving technology, and large heat exchanger.

Note:

The unit can operate in wide range, greatly reducing the ambient temperature limitation.Note:

cooling range may be up to -5 C.

loading changes of indoor environment, continually adjusts the flow rate of the refrigerant.

Meanwhile, the outdoor unit with DC Inverter compressor provides the capacity with certain amount of refrigerant exactly according to the total demands of indoor units.

fluctuation that occurs with a conventional ON/OFF control system.

Quiet operation Quiet operation during night time

Intelligently adjustment of outdoor fan control can reduce the operation noise up to 8dB(A) during night time and it can be lowered to 50dB(A)

2.0

3.0

3.5

4.04.07EER

COP4.37

structure can raise the high

and middle

performance NewDC motor

raises the low

performance

the DC Inverter Scroll Compressor can save up to 40% of energy consumption in a year.

concentrated winding.

technology, the DC Inverter compressor achieves stepless output regulation between 20Hz – 120Hz.

20 40 60 80 100

Com

pres

sor e

ffici

ency

7%

Distributed winding Concentrated winding

40%SAVINGS

Intelligent Defrost Technology

reliability

system pressure is too low, that can obviously lengthen the time gap between two defrost operations, hence reduce the time of defrosting.

75% with highly comfortable heating operation

High Efficiency Compressor

Heating

Defrosting starts if frost isdetected by the unit

Defrosting stopsafter completion

Hea

ting

Cap

acity

Defrosting

Time

270C

-200C

480C

-100C

HEATING COOLING

High Efficiency Oil-balanced TechnologyHigh pressure chamber compressor with

oil-balanced pipe can automatically drain out the excess oil which can prevent oil-unbalance between the compressors.

New patented oil separator allows the oil separating efficiency up to 99%.

outside of the modules allows high reliability.

Before Oil-balanced After Oil-balanced

EFFICIENT High EER/COP Rating

VERSATILE

MODEL FVI-L035A-A21G

3.5

10

FVI-L040A-A21G

4.0

12

FVI-L050A-A21G

5.0

14

FVI-L060A-A21G

6.0

16

High Static Pressure of Outdoor Fan

The outdoor unit can be installed in the

re-selection is necessary.

Modular Outdoor Unit Design8HP 64HP with 2HP

increments

Maximum capacity of outdoor unit is 64HP

Note:This value is based on the outdoor unit is located above the indoor unit.If the outdoor unit is located underneath the indoor unit, the value is 25m.

Flexible designLong piping design

– 150m– 70m

– 80m

indoor units – 10m

outdoor and indoor unit – 30m*

branch and the farthest indoor unit – 25m

FVI Mini

Floor area: 0.323m!

Note:This value is based on the outdoor unit which is located above the indoor unit.If the outdoor unit is located underneath the indoor unit, the value is 40m.

Long Piping DesignMaximum total piping length – 500mMaximum actual piping length – 150m

– 175mMaximum height difference between

indoor units – 15mMaximum height difference between

outdoor and indoor unit – 50m*Maximum piping length from first indoor

branch to the farthest indoor unit – 40m

No Module(s) Capacity Model Description Outdoor Max. Connection

HP kW Indoor Unit Combination (HP)

Model FVI-L035A-A21G FVI-L040A-A21G FVI-L050A-A21G FVI-L060A-A21G

12 HoursRotation

12 HoursRotation

12 HoursRotation

12 HoursRotation

Suction pipe

Discharge pipe

Auto-oil pipe

Compressors

Oil storage tanks

Oil equalizing pipe Oil equalizing pipe

Compact Design

Easy Installation

50m

Note:From the standard model that 4 modules connect in parallel, up to 64

connected, please contact us.

Various Combination110

12 types and 69 modelsMaximum diversity is 135%

Emergency OperationEach module is an independent sub-system, and the

of any one of the modules emergency operation can be performed after simple manual set up on the outdoor

modules will be changed without restart when the system accumulatively operates for 12 hours whichcan maximize the service life of the system.

RELIABLEModular Operating

1250mm

950mm340mm

COMFORTComfortable Precise Temperature Control

Wide Operation Range

Capacity

FUJIAIRE DC INVERTER TECHNOLOGY SAVES ENERGY BY 40%WITH PROVIDING OPTIMUM COMFORT

Comparison ofPower Consumption

High efficiency is realized by the use of DC Inverter Hermetic Scroll Compressors with high pressure chamber design and improved DC Inverter driving technology, and large heat exchanger.

Note:

The unit can operate in wide range, greatly reducing the ambient temperature limitation.Note:

cooling range may be up to -5 C.

loading changes of indoor environment, continually adjusts the flow rate of the refrigerant.

Meanwhile, the outdoor unit with DC Inverter compressor provides the capacity with certain amount of refrigerant exactly according to the total demands of indoor units.

fluctuation that occurs with a conventional ON/OFF control system.

Quiet operation Quiet operation during night time

Intelligently adjustment of outdoor fan control can reduce the operation noise up to 8dB(A) during night time and it can be lowered to 50dB(A)

2.0

3.0

3.5

4.04.07EER

COP4.37

structure can raise the high

and middle

performance NewDC motor

raises the low

performance

the DC Inverter Scroll Compressor can save up to 40% of energy consumption in a year.

concentrated winding.

technology, the DC Inverter compressor achieves stepless output regulation between 20Hz – 120Hz.

20 40 60 80 100

Com

pres

sor e

ffici

ency

7%

Distributed winding Concentrated winding

40%SAVINGS

Intelligent Defrost Technology

reliability

system pressure is too low, that can obviously lengthen the time gap between two defrost operations, hence reduce the time of defrosting.

75% with highly comfortable heating operation

High Efficiency Compressor

Heating

Defrosting starts if frost isdetected by the unit

Defrosting stopsafter completion

Hea

ting

Cap

acity

Defrosting

Time

270C

-200C

480C

-100C

HEATING COOLING

High Efficiency Oil-balanced TechnologyHigh pressure chamber compressor with

oil-balanced pipe can automatically drain out the excess oil which can prevent oil-unbalance between the compressors.

New patented oil separator allows the oil separating efficiency up to 99%.

outside of the modules allows high reliability.

Before Oil-balanced After Oil-balanced

EFFICIENT High EER/COP Rating

VERSATILE

MODEL FVI-L035A-A21G

3.5

10

FVI-L040A-A21G

4.0

12

FVI-L050A-A21G

5.0

14

FVI-L060A-A21G

6.0

16

High Static Pressure of Outdoor Fan

The outdoor unit can be installed in the

re-selection is necessary.

Modular Outdoor Unit Design8HP 64HP with 2HP

increments

Maximum capacity of outdoor unit is 64HP

Note:This value is based on the outdoor unit is located above the indoor unit.If the outdoor unit is located underneath the indoor unit, the value is 25m.

Flexible designLong piping design

– 150m– 70m

– 80m

indoor units – 10m

outdoor and indoor unit – 30m*

branch and the farthest indoor unit – 25m

FVI Mini

Floor area: 0.323m!

Note:This value is based on the outdoor unit which is located above the indoor unit.If the outdoor unit is located underneath the indoor unit, the value is 40m.

Long Piping DesignMaximum total piping length – 500mMaximum actual piping length – 150m

– 175mMaximum height difference between

indoor units – 15mMaximum height difference between

outdoor and indoor unit – 50m*Maximum piping length from first indoor

branch to the farthest indoor unit – 40m

No Module(s) Capacity Model Description Outdoor Max. Connection

HP kW Indoor Unit Combination (HP)

Model FVI-L035A-A21G FVI-L040A-A21G FVI-L050A-A21G FVI-L060A-A21G

12 HoursRotation

12 HoursRotation

12 HoursRotation

12 HoursRotation

Suction pipe

Discharge pipe

Auto-oil pipe

Compressors

Oil storage tanks

Oil equalizing pipe Oil equalizing pipe

Compact Design

Easy Installation

50m

Note:From the standard model that 4 modules connect in parallel, up to 64

connected, please contact us.

Various Combination110

12 types and 69 modelsMaximum diversity is 135%

Emergency OperationEach module is an independent sub-system, and the

of any one of the modules emergency operation can be performed after simple manual set up on the outdoor

modules will be changed without restart when the system accumulatively operates for 12 hours whichcan maximize the service life of the system.

RELIABLEModular Operating

1250mm

950mm340mm

COMFORTComfortable Precise Temperature Control

Wide Operation Range

Capacity

VRF Air Conditioning System

8HP / 10HP

22.4kW / 28kW

3.5HP / 4HP

5HP / 6HPR410A

Condition:

Model Cooling Only FVI-T032CA-A21N FVI-T036CA-A21N FVI-T040CA-A21N FVI-T045CA-A21N FVI-T050CA-A21N

Cool / Heat FVI-T032HA-A21N FVI-T036HA-A21N FVI-T040HA-A21N FVI-T045HA-A21N FVI-T050HA-A21N

FUJIAIRE (M) SDN. BHD.

Model Cooling Only FVI-T008CB-A21N FVI-T010CB-A21N FVI-T013CB-A21N FVI-T016CB-A21N Cool / Heat FVI-T008HB-A21N FVI-T010HB-A21N FVI-T013HB-A21N FVI-T016HB-A21N

Model Cooling Only FVI-E010CA-A21N FVI-E013CA-A21N FVI-E018CA-A21N FVI-E025CA-A21N FVI-E032CA-A21N FVI-E040CA-A21N FVI-E045CA-A21N Cool / Heat FVI-E010HA-A21N FVI-E013HA-A21N FVI-E018HA-A21N FVI-E025HA-A21N FVI-E032HA-A21N FVI-E040HA-A21N FVI-E045HA-A21N

Model Cooling Only FVI-C008CA-A21N FVI-C010CA-A21N FVI-C013CA-A21N FVI-C016CA-A21N FVI-C020CA-A21N FVI-C025CA-A21N Cool / Heat FVI-C008HA-A21N FVI-C010HA-A21N FVI-C013HA-A21N FVI-C016HA-A21N FVI-C020HA-A21N FVI-C025HA-A21N

Model Cooling Only FVI-D008CA-A21N FVI-D010CA-A21N FVI-D013CA-A21N FVI-D016CA-A21N FVI-D020CA-A21N FVI-D025CA-A21N FVI-D032CA-A21N FVI-D040CA-A21N FVI-D050CA-A21N Cool / Heat FVI-D008HA-A21N FVI-D010HA-A21N FVI-D013HA-A21N FVI-D016HA-A21N FVI-D020HA-A21N FVI-D025HA-A21N FVI-D032HA-A21N FVI-D040HA-A21N FVI-D050HA-A21N

Model Cooling Only FVI-D080CA-E21N FVI-D100CA-E21N Cool / Heat FVI-D080HA-E21N FVI-D100HA-E21N

t

Model FVI-L080A-E21G FVI-L100A-E21G FVI-L120A-E21G FVI-L140A-E21G FVI-L160A-E21G

Model Cooling Only FVI-T010CA-A21N FVI-T013CA-A21N FVI-T016CA-A21N FVI-T018CA-A21N FVI-T020CA-A21N FVI-T022CA-A21N FVI-T025CA-A21N FVI-T028CA-A21N

Cool / Heat FVI-T010HA-A21N FVI-T013HA-A21N FVI-T016HA-A21N FVI-T018HA-A21N FVI-T020HA-A21N FVI-T022HA-A21N FVI-T025HA-A21N FVI-T028HA-A21N

12HP / 14HP / 16HP

33.5kW / 40kW / 45kW

REMOTE CONTROLLER

Model Cooling Only FVI-W008CA-A21N FVI-W010CA-A21N FVI-W013CA-A21N FVI-W016CA-A21N FVI-W018CA-A21N FVI-W020CA-A21N FVI-W022CA-A21N FVI-W025CA-A21N

Cool / Heat FVI-W008HA-A21N FVI-W010HA-A21N FVI-W013HA-A21N FVI-W016HA-A21N FVI-W018HA-A21N FVI-W020HA-A21N FVI-W022HA-A21N FVI-W025HA-A21N

VRF Air Conditioning System

8HP / 10HP

22.4kW / 28kW

3.5HP / 4HP

5HP / 6HPR410A

Condition:

Model Cooling Only FVI-T032CA-A21N FVI-T036CA-A21N FVI-T040CA-A21N FVI-T045CA-A21N FVI-T050CA-A21N

Cool / Heat FVI-T032HA-A21N FVI-T036HA-A21N FVI-T040HA-A21N FVI-T045HA-A21N FVI-T050HA-A21N

FUJIAIRE (M) SDN. BHD.

Model Cooling Only FVI-T008CB-A21N FVI-T010CB-A21N FVI-T013CB-A21N FVI-T016CB-A21N Cool / Heat FVI-T008HB-A21N FVI-T010HB-A21N FVI-T013HB-A21N FVI-T016HB-A21N

Model Cooling Only FVI-E010CA-A21N FVI-E013CA-A21N FVI-E018CA-A21N FVI-E025CA-A21N FVI-E032CA-A21N FVI-E040CA-A21N FVI-E045CA-A21N Cool / Heat FVI-E010HA-A21N FVI-E013HA-A21N FVI-E018HA-A21N FVI-E025HA-A21N FVI-E032HA-A21N FVI-E040HA-A21N FVI-E045HA-A21N

Model Cooling Only FVI-C008CA-A21N FVI-C010CA-A21N FVI-C013CA-A21N FVI-C016CA-A21N FVI-C020CA-A21N FVI-C025CA-A21N Cool / Heat FVI-C008HA-A21N FVI-C010HA-A21N FVI-C013HA-A21N FVI-C016HA-A21N FVI-C020HA-A21N FVI-C025HA-A21N

Model Cooling Only FVI-D008CA-A21N FVI-D010CA-A21N FVI-D013CA-A21N FVI-D016CA-A21N FVI-D020CA-A21N FVI-D025CA-A21N FVI-D032CA-A21N FVI-D040CA-A21N FVI-D050CA-A21N Cool / Heat FVI-D008HA-A21N FVI-D010HA-A21N FVI-D013HA-A21N FVI-D016HA-A21N FVI-D020HA-A21N FVI-D025HA-A21N FVI-D032HA-A21N FVI-D040HA-A21N FVI-D050HA-A21N

Model Cooling Only FVI-D080CA-E21N FVI-D100CA-E21N Cool / Heat FVI-D080HA-E21N FVI-D100HA-E21N

t

Model FVI-L080A-E21G FVI-L100A-E21G FVI-L120A-E21G FVI-L140A-E21G FVI-L160A-E21G

Model Cooling Only FVI-T010CA-A21N FVI-T013CA-A21N FVI-T016CA-A21N FVI-T018CA-A21N FVI-T020CA-A21N FVI-T022CA-A21N FVI-T025CA-A21N FVI-T028CA-A21N

Cool / Heat FVI-T010HA-A21N FVI-T013HA-A21N FVI-T016HA-A21N FVI-T018HA-A21N FVI-T020HA-A21N FVI-T022HA-A21N FVI-T025HA-A21N FVI-T028HA-A21N

12HP / 14HP / 16HP

33.5kW / 40kW / 45kW

REMOTE CONTROLLER

Model Cooling Only FVI-W008CA-A21N FVI-W010CA-A21N FVI-W013CA-A21N FVI-W016CA-A21N FVI-W018CA-A21N FVI-W020CA-A21N FVI-W022CA-A21N FVI-W025CA-A21N

Cool / Heat FVI-W008HA-A21N FVI-W010HA-A21N FVI-W013HA-A21N FVI-W016HA-A21N FVI-W018HA-A21N FVI-W020HA-A21N FVI-W022HA-A21N FVI-W025HA-A21N