The complete control of technology is one of the pillars of MHI. KXZ models with VRF-T technology are an example: high-performance systems thanks to operating flexibility, high energy efficiency and easy installation.
Centralised management makes it possible to reduce electricity costs, thus saving in comparison with traditional systems.
KXZ can meet the needs of an increasing number of applications in the commercial and industrial sectors.
VRF MULTI SYSTEMS
81
NEW
Line-up outdoor units 82
In heat pump KXZ SYSTEM 86
KXZ MICRO COMPACT series 100
KXE6 MICRO LARGE CONNECTION series 102
KXZP MICRO SMART series 104
KXZ ADVANCED series 106
KXZX Hi-COP series 114
Heat recovery KXZ SYSTEM 118
KXZR 3-PIPE series 124
KXZRX Hi-COP series 130
Line-up indoor units 137
Indoor units 138
Post-treatment modular unit 166
EEV-KIT 168
Water cooled KXZW WATER series 132
VRF Multi systems
82
KXZ MICRO COMPACT
KXZP MICRO SMART
KXZ ADVANCED
KXZX Hi-COP
KXE6 MICRO LARGE CONNECTION
NEW
OUTDOOR HEAT PUMP UNITS
11.20 kW 14.00 kW 15.50 kW4HP 5HP 6HP
FDC112KXZEN1 FDC140KXZEN1 FDC155KXZEN1FDC112KXZES1 FDC140KXZES1 FDC155KXZES1
22.40 kW 28.00 kW 33.50 kW8HP 10HP 12HP
FDC224KXE6 FDC280KXE6 FDC335KXE6
22.40 kW 28.00 kW8HP 10HP
FDC224KXZPE1 FDC280KXZPE1
28.00 kW 33.50 kW 40.00 kW 45.00 kW 47.50 kW 50.00 kW 56.00 kW10HP 12HP 14HP 16HP 17HP 18HP 20HP
FDC280KXZE1 FDC335KXZE1 FDC400KXZE1 FDC450KXZE1 FDC475KXZE1 FDC500KXZE1 FDC560KXZE1
61.50 kW 67.00 kW 73.50 kW 80.00 kW 85.00 kW 90.00 kW 95.00 kW 100.00 kW 106.00 kW 112.00 kW22HP 24HP 26HP 28HP 30HP 32HP 34HP 36HP 38HP 40HP
FDC615KXZE1 FDC670KXZE1 FDC735KXZE1 FDC800KXZE1 FDC850KXZE1 FDC900KXZE1 FDC950KXZE1 FDC1000KXZE1 FDC1060KXZE1 FDC1120KXZE110+12 12+12 12+14 14+14 14+16 16+16 17+17 18+18 18+20 20+20
FDC280KXZE1FDC335KXZE1
FDC335KXZE1 FDC335KXZE1
FDC335KXZE1 FDC400KXZE1
FDC400KXZE1 FDC400KXZE1
FDC400KXZE1 FDC450KXZE1
FDC450KXZE1 FDC450KXZE1
FDC475KXZE1 FDC475KXZE1
FDC500KXZE1 FDC500KXZE1
FDC500KXZE1 FDC560KXZE1
FDC560KXZE1 FDC560KXZE1
120.00 kW 125.00 kW 130.00 kW 135.00 kW 142.50 kW 145.00 kW 150.00 kW 156.00 kW 162.00 kW 168.00 kW42HP 44HP 46HP 48HP 50HP 52HP 54HP 56HP 58HP 60HP
FDC1200KXZE1 FDC1250KXZE1 FDC1300KXZE1 FDC1350KXZE1 FDC1425KXZE1 FDC1450KXZE1 FDC1500KXZE1 FDC1560KXZE1 FDC1620KXZE1 FDC1680KXZE114+14+14 14+14+16 14+16+16 16+16+16 17+17+17 17+17+18 18+18+18 18+18+20 18+20+20 20+20+20
FDC400KXZE1 FDC400KXZE1 FDC400KXZE1
FDC400KXZE1 FDC400KXZE1 FDC450KXZE1
FDC400KXZE1 FDC450KXZE1 FDC450KXZE1
FDC450KXZE1 FDC450KXZE1 FDC450KXZE1
FDC475KXZE1 FDC475KXZE1 FDC475KXZE1
FDC475KXZE1 FDC475KXZE1 FDC500KXZE1
FDC500KXZE1 FDC500KXZE1 FDC500KXZE1
FDC500KXZE1 FDC500KXZE1 FDC560KXZE1
FDC500KXZE1 FDC560KXZE1 FDC560KXZE1
FDC560KXZE1 FDC560KXZE1 FDC560KXZE1
22.40 kW 28.00 kW 33.50 kW8HP 10HP 12HP
FDC224KXZXE1 FDC280KXZXE1 FDC335KXZXE1
45.00 kW 50.00 kW 56.00 kW 61.50 kW 67.00 kW16HP 18HP 20HP 22HP 24HP
FDC450KXZXE1 FDC500KXZXE1 FDC560KXZXE1 FDC615KXZXE1 FDC670KXZXE18+8 8+10 10+10 10+12 12+12
FDC224KXZXE1FDC224KXZXE1
FDC224KXZXE1FDC280KXZXE1
FDC280KXZXE1FDC280KXZXE1
FDC280KXZXE1FDC335KXZXE1
FDC335KXZXE1FDC335KXZXE1
73.50 kW 80.00 kW 85.00 kW 90.00 kW 95.00 kW 100.00 kW26HP 28HP 30HP 32HP 34HP 36HP
FDC735KXZXE1 FDC800KXZXE1 FDC850KXZXE1 FDC900KXZXE1 FDC950KXZXE1 FDC1000KXZXE18+8+10 8+10+10 10+10+10 10+10+12 10+12+12 12+12+12
FDC224KXZXE1FDC224KXZXE1FDC280KXZXE1
FDC224KXZXE1FDC280KXZXE1FDC280KXZXE1
FDC280KXZXE1FDC280KXZXE1FDC280KXZXE1
FDC280KXZXE1FDC280KXZXE1FDC335KXZXE1
FDC280KXZXE1FDC335KXZXE1FDC335KXZXE1
FDC335KXZXE1FDC335KXZXE1FDC335KXZXE1
VRF Multi systems
83
KXZRX Hi-COP
KXZR 3-PIPE
KXZW WATER
NEW
NEW
OUTDOOR HEAT RECOVERY UNITS
22.40 kW 28.00 kW 33.50 kW8HP 10HP 12HP
FDC224KXZRE1 FDC280KXZRE1 FDC335KXZRE1
40.00 kW 45.00 kW 47.50 kW 50.00 kW 56.00 kW 61.50 kW 67.00 kW14HP 16HP 17HP 18HP 20HP 22HP 24HP
FDC400KXZRE1 FDC450KXZRE1 FDC475KXZRE1 FDC500KXZRE1 FDC560KXZRE1 FDC615KXZRE1 FDC670KXZRE1
73.50 kW 80.00 kW 85.50 kW 90.00 kW 95.00 kW 100.00 kW 106.00 kW 112.00 kW26HP 28HP 30HP 32HP 34HP 36HP 38HP 40HP
FDC735KXZRE1 FDC800KXZRE1 FDC850KXZRE1 FDC900KXZRE1 FDC950KXZRE1 FDC1000KXZRE1 FDC1060KXZRE1 FDC1120KXZRE112+14 14+14 14+16 16+16 17+17 18+18 18+20 20+20
FDC335KXZXRE1FDC400KXZXRE1
FDC400KXZXRE1FDC400KXZXRE1
FDC400KXZXRE1FDC450KXZXRE1
FDC450KXZXRE1FDC450KXZXRE1
FDC475KXZXRE1FDC475KXZXRE1
FDC500KXZXRE1FDC500KXZXRE1
FDC500KXZXRE1FDC560KXZXRE1
FDC560KXZXRE1FDC560KXZXRE1
45.00 kW 50.00 kW 56.00 kW 61.50 kW 67.00 kW16HP 18HP 20HP 22HP 24HP
FDC450KXZRXE1 FDC500KXZRXE1 FDC560KXZRXE1 FDC615KXZRXE1 FDC670KXZRXE18+8 8+10 10+10 10+12 12+12
FDC224KXZRE1FDC224KXZRE1
FDC224KXZRE1FDC280KXZRE1
FDC280KXZRE1FDC280KXZRE1
FDC280KXZRE1FDC335KXZRE1
FDC335KXZRE1FDC335KXZRE1
73.5 kW 80.00 kW 85.00 kW 90.00 kW 95.00 kW 100.00 kW26HP 28HP 30HP 32HP 34HP 36HP
FDC735KXZRXE1 FDC800KXZRXE1 FDC850KXZRXE1 FDC900KXZRXE1 FDC950KXZRXE1 FDC1000KXZRXE18+8+10 8+10+10 10+10+10 10+10+12 10+12+12 12+12+12
FDC224KXZRE1FDC224KXZRE1FDC280KXZRE1
FDC224KXZRE1FDC280KXZRE1FDC280KXZRE1
FDC280KXZRE1FDC280KXZRE1FDC280KXZRE1
FDC280KXZRE1FDC280KXZRE1FDC335KXZRE1
FDC280KXZRE1FDC335KXZRE1FDC335KXZRE1
FDC335KXZRE1FDC335KXZRE1FDC335KXZRE1
22.40 kW 28.00 kW 33.50 kW8HP 10HP 12HP
FDC224KXZWE1 FDC280KXZWE1 FDC335KXZWE1
45.00 kW 50.00 kW 56.00 kW 61.50 kW 67.00 kW16HP 18HP 20HP 22HP 24HP
FDC450KXZWE1 FDC500KXZWE1 FDC560KXZWE1 FDC615KXZWE1 FDC670KXZWE18+8 8+10 10+10 10+12 12+12
FDC224KXZWE1FDC224KXZWE1
FDC224KXZWE1FDC280KXZWE1
FDC280KXZWE1FDC280KXZWE1
FDC280KXZWE1FDC335KXZWE1
FDC335KXZWE1FDC335KXZWE1
73.00 kW 77.50 kW 85.00 kW 90.00 kW 95.00 kW 100.00 kW26HP 28HP 30HP 32HP 34HP 36HP
FDC730KXZWE1 FDC775KXZWE1 FDC850KXZWE1 FDC900KXZWE1 FDC950KXZWE1 FDC1000KXZWE18+8+10 8+10+10 10+10+10 10+10+12 10+12+12 12+12+12
FDC224KXZWE1FDC224KXZWE1FDC280KXZWE1
FDC224KXZWE1FDC280KXZWE1FDC280KXZWE1
FDC280KXZWE1FDC280KXZWE1FDC280KXZWE1
FDC280KXZWE1FDC280KXZWE1FDC335KXZWE1
FDC280KXZWE1FDC335KXZWE1FDC335KXZWE1
FDC335KXZWE1FDC335KXZWE1FDC335KXZWE1
120.00 kW 125.00 kW 130.00 kW 135.00 kW 142.50 kW 145.00 kW 150.00 kW 156.00 kW 162.00 kW 168.00 kW42HP 44HP 46HP 48HP 50HP 52HP 54HP 56HP 58HP 60HP
FDC1200KXZRE1FDC1250KXZRE1FDC1300KXZRE1FDC1350KXZRE1FDC1425KXZRE1FDC1450KXZRE1FDC1500KXZRE1FDC1560KXZRE1FDC1620KXZRE1FDC1680KXZRE114+14+14 14+14+16 14+16+16 16+16+16 17+17+17 17+17+18 18+18+18 18+18+20 18+20+20 20+20+20
FDC400KXZRE1 FDC400KXZRE1 FDC400KXZRE1
FDC400KXZRE1 FDC400KXZRE1 FDC450KXZRE1
FDC400KXZRE1 FDC450KXZRE1 FDC450KXZRE1
FDC450KXZRE1 FDC450KXZRE1 FDC450KXZRE1
FDC475KXZRE1 FDC475KXZRE1 FDC475KXZRE1
FDC475KXZRE1 FDC475KXZRE1 FDC500KXZRE1
FDC500KXZRE1 FDC500KXZRE1 FDC500KXZRE1
FDC500KXZRE1 FDC500KXZRE1 FDC560KXZRE1
FDC500KXZRE1 FDC560KXZRE1 FDC560KXZRE1
FDC560KXZRE1 FDC560KXZRE1 FDC560KXZRE1
VRF Multi systems
INDOOR WATER COOLING UNITS
84
KXZ ADVANCED
KXZ MICRO COMPACT KXZP MICRO SMARTKXE6 MICRO LARGE CONNECTION
KXZX Hi-COP
KXZRX Hi-COP
KXZR 3-PIPE NEW
NEW
NEW
OUTDOOR UNITS - DESIGN FLEXIBILITY
Power can be connected to outdoor units
* When connecting the indoor units in the FDK, FDFL, FDFU or FDFW series, the power of the connectable indoor units cannot exceed 130%.
HP 4 5 6kW 11.2 14.0 15.5EER 4.44 3.54 2.98COP 4.36 3.83 3.62max no. connectable IU 8 10 10power of the connectable IUs (%) 80%~150%
HP 8 10 12kW 22.4 28.0 33.5EER 4.00 3.46 3.41COP 4.15 3.84 3.71max nr. connectable IU 15 19 22power of the connectable IUs (%) 50%~150%*
HP 8 10kW 22.4 28.0EER 4.00 3.56COP 4.67 4.33max nr. connectable IU 8 8power of the connectable IUs (%) 50%~120%
HP 10 12 14 16 17 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60kW 28.0 33.5 40.0 45.0 47.5 50.0 56.0 61.5 67.0 73.5 80.0 85.0 90.0 95.0 100.0 106.0 112.0 120.0 125.0 130.0 135.0 142.5 145.0 150.0 156.0 162.0 168.0EER 3.87 3.74 3.65 3.22 3.40 3.58 3.37 3.80 3.74 3.69 3.65 3.41 3.22 3.40 3.58 3.47 3.37 3.65 3.48 3.34 3.22 3.40 3.46 3.58 3.50 3.43 3.37COP 4.33 4.15 4.21 4.00 4.08 4.15 3.95 4.23 4.15 4.18 4.21 4.10 4.00 4.08 4.15 4.04 3.95 4.21 4.13 4.06 4.00 4.08 4.10 4.15 4.08 4.01 3.95max nr. connectable IU 24 29 34 39 41 43 48 53 58 63 69 73 78 80 80 80 80 80 80 80 80 80 80 80 80 80 80power of the connectable IUs (%) 50~130%
HP 8 10 12 16 18 20 22 24 26 28 30 32 34 36kW 22.4 28.0 33.5 45.0 50.0 56.0 61.5 67.0 73.5 80.0 85.0 90.0 95.0 100.0EER 4.50 4.03 3.86 4.50 4.24 4.03 3.94 3.85 4.30 4.15 4.03 3.96 3.91 3.86COP 4.50 4.61 4.47 4.50 4.55 4.60 4.54 4.46 4.53 4.57 4.61 4.57 4.51 4.46max nr. connectable IU 29 37 44 60 53 59 65 71 78 80 80 80 80 80power of the connectable IUs (%) 80~200% 80~160%
KXZKXZX
Connectable power: 130% (KXZ)Connectable power: 160%~200% (KXZX)
HP 16 18 20 22 24 26 28 30 32 34 36kW 45.0 50.4 56.0 61.5 68.0 73.5 80.0 85.0 90.0 96.0 101.0EER 4.37 3.99 3.79 3.61 3.48 4.16 4.02 3.84 3.69 3.56 3.46COP 4.87 4.63 4.52 4.30 4.13 4.76 4.71 4.58 4.39 4.24 4.11max nr. connectable IU 60 53 59 65 70 78 80 80 80 80 80power of the connectable IUs (%) 80~200% 80~160% 80~130%
HP 8 10 12 14 16 17 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60kW 22.4 28.0 33.5 40.0 45.0 47.5 50.0 56.0 61.5 67.0 73.5 80.0 85.0 90.0 95.0 100.0 106.0 112.0 120.0 125.0 130.0 135.0 142.5 145.0 150.0 156.0 162.0 168.0EER 4.35 3.79 3.47 3.46 3.11 3.20 3.29 3.05 2.88 2.62 3.47 3.46 3.27 3.11 3.21 3.29 3.16 3.06 3.46 3.33 3.21 3.11 3.21 3.23 3.29 3.20 3.13 3.06COP 4.84 4.52 4.12 4.09 3.95 4.10 4.10 3.90 3.80 3.60 4.11 4.10 4.03 3.95 4.09 4.12 4.00 3.90 4.10 4.05 4.00 3.95 4.10 4.10 4.11 4.03 3.97 3.91max nr. connectable IU 29 37 44 53 60 50 53 59 65 71 78 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80power of the connectable IUs (%) 50~200% 50~160% 50~130%
VRF Multi systems
85
KXZW WATER
HP 8 10 12 16 18 20 22 24 26 28 30 32 34 36kW 22.4 28.0 33.5 45.0 50.0 56.0 61.5 67.0 73.0 77.5 85.0 90.0 95.0 100.0EER 5.30 4.87 4.12 5.30 5.09 4.87 4.49 4.11 5.14 5.00 4.86 4.62 4.38 4.12COP 5.90 6.18 5.95 5.90 6.04 6.18 6.05 5.95 5.98 6.08 6.17 6.10 6.02 5.96max nr. connectable IU 22 28 33 44 50 56 61 67 72 78 80 80 80 80power of the connectable IUs (%) 50~150%
OUTDOOR UNITS - DESIGN FLEXIBILITY
Power can be connected to outdoor units
VRF Multi systems
86
› Refrigerant temperature control
› High efficiency
› High COP values
› 34% energy savings
› Compact design
› Design flexibility
› Fast installation
› Ease of maintenance
› Minimum operating costs
"Innovative technology for evolutionary standards in the air conditioning of industrial and commercial environments"
Functional control and innovative components make this system technology more efficient
VRF Multi systems KXZ seriesHeat pump
COP 4.6 KXZX
87
WIDE RANGE
THE SYSTEM Mitsubishi Heavy Industries' KXZ heat pump series with VRF-T technology is distinguished by the possibility of controlling the refrigerant temperature in the various stages of operation, improving the performance levels compared to traditional systems. KXZ is a unique system that provides an excellent performance both cooling and heating. Maximum level of design flexibility, reduction of energy consumption and advanced operating functions, centralised management of system and above all Hi-COP (KXZX), complete the profile of the KXZ series, which ensures reliability and efficiency over time.
APPLICATION IN NZEB SOLUTIONKXZ system with VRF-T technology is particularly suitable for applications on buildings constructed according to ZEB logic. In fact, the “zero-energy” buildings, realized according to ZEB logic, have the characteristics of reducing the energy consumption, but also of producing the required energy by renewable energy sources, since their goal is the self-sufficiency. To construct ZEB buildings, it is essential that energy efficiency is put as a priority condition since the construction project, taking into consideration all the components that contribute to the final result: heating, cooling, photovoltaic systems and domestic hot water, until the energy management of the entire structure. To achieve this result, one of the main application solutions is constituted by heat pumps, such as those of KXZ system with VRF-T technology.
WHY CHOOSE THE KXZ – VRF-T SYSTEM? HERE ARE 4 GOOD REASONS.
1. ENERGY SAVINGS UP TO 34%With VRF-T technology, refrigerant temperature control during the condensation and evaporation phases in the refrigerant system ensures energy savings up to 34% in cooling mode during the partial loads, compared to the traditional VRF models.
Traditional system cooling operation
Room temperature
Set temperature
Energy savings: Max 34%Room temperature
Set temperature
Compressor
Low pressure target
Control of the temperature difference
Compressor
Low pressure target
Constant level
In a traditional system, the refrigerant target pressure to be maintained is constant. As soon as room temperature reaches the temperature set by the user, the compressor is forced to decrease and increase the rpm by on-off cycles that affect the overall efficiency and performance.
KXZ system cooling operation with activation of VRF-T mod
With the new VRF-T, the refrigerant target pressure to be maintained is not constant, but adjusts proportionally to the difference between the room temperature and the desired temperature. This allows the Inverter compressors to modulate the rpm without ever stopping, thus expressing the maximum efficiency for a global energy saving operation.
Indoor units.16 types of units for a total of 91 models.The variety of types and capacities ensures an offer capable of meeting all the design and installation requirements.
Outdoor units.Up to 80 connectable indoor units. 5 product lines from 8 to 60HP (22.4~168.0 kW): Micro Compact, Micro Smart, Advanced, HiCOP and Water. Mitsubishi air conditioners with VRF-T technology all have double vertical fan and three-phase power supply. They can be installed also in twin combination, with only one refrigerant circuit. The total splitting distance reaches 1000 m.
VRF Multi systems KXZ series
88
2. COMPACT DESIGN, FOR EASY INSTALLATION
10~60HP (KXZ)
DC Inverter fan motor
Tetrahedral structure of heat exchanger
High efficiency heat exchanger with anti-corrosion Blue Fin
Dual condensate drain
New Scroll Multi-Port compressors, all Inverter. No On/Off
New vector Inverter control
3. NEW ELECTRICAL WINDING FOR THE COMPRESSOR, FOR HIGH PERFORMANCE AND EFFICENCY
The new compacted design of the motor winding significantly improves the electrical performance, which results in increased efficiency, especially in partial loads with a consequent increase in seasonal efficiency.
4. DC INVERTER COMPRESSOR, FOR HIGH SCOP
The multi-port discharge system of the compressor guarantees better volumetric performance. Optimisation of the pressure control, in particular to the medium compressor operation frequencies, with consequent improvement to seasonal efficiency performance.All KXZP/KXZ/KXZX outdoor units use DC Inverter compressors only, and no on/off compressor.
Discharge port
In the case of KXZP (8/10HP); KXZ (10/12/18/20HP) and KXZX (8HP)
Multi-port discharge
Adjustment of compression phase with multi-port discharge that ensures a greater efficiency
Total efficiency
* Used for KXZP SMART power 8/10HP; KXZ ADVANCED power 10/12/17/18/20HP and KXZX Hi-COP power 8HP and KXZR both standard and Hi-COP.
Supp
lied p
ower
New concentrated windings*
Windings distributedin standard mode
Increasein seasonal average
efficiencyCompressor speed
Heat pumpVRF Multi systems KXZ series
89
KXZ
manifold distributor
EXCHANGER EXCHANGER
NEW REFRIGERANT DISTRIBUTORThe new configuration composed of distributor and capillary has optimized the diffusion of refrigerant in the new heat exchanger, with a further increase in the total efficiency of system and a decrease in the possibility of icing on heat exchanger, with consequent reduction in defrost time.
Oil balance pipe
OIL LEVEL CONTROLMitsubishi oil level adjustment technology for the combination of two or three outdoor units allows operation with constant balancing, maintaining the units' performance and guaranteeing a long system life.
POWER OUTPUT CONTROLThe power output can be controlled and selected by the function of power cut through RC-EX3, remote control, to obtain a greater energy saving. The 5-step power control (100-80-60-40-0%) is available, that can be programmed in hour intervals, every week.
INVERTER CONTROL (VECTOR)The use of a new vector inverter control, allows the user to:• Increasetheresponsespeedofcompressorsatlowandhigh
speed.•Re-createexactlythesinusoidalwaveformofthevoltage
applied.• Increasetheefficiencyofcompressorsatlowspeedandpartial
loads.
Powe
r sup
ply
Operation time
NEW FAN DESIGN
New fan blades with serrated edges that treat a greater air volume, offering low resistance to air and reducing energy consumption.
Serrated edges
DC FAN MOTOR
The use of DC fan motors can help achieve excellent efficiency, with an increase higher than 60% compared to the previous models.
Rotor (squirrel cage ofconductor material)
Stator (coil)
Rotor (permanent magnet)
Stator (coil)
VRF Multi systems KXZ series
previous
90
ADVANTAGES FOR DESIGNERS
The system design phase requires flexible and advanced solutions, able to respond to each manufacturing solution.Below is a list of all the points that make KXZ - VRF-T a system equipped with all the advantages that meet new design standards.
1. HIGH SPLITTING LENGTH, FLEXIBLE DESIGN 1000 m [10~60HP
(KXZ series)]
The splitting height difference between indoor units has been increased up to 18 m, permitting the placement of indoor units on three additional storeys. The farthest indoor unit (160 m) or the total length (1000 m) contribute to the flexible design of the system.
Total length: 1000 m
max. 10 m
To the first branch: max 130 m
From the first branch pipe to the furthest IU: 90 m*
max. 5 m
Outdoor unit max. 0.4 m
Splitting height difference 50 m (outdoor unit higher) -> 70 m**40 m (outdoor unit lower)
Max height difference between IUs 18 m
Furthest indoor unit
160 m
Indoor unit
Indoor unit
Indoor unit
Thanks to the significant reduction in the weight and overall plan dimensions, the KXZ and KXE6 (Lc) MICRO outdoor units can be easily transported in a lift capable of containing 6 people (if permitted by the condominium regulations), with a consequent reduction in costs, time and working procedures.The outdoor units in the KXZ and KXZX series have a functional base, which makes it easier to lift and transport them to the place of installation. They are also characterised by the same overall plan dimensions, which facilitates the installation of the machines in series as well as optimising times and procedures for maintenance and replacement of each unit.
Lift
2. EASY TRANSPORT & INSTALLATION
H 1675 x L 1080 x D 480
Heat pumpVRF Multi systems KXZ series
91
1080 mm
970 mm
KXE6 Micro (Lc) KXZP SMART
480 mm
1505 mm
1675 mm
KXE6 Micro (Lc) KXZP SMART
221 kg
165 kg
-20° C
-15° C
+15.5° C
+50° C
-20° C
-15° C
+15.5° C
+46° C
3. WIDE OPERATING RANGE, FLEXIBLE DESIGN
The KXZP series enables operation in heating mode with an outdoor temperature limit of -20°C and a cooling range up to 50°C.This series allows for a more flexible system design, considering a heating range at low temperature conditions down to -20°C, and a cooling range up to 46°C.
KXZP
KXZ/KXZX
HEATING
Cooling
HEATING
Cooling
4. BLUE FIN FUNCTION, AGAINST CORROSION OF THE HEAT EXCHANGERS
The particular coating of the heat exchanger louvers guarantees perfect resistance to corrosion and deterioration caused by atmospheric agents.
5. COMPACT DESIGN
10% less23% less
10% less
25% less
6. EXTERNAL STATIC PRESSURE UP TO 35 PA
9. ADDITIONAL FUNCTIONS:
• POWER DEMAND FUNCTION The outdoor unit's rated power can be decreased.•SEASONAL OPTION A summer/winter season function change can be set.• OUTPUT SIGNAL OPTION Indicates start-up signal or error signal.
7. FUNCTION OF OUTDOOR FAN MOTORS
Function with pressure head useful for ducting.
8. AUTOMATIC FUNCTION FOR REDUCED WEAR
The outdoor units with multiple compressors are subject to wear. This automatic function balances the automatic operation of compressors, depending on the hours of operation.
VRF Multi systems KXZ series
92
8~60HP
Inverter
KXZ KXZP SMART
1. MONITORING FUNCTION
Thanks to a simple navigation menu, the displays on the outdoor unit boards are able to show all the vital parameters of the unit and any error messages for prompt intervention.
Connect a PC to the RS 232C port, available on the board, to monitor and save all the historical data of system for assistance and control activities. Our Mente PC software must be installed on the PC.
2. BACK UP FUNCTION, OPERATION RESTORED
The unit uses Inverter compressors only.In the event that one of them malfunctions, the unit can however operate at reduced capacity.
In multiple combinations of high capacity of two or three outdoor units, unit malfunction does not affect total operation of the system, which will continue to operate in a partial manner.
3. EASY ACCESS TO THE ELECTRICAL BOX FOR EASY MAINTENANCE
Inverter service and maintenance are now easier thanks to the new control box with a structure of 3 levels (KXZ) and 2 levels (KXZP SMART) with a hinged connection.
Running Compressor failure
KXZ: 18 and 20HP
Unit failure
Combination of two or three outdoor units
ADVANTAGES FOR INSTALLERS
Installing KXZ units in a system means having an installation able to satisfy the most varied requirements, thanks to useful functions and important features which make the life of the system easier to manage, during both installation and maintenance.
Heat pumpVRF Multi systems KXZ series
93
4. IMPROVED PRACTICALITY
Position of pipes:1) From the front2) To the right3) Below4) From the back
New holes for thread insertion, to prevent falls
Service panel maintenance
Clear rain cover
Unit installation and maintenance of unit are easier thanks to the reduced number of fixing screws on the service panel (from 5 to 2).
5. GAS TESTING FUNCTION
This function provides for a procedure capable of verifying whether the amount of refrigerant gas contained inside the system is correct. The positive side to this is evident, as it optimises the use of gases that are harmful to the environment, as required by current legislation.
6. AUTO-ADDRESSING FUNCTION
Simply power the unit and this automatic function will facilitate intelligent connection between multiple units.
7. ADDITIONAL FUNCTIONS
•Simplifiedtestprocedure
•Simplifiedfunctionforwiring
•Easyfunctionforrefrigerantinstallationandmaintenance
•Theunit'sdistinguishingfeatureisthatofbeingEasy Service, as it permits easy maintenance, easy electronic check and feedback by the protection system in case of malfunctions
VRF Multi systems KXZ series
94
1. REDUCED COSTS
Cost reduction is an advantage that relates to several aspects: - Savings in management costs- Savings in maintenance costs- Savings on annual consumption thanks to high energy
efficiency
2. COMPLETE SOLUTION
The only system for heating, cooling and management control that can fit any solution.
3. MAXIMUM RELIABILITY
- Well-tested systems in every condition- After-sales service and service network always available- Prompt availability of spare parts
4. INTEGRATION & BUILDING AUTOMATION
The KXZ- VRF-T system boasts integration with home automation systems or Building Automation for easier and more uniform management.
5. BEST ENERGY CLASS
Being in heat pump, the use of KXZ- VRF-T improves building energy classifications with higher scores, thus increasing building value.
A complete system in terms of comfort and smart control, that can be customised to meet the needs of all types of buildings, stores or housing solutions.KXZ with VRF-T technology, designed with integration in mind, is an ideal system because it allows end users to achieve maximum energy efficiency as well as manage several systems, with ease of use guaranteed by leading control standards.
Heat pumpVRF Multi systems KXZ series
ADVANTAGES FOR USERS
95
HEAD8-371-2/1B
REFRIGERANT CONNECTIONS
VRF-T systems are manufactured to the highest standards of quality and reliability and it is therefore essential for the installation procedures and materials to have the same qualitative features, to ensure trouble-free long-term operation. It is advisable to use high quality copper refrigerant piping, in coils or in straight, semi-rigid lengths. The copper piping should be chosen considering the higher operating pressure of R410A refrigerant gas and the increased pressure circulating in the system produced by reverse cycle operation. All materials used must comply with European standards (EN 12735). The branch pipe kits supplied must be used to connect the indoor units and the manifold kits must be used to connect the outdoor units (if necessary). It is forbidden to use standard accessories (elbow pipes, T-joints etc.). The branch pipes must be installed according to manufacturer guidelines and must allow a continuous flow of refrigerant in accordance with European standard E378:2017.All connecting welds must be made under slight nitrogen pressure to prevent the oxidation of the inner surface of the copper pipes. During installation, no accidental entry of condensate, dust or any other contaminant must be permitted. Once installation is complete, a leak test must be carried out to check for refrigerant leaks with pressurised nitrogen. The ends of the pipe must be bent and welded and an appropriate service valve affixed.
Additional refrigerant chargeOnly R410A refrigerant gas must be used, and this must be added by weight using an electronic meter. The amount of additional refrigerant must be carefully calculated according to the manufacturer’s guidelines, defined by the length and diameter of each section of the system piping.
Single outdoor unit
Refrigerant piping system with manifold kit Refrigerant piping system with branch pipe kit
KXZ ADVANCED - KXZX HiCOP
KXZ ADVANCED - KXZX HiCOP
Combined outdoor units
Refrigerant piping system with branch pipe kit
Refrigerant oil compensation pipe
Set of outdoor unit branch pipesOutdoor unit Set of branch pipes
2 units (for 615 ~ 1120) DOS-2A-3(B)3 units (for 1200 ~ 1680) DOS-3A-3
VRF Multi systems KXZ series
DOS-2A-3(B)
96
DIS-22-1G(1B)/DIS-180-1G(1B) HEAD6-180-1G(1B)
DIS-371-1G(1B)/DIS-540-3 DOS-2A-3(B)/DOS-3A-3
Combined outdoor units
HP 10 12 14 16 17 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60Liquid side Furthest IU
=<90 mø 9.52 ø 12.7 ø 15.88 ø 19.05
Gas side ø 22.22 ø 28.58 ø 34.92Liquid side Furthest IU
=> 90 mø 12.7 ø 15.88 ø 19.05 ø 22.22
Gas side ø 22.22 ø 28.58 ø 34.92
Liquid sideGas side
YES
NO
NO
vertical
horizontal
floor
floor
floor
floor
First branch pipe of the indoor unitTotal capacity of indoor units
Set of branch pipes
Set of manifoldsModel Branch pipes
~179 DIS-22-1G(1B) HEAD4-22-1G(1B) Max. 4 units180~370 DIS-180-1G(1B) HEAD6-180-1G(1B) Max. 6 units371~539 DIS-371-1G(1B) HEAD8-371-2(1B) Max. 8 units540~ DIS-540-3 HEAD8-540-3 Max. 8 units
Branch pipes Manifolds
YES
KXZ ADVANCED - KXZX HiCOP
REFRIGERANT CONNECTIONS
Refrigerant oil compensation pipe
Refrigerant piping system with manifold kit
HEAD8-540-3
DOS-2A-3(B)
Heat pumpVRF Multi systems KXZ series
97
ELECTRICAL CONNECTIONSVRF MHI systems require highly simplified electrical connections to the indoor units, thanks to a control circuit that uses 2 non-polarised conductors. The supply system has wiring that can be connected on the front, right, left or rear of the outdoor unit. For three-phase outdoor units and single phase indoor units, a separate power supply must be used. The interaction between the outdoor unit and indoor unit takes place via the control device only.
Outdoor unit power supply: three-phase, 4 wires, 380~415V Separated power supply system
Outd
oor u
nitEarth leakagebreaker
Circuitbreaker Ground
A Main power supply cable (4 wires)B Signal lines - Superlink (2 wires)C Indoor units power cable (2 wires)D Cables for the wired remote control (2 wires)
Earth leakagebreaker
Circuitbreaker
Indoor unit
wired remote control
Indoor unit power supply: single phase 220~240V
CAUTION: if the RCD is dedicated solely to protecting against leakage to earth, it will be necessary to install a circuit breaker.
The maximum number of indoor units that can be connected to a signal line is 128, and it is possible to create groups of outdoor and/or indoor units connected to the same outdoor unit or to separate outdoor units, as long as they are connected to the same signal line. The signal line can also be connected by adopting the method described below (multiple connectors).
0.75 mm2 1.25 mm2~1000 mm YES YES
1000~1500 mm YES NO
Signal line
IMPORTANT: A loop connection of the signal lines is NOT ALLOWED
A loop cannot be formed with the signal, therefore the section of the connection indicated with ........is not permitted
Length (m) Type of cables100~200 0.5 mm2 x 2 wires
~300 0.75 mm2 x 2 wires~400 1.25 mm2 x 2 wires~600 2.0 mm2 x 2 wires
Single outdoor unit
Combined outdoor units
OU signal terminal board
IU signal terminal board
The signal lines have no polarity therefore the connections listed below are permitted
Network connectors
Signal lines
Refrigerant lines
The signal line is 5 VDC and uses 2 non-polarised conductors marked A1 and B1. AB connects the outdoor unit to the indoor unit and vice versa. For the signal line with 2 conductors, use shielded cables measuring 0.75 or 1.25 mm2. Earth the shield on all the indoor and outdoor units.
If using combined outdoor units, connect:• Thesignallinebetweenindoorand
outdoor units, and the signal line between outdoor units that belong to the same
refrigerant line, to A1 and B1;• Thesignallinebetweenoutdoor
units belonging to a different refrigerant line to A2 and B2.
The specifications for the connection between the wired remote control and the indoor units (XY connection) are 0.3 mm2 x 2 wires. The maximum permitted length is 600 m. If the length exceeds 100 m, refer to the table.
Wired remote control
OU
IU
OUOUOU
IUIUIU
OU
IU
OU OU
IU IU
IU IU IU
OU OU OU OU
IU
IU
IU
IU
VRF Multi systems KXZ series
98
4545
5656
7171
2828
5656
total314
total198
It is possible to fix the operation mode of the system (cooling or heating) using a switch (SW3-7) on the outdoor unit PC board: this enables the user to decide the operation of the system inside the building (e.g. cooling only in summer/heating only in winter), to avoid unnecessary energy waste. It is also possible to wire the control switch to a remote location (inside the building), in a control room, or even linked to an ambient thermostat.
FIXED COOLING MODE/FIXED HEATING MODE (SUMMER/WINTER SWITCH)
Priority operating mode selection You can select the following priority operation modes (for the whole
system).
1. The first unit's operating mode commands the operating mode (default setting).
The system operates according to the mode selected by the majority of units in operation, taking into consideration the greater capacity between the sum of units in cooling mode and those in heating mode. The minority operating mode is set to fan mode automatically.
“Majority” operating mode
In “Master” function, if you select the cooling mode, the units set in heating mode switch to fan mode automatically.
“Master” operating mode
Operating modecooling capacity
45+45+56+56+56+56
Cooling mode
Fan mode
Operating modeheating capacity71+71+28+28
Fan mode
Heating mode
Cooling mode Heating mode "Master" mode: cooling
"Master" mode: cooling
OPERATING MODE
2. The last unit's operating mode determines the operating mode for whole system.
3. “Majority” operating mode4. “Master” operating mode
Heat pumpVRF Multi systems KXZ series
99
VRF Multi systems KXZ series
100
Connects up to 10 indoor units/150% capacity
FDC 112 KXZEN1/ZES1 11.2 kW single phase/three-phaseFDC 140 KXZEN1/ZES1 14.0 kW single phase/three-phaseFDC 155 KXZEN1/ZES1 15.5 kW single phase/three-phase
› Maximum energy efficiency: COP 4,36 (4HP)› Scroll DC Inverter compressor on all units› DC Inverter fan motors › 4 sound levels in Silent mode› New PCB cooling system: A refrigerant pipe branch passes to
the base of the PCB to prevent overheating
Diagrams and measurements
Max height difference between IUs 15 m
Indoor unit
Indoor unit
Outdoor unit
* The total length of piping, liquid side ø9.52 mm (3/8") should be 50 m or less.
Total length 100 m
Height difference:30 m top OU15 m bottom OU
Furthest IU: 70 m*
Operating range
terminal board
intake
intake
outlet(Service space)
All measurements are in mm.
A Service valve (gas side) ø 15.88 (5/8”) (flare fitting)
B Service valve (liquid side) ø 9.52 (3/8”) (flare fitting)
C Piping outputD Condensate drain ø 20 x 3 holesE Fixing bolt holes M10 x 4 holesF Cable output ø 30 x 3 holes
DimensionsExample of installation
1 2 3L1 open open 500L2 300 5 openL3 150 300 150L4 5 5 5
Notes:(1) The unit should not be surrounded by walls on
any side(2) Secure the unit using anchor bolts(3) In case of exposure to strong wind, direct the unit so
that the air expulsion grille is at 90° in relation to the prevailing wind direction
(4) Allow at least 1 m clearance above the unit(5) If there are obstacles in front of the air expulsion
grille, the height must not exceed the height of the unit
(6) The label with the installation data is positioned in the bottom right corner of the front panelMinimum installation space
HP 4 5 6Liquid side
Furthest IU =<70 mø 15.88 (5/8")
Gas side ø 9.52 (3/8")
Refrigerant connections
Branch pipes Manifolds
Outdoor unit
› Can connect 1.5 kW indoor units› New system for managing indoor unit priorities› "Pump down" safety function: to identify any gas leaks inside
the room (third-party sensor) and start up the refrigerant recall procedure by the outdoor unit, present inside the system
VRF Multi systems KXZ MICRO COMPACT seriesHeat pump
VRF-T TECHNOLOGYenergy savings up to 34% in cooling
HEAD4-22-1G(1B) HEAD6-180-1G(1B)
DIS-22-1G(1B)DIS-180-1G(1B)
NEW
101
1. EU Delegated Regulation No.626/2011 on the labelling indicating the energy consumption of air conditioners.2. EU Regulation No.206/2012 - N.2281/2016 - Value measured according to harmonised standard EN14825.3. Value measured according to harmonised standard EN14511.4. Refrigerant leakage contributes to climate change. When released into the atmosphere, refrigerants with a lower global warming potential (GWP) contribute less to global warming than those with a higher GWP. This appliance contains a
refrigerant with a GWP of 2088. If 1 kg of this refrigerant fluid were released into the atmosphere, therefore, the impact on global warming would be 2088 times higher than 1 kg of CO2, over a period of 100 years. Under no circumstances should the user try to intervene on the refrigerant circuit or disassemble the product. Always contact qualified personnel if necessary.
VRF Multi systems KXZ MICRO COMPACT series
KXE6 NEW KXZ4HP 6 units → 8 units5HP 8 units → 10 units15H6 8 units → 10 units2
Increased number of connectable IU
1. max capacity <=100% with 9 or 10 connected units2. max capacity <=100% with 9 or 10 connected units
* With limitations on maximum connectivity.
Models FDC112KXZEN1 FDC140KXZEN1 FDC155KXZEN1 FDC112KXZES1 FDC140KXZES1 FDC155KXZES1Nominal Cool. capacity (T=35°C) kW 11.20 14.00 15.50 11.20 14.00 15.50Cool. power consumption (T=35°C) kW 2.52 3.96 5.20 2.52 3.96 5.20Annual energy consumption in Cool. kWh/a - - - - - -Seasonal energy efficiency class in Cool. 626/20111 A+ - - A+ - -Seasonal energy efficiency index in Cool. SEER2 5.94 7.73 7.21 5.94 7.73 7.21Rated energy efficiency coefficient in Cool. EER3 4.44 3.54 2.98 4.44 3.54 2.98Nominal Heat. capacity (T=7°C) kW 11.20 14.00 15.50 11.20 14.00 15.50Heat. power consumption (T=7°C) kW 2.57 3.66 4.28 2.57 3.66 4.28Annual energy consumption in Heat. kWh/a - - - - - -Seasonal energy efficiency class in Heat. 626/20111 A+ - - A+ - -Seasonal energy efficiency index in Heat. SCOP2 4.17 4.59 4.55 4.17 4.59 4.55Rated energy efficiency coefficient in Heat. COP3 4.36 3.83 3.62 4.36 3.83 3.62Power Single phase 220~240V 50Hz Three-phase 380~415V 50HzRated current in Cool. A 12.2 19.6 25.7 4.1 6.5 8.6Rated current in Heat. A 12.6 18.3 21.4 4.2 6.1 7.1Sound pressure level dB(A) 52 53 54 52 53 54Sound power level dB(A) 69 71 71 69 71 71External dimensions (HxLxD) mm 845x970x370 845x970x370 845x970x370 845x970x370 845x970x370 845x970x370Exterior appearance (Munsell colour) Stucco white (4.2Y7.5 / 1.16) equivalentNet weight kg 85 85 85 87 87 87Refrigerant circuit/Compressor type and qty. RMT5126MDE21x1 RMT5126MDE21x1 RMT5126MDE21x1 RMT5126MDE31x1 RMT5126MDE31x1 RMT5126MDE31x1Motor kW 1.9 2.9 3.2 1.9 2.9 3.2Starting method In line, direct
Indoor System Units Number of connectable IU from 1 to 8 from 1 to 10* from 1 to 10* from 1 to 8 from 1 to 10* from 1 to 10*Total connectable capacity 90 ~ 168 112 ~ 210 124 ~ 233 90 ~ 168 112 ~ 210 124 ~ 233
Crankcase heater W 20 20 20 20 20 20Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveRefrigerant/GWP4 R410A R410A R410A R410A R410A R410AQuantity kg 5.00 5.00 5.00 5.00 5.00 5.00Tons of CO2 equivalent 10.44 10.44 10.44 10.44 10.44 10.44Refrigerant oil l 1.0 (M-MA68) 1.0 (M-MA68) 1.0 (M-MA68) 1.0 (M-MA68) 1.0 (M-MA68) 1.0 (M-MA68)Defrost control Microcomputer controlledAir treatment/Fan type and quantity Axial fan x 1Motor W 86x1 86x1 86x1 86x1 86x1 86x1Starting method Direct Direct Direct Direct Direct DirectAir flow (Standard) m3h 4500 4500 4500 4500 4500 4500Shock and vibration absorption Rubber vibration absorber (for compressor)Safety devices Compressor overheating protection, overcurrent protection, power transistor overheating protection, abnormal high pressure protection
Diameter cooling/refrigerant pipes mm (inch) Liquid side ø 3/8” (9.52)Gas side ø 5/8” (15.88)
Joining method by flare fittingsCondensate drain Hole for drain ø 20x3Piping insulation Necessary (on both sides, liquid and gas)Accessories - - - - - -
NEW
4-6HP (11.2~15.5 kW)
102
Up to the first branch pipe:max 130 m
From the first branch pipe to the furthest IU: 90 m* Furthest IU 160 m
Max height difference between IUs 18 m
Indoor unit
Indoor unit
Indoor unit
Outdoor unit
* With length difference between the furthest indoor unit and the nearest one from the first branch pipe < 40 m.
Total length 510 m
Height difference:50 m top OU40 m bottom OU
FDC224KXE6 FDC280KXE6 FDC335KXE6A Service valve (gas side) ø 19.05 (3/4”) (flare fitting) ø 19.05 (3/4”) (flare fitting) ø 19.05 (3/4”) (flare fitting)B Service valve (liquid side) ø 9.52 (3/8”) (flare fitting) ø 9.52 (3/8”) (flare fitting) ø 12.7 (1/2”) (flare fitting)C Piping output 4 holes 4 holes 4 holesD Hole for condensate drain ø 20 x 4 holes ø 20 x 4 holes ø 20 x 4 holesE Fixing bolt holes M10 x 4 holes M10 x 4 holes M10 x 4 holes
F Electrical connection outletø 30 x 2 holes (front)
ø 45 (side)ø 30 x 2 holes (rear)
ø 30 x 2 holes (front)ø 45 (side)
ø 30 x 2 holes (rear)
ø 30 x 2 holes (front)ø 45 (side)
ø 30 x 2 holes (rear)
G Connecting position of the local pipe (gas side) ø 19.05 (3/4”) (brazing) ø 22.22 (7/8”) (brazing) ø 25,4 (1”) (brazing)
Dimensions Example of installation1 2 3
L1 open open 1500(500)*1
L2 300 5 openL3 300 300 300L4 250(5)*2 250(5)*2 250(5)*2
Notes:(1) The unit should not be surrounded by walls on any side(2) Secure the unit using anchor bolts The anchor bolt must not
protrude more than 15 mm.(3) In case of exposure to strong wind, direct the unit so that the
air expulsion grille is at 90° in relation to the prevailing wind direction
(4) Allow at least 1 m clearance above the unit(5) If there are obstacles in front of the air expulsion grille, the height
must not exceed the height of the unit(6) The label with the installation data is positioned in the bottom
right corner of the front panel(7) Connect the service valve with the local pipe using the
connection pipe (gas side only)(8) The mark shows the position for the local pipe connection (gas
side only)
terminal board
intakeintake
outlet(Service space)
Minimum installation space
*1 The Figure in () shows the applicable value when the flexible flow adapter is installed.
*2 On condition of setting as it is specified in (), it is necessary to ensure 250 mm for L4 dimension when the compressor is replaced (i.e. if unit is moved).
Connect up to 22 indoor units/150% capacity
FDC 224 KXE6 22.4 kW three-phaseFDC 280 KXE6 28.0 kW three-phaseFDC 335 KXE6 33.5 kW three-phase
› 1 DC Inverter compressor (8 ~ 10 HP), 1 3D Scroll compressor (12 HP)
› High split: up to 510 m in total and with a maximum distance between the OU and the furthest IU of 160 m
Operating range
Diagrams and measurements
All measurements are in mm.
Outdoor unit
VRF Multi systems KXE6 MICRO LARGE CONNECTION seriesHeat pump
103
HP 8 10 12Liquid side Furthest IU
=<90 mø 9.52 ø 12.7
Gas side ø 19.05 ø 22.22 ø 28.58Liquid side Furthest IU =>
90 mø 12.7
Gas side ø 22.22 ø 28.58
Refrigerant connections Branch pipes Manifolds
2. EU Regulation No.2281/2016 - - Value measured according to harmonised standard EN14825.3. Value measured according to harmonised standard EN14511.4. Refrigerant leakage contributes to climate change. When released into the atmosphere, refrigerants with a lower global warming potential (GWP) contribute less to global warming than those with a higher GWP. This appliance contains a
refrigerant with a GWP of 2088. If 1 kg of this refrigerant fluid were released into the atmosphere, therefore, the impact on global warming would be 2088 times higher than 1 kg of CO2, over a period of 100 years. Under no circumstances should the user try to intervene on the refrigerant circuit or disassemble the product. Always contact qualified personnel if necessary.
VRF Multi systems KXE6 MICRO LARGE CONNECTION series
Models FDC224KXE6 FDC280KXE6 FDC335KXE6Nominal Cool. capacity (T=35°C) kW 22.40 28.00 33.50Cool. power consumption (T=35°C) kW 5.60 8.09 9.82Annual energy consumption in Cool. kWh/aSeasonal energy efficiency index in Cool. SEER2 6.55 6.03 5.77Rated energy efficiency coefficient in Cool. EER3 4.00 3.46 3.41Nominal Heat. capacity (T=7°C) kW 25.00 31.50 37.50Heat. power consumption (T=7°C) kW 6.03 8.21 10.12Annual energy consumption in Heat. kWh/aSeasonal energy efficiency index in Heat. SCOP2 4.55 4.54 4.49Rated energy efficiency coefficient in Heat. COP3 4.15 3.84 3.71Power Three-phase 380~415V 50HzRated current in Cool. A 9.25 13.22 15.87Rated current in Heat. A 9.85 13.41 16.36Sound pressure level dB(A) 59 60 61Sound power level dB(A) - - -External dimensions (hxlxd) mm 1675x1080x480Exterior appearance (Munsell colour) Stucco white (4.2Y7.5 / 1.1) equivalentNet weight kg 221 221 224Refrigerant circuit/Compressor type and qty. GTC5150NH40K×1 GTC5150NH40K×1 GTD5160NH40K×1Motor kW 3.81 5.22 7.25Starting method In line, direct
Indoor System Units Number of connectable IU from 1 to 15 from 1 to 19 from 1 to 22Total connectable capacity 112 ~ 336 140 ~ 420 167 ~ 502
Crankcase heater W 33 33 33Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveRefrigerant/GWP4 R410A/2088 R410A/2088 R410A/2088Quantity kg 11.50 11.50 11.50Tons of CO2 equivalent 24.01 24.01 24.01Refrigerant oil l 1.7 (M-MA32R) 1.7 (M-MA32R) 1.7 (M-MA32R)Defrost control Microcomputer controlledAir treatment/Fan type and quantity Axial fan x 2Motor W 144x2Starting method DirectAir flow (Standard) m3h 12000Shock and vibration absorption Rubber vibration absorber (for compressor)Safety devices Compressor overheating protection, overcurrent protection, power transistor overheating protection, abnormal high pressure protection
Diameter cooling/refrigerant pipes mm (inch) Liquid side ø 3/8” (9.52) Liquid side ø 3/8” (9.52) Liquid side ø 1/4” (12.7)Gas side ø 3/4” (19.05) Gas side ø 7/8” (22.22) Gas side ø 1” (25.4)
Joining method Liquid line flare/Gas line brazingCondensate drain Holes for drain ø20x4Piping insulation Necessary (on both sides, liquid and gas)Accessories - - -
DIS-22-1G/1BDIS-180-1G/1B
DIS-371-1G/1B HEAD4-22-1G/1B HEAD6-180-1G/1BHEAD8-371-2/1B
8~12 HP (22.4~33.5 kW)
104
Up to the first branch pipe: max 90 m
From the first branch pipe to the furthest IU: 40 m
Furthest IU 120 m
Max height difference between IUs 18 m
Indoor unit
Indoor unit
Indoor unit
Outdoor unit
Total length 150 m
Height difference:30 m top OU30 m bottom OU
intake
intake
outlet (Service space)
Minimum installation space
terminal board
Piping accessory(only for model FDC 280 KXZPE1)
Dimensions Example of installation1 2 3
L1 open open 500L2 300 5 openL3 150 300 150L4 250(5)* 250(5)* 250(5)*
* It is necessary to ensure 250 mm for L4 dimension when the compressor is replaced.
Connect up to 8 indoor units/120% capacity
FDC 224 KXZPE1 22.4 kW three-phaseFDC 280 KXZPE1 28.0 kW three-phase
› Maximum energy efficiency: COP 4.67 (8 HP)
› Only DC Inverter compressors
› High split: up to 150 m in total and with a maximum distance between the OU and the furthest IU of 120 m
› Compressor speed control
Operating range
Diagrams and measurementsAll measurements are in mm.
Ref. ItemA Gas side pipe fitting ø 19.05 (3/4”) (flare)B Liquid side pipe fitting ø 9.52 (3/8”) (flare)C Hole for draw-out cable (front - side) ø 30 x 2 holesD Hole for draw-out cable (front - side) ø 45 x 2 holesE Hole for draw-out cable (rear) ø 50F Pipe / cable draw-out port 4 holesG Condensate drain ø 20 x 3 holesH Fixing bolt hole M10 x 4 holes
Notes:(1) The unit should not be surrounded by walls on any side(2) Secure the unit using anchor bolts The anchor bolt must not
protrude more than 15 mm.(3) In case of exposure to strong wind, direct the unit so that
the air expulsion grille is at 90° in relation to the prevailing wind direction
(4) Allow at least 1 m clearance above the unit(5) If there are obstacles in front of the air expulsion grille, the
height must not exceed the height of the unit(6) The label with the installation data is positioned in the
bottom right corner of the front panel(7) Connect the service valve with the local pipe using the
connection pipe (gas side only) (The accessory pipe is used for FDC280KXZPE1 only)(8) Concerning the fixing of the accessory pipe, please refer to
the attached installation manual
VRF Multi systems KXZP MICRO SMART series
Outdoor unit
Heat pump
105
HEAD4-22-1G/1B HEAD6-180-1G/1B
DIS-22-1G/1BDIS-180-1G/1B
Branch pipes ManifoldsRefrigerant connections
HP 8 10Liquid side Furthest IU
=<90 mø 9.52
Gas side ø 19.05 ø 22.22Liquid side Furthest IU =>
90 mø 12.7
Gas side ø 22.22 ø 28.58
VRF Multi systems KXZP MICRO SMART series
2. EU Regulation No.2281/2016 - - Value measured according to harmonised standard EN14825.3. Value measured according to harmonised standard EN14511.4. Refrigerant leakage contributes to climate change. When released into the atmosphere, refrigerants with a lower global warming potential (GWP) contribute less to global warming than those with a higher GWP. This appliance contains a
refrigerant with a GWP of 2088. If 1 kg of this refrigerant fluid were released into the atmosphere, therefore, the impact on global warming would be 2088 times higher than 1 kg of CO2, over a period of 100 years. Under no circumstances should the user try to intervene on the refrigerant circuit or disassemble the product. Always contact qualified personnel if necessary.
Models FDC224KXZPE1 FDC280KXZPE1Nominal Cool. capacity kW 22.40 28.00Cool. power consumption kW 5.60 7.87Seasonal energy efficiency index in Cool. SEER2 6.65 6.68Rated energy efficiency coefficient in Cool. EER3 4.00 3.56Nominal Heat. capacity kW 22.40 28.00Heat. power consumption kW 4.80 6.47Seasonal energy efficiency index in Heat. SCOP2 4.34 4.50Rated energy efficiency coefficient in Heat. COP3 4.67 4.33Power Three-phase- 380-415V 50HzRated current in Cool. A 9.2 12.9Rated current in Heat. A 7.9 10.6Sound level dB(A) 60 63External dimensions (hxlxd) mm 1505×970×370 1505×970×370Exterior appearance (Munsell colour) Stucco white (4.2Y7.5 / 1.16) equivalent Stucco white (4.2Y7.5 / 1.16) equivalentNet weight kg 165 165Refrigerant circuit/Compressor type and qty. GTC5150NC40FK×1 GTC5150NC40FK×1Starting method Direct, in line Direct, in line
Indoor System Units Number of connectable IU from 1 to 8 from 1 to 8Total connectable capacity 112 ~ 268 140 ~ 336
Crankcase heater W 33*1 33*1Refrigerant circuit/Heat exchanger Pipes finned with Blue fin treatment and grooved internally Pipes finned with Blue fin treatment and grooved internallyRefrigerant control Electronic expansion valveRefrigerant/GWP4 R410A/2088Quantity kg 8.9 8.9Tons of CO2 equivalent 18.58 18.58Refrigerant oil l 1.45 (M-MA32R) 1.45 (M-MA32R)Defrost control Micro -computerised Micro -computerisedAir treatment/Fan type and quantity Axial fan x 2 Axial fan x 2Motor W 86×2 86×2Starting method Direct DirectAir flow (Standard) m3h 7800 8700Available static pressure Pa Max 35Shock and vibration absorption Rubber vibration absorber (for compressor)Safety devices Compressor overheating protection/overcurrent/power transistor overheating protection/abnormal high pressure protection
Diameter cooling/refrigerant pipes mm (inch) Liquid side ø 3/8” (9.52)Gas side: ø19.05 (3/4”) (ø22.22 (7/8”) Gas side: ø22.22 (7/8”) (ø25.4 (1”) (ø28.58 (1 1/8”)
Joining method Gas side: brazing / Liquid side: flareCondensate drain Drain holes: ø20 × 3pcs.Piping insulation Necessary (on both sides, liquid and gas)Accessories - -
8~10HP (22.4~28.0 kW)
106
Connect up to 29 indoor units/130% capacity
FDC 280 KXZE1 28.0 kWFDC 335 KXZE1 33.5 kW
› Maximum energy efficiency: COP 4.33 (10HP)
› Only DC Inverter compressors
› High split: up to 1000 m in total and with a maximum distance between the OU and the furthest IU of 160 m
* When connecting the indoor units in the following series: FDK, FDFL, FDFU or FDFW, the power of the connectable indoor units cannot exceed 130%.
VRF Multi system KXZ ADVANCED seriesHeat pumpModular outdoor units
2. EU Regulation No.2281/2016 - - Value measured according to harmonised standard EN14825.3. Value measured according to harmonised standard EN14511.4. Refrigerant leakage contributes to climate change. When released into the atmosphere, refrigerants with a lower global warming potential (GWP) contribute less to global warming than those with a higher GWP. This appliance contains a
refrigerant with a GWP of 2088. If 1 kg of this refrigerant fluid were released into the atmosphere, therefore, the impact on global warming would be 2088 times higher than 1 kg of CO2, over a period of 100 years. Under no circumstances should the user try to intervene on the refrigerant circuit or disassemble the product. Always contact qualified personnel if necessary.
Models FDC280KXZE1 FDC335KXZE1Nominal Cool. capacity kW 28.00 33.50Cool. power consumption kW 7.24 8.96Seasonal energy efficiency index in Cool. SEER2 7.25 7.38Rated energy efficiency coefficient in Cool. EER3 3.87 3.74Nominal Heat. capacity kW 31.50 37.50Heat. power consumption kW 7.28 9.04Seasonal energy efficiency index in Heat. SCOP2 4.89 4.85Rated energy efficiency coefficient in Heat. COP3 4.33 4.15Power Three-phase- 380-415V 50HzRated current in Cool. A 11.9 14.6Rated current in Heat. A 12 14.8Sound level dB(A) 57 61Outdoor(?) dimensions (hxlxd) mm 1690×1350×720Exterior appearance (Munsell colour) Stucco white (4.2Y7.5 / 1.16) equivalentNet weight kg 272 272Refrigerant circuit/Compressor type and qty. GTC5150NC47LF×1Motor kW 4.76*1 5.94*1Starting method Direct, in line
Indoor System Units Number of connectable IU from 1 to 24 from 1 to 29Total connectable capacity* 140 ~ 364 168 ~ 435
Crankcase heater W 33*1 33*1Refrigerant circuit/Heat exchanger Pipes finned with Blue fin treatment and grooved internallyRefrigerant control Electronic expansion valveRefrigerant/GWP4 R410A/2088Quantity kg 11.00 11.00Tons of CO2 equivalent 22.97 22.97Refrigerant oil l 2.25 (M-MA32R)Defrost control Micro -computerisedAir treatment/Fan type and quantity Axial fan x 2Motor W 386×2Starting method DirectAir flow (Standard) m3h 13200 16800Available static pressure Pa Max 50Shock and vibration absorption Rubber vibration absorber (for compressor)Safety devices Compressor overheating protection/overcurrent/power transistor overheating protection/abnormal high pressure protection
Diameter cooling/refrigerant pipes mm (inch) Liquid side ø 3/8” (9.52) Liquid side φ12.7 (1/2”)Gas side ø 7/8” (22.22) Gas side: ø25.4 (1”) (ø22.22 (7/8”))
Joining method Gas side: brazing / Liquid side: flareCondensate drain Drain holes: ø20 × 10pcs., ø45 x 3pcs.Piping insulation Necessary (on both sides, liquid and gas)Accessories - -
10~12HP (28.0~33.5 kW)
107
Operating rangeTotal length: 1000 m
Outdoor unit
Up to the first branch pipe: max 130 m
Indoor unit
Indoor unit
Indoor unitFrom the first branch pipe to the furthest IU: 90 m*
* With difference of length between the farthest indoor unit and the nearest one from the first branch pipe < 40 m (MAX 85 m)** Comply with installation conditions. For details, refer to the Technical Manual.
Furthest IU 160 m
Max height difference between IUs 18 m
Splitting height difference50 m (outdoor unit higher) –> 70 m**40 m (outdoor unit lower)
Diagrams and measurementsAll measurements are in mm.
rearView of refrigerant connections
References for the dimensions of the holes of the fixing boltsIncoming air
D (bottom)
C (front)C (right)
D (right)
C (rear)
D (front)
Label with instructions
Box for power cable wiring
Box for signal cable wiring
7-segment displayinspection hole
D (left)
Drain pipe
Notes:(1) Secure the unit using anchor bolts(2) Allow at least 2 m clearance above the unit(3) The adhesive label with the installation data should be positioned under the front panel (right side)(4) The inlet openings for the electrical and refrigerant connections are pre-cut (open using a cutter)(5) For the piping inlet, use the ø 88 hole(6) Use the fixing holes (M10) indicated with “L” and “J” when replacing an outdoor unit belonging to the old series(7) Connect the refrigerant oil compensation pipe (“K”) when using in combination with the outdoor unit
Ref. Item FDC280KXZE1 FDC335KXZE1A Gas side pipe fitting ø 22.22 (7/8”) (brazing) ø 25.4 (1”) (brazing)B Liquid side pipe fitting ø 9.52 (3/8”) (flare) ø 12.7 (1/2”) (flare)C Refrigerant pipe outlet ø88 (or ø100)D Power cable inlet ø 50 (right - left - front), slot 40 x 80 (at bottom)F Fixing bolt hole M10 x 4 holesG Condensate drain pipe connection ø 45 x 3 holesH Condensate drain ø 20 x 10 holesK Refrigerant oil compensation pipe connection ø 9.52 (3/8”) flareL Opening for movement 230 x 60
Example of installationDimensions 1 2
L1 500 openL2 10(30) 10(30)L3 100 100L4 10(30) openH1 1500 openH2 unlimited unlimitedH3 1000 unlimitedH4 unlimited open
Installation spaces
H3
H4H1Intake
Intake
H2
Intake
VRF Multi system KXZ ADVANCED series
108
Connect up to 48 indoor units/130% capacity
FDC 400 KXZE1 40.0 kWFDC 450 KXZE1 45.0 kWFDC 475 KXZE1 47.5 kW
› Maximum energy efficiency: COP 4.21 (14 HP)
› Only DC Inverter compressors
› High split: up to 1000 m in total and with a maximum distance between the OU and the furthest IU of 160 m
FDC 500 KXZE1 50.0 kWFDC 560 KXZE1 56.0 kW
Modular outdoor units
Heat pumpVRF Multi system KXZ ADVANCED series
* When connecting the indoor units in the following series: FDK, FDFL, FDFU or FDFW, the power of the connectable indoor units cannot exceed 130%. 2. EU Regulation No.2281/2016 - - Value measured according to harmonised standard EN14825.3. Value measured according to harmonised standard EN14511.4. Refrigerant leakage contributes to climate change. When released into the atmosphere, refrigerants with a lower global warming potential (GWP) contribute less to global warming than those with a higher GWP. This appliance contains a
refrigerant with a GWP of 2088. If 1 kg of this refrigerant fluid were released into the atmosphere, therefore, the impact on global warming would be 2088 times higher than 1 kg of CO2, over a period of 100 years. Under no circumstances should the user try to intervene on the refrigerant circuit or disassemble the product. Always contact qualified personnel if necessary.
Models FDC400KXZE1 FDC450KXZE1 FDC475KXZE1 FDC500KXZE1 FDC560KXZE1Nominal Cool. capacity kW 40.00 45.00 47.50 50.00 56.00Cool. power consumption kW 10.96 13.98 13.98 13.97 16.62Seasonal energy efficiency index in Cool. SEER2 6.66 6.36 6.84 7.29 6.45Rated energy efficiency coefficient in Cool. EER3 3.65 3.22 3.40 3.58 3.37Nominal Heat. capacity kW 45.00 50.00 53.00 56.00 63.00Heat. power consumption kW 10.69 12.50 13.00 13.49 15.59Seasonal energy efficiency index in Heat. SCOP2 4.23 4.36 4.31 4.58 4.30Rated energy efficiency coefficient in Heat. COP3 4.21 4.00 4.08 4.15 4.04Power Three-phase- 380-415V 50HzRated current in Cool. A 17.5 22.4 22.6 22.6 26.9Rated current in Heat. A 17.5 20.4 21 21.8 25.8Sound level dB(A) 62 61 61 62 66External dimensions (hxlxd) mm 2048x1350x720Exterior appearance (Munsell colour) Stucco white (4.2Y7.5 / 1.16) equivalentNet weight kg 317 317 370 370 370Refrigerant circuit/Compressor type and qty. GUC5185ND47Vx1 GTC5150NC47LFx2Motor kW 7.32*1 9.32*1 4.64*2 4.91*2 5.36*2Starting method Direct, in line
Indoor System Units Number of connectable IU from 1 to 34 from 1 to 39 from 1 to 41 from 1 to 43 from 1 to 48Total connectable capacity* 200 ~ 520 225 ~ 585 238 ~ 617 250 ~ 650 280 ~ 728
Crankcase heater W 40*1 40*1 33*2 33*2 33*2Refrigerant circuit/Heat exchanger Pipes finned with Blue fin treatment and grooved internallyRefrigerant control Electronic expansion valveRefrigerant/GWP4 R410A/2088Quantity kg 11.50 11.50 11.50 11.50 11.50Tons of CO2 equivalent 24.01 24.01 24.01 24.01 24.01Refrigerant oil l 2.9 (M-MA32R) 4.2 (M-MA32R)Defrost control Micro -computerisedAir treatment/Fan type and quantity Axial fan x 2Motor W 386×2Starting method DirectAir flow (Standard) m3h 16800 16800 16800 16800 18600Available static pressure Pa Max 50Shock and vibration absorption Rubber vibration absorber (for compressor)Safety devices Compressor overheating protection/overcurrent/power transistor overheating protection/abnormal high pressure protection
Diameter cooling/refrigerant pipes mm (inch) Liquid side φ12.7 (1/2”)Gas side: ø25.4 (1”) (ø28.58 (11/8”)) Gas side: φ28.58 (11/8”)
Joining method Gas side: brazing / Liquid side: flareCondensate drain Drain holes: ø20 × 10pcs., ø45 x 3pcs.Piping insulation Necessary (on both sides, liquid and gas)Accessories - - - - -
14~20HP (40.0~56.0 kW)
109
Operating rangeTotal length: 1000 m
Outdoor unit
Up to the first branch pipe: max 130 m
Indoor unit
Indoor unit
Indoor unitFrom the first branch pipe to the furthest IU: 90 m*
* With difference of length between the farthest indoor unit and the nearest one from the first branch pipe < 40 m (MAX 85 m)
** Comply with installation conditions. For details, refer to the Technical Manual.
Furthest IU 160 m
Max height difference between IUs 18 m
Splitting height difference50 m (outdoor unit higher) –> 70 m**40 m (outdoor unit lower)
rear
View of refrigerant connections
References for the dimensions of the holes of the fixing boltsIncoming air
D (bottom)
C (front) C (right)
D (right)
C (rear)
D (front)
Label with instructions
Box for power cable wiring
Box for signal cable wiring
7-segment displayinspection hole
D (left)
Drain pipe
C (bottom)
Installation spaces
Intake
Intake
Notes:(1) Secure the unit using anchor bolts(2) Allow at least 2 m clearance above the unit(3) The adhesive label with the installation data should be positioned under the front panel (right side)(4) The inlet openings for the electrical and refrigerant connections are pre-cut (open using a cutter)(5) For the piping inlet, use the ø 88 hole(6) Use the fixing holes (M10) indicated with “L” and “J” when replacing an outdoor unit belonging to the old series(7) Connect the refrigerant oil compensation pipe (“K”) when using in combination with the outdoor unit
Ref. Item FDC400KXZE1 FDC450~560KXZE1A Gas side pipe fitting ø 25.4 (1”) (brazing) ø 28.58 (11/8”) (brazing)B Liquid side pipe fitting ø 12.7 (1/2”) (flare)C Refrigerant pipe outlet ø 88 (or ø 100)D Power cable inlet ø 50 (right - left - front), slot 40 x 80 (at bottom)F Fixing bolt hole M10 x 4 holesG Condensate drain pipe connection ø 45 x 3 holesH Condensate drain ø 20 x 10 holesK Refrigerant oil compensation pipe connection ø 9.52 (3/8”) flareL Opening for movement 230 x 60
Example of installationDimensions 1 2
L1 500 openL2 10(30) 10(30)L3 100 100L4 10(30) openH1 1500 openH2 unlimited unlimitedH3 1000 unlimitedH4 unlimited open
Intake
H2H4
H1
H3
VRF Multi system KXZ ADVANCED series
Diagrams and measurementsAll measurements are in mm.
110
Total length: 1000 m
max. 10 m (equalisation pipe oil)
* With difference of length between the farthest indoor unit and the nearest one from the first branch pipe < 40 m (MAX 85 m)
** Comply with installation conditions. For details, refer to the Technical Manual.
max. 0.4 m
Max height difference between IUs 18 m
Outdoor unit
max. 5 m
Indoor unit
Indoor unit
Indoor unit
Up to the first branch pipe: max 130 m
Furthest IU 160 m
From the first branch pipe to the furthest IU: 90 m*
Splitting height difference50 m (outdoor unit higher) –> 70 m**40 m (outdoor unit lower)
Connect up to 58 indoor units/130% capacity
FDC 615 KXZE1 (FDC280+FDC335) 61.5 kWFDC 670 KXZE1 (FDC335+FDC335) 67.0 kW
› Maximum energy efficiency: COP 4.23 (22HP)
› Only DC Inverter compressors
› High split: up to 1000 m in total and with a maximum distance between the OU and the furthest IU of 160 m
Operating range
Combinations
* When connecting the indoor units in the following series: FDK, FDFL, FDFU or FDFW, the power of the connectable indoor units cannot exceed 130%. 3. Value measured according to harmonised standard EN14511.
Modular outdoor units
Heat pumpVRF Multi system KXZ ADVANCED series
Models FDC615KXZE1 FDC670KXZE1
CombinationsFDC280KXZE1 FDC335KXZE1FDC335KXZE1 FDC335KXZE1
- -Power supply Three-phase- 380-415V 50HzNominal Cool. capacity kW 61.50 67.00Cool. power consumption kW 16.2 17.92Rated energy efficiency coefficient in Cool. EER3 3.80 3.74Nominal Heat. capacity kW 69.00 75.00Heat. power consumption kW 16.32 18.08Rated energy efficiency coefficient in Heat. COP3 4.23 4.15Rated current in Cool. A 26.50 29.20Rated current in Heat. A 26.80 29.60
Indoor System Units Number of connectable IU from 2 to 53 from 2 to 58Total connectable capacity* 308 ~ 799 335 ~ 871
Net weight kg 544 544
Diameter cooling/refrigerant pipes mm (inch) Liquid side ø 1/2” (12.7)mm (inch) Gas side: ø28.58 (1.1/8”)
Oil equalisation mm (inch) ø 3/8” (9.52)
22~24HP (61.5~67.0 kW)
111
Connect up to 80 indoor units/130% capacity
FDC 735 KXZE1 (FDC335+FDC400) 73.5 kWFDC 800 KXZE1 (FDC400+FDC400) 80.0 kWFDC 850 KXZE1 (FDC400+FDC450) 85.0 kWFDC 900 KXZE1 (FDC450+FDC450) 90.0 kW
› Maximum energy efficiency: COP 4.21 (28HP)
› Only DC Inverter compressors
› High split: up to 1000 m in total and with a maximum distance between the OU and the furthest IU of 160 m
FDC 950 KXZE1 (FDC475+FDC475) 95.0 kWFDC 1000 KXZE1 (FDC500+FDC500) 100.0 kWFDC 1060 KXZE1 (FDC500+FDC560) 106.0 kWFDC 1120 KXZE1 (FDC560+FDC560) 112.0 kW
Total length: 1000 m
max. 10 m (equalisation pipe oil)
* With difference of length between the farthest indoor unit and the nearest one from the first branch pipe < 40 m (MAX 85 m)
** Comply with installation conditions. For details, refer to the Technical Manual.
max. 0.4 m
Max height difference between IUs 18 m
Outdoor unit
max. 5 m
Indoor unit
Indoor unit
Indoor unit
Up to the first branch pipe: max 130 m
Furthest IU 160 m
From the first branch pipe to the furthest IU: 90 m*
Splitting height difference50 m (outdoor unit higher) –> 70 m**40 m (outdoor unit lower)
Operating range
Combinations
Modular outdoor units
Heat pumpVRF Multi system KXZ ADVANCED series
* When connecting the indoor units in the following series: FDK, FDFL, FDFU or FDFW, the power of the connectable indoor units cannot exceed 130%. 3. Value measured according to harmonised standard EN14511.
Models FDC735KXZE1 FDC800KXZE1 FDC850KXZE1 FDC900KXZE1 FDC950KXZE1 FDC1000KXZE1 FDC1060KXZE1 FDC1120KXZE1
CombinationsFDC335KXZE1 FDC400KXZE1 FDC400KXZE1 FDC450KXZE1 FDC475KXZE1 FDC500KXZE1 FDC500KXZE1 FDC560KXZE1FDC400KXZE1 FDC400KXZE1 FDC450KXZE1 FDC450KXZE1 FDC475KXZE1 FDC500KXZE1 FDC560KXZE1 FDC560KXZE1
- - - - - - - -Power supply Three-phase- 380-415V 50HzNominal Cool. capacity kW 73.50 80.00 85.00 90.00 95.00 100.00 106.00 112.00Cool. power consumption kW 19.92 21.92 24.94 27.96 27.96 27.94 30.59 33.24Rated energy efficiency coefficient in Cool. EER3 3.69 3.65 3.41 3.22 3.40 3.58 3.47 3.37Nominal Heat. capacity kW 82.50 90.00 95.00 100.00 106.00 112.00 119.00 126.00Heat. power consumption kW 19.73 21.38 23.19 25 26 26.98 29.44 31.9Rated energy efficiency coefficient in Heat. COP3 4.18 4.21 4.10 4.00 4.08 4.15 4.04 3.95Rated current in Cool. A 32.10 35.00 39.90 44.80 45.20 45.20 49.50 53.80Rated current in Heat. A 32.30 35.00 37.90 40.80 42.00 43.60 47.60 51.60
Indoor System Units Number of connectable IU from 2 to 63 from 2 to 69 from 2 to 73 from 2 to 78 from 2 to 80 from 2 to 80 from 2 to 80 from 2 to 80Total connectable capacity* 368 ~ 955 400 ~ 1040 425 ~ 1105 450 ~ 1170 475 ~ 1235 500 ~ 1300 530 ~ 1378 560 ~ 1456
Net weight kg 589 634 634 634 740 740 740 740
Diameter cooling/refrigerant pipes mm (inch) Liquid side ø 5/8” (15.88) Liquid side: ø19.05 (3/4”)mm (inch) Gas side: ø31.75 (1.1/4”) (ø34.92 (1.3/8”) Gas side: ø38.1 (1.1/2”) (ø34.92 (1.3/8”)
Oil equalisation mm (inch) ø 3/8” (9.52)
26~40HP (73.5~112.0 kW)
112
Connect up to 80 indoor units/130% capacity
FDC 1200 KXZE1 (FDC400+FDC400+FDC400) 120.0 kWFDC 1250 KXZE1 (FDC400+FDC400+FDC450) 125.0 kWFDC 1300 KXZE1 (FDC400+FDC450+FDC450) 130.0 kWFDC 1350 KXZE1 (FDC450+FDC450+FDC450) 135.0 kWFDC 1425 KXZE1 (FDC475+FDC475+FDC475) 142.5 kW
› Maximum energy efficiency: COP 4.21 (42HP)
› Only DC Inverter compressors
› High split: up to 1000 m in total and with a maximum distance between the OU and the furthest IU of 160 m
FDC 1450 KXZE1 (FDC475+FDC475+FDC500) 145.0 kWFDC 1500 KXZE1 (FDC500+FDC500+FDC500) 150.0 kWFDC 1560 KXZE1 (FDC500+FDC500+FDC560) 156.0 kWFDC 1620 KXZE1 (FDC500+FDC560+FDC560) 162.0 kWFDC 1680 KXZE1 (FDC560+FDC560+FDC560) 168.0 kW
Total length: 1000 m
max. 10 m (equalisation pipe oil)
* With difference of length between the farthest indoor unit and the nearest one from the first branch pipe < 40 m (MAX 85 m)** Comply with installation conditions. For details, refer to the Technical Manual.
max. 0.4 m
Max height difference between IUs 18 m
Outdoor unit
max. 5 m
Indoor unit
Indoor unit
Indoor unit
Up to the first branch pipe: max 130 m
Furthest IU 160 m
From the first branch pipe to the furthest IU: 90 m*
Splitting height difference50 m (outdoor unit higher) –> 70 m**40 m (outdoor unit lower)
Operating range
Combinations
Modular outdoor units
Heat pumpVRF Multi system KXZ ADVANCED series
Models FDC1200KXZE1 FDC1250KXZE1 FDC1300KXZE1 FDC1350KXZE1 FDC1425KXZE1 FDC1450KXZE1 FDC1500KXZE1 FDC1560KXZE1 FDC1620KXZE1 FDC1680KXZE1
CombinationsFDC400KXZE1 FDC400KXZE1 FDC400KXZE1 FDC450KXZE1 FDC475KXZE1 FDC475KXZE1 FDC500KXZE1 FDC500KXZE1 FDC500KXZE1 FDC560KXZE1FDC400KXZE1 FDC400KXZE1 FDC450KXZE1 FDC450KXZE1 FDC475KXZE1 FDC475KXZE1 FDC500KXZE1 FDC500KXZE1 FDC560KXZE1 FDC560KXZE1FDC400KXZE1 FDC450KXZE1 FDC450KXZE1 FDC450KXZE1 FDC475KXZE1 FDC500KXZE1 FDC500KXZE1 FDC560KXZE1 FDC560KXZE1 FDC560KXZE1
Power supply Three-phase- 380-415V 50HzNominal Cool. capacity kW 120.00 125.00 130.00 135.00 142.5 145.00 150.00 156.00 162.00 168.00Cool. power consumption kW 32.88 35.9 38.92 41.94 41.94 41.93 41.91 44.56 47.21 49.86Rated energy efficiency coefficient in Cool. EER3 3.65 3.48 3.34 3.22 3.40 3.46 3.58 3.50 3.43 3.37Nominal Heat. capacity kW 135.00 140.00 145.00 150.00 159.00 162.00 168.00 175.00 182.00 189.00Heat. power consumption kW 32.07 33.88 35.69 37.5 39 39.49 40.47 42.93 45.39 47.85Rated energy efficiency coefficient in Heat. COP3 4.21 4.13 4.06 4.00 4.08 4.10 4.15 4.08 4.01 3.95Rated current in Cool. A 52.50 57.40 62.30 67.20 67.80 67.80 67.80 72.10 76.40 80.70Rated current in Heat. A 52.50 55.40 58.30 61.20 63.00 63.80 65.40 69.40 73.40 77.40
Indoor System Units Number of connectable IU from 3 to 80 from 3 to 80 from 3 to 80 from 3 to 80 from 3 to 80 from 3 to 80 from 3 to 80 from 3 to 80 from 3 to 80 from 3 to 80Total connectable capacity* 600 ~ 1560 625 ~ 1625 650 ~ 1690 675 ~ 1755 713 ~ 1852 725 ~ 1885 750 ~ 1950 780 ~ 2080 810 ~ 2106 840 ~ 2184
Net weight kg 951 951 951 951 1110 1110 1110 1110 1110 1110
Diameter cooling/refrigerant pipes mm (inch) Liquid side: ø19.05 (3/4”)mm (inch) Gas side: ø38.1 (1.1/2”) (ø34.92 (1.3/8”)
Oil equalisation mm (inch) ø 3/8” (9.52)
* When connecting the indoor units in the following series: FDK, FDFL, FDFU or FDFW, the power of the connectable indoor units cannot exceed 130%. 3. Value measured according to harmonised standard EN14511.
42~60HP (120.0~168.0 kW)
113
114
FDC 224 KXZXE1 22.4 kWFDC 280 KXZXE1 28.0 kWFDC 335 KXZXE1 33.5 kW
› Maximum energy efficiency: COP 4.61 (10HP)
› Only DC Inverter compressors
› High split: up to 1000 m in total and with a maximum distance between the OU and the furthest IU of 160 m
Connect up to 44 indoor units/200% capacity Connects up to 80 indoor units/160% (FDC 450 KXZE1 200%) capacity
Combinations 16~36HP (45.0~67.0 kW)
FDC 450 KXZXE1 (FDC224+FDC224)FDC 500 KXZXE1 (FDC224+FDC280)FDC 560 KXZXE1 (FDC280+FDC280)FDC 615 KXZXE1 (FDC280+FDC335)FDC 670 KXZXE1 (FDC335+FDC335)FDC 735 KXZXE1 (FDC224+FDC224+FDC280)FDC 800 KXZXE1 (FDC224+FDC280+FDC280)FDC 850 KXZXE1 (FDC280+FDC280+FDC280)FDC 900 KXZXE1 (FDC280+FDC280+FDC335)FDC 950 KXZXE1 (FDC280+FDC335+FDC335)FDC 1000 KXZXE1 (FDC335+FDC335+FDC335)
45.0 kW50.0 kW56.0 kW61.5 kW67.0 kW73.5 kW80.0 kW85.0 kW90.0 kW95.0 kW100.0 kW
Total length: 1000 m
max. 10 m (equalisation pipe oil)
* With difference of length between the farthest indoor unit and the nearest one from the first branch pipe < 40 m (MAX 85 m)
** Comply with installation conditions. For details, refer to the Technical Manual.
max. 0.4 m
Max height difference between IUs 18 m
Outdoor unit
max. 5 m
Indoor unit
Indoor unit
Indoor unit
Up to the first branch pipe: max 130 m
Furthest IU 160 m
From the first branch pipe to the furthest IU: 90 m*
Splitting height difference50 m (outdoor unit higher) –> 70 m**40 m (outdoor unit lower)
Operating range
CHARACTERISTICS Hi-COP
› High efficiency
› Low consumption
› High energy savings
VRF Multi system KXZX Hi-COP series
Modular outdoor units
Heat pump
FDC 224 KXZXE1 FDC 280~335 KXZXE1
8~12 HP (22.4~33.5 kW)
115
* When connecting the indoor units in the following series: FDK, FDFL, FDFU or FDFW, the power of the connectable indoor units cannot exceed 130%.
Combinations
VRF Multi system KXZX Hi-COP series
Models FDC224KXZXE1 FDC280KXZXE1 FDC335KXZXE1Nominal Cool. capacity kW 22.40 28.00 33.50Cool. power consumption kW 4.98 6.95 8.68Seasonal energy efficiency index in Cool. SEER2 7.58 7.27 7.41Rated energy efficiency coefficient in Cool. EER3 4.50 4.03 3.86Nominal Heat. capacity kW 25.00 31.50 37.50Heat. power consumption kW 5.56 6.83 8.39Seasonal energy efficiency index in Heat. SCOP2 4.86 4.91 4.86Rated energy efficiency coefficient in Heat. COP3 4.50 4.61 4.47Power Three-phase- 380-415V 50HzRated current in Cool. A 8.7 11.7 14.7Rated current in Heat. A 9.6 11.7 14.3Sound level dB(A) 56 56 62External dimensions (hxlxd) mm 1690×1350×720 2048×1350×720Exterior appearance (Munsell colour) Stucco white (4.2Y7.5 / 1.16) equivalentNet weight kg 280 325 325Refrigerant circuit/Compressor type and qty. GTC5150NC47LF×1 GUC5185ND47V×1Motor kW 3.23*1 4.60*1 5.72*1Starting method Direct, in line
Indoor System Units Number of connectable IU from 1 to 29 from 1 to 37 from 1 to 44Total connectable capacity* 180 ~ 448 224 ~ 560 268 ~ 670
Crankcase heater W 33*1 40*1 40*1Refrigerant circuit/Heat exchanger Pipes finned with Blue fin treatment and grooved internallyRefrigerant control Electronic expansion valveRefrigerant/GWP4 R410A/2088Quantity kg 11 11.5 11.5Tons of CO2 equivalent 22.97 24.01 24.01Refrigerant oil l 2.25 (M-MA32R) 2.9 (M-MA32R)Defrost control Micro -computerisedAir treatment/Fan type and quantity Axial fan x 2Motor W 386×2Starting method DirectAir flow (Standard) m3h 13200 13200 16800Available static pressure Pa Max 50Shock and vibration absorption Rubber vibration absorber (for compressor)Safety devices Compressor overheating protection/overcurrent/power transistor overheating protection/abnormal high pressure protection
Diameter cooling/refrigerant pipes mm (inch) Liquid side ø 3/8” (9.52) Liquid side ø 3/8” (9.52) Liquid side φ12.7 (1/2”)Gas side: ø19.05 (3/4”) Gas side ø 7/8” (22.22) Gas side: ø25.4 (1”) (ø22.22 (7/8”))
Joining method Gas side: brazing / Liquid side: flareCondensate drain Drain holes: ø20 × 10pcs., ø45 x 3pcs.Piping insulation Necessary (on both sides, liquid and gas)Accessories - - -
2. EU Regulation No.2281/2016 - - Value measured according to harmonised standard EN14825.3. Value measured according to harmonised standard EN14511.4. Refrigerant leakage contributes to climate change. When released into the atmosphere, refrigerants with a lower global warming potential (GWP) contribute less to global warming than those with a higher GWP. This appliance contains a
refrigerant with a GWP of 2088. If 1 kg of this refrigerant fluid were released into the atmosphere, therefore, the impact on global warming would be 2088 times higher than 1 kg of CO2, over a period of 100 years. Under no circumstances should the user try to intervene on the refrigerant circuit or disassemble the product. Always contact qualified personnel if necessary.
* When connecting the indoor units in the following series: FDK, FDFL, FDFU or FDFW, the power of the connectable indoor units cannot exceed 130%.3. Value measured according to harmonised standard EN14511.
Models FDC450KXZXE1 FDC500KXZXE1 FDC560KXZXE1 FDC615KXZXE1 FDC670KXZXE1 FDC735KXZXE1
CombinationsFDC224KXZXE1 FDC224KXZXE1 FDC280KXZXE1 FDC280KXZXE1 FDC335KXZXE1 FDC224KXZXE1FDC224KXZXE1 FDC280KXZXE1 FDC280KXZXE1 FDC335KXZXE1 FDC335KXZXE1 FDC224KXZXE1
- - - - - FDC280KXZXE1Power supply Three-phase- 380-415V 50HzNominal Cool. capacity kW 45.00 50.00 56.00 61.50 67.00 73.50Cool. power consumption kW 10 11.8 13.9 15.6 17.4 17.1Rated energy efficiency coefficient in Cool. EER3 4.50 4.24 4.03 3.94 3.85 4.30Nominal Heat. capacity kW 50.00 56.0 63.0 69.00 75.00 82.50Heat. power consumption kW 11.1 12.3 13.7 15.2 16.8 18.2Rated energy efficiency coefficient in Heat. COP3 4.50 4.55 4.60 4.54 4.46 4.53Rated current in Cool. A 17.50 20.00 23.50 26.40 29.30 29.40Rated current in Heat. A 19.20 21.20 23.30 26.00 28.60 31.40
Indoor System Units Number of connectable IU from 2 to 60 from 2 to 53 from 2 to 59 from 2 to 65 from 2 to 71 from 3 to 78Total connectable capacity* 360 ~ 900 400 ~ 800 448 ~ 896 492 ~ 984 536 ~ 1072 588 ~ 1176
Net weight kg 560 605 650 650 650 885
Diameter cooling/refrigerant pipes mm (inch) Liquid side ø 1/2” (12.7) Liquid side ø 5/8” (15.88) Liquid side ø 1/2” (12.7) Liquid side ø 5/8” (15.88)mm (inch) Gas side: ø28.58 (1.1/8”) Gas side: ø31.75 (1.1/4”) (ø34.92 (1.3/8”)
Oil equalisation mm (inch) ø 3/8” (9.52)
Models FDC800KXZXE1 FDC850KXZXE1 FDC900KXZXE1 FDC950KXZXE1 FDC1000KXZXE1
CombinationsFDC224KXZXE1 FDC280KXZXE1 FDC280KXZXE1 FDC280KXZXE1 FDC335KXZXE1FDC280KXZXE1 FDC280KXZXE1 FDC280KXZXE1 FDC335KXZXE1 FDC335KXZXE1FDC280KXZXE1 FDC280KXZXE1 FDC335KXZXE1 FDC335KXZXE1 FDC335KXZXE1
Power supply Three-phase- 380-415V 50HzNominal Cool. capacity kW 80 85.0 90 95.0 100.0Cool. power consumption kW 19.3 21.1 22.7 24.3 25.9Rated energy efficiency coefficient in Cool. EER3 4.15 4.03 3.96 3.91 3.86Nominal Heat. capacity kW 90.0 95.0 100 106.0 112.0Heat. power consumption kW 19.7 20.6 21.9 23.5 25.1Rated energy efficiency coefficient in Heat. COP3 4.57 4.61 4.57 4.51 4.46Rated current in Cool. A 32.90 35.60 38.40 41.00 43.70Rated current in Heat. A 33.50 35.20 37.40 40.10 42.80
Indoor System Units Number of connectable IU from 3 to 80 from 3 to 80 from 3 to 80 from 3 to 80 from 3 to 80Total connectable capacity* 640 ~ 1280 680 ~ 1360 720 ~ 1440 760 ~ 1520 800 ~ 1600
Net weight kg 930 975 975 975 975
Diameter cooling/refrigerant pipes mm (inch) Liquid side ø 5/8” (15.88)mm (inch) Gas side: ø31.75 (1.1/4”) (ø34.92 (1.3/8”) Gas side: ø38.1 (1.1/2”)
Oil equalisation mm (inch) ø 3/8” (9.52)
116
Diagrams and measurementsAll measurements are in mm.
rear
View of refrigerant connections
References for the dimensions of the holes of the fixing bolts
Incoming air
D (bottom)
C (front) C (right)
D (right)
C (rear)
D (front)
Label with instructions
Box for power cable wiring
Box for signal cable wiring
7-segment displayinspection hole
D (left)
C (bottom)
Drain pipe
Installation spaces
H3
H4H1Intake
Intake
Intak
e
H2
Intake
Notes:(1) Secure the unit using anchor bolts(2) Allow at least 2 m clearance above the unit(3) The adhesive label with the installation data should be positioned under the front panel (right side)(4) The inlet openings for the electrical and refrigerant connections are pre-cut (open using a cutter)(5) For the piping inlet, use the ø 88 hole(6) Use the fixing holes (M10) indicated with “L” and “J” when replacing an outdoor unit belonging to the old series(7) Connect the refrigerant oil compensation pipe (“K”) when using in combination with the outdoor unit
Ref. Item FDC224KXZXE1A Gas side pipe fitting ø 19.05 (3/4”) (brazing)B Liquid side pipe fitting ø 9.52 (3/8”) (flare)C Refrigerant pipe outlet ø 88 (or ø 100)D Power cable inlet ø 50 (right - left - front), slot 40 x 80 (at bottom)F Fixing bolt hole M10 x 4 holesG Condensate drain pipe connection ø 4 5 x 3 holesH Condensate drain ø 20 x 10 holesK Refrigerant oil compensation pipe connection ø 9.52 (3/8”) flareL Opening for movement 230 x 60
Example of installationDimensions 1 2
L1 500 openL2 10(30) 10(30)L3 100 100L4 10(30) openH1 1500 openH2 unlimited unlimitedH3 1000 unlimitedH4 unlimited open
Modular outdoor units
Heat pumpVRF Multi system KXZX Hi-COP series
FDC 224 KXZXE1
117
Diagrams and measurementsAll measurements are in mm.
rearView of refrigerant connections
References for the dimensions of the holes of the fixing boltsIncoming air
D (bottom)
C (front) C (right)
D (right)
C (rear)
D (front)
Label with instructions
Box for power cable wiring
Box for signal cable wiring
7-segment displayinspection hole
D (left)
C (bottom)
Drain pipe
Installation spaces
H3
H4H1Intake
Intake Intak
e
H2
Intake
Notes:(1) Secure the unit using anchor bolts(2) Allow at least 2 m clearance above the unit(3) The adhesive label with the installation data should be positioned under the front panel (right side)(4) The inlet openings for the electrical and refrigerant connections are pre-cut (open using a cutter)(5) For the piping inlet, use the ø 88 hole(6) Use the fixing holes (M10) indicated with “L” and “J” when replacing an outdoor unit belonging to the old series(7) Connect the refrigerant oil compensation pipe (“K”) when using in combination with the outdoor unit
Ref. Item FDC280KXZXE1 FDC335KXZXE1A Gas side pipe fitting ø 22.22 (7/8”) (brazing) ø 25.4 (1”) (brazing)B Liquid side pipe fitting ø 9.52 (3/8”) (flare) ø 12.7 (1/2”) (flare)C Refrigerant pipe outlet ø 88 (or ø 100)D Power cable inlet ø 50 (right - left - front), slot 40 x 80 (at bottom)F Fixing bolt hole M10 x 4 holesG Condensate drain pipe connection ø 45 x 3 holesH Condensate drain ø 20 x 10 holesK Refrigerant oil compensation pipe connection ø 9.52 (3/8”) flareL Opening for movement 230 x 60
Example of installationDimensions 1 2
L1 500 openL2 10(30) 10(30)L3 100 100L4 10(30) openH1 1500 openH2 unlimited unlimitedH3 1000 unlimitedH4 unlimited open
VRF Multi system KXZX Hi-COP series
FDC 280~335 KXZXE1
118
VRF Multi system KXZR 3-PIPE seriesHeat recovery
Simultaneous heating and coolingThese heat recovery systems work with 3 interconnecting pipes and therefore are commonly referred to as "3-pipe" systems. These systems offer both heating and cooling in a single indoor unit, based on the room conditions/requirements. The systems incorporate a highly sophisticated air conditioning control for multiple indoor areas, regardless of the cooling or heating needs, for applications where the building orientation (N, S, E, W) may result in a heat increase/loss on different sides of the same building.The range starts from a cooling capacity of 22.4 kW and goes up to 20HP with a cooling capacity of 56.0 kW. The outdoor units can also be combined in "pairs" or in "triple combination", reaching 60 HP/168.0 kW on a single system.
During defrost or during automatic compressor protection, activated every hour during heating, the heating operation stops and restarts temporarily after a specific time interval. The series is equipped with the same automatic compressor protection even in cooling mode. During this protection period, only the air flow is active and the cooling operation restarts at the end of a specific time interval.
DESIGN FLEXIBILITYTotal power of the indoor units
HP KXZR8~16 200%
17~34 160%36~60 130%
HP KXZRX16 200%
18~34 160%36 130%
• Where total power is higher than 130%, an additional refrigerant charge is required on site.
* With 8-34HP systems, if one or more of the FDK, FDFL, FDFU and/or FDFW series are connected to the system, the total power of the indoor units cannot exceed 130%.
Connectable indoor unitsIt is possible to connect up to 80 indoor units to the outdoor unit of greater power size. 16 different types of indoor units are available, visible or recessed, in different sizes, for a total of 91 overall possibilities.
Heat recovery systems
The KXZR series has an an extensible system design, considering a heating range at low temperature conditions down to -20°C, and a cooling range up to 46°C (previous model: 43°C).
HEATING
Cooling
The interconnection piping system has a unique arrangement with two of the interconnecting pipes passing through an PFD distribution controller and the third tube connected directly to each indoor unit from the main pipe path. This reduces installation times and the number of braze-welded connections on the site. The PFD distribution controllers are available for single connection or as a 4-way combined PFD connection, with each connected unit characterised by independent cooling or heating.
Outdoor unit
Wide operating range
CompressorAccumulator
Balanced cooling and heating operationReceiver
High pressure gas
Low pressure gas
Indoor unit Indoor unit Indoor unit Indoor unit
Flow divider
This model is not suitable for the use of annual cooling operations, for example for the server room, especially in areas where the outdoor air temperature falls below 5°C. In case of mixed operation in cooling and heating with outdoor air temperature lower than 5°C, the cooling power can decrease with respect to the operating power in cooling mode only.
NEW
119
VRF Multi system KXZR 3-PIPE seriesHeat recovery
Continuous control of the heating power reduces compressor frequency by modulating it at the minimum speed for a longer period of time. The total number of defrost cycles is considerably reduced, increasing the total power delivered and ensuring high comfort.
Improved cooling capacity at low outdoor temperatureThe small partitions of the exchanger and the internal pressure control allow the outdoor unit to operate in cooling mode even in low ambient temperature conditions, for greater capacity in very low environmental conditions (-5°C) compared to the previous model.
2-partition heat plate exchanger
KXZRE1
Exchanger resizing allows for better control of the pressure at low load regimes.
In the previous model, in the presence of a strong heating demands and simultaneous low cooling demands in low ambient temperature conditions, the pressure control is adjusted to maintain a greater heating power compared to a sufficient cooling power.The new heat exchanger and pressure control adopted in the KXZR series has simultaneously improved its capacity for both heating and cooling power *. * The cooling system has priority for the required heating mode compared to a very low cooling demand, where most of the indoor units are used in heating mode.
previous model
KXZRE1
Time
During simultaneous cooling and heating at an outside temperature of -5°C.
Continuous heating up to 5 hours without outside temperature constraints
CONTINUOUS HEATING POWER CONTROL
Delivery air temperature in the cooled room
Output temperature from indoor units °C
defrost defrost defrost
Traditional control
Output temperature from indoor units °C
defrost defrost
Continuous control of heating power and overall increase of supplied power
Output temperature from indoor units °C
Imperceptible temperature oscillation
300 minutes
Previous mode
The 4-partition heat exchanger reduces dimensions.
120
DIS-22-1-RG(RB)DIS-180-1-RG(RB)
DOS-2A-3-R
Single outdoor unit
YES
vertical
horizontal
floor
floor
floor
floor
NO
NO
YESBranch pipes Manifolds
HP 8 10 12 14 16 17 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60Liquid side
Furthest IU =<90 m
ø 9.52 ø 12.7 ø 15.88 ø 19.05Intake gas ø 19.05 ø 22.22 ø 28.58 ø 34.92Delivery gas ø 15.88 ø 19.05 ø 22.22 ø 28.58Liquid side
Furthest IU => 90 m
ø 12.7 ø 15.88 ø 19.05 ø 22.22Intake gas ø 22.22 ø 28.58 ø 34.92Delivery gas ø 15.88 ø 19.05 ø 22.22 ø 28.58
If the longest distance (measured between the outdoor unit and the furthest indoor unit) is 90 m or more (actual length), change the size of the main pipe according to the following table.
Even if the longest distance exceeds 90 m (actual length), it is not necessary to change the size of the exhaust gas pipes.
Heat recoveryVRF Multi system KXZR 3-PIPE series
REFRIGERANT CONNECTIONSVRF-T systems are manufactured to the highest standards of quality and reliability and it is therefore essential for the installation procedures and materials to have the same qualitative features, to ensure trouble-free long-term operation. It is advisable to use high quality copper refrigerant piping, in coils or in straight, semi-rigid lengths. The copper piping should be chosen considering the higher operating pressure of R410A refrigerant gas and the increased pressure circulating in the system produced by reverse cycle operation. All materials used must comply with European standards (EN 12735). The branch pipe kits supplied must be used to connect the indoor units and the manifold kits must be used to connect the outdoor units (if necessary). It is forbidden to use standard accessories (elbow pipes, T-joints etc.). The branch pipes must be installed according to manufacturer guidelines and must allow a continuous flow of refrigerant in accordance with European standard E378:2017.All connecting welds must be made under slight nitrogen pressure to prevent the oxidation of the inner surface of the copper pipes. During installation, no accidental entry of condensate, dust or any other contaminant must be permitted. Once installation is complete, a leak test must be carried out to check for refrigerant leaks with pressurised nitrogen. The ends of the pipe must be bent and welded and an appropriate service valve affixed.
Additional refrigerant chargeOnly R410A refrigerant gas must be used, and this must be added by weight using an electronic meter. The amount of additional refrigerant must be carefully calculated according to the manufacturer’s guidelines, defined by the length and diameter of each section of the system piping.
NEW
121
DOS-2A-3-R DOS-2A-3-R
Combined outdoor units
First branch pipe of the indoor unitTotal capacity of indoor units
Set of branch pipes
~179 DIS-22-1-RG(RB)180~370 DIS-180-1-RG(RB)371~539 DIS-371-2-RG(RB)540~ DIS-540-2-RG
Set of outdoor unit branch pipesOutdoor unit Set of branch pipes2 units (for 735 ~ 1120) DOS-2A-3-R3 units (for 1200 ~ 1680) DOS-3A-3-R
Downstream of the PFDTotal capacity of indoor units
Set of branch pipes
~179 DIS-22-1-G(B)180~370 DIS-180-1-G(B)371~539 DIS-371-1-G(B)540~ DIS-540-3
Refrigerant oil compensation pipe Refrigerant oil compensation
pipe
ELECTRICAL CONNECTIONSVRF MHI systems require highly simplified electrical connections to the indoor units, thanks to a control circuit that uses 2 non-polarised conductors. The supply system has wiring that can be connected on the front, right, left or rear of the outdoor unit. For three-phase outdoor units and single phase indoor units, a separate power supply must be used. The interaction between the outdoor unit and indoor unit takes place via the control device only.
Outdoor unit power supply: three-phase, 4 wires, 380~415V Separate power system
Outd
oor u
nitEarth leakagebreaker
Circuitbreaker Ground
A Main power supply cable (4 wires)B Signal lines - Superlink (2 wires)C Indoor units power cable (2 wires)D Cables for the wired remote control (2 wires)
Earth leakagebreaker
Circuitbreaker
Indoor unit
wired remote control
Indoor unit power supply: single phase 220~240V
IMPORTANT: if the RCD is dedicated solely to protecting against leakage to earth, it will be necessary to install a circuit breaker.
VRF Multi system KXZR 3-PIPE seriesHeat recovery
REFRIGERANT CONNECTIONS
122
PFD 1124-E, PFD 1804-E, PFD 2804-E, PFD 1124X4-E
Designed and manufactured at Mitsubishi Heavy Industries specialist research laboratories, the PFD flow divider now enables all indoor units to be integrated into an air conditioning network, to switch from cooling mode to heating mode, or vice versa, while the whole system remains operational, thus preventing costly power on and power off cycles. In case of conversion from cooling mode to heating mode and vice versa, by simply combining the indoor unit and the PFD box, the sound level is reduced, thanks to the shutdown of the compressor which, however, does not lead to any reduction in capacity. The risk of refrigerant leaks is reduced by changing the welding method between the refrigerant piping and the PFD box. By using the optional extension cable for the PFD box, equipped with a connector, it is possible to further separate the PFD box from the indoor unit. This enables a reduction in sound level caused by the PDF box and the flow of refrigerant.
Relay kit4-outlet PFD
FLOW DIVIDER
Heat recoveryVRF Multi system KXZR 3-PIPE series
ELECTRICAL CONNECTIONS
The maximum number of indoor units that can be connected to a signal line is 128, and it is possible to create groups of outdoor and/or indoor units connected to the same outdoor unit or to separate outdoor units, as long as they are connected to the same signal line. The signal line can also be connected by adopting the method described below (multiple connectors).
0.75 mm2 1.25 mm2~1000 mm YES YES
1000~1500 mm YES NO
Signal lineSingle outdoor unit
Combined outdoor units
OU signal terminal board
IU signal terminal board
The signal lines have no polarity therefore the connections listed below are permitted
Signal lines
The signal line is 5 VDC and uses 2 non-polarised conductors marked A1 and B1. AB connects the outdoor unit to the indoor unit and vice versa. For the signal line with 2 conductors, use shielded cables measuring 0.75 or 1.25 mm2. Earth the shield on all the indoor
and outdoor units.If using combined outdoor units, connect:• Thesignallinebetweenindoorand
outdoor units, and the signal line between outdoor units that belong to the same
refrigerant line, to A1 and B1;• Thesignallinebetweenoutdoor
units belonging to a different refrigerant line to A2 and B2.
OU OU OU
IU
IU
IU
IU
IMPORTANT: A loop connection of the signal lines is NOT ALLOWED
A loop cannot be formed with the signal, therefore the section of the connection indicated with ........is not permitted
OU
IU
OUOUOU
IUIUIU
OU
IU
OU OU
IU IU
IU IU IU
Length (m) Type of cables100~200 0.5 mm2 x 2 wires
~300 0.75 mm2 x 2 wires~400 1.25 mm2 x 2 wires~600 2.0 mm2 x 2 wires
The specifications for the connection between the wired remote control and the indoor units (XY connection) are 0.3 mm2 x 2 wires. The maximum permitted length is 600 m. If the length exceeds 100 m, refer to the table.
Wired remote control
NEW
123
PFD 1124-E, PFD 1804-E, PFD 2804-E, PFD 1124X4-E
PFD
240V AC
kit
220/240V AC 12V DC
SC-SL1N/2NA/4-AE
FLOW DIVIDER
The remote control settings (such as power on/off of single indoor units, temperature setting, as well as controlling the heating/cooling procedures) are possible via a remote control connected to each indoor unit. At the same time, together with the individual remote control, the SC-SL1N/2NA/4-AE centralised control panels can also be used. For more details, refer to the Installation Manual.
Selection and control from centralised panel
Ease of installationThe design PFD flow divider makes it possible to connect the liquid line of the indoor unit directly from the liquid piping coming from the outdoor unit, therefore bypassing the PFD. This reduces the number of connections per indoor unit and, consequently, installation times and costs. Groups of indoor units up to a total capacity of 44.8 kW (11.2 kW x 4) can be connected to a single PFD by means of branch pipes, therefore the units in this group will all operate in the same mode,cooling or heating. The PFD1124X4-E 4-pipe control device, able to connect up to 4 indoor units with individual operation - simultaneous cooling or heating - is also available. The PFD flow divider is connected to the indoor unit with a 3-wire signal cable via a relay kit (supplied) to be installed within a maximum distance of 2 metres. The indoor unit, on the other hand, can be installed up to a distance of 40 m. The PFD electric power supply may derive directly from the indoor unit or from other sources.
IU
up to 2 m
the maximum distance between the PFD and the IU cannot exceed 40 m
PFD Relay
OU
IU
Delivery gas side
Intake gas side
Gas side
Liquid side
Flow divider Total IU power downstream Indoor units that can be connected*PFD1124-E less than 11.2 kW 1-5PFD1804-E less than 18.0 kW 1-8PFD2804-E less than 28.0 kW 1-10
PFD1124X4-E less than 44.8 kW (11.2 kW x 4) up to 20
VRF Multi system KXZR 3-PIPE seriesHeat recovery
* Refer to the technical manuals for specifications.
124
Connects up to 44 indoor units/200% capacity
FDC 224 KXZRE1 22.4 kWFDC 280 KXZRE1 28.0 kWFDC 335 KXZRE1 33.5 kW
› Maximum energy efficiency: COP 4.84
› The units use a Multi-port DC Inverter compressor with concentrated electric winding
› High split: up to 1000 m in total and with a maximum distance between the OU and the furthest IU of 160 m
Heat recoveryModular outdoor units
VRF Multi system KXZR 3-PIPE series
Models FDC224KXZRE1 FDC280KXZRE1 FDC335KXZRE1Nominal Cool. capacity kW 22.40 28.00 33.50Cool. power consumption kW 5.15 8.08 9.98Seasonal energy efficiency index in Cool. SEER1 6.27 6.11 7.00Rated energy efficiency coefficient in Cool. EER2 4.35 3.47 3.36Nominal Heat. capacity kW 22.40 31.50 37.50Heat. power consumption kW 4.62 8.11 9.55Seasonal energy efficiency index in Heat. SCOP1 4.06 4.02 4.84Rated energy efficiency coefficient in Heat. COP2 4.85 3.88 3.93Power Three-phase- 380-415V 50HzRated current in Cool. A 9.00 12.90 15.90Rated current in Heat. A 8.00 12.80 15.50Sound pressure level dB(A) 55 55 61Sound power level dB(A) 73 74 81External dimensions (HxLxD) mm 1690x1350x720Exterior appearance (Munsell colour) Stucco white (4.2Y7.5 / 1.1) equivalentNet weight kg 289 289 289Refrigerant circuit/Compressor type and qty. GTC5150NC47LFMotor kW 3.41x1 4.80x1 6.54x1Starting method Direct, in line
Indoor System Units Number of connectable IU from 1 to 29 from 1 to 37 from 1 to 44Total connectable capacity 112 - 448 140 - 560 167 - 670
Crankcase heater W 33x1Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveRefrigerant/GWP3 R410A/2088Quantity kg 11.50 11.50 11.50Tons of CO2 equivalent 24.01 24.01 24.01Refrigerant oil l 2.35 (M-MA32R)Defrost control ComputerisedAir treatment/Fan type and quantity Axial fan x 2Motor W 386x2Starting method DirectAir flow (Standard) m3h 13200 16800Shock and vibration absorption Rubber vibration absorber (for compressor)Safety devices Compressor overheating protection/overcurrent/power transistor overheating protection/abnormal high pressure protectionDiameter cooling/refrigerant pipesLiquid side mm (inch) ø9.52 (3/8”) ø12.7 (1/2”)Delivery gas line mm (inch) ø19.05 (3/4”) ø22.22 (7/8”) ø25.4 (1”) (ø22.22 7/8”)Intake gas line mm (inch) ø15.88 (5/8”) ø19.05 (3/4”)Joining method Gas side brazing / Liquid side flareCondensate drain Drain holes ø20 x 6pcs., ø45 x 3pcs.Piping insulation Necessary (on both sides, liquid and gas)Accessories - - -
1. EU Regulation No.2281/2016 - - Value measured according to harmonised standard EN14825.2. Value measured according to harmonised standard EN14511.3.Refrigerant leakage contributes to climate change. When released into the atmosphere, refrigerants with a lower global warming potential (GWP) contribute less to global warming than those with a higher GWP. This appliance contains a
refrigerant with a GWP of 2088. If 1 kg of this refrigerant fluid were released into the atmosphere, therefore, the impact on global warming would be 2088 times higher than 1 kg of CO2, over a period of 100 years. Under no circumstances should the user try to intervene on the refrigerant circuit or disassemble the product. Always contact qualified personnel if necessary.
NEW
8~12HP (22.4~33.5 kW)
125
Operating rangeTotal length: 1000 m
Outdoor unit
Up to the first branch pipe: max 130 m
Indoor unit
Indoor unit
Indoor unitFrom the first branch pipe to the furthest IU: 90 m*
* With difference of length between the farthest indoor unit and the nearest one from the first branch pipe < 40 m.
Furthest IU 160 m
Max height difference between IUs 18 m
Splitting height difference50 m (outdoor unit higher) 40 m (outdoor unit lower)
Diagrams and measurementsAll measurements are in mm.
(left)
(front)
(front)(right)
(right)
(right)
Label
7-segment display
bottomback - view of refrigerant connections
Box for signal cable wiring
Box for power cable wiring
Intak
e
IntakeInt
ake
Service spaces
Incoming air
Drain pipe
H1
H3
H4H2
Example of installation
Dimensions 1 2L1 500 openL2 10(30) 10(30)L3 100 100L4 10(30) openH1 1500 openH2 unlimited unlimitedH3 1000 unlimitedH4 unlimited open
Ref. Item 224 280 335A Intake gas piping connection ø 19.05 (3/4")(brazing) ø 22.22 (7/8")(brazing) ø 25.4 (1”) (brazing)B Liquid side pipe fitting ø 9.52 (flare) ø 12.7 (flare)C Delivery gas piping connection ø 15.88 (3/8")(brazing) ø 19.05 (3/4")(brazing)D Power cable inlet ø 50 (right-left-front), 40x80 (lower side)F Fixing bolt hole M10 x 4 holesG Condensate drain pipe connection ø 45 x 3 holesH Condensate drain ø 20 x 10 holesK Refrigerant oil compensation pipe connection ø 9.52 (3/8”) (flare)L Opening for movement 230 x 60N Refrigerant pipe outlet ø 88 (or ø 100)
VRF Multi system KXZR 3-PIPE seriesNEW
126
Connects up to 71indoor units and up to 160% capacity (200% for FDC 400~450)
› Maximum energy efficiency: COP 4.10
> The units use a Multi-port DC Inverter compressor with concentrated electric winding
› High split: up to 1000 m in total and with a maximum distance between the OU and the furthest IU of 160 m
FDC 400 KXZRE1 40.0 kWFDC 450 KXZRE1 45.0 kWFDC 475 KXZRE1 47.5 kW
FDC 500 KXZRE1 50.0 kWFDC 560 KXZRE1 56.0 kWFDC 615 KXZRE1 61.5 kW
FDC 670 KXZRE1 67.0 kW
Heat recoveryModular outdoor units
VRF Multi system KXZR 3-PIPE series
1. EU Regulation No.2281/2016 - - Value measured according to harmonised standard EN14825.2. Value measured according to harmonised standard EN14511.3.Refrigerant leakage contributes to climate change. When released into the atmosphere, refrigerants with a lower global warming potential (GWP) contribute less to global warming than those with a higher GWP. This appliance contains a
refrigerant with a GWP of 2088. If 1 kg of this refrigerant fluid were released into the atmosphere, therefore, the impact on global warming would be 2088 times higher than 1 kg of CO2, over a period of 100 years. Under no circumstances should the user try to intervene on the refrigerant circuit or disassemble the product. Always contact qualified personnel if necessary.
Models FDC400KXZRE1 FDC450KXZRE1 FDC475KXZRE1 FDC500KXZRE1 FDC560KXZRE1 FDC615KXZRE1 FDC670KXZRE1Nominal Cool. capacity kW 40.00 45.00 47.50 50.00 56.00 61.50 67.00Cool. power consumption kW 11.55 14.45 14.82 15.19 18.31 21.35 25.51Seasonal energy efficiency index in Cool. SEER1 6.34 6.04 6.60 7.01 6.25 5.79 5.78Rated energy efficiency coefficient in Cool. EER2 3.46 3.11 3.21 3.29 3.06 2.88 2.63Nominal Heat. capacity kW 40.00 45.00 47.50 50.00 56.00 61.50 63.00Heat. power consumption kW 9.76 11.38 11.58 12.17 14.33 16.15 17.47Seasonal energy efficiency index in Heat. SCOP1 4.22 4.33 4.27 4.54 4.29 4.34 4.66Rated energy efficiency coefficient in Heat. COP2 4.10 3.95 4.10 4.11 3.91 3.81 3.61Power Three-phase- 380-415V 50HzRated current in Cool. A 18.50 23.20 24.00 24.60 29.60 34.60 41.30Rated current in Heat. A 16.00 18.60 18.80 19.70 23.20 26.20 28.30Sound pressure level dB(A) 60 62 61 61 64 65 65Sound power level dB(A) 81 82 81 81 84 84 84External dimensions (HxLxD) mm 2048x1350x720Exterior appearance (Munsell colour) Stucco white (4.2Y7.5 / 1.1) equivalentNet weight kg 357 410Refrigerant circuit/Compressor type and qty. GUC5185ND47V GTC5150NC47LF×2Motor kW 7.92×1 9.73×1 4.53×2 4.84×2 5.79×2 7.05×2 9.87×2Starting method Direct, in line
Indoor System Units Number of connectable IU from 1 to 53 from 1 to 60 from 1 to 50 from 1 to 53 from 1 to 59 from 1 to 65 from 1 to 71Total connectable capacity 200 - 800 225 - 900 240 - 760 250 - 800 280 - 896 308 - 984 335 - 1172
Crankcase heater W 40 33×2Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveRefrigerant/GWP3 R410A/2088Quantity kg 11.50Tons of CO2 equivalent 24.01Refrigerant oil l 3.3 (M-MA32R) 4.4 (M-MA32R)Defrost control ComputerisedAir treatment/Fan type and quantity Axial fan x 2Motor W 386x2Starting method DirectAir flow (Standard) m3h 16800 18600Shock and vibration absorption Rubber vibration absorber (for compressor)Safety devices Compressor overheating protection/overcurrent/power transistor overheating protection/abnormal high pressure protectionDiameter cooling/refrigerant pipesLiquid side mm (inch) ø12.7 (1/2”)Delivery gas line mm (inch) ø25.4 (1”) (ø28.58 1-1/8”) ø28.58 (1 - 1/8”)Intake gas line mm (inch) ø22.22 (7/8”) ø25.4 (1”) (ø22.22 7/8”)Joining method Gas side brazing / Liquid side flareCondensate drain Drain holes ø20 x 6pcs., ø45 x 3pcs.Piping insulation Necessary (on both sides, liquid and gas)Accessories - - - - - - -
NEW
14~24HP (40.0~67.0 kW)
127
Operating rangeTotal length: 1000 m
Outdoor unit
Up to the first branch pipe: max 130 m
Indoor unit
Indoor unit
Indoor unitFrom the first branch pipe to the furthest IU: 90 m*
* With difference of length between the farthest indoor unit and the nearest one from the first branch pipe < 40 m.
Furthest IU 160 m
Max height difference between IUs 18 m
Splitting height difference50 m (outdoor unit higher) 40 m (outdoor unit lower)
Diagrams and measurementsAll measurements are in mm.
rear
View of refrigerant connections
References for the dimensions of the holes of the fixing boltsIncoming air
D (bottom)
C (front) C (right)
D (right)
C (rear)
D (front)
Label with instructions
Box for power cable wiring
Box for signal cable wiring
7-segment displayinspection hole
D (left)
C (bottom)
Drain pipe
Installation spaces
H3
H4H1Intake
Intak
e
H2
Intake
Intake
Example of installation
Dimensions 1 2L1 500 openL2 10(30) 10(30)L3 100 100L4 10(30) openH1 1500 openH2 unlimited unlimitedH3 1000 unlimitedH4 unlimited open
Ref. Item 400 450 475 500 560 615 670A Intake gas piping connection ø 25.4 (1”) (brazing) ø 28.58 (1 - 1/8") (brazing)B Liquid side pipe fitting ø 12.7 (flare)C Delivery gas piping connection ø 22.22 (7/8")(brazing) ø 25.4 (1”) (brazing)D Power cable inlet ø 50 (right-left-front), 40x80 (lower side)F Fixing bolt hole M10 x 4 holesG Condensate drain pipe connection ø 45 x 3 holesH Condensate drain ø 20 x 10 holesK Refrigerant oil compensation pipe connection ø 9.52 (3/8”) (flare)L Opening for movement 230 x 60N Refrigerant pipe outlet ø 88 (or ø 100)
VRF Multi system KXZR 3-PIPE seriesNEW
128
Operating rangeTotal length: 1000 m
Outdoor unit
Up to the first branch pipe: max 130 m
Indoor unit
Indoor unit
Indoor unitFrom the first branch pipe to the furthest IU: 90 m*
* With difference of length between the farthest indoor unit and the nearest one from the first branch pipe < 40 m.
Furthest IU 160 m
Max height difference between IUs 18 m
Splitting height difference50 m (outdoor unit higher) 40 m (outdoor unit lower)
Connects up to 80 indoor units and up to 160% capacity (FDC 735~950) and up to 130% capacity (FDC 1000~1120)
› Maximum energy efficiency: COP 4.12› The units use a Multi-port DC Inverter compressor with concentrated electric winding
› High split: up to 1000 m in total and with a maximum distance between the OU and the furthest IU of 160 m
FDC 735 KXZRE1 (FDC335+FDC400) 73.5 kWFDC 800 KXZRE1 (FDC400+FDC400) 80.0 kWFDC 850 KXZRE1 (FDC400+FDC450) 85.0 kWFDC 900 KXZRE1 (FDC450+FDC450) 90.0 kW
FDC 950 KXZRE1 (FDC475+FDC750) 95.0 kWFDC 1000 KXZRE1 (FDC500+FDC500) 100.0 kWFDC 1060 KXZRE1 (FDC500+FDC560) 106.0 kWFDC 1120 KXZRE1 (FDC560+FDC560) 112.0 kW
Heat recoveryModular outdoor units
VRF Multi system KXZR 3-PIPE series
Combinations
1. Value measured according to harmonised standard EN14511.
Models FDC735KXZRE1 FDC800KXZRE1 FDC850KXZRE1 FDC900KXZRE1 FDC950KXZRE1 FDC1000KXZRE1 FDC1060KXZRE1 FDC1120KXZRE1
Combined units FDC335KXZRE1 FDC400KXZRE1 FDC400KXZRE1 FDC450KXZRE1 FDC475KXZRE1 FDC500KXZRE1 FDC500KXZRE1 FDC560KXZRE1FDC400KXZRE1 FDC400KXZRE1 FDC450KXZRE1 FDC450KXZRE1 FDC475KXZRE1 FDC500KXZRE1 FDC560KXZRE1 FDC560KXZRE1
Power supply Three-phase- 380-415V 50HzNominal Cool. capacity kW 73.50 80.00 85.0 90.0 95.0 100.0 106.0 112.0Cool. power consumption kW 21.20 23.10 26.00 28.90 29.60 30.40 33.50 36.60Rated energy efficiency coefficient in Cool. EER1 3.47 3.46 3.27 3.11 3.21 3.29 3.16 3.06Nominal Heat. capacity kW 73.5 80.0 85 90.0 95.0 100.0 106.0 112.0Heat. power consumption kW 17.90 19.50 21.1 22.8 23.2 24.3 26.5 28.7Rated energy efficiency coefficient in Heat. COP1 4.11 4.10 4.03 3.95 4.09 4.12 4.00 3.90Rated current in Cool. A 34.30 37.00 41.70 46.40 48.00 49.20 54.20 59.20Rated current in Heat. A 29.30 32.00 34.60 37.20 37.60 39.40 49.20 46.40Net weight kg 646 714 714 714 820 820 820 820Diameter cooling/refrigerant pipesLiquid side mm (inch) ø15.88 (5/8”)Delivery gas line mm (inch) ø31.75 (1-1/4”) ø34.92 (1-3/8”) ø38.1 (1-1/2”) ø34.92 (1-3/8”)Intake gas line mm (inch) ø25.4 (1”) ø28.58 (1-1/8”) ø28.58 (1-1/8”) ø31.75 (1-1/4”) ø28.58 (1-1/8”)Oil equalisation mm (inch) ø9.52 (3/8”)Accessories -
NEW
26~40HP (73.5~112.0 kW)
129
Operating rangeTotal length: 1000 m
Outdoor unit
Up to the first branch pipe: max 130 m
Indoor unit
Indoor unit
Indoor unitFrom the first branch pipe to the furthest IU: 90 m*
* With difference of length between the farthest indoor unit and the nearest one from the first branch pipe < 40 m.
Furthest IU 160 m
Max height difference between IUs 18 m
Splitting height difference50 m (outdoor unit higher) 40 m (outdoor unit lower)
Connects up to 80 indoor units/130% capacity
› Maximum energy efficiency: COP 4.11
› The units use a Multi-port DC Inverter compressor with concentrated winding
› High split: up to 1000 m in total and with a maximum distance between the OU and the furthest IU of 160 m
FDC 1200 KXZRE1 (FDC400+FDC400+FDC400) 120.0 kWFDC 1250 KXZRE1 (FDC400+FDC400+FDC450) 125.0 kWFDC 1300 KXZRE1 (FDC400+FDC450+FDC450) 130.0 kWFDC 1350 KXZRE1 (FDC450+FDC450+FDC450) 135.0 kWFDC 1425 KXZRE1 (FDC475+FDC475+FDC475) 142.5 kW
FDC 1450 KXZRE1 (FDC475+FDC475+FDC500) 145.0 kWFDC 1500 KXZRE1 (FDC500+FDC500+FDC500) 150.0 kWFDC 1560 KXZRE1 (FDC500+FDC500+FDC560) 156.0 kWFDC 1620 KXZRE1 (FDC500+FDC560+FDC560) 162.0 kWFDC 1680 KXZRE1 (FDC560+FDC560+FDC560) 168.0 kW
Heat recoveryModular outdoor units
VRF Multi system KXZR 3-PIPE series
Models FDC1200KXZRE1 FDC1250KXZRE1 FDC1300KXZRE1 FDC1350KXZRE1 FDC1425KXZRE1 FDC1450KXZRE1 FDC1500KXZRE1 FDC1560KXZRE1 FDC1620KXZRE1 FDC1680KXZRE1
Combined unitsFDC400KXZRE1 FDC400KXZRE1 FDC400KXZRE1 FDC450KXZRE1 FDC475KXZRE1 FDC475KXZRE1 FDC500KXZRE1 FDC500KXZRE1 FDC500KXZRE1 FDC560KXZRE1FDC400KXZRE1 FDC400KXZRE1 FDC450KXZRE1 FDC450KXZRE1 FDC475KXZRE1 FDC475KXZRE1 FDC500KXZRE1 FDC500KXZRE1 FDC560KXZRE1 FDC560KXZRE1FDC400KXZRE1 FDC450KXZRE1 FDC450KXZRE1 FDC450KXZRE1 FDC475KXZRE1 FDC500KXZRE1 FDC500KXZRE1 FDC560KXZRE1 FDC560KXZRE1 FDC560KXZRE1
Power supply Three-phase- 380-415V 50HzNominal Cool. capacity kW 120.00 125.00 130.00 135.00 142.50 145.00 150.00 156.00 162.00 168.00Cool. power consumption kW 34.65 37.55 40.45 43.55 44.46 44.83 45.57 48.69 51.81 54.93Rated energy efficiency coefficient in Cool. EER1 3.46 3.33 3.21 3.10 3.21 3.23 3.29 3.20 3.13 3.06Nominal Heat. capacity kW 120.00 125.00 130.00 135.00 142.50 145.00 150.00 156.00 162.00 168.00Heat. power consumption kW 29.28 30.9 32.52 34.14 34.74 35.33 36.51 38.67 40.83 42.99Rated energy efficiency coefficient in Heat. COP1 4.10 4.05 4.00 3.95 4.10 4.10 4.11 4.03 3.97 3.91Rated current in Cool. A 55.50 60.20 64.90 69.60 72.00 72.60 73.80 78.80 83.80 88.80Rated current in Heat. A 48.00 50.60 53.20 55.80 56.40 57.30 59.10 62.60 66.10 69.60Net weight kg 1071 1071 1071 1071 1230 1230 1230 1230 1230 1230Diameter cooling/refrigerant pipesLiquid side mm (inch) ø19.05 (3/4”)Delivery gas line mm (inch) ø38.1 (1-1/2”) ø34.92 (1-3/8”)Intake gas line mm (inch) ø31.75 (1-1/4”) ø28.58 (1-1/8”)Oil equalisation mm (inch) ø9.52 (3/8”)Accessories - - - - - - - - - -
Combinations
1. Value measured according to harmonised standard EN14511.
NEW
42~60HP (120.0~168.0 kW)
130
FDC 450 KXZRXE1 (FDC224+FDC224) 45.0 kWFDC 500 KXZRXE1 (FDC224+FDC280) 50.0 kWFDC 560 KXZRXE1 (FDC280+FDC280) 56.0 kW
FDC 615 KXZRXE1 (FDC280+FDC335) 61.5 kWFDC 670 KXZRXE1 (FDC335+FDC335) 67.0 kW
Connects up to 70 indoor units and up to 160% capacity (FDC 500~670) and up to 200% capacity (FDC 450)
› Maximum energy efficiency: COP 4.87
› The units use a Multi-port DC Inverter compressor with concentrated electric winding
› High split: up to 1000 m in total and with a maximum distance between the OU and the furthest IU of 160 m
Operating rangeTotal length: 1000 m
Outdoor unit
Up to the first branch pipe: max 130 m
Indoor unit
Indoor unit
Indoor unitFrom the first branch pipe to the furthest IU: 90 m*
* With difference of length between the farthest indoor unit and the nearest one from the first branch pipe < 40 m.
Furthest IU 160 m
Max height difference between IUs 18 m
Splitting height difference50 m (outdoor unit higher) 40 m (outdoor unit lower)
VRF Multi system KXZRX Hi-COP seriesHeat recoveryModular outdoor units
Combinations
1. Value measured according to harmonised standard EN14511.
Models FDC450KXZRXE1 FDC500KXZRXE1 FDC560KXZRXE1 FDC615KXZRXE1 FDC670KXZRXE1
Combined units FDC224KXZRE1 FDC224KXZRE1 FDC280KXZRE1 FDC280KXZRE1 FDC335KXZRE1FDC224KXZRE1 FDC280KXZRE1 FDC280KXZRE1 FDC335KXZRE1 FDC335KXZRE1
Power supply Three-phase- 380-415V 50HzNominal Cool. capacity kW 45.00 50.00 56.00 61.5 67.00Cool. power consumption kW 10.29 12.53 14.76 17.02 19.28Rated energy efficiency coefficient in Cool. EER1 4.37 3.99 3.79 3.61 3.48Nominal Heat. capacity kW 45.00 50.00 56.00 61.5 67.00Heat. power consumption kW 9.24 10.81 12.38 14.31 16.24Rated energy efficiency coefficient in Heat. COP1 4.87 4.63 4.52 4.30 4.13Rated current in Cool. A 18.00 21.20 24.40 28.00 31.60Rated current in Heat. A 16.00 18.30 20.60 23.60 26.60Net weight kg 578 578 578 578 578Diameter cooling/refrigerant pipesLiquid side mm (inch) ø12.7 (1/2”)Delivery gas line mm (inch) ø28.58 (1-1/8”)Intake gas line mm (inch) ø22.22 (7/8”) ø25.4 (1”) ø22.22 (7/8”)Oil equalisation mm (inch) ø9.52 (3/8”)Accessories -
NEW
16~24HP (45.0~67.0 kW)
131
Operating rangeTotal length: 1000 m
Outdoor unit
Up to the first branch pipe: max 130 m
Indoor unit
Indoor unit
Indoor unitFrom the first branch pipe to the furthest IU: 90 m*
* With difference of length between the farthest indoor unit and the nearest one from the first branch pipe < 40 m.
Furthest IU 160 m
Max height difference between IUs 18 m
Splitting height difference50 m (outdoor unit higher) 40 m (outdoor unit lower)
Connects up to 80 indoor units and up to 160% capacity (FDC 735~950) and up to 130% capacity (FDC 1000)
› Maximum energy efficiency: COP 4.76› The units use a Multi-port DC Inverter compressor with concentrated winding
› High split: up to 1000 m in total and with a maximum distance between the OU and the furthest IU of 160 m
FDC 735 KXZRXE1 (FDC224+FDC224+FDC280) 73.5 kWFDC 800 KXZRXE1 (FDC224+FDC280+FDC280) 80.0 kWFDC 850 KXZRXE1 (FDC280+FDC280+FDC280) 85.0 kW
FDC 900 KXZRXE1 (FDC280+FDC280+FDC335) 90.0 kWFDC 950 KXZRXE1 (FDC280+FDC335+FDC335) 95.0 kWFDC 1000 KXZRXE1 (FDC335+FDC335+FDC335) 100.0 kW
Heat recoveryModular outdoor units
VRF Multi system KXZRX Hi-COP series
Combinations
1. Value measured according to harmonised standard EN14511.
Models FDC735KXZRXE1 FDC800KXZRXE1 FDC850KXZRXE1 FDC900KXZRXE1 FDC950KXZRXE1 FDC1000KXZRXE1
Combined unitsFDC224KXZRE1 FDC224KXZRE1 FDC280KXZRE1 FDC280KXZRE1 FDC280KXZRE1 FDC335KXZRE1FDC224KXZRE1 FDC280KXZRE1 FDC280KXZRE1 FDC280KXZRE1 FDC335KXZRE1 FDC335KXZRE1FDC280KXZRE1 FDC280KXZRE1 FDC280KXZRE1 FDC335KXZRE1 FDC335KXZRE1 FDC335KXZRE1
Power supply Three-phase- 380-415V 50HzNominal Cool. capacity kW 73.50 80.00 85.00 90.00 95.00 100.00Cool. power consumption kW 17.67 19.91 22.14 24.90 26.66 28.92Rated energy efficiency coefficient in Cool. EER1 4.16 4.02 3.84 3.61 3.56 3.46Nominal Heat. capacity kW 73.50 80.00 85.00 90.00 95.00 100.00Heat. power consumption kW 15.43 17 18.57 20.5 22.43 24.36Rated energy efficiency coefficient in Heat. COP1 4.76 4.71 4.58 4.39 4.24 4.11Rated current in Cool. A 30.20 33.40 36.60 40.20 43.80 47.40Rated current in Heat. A 26.30 28.60 30.90 33.90 36.90 39.90Net weight kg 867 867 867 867 867 867Diameter cooling/refrigerant pipesLiquid side mm (inch) ø15.88 (5/8”)Delivery gas line mm (inch) ø31.75 (1-1/4”) ø34.92 (1-3/8”) ø38.1 (1-1/2”) ø34.92 (1-3/8”)Intake gas line mm (inch) ø25.4 (1”) ø28.58 (1-1/8”) ø28.58 (1-1/8”)Oil equalisation mm (inch) ø9.52 (3/8”)Accessories - - - - - -
NEW
26~36HP (73.5~100.0 kW)
132
FDC 224 KXZWE1 22.4 kWFDC 280 KXZWE1 28.0 kWFDC 335 KXZWE1 33.5 kW
Connect up to 33 indoor units/150% capacity
1) ENERGY SAVING Reduced operating costs
2) FLEXIBLE DESIGN• Compactdesign• Easytransportandinstallation
3) BMS (BUILDING MANAGEMENT SYSTEM) The same system for controlling the air-cooled system (KXZ)
4) SERVICE AND MAINTENANCE• Easyfrontaccesstothemainparts(compressor,control,
plate heat exchanger, etc.) • Widerangeofcontrolsoftwareandmaintenance
instruments (Mente PC, SL-Checker, etc.)
APPLICABLE ON:
• Skyscrapers 100 metres or higher• Glass façades; outside of
buildings Possibility to hide the
motocondensing unit
Outdoor engine room units (renovation projects)
Total length: 510 m
Engine room
Furthest IU 160 m
Cooling towerWater pipes
Up to the first branch pipe: max 130 m
From the first branch pipe to the furthest IU: 90 m
Max height difference between IUs 15 m
Height difference:40 m OU low
Height difference: 50 m
Outdoor units on every floor (new construction projects)
Total length: 510 m
Outdoor unit
Indoor unit
Furthest IU 160 m
Cooling tower
Refrigerant pipes
Water pipes
Water cooledOutdoor unit
VRF Multi system KXZW WATER series
FDC224~335KXZWE1
8~12 HP (22.4~33.5 kW)
133
Ref. ItemA High/low gas side piping
Please see OU specifications for refrigerant pipes.
B Gas side inletC Liquid side pipingD Parallel oilF Incoming water R1 1/4”G Outgoing water R1 1/4”H Condensate drain outlet Rp 1/2”, 2 holesJ Electrical absorption ø 35K Signal cable absorption ø 35L Fixing bolt hole ø 18 x 4 holes
DimensionsFDC-KXZWE1
224, 280 335C1 142 139C2 322 316
DimensionsExample of installation
1L1 600 or moreL2 20 or moreL3 500 or moreL4 20 or moreL5 300 or more
Model FDC224KXZWE1 FDC280KXZWE1 FDC335KXZWE1 Connection typeHigh/low gas side piping ø 19.05 (3/4”) ø 22.22 (7/8”) ø 25.4 (1”) BrazingGas side inlet ø 9.52 (3/8”) ø 9.52 (3/8”) ø 12.7 (1/2”)
FlangeLiquid side piping ø 9.52 (3/8”) ø 9.52 (3/8”) ø 9.52 (3/8”)
* When connecting the indoor units in the following series: FDK, FDFL, FDFU or FDFW, the power of the connectable indoor units cannot exceed 130%. 1. Value measured according to harmonised standard EN14511.
Models FDC224KXZWE1 FDC280KXZWE1 FDC335KXZWE1Nominal Cool. capacity* kW 22.40 28.00 33.50Cool. power consumption kW 4.23 5.75 8.13Rated energy efficiency coefficient in Cool. EER1 5.30 4.87 4.12Nominal Heat. capacity kW 25.00 31.50 37.50Heat. power consumption kW 4.24 5.10 6.30Rated energy efficiency coefficient in Heat. COP1 5.90 6.18 5.95Power Three-phase- 380-415V 50HzRated cool. current in A 7.14 9.64 13.40Rated heat. current in A 7.13 8.59 10.50Sound level dB(A) 48 50 52External dimensions (HxLxD) mm 1100 x 780 x 550 1100 x 780 x 550 1100 x 780 x 550Exterior appearance (Munsell colour) Stucco white (4.2Y7.5 / 1.16) equivalentNet weight kg 185
Indoor System Units Number of connectable IU from 1 to 22 from 1 to 28 from 1 to 33Total connectable capacity* 112 ~ 336 140 ~ 420 167 ~ 503
Crankcase heater W 33 x 1 33 x 1 33 x 1Refrigerant circuit/Heat exchanger Heat plate exchangerRefrigerant control Electronic expansion valveRefrigerant R410AQuantity kg 9.9Safety devices Compressor overheating protection/overcurrent/power transistor overheating protection/abnormal high pressure protection
Diameter cooling/refrigerant pipes mm (inch) Liquid side: ø 9.52 (3/8”) Liquid side: ø 12.7 (1/2”)Gas side: ø 19.05 (3/4”) Gas side: ø 22.22 (7/8”) Gas side: ø 25.4 (1”) [ø 22.22 (7/8”)]
Oil equalisation - - -Joining method Gas side: flange / Liquid side: flare
Water pipe diameterWater inlet R1 1/4”
Water outlet R1 1/4”Condensate outlet Rp 1/2” (internal threading)
wall
Pipes
(rear)
(front)
Label with instructions
Box for power cable wiring
Box for signal cable wiring
7-segment displayinspection hole
VIEW A
(Service space)
Installation space
wall
wallwall
Dimensions after pipe connection
Diagrams and measurementsAll measurements are in mm.
VRF Multi system KXZW WATER series
134
Connect up to 80 indoor units/150% capacity
45.0 kW50.0 kW56.0 kW61.5 kW67.0 kW73.0 kW
FDC 775 KXZWE1 (FDC224+FDC280x2) FDC 850 KXZWE1 (FDC280x3)FDC 900 KXZWE1 (FDC280x2+FDC335)FDC 950 KXZWE1 (FDC280+FDC335x2)FDC 1000 KXZWE1 (FDC335x3)
FDC 450 KXZWE1 (FDC224x2)FDC 500 KXZWE1 (FDC224+FDC280)FDC 560 KXZWE1 (FDC280x2)FDC 615 KXZWE1 (FDC280+FDC335)FDC 670 KXZWE1 (FDC335x2)FDC 730 KXZWE1 (FDC224x2+FDC280)
77.5 kW 85.0 kW90.0 kW95.0 kW100.0 kW
1) ENERGY SAVING Reduced operating costs
2) FLEXIBLE DESIGN• Compactdesign• Easytransportandinstallation
3) BMS (BUILDING MANAGEMENT SYSTEM) The same system for controlling the air-cooled system (KXZ)4) SERVICE AND MAINTENANCE• Easyfrontaccesstothemainparts(compressor,control,
plate heat exchanger, etc.) • Widerangeofcontrolsoftwareandmaintenance
instruments (Mente PC, SL-Checker, etc.)
VRF Multi system KXZW WATER seriesWater cooledModular outdoor units
APPLICABLE ON:
• Skyscrapers 100 metres or higher• Glass façades; outside of buildings Possibility to hide the motocondensing unit
FDC224~670KXZWE1
FDC730~1000KXZWE1
16~36HP (45.0~100.0 kW)
135
Models FDC450KXZWE1 FDC500KXZWE1 FDC560KXZWE1 FDC615KXZWE1 FDC670KXZWE1
Combined unitsFDC224KXZWE1 FDC224KXZWE1 FDC280KXZWE1 FDC280KXZWE1 FDC335KXZWE1FDC224KXZWE1 FDC280KXZWE1 FDC280KXZWE1 FDC335KXZWE1 FDC335KXZWE1
- - - - -Nominal Cool. capacity kW 45.00 50.00 56.00 61.50 67.00Cool. power consumption kW 8.49 9.83 11.50 13.70 16.30Rated energy efficiency coefficient in Cool. EER1 5.30 5.09 4.87 4.49 4.11Nominal Heat. capacity kW 50.00 56.00 63.00 69.00 75.00Heat. power consumption kW 8.47 9.27 10.20 11.40 12.60Rated energy efficiency coefficient in Heat. COP1 5.90 6.04 6.18 6.05 5.95Power Three-phase- 380-415V 50HzRated cool. current in A 14.30 16.50 19.30 22.70 26.80Rated heat. current in A 14.30 15.60 17.20 19.10 21.00Sound level dB(A) 51 52 53 54 55External dimensions (HxLxD) mm 1100 x 780 x 550 x 2Exterior appearance (Munsell colour) Stucco white (4.2Y7.5 / 1.16) equivalentNet weight kg 185 x 2
Indoor System Units Number of connectable IU from 1 to 44 from 1 to 50 from 1 to 56 from 2 to 61 from 2 to 67Total connectable capacity* 224 ~ 672 252 ~ 756 280 ~ 840 307 ~ 923 335 ~ 1005
Crankcase heater W 33 x 2Refrigerant circuit/Heat exchanger Heat plate exchangerRefrigerant control Electronic expansion valveRefrigerant R410AQuantity kg 9.9 x 2Safety devices Compressor overheating protection/overcurrent/power transistor overheating protection/abnormal high pressure protection
Diameter cooling/refrigerant pipes mm (inch) Liquid side: ø 12.7 (1/2”)Gas side: ø 28.58 (1, 1/8”)
Oil equalisation ø 9.52 (3/8”)Joining method Gas side: flange / Liquid side: flare
Water pipe diameterWater inlet R1 1/4”
Water outlet R1 1/4”Condensate outlet Rp 1/2” (internal threading)
Models FDC730KXZWE1 FDC775KXZWE1 FDC850KXZWE1 FDC900KXZWE1 FDC950KXZWE1 FDC1000KXZWE1
Combined unitsFDC224KXZWE1 FDC224KXZWE1 FDC280KXZWE1 FDC280KXZWE1 FDC280KXZWE1 FDC335KXZWE1FDC224KXZWE1 FDC280KXZWE1 FDC280KXZWE1 FDC280KXZWE1 FDC335KXZWE1 FDC335KXZWE1FDC280KXZWE1 FDC280KXZWE1 FDC280KXZWE1 FDC335KXZWE1 FDC335KXZWE1 FDC335KXZWE1
Nominal Cool. capacity kW 73.00 77.50 85.00 90.00 95.00 100.00Cool. power consumption kW 14.20 15.50 17.50 19.50 21.70 24.30Rated energy efficiency coefficient in Cool. EER1 5.14 5.00 4.86 4.62 4.38 4.12Nominal Heat. capacity kW 82.50 90.00 95.00 100.00 106.00 112.00Heat. power consumption kW 13.80 14.80 15.40 16.40 17.60 18.80Rated energy efficiency coefficient in Heat. COP1 5.98 6.08 6.17 6.10 6.02 5.96Power Three-phase- 380-415V 50HzRated cool. current in A 23.80 26.00 29.30 32.50 36.00 40.00Rated heat. current in A 23.20 24.90 25.90 27.50 29.40 31.40Sound level dB(A) 54 54 55 56 56 57External dimensions (HxLxD) mm 1100 x 780 x 550 x 3Exterior appearance (Munsell colour) Stucco white (4.2Y7.5 / 1.16) equivalentNet weight kg 185 x 3
Indoor System Units Number of connectable IU from 2 to 72 from 2 to 78 from 2 to 80 from 2 to 80 from 2 to 80 from 2 to 80Total connectable capacity* 364 ~ 1092 392 ~ 1176 420 ~ 1275 447 ~ 1343 475 ~ 1425 502 ~ 1508
Crankcase heater W 33 x 3Refrigerant circuit/Heat exchanger Heat plate exchangerRefrigerant control Electronic expansion valveRefrigerant R410AQuantity kg 9.9 x 3Safety devices Compressor overheating protection/overcurrent/power transistor overheating protection/abnormal high pressure protection
Diameter cooling/refrigerant pipes mm (inch)Liquid side: ø 15.88 (5/8”)
Gas side: ø 31.75 (1 1/4”) [ø 34.92 (1 3/8”)] Gas side: ø 38.1 (1 1/2”) [ø 34.92 (1 3/8”)]
Oil equalisation ø 9.52 (3/8”)Joining method Gas side: flange / Liquid side: flare
Water pipe diameterWater inlet R1 1/4”
Water outlet R1 1/4”Condensate outlet Rp 1/2” (internal threading)
Combinations
* When connecting the indoor units in the following series: FDK, FDFL, FDFU or FDFW, the power of the connectable indoor units cannot exceed 130%. 1. Value measured according to harmonised standard EN14511.
* When connecting the indoor units in the following series: FDK, FDFL, FDFU or FDFW, the power of the connectable indoor units cannot exceed 130%. 1. Value measured according to harmonised standard EN14511.
VRF Multi system KXZW WATER series
Combinations
136
137
HP 0.5 0.8 1 1.25 1.6 2 2.5 3.2 4 6 6 8 10kW 1.5 2.2 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0 16.0 22.4 28.0
m3/h 250 350 500 800 1000
INDOOR UNITS
Cass
ette
uni
ts
84x84
60x60
2-way
1-way
ducted 1-way
compact
Duc
ted
with high adjustable
head
with low and medium
adjustable head
all-outside air
with low adjustable
head
design
Wall
Ceiling
Floo
r
recessed
console
Post-treatment modu-lar unit
VRF Multi systems
FDT
SAF DXSAF DXSAF DXSAF DXSAF DX
NEW
NEW
FDTC
FDTW
FDTS
FDTQ
FDU
FDUM
FDU F
FDUT
FDUH
FDK
FDE
FDFW
FDFU
• • • • • • • • •• • • • • •
• • • • • • •• •
• • •• • • • • • • • •
• • • • • • • • • •• • • •
•• • • • • •• • •
• • • • • • • •• • • • • •
• • •• • • •
138
› 9 power levels (2.80 ~ 16.00 kW)› Ideal for commercial applications: the cassette becomes invisible because it is
completely built into the false ceiling › Removable caps on the 4 corners for easy installation› Easy condensate drain pan control› Anti-draft panel: flexible flap control for FDT (optional)› Condensate drain pump as standard: raises condensation up to 850 mm from
the flush panel
Cassette 84x84
Standard panel
Anti-draft panel
VRF Multi systemsIndoor units
ANTI-DRAFT PANEL page 34Maximum comfort without direct drafts:new flap control for increased flexibility.
Model FDT28KXZE1 FDT36KXZE1 FDT45KXZE1 FDT56KXZE1 FDT71KXZE1 FDT90KXZE1 FDT112KXZE1 FDT140KXZE1 FDT160KXZE1Standard panel T-PSA-5AW-EAnti-draft panel T-PSAE-5AW-ENominal Cool. capacity kw 2.80 3.60 4.50 5.60 7.10 9.00 11.20 14.00 16.00Nominal Heat. capacity kw 3.20 4.00 5.00 6.30 8.00 10.00 12.50 16.00 18.00Power 220-240V~ 50HzCool. power consumption kw 0.02 - 0.02 0.03 - 0.03 0.03 - 0.03 0.04 - 0.04 0.08 - 0.08 0.13 - 0.13 0.14 - 0.14 0.14 - 0.14 0.14 - 0.14Heat. power consumption kw 0.02 - 0.02 0.03 - 0.03 0.03 - 0.03 0.04 - 0.04 0.08 - 0.08 0.13 - 0.13 0.14 - 0.14 0.14 - 0.14 0.14 - 0.14Rated current in Cool. A 0.2 - 0.19 0.3 - 0.28 0.3 - 0.28 0.36 - 0.33 0.70 - 0.64 1.04 - 0.95 1.12 - 1.02 1.12 - 1.02 1.12 - 1.02Rated current in Heat. A 0.2 - 0.19 0.3 - 0.28 0.3 - 0.28 0.36 - 0.33 0.70 - 0.64 1.04 - 0.95 1.12 - 1.02 1.12 - 1.02 1.12 - 1.02Sound pressure level dB(A) P-Hi 33 Hi 31 Me 29 Lo 27 P-Hi 34 Hi 31 Me 29 Lo 27 P-Hi 35 Hi 33 Me 31 Lo 27 P-Hi 38 Hi 33 Me 31 Lo 27 P-Hi 47 Hi 35 Me 32 Lo 28 P-Hi 49 Hi 38 Me 36 Lo 31 P-Hi 49 Hi 39 Me 37 Lo 31 P-Hi 49 Hi 42 Me 39 Lo 32 P-Hi 49 Hi 42 Me 39 Lo 33Sound power level dB(A) 49 49 50 55 62 65 66 66 66
External dimensions (HxLxD) mm Unit 236 × 840 × 840 Unit 298 × 840 × 840Panel 35 × 950 × 950
Exterior appearance Chalk whiteMunsell colour (6.8Y8.9 / 0.2) similarNet weight kg Unit 20 Panel 5 Unit 21.5 Panel 5 Unit 25 Panel 5Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Turbo fan × 1Motor W 58 58 58 58 58 120 120 120 120Starting method Direct, in lineAir flow (standard) m3h PHi 900 Hi 840 Me 720 Lo 600 PHi 960 Hi 840 Me 720 Lo 600 PHi 1020 Hi 900 Me 780 Lo 600 PHi 1200 Hi 960 Me 780 Lo 660 PHi 1680 Hi 1020 Me 840 Lo 720 PHi 2220 Hi 1500 Me 1320 Lo 900 PHi 2280 Hi 1560 Me 1380 Lo 1020 PHi 2280 Hi 1680 Me 1500 Lo 1080 PHi 2280 Hi 1740 Me 1560 Lo 1140Static pressure Pa 0Renewal air inlet PossibleAir filter and quantity Plastic mesh filter x 1 (washable)Shock and vibration absorption Rubber vibration absorber (for fan motor)Thermal and acoustic insulation Polyurethane foam
Optional control devices Wired remote control: RC-EX3, RC-E5, RCH-E3Remote control kit: RCN-T-5AW-E2
Ambient temperature control Electronically-controlled thermostat
Safety devices Overvoltage protection for the fan motorAnti-frost protection thermostat
Diameter cooling/refrigerant pipes mm (inch) Liquid side: ø6.35 (1/4”)Gas side: ø9.52 (3/8”)
Joining method by flare fittingsRefrigerant R410ADrain pump Built-inCondensate drain Connectable with VP25 Connectable with VP20Piping insulation Necessary (on both sides, liquid and gas)Accessories included Assembly kit, Condensate pipe
FDT 28~160KXZE1
T-PSAE-5AW-E
T-PSA-5AW-E
NEW
139
All measurements are in mm.
Hole dimension
Suspension rod spacing
Susp
ensio
n rod
spac
ing: P
2 (7
70)
Electrical box
Condensate pipe(accessory)On-site connection
Extraction grilleAir delivery
Decorative panel
Space for installation and service
or mo
re
or moreobstacle
When installing more than one unit, it is necessary to keep a distance of 5 m or more between one machine and the next.
Installation plate for suspension rod
50 or
more
Electrical box
Fixing
Holes for self-tapping screws
Fixing
Holes for self-tapping screws
850
or les
sMa
x. ris
e
Diagrams and measurements
Anti-draft function(*1)
Holes for self-tapping screws
860~910 Hole dimension
Suspension rod spacing: P1 (770)
Susp
ensio
n rod
spac
ing: P
2 (7
70) Electrical
box
Condensate pipe(accessory)On-site connection
Extraction grilleAir delivery
Decorative panel
Space for installation and service
or mo
re
or moreobstacle
When installing more than one unit, it is necessary to keep a distance of 5 m or more between one machine and the next.
Installation plate for suspension rod
50 or
more
Electrical box
Fixing
Holes for self-tapping screws
Fixing
Holes for self-tapping screws
850
or les
sMa
x. ris
e
Anti-draft function(*1)
Holes for self-tapping screws
Note:1. The label with the model code is applied inside the extraction grille.3. Section 1 (* 1) is only available on panel T-PSA-5AW.
Ref. ItemModel FDT28KXZE1 FDT36~56KXZE1 FDT71KXZE1
A Gas side ø 9.52 (3/8") flare ø 12.7 (1/2") flare ø 15.88 (5/8") flareB Liquid side ø 6.35 (1/4") flare ø 9.52 (3/8") flareC Condensate drain VP25 (O.D. 32)D Hole for electrical cables
F Suspension rods M10 or M8G External air intake ø 125 pre-cutH Outlet air intake ø 200 pre-cut
Ref. ItemA Gas side ø 15.88 (5/8") flareB Liquid side ø 9.52 (3/8") flareC Condensate drain VP25 (O.D. 32)D Hole for electrical cables
F Suspension rods M10 or M8G External air intake ø 125 pre-cutH Outlet air intake ø 200 pre-cut
FDT 28~71KXZE1
FDT 90~160KXZE1
140
300 m
m
TC-OAS-ETC-OAD-E
075 mm
› 6 power levels (1.50 ~ 5.60 kW)› Ideal for insertion into modular ceilings › Maximum compactness: only 24.8 cm in height.› RCN-TC-24W-E2 corner kit with remote control (optional)› Removable caps on the 4 corners for easy installation› Condensate drain pump as standard› Panel: TC-PSA-25W-E
Cassette 60X60
AIR RENEWAL AIR FLOW
The shape and angle of the deflector lead air away from the ceiling to prevent stains.
Optional accessories for outdoor air intake, TC-OAD-E, TC-OAS-E
outdoor airfalse ceiling
panel
Values for 1 channel(?)Air flow: 1.3m3/min (78m3/h)(10% approx. of the max air flow)Press. Static: 12 Pa (at max air flow)
Notes:1 channel = about 10% of total unit air flow;2 channel = about 20% of total FDTC air flow;
Model FDTC15KXE6F* FDTC22KXE6F FDTC28KXE6F FDTC36KXE6F FDTC45KXE6F FDTC56KXE6FPanel (optional) TC-PSA-25W-ENominal Cool. capacity kW 1.50 2.20 2.80 3.60 4.50 5.60Nominal Heat. capacity kW 1.70 2.50 3.20 4.00 5.00 6.30Power 220-240V~ 50HzCool. power consumption kW 0.02 - 0.02 0.03 - 0.03 0.03 - 0.03 0.03 - 0.03 0.05 - 0.05 0.05 - 0.05Heat. power consumption kW 0.02 - 0.02 0.03 - 0.03 0.03 - 0.03 0.03 - 0.03 0.05 - 0.05 0.05 - 0.05Rated cool. current in A 0.06 - 0.05 0.15 - 0.14 0.15 - 0.14 0.15 - 0.14 0.25 - 0.23 0.25 - 0.23Rated heat. current in A 0.06 - 0.05 0.15 - 0.14 0.15 - 0.14 0.15 - 0.14 0.25 - 0.23 0.25 - 0.23Sound pressure level dB(A) Hi 32 Me 28 Lo 25 Hi 35 Me 33 Lo 30 Hi 38 Me 36 Lo 31 Hi 40 Me 37 Lo 31 Hi 45 Me 39 Lo 31Sound power level dB(A) 56 58 60
External dimensions (HxLxD) mm Unit 248 x 570 x 570Panel 35 x 700 x 700
Exterior appearance Chalk whiteMunsell colour ( 6.8Y8.9 / 0.2) similarNet weight kg Unit 14 Panel 3.5 Unit 15 Panel 3.5Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Turbo fan x 1Motor W 33Starting method Direct, in lineAir flow (standard) m3/h Hi 420 Med 330 Lo 270 Hi 570 Me 510 Lo 420 Hi 600 Me 540 Lo 420 Hi 780 Me 600 Lo 420Static pressure Pa 0Renewal air inlet Possible with accessoriesAir filter and quantity Plastic mesh filter x 1 (washable)Shock and vibration absorption Rubber sleeve (for fan motor)Thermal and acoustic insulation Polyurethane foamControl devices Optional wired remote control RC-E5, optional RCH-E3, optional RCN-TC-24W-E2, optional RC-EX3Ambient temperature control Electronically-controlled thermostat
Safety devices Overvoltage protection for the fan motorAnti-frost protection thermostat
Diameter cooling/refrigerant pipes mm (inch) Liquid side: ø 6.35 (1/4")Gas side: ø 9.52 (3/8") Gas side: ø 12.7 (1/2")
Joining method by flare fittingsRefrigerant R410ADrain pump Built-inCondensate drain Connectable with VP20Piping insulation Necessary (on both sides, liquid and gas)Accessories Assembly kit, TC-OAS-E (Optional), TC-OAD-E (Optional)
* Unit can only be connected with OU KXE6 from 8HP to 12HP and all KXZ OU.
Indoor units
VRF Multi systems
FDTC 15~56KXE6F
141
All measurements are in mm.Diagrams and measurements
Ref. ItemModel FDTC15~28KXE6F FDTC36~56KXE6F
A Gas side ø 9.52 (3/8") flare ø 12.7 (1/2") flareB Liquid side ø 6.35 (1/4") flareC Condensate drain VP25 (note 2)D Hole for electrical cables ø 25F Suspension rods M10 or M8G External air intake Pre-cut
Space for installation and service
or mo
re
or moreobstacle
When installing more than one unit, it is necessary to keep a distance of 4 m or more between one machine and the next.
Suspension rod spacing
Susp
ensio
n rod
spac
ing
Electrical box
Condensate pipe(accessory)On-site connection
Extraction grille
Air delivery
Decorative panel
Holes for self-tapping screws
or les
sMa
x. ris
e
Notes: 1. The label with the model code is applied inside the extraction grille.2. Prepare the connection for the VP25 condensate drain on site.3. This unit has been designed to be inserted into an inspectable ceiling. In case of installation in an inspectable ceiling, provide for an inspection opening on the side of the electrical box.
or mo
re
Installation plate for suspension rod
or les
sMa
x. ris
e
Ultra-thin design, only 248 mm over the ceiling Standard condensate drain pump
FDTC 15~56KXE6F
142
› 7 power levels (2.80 ~ 14.00 kW)› Can be fully built in to the false ceiling, enabling uniform air distribution in
environments with a rectangular perimeter› Panels: TW-PSA-26W-E (models FDTW 28/45/56/71 KXE6F); TW-PSA-46W-E
(models FDTW 90/112/140 KXE6F)
2-way cassette
INDIVIDUAL CONTROL OF AIR OUTLET LOUVERS CONDENSATE DRAIN PUMP
The new design of the louvers ensures uniform, wide-ranging air distribution throughout the area to be conditioned. The enlargement of the delivery vents has significantly reduced the load on the fan motor, resulting in increased energy efficiency.
750 o
r less
Maxim
um ris
e
Model FDTW28KXE6F FDTW45KXE6F FDTW56KXE6F FDTW71KXE6F FDTW90KXE6F FDTW112KXE6F FDTW140KXE6FPanel (optional) TW-PSA-26W-E TW-PSA-46W-ENominal Cool. capacity kW 2.80 4.50 5.60 7.10 9.00 11.20 14.00Nominal Heat. capacity kW 3.20 5.00 6.30 8.00 10.00 12.50 16.00Power 220-240V~ 50HzCool. power consumption kW 0.09 - 0.09 0.10 - 0.10 0.10 - 0.10 0.14 - 0.14 0.19 - 0.19 0.19 - 0.19 0.19 - 0.19Heat. power consumption kW 0.09 - 0.09 0.10 - 0.10 0.10 - 0.10 0.14 - 0.14 0.19 - 0.19 0.19 - 0.19 0.19 - 0.19Rated cool. current in A 0.45 - 0.45 0.55 - 0.55 0.55 - 0.55 0.75 - 0.75 1.00 - 1.00 1.00 - 1.00 1.00 - 1.00Rated heat. current in A 0.45 - 0.45 0.55 - 0.55 0.55 - 0.55 0.75 - 0.75 1.00 - 1.00 1.00 - 1.00 1.00 - 1.00Sound pressure level dB(A) Hi 38 Me 34 Lo 31 Hi 45 Me 41 Lo 37Sound power level dB(A) 58 65 -
External dimensions (HxLxD) mm Unit 325 x 820 x 620 Unit 325 x 1535 x 620Panel 20 x 1120 x 680 Panel 20 x 1835 x 680
Exterior appearance Chalk whiteMunsell colour (6.8Y8.9 / 0.2) similarNet weight kg Unit 20 Panel 8.5 Unit 21 Panel 8.5 Unit 23 Panel 8.5 Unit 35 Panel 13Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Turbo fan x 1Motor W 30 35 40 35 x 2Starting method Direct, in lineAir flow (standard) m3/h Hi 720 Me 600 Lo 540 Hi 1620 Me 1380 Lo 1200Static pressure Pa 0Renewal air inlet PossibleAir filter and quantity Plastic mesh filter x 1 (washable) Plastic mesh filter x 2 (washable)Shock and vibration absorption Rubber sleeve (for fan motor)Thermal and acoustic insulation Polyurethane foamControl devices Optional wired remote control RC-E5, optional RCH-E3, optional RCN-TW-E2, optional RC-EX3Ambient temperature control Electronically-controlled thermostat
Safety devices Overvoltage protection for the fan motorAnti-frost protection thermostat
Diameter cooling/refrigerant pipes mm (inch.)
Liquid side: ø 6.35 (1/4") Liquid side: ø 9.52 (3/8")Gas side: ø 9.52 (3/8") Gas side: ø 12.7 (1/2") Gas side: ø 15.88 (5/8")
Joining method by flare fittingsRefrigerant R410ADrain pump Built-inCondensate drain Connectable with VP25Piping insulation Necessary (on both sides, liquid and gas)Accessories Assembly kit
Indoor units
VRF Multi systems
FDTW 28~140KXE6F
143
All measurements are in mm.Diagrams and measurements
Space for installation and service
or more
obstacle
When installing more than one unit, it is necessary to keep a distance of 4 m or more between one machine and the next.
Ceiling hole dimension
Ceilin
g hole
dime
nsion
Electrical box
Condensate pipe(accessory)On-site connection
Decorative panel
Suspension rod spacing
Suspen
sion ro
d spac
ing
or les
sMa
x. ris
e
Air delivery Extraction grille
Slot for suspension rod
or moreor more or more
Panel centre
Electrical box
Ceiling hole dimension
Ceilin
g hole
dime
nsion
Electrical box
Condensate pipe(accessory)On-site connection
Suspension rod spacing
or les
sMa
x. ris
e
Slot for suspension rod
Panel centre
Electrical box
Suspen
sion ro
d spac
ing
Space for installation and service
or more
obstacle
When installing more than one unit, it is necessary to keep a distance of 4 m or more between one machine and the next.
Decorative panel
Air delivery
Extraction grille
or moreor more or more
Ref. ItemModel FDTW28KXE6F FDTW45~56KXE6F FDTW71KXE6F FDTW90~140KXE6F
A Gas side ø 9.52 (3/8") flare ø 12.7 (1/2") flare ø 15.88 (5/8") flareB Liquid side ø 6.35 (1/4") flare ø 9.52 (3/8") flareC Condensate drain VP25 (note 2)D Hole for electrical cablesF Suspension rods M10G External air intake Pre-cutH Outlet air intake Pre-cut
Notes: 1. The label with the model code is applied inside the extraction grille.2. Prepare the connection for the VP25 condensate drain on site.
FDTW 28~140KXE6F
FDTW 90~140KXE6F
144
1-way cassette
› 2 power levels (4.50 and 7.10 kW)› Can be mounted on the ceiling with a suspended unit or built into the false
ceiling› Maximum compactness: only 22 cm high, ideal for installations in
environments with low false ceilings› Wide air flow, ideal for environments with very high ceilings› Possibility to connect air renewal ducts› Panel: TS-PSA-3AW-E
Ultra-compact design: its height of only 22 cm and weight of 27/28 kg guarantee easy and quick installation.
INDIVIDUAL CONTROL OF AIR OUTLET LOUVERSULTRA-COMPACT MODEL
The new design of the louvers ensures uniform, wide-ranging air distribution throughout the area to be conditioned. The enlargement of the delivery vents has significantly reduced the load on the fan motor, resulting in increased energy efficiency.
Model FDTS45KXE6F FDTS71KXE6FPanel (optional) TS-PSA-3AW-ENominal Cool. capacity kW 4.50 7.10Nominal Heat. capacity kW 5.00 8.00Power 220-240V~ 50HzCool. power consumption kW 0.04 - 0.04 0.09 - 0.09Heat. power consumption kW 0.04 - 0.04 0.09 - 0.09Rated cool. current in A 0.27 - 0.25 0.60 - 0.55Rated heat. current in A 0.27 - 0.25 0.60 - 0.55Sound pressure level dB(A) Hi 40 Me 38 Lo 35 Hi 44 Me 41 Lo 36Sound power level dB(A) 60 61
External dimensions (HxLxD) mm Unit 220 x 1150 x 565Panel 35 x 1250 x 650
Exterior appearance Chalk whiteMunsell colour (6.8Y8.9 / 0.2) similarNet weight kg Unit 27 Panel 5 Unit 28 Panel 5Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Centrifugal fan x 4Motor W 35 70Starting method Direct, in lineAir flow (standard) m3h Hi 720 Me 660 Lo 570 Hi 900 Me 720 Lo 600Static pressure Pa 0Renewal air inlet PossibleAir filter and quantity Plastic mesh filter x 2 (washable) Plastic mesh filter x 3 (washable)Shock and vibration absorption Rubber sleeve (for fan motor)Thermal and acoustic insulation Polyurethane foamControl devices Optional wired remote control RC-E5, optional RCH-E3, optional RCN-TS-E2, optional RC-EX3Ambient temperature control Electronically-controlled thermostat
Safety devices Overvoltage protection for the fan motorAnti-frost protection thermostat
Diameter cooling/refrigerant pipes mm (inch) Liquid side: ø 6.35 (1/4") Liquid side: ø 9.52 (3/8")Gas side: ø 12.7 (1/2") Gas side: ø 15.88 (5/8")
Joining method by flare fittingsRefrigerant R410ADrain pump Built-inCondensate drain Connectable with VP25Piping insulation Necessary (on both sides, liquid and gas)Accessories Assembly kit
Indoor units
VRF Multi systems
FDTS 45-71KXE6F
145
FDTS 45-71KXE6F
All measurements are in mm.Diagrams and measurements
Ref. ItemModel FDTS45KXE6F FDTS71KXE6F
A Gas side ø 12.7 (1/2") flare ø 15.88 (5/8") flareB Liquid side ø 6.35 (1/4") flare ø 9.52 (3/8") flareC Condensate drain VP25 (note 2)D Hole for electrical cablesF Suspension rods M10G External air intake Pre-cutH Condensate drain (dr. nat.) VP25
Ceiling hole dimension
Ceilin
g hole
dime
nsion
Condensate pipe(accessory)On-site connection
or les
sMa
x. ris
e
Panel centre
Electrical box
Space for installation and service
or mo
re
obstacle
When installing more than one unit, it is necessary to keep a distance of 4 m or more between one machine and the next.
Decorative panel
Air delivery
Extraction grille
or more
Air delivery
Extraction grille
or moreor more
Notes: 1. The label with the model code is applied inside the extraction grille.2. Prepare the connection for the VP25 condensate drain on site.
146
1-way compact ducted cassette
› 3 power levels (2.20 ~ 3.60 kW)› Ideal for smaller environments, with a fan speed of only 300 m3/h› Panel with direct delivery› Panel equipped with motorised louver for comfortable air flow distribution› Condensate drain pump as standard h 60 cm
PANELULTRA-COMPACT MODEL
TQ-PSA-15W-E
Air delivery
Extraction grille
Model a b c d
TQ-PSA-15W-E 625 514 650 580Holes for self-tapping screws
External air intake (pre-cut)
Model FDTQ22KXE6F FDTQ28KXE6F FDTQ36KXE6FPanel (optional) Direct delivery
TQ-PSA-15W-ENominal Cool. capacity kW 2.20 2.80 3.60Nominal Heat. capacity kW 2.50 3.20 4.00Power 220-240V~ 50HzCool. power consumption kW 0.05 - 0.07 0.05 - 0.07 0.05 - 0.07Heat. power consumption kW 0.05 - 0.07 0.05 - 0.07 0.05 - 0.07Nominal Cool. current A 0.25 - 0.32 0.25 - 0.32 0.25 - 0.32Nominal Heat. current A 0.25 - 0.32 0.25 - 0.32 0.25 - 0.32Sound pressure level dB(A) Hi 41 Me 38 Lo 33Sound power level dB(A) 60
External dimensions (HxLxD) mm Unit 250 x 570 x 570Panel 35 x 625 x 650
Exterior appearance Chalk whiteMunsell colour (6.8Y8.9 / 0.2) similarNet weight kg Unit 23 Panel 2.5Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Centrifugal fan x 1Motor W 30Starting method Direct, in lineAir flow (standard) m3/h Hi 420 Me 360 Lo 300Static pressure Pa 0Renewal air inlet PossibleAir filter and quantity Plastic mesh filter x 1 (washable)Shock and vibration absorption Rubber sleeve (for fan motor)Thermal and acoustic insulation Polyurethane foamControl devices Optional wired remote control RC-E5, optional RCH-E3, optional RCN-KIT4-E2, optional RC-EX3Ambient temperature control Electronically-controlled thermostat
Safety devices Overvoltage protection for the fan motorAnti-frost protection thermostat
Diameter cooling/refrigerant pipes mm (inch) Liquid side: ø 6.35 (1/4")Gas side: ø 9.52 (3/8") Gas side: ø 12.7 (1/2")
Joining method by flare fittingsRefrigerant R410ADrain pump Built-inCondensate drain Connectable with VP20Piping insulation Necessary (on both sides, liquid and gas)Accessories Assembly kit
Indoor units
VRF Multi systems
FDTQ 22~36KXE6F
147
All measurements are in mm.Diagrams and measurements
Direct delivery (TQ-PSA-15W-E)
Ref. ItemModel FDTQ22~28KXE6F FDTQ36KXE6F
A Gas side ø 9.52 (3/8") flare ø 12.7 (1/2") flareB Liquid side ø 6.35 (1/4") flareC Condensate drain VP25 (note 2)D Hole for electrical cables ø 30E Suspension rods M10F1.2 External air intake Pre-cut
Space for installation and service
or mo
re
obstacle
When installing more than one unit, it is necessary to keep a distance of 3 m or more between one machine and the next.
or more
Condensate pipe(accessory)On-site connection
Suspension rod spacing
or mo
re
Condensate pipe(accessory)On-site connection
Installation plate for suspension rod
Suspension rod spacingHole dimension
Centre of panel
Electrical box
Installation plate for suspension rod
Centre of panel
Electrical box Su
spen
sion r
od sp
acing
Hole
dimen
sion
Susp
ensio
n rod
spac
ing
Holes for self-tapping screws
Holes for self-tapping screws
or les
sMa
x. ris
e
or moreor more
Notes: 1. The label with the model code is applied inside the extraction grille.2. Prepare the connection for the VP25 condensate drain on site.3. This unit has been designed to be inserted into an inspectable ceiling.
or more
FDTQ 22~36KXE6F
148
High adjustable head ducted
› 9 power levels (4.50 ~ 28.00 kW)› Units with rear recovery› Adjustable 100~200 Pa head for models from 4.50 to 16.00 kW and only 200
Pa for models from 22.40 to 28.00 kW› Maximum compactness: only 28 cm (models from 4.50 to
16.00 kW) and 37.9 cm high (22.40 and 28.00 kW models)› Integrated condensate drain pump for models from 4.50 to 16.00 kW
COMPACT SIZE
Models from 4.50 to 16.00 kW Models from 22.40 to 28.00 kW
Indoor units
VRF Multi systems
Model FDU45KXE6F FDU56KXE6F FDU71KXE6F FDU90KXE6F FDU112KXE6F FDU140KXE6F FDU160KXE6F FDU 224KXZE1 FDU 280KXZE1Nominal Cool. capacity kW 4.50 5.60 7.10 9.00 11.20 14.00 16.00 22.40 28.00Nominal Heat. capacity kW 5.00 6.30 8.00 10.00 12.50 16.00 18.00 25.00 31.50Power 220-240V~ 50HzCool. power consumption kW 0.10 - 0.10 0.10 - 0.10 0.24 - 0.25 0.24 - 0.25 0.31 - 0.32 0.35 - 0.36 0.42 - 0.43 1.16 - 1.20 1.16 - 1.20Heat. power consumption kW 0.10 - 0.10 0.10 - 0.10 0.24 - 0.25 0.24 - 0.25 0.31 - 0.32 0.35 - 0.36 0.42 - 0.43 1.16 - 1.20 1.16 - 1.20Rated cool. current in A 0.63 - 0.58 0.63 - 0.58 1.80 - 1.70 1.80 - 1.70 2.00 - 2.00 2.30 - 2.20 2.70 - 2.50 6.8 - 6.5 6.8 - 6.5Rated heat. current in A 0.63 - 0.58 0.63 - 0.58 1.80 - 1.70 1.80 - 1.70 2.00 - 2.00 2.30 - 2.20 2.70 - 2.50 6.8 - 6.5 6.8 - 6.5Sound pressure level dB(A) Hi 32 Med 29 Lo 26 Hi 32 Med 29 Lo 26 Hi 33 Med 29 Lo 25 Hi 33 Med 29 Lo 25 Hi 38 Med 36 Lo 30 Hi 40 Med 34 Lo 29 Hi 40 Med 35 Lo 30 P-Hi 52 Hi 50 Med 47 Lo 35Sound power level dB(A) 60 60 65 65 75 75External dimensions (hxlxd) mm 280 ×750 × 635 280 ×750 × 635 280 ×950 × 635 280 ×950 × 635 280 ×1.370 × 740 280 ×1.370 × 740 280 ×1.370 × 740 379 × 1.600 × 893 379 × 1.600 × 893Net weight kg 29 29 34 34 54 54 54 89 89Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Centrifugal fan x 1 Centrifugal fan x 2 Centrifugal fan x 3Motor W 100 100 130 130 100 + 130 100 + 200 100 + 200 130 + 350 130 + 350Starting method Direct, in lineAir flow (standard) m3h Hi 600 Med 540 Lo 480 Hi 1140 Med 900 Lo 600 Hi 1680 Med 1500 Lo 1140 Hi 1920 Med 1560 Lo 1200 Hi 2100 Med 1680 Lo 1320 P-Hi 4800 Hi 4320 Med 3840 Lo 3360Static pressure Pa Standard 100 Max 200 Max 200 Max 200Renewal air inlet PossibleAir filter and quantity To be found locallyShock and vibration absorption Rubber sleeve (for fan motor)Thermal and acoustic insulation Polyurethane foamControl devices Optional wired remote control RC-E5, optional RCH-E3, optional RCN-KIT4-E2, optional RC-EX3Ambient temperature control Electronically-controlled thermostat
Safety devices Overvoltage protection for the fan motorAnti-frost protection thermostat
Diameter cooling/refrigerant pipes mm (in) Liquid side: ø6.35 (1/4”) Liquid side ø9.52 (3/8”)Gas side: ø12.7 (1/2”) Gas side ø15.88 (5/8”) Gas side ø19.05 (3/4”) Gas side ø22.2 (7/8”)
Joining method by flare fittings by blazingRefrigerant R410ADrain pump Built-in -Condensate drain Connectable with VP25Piping insulation Necessary (on both sides, liquid and gas)Accessories -
FDU 45~160KXE6F
FDU 224~280KXZE1
149
Diagrams and measurements
Ref. ItemA Gas side ø 12.7 (1/2") flareB Liquid side ø 6.35 (1/4") flareC1 Condensate drain VP25 (note 2)C2 Condensate drain (dr. nat.) VP20D Hole for electrical cablesE Suspension rods M10F Inspection hole 450 x 450G External air intake Pre-cutH Outlet air intake Pre-cut
Notes: 1. The label with the model code is applied inside the extraction grille.2. Prepare the connection for the VP25 condensate drain on site.
Space for installation and service
or mo
re
Condensate pipe(accessory)On-site connection
Suspension rod spacingInstallation plate for suspension rod
Electrical box
Susp
ensio
n rod
spac
ing
Holes for self-tapping screws
Hole
VIEW M
Holes for self-tapping screws
Dimen
sions
of
ducti
ng
Air delivery
Dimensions of ducting
or les
sMa
x. rise
Dimen
sions
of
ducti
ng Dimensions of ducting
Inletduct
Inspectionhole or
more
Ref. ItemA Gas side ø 15.88 (5/8") flareB Liquid side ø 9.52 (3/8") flareC1 Condensate drain VP25 (note 2)C2 Condensate drain (dr. nat.) VP20D Hole for electrical cablesE Suspension rods M10F Inspection hole 450 x 450G External air intake Pre-cutH Outlet air intake Pre-cut
Notes: 1. The label with the model code is applied inside the extraction grille.2. Prepare the connection for the VP25 condensate drain on site.
Space for installation and service
or mo
re
Condensate pipe(accessory)On-site connection
Suspension rod spacingInstallation plate for suspension rod
Electrical box
Susp
ensio
n rod
spac
ing
Holes for self-tapping screws
VIEW M
Holes for self-tapping screws
Dimen
sions
of
ducti
ng Air delivery
Dimensions of ducting
or les
sMa
x. rise
Dimen
sions
of
ducti
ng Dimensions of ducting
Inletduct
Inspectionhole
or mo
re
Notes: 1. The label with the model code is applied inside the extraction grille.2. Prepare the connection for the VP25 condensate drain on site.
Space for installation and service
or mo
re
Condensate pipe(accessory)On-site connection
Suspension rod spacingInstallation plate for suspension rod
Electrical box
Susp
ensio
n rod
spac
ing
Holes for self-tapping screws
VIEW M
Holes for self-tapping screws
Dimen
sions
of
ducti
ng
Air delivery
Dimensions of ducting
or les
sMa
x. rise Dimensions
of ducting
Inletduct
Inspectionhole
or mo
re
Hole
Hole
Dimen
sions
of
ducti
ng
Ref. ItemA Gas side ø 15.88 (5/8") flareB Liquid side ø 9.52 (3/8") flareC1 Condensate drain VP25 (note 2)C2 Condensate drain (dr. nat.) VP20D Hole for electrical cablesE Suspension rods M10F Inspection hole 450 x 450G External air intake Pre-cutH Outlet air intake Pre-cut
Ref. ItemModel FDU 224KXZE1 FDU 280KXZE1
A Gas side ø 19.05 (3/4") flare
ø 22.22 (7/8") flare
B Liquid side ø 9.52 (3/8") flareC Condensate drain VP25 (note 2)D Hole for electrical cables
E Suspension rods M10F Inspection hole 450 x 450
Dimensions of ducting
Dimen
sions
of
ducti
ng
Dimen
sions
of
ducti
ng
Air delivery
Dimensions of ducting
Susp
ensio
n rod
spac
ing
Space for installation and service
or mo
re
Installation plate for suspension rod
All measurements are in mm.
FDU 45~56KXE6F
FDU 112~140KXE6F
FDU 71~90KXE6F
FDU 224~280KXZE1
150
Ducted with adjustable medium and low head
› 10 power levels (2.20 ~ 16.00 kW)› Ultra-compact design: only 28 cm in height.› Optional UM-FL1EF (FDUM 22~56KXE6F), UM-FL2EF (FDUM 71~90KXE6F),
UM-FL3EF (FDUM 112~160KXE6F)› ESP function: automatic maintenance of the air flow rate as flow resistance
varies
Model FDUM22KXE6F FDUM28KXE6F FDUM36KXE6F FDUM45KXE6F FDUM56KXE6F FDUM71KXE6F FDUM90KXE6F FDUM112KXE6F FDUM140KXE6F FDUM160KXE6FNominal Cool. capacity kW 2.20 2.80 3.60 4.50 5.60 7.10 9.00 11.20 14.00 16.00Nominal Heat. capacity kW 2.50 3.20 4.00 5.00 6.30 8.00 10.00 12.50 16.00 18.00Power 220-240V~ 50HzCool. power consumption kW 0.10 - 0.10 0.10 - 0.10 0.10 - 0.10 0.10 - 0.10 0.10 - 0.10 0.20 - 0.20 0.20 - 0.20 0.29 - 0.29 0.33 - 0.33 0.33 - 0.33Heat. power consumption kW 0.10 - 0.10 0.10 - 0.10 0.10 - 0.10 0.10 - 0.10 0.10 - 0.10 0.20 - 0.20 0.20 - 0.20 0.29 - 0.29 0.33 - 0.33 0.33 - 0.33Rated cool. current in A 0.46 - 0.42 0.46 - 0.42 0.46 - 0.42 0.46 - 0.42 0.46 - 0.42 0.91 - 0.83 0.91 - 0.83 1.32 - 1.21 1.50 - 1.38 1.50 - 1.38Rated heat. current in A 0.46 - 0.42 0.46 - 0.42 0.46 - 0.42 0.46 - 0.42 0.46 - 0.42 0.91 - 0.83 0.91 - 0.83 1.32 - 1.21 1.50 - 1.38 1.50 - 1.38Sound pressure level dB(A) Hi 32 Me 29 Lo 26 Hi 33 Me 29 Lo 25 Hi 38 Me 36 Lo 30 Hi 40 Me 34 Lo 29 Hi 40 Me 34 Lo 29Sound power level dB(A) 60 64 -External dimensions (HxLxD) mm 280 x 750 x 635 280 x 950 x 635 280 x 950 x 635 280 x 1370 x 740Net weight kg 29 34 54Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Centrifugal fan x 2Motor W 100 130 100 + 130 100 + 200Starting method Direct, in lineAir flow (standard) m3/h Hi 600 Me 540 Lo 480 Hi 1140 Me 900 Lo 600 Hi 1680 Me 1500 Lo 1140 Hi 1920 Me 1560 Lo 1200Static pressure Pa Max 100Renewal air inlet PossibleAir filter and quantity OptionalShock and vibration absorption Rubber sleeve (for fan motor)Thermal and acoustic insulation Polyurethane foamControl devices Optional wired remote control RC-E5, optional RCH-E3, optional RCN-KIT4-E2, optional RC-EX3Ambient temperature control Electronically-controlled thermostat
Safety devices Overvoltage protection for the fan motorAnti-frost protection thermostat
Diameter cooling/refrigerant pipes mm (inch) Liquid side: ø 6.35 (1/4") Liquid side: ø 9.52 (3/8")Gas side: ø 9.52 (3/8") Gas side: ø 12.7 (1/2") Gas side: ø 15.88 (5/8")
Joining method by flare fittingsRefrigerant R410ADrain pump Built-inCondensate drain Connectable with VP20 or VP25 Piping insulation Necessary (on both sides, liquid and gas)Accessories UM-FL1EF (Optional) UM-FL2EF (Optional) UM-FL3EF(Optional)
Indoor units
VRF Multi systems
FDUM 22~160KXE6F
151
Diagrams and measurements
Ref. ItemModel FDUM22~28KXE6F FDUM36~56KXE6F FDUM71~90KXE6F FDUM112~160KXE6F
A Gas side ø 9.52 (3/8") flare ø 12.7 (1/2") flare ø 15.88 (5/8") flareB Liquid side ø 6.35 (1/4") flare ø 9.52 (3/8") flareC1 Condensate drain VP25 (note 2)C2 Condensate drain (dr. nat.) VP20D Hole for electrical cablesE Suspension rods M10F External air intake Pre-cutG Outlet air intake Pre-cutH Inspection hole 450 x 450
Notes: 1. The label with the model code is applied inside the extraction grille.2. Prepare the connection for the VP25 condensate drain on site.
Space for installation and service
or mo
re
Suspension rod spacingInstallation plate for suspension rod
Electrical box
Susp
ensio
n rod
spac
ing
Holes for self-tapping screws
Hole
Holes for self-tapping screws
Inspectionhole
or mo
re
VIEW M
VIEW M
Space for installation and service
or mo
re
Suspension rod spacingInstallation plate for suspension rod
Electrical box
Susp
ensio
n rod
spac
ing
Holes for self-tapping screws
Holes for self-tapping screws
Inspectionhole
or mo
re
Space for installation and service
or mo
re
Suspension rod spacingInstallation plate for suspension rod
Electrical box
Suspe
nsion
rod s
pacin
g
Holes for self-tapping screws
Holes for self-tapping screws
Inspectionhole
or mo
re
Hole
Hole
VIEW M
Condensate pipe(accessory)On-site connection
Dimen
sions
of du
cting
Air delivery
Dimensions of ducting
or les
sMa
x. rise
Dimensions of ducting
Inletduct
Dimen
sions
of
ducti
ng
Holes for self-tapping screws
Condensate pipe(accessory)On-site connection
Dimen
sions
of du
cting
Air delivery
Dimensions of ducting
or les
sMa
x. rise
Dimensions of ducting
Inletduct
Dimen
sions
of
ducti
ng
Holes for self-tapping screws
Condensate pipe(accessory)
On-site connection
Dimen
sions
of du
cting
Air delivery
Dimensions of ducting
or les
sMa
x. rise
Dimensions of ducting
InletductHoles for
self-tapping screws
Dimen
sions
of du
cting
All measurements are in mm.
FDUM 71~90KXE6F
FDUM 112~160KXE6F
FDUM 22~56KXE6F
152
All-outside air ducted
› 4 power levels (9.00 ~ 28.00 kW)› Maximum compactness: only 28 cm (9.00~14.00 kW) and only 37.9 cm (22.40~28.00 kW)› Max pressure head of fans: 200 Pa.› Automatic function “all-outside air“ to save energy when the outdoor
temperature drops below the set temperature.› Can be connected to 8~60HP outdoor units except Micro Compact KXZ
(4~6HP) and KXZ Smart
AIR CONDITIONING AND OUTDOOR AIR INTAKE
The diagram below illustrates the integration of the FDU-F unit inside a KXZ system
NoteCheck the possible connections and limits of use on the technical documentation.
FDU-FIU IU
KXZ OU
Air conditioning Outsiderenewal air co
rrido
r
rooms
Outgoing air
Renew
al air
Outside air
Outside airRen
ewal a
ir
The compact design, the fan head of 200 Pa and the lowest noise level on the market make the unit suitable for installation in environments designed to ensure comfort and relaxation
Indoor units
VRF Multi systems
Model FDU650FKXZE1 FDU1100FKXZE1 FDU1800FKXZE1 FDU2400FKXZE1Nominal Cool. capacity kW 9.00 14.00 22.40 28.00Nominal Heat. capacity kW 6.50 10.50 16.00 21.50Power 220-240V~ 50HzCool. power consumption kW 0.24 - 0.25 0.35 - 0.36 1.16 - 1.20 1.16 - 1.20Heat. power consumption kW 0.24 - 0.25 0.35 - 0.36 1.16 - 1.20 1.16 - 1.20Rated current in Cool. A 1.80 - 1.70 2.30 - 2.20 6.80 - 6.50 6.80 - 6.50Rated current in Heat. A 1.80 - 1.70 2.30 - 2.20 6.80 - 6.50 6.80 - 6.50Sound power level dB(A) 55 62 68 70Sound pressure level dB(A) Hi 31 Hi 37 Hi 42 Hi 45External dimensions (HxLxD) mm 280 × 950 × 635 280 × 1370 × 740 379 × 1600 × 893 379 × 1600 × 893Net weight kg 34 54 89 89Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Centrifugal fan x 2 Centrifugal fan x 3Motor W 130 100 + 200 130 + 350 130 + 350Starting method Direct, in lineAir flow (standard) m3h Hi 660 Hi 1080 Hi 1800 Hi 2400Static pressure Pa Max: 200 Max: 200 Max: 200 Max: 200Air filter and quantity To be found locallyShock and vibration absorption Rubber vibration absorber (for fan motor)Thermal and acoustic insulation Polyurethane foam
Control devices Wired remote control: RC-EX3, RC-E5, RCH-E3Remote control kit: RCN-KIT4-E2
Ambient temperature control Electronic thermostat
Safety devices Thermal protection for the fan motorAnti-frost protection thermostat
Diameter cooling/refrigerant pipes mm (inch) Liquid side ø9.52 (3/8”)Gas side ø15.88 (5/8”) Gas side ø19.05 (3/4”) Gas side ø22.22 (7/8”)
Joining method by flare fittings by blazingRefrigerant R410ADrain pump Built-inCondensate drain Connectable with VP25Piping insulation Necessary (on both sides, liquid and gas)Accessories included Condensate drain pipe
FDU 650~2400FKXZE1
153
Diagrams and measurements
Ref. Item FDU650FKXZE1A Gas side ø 15.88 (5/8") flareB Liquid side ø 9.52 (3/8") flareC1 Condensate drain VP25 (note 2)C2 Condensate drain (dr. nat.) VP20D Hole for electrical cablesE Suspension rods M10F Outside air openingG Air outlet openingH Inspection hole 450 x 450
Ref. Item FDU1800FKXZE1 FDU2400FKXZE1
A Gas side ø 19.05 (3/4") flare
ø 22.22 (7/8") flare
B Liquid side ø 9.52 (3/8") flareC Condensate drain VP25 (note 2)D Hole for electrical cables
E Suspension rods M10F Inspection hole 450 x 450
Ref. Item FDU1100FKXZE1A Gas side ø 15.88 (5/8") flareB Liquid side ø 9.52 (3/8") flareC1 Condensate drain VP25 (note 2)C2 Condensate drain (dr. nat.) VP20D Hole for electrical cablesE Suspension rods M10F Outside air openingG Air outlet openingH Inspection hole 450 x 450
Notes: 1. The label with the model code is applied inside the extraction grille.2. Prepare the connection for the VP25 condensate drain on site.
Space for installation and service
or mo
re
Condensate pipe(accessory)On-site connection
Suspension rod spacingInstallation plate for suspension rod
Electrical box
Susp
ensio
n rod
spac
ing
Holes for self-tapping screws
VIEW M
Holes for self-tapping screws
Dimen
sions
of
ducti
ng Air delivery
Dimensions of ducting
or les
sMa
x. rise
Dimensions of ducting
Inlet duct
Inspection hole
or mo
re
Notes: 1. The label with the model code is applied inside the extraction grille.2. Prepare the connection for the VP25 condensate drain on site.
Space for installation and service
or mo
re
Suspension rod spacingInstallation plate for suspension rod
Electrical box
Susp
ensio
n rod
spac
ing
Holes for self-tapping screws
Holes for self-tapping screws
Dimen
sions
of
ducti
ng
Air delivery
Dimensions of ducting
or les
sMa
x. rise
Dimensions of ducting
Inlet duct
Inspection hole
or mo
re
Hole
Hole
Dimen
sions
of du
cting
Dimensions of ducting
Dimen
sions
of du
cting
Air delivery
Inlet duct
Susp
ensio
n rod
spac
ing
Notes: 1. The label with the model code is applied inside the extraction grille.
Space for installation and service
or mo
re
Inspectionhole or
more
Installation plate for suspension rod
Electrical box
Suspension rod spacing
Dimensions of ducting
Dimen
sions
of du
cting
VIEW M
Dimen
sions
of du
cting
All measurements are in mm.
FDU 650FKXZE1
FDU 1100FKXZE1
FDU 1800~2400FKXZE1
154
Ducted with low adjustable head
› 7 power levels (1.50 ~ 7.10 kW)› Ideal for applications in hotels, hospitals and small offices› Optional filter kit: UT-FL1EF (FDUT 15~36); UT-FL2EF (FDUT 45~56); UT-FL3EF (FDUT 71)› Ducting flange: UT-SAT1EF (FDUT 15~36); UT-SAT2EF (FDUT 45~56); UT-SAT3EF (FDUT 71)
COMPACT SIZE
Extremely quiet: only 22 dB(A) for models from 1.50 - 2.80 kW.
models FDUT 15, 22, 28, 36 KXE6F models FDUT 45, 56 KXE6F
VERY QUIET OPERATION
Unit
Model FDUT15KXE6F-E FDUT22KXE6F-E FDUT28KXE6F-E FDUT36KXE6F-E FDUT45KXE6F-E FDUT56KXE6F-E FDUT71KXE6F-ERear recovery
Nominal Cool. capacity kW 1.50 2.20 2.80 3.60 4.50 5.60 7.10Nominal Heat. capacity kW 1.70 2.50 3.20 4.00 5.00 6.00 8.00Power 220-240V~ 50HzCool. power consumption kW 0.06 - 0.06 0.07 - 0.07 0.07 - 0.07 0.07 - 0.07 0.08 - 0.08 0.08 - 0.08 0.08 - 0.08Heat. power consumption kW 0.06 - 0.06 0.07 - 0.07 0.07 - 0.07 0.07 - 0.07 0.08 - 0.08 0.08 - 0.08 0.07 - 0.07Rated cool. current in A 0.27 - 0.27 0.28 - 0.25 0.28 - 0.25 0.32 - 0.29 0.36 - 0.33 0.38 - 0.35 0.42 - 0.42Rated heat. current in A 0.27 - 0.27 0.29 - 0.25 0.29 - 0.25 0.33 - 0.28 0.34 - 0.32 0.35 - 0.33 0.46 - 0.46Sound pressure level dB(A) Hi 28 Me 26 Lo 22 Hi 33 Me 30 Lo 26 Hi 34 Me 32 lo 28 Hi 35 Me 33 Lo 30 Hi 35 Me 31 Lo 28Sound power level dB(A) 52 57 58 59 59External dimensions (HxLxD) mm 200 x 750 x 500 200 x 950 x 500 220 x 1150 x 565Net weight kg 21 22 25 31Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Centrifugal fan x 2 Centrifugal fan x 3 Centrifugal fan x 4Motor W 14 38 100Starting method Direct, in lineAir flow (standard) m3/h Hi 360 Me 300 Lo 240 Hi 450 Me 360 Lo 300 Hi 510 Me 420 Lo 330 Hi 690 Me 540 Lo 420 Hi 750 Me 540 Lo 432 Hi 960 Me 780 Lo 570Static pressure Pa St, 10 Max 35 St, 10 Max 50Renewal air inlet Not possibleAir filter and quantity UT-FL1EF (Optional) UT-FL2EF (Optional) UT-FL3EF (Optional)Shock and vibration absorption Rubber sleeve (for fan motor)Thermal and acoustic insulation Polyurethane foamControl devices Optional wired remote control RC-E5, optional RCH-E3, optional RCN-KIT4-E2, optional RC-EX3Ambient temperature control Electronically-controlled thermostat
Safety devices Thermal protection for the fan motorAnti-frost protection thermostat
Diameter cooling/refrigerant pipes mm (inch) Liquid side: ø 6.35 (1/4”) Liquid side: ø 9.52 (3/8”)Gas side: ø 9.52 (3/8”) Gas side: ø 12.7 (1/2”) Gas side: ø 15.88 (5/8")
Joining method by flare fittingsRefrigerant R410ADrain pump Built-inCondensate drain Connectable with VP25Piping insulation Necessary (on both sides, liquid and gas)Accessories Assembly kit, UT-SAT1EF (Flange) Assembly kit, UT-SAT2EF (Flange) Assembly kit, UT-SAT3EF (Flange)
Indoor units
VRF Multi systems
FDUT 15~71KXE6F-E
155
Diagrams and measurements
Ref. ItemModel FDUT15~28KXE6F-E
A Gas side ø 9.52 (3/8") flareB Liquid side ø 6.35 (1/4") flare
C1 Condensate drain VP25 (used with connected connector)
C2 Condensate drain (dr. nat.) VP25 (used with connected connector)
D Hole for electrical cables ø 25 x 2E Suspension rods M10F Inspection hole 450 x 450; 270 x 770
Ref. ItemModel FDUT45~56KXE6F-E
A Gas side ø 12.7 (1/2") flareB Liquid side ø 6.35 (1/4") flare
C1 Condensate drain VP25 (used with connected connector)
C2 Condensate drain (dr. nat.) VP25 (used with connected connector)
D Hole for electrical cables ø 25 x 2E Suspension rods M10F Inspection hole 450 x 450; 270 x 770
Ref. ItemA Gas side ø 15.88 (5/8") flareB Liquid side ø 9.52 (3/8") flare
C1 Condensate drain VP25 (used with connected connector)
C2 Condensate drain (dr. nat.) VP25 (used with connected connector)
D Hole for electrical cables ø 25 x 2E Suspension rods M10F Inspection hole 450 x 450; 270 x 770
Dimensions of ducting
Inlet duct
Dimen
sions
of du
cting
Dimensions of ducting
Dimen
sions
of du
cting
Dimensions of ducting
Dimen
sions
of du
cting
Suspension rod spacing
Installation plate for suspension rod
Electrical box
Condensate pipe(accessory)On-site connection
Inlet duct
Inlet duct
Susp
ensio
n rod
spac
ing
Suspension rod spacing
Installation plate for suspension rod
Electrical box
Condensate pipe(accessory)On-site connection
Susp
ensio
n rod
spac
ing
Suspension rod spacing
Installation plate for suspension rod
Electrical box
Condensate pipe(accessory)On-site connection
Susp
ensio
n rod
spac
ingDim
ensio
ns of
ducti
ng
Air delivery
or les
sMa
x. rise
Dimensions of ducting
Dimen
sions
of du
cting
Air delivery
or les
sMa
x. rise
Dimensions of ducting
Dimen
sions
of du
cting
Air delivery
or les
sMa
x. rise
Dimensions of ducting
Space for installation and service
obstacleor more
obstacleView from lower side
of unitInlet from rear with duct Inlet from rear or more
or more obstacle
or mo
re
or more obstacle
or mo
reor
more
or mo
re
Space for installation and service
obstacleor more
obstacleView from lower side
of unitInlet from rear with duct Inlet from rear or
more
or more obstacle
or mo
re
or more obstacle
or mo
reor
more
or mo
re
Space for installation and service
obstacleor more
obstacleView from lower side
of unit
Inlet from rear with duct Inlet from rear
or more
obstacle or mo
re or mo
re
or more
obstacle or mo
re or mo
re
Ref. ItemModel FDUT36KXE6F-E
A Gas side ø 12.7 (1/2") flareB Liquid side ø 6.35 (1/4") flare
C1 Condensate drain VP25 (used with connected connector)
C2 Condensate drain (dr. nat.) VP25 (used with connected connector)
D Hole for electrical cables ø 25 x 2E Suspension rods M10F Inspection hole 450 x 450; 270 x 770
All measurements are in mm.
FDUT 45~56KXE6F-E
FDUT 71KXE6F-E
FDUT 15~36KXE6F-E
156
Ducted compact
› 3 power levels (2.20 ~ 3.60 kW)› Maximum compactness: only 25.7 cm in height.› Maximum installation flexibility› Rear air intake from back› Extremely quiet: only 27 dB(A)› UH-DU-E condensate drain kit (optional)› UH-FL-1E filter kit (optional)
The electrical box and the condensate drain pump can be installed on both sides of the unit, while the incoming air penetrates through the bottom or the back.The lowest noise impact on the market makes the unit suitable for installation in rooms designed to ensure comfort and relaxation. Compact and lightweight, FDUH is ideal for installation in hotels, hospitals and small offices.Furthermore, the application of the RCH-E3 remote control (optional) enables the user to take advantage of a simplified device to prepare and make the environment to be air conditions as comfortable as possible.
Electrical box
Condensate drain fall
ELECTRICAL BOX
Model FDUH22KXE6F FDUH28KXE6F FDUH36KXE6FNominal Cool. capacity kw 2.20 2.80 3.60Nominal Heat. capacity kw 2.50 3.20 4.00Power 220-240V~ 50HzCool. power consumption kw 0.05 - 0.07 0.05 - 0.07 0.05 - 0.07Heat. power consumption kw 0.05 - 0.07 0.05 - 0.07 0.05 - 0.07Rated cool. current in A 0.25 - 0.32 0.25 - 0.32 0.25 - 0.32Rated heat. current in A 0.25 - 0.32 0.25 - 0.32 0.25 - 0.32Sound pressure level dB(A) Hi 33 Me 30 Lo 27Sound power level dB(A) 60External dimensions (HxLxD) mm Unit 257 x 570 x 530Net weight kg 22Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Centrifugal fan x 1Motor W 30Starting method Direct, in lineAir flow (standard) m3/h Hi 420 Me 390 Lo 360Static pressure Pa 30Renewal air inlet Not possibleAir filter and quantity OptionalShock and vibration absorption Rubber sleeve (for fan motor)Thermal and acoustic insulation Polyurethane foamControl devices Optional wired remote control RC-E5, optional RCH-E3, optional RCN-KIT4-E2, optional RC-EX3Ambient temperature control Electronically-controlled thermostat
Safety devices Overvoltage protection for the fan motorAnti-frost protection thermostat
Diameter cooling/refrigerant pipes mm (inch) Liquid side: ø 6.35 (1/4")Gas side: ø 9.52 (3/8") Gas side: ø 12.7 (1/2")
Joining method by flare fittingsRefrigerant R410ACondensate drain Connectable with VP20Piping insulation Necessary (on both sides, liquid and gas)Accessories UH-FL1E (filter); UH-DU-E (condensate drain pump)
Indoor units
VRF Multi systems
FDUH 22~36KXE6F
157
Diagrams and measurements
Ref. ItemModel FDUH22~28KXE6F FDUH36KXE6F
A Gas side ø 9.52 (3/8") flare ø 12.7 (1/2") flareB Liquid side ø 6.35 (1/4") flareC1,2 Condensate drain VP20 (note 2)D Hole for electrical cables ø 30E Suspension rods M10F Inspection hole 635 x 890 (note 3)
Notes: 1. The label with the model code is applied inside the extraction grille.2. Prepare the connection for the VP20 condensate drain on site (for drain pipes you can choose C1 or C2).3. When the electrical box is found on the rear, the installation space must be modified for this new position.4. The electrical box and condensate drain pipe can be moved to the rear.
Space for installation and serviceSuspension rod spacing
Electrical box
Holes for self-tapping screws
Condensate pipe(accessory)On-site connection (note 4)
Air delivery
Dimensions of ducting
Dimen
sions
of du
cting
air ou
tlet
Note 4Su
spen
sion r
od sp
acing
Holes for self-tapping screws
VIEW G
VIEW G
Lower plate(Can be located on the rear side)
(Can be located on the rear side)
Holes for self-tapping screws
In case of bottom air intake
All measurements are in mm.
FDUH 22~36KXE6F
158
› 8 power levels (1.50 ~ 9.00 kW)› Simple, modern design for seamless integration into any environment (1.50~5.60 kW)› Maximum compactness: only 23 cm in depth (1.50~5.60 kW models)› Simplified maintenance and cleaning thanks to the easily
removable front panel
Wall
Indoor units
VRF Multi systems
Model FDK15KXZE1 FDK22KXZE1 FDK28KXZE1 FDK36KXZE1 FDK45KXZE1 FDK56KXZE1 FDK71KXZE1 FDK90KXZE1Nominal Cool. capacity kW 1.50 2.20 2.80 3.60 4.50 5.60 7.10 9.00Nominal Heat. capacity kW 1.70 2.50 3.20 4.00 5.00 6.30 8.00 10.00Power 220-240V~ 50HzCool. power consumption kW 0.02 0.02 0.02 0.03 0.03 0.03 0.04 0.05Heat. power consumption kW 0.02 0.02 0.02 0.03 0.03 0.03 0.04 0.05Rated current in Cool. A 0.18 - 0.16 0.18 - 0.16 0.18 - 0.16 0.27 - 0.25 0.27 - 0.25 0.27 - 0.25 0.34 - 0.31 0.42 - 0.39Rated current in Heat. A 0.18 - 0.16 0.18 - 0.16 0.18 - 0.16 0.27 - 0.25 0.27 - 0.25 0.27 - 0.25 0.34 - 0.31 0.42 - 0.39Sound pressure level in Cool. dB(A) PHi 38 Hi 34 Me 31 Lo 28 PHi 38 Hi 36 Me 32 Lo 28 PHi 38 Hi 36 Me 32 Lo 28 PHi 40 Hi 38 Me 33 Lo 28 PHi 43 Hi 41 Me 36 Lo 33 PHi 43 Hi 41 Me 36 Lo 33 PHi 42 Hi 40 Me 37 Lo 35 PHi 44 Hi 42 Me 39 Lo 35Sound pressure level in Heat. PHi 38 Hi 34 Me 31 Lo 28 PHi 38 Hi 36 Me 32 Lo 28 PHi 38 Hi 36 Me 32 Lo 28 PHi 40 Hi 38 Me 33 Lo 28 PHi 43 Hi 41 Me 36 Lo 33 PHi 44 Hi 42 Me 37 Lo 33 PHi 42 Hi 40 Me 37 Lo 35 PHi 44 Hi 42 Me 39 Lo 35Sound power level in Cool. dB(A) 54 55 55 58 58 58 59 61Sound power level in Heat. 54 55 55 58 58 61 59 61External dimensions (HxLxD) mm 290 × 870 × 230 290 × 870 × 230 290 × 870 × 230 290 × 870 × 230 290 × 870 × 230 290 × 870 × 230 339 × 1197 × 262 339 × 1197 × 262Exterior appearance Snow whiteMunsell colour (8.0Y9.3/0.1) similar (8.0Y9.3/0.1) similar (8.0Y9.3/0.1) similar (8.0Y9.3/0.1) similar (8.0Y9.3/0.1) similar (8.0Y9.3/0.1) similar (8.0Y9.3/0.1) similar (8.0Y9.3/0.1) similarNet weight kg 11.5 11 11 12 11.5 11.5 17 17Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Tangential × 1Motor W 42 42 42 42 42 42 56 56Starting method Direct, in lineAir flow in Cool. m3h PHi 342 Hi 300 Me 270 Lo 216 PHi 510 Hi 480 Me 360 Lo 300 PHi 510 Hi 480 Me 360 Lo 300 PHi 660 Hi 600 Me 480 Lo 420 PHi 720 Hi 660 Me 540 Lo 480 PHi 720 Hi 660 Me 540 Lo 480 PHi 1260 Hi 1140 Me 960 Lo 840 PHi 1380 Hi 1260 Me 1140 Lo 960Air flow in Heat. PHi 342 Hi 300 Me 270 Lo 216 PHi 510 Hi 480 Me 360 Lo 300 PHi 510 Hi 480 Me 360 Lo 300 PHi 660 Hi 600 Me 480 Lo 420 PHi 720 Hi 660 Me 540 Lo 480 PHi 780 Hi 720 Me 600 Lo 480 PHi 1260 Hi 1140 Me 960 Lo 840 PHi 1380 Hi 1260 Me 1140 Lo 960Static pressure Pa 0Renewal air inlet Not availableAir filter and quantity Propylene mesh filter x 2 (washable)Shock and vibration absorption Rubber vibration absorber (for fan motor)Thermal and acoustic insulation Polyurethane foam
Control devices Wired remote control: RC-EX3, RC-E5, RCH-E3Remote control kit: RCN-K-E2 Remote control kit: RCN-K71-E2
Ambient temperature control Electronically-controlled thermostat
Safety devices Thermal protection for the fan motorAnti-frost protection thermostat
Diameter cooling/refrigerant pipes mm (inch) Liquid side: ø6.35 (1/4”) Liquid side ø9.52 (3/8”)Gas side: ø9.52 (3/8”) Gas side ø12.7 (1/2”) Gas side ø15.88 (5/8”)
Joining method by flare fittingsRefrigerant R410ACondensate drain Connectable with VP16Piping insulation Necessary (on both sides, liquid and gas)Accessories included Assembly kit
FDK 15~90KXZE1
FDK 15~56KXZE1
NEW
FDK 71~90KXZE1
159
Diagrams and measurementsAll measurements are in mm.
Ref. ItemModel FDK22~28KXZE1 FDK36~56KXZE1
A Gas side ø 9.52 (3/8") flare ø 12.7 (1/2") flareB Liquid side ø 6.35 (1/4") flareC Hole for right rear pip. ø 65D Hole for left rear pip. ø 65E Condensate drain pipe VP16F Electrical cable outletG Pipe output (both sides)
Pipe output from bottom(see image above)
(Service space)
Installation plate Unit
Space for installation and maintenance front view
Ref. ItemModel FDK 71~90KXZE1
A Gas side ø 15.88 (5/8") flareB Liquid side ø 9.52 (3/8") flareC Hole for right rear pip. ø 65D Hole for left rear pip. ø 65E Condensate drain pipe VP16F Electrical cable outletG Pipe output (both sides)
(Service space)
(Serv
ice sp
ace)
(Serv
ice sp
ace)
Electrical box
Pipe output from bottom(see image above)
(Service space)Installation plate Unit
Space for installation and maintenance front view
(Service space)
(Serv
ice
spac
e)
Electrical box
(Serv
ice
spac
e)
FDK 71~90KXZE1
FDK 15~56KXZE1
160
Ceiling
› 6 power levels (3.60 ~ 14.0 kW)› Ideal for very large environments, thanks to the particularly wide air flow› Maximum compactness: only 21 cm high (3.60 to 7.00 kW models)› Quick and easy installation, thanks to a net weight of only 28 kg (3.60 to 5.60
kW models)› Reception kit for RCN-E-E2 infrared remote control (optional)
FLEXIBLE PIPE ORIENTATION
Maximum flexibility: the refrigerant piping can be attached in 3 different positions (rear, top, right), as can that of the condensate drain (left, right).
Top
Rear
Right
Indoor units
VRF Multi systems
Model FDE36KXZE1 FDE45KXZE1 FDE56KXZE1 FDE71KXZE1 FDE112KXZE1 FDE140KXZE1Nominal Cool. capacity kW 3.60 4.50 5.60 7.00 11.20 14.00Nominal Heat. capacity kW 4.00 5.00 6.30 8.00 12.50 16.00Power 220-240V~ 50HzCool. power consumption kW 0.05 - 0.06 0.05 - 0.06 0.05 - 0.06 0.10 - 0.11 0.14 - 0.16 0.16 - 0.18Heat. power consumption kW 0.05 - 0.06 0.05 - 0.06 0.05 - 0.06 0.09 - 0.10 0.13 - 0.15 0.15 - 0.17Rated current in Cool. A 0.25 - 0.26 0.25 - 0.26 0.25 - 0.26 0.46 - 0.48 0.65 - 0.67 0.77 - 0.78Rated current in Heat. A 0.23 - 0.25 0.23 - 0.25 0.23 - 0.25 0.42 - 0.44 0.59 - 0.63 0.70 - 0.72Sound pressure level dB(A) Hi 39 Me 38 Lo 36 Hi 39 Me 38 Lo 36 Hi 39 Me 38 Lo 36 Hi 41 Me 39 Lo 37 Hi 44 Me 41 Lo 39 Hi 46 Me 44 Lo 43Sound power level dB(A) 60 60 60 62External dimensions (hxlxd) mm 210 × 1.070 × 690 210 × 1.070 × 690 210 × 1.070 × 690 210 × 1.320 × 690 250 × 1.620 × 690 250 × 1.620 × 690Exterior appearance Chalk whiteMunsell colour (6.8Y8.9 / 0.2 ) similarNet weight kg 28 28 28 37 49 49Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Centrifugal fan x 2 Centrifugal fan x 4Motor W 25 25 25 20 × 2 30 × 2 40 × 2Starting method Direct, in lineAir flow (standard) m3h Hi 600 Me 540 Lo 420 Hi 600 Me 540 Lo 420 Hi 600 Me 540 Lo 420 Hi 960 Me 840 Lo 720 Hi 1560 Me 1380 Lo 1260 Hi 1740 Me 1560 Lo 1380Static pressure Pa 0Renewal air inlet Not possibleAir filter and quantity Plastic mesh filter x 2 (washable)Shock and vibration absorption Rubber sleeve (for fan motor)Thermal and acoustic insulation Polyurethane foamControl devices Optional wired remote control RC-E5, optional RCH-E3, optional RCN-E-E2, optional RC-EX3Ambient temperature control Electronically-controlled thermostat
Safety devices Overvoltage protection for the fan motorAnti-frost protection thermostat
Diameter cooling/refrigerant pipes mm (inch) Liquid side ø6.35 (1/4”) Liquid side ø9.52 (3/8”)Gas side ø12.7 (1/2”) Gas side ø15.88 (5/8”)
Joining method by flare fittingsRefrigerant R410ACondensate drain Connectable with VP20Piping insulation Necessary (on both sides, liquid and gas)Accessories Assembly kit
FDE 36~140KXZE1
161
Diagrams and measurements
Space for installation and service
obstacle
When installing more than one unit, it is necessary to keep a distance of 4 m or more between one machine and the next.
or more
Condensate pipe (accessory)On-site connection
Suspension rod spacing
or mo
re
Air delivery
Extraction grille
Suspension rod spacing
The slope of the condensate drain pipe inside the unit must be 10 mm.
Ref. ItemA Gas side ø 12.7 (1/2") flareB Liquid side ø 6.35 (1/4") flareC1,2 Condensate drain VP20D Hole for suspension cables M10 or M8E Rear pre-cut PE coverF Top pre-cut Cover plateG Hole for condensate drain Pre-cut
or more
or more
Position for bottom and top pre-cut
Hole for condensate drain pipe (left output)
Piping can be connected in 3 different directions. Remove the pre-cut part, using a cutter of a similar instrument.
Notes: 1. The label with the model code is applied inside the extraction grille.
Space for installation and service
obstacle
When installing more than one unit, it is necessary to keep a distance of 4.5 m or more between one machine and the next.
or more
Condensate pipe (accessory)On-site connection
Suspension rod spacing
or mo
re
Air delivery
Extraction grille
Suspension rod spacing The slope of the condensate drain pipe inside the unit must be 10 mm.
Ref. ItemA Gas side ø 15.88 (5/8") flareB Liquid side ø 9.52 (3/8") flareC1,2 Condensate drain VP20D Hole for suspension cables M10 or M8E Rear pre-cut PE coverF Top pre-cut Cover plateG Hole for condensate drain Pre-cut
or moreor more
Position for bottom and top pre-cut
Hole for condensate drain pipe (left output)
Piping can be connected in 3 different directions. Remove the pre-cut part, using a cutter of a similar instrument.
Notes: 1. The label with the model code is applied inside the extraction grille.
Right pre-cut
Right pre-cut
Space for installation and service
obstacle
When installing more than one unit, it is necessary to keep a distance of 5 m or more between one machine and the next.
or more
Condensate pipe (accessory)On-site connection
Suspension rod spacing
or mo
re
Air delivery
Extraction grille
Suspension rod spacing
The slope of the condensate drain pipe inside the unit must be 10 mm.
Ref. ItemA Gas side ø 15.88 (5/8") flareB Liquid side ø 9.52 (3/8") flareC1,2 Condensate drain VP20D Hole for susp. cables M10 or M8E Rear pre-cut PE coverF Top pre-cut Cover plateG Hole for condensate drain Pre-cut
or more
or more
Position for bottom and top pre-cut
Hole for condensate drain pipe (left output)
Piping can be connected in 3 different directions. Remove the pre-cut part, using a cutter of a similar instrument.
Notes: 1. The label with the model code is applied inside the extraction grille.
Right pre-cut
All measurements are in mm.
FDE 71KXZE1
FDE 112~140KXZE1
FDE 36~56KXZE1
162
Console
› 3 power levels (2.80 ~ 5.60 kW)› Particularly wide, uniform air flow› Maximum compactness: only 23.8 cm in depth› Quick and easy installation, thanks to a net weight of only 19 kg (2.80 kW model)› Reception kit for RCN-FW-E2 infrared remote control (optional)
Simultaneous louver selection - top and bottom - can be selected at the same time using the special button. Control all other functions on the unit with the special remote control.
With infrared remote control use
UNIFORM AIR DISTRIBUTION
Model FDFW28KXE6F FDFW45KXE6F FDFW56KXE6FNominal Cool. capacity kW 2.80 4.50 5.60Nominal Heat. capacity kW 3.20 5.00 6.30Power 220-240V~ 50HzCool. power consumption kW 0.02 - 0.02 0.02 - 0.02 0.03 - 0.03Heat. power consumption kW 0.02 - 0.02 0.02 - 0.02 0.03 - 0.03Rated cool. current in A 0.10 - 0.09 0.10 - 0.09 0.15 - 0.14Rated heat. current in A 0.10 - 0.09 0.10 - 0.09 0.15 - 0.14Sound pressure level dB(A) Hi 36 Me 34 Lo 30 Hi 38 Me 36 Lo 33 Hi 44 Me 37 Lo 33Sound power level dB(A) 55 57 60External dimensions (HxLxD) mm 600 x 860 x 238Exterior appearance Fine snowMunsell colour ( 8.0Y9.3 / 0.1 ) similarNet weight kg 19 20Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Turbo fan x 1Motor W 40Starting method Direct, in lineAir flow (standard) m3/h Hi 540 Me 480 Lo 420 Hi 660 Me 540 Lo 480Static pressure Pa 0Renewal air inlet Not possibleAir filter and quantity Propylene mesh filter x 1 (washable)Shock and vibration absorption Rubber sleeve (for fan motor)Thermal and acoustic insulation Polyurethane foamControl devices Optional wired remote control RC-E5, optional RCH-E3, optional ; RCN-FW-E2, optional RC-EX3Ambient temperature control Electronically-controlled thermostat
Safety devices Overvoltage protection for the fan motorAnti-frost protection thermostat
Diameter cooling/refrigerant pipes mm (inch) Liquid side: ø 6.35 (1/4")Gas side: ø 9.52 (3/8") Gas side: ø 12.7 (1/2")
Joining method by flare fittingsRefrigerant R410ACondensate drain Connectable with VP16 (I,D, 16.0)Piping insulation Necessary (on both sides, liquid and gas)Accessories Assembly kit
Indoor units
VRF Multi systems
FDFW 28~56KXE6F
163
Diagrams and measurements
Unit
Service space
Space for installation and maintenance front view
Pipe output from bottom(see image above)
Notes: 1. The label with the model code is applied inside the extraction grille.2. When installing on walls, leave the unit at least 150 mm from the ground.
Service space
Assembly plate
Ref. ItemModel FDFW28KXE6F FDFW45~56KXE6F
A Gas side ø 9.52 (3/8") flare ø 12.7 (1/2") flareB Liquid side ø 6.35 (1/4") flareC Hole for right rear pip. ø 65D Hole for left rear pip. ø 65E Condensate drain pipe VP16F Screw for fixing the indoor unit ø 5G Pipe output (both sides)
All measurements are in mm.
FDFW 28~56KXE6F
164
Flush floor
› 4 power levels (2.80 ~ 7.10 kW)› Maximum compactness: only 63 cm high and 22.5 cm deep
Model FDFU28KXE6F FDFU45KXE6F FDFU56KXE6F FDFU71KXE6FNominal Cool. capacity kW 2.80 4.50 5.60 7.10Nominal Heat. capacity kW 3.20 5.00 6.30 8.00Power 220-240V~ 50HzCool. power consumption kW 0.09 - 0.10 0.09 - 0.10 0.09 - 0.10 0.09 - 0.10Heat. power consumption kW 0.09 - 0.10 0.09 - 0.10 0.09 - 0.10 0.09 - 0.10Rated cool. current in A 0.41 - 0.42 0.41 - 0.42 0.41 - 0.42 0.41 - 0.42Rated heat. current in A 0.41 - 0.42 0.41 - 0.42 0.41 - 0.42 0.41 - 0.42Sound pressure level dB(A) Hi 41 Me 38 Lo 36 Hi 43 Me 41 Lo 40Sound power level dB(A) 58 60External dimensions (HxLxD) mm 630 x 1077 x 225 630 x 1362 x 225Net weight kg 25 32Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Centrifugal fan x 2Motor W 30 40Starting method Direct, in lineAir flow (standard) m3/h Hi 720 Me 660 Lo 600 Hi 840 Me 720 Lo 600 Hi 1080 Me 900 Lo 720Static pressure Pa 0Renewal air inlet Not possibleAir filter and quantity Propylene mesh filter x 1 (washable)Shock and vibration absorption Rubber sleeve (for fan motor)Thermal and acoustic insulation Polyurethane foamControl devices Optional wired remote control RC-E5, optional RCH-E3, optional RCN-KIT4-E2, optional RC-EX3Ambient temperature control Electronically-controlled thermostat
Safety devices Overvoltage protection for the fan motorAnti-frost protection thermostat
Diameter cooling/refrigerant pipes mm (inch) Liquid side: ø 6.35 (1/4") Liquid side: ø 9.52 (3/8")Gas side:ø 9.52 (3/8") Gas side: ø 12.7 (1/2") Gas side: ø 15.88 (5/8")
Joining method by flare fittingsRefrigerant R410ACondensate drain Connectable with VP20Piping insulation Necessary (on both sides, liquid and gas)Accessories Assembly kit
Indoor units
VRF Multi systems
FDFU 28~71KXE6F
165
Diagrams and measurements
DIMENSIONS
Model a b c d e
FDFU 28~56KXE6F 786 810 722 750 806FDFU 71KXE6F 1071 1095 1007 1035 1091
Notes: 1. The label with the model code is applied inside the extraction grille.
Ref. ItemModel FDFU28KXE6F FDFU45~56KXE6F FDFU71KXE6F
A Gas side ø 9.52 (3/8") flare ø 12.7 (1/2") flare ø 15.88 (5/8") flareB Liquid side ø 6.35 (1/4") flare ø 9.52 (3/8") flareC Condensate drain Lead screw PT20A, 360 mmD Slot M10E Metal arms for floor fixing M8
Slot
Air filter
Electrical box
Level adjustment screw
Slot
Hose
Electronic expansion valve box
Space for installation and service
lining lining
All measurements are in mm.
FDFU 28~71KXE6F
166
The simple and flexible solution for increasing comfort in buildings, with high energy performance
DXA-DU-E: condensate drain kit up to 60 cm (optional)
The SAF DX units, available in 5 power ratings, is a device designed to increase the comfort capacity of KXZ systems located in buildings, with their high quality profile in terms of energy.Extremely flexible in that it operates independently from the regenerator, it is able to optimise temperature of the primary air taken in by the SAF regenerators or by similar systems installed in the building. Its compact size and installation separate from the fan unit, solve numerous installation problems; the lack of moving parts makes it possible to install the unit in a wider range of locations and reduces noise to a minimum.
•CanbecombinedwithallindoorandoutdoorunitsintheKXZrange*.
•CanbeconnectedtotheSuperlinknetworkandalltheavailablecentralised controls.
•ItispossibletousealltheKXZserieslocalcontrols(tointegrateinto the system seamlessly and easily).
•Thecondensatedrainpumpisavailableasanoptional.•Theextractiontemperatureordeliverytemperaturecanbe
controlled alternately**.
Note* If using the SAF DX, the load index available for the outdoor unit is reduced to 100% of
the rated capacity.** The available options vary depending on configurations.
The SAF DX post-treatment is not intended to replace an indoor unit.
SAF DX
Indoor air
Air expelled
Outside air
Heatexchanger
Inlet air
Renewal air delivery T. sensorT Sensor. air renewal
Direct expansion coil for heating or cooling
Unit model SAF DX250E6 SAF DX350E6 SAF DX500E6 SAF DX800E6 SAF DX1000E6Nominal Cool. capacity* kW 2.00 2.80 3.60 5.60 6.30Nominal Heat. capacity* kW 1.80 2.20 2.80 4.50 5.60Power Single phase 220-240V~ 50HzCool. power consumption W 7.20Heat. power consumption W 7.20Rated cool. current in A 0.05Rated heat. current in A 0.05External dimensions (HxLxD) mm 315 x 452 x 422 315 x 537 x 422 315 x 682 x 422 315 x 822 x 422Net weight kg 12.3 13.6 16.1 18.4Air flow (standard) m3/h 250 350 500 800 1000Static pressure Pa 38 66Control devices Optional wired remote control RC-E5, optional RCH-E3, optional RCN-KIT-3-E
Diameter cooling/refrigerant pipes mm (in) Liquid side: ø 6.35 (1/4”) Liquid side: ø 6.35 (1/4”) Liquid side: ø 9.52 (3/8”)Gas side: ø 9.52 (3/8”) Gas side: ø 12.7 (1/2”) Gas side: ø 15.88 (5/8”)
* Measured under the conditions specified in the table.
Inlet air temperature/ventilation Outdoor temperature StandardMode DB WB DB WBCooling * 27° C 19° C 35° C 24° C ISO- T1Heating** 20° C 7° C 6° C
** ISO-T1-compliant test.
Post-treatment modular unit SAF DX
SAF DX250E6SAF DX350E6SAF DX500E6SAF DX800E6SAF DX1000E6
SAF DX250~1000E6
167
Diagrams and measurements
Space for installation and service Space for installation and service
Dimensions of ducting
Electrical box
Indoor air
Outside airDim
ensio
ns of
ducti
ng
Inspection holeInspection hole
Dimensions of ducting
Electrical box
Indoor air
Outside air
Dimen
sions
of du
cting
Label with model code
Label with model code
Ref. ItemA Gas side ø 9.52 (3/8") flareB Liquid side ø 6.35 (1/4") flareC Condensate drain R1D Hole for power supply lineE Wiring holeF Suspension rods M10
Ref. ItemA Gas side ø 12.7 (1/2") flareB Liquid side ø 6.35 (1/4") flareC Condensate drain R1D Hole for power supply lineE Wiring holeF Suspension rods M10
Space for installation and serviceSpace for installation and service
Dimensions of ducting
Electrical box
Indoor air
Outside air
Dimen
sions
of du
cting
Inspection holeInspection hole
Dimensions of ducting
Electrical box
Indoor air
Outside air
Dimen
sions
of du
cting
Label with model code
Label with model code
Ref. ItemA Gas side ø 12.7 (1/2") flareB Liquid side ø 6.35 (1/4") flareC Condensate drain R1D Hole for power supply lineE Wiring holeF Suspension rods M10
Ref. ItemA Gas side ø 15.88 (5/8") flareB Liquid side ø 9.52 (3/8") flareC Condensate drain R1D Hole for power supply lineE Wiring holeF Suspension rods M10
All measurements are in mm.
Post-treatment modular unit SAF DX
SAF DX500E6SAF DX250E6, SAF DX350E6
SAF DX1000E6SAF DX800E6
168
EEV-KIT is a control kit for any type of AHU and/or fan coil with direct expansion coil that can be found on the market, which permits connection with KXZ OU.EEV-KIT consists of an electronic control system and an electronic expansion valve for refrigerant flow control.
(Air handling unit*) OU
* Can be found by different manufacturers on the market
Type of systemEEV-KIT
EEVKIT6-E-M EEVKIT6-E-CSingle - 1 or more boxes in parallel*
Multiple 1 box (Master) Multiple boxes (Slave)
Applications
Model EEV6-71-E EEV6-160-E EEV6-280-ESize (kW) 2.20~7.10 9.00~16.00 22.40~28.00
* Can connect to a single cooling system. In the case of more than one cooling system, make sure to use EEV-KIT control ASSY for multiple systems.
EEV-Control Assy EEV-Set
EEV-Set
FanFan
System configuration
• Inthecaseofasinglecoolingsystem,youmustuseoneEEVKIT6-E-C control for each expansion valve up to a maximum of 32.
• Inthecaseofamultiplecoolingsystem,youmustuseoneEEVKIT6-E-M 1 master control + no. EEVKIT6-E-C controls up to a maximum of 32.
• TheEEVKIT6-E-Ccontroliscommonuseforsingleandmultiplesystems.
Single cooling systemAsystem composed of several outdoor units with a single cooling circuit (see the two examples below). In the figure to the left, system A uses one single EEV-KIT. In the figure to the right, system B uses more than one EEV-KIT.
System A System B
This system only has an EEV-KIT installed on an internal coil consisting of a single exchanger. This type of system can be applied to internal coils with maximum power 10HP (28 kW).
It is a system that has more than one EEV-KIT installed in an internal coil consisting of multiple exchangers in a single cooling circuit. This system can reach a maximum power of 60HP (KXZ), 48HP (KXE6).
AHU
Control
valve 1
valve 2
control 1
control 2
AHU control system EEV-KIT
169
RC-E5
SC-SL4-AE/BE
SC-SL4-AE/BE
RC-E5
Advantages
• Possibilityofexpandingthesystemwithrespecttothesinglesystemuptoapowerof896kW (indoor unit: composed of 32 circuits, 28 kW).• Possibilityofremotecontrolthroughaspecialconnector.•Possibilityofcontrollingsteps.
SUPERLINK II CONNECTION
AHU
Fan
Master control
This system is composed of an air handling unit with the following characteristics:1. Multiple cooling circuits2. Presence of a Master control system that controls the whole system.
Multiple cooling system
Parts to be added to the single cooling system
•AMastercontrolsystem.• TheSlavecontrolsystemandtheexpansionvalvearethesamethatareusedforthesingle
cooling system.
EEV Master control
2 sensors
Air intake Delivery air
EEV Slave control
3 sensors1 EEV-KIT
filters filters
Heat exchanger temperature sensors (Thi-R1, R2, R3)
EEV Slave control
3 sensors1 EEV-KIT
filters filters
Heat exchanger temperature sensors (Thi-R1, R2, R3)
Single cooling system
System A
System B
Control line from remote
Superlink adapter
Multiple system
Multiple cooling system
Superlink adapter
Control line from remote
System A
DX-FCU: Direct expansion fan coilDX-AHU: Direct expansion air handling unit
Control system for UTA EEV-KIT