correlation based thermal design of air transport

135
CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT RACK CHASSIS A THESIS SUBMITTED TO THE GRADUATE SCHOOL OF NATURAL AND APPLIED SCIENCES OF MIDDLE EAST TECHNICAL UNIVERSITY BY BEKĐR ONUR ÇOLPA IN PARTIAL FULFILLMENT OF THE REQUIREMENTS FOR THE DEGREE OF MASTER OF SCIENCE IN MECHANICAL ENGINEERING AUGUST 2011

Upload: vankhuong

Post on 14-Dec-2016

213 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT RACK CHASSIS

A THESIS SUBMITTED TO THE GRADUATE SCHOOL OF NATURAL AND APPLIED SCIENCES

OF MIDDLE EAST TECHNICAL UNIVERSITY

BY

BEKĐR ONUR ÇOLPA

IN PARTIAL FULFILLMENT OF THE REQUIREMENTS

FOR THE DEGREE OF MASTER OF SCIENCE

IN MECHANICAL ENGINEERING

AUGUST 2011

Page 2: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

Approval of the thesis:

CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT RACK CHASSIS

submitted by BEKĐR ONUR ÇOLPA in partial fulfillment of the requirements for the degree of Master of Science in Mechanical Engineering Department, Middle

East Technical University by, Prof. Dr. Canan Özgen ________________ Dean, Graduate School of Natural and Applied Sciences

Prof. Dr. Süha Oral ________________ Head of Department, Mechanical Engineering

Assoc. Prof. Dr. Đlker Tarı ________________ Supervisor, Mechanical Engineering Dept., METU

Examining Committee Members:

Asst. Prof. Dr. Cüneyt Sert ________________ Supervisor, Mechanical Engineering Dept., METU

Assoc. Prof. Dr. Đlker Tarı ________________ Supervisor, Mechanical Engineering Dept., METU

Asst. Prof. Dr. Ahmet Yozgatlıgil ________________ Supervisor, Mechanical Engineering Dept., METU

Asst. Prof. Dr. Tuba Okutucu Özyurt ________________ Supervisor, Mechanical Engineering Dept., METU

Mustafa Ocak, M.Sc. ________________ Mechanical Engineer, ASELSAN

Date: 19.08.2011

Page 3: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

iii

I hereby declare that all information in this document has been obtained and

presented in accordance with academic rules and ethical conduct. I also declare

that, as required by these rules and conduct, I have fully cited and referenced

all material and results that are not original to this work.

Name, Last Name : Bekir Onur ÇOLPA

Signature :

Page 4: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

iv

ABSTRACT

CORRELATION BASED THERMAL DESIGN OF AIR

TRANSPORT RACK CHASSIS

Çolpa, Bekir Onur

M.Sc., Department of Mechanical Engineering

Supervisor: Assoc. Prof. Dr. Đlker Tarı

August 2011, 117 pages

In this thesis, a Thermal Model Tool (TMT) is developed for standard Avionic

Transport Rack (ATR) chassis and thermal design of a standard ATR chassis is done

using developed TMT. This ATR chassis is a Digital Moving Map (DMAP) of a

helicopter and the tool is used to determine the cooling channel details of DMAP.

TMT decreases design process steps and eliminates the complexity of the design.

Experimental studies are conducted on one of the existing chassis produced in

Aselsan Inc. for different operating conditions. There are two different operating

conditions for the chassis as 25 ºC and 55 ºC, which are given, in military standard

MIL-STD-810F. Critical temperature values are measured, which are used in

analytical calculations, and results are represented.

At the first step, outputs of the experimental studies are used in analytical calculation

in order to develop TMT. Secondly, heat dissipation rate of two different chassis are

Page 5: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

v

calculated easily by using the TMT, and without making effort for CFD analysis, the

necessary number of plate fins of the chassis are assessed considering given

geometrical constraints and heat loads. Finally, cooling channels are generated using

the results of TMT.

In the next step the chassis, which are designed using the results of TMT, are

analyzed numerically by using Icepak Computational Fluid Dynamics (CFD) tool

and results of TMT are verified. The cooling capacities of the decided plate fins,

which are obtained by TMT, are checked whether or not the required heat dissipation

rates are ensured.

Consequently, TMT is tested under for two different operating conditions on two

different chassis. Analytical and numerical studies for both conditions are compared

and discussed in detail. Comparisons show that, developed TMT results are

meaningful and close to numerical results, therefore TMT can be used in

forthcoming ATR chassis designs.

Keywords: ATR chassis, Forced Convection Cooling, CFD.

Page 6: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

vi

ÖZ

ATR STANDARTLARINDAKĐ ŞASENĐN KOLERASYON

TABANLI TERMAL TASARIMI

Çolpa, Bekir Onur

Yüksek Lisans, Makina Mühendisliği Bölümü

Tez Yöneticisi: Doç. Dr. Đlker Tarı

Ağustos 2011, 117 sayfa

Bu tez çalışmasında standart Avionic Transport Rack (ATR) şaseler için Termal

Modelleme Aracı (TMA) geliştirilmiş ve bu araç kullanılarak standart bir ATR

şasenin termal tasarımı yapılmıştır. Bu ATR şase bir helikopterin Hareketli Sayısal

Harita Birimidir (HSHB). TMA HSHB’nin soğutma kanallarının detaylarının

belirlenmesinde kullanılmaktadır. TMA tasarım sürecini kısaltmakta ve tasarım

aşamasındaki karmaşıklıkları ortadan kaldırmaktadır.

Aselsan A.Ş. bünyesinde mevcut olan bir şase üzerinde 25 ºC ve 55 ºC ortam

koşullarında deneyler yapılmıştır. Bu ortam koşulları askeri standart olan MIL-STD-

810F dokümanında belirtilmektedir. Deneyler sırasında, analitik çalışmalarda

kullanılmak üzere kritik olan sıcaklık değerleri ölçülmüş olup sonuçlar verilmiştir.

Deneysel sonuçlar TMA’nın geliştirilmesi için kullanılmıştır. Herhangi bir

Hesaplamalı Akışkanlar Dinamiği (HAD) analizi yapılmadan TMA kullanılarak iki

Page 7: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

vii

faklı şase için gerekli olan plaka kanatcık sayıları hesaplanmıştır. Bu hesaplama

işlemi sırasında önceden verilmiş olan ısı yükleri ve geometrik kısıtlamalar göz

önünde bulundurulmuştur. TMA sonuçlarına göre şaselerin soğutma kanalları

şekillendirilmiştir.

Daha sonra, soğutma kanal detayları belirlenmiş olan şase HAD aracı olan Icepak

kullanılarak analiz edilmiştir. Böylece, karar verilen plaka kanatçıkların ısı atım

kapasitelerinin doğruluğu kontrol edilmiştir.

Sonuç olarak, TMA iki farklı çalışma koşulu için iki farklı şase üzerinde test

edilmiştir. Analitik ve numerik çalışmalar her iki çalışma şartı için de karşılaştırılmış

ve detaylı olarak incelenmiştir. Değerlendirmeler neticesinde TMA sonuçlarının

anlamlı ve numerik çalışma sonuçlarına yakın olduğu ortaya çıkmıştır. TMA’nın

yeni ATR şase tasarımları sırasında kullanılabileceği görülmüştür.

Anahtar Kelimeler: ATR şaseler, Zorlanmış Taşınımla Soğutma, HAD.

Page 8: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

viii

To My Wife

Page 9: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

ix

ACKNOWLEDGMENTS

The author wishes to express his sincere appreciation to his supervisor Assoc. Prof.

Dr. Đlker TARI for the endless support, encouragement, and patience during his

research activities.

The author would like to thank ASELSAN, Inc. and his manager Mr. Đhsan ÖZSOY,

for his support and guidance in his study and let to use experimental facilities of

mechanical/optical design department.

The author is thankful to his superior Serkan DÖRTKARDEŞLER for the

encouragement and guidance. Without his unconditional support in guiding the

author to study electronics cooling, this dissertation would never have come into

existence.

The author would like to express his appreciation to his colleagues Mustafa OCAK

and Ahmet Hakan SEZGĐN for their assistance and valuable support.

Lastly, the author would like to express his endless gratitude to his wife for her love,

support, and faith in him.

Page 10: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

x

TABLE OF CONTENTS

ABSTRACT................................................................................................................ iv

ÖZ ............................................................................................................................... vi

ACKNOWLEDGMENTS .......................................................................................... ix

TABLE OF CONTENTS............................................................................................. x

LIST OF TABLES .....................................................................................................xii

LIST OF FIGURES .................................................................................................. xiv

LIST OF SYMBOLS ...............................................................................................xvii

CHAPTERS ................................................................................................................. 1

1 INTRODUCTION..................................................................................................... 1

1.1 ATR Chassis....................................................................................................... 3

1.1.1 Flow-Through Cooling Method .................................................................. 5

1.1.2 Natural Convection Cooling Method.......................................................... 6

1.2 VME Cards......................................................................................................... 9

1.3 Vaneaxial Fans ................................................................................................. 13

1.4 Literature Review............................................................................................. 14

2 EXPERIMENTAL STUDIES................................................................................. 26

2.1 Assumptions..................................................................................................... 29

2.1.1 Assumption-1 ............................................................................................ 29

2.1.2 Assumption-2 ............................................................................................ 30

2.2 25 °C Ambient Temperature Experiments....................................................... 34

2.3 55 °C Ambient Temperature Experiments....................................................... 39

3 ANALYTICAL STUDIES...................................................................................... 43

3.1 DMAP Analytical Studies................................................................................ 44

3.1.1 Heat Transfer Calculations........................................................................ 47

3.1.2 Pressure Drop Calculations....................................................................... 50

Page 11: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

xi

3.1.3 Thermal Model Generation and Solutions ................................................ 53

3.1.3.1 25 ºC Operating Condition Calculations............................................ 54

3.1.3.2 55 ºC Operating Condition Calculations............................................ 62

3.1.3.3 25 ºC and 55 ºC Fin Number Comparison ......................................... 63

3.1.4 Radiative Heat Transfer Calculations ....................................................... 65

3.2 ACCC Analytical Studies ................................................................................ 73

4 NUMERICAL STUDIES ....................................................................................... 76

4.1 Numerical Studies of DMAP ........................................................................... 77

4.1.1 Boundary Conditions and Basic Parameters of DMAP ............................ 78

4.1.2 Grid Generation on DMAP ....................................................................... 80

4.1.3 Numerical Solution of DMAP .................................................................. 83

4.1.3.1 25 ºC Operating Condition Solution of DMAP ................................. 84

4.1.3.2 55º Operating Condition Solution of DMAP ..................................... 87

4.2 Numerical Studies of ACCC............................................................................ 88

4.2.1 Boundary Conditions and Basic Parameters of ACCC............................. 90

4.2.2 Grid Generation on ACCC........................................................................ 90

4.2.3 Numerical Solution of ACCC ................................................................... 91

4.2.3.1 25 ºC Operating Condition Solution of ACCC .................................. 91

4.2.3.2 55 ºC Operating Condition Solution of ACCC .................................. 93

5 DISCUSSION ......................................................................................................... 95

REFERENCES........................................................................................................... 99

APENDICES............................................................................................................ 102

A. COOLING CHANNEL DIMENSIONS OF DMAP .......................................... 102

B. FAN PERFORMANCE CURVE AND DIMENSIONS..................................... 104

C. MATHCAD CODE FOR FIN OPTIMIZATION ............................................... 108

D. ANALYTICAL RESULTS................................................................................. 114

Page 12: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

xii

LIST OF TABLES

Table 1.1 Standard ATR case dimensions [1].............................................................. 4

Table 1.2 Power loads of the VME cards. ................................................................. 11

Table 1.3 General Specifications of Aximax 2 [12]. ................................................. 14

Table 1.4 Fin manufacturing limits based on Iyengar [10].................................... 15

Table 1.5. Manufacturability Constraints [11]........................................................... 17

Table 1.6 Thermal performance of heat sink [26]...................................................... 25

Table 2.1 Power loads of cards .................................................................................. 35

Table 2.2 Opposite channels thermocouple results.................................................... 39

Table 2.3 Measured slot temperatures at 25 ºC.......................................................... 39

Table 2.4 Measured slot temperatures at 55 ºC.......................................................... 42

Table 3.1 Fan Curve Data (DMAP). .......................................................................... 50

Table 3.2 Air properties at 25 ºC. .............................................................................. 54

Table 3.3 DMAP channel dimensions. ...................................................................... 55

Table 3.4 Critical temperatures of 25 ºC operating condition.................................... 58

Table 3.5 LTD and efficiency of channel at 25 ºC..................................................... 59

Table 3.6 Calculation results at 25 ºC for the number of plate fins 15. ..................... 60

Table 3.7 Calculation results at 25 ºC for the number of plate fins 17. ..................... 61

Table 3.8 Air properties at 55 ºC. .............................................................................. 62

Table 3.9 Critical temperatures of 55 ºC operating condition.................................... 62

Table 3.10 Calculation results at 55 ºC for the number of plate fins 21. ................... 63

Table 3.11 25 ºC and 55 ºC results comparison. ........................................................ 63

Table 3.12 Wall Numbers. ......................................................................................... 67

Table 3.13 View factors. ............................................................................................ 69

Table 3.14 Fan Curve Data (DMAP). ........................................................................ 74

Table 3.15 ACCC Channel Dimensions. ................................................................... 75

Page 13: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

xiii

Table 3.16 Calculation results for 24 number of plate fins (ACCC). ........................ 75

Table 4.1 25 ºC results of DMAP for different number of elements. ........................ 84

Table 4.2 Temperature results of points at 25 ºC operating condition (DMAP). ...... 86

Table 4.3 Results of points at 25 ºC operating condition (DMAP). .......................... 86

Table 4.4 Temperature results of points at 55 ºC operating condition (DMAP). ...... 87

Table 4.5 Temperature results of points at 25 ºC operating condition (DMAP). ...... 88

Table 4.6 Temperature results of points at 25 ºC operating condition (ACCC). ....... 92

Table 4.7 Temperature results of points at 25 ºC operating condition (ACCC). ....... 93

Table 4.8 Temperature results of points at 55 ºC operating condition (ACCC). ....... 93

Table 4.9 Temperature results of points at 25 ºC operating condition....................... 94

Table 5.1 Results of experimental studies. ................................................................ 96

Table 5.2 Analytical and numerical results of DMAP............................................... 96

Table 5.3 Analytical and numerical studies results of ACCC. .................................. 97

Page 14: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

xiv

LIST OF FIGURES

Figure 1.1 Example of a standard ATR chassis [3]. .................................................... 2

Figure 1.2 Example of a standard VME card [3]. ........................................................ 2

Figure 1.3 Standard ATR case dimensions [23]. ......................................................... 3

Figure 1.4 Flow-through cooling chassis [2] ............................................................... 6

Figure 1.5 Forced convection cooling chassis with cooling channels [3].................... 7

Figure 1.6 Natural Convection cooling chassis [4]...................................................... 7

Figure 1.7 Draft model of the chassis. ......................................................................... 8

Figure 1.8 Placement of Fan. ....................................................................................... 9

Figure 1.9 Standard VME card sizes [5]. ................................................................... 10

Figure 1.10 Thermal Plate.......................................................................................... 10

Figure 1.11 Placement of slots. .................................................................................. 12

Figure 1.12 Aximax 2 fan [12]................................................................................... 13

Figure 1.13 Fin thickness and number influence on fin stack thermal resistance [9] 16

Figure 1.14 Short chassis, top to bottom flow, 250Pa pressure drop, 85C edge [9]. . 16

Figure 1.15 Side-inlet-side-exit (SISE) rectangular plate fin heat sink conf. [11]. ... 17

Figure 1.16 Practical model of a conventional plate-fin heat sink [20]. .................... 18

Figure 1.17 Rectangular model: T0= 300 K, Tw =423 K [24].................................... 20

Figure 1.18 Aerodynamic model: T0= 300 K, Tw =423 K [24]. ................................ 20

Figure 1.19 Rounded inlet model (Rounded I): T0= 300 K, Tw =423 K. [24]. .......... 20

Figure 1.20 Rounded inlet and outlet model: T0= 300 K, Tw =423 K [24]................ 21

Figure 1.21 The geometric parameters [25]. .............................................................. 22

Figure 1.22 The effect of the stagger when the spacing is fixed at Wopt (β = 1) N=4,

ReL=103) [25]. ............................................................................................................ 23

Figure 1.23 The effect of the stagger parameter on the optimal spacing and the

maximum overall thermal conductance (A = 0.5, N = 4, ReL = 103) [25]. ................ 24

Page 15: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

xv

Figure 2.1 ACCC (Avionic Central Control Computer)............................................ 26

Figure 2.2 Dewetron measuring device. .................................................................... 27

Figure 2.3 Dewetron measuring device (continued). ................................................. 27

Figure 2.4 Fast response surface-mount thermocouple.............................................. 28

Figure 2.5 Thermocouples on the left wall. ............................................................... 29

Figure 2.6 Thermocouple in the cooling channel...................................................... 30

Figure 2.7 Detailed view of thermocouples on the right wall.................................... 31

Figure 2.8 All thermocouples on both sides. ............................................................. 32

Figure 2.9 VME cards in slots. .................................................................................. 32

Figure 2.10 Experiment setup. ................................................................................... 33

Figure 2.11 Experiment results of 25 ºC operating condition.................................... 35

Figure 2.12 Temperatures of slot5 and slot5_c while ACCC does not operate......... 36

Figure 2.13 Temperatures of slot5 and slot5_c while ACCC operates...................... 37

Figure 2.14 Temperatures of opposite walls. ............................................................. 38

Figure 2.15 ACS Test chamber.................................................................................. 40

Figure 2.16 55 ºC non-operating measurement results. ............................................. 41

Figure 2.17 55 ºC operating measurement results. .................................................... 42

Figure 3.1 Flow chart of DMAP. ............................................................................... 45

Figure 3.2 Chassis cooling method. ........................................................................... 46

Figure 3.3 General cooling method of convection..................................................... 47

Figure 3.4 Viscous sub layer...................................................................................... 49

Figure 3.5 Fan Curve Data Plot. ................................................................................ 51

Figure 3.6 Trend Line Added Fan Curve Plot (DMAP). ........................................... 52

Figure 3.7 Results of TMT for the operating conditions 25 ºC and 55 ºC................. 64

Figure 3.8 General view of DMAP in the chamber ................................................... 66

Figure 3.9 Walls numbers. ......................................................................................... 67

Figure 3.10 View factors............................................................................................ 68

Figure 3.11 Propimax 2 Fan....................................................................................... 73

Figure 3.12 Trend Line Added Fan Curve Plot (ACCC). .......................................... 74

Figure 4.1 3D Model of DMAP. ................................................................................ 78

Page 16: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

xvi

Figure 4.2 Computational Model of DMAP. ............................................................. 79

Figure 4.3 Meshed view of the chassis. ..................................................................... 81

Figure 4.4 Mesh Control Parameters. ........................................................................ 81

Figure 4.5 Detailed view of meshed fin. .................................................................... 82

Figure 4.6 Quality of the mesh................................................................................... 82

Figure 4.7 Advanced solver setup window. ............................................................... 83

Figure 4.8 Control points. .......................................................................................... 85

Figure 4.9 Wall temperature contour view of 25 ºC analyses (DMAP). ................... 86

Figure 4.10 Wall temperature contour view of 55 ºC analyses (DMAP). ................. 87

Figure 4.11 3D Model of ACCC................................................................................ 89

Figure 4.12 3D Model of ACCC (continued). ........................................................... 89

Figure 4.13 Meshed view of the chassis. ................................................................... 90

Figure 4.14 Wall temperature contour view of 25 ºC analyses (ACCC). .................. 92

Figure 4.15 Wall temperature contour view of 55 ºC analyses (ACCC). .................. 94

Figure A.1 Front section view of cooling channels. ................................................ 102

Figure A.2 Side view of cooling channel................................................................. 103

Figure B.1 Fan performance curve of Aximax 2…………………………………..104

Figure B.2 Dimensions of Aximax 2…………………………………...…………105

Figure B.3 Fan performance curve of Propimax 2……………………..………….106

Figure B.4 Dimensions of Propimax 2…………………………………………….107

Page 17: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

xvii

LIST OF SYMBOLS

Latin Symbols

Q : Rate of heat transfer

airmm••

= : Cooling air mass flow rate

ieair TTT −=∆ : Temperature difference of cooling air exit and inlet

iT : Cooling air inlet temperature

eT : Cooling air exit temperature

pairp CC = : Specific heat capacity of air

n : Fin number

b : Fin thickness

a : Distance between two plate fins

H : Channel height

L : Channel length

w : Channel width

P : Wetted perimeter of cooling channel

allP : Total perimeter of cooling channel

allA : Total convection surface area

sA : Section flow area of one channel

sallA : All section flow area of one channel

HD : Hydraulic diameter

airV : Velocity of cooling air in the channel

Page 18: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

xviii

VFR : Volumetric flow rate

Re : Reynolds number of channel cooling air

f : Friction factor of channel

Nu : Nusselt Number

h : Convection heat transfer coefficient

me : Efficiency equation coefficient

fA : Single channel surface area

lnT∆ : Logarithmic mean temperature difference

wT : Wall temperature

Pr : Prandtl Number

airk : Thermal conductivity of air

alk : Thermal conductivity of aluminum

calQ : Calculated heat dissipation rate

Greek Symbols

airρ : Air density

fη : Single fin efficiency

0η : All fins efficiency

airµ : Dynamic viscosity

Page 19: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

1

CHAPTERS

CHAPTER 1

1 INTRODUCTION

In this thesis, a correlation based Thermal Model Tool (TMT) is developed for

standard Air Transport Rack (ATR) chassis and using the developed TMT, thermal

designs of standard ATR chassis are done in Aselsan Inc.

An ATR chassis is an avionic box. Design of a chassis starts with the given

geometrical and thermal constraints and mainly has three steps. At the first step, the

three dimensional (3D) model is generated. At the second step, the geometry is

numerically analyzed to determine if the given heat loads can be dissipated. Finally,

the designed model is produced and experimental studies are performed in order to

make the verification of analytical and numerical studies.

This thesis mainly consists of five chapters as; introduction, experimental studies,

analytical studies, numerical (Computational Fluid Dynamics (CFD)) studies and

discussion. In the introduction chapter, military ATR chassis are introduced. Types

of ATR chassis, dimensions, electronic card types, and cooling fans are explained. In

addition, new design ATR chassis with the name Digital Moving Map (DMAP) is

introduced. In the experimental studies chapter, results of the necessary experiments

that are done on the existing chassis are presented. In the analytical studies chapter,

by using the results of the experimental studies, mathematical model for the chassis

are prepared and TMT is developed. Cooling channel details of the DMAP are

studied by using TMT and necessary plate fin numbers are determined for different

operating conditions. Moreover, an existing chassis heat dissipation capacity is

Page 20: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

2

calculated using TMT for a second case. In the CFD studies chapter, thermal

behavior of the created new design and existing chassis are analyzed with a CFD

tool. Finally, in the discussion chapter, results of TMT and CFD studies are

compared and future work subjects are stated.

VME cards are the compositions of Printed Circuit Boards (PCBs) and electronic

components. Example of an ATR chassis and a VME card are shown in Figure 1.1

and Figure 1.2 respectively. According to the standards, various chassis and VME

cards were manufactured in Aselsan Inc., previously.

Figure 1.1 Example of a standard ATR chassis [3].

Figure 1.2 Example of a standard VME card [3].

Page 21: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

3

1.1 ATR Chassis

ATR chassis are military enclosures to provide a working environment to the

electrical/electronic equipment against the environmental factors. These types of

enclosures must have specific dimensions and interfaces, which are described in the

military standard called “ARINC 404A, Air Transport Equipment Cases and

Racking”. The reason of having a standard is to ensure the interface compatibility

between the manufacturers. It is expected that a device with a specific case

dimension produced by a manufacturer will fit in a mounting produced by another

manufacturer [1].

All interface types and envelope dimensions of the chassis are described in ARINC

404A [1]. Standard ATR case dimensions are given in Figure 1.3 and Table 1.1.

Figure 1.3 Standard ATR case dimensions [23].

Page 22: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

4

Table 1.1 Standard ATR case dimensions [1].

Approx. Volume

Width(W) Length(L1) Length(L2) Height(H) ATR Size

[liter] [±0.76mm] [±1mm] [mm] [mm]

1/4 Short 3.52 57.15 318 320.5 193.5

1/4 Long 5.49 57.15 495.8 498.3 193.5

3/8 Short 5.57 90.41 318 320.5 193.5

3/8 Long 8.69 90.41 495.8 498.3 193.5

1/2 Short 7.7 123.95 318 320.5 193.5

1/2 Long 11.88 123.95 495.8 498.3 193.5

3/4 Short 11.8 190.5 318 320.5 193.5

3/4 Long 18.36 190.5 495.8 498.3 193.5

1 Short 15.96 257.05 318 320.5 193.5

1 Long 24.75 257.05 495.8 498.3 193.5

1 1/2 Long 37.62 390.65 495.8 498.3 193.5

Notes: Per ARINC characteristic 561 INS. the standard dimension ‘H’ = 193.5 mm may be increased to a maximum ‘H’ dimension of 269.88 mm when necessary for equipment reasons.

Military enclosure systems have difficult heat management problems and specific

environmental factors affect these enclosures. Therefore, cooling is essential for

these types of enclosures. The purpose of cooling system is to maintain the internal

components of electrical/electronic equipment at temperatures, which will achieve a

long and predictable service life [1].

There are two basic cooling methods that are described for ATR chassis: Flow-

Through and Natural Convection. If the heat load is very high, Liquid Cooling

method can also be used in some applications to cool the ATR chassis. However, it is

very difficult to control the behavior of the liquid in high altitudes and accelerations,

so liquid cooling is not a preferred method for most of the cases. Therefore, Flow-

Through and Natural Convection are the most frequently used methods.

Page 23: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

5

1.1.1 Flow-Through Cooling Method

The standard mode of cooling will be to draw air through the unit by applying a

differential pressure between the inlet and outlet sections of the unit. This normally

should consist of suction applied to the inlet of the unit to create air movement. This

type of cooling method has two subgroups:

• Direct forced convection cooling inside the chassis.

• Forced convection cooling via cooling channels.

In the first subgroup, the cooling air is forced inside the chassis, and the electronic

components are cooled directly by the cooling air. However, this type of cooling is

not applied if the ATR chassis is not positioned in the cockpit since the ATR chassis

must be insulated against environmental conditions. Otherwise, environmental

conditions will increase maintenance and reduce service life. Besides that, some

electronic components do not operate when exposed to moisture and this is another

reason for sealing.

In Figure 1.4, an example chassis is shown for the first subgroup of flow-through

cooling. Cooling air is sucked from the front panel of the chassis and flows through

the electronic cards. In this manner, generated heat is dissipated to the cooling air

directly. Finally, cooling air leaves the chassis with increased temperature.

Additionally, this chassis has mass and dimension advantages since there is no need

for cooling channels,

Page 24: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

6

Figure 1.4 Flow-through cooling chassis [2]

In the second subgroup, cooling air does not flow through the electronic cards.

Cooling channels are created with fins and cooling air flows through these channels.

The generated heat is conducted to the walls of the cooling channel and the heat is

dissipated to the cooling air by convection. In this manner, the chassis is cooled

unaffected by the environment. Ability to place the chassis at any point in the air

vehicle is an advantage of this method.

However, existence external cooling channels increase both the dimensions and the

mass, which is a disadvantage of this method. In Figure 1.5, an example chassis with

cooling channels is shown.

1.1.2 Natural Convection Cooling Method

Heat dissipation of natural convection is lower than forced convection. In addition,

this type of cooling allows sealing. If the rate of generated heat is low and insulation

is required for the chassis, this cooling type should be preferred.

Page 25: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

7

Figure 1.5 Forced convection cooling chassis with cooling channels [3]

In Figure 1.6, an example for the natural convection chassis is shown. In such a kind

of chassis, the generated heat is conducted to the chassis and the chassis is cooled by

natural convection.

Figure 1.6 Natural Convection cooling chassis [4].

Page 26: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

8

The ATR chassis, which is the subject of this thesis, must have high heat dissipation

rates because of generated high heat values and the chassis must be sealed due to the

location in the helicopter. In addition, placement of the chassis is in the tail section of

the helicopter and may be affected by rain or other environmental conditions. These

two limitations identify the cooling method for the chassis. The chassis must be

sealed and must have high heat dissipation rates. Therefore, forced convection

method with cooling channels is convenient for the chassis. For this purpose, plate

fins or pin fins can be used inside the cooling channels. Plate fins are preferable to

pin fins for the advantages of low production cost, more convection surface area, and

directed flow. Furthermore, machining or casting plate fins are easier than pin fins.

There are side-cooling channels on the chassis. The draft model of the chassis with

side plate fins is shown in Figure 1.7.

Figure 1.7 Draft model of the chassis.

Ametek Rotron fans are used in Aselsan Inc. because they meet the military

requirements. One of the existing fans is selected also for this study. Fan is placed at

the rear side of the chassis as shown in Figure 1.8. Cooling air is sucked from suction

Cooling air inlet section (On both sides).

Page 27: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

9

opening of the channels shown in Figure 1.7. Cooling air accumulates at the front

side of the fan and exhausts to the environment with high temperature.

Figure 1.8 Placement of Fan.

1.2 VME Cards

Printed Circuit Board (PCB) has conductive pathways and connects electronic

components electrically. Furthermore, PCB is used to mechanically support the

electronic components and is also called as Printed Wiring Board (PWB) or etched

wiring board. If a PCB is populated with electronic components, it is called as

Printed Circuit Assembly (PCA), also known as a Printed Circuit Board Assembly

(PCBA). Much more layout effort and higher initial cost are required for PCBs than

either wire wrap or point-to-point constructions. Besides this for high-volume

production, PCBs are much cheaper and faster to produce.

There are three basic VME card sizes, which are 9U, 6U, and 3U. 6U card has two

different models. All sizes are shown in Figure 1.9.

Page 28: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

10

Figure 1.9 Standard VME card sizes [5].

The cooling of VME cards is done with thermal plates. Generated heat is conducted

to thermal plates and through them to the chassis. In Aselsan Inc., also thermal plates

are designed for the used VME cards. One of the designed thermal plates is shown in

Figure 1.10.

Figure 1.10 Thermal Plate.

Page 29: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

11

There are four different VME cards in the new design chassis DMAP. One of them is

power card and the rest 3 are the processor cards each having a special mission. For

instance, the card with the special name “AIK” has the mission of image processing.

In Table 1.2, the list of the used VME cards is given with their power loads. In

addition, the placements of slots are shown in Figure 1.11. There is approximately

100W (28V x 3.5A) power load inside the chassis, which is generated by the VME

cards.

Table 1.2 Power loads of the VME cards.

Slot Number Card Name Power

Consumption [A]

Slot-1 AIK+1553+429 1.1

Slot-2 VIK 0.6

Slot-3 AIK 0.8

Slot-4 Power Card 1

Total heat load and geometrical details are parameters for the design. Cooling

channel dimensions are shown clearly in Appendix A. The height, width, and length

of the channel are 158 mm, 10 mm and 330 mm respectively. These are the available

dimensions for plate fin placements. By using the given geometrical constraints,

DMAP is modeled by using proEngineer tool as shown in Figure 1.8. Unknowns are

the plate fin details for the cooling channels. Analytical calculations are done in

order to find the sufficient number of plate fins for the given heat load by considering

given parameters for the cooling channels and ambient operating conditions 25 ºC

and 55 ºC.

Page 30: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

12

Figure 1.11 Placement of slots.

Slot-1

Slot-2

Slot-3

Slot-4

Page 31: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

13

1.3 Vaneaxial Fans

Two Ametek Rotron Aximax 2 (Figure 1.12) fan is used in the back of the chassis,

which is a Vaneaxial fan. Small Vaneaxial is a high-speed and compact fan type,

whose airflow is parallel to the motor shaft. For minimum acoustical noise and

maximum aerodynamic efficiency, the guide vanes and impeller are of airfoil

constructions. These fans are designed for use in airborne avionic boxes where sizes,

weight, and reliability are critical, and where high heat loads must be dissipated with

cooling air. Optional internal Fan Performance Sensor (FPS) or an external Low

Speed Warning Device (LSWD) is available for most units [12].

Figure 1.12 Aximax 2 fan [12].

Vaneaxial Fans are axial flow air moving devices. In these fans, the motor rotor is

cast inside the impeller to achieve the smallest possible axial dimension. Through

those true airfoil blade designs, the higher aerodynamic performance and efficiencies

can be achieved [12].

Those fans are military, compact, and quiet designs, which are used mostly for

cooling electronic enclosures under severe environmental conditions in airborne,

ground based and shipboard applications where air can move freely with low static

pressure. Axiamax 2 fan can be designed to meet the military standard MIL-STD-

Page 32: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

14

810C requirements [12]. The general specifications of Aximax 2 are given in Table

1.3 and dimensions and critical performance curve are given in Appendix B.

Table 1.3 General Specifications of Aximax 2 [12].

Physical envelope: 55.3 mm Dia. x 42.2 Length

Weight: approximately 120 gr.

Die cast aluminum Venturi and Rotorprop

Specially designed for cooling electronics in aircraft, ground-based and

shipboard applications

All aluminum components finished with chemical conversion coating

per MIL-C-5541

Top coat of lusterless black enamel, color #37038, per Federal Standard

595 conforming to TT-E-489 Type B.

Corrosion-resistant stainless steel shaft and hardware.

Meets or exceed the requirements of MIL-B-23071 and other applicable

U.S. military and commercial aerospace specifications.

Max free delivery airflow of 59 CFM.

Ambient temperature range: -54 °C to 100 °C.

Acoustic levels as low as 55 dBA.

1.4 Literature Review

In the literature, there are many studies done on the plate fins related with the air-

cooled heat sinks. However, the number of studies done related with the heat sinks or

cooling channels placed on ATR chassis are not so much. In this section, studies

conducted by van Engelenhoven et al [9], Iyengar and Bar-Cohen [11], Wu et al [20],

Leon et al [24] and Fowler et al [25] are examined.

Page 33: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

15

Jesse and Gary [9] had done one of the studies about ATR chassis. In the study, by

considering pressure drop requirement and fin manufacturing capabilities for

ruggedized military electronics, they examined chassis-level air-cooling limits. In

order to maximize the heat dissipation rate of an air-cooled chassis, they optimized

longitudinal plate fin (included in side wall ducts) geometry. For the optimization,

numerical and analytical models were developed. The results of the studies were

presented in the form of a performance map. Results showed the differences of

specified set of mass flow, pressure drop, and heat transfer requirements between

different fin manufacturing processes. According to the results, if isothermal

boundaries could be achieved instead of isoflux boundary condition assumption, the

heat transfer capacity of the chassis would increase. Studies were done on different

manufacturing process given in Table 1.4.

One of the results of the study shows the influence of fin thickness on thermal

resistance (Figure 1.13). Studies were done for different edge temperatures as 55 ºC,

70 ºC and 85 ºC and for two different chassis types as long and short. One of the

performance maps is given in Figure 1.14. To maximize heat transfer in all cases

bonded or folded fins with a thickness of 0.254 mm were obtained.

Table 1.4 Fin manufacturing limits based on Iyengar [10].

Process Min & [mm]

Extrusion 1.575

Forging or Gang saw 1

Skiving 0.6

Swaging 0.5

Bonded 0.254

Folded 0.05

Page 34: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

16

Figure 1.13 Fin thickness and number influence on fin stack thermal resistance [9]

Figure 1.14 Short chassis, top to bottom flow, 250Pa pressure drop, 85C edge [9].

Page 35: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

17

Iyengar and Bar-Cohen [11] made the next study. In order to find the maximum heat

transfer capabilities of the heat sinks, analytical model, and the thermofluid

performance of the heat sink was characterized. In addition, least-material

optimization was done to achieve optimal material usage. Different production

methodologies (extruded, die-casting, bonding, folding, modified die-casting, skiving

and machining) were examined. The manufactures with different methods are given

in Table 1.5 and parameters were defined in Figure 1.15.

Figure 1.15 Side-inlet-side-exit (SISE) rectangular plate fin heat sink conf. [11].

Table 1.5. Manufacturability Constraints [11]

In the study, to identify the maximum heat transfer capability, optimization

procedure was adopted. A least-material optimization was done. With respect to

Page 36: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

18

mass-specific heat dissipation, magnesium was found to be the most efficient

material.

The next examined study had done by Wu et al. [20] predicts the hydraulic and

thermal performance of a plate-fin heat sink. They developed all-in-one asymptotic

model for a wide range of Reynolds numbers, including laminar, transition, and

turbulent flows as Re<5000. The model can predict pressure drops with accuracy

within -13.87% to 8.4%. They developed a practical model for convectional plate-fin

heat sink. The model derives a pressure drop correlation for the working fluid.

Figure 1.16 Practical model of a conventional plate-fin heat sink [20].

They divided the pressure drop inside the heat sink into two parts as the friction term

and the term due to the change of flow section. The heat sink pressure drop was

considered as in Eqn. 1.1, where fapp is the fanning friction factor, Kc and Ke are the

contraction and expansion pressure loss coefficients. V is the velocity of coolant; L

and Dh are the channel length and hydraulic diameter, respectively.

2

2

14 VKK

D

LfP ec

h

app ρ

++=∆ ( 1.1)

Page 37: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

19

They generated an asymptotic correlation for the general friction factor as in the Eqn.

1.2.

( ) nn

turb

n

lamapp fff/1

+= ( 1.2)

Because all the flows in the thesis study are turbulent, only the ( ) nn

turbf/1

part of the

Eqn. 1.2 is used. They gave the equation of this part as in Eqn. 1.3.

175.02.0Re0962.0

−⋅=h

c

appD

Lf ( 1.3)

Also they gave the equations for Kc and Ke as Eqns. 1.4 and 1.5.

2

4.08.0

−=

p

aK c ( 1.4)

−=

p

a

p

aK c 4.01

2

( 1.5)

Leon et al. [24] worked on the influence of cooling channel fin shape on the pressure

drop caused by flow resistance of a heat sink. They developed a new manner to

optimize the heat sink. They emphasized not only on maximum heat transfer flux,

but also on minimum flow resistance with the developed manner. They studied

numerically using the computational fluid dynamic software FLUENT.

They found the advantages of using aerodynamic shaped fins if the Reynolds

number, is greater or equal than about 800. The authors suggested some preliminary

profile shapes and they considered this research as a unique approach if the study is

compared to other studies where the flow resistance has not been taken into account.

Page 38: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

20

The authors studied on 4 different fin geometries. Figure 1.17 shows a standard

arrangement of rectangular fins. Figure 1.18 shows fins with an aerodynamic shape

(airfoil shape). The purpose of this arrangement was stated as to lower the

aerodynamic drag. The cooling fin area was the same as in the rectangular

arrangement. Figure 1.19, and Figure 1.20 show fins where the inlet edge or the inlet

and outlet edges are rounded.

Figure 1.17 Rectangular model: T0= 300 K, Tw =423 K [24].

Figure 1.18 Aerodynamic model: T0= 300 K, Tw =423 K [24].

Figure 1.19 Rounded inlet model (Rounded I): T0= 300 K, Tw =423 K. [24].

Page 39: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

21

Figure 1.20 Rounded inlet and outlet model: T0= 300 K, Tw =423 K [24].

As conclusion, the authors stated that, if the Reynolds number was greater or equal

than about 800, the reduction of the flow resistance could be achieved by the use of

aerodynamic profiles. In this manner, the value of the removed heat was not affected.

They suggested that as a practical optimum, a cooling fin with a rounded leading

edge.

They concluded that, for very small Reynolds numbers around 100 or less, they

found that it was useless to introduce any type of aerodynamic layout. Flow resistant

reduction would permit to use of lighter fans without affecting the removed heat. As

a result, noise level of the fan, fan size and power consumption would be reduced.

Lastly, they stated that the given conclusions are valid for any type of heat sink

where the flow is parallel to the fins.

Fowler et al. [25] studied the optimal geometric arrangement of staggered parallel

plates in a fixed volume with forced convection heat transfer experimentally and

numerically. They tried to maximize the total heat transfer rate when the maximum

temperature at a point inside the volume cannot exceed a certain level.

The study was done in two parts as experimental and numerical. Experimental results

are reported for air in the range 1000 < Re < 6000, where L is the swept length of the

fixed volume. They supported the findings with numerical results to 100<Re< 10000.

In addition, they showed that there is an optimal way to stagger the plates. The

geometric parameters are shown in Figure 1.21.

Page 40: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

22

Figure 1.21 The geometric parameters [25].

Authors investigated the effect of changing the stagger parameter β in two ways as in

Figure 1.22 and Figure 1.23.

They interpreted Figure 1.22 as “the spacing W was set equal to the optimal value

Wopt that corresponds to perfectly staggered plates (β=1). As the stagger parameter

varies over [0, 1] interval, the overall thermal conductance exhibits a maximum at a

certain β value (called βopt). This maximum becomes sharper as A decreases below

A=1: in this range the stagger associated with maximum q is closely approximated

by βopt=A. Perfectly staggered plates (β=1) are always better than in-line plates

(β=0); however, β=1 is not the optimal stagger parameter when A<1. Figure 1.22

also shows that when A>1 the effect of β on q is relatively insignificant” [25].

Page 41: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

23

Figure 1.22 The effect of the stagger when the spacing is fixed at Wopt (β = 1) (N=4,ReL=103) [25].

They interpreted Figure 1.23 as the alternative to determine the optimal spacing that

corresponds to each value of the stagger parameter, namely Wopt(β). This route was

followed in the construction of Figure 1.23, where A = 0.5, N = 4 and ReL = 103. The

optimal spacing increases by roughly 7% as β decreases from 1 to 0. In other words,

the optimal spacing for in-line plates is slightly larger than for perfectly staggered

plates. The corresponding β effect on the maximized overall conductance is also

small (within 6%). There is a weak q maximum at β = 0.5, and, as might be expected,

we learn again that perfectly staggered plates (β = 1) perform better than in-line

plates (β = 0)” [25].

Page 42: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

24

Figure 1.23 The effect of the stagger parameter on the optimal spacing and the maximum overall

thermal conductance (A = 0.5, N = 4, ReL = 103) [25].

Jouhara and Axcell [26] studied the thermal conditions within a heat sink with

rectangular fins under laminar forced convection cooling. To model the increase in

air temperature through channels, classical heat transfer theory and a computational

approach were used. They represented the variation of the key heat transfer

parameters with axial distance, the rapid changes in heat transfer coefficient fin

efficiency near the leading edges of the cooling fins. They described the

mathematical modeling and solution techniques for each method in detail.

Four different approaches were used during their study:

• Idealized case: In this case study they assumed that the fin surfaces were at a

uniform temperature equal to that of the base plate.

• Approximate analysis: Heat transfer with non-uniform wall temperatures.

• Analysis using numerical integration along the flow passage: They assumed

that both the heat transfer coefficient and the fin efficiency vary along the

flow.

Page 43: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

25

• Finite element/CFD study: The computational study was performed.

Authors obtained the results for each of the different theory. They presented the

predicted thermal performance results of a single heat sink using the four methods,

which is given in Table 1.6 for approach velocities from 1 to 8 m/s.

Table 1.6 Thermal performance of heat sink [26].

Initially, they presented for idealized fins which are 100% efficient using an

expression for mean Nusselt number. Next, they utilized a uniform fin efficiency

based on the mean Nusselt number. Then they introduced more detail by allowing

both Nusselt number and fin efficiency to vary along the flow passage. Finally, they

modeled the effects of flow disturbance at entry to the heat sink and axial conduction

in the cooling fins in a CFD.

They concluded the study as stating that “although the calculations show that heat

transfer coefficients and fin efficiencies vary substantially along the flow path, good

engineering accuracy for heat sink performance can be obtained for laminar flow

using calculations in which mean values for the Nusselt number and fin efficiency

are calculated from analytical expressions” [26].

Page 44: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

26

CHAPTER 2

2 EXPERIMENTAL STUDIES

Aim of the experimental studies is to obtain critical wall temperature values for

different operating conditions. The critical wall temperatures are used in analytical

calculations to develop TMT and to obtain appropriate number of fins for the chassis

DMAP.

There are existing chassis in Aselsan Inc. used for different applications.

Experimental studies are conducted on one of the existing chassis, which is an

Avionic Central Control Computer (ACCC) of a helicopter, shown in Figure 2.1.

Figure 2.1 ACCC (Avionic Central Control Computer).

Page 45: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

27

In the experimental studies, temperatures of walls and cooling air are measured by

Dewetron data acquisition system shown in Figure 2.3. The system has 32 channels

and the sampling rate of the system is set to be 1s. Moreover, two thermocouple

interface pads are utilized to connect thermocouples to the system.

Figure 2.2 Dewetron measuring device.

Figure 2.3 Dewetron measuring device (continued).

Page 46: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

28

Fast response surface-mount thermocouples (Figure 2.4) are used for the

measurements of wall temperatures. The thermocouple has a bare sensing element

with a nominal 0.025 mm thick, 25.4 mm length and 9.5 mm width [18]. 30 AWG

(0.0254 mm) thermocouple wire with a temperature sensitivity of ± 1.1 °C is used for

the fast response thermocouples [19].

Figure 2.4 Fast response surface-mount thermocouple.

Since generated heats are different in the slots, wall temperatures of the slots are

different as well. However, in the analytical calculations, a single wall temperature is

used. Because of that the mean temperature of all slots are necessary. Therefore, in

order to get temperature degrees of each slot, thermocouples are used on slots as

shown in Figure 2.5. Due to the empty slots 8 and 9, thermocouples are not placed on

these slots. Temperature values of each slot are measured on the left wall. Average

temperature of slots is calculated to obtain critical wall temperature.

Page 47: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

29

Figure 2.5 Thermocouples on the left wall.

2.1 Assumptions

Before starting experiments, some assumptions are done in order to facilitate the

studies. The assumptions are listed as below:

• Inside and outside temperatures of the plate finned wall are close to each

other.

• Left and right side wall temperatures are close to each other and symmetry

condition is acceptable.

2.1.1 Assumption-1

Firstly, assumed that inside and outside temperatures of the plate finned wall is close

to each other. Although the convection occurs between outside wall of chassis and

Slot 11

Slot 10

Slot 7

Slot 6

Slot 5

Slot 4

Slot 3

Slot 2

Slot 1

Page 48: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

30

the cooling air, it is not easy to make proper temperature measurements at the outside

wall, as fan is operating. In such a situation, cooling air also flows over the

thermocouples and cools them. This causes to measurement errors. Therefore,

assumed that inside and outside temperatures of wall are close to each other because

of thin (2 mm) wall thickness. In order to verify this assumption, an additional

thermocouple is placed on the cooling channel as shown in Figure 2.6. This

thermocouple coincides with 5th slot thermocouple, which is inside the chassis. The

temperature measurements of both thermocouples are compared to see if the

assumption is true. Detailed verification of the assumption is given in Section 2.2 and

Figure 2.12.

Figure 2.6 Thermocouple in the cooling channel.

2.1.2 Assumption-2

Second assumption is the symmetry condition. Assumed that left and right cooling

channels have the same cooling capacity and symmetry condition is applicable. By

This thermocouple coincides with 5th slot thermocouple.

Page 49: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

31

considering the fragile features of the thermocouples and placements difficulties,

measurement are done for one of the sidewalls. Therefore, to verify this assumption

and understand general characteristics of the sidewalls, additional thermocouples are

placed on the right wall of the ACCC (Figure 2.7).

Figure 2.7 Detailed view of thermocouples on the right wall.

Three thermocouples are stuck on 1st, 5th and 11th slots of the right wall. The

temperature values measured with these thermocouples are compared with same slot

left wall thermocouple measurements. For instance, left wall 1st slot thermocouple

measurement is compared with right wall 1st slot thermocouple measurement. The

thermocouples on the opposite side of the slots are named as Slot 1o, Slot 5o and Slot

11o as shown in Figure 2.7. Results are examined and temperature differences of left

and right wall are determined. All placed thermocouples are shown in Figure 2.8.

Slot 1o Slot 5o Slot 11o

Page 50: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

32

Figure 2.8 All thermocouples on both sides.

There are 3 additional thermocouples in the battery case of the ACCC. Temperature

limit of in use battery is 100 °C maximum, so with these thermocouples, battery case

temperature is identified if there is any challenge. After thermocouples are stuck on

the related slots, electronic card of each slots are placed as shown in Figure 2.9.

Figure 2.9 VME cards in slots.

Battery Case

Left Wall

Right Wall

Page 51: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

33

19 thermocouples are utilized during experiments at below given positions:

• 9 pieces, on the left wall

• 3 pieces, on the right wall

• 3 pieces, in the battery case

• 1 piece on the left wall air side

• 1 piece for operating condition

Cooling air inlet temperature is measured by the thermocouple allocated for

operating condition. Thermocouples are put out from the chassis using “Elapsed

Time Meter (ETM)” and “Grounding Screw” holes as shown in Figure 2.10. The

general view of experiment setup is also shown in Figure 2.10.

Figure 2.10 Experiment setup.

Grounding Screw Hole

ETM Hole

Page 52: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

34

The experiments are built for two main conditions. Firstly, 25 °C ambient cooling air

experiment is performed. In this experiment, inside and outside temperatures

differences of the wall are examined. It is important to indicate that fan does not

operate in this measurement. Hereby it is showed that measuring wall temperatures

from inside of the wall is convenient. In the next step, left and right wall

temperatures are evaluated to show that both wall temperatures are close to each

other, so analytical calculations can be done by using temperature measurements of

one wall with negligible errors. Secondly, the same experiment is performed at 55 °C

ambient temperature and the same measurements are done for this alternative as well.

2.2 25 °C Ambient Temperature Experiments

This experiment is performed at 25 °C ambient air temperature. Experiment duration

is approximately 110 minutes. 19 thermocouples are used for data collection.

Approximately 60 minutes later, ACCC reaches to steady state condition and

measured temperatures do not change any more. Power input to the ACCC is

calculated by using power supply current rate input. This power load can be thought

as the heat load on the system, which must be dissipated. Up to 25th minute, power

supply shows that 6.1 A current rate with 28 V. This shows that power input to

ACCC is approximately 170 W. All cards placed in the chassis with the order stated

in Table 2.1.

Experiment results are analyzed and temperature values are plotted as shown in

Figure 2.11. ACCC is cooled by 2 fans and these fans are controlled with a fan

control card. This card is placed at the bottom of the ACCC and has a relay on it. Fan

control card starts up the fans when the relay temperature reaches to 45 °C.

Therefore, fans must be operating later than ACCC.

Page 53: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

35

Table 2.1 Power loads of cards

Slot Number

Card Name Power

Consumption [A]

Slot-11 Power Card 1.1

Slot-12 Power Card 0.0

Slot-1 AIK+1553+429 1.2

Slot-2 AIK+GIK+GIK 1.1

Slot-3 VIK 0.7

Slot-4 AIK+GIK+GIK 1.0

Slot-5 AIK 0.8

Slot-6 AAK 0.1

Slot-7 AAK 0.1

Slot-10 GDK 0.0

Experiment results show that fans start to operate 25 minutes later than ACCC. Up to

minutes 25, fans are turned off by fan control card and all temperatures increase.

When the relay of fan control card reaches to 45 °C, fans start to operate and all

temperatures start to decrease.

Slot Temperatures - Time

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

0 10 20 30 40 50 60 70 80 90 100 110

Time [Min.]

Tem

pera

ture

[°C

]

slot1 slot2 slot3 slot4 slot5

slot6 slot7 slot10 slot11

Figure 2.11 Experiment results of 25 ºC operating condition.

Page 54: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

36

In order to see the inside and outside temperature differences of left wall, cooling

data of ACCC are also collected. In this experiment, ACCC is not operating and left

for cooling. Time scaled cooling temperatures graph is given in Figure 2.12. Results

show that slot5 temperature is closed to slot5_channel temperature. This

measurement shows that, measuring wall temperatures from inside is reasonable.

Wall Temperatures - Time

27

28

29

30

31

32

33

34

35

36

37

0 5 10 15 20 25 30 35 40 45 50 55 60

Time [Min.]

Tem

pera

ture

[°C

]

slot5 slot5_c

Figure 2.12 Temperatures of slot5 and slot5_c while ACCC does not operate.

The reason of doing this measurement while ACCC is out of service is not to affect

thermocouples by flowing air. There is also an additional measurement data taken

while experiment started. This data is shown in Figure 2.13. Critical minute 25 is

marked. Up to this point, fans do not operate and again slot5 and slot5_c

thermocouple values are closed to each other. However, when fans started to operate

it is shown that there are differences between measured temperature values. As

Page 55: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

37

stated, the reason of the difference can be thought as the affect of cooling air on

slot5_c thermocouple.

Therefore, first assumption is verified and measuring wall temperatures from inside

of the wall does not cause to inaccuracy. Quite the contrary, wall inside measurement

gives more reliable results than wall outside measurement.

Wall Temperatures - Time

24

26

28

30

32

34

36

38

40

42

0 10 20 30 40 50 60 70 80 90 100 110 120

Time [Min.]

Tem

pera

ture

[°C

]

slot5 slot5_c

25

Figure 2.13 Temperatures of slot5 and slot5_c while ACCC operates.

Also second assumption must be verified if it is possible to continue experiments by

measuring only left wall temperature values. Because in analytical calculations,

dissipated heat is calculated for only one wall by assuming symmetry condition is

applicable.

Page 56: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

38

To examine if symmetry condition is convenient right wall slot temperatures are

compared with left wall slot temperatures. Right wall 1st, 5th and 11th slot

temperatures are compared with the left wall 1st, 5th and 11th slot temperatures

respectively. In Figure 2.14 results of these measurements are given.

Wall Temperatures - Time

25

27

29

31

33

35

37

39

41

43

0 10 20 30 40 50 60 70 80 90 100 110

Time [Min.]

Tem

pera

ture

[°C

]

slot1 slot5 slot11

slot1o slot5o slot11o

Figure 2.14 Temperatures of opposite walls.

Summary of above graphs is tabulated as below. Temperature differences between

slot1, slot5 and slot11 thermocouples are 2.1 °C, 2.2 °C and 0.8 °C respectively.

However, measured data show that left wall of the ACCC is hotter than right wall;

temperature differences do not constitute big errors in analytical calculations. On the

other hand, analytical calculations will be done for the more critical left wall

temperature values.

ACCC reaches to steady state condition approximately 60 minutes later as shown in

Figure 2.13. The steady state slot temperatures are tabulated Table 2.3. There are

Page 57: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

39

totally 9 thermocouples on the slots and the average value of measured temperatures

is calculated as 33.3 °C for the left wall.

Table 2.2 Opposite channels thermocouple results.

Thermocouples Temperatures [°C] ∆T [°C]

slot1 (L) 33.7

slot1o (R) 31.6 2.1

slot5 (L) 33.8

slot5o (R) 31.6 2.2

slot11 (L) 30.7

slot11o (R) 29.8 0.8

As it is seen both in Figure 2.14 and Table 2.2, slot temperatures are distinct from

each other as a result of different power loads of electronic cards (details of heat

loads of each card is given in Table 2.1). These various power loads are converted to

the heat loads, which cause different temperature levels on the slots.

Table 2.3 Measured slot temperatures at 25 ºC.

Slot1 Slot2 Slot3 Slot4 Slot5 Slot6 Slot7 Slot10 Slot11 Average

Steady State Temperatures [°C]

33.7 36.6 34.7 34.6 33.8 32.7 31.8 30.8 30.7 33.3

2.3 55 °C Ambient Temperature Experiments

This experiment is conducted at 55 °C ambient air temperature in a test chamber,

which is shown in Figure 2.15. ACCC is placed in the chamber and the temperature

of the chamber is set to 55 °C.

Page 58: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

40

The necessary condition in order to conduct the experiment is convergence of ACCC

to 55 °C. Data collection is started and measurements are saved in order to confirm if

ACCC reached to 55 °C steady state condition. As it is seen in Figure 2.16, all

thermocouples are converged to 55 °C approximately 155 minutes later. Actually,

155 minutes time window is the convergence of ACCC to 55 °C and does not

operate during the convergence time window.

Figure 2.15 ACS Test chamber.

Page 59: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

41

Temperature - Time

20

25

30

35

40

45

50

55

60

0 20 40 60 80 100 120 140 160

Time [Min.]

Tem

pera

ture

[°C

]

slot1 slot2 slot3 slot4 slot5 slot6 slot7 slot10 slot11

Figure 2.16 55 ºC non-operating measurement results.

Experiment duration is approximately 75 minutes. 19 thermocouples are used for

data collection. Approximately 60 minutes later ACCC reaches to steady state

condition and measured temperatures do not change any more.

According to experimental results, steady state slot temperatures are tabulated in

Table 2.4. Most critical temperature is shown in the Slot2 which is 66.7 °C. Average

temperature of the slots is calculated as 63.3 °C.

Page 60: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

42

Table 2.4 Measured slot temperatures at 55 ºC.

Slot1 Slot2 Slot3 Slot4 Slot5 Slot6 Slot7 Slot10 Slot11 Average

Steady State Temperatures [°C]

63.6 66.7 64.7 64.7 63.7 62.6 61.8 60.6 61.0 63.3

Besides all these measurements, critical CPU junction temperature values are also

collected. It is seen that for this chassis, CPUs work on the critical temperature limit,

which is 95 ºC. Therefore, measured wall temperature values are the design

considerations for the next studies.

Temperature - Time

50

51

52

53

54

55

56

57

58

59

60

61

62

63

64

65

66

67

68

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80

Time [Min.]

Temperature [°C]

slot1 slot2 slot3 slot4 slot5 slot6 slot7 slot10 slot11

Figure 2.17 55 ºC operating measurement results.

Page 61: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

43

CHAPTER 3

3 ANALYTICAL STUDIES

In Aselsan Inc., in particular, but also in the most of the electronic industry, in

generally, design of an ATR chassis is done with the cooperation of Mechanical

Design and CFD Analysis departments. Mechanical design engineers decide about

the cooling channel details by using the previous design experiences. For instance, a

mechanical design engineer tries to apply the plate fin details of previous chassis to

the new design without any knowledge if the same plate fin details are applicable to

the new conditions. After design is completed, the model is transferred to CFD

analysis team to understand if the cooling capacity of the chassis is sufficient or not.

Generally, new designs do not meet necessary cooling requirements. At this stage,

analysis team gives some feedback to the mechanical designer in order to change the

cooling channel details. This change is done by increasing or decreasing the number

of plate fins, by changing the width of the channel or by changing the thickness of

the plate fins. All these parameters are unknowns and there are many options with

different combinations. At this stage, there is an uncertainty and the mechanical

design engineer does not know which way to go. The CFD analysis team must verify

every new option tried by the mechanical design engineer before production and

every loop between the design engineer and the analysis team takes several weeks.

This trial and error procedure between the design engineer and the analysis team

causes time and money loses.

Page 62: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

44

The aim of the analytical studies is to develop a Thermal Model Tool (TMT), which

will be used by mechanical design engineers before starting to the mechanical

design. By using this tool, initial thermal design process of the ATR chassis will be

completed in order to make more affective designs.

During analytical studies, thermal mathematical model of the chassis is generated.

The generated thermal model can be carried out not only for DMAP but also for any

type of ATR chassis. The input of the model is critical wall temperatures obtained

from experimental studies and geometrical limitations. By using given limitations,

the mathematical model will give a basic feedback to mechanical designer about the

cooling channel geometry of the chassis. The mechanical designer uses the feedback

and checks if it is possible to dissipate the generated heat within the chassis, which

will be formed with given constraints.

In the analytical calculations chapter, two different ATR chassis are considered. One

of them is the new design chassis DMAP and the second one is the existing chassis,

on which the experimental studies were carried out, ACCC. Thermal model tool is

developed on DMAP and analytical calculations are done for both DMAP and

ACCC. Although ACCC is not a new design chassis, the aim of the analytical studies

for ACCC is to test the TMT on a different chassis.

3.1 DMAP Analytical Studies

As mentioned in Page 8, forced convection method is used, and the chassis has

cooling channels. General flow chart of the chassis is shown in the given cross

sectional view Figure 3.1. Cooling air is sucked from the side air intake openings,

flows via the plate-fins, collected in front of the fan, and exhausted to the

environment.

Page 63: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

45

Figure 3.1 Flow chart of DMAP.

Cooling air opening

Cooling air opening

Plate Fins Plate Fins

Cooling air coolectin section

Page 64: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

46

Figure 3.2 shows the cooling method of chassis. The generated heat is conducted

from central processing units (CPU) to thermal plate and then conducted to slot of

chassis. Similarly, heat is conducted to finned structure. Cooling air is flowing

through finned structure; in this way heat is dissipated by convection to the cooling

air. Because the same VME size electronic cards are used, sizes of the thermal plates

are also the same for all of the cards. Moreover, behavior of the thermal plates is

similar and known from previous studies. For this reason, convection section of the

cooling is considered in mathematical model and conduction is not studied.

Figure 3.2 Chassis cooling method.

On the electronic cards, CPU is the most critical component and this study is based

on the critical operating temperature of the CPUs. Critical junction temperature for

the CPUs is 95 °C. By using the results of experiments, it is learnt that the average

slot wall temperature is about 63.3 ºC when the CPU reaches to critical junction

temperature (95 °C). This case occurs at 55 °C operating condition. In the

mathematical model of the chassis, well-known empirical connection correlations are

PCB, E. component, thermal plate

Cold Air

Air Channel

Slot

Fin Structure

Page 65: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

47

used. At the end of the analytical studies, radiative heat transfer is examined also to

understand if the rate of transferred heat by radiation is negligible or not.

Analytical calculations are observed under two topics; heat transfer calculations and

pressure drop calculations.

3.1.1 Heat Transfer Calculations

General cooling method of convection is summarized in Figure 3.3. Heat transfer to a

fluid flowing in a tube is equal to the increase in the enthalpy of the fluid. Energy

balance equation can be written as:

)( iep TTCmQ −=••

( 3.1)

This is the cooling capacity of flowing air inside the cooling channel and equal to the

dissipated heat load. Dissipated heat is transferred to cooling air by convection. So

energy balance equation can be written as:

lnThATCmQ channelairairpair ∆=∆=••

( 3.2)

Figure 3.3 General cooling method of convection

Page 66: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

48

Q = heat load to be dissipated

airmm••

= = cooling air mass flow rate

ieair TTT −=∆ = temperature difference of cooling air exit and inlet

iT = cooling air inlet temperature

eT = cooling air exit temperature

airpp CC = = specific heat capacity of air

h = convection heat transfer coefficient

channelA = surface area of convection

lnT∆ = logarithmic temperature difference

In the mathematical model, by using heat load (generated heat), necessary cooling

surface area, or in other words necessary number of plate fins are calculated. In

calculations, most critical variable is convection heat transfer coefficient and can be

calculated from Nusselt number.

4.0=n for heating and 3.0=n for cooling. nNu PrRe023.0 8.0= ( 3.3)

This equation is known as Dittus-Boelter equation [6].

Eq. 2.3 is fairly simple, and it may give errors as large as 25 percent. This error can

be reduced considerably by using more complex but more accurate relations such as

the second Petukhov correlation [6] expressed as:

)1(Pr)8/(7.1207.1

PrRe)8/(3/25.0 −+

=f

fNu ( 3.4)

Page 67: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

49

The accuracy of this relation at lower Reynolds numbers is improved by modifying it

as [6]:

)1(Pr)8/(7.121

Pr)1000)(Re8/(3/25.0 −+

−=

f

fNu

<<

≤≤

63 105Re103

2000Pr5.0

xx ( 3.5)

Cengel [6] stated that, the turbulent flow in circular tube relations could be used for

turbulent flow in noncircular tubes. His explanation on the subject is: “The velocity

and temperature profiles in turbulent flow are nearly straight lines in the core region,

and any significant velocity and temperature gradients occur in the viscous sub

layer.” [6] Figure 3.4 shows the turbulent, overlap and laminar sub layers.

Figure 3.4 Viscous sub layer.

“Despite the small thickness of laminar sub layer (usually much less than 1 percent

of the pipe diameter), the characteristics of the flow in this layer are very important

since they set the stage for flow in the rest of the pipe. Therefore, pressure drop and

heat transfer characteristics of turbulent flow in tubes are dominated by the very thin

viscous sub layer next to the wall surface, and the shape of the core region is not of

much significance. Consequently, the turbulent flow relations given above for

circular tubes can also be used for noncircular tubes with reasonable accuracy by

replacing the diameter D in the evaluation of the Reynolds number by the hydraulic

diameter pAD ch /4= .” [6]

Page 68: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

50

3.1.2 Pressure Drop Calculations

In analytical calculations, pressure drop through the cooling channel is also

considered. Depending on the plate fin number, operating point of the fan in use is

changing and as a result, flow rate decreases or increases. If the equation of the fan

performance curve is known, it is possible to calculate the volumetric flow rate

against the known pressure value.

Fan performance curve is known, and given in the Appendix B. Volumetric flow rate

(VFR) values against the pressure values are determined from the fan performance

curve and tabulated (Table 3.1).

Table 3.1 Fan Curve Data (DMAP).

Volumetric Flow Rate [CFM] Pressure [Inches of Water] 0.0 2.72 2.5 2.56 5.0 2.36 7.5 2.20

10.0 2.04 12.5 1.96 15.0 1.94 16.0 1.96 18.0 2.00 20.0 2.06 22.5 2.16 25.0 2.24 27.5 2.27 28.5 2.28 30.0 2.24 32.5 2.10 34.0 2.00 37.5 1.76 41.5 1.40 43.5 1.20 47.0 0.80 53.0 0.00

Page 69: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

51

By using fan curve data values, performance curve is plotted again changing the axes

positions as VFR (y axis) and Pressure (x axis) (Figure 3.5). The aim of converting

the axes of the fan performance curve is getting a VFR equation dependent on the

pressure values.

Pressure - VFR

0

10

20

30

40

50

60

0.0 0.5 1.0 1.5 2.0 2.5 3.0

Pressure [Inches of Water]

VF

R [

CF

M]

Figure 3.5 Fan Curve Data Plot.

Because it is not possible to add a trend line to a graph given in Figure 3.5, the graph

is divided into three parts and 4th order trend lines are added to the each part as

shown in Figure 3.6. In next steps, according to results of VFR calculations, trend

line selection will be done.

On this new plot, units of VFR and pressure data are converted to m3/s and Pa

respectively. Equations of the trend lines are added also on the graph. Because there

are two cooling channels on the chassis, the VFR values are divided into two. In this

Page 70: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

52

case, if the pressure drop is known, VFR can be calculated by using the trend line

equations.

VFR - Pressure

y = -7E-14x4 + 6E-11x

3 - 2E-08x

2 - 4E-06x + 0.0125

y = 2E-10x4 - 4E-07x

3 + 0.0003x

2 - 0.0912x + 11.568

y = 9E-12x4 - 2E-08x

3 + 2E-05x

2 - 0.008x + 1.1956

0

0.0021

0.0042

0.0063

0.0084

0.0105

0.0126

0.0147

0 100 200 300 400 500 600 700 800

Pressure [Pa]

VF

R [

m3

/s]

Figure 3.6 Trend Line Added Fan Curve Plot (DMAP).

Pressure drop through the plate fins can be calculated by using the Eqn. 3.6. Before

starting to the calculations, an initial velocity value is defined and this value is

updated in a loop with iteration.

2

2

14 VKK

D

LfP ec

h

app ρ

++=∆ ( 3.6)

175.02.0Re0962.0

−⋅=h

c

appD

Lf ( 3.7)

Page 71: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

53

2

4.08.0

−=

p

aK c ( 3.8)

−=

p

a

p

aK c 4.01

2

( 3.9)

The calculated pressure drop is the result of plate fins. In addition, pressure drop of

the chassis without any plate fin must be known. In this instance, a simple flow

analysis is done to find the pressure drop of the chassis.

Two different pressure drop values are obtained. One of them is analytically

calculated pressure drop value for plate fins and the other one belongs to the chassis,

which does not have any plate fins. Both of them are summed up and a total pressure

drop value is obtained for the chassis with plate fins. By using the trend line

equations, VFR value is calculated corresponding the total pressure drop. The

calculated VFR value is used for thermal calculations.

3.1.3 Thermal Model Generation and Solutions

The DMAP has different operating conditions, which are given in MIL-STD-810F as

25 ºC and 55 ºC [7]. The DMAP also must also be operated in negative temperature

values up to -40 ºC. Since there is no need for cooling in minus temperatures, only

25 ºC, and 55 ºC operating conditions are considered and calculations are done for

these two conditions.

Calculations are done by using Mathcad software and the code is given in Appendix

C. Appropriate number of plate fins are selected for the necessary cooling capacity

Page 72: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

54

by considering both ambient 25 ºC and 55 ºC operating conditions. Analytical

calculations are done according to given constraint.

Most critical input for the analytical calculations is wall temperatures. Experimental

studies done in Aselsan Inc., results of which are represented in Chapter 2, show that

if the average wall temperature of the chassis is about 63.3 °C at 55 °C operating

condition, the CPUs of the electronic processor cards do not reach to the critical

junction temperature. Plate fin detail must be selected for the critical operating

condition 55 °C at which the major cooling problem occurs. Although cooling is not

critical for 25 °C operating condition, analytical calculations are done for this

condition in order to verify the mathematical model twice. Therefore, 33.3 °C wall

temperature of the 25 °C operating condition is used for 25 °C calculations.

3.1.3.1 25 ºC Operating Condition Calculations

25 ºC ambient temperature is one of the operating conditions for the DMAP. Air

properties are given in Table 3.2 are taken from Incropera and DeWitt [8] and

interpolated to 298 K.

Table 3.2 Air properties at 25 ºC.

Cpair (J/kgK) 1007

ρair (kg/m3) 1.1707

µair (kg/ms) 1.836x10-5

Pr 0.708

kair (W/mK) 0.0261

Page 73: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

55

Steps of an example calculation are explained here for the number of plate fins 15.

Because the pressure drop of the chassis without any plate fin is needed, by using

Icepak, a flow analysis is done. The result is used in the analytical model to calculate

the total pressure drop values for different plate fin numbers. Fan operating point

gives the pressure drop value and is obtained as 260 Pa. By using the first trend line

equation of Figure 3.6, total pressure drop and corresponding velocity is calculated

with the initial velocity 10 m/s.

Calculation is done by iteration and finally updated velocity value is 7.7 m/s for the

number of fins=15. Pressure drop along the 15 fins is calculated as 61.6 Pa.

Therefore, calculated VFR value is also updated. The last updated VFR value is

0.01034 m3/s. The VFR value is in the range of first trend line equation. Therefore,

first trend line selection for the VFR calculation is confirmed. After calculations of

VFR, thermal calculations are done. Dimensions of the cooling channel are given in

Table 3.3.

Table 3.3 DMAP channel dimensions.

Channel height (m) h 0.158

Channel length (m) L 0.3

Channel width (m) w 0.01

Fin thickness (m) b 0.0016

“n” shows the number of fins and n = 10..40.

“a” shows the distance between two plate fins and can be calculated as below:

1+

⋅−=

n

bnha ( 3.10)

Page 74: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

56

Wetted perimeter of cooling channel,

2)( ⋅+= awP ( 3.11)

Total perimeter of all cooling channels,

PnPall ⋅+= )1( ( 3.12)

Total convection surface area,

LPA allall ⋅= ( 3.13)

Section flow area of one channel

awAs ⋅= ( 3.14)

All section flow area of channels

)1( +⋅= nAA ssall ( 3.15)

Hydraulic diameter cooling channel,

P

AD s

H ⋅= 4 ( 3.16)

Velocity of the cooling air in the channel,

sall

air

airA

VFRV = ( 3.17)

Reynolds number formulation

air

Hairair DV

µ

ρ ⋅⋅=Re ( 3.18)

Page 75: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

57

Now friction factor and can Nusselt number be calculated by using Petukhov

correlation:

2)64.1log(Re)82.1(

1

−⋅=f ( 3.19)

( )

−⋅

⋅+

⋅−⋅

=

1Pr8

7.121

Pr1000Re8

3

25.0f

f

Nu ( 3.20)

Most critical parameters for the calculations are Vair and Re. For the selected number

of fins, these two parameters can be calculated. Indeed if the number of fins

increases, pressure drop also increases and operating point of fan must be changed.

Therefore, pressure drop calculations are also done.

After the calculation of Nusselt number, convection heat transfer coefficient can be

calculated by using the Eqn. 3.21:

NuD

kh

H

air ⋅= ( 3.21)

In order to find a result closer to experimental studies, fin efficiencies also must be

calculated. The calculation terms of fin efficiency are given below:

( )( )

2

1

2

⋅⋅

+⋅=

Lbk

Lbhme

al

( 3.22)

( )wme

wmef

⋅=

tanhη ( 3.23)

Page 76: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

58

2⋅⋅= LwA f ( 3.24)

( )( )

f

all

f

oA

Anηη −⋅

⋅+−= 1

11 ( 3.25)

Operating condition temperature is the inlet temperature of cooling air. For the

cooling air outlet temperature, 0.1 ºC difference initial value is assumed and finally

the value is updated with iteration. The critical temperature values used in the

calculations are given in Table 3.4.

Table 3.4 Critical temperatures of 25 ºC operating condition.

Tw (Wall temperature K) 306.5

Ti (Cooling air inlet temperature K) 298

Te (Cooling air outlet temperature K) 301.8

It is necessary to calculate the logarithmic temperature difference for the heat

dissipation calculation.

ewe TTT −=∆ ( 3.26)

iwi TTT −=∆ ( 3.27)

Logarithmic temperature difference (LTD) formulation:

∆−∆=∆

i

e

ie

T

T

TTT

lnln ( 3.28)

Page 77: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

59

By using the above given definitions, calculations are done for the LTD and

efficiency. Results are given in Table 3.5.

Table 3.5 LTD and efficiency of channel at 25 ºC.

∆Tln (K) 6.2

me (1/m) 19

ηf 0.988

ηo 0.994

Finally, total heat dissipation rate of the plate fins can be calculated from:

( )lnTAhQ allocal ∆⋅⋅⋅= η ( 3.29)

However, convection heat transfer calculations are done, it is necessary also to see

the cooling air heat transfer capacities of the cooling channels.

In order to calculate the heat transfer capacity of the channel cooling air, Eqn. 3.30 is

used:

)( ieairaircapat TTCpMFRQ −⋅⋅= ( 3.30)

Heat dissipation capacities of cooling air and convection heat transfer must be same.

Therefore, a new temperature difference value (∆Tn) is calculated by using Eqn. 3.31.

airair

cal

nCpMFR

QT

⋅=∆ ( 3.31)

Page 78: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

60

The assumed exit temperature value is iterated by using new ∆Tn. Therefore, Qcapat is

compensated to the value Qcal with small errors.

First mathematical model is solved for the 15 number of plate fins in order to show

an example calculation step. Results are tabulated and given in Table 3.6. In the next

step, by using the given definitions, calculations are done to find the appropriate fin

configuration.

Table 3.6 Calculation results at 25 ºC for the number of plate fins 15.

Operating Condition (ºC) 25

Number of fins 15

a (mm) 8.4

∆P (Pa) 61.6

Vair (m/s) 7.7

VFR (cfm) 22

Re 4502

Nu 15.1

h (W/m2K) 43.4

∆T (K) 3.9

ƞo 0.9935

Qcal (W) 47.7

For the next study, all calculations are done in order to find the appropriate number

of fins to dissipate the given heat load. Below terms are calculated for the fin number

range 10-40.

� Distance between two plate fins (a),

� Pressure drop (∆P),

� Velocity values for each number of plate fin (Vair),

� Volumetric flow rate (VFR),

� Reynolds numbers (Re),

� Nusselt number (Nu),

Page 79: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

61

� Convection heat transfer coefficient (h),

� Cooling air inlet and exit temperature difference (∆T),

� Fin efficiency (η0),

� Calculated heat dissipation rate (Qcal),

The total generated heat inside the chassis is calculated as approximately 100 W in

the Chapter 1, Page 11. Therefore, 50 W heat load must be dissipated via two

symmetric cooling channels. In order to achieve this goal, iterations are done on the

mathematical model and 17 number of plate fins are selected.

Calculation results for 17 number of plate fins are tabulated and given in Table 3.7.

Table 3.7 Calculation results at 25 ºC for the number of plate fins 17.

Operating Condition (ºC) 25

Number of fins 17

a (mm) 7.3

∆P (Pa) 69.7

Vair (m/s) 7.9

VFR (cfm) 21.9

Re 4234

Nu 14.3

h (W/m2K) 44.3

∆T (K) 4.1

ƞo 0.993

Qcal (W) 50.4

Same calculations are performed for 55 ºC operating condition and appropriate

number of fin is decided.

Page 80: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

62

3.1.3.2 55 ºC Operating Condition Calculations

Formulations used for the 25 ºC calculations are applicable for the 55 ºC calculations

by using the properties of air given in Table 3.8, which are valid for 55 ºC. Besides

the air properties, cooling air inlet and wall temperatures are also different. Similarly

0.1 ºC initial temperature difference is assumed between inlet and exhaust air.

Critical wall temperature is also known for the 55 ºC ambient conditions.

Table 3.8 Air properties at 55 ºC.

Cpair (J/kgK) 1008.1

ρair (kg/m3) 1.0682

µair (kg/ms) 1.978x10-5

Pr 0.703

kair (W/mK) 0.0284

The critical temperature of electronic cards components is approximately 95 ºC and

known that if the wall temperature of the chassis is approximate 63.3 ºC, components

of the electronic cards do not reach to the critical temperature. Actually, this is the

design criterion. In the analytical calculations, this critical wall temperature is used.

Therefore, the calculations start with the wall temperature 336.5 K. The critical

temperature values used in the calculations are given in Table 3.9.

Table 3.9 Critical temperatures of 55 ºC operating condition

Tw (Wall temperature K) 336.5

Ti (Cooling air inlet temperature K) 328

Te (Cooling air outlet temperature K) 333

Page 81: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

63

The same calculations to find the appropriate number of fin to dissipate 100 W heat

load are done and results are tabulated (Table 3.10) for the 55 ºC operating

conditions. Iterations are done and to dissipate 50 W heat load via each channel,

number of plate fins is found as 21.

Table 3.10 Calculation results at 55 ºC for the number of plate fins 21.

Operating Condition (ºC) 55

Number of fins 21

a (mm) 5.7

∆P (Pa) 82.7

Vair (m/s) 8.2

VFR (cfm) 21.7

Re 3205

Nu 10.8

h (W/m2K) 42.3

∆T (K) 4.6

ƞo 0.9926

Qcal (W) 50.7

3.1.3.3 25 ºC and 55 ºC Fin Number Comparison

There are totally 100 W heat loads to dissipate and there are 2 different operating

conditions. The calculations are done for both 25 ºC and 55 ºC operating conditions

in order to find the necessary plate fin numbers. After the calculations are done the

values are tabulated and given in Table 3.11.

Table 3.11 25 ºC and 55 ºC results comparison.

Operating Conditions ºC

Necessary fin number to dissipate 50 W

25 17

55 21

Page 82: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

64

If the both operating conditions compared it is seen that more fin number is

necessary for the 55 ºC condition. Therefore, 55 ºC condition can be taken as the

worst case and fin number selection must be done for this case. Therefore, 21 plate

fin numbers must be used on the cooling channels.

Actually, it may be possible to dissipate more heat loads by using much more plate

fin numbers. However, using more fin numbers than necessary generates useless

mass load on the chassis. Because this chassis is helicopter equipment, mass is an

important criterion. On the other hand, it is not easy to produce plate fins with small

pitches. Chassis having more plate fins increases the cost of the production.

All calculation results of 25 ºC and 55 ºC operating conditions tabulated and given in

Appendix D. The plotted results are in Figure 3.7. Selection of number of fins for a

new chassis with similar dimensions can be done by using the quick reference tables

or for a different size chassis TMT is applicable.

Number of Fin - Qcal

0

10

20

30

40

50

60

70

80

0 5 10 15 20 25 30 35 40 45 50 55

Number of Fin

Qca

l [W

]

25ºC

55ºC

Figure 3.7 Results of TMT for the operating conditions 25 ºC and 55 ºC.

Page 83: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

65

While all cooling calculations are done, assumed that all the generated heat is

dissipated by convection. In order words, the amount of dissipated heat by

conduction and radiation can be neglected. In order to support conduction negligence

below explanation is useful:

Chassis surfaces do not have any contact with anywhere. Only bottom surface of the

chassis has a contact with the mounting tray but the mounting tray is mounted to the

ground with elastic isolators. Therefore, there is not any contact with anywhere for

the conduction cooling. In order to see if the negligence of the radiation is true,

radiation heat transfer is also checked.

3.1.4 Radiative Heat Transfer Calculations

In this section, radiative heat transfer calculations are done. Results are examined to

understand if neglecting radiave heat transfer is meaningful for this study. In order to

simulate the real test case, a cabinet is formed which is used instead of test oven and

a block is placed inside the oven, which is substituting the chassis.

Because front surface of chassis is used as a connector plate and the back surface is

used for cooling air output, radiative heat transfer from these two planes are

neglected since these plates do not have a considerable surface area. These two

surfaces are shown in Figure 3.8.

In addition, bottom surface of the chassis is in perfect contact with the oven surface

and thus only 3 walls (2 side surfaces and 1 top surface) of chassis are considered for

radiative heat transfer calculations. To calculate radiative heat transfer from

considered walls, eqn. 3.32 is used.

,11

11bj

N

j

jibioijji

N

j ji

i EFEHqFq

∑∑=

−−

=

−=+

−−

εε .,...,2,1 Ni = ( 3.32)

Page 84: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

66

jiF − term is for the view factors between the walls of the whole system. Wall

numbers are shown in Figure 3.9.

Figure 3.8 General view of DMAP in the chamber

Front Surface Back Surface

Page 85: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

67

Figure 3.9 Walls numbers.

To describe wall numbers clearly, Table 3.12 is given.

Table 3.12 Wall Numbers.

Wall Descriptions Wall Number

DMAP body minz 1

DMAP body maxy 2

DMAP body maxz 3

OVEN body maxx 4

OVEN body maxy 5

OVEN body maxz 6

OVEN body minx 7

OVEN body miny 8

OVEN body minz 9

5 - Top wall

4 - Rear wall

7 - Front wall

8 – Bottom wall

6 – Right wall 9 – Left wall

1 – DMAP Left Wall

2 – DMAP Top Wall

3 – DMAP right Wall

Oven

DMAP

Page 86: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

68

To calculate view factors it is not easy to use a view factor catalogue because of 3D

geometry. View factor catalogues are useful for simple 2D planes. Therefore, Icepak

is used to get view factor values. The geometry is defined and Icepak calculates view

factors. An example result is given in Figure 3.10. These view factor values are

exported and Table 3.13 is formed. These values are used as jiF − in Eqn. 3.32. There

are 9 unknown radiative heat transfer values as 987654321 ,,,,,,,, qqqqqqqqq . Eqn.

3.32 must be written for all 9 walls. At the end of solution all radiative heat transfer

values of all walls are obtained.

Figure 3.10 View factors.

0.2 emissivity value can be used for oven walls ( 987654 ,,,,, εεεεεε ) and 0.3

emissivity value is convenient for chassis walls ( 321 ,, εεε ). Because there is no

external radiation there is no oiH term in the equation. Equations are written in

matrix form and Mathcad is used to solve the equations.

Page 87: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

69

Table 3.13 View factors.

F12 0.00000 F21 0.00000 F31 0.00000 F41 0.00371 F51 0.00145

F13 0.00000 F23 0.00000 F32 0.00000 F42 0.00666 F52 0.01171

F14 0.07074 F24 0.17293 F34 0.07066 F43 0.00371 F53 0.00145

F15 0.02764 F25 0.30409 F35 0.02761 F45 0.19988 F54 0.19988

F16 0.00000 F26 0.17131 F36 0.42392 F46 0.19954 F56 0.19991

F17 0.07478 F27 0.18037 F37 0.07478 F47 0.19505 F57 0.19976

F18 0.40303 F28 0.00000 F38 0.40303 F48 0.18272 F58 0.18539

F19 0.42382 F29 0.17131 F39 0.00000 F49 0.19958 F59 0.19981

F61 0.00000 F71 0.00392 F81 0.02199 F91 0.02223

F62 0.00660 F72 0.00695 F82 0.00000 F92 0.00660

F63 0.02224 F73 0.00392 F83 0.02199 F93 0.00000

F64 0.19954 F74 0.19505 F84 0.19004 F94 0.19958

F65 0.19991 F75 0.19976 F85 0.19282 F95 0.19981

F67 0.19952 F76 0.19952 F86 0.18461 F96 0.19295

F68 0.17750 F78 0.18199 F87 0.18928 F97 0.19948

F69 0.19295 F79 0.19948 F89 0.18473 F98 0.17762

There are 3 matrixes. A is the unknown “q” matrix. B is the coefficient matrix of

unknown “q” values. Finally C is the known values matrix. All matrixes are shown

below. According to Eqn. 2.27, CBA =* . Because it is wanted to find unknown “q”

values, the matrix equation CBA *1−= is used. The critical input for the

calculations is wall temperature values and is the result of experiments. The

calculations are done for the operating temperature 25°C. So all chassis walls are at

306.3K and oven walls are at 298K.

By using Mathcad the matrix multiplication is done.

Page 88: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

70

⋅−⋅−⋅−⋅−⋅−⋅−⋅−⋅−

⋅−⋅−⋅−⋅−⋅−⋅−⋅−⋅−

⋅−⋅−⋅−⋅−⋅−⋅−⋅−⋅−

⋅−⋅−⋅−⋅−⋅−⋅−⋅−⋅−

⋅−⋅−⋅−⋅−⋅−⋅−⋅−⋅−

⋅−⋅−⋅−⋅−⋅−⋅−⋅−⋅−

⋅−⋅−⋅−⋅−⋅−⋅−⋅−⋅−

⋅−⋅−⋅−⋅−⋅−⋅−⋅−⋅−

⋅−⋅−⋅−⋅−⋅−⋅−⋅−⋅−

=

8987976965954943932921919

9897876865854843832821818

9798786765754743732721717

9698687675654643632621616

9598587576564543532521515

9498487476465454432421414

9398387376365354342321313

9298287276265254243231212

9198187176165154143132121

EbFEbFEbFEbFEbFEbFEbFEbFEb

EbFEbFEbFEbFEbFEbFEbFEbFEb

EbFEbFEbFEbFEbFEbFEbFEbFEb

EbFEbFEbFEbFEbFEbFEbFEbFEb

EbFEbFEbFEbFEbFEbFEbFEbFEb

EbFEbFEbFEbFEbFEbFEbFEbFEb

EbFEbFEbFEbFEbFEbFEbFEbFEb

EbFEbFEbFEbFEbFEbFEbFEbFEb

EbFEbFEbFEbFEbFEbFEbFEbFEb

C

=

9

8

7

6

5

4

3

2

1

q

q

q

q

q

q

q

q

q

A

2.0

2.0

2.0

2.0

2.0

2.0

3.0

3.0

3.0

9

8

7

6

5

4

3

2

1

=

=

=

=

=

=

=

=

=

ε

ε

ε

ε

ε

ε

ε

ε

ε

KT

KT

KT

KT

KT

KT

KT

KT

KT

298

298

298

298

298

298

3.306

3.306

3.306

9

8

7

6

5

4

3

2

1

=

=

=

=

=

=

=

=

=

4

99

4

88

4

77

4

66

4

55

4

44

4

33

4

22

4

11

TEb

TEb

TEb

TEb

TEb

TEb

TEb

TEb

TEb

⋅=

⋅=

⋅=

⋅=

⋅=

⋅=

⋅=

⋅=

⋅=

σ

σ

σ

σ

σ

σ

σ

σ

σ

42

81067.5Km

W⋅×= −σ

Page 89: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

71

Page 90: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

72

Mathcad result is shown below. To calculate all radiation heat transfer values we

must multiply below “q” results by area of walls.

2

618.1

577.2

664.1

618.1

564.1

21.2

69.11

285.11

688.11

m

WA ⋅

= 2

3

2

1

/

7.11

3.11

7.11

mW

q

q

q

Area of wall 1 is = 052.0332.0158.0 =x m2

Area of wall 2 is = 039.0332.0116.0 =x m2

Area of wall 3 is = 052.0332.0158.0 =x m2

The radiative heat transfer results of chassis walls are given below. The value Q1, Q2

and Q3 are the radiative heat dissipation rates of surfaces 1, 2 and 3 respectively

shown in Figure 3.9.

9.01 ≈Q W

7.02 ≈Q W

9.03 ≈Q W

In conclusion, wall temperatures are the results of experiments. If the radiative heat

transfer calculation results are examined it is seen that totally 2.5 W heat rate is

dissipated with radiation. If the radiation and convection results are examined

together, it seen that 2.5 W can be neglected compared to 100 W total load.

Therefore, radiative heat transfer neglect is meaningful while analytical calculations

are done.

Page 91: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

73

3.2 ACCC Analytical Studies

ACCC is the existing chassis on which experimental studies are performed. The

purpose of the analytical studies on ACCC is to indicate the applicability of TMT on

different chassis. The TMT is developed on DMAP but can be applied on any type of

ATR chassis by changing specific parameters as dimensions and trend line

equation of the used fan. Number of plate fins=24 was used in the design of ACCC

and the chassis was produced in this wise. Therefore, dissipated heat is calculated by

using TMT for the number of fins 24 for both the operating conditions 25 ºC and 55

ºC. Similar to the DMAP studies, in the next step numerical studies are done for

ACCC and results are compared.

Ametek Rotron Propimax 2 fan shown in Figure 3.11 is used in ACCC. Fan

performance curve and dimensions of the fan is given in Appendix B. VFR –

Pressure plot is needed to get a fan curve dimension. Therefore, fan curve data is

acquired on the fan performance curve. VFR (y axis) and Pressure (x axis) graph is

plotted by converting VFR and pressure units to m3/s and Pa respectively (Figure

3.12). A 4th order trend line with equation is added on the curve.

Figure 3.11 Propimax 2 Fan.

Page 92: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

74

Table 3.14 Fan Curve Data (DMAP).

Volumetric Flow Rate [CFM]

Pressure [Inches of Water]

0 3.2

7.1 3

20 2.6

40 1.9

60 1.4

80 1.1

100 0.7

118.6 0

VFR - Pressure

y = -5E-13x4 + 9E-10x

3 - 5E-07x

2 + 1E-05x + 0.056

0.000

0.010

0.020

0.030

0.040

0.050

0.060

0 100 200 300 400 500 600 700 800 900

Pressure [Pa]

VF

R [

m3/s

]

Figure 3.12 Trend Line Added Fan Curve Plot (ACCC).

Page 93: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

75

Pressure drop value of the ACCC without any plate fins is required to use in TMT.

Therefore, a quick CFD flow analysis is performed and 435 Pa pressure drop is

obtained. Calculations are made for both 25 ºC and 55 ºC operating conditions using

trend line equation, pressure drop and dimensions of ACCC (Table 3.15) and results

are tabulated and given in Table 3.16. Numerical studies will be performed using the

same inputs and results will be compared.

Table 3.15 ACCC Channel Dimensions.

Channel height (m) h 0.192

Channel length (m) L 0.30

Channel width (m) w 0.0068

Fin thickness (m) b 0.0016

Table 3.16 Calculation results for 24 number of plate fins (ACCC).

Operating Condition (ºC) 55 25

Number of fins 24

a (mm) 6.1

∆P (Pa) 165.2 160.4

Vair (m/s) 11.1 11.3

VFR (cfm) 24.5 25

Re 4564 3945

Nu 15.3 13.3

h (W/m2K) 62 58.7

∆T (K) 5 5

ƞo 0.9959 0.9961

Qcal (W) 67.5 63.5

Page 94: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

76

CHAPTER 4

4 NUMERICAL STUDIES

Numerical studies are conducted to verify analytical calculations. In the analytical

calculations chapter, necessary number of fin was selected to dissipate the generated

heat loads for the chassis DMAP. This chapter involves numerical investigations of

the designed chassis. Numerical studies performed using Icepak 4.4.8 that is a CFD

software that solves mass, momentum and energy conservation equations to simulate

fluid flows with heat transfer. Radiative transport equation is not included in the

computations because of the negligence of radiative heat transfer in analytical

calculations.

Numerical studies are carried out for the chassis DMAP and ACCC both for 25 ºC

and 55 ºC operating conditions. Steps of the numerical studies can be listed as below:

• 3D model creation: The geometry is modeled in Icepak with the same

constraints used in analytical studies.

• Meshing: The created model is meshed using the right meshing parameters

with the appropriate meshing procedure.

• Solution: The meshed model is solved using the right solution procedure and

results are examined.

Page 95: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

77

4.1 Numerical Studies of DMAP

At the first step, the geometry is modeled in the Icepak with the known constraints,

which are used in analytical calculations. Cooling channels are created on the side of

the chassis and plate fins are placed in the cooling channels. There is a cabinet

geometry, which surrounds the chassis. The general view of the created 3D model is

shown in Figure 4.1.

The fan is placed at the back cover of the chassis as in the real model. Ametek

Rotron Vaneaxial Aximax 2 model fan is used in the design. The fan performance

curve (shown in Appendix A) is used during the analysis.

In order to reduce the mesh size and analysis time inside the chassis is defined as

hollow block shown in Figure 4.1. Therefore, as in the mathematical model only

cooling channels of the chassis are analyzed.

Wall temperature values were used as inputs for analytical calculations and necessary

number of plate fns are calculated for the given heat load. In numerical calculations

dissipated heat, which is the result of TMT, defined as total power on the sidewalls

and wall temperatures are found numerically.

Page 96: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

78

Figure 4.1 3D Model of DMAP.

4.1.1 Boundary Conditions and Basic Parameters of DMAP

Icepak automatically creates a cabinet to use as computational domain shown in

Figure 4.2 with blue boundary lines. The cabinet dimensions are modified to 116 x

158 x 332 mm in X-Y-Z directions respectively. Because radiation is not included,

there is no clearance between cabinet and DMAP walls. Except sidewalls, other four

walls of the cabinet are adiabatic. Because in the analytical calculations, studies are

conducted only for the cooling channels. Sidewalls are defined as opening and open

to mass and heat transfer. However, sidewalls of the chassis are defined adiabatic

Plate Fins

Cooling Channels

Fan

Hollow Block

Page 97: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

79

except front air intake openings shown in Figure 4.2. The adiabatic sidewall of the

chassis is hidden in the Figure 4.2 to show the plate fins. The analytically calculated

50 W heat load is defined on the sidewalls as boundary conditions. Inlet sections are

defined as openings for the boundary conditions with the ambient temperature. Fan is

the outlet boundary for the chassis.

Figure 4.2 Computational Model of DMAP.

In the numerical calculations, flow and temperature equations are solved and

radiative heat transfer is neglected. Because the velocity and Re is calculated in

analytical studies about 7.9 m/s and 4200 respectively, turbulent two-equation flow

regime is selected. Ambient temperature is defined as 25 ºC for the first and 55 ºC for

the second simulation. Because the problem is not time dependent, time variation is

chosen as steady.

Cabinet

Opening (On both sides)

Page 98: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

80

4.1.2 Grid Generation on DMAP

There are three types of meshers available in ANSYS Icepak: hexahedral, tetrahedral

and hex-dominant. The hexahedral unstructured mesher (the default for most

applications) is widely used and the most appropriate mesher [22]. Because the

geometry is not complicated and does not include spherical or ellipsoidal objects, the

hexahedral mesher is selected. Because mesh generation should be an iterative

procedure for best results, different numerical studies are done to find the true mesh

size changing the max size ratios. Therefore, mesh independence of the solution is

also verified.

For the fist case (number of plate fins 17), DMAP is meshed using mesh control

parameters given in Figure 4.4. By using per-object mesh parameters given, element

height of the fin is controlled and defined as 0.1 mm for refinement. 1,247,124

number of elements are generated shown in Figure 4.3 and quality ranges of the

elements are shown in Figure 4.6. Detailed view of a meshed fin is shown in Figure

4.5. Different numerical studies are performed for the max size ratios 2, 1.7 and 1.5.

Page 99: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

81

Figure 4.3 Meshed view of the chassis.

Figure 4.4 Mesh Control Parameters.

Page 100: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

82

Figure 4.5 Detailed view of meshed fin.

Figure 4.6 Quality of the mesh.

Page 101: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

83

4.1.3 Numerical Solution of DMAP

First-order discretization scheme is selected for the temperature and momentum.

Then by default, pressure equation is solved using the standard scheme, which gives

a relatively quick and accurate solution [19,22]. Under-relaxation factors and linear

solver settings are used as default. The version of the solver is selected as single

precision since the geometry does not have very disparate length scales [22].

Advanced solver setup window is shown in Figure 4.7. Turbulent, two-equation

model is used for the solution.

Figure 4.7 Advanced solver setup window.

Page 102: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

84

4.1.3.1 25 ºC Operating Condition Solution of DMAP

25 ºC analysis is done to verify the TMT results of 25 ºC. Therefore; the chassis has

number of plate fins 17 for this analysis. Operating condition is selected as 25 ºC and

50W heat load is defined on each wall as the design criteria. Analysis is completed

approximately after 1500 iterations. In order to understand if the convergence occurs;

points are placed on different zones of the chassis. Velocity, pressure, and

temperature curves of the points are followed if the change in the values stopped.

The points with the name W-1, W-2 and W-3 are on the wall and the point with the

name C is in the channel.

This study is repeated for three different mesh options, which are generated changing

max size units as 2, 1.7 and 1.5. The results of max size ratio 2 are given in detail and

the results of other size ratios are given in Table 4.1. ∆T shows the temperature

difference of cooling air between inlet and outlet sections. Qcal terms are calculated

using the VFR and �T variables and air properties with the heat transfer capacity

equation TCmQ ∆⋅⋅= .

Table 4.1 25 ºC results of DMAP for different number of elements.

Max Size ratio 1.5 1.7 2

Number of elements 2803737 1652596 1247124

∆P (Pa) 78.8 76.2 76.5

Vair (m/s) 7.2 7.2 7.1

VFR (CFM) 20.1 19.9 19.5

∆T (ºC) 4.9 4.9 4.9

Wall Temp. (ºC) 30.2 30.3 30.3

Qcal (W) 54 53 51

Because the results are nearly the same, it is possible to say that the analyses are

independent of mesh sizes. If the max size ratio is too high and as a result if the

overall mesh is too coarse, the resulting solution may be inaccurate. If the max size

ratio is too low and as a result if the overall mesh is too fine, the computational cost

Page 103: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

85

may become prohibitive. In summary, the cost and accuracy of the solution are

directly dependent on the quality and size of the mesh [22]. All terms given in Table

4.1 are the direct results of the simulations except Qcal term. The simulation result

with the max size ratio 2 is believed to be most accurate. Because the Qcal output of

this simulation is closest to the defined 50 W heat load on the wall. Therefore, next

grids are generated for all simulations using the max size ratio 2, which has also

minimum element size.

During analytical studies, calculations are done using the same temperature values

along the fins. To verify this, also 6 different points are placed on one of the plate

fin, which is in the left cooling channel. Detailed view of these points is shown in

Figure 4.8. As shown temperature values are very close to each other along the fin.

Figure 4.8 Control points.

Page 104: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

86

Wall temperature results are given in Table 4.2. The average temperature of the wall

is calculated as 30.2 °C using the points on the wall. In addition, mean temperature

value of the wall, shown in Figure 4.9, is 30.3 °C. In the analytical calculations 33.3

°C values is used for the wall temperature.

Table 4.2 Temperature results of points at 25 ºC operating condition (DMAP).

W-1 W-2 W-3

29.1 ºC 30.3 ºC 31.3 ºC

Average: 30.2 ºC

Figure 4.9 Wall temperature contour view of 25 ºC analyses (DMAP).

Numerical study results of 25 °C are given in Table 4.3 with the results of 25 °C

analytical studies.

Table 4.3 Results of points at 25 ºC operating condition (DMAP).

25 ºC (17 Fin)

Analytical Numerical

∆P (Pa) 69.7 76.5

Vair (m/s) 7.9 7.1

VFR (cfm) 21.9 19.5

∆T (K) 4.1 4.9

Wall Temp. (ºC) 33.3 30.3

Qcal (W) 50.4 51

Page 105: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

87

4.1.3.2 55º Operating Condition Solution of DMAP

Same analysis is done for the 55 °C operating condition and results are tabulated in

Table 4.4. In the analytical calculations 63.3 ºC average wall temperature is used for

55 ºC operating conditions. If analysis results are examined, average wall

temperature is shown as 59.9 ºC. In addition, mean temperature value of the wall,

shown in Figure 4.10, is 60 °C.

Table 4.4 Temperature results of points at 55 ºC operating condition (DMAP).

W-1 W-2 W-3

58.7 ºC 59.9 ºC 61.1 ºC

Average: 59.9 ºC

Figure 4.10 Wall temperature contour view of 55 ºC analyses (DMAP).

Numerical study results of 55 °C are given in Table 4.4 with the results of 55 °C

analytical studies.

Page 106: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

88

Table 4.5 Temperature results of points at 25 ºC operating condition (DMAP).

55 ºC (21 Fin)

Analytical Numerical

∆P (Pa) 82.3 110.4

Vair (m/s) 8.2 7.8

VFR (cfm) 21.7 21

∆T (K) 4.6 5.1

Wall Temp. (ºC) 63.3 60

Qcal (W) 50.7 51

4.2 Numerical Studies of ACCC

Same procedures of numerical studies of DMAP given in section 4.1 are followed for

the numerical studies of ACCC. The general view of the created 3D model is shown

in Figure 4.1. Similar to DMAP, to reduce the mesh size and analysis time inside the

chassis is defined as hollow block.

The fan is placed at the back cover of the chassis as in the real model. Ametek

Rotron Propimax 2 model fan is used in the design. The curve of the fan, which is

given in Appendix B, is used during the analysis.

Page 107: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

89

Figure 4.11 3D Model of ACCC.

Figure 4.12 3D Model of ACCC (continued).

Hollow Block

Air intake

Air exhaust

Cooling Channels

Plate Fins

Fans

Cabinet Boundary

Page 108: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

90

4.2.1 Boundary Conditions and Basic Parameters of ACCC

The generated cabinet dimensions are 257.8 x 192 x 380 mm in X-Y-Z directions

respectively. Air intake and exhaust sections of ACCC are at the front and back sides

as shown in Figure 4.11 and Figure 4.12. Therefore, front and back walls of the

cabinet are defined as openings; other four walls of the cabinet are adiabatic. Basic

parameters of the solution are same with the DMAP. Turbulent two-equation flow

regime is selected. Ambient temperature is defined as 25 ºC for the first simulation

and 55 ºC for the second simulation. Time variation is chosen as steady.

4.2.2 Grid Generation on ACCC

ACCC is meshed using the same mesh control parameters given in section 4.1.2.

1,727,574 number of elements are generated shown in Figure 4.13.

Figure 4.13 Meshed view of the chassis.

Page 109: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

91

4.2.3 Numerical Solution of ACCC

Same solution setting is used given in section 4.1.3. First-order discretization scheme

is selected for the temperature and momentum and by default pressure equation is

solved using the standard scheme. Under-relaxation factors and linear solver settings

are used as default. The version of the solver is selected as single precision.

Turbulent, two-equation model is used.

4.2.3.1 25 ºC Operating Condition Solution of ACCC

25 ºC analysis is preformed to verify the TMT results of 25 ºC of ACCC. Operating

condition is selected as 25 ºC. 68 W heat loads is defined on each wall as the result

of TMT solution. Analysis is completed approximately after 1000 iterations. In order

to understand if the convergence is came true; points are placed on different zones of

the chassis. The points with the name W-1, W-2 and W-3 are on the wall and the

point with the name C is in the channel.

Page 110: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

92

Figure 4.14 Wall temperature contour view of 25 ºC analyses (ACCC).

The result of the analysis is given inTable 4.6. The average temperature of the wall is

calculated as 30.0°C using the points on the wall. In addition, mean temperature

value of the wall, shown in Figure 4.14, is 30.2°C. In the analytical calculations

33.3°C values is used for the wall temperature.

Table 4.6 Temperature results of points at 25 ºC operating condition (ACCC).

W-1 W-2 W-3

28.9 ºC 30.0 ºC 31.2 ºC

Average: 30.0 ºC

Numerical study results of 25 °C are given in Table 4.7 with the results of 25 °C

analytical studies.

Page 111: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

93

Table 4.7 Temperature results of points at 25 ºC operating condition (ACCC).

25 ºC (24 Fin)

Analytical Numerical

∆P (Pa) 165.2 167

Vair (m/s) 11.1 10.8

VFR (cfm) 24.5 23.9

∆T (K) 4.9 5

Wall Temp. (ºC) 33.3 30.4

Qcal (W) 67.5 68

4.2.3.2 55 ºC Operating Condition Solution of ACCC

Same analysis is done for the 55 °C operating condition and results are tabulated in

Table 4.8. In the analytical calculations average 63.5 ºC average wall temperature is

used for 55 ºC operating conditions. If analysis results are examined, average wall

temperature is shown as 59.9 ºC. In addition, mean temperature value of the wall,

shown in Figure 4.10, is 60 °C.

Table 4.8 Temperature results of points at 55 ºC operating condition (ACCC).

W-1 W-2 W-3

58.8 ºC 59.9 ºC 61.0 ºC

59.9 ºC

Page 112: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

94

Figure 4.15 Wall temperature contour view of 55 ºC analyses (ACCC).

Numerical study results of 55 °C are given in Table 4.9 with the results of 55 °C

analytical studies.

Table 4.9 Temperature results of points at 25 ºC operating condition.

55 ºC (24 Fin)

Analytical Numerical

∆P (Pa) 160.4 167

Vair (m/s) 11.3 11.8

VFR (cfm) 25 26.2

∆T (K) 5 4.7

Wall Temp. (ºC) 63.3 60

Qcal (W) 63.5 64

Page 113: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

95

CHAPTER 5

5 DISCUSSION

The aim of this thesis is to develop a thermal model tool (TMT) for standard Avionic

Transport Rack (ATR) chassis and make the thermal design of a standard ATR

chassis Digital Moving Map (DMAP) using developed TMT.

The results of experimental studies are utilized in analytical studies by considering

mechanical and thermal limitations, subsequently TMT is developed. To double

check the accuracy of TMT, also plate fin details of the existing chassis ACCC

(Avionic Central Control Computer) is determined in analytical studies chapter. In

the next step, numerical verification of TMT is accomplished. Eventually, the

purpose of the thesis study is achieved its goal.

In this section, experimental, analytical, and numerical studies results are compared.

All these studies are done for both 25 ºC and 55 ºC operating conditions however, the

critical operating condition is 55 ºC because of cooling problems at high

temperatures. All studies are based on the critical wall temperatures determined in

experimental studies. At the 55 °C operating condition, average critical wall

temperature is measured as 63.3 °C. This temperature value is the results of

experimental studies of ACCC. When the wall temperature is approximately 63.3 °C

at 55 °C operating condition, junction temperatures of the CPUs are in the safe

operation range. However, if the wall temperature exceeds 63.3 °C, the junction

temperatures of the CPUs are over the safe operating temperature range. Therefore,

in all studies for the operating condition 55 °C, 63.3 °C critical wall temperature is

Page 114: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

96

considered. Besides this, average wall temperature is known for 25 °C operating

condition and this is used in order to double check the TMT.

The summary of the experimental studies are given in Table 5.1. Average wall

temperatures are calculated 33.3°C and 63.3°C for the 25 °C and 55 °C operating

conditions respectively.

Table 5.1 Results of experimental studies.

Operating Condition

Slot1 Slot2 Slot3 Slot4 Slot5 Slot6 Slot7 Slot10 Slot11 Average

Steady State Temperatures [°C]

25 33.7 36.6 34.7 34.6 33.8 32.7 31.8 30.8 30.7 33.3

55 63.6 66.7 64.7 64.7 63.7 62.6 61.8 61.0 60.5 63.3

The summary of the analytical and numerical studies is given in Table 5.2 and Table

5.3 for DMAP and ACCC respectively. Calculations are done for both 25 °C and 55

°C operating conditions using TMT.

Table 5.2 Analytical and numerical results of DMAP.

DMAP

25 ºC (17 Fin) 55 ºC (21 Fin)

Analytical Numerical Analytical Numerical

∆P (Pa) 69.7 78.8 82.3 110.4

Vair (m/s) 7.9 7.1 8.2 7.8

VFR (cfm) 21.9 20 21.7 21

∆T (K) 4.1 4.9 4.6 5.1

Wall Temp. (ºC) 33.3 30.3 63.3 60

Qcal (W) 50.4 51 50.7 51

Page 115: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

97

Table 5.3 Analytical and numerical studies results of ACCC.

ACCC

25 ºC (24 Fin) 55 ºC (24 Fin)

Analytical Numerical Analytical Numerical

∆P (Pa) 165.2 167 160.4 167

Vair (m/s) 11.1 10.8 11.3 11.8

VFR (cfm) 24.5 23.9 25 26.2

∆T (K) 4.9 5 5 4.7

Wall Temp. (ºC) 33.3 30.4 63.3 60

Qcal (W) 67.5 68 63.5 64

Four different case studies are conducted both analytically and numerically. It is

observed that the results are close. The generated TMT is verified numerically both

for DMAP and ACCC. In the next designs, the results of this thesis will be used and

without doing long-term numerical analysis, effective plate fin number will be

determined. By using generated tables for different operating conditions, heat

dissipation capacities of similar size chassis will be determined easily. In addition, by

using the TMT, heat dissipation capacities of different size chassis will be

determined without numerical studies in great detail.

Plate fin numbers are selected for the worst-case 55 °C operating conditions for the

new design chassis DMAP. As shown in Table 5.2, 21 plate fins are sufficient for the

cooling channels to dissipate 50 W heat load via each channel.

In this study;

• Uniform heat distribution on the chassis wall is assumed and only one

thermocouple is placed on each slot.

• Fin temperature is assumed same along the fins.

Page 116: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

98

• Symmetry condition is assumed between left and right walls of the chassis.

In the future work;

• Heat distribution maps on the walls can be generated by using a thermal

camera.

• Differences between cooling channels can be determined and numbers of

each cooling channel can be calculated separately.

Page 117: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

99

REFERENCES

[1] Aeronautical Radio, Inc., 1974, “Air Transport Equipment Cases and

Racking,” ARINC 404A.

[2] Macrolink Inc., http://www.macrolink.com/CHASSIS/ATR/ml750t.htm, last

visited on April 2011.

[3] CM Computer, http://www.cmcomputer.com/light/files/pdf/CM-ATRX5-

DataSheet .pdf, last visited on April 2011.

[4] APLabs,

http://www.aplabs.com/products/5971_half%20atr_conduction_cooled_chas

sis.html, last visited on April 2011.

[5] Interfacebus, http://www.interfacebus.com/ieee1101-euro-cardmechanical-

standard. html, last visited on April 2011.

[6] Cengel, Y.A., Heat Transfer: A Practical Approach, 2nd ed., McGraw-Hill,

2003, Chap. 8.

[7] Department of Defense Test Method Standard, “Environmental Engineering

Considerations and Laboratory Tests,” MIL-STD-810F, 2003.

[8] Debentli, T., Ed., Isı ve Kütle Geçişinin Temelleri, Beyoğlu, Istanbul, 2001,

Bölüm 8.

[9] VanEngelenhoven, J, Solbrekken, G. L., and Geisler, K. J. L., “Thermal

Performance Maps for Forced Air Cooling of Ruggedized Electronics

Page 118: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

100

Enclosures”, IPACK2007-33641, Vancouver, British Columbia, Canada,

2007.

[10] Iyengar, M., “Resource Constrainted Heat Sink Optimization”, Ph.D. thesis,

University of Minnesota, 2003.

[11] Iyengar M., and Bar-Cohen A., “Design for Manufacturability of SISE

Parallel Plate Forced Convection Heat Sinks”, Fellow, IEEE, Vol. 24, No. 2,

June 2001.

[12] Ametek Inc., www.ametek.com, last visited on April 2011.

[13] The Institute of Electrical and Electronics Engineers, “IEEE Standard for

Mechanical Core Specifications for Conduction-Cooled Eurocards," New

York, 2001.

[14] Muzychka, Y. S., and Yovanovich, M.M. “Laminar Forced Convection Heat

Transfer in the Combined Entry Region of Non-Circular Ducts,” Journal of

Heat Transfer, vol.126, pp. 54-61, 2004.

[15] Copeland, D., “Optimization of Parallel Plate Heatsinks for Forced

Convection,” Sizteenth IEEE Semi-Therm Symposium, pp. 266-272, 2000.

[16] Lee, S., “Optimum Design and Selection of Heat Sinks”, Eleventh IEEE

Semi-Therm Symposium, pp. 48-54, 1995.

[17] Bar-Cohen, A., and Iyengar, M., “Design and Optimization of Air-Cooled

Heat Sinks for Sustainable Development”, IEEE Transactions on

Components and Packaging Technologies, vol. 25, no. 4, 2002.

Page 119: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

101

[18] Omega Engineering, “SA1XL Series Surface Thermocouples Specs”,

http://www.omega.co.uk/Temperature/pdf/SA1XL.pdf , last visited on June

2011.

[19] Ocak, M., “Conduction Based Compact Thermal Modeling for Thermal

Analysis of Electronic Components”, M.Sc. Thesis, METU, Ankara, June

2010.

[20] Wu H., Hsiao Y., Huang H., Tang P., Chen S., “A Practical Plate-Fin Heat

Sink Model”, Applied Thermal Engineering 31, pp. 984-992, 2011.

[21] Modest M. F., “Radiative Heat Transfer,” 2nd Edition, Academic Press, 2003.

[22] ANSYS ICEPAK 12.0 User’s Guide, Fluent Inc., 2009.

[23] Elma Electronics, http://pdf.directindustry.com/pdf/elma-electronic/cots-

catalogue/6089-1720-_29.html, last visited on April 2011.

[24] Leon, O., Mey, G. D.,Dick, E., “Study of the optimal layout of cooling fins in

forced convection cooling”, Microelectronics Reliability 42, pp. 1101–1111,

2002.

[25] Fowler, A. J., Ledezma, G. A., and BEJAN, A., “Optimal geometric

arrangement of staggered plates in forced convection”, Int. J. Heat Mass

TransJer., vol. 40, no. 8, pp. 1795-1805, 1997.

[26] Jouhara, H., Axcell, B.P., “Modelling and simulation techniques for forced

convection heat transfer in heat sinks with rectangular fins”, Simulation

Modelling Practice and Theory 17, pp. 871–882, 2009.

Page 120: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

102

APPENDIX A

APENDICES

A. COOLING CHANNEL DIMENSIONS OF DMAP

Figure A.1 Front section view of cooling channels.

Page 121: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

103

Figure A.2 Side view of cooling channel.

Page 122: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

104

APPENDIX B

B. FAN PERFORMANCE CURVE AND DIMENSIONS

Figure B.1 Fan performance curve of Aximax 2.

Page 123: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

105

Figure B.2 Dimensions of Aximax 2.

Page 124: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

106

Figure B.3 Fan performance curve of Propimax 2.

Page 125: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

107

Figure B.4 Dimensions of Propimax 2.

Page 126: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

108

APPENDIX C

C.MATHCAD CODE FOR FIN OPTIMIZATION

n 1 50..:=

CP.air 1007J

kg K⋅:=

ρair 1.1707kg

m3

:=

µair 1.836105−

⋅kg

m s⋅:=

kal 151W

m K⋅:=

kair 0.0261W

m K⋅:=

Pr 0.708:=

L 0.3 m⋅:= Channel lenth

w 0.01m:= Channel width

H 0.158m:= Channel height

b 0.0016m⋅:= Fin thickness

an

H n b⋅−

n 1+:= Distance between two fins

Pn

w an

+( ) 2⋅:= Channel perimeter

Palln

n 1+( ) Pn

⋅:= All channel perimeter

Palln

n 1+( ) Pn

⋅:= All channel perimeter

Aalln

Palln

L⋅:= Total convection surface area

Page 127: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

109

DHn

4As

n

Pn

⋅:=

Asn

w an

⋅:= Channel flow section area

Asalln

Asn

n 1+( )⋅:= All channel flow section area

pn

an

b+:=

Kcn0.8 0.4

an

pn

2

−:=

Ken1

an

pn

2

0.4an

pn

−:=

Page 128: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

110

Hizn

Vairi 0.1m

s←

Rein

ρair Vairi⋅ DHn

µair←

fn

0.0962 Rein( )

0.2−⋅

L

DHn

0.175−

∆Pn

4 fn

⋅L

DHn

⋅ Kcn+ Ken

+

1

2⋅ ρair⋅ Vairi( )

2⋅

1

Pa←

∆Ptn

260 ∆Pn

+←

VFRairn

7− 1014−

⋅ ∆Ptn( )

4⋅ 6 10

11−⋅ ∆Pt

n( )3

⋅+ 2 108−

⋅ ∆Ptn( )

2⋅− 4 10

6−⋅ ∆Pt

n⋅− 0.0125+

m3

s←

Vairn

VFRairn

Asalln

Vairi Vairi 0.001m

s+←

Rein

ρair Vairi⋅ DHn

µair←

fn

0.0962 Rein( )

0.2−⋅

L

DHn

0.175−

∆Pn

4 fn

⋅L

DHn

⋅ Kcn+ Ken

+

1

2⋅ ρair⋅ Vairi( )

2⋅

1

Pa←

∆Ptn

260 ∆Pn

+←

VFRairn

7− 1014−

⋅ ∆Ptn( )

4⋅ 6 10

11−⋅ ∆Pt

n( )3

⋅+ 2 108−

⋅ ∆Ptn( )

2⋅− 4 10

6−⋅ ∆Pt

n⋅− 0.0125+

m3

s←

Vairn

VFRairn

Asalln

Vairi Vairn

− 0.01m

s>while

Vairi

:=

Page 129: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

111

Vair Hiz:=

Ren

ρair Vairn

⋅ DHn

µair:=

fn

0.0962 Ren( )

0.2−⋅

L

DHn

0.175−

:=

∆Pn

4 fn

⋅L

DHn

⋅ Kcn+ Ken

+

1

2⋅ ρair⋅ Vair

n( )2

1

Pa:=

VFRairn

Vairn

Asalln

⋅:=

MFRairn

VFRairn

ρair⋅:=

ffn

1

1.82 log Ren( )⋅ 1.64−( )

2:=

nun

ffn

8

Ren

1000−( )⋅ Pr⋅

1 12.7ff

n

8

0.5

⋅ Pr

2

31−

⋅+

:=

hn

kair

DHn

nun

⋅:=

men

hn

2⋅ b L+( )

kal b L⋅( )⋅

1

2

:=

ηfn

tanh men

w⋅( )me

n( ) w⋅:=

Af w L⋅ 2⋅:=

Page 130: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

112

ηon

1n 1+( ) Af⋅

Aalln

1 ηfn

−( )⋅−:=

Tw 306.5K:=

Ti 298K:=

DeltaTn

tt 0.1K←

Ten298K tt+←

∆T enTw Ten

−←

∆T i Tw Ti−←

∆T lnn

∆T en∆T i−

ln

∆T en

∆T i

Qcaln

ηon

hn

Aalln

⋅ ∆T lnn⋅

⋅←

∆Tnn

Qcaln

MFRairn

CP.air⋅←

tt tt 0.01K+←

Ten298K tt+←

∆T enTw Ten

−←

∆T i Tw Ti−←

∆T lnn

∆T en∆T i−

ln

∆T en

∆T i

Qcaln

ηon

hn

Aalln

⋅ ∆T lnn⋅

⋅←

∆Tnn

Qcaln

MFRairn

CP.air⋅←

∆Tnn

tt− 0.05K>while

tt

:=

Page 131: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

113

Ten298K DeltaT

n+:=

Qcapatn

MFRairn

CP.air⋅ TenTi−

⋅:=

0 2.5 5 7.5 10 12.5 15 17.5 20 22.5 25 27.5 30 32.5 35 37.5 40 42.5 45 47.5 5020

25

30

35

40

45

50

55

60

65

70

Qcapatn

n

Page 132: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

114

APPENDIX D

D. ANALYTICAL RESULTS

25 ºC ANALYTICAL RESULTS

a ∆P V VFR Re Fin

Number [mm] [Pa] [m/s] [CFM] [-]

10 12.9 44.0 7.4 22.3 5.3E+03

11 11.7 47.3 7.5 22.2 5.1E+03

12 10.7 50.7 7.5 22.2 5.0E+03

13 9.8 54.2 7.6 22.1 4.8E+03

14 9.0 57.8 7.7 22.1 4.6E+03

15 8.4 61.6 7.7 22.0 4.5E+03

16 7.8 65.6 7.8 21.9 4.4E+03

17 7.3 69.7 7.9 21.9 4.2E+03

18 6.8 74.0 8.0 21.8 4.1E+03

19 6.4 78.4 8.0 21.7 4.0E+03

20 6.0 83.0 8.1 21.6 3.9E+03

21 5.7 87.8 8.2 21.6 3.8E+03

22 5.3 92.8 8.3 21.5 3.7E+03

23 5.1 98.0 8.3 21.4 3.6E+03

24 4.8 103.4 8.4 21.3 3.5E+03

25 4.5 108.9 8.5 21.2 3.4E+03

26 4.3 114.7 8.6 21.1 3.3E+03

27 4.1 120.7 8.6 21.0 3.2E+03

28 3.9 127.0 8.7 20.9 3.1E+03

29 3.7 133.4 8.8 20.8 3.0E+03

30 3.5 140.1 8.9 20.6 3.0E+03

31 3.4 147.0 8.9 20.5 2.9E+03

32 3.2 154.1 9.0 20.4 2.8E+03

33 3.1 161.4 9.1 20.2 2.7E+03

34 3.0 168.9 9.1 20.0 2.7E+03

35 2.8 176.6 9.2 19.9 2.6E+03

36 2.7 184.6 9.3 19.7 2.5E+03

37 2.6 192.7 9.3 19.5 2.5E+03

38 2.5 200.9 9.4 19.3 2.4E+03

39 2.4 209.4 9.4 19.1 2.3E+03

40 2.3 217.9 9.5 18.9 2.3E+03

Page 133: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

115

Nu h ∆T ƞo Qcal Fin

Number [-] [W/m2K] [K] [-] [W]

10 17.6 40.8 3.3 0.9951 40.8

11 17.1 41.3 3.4 0.9948 42.2

12 16.6 41.9 3.5 0.9945 43.7

13 16.1 42.4 3.7 0.9941 45.0

14 15.6 42.9 3.8 0.9938 46.4

15 15.1 43.4 3.9 0.9935 47.7

16 14.7 43.8 4.0 0.9933 49.0

17 14.3 44.3 4.1 0.9930 50.4

18 13.9 44.8 4.3 0.9927 51.7

19 13.5 45.2 4.4 0.9925 52.8

20 13.1 45.7 4.5 0.9922 54.1

21 12.8 46.1 4.6 0.9920 55.2

22 12.4 46.5 4.7 0.9917 56.4

23 12.1 46.9 4.8 0.9915 57.5

24 11.7 47.3 4.9 0.9913 58.5

25 11.4 47.6 5.1 0.9911 59.6

26 11.1 48.0 5.2 0.9908 60.5

27 10.8 48.3 5.3 0.9906 61.4

28 10.5 48.6 5.4 0.9905 62.3

29 10.2 48.9 5.5 0.9903 63.1

30 9.9 49.1 5.6 0.9901 63.8

31 9.6 49.4 5.7 0.9899 64.4

32 9.3 49.5 5.8 0.9898 65.1

33 9.0 49.7 5.8 0.9896 65.6

34 8.7 49.8 5.9 0.9895 66.0

35 8.4 49.8 6.0 0.9894 66.5

36 8.2 49.8 6.1 0.9893 66.7

37 7.9 49.8 6.2 0.9892 67.0

38 7.6 49.7 6.3 0.9892 67.1

39 7.3 49.5 6.3 0.9891 67.2

40 7.0 49.2 6.4 0.9891 67.1

Page 134: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

116

55 ºC ANALYTICAL RESULTS

a ∆P V VFR Re Fin

Number [mm] [Pa] [m/s] [CFM] [-]

10 12.9 41.3 7.4 22.3 4.5E+03

11 11.7 44.4 7.5 22.3 4.4E+03

12 10.7 47.6 7.6 22.2 4.2E+03

13 9.8 50.9 7.6 22.2 4.1E+03

14 9.0 54.3 7.7 22.1 3.9E+03

15 8.4 57.9 7.8 22.1 3.8E+03

16 7.8 61.6 7.8 22.0 3.7E+03

17 7.3 65.5 7.9 21.9 3.6E+03

18 6.8 69.5 8.0 21.9 3.5E+03

19 6.4 73.7 8.1 21.8 3.4E+03

20 6.0 78.1 8.1 21.7 3.3E+03

21 5.7 82.7 8.2 21.7 3.2E+03

22 5.3 87.4 8.3 21.6 3.1E+03

23 5.1 92.3 8.4 21.5 3.0E+03

24 4.8 97.5 8.4 21.4 3.0E+03

25 4.5 102.8 8.5 21.3 2.9E+03

26 4.3 108.3 8.6 21.2 2.8E+03

27 4.1 114.0 8.7 21.1 2.7E+03

28 3.9 120.0 8.8 21.0 2.7E+03

29 3.7 126.2 8.8 20.9 2.6E+03

30 3.5 132.6 8.9 20.8 2.5E+03

31 3.4 139.2 9.0 20.6 2.5E+03

32 3.2 146.1 9.1 20.5 2.4E+03

33 3.1 153.2 9.1 20.4 2.3E+03

34 3.0 160.5 9.2 20.2 2.3E+03

35 2.8 168.0 9.3 20.1 2.2E+03

36 2.7 175.8 9.4 19.9 2.2E+03

37 2.6 183.7 9.4 19.7 2.1E+03

38 2.5 191.9 9.5 19.5 2.0E+03

39 2.4 200.2 9.5 19.3 2.0E+03

40 2.3 208.7 9.6 19.1 1.9E+03

Page 135: CORRELATION BASED THERMAL DESIGN OF AIR TRANSPORT

117

Nu h ∆T ƞo Qcal Fin

Number [-] [W/m2K] [K] [-] [W]

10 15.1 38.1 3.3 0.9954 37.9

11 14.6 38.6 3.5 0.9951 39.2

12 14.2 39.0 3.6 0.9948 40.4

13 13.7 39.4 3.7 0.9945 41.7

14 13.3 39.8 3.8 0.9943 42.9

15 12.9 40.2 3.9 0.9940 44.2

16 12.5 40.6 4.1 0.9938 45.3

17 12.1 40.9 4.2 0.9935 46.5

18 11.8 41.3 4.3 0.9933 47.6

19 11.4 41.6 4.4 0.9930 48.6

20 11.1 42.0 4.5 0.9928 49.7

21 10.8 42.3 4.6 0.9926 50.7

22 10.4 42.6 4.7 0.9924 51.6

23 10.1 42.8 4.8 0.9922 52.6

24 9.8 43.1 4.9 0.9920 53.5

25 9.5 43.3 5.0 0.9918 54.4

26 9.2 43.5 5.1 0.9917 55.2

27 9.0 43.7 5.2 0.9915 55.9

28 8.7 43.9 5.3 0.9914 56.6

29 8.4 44.0 5.4 0.9912 57.2

30 8.1 44.1 5.5 0.9911 57.9

31 7.9 44.2 5.6 0.9910 58.5

32 7.6 44.2 5.7 0.9909 58.9

33 7.3 44.2 5.7 0.9908 59.3

34 7.1 44.1 5.8 0.9907 59.6

35 6.8 44.0 5.9 0.9906 60.0

36 6.6 43.8 6.0 0.9906 60.2

37 6.3 43.5 6.0 0.9906 60.2

38 6.1 43.2 6.1 0.9905 60.3

39 5.8 42.8 6.1 0.9906 60.1

40 5.6 42.3 6.2 0.9906 60.0