CIGRE WG A3.07
CONTROLLED SWITCHING
CIRCUIT BREAKER CONSIDERATIONS
Victor F. HermosilloALSTOM T&D
Seminar/Workshop on Controlled SwitchingCIGRE WG A3.07
IEEE/PES Switchgear Committee MeetingSt. Pete Beach, Florida
May 2003
![Page 2: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/2.jpg)
�
CIGRE WG A3.07
Circuit Breaker Considerations
� Circuit breaker characteristics� Interrupter wear� Life extension, maintenance intervals� Circuit breaker performance� Benefits for switched equipment� Benefits for the power system & equipment� Conclusions
OUTLINE
![Page 3: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/3.jpg)
�
CIGRE WG A3.07
Circuit Breaker Characteristics
Independent-Pole Operated
![Page 4: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/4.jpg)
�
CIGRE WG A3.07
Independent-Pole Operated
![Page 5: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/5.jpg)
�
CIGRE WG A3.07
Mechanically-Staggered Linkage
Circuit Breaker Characteristics
![Page 6: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/6.jpg)
�
CIGRE WG A3.07
Mechanically-Staggered Linkage
![Page 7: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/7.jpg)
�
CIGRE WG A3.07
Spring Mechanism
![Page 8: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/8.jpg)
�
CIGRE WG A3.07
Hydraulic Mechanism
![Page 9: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/9.jpg)
�
CIGRE WG A3.07
� Effect of idle time� Influence of ambient temperature on operating time� Hydraulic pressure - Spring constant
-1
0
1
2
3
0.1 1 10 100 1000
idle time (hrs)
clos
ing
time
varia
tion
(ms)
HydraulicMechanism
SpringMechanism
Timing Characteristics
![Page 10: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/10.jpg)
�
CIGRE WG A3.07
0 30 60 90 120 150 180 210 240 270 300 330 3600,0
0,2
0,4
0,6
0,8
1,0
T Target Target Pointnominal instant of contact touch
Volta
ge a
cros
s cir
cuit-b
rake
r (ab
solut
e va
lue) [
pu]
�t making
k + k0 �
k - k0 �
Controlled Closing - RDDS
![Page 11: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/11.jpg)
�
CIGRE WG A3.07
Live-Tank Circuit Breaker
![Page 12: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/12.jpg)
�
CIGRE WG A3.07
Field Simulation
15 mm and 4.0 msfrom contact touch
02040
6080
100120140
160180200
0.000 0.004 0.008 0.012 0.016
0
5
10
15
20
25
30
35
40
0 5 10 15 20 25 30 35 40
d (mm)
E (k
V/m
m)
Controlled Closing - RDDS
Emax
![Page 13: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/13.jpg)
�
CIGRE WG A3.07
Benefits for the Circuit Breaker
� Extension of circuit breaker life,
� Increase in time intervals between interruptermaintenance or retrofit,
� Added value associated with circuit breakerperformance enhancement during currentinterruption in the thermal or in the dielectricregion.
![Page 14: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/14.jpg)
�
CIGRE WG A3.07
Interrupter Wear
![Page 15: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/15.jpg)
�
CIGRE WG A3.07
Interrupter Wear
Benefits of controlled switching for the purposesof life extension, reduction of maintenance cost:
� Decrease in magnitude of energization currents.
� Reduce associated interrupter wear.
� Lower probability of occurrence of damagingrestrikes.
![Page 16: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/16.jpg)
�
CIGRE WG A3.07
Interrupter Wear
� Arcing contact wear
– Source is burning arc across the gap.
– Loss of material caused by vaporization, melting andburnoff.
– Consequences are contact shape distortion andincrease in surface roughness.
![Page 17: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/17.jpg)
�
CIGRE WG A3.07
Electrical Wear of an Interrupter
� Depends on:– contact material composition
and micro-structure– contact surface porosity– initial contact shape– manufacturing process– arc current duration,
amplitude, shape� Implications
– erosion, burnoff, vaporization– change in shape, surface
Arcing Contact Wear
![Page 18: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/18.jpg)
�
CIGRE WG A3.07
� Depends on:– nozzle geometry– material (teflon) and fillers
� Implications:– increase in diameter of throat– flake-off, erosion, vaporization of
inside surface– changes to the dynamic gas flow
during interruption– degradation of breaker
performance (thermal region)
Teflon Nozzle Ablation
Electrical Wear of an Interrupter
![Page 19: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/19.jpg)
�
CIGRE WG A3.07
Interrupter Wear
� Definition of maintenanceinterval
� Number of allowableoperations betweenmaintenance/refurbishment
� Simple relation between theinterrupted current and amaximum number ofoperations
![Page 20: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/20.jpg)
�
CIGRE WG A3.07
Improved Assessment of Interrupter Wear
� Separate limits forarcing contact wearand nozzle ablation
� Specific to interrupterdesign
� Can be implementedtogether withelectronic monitoring
![Page 21: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/21.jpg)
�
CIGRE WG A3.07
Maintenance Intervals and Costs
![Page 22: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/22.jpg)
�
CIGRE WG A3.07
Circuit Breaker Performance Enhancement
� Improve performance during interruption– Thermal region of interruption– Dielectric region of interruption
� Increase or decrease arcing time– Life extension– Unusual system voltages (25 Hz rail system)– Higher X/R ratios– Further reduce restrike probability for severe TRV
applications
![Page 23: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/23.jpg)
�
CIGRE WG A3.07
Thermal (Energy Balance) Region
• Rate of Rise of Recovery Voltage (RRRV)• Initial Transient Recovery Voltage (ITRV)• Reignition if current re-established <1/4 cycle
successful interruption failure (reignition)
ETRVETRV
Circuit Breaker Performance Enhancement
ifault
vTRV
![Page 24: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/24.jpg)
�
CIGRE WG A3.07
Circuit Breaker Performance Enhancement
![Page 25: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/25.jpg)
�
CIGRE WG A3.07
Dielectric Region
• Peak value of the transient recovery voltage• Restrike if current re-established >1/4 cycle
successful interruption failure (restrike)
ETRV ETRV
Circuit Breaker Performance Enhancement
ifault
vTRV
![Page 26: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/26.jpg)
�
CIGRE WG A3.07
Circuit Breaker Performance Enhancement
Contact CoordinationVoltage Gradients on Interrupter Components
E1E3
E5
E4E2
E6
stationary side -0.5 pu
moving side +0.5 pu
Contact coordination HGF1014/63 kA
02468
101214161820
0 20 40 60 80 100 120 140
gap (mm)
E (%
/mm
)
E1
E2
E3
E4
E5
E6
![Page 27: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/27.jpg)
�
CIGRE WG A3.07
Circuit Breaker Performance Enhancement
![Page 28: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/28.jpg)
�
CIGRE WG A3.07
Circuit Breaker Performance Enhancement
![Page 29: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/29.jpg)
�
CIGRE WG A3.07
Circuit Breaker Performance Enhancement
![Page 30: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/30.jpg)
�
CIGRE WG A3.07
Benefits for Power System and Equipment
![Page 31: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/31.jpg)
�
CIGRE WG A3.07
Benefits for Power System and Equipment
![Page 32: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/32.jpg)
�
CIGRE WG A3.07
� Technical and economic benefits– reduction of stresses on switched equipment leading to
life extension,– control of local transients in the substation,– local surge supression, reducing possible coupling to
the control and protection scheme,– decrease in the severity of remote transients and their
effects on sensitive loads.
Benefits for Power System and Equipment
![Page 33: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/33.jpg)
�
CIGRE WG A3.07
Benefits for Power System and Equipment
![Page 34: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/34.jpg)
�
CIGRE WG A3.07
� Suceptibility– Compromise of system of equipment function– Frequency dependent
� Mechanism– Coupling
• conductive, inductive, radiative– Modes
• common mode, differential mode
Benefits for Power System and Equipment
![Page 35: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/35.jpg)
�
CIGRE WG A3.07
� Conclusions– Effective means of reducing switching transients and
their effects on a power system and equipment• life extension• reduction of maintenance costs• system reliability• power quality
– Enhancement of circuit breaker performance– Alternative to tradition means of transient control
Benefits of Controlled Switching
![Page 36: CONTROLLED SWITCHING CIRCUIT BREAKER CONSIDERATIONS · 2014. 1. 14. · ALSTOM T&D Seminar/Workshop on Controlled Switching CIGRE WG A3.07 IEEE/PES Switchgear Committee Meeting](https://reader035.vdocuments.us/reader035/viewer/2022081618/60abde86e73b9d321c4aada1/html5/thumbnails/36.jpg)
�
CIGRE WG A3.07
� Conclusions– Assessment depends on conditions:
• new or existing installation• planned or unplanned effects
– Driver may be:• desire to acquire experience• problem solving• preventive or corrective
– Can be used in combination with other means oftransient control
Benefits of Controlled Switching