Control House and Relay Design Considerations for EMP Resiliency
Roy Mao, Harsh Vardhan – GE Grid Solutions
Aaron Ingham, Barry Howe, Sarah Pink – Trachte
Curtis Birnbach – Advanced Fusion Systems LLC
Mark Adamiak – Adamiak Consulting LLC
2019 Texas A&M Protective Relaying Conference
![Page 2: Control House and Relay Design Considerations for EMP ...prorelay.tamu.edu/.../sites/3/2019/03/Control-House...Control House and Relay Design Considerations for EMP Resiliency Roy](https://reader033.vdocuments.us/reader033/viewer/2022050215/5f60fcc801f7301bf279046c/html5/thumbnails/2.jpg)
Electro Magnetic Pulse - EMP
Classification of wave into 3 time frames
![Page 3: Control House and Relay Design Considerations for EMP ...prorelay.tamu.edu/.../sites/3/2019/03/Control-House...Control House and Relay Design Considerations for EMP Resiliency Roy](https://reader033.vdocuments.us/reader033/viewer/2022050215/5f60fcc801f7301bf279046c/html5/thumbnails/3.jpg)
EMP E1 Pulse Shape – Rise Time ≈ 1 nsec
![Page 4: Control House and Relay Design Considerations for EMP ...prorelay.tamu.edu/.../sites/3/2019/03/Control-House...Control House and Relay Design Considerations for EMP Resiliency Roy](https://reader033.vdocuments.us/reader033/viewer/2022050215/5f60fcc801f7301bf279046c/html5/thumbnails/4.jpg)
Man-Made EMP Pulse Shape – Before tuning
Time Scale: 10 nsec/div
![Page 5: Control House and Relay Design Considerations for EMP ...prorelay.tamu.edu/.../sites/3/2019/03/Control-House...Control House and Relay Design Considerations for EMP Resiliency Roy](https://reader033.vdocuments.us/reader033/viewer/2022050215/5f60fcc801f7301bf279046c/html5/thumbnails/5.jpg)
Conducted EMP Path: CCVT
![Page 6: Control House and Relay Design Considerations for EMP ...prorelay.tamu.edu/.../sites/3/2019/03/Control-House...Control House and Relay Design Considerations for EMP Resiliency Roy](https://reader033.vdocuments.us/reader033/viewer/2022050215/5f60fcc801f7301bf279046c/html5/thumbnails/6.jpg)
CCVT Frequency Response Plot
0.00001
0.0001
0.001
0.01
0.1
1
1 10 100 1000 10000
FrequencyG
ain
(P
U)
One Source Of Conducted EMP – With Attenuation…
![Page 7: Control House and Relay Design Considerations for EMP ...prorelay.tamu.edu/.../sites/3/2019/03/Control-House...Control House and Relay Design Considerations for EMP Resiliency Roy](https://reader033.vdocuments.us/reader033/viewer/2022050215/5f60fcc801f7301bf279046c/html5/thumbnails/7.jpg)
Conducted EMP Mitigation: Optical Sensing
Faraday Current Sensor
Pockels Voltage Sensor
Provides Complete Electrical Isolation from Conducted EMP
![Page 8: Control House and Relay Design Considerations for EMP ...prorelay.tamu.edu/.../sites/3/2019/03/Control-House...Control House and Relay Design Considerations for EMP Resiliency Roy](https://reader033.vdocuments.us/reader033/viewer/2022050215/5f60fcc801f7301bf279046c/html5/thumbnails/8.jpg)
![Page 9: Control House and Relay Design Considerations for EMP ...prorelay.tamu.edu/.../sites/3/2019/03/Control-House...Control House and Relay Design Considerations for EMP Resiliency Roy](https://reader033.vdocuments.us/reader033/viewer/2022050215/5f60fcc801f7301bf279046c/html5/thumbnails/9.jpg)
DHS Goals to Address EMP and GMD Events
• GOAL 1: Improve risk awareness of electromagnetic threats and hazards
• GOAL 2: Enhance capabilities to protect critical infrastructure from the impact of an electromagnetic incident (including new technology)
• GOAL 3: Promote effective electromagnetic-incident response and recovery efforts
![Page 10: Control House and Relay Design Considerations for EMP ...prorelay.tamu.edu/.../sites/3/2019/03/Control-House...Control House and Relay Design Considerations for EMP Resiliency Roy](https://reader033.vdocuments.us/reader033/viewer/2022050215/5f60fcc801f7301bf279046c/html5/thumbnails/10.jpg)
“Best” EMP-Resistant Design Practices: Grounding
• Low impedance ground conductors are essential• 6 inch wide by 0.08” copper is a good size for facility
grounds• Sub-surface ground systems should be low impedance
mesh of welded copper straps rather than a single heavy round wire at the perimeter of the protected area
• Round wire grounds should be avoided at all costs. They are inherently high impedance and reflect fast pulses rather than passing them to ground.
• All cable shields must be grounded at Point of Entry (POE)
![Page 11: Control House and Relay Design Considerations for EMP ...prorelay.tamu.edu/.../sites/3/2019/03/Control-House...Control House and Relay Design Considerations for EMP Resiliency Roy](https://reader033.vdocuments.us/reader033/viewer/2022050215/5f60fcc801f7301bf279046c/html5/thumbnails/11.jpg)
“Best” EMP-Resistant Design Practices: Buildings
• Conductors and buildings should be shielded with solid metal which covers all surfaces • Best performance: Seams/joints welded or soldered
• All cable entries must use proper shielding and bypass techniques• Waveguide style cable Points of Entry (POE) are essential • Cable shields need to be grounded to the exterior of the
waveguide POE• Doors must have a continuous electrical contact around
their perimeter when closed• Battery banks should be inside the shielded buildings, and
include shielded vent for hydrogen venting
![Page 12: Control House and Relay Design Considerations for EMP ...prorelay.tamu.edu/.../sites/3/2019/03/Control-House...Control House and Relay Design Considerations for EMP Resiliency Roy](https://reader033.vdocuments.us/reader033/viewer/2022050215/5f60fcc801f7301bf279046c/html5/thumbnails/12.jpg)
“Best” IED Design Practices
• Metal shielding on IED modules and chassis
• Use of copper strap/braiddue for lower inductance ground
• Use of Hardware Watchdog Timers
• Use of Error Correcting Code (ECC) Memory
• Use of Transient Voltage Suppression (TVS) Diodes
![Page 13: Control House and Relay Design Considerations for EMP ...prorelay.tamu.edu/.../sites/3/2019/03/Control-House...Control House and Relay Design Considerations for EMP Resiliency Roy](https://reader033.vdocuments.us/reader033/viewer/2022050215/5f60fcc801f7301bf279046c/html5/thumbnails/13.jpg)
Overall Control House View
Corner joints are electrically bonded by continuous, mechanically-fastened, conductive brackets
![Page 14: Control House and Relay Design Considerations for EMP ...prorelay.tamu.edu/.../sites/3/2019/03/Control-House...Control House and Relay Design Considerations for EMP Resiliency Roy](https://reader033.vdocuments.us/reader033/viewer/2022050215/5f60fcc801f7301bf279046c/html5/thumbnails/14.jpg)
“Sealed” Door Design
![Page 15: Control House and Relay Design Considerations for EMP ...prorelay.tamu.edu/.../sites/3/2019/03/Control-House...Control House and Relay Design Considerations for EMP Resiliency Roy](https://reader033.vdocuments.us/reader033/viewer/2022050215/5f60fcc801f7301bf279046c/html5/thumbnails/15.jpg)
Air Exchange Design
![Page 16: Control House and Relay Design Considerations for EMP ...prorelay.tamu.edu/.../sites/3/2019/03/Control-House...Control House and Relay Design Considerations for EMP Resiliency Roy](https://reader033.vdocuments.us/reader033/viewer/2022050215/5f60fcc801f7301bf279046c/html5/thumbnails/16.jpg)
Cable Entry/Exit System
![Page 17: Control House and Relay Design Considerations for EMP ...prorelay.tamu.edu/.../sites/3/2019/03/Control-House...Control House and Relay Design Considerations for EMP Resiliency Roy](https://reader033.vdocuments.us/reader033/viewer/2022050215/5f60fcc801f7301bf279046c/html5/thumbnails/17.jpg)
Cable Entry/Exit System via Wavequide
![Page 18: Control House and Relay Design Considerations for EMP ...prorelay.tamu.edu/.../sites/3/2019/03/Control-House...Control House and Relay Design Considerations for EMP Resiliency Roy](https://reader033.vdocuments.us/reader033/viewer/2022050215/5f60fcc801f7301bf279046c/html5/thumbnails/18.jpg)
Test Chamber with Test Generator and Control House
Radiating antenna
E/B FieldSensors
![Page 19: Control House and Relay Design Considerations for EMP ...prorelay.tamu.edu/.../sites/3/2019/03/Control-House...Control House and Relay Design Considerations for EMP Resiliency Roy](https://reader033.vdocuments.us/reader033/viewer/2022050215/5f60fcc801f7301bf279046c/html5/thumbnails/19.jpg)
Control Room with Pulse Displays
![Page 20: Control House and Relay Design Considerations for EMP ...prorelay.tamu.edu/.../sites/3/2019/03/Control-House...Control House and Relay Design Considerations for EMP Resiliency Roy](https://reader033.vdocuments.us/reader033/viewer/2022050215/5f60fcc801f7301bf279046c/html5/thumbnails/20.jpg)
IED Performance Categories
Category 1: There were NO IED component failures and the IED continued to operate without interruption
Category 2: There were NO IED component failures, however, the IED locked-up and had to be reset or auto re-booted
Category 3: There were component failures in the IED and normal operation was no longer possible
![Page 21: Control House and Relay Design Considerations for EMP ...prorelay.tamu.edu/.../sites/3/2019/03/Control-House...Control House and Relay Design Considerations for EMP Resiliency Roy](https://reader033.vdocuments.us/reader033/viewer/2022050215/5f60fcc801f7301bf279046c/html5/thumbnails/21.jpg)
IED Monitoring – Communicating and Re-boots
IED IED IED…
Ethernet Switch
Test Chamber
Shielded Control House
Control Room
All IED found to be communicating – No Re-Boots or Lock-ups
Multimode Fiber Cable
![Page 22: Control House and Relay Design Considerations for EMP ...prorelay.tamu.edu/.../sites/3/2019/03/Control-House...Control House and Relay Design Considerations for EMP Resiliency Roy](https://reader033.vdocuments.us/reader033/viewer/2022050215/5f60fcc801f7301bf279046c/html5/thumbnails/22.jpg)
Control House Attenuation (with cables into house)
![Page 23: Control House and Relay Design Considerations for EMP ...prorelay.tamu.edu/.../sites/3/2019/03/Control-House...Control House and Relay Design Considerations for EMP Resiliency Roy](https://reader033.vdocuments.us/reader033/viewer/2022050215/5f60fcc801f7301bf279046c/html5/thumbnails/23.jpg)
Direct EMP Signal Radiation
RELAY
IEDs have Passed the Radiated 50kV/m EMP Test with NO HW failures and NO Lockup
![Page 24: Control House and Relay Design Considerations for EMP ...prorelay.tamu.edu/.../sites/3/2019/03/Control-House...Control House and Relay Design Considerations for EMP Resiliency Roy](https://reader033.vdocuments.us/reader033/viewer/2022050215/5f60fcc801f7301bf279046c/html5/thumbnails/24.jpg)
Conclusions
• Nuclear EMP is a low probability / high consequence event
• Man Made EMP is more probable but only has one wave
• EMP effects manifest themselves through both Radiated and Conducted
signals
• There are many design practices that can be employed to mitigate effects
from both Radiated and Conducted signals
• Testing has demonstrated how a shielded and well grounded control house
can minimize effects from both Radiated and Conducted EMP
• Testing in the industry in ongoing
![Page 25: Control House and Relay Design Considerations for EMP ...prorelay.tamu.edu/.../sites/3/2019/03/Control-House...Control House and Relay Design Considerations for EMP Resiliency Roy](https://reader033.vdocuments.us/reader033/viewer/2022050215/5f60fcc801f7301bf279046c/html5/thumbnails/25.jpg)