control box rmg88.620
DESCRIPTION
CONTROL BOX RMG88.620. Dedicated to:. Gas burners. GS SERIES ONE STAGE TWO STAGE. GAS SERIES ONE STAGE TWO STAGE. RS SERIES ONE STAGE TWO STAGE. MODELS. FEATURES. RMG88.620A2RL. RMG88.620A1RL. Mode operation………….…. Intermittent. Intermittent. Main voltage…………….…. - PowerPoint PPT PresentationTRANSCRIPT
BUrners TRAining CEntre
CONTROL BOX RMG88.620CONTROL BOX RMG88.620
BUrners TRAining CEntre
GS SERIESONE STAGETWO STAGE
Dedicated to:Dedicated to:
RS SERIESONE STAGETWO STAGE
Gas burnersGas burners
GAS SERIESONE STAGETWO STAGE
BUrners TRAining CEntre
FEATURES
MODELS
RMG88.620A2RL RMG88.620A1RL
Main voltage…………….…... AC 220-240 V +10% -15% AC 100-120 V +10% -15%
Frequency…………….…... 50-60 Hz +/-6% 50-60 Hz +/-6%
Under Voltage protection…... Approx. AC 170 V Approx. AC 70 V
Primary fuse…………….…... Max 16 A Max 16 A
Power consumption……..…... 20 VA 20 VA
Internal fuse…….……..…... T6.3H250V (IEC 127-215) T6.3
Polarity...………….……..…... Must be observed (checked) Must be observed (checked)
Flame signal (current ioniz.)…. 1.5 A (pre-purge)3 A (operation)
1.5 A (pre-purge)3 A (operation)
Mode operation………….…... Intermittent Intermittent
Voltage at ionization probe.…. AC 115-230 V AC 50-120 V
BUrners TRAining CEntre
Timings of cycleRMG88.620A2RLRMG88.620A1RL NOTES
Waiting time………….…... 2 sec………………………….. Beginning when both# 4 & # 9 are energised.If not input to # 4 within60 sec since # 9 is energised lock out
Checked Pre-purge time (min).. 40 sec (55sec on A1RL type)...
Max time for theair P.Switch to change……... 10 sec
Ignition safety time……..…... 3 sec
Interval 1st 2nd stage..…... 10 sec…………………………. Interval between # 12 # 14 outputs
Post-ignition time……….…... 2 sec
Voltage at # 3 …….………. . 25 sec…………………………...to manage a servomotor
Time between no voltageat # 4 (P.switch at workingposition) and both # 12and # 13 outputs
BUrners TRAining CEntre
CONTROL PROGRAM IN EVENT OF FAULTCause Reponse
Mains failure Restart with program sequence
Voltage dropped belowundervoltage threshold
Restart with program sequence
Premature flame signal Lock-out
Burner does not ignite withinsafety time
Lock-out
Loss of flame during operation Immediate lock out
Air pressure switch welded inindle position
Lock-out 10 secs after the motor start
Air pressure switch in workingposition at beginning
Prevention of start-up and about 1 minafter, lock-out
Air pressure failure within pre-purge
4 new starts, then lock-out
Air pressure failure atoparation
Immediate lock-out
BUrners TRAining CEntre
INDICATION OF OPERATION
Color code table
Stand-by and waiting statuses
Pre-purging
Ignition phase, ignition controlled
Operation, flame OK
Operation, poor flame
Undervoltage, built-in fuse
Fault, alarm
Extraneous light
Error code output (e.g. 2 blinks)
BUrners TRAining CEntre
Operating concept
Burner control has initiated lockoutRed fault LED on
Reset Press lockout reset button for about 1 s
Diagnosis of cause of fault – Press lockout reset button for > 3 s– Press again lockout reset button for > 3 s– Read blink code of red fault LED
«Error code table A»
SELF-DIAGNOSTIC
BUrners TRAining CEntre
Error code table A
Blink code Possible cause
2 x No establishment of flame at the end of «TSA»– Faulty or soiled detector electrode
– Faulty or soiled fuel valves– Poor adjustment of burner
– Faulty ignition equipment
3 x Faulty air pressure monitor – «LP» faulty
– «LP» incorrectly adjusted – Fan motor does not run
4 x extraneous light on burner startup
7 x Loss of flame during operation– Poor adjustment of burner
– Faulty or soiled fuel valves – Short-circuit between detector electrode and ground
10 x Wiring error or internal fault, output contact, unidentifiable fault, e.g. faults that occurred simultaneously