conference room uniflair synergetic application of: precision air conditioning; water chiller;...
TRANSCRIPT
![Page 1: CONFERENCE ROOM UNIFLAIR Synergetic application of: Precision air conditioning; Water chiller; Access floor](https://reader035.vdocuments.us/reader035/viewer/2022072013/56649e615503460f94b5cd95/html5/thumbnails/1.jpg)
CONFERENCE ROOM UNIFLAIR
Synergetic application of:Precision air conditioning;Water chiller;Access floor.
![Page 2: CONFERENCE ROOM UNIFLAIR Synergetic application of: Precision air conditioning; Water chiller; Access floor](https://reader035.vdocuments.us/reader035/viewer/2022072013/56649e615503460f94b5cd95/html5/thumbnails/2.jpg)
DESIGN DATA
Room surface: 170 sqmMax people considered: 90 peopleFresh air flow rate/person: 30 cm/hCooling capacity: 250 W/sqmHeating capacity: 200 W/sqmRecirculating air flow rate: 6000 cm/hExtracting air flow rate: 2 x 1400 cm/h
![Page 3: CONFERENCE ROOM UNIFLAIR Synergetic application of: Precision air conditioning; Water chiller; Access floor](https://reader035.vdocuments.us/reader035/viewer/2022072013/56649e615503460f94b5cd95/html5/thumbnails/3.jpg)
SYSTEM DESCRIPTION
Air recirculationn.° 2 units SDC0600H3 c/w summer/winter selectorn.° 1 unit SDC0600T3 c/w summer/winter selectorn.° 1 spare unit SDC0600T3 c/w summer/winter selector
Fresh Air systemn.1 treating air unit installed under floor c/w hot/cold water coil and regulation;
Exhaust air extractionn.° 2 roof extractor;
Air distributionUnder floor distribution plenum;Perforated panels for the air supply;Supply grilles c/w flow regulation;
![Page 4: CONFERENCE ROOM UNIFLAIR Synergetic application of: Precision air conditioning; Water chiller; Access floor](https://reader035.vdocuments.us/reader035/viewer/2022072013/56649e615503460f94b5cd95/html5/thumbnails/4.jpg)
AIR RECIRCULATION
SDC0600T3 SDC0600H3
![Page 5: CONFERENCE ROOM UNIFLAIR Synergetic application of: Precision air conditioning; Water chiller; Access floor](https://reader035.vdocuments.us/reader035/viewer/2022072013/56649e615503460f94b5cd95/html5/thumbnails/5.jpg)
FRESH TREATED AIR SUPPLY
![Page 6: CONFERENCE ROOM UNIFLAIR Synergetic application of: Precision air conditioning; Water chiller; Access floor](https://reader035.vdocuments.us/reader035/viewer/2022072013/56649e615503460f94b5cd95/html5/thumbnails/6.jpg)
Separation wall
EXHAUST AIR EXTRACTION
Front section Side section
![Page 7: CONFERENCE ROOM UNIFLAIR Synergetic application of: Precision air conditioning; Water chiller; Access floor](https://reader035.vdocuments.us/reader035/viewer/2022072013/56649e615503460f94b5cd95/html5/thumbnails/7.jpg)
THE ACCESS FLOORSurface: 170sqmFloor height: 300mmPerforated panel: 70 pcSupply grilles: 25 pcExhaust air grilles: 25 pc
![Page 8: CONFERENCE ROOM UNIFLAIR Synergetic application of: Precision air conditioning; Water chiller; Access floor](https://reader035.vdocuments.us/reader035/viewer/2022072013/56649e615503460f94b5cd95/html5/thumbnails/8.jpg)
• Calcium sulphate panels finished with linoleum FORBO MARMOLEUM in 3 colours. Intermediate floor finished with parquet ACERO CANADESE A LISTONI.
• The structure is a 8 stringers type, 300 mm height;• The air supply is guaranteed by 70 perforated panels and 25
grilles c/w flow regulation system;
THE ACCESS FLOOR
![Page 9: CONFERENCE ROOM UNIFLAIR Synergetic application of: Precision air conditioning; Water chiller; Access floor](https://reader035.vdocuments.us/reader035/viewer/2022072013/56649e615503460f94b5cd95/html5/thumbnails/9.jpg)
FLOW RATE DIAGRAM
0
200
400
600
800
1000
1200
1400
1600
0 5 10 15 20 25 30 35 40 45 50
Air
flo
w r
ate
[c
m/h
]
ADJUSTABLE GRILLE600 x 150
PERFORATED PANEL