conference room uniflair synergetic application of: precision air conditioning; water chiller;...

9
CONFERENCE ROOM UNIFLAIR Synergetic application of: Precision air conditioning; Water chiller; Access floor.

Upload: priscilla-hopkins

Post on 28-Dec-2015

213 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CONFERENCE ROOM UNIFLAIR Synergetic application of: Precision air conditioning; Water chiller; Access floor

CONFERENCE ROOM UNIFLAIR

Synergetic application of:Precision air conditioning;Water chiller;Access floor.

Page 2: CONFERENCE ROOM UNIFLAIR Synergetic application of: Precision air conditioning; Water chiller; Access floor

DESIGN DATA

Room surface: 170 sqmMax people considered: 90 peopleFresh air flow rate/person: 30 cm/hCooling capacity: 250 W/sqmHeating capacity: 200 W/sqmRecirculating air flow rate: 6000 cm/hExtracting air flow rate: 2 x 1400 cm/h

Page 3: CONFERENCE ROOM UNIFLAIR Synergetic application of: Precision air conditioning; Water chiller; Access floor

SYSTEM DESCRIPTION

Air recirculationn.° 2 units SDC0600H3 c/w summer/winter selectorn.° 1 unit SDC0600T3 c/w summer/winter selectorn.° 1 spare unit SDC0600T3 c/w summer/winter selector

Fresh Air systemn.1 treating air unit installed under floor c/w hot/cold water coil and regulation;

Exhaust air extractionn.° 2 roof extractor;

Air distributionUnder floor distribution plenum;Perforated panels for the air supply;Supply grilles c/w flow regulation;

Page 4: CONFERENCE ROOM UNIFLAIR Synergetic application of: Precision air conditioning; Water chiller; Access floor

AIR RECIRCULATION

SDC0600T3 SDC0600H3

Page 5: CONFERENCE ROOM UNIFLAIR Synergetic application of: Precision air conditioning; Water chiller; Access floor

FRESH TREATED AIR SUPPLY

Page 6: CONFERENCE ROOM UNIFLAIR Synergetic application of: Precision air conditioning; Water chiller; Access floor

Separation wall

EXHAUST AIR EXTRACTION

Front section Side section

Page 7: CONFERENCE ROOM UNIFLAIR Synergetic application of: Precision air conditioning; Water chiller; Access floor

THE ACCESS FLOORSurface: 170sqmFloor height: 300mmPerforated panel: 70 pcSupply grilles: 25 pcExhaust air grilles: 25 pc

Page 8: CONFERENCE ROOM UNIFLAIR Synergetic application of: Precision air conditioning; Water chiller; Access floor

• Calcium sulphate panels finished with linoleum FORBO MARMOLEUM in 3 colours. Intermediate floor finished with parquet ACERO CANADESE A LISTONI.

• The structure is a 8 stringers type, 300 mm height;• The air supply is guaranteed by 70 perforated panels and 25

grilles c/w flow regulation system;

THE ACCESS FLOOR

Page 9: CONFERENCE ROOM UNIFLAIR Synergetic application of: Precision air conditioning; Water chiller; Access floor

FLOW RATE DIAGRAM

0

200

400

600

800

1000

1200

1400

1600

0 5 10 15 20 25 30 35 40 45 50

Air

flo

w r

ate

[c

m/h

]

ADJUSTABLE GRILLE600 x 150