Installation Instructions Original Instructions CompactLogix 5480 Controllers Catalog Numbers 5069-L430ERMW, 5069-L450ERMW, 5069-4100ERMW, 5069-L4200ERMW The CompactLogix™ 5480 controllers are Logix-based real-time controllers that run an instance of Windows 10 Internet of Things Enterprise, also known as a commercial operating system (COS). Topic Page Summary of Changes 2 About the Controller 5 Required System Components 6 Install the Controller onto the DIN Rail 9 Connect External Power Supplies to the Controller 9 Connect Control Signals Via UPS Control RTB 14 Install Compact 5000 I/O Modules 18 Install the End Cap 18 Power the System 18 Set the Network Internet Protocol (IP) Addresses 19 Connect the Controller to an EtherNet/IP Network 19 Remove and Replace the Controller 20 Replace the Fans 21 Use the COS For Windows-based Computing 23 Specifications 25 Additional Resources 26 IMPORTANT This publication describes how to install the CompactLogix 5480 controllers. The manner in which you use the controller after it is installed dictates the required tasks at installation: You can use CompactLogix 5480 controllers for real-time control just as you do with other Logix 5000™ controllers after it is installed. You are not required to act on the COS to use the Logix control engine. Before you can use the COS, you must install working controller firmware. This requirement applies even if you do not use the controller for real- time control. If you do not install working controller firmware, the COS does not start. In the out-of-box state, the controller uses firmware revision 1.xxx. On a CompactLogix 5480 controller, the minimum working controller firmware is revision 32.012. You can use an SD card or a flash programming tool to install controller firmware. To use an SD card to install controller firmware, you must remove the card, save the firmware to it, and reinstall the card before you turn on power to the controller for the first time. To use a flash programming tool to install controller firmware, you must install and power the controller first. For more information on the COS, see U se the C OS F or W indo ws-based C omputing on page 23.

Upload: others

Post on 10-Jan-2020

8 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

Installation Instructions

Original Instructions

CompactLogix 5480 ControllersCatalog Numbers 5069-L430ERMW 5069-L450ERMW 5069-4100ERMW 5069-L4200ERMW

The CompactLogixtrade 5480 controllers are Logix-based real-time controllers that run an instance of Windows 10 Internet of Things Enterprise also known as a commercial operating system (COS)

Topic Page

Summary of Changes 2

About the Controller 5

Required System Components 6

Install the Controller onto the DIN Rail 9

Connect External Power Supplies to the Controller 9

Connect Control Signals Via UPS Control RTB 14

Install Compact 5000 IO Modules 18

Install the End Cap 18

Power the System 18

Set the Network Internet Protocol (IP) Addresses 19

Connect the Controller to an EtherNetIP Network 19

Remove and Replace the Controller 20

Replace the Fans 21

Use the COS For Windows-based Computing 23

Specifications 25

Additional Resources 26

IMPORTANT This publication describes how to install the CompactLogix 5480 controllers The manner in which you use the controller after it is installed dictates the

required tasks at installation

bull You can use CompactLogix 5480 controllers for real-time control just as you do with other Logix 5000trade controllers after it is installed You are not required to act on the COS to use the Logix control engine

bull Before you can use the COS you must install working controller firmware This requirement applies even if you do not use the controller for real-time control If you do not install working controller firmware the COS does not start

In the out-of-box state the controller uses firmware revision 1xxx On a CompactLogix 5480 controller the minimum working controller firmware is

revision 32012

You can use an SD card or a flash programming tool to install controller firmware

ndash To use an SD card to install controller firmware you must remove the card save the firmware to it and reinstall the card before you turn on power

to the controller for the first time

ndash To use a flash programming tool to install controller firmware you must install and power the controller first

For more information on the COS see Use the COS For Windows-based Computing on page 23

CompactLogix 5480 Controllers

The CompactLogix 5480 controllers can operate in various applications including the use of local Compact 5000trade IO modules and remote IO modules and Integrated Motion over an EtherNetIPtrade network The controllers offer the following

bull Real-time control in industrial control systemsbull Windows-based computing on the COS that is independent of the Logix control enginebull High-speed bus packet transfer ratebull High-speed IO module communication motion control and use of Device Level Ring (DLR) Linear and Star EtherNetIP topologies

bull Multiple ports for use with the Logix control engine on the controller includingndash One USB programming port for temporary connectionndash One Gigabit Ethernet ports for high-speed IO communication and motion control

bull Multiple ports for use with the COS on the controller includingndash One Gigabit Ethernet port as a dedicated OS network interfacendash An integrated DisplayPort for high definition monitor connectivityndash Two USB 30 ports for OS peripheral and expanded data storage capability

You use the Studio 5000 Logix Designerreg application to configure CompactLogix 5480 controllers

For more information on the components that are required to install a CompactLogix 5480 controller see page 6 For more information on how to use the controller after you install it see the publications that are listed in Additional Resources on page 26

Summary of ChangesThis publication was revised for the following changes

bull Add the new controller catalog numbers that is the 5069-L430ERMW 5069-L450ERMW 5069-L4100ERMW and 5069-L4200ERMW

bull Provide more information on the COS For more information see Use the COS For Windows-based Computing on page 23

2 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

ATTENTION Read this document and the documents listed in the Additional Resources section about installation configuration and operation of this equipment before you install configure operate or maintain

this product Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes laws and standards

Activities including installation adjustments putting into service use assembly disassembly and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of

practice

If this equipment is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired

ATENCIOacuteN Antes de instalar configurar poner en funcionamiento o realizar el mantenimiento de este producto lea este documento y los documentos listados en la seccioacuten Recursos adicionales acerca de la

instalacioacuten configuracioacuten y operacioacuten de este equipo Los usuarios deben familiarizarse con las instrucciones de instalacioacuten y cableado y con los requisitos de todos los coacutedigos leyes y estaacutendares vigentes

El personal debidamente capacitado debe realizar las actividades relacionadas a la instalacioacuten ajustes puesta en servicio uso ensamblaje desensamblaje y mantenimiento de conformidad con el coacutedigo de

praacutectica aplicable

Si este equipo se usa de una manera no especificada por el fabricante la proteccioacuten provista por el equipo puede resultar afectada

ATENCcedilAtildeO Leia este e os demais documentos sobre instalaccedilatildeo configuraccedilatildeo e operaccedilatildeo do equipamento que estatildeo na seccedilatildeo Recursos adicionais antes de instalar configurar operar ou manter este produto Os

usuaacuterios devem se familiarizar com as instruccedilotildees de instalaccedilatildeo e fiaccedilatildeo aleacutem das especificaccedilotildees para todos os coacutedigos leis e normas aplicaacuteveis

Eacute necessaacuterio que as atividades incluindo instalaccedilatildeo ajustes colocaccedilatildeo em serviccedilo utilizaccedilatildeo montagem desmontagem e manutenccedilatildeo sejam realizadas por pessoal qualificado e especializado de acordo com o

coacutedigo de praacutetica aplicaacutevel

Caso este equipamento seja utilizado de maneira natildeo estabelecida pelo fabricante a proteccedilatildeo fornecida pelo equipamento pode ficar prejudicada

ВНИМАНИЕ Перед тем как устанавливать настраивать эксплуатировать или обслуживать данное оборудование прочитайте этот документ и документы перечисленные в разделе

laquoДополнительные ресурсыraquo В этих документах изложены сведения об установке настройке и эксплуатации данного оборудования Пользователи обязаны ознакомиться с инструкциями по

установке и прокладке соединений а также с требованиями всех применимых норм законов и стандартов

Все действия включая установку наладку ввод в эксплуатацию использование сборку разборку и техническое обслуживание должны выполняться обученным персоналом в соответствии с

применимыми нормами и правилами

Если оборудование используется не предусмотренным производителем образом защита оборудования может быть нарушена

ACHTUNG Lesen Sie dieses Dokument und die im Abschnitt bdquoWeitere Informationenldquoaufgefuumlhrten Dokumente die Informationen zu Installation Konfiguration und Bedienung dieses Produkts enthalten bevor

Sie dieses Produkt installieren konfigurieren bedienen oder warten Anwender muumlssen sich neben den Bestimmungen aller anwendbaren Vorschriften Gesetze und Normen zusaumltzlich mit den Installations- und

Verdrahtungsanweisungen vertraut machen

Arbeiten im Rahmen der Installation Anpassung Inbetriebnahme Verwendung Montage Demontage oder Instandhaltung duumlrfen nur durch ausreichend geschulte Mitarbeiter und in Uumlbereinstimmung mit den

anwendbaren Ausfuumlhrungsvorschriften vorgenommen werden

Wenn das Geraumlt in einer Weise verwendet wird die vom Hersteller nicht vorgesehen ist kann die Schutzfunktion beeintraumlchtigt sein

ATTENTION Lisez ce document et les documents listeacutes dans la section Ressources compleacutementaires relatifs agrave lrsquoinstallation la configuration et le fonctionnement de cet eacutequipement avant drsquoinstaller configurer

utiliser ou entretenir ce produit Les utilisateurs doivent se familiariser avec les instructions drsquoinstallation et de cacircblage en plus des exigences relatives aux codes lois et normes en vigueur

Les activiteacutes relatives agrave lrsquoinstallation le reacuteglage la mise en service lrsquoutilisation lrsquoassemblage le deacutemontage et lrsquoentretien doivent ecirctre reacutealiseacutees par des personnes formeacutees selon le code de pratique en vigueur

Si cet eacutequipement est utiliseacute drsquoune faccedilon qui nrsquoa pas eacuteteacute deacutefinie par le fabricant la protection fournie par lrsquoeacutequipement peut ecirctre compromise

ATTENZIONE Prima di installare configurare ed utilizzare il prodotto o effettuare interventi di manutenzione su di esso leggere il presente documento ed i documenti elencati nella sezione ldquoAltre risorserdquo

riguardanti lrsquoinstallazione la configurazione ed il funzionamento dellrsquoapparecchiatura Gli utenti devono leggere e comprendere le istruzioni di installazione e cablaggio oltre ai requisiti previsti dalle leggi codici

e standard applicabili

Le attivitagrave come installazione regolazioni utilizzo assemblaggio disassemblaggio e manutenzione devono essere svolte da personale adeguatamente addestrato nel rispetto delle procedure previste

Qualora lrsquoapparecchio venga utilizzato con modalitagrave diverse da quanto previsto dal produttore la sua funzione di protezione potrebbe venire compromessa

DİKKAT Bu uumlruumlnuumln kurulumu yapılandırılması işletilmesi veya bakımı oumlncesinde bu dokuumlmanı ve bu ekipmanın kurulumu yapılandırılması ve işletimi ile ilgili İlave Kaynaklar boumlluumlmuumlnde yer listelenmiş

dokuumlmanları okuyun Kullanıcılar yuumlruumlrluumlkteki tuumlm youmlnetmelikler yasalar ve standartların gereksinimlerine ek olarak kurulum ve kablolama talimatlarını da oumlğrenmek zorundadır

Kurulum ayarlama hizmete alma kullanma parccedilaları birleştirme parccedilaları soumlkme ve bakım gibi aktiviteler sadece uygun eğitimleri almış kişiler tarafından yuumlruumlrluumlkteki uygulama youmlnetmeliklerine uygun şekilde

yapılabilir

Bu ekipman uumlretici tarafından belirlenmiş amacın dışında kullanılırsa ekipman tarafından sağlanan koruma bozulabilir

POZOR Než začnete instalovat konfigurovat či provozovat tento vyacuterobek nebo provaacutedět jeho uacutedržbu přečtěte si tento dokument a dokumenty uvedeneacute v čaacutesti Dodatečneacute zdroje ohledně instalace konfigurace

a provozu tohoto zařiacutezeniacute Uživateleacute se musejiacute vedle požadavků všech relevantniacutech vyhlaacutešek zaacutekonů a norem nutně seznaacutemit takeacute s pokyny pro instalaci a elektrickeacute zapojeniacute

Činnosti zahrnujiacuteciacute instalaci nastaveniacute uvedeniacute do provozu užiacutevaacuteniacute montaacutež demontaacutež a uacutedržbu musiacute vykonaacutevat vhodně proškolenyacute personaacutel v souladu s přiacuteslušnyacutemi provaacuteděciacutemi předpisy

Pokud se toto zařiacutezeniacute použiacutevaacute způsobem neodpoviacutedajiacuteciacutem specifikaci vyacuterobce může byacutet narušena ochrana kterou toto zařiacutezeniacute poskytuje

UWAGA Przed instalacją konfiguracją użytkowaniem lub konserwacją tego produktu należy przeczytać niniejszy dokument oraz wszystkie dokumenty wymienione w sekcji Dodatkowe źroacutedła omawiające

instalację konfigurację i procedury użytkowania tego urządzenia Użytkownicy mają obowiązek zapoznać się z instrukcjami dotyczącymi instalacji oraz oprzewodowania jak roacutewnież z obowiązującymi kodeksami

prawem i normami

Działania obejmujące instalację regulację przekazanie do użytkowania użytkowanie montaż demontaż oraz konserwację muszą być wykonywane przez odpowiednio przeszkolony personel zgodnie z

obowiązującym kodeksem postępowania

Jeśli urządzenie jest użytkowane w sposoacuteb inny niż określony przez producenta zabezpieczenie zapewniane przez urządzenie może zostać ograniczone

OBS Laumls detta dokument samt dokumentet som staringr listat i avsnittet Oumlvriga resurser om installation konfigurering och drift av denna utrustning innan du installerar konfigurerar eller boumlrjar anvaumlnda eller utfoumlra

underharingllsarbete paring produkten Anvaumlndare maringste bekanta sig med instruktioner foumlr installation och kabeldragning foumlrutom krav enligt gaumlllande koder lagar och standarder

Aringtgaumlrder som installation justering service anvaumlndning montering demontering och underharingllsarbete maringste utfoumlras av personal med laumlmplig utbildning enligt laumlmpligt bruk

Om denna utrustning anvaumlnds paring ett saumltt som inte anges av tillverkaren kan det haumlnda att utrustningens skyddsanordningar foumlrsaumltts ur funktion

LET OP Lees dit document en de documenten die genoemd worden in de paragraaf Aanvullende informatie over de installatie configuratie en bediening van deze apparatuur voordat u dit product installeert

configureert bediend of onderhoudt Gebruikers moeten zich vertrouwd maken met de installatie en de bedradingsinstructies naast de vereisten van alle toepasselijke regels wetten en normen

Activiteiten zoals het installeren afstellen in gebruik stellen gebruiken monteren demonteren en het uitvoeren van onderhoud mogen uitsluitend worden uitgevoerd door hiervoor opgeleid personeel en in

overeenstemming met de geldende praktijkregels

Indien de apparatuur wordt gebruikt op een wijze die niet is gespecificeerd door de fabrikant dan bestaat het gevaar dat de beveiliging van de apparatuur niet goed werkt

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 3

CompactLogix 5480 Controllers

Environment and Enclosure

ATTENTION This equipment is intended for use in a Pollution Degree 2 industrial environment in overvoltage Category II applications (as defined in ENIEC

60664-1) at altitudes up to 2000 m (6562 ft) without derating

This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such

environments

This equipment is supplied as open-type equipment for indoor use It must be mounted within an enclosure that is suitably designed for those specific

environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts The enclosure must

have suitable flame-retardant properties to prevent or minimize the spread of flame complying with a flame spread rating of 5VA or be approved for the

application if nonmetallic The interior of the enclosure must be accessible only by the use of a tool Subsequent sections of this publication may contain more

information regarding specific enclosure type ratings that are required to comply with certain product safety certifications

In addition to this publication see the following

bull Industrial Automation Wiring and Grounding Guidelines publication 1770-41 for more installation requirements

bull NEMA 250 and ENIEC 60529 as applicable for explanations of the degrees of protection provided by enclosures

Prevent Electrostatic Discharge

ATTENTION This equipment is sensitive to electrostatic discharge which can cause internal damage and affect normal operation Follow these guidelines when

you handle this equipment

bull Touch a grounded object to discharge potential static

bull Wear an approved grounding wriststrap

bull Do not touch connectors or pins on component boards

bull Do not touch circuit components inside the equipment

bull Use a static-safe workstation if available

bull Store the equipment in appropriate static-safe packaging when not in use

ATTENTION

bull In case of malfunction or damage no attempts at repair should be made The controller should be returned to the manufacturer for repair Do not dismantle the controller

bull This equipment is certified for use only within the surrounding air temperature range of 0hellip60 degC (32hellip140 degF) The equipment must not be used outside of this range

bull The USB programming port is intended for temporary local programming purposes only and not intended for permanent connection The USB programming port connection is not to exceed 30 m (984 ft) and must not contain hubs You must connect the programming equipment to a ground system that is common with the controller

bull Devices that are connected to USB 30 ports must reside in the same control enclosure as the controller This requirement applies to devices that are powered by the USB 30 ports or not You must connect the devices to a ground system that is common with the controller Alternatively you can connect the device to the common ground system via a USB hub that provides galvanic isolation

bull USB 30 port connections are not to exceed 30 m (984 ft)

bull DisplayPort cables or adapters that are used with this product must be certified by VESA A list of certified equipment and cables is on the VESA website (wwwvesaorg) Use of non-certified cables and adapters can cause damage or improper operation DisplayPort connections are not to exceed 30 m (984 ft)

bull Displays that are connected to DisplayPort must connect to a ground system that is common with the controller Alternatively displays can be connected by a display extender that is connected to the common ground system with the controller and provides galvanic isolation

bull Use only a soft dry anti-static cloth to wipe down equipment Do not use any cleaning agents

Electrical Safety Considerations

ATTENTION Do not wire more than 2 conductors on a single RTB terminal

Waste Electrical and Electronic Equipment (WEEE)

At the end of its life this equipment should be collected separately from any unsorted municipal waste

4 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

About the ControllerThe following graphic shows a CompactLogix 5480 controller

IMPORTANTAny illustrations charts sample programs and layout examples that are shown in this publication are intended solely for the purposes of example Since

there are many variables and requirements that are associated with any particular installation Rockwell Automation does not assume responsibility or

liability for actual use that is based on the examples that are shown in this publication

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

1

6

7

9

8

2

3

4

14

11

16

10

5

1312

15

18

20

17

19

Front View

Bottom View

22

21

23

CompactLogix 5480 Controller Parts

Number Item Description

1 DIN rail latches Secure adapter to DIN rail

2 Mode switch Lets you choose the controller operating mode

3 SD card slot Location for SD card

4 Reset button Resets the controller to factory default condition

5 Four-character displayScrolls information about the controller such as firmware revision or project status

6 USB programming port Provides temporary connection to download projects

7 Ethernet port B1Lets the controller connect to the following networksbull Enterprise-level networkbull Device-level network

8 Ethernet port A1Lets the controller connect to device-level networks

9 Ethernet port A2

10Network and link status indicators for ports B1 A1 and A2 Show the state of the Ethernet ports and network

communication activity on each port

11Speed and link status indicators for port X1

12 Bottom fanHelps regulate controller temperature

Controller ships with fans installed You can replace fans if necessary

13Controller status indicators

Show the state of the controller in multiple respects

14 Top fanHelps regulate controller temperature

Controller ships with fans installed You can replace fans if necessary

15MOD power and SA power status indicators

Show the state of module (MOD) power and sensor actuator (SA) power respectively

16 UPS Control RTB

Connector for control signals to and from an uninterruptible power supply (UPS) that are used to support a controlled shutdown upon incoming power loss

17MOD power bus connector

MOD power bus connection that passes MOD power to the next local Compact 5000 IO module in the system

18 MOD power RTBConnector for external power supply to provide MOD power to the system

19 SA power bus connectorSA power bus connection that passes SA power to the next local Compact 5000 IO module in the system

20 SA power RTBConnector for external power supply to provide SA power to the systemlsquo

21 Ethernet port X1 Used with the COS on the controller

22 USB 30 portsConnectors for peripherals that are used with the COS on the controller(2)

(2) Devices that are connected to the controller via a USB 30 port must reside in the same control enclosure as

the controller This requirement applies to devices that are powered by the USB 30 ports or not You must

connect the devices to a ground system that is common with the controller Alternatively you can connect

the device to the common ground system via a USB hub that provides galvanic isolation

23DisplayPort connection(1)

(1) Any DisplayPort cables or adapters that are used with this product must be certified by VESA A list of

certified equipment and cables is on the VESA website (wwwvesaorg) Use of non-certified cables and

adapters can cause damage or improper operation

Connector to use a display with the COS on the controller

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 5

CompactLogix 5480 Controllers

Required System ComponentsBefore you install the controller verify that you have the following components

System PlanningFollow these rules when planning your system configuration

bull If the CompactLogix 5480 system includes only a controller you can mount the DIN rail in any orientation

bull If your CompactLogix 5480 system includes local Compact 5000 IO modules you must mount the DIN rail horizontally

bull The controller is the leftmost component in the system

bull Local Compact 5000 IO modules are installed to the right of the controller

bull The controller supports as many as 31 local Compact 5000 IO modules

bull Before power-up make sure that the end cap is installed on the right side of the controller or rightmost local Compact 5000 IO module if IO modules are used

Components Used to Install a CompactLogix 5480 Controller

Component Description

Removable Terminal Blocks (RTB)

An RTB that is used to connect MOD power (system-side power) to the controller - 5069-RTB4-SCREW RTB (Ships with the controller)

An RTB that is used to connect SA power (field-side power) - 5069-RTB6-SCREW RTB (Ships with the controller)

An RTB that is used to connect UPS (uninterruptible power) - 5069-L4UPSRTB (Ships with the controller)

External power supply for MOD power

A power supply that is adequately sized to provide MOD power that is system-side power to the CompactLogix 5480 system

For more information see System Power Considerations on page 8

External power supply for SA power

A power supply that is adequately sized to provide SA power that is field-side power to the CompactLogix 5480 system

IMPORTANT SA power is only required if your application includes local Compact 5000 IO modules that are connected to devices that use SA power

For more information see System Power Considerations on page 8

External uninterruptible power supply for UPS control signals

A power supply that provides UPS control signals so that the controller can save the state of the program when power is lost A UPS is only required if your system uses UPS control signals

For more information see Connect Control Signals Via UPS Control RTB on page 14

Tools

You use the following tools to wire the RTBsbull Screwdriverbull Wire stripperbull Wires

For more information on available wire sizes and wire insulation-stripping length see Specifications on page 25

DIN rail

Compatible zinc-plated chromate steel DIN rail

You can use the following DIN railsbull EN50022 - 35 x 75 mm (138 x 030 in)bull EN50022 - 35 x 15 mm (138 x 060 in)

EtherNetIP network components

If your CompactLogix 5480 controller operates on an EtherNetIP network you must install the network and all required components

Software

When you install the controller you assign IP addresses on the controller You can use the following to assign IP addresses

bull DHCP server

bull BOOTP DHCP EtherNetIP Commissioning tool version 30200 or later

bull RSLinxreg Classic software version 41000 or later

bull FactoryTalkreg Linx version 61000 or later

bull Logix Designer application version 320100 or later

For more information see Set the Network Internet Protocol (IP) Addresses on page 19

ATTENTION Do not discard the end cap Use this end cap

to cover the exposed interconnections on the last module

on the DIN rail Failure to do so could result in equipment

damage or injury from electric shock

Components Used to Install a CompactLogix 5480 Controller

Component Description

6 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpacingMaintain spacing from enclosure walls wireways and adjacent equipment Ambient temperature is higher at the top of an enclosed cabinet

The minimum distance on of a system that includes only a CompactLogix 5480 controller is as follows

bull 2500 mm (098 in) between the sides and the cabinet

bull 2500 mm (098 in) between the front of the controller and the cabinet

bull 5000 mm (196 in) between the top and bottom and the cabinet

We recommend that you install the controller near the bottom of the enclosure where ambient temperature is lower

Enclosure SelectionThis example is provided to help you size an enclosure for your CompactLogix 5480 controller You need heat dissipation data from all components that are planned for your enclosure to calculate the enclosure size

With no active method of heat dissipation for example air conditioning either of the following approximate equations can be used for a metal cabinet

The maximum ambient rating of the CompactLogix 5480 controller is 60 degC (140 degF) If the maximum external cabinet temperature is 20 degC (68 degF) then T=40

In this example with only the controller the heat dissipation is 72 W that is the sum of all components in the enclosure In the following equation T=40 and Q=72

In this example the enclosure must have a minimum exterior surface of 0386 m2

If any portion of the enclosure cannot transfer heat exclude that value from the calculation

The minimum installation clearance for a CompactLogix 5480 controller is 26700 x 18400 x 15200 mm (1050 x 725 x 600 in) HxWxD

The standard cabinet depth in this example is 15420 mm (600 in)

To meet cooling and clearance requirements in this example the cabinet must be approximately 30480 x 35560 x 15420 mm(1200 x 1400 x 600 in) HxWxD

A = 2DW +2DH + 2WH

A = 2 x (01542 x 03556) + 2 x (01542 x 03048) + 2 x (03556 x 03048) = 04204 m2

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

Top

Bottom

SideSide

End cap

Cabinet

Metric Imperial

Where

bull T = Temperature difference between inside air and outside ambient (degC)

bull Q = Heat that is generated in enclosure (Watts)

bull A = Enclosure surface area (m2)

Where

bull T = Temperature difference between inside air and outside ambient (degF)

bull Q = Heat that is generated in enclosure (Watts)

bull A = Enclosure surface area (ft2)

The exterior surface of all six sides of an enclosure is calculated as

A = 2dw + 2dh + 2wh

Where d (depth) w (width) and h (height) are in meters

The exterior surface of all six sides of an enclosure is calculated as

A = (2dw + 2dh + 2wh) 144

Where d (depth) w (width) and h (height) are in inches

038Q

180T - 110

A =

408Q

T - 110

A =

038(7200)

180(4000) - 110A =

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 7

CompactLogix 5480 Controllers

This example uses the following conditions

bull All sides of the enclosure transfer heatbull Only the CompactLogix 5480 controller is installedbull Ambient temperature = 20 degC (68 degF)

DimensionsThe controller dimensions are as follows

Ground ConsiderationsYou must ground DIN rails according to the Industrial Automation Wiring and Grounding Guidelines publication 1770-41

You can use the following DIN rails

bull EN50022 - 35 x 75 mm (138 x 030 in)bull EN50022 - 35 x 15 mm (138 x 060 in)

System Power ConsiderationsThe CompactLogix 5480 controller provides power to a CompactLogix 5480 system via RTBs that are connected to external power supplies and installed on the controller

The RTBs provide the following power to the system

IMPORTANT If any of the following conditions exist the enclosure must be larger

bull Any sides of the enclosure cannot transfer heat

bull More equipment is included in the system

bull Ambient temperature is higher than 20 degC (68 degF)

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

13021 mm

(513 in)

16620 mm

(654 in)

12654 mm

(498 in)

12002 mm

(473 in)

13366 mm

(526 in)

16000 mm

(630 in)

ATTENTION This product is grounded through the DIN rail to

chassis ground Use zinc-plated chromate-passivated steel DIN rail

to assure proper grounding The use of other DIN rail materials (for

example aluminum or plastic) that can corrode oxidize or are poor

conductors can result in improper or intermittent grounding

Secure DIN rail to mounting surface approximately every 200 mm

(78 in) and use end-anchors appropriately Be sure to ground the

DIN rail properly See Industrial Automation Wiring and Grounding

Guidelines Rockwell Automationreg publication 1770-41 for more

information

Power Type Description

MOD Power

System-side power that is used to operate the CompactLogix 5480 system MOD power is provided through the MOD power RTB and passed across the MOD power bus bull The total continuous current draw across the MOD power bus must not be

more than 10 A max at 1832V DC

You must calculate the total MOD power that the controller and all local Compact 5000 IO modules draw to make sure that no more than 10 A of MOD power is drawn(1)

bull Confirm that the external MOD power supply is adequately sized for the total MOD power bus current draw in the system including the MOD power inrush current requirements

(1) If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000

IO modules can draw a maximum of 10 A in addition to the current the controller draws

SA Power

Field-side power that can be used to power field-side devices that are connected to some Compact 5000 IO modules SA power is provided through the SA power RTB and passed across the SA power bus

bull SA power is only required if your application includes local Compact 5000 IO modules that are connected to devices that use SA power

bull If you are using DC voltage for SA power the total continuous current draw across the MOD power bus must not be more than 10 A max at 18hellip32V DC

bull If you are using AC voltage for SA power the total continuous current draw across the MOD power bus must not be more than 10 A max at 18hellip240V AC

bull You can use a 5069-FPD field potential distributor to establish additional SA power buses in a CompactLogix 5480 system

If your system includes AC and DC modules that require SA power you must use a 5069-FPD field potential distributor to establish a new SA power bus

You separate the module types by SA power bus For example install DC module on the first SA power bus in the system and install the AC modules on the second SA power bus in the system

bull Confirm that the external SA power supply is sized adequately for the total SA power current draw in the system

UPS Control

Control signals from an external UPS that let the controller save the state of the program if power is lost The external UPS provides the power that is required to save the program via the MOD power RTB A UPS is not required for controller operation

8 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Controller onto the DIN Rail

1 Confirm that the DIN rail latches are closed

2 If the DIN rail latches are open gently push the rear latch back until the front latch pops up and clicks

3 Position the controller so that the back of it faces the DIN rail

4 Press the controller against the DIN rail until you hear a click

5 Confirm that all latches have fully closed and the controller is latched securely

Connect External Power Supplies to the ControllerBefore you connect MOD power or SA power to the RTBs on the CompactLogix 5480 controller complete the following tasks

bull Read System Power Considerations on page 8

bull Confirm that the external power supplies that MOD power and SA power are adequately sized for your CompactLogix 5480 system For more information see page 8

bull Verify that the external power supplies are turned off

bull Install the MOD power RTB SA power RTB and the UPS Control RTB if used

bull If IO modules are used verify that they are installed on the correct SA power bus

DC-type modules must reside on an SA power bus that uses DC power and AC-type modules must reside on an SA power bus that uses AC power

For more information see the technical documentation for Compact 5000 IO modules

IMPORTANT Remember the following

bull CompactLogix 5480 controllers do not have an embedded power supply that powers the system

The system is powered by external power supplies via

connections to the various power RTBs on the controller

bull We recommend that you use 1606 power supplies from Rockwell Automation to provide MOD power SA power and UPS control

bull You must use an external power supply that is dedicated to the UPS connection

For more information about which 1606 power supplies

are best for each power type see the Switched Mode

Power Supply Specifications Technical Data publication

1606-TD002

bull You can connect power from one external power supply to the MOD power and SA power RTBs However as stated previously we strongly recommend that you use separate external power supplies for MOD power and SA power respectively

The practice of using separate external power supplies can

help prevent unintended consequences that can result if

you use one supply

If you use separate external power supplies the loss of

power from one external power supply does not affect the

availability of power from the other supply For example if

separate external power supplies are used and SA power is

lost MOD power remains available for the Compact 5000

IO modules

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPSR

B

F

R

B

F

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPSR

B

F

R

B

F

Closed PositionOpen Position

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 9

CompactLogix 5480 Controllers

Install the MOD Power RTB

1 Hook the bottom of the MOD power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect MOD PowerThe way that you connect power to the MOD power RTB depends on whether you use UPS control signals or not

bull If you are not using UPS control signals you connect the external power supply directly to the MOD power RTB

In this case proceed to Connect to the MOD Power RTB from a Standard External Power Supply on page 10

bull If you are using UPS control signals you connect a UPS to the MOD power RTB

In this case proceed to Connect to the MOD Power RTB from a UPS on page 15

Connect to the MOD Power RTB from a Standard External Power Supply

Before you connect an external power source to the MOD power RTB make sure that the MOD power source is properly sized

1 Verify that the external power supply is not powered

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the 24V DC (+) connection on the external power supply into the first MOD (+) terminal on the RTB

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the 24V DC (mdash) connection on the external power supply into the first MOD (mdash) terminal on the RTB

5069-L4200ERMW

MOD Power RTB

IMPORTANT Your application can require a power control device for example

a switch between the external 24V DC power source and the

controller to control when the controller is powered If so you

must install the power control device at the VDC+ terminal on

the RTB

If you install the power control device at the VDC- terminal the

controller can fail to power up or power down properly

10 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

The following diagram shows an external 24V DC power supply that is connected to the MOD power RTB when you are not using UPS control signals

Install the SA Power RTBInstall the SA power RTB even if you do not use SA power

1 Hook the bottom of the SA power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect SA DC Power

Before you connect an external DC power source to the SA power RTB make sure that the SA power source is properly sized

For more information o n SA power see SA Power on page 8

1 Confirm that MOD power and SA power sources are turned off

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the DC (+) connection on the external power supply into the first SA (+) terminal on the RTB

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

24V DC

Power

Supply

+

ndashIMPORTANT SA power is only required if your application includes local

Compact 5000 IO modules that require SA power to operate

or are connected to field-side devices that are powered by

SA power

5069-L4200ERMW

SA Power RTB

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 11

CompactLogix 5480 Controllers

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the DC (mdash) connection on the external power supply into the first SA (mdash) terminal on the RTB

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

7 Insert the wire from an Earth Ground location into the first

Ground ( ) on the RTB

The Earth Ground location can be the external SA power supply the DIN rail or other Earth Ground location

8 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

The following diagram shows an external 24V DC power supply that is connected to the SA power RTB when you do not use UPS control signals

TIP

This symbol denotes a Functional Ground terminal that provides a

low impedance path between electric circuits and earth for functional

purposes and provides noise immunity improvement This connection

must be made for functional purposes

5069-L4200ERMW

24V DC

Power

Supply

+

ndash

24V DC

Power

Supply

+

ndash

MOD

Power

SA DC

Power

Functional Ground

12 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Connect SA AC Power

Before you connect an external AC power source to the SA power RTB make sure that the SA power source is properly sized

For more information o n SA power see SA Power on page 8

1 Verify that the SA power source is not powered on

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the L1AC (+) connection on the external power supply into the first SA (+) terminal on the RTB

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the L2NAC(mdash) connection on the external power supply into the first SA(mdash) terminal on the RTB

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

7 Insert the wire from an Earth Ground location into the first

Ground ( ) on the RTB

The Earth Ground location can be the external SA power supply the DIN rail or other Earth Ground location

8 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

This diagram shows an external 240V AC power supply that is connected to the SA power RTB when you do not use UPS control signals

IMPORTANT SA power is only required if your application includes local

Compact 5000 IO modules that require SA power to operate

or are connected to field-side devices that are powered by

SA power

TIP

This symbol denotes a Functional Ground terminal that provides a

low impedance path between electric circuits and earth for functional

purposes and provides noise immunity improvement This connection

must be made for functional purposes

5069-L4200ERMW

24V DC

Power

Supply

+

ndash

240V AC

Power

Supply

+

ndash

MOD

Power

SA AC

Power

Functional Ground

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 13

CompactLogix 5480 Controllers

Connect Control Signals Via UPS Control RTBThe CompactLogix 5480 controller does not have an internal energy storage module that lets the controller save the state of the program if system-side power is lost You must connect an external uninterruptible power supply (UPS) to the UPS control RTB to save the state of the program if power is lost

You connect control signals from an external power supply to the UPS control RTB to let the controller experience a controlled shutdown upon an incoming power loss

When a UPS connection is detected the CompactLogix 5480 controller defaults to initiate shutdown 1 minute after a power loss indication

We recommend that you use 1606 switched mode uninterruptible power supplies from Rockwell Automation with a CompactLogix 5480 controller for example the 1606-XLS240-UPS power supply

For more information on Bulletin 1606 uninterruptible power supplies see the following

bull Bulletin 1606 DC-UPS Uninterruptible Power Supply Installation Instructions publication 1606-IN025

bull Bulletin 1606 Switched Mode Power Supplies Reference Manual publication 1606-RM036

The switched mode uninterruptible power supplies use a 12-volt battery module to bridge power failures and voltage fluctuations We recommend that you use the 1606-XLSBATASSY1 battery module from Rockwell Automation

You can use other accessories such as replacement batteries mounting kits and panelwall mounting brackets with the battery module

For more information on and the battery module and accessories that you can use with them see the following

bull Bulletin 1606 12V 7Ah Battery Modules Installation Instructions publication 1606-IN011

bull Bulletin 1606 Switched Mode Power Supply Battery Modules (12V 7Ah) Reference Manual publication 1606-RM037

UPS Control SignalsThese control signals are used on the UPS Control RTB

UPS Control RTB Terminals

Signal Description

UPS Ready (R)

An input signal from the UPS to the controller that indicates the UPS is working and can buffer during a power failure

The charge level for a UPS to be ready to buffer during a power failure varies For example the 1606-XLS240-UPS power supply must be greater than 85 charged to be ready

The letter R indicates the RTB terminal for this signal

Buffering (B)

An input signal from the UPS to the controller that indicates the UPS battery is providing power because the external power has failed

After a preset time (typically 1 minute after power failure) the controller performs an orderly shutdown by stopping execution and saving the state of the controller

The letter B indicates the RTB terminal for this signal

Battery Fail (F)

An input from the UPS to the controller that indicates the UPS battery has failed and the controller cannot operate from stored energy

In this case the controller does not attempt to save the state of the program when the external power fails The controller issues an alarm if a UPS was previously attached and ready to buffer

The letter F indicates the RTB terminal for this signal

Inhibit (I)

An output signal from the controller to the UPS that disables the UPS signal output The INHIBIT signal is triggered after data is backed up and the system is ready to shut down

The letter I indicates the RTB terminal for this signal

14 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the UPS Control RTBInstall the UPS control RTB even if you do not intend to connect uninterruptible power to the controller

1 Hook the bottom of the UPS power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect UPS Control Signals

1 Verify that all sources of MOD power and SA power are turned off

2 Verify the followingbull A 24V DC power supply is connected to the 24V IN

terminals on the UPSbull A 12V DC battery is connected to the 12V BAT terminals

on the UPS

For more information see the example graphic on page 17

Connect to the MOD Power RTB from a UPS

1 Daisy chain the wires from these connections on the UPSbull 24V OUT (+)bull Ready (1)bull Buffering (3)bull Battery Fail (5)bull Inhibit (7)

2 Connect one wire to each (+) terminal on the MOD power RTB as shown in the example graphic on page 17a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Daisy chain a wire that is connected to the 24V OUT (ndash) terminal on the UPS and a second wire

4 Connect one wire to each (ndash) terminal on the MOD power RTB a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

IMPORTANT The UPS terminal labels in this section represent the labels on

a 1606-XLS240-UPS power supply Your UPS terminals can be

labeled differently

5069-L4200ERMW

UPS Control RTB

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 15

CompactLogix 5480 Controllers

Connect to the UPS Control RTB from a UPS

1 Connect a wire from the Ready (2) connection on the UPS to the UPS Ready terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

2 Connect a wire from the Buffering (4) connection on the UPS to the Buffering terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Connect a wire from the Battery Fail (6) connection on the UPS to the Battery Fail terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

4 Connect a wire from the Inhibit (8) connection on the UPS to the Inhibit terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

16 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

This diagram shows a 1606-XLS240-UPS power supply battery that is connected to a CompactLogix 5480 controller

5069-L4200ERMW

UPS Ready

Buffering

Battery Fail

Inhibit

(7) Inhibit +

(8) Inhibit ndash

24V DC

Power

Supply

Ready

(1) (2)

+ ndash + ndash + ndash + ndash

N L PE

Buffering

(3) (4)

Battery Fail

(5) (6)

12V DC Battery

(for example 1606-XLSBATASSY1)

+ ndash

DC-UPS

(1606-XLS240-UPS)

24V

IN

12V

BAT

24V

OUT

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 17

CompactLogix 5480 Controllers

Disconnect Wires from the RTBsIf necessary complete these tasks to disconnect wires from any RTB on the controller

1 Turn the screwdriver counter-clockwise to open the terminal

2 Remove the wire

Install Compact 5000 IO ModulesComplete one of the following

bull If you do not use local Compact 5000 IO modules in the system proceed to Install the End Cap on page 18

bull If you use local Compact 5000 IO modules in the system install the modules to the right side of the controller

After the IO modules are installed install the end cap on the right side of the last IO module in the system For more information on how to install the end cap see page 18

For more information on how to install Compact 5000IO modules see the installation instructions available with each Compact 5000 IO module catalog number

Install the End CapYou must install an end cap on the right side of the last module in a CompactLogix 5480 system The end cap covers the exposed interconnections on the last module in the system If you do not install the end cap before powering the system equipment damage or injury from electric shock can result

If you do not intend to install Compact 5000 IO modules to the system before you turn on power to the controller install the end cap

1 Align the end cap with the interlocking pieces on the controller

2 Push the end cap toward the DIN rail until it locks into place

Power the System

After the end cap is installed on the last module in the system turn on power to the MOD power RTB and the SA power RTB

IMPORTANT Consider the following before you power the system

bull Make sure to remove the debris shield from the controller before power-up

bull As noted previously you must install working controller firmware to use the COS on the controller There are two ways to install working firmware The ways are described beginning on page 23

One of the methods to install working controller firmware

uses the SD card that ships with the controller

ndash If you intend to use the SD card to install working

controller firmware go to Use a Secure Digital Card

to Install Controller Firmware on page 24

Complete the steps described in that section apply

power to the controller and return to the next

section that is Set the Network Internet Protocol

(IP) Addresses on page 19

ndash If you do not intend to use the SD card to install

working controller firmware turn on the power now

and proceed to the next section

Top Interlocking

Pieces

End Cap

Bottom Interlocking

Pieces

18 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Set the Network Internet Protocol (IP) AddressesYou must set an IP address on Ethernet ports for the controller to operate on an EtherNetIP network via that port

Out-of-the-box the following applies to Ethernet ports A1 A2 and B1

bull The ports are DHCP-enabled and the IP address is set automatically via a DHCP server

If there is no DHCP server available to set the IP address you must set the IP address manually

bull If ports A1 and A2 are configured to use DLRLinear mode you set only one IP address that is used on both ports

bull Control ports must use unique subnets

When ports A1 and A2 are configured to use DLRLinear mode however they use the same subnet because they are configured as one port

You can use one of the following to set the IP address on the controller when it is in the out-of-the-box condition

bull DHCP server

bull BOOTP DHCP EtherNetIP Commissioning tool version 30200 or later

bull RSLinx Classic software version 41000 or later

bull FactoryTalk Linx software version 61000 or later

bull Logix Designer application version 320100 or later

For more information on how to set or change the IP address on a CompactLogix 5480 controller see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

Connect the Controller to an EtherNetIP Network

Use an RJ45 cable to connect the controller to an EtherNetIP network

1 If needed wire the RJ45 connector as shown

2 Connect RJ45 cables to the controller Ethernet ports

IMPORTANT Before you can connect a CompactLogix 5480 controller to an

EtherNetIP network you must first install the network and

its components

This section assumes that the EtherNetIP network is

installed

Connector Number

Color

1585J 8-pin Cables with Support for 101001000 Mbps

1585J 8-pin Cables with Support for 10100 Mbps

1585J 4-pin Cables with Support for 10100 Mbps

1WhiteOrange

BI_DA+ TxData +

2 Orange BI_DA- TxData -

3WhiteGreen

BI_DB+ Recv Data +

4 Blue BI_DC+ Unused mdash

5 WhiteBlue BI_DC- Unused mdash

6 Green BI_DB- Recv Data -

7WhiteBrown

BI_DD+ Unused mdash

8 Brown BI_DD- Unused mdash

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 19

CompactLogix 5480 Controllers

Remove and Replace the Controller

1 Turn off power to the MOD power and the SA power RTBs

2 If there are local Compact 5000 IO modules in the system remove them If not skip to step 3

3 Disconnect wires from the RTBs

For more information see Disconnect Wires from the RTBs on page 18

4 Pull the RTB handles to remove the RTBs

IMPORTANT When you remove MOD power from the controller you shut down

power to all modules in the CompactLogix 5480 system That is

all system-side is removed When you remove SA power from the

controller all field-side power that is provided by the controller is

removed If SA power that is provided via a 5069-FPD field

potential distributor the system does not lose SA power to the

right of the field potential distributor

In this case you must use a separate power source for the SA

power RTB on the field potential distributor

We strongly recommend that before you remove MOD power or

SA power that you take the appropriate actions to help prevent

unintended consequences that can result from a system power

shutdown

Despite the removal of power from SA RTBs on the controller or

field potential distributor the 5069-OB16 and 5069-OB16F

modules continue to receive field-side power The modules

receive power from an external power source that is connected to

the LA (+) and LA (ndash) module terminals

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

UPS Control RTB

MOD Power RTB

SA Power RTB

20 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

5 Remove all cables from the controller

6 Push down on the front of the DIN rail latches

A click indicates that the DIN rail latches are open

If the DIN rail latches fail to remain in the open position hold them down

7 Pull the controller off the DIN rail

8 Repeat the installation steps that are described beginning at Install the Controller onto the DIN Rail on page 9

9 Apply MOD power and if necessary SA power to the system

Replace the FansThe CompactLogix 5480 controller uses fans at the top and bottom of the controller to help maintain lower operating temperatures when the controller is operating

Fan use includes speed control and monitoring Faults indicate fan operating conditions as follows

bull Minor faults - Triggered when a fan is not operating at the requested speed or if a fan fails to operate at all

In your Logix Designer application project you can use the Minor Faults tab on the Controller Properties dialog box to monitor for these faults

bull Major fault - Triggered if both fans fail and the controller goes over the maximum operating temperature

In this case the controller stops operating

You can order replacement fans Replacement fans come in pairs The fans are unique by position and keyed to help make sure that you install the correct fan in each position

The fans are labeled Fan 1 - Top and Fan 2 - Bottom

Consider the following

bull We recommend that you replace the fans in pairs That is if you replace the one fan we recommend that you replace the other fan too

bull You can replace fans during controller operation The fans support removal and insertion under power

bull Do not remove both fans at once if the controller is operating That is remove a fan and install the replacement fan before you remove the other fan

Remove the Top Fan

1 Push up on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

TIP In your Logix Designer application project you can

use the Major Faults tab on the Controller

Properties dialog box to monitor for this fault

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

R

B

F

Open Position

IMPORTANT If you replace fans while the controller is operating

do not touch live voltage components

TIP If the hinges do not disengage when you push up on the front of the

fan then use a screwdriver as a pry tool

5069-L4200ERMW

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 21

CompactLogix 5480 Controllers

2 Pull the fan out of the slot at the top of the controller

Install the Top Replacement Fan

1 Insert the top replacement fan into the slot at the top of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push down on the top replacement fan until it clicks in place

Remove the Bottom Fan

1 Push the down on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

2 Pull the fan out of the slot at the bottom of the controller

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

TIP If the hinges do not disengage when you push down on the front of

the fan then use a screwdriver as a pry tool

5069-L4200ERMW

5069-L4200ERMW

22 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Bottom Replacement Fan

1 Insert the bottom replacement fan into the slot at the bottom of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push up on the bottom replacement fan until it clicks in place

Use the COS For Windows-based ComputingThe COS on a CompactLogix 5480 controller runs in parallel with the Logix control engine You are not required to use the COS

You can use the following methods to install working controller firmware when the controller is in the out-of-box state

bull ControlFLASHtrade or ControlFLASH Plustrade softwarebull Secure Digital (SD) card

Use a Flash Programming Tool to Install Controller FirmwareYou can use ControlFLASH and ControlFLASH Plus software to install controller firmware

The following requirements apply when you use ControlFLASH or ControlFLASH Plus to install working controller firmware

bull You must use one of the followingndash ControlFLASH software version 150100 or laterndash ControlFLASH Plus version 20000 or later

bull You must use a Linx-based software application with your flash programming toolndash With ControlFLASH software you can use RSLinx

Classic Lite RSLinx Classic RSLinx Enterprise or FactoryTalk Linx

ndash With ControlFLASH Plus software you must use FactoryTalk Linx

Minimum software versions apply with Linx-based software For more information on the minimum software version requirements see the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

5069-L4200ERMW

5069-L4200ERMW

IMPORTANT Before you can use the COS you must install working controller firmware The requirement applies even if you

are not using the controller for real-time control If you do not

install working controller firmware the COS does not start

In the out-of-box state the controller uses firmware revision

1xxx On a CompactLogix 5480 controller the minimum

working controller firmware is revision 32012

TIP We recommend that you connect your peripherals to the

ports that are dedicated to COS use before you install

controller firmware

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 23

CompactLogix 5480 Controllers

Download the Flash Programming Tool

ControlFLASH and ControlFLASH Plus software are available from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

Download the installation files and install the software

Download the Controller Firmware

After the flash programming tool is installed download the controller firmware from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

The initial download is a exe file You use the Rockwell Automation Download Manager to extract a dmk from the downloaded file

Install the Controller Firmware

To install the controller firmware via a flash programming tool you complete the following steps

1 To start the tool click StartgtAll ProgramsgtFlashing Programming ToolsgtControlFLASH or ControlFLASH Plus

2 Follow the prompts to complete the following stepsa Choose the controllerb Select the firmware revisionc Install the controller firmware

A dialog box confirms that the installation was successful

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use a flash programming tool to install controller firmware see the following

bull ControlFLASH Firmware Upgrade Kit User Manual publication 1756-UM105

bull ControlFLASH Plus Quick Start Guide publication CFP-QS001

bull CompactLogix 5480 Controllers User Manual publication 5069-UM002

Use a Secure Digital Card to Install Controller FirmwareYou can use an SD card to install controller firmware CompactLogix 5480 controllers ship with an SD card installed behind the front door on the controller

To use an SD card to install controller firmware complete the following steps

1 Before you turn on power to the controller remove the SD card from the controller

2 Install the SD card into another working CompactLogix 5480 controller that has a Logix Designer application project on it

3 Save the project to the SD card

4 Remove the SD card from the working controller and reinstall it in the new controller

5 Turn on power to the new controller

When the new controller powers up it automatically updates the firmware to the revision that is stored on the SD card

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use the SD card with the controller after valid firmware is installed and the controller is powered see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

IMPORTANT These steps only highlight the major tasks that you

complete to install controller firmware with ControlFLASH

To successfully install controller firmware you must complete other tasks that are not described here

For complete information on how to install controller

firmware see the publications listed at the end of the section

IMPORTANT To install controller firmware on a new CompactLogix 5480

controller via an SD card you must have another controller of

the same type that is already working

The SD card method requires that you save the Logix Designer

application project from the working controller to the SD card

before you use it in the new controller

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

SD Card Slot

24 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpecificationsThis table lists a subset of controller specifications For a complete list of specifications see the CompactLogix 5380 Compact GuardLogixreg 5380 and CompactLogix 5480 Controllers Specifications Technical Data publication 5069-TD002

Environmental Specifications - CompactLogix 5480 Controllers

Attribute 5069-L430ERMW 5069-L450ERMW 5069-4100ERMW 5069-L4200ERMW

Temperature operating

IEC 60068-2-1 (Test Ad Operating Cold)

IEC 60068-2-2 (Test Bd Operating Dry Heat)

IEC 60068-2-14 (Test Na Operating Thermal Shock)

0 degC lt Ta lt +60 degC

(+32 degF lt Ta lt +140 degF)

Temperature surrounding air max 60 degC (140 degF)

Enclosure Type Rating None (open-style)

Voltage and current ratings

MOD Power voltage range 18hellip32V DC

MOD Power power max 72 W

MOD Power current typical 4 A

MOD Power inrush 4 A for 15 ms

MOD Power Passthrough(1) 6 A 18hellip32V DC

MOD Power current rating max10 A

Do not exceed 10 A current draw at the MOD power RTB(4)

SA Power voltage ranges(2) 0hellip32V DC

0hellip240V AC 47hellip63 Hz

SA Power current max (2) 10 mA (DC power)

25 mA (AC power)

SA Power Passthrough(2) (3) 999 A 0hellip32V DC

9975 A 0hellip240V AC 47hellip63 Hz

SA Power current rating max(2) Do not exceed 10 A current draw at the SA power RTB

Isolation voltage

300V (continuous) Basic Insulation Type SA and MOD Power to Backplane

300V (continuous) Basic Insulation Type SA to MOD Power

300V (continuous) Basic Insulation Type Ethernet to Backplane

300V (continuous) Double Insulation Type Ethernet to MOD Power

300V (continuous) Double Insulation Type Ethernet to SA Power

50V (continuous) Functional Insulation Type Ethernet to USB ports and DisplayPort

300V (continuous) Basic Insulation Type USB ports and DisplayPort to Backplane

300V (continuous) Double Insulation Type USB ports and DisplayPort to MOD Power

300V (continuous) Double Insulation Type USB ports and DisplayPort to SA Power

No isolation between Ethernet ports

Type tested at 1500V AC for 60 s

Wire size

5069-RTB4-SCREW 5069-RTB6-SCREW connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 35 mm (014 in) max diameter including insulation single wire connection only

5069-RTB4-UPS connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 29 mm (011 in) max diameter including insulation single wire connection only

Ethernet connections

Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2

Insulation-stripping length 5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 12 mm (047 in)

Terminal block torque5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 04 Nbullm (35 lbbullin)

ATTENTION Do not wire more than two conductors on one RTB terminal

(1) Maximum level of MOD power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(2) SA power specifications are based on the number and type of Compact 5000 IO modules that are used in the system If the set of IO modules that is used in the system require AC and DC voltage you must install a 5069-FPD field

potential distributor to separate the module types

(3) Maximum level of SA power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(4) Remember MOD power usage includes the total power that the controller and local Compact 5000 IO modules use If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000 IO

modules can draw a maximum of 10 A in addition to the current that the controller draws

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 25

CompactLogix 5480 Controllers

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation

You can view or download publications at httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage To order paper copies of technical documentation contact your local Allen-Bradley distributor or Rockwell Automationreg sales representative

Resource Description

CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069-TD002

Provides specifications and other technical data for CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 controllers

CompactLogix 5480 Controllers User Manual publication 5069-UM002 Describes how to configure operate and monitor CompactLogix 5480 controllers

Industrial Automation Wiring and Grounding Guidelines publication 1770-41 Provides general guidelines for installing a Rockwell Automationreg industrial system

Product Certifications website rokautocertifications Provides declarations of conformity certificates and other certification details

26 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 2: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

CompactLogix 5480 Controllers

The CompactLogix 5480 controllers can operate in various applications including the use of local Compact 5000trade IO modules and remote IO modules and Integrated Motion over an EtherNetIPtrade network The controllers offer the following

bull Real-time control in industrial control systemsbull Windows-based computing on the COS that is independent of the Logix control enginebull High-speed bus packet transfer ratebull High-speed IO module communication motion control and use of Device Level Ring (DLR) Linear and Star EtherNetIP topologies

bull Multiple ports for use with the Logix control engine on the controller includingndash One USB programming port for temporary connectionndash One Gigabit Ethernet ports for high-speed IO communication and motion control

bull Multiple ports for use with the COS on the controller includingndash One Gigabit Ethernet port as a dedicated OS network interfacendash An integrated DisplayPort for high definition monitor connectivityndash Two USB 30 ports for OS peripheral and expanded data storage capability

You use the Studio 5000 Logix Designerreg application to configure CompactLogix 5480 controllers

For more information on the components that are required to install a CompactLogix 5480 controller see page 6 For more information on how to use the controller after you install it see the publications that are listed in Additional Resources on page 26

Summary of ChangesThis publication was revised for the following changes

bull Add the new controller catalog numbers that is the 5069-L430ERMW 5069-L450ERMW 5069-L4100ERMW and 5069-L4200ERMW

bull Provide more information on the COS For more information see Use the COS For Windows-based Computing on page 23

2 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

ATTENTION Read this document and the documents listed in the Additional Resources section about installation configuration and operation of this equipment before you install configure operate or maintain

this product Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes laws and standards

Activities including installation adjustments putting into service use assembly disassembly and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of

practice

If this equipment is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired

ATENCIOacuteN Antes de instalar configurar poner en funcionamiento o realizar el mantenimiento de este producto lea este documento y los documentos listados en la seccioacuten Recursos adicionales acerca de la

instalacioacuten configuracioacuten y operacioacuten de este equipo Los usuarios deben familiarizarse con las instrucciones de instalacioacuten y cableado y con los requisitos de todos los coacutedigos leyes y estaacutendares vigentes

El personal debidamente capacitado debe realizar las actividades relacionadas a la instalacioacuten ajustes puesta en servicio uso ensamblaje desensamblaje y mantenimiento de conformidad con el coacutedigo de

praacutectica aplicable

Si este equipo se usa de una manera no especificada por el fabricante la proteccioacuten provista por el equipo puede resultar afectada

ATENCcedilAtildeO Leia este e os demais documentos sobre instalaccedilatildeo configuraccedilatildeo e operaccedilatildeo do equipamento que estatildeo na seccedilatildeo Recursos adicionais antes de instalar configurar operar ou manter este produto Os

usuaacuterios devem se familiarizar com as instruccedilotildees de instalaccedilatildeo e fiaccedilatildeo aleacutem das especificaccedilotildees para todos os coacutedigos leis e normas aplicaacuteveis

Eacute necessaacuterio que as atividades incluindo instalaccedilatildeo ajustes colocaccedilatildeo em serviccedilo utilizaccedilatildeo montagem desmontagem e manutenccedilatildeo sejam realizadas por pessoal qualificado e especializado de acordo com o

coacutedigo de praacutetica aplicaacutevel

Caso este equipamento seja utilizado de maneira natildeo estabelecida pelo fabricante a proteccedilatildeo fornecida pelo equipamento pode ficar prejudicada

ВНИМАНИЕ Перед тем как устанавливать настраивать эксплуатировать или обслуживать данное оборудование прочитайте этот документ и документы перечисленные в разделе

laquoДополнительные ресурсыraquo В этих документах изложены сведения об установке настройке и эксплуатации данного оборудования Пользователи обязаны ознакомиться с инструкциями по

установке и прокладке соединений а также с требованиями всех применимых норм законов и стандартов

Все действия включая установку наладку ввод в эксплуатацию использование сборку разборку и техническое обслуживание должны выполняться обученным персоналом в соответствии с

применимыми нормами и правилами

Если оборудование используется не предусмотренным производителем образом защита оборудования может быть нарушена

ACHTUNG Lesen Sie dieses Dokument und die im Abschnitt bdquoWeitere Informationenldquoaufgefuumlhrten Dokumente die Informationen zu Installation Konfiguration und Bedienung dieses Produkts enthalten bevor

Sie dieses Produkt installieren konfigurieren bedienen oder warten Anwender muumlssen sich neben den Bestimmungen aller anwendbaren Vorschriften Gesetze und Normen zusaumltzlich mit den Installations- und

Verdrahtungsanweisungen vertraut machen

Arbeiten im Rahmen der Installation Anpassung Inbetriebnahme Verwendung Montage Demontage oder Instandhaltung duumlrfen nur durch ausreichend geschulte Mitarbeiter und in Uumlbereinstimmung mit den

anwendbaren Ausfuumlhrungsvorschriften vorgenommen werden

Wenn das Geraumlt in einer Weise verwendet wird die vom Hersteller nicht vorgesehen ist kann die Schutzfunktion beeintraumlchtigt sein

ATTENTION Lisez ce document et les documents listeacutes dans la section Ressources compleacutementaires relatifs agrave lrsquoinstallation la configuration et le fonctionnement de cet eacutequipement avant drsquoinstaller configurer

utiliser ou entretenir ce produit Les utilisateurs doivent se familiariser avec les instructions drsquoinstallation et de cacircblage en plus des exigences relatives aux codes lois et normes en vigueur

Les activiteacutes relatives agrave lrsquoinstallation le reacuteglage la mise en service lrsquoutilisation lrsquoassemblage le deacutemontage et lrsquoentretien doivent ecirctre reacutealiseacutees par des personnes formeacutees selon le code de pratique en vigueur

Si cet eacutequipement est utiliseacute drsquoune faccedilon qui nrsquoa pas eacuteteacute deacutefinie par le fabricant la protection fournie par lrsquoeacutequipement peut ecirctre compromise

ATTENZIONE Prima di installare configurare ed utilizzare il prodotto o effettuare interventi di manutenzione su di esso leggere il presente documento ed i documenti elencati nella sezione ldquoAltre risorserdquo

riguardanti lrsquoinstallazione la configurazione ed il funzionamento dellrsquoapparecchiatura Gli utenti devono leggere e comprendere le istruzioni di installazione e cablaggio oltre ai requisiti previsti dalle leggi codici

e standard applicabili

Le attivitagrave come installazione regolazioni utilizzo assemblaggio disassemblaggio e manutenzione devono essere svolte da personale adeguatamente addestrato nel rispetto delle procedure previste

Qualora lrsquoapparecchio venga utilizzato con modalitagrave diverse da quanto previsto dal produttore la sua funzione di protezione potrebbe venire compromessa

DİKKAT Bu uumlruumlnuumln kurulumu yapılandırılması işletilmesi veya bakımı oumlncesinde bu dokuumlmanı ve bu ekipmanın kurulumu yapılandırılması ve işletimi ile ilgili İlave Kaynaklar boumlluumlmuumlnde yer listelenmiş

dokuumlmanları okuyun Kullanıcılar yuumlruumlrluumlkteki tuumlm youmlnetmelikler yasalar ve standartların gereksinimlerine ek olarak kurulum ve kablolama talimatlarını da oumlğrenmek zorundadır

Kurulum ayarlama hizmete alma kullanma parccedilaları birleştirme parccedilaları soumlkme ve bakım gibi aktiviteler sadece uygun eğitimleri almış kişiler tarafından yuumlruumlrluumlkteki uygulama youmlnetmeliklerine uygun şekilde

yapılabilir

Bu ekipman uumlretici tarafından belirlenmiş amacın dışında kullanılırsa ekipman tarafından sağlanan koruma bozulabilir

POZOR Než začnete instalovat konfigurovat či provozovat tento vyacuterobek nebo provaacutedět jeho uacutedržbu přečtěte si tento dokument a dokumenty uvedeneacute v čaacutesti Dodatečneacute zdroje ohledně instalace konfigurace

a provozu tohoto zařiacutezeniacute Uživateleacute se musejiacute vedle požadavků všech relevantniacutech vyhlaacutešek zaacutekonů a norem nutně seznaacutemit takeacute s pokyny pro instalaci a elektrickeacute zapojeniacute

Činnosti zahrnujiacuteciacute instalaci nastaveniacute uvedeniacute do provozu užiacutevaacuteniacute montaacutež demontaacutež a uacutedržbu musiacute vykonaacutevat vhodně proškolenyacute personaacutel v souladu s přiacuteslušnyacutemi provaacuteděciacutemi předpisy

Pokud se toto zařiacutezeniacute použiacutevaacute způsobem neodpoviacutedajiacuteciacutem specifikaci vyacuterobce může byacutet narušena ochrana kterou toto zařiacutezeniacute poskytuje

UWAGA Przed instalacją konfiguracją użytkowaniem lub konserwacją tego produktu należy przeczytać niniejszy dokument oraz wszystkie dokumenty wymienione w sekcji Dodatkowe źroacutedła omawiające

instalację konfigurację i procedury użytkowania tego urządzenia Użytkownicy mają obowiązek zapoznać się z instrukcjami dotyczącymi instalacji oraz oprzewodowania jak roacutewnież z obowiązującymi kodeksami

prawem i normami

Działania obejmujące instalację regulację przekazanie do użytkowania użytkowanie montaż demontaż oraz konserwację muszą być wykonywane przez odpowiednio przeszkolony personel zgodnie z

obowiązującym kodeksem postępowania

Jeśli urządzenie jest użytkowane w sposoacuteb inny niż określony przez producenta zabezpieczenie zapewniane przez urządzenie może zostać ograniczone

OBS Laumls detta dokument samt dokumentet som staringr listat i avsnittet Oumlvriga resurser om installation konfigurering och drift av denna utrustning innan du installerar konfigurerar eller boumlrjar anvaumlnda eller utfoumlra

underharingllsarbete paring produkten Anvaumlndare maringste bekanta sig med instruktioner foumlr installation och kabeldragning foumlrutom krav enligt gaumlllande koder lagar och standarder

Aringtgaumlrder som installation justering service anvaumlndning montering demontering och underharingllsarbete maringste utfoumlras av personal med laumlmplig utbildning enligt laumlmpligt bruk

Om denna utrustning anvaumlnds paring ett saumltt som inte anges av tillverkaren kan det haumlnda att utrustningens skyddsanordningar foumlrsaumltts ur funktion

LET OP Lees dit document en de documenten die genoemd worden in de paragraaf Aanvullende informatie over de installatie configuratie en bediening van deze apparatuur voordat u dit product installeert

configureert bediend of onderhoudt Gebruikers moeten zich vertrouwd maken met de installatie en de bedradingsinstructies naast de vereisten van alle toepasselijke regels wetten en normen

Activiteiten zoals het installeren afstellen in gebruik stellen gebruiken monteren demonteren en het uitvoeren van onderhoud mogen uitsluitend worden uitgevoerd door hiervoor opgeleid personeel en in

overeenstemming met de geldende praktijkregels

Indien de apparatuur wordt gebruikt op een wijze die niet is gespecificeerd door de fabrikant dan bestaat het gevaar dat de beveiliging van de apparatuur niet goed werkt

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 3

CompactLogix 5480 Controllers

Environment and Enclosure

ATTENTION This equipment is intended for use in a Pollution Degree 2 industrial environment in overvoltage Category II applications (as defined in ENIEC

60664-1) at altitudes up to 2000 m (6562 ft) without derating

This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such

environments

This equipment is supplied as open-type equipment for indoor use It must be mounted within an enclosure that is suitably designed for those specific

environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts The enclosure must

have suitable flame-retardant properties to prevent or minimize the spread of flame complying with a flame spread rating of 5VA or be approved for the

application if nonmetallic The interior of the enclosure must be accessible only by the use of a tool Subsequent sections of this publication may contain more

information regarding specific enclosure type ratings that are required to comply with certain product safety certifications

In addition to this publication see the following

bull Industrial Automation Wiring and Grounding Guidelines publication 1770-41 for more installation requirements

bull NEMA 250 and ENIEC 60529 as applicable for explanations of the degrees of protection provided by enclosures

Prevent Electrostatic Discharge

ATTENTION This equipment is sensitive to electrostatic discharge which can cause internal damage and affect normal operation Follow these guidelines when

you handle this equipment

bull Touch a grounded object to discharge potential static

bull Wear an approved grounding wriststrap

bull Do not touch connectors or pins on component boards

bull Do not touch circuit components inside the equipment

bull Use a static-safe workstation if available

bull Store the equipment in appropriate static-safe packaging when not in use

ATTENTION

bull In case of malfunction or damage no attempts at repair should be made The controller should be returned to the manufacturer for repair Do not dismantle the controller

bull This equipment is certified for use only within the surrounding air temperature range of 0hellip60 degC (32hellip140 degF) The equipment must not be used outside of this range

bull The USB programming port is intended for temporary local programming purposes only and not intended for permanent connection The USB programming port connection is not to exceed 30 m (984 ft) and must not contain hubs You must connect the programming equipment to a ground system that is common with the controller

bull Devices that are connected to USB 30 ports must reside in the same control enclosure as the controller This requirement applies to devices that are powered by the USB 30 ports or not You must connect the devices to a ground system that is common with the controller Alternatively you can connect the device to the common ground system via a USB hub that provides galvanic isolation

bull USB 30 port connections are not to exceed 30 m (984 ft)

bull DisplayPort cables or adapters that are used with this product must be certified by VESA A list of certified equipment and cables is on the VESA website (wwwvesaorg) Use of non-certified cables and adapters can cause damage or improper operation DisplayPort connections are not to exceed 30 m (984 ft)

bull Displays that are connected to DisplayPort must connect to a ground system that is common with the controller Alternatively displays can be connected by a display extender that is connected to the common ground system with the controller and provides galvanic isolation

bull Use only a soft dry anti-static cloth to wipe down equipment Do not use any cleaning agents

Electrical Safety Considerations

ATTENTION Do not wire more than 2 conductors on a single RTB terminal

Waste Electrical and Electronic Equipment (WEEE)

At the end of its life this equipment should be collected separately from any unsorted municipal waste

4 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

About the ControllerThe following graphic shows a CompactLogix 5480 controller

IMPORTANTAny illustrations charts sample programs and layout examples that are shown in this publication are intended solely for the purposes of example Since

there are many variables and requirements that are associated with any particular installation Rockwell Automation does not assume responsibility or

liability for actual use that is based on the examples that are shown in this publication

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

1

6

7

9

8

2

3

4

14

11

16

10

5

1312

15

18

20

17

19

Front View

Bottom View

22

21

23

CompactLogix 5480 Controller Parts

Number Item Description

1 DIN rail latches Secure adapter to DIN rail

2 Mode switch Lets you choose the controller operating mode

3 SD card slot Location for SD card

4 Reset button Resets the controller to factory default condition

5 Four-character displayScrolls information about the controller such as firmware revision or project status

6 USB programming port Provides temporary connection to download projects

7 Ethernet port B1Lets the controller connect to the following networksbull Enterprise-level networkbull Device-level network

8 Ethernet port A1Lets the controller connect to device-level networks

9 Ethernet port A2

10Network and link status indicators for ports B1 A1 and A2 Show the state of the Ethernet ports and network

communication activity on each port

11Speed and link status indicators for port X1

12 Bottom fanHelps regulate controller temperature

Controller ships with fans installed You can replace fans if necessary

13Controller status indicators

Show the state of the controller in multiple respects

14 Top fanHelps regulate controller temperature

Controller ships with fans installed You can replace fans if necessary

15MOD power and SA power status indicators

Show the state of module (MOD) power and sensor actuator (SA) power respectively

16 UPS Control RTB

Connector for control signals to and from an uninterruptible power supply (UPS) that are used to support a controlled shutdown upon incoming power loss

17MOD power bus connector

MOD power bus connection that passes MOD power to the next local Compact 5000 IO module in the system

18 MOD power RTBConnector for external power supply to provide MOD power to the system

19 SA power bus connectorSA power bus connection that passes SA power to the next local Compact 5000 IO module in the system

20 SA power RTBConnector for external power supply to provide SA power to the systemlsquo

21 Ethernet port X1 Used with the COS on the controller

22 USB 30 portsConnectors for peripherals that are used with the COS on the controller(2)

(2) Devices that are connected to the controller via a USB 30 port must reside in the same control enclosure as

the controller This requirement applies to devices that are powered by the USB 30 ports or not You must

connect the devices to a ground system that is common with the controller Alternatively you can connect

the device to the common ground system via a USB hub that provides galvanic isolation

23DisplayPort connection(1)

(1) Any DisplayPort cables or adapters that are used with this product must be certified by VESA A list of

certified equipment and cables is on the VESA website (wwwvesaorg) Use of non-certified cables and

adapters can cause damage or improper operation

Connector to use a display with the COS on the controller

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 5

CompactLogix 5480 Controllers

Required System ComponentsBefore you install the controller verify that you have the following components

System PlanningFollow these rules when planning your system configuration

bull If the CompactLogix 5480 system includes only a controller you can mount the DIN rail in any orientation

bull If your CompactLogix 5480 system includes local Compact 5000 IO modules you must mount the DIN rail horizontally

bull The controller is the leftmost component in the system

bull Local Compact 5000 IO modules are installed to the right of the controller

bull The controller supports as many as 31 local Compact 5000 IO modules

bull Before power-up make sure that the end cap is installed on the right side of the controller or rightmost local Compact 5000 IO module if IO modules are used

Components Used to Install a CompactLogix 5480 Controller

Component Description

Removable Terminal Blocks (RTB)

An RTB that is used to connect MOD power (system-side power) to the controller - 5069-RTB4-SCREW RTB (Ships with the controller)

An RTB that is used to connect SA power (field-side power) - 5069-RTB6-SCREW RTB (Ships with the controller)

An RTB that is used to connect UPS (uninterruptible power) - 5069-L4UPSRTB (Ships with the controller)

External power supply for MOD power

A power supply that is adequately sized to provide MOD power that is system-side power to the CompactLogix 5480 system

For more information see System Power Considerations on page 8

External power supply for SA power

A power supply that is adequately sized to provide SA power that is field-side power to the CompactLogix 5480 system

IMPORTANT SA power is only required if your application includes local Compact 5000 IO modules that are connected to devices that use SA power

For more information see System Power Considerations on page 8

External uninterruptible power supply for UPS control signals

A power supply that provides UPS control signals so that the controller can save the state of the program when power is lost A UPS is only required if your system uses UPS control signals

For more information see Connect Control Signals Via UPS Control RTB on page 14

Tools

You use the following tools to wire the RTBsbull Screwdriverbull Wire stripperbull Wires

For more information on available wire sizes and wire insulation-stripping length see Specifications on page 25

DIN rail

Compatible zinc-plated chromate steel DIN rail

You can use the following DIN railsbull EN50022 - 35 x 75 mm (138 x 030 in)bull EN50022 - 35 x 15 mm (138 x 060 in)

EtherNetIP network components

If your CompactLogix 5480 controller operates on an EtherNetIP network you must install the network and all required components

Software

When you install the controller you assign IP addresses on the controller You can use the following to assign IP addresses

bull DHCP server

bull BOOTP DHCP EtherNetIP Commissioning tool version 30200 or later

bull RSLinxreg Classic software version 41000 or later

bull FactoryTalkreg Linx version 61000 or later

bull Logix Designer application version 320100 or later

For more information see Set the Network Internet Protocol (IP) Addresses on page 19

ATTENTION Do not discard the end cap Use this end cap

to cover the exposed interconnections on the last module

on the DIN rail Failure to do so could result in equipment

damage or injury from electric shock

Components Used to Install a CompactLogix 5480 Controller

Component Description

6 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpacingMaintain spacing from enclosure walls wireways and adjacent equipment Ambient temperature is higher at the top of an enclosed cabinet

The minimum distance on of a system that includes only a CompactLogix 5480 controller is as follows

bull 2500 mm (098 in) between the sides and the cabinet

bull 2500 mm (098 in) between the front of the controller and the cabinet

bull 5000 mm (196 in) between the top and bottom and the cabinet

We recommend that you install the controller near the bottom of the enclosure where ambient temperature is lower

Enclosure SelectionThis example is provided to help you size an enclosure for your CompactLogix 5480 controller You need heat dissipation data from all components that are planned for your enclosure to calculate the enclosure size

With no active method of heat dissipation for example air conditioning either of the following approximate equations can be used for a metal cabinet

The maximum ambient rating of the CompactLogix 5480 controller is 60 degC (140 degF) If the maximum external cabinet temperature is 20 degC (68 degF) then T=40

In this example with only the controller the heat dissipation is 72 W that is the sum of all components in the enclosure In the following equation T=40 and Q=72

In this example the enclosure must have a minimum exterior surface of 0386 m2

If any portion of the enclosure cannot transfer heat exclude that value from the calculation

The minimum installation clearance for a CompactLogix 5480 controller is 26700 x 18400 x 15200 mm (1050 x 725 x 600 in) HxWxD

The standard cabinet depth in this example is 15420 mm (600 in)

To meet cooling and clearance requirements in this example the cabinet must be approximately 30480 x 35560 x 15420 mm(1200 x 1400 x 600 in) HxWxD

A = 2DW +2DH + 2WH

A = 2 x (01542 x 03556) + 2 x (01542 x 03048) + 2 x (03556 x 03048) = 04204 m2

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

Top

Bottom

SideSide

End cap

Cabinet

Metric Imperial

Where

bull T = Temperature difference between inside air and outside ambient (degC)

bull Q = Heat that is generated in enclosure (Watts)

bull A = Enclosure surface area (m2)

Where

bull T = Temperature difference between inside air and outside ambient (degF)

bull Q = Heat that is generated in enclosure (Watts)

bull A = Enclosure surface area (ft2)

The exterior surface of all six sides of an enclosure is calculated as

A = 2dw + 2dh + 2wh

Where d (depth) w (width) and h (height) are in meters

The exterior surface of all six sides of an enclosure is calculated as

A = (2dw + 2dh + 2wh) 144

Where d (depth) w (width) and h (height) are in inches

038Q

180T - 110

A =

408Q

T - 110

A =

038(7200)

180(4000) - 110A =

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 7

CompactLogix 5480 Controllers

This example uses the following conditions

bull All sides of the enclosure transfer heatbull Only the CompactLogix 5480 controller is installedbull Ambient temperature = 20 degC (68 degF)

DimensionsThe controller dimensions are as follows

Ground ConsiderationsYou must ground DIN rails according to the Industrial Automation Wiring and Grounding Guidelines publication 1770-41

You can use the following DIN rails

bull EN50022 - 35 x 75 mm (138 x 030 in)bull EN50022 - 35 x 15 mm (138 x 060 in)

System Power ConsiderationsThe CompactLogix 5480 controller provides power to a CompactLogix 5480 system via RTBs that are connected to external power supplies and installed on the controller

The RTBs provide the following power to the system

IMPORTANT If any of the following conditions exist the enclosure must be larger

bull Any sides of the enclosure cannot transfer heat

bull More equipment is included in the system

bull Ambient temperature is higher than 20 degC (68 degF)

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

13021 mm

(513 in)

16620 mm

(654 in)

12654 mm

(498 in)

12002 mm

(473 in)

13366 mm

(526 in)

16000 mm

(630 in)

ATTENTION This product is grounded through the DIN rail to

chassis ground Use zinc-plated chromate-passivated steel DIN rail

to assure proper grounding The use of other DIN rail materials (for

example aluminum or plastic) that can corrode oxidize or are poor

conductors can result in improper or intermittent grounding

Secure DIN rail to mounting surface approximately every 200 mm

(78 in) and use end-anchors appropriately Be sure to ground the

DIN rail properly See Industrial Automation Wiring and Grounding

Guidelines Rockwell Automationreg publication 1770-41 for more

information

Power Type Description

MOD Power

System-side power that is used to operate the CompactLogix 5480 system MOD power is provided through the MOD power RTB and passed across the MOD power bus bull The total continuous current draw across the MOD power bus must not be

more than 10 A max at 1832V DC

You must calculate the total MOD power that the controller and all local Compact 5000 IO modules draw to make sure that no more than 10 A of MOD power is drawn(1)

bull Confirm that the external MOD power supply is adequately sized for the total MOD power bus current draw in the system including the MOD power inrush current requirements

(1) If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000

IO modules can draw a maximum of 10 A in addition to the current the controller draws

SA Power

Field-side power that can be used to power field-side devices that are connected to some Compact 5000 IO modules SA power is provided through the SA power RTB and passed across the SA power bus

bull SA power is only required if your application includes local Compact 5000 IO modules that are connected to devices that use SA power

bull If you are using DC voltage for SA power the total continuous current draw across the MOD power bus must not be more than 10 A max at 18hellip32V DC

bull If you are using AC voltage for SA power the total continuous current draw across the MOD power bus must not be more than 10 A max at 18hellip240V AC

bull You can use a 5069-FPD field potential distributor to establish additional SA power buses in a CompactLogix 5480 system

If your system includes AC and DC modules that require SA power you must use a 5069-FPD field potential distributor to establish a new SA power bus

You separate the module types by SA power bus For example install DC module on the first SA power bus in the system and install the AC modules on the second SA power bus in the system

bull Confirm that the external SA power supply is sized adequately for the total SA power current draw in the system

UPS Control

Control signals from an external UPS that let the controller save the state of the program if power is lost The external UPS provides the power that is required to save the program via the MOD power RTB A UPS is not required for controller operation

8 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Controller onto the DIN Rail

1 Confirm that the DIN rail latches are closed

2 If the DIN rail latches are open gently push the rear latch back until the front latch pops up and clicks

3 Position the controller so that the back of it faces the DIN rail

4 Press the controller against the DIN rail until you hear a click

5 Confirm that all latches have fully closed and the controller is latched securely

Connect External Power Supplies to the ControllerBefore you connect MOD power or SA power to the RTBs on the CompactLogix 5480 controller complete the following tasks

bull Read System Power Considerations on page 8

bull Confirm that the external power supplies that MOD power and SA power are adequately sized for your CompactLogix 5480 system For more information see page 8

bull Verify that the external power supplies are turned off

bull Install the MOD power RTB SA power RTB and the UPS Control RTB if used

bull If IO modules are used verify that they are installed on the correct SA power bus

DC-type modules must reside on an SA power bus that uses DC power and AC-type modules must reside on an SA power bus that uses AC power

For more information see the technical documentation for Compact 5000 IO modules

IMPORTANT Remember the following

bull CompactLogix 5480 controllers do not have an embedded power supply that powers the system

The system is powered by external power supplies via

connections to the various power RTBs on the controller

bull We recommend that you use 1606 power supplies from Rockwell Automation to provide MOD power SA power and UPS control

bull You must use an external power supply that is dedicated to the UPS connection

For more information about which 1606 power supplies

are best for each power type see the Switched Mode

Power Supply Specifications Technical Data publication

1606-TD002

bull You can connect power from one external power supply to the MOD power and SA power RTBs However as stated previously we strongly recommend that you use separate external power supplies for MOD power and SA power respectively

The practice of using separate external power supplies can

help prevent unintended consequences that can result if

you use one supply

If you use separate external power supplies the loss of

power from one external power supply does not affect the

availability of power from the other supply For example if

separate external power supplies are used and SA power is

lost MOD power remains available for the Compact 5000

IO modules

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPSR

B

F

R

B

F

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPSR

B

F

R

B

F

Closed PositionOpen Position

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 9

CompactLogix 5480 Controllers

Install the MOD Power RTB

1 Hook the bottom of the MOD power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect MOD PowerThe way that you connect power to the MOD power RTB depends on whether you use UPS control signals or not

bull If you are not using UPS control signals you connect the external power supply directly to the MOD power RTB

In this case proceed to Connect to the MOD Power RTB from a Standard External Power Supply on page 10

bull If you are using UPS control signals you connect a UPS to the MOD power RTB

In this case proceed to Connect to the MOD Power RTB from a UPS on page 15

Connect to the MOD Power RTB from a Standard External Power Supply

Before you connect an external power source to the MOD power RTB make sure that the MOD power source is properly sized

1 Verify that the external power supply is not powered

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the 24V DC (+) connection on the external power supply into the first MOD (+) terminal on the RTB

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the 24V DC (mdash) connection on the external power supply into the first MOD (mdash) terminal on the RTB

5069-L4200ERMW

MOD Power RTB

IMPORTANT Your application can require a power control device for example

a switch between the external 24V DC power source and the

controller to control when the controller is powered If so you

must install the power control device at the VDC+ terminal on

the RTB

If you install the power control device at the VDC- terminal the

controller can fail to power up or power down properly

10 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

The following diagram shows an external 24V DC power supply that is connected to the MOD power RTB when you are not using UPS control signals

Install the SA Power RTBInstall the SA power RTB even if you do not use SA power

1 Hook the bottom of the SA power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect SA DC Power

Before you connect an external DC power source to the SA power RTB make sure that the SA power source is properly sized

For more information o n SA power see SA Power on page 8

1 Confirm that MOD power and SA power sources are turned off

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the DC (+) connection on the external power supply into the first SA (+) terminal on the RTB

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

24V DC

Power

Supply

+

ndashIMPORTANT SA power is only required if your application includes local

Compact 5000 IO modules that require SA power to operate

or are connected to field-side devices that are powered by

SA power

5069-L4200ERMW

SA Power RTB

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 11

CompactLogix 5480 Controllers

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the DC (mdash) connection on the external power supply into the first SA (mdash) terminal on the RTB

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

7 Insert the wire from an Earth Ground location into the first

Ground ( ) on the RTB

The Earth Ground location can be the external SA power supply the DIN rail or other Earth Ground location

8 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

The following diagram shows an external 24V DC power supply that is connected to the SA power RTB when you do not use UPS control signals

TIP

This symbol denotes a Functional Ground terminal that provides a

low impedance path between electric circuits and earth for functional

purposes and provides noise immunity improvement This connection

must be made for functional purposes

5069-L4200ERMW

24V DC

Power

Supply

+

ndash

24V DC

Power

Supply

+

ndash

MOD

Power

SA DC

Power

Functional Ground

12 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Connect SA AC Power

Before you connect an external AC power source to the SA power RTB make sure that the SA power source is properly sized

For more information o n SA power see SA Power on page 8

1 Verify that the SA power source is not powered on

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the L1AC (+) connection on the external power supply into the first SA (+) terminal on the RTB

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the L2NAC(mdash) connection on the external power supply into the first SA(mdash) terminal on the RTB

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

7 Insert the wire from an Earth Ground location into the first

Ground ( ) on the RTB

The Earth Ground location can be the external SA power supply the DIN rail or other Earth Ground location

8 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

This diagram shows an external 240V AC power supply that is connected to the SA power RTB when you do not use UPS control signals

IMPORTANT SA power is only required if your application includes local

Compact 5000 IO modules that require SA power to operate

or are connected to field-side devices that are powered by

SA power

TIP

This symbol denotes a Functional Ground terminal that provides a

low impedance path between electric circuits and earth for functional

purposes and provides noise immunity improvement This connection

must be made for functional purposes

5069-L4200ERMW

24V DC

Power

Supply

+

ndash

240V AC

Power

Supply

+

ndash

MOD

Power

SA AC

Power

Functional Ground

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 13

CompactLogix 5480 Controllers

Connect Control Signals Via UPS Control RTBThe CompactLogix 5480 controller does not have an internal energy storage module that lets the controller save the state of the program if system-side power is lost You must connect an external uninterruptible power supply (UPS) to the UPS control RTB to save the state of the program if power is lost

You connect control signals from an external power supply to the UPS control RTB to let the controller experience a controlled shutdown upon an incoming power loss

When a UPS connection is detected the CompactLogix 5480 controller defaults to initiate shutdown 1 minute after a power loss indication

We recommend that you use 1606 switched mode uninterruptible power supplies from Rockwell Automation with a CompactLogix 5480 controller for example the 1606-XLS240-UPS power supply

For more information on Bulletin 1606 uninterruptible power supplies see the following

bull Bulletin 1606 DC-UPS Uninterruptible Power Supply Installation Instructions publication 1606-IN025

bull Bulletin 1606 Switched Mode Power Supplies Reference Manual publication 1606-RM036

The switched mode uninterruptible power supplies use a 12-volt battery module to bridge power failures and voltage fluctuations We recommend that you use the 1606-XLSBATASSY1 battery module from Rockwell Automation

You can use other accessories such as replacement batteries mounting kits and panelwall mounting brackets with the battery module

For more information on and the battery module and accessories that you can use with them see the following

bull Bulletin 1606 12V 7Ah Battery Modules Installation Instructions publication 1606-IN011

bull Bulletin 1606 Switched Mode Power Supply Battery Modules (12V 7Ah) Reference Manual publication 1606-RM037

UPS Control SignalsThese control signals are used on the UPS Control RTB

UPS Control RTB Terminals

Signal Description

UPS Ready (R)

An input signal from the UPS to the controller that indicates the UPS is working and can buffer during a power failure

The charge level for a UPS to be ready to buffer during a power failure varies For example the 1606-XLS240-UPS power supply must be greater than 85 charged to be ready

The letter R indicates the RTB terminal for this signal

Buffering (B)

An input signal from the UPS to the controller that indicates the UPS battery is providing power because the external power has failed

After a preset time (typically 1 minute after power failure) the controller performs an orderly shutdown by stopping execution and saving the state of the controller

The letter B indicates the RTB terminal for this signal

Battery Fail (F)

An input from the UPS to the controller that indicates the UPS battery has failed and the controller cannot operate from stored energy

In this case the controller does not attempt to save the state of the program when the external power fails The controller issues an alarm if a UPS was previously attached and ready to buffer

The letter F indicates the RTB terminal for this signal

Inhibit (I)

An output signal from the controller to the UPS that disables the UPS signal output The INHIBIT signal is triggered after data is backed up and the system is ready to shut down

The letter I indicates the RTB terminal for this signal

14 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the UPS Control RTBInstall the UPS control RTB even if you do not intend to connect uninterruptible power to the controller

1 Hook the bottom of the UPS power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect UPS Control Signals

1 Verify that all sources of MOD power and SA power are turned off

2 Verify the followingbull A 24V DC power supply is connected to the 24V IN

terminals on the UPSbull A 12V DC battery is connected to the 12V BAT terminals

on the UPS

For more information see the example graphic on page 17

Connect to the MOD Power RTB from a UPS

1 Daisy chain the wires from these connections on the UPSbull 24V OUT (+)bull Ready (1)bull Buffering (3)bull Battery Fail (5)bull Inhibit (7)

2 Connect one wire to each (+) terminal on the MOD power RTB as shown in the example graphic on page 17a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Daisy chain a wire that is connected to the 24V OUT (ndash) terminal on the UPS and a second wire

4 Connect one wire to each (ndash) terminal on the MOD power RTB a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

IMPORTANT The UPS terminal labels in this section represent the labels on

a 1606-XLS240-UPS power supply Your UPS terminals can be

labeled differently

5069-L4200ERMW

UPS Control RTB

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 15

CompactLogix 5480 Controllers

Connect to the UPS Control RTB from a UPS

1 Connect a wire from the Ready (2) connection on the UPS to the UPS Ready terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

2 Connect a wire from the Buffering (4) connection on the UPS to the Buffering terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Connect a wire from the Battery Fail (6) connection on the UPS to the Battery Fail terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

4 Connect a wire from the Inhibit (8) connection on the UPS to the Inhibit terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

16 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

This diagram shows a 1606-XLS240-UPS power supply battery that is connected to a CompactLogix 5480 controller

5069-L4200ERMW

UPS Ready

Buffering

Battery Fail

Inhibit

(7) Inhibit +

(8) Inhibit ndash

24V DC

Power

Supply

Ready

(1) (2)

+ ndash + ndash + ndash + ndash

N L PE

Buffering

(3) (4)

Battery Fail

(5) (6)

12V DC Battery

(for example 1606-XLSBATASSY1)

+ ndash

DC-UPS

(1606-XLS240-UPS)

24V

IN

12V

BAT

24V

OUT

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 17

CompactLogix 5480 Controllers

Disconnect Wires from the RTBsIf necessary complete these tasks to disconnect wires from any RTB on the controller

1 Turn the screwdriver counter-clockwise to open the terminal

2 Remove the wire

Install Compact 5000 IO ModulesComplete one of the following

bull If you do not use local Compact 5000 IO modules in the system proceed to Install the End Cap on page 18

bull If you use local Compact 5000 IO modules in the system install the modules to the right side of the controller

After the IO modules are installed install the end cap on the right side of the last IO module in the system For more information on how to install the end cap see page 18

For more information on how to install Compact 5000IO modules see the installation instructions available with each Compact 5000 IO module catalog number

Install the End CapYou must install an end cap on the right side of the last module in a CompactLogix 5480 system The end cap covers the exposed interconnections on the last module in the system If you do not install the end cap before powering the system equipment damage or injury from electric shock can result

If you do not intend to install Compact 5000 IO modules to the system before you turn on power to the controller install the end cap

1 Align the end cap with the interlocking pieces on the controller

2 Push the end cap toward the DIN rail until it locks into place

Power the System

After the end cap is installed on the last module in the system turn on power to the MOD power RTB and the SA power RTB

IMPORTANT Consider the following before you power the system

bull Make sure to remove the debris shield from the controller before power-up

bull As noted previously you must install working controller firmware to use the COS on the controller There are two ways to install working firmware The ways are described beginning on page 23

One of the methods to install working controller firmware

uses the SD card that ships with the controller

ndash If you intend to use the SD card to install working

controller firmware go to Use a Secure Digital Card

to Install Controller Firmware on page 24

Complete the steps described in that section apply

power to the controller and return to the next

section that is Set the Network Internet Protocol

(IP) Addresses on page 19

ndash If you do not intend to use the SD card to install

working controller firmware turn on the power now

and proceed to the next section

Top Interlocking

Pieces

End Cap

Bottom Interlocking

Pieces

18 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Set the Network Internet Protocol (IP) AddressesYou must set an IP address on Ethernet ports for the controller to operate on an EtherNetIP network via that port

Out-of-the-box the following applies to Ethernet ports A1 A2 and B1

bull The ports are DHCP-enabled and the IP address is set automatically via a DHCP server

If there is no DHCP server available to set the IP address you must set the IP address manually

bull If ports A1 and A2 are configured to use DLRLinear mode you set only one IP address that is used on both ports

bull Control ports must use unique subnets

When ports A1 and A2 are configured to use DLRLinear mode however they use the same subnet because they are configured as one port

You can use one of the following to set the IP address on the controller when it is in the out-of-the-box condition

bull DHCP server

bull BOOTP DHCP EtherNetIP Commissioning tool version 30200 or later

bull RSLinx Classic software version 41000 or later

bull FactoryTalk Linx software version 61000 or later

bull Logix Designer application version 320100 or later

For more information on how to set or change the IP address on a CompactLogix 5480 controller see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

Connect the Controller to an EtherNetIP Network

Use an RJ45 cable to connect the controller to an EtherNetIP network

1 If needed wire the RJ45 connector as shown

2 Connect RJ45 cables to the controller Ethernet ports

IMPORTANT Before you can connect a CompactLogix 5480 controller to an

EtherNetIP network you must first install the network and

its components

This section assumes that the EtherNetIP network is

installed

Connector Number

Color

1585J 8-pin Cables with Support for 101001000 Mbps

1585J 8-pin Cables with Support for 10100 Mbps

1585J 4-pin Cables with Support for 10100 Mbps

1WhiteOrange

BI_DA+ TxData +

2 Orange BI_DA- TxData -

3WhiteGreen

BI_DB+ Recv Data +

4 Blue BI_DC+ Unused mdash

5 WhiteBlue BI_DC- Unused mdash

6 Green BI_DB- Recv Data -

7WhiteBrown

BI_DD+ Unused mdash

8 Brown BI_DD- Unused mdash

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 19

CompactLogix 5480 Controllers

Remove and Replace the Controller

1 Turn off power to the MOD power and the SA power RTBs

2 If there are local Compact 5000 IO modules in the system remove them If not skip to step 3

3 Disconnect wires from the RTBs

For more information see Disconnect Wires from the RTBs on page 18

4 Pull the RTB handles to remove the RTBs

IMPORTANT When you remove MOD power from the controller you shut down

power to all modules in the CompactLogix 5480 system That is

all system-side is removed When you remove SA power from the

controller all field-side power that is provided by the controller is

removed If SA power that is provided via a 5069-FPD field

potential distributor the system does not lose SA power to the

right of the field potential distributor

In this case you must use a separate power source for the SA

power RTB on the field potential distributor

We strongly recommend that before you remove MOD power or

SA power that you take the appropriate actions to help prevent

unintended consequences that can result from a system power

shutdown

Despite the removal of power from SA RTBs on the controller or

field potential distributor the 5069-OB16 and 5069-OB16F

modules continue to receive field-side power The modules

receive power from an external power source that is connected to

the LA (+) and LA (ndash) module terminals

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

UPS Control RTB

MOD Power RTB

SA Power RTB

20 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

5 Remove all cables from the controller

6 Push down on the front of the DIN rail latches

A click indicates that the DIN rail latches are open

If the DIN rail latches fail to remain in the open position hold them down

7 Pull the controller off the DIN rail

8 Repeat the installation steps that are described beginning at Install the Controller onto the DIN Rail on page 9

9 Apply MOD power and if necessary SA power to the system

Replace the FansThe CompactLogix 5480 controller uses fans at the top and bottom of the controller to help maintain lower operating temperatures when the controller is operating

Fan use includes speed control and monitoring Faults indicate fan operating conditions as follows

bull Minor faults - Triggered when a fan is not operating at the requested speed or if a fan fails to operate at all

In your Logix Designer application project you can use the Minor Faults tab on the Controller Properties dialog box to monitor for these faults

bull Major fault - Triggered if both fans fail and the controller goes over the maximum operating temperature

In this case the controller stops operating

You can order replacement fans Replacement fans come in pairs The fans are unique by position and keyed to help make sure that you install the correct fan in each position

The fans are labeled Fan 1 - Top and Fan 2 - Bottom

Consider the following

bull We recommend that you replace the fans in pairs That is if you replace the one fan we recommend that you replace the other fan too

bull You can replace fans during controller operation The fans support removal and insertion under power

bull Do not remove both fans at once if the controller is operating That is remove a fan and install the replacement fan before you remove the other fan

Remove the Top Fan

1 Push up on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

TIP In your Logix Designer application project you can

use the Major Faults tab on the Controller

Properties dialog box to monitor for this fault

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

R

B

F

Open Position

IMPORTANT If you replace fans while the controller is operating

do not touch live voltage components

TIP If the hinges do not disengage when you push up on the front of the

fan then use a screwdriver as a pry tool

5069-L4200ERMW

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 21

CompactLogix 5480 Controllers

2 Pull the fan out of the slot at the top of the controller

Install the Top Replacement Fan

1 Insert the top replacement fan into the slot at the top of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push down on the top replacement fan until it clicks in place

Remove the Bottom Fan

1 Push the down on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

2 Pull the fan out of the slot at the bottom of the controller

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

TIP If the hinges do not disengage when you push down on the front of

the fan then use a screwdriver as a pry tool

5069-L4200ERMW

5069-L4200ERMW

22 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Bottom Replacement Fan

1 Insert the bottom replacement fan into the slot at the bottom of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push up on the bottom replacement fan until it clicks in place

Use the COS For Windows-based ComputingThe COS on a CompactLogix 5480 controller runs in parallel with the Logix control engine You are not required to use the COS

You can use the following methods to install working controller firmware when the controller is in the out-of-box state

bull ControlFLASHtrade or ControlFLASH Plustrade softwarebull Secure Digital (SD) card

Use a Flash Programming Tool to Install Controller FirmwareYou can use ControlFLASH and ControlFLASH Plus software to install controller firmware

The following requirements apply when you use ControlFLASH or ControlFLASH Plus to install working controller firmware

bull You must use one of the followingndash ControlFLASH software version 150100 or laterndash ControlFLASH Plus version 20000 or later

bull You must use a Linx-based software application with your flash programming toolndash With ControlFLASH software you can use RSLinx

Classic Lite RSLinx Classic RSLinx Enterprise or FactoryTalk Linx

ndash With ControlFLASH Plus software you must use FactoryTalk Linx

Minimum software versions apply with Linx-based software For more information on the minimum software version requirements see the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

5069-L4200ERMW

5069-L4200ERMW

IMPORTANT Before you can use the COS you must install working controller firmware The requirement applies even if you

are not using the controller for real-time control If you do not

install working controller firmware the COS does not start

In the out-of-box state the controller uses firmware revision

1xxx On a CompactLogix 5480 controller the minimum

working controller firmware is revision 32012

TIP We recommend that you connect your peripherals to the

ports that are dedicated to COS use before you install

controller firmware

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 23

CompactLogix 5480 Controllers

Download the Flash Programming Tool

ControlFLASH and ControlFLASH Plus software are available from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

Download the installation files and install the software

Download the Controller Firmware

After the flash programming tool is installed download the controller firmware from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

The initial download is a exe file You use the Rockwell Automation Download Manager to extract a dmk from the downloaded file

Install the Controller Firmware

To install the controller firmware via a flash programming tool you complete the following steps

1 To start the tool click StartgtAll ProgramsgtFlashing Programming ToolsgtControlFLASH or ControlFLASH Plus

2 Follow the prompts to complete the following stepsa Choose the controllerb Select the firmware revisionc Install the controller firmware

A dialog box confirms that the installation was successful

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use a flash programming tool to install controller firmware see the following

bull ControlFLASH Firmware Upgrade Kit User Manual publication 1756-UM105

bull ControlFLASH Plus Quick Start Guide publication CFP-QS001

bull CompactLogix 5480 Controllers User Manual publication 5069-UM002

Use a Secure Digital Card to Install Controller FirmwareYou can use an SD card to install controller firmware CompactLogix 5480 controllers ship with an SD card installed behind the front door on the controller

To use an SD card to install controller firmware complete the following steps

1 Before you turn on power to the controller remove the SD card from the controller

2 Install the SD card into another working CompactLogix 5480 controller that has a Logix Designer application project on it

3 Save the project to the SD card

4 Remove the SD card from the working controller and reinstall it in the new controller

5 Turn on power to the new controller

When the new controller powers up it automatically updates the firmware to the revision that is stored on the SD card

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use the SD card with the controller after valid firmware is installed and the controller is powered see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

IMPORTANT These steps only highlight the major tasks that you

complete to install controller firmware with ControlFLASH

To successfully install controller firmware you must complete other tasks that are not described here

For complete information on how to install controller

firmware see the publications listed at the end of the section

IMPORTANT To install controller firmware on a new CompactLogix 5480

controller via an SD card you must have another controller of

the same type that is already working

The SD card method requires that you save the Logix Designer

application project from the working controller to the SD card

before you use it in the new controller

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

SD Card Slot

24 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpecificationsThis table lists a subset of controller specifications For a complete list of specifications see the CompactLogix 5380 Compact GuardLogixreg 5380 and CompactLogix 5480 Controllers Specifications Technical Data publication 5069-TD002

Environmental Specifications - CompactLogix 5480 Controllers

Attribute 5069-L430ERMW 5069-L450ERMW 5069-4100ERMW 5069-L4200ERMW

Temperature operating

IEC 60068-2-1 (Test Ad Operating Cold)

IEC 60068-2-2 (Test Bd Operating Dry Heat)

IEC 60068-2-14 (Test Na Operating Thermal Shock)

0 degC lt Ta lt +60 degC

(+32 degF lt Ta lt +140 degF)

Temperature surrounding air max 60 degC (140 degF)

Enclosure Type Rating None (open-style)

Voltage and current ratings

MOD Power voltage range 18hellip32V DC

MOD Power power max 72 W

MOD Power current typical 4 A

MOD Power inrush 4 A for 15 ms

MOD Power Passthrough(1) 6 A 18hellip32V DC

MOD Power current rating max10 A

Do not exceed 10 A current draw at the MOD power RTB(4)

SA Power voltage ranges(2) 0hellip32V DC

0hellip240V AC 47hellip63 Hz

SA Power current max (2) 10 mA (DC power)

25 mA (AC power)

SA Power Passthrough(2) (3) 999 A 0hellip32V DC

9975 A 0hellip240V AC 47hellip63 Hz

SA Power current rating max(2) Do not exceed 10 A current draw at the SA power RTB

Isolation voltage

300V (continuous) Basic Insulation Type SA and MOD Power to Backplane

300V (continuous) Basic Insulation Type SA to MOD Power

300V (continuous) Basic Insulation Type Ethernet to Backplane

300V (continuous) Double Insulation Type Ethernet to MOD Power

300V (continuous) Double Insulation Type Ethernet to SA Power

50V (continuous) Functional Insulation Type Ethernet to USB ports and DisplayPort

300V (continuous) Basic Insulation Type USB ports and DisplayPort to Backplane

300V (continuous) Double Insulation Type USB ports and DisplayPort to MOD Power

300V (continuous) Double Insulation Type USB ports and DisplayPort to SA Power

No isolation between Ethernet ports

Type tested at 1500V AC for 60 s

Wire size

5069-RTB4-SCREW 5069-RTB6-SCREW connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 35 mm (014 in) max diameter including insulation single wire connection only

5069-RTB4-UPS connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 29 mm (011 in) max diameter including insulation single wire connection only

Ethernet connections

Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2

Insulation-stripping length 5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 12 mm (047 in)

Terminal block torque5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 04 Nbullm (35 lbbullin)

ATTENTION Do not wire more than two conductors on one RTB terminal

(1) Maximum level of MOD power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(2) SA power specifications are based on the number and type of Compact 5000 IO modules that are used in the system If the set of IO modules that is used in the system require AC and DC voltage you must install a 5069-FPD field

potential distributor to separate the module types

(3) Maximum level of SA power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(4) Remember MOD power usage includes the total power that the controller and local Compact 5000 IO modules use If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000 IO

modules can draw a maximum of 10 A in addition to the current that the controller draws

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 25

CompactLogix 5480 Controllers

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation

You can view or download publications at httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage To order paper copies of technical documentation contact your local Allen-Bradley distributor or Rockwell Automationreg sales representative

Resource Description

CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069-TD002

Provides specifications and other technical data for CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 controllers

CompactLogix 5480 Controllers User Manual publication 5069-UM002 Describes how to configure operate and monitor CompactLogix 5480 controllers

Industrial Automation Wiring and Grounding Guidelines publication 1770-41 Provides general guidelines for installing a Rockwell Automationreg industrial system

Product Certifications website rokautocertifications Provides declarations of conformity certificates and other certification details

26 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 3: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

CompactLogix 5480 Controllers

ATTENTION Read this document and the documents listed in the Additional Resources section about installation configuration and operation of this equipment before you install configure operate or maintain

this product Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes laws and standards

Activities including installation adjustments putting into service use assembly disassembly and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of

practice

If this equipment is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired

ATENCIOacuteN Antes de instalar configurar poner en funcionamiento o realizar el mantenimiento de este producto lea este documento y los documentos listados en la seccioacuten Recursos adicionales acerca de la

instalacioacuten configuracioacuten y operacioacuten de este equipo Los usuarios deben familiarizarse con las instrucciones de instalacioacuten y cableado y con los requisitos de todos los coacutedigos leyes y estaacutendares vigentes

El personal debidamente capacitado debe realizar las actividades relacionadas a la instalacioacuten ajustes puesta en servicio uso ensamblaje desensamblaje y mantenimiento de conformidad con el coacutedigo de

praacutectica aplicable

Si este equipo se usa de una manera no especificada por el fabricante la proteccioacuten provista por el equipo puede resultar afectada

ATENCcedilAtildeO Leia este e os demais documentos sobre instalaccedilatildeo configuraccedilatildeo e operaccedilatildeo do equipamento que estatildeo na seccedilatildeo Recursos adicionais antes de instalar configurar operar ou manter este produto Os

usuaacuterios devem se familiarizar com as instruccedilotildees de instalaccedilatildeo e fiaccedilatildeo aleacutem das especificaccedilotildees para todos os coacutedigos leis e normas aplicaacuteveis

Eacute necessaacuterio que as atividades incluindo instalaccedilatildeo ajustes colocaccedilatildeo em serviccedilo utilizaccedilatildeo montagem desmontagem e manutenccedilatildeo sejam realizadas por pessoal qualificado e especializado de acordo com o

coacutedigo de praacutetica aplicaacutevel

Caso este equipamento seja utilizado de maneira natildeo estabelecida pelo fabricante a proteccedilatildeo fornecida pelo equipamento pode ficar prejudicada

ВНИМАНИЕ Перед тем как устанавливать настраивать эксплуатировать или обслуживать данное оборудование прочитайте этот документ и документы перечисленные в разделе

laquoДополнительные ресурсыraquo В этих документах изложены сведения об установке настройке и эксплуатации данного оборудования Пользователи обязаны ознакомиться с инструкциями по

установке и прокладке соединений а также с требованиями всех применимых норм законов и стандартов

Все действия включая установку наладку ввод в эксплуатацию использование сборку разборку и техническое обслуживание должны выполняться обученным персоналом в соответствии с

применимыми нормами и правилами

Если оборудование используется не предусмотренным производителем образом защита оборудования может быть нарушена

ACHTUNG Lesen Sie dieses Dokument und die im Abschnitt bdquoWeitere Informationenldquoaufgefuumlhrten Dokumente die Informationen zu Installation Konfiguration und Bedienung dieses Produkts enthalten bevor

Sie dieses Produkt installieren konfigurieren bedienen oder warten Anwender muumlssen sich neben den Bestimmungen aller anwendbaren Vorschriften Gesetze und Normen zusaumltzlich mit den Installations- und

Verdrahtungsanweisungen vertraut machen

Arbeiten im Rahmen der Installation Anpassung Inbetriebnahme Verwendung Montage Demontage oder Instandhaltung duumlrfen nur durch ausreichend geschulte Mitarbeiter und in Uumlbereinstimmung mit den

anwendbaren Ausfuumlhrungsvorschriften vorgenommen werden

Wenn das Geraumlt in einer Weise verwendet wird die vom Hersteller nicht vorgesehen ist kann die Schutzfunktion beeintraumlchtigt sein

ATTENTION Lisez ce document et les documents listeacutes dans la section Ressources compleacutementaires relatifs agrave lrsquoinstallation la configuration et le fonctionnement de cet eacutequipement avant drsquoinstaller configurer

utiliser ou entretenir ce produit Les utilisateurs doivent se familiariser avec les instructions drsquoinstallation et de cacircblage en plus des exigences relatives aux codes lois et normes en vigueur

Les activiteacutes relatives agrave lrsquoinstallation le reacuteglage la mise en service lrsquoutilisation lrsquoassemblage le deacutemontage et lrsquoentretien doivent ecirctre reacutealiseacutees par des personnes formeacutees selon le code de pratique en vigueur

Si cet eacutequipement est utiliseacute drsquoune faccedilon qui nrsquoa pas eacuteteacute deacutefinie par le fabricant la protection fournie par lrsquoeacutequipement peut ecirctre compromise

ATTENZIONE Prima di installare configurare ed utilizzare il prodotto o effettuare interventi di manutenzione su di esso leggere il presente documento ed i documenti elencati nella sezione ldquoAltre risorserdquo

riguardanti lrsquoinstallazione la configurazione ed il funzionamento dellrsquoapparecchiatura Gli utenti devono leggere e comprendere le istruzioni di installazione e cablaggio oltre ai requisiti previsti dalle leggi codici

e standard applicabili

Le attivitagrave come installazione regolazioni utilizzo assemblaggio disassemblaggio e manutenzione devono essere svolte da personale adeguatamente addestrato nel rispetto delle procedure previste

Qualora lrsquoapparecchio venga utilizzato con modalitagrave diverse da quanto previsto dal produttore la sua funzione di protezione potrebbe venire compromessa

DİKKAT Bu uumlruumlnuumln kurulumu yapılandırılması işletilmesi veya bakımı oumlncesinde bu dokuumlmanı ve bu ekipmanın kurulumu yapılandırılması ve işletimi ile ilgili İlave Kaynaklar boumlluumlmuumlnde yer listelenmiş

dokuumlmanları okuyun Kullanıcılar yuumlruumlrluumlkteki tuumlm youmlnetmelikler yasalar ve standartların gereksinimlerine ek olarak kurulum ve kablolama talimatlarını da oumlğrenmek zorundadır

Kurulum ayarlama hizmete alma kullanma parccedilaları birleştirme parccedilaları soumlkme ve bakım gibi aktiviteler sadece uygun eğitimleri almış kişiler tarafından yuumlruumlrluumlkteki uygulama youmlnetmeliklerine uygun şekilde

yapılabilir

Bu ekipman uumlretici tarafından belirlenmiş amacın dışında kullanılırsa ekipman tarafından sağlanan koruma bozulabilir

POZOR Než začnete instalovat konfigurovat či provozovat tento vyacuterobek nebo provaacutedět jeho uacutedržbu přečtěte si tento dokument a dokumenty uvedeneacute v čaacutesti Dodatečneacute zdroje ohledně instalace konfigurace

a provozu tohoto zařiacutezeniacute Uživateleacute se musejiacute vedle požadavků všech relevantniacutech vyhlaacutešek zaacutekonů a norem nutně seznaacutemit takeacute s pokyny pro instalaci a elektrickeacute zapojeniacute

Činnosti zahrnujiacuteciacute instalaci nastaveniacute uvedeniacute do provozu užiacutevaacuteniacute montaacutež demontaacutež a uacutedržbu musiacute vykonaacutevat vhodně proškolenyacute personaacutel v souladu s přiacuteslušnyacutemi provaacuteděciacutemi předpisy

Pokud se toto zařiacutezeniacute použiacutevaacute způsobem neodpoviacutedajiacuteciacutem specifikaci vyacuterobce může byacutet narušena ochrana kterou toto zařiacutezeniacute poskytuje

UWAGA Przed instalacją konfiguracją użytkowaniem lub konserwacją tego produktu należy przeczytać niniejszy dokument oraz wszystkie dokumenty wymienione w sekcji Dodatkowe źroacutedła omawiające

instalację konfigurację i procedury użytkowania tego urządzenia Użytkownicy mają obowiązek zapoznać się z instrukcjami dotyczącymi instalacji oraz oprzewodowania jak roacutewnież z obowiązującymi kodeksami

prawem i normami

Działania obejmujące instalację regulację przekazanie do użytkowania użytkowanie montaż demontaż oraz konserwację muszą być wykonywane przez odpowiednio przeszkolony personel zgodnie z

obowiązującym kodeksem postępowania

Jeśli urządzenie jest użytkowane w sposoacuteb inny niż określony przez producenta zabezpieczenie zapewniane przez urządzenie może zostać ograniczone

OBS Laumls detta dokument samt dokumentet som staringr listat i avsnittet Oumlvriga resurser om installation konfigurering och drift av denna utrustning innan du installerar konfigurerar eller boumlrjar anvaumlnda eller utfoumlra

underharingllsarbete paring produkten Anvaumlndare maringste bekanta sig med instruktioner foumlr installation och kabeldragning foumlrutom krav enligt gaumlllande koder lagar och standarder

Aringtgaumlrder som installation justering service anvaumlndning montering demontering och underharingllsarbete maringste utfoumlras av personal med laumlmplig utbildning enligt laumlmpligt bruk

Om denna utrustning anvaumlnds paring ett saumltt som inte anges av tillverkaren kan det haumlnda att utrustningens skyddsanordningar foumlrsaumltts ur funktion

LET OP Lees dit document en de documenten die genoemd worden in de paragraaf Aanvullende informatie over de installatie configuratie en bediening van deze apparatuur voordat u dit product installeert

configureert bediend of onderhoudt Gebruikers moeten zich vertrouwd maken met de installatie en de bedradingsinstructies naast de vereisten van alle toepasselijke regels wetten en normen

Activiteiten zoals het installeren afstellen in gebruik stellen gebruiken monteren demonteren en het uitvoeren van onderhoud mogen uitsluitend worden uitgevoerd door hiervoor opgeleid personeel en in

overeenstemming met de geldende praktijkregels

Indien de apparatuur wordt gebruikt op een wijze die niet is gespecificeerd door de fabrikant dan bestaat het gevaar dat de beveiliging van de apparatuur niet goed werkt

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 3

CompactLogix 5480 Controllers

Environment and Enclosure

ATTENTION This equipment is intended for use in a Pollution Degree 2 industrial environment in overvoltage Category II applications (as defined in ENIEC

60664-1) at altitudes up to 2000 m (6562 ft) without derating

This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such

environments

This equipment is supplied as open-type equipment for indoor use It must be mounted within an enclosure that is suitably designed for those specific

environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts The enclosure must

have suitable flame-retardant properties to prevent or minimize the spread of flame complying with a flame spread rating of 5VA or be approved for the

application if nonmetallic The interior of the enclosure must be accessible only by the use of a tool Subsequent sections of this publication may contain more

information regarding specific enclosure type ratings that are required to comply with certain product safety certifications

In addition to this publication see the following

bull Industrial Automation Wiring and Grounding Guidelines publication 1770-41 for more installation requirements

bull NEMA 250 and ENIEC 60529 as applicable for explanations of the degrees of protection provided by enclosures

Prevent Electrostatic Discharge

ATTENTION This equipment is sensitive to electrostatic discharge which can cause internal damage and affect normal operation Follow these guidelines when

you handle this equipment

bull Touch a grounded object to discharge potential static

bull Wear an approved grounding wriststrap

bull Do not touch connectors or pins on component boards

bull Do not touch circuit components inside the equipment

bull Use a static-safe workstation if available

bull Store the equipment in appropriate static-safe packaging when not in use

ATTENTION

bull In case of malfunction or damage no attempts at repair should be made The controller should be returned to the manufacturer for repair Do not dismantle the controller

bull This equipment is certified for use only within the surrounding air temperature range of 0hellip60 degC (32hellip140 degF) The equipment must not be used outside of this range

bull The USB programming port is intended for temporary local programming purposes only and not intended for permanent connection The USB programming port connection is not to exceed 30 m (984 ft) and must not contain hubs You must connect the programming equipment to a ground system that is common with the controller

bull Devices that are connected to USB 30 ports must reside in the same control enclosure as the controller This requirement applies to devices that are powered by the USB 30 ports or not You must connect the devices to a ground system that is common with the controller Alternatively you can connect the device to the common ground system via a USB hub that provides galvanic isolation

bull USB 30 port connections are not to exceed 30 m (984 ft)

bull DisplayPort cables or adapters that are used with this product must be certified by VESA A list of certified equipment and cables is on the VESA website (wwwvesaorg) Use of non-certified cables and adapters can cause damage or improper operation DisplayPort connections are not to exceed 30 m (984 ft)

bull Displays that are connected to DisplayPort must connect to a ground system that is common with the controller Alternatively displays can be connected by a display extender that is connected to the common ground system with the controller and provides galvanic isolation

bull Use only a soft dry anti-static cloth to wipe down equipment Do not use any cleaning agents

Electrical Safety Considerations

ATTENTION Do not wire more than 2 conductors on a single RTB terminal

Waste Electrical and Electronic Equipment (WEEE)

At the end of its life this equipment should be collected separately from any unsorted municipal waste

4 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

About the ControllerThe following graphic shows a CompactLogix 5480 controller

IMPORTANTAny illustrations charts sample programs and layout examples that are shown in this publication are intended solely for the purposes of example Since

there are many variables and requirements that are associated with any particular installation Rockwell Automation does not assume responsibility or

liability for actual use that is based on the examples that are shown in this publication

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

1

6

7

9

8

2

3

4

14

11

16

10

5

1312

15

18

20

17

19

Front View

Bottom View

22

21

23

CompactLogix 5480 Controller Parts

Number Item Description

1 DIN rail latches Secure adapter to DIN rail

2 Mode switch Lets you choose the controller operating mode

3 SD card slot Location for SD card

4 Reset button Resets the controller to factory default condition

5 Four-character displayScrolls information about the controller such as firmware revision or project status

6 USB programming port Provides temporary connection to download projects

7 Ethernet port B1Lets the controller connect to the following networksbull Enterprise-level networkbull Device-level network

8 Ethernet port A1Lets the controller connect to device-level networks

9 Ethernet port A2

10Network and link status indicators for ports B1 A1 and A2 Show the state of the Ethernet ports and network

communication activity on each port

11Speed and link status indicators for port X1

12 Bottom fanHelps regulate controller temperature

Controller ships with fans installed You can replace fans if necessary

13Controller status indicators

Show the state of the controller in multiple respects

14 Top fanHelps regulate controller temperature

Controller ships with fans installed You can replace fans if necessary

15MOD power and SA power status indicators

Show the state of module (MOD) power and sensor actuator (SA) power respectively

16 UPS Control RTB

Connector for control signals to and from an uninterruptible power supply (UPS) that are used to support a controlled shutdown upon incoming power loss

17MOD power bus connector

MOD power bus connection that passes MOD power to the next local Compact 5000 IO module in the system

18 MOD power RTBConnector for external power supply to provide MOD power to the system

19 SA power bus connectorSA power bus connection that passes SA power to the next local Compact 5000 IO module in the system

20 SA power RTBConnector for external power supply to provide SA power to the systemlsquo

21 Ethernet port X1 Used with the COS on the controller

22 USB 30 portsConnectors for peripherals that are used with the COS on the controller(2)

(2) Devices that are connected to the controller via a USB 30 port must reside in the same control enclosure as

the controller This requirement applies to devices that are powered by the USB 30 ports or not You must

connect the devices to a ground system that is common with the controller Alternatively you can connect

the device to the common ground system via a USB hub that provides galvanic isolation

23DisplayPort connection(1)

(1) Any DisplayPort cables or adapters that are used with this product must be certified by VESA A list of

certified equipment and cables is on the VESA website (wwwvesaorg) Use of non-certified cables and

adapters can cause damage or improper operation

Connector to use a display with the COS on the controller

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 5

CompactLogix 5480 Controllers

Required System ComponentsBefore you install the controller verify that you have the following components

System PlanningFollow these rules when planning your system configuration

bull If the CompactLogix 5480 system includes only a controller you can mount the DIN rail in any orientation

bull If your CompactLogix 5480 system includes local Compact 5000 IO modules you must mount the DIN rail horizontally

bull The controller is the leftmost component in the system

bull Local Compact 5000 IO modules are installed to the right of the controller

bull The controller supports as many as 31 local Compact 5000 IO modules

bull Before power-up make sure that the end cap is installed on the right side of the controller or rightmost local Compact 5000 IO module if IO modules are used

Components Used to Install a CompactLogix 5480 Controller

Component Description

Removable Terminal Blocks (RTB)

An RTB that is used to connect MOD power (system-side power) to the controller - 5069-RTB4-SCREW RTB (Ships with the controller)

An RTB that is used to connect SA power (field-side power) - 5069-RTB6-SCREW RTB (Ships with the controller)

An RTB that is used to connect UPS (uninterruptible power) - 5069-L4UPSRTB (Ships with the controller)

External power supply for MOD power

A power supply that is adequately sized to provide MOD power that is system-side power to the CompactLogix 5480 system

For more information see System Power Considerations on page 8

External power supply for SA power

A power supply that is adequately sized to provide SA power that is field-side power to the CompactLogix 5480 system

IMPORTANT SA power is only required if your application includes local Compact 5000 IO modules that are connected to devices that use SA power

For more information see System Power Considerations on page 8

External uninterruptible power supply for UPS control signals

A power supply that provides UPS control signals so that the controller can save the state of the program when power is lost A UPS is only required if your system uses UPS control signals

For more information see Connect Control Signals Via UPS Control RTB on page 14

Tools

You use the following tools to wire the RTBsbull Screwdriverbull Wire stripperbull Wires

For more information on available wire sizes and wire insulation-stripping length see Specifications on page 25

DIN rail

Compatible zinc-plated chromate steel DIN rail

You can use the following DIN railsbull EN50022 - 35 x 75 mm (138 x 030 in)bull EN50022 - 35 x 15 mm (138 x 060 in)

EtherNetIP network components

If your CompactLogix 5480 controller operates on an EtherNetIP network you must install the network and all required components

Software

When you install the controller you assign IP addresses on the controller You can use the following to assign IP addresses

bull DHCP server

bull BOOTP DHCP EtherNetIP Commissioning tool version 30200 or later

bull RSLinxreg Classic software version 41000 or later

bull FactoryTalkreg Linx version 61000 or later

bull Logix Designer application version 320100 or later

For more information see Set the Network Internet Protocol (IP) Addresses on page 19

ATTENTION Do not discard the end cap Use this end cap

to cover the exposed interconnections on the last module

on the DIN rail Failure to do so could result in equipment

damage or injury from electric shock

Components Used to Install a CompactLogix 5480 Controller

Component Description

6 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpacingMaintain spacing from enclosure walls wireways and adjacent equipment Ambient temperature is higher at the top of an enclosed cabinet

The minimum distance on of a system that includes only a CompactLogix 5480 controller is as follows

bull 2500 mm (098 in) between the sides and the cabinet

bull 2500 mm (098 in) between the front of the controller and the cabinet

bull 5000 mm (196 in) between the top and bottom and the cabinet

We recommend that you install the controller near the bottom of the enclosure where ambient temperature is lower

Enclosure SelectionThis example is provided to help you size an enclosure for your CompactLogix 5480 controller You need heat dissipation data from all components that are planned for your enclosure to calculate the enclosure size

With no active method of heat dissipation for example air conditioning either of the following approximate equations can be used for a metal cabinet

The maximum ambient rating of the CompactLogix 5480 controller is 60 degC (140 degF) If the maximum external cabinet temperature is 20 degC (68 degF) then T=40

In this example with only the controller the heat dissipation is 72 W that is the sum of all components in the enclosure In the following equation T=40 and Q=72

In this example the enclosure must have a minimum exterior surface of 0386 m2

If any portion of the enclosure cannot transfer heat exclude that value from the calculation

The minimum installation clearance for a CompactLogix 5480 controller is 26700 x 18400 x 15200 mm (1050 x 725 x 600 in) HxWxD

The standard cabinet depth in this example is 15420 mm (600 in)

To meet cooling and clearance requirements in this example the cabinet must be approximately 30480 x 35560 x 15420 mm(1200 x 1400 x 600 in) HxWxD

A = 2DW +2DH + 2WH

A = 2 x (01542 x 03556) + 2 x (01542 x 03048) + 2 x (03556 x 03048) = 04204 m2

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

Top

Bottom

SideSide

End cap

Cabinet

Metric Imperial

Where

bull T = Temperature difference between inside air and outside ambient (degC)

bull Q = Heat that is generated in enclosure (Watts)

bull A = Enclosure surface area (m2)

Where

bull T = Temperature difference between inside air and outside ambient (degF)

bull Q = Heat that is generated in enclosure (Watts)

bull A = Enclosure surface area (ft2)

The exterior surface of all six sides of an enclosure is calculated as

A = 2dw + 2dh + 2wh

Where d (depth) w (width) and h (height) are in meters

The exterior surface of all six sides of an enclosure is calculated as

A = (2dw + 2dh + 2wh) 144

Where d (depth) w (width) and h (height) are in inches

038Q

180T - 110

A =

408Q

T - 110

A =

038(7200)

180(4000) - 110A =

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 7

CompactLogix 5480 Controllers

This example uses the following conditions

bull All sides of the enclosure transfer heatbull Only the CompactLogix 5480 controller is installedbull Ambient temperature = 20 degC (68 degF)

DimensionsThe controller dimensions are as follows

Ground ConsiderationsYou must ground DIN rails according to the Industrial Automation Wiring and Grounding Guidelines publication 1770-41

You can use the following DIN rails

bull EN50022 - 35 x 75 mm (138 x 030 in)bull EN50022 - 35 x 15 mm (138 x 060 in)

System Power ConsiderationsThe CompactLogix 5480 controller provides power to a CompactLogix 5480 system via RTBs that are connected to external power supplies and installed on the controller

The RTBs provide the following power to the system

IMPORTANT If any of the following conditions exist the enclosure must be larger

bull Any sides of the enclosure cannot transfer heat

bull More equipment is included in the system

bull Ambient temperature is higher than 20 degC (68 degF)

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

13021 mm

(513 in)

16620 mm

(654 in)

12654 mm

(498 in)

12002 mm

(473 in)

13366 mm

(526 in)

16000 mm

(630 in)

ATTENTION This product is grounded through the DIN rail to

chassis ground Use zinc-plated chromate-passivated steel DIN rail

to assure proper grounding The use of other DIN rail materials (for

example aluminum or plastic) that can corrode oxidize or are poor

conductors can result in improper or intermittent grounding

Secure DIN rail to mounting surface approximately every 200 mm

(78 in) and use end-anchors appropriately Be sure to ground the

DIN rail properly See Industrial Automation Wiring and Grounding

Guidelines Rockwell Automationreg publication 1770-41 for more

information

Power Type Description

MOD Power

System-side power that is used to operate the CompactLogix 5480 system MOD power is provided through the MOD power RTB and passed across the MOD power bus bull The total continuous current draw across the MOD power bus must not be

more than 10 A max at 1832V DC

You must calculate the total MOD power that the controller and all local Compact 5000 IO modules draw to make sure that no more than 10 A of MOD power is drawn(1)

bull Confirm that the external MOD power supply is adequately sized for the total MOD power bus current draw in the system including the MOD power inrush current requirements

(1) If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000

IO modules can draw a maximum of 10 A in addition to the current the controller draws

SA Power

Field-side power that can be used to power field-side devices that are connected to some Compact 5000 IO modules SA power is provided through the SA power RTB and passed across the SA power bus

bull SA power is only required if your application includes local Compact 5000 IO modules that are connected to devices that use SA power

bull If you are using DC voltage for SA power the total continuous current draw across the MOD power bus must not be more than 10 A max at 18hellip32V DC

bull If you are using AC voltage for SA power the total continuous current draw across the MOD power bus must not be more than 10 A max at 18hellip240V AC

bull You can use a 5069-FPD field potential distributor to establish additional SA power buses in a CompactLogix 5480 system

If your system includes AC and DC modules that require SA power you must use a 5069-FPD field potential distributor to establish a new SA power bus

You separate the module types by SA power bus For example install DC module on the first SA power bus in the system and install the AC modules on the second SA power bus in the system

bull Confirm that the external SA power supply is sized adequately for the total SA power current draw in the system

UPS Control

Control signals from an external UPS that let the controller save the state of the program if power is lost The external UPS provides the power that is required to save the program via the MOD power RTB A UPS is not required for controller operation

8 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Controller onto the DIN Rail

1 Confirm that the DIN rail latches are closed

2 If the DIN rail latches are open gently push the rear latch back until the front latch pops up and clicks

3 Position the controller so that the back of it faces the DIN rail

4 Press the controller against the DIN rail until you hear a click

5 Confirm that all latches have fully closed and the controller is latched securely

Connect External Power Supplies to the ControllerBefore you connect MOD power or SA power to the RTBs on the CompactLogix 5480 controller complete the following tasks

bull Read System Power Considerations on page 8

bull Confirm that the external power supplies that MOD power and SA power are adequately sized for your CompactLogix 5480 system For more information see page 8

bull Verify that the external power supplies are turned off

bull Install the MOD power RTB SA power RTB and the UPS Control RTB if used

bull If IO modules are used verify that they are installed on the correct SA power bus

DC-type modules must reside on an SA power bus that uses DC power and AC-type modules must reside on an SA power bus that uses AC power

For more information see the technical documentation for Compact 5000 IO modules

IMPORTANT Remember the following

bull CompactLogix 5480 controllers do not have an embedded power supply that powers the system

The system is powered by external power supplies via

connections to the various power RTBs on the controller

bull We recommend that you use 1606 power supplies from Rockwell Automation to provide MOD power SA power and UPS control

bull You must use an external power supply that is dedicated to the UPS connection

For more information about which 1606 power supplies

are best for each power type see the Switched Mode

Power Supply Specifications Technical Data publication

1606-TD002

bull You can connect power from one external power supply to the MOD power and SA power RTBs However as stated previously we strongly recommend that you use separate external power supplies for MOD power and SA power respectively

The practice of using separate external power supplies can

help prevent unintended consequences that can result if

you use one supply

If you use separate external power supplies the loss of

power from one external power supply does not affect the

availability of power from the other supply For example if

separate external power supplies are used and SA power is

lost MOD power remains available for the Compact 5000

IO modules

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPSR

B

F

R

B

F

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPSR

B

F

R

B

F

Closed PositionOpen Position

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 9

CompactLogix 5480 Controllers

Install the MOD Power RTB

1 Hook the bottom of the MOD power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect MOD PowerThe way that you connect power to the MOD power RTB depends on whether you use UPS control signals or not

bull If you are not using UPS control signals you connect the external power supply directly to the MOD power RTB

In this case proceed to Connect to the MOD Power RTB from a Standard External Power Supply on page 10

bull If you are using UPS control signals you connect a UPS to the MOD power RTB

In this case proceed to Connect to the MOD Power RTB from a UPS on page 15

Connect to the MOD Power RTB from a Standard External Power Supply

Before you connect an external power source to the MOD power RTB make sure that the MOD power source is properly sized

1 Verify that the external power supply is not powered

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the 24V DC (+) connection on the external power supply into the first MOD (+) terminal on the RTB

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the 24V DC (mdash) connection on the external power supply into the first MOD (mdash) terminal on the RTB

5069-L4200ERMW

MOD Power RTB

IMPORTANT Your application can require a power control device for example

a switch between the external 24V DC power source and the

controller to control when the controller is powered If so you

must install the power control device at the VDC+ terminal on

the RTB

If you install the power control device at the VDC- terminal the

controller can fail to power up or power down properly

10 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

The following diagram shows an external 24V DC power supply that is connected to the MOD power RTB when you are not using UPS control signals

Install the SA Power RTBInstall the SA power RTB even if you do not use SA power

1 Hook the bottom of the SA power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect SA DC Power

Before you connect an external DC power source to the SA power RTB make sure that the SA power source is properly sized

For more information o n SA power see SA Power on page 8

1 Confirm that MOD power and SA power sources are turned off

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the DC (+) connection on the external power supply into the first SA (+) terminal on the RTB

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

24V DC

Power

Supply

+

ndashIMPORTANT SA power is only required if your application includes local

Compact 5000 IO modules that require SA power to operate

or are connected to field-side devices that are powered by

SA power

5069-L4200ERMW

SA Power RTB

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 11

CompactLogix 5480 Controllers

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the DC (mdash) connection on the external power supply into the first SA (mdash) terminal on the RTB

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

7 Insert the wire from an Earth Ground location into the first

Ground ( ) on the RTB

The Earth Ground location can be the external SA power supply the DIN rail or other Earth Ground location

8 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

The following diagram shows an external 24V DC power supply that is connected to the SA power RTB when you do not use UPS control signals

TIP

This symbol denotes a Functional Ground terminal that provides a

low impedance path between electric circuits and earth for functional

purposes and provides noise immunity improvement This connection

must be made for functional purposes

5069-L4200ERMW

24V DC

Power

Supply

+

ndash

24V DC

Power

Supply

+

ndash

MOD

Power

SA DC

Power

Functional Ground

12 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Connect SA AC Power

Before you connect an external AC power source to the SA power RTB make sure that the SA power source is properly sized

For more information o n SA power see SA Power on page 8

1 Verify that the SA power source is not powered on

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the L1AC (+) connection on the external power supply into the first SA (+) terminal on the RTB

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the L2NAC(mdash) connection on the external power supply into the first SA(mdash) terminal on the RTB

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

7 Insert the wire from an Earth Ground location into the first

Ground ( ) on the RTB

The Earth Ground location can be the external SA power supply the DIN rail or other Earth Ground location

8 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

This diagram shows an external 240V AC power supply that is connected to the SA power RTB when you do not use UPS control signals

IMPORTANT SA power is only required if your application includes local

Compact 5000 IO modules that require SA power to operate

or are connected to field-side devices that are powered by

SA power

TIP

This symbol denotes a Functional Ground terminal that provides a

low impedance path between electric circuits and earth for functional

purposes and provides noise immunity improvement This connection

must be made for functional purposes

5069-L4200ERMW

24V DC

Power

Supply

+

ndash

240V AC

Power

Supply

+

ndash

MOD

Power

SA AC

Power

Functional Ground

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 13

CompactLogix 5480 Controllers

Connect Control Signals Via UPS Control RTBThe CompactLogix 5480 controller does not have an internal energy storage module that lets the controller save the state of the program if system-side power is lost You must connect an external uninterruptible power supply (UPS) to the UPS control RTB to save the state of the program if power is lost

You connect control signals from an external power supply to the UPS control RTB to let the controller experience a controlled shutdown upon an incoming power loss

When a UPS connection is detected the CompactLogix 5480 controller defaults to initiate shutdown 1 minute after a power loss indication

We recommend that you use 1606 switched mode uninterruptible power supplies from Rockwell Automation with a CompactLogix 5480 controller for example the 1606-XLS240-UPS power supply

For more information on Bulletin 1606 uninterruptible power supplies see the following

bull Bulletin 1606 DC-UPS Uninterruptible Power Supply Installation Instructions publication 1606-IN025

bull Bulletin 1606 Switched Mode Power Supplies Reference Manual publication 1606-RM036

The switched mode uninterruptible power supplies use a 12-volt battery module to bridge power failures and voltage fluctuations We recommend that you use the 1606-XLSBATASSY1 battery module from Rockwell Automation

You can use other accessories such as replacement batteries mounting kits and panelwall mounting brackets with the battery module

For more information on and the battery module and accessories that you can use with them see the following

bull Bulletin 1606 12V 7Ah Battery Modules Installation Instructions publication 1606-IN011

bull Bulletin 1606 Switched Mode Power Supply Battery Modules (12V 7Ah) Reference Manual publication 1606-RM037

UPS Control SignalsThese control signals are used on the UPS Control RTB

UPS Control RTB Terminals

Signal Description

UPS Ready (R)

An input signal from the UPS to the controller that indicates the UPS is working and can buffer during a power failure

The charge level for a UPS to be ready to buffer during a power failure varies For example the 1606-XLS240-UPS power supply must be greater than 85 charged to be ready

The letter R indicates the RTB terminal for this signal

Buffering (B)

An input signal from the UPS to the controller that indicates the UPS battery is providing power because the external power has failed

After a preset time (typically 1 minute after power failure) the controller performs an orderly shutdown by stopping execution and saving the state of the controller

The letter B indicates the RTB terminal for this signal

Battery Fail (F)

An input from the UPS to the controller that indicates the UPS battery has failed and the controller cannot operate from stored energy

In this case the controller does not attempt to save the state of the program when the external power fails The controller issues an alarm if a UPS was previously attached and ready to buffer

The letter F indicates the RTB terminal for this signal

Inhibit (I)

An output signal from the controller to the UPS that disables the UPS signal output The INHIBIT signal is triggered after data is backed up and the system is ready to shut down

The letter I indicates the RTB terminal for this signal

14 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the UPS Control RTBInstall the UPS control RTB even if you do not intend to connect uninterruptible power to the controller

1 Hook the bottom of the UPS power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect UPS Control Signals

1 Verify that all sources of MOD power and SA power are turned off

2 Verify the followingbull A 24V DC power supply is connected to the 24V IN

terminals on the UPSbull A 12V DC battery is connected to the 12V BAT terminals

on the UPS

For more information see the example graphic on page 17

Connect to the MOD Power RTB from a UPS

1 Daisy chain the wires from these connections on the UPSbull 24V OUT (+)bull Ready (1)bull Buffering (3)bull Battery Fail (5)bull Inhibit (7)

2 Connect one wire to each (+) terminal on the MOD power RTB as shown in the example graphic on page 17a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Daisy chain a wire that is connected to the 24V OUT (ndash) terminal on the UPS and a second wire

4 Connect one wire to each (ndash) terminal on the MOD power RTB a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

IMPORTANT The UPS terminal labels in this section represent the labels on

a 1606-XLS240-UPS power supply Your UPS terminals can be

labeled differently

5069-L4200ERMW

UPS Control RTB

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 15

CompactLogix 5480 Controllers

Connect to the UPS Control RTB from a UPS

1 Connect a wire from the Ready (2) connection on the UPS to the UPS Ready terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

2 Connect a wire from the Buffering (4) connection on the UPS to the Buffering terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Connect a wire from the Battery Fail (6) connection on the UPS to the Battery Fail terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

4 Connect a wire from the Inhibit (8) connection on the UPS to the Inhibit terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

16 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

This diagram shows a 1606-XLS240-UPS power supply battery that is connected to a CompactLogix 5480 controller

5069-L4200ERMW

UPS Ready

Buffering

Battery Fail

Inhibit

(7) Inhibit +

(8) Inhibit ndash

24V DC

Power

Supply

Ready

(1) (2)

+ ndash + ndash + ndash + ndash

N L PE

Buffering

(3) (4)

Battery Fail

(5) (6)

12V DC Battery

(for example 1606-XLSBATASSY1)

+ ndash

DC-UPS

(1606-XLS240-UPS)

24V

IN

12V

BAT

24V

OUT

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 17

CompactLogix 5480 Controllers

Disconnect Wires from the RTBsIf necessary complete these tasks to disconnect wires from any RTB on the controller

1 Turn the screwdriver counter-clockwise to open the terminal

2 Remove the wire

Install Compact 5000 IO ModulesComplete one of the following

bull If you do not use local Compact 5000 IO modules in the system proceed to Install the End Cap on page 18

bull If you use local Compact 5000 IO modules in the system install the modules to the right side of the controller

After the IO modules are installed install the end cap on the right side of the last IO module in the system For more information on how to install the end cap see page 18

For more information on how to install Compact 5000IO modules see the installation instructions available with each Compact 5000 IO module catalog number

Install the End CapYou must install an end cap on the right side of the last module in a CompactLogix 5480 system The end cap covers the exposed interconnections on the last module in the system If you do not install the end cap before powering the system equipment damage or injury from electric shock can result

If you do not intend to install Compact 5000 IO modules to the system before you turn on power to the controller install the end cap

1 Align the end cap with the interlocking pieces on the controller

2 Push the end cap toward the DIN rail until it locks into place

Power the System

After the end cap is installed on the last module in the system turn on power to the MOD power RTB and the SA power RTB

IMPORTANT Consider the following before you power the system

bull Make sure to remove the debris shield from the controller before power-up

bull As noted previously you must install working controller firmware to use the COS on the controller There are two ways to install working firmware The ways are described beginning on page 23

One of the methods to install working controller firmware

uses the SD card that ships with the controller

ndash If you intend to use the SD card to install working

controller firmware go to Use a Secure Digital Card

to Install Controller Firmware on page 24

Complete the steps described in that section apply

power to the controller and return to the next

section that is Set the Network Internet Protocol

(IP) Addresses on page 19

ndash If you do not intend to use the SD card to install

working controller firmware turn on the power now

and proceed to the next section

Top Interlocking

Pieces

End Cap

Bottom Interlocking

Pieces

18 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Set the Network Internet Protocol (IP) AddressesYou must set an IP address on Ethernet ports for the controller to operate on an EtherNetIP network via that port

Out-of-the-box the following applies to Ethernet ports A1 A2 and B1

bull The ports are DHCP-enabled and the IP address is set automatically via a DHCP server

If there is no DHCP server available to set the IP address you must set the IP address manually

bull If ports A1 and A2 are configured to use DLRLinear mode you set only one IP address that is used on both ports

bull Control ports must use unique subnets

When ports A1 and A2 are configured to use DLRLinear mode however they use the same subnet because they are configured as one port

You can use one of the following to set the IP address on the controller when it is in the out-of-the-box condition

bull DHCP server

bull BOOTP DHCP EtherNetIP Commissioning tool version 30200 or later

bull RSLinx Classic software version 41000 or later

bull FactoryTalk Linx software version 61000 or later

bull Logix Designer application version 320100 or later

For more information on how to set or change the IP address on a CompactLogix 5480 controller see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

Connect the Controller to an EtherNetIP Network

Use an RJ45 cable to connect the controller to an EtherNetIP network

1 If needed wire the RJ45 connector as shown

2 Connect RJ45 cables to the controller Ethernet ports

IMPORTANT Before you can connect a CompactLogix 5480 controller to an

EtherNetIP network you must first install the network and

its components

This section assumes that the EtherNetIP network is

installed

Connector Number

Color

1585J 8-pin Cables with Support for 101001000 Mbps

1585J 8-pin Cables with Support for 10100 Mbps

1585J 4-pin Cables with Support for 10100 Mbps

1WhiteOrange

BI_DA+ TxData +

2 Orange BI_DA- TxData -

3WhiteGreen

BI_DB+ Recv Data +

4 Blue BI_DC+ Unused mdash

5 WhiteBlue BI_DC- Unused mdash

6 Green BI_DB- Recv Data -

7WhiteBrown

BI_DD+ Unused mdash

8 Brown BI_DD- Unused mdash

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 19

CompactLogix 5480 Controllers

Remove and Replace the Controller

1 Turn off power to the MOD power and the SA power RTBs

2 If there are local Compact 5000 IO modules in the system remove them If not skip to step 3

3 Disconnect wires from the RTBs

For more information see Disconnect Wires from the RTBs on page 18

4 Pull the RTB handles to remove the RTBs

IMPORTANT When you remove MOD power from the controller you shut down

power to all modules in the CompactLogix 5480 system That is

all system-side is removed When you remove SA power from the

controller all field-side power that is provided by the controller is

removed If SA power that is provided via a 5069-FPD field

potential distributor the system does not lose SA power to the

right of the field potential distributor

In this case you must use a separate power source for the SA

power RTB on the field potential distributor

We strongly recommend that before you remove MOD power or

SA power that you take the appropriate actions to help prevent

unintended consequences that can result from a system power

shutdown

Despite the removal of power from SA RTBs on the controller or

field potential distributor the 5069-OB16 and 5069-OB16F

modules continue to receive field-side power The modules

receive power from an external power source that is connected to

the LA (+) and LA (ndash) module terminals

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

UPS Control RTB

MOD Power RTB

SA Power RTB

20 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

5 Remove all cables from the controller

6 Push down on the front of the DIN rail latches

A click indicates that the DIN rail latches are open

If the DIN rail latches fail to remain in the open position hold them down

7 Pull the controller off the DIN rail

8 Repeat the installation steps that are described beginning at Install the Controller onto the DIN Rail on page 9

9 Apply MOD power and if necessary SA power to the system

Replace the FansThe CompactLogix 5480 controller uses fans at the top and bottom of the controller to help maintain lower operating temperatures when the controller is operating

Fan use includes speed control and monitoring Faults indicate fan operating conditions as follows

bull Minor faults - Triggered when a fan is not operating at the requested speed or if a fan fails to operate at all

In your Logix Designer application project you can use the Minor Faults tab on the Controller Properties dialog box to monitor for these faults

bull Major fault - Triggered if both fans fail and the controller goes over the maximum operating temperature

In this case the controller stops operating

You can order replacement fans Replacement fans come in pairs The fans are unique by position and keyed to help make sure that you install the correct fan in each position

The fans are labeled Fan 1 - Top and Fan 2 - Bottom

Consider the following

bull We recommend that you replace the fans in pairs That is if you replace the one fan we recommend that you replace the other fan too

bull You can replace fans during controller operation The fans support removal and insertion under power

bull Do not remove both fans at once if the controller is operating That is remove a fan and install the replacement fan before you remove the other fan

Remove the Top Fan

1 Push up on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

TIP In your Logix Designer application project you can

use the Major Faults tab on the Controller

Properties dialog box to monitor for this fault

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

R

B

F

Open Position

IMPORTANT If you replace fans while the controller is operating

do not touch live voltage components

TIP If the hinges do not disengage when you push up on the front of the

fan then use a screwdriver as a pry tool

5069-L4200ERMW

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 21

CompactLogix 5480 Controllers

2 Pull the fan out of the slot at the top of the controller

Install the Top Replacement Fan

1 Insert the top replacement fan into the slot at the top of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push down on the top replacement fan until it clicks in place

Remove the Bottom Fan

1 Push the down on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

2 Pull the fan out of the slot at the bottom of the controller

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

TIP If the hinges do not disengage when you push down on the front of

the fan then use a screwdriver as a pry tool

5069-L4200ERMW

5069-L4200ERMW

22 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Bottom Replacement Fan

1 Insert the bottom replacement fan into the slot at the bottom of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push up on the bottom replacement fan until it clicks in place

Use the COS For Windows-based ComputingThe COS on a CompactLogix 5480 controller runs in parallel with the Logix control engine You are not required to use the COS

You can use the following methods to install working controller firmware when the controller is in the out-of-box state

bull ControlFLASHtrade or ControlFLASH Plustrade softwarebull Secure Digital (SD) card

Use a Flash Programming Tool to Install Controller FirmwareYou can use ControlFLASH and ControlFLASH Plus software to install controller firmware

The following requirements apply when you use ControlFLASH or ControlFLASH Plus to install working controller firmware

bull You must use one of the followingndash ControlFLASH software version 150100 or laterndash ControlFLASH Plus version 20000 or later

bull You must use a Linx-based software application with your flash programming toolndash With ControlFLASH software you can use RSLinx

Classic Lite RSLinx Classic RSLinx Enterprise or FactoryTalk Linx

ndash With ControlFLASH Plus software you must use FactoryTalk Linx

Minimum software versions apply with Linx-based software For more information on the minimum software version requirements see the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

5069-L4200ERMW

5069-L4200ERMW

IMPORTANT Before you can use the COS you must install working controller firmware The requirement applies even if you

are not using the controller for real-time control If you do not

install working controller firmware the COS does not start

In the out-of-box state the controller uses firmware revision

1xxx On a CompactLogix 5480 controller the minimum

working controller firmware is revision 32012

TIP We recommend that you connect your peripherals to the

ports that are dedicated to COS use before you install

controller firmware

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 23

CompactLogix 5480 Controllers

Download the Flash Programming Tool

ControlFLASH and ControlFLASH Plus software are available from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

Download the installation files and install the software

Download the Controller Firmware

After the flash programming tool is installed download the controller firmware from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

The initial download is a exe file You use the Rockwell Automation Download Manager to extract a dmk from the downloaded file

Install the Controller Firmware

To install the controller firmware via a flash programming tool you complete the following steps

1 To start the tool click StartgtAll ProgramsgtFlashing Programming ToolsgtControlFLASH or ControlFLASH Plus

2 Follow the prompts to complete the following stepsa Choose the controllerb Select the firmware revisionc Install the controller firmware

A dialog box confirms that the installation was successful

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use a flash programming tool to install controller firmware see the following

bull ControlFLASH Firmware Upgrade Kit User Manual publication 1756-UM105

bull ControlFLASH Plus Quick Start Guide publication CFP-QS001

bull CompactLogix 5480 Controllers User Manual publication 5069-UM002

Use a Secure Digital Card to Install Controller FirmwareYou can use an SD card to install controller firmware CompactLogix 5480 controllers ship with an SD card installed behind the front door on the controller

To use an SD card to install controller firmware complete the following steps

1 Before you turn on power to the controller remove the SD card from the controller

2 Install the SD card into another working CompactLogix 5480 controller that has a Logix Designer application project on it

3 Save the project to the SD card

4 Remove the SD card from the working controller and reinstall it in the new controller

5 Turn on power to the new controller

When the new controller powers up it automatically updates the firmware to the revision that is stored on the SD card

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use the SD card with the controller after valid firmware is installed and the controller is powered see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

IMPORTANT These steps only highlight the major tasks that you

complete to install controller firmware with ControlFLASH

To successfully install controller firmware you must complete other tasks that are not described here

For complete information on how to install controller

firmware see the publications listed at the end of the section

IMPORTANT To install controller firmware on a new CompactLogix 5480

controller via an SD card you must have another controller of

the same type that is already working

The SD card method requires that you save the Logix Designer

application project from the working controller to the SD card

before you use it in the new controller

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

SD Card Slot

24 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpecificationsThis table lists a subset of controller specifications For a complete list of specifications see the CompactLogix 5380 Compact GuardLogixreg 5380 and CompactLogix 5480 Controllers Specifications Technical Data publication 5069-TD002

Environmental Specifications - CompactLogix 5480 Controllers

Attribute 5069-L430ERMW 5069-L450ERMW 5069-4100ERMW 5069-L4200ERMW

Temperature operating

IEC 60068-2-1 (Test Ad Operating Cold)

IEC 60068-2-2 (Test Bd Operating Dry Heat)

IEC 60068-2-14 (Test Na Operating Thermal Shock)

0 degC lt Ta lt +60 degC

(+32 degF lt Ta lt +140 degF)

Temperature surrounding air max 60 degC (140 degF)

Enclosure Type Rating None (open-style)

Voltage and current ratings

MOD Power voltage range 18hellip32V DC

MOD Power power max 72 W

MOD Power current typical 4 A

MOD Power inrush 4 A for 15 ms

MOD Power Passthrough(1) 6 A 18hellip32V DC

MOD Power current rating max10 A

Do not exceed 10 A current draw at the MOD power RTB(4)

SA Power voltage ranges(2) 0hellip32V DC

0hellip240V AC 47hellip63 Hz

SA Power current max (2) 10 mA (DC power)

25 mA (AC power)

SA Power Passthrough(2) (3) 999 A 0hellip32V DC

9975 A 0hellip240V AC 47hellip63 Hz

SA Power current rating max(2) Do not exceed 10 A current draw at the SA power RTB

Isolation voltage

300V (continuous) Basic Insulation Type SA and MOD Power to Backplane

300V (continuous) Basic Insulation Type SA to MOD Power

300V (continuous) Basic Insulation Type Ethernet to Backplane

300V (continuous) Double Insulation Type Ethernet to MOD Power

300V (continuous) Double Insulation Type Ethernet to SA Power

50V (continuous) Functional Insulation Type Ethernet to USB ports and DisplayPort

300V (continuous) Basic Insulation Type USB ports and DisplayPort to Backplane

300V (continuous) Double Insulation Type USB ports and DisplayPort to MOD Power

300V (continuous) Double Insulation Type USB ports and DisplayPort to SA Power

No isolation between Ethernet ports

Type tested at 1500V AC for 60 s

Wire size

5069-RTB4-SCREW 5069-RTB6-SCREW connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 35 mm (014 in) max diameter including insulation single wire connection only

5069-RTB4-UPS connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 29 mm (011 in) max diameter including insulation single wire connection only

Ethernet connections

Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2

Insulation-stripping length 5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 12 mm (047 in)

Terminal block torque5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 04 Nbullm (35 lbbullin)

ATTENTION Do not wire more than two conductors on one RTB terminal

(1) Maximum level of MOD power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(2) SA power specifications are based on the number and type of Compact 5000 IO modules that are used in the system If the set of IO modules that is used in the system require AC and DC voltage you must install a 5069-FPD field

potential distributor to separate the module types

(3) Maximum level of SA power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(4) Remember MOD power usage includes the total power that the controller and local Compact 5000 IO modules use If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000 IO

modules can draw a maximum of 10 A in addition to the current that the controller draws

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 25

CompactLogix 5480 Controllers

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation

You can view or download publications at httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage To order paper copies of technical documentation contact your local Allen-Bradley distributor or Rockwell Automationreg sales representative

Resource Description

CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069-TD002

Provides specifications and other technical data for CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 controllers

CompactLogix 5480 Controllers User Manual publication 5069-UM002 Describes how to configure operate and monitor CompactLogix 5480 controllers

Industrial Automation Wiring and Grounding Guidelines publication 1770-41 Provides general guidelines for installing a Rockwell Automationreg industrial system

Product Certifications website rokautocertifications Provides declarations of conformity certificates and other certification details

26 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU ltFEFF00560065007200770065006e00640065006e0020005300690065002000640069006500730065002000450069006e007300740065006c006c0075006e00670065006e0020007a0075006d002000450072007300740065006c006c0065006e00200076006f006e002000410064006f006200650020005000440046002d0044006f006b0075006d0065006e00740065006e002c00200076006f006e002000640065006e0065006e002000530069006500200068006f00630068007700650072007400690067006500200044007200750063006b006500200061007500660020004400650073006b0074006f0070002d0044007200750063006b00650072006e00200075006e0064002000500072006f006f0066002d00470065007200e400740065006e002000650072007a0065007500670065006e0020006d00f60063006800740065006e002e002000450072007300740065006c006c007400650020005000440046002d0044006f006b0075006d0065006e007400650020006b00f6006e006e0065006e0020006d006900740020004100630072006f00620061007400200075006e0064002000410064006f00620065002000520065006100640065007200200035002e00300020006f0064006500720020006800f600680065007200200067006500f600660066006e00650074002000770065007200640065006e002egt ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR ltFEFF004200720075006b00200064006900730073006500200069006e006e007300740069006c006c0069006e00670065006e0065002000740069006c002000e50020006f0070007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740065007200200066006f00720020007500740073006b00720069006600740020006100760020006800f800790020006b00760061006c00690074006500740020007000e500200062006f007200640073006b0072006900760065007200200065006c006c00650072002000700072006f006f006600650072002e0020005000440046002d0064006f006b0075006d0065006e00740065006e00650020006b0061006e002000e50070006e00650073002000690020004100630072006f00620061007400200065006c006c00650072002000410064006f00620065002000520065006100640065007200200035002e003000200065006c006c00650072002000730065006e006500720065002egt PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 4: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

CompactLogix 5480 Controllers

Environment and Enclosure

ATTENTION This equipment is intended for use in a Pollution Degree 2 industrial environment in overvoltage Category II applications (as defined in ENIEC

60664-1) at altitudes up to 2000 m (6562 ft) without derating

This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such

environments

This equipment is supplied as open-type equipment for indoor use It must be mounted within an enclosure that is suitably designed for those specific

environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts The enclosure must

have suitable flame-retardant properties to prevent or minimize the spread of flame complying with a flame spread rating of 5VA or be approved for the

application if nonmetallic The interior of the enclosure must be accessible only by the use of a tool Subsequent sections of this publication may contain more

information regarding specific enclosure type ratings that are required to comply with certain product safety certifications

In addition to this publication see the following

bull Industrial Automation Wiring and Grounding Guidelines publication 1770-41 for more installation requirements

bull NEMA 250 and ENIEC 60529 as applicable for explanations of the degrees of protection provided by enclosures

Prevent Electrostatic Discharge

ATTENTION This equipment is sensitive to electrostatic discharge which can cause internal damage and affect normal operation Follow these guidelines when

you handle this equipment

bull Touch a grounded object to discharge potential static

bull Wear an approved grounding wriststrap

bull Do not touch connectors or pins on component boards

bull Do not touch circuit components inside the equipment

bull Use a static-safe workstation if available

bull Store the equipment in appropriate static-safe packaging when not in use

ATTENTION

bull In case of malfunction or damage no attempts at repair should be made The controller should be returned to the manufacturer for repair Do not dismantle the controller

bull This equipment is certified for use only within the surrounding air temperature range of 0hellip60 degC (32hellip140 degF) The equipment must not be used outside of this range

bull The USB programming port is intended for temporary local programming purposes only and not intended for permanent connection The USB programming port connection is not to exceed 30 m (984 ft) and must not contain hubs You must connect the programming equipment to a ground system that is common with the controller

bull Devices that are connected to USB 30 ports must reside in the same control enclosure as the controller This requirement applies to devices that are powered by the USB 30 ports or not You must connect the devices to a ground system that is common with the controller Alternatively you can connect the device to the common ground system via a USB hub that provides galvanic isolation

bull USB 30 port connections are not to exceed 30 m (984 ft)

bull DisplayPort cables or adapters that are used with this product must be certified by VESA A list of certified equipment and cables is on the VESA website (wwwvesaorg) Use of non-certified cables and adapters can cause damage or improper operation DisplayPort connections are not to exceed 30 m (984 ft)

bull Displays that are connected to DisplayPort must connect to a ground system that is common with the controller Alternatively displays can be connected by a display extender that is connected to the common ground system with the controller and provides galvanic isolation

bull Use only a soft dry anti-static cloth to wipe down equipment Do not use any cleaning agents

Electrical Safety Considerations

ATTENTION Do not wire more than 2 conductors on a single RTB terminal

Waste Electrical and Electronic Equipment (WEEE)

At the end of its life this equipment should be collected separately from any unsorted municipal waste

4 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

About the ControllerThe following graphic shows a CompactLogix 5480 controller

IMPORTANTAny illustrations charts sample programs and layout examples that are shown in this publication are intended solely for the purposes of example Since

there are many variables and requirements that are associated with any particular installation Rockwell Automation does not assume responsibility or

liability for actual use that is based on the examples that are shown in this publication

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

1

6

7

9

8

2

3

4

14

11

16

10

5

1312

15

18

20

17

19

Front View

Bottom View

22

21

23

CompactLogix 5480 Controller Parts

Number Item Description

1 DIN rail latches Secure adapter to DIN rail

2 Mode switch Lets you choose the controller operating mode

3 SD card slot Location for SD card

4 Reset button Resets the controller to factory default condition

5 Four-character displayScrolls information about the controller such as firmware revision or project status

6 USB programming port Provides temporary connection to download projects

7 Ethernet port B1Lets the controller connect to the following networksbull Enterprise-level networkbull Device-level network

8 Ethernet port A1Lets the controller connect to device-level networks

9 Ethernet port A2

10Network and link status indicators for ports B1 A1 and A2 Show the state of the Ethernet ports and network

communication activity on each port

11Speed and link status indicators for port X1

12 Bottom fanHelps regulate controller temperature

Controller ships with fans installed You can replace fans if necessary

13Controller status indicators

Show the state of the controller in multiple respects

14 Top fanHelps regulate controller temperature

Controller ships with fans installed You can replace fans if necessary

15MOD power and SA power status indicators

Show the state of module (MOD) power and sensor actuator (SA) power respectively

16 UPS Control RTB

Connector for control signals to and from an uninterruptible power supply (UPS) that are used to support a controlled shutdown upon incoming power loss

17MOD power bus connector

MOD power bus connection that passes MOD power to the next local Compact 5000 IO module in the system

18 MOD power RTBConnector for external power supply to provide MOD power to the system

19 SA power bus connectorSA power bus connection that passes SA power to the next local Compact 5000 IO module in the system

20 SA power RTBConnector for external power supply to provide SA power to the systemlsquo

21 Ethernet port X1 Used with the COS on the controller

22 USB 30 portsConnectors for peripherals that are used with the COS on the controller(2)

(2) Devices that are connected to the controller via a USB 30 port must reside in the same control enclosure as

the controller This requirement applies to devices that are powered by the USB 30 ports or not You must

connect the devices to a ground system that is common with the controller Alternatively you can connect

the device to the common ground system via a USB hub that provides galvanic isolation

23DisplayPort connection(1)

(1) Any DisplayPort cables or adapters that are used with this product must be certified by VESA A list of

certified equipment and cables is on the VESA website (wwwvesaorg) Use of non-certified cables and

adapters can cause damage or improper operation

Connector to use a display with the COS on the controller

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 5

CompactLogix 5480 Controllers

Required System ComponentsBefore you install the controller verify that you have the following components

System PlanningFollow these rules when planning your system configuration

bull If the CompactLogix 5480 system includes only a controller you can mount the DIN rail in any orientation

bull If your CompactLogix 5480 system includes local Compact 5000 IO modules you must mount the DIN rail horizontally

bull The controller is the leftmost component in the system

bull Local Compact 5000 IO modules are installed to the right of the controller

bull The controller supports as many as 31 local Compact 5000 IO modules

bull Before power-up make sure that the end cap is installed on the right side of the controller or rightmost local Compact 5000 IO module if IO modules are used

Components Used to Install a CompactLogix 5480 Controller

Component Description

Removable Terminal Blocks (RTB)

An RTB that is used to connect MOD power (system-side power) to the controller - 5069-RTB4-SCREW RTB (Ships with the controller)

An RTB that is used to connect SA power (field-side power) - 5069-RTB6-SCREW RTB (Ships with the controller)

An RTB that is used to connect UPS (uninterruptible power) - 5069-L4UPSRTB (Ships with the controller)

External power supply for MOD power

A power supply that is adequately sized to provide MOD power that is system-side power to the CompactLogix 5480 system

For more information see System Power Considerations on page 8

External power supply for SA power

A power supply that is adequately sized to provide SA power that is field-side power to the CompactLogix 5480 system

IMPORTANT SA power is only required if your application includes local Compact 5000 IO modules that are connected to devices that use SA power

For more information see System Power Considerations on page 8

External uninterruptible power supply for UPS control signals

A power supply that provides UPS control signals so that the controller can save the state of the program when power is lost A UPS is only required if your system uses UPS control signals

For more information see Connect Control Signals Via UPS Control RTB on page 14

Tools

You use the following tools to wire the RTBsbull Screwdriverbull Wire stripperbull Wires

For more information on available wire sizes and wire insulation-stripping length see Specifications on page 25

DIN rail

Compatible zinc-plated chromate steel DIN rail

You can use the following DIN railsbull EN50022 - 35 x 75 mm (138 x 030 in)bull EN50022 - 35 x 15 mm (138 x 060 in)

EtherNetIP network components

If your CompactLogix 5480 controller operates on an EtherNetIP network you must install the network and all required components

Software

When you install the controller you assign IP addresses on the controller You can use the following to assign IP addresses

bull DHCP server

bull BOOTP DHCP EtherNetIP Commissioning tool version 30200 or later

bull RSLinxreg Classic software version 41000 or later

bull FactoryTalkreg Linx version 61000 or later

bull Logix Designer application version 320100 or later

For more information see Set the Network Internet Protocol (IP) Addresses on page 19

ATTENTION Do not discard the end cap Use this end cap

to cover the exposed interconnections on the last module

on the DIN rail Failure to do so could result in equipment

damage or injury from electric shock

Components Used to Install a CompactLogix 5480 Controller

Component Description

6 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpacingMaintain spacing from enclosure walls wireways and adjacent equipment Ambient temperature is higher at the top of an enclosed cabinet

The minimum distance on of a system that includes only a CompactLogix 5480 controller is as follows

bull 2500 mm (098 in) between the sides and the cabinet

bull 2500 mm (098 in) between the front of the controller and the cabinet

bull 5000 mm (196 in) between the top and bottom and the cabinet

We recommend that you install the controller near the bottom of the enclosure where ambient temperature is lower

Enclosure SelectionThis example is provided to help you size an enclosure for your CompactLogix 5480 controller You need heat dissipation data from all components that are planned for your enclosure to calculate the enclosure size

With no active method of heat dissipation for example air conditioning either of the following approximate equations can be used for a metal cabinet

The maximum ambient rating of the CompactLogix 5480 controller is 60 degC (140 degF) If the maximum external cabinet temperature is 20 degC (68 degF) then T=40

In this example with only the controller the heat dissipation is 72 W that is the sum of all components in the enclosure In the following equation T=40 and Q=72

In this example the enclosure must have a minimum exterior surface of 0386 m2

If any portion of the enclosure cannot transfer heat exclude that value from the calculation

The minimum installation clearance for a CompactLogix 5480 controller is 26700 x 18400 x 15200 mm (1050 x 725 x 600 in) HxWxD

The standard cabinet depth in this example is 15420 mm (600 in)

To meet cooling and clearance requirements in this example the cabinet must be approximately 30480 x 35560 x 15420 mm(1200 x 1400 x 600 in) HxWxD

A = 2DW +2DH + 2WH

A = 2 x (01542 x 03556) + 2 x (01542 x 03048) + 2 x (03556 x 03048) = 04204 m2

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

Top

Bottom

SideSide

End cap

Cabinet

Metric Imperial

Where

bull T = Temperature difference between inside air and outside ambient (degC)

bull Q = Heat that is generated in enclosure (Watts)

bull A = Enclosure surface area (m2)

Where

bull T = Temperature difference between inside air and outside ambient (degF)

bull Q = Heat that is generated in enclosure (Watts)

bull A = Enclosure surface area (ft2)

The exterior surface of all six sides of an enclosure is calculated as

A = 2dw + 2dh + 2wh

Where d (depth) w (width) and h (height) are in meters

The exterior surface of all six sides of an enclosure is calculated as

A = (2dw + 2dh + 2wh) 144

Where d (depth) w (width) and h (height) are in inches

038Q

180T - 110

A =

408Q

T - 110

A =

038(7200)

180(4000) - 110A =

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 7

CompactLogix 5480 Controllers

This example uses the following conditions

bull All sides of the enclosure transfer heatbull Only the CompactLogix 5480 controller is installedbull Ambient temperature = 20 degC (68 degF)

DimensionsThe controller dimensions are as follows

Ground ConsiderationsYou must ground DIN rails according to the Industrial Automation Wiring and Grounding Guidelines publication 1770-41

You can use the following DIN rails

bull EN50022 - 35 x 75 mm (138 x 030 in)bull EN50022 - 35 x 15 mm (138 x 060 in)

System Power ConsiderationsThe CompactLogix 5480 controller provides power to a CompactLogix 5480 system via RTBs that are connected to external power supplies and installed on the controller

The RTBs provide the following power to the system

IMPORTANT If any of the following conditions exist the enclosure must be larger

bull Any sides of the enclosure cannot transfer heat

bull More equipment is included in the system

bull Ambient temperature is higher than 20 degC (68 degF)

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

13021 mm

(513 in)

16620 mm

(654 in)

12654 mm

(498 in)

12002 mm

(473 in)

13366 mm

(526 in)

16000 mm

(630 in)

ATTENTION This product is grounded through the DIN rail to

chassis ground Use zinc-plated chromate-passivated steel DIN rail

to assure proper grounding The use of other DIN rail materials (for

example aluminum or plastic) that can corrode oxidize or are poor

conductors can result in improper or intermittent grounding

Secure DIN rail to mounting surface approximately every 200 mm

(78 in) and use end-anchors appropriately Be sure to ground the

DIN rail properly See Industrial Automation Wiring and Grounding

Guidelines Rockwell Automationreg publication 1770-41 for more

information

Power Type Description

MOD Power

System-side power that is used to operate the CompactLogix 5480 system MOD power is provided through the MOD power RTB and passed across the MOD power bus bull The total continuous current draw across the MOD power bus must not be

more than 10 A max at 1832V DC

You must calculate the total MOD power that the controller and all local Compact 5000 IO modules draw to make sure that no more than 10 A of MOD power is drawn(1)

bull Confirm that the external MOD power supply is adequately sized for the total MOD power bus current draw in the system including the MOD power inrush current requirements

(1) If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000

IO modules can draw a maximum of 10 A in addition to the current the controller draws

SA Power

Field-side power that can be used to power field-side devices that are connected to some Compact 5000 IO modules SA power is provided through the SA power RTB and passed across the SA power bus

bull SA power is only required if your application includes local Compact 5000 IO modules that are connected to devices that use SA power

bull If you are using DC voltage for SA power the total continuous current draw across the MOD power bus must not be more than 10 A max at 18hellip32V DC

bull If you are using AC voltage for SA power the total continuous current draw across the MOD power bus must not be more than 10 A max at 18hellip240V AC

bull You can use a 5069-FPD field potential distributor to establish additional SA power buses in a CompactLogix 5480 system

If your system includes AC and DC modules that require SA power you must use a 5069-FPD field potential distributor to establish a new SA power bus

You separate the module types by SA power bus For example install DC module on the first SA power bus in the system and install the AC modules on the second SA power bus in the system

bull Confirm that the external SA power supply is sized adequately for the total SA power current draw in the system

UPS Control

Control signals from an external UPS that let the controller save the state of the program if power is lost The external UPS provides the power that is required to save the program via the MOD power RTB A UPS is not required for controller operation

8 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Controller onto the DIN Rail

1 Confirm that the DIN rail latches are closed

2 If the DIN rail latches are open gently push the rear latch back until the front latch pops up and clicks

3 Position the controller so that the back of it faces the DIN rail

4 Press the controller against the DIN rail until you hear a click

5 Confirm that all latches have fully closed and the controller is latched securely

Connect External Power Supplies to the ControllerBefore you connect MOD power or SA power to the RTBs on the CompactLogix 5480 controller complete the following tasks

bull Read System Power Considerations on page 8

bull Confirm that the external power supplies that MOD power and SA power are adequately sized for your CompactLogix 5480 system For more information see page 8

bull Verify that the external power supplies are turned off

bull Install the MOD power RTB SA power RTB and the UPS Control RTB if used

bull If IO modules are used verify that they are installed on the correct SA power bus

DC-type modules must reside on an SA power bus that uses DC power and AC-type modules must reside on an SA power bus that uses AC power

For more information see the technical documentation for Compact 5000 IO modules

IMPORTANT Remember the following

bull CompactLogix 5480 controllers do not have an embedded power supply that powers the system

The system is powered by external power supplies via

connections to the various power RTBs on the controller

bull We recommend that you use 1606 power supplies from Rockwell Automation to provide MOD power SA power and UPS control

bull You must use an external power supply that is dedicated to the UPS connection

For more information about which 1606 power supplies

are best for each power type see the Switched Mode

Power Supply Specifications Technical Data publication

1606-TD002

bull You can connect power from one external power supply to the MOD power and SA power RTBs However as stated previously we strongly recommend that you use separate external power supplies for MOD power and SA power respectively

The practice of using separate external power supplies can

help prevent unintended consequences that can result if

you use one supply

If you use separate external power supplies the loss of

power from one external power supply does not affect the

availability of power from the other supply For example if

separate external power supplies are used and SA power is

lost MOD power remains available for the Compact 5000

IO modules

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPSR

B

F

R

B

F

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPSR

B

F

R

B

F

Closed PositionOpen Position

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 9

CompactLogix 5480 Controllers

Install the MOD Power RTB

1 Hook the bottom of the MOD power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect MOD PowerThe way that you connect power to the MOD power RTB depends on whether you use UPS control signals or not

bull If you are not using UPS control signals you connect the external power supply directly to the MOD power RTB

In this case proceed to Connect to the MOD Power RTB from a Standard External Power Supply on page 10

bull If you are using UPS control signals you connect a UPS to the MOD power RTB

In this case proceed to Connect to the MOD Power RTB from a UPS on page 15

Connect to the MOD Power RTB from a Standard External Power Supply

Before you connect an external power source to the MOD power RTB make sure that the MOD power source is properly sized

1 Verify that the external power supply is not powered

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the 24V DC (+) connection on the external power supply into the first MOD (+) terminal on the RTB

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the 24V DC (mdash) connection on the external power supply into the first MOD (mdash) terminal on the RTB

5069-L4200ERMW

MOD Power RTB

IMPORTANT Your application can require a power control device for example

a switch between the external 24V DC power source and the

controller to control when the controller is powered If so you

must install the power control device at the VDC+ terminal on

the RTB

If you install the power control device at the VDC- terminal the

controller can fail to power up or power down properly

10 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

The following diagram shows an external 24V DC power supply that is connected to the MOD power RTB when you are not using UPS control signals

Install the SA Power RTBInstall the SA power RTB even if you do not use SA power

1 Hook the bottom of the SA power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect SA DC Power

Before you connect an external DC power source to the SA power RTB make sure that the SA power source is properly sized

For more information o n SA power see SA Power on page 8

1 Confirm that MOD power and SA power sources are turned off

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the DC (+) connection on the external power supply into the first SA (+) terminal on the RTB

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

24V DC

Power

Supply

+

ndashIMPORTANT SA power is only required if your application includes local

Compact 5000 IO modules that require SA power to operate

or are connected to field-side devices that are powered by

SA power

5069-L4200ERMW

SA Power RTB

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 11

CompactLogix 5480 Controllers

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the DC (mdash) connection on the external power supply into the first SA (mdash) terminal on the RTB

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

7 Insert the wire from an Earth Ground location into the first

Ground ( ) on the RTB

The Earth Ground location can be the external SA power supply the DIN rail or other Earth Ground location

8 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

The following diagram shows an external 24V DC power supply that is connected to the SA power RTB when you do not use UPS control signals

TIP

This symbol denotes a Functional Ground terminal that provides a

low impedance path between electric circuits and earth for functional

purposes and provides noise immunity improvement This connection

must be made for functional purposes

5069-L4200ERMW

24V DC

Power

Supply

+

ndash

24V DC

Power

Supply

+

ndash

MOD

Power

SA DC

Power

Functional Ground

12 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Connect SA AC Power

Before you connect an external AC power source to the SA power RTB make sure that the SA power source is properly sized

For more information o n SA power see SA Power on page 8

1 Verify that the SA power source is not powered on

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the L1AC (+) connection on the external power supply into the first SA (+) terminal on the RTB

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the L2NAC(mdash) connection on the external power supply into the first SA(mdash) terminal on the RTB

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

7 Insert the wire from an Earth Ground location into the first

Ground ( ) on the RTB

The Earth Ground location can be the external SA power supply the DIN rail or other Earth Ground location

8 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

This diagram shows an external 240V AC power supply that is connected to the SA power RTB when you do not use UPS control signals

IMPORTANT SA power is only required if your application includes local

Compact 5000 IO modules that require SA power to operate

or are connected to field-side devices that are powered by

SA power

TIP

This symbol denotes a Functional Ground terminal that provides a

low impedance path between electric circuits and earth for functional

purposes and provides noise immunity improvement This connection

must be made for functional purposes

5069-L4200ERMW

24V DC

Power

Supply

+

ndash

240V AC

Power

Supply

+

ndash

MOD

Power

SA AC

Power

Functional Ground

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 13

CompactLogix 5480 Controllers

Connect Control Signals Via UPS Control RTBThe CompactLogix 5480 controller does not have an internal energy storage module that lets the controller save the state of the program if system-side power is lost You must connect an external uninterruptible power supply (UPS) to the UPS control RTB to save the state of the program if power is lost

You connect control signals from an external power supply to the UPS control RTB to let the controller experience a controlled shutdown upon an incoming power loss

When a UPS connection is detected the CompactLogix 5480 controller defaults to initiate shutdown 1 minute after a power loss indication

We recommend that you use 1606 switched mode uninterruptible power supplies from Rockwell Automation with a CompactLogix 5480 controller for example the 1606-XLS240-UPS power supply

For more information on Bulletin 1606 uninterruptible power supplies see the following

bull Bulletin 1606 DC-UPS Uninterruptible Power Supply Installation Instructions publication 1606-IN025

bull Bulletin 1606 Switched Mode Power Supplies Reference Manual publication 1606-RM036

The switched mode uninterruptible power supplies use a 12-volt battery module to bridge power failures and voltage fluctuations We recommend that you use the 1606-XLSBATASSY1 battery module from Rockwell Automation

You can use other accessories such as replacement batteries mounting kits and panelwall mounting brackets with the battery module

For more information on and the battery module and accessories that you can use with them see the following

bull Bulletin 1606 12V 7Ah Battery Modules Installation Instructions publication 1606-IN011

bull Bulletin 1606 Switched Mode Power Supply Battery Modules (12V 7Ah) Reference Manual publication 1606-RM037

UPS Control SignalsThese control signals are used on the UPS Control RTB

UPS Control RTB Terminals

Signal Description

UPS Ready (R)

An input signal from the UPS to the controller that indicates the UPS is working and can buffer during a power failure

The charge level for a UPS to be ready to buffer during a power failure varies For example the 1606-XLS240-UPS power supply must be greater than 85 charged to be ready

The letter R indicates the RTB terminal for this signal

Buffering (B)

An input signal from the UPS to the controller that indicates the UPS battery is providing power because the external power has failed

After a preset time (typically 1 minute after power failure) the controller performs an orderly shutdown by stopping execution and saving the state of the controller

The letter B indicates the RTB terminal for this signal

Battery Fail (F)

An input from the UPS to the controller that indicates the UPS battery has failed and the controller cannot operate from stored energy

In this case the controller does not attempt to save the state of the program when the external power fails The controller issues an alarm if a UPS was previously attached and ready to buffer

The letter F indicates the RTB terminal for this signal

Inhibit (I)

An output signal from the controller to the UPS that disables the UPS signal output The INHIBIT signal is triggered after data is backed up and the system is ready to shut down

The letter I indicates the RTB terminal for this signal

14 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the UPS Control RTBInstall the UPS control RTB even if you do not intend to connect uninterruptible power to the controller

1 Hook the bottom of the UPS power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect UPS Control Signals

1 Verify that all sources of MOD power and SA power are turned off

2 Verify the followingbull A 24V DC power supply is connected to the 24V IN

terminals on the UPSbull A 12V DC battery is connected to the 12V BAT terminals

on the UPS

For more information see the example graphic on page 17

Connect to the MOD Power RTB from a UPS

1 Daisy chain the wires from these connections on the UPSbull 24V OUT (+)bull Ready (1)bull Buffering (3)bull Battery Fail (5)bull Inhibit (7)

2 Connect one wire to each (+) terminal on the MOD power RTB as shown in the example graphic on page 17a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Daisy chain a wire that is connected to the 24V OUT (ndash) terminal on the UPS and a second wire

4 Connect one wire to each (ndash) terminal on the MOD power RTB a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

IMPORTANT The UPS terminal labels in this section represent the labels on

a 1606-XLS240-UPS power supply Your UPS terminals can be

labeled differently

5069-L4200ERMW

UPS Control RTB

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 15

CompactLogix 5480 Controllers

Connect to the UPS Control RTB from a UPS

1 Connect a wire from the Ready (2) connection on the UPS to the UPS Ready terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

2 Connect a wire from the Buffering (4) connection on the UPS to the Buffering terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Connect a wire from the Battery Fail (6) connection on the UPS to the Battery Fail terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

4 Connect a wire from the Inhibit (8) connection on the UPS to the Inhibit terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

16 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

This diagram shows a 1606-XLS240-UPS power supply battery that is connected to a CompactLogix 5480 controller

5069-L4200ERMW

UPS Ready

Buffering

Battery Fail

Inhibit

(7) Inhibit +

(8) Inhibit ndash

24V DC

Power

Supply

Ready

(1) (2)

+ ndash + ndash + ndash + ndash

N L PE

Buffering

(3) (4)

Battery Fail

(5) (6)

12V DC Battery

(for example 1606-XLSBATASSY1)

+ ndash

DC-UPS

(1606-XLS240-UPS)

24V

IN

12V

BAT

24V

OUT

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 17

CompactLogix 5480 Controllers

Disconnect Wires from the RTBsIf necessary complete these tasks to disconnect wires from any RTB on the controller

1 Turn the screwdriver counter-clockwise to open the terminal

2 Remove the wire

Install Compact 5000 IO ModulesComplete one of the following

bull If you do not use local Compact 5000 IO modules in the system proceed to Install the End Cap on page 18

bull If you use local Compact 5000 IO modules in the system install the modules to the right side of the controller

After the IO modules are installed install the end cap on the right side of the last IO module in the system For more information on how to install the end cap see page 18

For more information on how to install Compact 5000IO modules see the installation instructions available with each Compact 5000 IO module catalog number

Install the End CapYou must install an end cap on the right side of the last module in a CompactLogix 5480 system The end cap covers the exposed interconnections on the last module in the system If you do not install the end cap before powering the system equipment damage or injury from electric shock can result

If you do not intend to install Compact 5000 IO modules to the system before you turn on power to the controller install the end cap

1 Align the end cap with the interlocking pieces on the controller

2 Push the end cap toward the DIN rail until it locks into place

Power the System

After the end cap is installed on the last module in the system turn on power to the MOD power RTB and the SA power RTB

IMPORTANT Consider the following before you power the system

bull Make sure to remove the debris shield from the controller before power-up

bull As noted previously you must install working controller firmware to use the COS on the controller There are two ways to install working firmware The ways are described beginning on page 23

One of the methods to install working controller firmware

uses the SD card that ships with the controller

ndash If you intend to use the SD card to install working

controller firmware go to Use a Secure Digital Card

to Install Controller Firmware on page 24

Complete the steps described in that section apply

power to the controller and return to the next

section that is Set the Network Internet Protocol

(IP) Addresses on page 19

ndash If you do not intend to use the SD card to install

working controller firmware turn on the power now

and proceed to the next section

Top Interlocking

Pieces

End Cap

Bottom Interlocking

Pieces

18 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Set the Network Internet Protocol (IP) AddressesYou must set an IP address on Ethernet ports for the controller to operate on an EtherNetIP network via that port

Out-of-the-box the following applies to Ethernet ports A1 A2 and B1

bull The ports are DHCP-enabled and the IP address is set automatically via a DHCP server

If there is no DHCP server available to set the IP address you must set the IP address manually

bull If ports A1 and A2 are configured to use DLRLinear mode you set only one IP address that is used on both ports

bull Control ports must use unique subnets

When ports A1 and A2 are configured to use DLRLinear mode however they use the same subnet because they are configured as one port

You can use one of the following to set the IP address on the controller when it is in the out-of-the-box condition

bull DHCP server

bull BOOTP DHCP EtherNetIP Commissioning tool version 30200 or later

bull RSLinx Classic software version 41000 or later

bull FactoryTalk Linx software version 61000 or later

bull Logix Designer application version 320100 or later

For more information on how to set or change the IP address on a CompactLogix 5480 controller see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

Connect the Controller to an EtherNetIP Network

Use an RJ45 cable to connect the controller to an EtherNetIP network

1 If needed wire the RJ45 connector as shown

2 Connect RJ45 cables to the controller Ethernet ports

IMPORTANT Before you can connect a CompactLogix 5480 controller to an

EtherNetIP network you must first install the network and

its components

This section assumes that the EtherNetIP network is

installed

Connector Number

Color

1585J 8-pin Cables with Support for 101001000 Mbps

1585J 8-pin Cables with Support for 10100 Mbps

1585J 4-pin Cables with Support for 10100 Mbps

1WhiteOrange

BI_DA+ TxData +

2 Orange BI_DA- TxData -

3WhiteGreen

BI_DB+ Recv Data +

4 Blue BI_DC+ Unused mdash

5 WhiteBlue BI_DC- Unused mdash

6 Green BI_DB- Recv Data -

7WhiteBrown

BI_DD+ Unused mdash

8 Brown BI_DD- Unused mdash

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 19

CompactLogix 5480 Controllers

Remove and Replace the Controller

1 Turn off power to the MOD power and the SA power RTBs

2 If there are local Compact 5000 IO modules in the system remove them If not skip to step 3

3 Disconnect wires from the RTBs

For more information see Disconnect Wires from the RTBs on page 18

4 Pull the RTB handles to remove the RTBs

IMPORTANT When you remove MOD power from the controller you shut down

power to all modules in the CompactLogix 5480 system That is

all system-side is removed When you remove SA power from the

controller all field-side power that is provided by the controller is

removed If SA power that is provided via a 5069-FPD field

potential distributor the system does not lose SA power to the

right of the field potential distributor

In this case you must use a separate power source for the SA

power RTB on the field potential distributor

We strongly recommend that before you remove MOD power or

SA power that you take the appropriate actions to help prevent

unintended consequences that can result from a system power

shutdown

Despite the removal of power from SA RTBs on the controller or

field potential distributor the 5069-OB16 and 5069-OB16F

modules continue to receive field-side power The modules

receive power from an external power source that is connected to

the LA (+) and LA (ndash) module terminals

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

UPS Control RTB

MOD Power RTB

SA Power RTB

20 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

5 Remove all cables from the controller

6 Push down on the front of the DIN rail latches

A click indicates that the DIN rail latches are open

If the DIN rail latches fail to remain in the open position hold them down

7 Pull the controller off the DIN rail

8 Repeat the installation steps that are described beginning at Install the Controller onto the DIN Rail on page 9

9 Apply MOD power and if necessary SA power to the system

Replace the FansThe CompactLogix 5480 controller uses fans at the top and bottom of the controller to help maintain lower operating temperatures when the controller is operating

Fan use includes speed control and monitoring Faults indicate fan operating conditions as follows

bull Minor faults - Triggered when a fan is not operating at the requested speed or if a fan fails to operate at all

In your Logix Designer application project you can use the Minor Faults tab on the Controller Properties dialog box to monitor for these faults

bull Major fault - Triggered if both fans fail and the controller goes over the maximum operating temperature

In this case the controller stops operating

You can order replacement fans Replacement fans come in pairs The fans are unique by position and keyed to help make sure that you install the correct fan in each position

The fans are labeled Fan 1 - Top and Fan 2 - Bottom

Consider the following

bull We recommend that you replace the fans in pairs That is if you replace the one fan we recommend that you replace the other fan too

bull You can replace fans during controller operation The fans support removal and insertion under power

bull Do not remove both fans at once if the controller is operating That is remove a fan and install the replacement fan before you remove the other fan

Remove the Top Fan

1 Push up on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

TIP In your Logix Designer application project you can

use the Major Faults tab on the Controller

Properties dialog box to monitor for this fault

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

R

B

F

Open Position

IMPORTANT If you replace fans while the controller is operating

do not touch live voltage components

TIP If the hinges do not disengage when you push up on the front of the

fan then use a screwdriver as a pry tool

5069-L4200ERMW

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 21

CompactLogix 5480 Controllers

2 Pull the fan out of the slot at the top of the controller

Install the Top Replacement Fan

1 Insert the top replacement fan into the slot at the top of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push down on the top replacement fan until it clicks in place

Remove the Bottom Fan

1 Push the down on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

2 Pull the fan out of the slot at the bottom of the controller

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

TIP If the hinges do not disengage when you push down on the front of

the fan then use a screwdriver as a pry tool

5069-L4200ERMW

5069-L4200ERMW

22 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Bottom Replacement Fan

1 Insert the bottom replacement fan into the slot at the bottom of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push up on the bottom replacement fan until it clicks in place

Use the COS For Windows-based ComputingThe COS on a CompactLogix 5480 controller runs in parallel with the Logix control engine You are not required to use the COS

You can use the following methods to install working controller firmware when the controller is in the out-of-box state

bull ControlFLASHtrade or ControlFLASH Plustrade softwarebull Secure Digital (SD) card

Use a Flash Programming Tool to Install Controller FirmwareYou can use ControlFLASH and ControlFLASH Plus software to install controller firmware

The following requirements apply when you use ControlFLASH or ControlFLASH Plus to install working controller firmware

bull You must use one of the followingndash ControlFLASH software version 150100 or laterndash ControlFLASH Plus version 20000 or later

bull You must use a Linx-based software application with your flash programming toolndash With ControlFLASH software you can use RSLinx

Classic Lite RSLinx Classic RSLinx Enterprise or FactoryTalk Linx

ndash With ControlFLASH Plus software you must use FactoryTalk Linx

Minimum software versions apply with Linx-based software For more information on the minimum software version requirements see the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

5069-L4200ERMW

5069-L4200ERMW

IMPORTANT Before you can use the COS you must install working controller firmware The requirement applies even if you

are not using the controller for real-time control If you do not

install working controller firmware the COS does not start

In the out-of-box state the controller uses firmware revision

1xxx On a CompactLogix 5480 controller the minimum

working controller firmware is revision 32012

TIP We recommend that you connect your peripherals to the

ports that are dedicated to COS use before you install

controller firmware

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 23

CompactLogix 5480 Controllers

Download the Flash Programming Tool

ControlFLASH and ControlFLASH Plus software are available from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

Download the installation files and install the software

Download the Controller Firmware

After the flash programming tool is installed download the controller firmware from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

The initial download is a exe file You use the Rockwell Automation Download Manager to extract a dmk from the downloaded file

Install the Controller Firmware

To install the controller firmware via a flash programming tool you complete the following steps

1 To start the tool click StartgtAll ProgramsgtFlashing Programming ToolsgtControlFLASH or ControlFLASH Plus

2 Follow the prompts to complete the following stepsa Choose the controllerb Select the firmware revisionc Install the controller firmware

A dialog box confirms that the installation was successful

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use a flash programming tool to install controller firmware see the following

bull ControlFLASH Firmware Upgrade Kit User Manual publication 1756-UM105

bull ControlFLASH Plus Quick Start Guide publication CFP-QS001

bull CompactLogix 5480 Controllers User Manual publication 5069-UM002

Use a Secure Digital Card to Install Controller FirmwareYou can use an SD card to install controller firmware CompactLogix 5480 controllers ship with an SD card installed behind the front door on the controller

To use an SD card to install controller firmware complete the following steps

1 Before you turn on power to the controller remove the SD card from the controller

2 Install the SD card into another working CompactLogix 5480 controller that has a Logix Designer application project on it

3 Save the project to the SD card

4 Remove the SD card from the working controller and reinstall it in the new controller

5 Turn on power to the new controller

When the new controller powers up it automatically updates the firmware to the revision that is stored on the SD card

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use the SD card with the controller after valid firmware is installed and the controller is powered see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

IMPORTANT These steps only highlight the major tasks that you

complete to install controller firmware with ControlFLASH

To successfully install controller firmware you must complete other tasks that are not described here

For complete information on how to install controller

firmware see the publications listed at the end of the section

IMPORTANT To install controller firmware on a new CompactLogix 5480

controller via an SD card you must have another controller of

the same type that is already working

The SD card method requires that you save the Logix Designer

application project from the working controller to the SD card

before you use it in the new controller

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

SD Card Slot

24 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpecificationsThis table lists a subset of controller specifications For a complete list of specifications see the CompactLogix 5380 Compact GuardLogixreg 5380 and CompactLogix 5480 Controllers Specifications Technical Data publication 5069-TD002

Environmental Specifications - CompactLogix 5480 Controllers

Attribute 5069-L430ERMW 5069-L450ERMW 5069-4100ERMW 5069-L4200ERMW

Temperature operating

IEC 60068-2-1 (Test Ad Operating Cold)

IEC 60068-2-2 (Test Bd Operating Dry Heat)

IEC 60068-2-14 (Test Na Operating Thermal Shock)

0 degC lt Ta lt +60 degC

(+32 degF lt Ta lt +140 degF)

Temperature surrounding air max 60 degC (140 degF)

Enclosure Type Rating None (open-style)

Voltage and current ratings

MOD Power voltage range 18hellip32V DC

MOD Power power max 72 W

MOD Power current typical 4 A

MOD Power inrush 4 A for 15 ms

MOD Power Passthrough(1) 6 A 18hellip32V DC

MOD Power current rating max10 A

Do not exceed 10 A current draw at the MOD power RTB(4)

SA Power voltage ranges(2) 0hellip32V DC

0hellip240V AC 47hellip63 Hz

SA Power current max (2) 10 mA (DC power)

25 mA (AC power)

SA Power Passthrough(2) (3) 999 A 0hellip32V DC

9975 A 0hellip240V AC 47hellip63 Hz

SA Power current rating max(2) Do not exceed 10 A current draw at the SA power RTB

Isolation voltage

300V (continuous) Basic Insulation Type SA and MOD Power to Backplane

300V (continuous) Basic Insulation Type SA to MOD Power

300V (continuous) Basic Insulation Type Ethernet to Backplane

300V (continuous) Double Insulation Type Ethernet to MOD Power

300V (continuous) Double Insulation Type Ethernet to SA Power

50V (continuous) Functional Insulation Type Ethernet to USB ports and DisplayPort

300V (continuous) Basic Insulation Type USB ports and DisplayPort to Backplane

300V (continuous) Double Insulation Type USB ports and DisplayPort to MOD Power

300V (continuous) Double Insulation Type USB ports and DisplayPort to SA Power

No isolation between Ethernet ports

Type tested at 1500V AC for 60 s

Wire size

5069-RTB4-SCREW 5069-RTB6-SCREW connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 35 mm (014 in) max diameter including insulation single wire connection only

5069-RTB4-UPS connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 29 mm (011 in) max diameter including insulation single wire connection only

Ethernet connections

Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2

Insulation-stripping length 5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 12 mm (047 in)

Terminal block torque5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 04 Nbullm (35 lbbullin)

ATTENTION Do not wire more than two conductors on one RTB terminal

(1) Maximum level of MOD power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(2) SA power specifications are based on the number and type of Compact 5000 IO modules that are used in the system If the set of IO modules that is used in the system require AC and DC voltage you must install a 5069-FPD field

potential distributor to separate the module types

(3) Maximum level of SA power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(4) Remember MOD power usage includes the total power that the controller and local Compact 5000 IO modules use If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000 IO

modules can draw a maximum of 10 A in addition to the current that the controller draws

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 25

CompactLogix 5480 Controllers

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation

You can view or download publications at httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage To order paper copies of technical documentation contact your local Allen-Bradley distributor or Rockwell Automationreg sales representative

Resource Description

CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069-TD002

Provides specifications and other technical data for CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 controllers

CompactLogix 5480 Controllers User Manual publication 5069-UM002 Describes how to configure operate and monitor CompactLogix 5480 controllers

Industrial Automation Wiring and Grounding Guidelines publication 1770-41 Provides general guidelines for installing a Rockwell Automationreg industrial system

Product Certifications website rokautocertifications Provides declarations of conformity certificates and other certification details

26 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR ltFEFF004200720075006b00200064006900730073006500200069006e006e007300740069006c006c0069006e00670065006e0065002000740069006c002000e50020006f0070007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740065007200200066006f00720020007500740073006b00720069006600740020006100760020006800f800790020006b00760061006c00690074006500740020007000e500200062006f007200640073006b0072006900760065007200200065006c006c00650072002000700072006f006f006600650072002e0020005000440046002d0064006f006b0075006d0065006e00740065006e00650020006b0061006e002000e50070006e00650073002000690020004100630072006f00620061007400200065006c006c00650072002000410064006f00620065002000520065006100640065007200200035002e003000200065006c006c00650072002000730065006e006500720065002egt PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 5: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

CompactLogix 5480 Controllers

About the ControllerThe following graphic shows a CompactLogix 5480 controller

IMPORTANTAny illustrations charts sample programs and layout examples that are shown in this publication are intended solely for the purposes of example Since

there are many variables and requirements that are associated with any particular installation Rockwell Automation does not assume responsibility or

liability for actual use that is based on the examples that are shown in this publication

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

1

6

7

9

8

2

3

4

14

11

16

10

5

1312

15

18

20

17

19

Front View

Bottom View

22

21

23

CompactLogix 5480 Controller Parts

Number Item Description

1 DIN rail latches Secure adapter to DIN rail

2 Mode switch Lets you choose the controller operating mode

3 SD card slot Location for SD card

4 Reset button Resets the controller to factory default condition

5 Four-character displayScrolls information about the controller such as firmware revision or project status

6 USB programming port Provides temporary connection to download projects

7 Ethernet port B1Lets the controller connect to the following networksbull Enterprise-level networkbull Device-level network

8 Ethernet port A1Lets the controller connect to device-level networks

9 Ethernet port A2

10Network and link status indicators for ports B1 A1 and A2 Show the state of the Ethernet ports and network

communication activity on each port

11Speed and link status indicators for port X1

12 Bottom fanHelps regulate controller temperature

Controller ships with fans installed You can replace fans if necessary

13Controller status indicators

Show the state of the controller in multiple respects

14 Top fanHelps regulate controller temperature

Controller ships with fans installed You can replace fans if necessary

15MOD power and SA power status indicators

Show the state of module (MOD) power and sensor actuator (SA) power respectively

16 UPS Control RTB

Connector for control signals to and from an uninterruptible power supply (UPS) that are used to support a controlled shutdown upon incoming power loss

17MOD power bus connector

MOD power bus connection that passes MOD power to the next local Compact 5000 IO module in the system

18 MOD power RTBConnector for external power supply to provide MOD power to the system

19 SA power bus connectorSA power bus connection that passes SA power to the next local Compact 5000 IO module in the system

20 SA power RTBConnector for external power supply to provide SA power to the systemlsquo

21 Ethernet port X1 Used with the COS on the controller

22 USB 30 portsConnectors for peripherals that are used with the COS on the controller(2)

(2) Devices that are connected to the controller via a USB 30 port must reside in the same control enclosure as

the controller This requirement applies to devices that are powered by the USB 30 ports or not You must

connect the devices to a ground system that is common with the controller Alternatively you can connect

the device to the common ground system via a USB hub that provides galvanic isolation

23DisplayPort connection(1)

(1) Any DisplayPort cables or adapters that are used with this product must be certified by VESA A list of

certified equipment and cables is on the VESA website (wwwvesaorg) Use of non-certified cables and

adapters can cause damage or improper operation

Connector to use a display with the COS on the controller

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 5

CompactLogix 5480 Controllers

Required System ComponentsBefore you install the controller verify that you have the following components

System PlanningFollow these rules when planning your system configuration

bull If the CompactLogix 5480 system includes only a controller you can mount the DIN rail in any orientation

bull If your CompactLogix 5480 system includes local Compact 5000 IO modules you must mount the DIN rail horizontally

bull The controller is the leftmost component in the system

bull Local Compact 5000 IO modules are installed to the right of the controller

bull The controller supports as many as 31 local Compact 5000 IO modules

bull Before power-up make sure that the end cap is installed on the right side of the controller or rightmost local Compact 5000 IO module if IO modules are used

Components Used to Install a CompactLogix 5480 Controller

Component Description

Removable Terminal Blocks (RTB)

An RTB that is used to connect MOD power (system-side power) to the controller - 5069-RTB4-SCREW RTB (Ships with the controller)

An RTB that is used to connect SA power (field-side power) - 5069-RTB6-SCREW RTB (Ships with the controller)

An RTB that is used to connect UPS (uninterruptible power) - 5069-L4UPSRTB (Ships with the controller)

External power supply for MOD power

A power supply that is adequately sized to provide MOD power that is system-side power to the CompactLogix 5480 system

For more information see System Power Considerations on page 8

External power supply for SA power

A power supply that is adequately sized to provide SA power that is field-side power to the CompactLogix 5480 system

IMPORTANT SA power is only required if your application includes local Compact 5000 IO modules that are connected to devices that use SA power

For more information see System Power Considerations on page 8

External uninterruptible power supply for UPS control signals

A power supply that provides UPS control signals so that the controller can save the state of the program when power is lost A UPS is only required if your system uses UPS control signals

For more information see Connect Control Signals Via UPS Control RTB on page 14

Tools

You use the following tools to wire the RTBsbull Screwdriverbull Wire stripperbull Wires

For more information on available wire sizes and wire insulation-stripping length see Specifications on page 25

DIN rail

Compatible zinc-plated chromate steel DIN rail

You can use the following DIN railsbull EN50022 - 35 x 75 mm (138 x 030 in)bull EN50022 - 35 x 15 mm (138 x 060 in)

EtherNetIP network components

If your CompactLogix 5480 controller operates on an EtherNetIP network you must install the network and all required components

Software

When you install the controller you assign IP addresses on the controller You can use the following to assign IP addresses

bull DHCP server

bull BOOTP DHCP EtherNetIP Commissioning tool version 30200 or later

bull RSLinxreg Classic software version 41000 or later

bull FactoryTalkreg Linx version 61000 or later

bull Logix Designer application version 320100 or later

For more information see Set the Network Internet Protocol (IP) Addresses on page 19

ATTENTION Do not discard the end cap Use this end cap

to cover the exposed interconnections on the last module

on the DIN rail Failure to do so could result in equipment

damage or injury from electric shock

Components Used to Install a CompactLogix 5480 Controller

Component Description

6 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpacingMaintain spacing from enclosure walls wireways and adjacent equipment Ambient temperature is higher at the top of an enclosed cabinet

The minimum distance on of a system that includes only a CompactLogix 5480 controller is as follows

bull 2500 mm (098 in) between the sides and the cabinet

bull 2500 mm (098 in) between the front of the controller and the cabinet

bull 5000 mm (196 in) between the top and bottom and the cabinet

We recommend that you install the controller near the bottom of the enclosure where ambient temperature is lower

Enclosure SelectionThis example is provided to help you size an enclosure for your CompactLogix 5480 controller You need heat dissipation data from all components that are planned for your enclosure to calculate the enclosure size

With no active method of heat dissipation for example air conditioning either of the following approximate equations can be used for a metal cabinet

The maximum ambient rating of the CompactLogix 5480 controller is 60 degC (140 degF) If the maximum external cabinet temperature is 20 degC (68 degF) then T=40

In this example with only the controller the heat dissipation is 72 W that is the sum of all components in the enclosure In the following equation T=40 and Q=72

In this example the enclosure must have a minimum exterior surface of 0386 m2

If any portion of the enclosure cannot transfer heat exclude that value from the calculation

The minimum installation clearance for a CompactLogix 5480 controller is 26700 x 18400 x 15200 mm (1050 x 725 x 600 in) HxWxD

The standard cabinet depth in this example is 15420 mm (600 in)

To meet cooling and clearance requirements in this example the cabinet must be approximately 30480 x 35560 x 15420 mm(1200 x 1400 x 600 in) HxWxD

A = 2DW +2DH + 2WH

A = 2 x (01542 x 03556) + 2 x (01542 x 03048) + 2 x (03556 x 03048) = 04204 m2

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

Top

Bottom

SideSide

End cap

Cabinet

Metric Imperial

Where

bull T = Temperature difference between inside air and outside ambient (degC)

bull Q = Heat that is generated in enclosure (Watts)

bull A = Enclosure surface area (m2)

Where

bull T = Temperature difference between inside air and outside ambient (degF)

bull Q = Heat that is generated in enclosure (Watts)

bull A = Enclosure surface area (ft2)

The exterior surface of all six sides of an enclosure is calculated as

A = 2dw + 2dh + 2wh

Where d (depth) w (width) and h (height) are in meters

The exterior surface of all six sides of an enclosure is calculated as

A = (2dw + 2dh + 2wh) 144

Where d (depth) w (width) and h (height) are in inches

038Q

180T - 110

A =

408Q

T - 110

A =

038(7200)

180(4000) - 110A =

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 7

CompactLogix 5480 Controllers

This example uses the following conditions

bull All sides of the enclosure transfer heatbull Only the CompactLogix 5480 controller is installedbull Ambient temperature = 20 degC (68 degF)

DimensionsThe controller dimensions are as follows

Ground ConsiderationsYou must ground DIN rails according to the Industrial Automation Wiring and Grounding Guidelines publication 1770-41

You can use the following DIN rails

bull EN50022 - 35 x 75 mm (138 x 030 in)bull EN50022 - 35 x 15 mm (138 x 060 in)

System Power ConsiderationsThe CompactLogix 5480 controller provides power to a CompactLogix 5480 system via RTBs that are connected to external power supplies and installed on the controller

The RTBs provide the following power to the system

IMPORTANT If any of the following conditions exist the enclosure must be larger

bull Any sides of the enclosure cannot transfer heat

bull More equipment is included in the system

bull Ambient temperature is higher than 20 degC (68 degF)

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

13021 mm

(513 in)

16620 mm

(654 in)

12654 mm

(498 in)

12002 mm

(473 in)

13366 mm

(526 in)

16000 mm

(630 in)

ATTENTION This product is grounded through the DIN rail to

chassis ground Use zinc-plated chromate-passivated steel DIN rail

to assure proper grounding The use of other DIN rail materials (for

example aluminum or plastic) that can corrode oxidize or are poor

conductors can result in improper or intermittent grounding

Secure DIN rail to mounting surface approximately every 200 mm

(78 in) and use end-anchors appropriately Be sure to ground the

DIN rail properly See Industrial Automation Wiring and Grounding

Guidelines Rockwell Automationreg publication 1770-41 for more

information

Power Type Description

MOD Power

System-side power that is used to operate the CompactLogix 5480 system MOD power is provided through the MOD power RTB and passed across the MOD power bus bull The total continuous current draw across the MOD power bus must not be

more than 10 A max at 1832V DC

You must calculate the total MOD power that the controller and all local Compact 5000 IO modules draw to make sure that no more than 10 A of MOD power is drawn(1)

bull Confirm that the external MOD power supply is adequately sized for the total MOD power bus current draw in the system including the MOD power inrush current requirements

(1) If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000

IO modules can draw a maximum of 10 A in addition to the current the controller draws

SA Power

Field-side power that can be used to power field-side devices that are connected to some Compact 5000 IO modules SA power is provided through the SA power RTB and passed across the SA power bus

bull SA power is only required if your application includes local Compact 5000 IO modules that are connected to devices that use SA power

bull If you are using DC voltage for SA power the total continuous current draw across the MOD power bus must not be more than 10 A max at 18hellip32V DC

bull If you are using AC voltage for SA power the total continuous current draw across the MOD power bus must not be more than 10 A max at 18hellip240V AC

bull You can use a 5069-FPD field potential distributor to establish additional SA power buses in a CompactLogix 5480 system

If your system includes AC and DC modules that require SA power you must use a 5069-FPD field potential distributor to establish a new SA power bus

You separate the module types by SA power bus For example install DC module on the first SA power bus in the system and install the AC modules on the second SA power bus in the system

bull Confirm that the external SA power supply is sized adequately for the total SA power current draw in the system

UPS Control

Control signals from an external UPS that let the controller save the state of the program if power is lost The external UPS provides the power that is required to save the program via the MOD power RTB A UPS is not required for controller operation

8 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Controller onto the DIN Rail

1 Confirm that the DIN rail latches are closed

2 If the DIN rail latches are open gently push the rear latch back until the front latch pops up and clicks

3 Position the controller so that the back of it faces the DIN rail

4 Press the controller against the DIN rail until you hear a click

5 Confirm that all latches have fully closed and the controller is latched securely

Connect External Power Supplies to the ControllerBefore you connect MOD power or SA power to the RTBs on the CompactLogix 5480 controller complete the following tasks

bull Read System Power Considerations on page 8

bull Confirm that the external power supplies that MOD power and SA power are adequately sized for your CompactLogix 5480 system For more information see page 8

bull Verify that the external power supplies are turned off

bull Install the MOD power RTB SA power RTB and the UPS Control RTB if used

bull If IO modules are used verify that they are installed on the correct SA power bus

DC-type modules must reside on an SA power bus that uses DC power and AC-type modules must reside on an SA power bus that uses AC power

For more information see the technical documentation for Compact 5000 IO modules

IMPORTANT Remember the following

bull CompactLogix 5480 controllers do not have an embedded power supply that powers the system

The system is powered by external power supplies via

connections to the various power RTBs on the controller

bull We recommend that you use 1606 power supplies from Rockwell Automation to provide MOD power SA power and UPS control

bull You must use an external power supply that is dedicated to the UPS connection

For more information about which 1606 power supplies

are best for each power type see the Switched Mode

Power Supply Specifications Technical Data publication

1606-TD002

bull You can connect power from one external power supply to the MOD power and SA power RTBs However as stated previously we strongly recommend that you use separate external power supplies for MOD power and SA power respectively

The practice of using separate external power supplies can

help prevent unintended consequences that can result if

you use one supply

If you use separate external power supplies the loss of

power from one external power supply does not affect the

availability of power from the other supply For example if

separate external power supplies are used and SA power is

lost MOD power remains available for the Compact 5000

IO modules

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPSR

B

F

R

B

F

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPSR

B

F

R

B

F

Closed PositionOpen Position

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 9

CompactLogix 5480 Controllers

Install the MOD Power RTB

1 Hook the bottom of the MOD power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect MOD PowerThe way that you connect power to the MOD power RTB depends on whether you use UPS control signals or not

bull If you are not using UPS control signals you connect the external power supply directly to the MOD power RTB

In this case proceed to Connect to the MOD Power RTB from a Standard External Power Supply on page 10

bull If you are using UPS control signals you connect a UPS to the MOD power RTB

In this case proceed to Connect to the MOD Power RTB from a UPS on page 15

Connect to the MOD Power RTB from a Standard External Power Supply

Before you connect an external power source to the MOD power RTB make sure that the MOD power source is properly sized

1 Verify that the external power supply is not powered

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the 24V DC (+) connection on the external power supply into the first MOD (+) terminal on the RTB

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the 24V DC (mdash) connection on the external power supply into the first MOD (mdash) terminal on the RTB

5069-L4200ERMW

MOD Power RTB

IMPORTANT Your application can require a power control device for example

a switch between the external 24V DC power source and the

controller to control when the controller is powered If so you

must install the power control device at the VDC+ terminal on

the RTB

If you install the power control device at the VDC- terminal the

controller can fail to power up or power down properly

10 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

The following diagram shows an external 24V DC power supply that is connected to the MOD power RTB when you are not using UPS control signals

Install the SA Power RTBInstall the SA power RTB even if you do not use SA power

1 Hook the bottom of the SA power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect SA DC Power

Before you connect an external DC power source to the SA power RTB make sure that the SA power source is properly sized

For more information o n SA power see SA Power on page 8

1 Confirm that MOD power and SA power sources are turned off

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the DC (+) connection on the external power supply into the first SA (+) terminal on the RTB

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

24V DC

Power

Supply

+

ndashIMPORTANT SA power is only required if your application includes local

Compact 5000 IO modules that require SA power to operate

or are connected to field-side devices that are powered by

SA power

5069-L4200ERMW

SA Power RTB

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 11

CompactLogix 5480 Controllers

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the DC (mdash) connection on the external power supply into the first SA (mdash) terminal on the RTB

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

7 Insert the wire from an Earth Ground location into the first

Ground ( ) on the RTB

The Earth Ground location can be the external SA power supply the DIN rail or other Earth Ground location

8 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

The following diagram shows an external 24V DC power supply that is connected to the SA power RTB when you do not use UPS control signals

TIP

This symbol denotes a Functional Ground terminal that provides a

low impedance path between electric circuits and earth for functional

purposes and provides noise immunity improvement This connection

must be made for functional purposes

5069-L4200ERMW

24V DC

Power

Supply

+

ndash

24V DC

Power

Supply

+

ndash

MOD

Power

SA DC

Power

Functional Ground

12 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Connect SA AC Power

Before you connect an external AC power source to the SA power RTB make sure that the SA power source is properly sized

For more information o n SA power see SA Power on page 8

1 Verify that the SA power source is not powered on

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the L1AC (+) connection on the external power supply into the first SA (+) terminal on the RTB

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the L2NAC(mdash) connection on the external power supply into the first SA(mdash) terminal on the RTB

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

7 Insert the wire from an Earth Ground location into the first

Ground ( ) on the RTB

The Earth Ground location can be the external SA power supply the DIN rail or other Earth Ground location

8 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

This diagram shows an external 240V AC power supply that is connected to the SA power RTB when you do not use UPS control signals

IMPORTANT SA power is only required if your application includes local

Compact 5000 IO modules that require SA power to operate

or are connected to field-side devices that are powered by

SA power

TIP

This symbol denotes a Functional Ground terminal that provides a

low impedance path between electric circuits and earth for functional

purposes and provides noise immunity improvement This connection

must be made for functional purposes

5069-L4200ERMW

24V DC

Power

Supply

+

ndash

240V AC

Power

Supply

+

ndash

MOD

Power

SA AC

Power

Functional Ground

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 13

CompactLogix 5480 Controllers

Connect Control Signals Via UPS Control RTBThe CompactLogix 5480 controller does not have an internal energy storage module that lets the controller save the state of the program if system-side power is lost You must connect an external uninterruptible power supply (UPS) to the UPS control RTB to save the state of the program if power is lost

You connect control signals from an external power supply to the UPS control RTB to let the controller experience a controlled shutdown upon an incoming power loss

When a UPS connection is detected the CompactLogix 5480 controller defaults to initiate shutdown 1 minute after a power loss indication

We recommend that you use 1606 switched mode uninterruptible power supplies from Rockwell Automation with a CompactLogix 5480 controller for example the 1606-XLS240-UPS power supply

For more information on Bulletin 1606 uninterruptible power supplies see the following

bull Bulletin 1606 DC-UPS Uninterruptible Power Supply Installation Instructions publication 1606-IN025

bull Bulletin 1606 Switched Mode Power Supplies Reference Manual publication 1606-RM036

The switched mode uninterruptible power supplies use a 12-volt battery module to bridge power failures and voltage fluctuations We recommend that you use the 1606-XLSBATASSY1 battery module from Rockwell Automation

You can use other accessories such as replacement batteries mounting kits and panelwall mounting brackets with the battery module

For more information on and the battery module and accessories that you can use with them see the following

bull Bulletin 1606 12V 7Ah Battery Modules Installation Instructions publication 1606-IN011

bull Bulletin 1606 Switched Mode Power Supply Battery Modules (12V 7Ah) Reference Manual publication 1606-RM037

UPS Control SignalsThese control signals are used on the UPS Control RTB

UPS Control RTB Terminals

Signal Description

UPS Ready (R)

An input signal from the UPS to the controller that indicates the UPS is working and can buffer during a power failure

The charge level for a UPS to be ready to buffer during a power failure varies For example the 1606-XLS240-UPS power supply must be greater than 85 charged to be ready

The letter R indicates the RTB terminal for this signal

Buffering (B)

An input signal from the UPS to the controller that indicates the UPS battery is providing power because the external power has failed

After a preset time (typically 1 minute after power failure) the controller performs an orderly shutdown by stopping execution and saving the state of the controller

The letter B indicates the RTB terminal for this signal

Battery Fail (F)

An input from the UPS to the controller that indicates the UPS battery has failed and the controller cannot operate from stored energy

In this case the controller does not attempt to save the state of the program when the external power fails The controller issues an alarm if a UPS was previously attached and ready to buffer

The letter F indicates the RTB terminal for this signal

Inhibit (I)

An output signal from the controller to the UPS that disables the UPS signal output The INHIBIT signal is triggered after data is backed up and the system is ready to shut down

The letter I indicates the RTB terminal for this signal

14 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the UPS Control RTBInstall the UPS control RTB even if you do not intend to connect uninterruptible power to the controller

1 Hook the bottom of the UPS power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect UPS Control Signals

1 Verify that all sources of MOD power and SA power are turned off

2 Verify the followingbull A 24V DC power supply is connected to the 24V IN

terminals on the UPSbull A 12V DC battery is connected to the 12V BAT terminals

on the UPS

For more information see the example graphic on page 17

Connect to the MOD Power RTB from a UPS

1 Daisy chain the wires from these connections on the UPSbull 24V OUT (+)bull Ready (1)bull Buffering (3)bull Battery Fail (5)bull Inhibit (7)

2 Connect one wire to each (+) terminal on the MOD power RTB as shown in the example graphic on page 17a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Daisy chain a wire that is connected to the 24V OUT (ndash) terminal on the UPS and a second wire

4 Connect one wire to each (ndash) terminal on the MOD power RTB a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

IMPORTANT The UPS terminal labels in this section represent the labels on

a 1606-XLS240-UPS power supply Your UPS terminals can be

labeled differently

5069-L4200ERMW

UPS Control RTB

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 15

CompactLogix 5480 Controllers

Connect to the UPS Control RTB from a UPS

1 Connect a wire from the Ready (2) connection on the UPS to the UPS Ready terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

2 Connect a wire from the Buffering (4) connection on the UPS to the Buffering terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Connect a wire from the Battery Fail (6) connection on the UPS to the Battery Fail terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

4 Connect a wire from the Inhibit (8) connection on the UPS to the Inhibit terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

16 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

This diagram shows a 1606-XLS240-UPS power supply battery that is connected to a CompactLogix 5480 controller

5069-L4200ERMW

UPS Ready

Buffering

Battery Fail

Inhibit

(7) Inhibit +

(8) Inhibit ndash

24V DC

Power

Supply

Ready

(1) (2)

+ ndash + ndash + ndash + ndash

N L PE

Buffering

(3) (4)

Battery Fail

(5) (6)

12V DC Battery

(for example 1606-XLSBATASSY1)

+ ndash

DC-UPS

(1606-XLS240-UPS)

24V

IN

12V

BAT

24V

OUT

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 17

CompactLogix 5480 Controllers

Disconnect Wires from the RTBsIf necessary complete these tasks to disconnect wires from any RTB on the controller

1 Turn the screwdriver counter-clockwise to open the terminal

2 Remove the wire

Install Compact 5000 IO ModulesComplete one of the following

bull If you do not use local Compact 5000 IO modules in the system proceed to Install the End Cap on page 18

bull If you use local Compact 5000 IO modules in the system install the modules to the right side of the controller

After the IO modules are installed install the end cap on the right side of the last IO module in the system For more information on how to install the end cap see page 18

For more information on how to install Compact 5000IO modules see the installation instructions available with each Compact 5000 IO module catalog number

Install the End CapYou must install an end cap on the right side of the last module in a CompactLogix 5480 system The end cap covers the exposed interconnections on the last module in the system If you do not install the end cap before powering the system equipment damage or injury from electric shock can result

If you do not intend to install Compact 5000 IO modules to the system before you turn on power to the controller install the end cap

1 Align the end cap with the interlocking pieces on the controller

2 Push the end cap toward the DIN rail until it locks into place

Power the System

After the end cap is installed on the last module in the system turn on power to the MOD power RTB and the SA power RTB

IMPORTANT Consider the following before you power the system

bull Make sure to remove the debris shield from the controller before power-up

bull As noted previously you must install working controller firmware to use the COS on the controller There are two ways to install working firmware The ways are described beginning on page 23

One of the methods to install working controller firmware

uses the SD card that ships with the controller

ndash If you intend to use the SD card to install working

controller firmware go to Use a Secure Digital Card

to Install Controller Firmware on page 24

Complete the steps described in that section apply

power to the controller and return to the next

section that is Set the Network Internet Protocol

(IP) Addresses on page 19

ndash If you do not intend to use the SD card to install

working controller firmware turn on the power now

and proceed to the next section

Top Interlocking

Pieces

End Cap

Bottom Interlocking

Pieces

18 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Set the Network Internet Protocol (IP) AddressesYou must set an IP address on Ethernet ports for the controller to operate on an EtherNetIP network via that port

Out-of-the-box the following applies to Ethernet ports A1 A2 and B1

bull The ports are DHCP-enabled and the IP address is set automatically via a DHCP server

If there is no DHCP server available to set the IP address you must set the IP address manually

bull If ports A1 and A2 are configured to use DLRLinear mode you set only one IP address that is used on both ports

bull Control ports must use unique subnets

When ports A1 and A2 are configured to use DLRLinear mode however they use the same subnet because they are configured as one port

You can use one of the following to set the IP address on the controller when it is in the out-of-the-box condition

bull DHCP server

bull BOOTP DHCP EtherNetIP Commissioning tool version 30200 or later

bull RSLinx Classic software version 41000 or later

bull FactoryTalk Linx software version 61000 or later

bull Logix Designer application version 320100 or later

For more information on how to set or change the IP address on a CompactLogix 5480 controller see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

Connect the Controller to an EtherNetIP Network

Use an RJ45 cable to connect the controller to an EtherNetIP network

1 If needed wire the RJ45 connector as shown

2 Connect RJ45 cables to the controller Ethernet ports

IMPORTANT Before you can connect a CompactLogix 5480 controller to an

EtherNetIP network you must first install the network and

its components

This section assumes that the EtherNetIP network is

installed

Connector Number

Color

1585J 8-pin Cables with Support for 101001000 Mbps

1585J 8-pin Cables with Support for 10100 Mbps

1585J 4-pin Cables with Support for 10100 Mbps

1WhiteOrange

BI_DA+ TxData +

2 Orange BI_DA- TxData -

3WhiteGreen

BI_DB+ Recv Data +

4 Blue BI_DC+ Unused mdash

5 WhiteBlue BI_DC- Unused mdash

6 Green BI_DB- Recv Data -

7WhiteBrown

BI_DD+ Unused mdash

8 Brown BI_DD- Unused mdash

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 19

CompactLogix 5480 Controllers

Remove and Replace the Controller

1 Turn off power to the MOD power and the SA power RTBs

2 If there are local Compact 5000 IO modules in the system remove them If not skip to step 3

3 Disconnect wires from the RTBs

For more information see Disconnect Wires from the RTBs on page 18

4 Pull the RTB handles to remove the RTBs

IMPORTANT When you remove MOD power from the controller you shut down

power to all modules in the CompactLogix 5480 system That is

all system-side is removed When you remove SA power from the

controller all field-side power that is provided by the controller is

removed If SA power that is provided via a 5069-FPD field

potential distributor the system does not lose SA power to the

right of the field potential distributor

In this case you must use a separate power source for the SA

power RTB on the field potential distributor

We strongly recommend that before you remove MOD power or

SA power that you take the appropriate actions to help prevent

unintended consequences that can result from a system power

shutdown

Despite the removal of power from SA RTBs on the controller or

field potential distributor the 5069-OB16 and 5069-OB16F

modules continue to receive field-side power The modules

receive power from an external power source that is connected to

the LA (+) and LA (ndash) module terminals

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

UPS Control RTB

MOD Power RTB

SA Power RTB

20 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

5 Remove all cables from the controller

6 Push down on the front of the DIN rail latches

A click indicates that the DIN rail latches are open

If the DIN rail latches fail to remain in the open position hold them down

7 Pull the controller off the DIN rail

8 Repeat the installation steps that are described beginning at Install the Controller onto the DIN Rail on page 9

9 Apply MOD power and if necessary SA power to the system

Replace the FansThe CompactLogix 5480 controller uses fans at the top and bottom of the controller to help maintain lower operating temperatures when the controller is operating

Fan use includes speed control and monitoring Faults indicate fan operating conditions as follows

bull Minor faults - Triggered when a fan is not operating at the requested speed or if a fan fails to operate at all

In your Logix Designer application project you can use the Minor Faults tab on the Controller Properties dialog box to monitor for these faults

bull Major fault - Triggered if both fans fail and the controller goes over the maximum operating temperature

In this case the controller stops operating

You can order replacement fans Replacement fans come in pairs The fans are unique by position and keyed to help make sure that you install the correct fan in each position

The fans are labeled Fan 1 - Top and Fan 2 - Bottom

Consider the following

bull We recommend that you replace the fans in pairs That is if you replace the one fan we recommend that you replace the other fan too

bull You can replace fans during controller operation The fans support removal and insertion under power

bull Do not remove both fans at once if the controller is operating That is remove a fan and install the replacement fan before you remove the other fan

Remove the Top Fan

1 Push up on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

TIP In your Logix Designer application project you can

use the Major Faults tab on the Controller

Properties dialog box to monitor for this fault

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

R

B

F

Open Position

IMPORTANT If you replace fans while the controller is operating

do not touch live voltage components

TIP If the hinges do not disengage when you push up on the front of the

fan then use a screwdriver as a pry tool

5069-L4200ERMW

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 21

CompactLogix 5480 Controllers

2 Pull the fan out of the slot at the top of the controller

Install the Top Replacement Fan

1 Insert the top replacement fan into the slot at the top of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push down on the top replacement fan until it clicks in place

Remove the Bottom Fan

1 Push the down on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

2 Pull the fan out of the slot at the bottom of the controller

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

TIP If the hinges do not disengage when you push down on the front of

the fan then use a screwdriver as a pry tool

5069-L4200ERMW

5069-L4200ERMW

22 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Bottom Replacement Fan

1 Insert the bottom replacement fan into the slot at the bottom of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push up on the bottom replacement fan until it clicks in place

Use the COS For Windows-based ComputingThe COS on a CompactLogix 5480 controller runs in parallel with the Logix control engine You are not required to use the COS

You can use the following methods to install working controller firmware when the controller is in the out-of-box state

bull ControlFLASHtrade or ControlFLASH Plustrade softwarebull Secure Digital (SD) card

Use a Flash Programming Tool to Install Controller FirmwareYou can use ControlFLASH and ControlFLASH Plus software to install controller firmware

The following requirements apply when you use ControlFLASH or ControlFLASH Plus to install working controller firmware

bull You must use one of the followingndash ControlFLASH software version 150100 or laterndash ControlFLASH Plus version 20000 or later

bull You must use a Linx-based software application with your flash programming toolndash With ControlFLASH software you can use RSLinx

Classic Lite RSLinx Classic RSLinx Enterprise or FactoryTalk Linx

ndash With ControlFLASH Plus software you must use FactoryTalk Linx

Minimum software versions apply with Linx-based software For more information on the minimum software version requirements see the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

5069-L4200ERMW

5069-L4200ERMW

IMPORTANT Before you can use the COS you must install working controller firmware The requirement applies even if you

are not using the controller for real-time control If you do not

install working controller firmware the COS does not start

In the out-of-box state the controller uses firmware revision

1xxx On a CompactLogix 5480 controller the minimum

working controller firmware is revision 32012

TIP We recommend that you connect your peripherals to the

ports that are dedicated to COS use before you install

controller firmware

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 23

CompactLogix 5480 Controllers

Download the Flash Programming Tool

ControlFLASH and ControlFLASH Plus software are available from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

Download the installation files and install the software

Download the Controller Firmware

After the flash programming tool is installed download the controller firmware from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

The initial download is a exe file You use the Rockwell Automation Download Manager to extract a dmk from the downloaded file

Install the Controller Firmware

To install the controller firmware via a flash programming tool you complete the following steps

1 To start the tool click StartgtAll ProgramsgtFlashing Programming ToolsgtControlFLASH or ControlFLASH Plus

2 Follow the prompts to complete the following stepsa Choose the controllerb Select the firmware revisionc Install the controller firmware

A dialog box confirms that the installation was successful

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use a flash programming tool to install controller firmware see the following

bull ControlFLASH Firmware Upgrade Kit User Manual publication 1756-UM105

bull ControlFLASH Plus Quick Start Guide publication CFP-QS001

bull CompactLogix 5480 Controllers User Manual publication 5069-UM002

Use a Secure Digital Card to Install Controller FirmwareYou can use an SD card to install controller firmware CompactLogix 5480 controllers ship with an SD card installed behind the front door on the controller

To use an SD card to install controller firmware complete the following steps

1 Before you turn on power to the controller remove the SD card from the controller

2 Install the SD card into another working CompactLogix 5480 controller that has a Logix Designer application project on it

3 Save the project to the SD card

4 Remove the SD card from the working controller and reinstall it in the new controller

5 Turn on power to the new controller

When the new controller powers up it automatically updates the firmware to the revision that is stored on the SD card

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use the SD card with the controller after valid firmware is installed and the controller is powered see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

IMPORTANT These steps only highlight the major tasks that you

complete to install controller firmware with ControlFLASH

To successfully install controller firmware you must complete other tasks that are not described here

For complete information on how to install controller

firmware see the publications listed at the end of the section

IMPORTANT To install controller firmware on a new CompactLogix 5480

controller via an SD card you must have another controller of

the same type that is already working

The SD card method requires that you save the Logix Designer

application project from the working controller to the SD card

before you use it in the new controller

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

SD Card Slot

24 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpecificationsThis table lists a subset of controller specifications For a complete list of specifications see the CompactLogix 5380 Compact GuardLogixreg 5380 and CompactLogix 5480 Controllers Specifications Technical Data publication 5069-TD002

Environmental Specifications - CompactLogix 5480 Controllers

Attribute 5069-L430ERMW 5069-L450ERMW 5069-4100ERMW 5069-L4200ERMW

Temperature operating

IEC 60068-2-1 (Test Ad Operating Cold)

IEC 60068-2-2 (Test Bd Operating Dry Heat)

IEC 60068-2-14 (Test Na Operating Thermal Shock)

0 degC lt Ta lt +60 degC

(+32 degF lt Ta lt +140 degF)

Temperature surrounding air max 60 degC (140 degF)

Enclosure Type Rating None (open-style)

Voltage and current ratings

MOD Power voltage range 18hellip32V DC

MOD Power power max 72 W

MOD Power current typical 4 A

MOD Power inrush 4 A for 15 ms

MOD Power Passthrough(1) 6 A 18hellip32V DC

MOD Power current rating max10 A

Do not exceed 10 A current draw at the MOD power RTB(4)

SA Power voltage ranges(2) 0hellip32V DC

0hellip240V AC 47hellip63 Hz

SA Power current max (2) 10 mA (DC power)

25 mA (AC power)

SA Power Passthrough(2) (3) 999 A 0hellip32V DC

9975 A 0hellip240V AC 47hellip63 Hz

SA Power current rating max(2) Do not exceed 10 A current draw at the SA power RTB

Isolation voltage

300V (continuous) Basic Insulation Type SA and MOD Power to Backplane

300V (continuous) Basic Insulation Type SA to MOD Power

300V (continuous) Basic Insulation Type Ethernet to Backplane

300V (continuous) Double Insulation Type Ethernet to MOD Power

300V (continuous) Double Insulation Type Ethernet to SA Power

50V (continuous) Functional Insulation Type Ethernet to USB ports and DisplayPort

300V (continuous) Basic Insulation Type USB ports and DisplayPort to Backplane

300V (continuous) Double Insulation Type USB ports and DisplayPort to MOD Power

300V (continuous) Double Insulation Type USB ports and DisplayPort to SA Power

No isolation between Ethernet ports

Type tested at 1500V AC for 60 s

Wire size

5069-RTB4-SCREW 5069-RTB6-SCREW connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 35 mm (014 in) max diameter including insulation single wire connection only

5069-RTB4-UPS connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 29 mm (011 in) max diameter including insulation single wire connection only

Ethernet connections

Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2

Insulation-stripping length 5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 12 mm (047 in)

Terminal block torque5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 04 Nbullm (35 lbbullin)

ATTENTION Do not wire more than two conductors on one RTB terminal

(1) Maximum level of MOD power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(2) SA power specifications are based on the number and type of Compact 5000 IO modules that are used in the system If the set of IO modules that is used in the system require AC and DC voltage you must install a 5069-FPD field

potential distributor to separate the module types

(3) Maximum level of SA power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(4) Remember MOD power usage includes the total power that the controller and local Compact 5000 IO modules use If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000 IO

modules can draw a maximum of 10 A in addition to the current that the controller draws

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 25

CompactLogix 5480 Controllers

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation

You can view or download publications at httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage To order paper copies of technical documentation contact your local Allen-Bradley distributor or Rockwell Automationreg sales representative

Resource Description

CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069-TD002

Provides specifications and other technical data for CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 controllers

CompactLogix 5480 Controllers User Manual publication 5069-UM002 Describes how to configure operate and monitor CompactLogix 5480 controllers

Industrial Automation Wiring and Grounding Guidelines publication 1770-41 Provides general guidelines for installing a Rockwell Automationreg industrial system

Product Certifications website rokautocertifications Provides declarations of conformity certificates and other certification details

26 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA ltFEFF005500740069006c0069007a007a006100720065002000710075006500730074006500200069006d0070006f007300740061007a0069006f006e00690020007000650072002000630072006500610072006500200064006f00630075006d0065006e00740069002000410064006f006200650020005000440046002000700065007200200075006e00610020007300740061006d007000610020006400690020007100750061006c0069007400e00020007300750020007300740061006d00700061006e0074006900200065002000700072006f006f0066006500720020006400650073006b0074006f0070002e0020004900200064006f00630075006d0065006e007400690020005000440046002000630072006500610074006900200070006f00730073006f006e006f0020006500730073006500720065002000610070006500720074006900200063006f006e0020004100630072006f00620061007400200065002000410064006f00620065002000520065006100640065007200200035002e003000200065002000760065007200730069006f006e006900200073007500630063006500730073006900760065002egt JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 6: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

CompactLogix 5480 Controllers

Required System ComponentsBefore you install the controller verify that you have the following components

System PlanningFollow these rules when planning your system configuration

bull If the CompactLogix 5480 system includes only a controller you can mount the DIN rail in any orientation

bull If your CompactLogix 5480 system includes local Compact 5000 IO modules you must mount the DIN rail horizontally

bull The controller is the leftmost component in the system

bull Local Compact 5000 IO modules are installed to the right of the controller

bull The controller supports as many as 31 local Compact 5000 IO modules

bull Before power-up make sure that the end cap is installed on the right side of the controller or rightmost local Compact 5000 IO module if IO modules are used

Components Used to Install a CompactLogix 5480 Controller

Component Description

Removable Terminal Blocks (RTB)

An RTB that is used to connect MOD power (system-side power) to the controller - 5069-RTB4-SCREW RTB (Ships with the controller)

An RTB that is used to connect SA power (field-side power) - 5069-RTB6-SCREW RTB (Ships with the controller)

An RTB that is used to connect UPS (uninterruptible power) - 5069-L4UPSRTB (Ships with the controller)

External power supply for MOD power

A power supply that is adequately sized to provide MOD power that is system-side power to the CompactLogix 5480 system

For more information see System Power Considerations on page 8

External power supply for SA power

A power supply that is adequately sized to provide SA power that is field-side power to the CompactLogix 5480 system

IMPORTANT SA power is only required if your application includes local Compact 5000 IO modules that are connected to devices that use SA power

For more information see System Power Considerations on page 8

External uninterruptible power supply for UPS control signals

A power supply that provides UPS control signals so that the controller can save the state of the program when power is lost A UPS is only required if your system uses UPS control signals

For more information see Connect Control Signals Via UPS Control RTB on page 14

Tools

You use the following tools to wire the RTBsbull Screwdriverbull Wire stripperbull Wires

For more information on available wire sizes and wire insulation-stripping length see Specifications on page 25

DIN rail

Compatible zinc-plated chromate steel DIN rail

You can use the following DIN railsbull EN50022 - 35 x 75 mm (138 x 030 in)bull EN50022 - 35 x 15 mm (138 x 060 in)

EtherNetIP network components

If your CompactLogix 5480 controller operates on an EtherNetIP network you must install the network and all required components

Software

When you install the controller you assign IP addresses on the controller You can use the following to assign IP addresses

bull DHCP server

bull BOOTP DHCP EtherNetIP Commissioning tool version 30200 or later

bull RSLinxreg Classic software version 41000 or later

bull FactoryTalkreg Linx version 61000 or later

bull Logix Designer application version 320100 or later

For more information see Set the Network Internet Protocol (IP) Addresses on page 19

ATTENTION Do not discard the end cap Use this end cap

to cover the exposed interconnections on the last module

on the DIN rail Failure to do so could result in equipment

damage or injury from electric shock

Components Used to Install a CompactLogix 5480 Controller

Component Description

6 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpacingMaintain spacing from enclosure walls wireways and adjacent equipment Ambient temperature is higher at the top of an enclosed cabinet

The minimum distance on of a system that includes only a CompactLogix 5480 controller is as follows

bull 2500 mm (098 in) between the sides and the cabinet

bull 2500 mm (098 in) between the front of the controller and the cabinet

bull 5000 mm (196 in) between the top and bottom and the cabinet

We recommend that you install the controller near the bottom of the enclosure where ambient temperature is lower

Enclosure SelectionThis example is provided to help you size an enclosure for your CompactLogix 5480 controller You need heat dissipation data from all components that are planned for your enclosure to calculate the enclosure size

With no active method of heat dissipation for example air conditioning either of the following approximate equations can be used for a metal cabinet

The maximum ambient rating of the CompactLogix 5480 controller is 60 degC (140 degF) If the maximum external cabinet temperature is 20 degC (68 degF) then T=40

In this example with only the controller the heat dissipation is 72 W that is the sum of all components in the enclosure In the following equation T=40 and Q=72

In this example the enclosure must have a minimum exterior surface of 0386 m2

If any portion of the enclosure cannot transfer heat exclude that value from the calculation

The minimum installation clearance for a CompactLogix 5480 controller is 26700 x 18400 x 15200 mm (1050 x 725 x 600 in) HxWxD

The standard cabinet depth in this example is 15420 mm (600 in)

To meet cooling and clearance requirements in this example the cabinet must be approximately 30480 x 35560 x 15420 mm(1200 x 1400 x 600 in) HxWxD

A = 2DW +2DH + 2WH

A = 2 x (01542 x 03556) + 2 x (01542 x 03048) + 2 x (03556 x 03048) = 04204 m2

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

Top

Bottom

SideSide

End cap

Cabinet

Metric Imperial

Where

bull T = Temperature difference between inside air and outside ambient (degC)

bull Q = Heat that is generated in enclosure (Watts)

bull A = Enclosure surface area (m2)

Where

bull T = Temperature difference between inside air and outside ambient (degF)

bull Q = Heat that is generated in enclosure (Watts)

bull A = Enclosure surface area (ft2)

The exterior surface of all six sides of an enclosure is calculated as

A = 2dw + 2dh + 2wh

Where d (depth) w (width) and h (height) are in meters

The exterior surface of all six sides of an enclosure is calculated as

A = (2dw + 2dh + 2wh) 144

Where d (depth) w (width) and h (height) are in inches

038Q

180T - 110

A =

408Q

T - 110

A =

038(7200)

180(4000) - 110A =

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 7

CompactLogix 5480 Controllers

This example uses the following conditions

bull All sides of the enclosure transfer heatbull Only the CompactLogix 5480 controller is installedbull Ambient temperature = 20 degC (68 degF)

DimensionsThe controller dimensions are as follows

Ground ConsiderationsYou must ground DIN rails according to the Industrial Automation Wiring and Grounding Guidelines publication 1770-41

You can use the following DIN rails

bull EN50022 - 35 x 75 mm (138 x 030 in)bull EN50022 - 35 x 15 mm (138 x 060 in)

System Power ConsiderationsThe CompactLogix 5480 controller provides power to a CompactLogix 5480 system via RTBs that are connected to external power supplies and installed on the controller

The RTBs provide the following power to the system

IMPORTANT If any of the following conditions exist the enclosure must be larger

bull Any sides of the enclosure cannot transfer heat

bull More equipment is included in the system

bull Ambient temperature is higher than 20 degC (68 degF)

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

13021 mm

(513 in)

16620 mm

(654 in)

12654 mm

(498 in)

12002 mm

(473 in)

13366 mm

(526 in)

16000 mm

(630 in)

ATTENTION This product is grounded through the DIN rail to

chassis ground Use zinc-plated chromate-passivated steel DIN rail

to assure proper grounding The use of other DIN rail materials (for

example aluminum or plastic) that can corrode oxidize or are poor

conductors can result in improper or intermittent grounding

Secure DIN rail to mounting surface approximately every 200 mm

(78 in) and use end-anchors appropriately Be sure to ground the

DIN rail properly See Industrial Automation Wiring and Grounding

Guidelines Rockwell Automationreg publication 1770-41 for more

information

Power Type Description

MOD Power

System-side power that is used to operate the CompactLogix 5480 system MOD power is provided through the MOD power RTB and passed across the MOD power bus bull The total continuous current draw across the MOD power bus must not be

more than 10 A max at 1832V DC

You must calculate the total MOD power that the controller and all local Compact 5000 IO modules draw to make sure that no more than 10 A of MOD power is drawn(1)

bull Confirm that the external MOD power supply is adequately sized for the total MOD power bus current draw in the system including the MOD power inrush current requirements

(1) If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000

IO modules can draw a maximum of 10 A in addition to the current the controller draws

SA Power

Field-side power that can be used to power field-side devices that are connected to some Compact 5000 IO modules SA power is provided through the SA power RTB and passed across the SA power bus

bull SA power is only required if your application includes local Compact 5000 IO modules that are connected to devices that use SA power

bull If you are using DC voltage for SA power the total continuous current draw across the MOD power bus must not be more than 10 A max at 18hellip32V DC

bull If you are using AC voltage for SA power the total continuous current draw across the MOD power bus must not be more than 10 A max at 18hellip240V AC

bull You can use a 5069-FPD field potential distributor to establish additional SA power buses in a CompactLogix 5480 system

If your system includes AC and DC modules that require SA power you must use a 5069-FPD field potential distributor to establish a new SA power bus

You separate the module types by SA power bus For example install DC module on the first SA power bus in the system and install the AC modules on the second SA power bus in the system

bull Confirm that the external SA power supply is sized adequately for the total SA power current draw in the system

UPS Control

Control signals from an external UPS that let the controller save the state of the program if power is lost The external UPS provides the power that is required to save the program via the MOD power RTB A UPS is not required for controller operation

8 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Controller onto the DIN Rail

1 Confirm that the DIN rail latches are closed

2 If the DIN rail latches are open gently push the rear latch back until the front latch pops up and clicks

3 Position the controller so that the back of it faces the DIN rail

4 Press the controller against the DIN rail until you hear a click

5 Confirm that all latches have fully closed and the controller is latched securely

Connect External Power Supplies to the ControllerBefore you connect MOD power or SA power to the RTBs on the CompactLogix 5480 controller complete the following tasks

bull Read System Power Considerations on page 8

bull Confirm that the external power supplies that MOD power and SA power are adequately sized for your CompactLogix 5480 system For more information see page 8

bull Verify that the external power supplies are turned off

bull Install the MOD power RTB SA power RTB and the UPS Control RTB if used

bull If IO modules are used verify that they are installed on the correct SA power bus

DC-type modules must reside on an SA power bus that uses DC power and AC-type modules must reside on an SA power bus that uses AC power

For more information see the technical documentation for Compact 5000 IO modules

IMPORTANT Remember the following

bull CompactLogix 5480 controllers do not have an embedded power supply that powers the system

The system is powered by external power supplies via

connections to the various power RTBs on the controller

bull We recommend that you use 1606 power supplies from Rockwell Automation to provide MOD power SA power and UPS control

bull You must use an external power supply that is dedicated to the UPS connection

For more information about which 1606 power supplies

are best for each power type see the Switched Mode

Power Supply Specifications Technical Data publication

1606-TD002

bull You can connect power from one external power supply to the MOD power and SA power RTBs However as stated previously we strongly recommend that you use separate external power supplies for MOD power and SA power respectively

The practice of using separate external power supplies can

help prevent unintended consequences that can result if

you use one supply

If you use separate external power supplies the loss of

power from one external power supply does not affect the

availability of power from the other supply For example if

separate external power supplies are used and SA power is

lost MOD power remains available for the Compact 5000

IO modules

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPSR

B

F

R

B

F

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPSR

B

F

R

B

F

Closed PositionOpen Position

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 9

CompactLogix 5480 Controllers

Install the MOD Power RTB

1 Hook the bottom of the MOD power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect MOD PowerThe way that you connect power to the MOD power RTB depends on whether you use UPS control signals or not

bull If you are not using UPS control signals you connect the external power supply directly to the MOD power RTB

In this case proceed to Connect to the MOD Power RTB from a Standard External Power Supply on page 10

bull If you are using UPS control signals you connect a UPS to the MOD power RTB

In this case proceed to Connect to the MOD Power RTB from a UPS on page 15

Connect to the MOD Power RTB from a Standard External Power Supply

Before you connect an external power source to the MOD power RTB make sure that the MOD power source is properly sized

1 Verify that the external power supply is not powered

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the 24V DC (+) connection on the external power supply into the first MOD (+) terminal on the RTB

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the 24V DC (mdash) connection on the external power supply into the first MOD (mdash) terminal on the RTB

5069-L4200ERMW

MOD Power RTB

IMPORTANT Your application can require a power control device for example

a switch between the external 24V DC power source and the

controller to control when the controller is powered If so you

must install the power control device at the VDC+ terminal on

the RTB

If you install the power control device at the VDC- terminal the

controller can fail to power up or power down properly

10 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

The following diagram shows an external 24V DC power supply that is connected to the MOD power RTB when you are not using UPS control signals

Install the SA Power RTBInstall the SA power RTB even if you do not use SA power

1 Hook the bottom of the SA power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect SA DC Power

Before you connect an external DC power source to the SA power RTB make sure that the SA power source is properly sized

For more information o n SA power see SA Power on page 8

1 Confirm that MOD power and SA power sources are turned off

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the DC (+) connection on the external power supply into the first SA (+) terminal on the RTB

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

24V DC

Power

Supply

+

ndashIMPORTANT SA power is only required if your application includes local

Compact 5000 IO modules that require SA power to operate

or are connected to field-side devices that are powered by

SA power

5069-L4200ERMW

SA Power RTB

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 11

CompactLogix 5480 Controllers

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the DC (mdash) connection on the external power supply into the first SA (mdash) terminal on the RTB

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

7 Insert the wire from an Earth Ground location into the first

Ground ( ) on the RTB

The Earth Ground location can be the external SA power supply the DIN rail or other Earth Ground location

8 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

The following diagram shows an external 24V DC power supply that is connected to the SA power RTB when you do not use UPS control signals

TIP

This symbol denotes a Functional Ground terminal that provides a

low impedance path between electric circuits and earth for functional

purposes and provides noise immunity improvement This connection

must be made for functional purposes

5069-L4200ERMW

24V DC

Power

Supply

+

ndash

24V DC

Power

Supply

+

ndash

MOD

Power

SA DC

Power

Functional Ground

12 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Connect SA AC Power

Before you connect an external AC power source to the SA power RTB make sure that the SA power source is properly sized

For more information o n SA power see SA Power on page 8

1 Verify that the SA power source is not powered on

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the L1AC (+) connection on the external power supply into the first SA (+) terminal on the RTB

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the L2NAC(mdash) connection on the external power supply into the first SA(mdash) terminal on the RTB

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

7 Insert the wire from an Earth Ground location into the first

Ground ( ) on the RTB

The Earth Ground location can be the external SA power supply the DIN rail or other Earth Ground location

8 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

This diagram shows an external 240V AC power supply that is connected to the SA power RTB when you do not use UPS control signals

IMPORTANT SA power is only required if your application includes local

Compact 5000 IO modules that require SA power to operate

or are connected to field-side devices that are powered by

SA power

TIP

This symbol denotes a Functional Ground terminal that provides a

low impedance path between electric circuits and earth for functional

purposes and provides noise immunity improvement This connection

must be made for functional purposes

5069-L4200ERMW

24V DC

Power

Supply

+

ndash

240V AC

Power

Supply

+

ndash

MOD

Power

SA AC

Power

Functional Ground

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 13

CompactLogix 5480 Controllers

Connect Control Signals Via UPS Control RTBThe CompactLogix 5480 controller does not have an internal energy storage module that lets the controller save the state of the program if system-side power is lost You must connect an external uninterruptible power supply (UPS) to the UPS control RTB to save the state of the program if power is lost

You connect control signals from an external power supply to the UPS control RTB to let the controller experience a controlled shutdown upon an incoming power loss

When a UPS connection is detected the CompactLogix 5480 controller defaults to initiate shutdown 1 minute after a power loss indication

We recommend that you use 1606 switched mode uninterruptible power supplies from Rockwell Automation with a CompactLogix 5480 controller for example the 1606-XLS240-UPS power supply

For more information on Bulletin 1606 uninterruptible power supplies see the following

bull Bulletin 1606 DC-UPS Uninterruptible Power Supply Installation Instructions publication 1606-IN025

bull Bulletin 1606 Switched Mode Power Supplies Reference Manual publication 1606-RM036

The switched mode uninterruptible power supplies use a 12-volt battery module to bridge power failures and voltage fluctuations We recommend that you use the 1606-XLSBATASSY1 battery module from Rockwell Automation

You can use other accessories such as replacement batteries mounting kits and panelwall mounting brackets with the battery module

For more information on and the battery module and accessories that you can use with them see the following

bull Bulletin 1606 12V 7Ah Battery Modules Installation Instructions publication 1606-IN011

bull Bulletin 1606 Switched Mode Power Supply Battery Modules (12V 7Ah) Reference Manual publication 1606-RM037

UPS Control SignalsThese control signals are used on the UPS Control RTB

UPS Control RTB Terminals

Signal Description

UPS Ready (R)

An input signal from the UPS to the controller that indicates the UPS is working and can buffer during a power failure

The charge level for a UPS to be ready to buffer during a power failure varies For example the 1606-XLS240-UPS power supply must be greater than 85 charged to be ready

The letter R indicates the RTB terminal for this signal

Buffering (B)

An input signal from the UPS to the controller that indicates the UPS battery is providing power because the external power has failed

After a preset time (typically 1 minute after power failure) the controller performs an orderly shutdown by stopping execution and saving the state of the controller

The letter B indicates the RTB terminal for this signal

Battery Fail (F)

An input from the UPS to the controller that indicates the UPS battery has failed and the controller cannot operate from stored energy

In this case the controller does not attempt to save the state of the program when the external power fails The controller issues an alarm if a UPS was previously attached and ready to buffer

The letter F indicates the RTB terminal for this signal

Inhibit (I)

An output signal from the controller to the UPS that disables the UPS signal output The INHIBIT signal is triggered after data is backed up and the system is ready to shut down

The letter I indicates the RTB terminal for this signal

14 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the UPS Control RTBInstall the UPS control RTB even if you do not intend to connect uninterruptible power to the controller

1 Hook the bottom of the UPS power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect UPS Control Signals

1 Verify that all sources of MOD power and SA power are turned off

2 Verify the followingbull A 24V DC power supply is connected to the 24V IN

terminals on the UPSbull A 12V DC battery is connected to the 12V BAT terminals

on the UPS

For more information see the example graphic on page 17

Connect to the MOD Power RTB from a UPS

1 Daisy chain the wires from these connections on the UPSbull 24V OUT (+)bull Ready (1)bull Buffering (3)bull Battery Fail (5)bull Inhibit (7)

2 Connect one wire to each (+) terminal on the MOD power RTB as shown in the example graphic on page 17a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Daisy chain a wire that is connected to the 24V OUT (ndash) terminal on the UPS and a second wire

4 Connect one wire to each (ndash) terminal on the MOD power RTB a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

IMPORTANT The UPS terminal labels in this section represent the labels on

a 1606-XLS240-UPS power supply Your UPS terminals can be

labeled differently

5069-L4200ERMW

UPS Control RTB

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 15

CompactLogix 5480 Controllers

Connect to the UPS Control RTB from a UPS

1 Connect a wire from the Ready (2) connection on the UPS to the UPS Ready terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

2 Connect a wire from the Buffering (4) connection on the UPS to the Buffering terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Connect a wire from the Battery Fail (6) connection on the UPS to the Battery Fail terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

4 Connect a wire from the Inhibit (8) connection on the UPS to the Inhibit terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

16 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

This diagram shows a 1606-XLS240-UPS power supply battery that is connected to a CompactLogix 5480 controller

5069-L4200ERMW

UPS Ready

Buffering

Battery Fail

Inhibit

(7) Inhibit +

(8) Inhibit ndash

24V DC

Power

Supply

Ready

(1) (2)

+ ndash + ndash + ndash + ndash

N L PE

Buffering

(3) (4)

Battery Fail

(5) (6)

12V DC Battery

(for example 1606-XLSBATASSY1)

+ ndash

DC-UPS

(1606-XLS240-UPS)

24V

IN

12V

BAT

24V

OUT

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 17

CompactLogix 5480 Controllers

Disconnect Wires from the RTBsIf necessary complete these tasks to disconnect wires from any RTB on the controller

1 Turn the screwdriver counter-clockwise to open the terminal

2 Remove the wire

Install Compact 5000 IO ModulesComplete one of the following

bull If you do not use local Compact 5000 IO modules in the system proceed to Install the End Cap on page 18

bull If you use local Compact 5000 IO modules in the system install the modules to the right side of the controller

After the IO modules are installed install the end cap on the right side of the last IO module in the system For more information on how to install the end cap see page 18

For more information on how to install Compact 5000IO modules see the installation instructions available with each Compact 5000 IO module catalog number

Install the End CapYou must install an end cap on the right side of the last module in a CompactLogix 5480 system The end cap covers the exposed interconnections on the last module in the system If you do not install the end cap before powering the system equipment damage or injury from electric shock can result

If you do not intend to install Compact 5000 IO modules to the system before you turn on power to the controller install the end cap

1 Align the end cap with the interlocking pieces on the controller

2 Push the end cap toward the DIN rail until it locks into place

Power the System

After the end cap is installed on the last module in the system turn on power to the MOD power RTB and the SA power RTB

IMPORTANT Consider the following before you power the system

bull Make sure to remove the debris shield from the controller before power-up

bull As noted previously you must install working controller firmware to use the COS on the controller There are two ways to install working firmware The ways are described beginning on page 23

One of the methods to install working controller firmware

uses the SD card that ships with the controller

ndash If you intend to use the SD card to install working

controller firmware go to Use a Secure Digital Card

to Install Controller Firmware on page 24

Complete the steps described in that section apply

power to the controller and return to the next

section that is Set the Network Internet Protocol

(IP) Addresses on page 19

ndash If you do not intend to use the SD card to install

working controller firmware turn on the power now

and proceed to the next section

Top Interlocking

Pieces

End Cap

Bottom Interlocking

Pieces

18 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Set the Network Internet Protocol (IP) AddressesYou must set an IP address on Ethernet ports for the controller to operate on an EtherNetIP network via that port

Out-of-the-box the following applies to Ethernet ports A1 A2 and B1

bull The ports are DHCP-enabled and the IP address is set automatically via a DHCP server

If there is no DHCP server available to set the IP address you must set the IP address manually

bull If ports A1 and A2 are configured to use DLRLinear mode you set only one IP address that is used on both ports

bull Control ports must use unique subnets

When ports A1 and A2 are configured to use DLRLinear mode however they use the same subnet because they are configured as one port

You can use one of the following to set the IP address on the controller when it is in the out-of-the-box condition

bull DHCP server

bull BOOTP DHCP EtherNetIP Commissioning tool version 30200 or later

bull RSLinx Classic software version 41000 or later

bull FactoryTalk Linx software version 61000 or later

bull Logix Designer application version 320100 or later

For more information on how to set or change the IP address on a CompactLogix 5480 controller see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

Connect the Controller to an EtherNetIP Network

Use an RJ45 cable to connect the controller to an EtherNetIP network

1 If needed wire the RJ45 connector as shown

2 Connect RJ45 cables to the controller Ethernet ports

IMPORTANT Before you can connect a CompactLogix 5480 controller to an

EtherNetIP network you must first install the network and

its components

This section assumes that the EtherNetIP network is

installed

Connector Number

Color

1585J 8-pin Cables with Support for 101001000 Mbps

1585J 8-pin Cables with Support for 10100 Mbps

1585J 4-pin Cables with Support for 10100 Mbps

1WhiteOrange

BI_DA+ TxData +

2 Orange BI_DA- TxData -

3WhiteGreen

BI_DB+ Recv Data +

4 Blue BI_DC+ Unused mdash

5 WhiteBlue BI_DC- Unused mdash

6 Green BI_DB- Recv Data -

7WhiteBrown

BI_DD+ Unused mdash

8 Brown BI_DD- Unused mdash

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 19

CompactLogix 5480 Controllers

Remove and Replace the Controller

1 Turn off power to the MOD power and the SA power RTBs

2 If there are local Compact 5000 IO modules in the system remove them If not skip to step 3

3 Disconnect wires from the RTBs

For more information see Disconnect Wires from the RTBs on page 18

4 Pull the RTB handles to remove the RTBs

IMPORTANT When you remove MOD power from the controller you shut down

power to all modules in the CompactLogix 5480 system That is

all system-side is removed When you remove SA power from the

controller all field-side power that is provided by the controller is

removed If SA power that is provided via a 5069-FPD field

potential distributor the system does not lose SA power to the

right of the field potential distributor

In this case you must use a separate power source for the SA

power RTB on the field potential distributor

We strongly recommend that before you remove MOD power or

SA power that you take the appropriate actions to help prevent

unintended consequences that can result from a system power

shutdown

Despite the removal of power from SA RTBs on the controller or

field potential distributor the 5069-OB16 and 5069-OB16F

modules continue to receive field-side power The modules

receive power from an external power source that is connected to

the LA (+) and LA (ndash) module terminals

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

UPS Control RTB

MOD Power RTB

SA Power RTB

20 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

5 Remove all cables from the controller

6 Push down on the front of the DIN rail latches

A click indicates that the DIN rail latches are open

If the DIN rail latches fail to remain in the open position hold them down

7 Pull the controller off the DIN rail

8 Repeat the installation steps that are described beginning at Install the Controller onto the DIN Rail on page 9

9 Apply MOD power and if necessary SA power to the system

Replace the FansThe CompactLogix 5480 controller uses fans at the top and bottom of the controller to help maintain lower operating temperatures when the controller is operating

Fan use includes speed control and monitoring Faults indicate fan operating conditions as follows

bull Minor faults - Triggered when a fan is not operating at the requested speed or if a fan fails to operate at all

In your Logix Designer application project you can use the Minor Faults tab on the Controller Properties dialog box to monitor for these faults

bull Major fault - Triggered if both fans fail and the controller goes over the maximum operating temperature

In this case the controller stops operating

You can order replacement fans Replacement fans come in pairs The fans are unique by position and keyed to help make sure that you install the correct fan in each position

The fans are labeled Fan 1 - Top and Fan 2 - Bottom

Consider the following

bull We recommend that you replace the fans in pairs That is if you replace the one fan we recommend that you replace the other fan too

bull You can replace fans during controller operation The fans support removal and insertion under power

bull Do not remove both fans at once if the controller is operating That is remove a fan and install the replacement fan before you remove the other fan

Remove the Top Fan

1 Push up on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

TIP In your Logix Designer application project you can

use the Major Faults tab on the Controller

Properties dialog box to monitor for this fault

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

R

B

F

Open Position

IMPORTANT If you replace fans while the controller is operating

do not touch live voltage components

TIP If the hinges do not disengage when you push up on the front of the

fan then use a screwdriver as a pry tool

5069-L4200ERMW

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 21

CompactLogix 5480 Controllers

2 Pull the fan out of the slot at the top of the controller

Install the Top Replacement Fan

1 Insert the top replacement fan into the slot at the top of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push down on the top replacement fan until it clicks in place

Remove the Bottom Fan

1 Push the down on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

2 Pull the fan out of the slot at the bottom of the controller

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

TIP If the hinges do not disengage when you push down on the front of

the fan then use a screwdriver as a pry tool

5069-L4200ERMW

5069-L4200ERMW

22 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Bottom Replacement Fan

1 Insert the bottom replacement fan into the slot at the bottom of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push up on the bottom replacement fan until it clicks in place

Use the COS For Windows-based ComputingThe COS on a CompactLogix 5480 controller runs in parallel with the Logix control engine You are not required to use the COS

You can use the following methods to install working controller firmware when the controller is in the out-of-box state

bull ControlFLASHtrade or ControlFLASH Plustrade softwarebull Secure Digital (SD) card

Use a Flash Programming Tool to Install Controller FirmwareYou can use ControlFLASH and ControlFLASH Plus software to install controller firmware

The following requirements apply when you use ControlFLASH or ControlFLASH Plus to install working controller firmware

bull You must use one of the followingndash ControlFLASH software version 150100 or laterndash ControlFLASH Plus version 20000 or later

bull You must use a Linx-based software application with your flash programming toolndash With ControlFLASH software you can use RSLinx

Classic Lite RSLinx Classic RSLinx Enterprise or FactoryTalk Linx

ndash With ControlFLASH Plus software you must use FactoryTalk Linx

Minimum software versions apply with Linx-based software For more information on the minimum software version requirements see the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

5069-L4200ERMW

5069-L4200ERMW

IMPORTANT Before you can use the COS you must install working controller firmware The requirement applies even if you

are not using the controller for real-time control If you do not

install working controller firmware the COS does not start

In the out-of-box state the controller uses firmware revision

1xxx On a CompactLogix 5480 controller the minimum

working controller firmware is revision 32012

TIP We recommend that you connect your peripherals to the

ports that are dedicated to COS use before you install

controller firmware

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 23

CompactLogix 5480 Controllers

Download the Flash Programming Tool

ControlFLASH and ControlFLASH Plus software are available from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

Download the installation files and install the software

Download the Controller Firmware

After the flash programming tool is installed download the controller firmware from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

The initial download is a exe file You use the Rockwell Automation Download Manager to extract a dmk from the downloaded file

Install the Controller Firmware

To install the controller firmware via a flash programming tool you complete the following steps

1 To start the tool click StartgtAll ProgramsgtFlashing Programming ToolsgtControlFLASH or ControlFLASH Plus

2 Follow the prompts to complete the following stepsa Choose the controllerb Select the firmware revisionc Install the controller firmware

A dialog box confirms that the installation was successful

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use a flash programming tool to install controller firmware see the following

bull ControlFLASH Firmware Upgrade Kit User Manual publication 1756-UM105

bull ControlFLASH Plus Quick Start Guide publication CFP-QS001

bull CompactLogix 5480 Controllers User Manual publication 5069-UM002

Use a Secure Digital Card to Install Controller FirmwareYou can use an SD card to install controller firmware CompactLogix 5480 controllers ship with an SD card installed behind the front door on the controller

To use an SD card to install controller firmware complete the following steps

1 Before you turn on power to the controller remove the SD card from the controller

2 Install the SD card into another working CompactLogix 5480 controller that has a Logix Designer application project on it

3 Save the project to the SD card

4 Remove the SD card from the working controller and reinstall it in the new controller

5 Turn on power to the new controller

When the new controller powers up it automatically updates the firmware to the revision that is stored on the SD card

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use the SD card with the controller after valid firmware is installed and the controller is powered see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

IMPORTANT These steps only highlight the major tasks that you

complete to install controller firmware with ControlFLASH

To successfully install controller firmware you must complete other tasks that are not described here

For complete information on how to install controller

firmware see the publications listed at the end of the section

IMPORTANT To install controller firmware on a new CompactLogix 5480

controller via an SD card you must have another controller of

the same type that is already working

The SD card method requires that you save the Logix Designer

application project from the working controller to the SD card

before you use it in the new controller

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

SD Card Slot

24 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpecificationsThis table lists a subset of controller specifications For a complete list of specifications see the CompactLogix 5380 Compact GuardLogixreg 5380 and CompactLogix 5480 Controllers Specifications Technical Data publication 5069-TD002

Environmental Specifications - CompactLogix 5480 Controllers

Attribute 5069-L430ERMW 5069-L450ERMW 5069-4100ERMW 5069-L4200ERMW

Temperature operating

IEC 60068-2-1 (Test Ad Operating Cold)

IEC 60068-2-2 (Test Bd Operating Dry Heat)

IEC 60068-2-14 (Test Na Operating Thermal Shock)

0 degC lt Ta lt +60 degC

(+32 degF lt Ta lt +140 degF)

Temperature surrounding air max 60 degC (140 degF)

Enclosure Type Rating None (open-style)

Voltage and current ratings

MOD Power voltage range 18hellip32V DC

MOD Power power max 72 W

MOD Power current typical 4 A

MOD Power inrush 4 A for 15 ms

MOD Power Passthrough(1) 6 A 18hellip32V DC

MOD Power current rating max10 A

Do not exceed 10 A current draw at the MOD power RTB(4)

SA Power voltage ranges(2) 0hellip32V DC

0hellip240V AC 47hellip63 Hz

SA Power current max (2) 10 mA (DC power)

25 mA (AC power)

SA Power Passthrough(2) (3) 999 A 0hellip32V DC

9975 A 0hellip240V AC 47hellip63 Hz

SA Power current rating max(2) Do not exceed 10 A current draw at the SA power RTB

Isolation voltage

300V (continuous) Basic Insulation Type SA and MOD Power to Backplane

300V (continuous) Basic Insulation Type SA to MOD Power

300V (continuous) Basic Insulation Type Ethernet to Backplane

300V (continuous) Double Insulation Type Ethernet to MOD Power

300V (continuous) Double Insulation Type Ethernet to SA Power

50V (continuous) Functional Insulation Type Ethernet to USB ports and DisplayPort

300V (continuous) Basic Insulation Type USB ports and DisplayPort to Backplane

300V (continuous) Double Insulation Type USB ports and DisplayPort to MOD Power

300V (continuous) Double Insulation Type USB ports and DisplayPort to SA Power

No isolation between Ethernet ports

Type tested at 1500V AC for 60 s

Wire size

5069-RTB4-SCREW 5069-RTB6-SCREW connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 35 mm (014 in) max diameter including insulation single wire connection only

5069-RTB4-UPS connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 29 mm (011 in) max diameter including insulation single wire connection only

Ethernet connections

Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2

Insulation-stripping length 5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 12 mm (047 in)

Terminal block torque5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 04 Nbullm (35 lbbullin)

ATTENTION Do not wire more than two conductors on one RTB terminal

(1) Maximum level of MOD power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(2) SA power specifications are based on the number and type of Compact 5000 IO modules that are used in the system If the set of IO modules that is used in the system require AC and DC voltage you must install a 5069-FPD field

potential distributor to separate the module types

(3) Maximum level of SA power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(4) Remember MOD power usage includes the total power that the controller and local Compact 5000 IO modules use If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000 IO

modules can draw a maximum of 10 A in addition to the current that the controller draws

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 25

CompactLogix 5480 Controllers

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation

You can view or download publications at httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage To order paper copies of technical documentation contact your local Allen-Bradley distributor or Rockwell Automationreg sales representative

Resource Description

CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069-TD002

Provides specifications and other technical data for CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 controllers

CompactLogix 5480 Controllers User Manual publication 5069-UM002 Describes how to configure operate and monitor CompactLogix 5480 controllers

Industrial Automation Wiring and Grounding Guidelines publication 1770-41 Provides general guidelines for installing a Rockwell Automationreg industrial system

Product Certifications website rokautocertifications Provides declarations of conformity certificates and other certification details

26 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 7: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

CompactLogix 5480 Controllers

SpacingMaintain spacing from enclosure walls wireways and adjacent equipment Ambient temperature is higher at the top of an enclosed cabinet

The minimum distance on of a system that includes only a CompactLogix 5480 controller is as follows

bull 2500 mm (098 in) between the sides and the cabinet

bull 2500 mm (098 in) between the front of the controller and the cabinet

bull 5000 mm (196 in) between the top and bottom and the cabinet

We recommend that you install the controller near the bottom of the enclosure where ambient temperature is lower

Enclosure SelectionThis example is provided to help you size an enclosure for your CompactLogix 5480 controller You need heat dissipation data from all components that are planned for your enclosure to calculate the enclosure size

With no active method of heat dissipation for example air conditioning either of the following approximate equations can be used for a metal cabinet

The maximum ambient rating of the CompactLogix 5480 controller is 60 degC (140 degF) If the maximum external cabinet temperature is 20 degC (68 degF) then T=40

In this example with only the controller the heat dissipation is 72 W that is the sum of all components in the enclosure In the following equation T=40 and Q=72

In this example the enclosure must have a minimum exterior surface of 0386 m2

If any portion of the enclosure cannot transfer heat exclude that value from the calculation

The minimum installation clearance for a CompactLogix 5480 controller is 26700 x 18400 x 15200 mm (1050 x 725 x 600 in) HxWxD

The standard cabinet depth in this example is 15420 mm (600 in)

To meet cooling and clearance requirements in this example the cabinet must be approximately 30480 x 35560 x 15420 mm(1200 x 1400 x 600 in) HxWxD

A = 2DW +2DH + 2WH

A = 2 x (01542 x 03556) + 2 x (01542 x 03048) + 2 x (03556 x 03048) = 04204 m2

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

Top

Bottom

SideSide

End cap

Cabinet

Metric Imperial

Where

bull T = Temperature difference between inside air and outside ambient (degC)

bull Q = Heat that is generated in enclosure (Watts)

bull A = Enclosure surface area (m2)

Where

bull T = Temperature difference between inside air and outside ambient (degF)

bull Q = Heat that is generated in enclosure (Watts)

bull A = Enclosure surface area (ft2)

The exterior surface of all six sides of an enclosure is calculated as

A = 2dw + 2dh + 2wh

Where d (depth) w (width) and h (height) are in meters

The exterior surface of all six sides of an enclosure is calculated as

A = (2dw + 2dh + 2wh) 144

Where d (depth) w (width) and h (height) are in inches

038Q

180T - 110

A =

408Q

T - 110

A =

038(7200)

180(4000) - 110A =

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 7

CompactLogix 5480 Controllers

This example uses the following conditions

bull All sides of the enclosure transfer heatbull Only the CompactLogix 5480 controller is installedbull Ambient temperature = 20 degC (68 degF)

DimensionsThe controller dimensions are as follows

Ground ConsiderationsYou must ground DIN rails according to the Industrial Automation Wiring and Grounding Guidelines publication 1770-41

You can use the following DIN rails

bull EN50022 - 35 x 75 mm (138 x 030 in)bull EN50022 - 35 x 15 mm (138 x 060 in)

System Power ConsiderationsThe CompactLogix 5480 controller provides power to a CompactLogix 5480 system via RTBs that are connected to external power supplies and installed on the controller

The RTBs provide the following power to the system

IMPORTANT If any of the following conditions exist the enclosure must be larger

bull Any sides of the enclosure cannot transfer heat

bull More equipment is included in the system

bull Ambient temperature is higher than 20 degC (68 degF)

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

13021 mm

(513 in)

16620 mm

(654 in)

12654 mm

(498 in)

12002 mm

(473 in)

13366 mm

(526 in)

16000 mm

(630 in)

ATTENTION This product is grounded through the DIN rail to

chassis ground Use zinc-plated chromate-passivated steel DIN rail

to assure proper grounding The use of other DIN rail materials (for

example aluminum or plastic) that can corrode oxidize or are poor

conductors can result in improper or intermittent grounding

Secure DIN rail to mounting surface approximately every 200 mm

(78 in) and use end-anchors appropriately Be sure to ground the

DIN rail properly See Industrial Automation Wiring and Grounding

Guidelines Rockwell Automationreg publication 1770-41 for more

information

Power Type Description

MOD Power

System-side power that is used to operate the CompactLogix 5480 system MOD power is provided through the MOD power RTB and passed across the MOD power bus bull The total continuous current draw across the MOD power bus must not be

more than 10 A max at 1832V DC

You must calculate the total MOD power that the controller and all local Compact 5000 IO modules draw to make sure that no more than 10 A of MOD power is drawn(1)

bull Confirm that the external MOD power supply is adequately sized for the total MOD power bus current draw in the system including the MOD power inrush current requirements

(1) If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000

IO modules can draw a maximum of 10 A in addition to the current the controller draws

SA Power

Field-side power that can be used to power field-side devices that are connected to some Compact 5000 IO modules SA power is provided through the SA power RTB and passed across the SA power bus

bull SA power is only required if your application includes local Compact 5000 IO modules that are connected to devices that use SA power

bull If you are using DC voltage for SA power the total continuous current draw across the MOD power bus must not be more than 10 A max at 18hellip32V DC

bull If you are using AC voltage for SA power the total continuous current draw across the MOD power bus must not be more than 10 A max at 18hellip240V AC

bull You can use a 5069-FPD field potential distributor to establish additional SA power buses in a CompactLogix 5480 system

If your system includes AC and DC modules that require SA power you must use a 5069-FPD field potential distributor to establish a new SA power bus

You separate the module types by SA power bus For example install DC module on the first SA power bus in the system and install the AC modules on the second SA power bus in the system

bull Confirm that the external SA power supply is sized adequately for the total SA power current draw in the system

UPS Control

Control signals from an external UPS that let the controller save the state of the program if power is lost The external UPS provides the power that is required to save the program via the MOD power RTB A UPS is not required for controller operation

8 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Controller onto the DIN Rail

1 Confirm that the DIN rail latches are closed

2 If the DIN rail latches are open gently push the rear latch back until the front latch pops up and clicks

3 Position the controller so that the back of it faces the DIN rail

4 Press the controller against the DIN rail until you hear a click

5 Confirm that all latches have fully closed and the controller is latched securely

Connect External Power Supplies to the ControllerBefore you connect MOD power or SA power to the RTBs on the CompactLogix 5480 controller complete the following tasks

bull Read System Power Considerations on page 8

bull Confirm that the external power supplies that MOD power and SA power are adequately sized for your CompactLogix 5480 system For more information see page 8

bull Verify that the external power supplies are turned off

bull Install the MOD power RTB SA power RTB and the UPS Control RTB if used

bull If IO modules are used verify that they are installed on the correct SA power bus

DC-type modules must reside on an SA power bus that uses DC power and AC-type modules must reside on an SA power bus that uses AC power

For more information see the technical documentation for Compact 5000 IO modules

IMPORTANT Remember the following

bull CompactLogix 5480 controllers do not have an embedded power supply that powers the system

The system is powered by external power supplies via

connections to the various power RTBs on the controller

bull We recommend that you use 1606 power supplies from Rockwell Automation to provide MOD power SA power and UPS control

bull You must use an external power supply that is dedicated to the UPS connection

For more information about which 1606 power supplies

are best for each power type see the Switched Mode

Power Supply Specifications Technical Data publication

1606-TD002

bull You can connect power from one external power supply to the MOD power and SA power RTBs However as stated previously we strongly recommend that you use separate external power supplies for MOD power and SA power respectively

The practice of using separate external power supplies can

help prevent unintended consequences that can result if

you use one supply

If you use separate external power supplies the loss of

power from one external power supply does not affect the

availability of power from the other supply For example if

separate external power supplies are used and SA power is

lost MOD power remains available for the Compact 5000

IO modules

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPSR

B

F

R

B

F

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPSR

B

F

R

B

F

Closed PositionOpen Position

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 9

CompactLogix 5480 Controllers

Install the MOD Power RTB

1 Hook the bottom of the MOD power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect MOD PowerThe way that you connect power to the MOD power RTB depends on whether you use UPS control signals or not

bull If you are not using UPS control signals you connect the external power supply directly to the MOD power RTB

In this case proceed to Connect to the MOD Power RTB from a Standard External Power Supply on page 10

bull If you are using UPS control signals you connect a UPS to the MOD power RTB

In this case proceed to Connect to the MOD Power RTB from a UPS on page 15

Connect to the MOD Power RTB from a Standard External Power Supply

Before you connect an external power source to the MOD power RTB make sure that the MOD power source is properly sized

1 Verify that the external power supply is not powered

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the 24V DC (+) connection on the external power supply into the first MOD (+) terminal on the RTB

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the 24V DC (mdash) connection on the external power supply into the first MOD (mdash) terminal on the RTB

5069-L4200ERMW

MOD Power RTB

IMPORTANT Your application can require a power control device for example

a switch between the external 24V DC power source and the

controller to control when the controller is powered If so you

must install the power control device at the VDC+ terminal on

the RTB

If you install the power control device at the VDC- terminal the

controller can fail to power up or power down properly

10 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

The following diagram shows an external 24V DC power supply that is connected to the MOD power RTB when you are not using UPS control signals

Install the SA Power RTBInstall the SA power RTB even if you do not use SA power

1 Hook the bottom of the SA power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect SA DC Power

Before you connect an external DC power source to the SA power RTB make sure that the SA power source is properly sized

For more information o n SA power see SA Power on page 8

1 Confirm that MOD power and SA power sources are turned off

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the DC (+) connection on the external power supply into the first SA (+) terminal on the RTB

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

24V DC

Power

Supply

+

ndashIMPORTANT SA power is only required if your application includes local

Compact 5000 IO modules that require SA power to operate

or are connected to field-side devices that are powered by

SA power

5069-L4200ERMW

SA Power RTB

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 11

CompactLogix 5480 Controllers

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the DC (mdash) connection on the external power supply into the first SA (mdash) terminal on the RTB

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

7 Insert the wire from an Earth Ground location into the first

Ground ( ) on the RTB

The Earth Ground location can be the external SA power supply the DIN rail or other Earth Ground location

8 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

The following diagram shows an external 24V DC power supply that is connected to the SA power RTB when you do not use UPS control signals

TIP

This symbol denotes a Functional Ground terminal that provides a

low impedance path between electric circuits and earth for functional

purposes and provides noise immunity improvement This connection

must be made for functional purposes

5069-L4200ERMW

24V DC

Power

Supply

+

ndash

24V DC

Power

Supply

+

ndash

MOD

Power

SA DC

Power

Functional Ground

12 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Connect SA AC Power

Before you connect an external AC power source to the SA power RTB make sure that the SA power source is properly sized

For more information o n SA power see SA Power on page 8

1 Verify that the SA power source is not powered on

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the L1AC (+) connection on the external power supply into the first SA (+) terminal on the RTB

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the L2NAC(mdash) connection on the external power supply into the first SA(mdash) terminal on the RTB

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

7 Insert the wire from an Earth Ground location into the first

Ground ( ) on the RTB

The Earth Ground location can be the external SA power supply the DIN rail or other Earth Ground location

8 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

This diagram shows an external 240V AC power supply that is connected to the SA power RTB when you do not use UPS control signals

IMPORTANT SA power is only required if your application includes local

Compact 5000 IO modules that require SA power to operate

or are connected to field-side devices that are powered by

SA power

TIP

This symbol denotes a Functional Ground terminal that provides a

low impedance path between electric circuits and earth for functional

purposes and provides noise immunity improvement This connection

must be made for functional purposes

5069-L4200ERMW

24V DC

Power

Supply

+

ndash

240V AC

Power

Supply

+

ndash

MOD

Power

SA AC

Power

Functional Ground

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 13

CompactLogix 5480 Controllers

Connect Control Signals Via UPS Control RTBThe CompactLogix 5480 controller does not have an internal energy storage module that lets the controller save the state of the program if system-side power is lost You must connect an external uninterruptible power supply (UPS) to the UPS control RTB to save the state of the program if power is lost

You connect control signals from an external power supply to the UPS control RTB to let the controller experience a controlled shutdown upon an incoming power loss

When a UPS connection is detected the CompactLogix 5480 controller defaults to initiate shutdown 1 minute after a power loss indication

We recommend that you use 1606 switched mode uninterruptible power supplies from Rockwell Automation with a CompactLogix 5480 controller for example the 1606-XLS240-UPS power supply

For more information on Bulletin 1606 uninterruptible power supplies see the following

bull Bulletin 1606 DC-UPS Uninterruptible Power Supply Installation Instructions publication 1606-IN025

bull Bulletin 1606 Switched Mode Power Supplies Reference Manual publication 1606-RM036

The switched mode uninterruptible power supplies use a 12-volt battery module to bridge power failures and voltage fluctuations We recommend that you use the 1606-XLSBATASSY1 battery module from Rockwell Automation

You can use other accessories such as replacement batteries mounting kits and panelwall mounting brackets with the battery module

For more information on and the battery module and accessories that you can use with them see the following

bull Bulletin 1606 12V 7Ah Battery Modules Installation Instructions publication 1606-IN011

bull Bulletin 1606 Switched Mode Power Supply Battery Modules (12V 7Ah) Reference Manual publication 1606-RM037

UPS Control SignalsThese control signals are used on the UPS Control RTB

UPS Control RTB Terminals

Signal Description

UPS Ready (R)

An input signal from the UPS to the controller that indicates the UPS is working and can buffer during a power failure

The charge level for a UPS to be ready to buffer during a power failure varies For example the 1606-XLS240-UPS power supply must be greater than 85 charged to be ready

The letter R indicates the RTB terminal for this signal

Buffering (B)

An input signal from the UPS to the controller that indicates the UPS battery is providing power because the external power has failed

After a preset time (typically 1 minute after power failure) the controller performs an orderly shutdown by stopping execution and saving the state of the controller

The letter B indicates the RTB terminal for this signal

Battery Fail (F)

An input from the UPS to the controller that indicates the UPS battery has failed and the controller cannot operate from stored energy

In this case the controller does not attempt to save the state of the program when the external power fails The controller issues an alarm if a UPS was previously attached and ready to buffer

The letter F indicates the RTB terminal for this signal

Inhibit (I)

An output signal from the controller to the UPS that disables the UPS signal output The INHIBIT signal is triggered after data is backed up and the system is ready to shut down

The letter I indicates the RTB terminal for this signal

14 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the UPS Control RTBInstall the UPS control RTB even if you do not intend to connect uninterruptible power to the controller

1 Hook the bottom of the UPS power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect UPS Control Signals

1 Verify that all sources of MOD power and SA power are turned off

2 Verify the followingbull A 24V DC power supply is connected to the 24V IN

terminals on the UPSbull A 12V DC battery is connected to the 12V BAT terminals

on the UPS

For more information see the example graphic on page 17

Connect to the MOD Power RTB from a UPS

1 Daisy chain the wires from these connections on the UPSbull 24V OUT (+)bull Ready (1)bull Buffering (3)bull Battery Fail (5)bull Inhibit (7)

2 Connect one wire to each (+) terminal on the MOD power RTB as shown in the example graphic on page 17a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Daisy chain a wire that is connected to the 24V OUT (ndash) terminal on the UPS and a second wire

4 Connect one wire to each (ndash) terminal on the MOD power RTB a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

IMPORTANT The UPS terminal labels in this section represent the labels on

a 1606-XLS240-UPS power supply Your UPS terminals can be

labeled differently

5069-L4200ERMW

UPS Control RTB

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 15

CompactLogix 5480 Controllers

Connect to the UPS Control RTB from a UPS

1 Connect a wire from the Ready (2) connection on the UPS to the UPS Ready terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

2 Connect a wire from the Buffering (4) connection on the UPS to the Buffering terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Connect a wire from the Battery Fail (6) connection on the UPS to the Battery Fail terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

4 Connect a wire from the Inhibit (8) connection on the UPS to the Inhibit terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

16 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

This diagram shows a 1606-XLS240-UPS power supply battery that is connected to a CompactLogix 5480 controller

5069-L4200ERMW

UPS Ready

Buffering

Battery Fail

Inhibit

(7) Inhibit +

(8) Inhibit ndash

24V DC

Power

Supply

Ready

(1) (2)

+ ndash + ndash + ndash + ndash

N L PE

Buffering

(3) (4)

Battery Fail

(5) (6)

12V DC Battery

(for example 1606-XLSBATASSY1)

+ ndash

DC-UPS

(1606-XLS240-UPS)

24V

IN

12V

BAT

24V

OUT

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 17

CompactLogix 5480 Controllers

Disconnect Wires from the RTBsIf necessary complete these tasks to disconnect wires from any RTB on the controller

1 Turn the screwdriver counter-clockwise to open the terminal

2 Remove the wire

Install Compact 5000 IO ModulesComplete one of the following

bull If you do not use local Compact 5000 IO modules in the system proceed to Install the End Cap on page 18

bull If you use local Compact 5000 IO modules in the system install the modules to the right side of the controller

After the IO modules are installed install the end cap on the right side of the last IO module in the system For more information on how to install the end cap see page 18

For more information on how to install Compact 5000IO modules see the installation instructions available with each Compact 5000 IO module catalog number

Install the End CapYou must install an end cap on the right side of the last module in a CompactLogix 5480 system The end cap covers the exposed interconnections on the last module in the system If you do not install the end cap before powering the system equipment damage or injury from electric shock can result

If you do not intend to install Compact 5000 IO modules to the system before you turn on power to the controller install the end cap

1 Align the end cap with the interlocking pieces on the controller

2 Push the end cap toward the DIN rail until it locks into place

Power the System

After the end cap is installed on the last module in the system turn on power to the MOD power RTB and the SA power RTB

IMPORTANT Consider the following before you power the system

bull Make sure to remove the debris shield from the controller before power-up

bull As noted previously you must install working controller firmware to use the COS on the controller There are two ways to install working firmware The ways are described beginning on page 23

One of the methods to install working controller firmware

uses the SD card that ships with the controller

ndash If you intend to use the SD card to install working

controller firmware go to Use a Secure Digital Card

to Install Controller Firmware on page 24

Complete the steps described in that section apply

power to the controller and return to the next

section that is Set the Network Internet Protocol

(IP) Addresses on page 19

ndash If you do not intend to use the SD card to install

working controller firmware turn on the power now

and proceed to the next section

Top Interlocking

Pieces

End Cap

Bottom Interlocking

Pieces

18 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Set the Network Internet Protocol (IP) AddressesYou must set an IP address on Ethernet ports for the controller to operate on an EtherNetIP network via that port

Out-of-the-box the following applies to Ethernet ports A1 A2 and B1

bull The ports are DHCP-enabled and the IP address is set automatically via a DHCP server

If there is no DHCP server available to set the IP address you must set the IP address manually

bull If ports A1 and A2 are configured to use DLRLinear mode you set only one IP address that is used on both ports

bull Control ports must use unique subnets

When ports A1 and A2 are configured to use DLRLinear mode however they use the same subnet because they are configured as one port

You can use one of the following to set the IP address on the controller when it is in the out-of-the-box condition

bull DHCP server

bull BOOTP DHCP EtherNetIP Commissioning tool version 30200 or later

bull RSLinx Classic software version 41000 or later

bull FactoryTalk Linx software version 61000 or later

bull Logix Designer application version 320100 or later

For more information on how to set or change the IP address on a CompactLogix 5480 controller see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

Connect the Controller to an EtherNetIP Network

Use an RJ45 cable to connect the controller to an EtherNetIP network

1 If needed wire the RJ45 connector as shown

2 Connect RJ45 cables to the controller Ethernet ports

IMPORTANT Before you can connect a CompactLogix 5480 controller to an

EtherNetIP network you must first install the network and

its components

This section assumes that the EtherNetIP network is

installed

Connector Number

Color

1585J 8-pin Cables with Support for 101001000 Mbps

1585J 8-pin Cables with Support for 10100 Mbps

1585J 4-pin Cables with Support for 10100 Mbps

1WhiteOrange

BI_DA+ TxData +

2 Orange BI_DA- TxData -

3WhiteGreen

BI_DB+ Recv Data +

4 Blue BI_DC+ Unused mdash

5 WhiteBlue BI_DC- Unused mdash

6 Green BI_DB- Recv Data -

7WhiteBrown

BI_DD+ Unused mdash

8 Brown BI_DD- Unused mdash

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 19

CompactLogix 5480 Controllers

Remove and Replace the Controller

1 Turn off power to the MOD power and the SA power RTBs

2 If there are local Compact 5000 IO modules in the system remove them If not skip to step 3

3 Disconnect wires from the RTBs

For more information see Disconnect Wires from the RTBs on page 18

4 Pull the RTB handles to remove the RTBs

IMPORTANT When you remove MOD power from the controller you shut down

power to all modules in the CompactLogix 5480 system That is

all system-side is removed When you remove SA power from the

controller all field-side power that is provided by the controller is

removed If SA power that is provided via a 5069-FPD field

potential distributor the system does not lose SA power to the

right of the field potential distributor

In this case you must use a separate power source for the SA

power RTB on the field potential distributor

We strongly recommend that before you remove MOD power or

SA power that you take the appropriate actions to help prevent

unintended consequences that can result from a system power

shutdown

Despite the removal of power from SA RTBs on the controller or

field potential distributor the 5069-OB16 and 5069-OB16F

modules continue to receive field-side power The modules

receive power from an external power source that is connected to

the LA (+) and LA (ndash) module terminals

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

UPS Control RTB

MOD Power RTB

SA Power RTB

20 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

5 Remove all cables from the controller

6 Push down on the front of the DIN rail latches

A click indicates that the DIN rail latches are open

If the DIN rail latches fail to remain in the open position hold them down

7 Pull the controller off the DIN rail

8 Repeat the installation steps that are described beginning at Install the Controller onto the DIN Rail on page 9

9 Apply MOD power and if necessary SA power to the system

Replace the FansThe CompactLogix 5480 controller uses fans at the top and bottom of the controller to help maintain lower operating temperatures when the controller is operating

Fan use includes speed control and monitoring Faults indicate fan operating conditions as follows

bull Minor faults - Triggered when a fan is not operating at the requested speed or if a fan fails to operate at all

In your Logix Designer application project you can use the Minor Faults tab on the Controller Properties dialog box to monitor for these faults

bull Major fault - Triggered if both fans fail and the controller goes over the maximum operating temperature

In this case the controller stops operating

You can order replacement fans Replacement fans come in pairs The fans are unique by position and keyed to help make sure that you install the correct fan in each position

The fans are labeled Fan 1 - Top and Fan 2 - Bottom

Consider the following

bull We recommend that you replace the fans in pairs That is if you replace the one fan we recommend that you replace the other fan too

bull You can replace fans during controller operation The fans support removal and insertion under power

bull Do not remove both fans at once if the controller is operating That is remove a fan and install the replacement fan before you remove the other fan

Remove the Top Fan

1 Push up on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

TIP In your Logix Designer application project you can

use the Major Faults tab on the Controller

Properties dialog box to monitor for this fault

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

R

B

F

Open Position

IMPORTANT If you replace fans while the controller is operating

do not touch live voltage components

TIP If the hinges do not disengage when you push up on the front of the

fan then use a screwdriver as a pry tool

5069-L4200ERMW

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 21

CompactLogix 5480 Controllers

2 Pull the fan out of the slot at the top of the controller

Install the Top Replacement Fan

1 Insert the top replacement fan into the slot at the top of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push down on the top replacement fan until it clicks in place

Remove the Bottom Fan

1 Push the down on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

2 Pull the fan out of the slot at the bottom of the controller

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

TIP If the hinges do not disengage when you push down on the front of

the fan then use a screwdriver as a pry tool

5069-L4200ERMW

5069-L4200ERMW

22 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Bottom Replacement Fan

1 Insert the bottom replacement fan into the slot at the bottom of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push up on the bottom replacement fan until it clicks in place

Use the COS For Windows-based ComputingThe COS on a CompactLogix 5480 controller runs in parallel with the Logix control engine You are not required to use the COS

You can use the following methods to install working controller firmware when the controller is in the out-of-box state

bull ControlFLASHtrade or ControlFLASH Plustrade softwarebull Secure Digital (SD) card

Use a Flash Programming Tool to Install Controller FirmwareYou can use ControlFLASH and ControlFLASH Plus software to install controller firmware

The following requirements apply when you use ControlFLASH or ControlFLASH Plus to install working controller firmware

bull You must use one of the followingndash ControlFLASH software version 150100 or laterndash ControlFLASH Plus version 20000 or later

bull You must use a Linx-based software application with your flash programming toolndash With ControlFLASH software you can use RSLinx

Classic Lite RSLinx Classic RSLinx Enterprise or FactoryTalk Linx

ndash With ControlFLASH Plus software you must use FactoryTalk Linx

Minimum software versions apply with Linx-based software For more information on the minimum software version requirements see the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

5069-L4200ERMW

5069-L4200ERMW

IMPORTANT Before you can use the COS you must install working controller firmware The requirement applies even if you

are not using the controller for real-time control If you do not

install working controller firmware the COS does not start

In the out-of-box state the controller uses firmware revision

1xxx On a CompactLogix 5480 controller the minimum

working controller firmware is revision 32012

TIP We recommend that you connect your peripherals to the

ports that are dedicated to COS use before you install

controller firmware

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 23

CompactLogix 5480 Controllers

Download the Flash Programming Tool

ControlFLASH and ControlFLASH Plus software are available from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

Download the installation files and install the software

Download the Controller Firmware

After the flash programming tool is installed download the controller firmware from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

The initial download is a exe file You use the Rockwell Automation Download Manager to extract a dmk from the downloaded file

Install the Controller Firmware

To install the controller firmware via a flash programming tool you complete the following steps

1 To start the tool click StartgtAll ProgramsgtFlashing Programming ToolsgtControlFLASH or ControlFLASH Plus

2 Follow the prompts to complete the following stepsa Choose the controllerb Select the firmware revisionc Install the controller firmware

A dialog box confirms that the installation was successful

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use a flash programming tool to install controller firmware see the following

bull ControlFLASH Firmware Upgrade Kit User Manual publication 1756-UM105

bull ControlFLASH Plus Quick Start Guide publication CFP-QS001

bull CompactLogix 5480 Controllers User Manual publication 5069-UM002

Use a Secure Digital Card to Install Controller FirmwareYou can use an SD card to install controller firmware CompactLogix 5480 controllers ship with an SD card installed behind the front door on the controller

To use an SD card to install controller firmware complete the following steps

1 Before you turn on power to the controller remove the SD card from the controller

2 Install the SD card into another working CompactLogix 5480 controller that has a Logix Designer application project on it

3 Save the project to the SD card

4 Remove the SD card from the working controller and reinstall it in the new controller

5 Turn on power to the new controller

When the new controller powers up it automatically updates the firmware to the revision that is stored on the SD card

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use the SD card with the controller after valid firmware is installed and the controller is powered see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

IMPORTANT These steps only highlight the major tasks that you

complete to install controller firmware with ControlFLASH

To successfully install controller firmware you must complete other tasks that are not described here

For complete information on how to install controller

firmware see the publications listed at the end of the section

IMPORTANT To install controller firmware on a new CompactLogix 5480

controller via an SD card you must have another controller of

the same type that is already working

The SD card method requires that you save the Logix Designer

application project from the working controller to the SD card

before you use it in the new controller

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

SD Card Slot

24 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpecificationsThis table lists a subset of controller specifications For a complete list of specifications see the CompactLogix 5380 Compact GuardLogixreg 5380 and CompactLogix 5480 Controllers Specifications Technical Data publication 5069-TD002

Environmental Specifications - CompactLogix 5480 Controllers

Attribute 5069-L430ERMW 5069-L450ERMW 5069-4100ERMW 5069-L4200ERMW

Temperature operating

IEC 60068-2-1 (Test Ad Operating Cold)

IEC 60068-2-2 (Test Bd Operating Dry Heat)

IEC 60068-2-14 (Test Na Operating Thermal Shock)

0 degC lt Ta lt +60 degC

(+32 degF lt Ta lt +140 degF)

Temperature surrounding air max 60 degC (140 degF)

Enclosure Type Rating None (open-style)

Voltage and current ratings

MOD Power voltage range 18hellip32V DC

MOD Power power max 72 W

MOD Power current typical 4 A

MOD Power inrush 4 A for 15 ms

MOD Power Passthrough(1) 6 A 18hellip32V DC

MOD Power current rating max10 A

Do not exceed 10 A current draw at the MOD power RTB(4)

SA Power voltage ranges(2) 0hellip32V DC

0hellip240V AC 47hellip63 Hz

SA Power current max (2) 10 mA (DC power)

25 mA (AC power)

SA Power Passthrough(2) (3) 999 A 0hellip32V DC

9975 A 0hellip240V AC 47hellip63 Hz

SA Power current rating max(2) Do not exceed 10 A current draw at the SA power RTB

Isolation voltage

300V (continuous) Basic Insulation Type SA and MOD Power to Backplane

300V (continuous) Basic Insulation Type SA to MOD Power

300V (continuous) Basic Insulation Type Ethernet to Backplane

300V (continuous) Double Insulation Type Ethernet to MOD Power

300V (continuous) Double Insulation Type Ethernet to SA Power

50V (continuous) Functional Insulation Type Ethernet to USB ports and DisplayPort

300V (continuous) Basic Insulation Type USB ports and DisplayPort to Backplane

300V (continuous) Double Insulation Type USB ports and DisplayPort to MOD Power

300V (continuous) Double Insulation Type USB ports and DisplayPort to SA Power

No isolation between Ethernet ports

Type tested at 1500V AC for 60 s

Wire size

5069-RTB4-SCREW 5069-RTB6-SCREW connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 35 mm (014 in) max diameter including insulation single wire connection only

5069-RTB4-UPS connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 29 mm (011 in) max diameter including insulation single wire connection only

Ethernet connections

Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2

Insulation-stripping length 5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 12 mm (047 in)

Terminal block torque5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 04 Nbullm (35 lbbullin)

ATTENTION Do not wire more than two conductors on one RTB terminal

(1) Maximum level of MOD power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(2) SA power specifications are based on the number and type of Compact 5000 IO modules that are used in the system If the set of IO modules that is used in the system require AC and DC voltage you must install a 5069-FPD field

potential distributor to separate the module types

(3) Maximum level of SA power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(4) Remember MOD power usage includes the total power that the controller and local Compact 5000 IO modules use If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000 IO

modules can draw a maximum of 10 A in addition to the current that the controller draws

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 25

CompactLogix 5480 Controllers

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation

You can view or download publications at httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage To order paper copies of technical documentation contact your local Allen-Bradley distributor or Rockwell Automationreg sales representative

Resource Description

CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069-TD002

Provides specifications and other technical data for CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 controllers

CompactLogix 5480 Controllers User Manual publication 5069-UM002 Describes how to configure operate and monitor CompactLogix 5480 controllers

Industrial Automation Wiring and Grounding Guidelines publication 1770-41 Provides general guidelines for installing a Rockwell Automationreg industrial system

Product Certifications website rokautocertifications Provides declarations of conformity certificates and other certification details

26 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 8: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

CompactLogix 5480 Controllers

This example uses the following conditions

bull All sides of the enclosure transfer heatbull Only the CompactLogix 5480 controller is installedbull Ambient temperature = 20 degC (68 degF)

DimensionsThe controller dimensions are as follows

Ground ConsiderationsYou must ground DIN rails according to the Industrial Automation Wiring and Grounding Guidelines publication 1770-41

You can use the following DIN rails

bull EN50022 - 35 x 75 mm (138 x 030 in)bull EN50022 - 35 x 15 mm (138 x 060 in)

System Power ConsiderationsThe CompactLogix 5480 controller provides power to a CompactLogix 5480 system via RTBs that are connected to external power supplies and installed on the controller

The RTBs provide the following power to the system

IMPORTANT If any of the following conditions exist the enclosure must be larger

bull Any sides of the enclosure cannot transfer heat

bull More equipment is included in the system

bull Ambient temperature is higher than 20 degC (68 degF)

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

13021 mm

(513 in)

16620 mm

(654 in)

12654 mm

(498 in)

12002 mm

(473 in)

13366 mm

(526 in)

16000 mm

(630 in)

ATTENTION This product is grounded through the DIN rail to

chassis ground Use zinc-plated chromate-passivated steel DIN rail

to assure proper grounding The use of other DIN rail materials (for

example aluminum or plastic) that can corrode oxidize or are poor

conductors can result in improper or intermittent grounding

Secure DIN rail to mounting surface approximately every 200 mm

(78 in) and use end-anchors appropriately Be sure to ground the

DIN rail properly See Industrial Automation Wiring and Grounding

Guidelines Rockwell Automationreg publication 1770-41 for more

information

Power Type Description

MOD Power

System-side power that is used to operate the CompactLogix 5480 system MOD power is provided through the MOD power RTB and passed across the MOD power bus bull The total continuous current draw across the MOD power bus must not be

more than 10 A max at 1832V DC

You must calculate the total MOD power that the controller and all local Compact 5000 IO modules draw to make sure that no more than 10 A of MOD power is drawn(1)

bull Confirm that the external MOD power supply is adequately sized for the total MOD power bus current draw in the system including the MOD power inrush current requirements

(1) If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000

IO modules can draw a maximum of 10 A in addition to the current the controller draws

SA Power

Field-side power that can be used to power field-side devices that are connected to some Compact 5000 IO modules SA power is provided through the SA power RTB and passed across the SA power bus

bull SA power is only required if your application includes local Compact 5000 IO modules that are connected to devices that use SA power

bull If you are using DC voltage for SA power the total continuous current draw across the MOD power bus must not be more than 10 A max at 18hellip32V DC

bull If you are using AC voltage for SA power the total continuous current draw across the MOD power bus must not be more than 10 A max at 18hellip240V AC

bull You can use a 5069-FPD field potential distributor to establish additional SA power buses in a CompactLogix 5480 system

If your system includes AC and DC modules that require SA power you must use a 5069-FPD field potential distributor to establish a new SA power bus

You separate the module types by SA power bus For example install DC module on the first SA power bus in the system and install the AC modules on the second SA power bus in the system

bull Confirm that the external SA power supply is sized adequately for the total SA power current draw in the system

UPS Control

Control signals from an external UPS that let the controller save the state of the program if power is lost The external UPS provides the power that is required to save the program via the MOD power RTB A UPS is not required for controller operation

8 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Controller onto the DIN Rail

1 Confirm that the DIN rail latches are closed

2 If the DIN rail latches are open gently push the rear latch back until the front latch pops up and clicks

3 Position the controller so that the back of it faces the DIN rail

4 Press the controller against the DIN rail until you hear a click

5 Confirm that all latches have fully closed and the controller is latched securely

Connect External Power Supplies to the ControllerBefore you connect MOD power or SA power to the RTBs on the CompactLogix 5480 controller complete the following tasks

bull Read System Power Considerations on page 8

bull Confirm that the external power supplies that MOD power and SA power are adequately sized for your CompactLogix 5480 system For more information see page 8

bull Verify that the external power supplies are turned off

bull Install the MOD power RTB SA power RTB and the UPS Control RTB if used

bull If IO modules are used verify that they are installed on the correct SA power bus

DC-type modules must reside on an SA power bus that uses DC power and AC-type modules must reside on an SA power bus that uses AC power

For more information see the technical documentation for Compact 5000 IO modules

IMPORTANT Remember the following

bull CompactLogix 5480 controllers do not have an embedded power supply that powers the system

The system is powered by external power supplies via

connections to the various power RTBs on the controller

bull We recommend that you use 1606 power supplies from Rockwell Automation to provide MOD power SA power and UPS control

bull You must use an external power supply that is dedicated to the UPS connection

For more information about which 1606 power supplies

are best for each power type see the Switched Mode

Power Supply Specifications Technical Data publication

1606-TD002

bull You can connect power from one external power supply to the MOD power and SA power RTBs However as stated previously we strongly recommend that you use separate external power supplies for MOD power and SA power respectively

The practice of using separate external power supplies can

help prevent unintended consequences that can result if

you use one supply

If you use separate external power supplies the loss of

power from one external power supply does not affect the

availability of power from the other supply For example if

separate external power supplies are used and SA power is

lost MOD power remains available for the Compact 5000

IO modules

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPSR

B

F

R

B

F

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPSR

B

F

R

B

F

Closed PositionOpen Position

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 9

CompactLogix 5480 Controllers

Install the MOD Power RTB

1 Hook the bottom of the MOD power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect MOD PowerThe way that you connect power to the MOD power RTB depends on whether you use UPS control signals or not

bull If you are not using UPS control signals you connect the external power supply directly to the MOD power RTB

In this case proceed to Connect to the MOD Power RTB from a Standard External Power Supply on page 10

bull If you are using UPS control signals you connect a UPS to the MOD power RTB

In this case proceed to Connect to the MOD Power RTB from a UPS on page 15

Connect to the MOD Power RTB from a Standard External Power Supply

Before you connect an external power source to the MOD power RTB make sure that the MOD power source is properly sized

1 Verify that the external power supply is not powered

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the 24V DC (+) connection on the external power supply into the first MOD (+) terminal on the RTB

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the 24V DC (mdash) connection on the external power supply into the first MOD (mdash) terminal on the RTB

5069-L4200ERMW

MOD Power RTB

IMPORTANT Your application can require a power control device for example

a switch between the external 24V DC power source and the

controller to control when the controller is powered If so you

must install the power control device at the VDC+ terminal on

the RTB

If you install the power control device at the VDC- terminal the

controller can fail to power up or power down properly

10 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

The following diagram shows an external 24V DC power supply that is connected to the MOD power RTB when you are not using UPS control signals

Install the SA Power RTBInstall the SA power RTB even if you do not use SA power

1 Hook the bottom of the SA power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect SA DC Power

Before you connect an external DC power source to the SA power RTB make sure that the SA power source is properly sized

For more information o n SA power see SA Power on page 8

1 Confirm that MOD power and SA power sources are turned off

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the DC (+) connection on the external power supply into the first SA (+) terminal on the RTB

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

24V DC

Power

Supply

+

ndashIMPORTANT SA power is only required if your application includes local

Compact 5000 IO modules that require SA power to operate

or are connected to field-side devices that are powered by

SA power

5069-L4200ERMW

SA Power RTB

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 11

CompactLogix 5480 Controllers

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the DC (mdash) connection on the external power supply into the first SA (mdash) terminal on the RTB

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

7 Insert the wire from an Earth Ground location into the first

Ground ( ) on the RTB

The Earth Ground location can be the external SA power supply the DIN rail or other Earth Ground location

8 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

The following diagram shows an external 24V DC power supply that is connected to the SA power RTB when you do not use UPS control signals

TIP

This symbol denotes a Functional Ground terminal that provides a

low impedance path between electric circuits and earth for functional

purposes and provides noise immunity improvement This connection

must be made for functional purposes

5069-L4200ERMW

24V DC

Power

Supply

+

ndash

24V DC

Power

Supply

+

ndash

MOD

Power

SA DC

Power

Functional Ground

12 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Connect SA AC Power

Before you connect an external AC power source to the SA power RTB make sure that the SA power source is properly sized

For more information o n SA power see SA Power on page 8

1 Verify that the SA power source is not powered on

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the L1AC (+) connection on the external power supply into the first SA (+) terminal on the RTB

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the L2NAC(mdash) connection on the external power supply into the first SA(mdash) terminal on the RTB

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

7 Insert the wire from an Earth Ground location into the first

Ground ( ) on the RTB

The Earth Ground location can be the external SA power supply the DIN rail or other Earth Ground location

8 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

This diagram shows an external 240V AC power supply that is connected to the SA power RTB when you do not use UPS control signals

IMPORTANT SA power is only required if your application includes local

Compact 5000 IO modules that require SA power to operate

or are connected to field-side devices that are powered by

SA power

TIP

This symbol denotes a Functional Ground terminal that provides a

low impedance path between electric circuits and earth for functional

purposes and provides noise immunity improvement This connection

must be made for functional purposes

5069-L4200ERMW

24V DC

Power

Supply

+

ndash

240V AC

Power

Supply

+

ndash

MOD

Power

SA AC

Power

Functional Ground

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 13

CompactLogix 5480 Controllers

Connect Control Signals Via UPS Control RTBThe CompactLogix 5480 controller does not have an internal energy storage module that lets the controller save the state of the program if system-side power is lost You must connect an external uninterruptible power supply (UPS) to the UPS control RTB to save the state of the program if power is lost

You connect control signals from an external power supply to the UPS control RTB to let the controller experience a controlled shutdown upon an incoming power loss

When a UPS connection is detected the CompactLogix 5480 controller defaults to initiate shutdown 1 minute after a power loss indication

We recommend that you use 1606 switched mode uninterruptible power supplies from Rockwell Automation with a CompactLogix 5480 controller for example the 1606-XLS240-UPS power supply

For more information on Bulletin 1606 uninterruptible power supplies see the following

bull Bulletin 1606 DC-UPS Uninterruptible Power Supply Installation Instructions publication 1606-IN025

bull Bulletin 1606 Switched Mode Power Supplies Reference Manual publication 1606-RM036

The switched mode uninterruptible power supplies use a 12-volt battery module to bridge power failures and voltage fluctuations We recommend that you use the 1606-XLSBATASSY1 battery module from Rockwell Automation

You can use other accessories such as replacement batteries mounting kits and panelwall mounting brackets with the battery module

For more information on and the battery module and accessories that you can use with them see the following

bull Bulletin 1606 12V 7Ah Battery Modules Installation Instructions publication 1606-IN011

bull Bulletin 1606 Switched Mode Power Supply Battery Modules (12V 7Ah) Reference Manual publication 1606-RM037

UPS Control SignalsThese control signals are used on the UPS Control RTB

UPS Control RTB Terminals

Signal Description

UPS Ready (R)

An input signal from the UPS to the controller that indicates the UPS is working and can buffer during a power failure

The charge level for a UPS to be ready to buffer during a power failure varies For example the 1606-XLS240-UPS power supply must be greater than 85 charged to be ready

The letter R indicates the RTB terminal for this signal

Buffering (B)

An input signal from the UPS to the controller that indicates the UPS battery is providing power because the external power has failed

After a preset time (typically 1 minute after power failure) the controller performs an orderly shutdown by stopping execution and saving the state of the controller

The letter B indicates the RTB terminal for this signal

Battery Fail (F)

An input from the UPS to the controller that indicates the UPS battery has failed and the controller cannot operate from stored energy

In this case the controller does not attempt to save the state of the program when the external power fails The controller issues an alarm if a UPS was previously attached and ready to buffer

The letter F indicates the RTB terminal for this signal

Inhibit (I)

An output signal from the controller to the UPS that disables the UPS signal output The INHIBIT signal is triggered after data is backed up and the system is ready to shut down

The letter I indicates the RTB terminal for this signal

14 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the UPS Control RTBInstall the UPS control RTB even if you do not intend to connect uninterruptible power to the controller

1 Hook the bottom of the UPS power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect UPS Control Signals

1 Verify that all sources of MOD power and SA power are turned off

2 Verify the followingbull A 24V DC power supply is connected to the 24V IN

terminals on the UPSbull A 12V DC battery is connected to the 12V BAT terminals

on the UPS

For more information see the example graphic on page 17

Connect to the MOD Power RTB from a UPS

1 Daisy chain the wires from these connections on the UPSbull 24V OUT (+)bull Ready (1)bull Buffering (3)bull Battery Fail (5)bull Inhibit (7)

2 Connect one wire to each (+) terminal on the MOD power RTB as shown in the example graphic on page 17a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Daisy chain a wire that is connected to the 24V OUT (ndash) terminal on the UPS and a second wire

4 Connect one wire to each (ndash) terminal on the MOD power RTB a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

IMPORTANT The UPS terminal labels in this section represent the labels on

a 1606-XLS240-UPS power supply Your UPS terminals can be

labeled differently

5069-L4200ERMW

UPS Control RTB

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 15

CompactLogix 5480 Controllers

Connect to the UPS Control RTB from a UPS

1 Connect a wire from the Ready (2) connection on the UPS to the UPS Ready terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

2 Connect a wire from the Buffering (4) connection on the UPS to the Buffering terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Connect a wire from the Battery Fail (6) connection on the UPS to the Battery Fail terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

4 Connect a wire from the Inhibit (8) connection on the UPS to the Inhibit terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

16 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

This diagram shows a 1606-XLS240-UPS power supply battery that is connected to a CompactLogix 5480 controller

5069-L4200ERMW

UPS Ready

Buffering

Battery Fail

Inhibit

(7) Inhibit +

(8) Inhibit ndash

24V DC

Power

Supply

Ready

(1) (2)

+ ndash + ndash + ndash + ndash

N L PE

Buffering

(3) (4)

Battery Fail

(5) (6)

12V DC Battery

(for example 1606-XLSBATASSY1)

+ ndash

DC-UPS

(1606-XLS240-UPS)

24V

IN

12V

BAT

24V

OUT

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 17

CompactLogix 5480 Controllers

Disconnect Wires from the RTBsIf necessary complete these tasks to disconnect wires from any RTB on the controller

1 Turn the screwdriver counter-clockwise to open the terminal

2 Remove the wire

Install Compact 5000 IO ModulesComplete one of the following

bull If you do not use local Compact 5000 IO modules in the system proceed to Install the End Cap on page 18

bull If you use local Compact 5000 IO modules in the system install the modules to the right side of the controller

After the IO modules are installed install the end cap on the right side of the last IO module in the system For more information on how to install the end cap see page 18

For more information on how to install Compact 5000IO modules see the installation instructions available with each Compact 5000 IO module catalog number

Install the End CapYou must install an end cap on the right side of the last module in a CompactLogix 5480 system The end cap covers the exposed interconnections on the last module in the system If you do not install the end cap before powering the system equipment damage or injury from electric shock can result

If you do not intend to install Compact 5000 IO modules to the system before you turn on power to the controller install the end cap

1 Align the end cap with the interlocking pieces on the controller

2 Push the end cap toward the DIN rail until it locks into place

Power the System

After the end cap is installed on the last module in the system turn on power to the MOD power RTB and the SA power RTB

IMPORTANT Consider the following before you power the system

bull Make sure to remove the debris shield from the controller before power-up

bull As noted previously you must install working controller firmware to use the COS on the controller There are two ways to install working firmware The ways are described beginning on page 23

One of the methods to install working controller firmware

uses the SD card that ships with the controller

ndash If you intend to use the SD card to install working

controller firmware go to Use a Secure Digital Card

to Install Controller Firmware on page 24

Complete the steps described in that section apply

power to the controller and return to the next

section that is Set the Network Internet Protocol

(IP) Addresses on page 19

ndash If you do not intend to use the SD card to install

working controller firmware turn on the power now

and proceed to the next section

Top Interlocking

Pieces

End Cap

Bottom Interlocking

Pieces

18 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Set the Network Internet Protocol (IP) AddressesYou must set an IP address on Ethernet ports for the controller to operate on an EtherNetIP network via that port

Out-of-the-box the following applies to Ethernet ports A1 A2 and B1

bull The ports are DHCP-enabled and the IP address is set automatically via a DHCP server

If there is no DHCP server available to set the IP address you must set the IP address manually

bull If ports A1 and A2 are configured to use DLRLinear mode you set only one IP address that is used on both ports

bull Control ports must use unique subnets

When ports A1 and A2 are configured to use DLRLinear mode however they use the same subnet because they are configured as one port

You can use one of the following to set the IP address on the controller when it is in the out-of-the-box condition

bull DHCP server

bull BOOTP DHCP EtherNetIP Commissioning tool version 30200 or later

bull RSLinx Classic software version 41000 or later

bull FactoryTalk Linx software version 61000 or later

bull Logix Designer application version 320100 or later

For more information on how to set or change the IP address on a CompactLogix 5480 controller see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

Connect the Controller to an EtherNetIP Network

Use an RJ45 cable to connect the controller to an EtherNetIP network

1 If needed wire the RJ45 connector as shown

2 Connect RJ45 cables to the controller Ethernet ports

IMPORTANT Before you can connect a CompactLogix 5480 controller to an

EtherNetIP network you must first install the network and

its components

This section assumes that the EtherNetIP network is

installed

Connector Number

Color

1585J 8-pin Cables with Support for 101001000 Mbps

1585J 8-pin Cables with Support for 10100 Mbps

1585J 4-pin Cables with Support for 10100 Mbps

1WhiteOrange

BI_DA+ TxData +

2 Orange BI_DA- TxData -

3WhiteGreen

BI_DB+ Recv Data +

4 Blue BI_DC+ Unused mdash

5 WhiteBlue BI_DC- Unused mdash

6 Green BI_DB- Recv Data -

7WhiteBrown

BI_DD+ Unused mdash

8 Brown BI_DD- Unused mdash

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 19

CompactLogix 5480 Controllers

Remove and Replace the Controller

1 Turn off power to the MOD power and the SA power RTBs

2 If there are local Compact 5000 IO modules in the system remove them If not skip to step 3

3 Disconnect wires from the RTBs

For more information see Disconnect Wires from the RTBs on page 18

4 Pull the RTB handles to remove the RTBs

IMPORTANT When you remove MOD power from the controller you shut down

power to all modules in the CompactLogix 5480 system That is

all system-side is removed When you remove SA power from the

controller all field-side power that is provided by the controller is

removed If SA power that is provided via a 5069-FPD field

potential distributor the system does not lose SA power to the

right of the field potential distributor

In this case you must use a separate power source for the SA

power RTB on the field potential distributor

We strongly recommend that before you remove MOD power or

SA power that you take the appropriate actions to help prevent

unintended consequences that can result from a system power

shutdown

Despite the removal of power from SA RTBs on the controller or

field potential distributor the 5069-OB16 and 5069-OB16F

modules continue to receive field-side power The modules

receive power from an external power source that is connected to

the LA (+) and LA (ndash) module terminals

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

UPS Control RTB

MOD Power RTB

SA Power RTB

20 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

5 Remove all cables from the controller

6 Push down on the front of the DIN rail latches

A click indicates that the DIN rail latches are open

If the DIN rail latches fail to remain in the open position hold them down

7 Pull the controller off the DIN rail

8 Repeat the installation steps that are described beginning at Install the Controller onto the DIN Rail on page 9

9 Apply MOD power and if necessary SA power to the system

Replace the FansThe CompactLogix 5480 controller uses fans at the top and bottom of the controller to help maintain lower operating temperatures when the controller is operating

Fan use includes speed control and monitoring Faults indicate fan operating conditions as follows

bull Minor faults - Triggered when a fan is not operating at the requested speed or if a fan fails to operate at all

In your Logix Designer application project you can use the Minor Faults tab on the Controller Properties dialog box to monitor for these faults

bull Major fault - Triggered if both fans fail and the controller goes over the maximum operating temperature

In this case the controller stops operating

You can order replacement fans Replacement fans come in pairs The fans are unique by position and keyed to help make sure that you install the correct fan in each position

The fans are labeled Fan 1 - Top and Fan 2 - Bottom

Consider the following

bull We recommend that you replace the fans in pairs That is if you replace the one fan we recommend that you replace the other fan too

bull You can replace fans during controller operation The fans support removal and insertion under power

bull Do not remove both fans at once if the controller is operating That is remove a fan and install the replacement fan before you remove the other fan

Remove the Top Fan

1 Push up on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

TIP In your Logix Designer application project you can

use the Major Faults tab on the Controller

Properties dialog box to monitor for this fault

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

R

B

F

Open Position

IMPORTANT If you replace fans while the controller is operating

do not touch live voltage components

TIP If the hinges do not disengage when you push up on the front of the

fan then use a screwdriver as a pry tool

5069-L4200ERMW

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 21

CompactLogix 5480 Controllers

2 Pull the fan out of the slot at the top of the controller

Install the Top Replacement Fan

1 Insert the top replacement fan into the slot at the top of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push down on the top replacement fan until it clicks in place

Remove the Bottom Fan

1 Push the down on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

2 Pull the fan out of the slot at the bottom of the controller

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

TIP If the hinges do not disengage when you push down on the front of

the fan then use a screwdriver as a pry tool

5069-L4200ERMW

5069-L4200ERMW

22 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Bottom Replacement Fan

1 Insert the bottom replacement fan into the slot at the bottom of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push up on the bottom replacement fan until it clicks in place

Use the COS For Windows-based ComputingThe COS on a CompactLogix 5480 controller runs in parallel with the Logix control engine You are not required to use the COS

You can use the following methods to install working controller firmware when the controller is in the out-of-box state

bull ControlFLASHtrade or ControlFLASH Plustrade softwarebull Secure Digital (SD) card

Use a Flash Programming Tool to Install Controller FirmwareYou can use ControlFLASH and ControlFLASH Plus software to install controller firmware

The following requirements apply when you use ControlFLASH or ControlFLASH Plus to install working controller firmware

bull You must use one of the followingndash ControlFLASH software version 150100 or laterndash ControlFLASH Plus version 20000 or later

bull You must use a Linx-based software application with your flash programming toolndash With ControlFLASH software you can use RSLinx

Classic Lite RSLinx Classic RSLinx Enterprise or FactoryTalk Linx

ndash With ControlFLASH Plus software you must use FactoryTalk Linx

Minimum software versions apply with Linx-based software For more information on the minimum software version requirements see the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

5069-L4200ERMW

5069-L4200ERMW

IMPORTANT Before you can use the COS you must install working controller firmware The requirement applies even if you

are not using the controller for real-time control If you do not

install working controller firmware the COS does not start

In the out-of-box state the controller uses firmware revision

1xxx On a CompactLogix 5480 controller the minimum

working controller firmware is revision 32012

TIP We recommend that you connect your peripherals to the

ports that are dedicated to COS use before you install

controller firmware

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 23

CompactLogix 5480 Controllers

Download the Flash Programming Tool

ControlFLASH and ControlFLASH Plus software are available from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

Download the installation files and install the software

Download the Controller Firmware

After the flash programming tool is installed download the controller firmware from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

The initial download is a exe file You use the Rockwell Automation Download Manager to extract a dmk from the downloaded file

Install the Controller Firmware

To install the controller firmware via a flash programming tool you complete the following steps

1 To start the tool click StartgtAll ProgramsgtFlashing Programming ToolsgtControlFLASH or ControlFLASH Plus

2 Follow the prompts to complete the following stepsa Choose the controllerb Select the firmware revisionc Install the controller firmware

A dialog box confirms that the installation was successful

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use a flash programming tool to install controller firmware see the following

bull ControlFLASH Firmware Upgrade Kit User Manual publication 1756-UM105

bull ControlFLASH Plus Quick Start Guide publication CFP-QS001

bull CompactLogix 5480 Controllers User Manual publication 5069-UM002

Use a Secure Digital Card to Install Controller FirmwareYou can use an SD card to install controller firmware CompactLogix 5480 controllers ship with an SD card installed behind the front door on the controller

To use an SD card to install controller firmware complete the following steps

1 Before you turn on power to the controller remove the SD card from the controller

2 Install the SD card into another working CompactLogix 5480 controller that has a Logix Designer application project on it

3 Save the project to the SD card

4 Remove the SD card from the working controller and reinstall it in the new controller

5 Turn on power to the new controller

When the new controller powers up it automatically updates the firmware to the revision that is stored on the SD card

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use the SD card with the controller after valid firmware is installed and the controller is powered see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

IMPORTANT These steps only highlight the major tasks that you

complete to install controller firmware with ControlFLASH

To successfully install controller firmware you must complete other tasks that are not described here

For complete information on how to install controller

firmware see the publications listed at the end of the section

IMPORTANT To install controller firmware on a new CompactLogix 5480

controller via an SD card you must have another controller of

the same type that is already working

The SD card method requires that you save the Logix Designer

application project from the working controller to the SD card

before you use it in the new controller

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

SD Card Slot

24 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpecificationsThis table lists a subset of controller specifications For a complete list of specifications see the CompactLogix 5380 Compact GuardLogixreg 5380 and CompactLogix 5480 Controllers Specifications Technical Data publication 5069-TD002

Environmental Specifications - CompactLogix 5480 Controllers

Attribute 5069-L430ERMW 5069-L450ERMW 5069-4100ERMW 5069-L4200ERMW

Temperature operating

IEC 60068-2-1 (Test Ad Operating Cold)

IEC 60068-2-2 (Test Bd Operating Dry Heat)

IEC 60068-2-14 (Test Na Operating Thermal Shock)

0 degC lt Ta lt +60 degC

(+32 degF lt Ta lt +140 degF)

Temperature surrounding air max 60 degC (140 degF)

Enclosure Type Rating None (open-style)

Voltage and current ratings

MOD Power voltage range 18hellip32V DC

MOD Power power max 72 W

MOD Power current typical 4 A

MOD Power inrush 4 A for 15 ms

MOD Power Passthrough(1) 6 A 18hellip32V DC

MOD Power current rating max10 A

Do not exceed 10 A current draw at the MOD power RTB(4)

SA Power voltage ranges(2) 0hellip32V DC

0hellip240V AC 47hellip63 Hz

SA Power current max (2) 10 mA (DC power)

25 mA (AC power)

SA Power Passthrough(2) (3) 999 A 0hellip32V DC

9975 A 0hellip240V AC 47hellip63 Hz

SA Power current rating max(2) Do not exceed 10 A current draw at the SA power RTB

Isolation voltage

300V (continuous) Basic Insulation Type SA and MOD Power to Backplane

300V (continuous) Basic Insulation Type SA to MOD Power

300V (continuous) Basic Insulation Type Ethernet to Backplane

300V (continuous) Double Insulation Type Ethernet to MOD Power

300V (continuous) Double Insulation Type Ethernet to SA Power

50V (continuous) Functional Insulation Type Ethernet to USB ports and DisplayPort

300V (continuous) Basic Insulation Type USB ports and DisplayPort to Backplane

300V (continuous) Double Insulation Type USB ports and DisplayPort to MOD Power

300V (continuous) Double Insulation Type USB ports and DisplayPort to SA Power

No isolation between Ethernet ports

Type tested at 1500V AC for 60 s

Wire size

5069-RTB4-SCREW 5069-RTB6-SCREW connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 35 mm (014 in) max diameter including insulation single wire connection only

5069-RTB4-UPS connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 29 mm (011 in) max diameter including insulation single wire connection only

Ethernet connections

Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2

Insulation-stripping length 5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 12 mm (047 in)

Terminal block torque5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 04 Nbullm (35 lbbullin)

ATTENTION Do not wire more than two conductors on one RTB terminal

(1) Maximum level of MOD power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(2) SA power specifications are based on the number and type of Compact 5000 IO modules that are used in the system If the set of IO modules that is used in the system require AC and DC voltage you must install a 5069-FPD field

potential distributor to separate the module types

(3) Maximum level of SA power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(4) Remember MOD power usage includes the total power that the controller and local Compact 5000 IO modules use If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000 IO

modules can draw a maximum of 10 A in addition to the current that the controller draws

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 25

CompactLogix 5480 Controllers

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation

You can view or download publications at httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage To order paper copies of technical documentation contact your local Allen-Bradley distributor or Rockwell Automationreg sales representative

Resource Description

CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069-TD002

Provides specifications and other technical data for CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 controllers

CompactLogix 5480 Controllers User Manual publication 5069-UM002 Describes how to configure operate and monitor CompactLogix 5480 controllers

Industrial Automation Wiring and Grounding Guidelines publication 1770-41 Provides general guidelines for installing a Rockwell Automationreg industrial system

Product Certifications website rokautocertifications Provides declarations of conformity certificates and other certification details

26 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB ltFEFF005500740069006c0069007a006500200065007300730061007300200063006f006e00660069006700750072006100e700f50065007300200064006500200066006f0072006d00610020006100200063007200690061007200200064006f00630075006d0065006e0074006f0073002000410064006f0062006500200050004400460020007000610072006100200069006d0070007200650073007300f5006500730020006400650020007100750061006c0069006400610064006500200065006d00200069006d00700072006500730073006f0072006100730020006400650073006b0074006f00700020006500200064006900730070006f00730069007400690076006f0073002000640065002000700072006f00760061002e0020004f007300200064006f00630075006d0065006e0074006f00730020005000440046002000630072006900610064006f007300200070006f00640065006d0020007300650072002000610062006500720074006f007300200063006f006d0020006f0020004100630072006f006200610074002000650020006f002000410064006f00620065002000520065006100640065007200200035002e0030002000650020007600650072007300f50065007300200070006f00730074006500720069006f007200650073002egt SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 9: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

CompactLogix 5480 Controllers

Install the Controller onto the DIN Rail

1 Confirm that the DIN rail latches are closed

2 If the DIN rail latches are open gently push the rear latch back until the front latch pops up and clicks

3 Position the controller so that the back of it faces the DIN rail

4 Press the controller against the DIN rail until you hear a click

5 Confirm that all latches have fully closed and the controller is latched securely

Connect External Power Supplies to the ControllerBefore you connect MOD power or SA power to the RTBs on the CompactLogix 5480 controller complete the following tasks

bull Read System Power Considerations on page 8

bull Confirm that the external power supplies that MOD power and SA power are adequately sized for your CompactLogix 5480 system For more information see page 8

bull Verify that the external power supplies are turned off

bull Install the MOD power RTB SA power RTB and the UPS Control RTB if used

bull If IO modules are used verify that they are installed on the correct SA power bus

DC-type modules must reside on an SA power bus that uses DC power and AC-type modules must reside on an SA power bus that uses AC power

For more information see the technical documentation for Compact 5000 IO modules

IMPORTANT Remember the following

bull CompactLogix 5480 controllers do not have an embedded power supply that powers the system

The system is powered by external power supplies via

connections to the various power RTBs on the controller

bull We recommend that you use 1606 power supplies from Rockwell Automation to provide MOD power SA power and UPS control

bull You must use an external power supply that is dedicated to the UPS connection

For more information about which 1606 power supplies

are best for each power type see the Switched Mode

Power Supply Specifications Technical Data publication

1606-TD002

bull You can connect power from one external power supply to the MOD power and SA power RTBs However as stated previously we strongly recommend that you use separate external power supplies for MOD power and SA power respectively

The practice of using separate external power supplies can

help prevent unintended consequences that can result if

you use one supply

If you use separate external power supplies the loss of

power from one external power supply does not affect the

availability of power from the other supply For example if

separate external power supplies are used and SA power is

lost MOD power remains available for the Compact 5000

IO modules

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPSR

B

F

R

B

F

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPSR

B

F

R

B

F

Closed PositionOpen Position

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 9

CompactLogix 5480 Controllers

Install the MOD Power RTB

1 Hook the bottom of the MOD power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect MOD PowerThe way that you connect power to the MOD power RTB depends on whether you use UPS control signals or not

bull If you are not using UPS control signals you connect the external power supply directly to the MOD power RTB

In this case proceed to Connect to the MOD Power RTB from a Standard External Power Supply on page 10

bull If you are using UPS control signals you connect a UPS to the MOD power RTB

In this case proceed to Connect to the MOD Power RTB from a UPS on page 15

Connect to the MOD Power RTB from a Standard External Power Supply

Before you connect an external power source to the MOD power RTB make sure that the MOD power source is properly sized

1 Verify that the external power supply is not powered

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the 24V DC (+) connection on the external power supply into the first MOD (+) terminal on the RTB

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the 24V DC (mdash) connection on the external power supply into the first MOD (mdash) terminal on the RTB

5069-L4200ERMW

MOD Power RTB

IMPORTANT Your application can require a power control device for example

a switch between the external 24V DC power source and the

controller to control when the controller is powered If so you

must install the power control device at the VDC+ terminal on

the RTB

If you install the power control device at the VDC- terminal the

controller can fail to power up or power down properly

10 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

The following diagram shows an external 24V DC power supply that is connected to the MOD power RTB when you are not using UPS control signals

Install the SA Power RTBInstall the SA power RTB even if you do not use SA power

1 Hook the bottom of the SA power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect SA DC Power

Before you connect an external DC power source to the SA power RTB make sure that the SA power source is properly sized

For more information o n SA power see SA Power on page 8

1 Confirm that MOD power and SA power sources are turned off

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the DC (+) connection on the external power supply into the first SA (+) terminal on the RTB

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

24V DC

Power

Supply

+

ndashIMPORTANT SA power is only required if your application includes local

Compact 5000 IO modules that require SA power to operate

or are connected to field-side devices that are powered by

SA power

5069-L4200ERMW

SA Power RTB

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 11

CompactLogix 5480 Controllers

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the DC (mdash) connection on the external power supply into the first SA (mdash) terminal on the RTB

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

7 Insert the wire from an Earth Ground location into the first

Ground ( ) on the RTB

The Earth Ground location can be the external SA power supply the DIN rail or other Earth Ground location

8 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

The following diagram shows an external 24V DC power supply that is connected to the SA power RTB when you do not use UPS control signals

TIP

This symbol denotes a Functional Ground terminal that provides a

low impedance path between electric circuits and earth for functional

purposes and provides noise immunity improvement This connection

must be made for functional purposes

5069-L4200ERMW

24V DC

Power

Supply

+

ndash

24V DC

Power

Supply

+

ndash

MOD

Power

SA DC

Power

Functional Ground

12 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Connect SA AC Power

Before you connect an external AC power source to the SA power RTB make sure that the SA power source is properly sized

For more information o n SA power see SA Power on page 8

1 Verify that the SA power source is not powered on

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the L1AC (+) connection on the external power supply into the first SA (+) terminal on the RTB

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the L2NAC(mdash) connection on the external power supply into the first SA(mdash) terminal on the RTB

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

7 Insert the wire from an Earth Ground location into the first

Ground ( ) on the RTB

The Earth Ground location can be the external SA power supply the DIN rail or other Earth Ground location

8 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

This diagram shows an external 240V AC power supply that is connected to the SA power RTB when you do not use UPS control signals

IMPORTANT SA power is only required if your application includes local

Compact 5000 IO modules that require SA power to operate

or are connected to field-side devices that are powered by

SA power

TIP

This symbol denotes a Functional Ground terminal that provides a

low impedance path between electric circuits and earth for functional

purposes and provides noise immunity improvement This connection

must be made for functional purposes

5069-L4200ERMW

24V DC

Power

Supply

+

ndash

240V AC

Power

Supply

+

ndash

MOD

Power

SA AC

Power

Functional Ground

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 13

CompactLogix 5480 Controllers

Connect Control Signals Via UPS Control RTBThe CompactLogix 5480 controller does not have an internal energy storage module that lets the controller save the state of the program if system-side power is lost You must connect an external uninterruptible power supply (UPS) to the UPS control RTB to save the state of the program if power is lost

You connect control signals from an external power supply to the UPS control RTB to let the controller experience a controlled shutdown upon an incoming power loss

When a UPS connection is detected the CompactLogix 5480 controller defaults to initiate shutdown 1 minute after a power loss indication

We recommend that you use 1606 switched mode uninterruptible power supplies from Rockwell Automation with a CompactLogix 5480 controller for example the 1606-XLS240-UPS power supply

For more information on Bulletin 1606 uninterruptible power supplies see the following

bull Bulletin 1606 DC-UPS Uninterruptible Power Supply Installation Instructions publication 1606-IN025

bull Bulletin 1606 Switched Mode Power Supplies Reference Manual publication 1606-RM036

The switched mode uninterruptible power supplies use a 12-volt battery module to bridge power failures and voltage fluctuations We recommend that you use the 1606-XLSBATASSY1 battery module from Rockwell Automation

You can use other accessories such as replacement batteries mounting kits and panelwall mounting brackets with the battery module

For more information on and the battery module and accessories that you can use with them see the following

bull Bulletin 1606 12V 7Ah Battery Modules Installation Instructions publication 1606-IN011

bull Bulletin 1606 Switched Mode Power Supply Battery Modules (12V 7Ah) Reference Manual publication 1606-RM037

UPS Control SignalsThese control signals are used on the UPS Control RTB

UPS Control RTB Terminals

Signal Description

UPS Ready (R)

An input signal from the UPS to the controller that indicates the UPS is working and can buffer during a power failure

The charge level for a UPS to be ready to buffer during a power failure varies For example the 1606-XLS240-UPS power supply must be greater than 85 charged to be ready

The letter R indicates the RTB terminal for this signal

Buffering (B)

An input signal from the UPS to the controller that indicates the UPS battery is providing power because the external power has failed

After a preset time (typically 1 minute after power failure) the controller performs an orderly shutdown by stopping execution and saving the state of the controller

The letter B indicates the RTB terminal for this signal

Battery Fail (F)

An input from the UPS to the controller that indicates the UPS battery has failed and the controller cannot operate from stored energy

In this case the controller does not attempt to save the state of the program when the external power fails The controller issues an alarm if a UPS was previously attached and ready to buffer

The letter F indicates the RTB terminal for this signal

Inhibit (I)

An output signal from the controller to the UPS that disables the UPS signal output The INHIBIT signal is triggered after data is backed up and the system is ready to shut down

The letter I indicates the RTB terminal for this signal

14 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the UPS Control RTBInstall the UPS control RTB even if you do not intend to connect uninterruptible power to the controller

1 Hook the bottom of the UPS power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect UPS Control Signals

1 Verify that all sources of MOD power and SA power are turned off

2 Verify the followingbull A 24V DC power supply is connected to the 24V IN

terminals on the UPSbull A 12V DC battery is connected to the 12V BAT terminals

on the UPS

For more information see the example graphic on page 17

Connect to the MOD Power RTB from a UPS

1 Daisy chain the wires from these connections on the UPSbull 24V OUT (+)bull Ready (1)bull Buffering (3)bull Battery Fail (5)bull Inhibit (7)

2 Connect one wire to each (+) terminal on the MOD power RTB as shown in the example graphic on page 17a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Daisy chain a wire that is connected to the 24V OUT (ndash) terminal on the UPS and a second wire

4 Connect one wire to each (ndash) terminal on the MOD power RTB a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

IMPORTANT The UPS terminal labels in this section represent the labels on

a 1606-XLS240-UPS power supply Your UPS terminals can be

labeled differently

5069-L4200ERMW

UPS Control RTB

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 15

CompactLogix 5480 Controllers

Connect to the UPS Control RTB from a UPS

1 Connect a wire from the Ready (2) connection on the UPS to the UPS Ready terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

2 Connect a wire from the Buffering (4) connection on the UPS to the Buffering terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Connect a wire from the Battery Fail (6) connection on the UPS to the Battery Fail terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

4 Connect a wire from the Inhibit (8) connection on the UPS to the Inhibit terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

16 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

This diagram shows a 1606-XLS240-UPS power supply battery that is connected to a CompactLogix 5480 controller

5069-L4200ERMW

UPS Ready

Buffering

Battery Fail

Inhibit

(7) Inhibit +

(8) Inhibit ndash

24V DC

Power

Supply

Ready

(1) (2)

+ ndash + ndash + ndash + ndash

N L PE

Buffering

(3) (4)

Battery Fail

(5) (6)

12V DC Battery

(for example 1606-XLSBATASSY1)

+ ndash

DC-UPS

(1606-XLS240-UPS)

24V

IN

12V

BAT

24V

OUT

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 17

CompactLogix 5480 Controllers

Disconnect Wires from the RTBsIf necessary complete these tasks to disconnect wires from any RTB on the controller

1 Turn the screwdriver counter-clockwise to open the terminal

2 Remove the wire

Install Compact 5000 IO ModulesComplete one of the following

bull If you do not use local Compact 5000 IO modules in the system proceed to Install the End Cap on page 18

bull If you use local Compact 5000 IO modules in the system install the modules to the right side of the controller

After the IO modules are installed install the end cap on the right side of the last IO module in the system For more information on how to install the end cap see page 18

For more information on how to install Compact 5000IO modules see the installation instructions available with each Compact 5000 IO module catalog number

Install the End CapYou must install an end cap on the right side of the last module in a CompactLogix 5480 system The end cap covers the exposed interconnections on the last module in the system If you do not install the end cap before powering the system equipment damage or injury from electric shock can result

If you do not intend to install Compact 5000 IO modules to the system before you turn on power to the controller install the end cap

1 Align the end cap with the interlocking pieces on the controller

2 Push the end cap toward the DIN rail until it locks into place

Power the System

After the end cap is installed on the last module in the system turn on power to the MOD power RTB and the SA power RTB

IMPORTANT Consider the following before you power the system

bull Make sure to remove the debris shield from the controller before power-up

bull As noted previously you must install working controller firmware to use the COS on the controller There are two ways to install working firmware The ways are described beginning on page 23

One of the methods to install working controller firmware

uses the SD card that ships with the controller

ndash If you intend to use the SD card to install working

controller firmware go to Use a Secure Digital Card

to Install Controller Firmware on page 24

Complete the steps described in that section apply

power to the controller and return to the next

section that is Set the Network Internet Protocol

(IP) Addresses on page 19

ndash If you do not intend to use the SD card to install

working controller firmware turn on the power now

and proceed to the next section

Top Interlocking

Pieces

End Cap

Bottom Interlocking

Pieces

18 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Set the Network Internet Protocol (IP) AddressesYou must set an IP address on Ethernet ports for the controller to operate on an EtherNetIP network via that port

Out-of-the-box the following applies to Ethernet ports A1 A2 and B1

bull The ports are DHCP-enabled and the IP address is set automatically via a DHCP server

If there is no DHCP server available to set the IP address you must set the IP address manually

bull If ports A1 and A2 are configured to use DLRLinear mode you set only one IP address that is used on both ports

bull Control ports must use unique subnets

When ports A1 and A2 are configured to use DLRLinear mode however they use the same subnet because they are configured as one port

You can use one of the following to set the IP address on the controller when it is in the out-of-the-box condition

bull DHCP server

bull BOOTP DHCP EtherNetIP Commissioning tool version 30200 or later

bull RSLinx Classic software version 41000 or later

bull FactoryTalk Linx software version 61000 or later

bull Logix Designer application version 320100 or later

For more information on how to set or change the IP address on a CompactLogix 5480 controller see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

Connect the Controller to an EtherNetIP Network

Use an RJ45 cable to connect the controller to an EtherNetIP network

1 If needed wire the RJ45 connector as shown

2 Connect RJ45 cables to the controller Ethernet ports

IMPORTANT Before you can connect a CompactLogix 5480 controller to an

EtherNetIP network you must first install the network and

its components

This section assumes that the EtherNetIP network is

installed

Connector Number

Color

1585J 8-pin Cables with Support for 101001000 Mbps

1585J 8-pin Cables with Support for 10100 Mbps

1585J 4-pin Cables with Support for 10100 Mbps

1WhiteOrange

BI_DA+ TxData +

2 Orange BI_DA- TxData -

3WhiteGreen

BI_DB+ Recv Data +

4 Blue BI_DC+ Unused mdash

5 WhiteBlue BI_DC- Unused mdash

6 Green BI_DB- Recv Data -

7WhiteBrown

BI_DD+ Unused mdash

8 Brown BI_DD- Unused mdash

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 19

CompactLogix 5480 Controllers

Remove and Replace the Controller

1 Turn off power to the MOD power and the SA power RTBs

2 If there are local Compact 5000 IO modules in the system remove them If not skip to step 3

3 Disconnect wires from the RTBs

For more information see Disconnect Wires from the RTBs on page 18

4 Pull the RTB handles to remove the RTBs

IMPORTANT When you remove MOD power from the controller you shut down

power to all modules in the CompactLogix 5480 system That is

all system-side is removed When you remove SA power from the

controller all field-side power that is provided by the controller is

removed If SA power that is provided via a 5069-FPD field

potential distributor the system does not lose SA power to the

right of the field potential distributor

In this case you must use a separate power source for the SA

power RTB on the field potential distributor

We strongly recommend that before you remove MOD power or

SA power that you take the appropriate actions to help prevent

unintended consequences that can result from a system power

shutdown

Despite the removal of power from SA RTBs on the controller or

field potential distributor the 5069-OB16 and 5069-OB16F

modules continue to receive field-side power The modules

receive power from an external power source that is connected to

the LA (+) and LA (ndash) module terminals

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

UPS Control RTB

MOD Power RTB

SA Power RTB

20 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

5 Remove all cables from the controller

6 Push down on the front of the DIN rail latches

A click indicates that the DIN rail latches are open

If the DIN rail latches fail to remain in the open position hold them down

7 Pull the controller off the DIN rail

8 Repeat the installation steps that are described beginning at Install the Controller onto the DIN Rail on page 9

9 Apply MOD power and if necessary SA power to the system

Replace the FansThe CompactLogix 5480 controller uses fans at the top and bottom of the controller to help maintain lower operating temperatures when the controller is operating

Fan use includes speed control and monitoring Faults indicate fan operating conditions as follows

bull Minor faults - Triggered when a fan is not operating at the requested speed or if a fan fails to operate at all

In your Logix Designer application project you can use the Minor Faults tab on the Controller Properties dialog box to monitor for these faults

bull Major fault - Triggered if both fans fail and the controller goes over the maximum operating temperature

In this case the controller stops operating

You can order replacement fans Replacement fans come in pairs The fans are unique by position and keyed to help make sure that you install the correct fan in each position

The fans are labeled Fan 1 - Top and Fan 2 - Bottom

Consider the following

bull We recommend that you replace the fans in pairs That is if you replace the one fan we recommend that you replace the other fan too

bull You can replace fans during controller operation The fans support removal and insertion under power

bull Do not remove both fans at once if the controller is operating That is remove a fan and install the replacement fan before you remove the other fan

Remove the Top Fan

1 Push up on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

TIP In your Logix Designer application project you can

use the Major Faults tab on the Controller

Properties dialog box to monitor for this fault

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

R

B

F

Open Position

IMPORTANT If you replace fans while the controller is operating

do not touch live voltage components

TIP If the hinges do not disengage when you push up on the front of the

fan then use a screwdriver as a pry tool

5069-L4200ERMW

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 21

CompactLogix 5480 Controllers

2 Pull the fan out of the slot at the top of the controller

Install the Top Replacement Fan

1 Insert the top replacement fan into the slot at the top of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push down on the top replacement fan until it clicks in place

Remove the Bottom Fan

1 Push the down on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

2 Pull the fan out of the slot at the bottom of the controller

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

TIP If the hinges do not disengage when you push down on the front of

the fan then use a screwdriver as a pry tool

5069-L4200ERMW

5069-L4200ERMW

22 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Bottom Replacement Fan

1 Insert the bottom replacement fan into the slot at the bottom of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push up on the bottom replacement fan until it clicks in place

Use the COS For Windows-based ComputingThe COS on a CompactLogix 5480 controller runs in parallel with the Logix control engine You are not required to use the COS

You can use the following methods to install working controller firmware when the controller is in the out-of-box state

bull ControlFLASHtrade or ControlFLASH Plustrade softwarebull Secure Digital (SD) card

Use a Flash Programming Tool to Install Controller FirmwareYou can use ControlFLASH and ControlFLASH Plus software to install controller firmware

The following requirements apply when you use ControlFLASH or ControlFLASH Plus to install working controller firmware

bull You must use one of the followingndash ControlFLASH software version 150100 or laterndash ControlFLASH Plus version 20000 or later

bull You must use a Linx-based software application with your flash programming toolndash With ControlFLASH software you can use RSLinx

Classic Lite RSLinx Classic RSLinx Enterprise or FactoryTalk Linx

ndash With ControlFLASH Plus software you must use FactoryTalk Linx

Minimum software versions apply with Linx-based software For more information on the minimum software version requirements see the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

5069-L4200ERMW

5069-L4200ERMW

IMPORTANT Before you can use the COS you must install working controller firmware The requirement applies even if you

are not using the controller for real-time control If you do not

install working controller firmware the COS does not start

In the out-of-box state the controller uses firmware revision

1xxx On a CompactLogix 5480 controller the minimum

working controller firmware is revision 32012

TIP We recommend that you connect your peripherals to the

ports that are dedicated to COS use before you install

controller firmware

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 23

CompactLogix 5480 Controllers

Download the Flash Programming Tool

ControlFLASH and ControlFLASH Plus software are available from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

Download the installation files and install the software

Download the Controller Firmware

After the flash programming tool is installed download the controller firmware from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

The initial download is a exe file You use the Rockwell Automation Download Manager to extract a dmk from the downloaded file

Install the Controller Firmware

To install the controller firmware via a flash programming tool you complete the following steps

1 To start the tool click StartgtAll ProgramsgtFlashing Programming ToolsgtControlFLASH or ControlFLASH Plus

2 Follow the prompts to complete the following stepsa Choose the controllerb Select the firmware revisionc Install the controller firmware

A dialog box confirms that the installation was successful

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use a flash programming tool to install controller firmware see the following

bull ControlFLASH Firmware Upgrade Kit User Manual publication 1756-UM105

bull ControlFLASH Plus Quick Start Guide publication CFP-QS001

bull CompactLogix 5480 Controllers User Manual publication 5069-UM002

Use a Secure Digital Card to Install Controller FirmwareYou can use an SD card to install controller firmware CompactLogix 5480 controllers ship with an SD card installed behind the front door on the controller

To use an SD card to install controller firmware complete the following steps

1 Before you turn on power to the controller remove the SD card from the controller

2 Install the SD card into another working CompactLogix 5480 controller that has a Logix Designer application project on it

3 Save the project to the SD card

4 Remove the SD card from the working controller and reinstall it in the new controller

5 Turn on power to the new controller

When the new controller powers up it automatically updates the firmware to the revision that is stored on the SD card

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use the SD card with the controller after valid firmware is installed and the controller is powered see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

IMPORTANT These steps only highlight the major tasks that you

complete to install controller firmware with ControlFLASH

To successfully install controller firmware you must complete other tasks that are not described here

For complete information on how to install controller

firmware see the publications listed at the end of the section

IMPORTANT To install controller firmware on a new CompactLogix 5480

controller via an SD card you must have another controller of

the same type that is already working

The SD card method requires that you save the Logix Designer

application project from the working controller to the SD card

before you use it in the new controller

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

SD Card Slot

24 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpecificationsThis table lists a subset of controller specifications For a complete list of specifications see the CompactLogix 5380 Compact GuardLogixreg 5380 and CompactLogix 5480 Controllers Specifications Technical Data publication 5069-TD002

Environmental Specifications - CompactLogix 5480 Controllers

Attribute 5069-L430ERMW 5069-L450ERMW 5069-4100ERMW 5069-L4200ERMW

Temperature operating

IEC 60068-2-1 (Test Ad Operating Cold)

IEC 60068-2-2 (Test Bd Operating Dry Heat)

IEC 60068-2-14 (Test Na Operating Thermal Shock)

0 degC lt Ta lt +60 degC

(+32 degF lt Ta lt +140 degF)

Temperature surrounding air max 60 degC (140 degF)

Enclosure Type Rating None (open-style)

Voltage and current ratings

MOD Power voltage range 18hellip32V DC

MOD Power power max 72 W

MOD Power current typical 4 A

MOD Power inrush 4 A for 15 ms

MOD Power Passthrough(1) 6 A 18hellip32V DC

MOD Power current rating max10 A

Do not exceed 10 A current draw at the MOD power RTB(4)

SA Power voltage ranges(2) 0hellip32V DC

0hellip240V AC 47hellip63 Hz

SA Power current max (2) 10 mA (DC power)

25 mA (AC power)

SA Power Passthrough(2) (3) 999 A 0hellip32V DC

9975 A 0hellip240V AC 47hellip63 Hz

SA Power current rating max(2) Do not exceed 10 A current draw at the SA power RTB

Isolation voltage

300V (continuous) Basic Insulation Type SA and MOD Power to Backplane

300V (continuous) Basic Insulation Type SA to MOD Power

300V (continuous) Basic Insulation Type Ethernet to Backplane

300V (continuous) Double Insulation Type Ethernet to MOD Power

300V (continuous) Double Insulation Type Ethernet to SA Power

50V (continuous) Functional Insulation Type Ethernet to USB ports and DisplayPort

300V (continuous) Basic Insulation Type USB ports and DisplayPort to Backplane

300V (continuous) Double Insulation Type USB ports and DisplayPort to MOD Power

300V (continuous) Double Insulation Type USB ports and DisplayPort to SA Power

No isolation between Ethernet ports

Type tested at 1500V AC for 60 s

Wire size

5069-RTB4-SCREW 5069-RTB6-SCREW connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 35 mm (014 in) max diameter including insulation single wire connection only

5069-RTB4-UPS connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 29 mm (011 in) max diameter including insulation single wire connection only

Ethernet connections

Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2

Insulation-stripping length 5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 12 mm (047 in)

Terminal block torque5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 04 Nbullm (35 lbbullin)

ATTENTION Do not wire more than two conductors on one RTB terminal

(1) Maximum level of MOD power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(2) SA power specifications are based on the number and type of Compact 5000 IO modules that are used in the system If the set of IO modules that is used in the system require AC and DC voltage you must install a 5069-FPD field

potential distributor to separate the module types

(3) Maximum level of SA power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(4) Remember MOD power usage includes the total power that the controller and local Compact 5000 IO modules use If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000 IO

modules can draw a maximum of 10 A in addition to the current that the controller draws

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 25

CompactLogix 5480 Controllers

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation

You can view or download publications at httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage To order paper copies of technical documentation contact your local Allen-Bradley distributor or Rockwell Automationreg sales representative

Resource Description

CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069-TD002

Provides specifications and other technical data for CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 controllers

CompactLogix 5480 Controllers User Manual publication 5069-UM002 Describes how to configure operate and monitor CompactLogix 5480 controllers

Industrial Automation Wiring and Grounding Guidelines publication 1770-41 Provides general guidelines for installing a Rockwell Automationreg industrial system

Product Certifications website rokautocertifications Provides declarations of conformity certificates and other certification details

26 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 10: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

CompactLogix 5480 Controllers

Install the MOD Power RTB

1 Hook the bottom of the MOD power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect MOD PowerThe way that you connect power to the MOD power RTB depends on whether you use UPS control signals or not

bull If you are not using UPS control signals you connect the external power supply directly to the MOD power RTB

In this case proceed to Connect to the MOD Power RTB from a Standard External Power Supply on page 10

bull If you are using UPS control signals you connect a UPS to the MOD power RTB

In this case proceed to Connect to the MOD Power RTB from a UPS on page 15

Connect to the MOD Power RTB from a Standard External Power Supply

Before you connect an external power source to the MOD power RTB make sure that the MOD power source is properly sized

1 Verify that the external power supply is not powered

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the 24V DC (+) connection on the external power supply into the first MOD (+) terminal on the RTB

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the 24V DC (mdash) connection on the external power supply into the first MOD (mdash) terminal on the RTB

5069-L4200ERMW

MOD Power RTB

IMPORTANT Your application can require a power control device for example

a switch between the external 24V DC power source and the

controller to control when the controller is powered If so you

must install the power control device at the VDC+ terminal on

the RTB

If you install the power control device at the VDC- terminal the

controller can fail to power up or power down properly

10 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

The following diagram shows an external 24V DC power supply that is connected to the MOD power RTB when you are not using UPS control signals

Install the SA Power RTBInstall the SA power RTB even if you do not use SA power

1 Hook the bottom of the SA power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect SA DC Power

Before you connect an external DC power source to the SA power RTB make sure that the SA power source is properly sized

For more information o n SA power see SA Power on page 8

1 Confirm that MOD power and SA power sources are turned off

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the DC (+) connection on the external power supply into the first SA (+) terminal on the RTB

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

24V DC

Power

Supply

+

ndashIMPORTANT SA power is only required if your application includes local

Compact 5000 IO modules that require SA power to operate

or are connected to field-side devices that are powered by

SA power

5069-L4200ERMW

SA Power RTB

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 11

CompactLogix 5480 Controllers

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the DC (mdash) connection on the external power supply into the first SA (mdash) terminal on the RTB

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

7 Insert the wire from an Earth Ground location into the first

Ground ( ) on the RTB

The Earth Ground location can be the external SA power supply the DIN rail or other Earth Ground location

8 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

The following diagram shows an external 24V DC power supply that is connected to the SA power RTB when you do not use UPS control signals

TIP

This symbol denotes a Functional Ground terminal that provides a

low impedance path between electric circuits and earth for functional

purposes and provides noise immunity improvement This connection

must be made for functional purposes

5069-L4200ERMW

24V DC

Power

Supply

+

ndash

24V DC

Power

Supply

+

ndash

MOD

Power

SA DC

Power

Functional Ground

12 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Connect SA AC Power

Before you connect an external AC power source to the SA power RTB make sure that the SA power source is properly sized

For more information o n SA power see SA Power on page 8

1 Verify that the SA power source is not powered on

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the L1AC (+) connection on the external power supply into the first SA (+) terminal on the RTB

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the L2NAC(mdash) connection on the external power supply into the first SA(mdash) terminal on the RTB

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

7 Insert the wire from an Earth Ground location into the first

Ground ( ) on the RTB

The Earth Ground location can be the external SA power supply the DIN rail or other Earth Ground location

8 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

This diagram shows an external 240V AC power supply that is connected to the SA power RTB when you do not use UPS control signals

IMPORTANT SA power is only required if your application includes local

Compact 5000 IO modules that require SA power to operate

or are connected to field-side devices that are powered by

SA power

TIP

This symbol denotes a Functional Ground terminal that provides a

low impedance path between electric circuits and earth for functional

purposes and provides noise immunity improvement This connection

must be made for functional purposes

5069-L4200ERMW

24V DC

Power

Supply

+

ndash

240V AC

Power

Supply

+

ndash

MOD

Power

SA AC

Power

Functional Ground

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 13

CompactLogix 5480 Controllers

Connect Control Signals Via UPS Control RTBThe CompactLogix 5480 controller does not have an internal energy storage module that lets the controller save the state of the program if system-side power is lost You must connect an external uninterruptible power supply (UPS) to the UPS control RTB to save the state of the program if power is lost

You connect control signals from an external power supply to the UPS control RTB to let the controller experience a controlled shutdown upon an incoming power loss

When a UPS connection is detected the CompactLogix 5480 controller defaults to initiate shutdown 1 minute after a power loss indication

We recommend that you use 1606 switched mode uninterruptible power supplies from Rockwell Automation with a CompactLogix 5480 controller for example the 1606-XLS240-UPS power supply

For more information on Bulletin 1606 uninterruptible power supplies see the following

bull Bulletin 1606 DC-UPS Uninterruptible Power Supply Installation Instructions publication 1606-IN025

bull Bulletin 1606 Switched Mode Power Supplies Reference Manual publication 1606-RM036

The switched mode uninterruptible power supplies use a 12-volt battery module to bridge power failures and voltage fluctuations We recommend that you use the 1606-XLSBATASSY1 battery module from Rockwell Automation

You can use other accessories such as replacement batteries mounting kits and panelwall mounting brackets with the battery module

For more information on and the battery module and accessories that you can use with them see the following

bull Bulletin 1606 12V 7Ah Battery Modules Installation Instructions publication 1606-IN011

bull Bulletin 1606 Switched Mode Power Supply Battery Modules (12V 7Ah) Reference Manual publication 1606-RM037

UPS Control SignalsThese control signals are used on the UPS Control RTB

UPS Control RTB Terminals

Signal Description

UPS Ready (R)

An input signal from the UPS to the controller that indicates the UPS is working and can buffer during a power failure

The charge level for a UPS to be ready to buffer during a power failure varies For example the 1606-XLS240-UPS power supply must be greater than 85 charged to be ready

The letter R indicates the RTB terminal for this signal

Buffering (B)

An input signal from the UPS to the controller that indicates the UPS battery is providing power because the external power has failed

After a preset time (typically 1 minute after power failure) the controller performs an orderly shutdown by stopping execution and saving the state of the controller

The letter B indicates the RTB terminal for this signal

Battery Fail (F)

An input from the UPS to the controller that indicates the UPS battery has failed and the controller cannot operate from stored energy

In this case the controller does not attempt to save the state of the program when the external power fails The controller issues an alarm if a UPS was previously attached and ready to buffer

The letter F indicates the RTB terminal for this signal

Inhibit (I)

An output signal from the controller to the UPS that disables the UPS signal output The INHIBIT signal is triggered after data is backed up and the system is ready to shut down

The letter I indicates the RTB terminal for this signal

14 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the UPS Control RTBInstall the UPS control RTB even if you do not intend to connect uninterruptible power to the controller

1 Hook the bottom of the UPS power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect UPS Control Signals

1 Verify that all sources of MOD power and SA power are turned off

2 Verify the followingbull A 24V DC power supply is connected to the 24V IN

terminals on the UPSbull A 12V DC battery is connected to the 12V BAT terminals

on the UPS

For more information see the example graphic on page 17

Connect to the MOD Power RTB from a UPS

1 Daisy chain the wires from these connections on the UPSbull 24V OUT (+)bull Ready (1)bull Buffering (3)bull Battery Fail (5)bull Inhibit (7)

2 Connect one wire to each (+) terminal on the MOD power RTB as shown in the example graphic on page 17a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Daisy chain a wire that is connected to the 24V OUT (ndash) terminal on the UPS and a second wire

4 Connect one wire to each (ndash) terminal on the MOD power RTB a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

IMPORTANT The UPS terminal labels in this section represent the labels on

a 1606-XLS240-UPS power supply Your UPS terminals can be

labeled differently

5069-L4200ERMW

UPS Control RTB

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 15

CompactLogix 5480 Controllers

Connect to the UPS Control RTB from a UPS

1 Connect a wire from the Ready (2) connection on the UPS to the UPS Ready terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

2 Connect a wire from the Buffering (4) connection on the UPS to the Buffering terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Connect a wire from the Battery Fail (6) connection on the UPS to the Battery Fail terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

4 Connect a wire from the Inhibit (8) connection on the UPS to the Inhibit terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

16 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

This diagram shows a 1606-XLS240-UPS power supply battery that is connected to a CompactLogix 5480 controller

5069-L4200ERMW

UPS Ready

Buffering

Battery Fail

Inhibit

(7) Inhibit +

(8) Inhibit ndash

24V DC

Power

Supply

Ready

(1) (2)

+ ndash + ndash + ndash + ndash

N L PE

Buffering

(3) (4)

Battery Fail

(5) (6)

12V DC Battery

(for example 1606-XLSBATASSY1)

+ ndash

DC-UPS

(1606-XLS240-UPS)

24V

IN

12V

BAT

24V

OUT

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 17

CompactLogix 5480 Controllers

Disconnect Wires from the RTBsIf necessary complete these tasks to disconnect wires from any RTB on the controller

1 Turn the screwdriver counter-clockwise to open the terminal

2 Remove the wire

Install Compact 5000 IO ModulesComplete one of the following

bull If you do not use local Compact 5000 IO modules in the system proceed to Install the End Cap on page 18

bull If you use local Compact 5000 IO modules in the system install the modules to the right side of the controller

After the IO modules are installed install the end cap on the right side of the last IO module in the system For more information on how to install the end cap see page 18

For more information on how to install Compact 5000IO modules see the installation instructions available with each Compact 5000 IO module catalog number

Install the End CapYou must install an end cap on the right side of the last module in a CompactLogix 5480 system The end cap covers the exposed interconnections on the last module in the system If you do not install the end cap before powering the system equipment damage or injury from electric shock can result

If you do not intend to install Compact 5000 IO modules to the system before you turn on power to the controller install the end cap

1 Align the end cap with the interlocking pieces on the controller

2 Push the end cap toward the DIN rail until it locks into place

Power the System

After the end cap is installed on the last module in the system turn on power to the MOD power RTB and the SA power RTB

IMPORTANT Consider the following before you power the system

bull Make sure to remove the debris shield from the controller before power-up

bull As noted previously you must install working controller firmware to use the COS on the controller There are two ways to install working firmware The ways are described beginning on page 23

One of the methods to install working controller firmware

uses the SD card that ships with the controller

ndash If you intend to use the SD card to install working

controller firmware go to Use a Secure Digital Card

to Install Controller Firmware on page 24

Complete the steps described in that section apply

power to the controller and return to the next

section that is Set the Network Internet Protocol

(IP) Addresses on page 19

ndash If you do not intend to use the SD card to install

working controller firmware turn on the power now

and proceed to the next section

Top Interlocking

Pieces

End Cap

Bottom Interlocking

Pieces

18 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Set the Network Internet Protocol (IP) AddressesYou must set an IP address on Ethernet ports for the controller to operate on an EtherNetIP network via that port

Out-of-the-box the following applies to Ethernet ports A1 A2 and B1

bull The ports are DHCP-enabled and the IP address is set automatically via a DHCP server

If there is no DHCP server available to set the IP address you must set the IP address manually

bull If ports A1 and A2 are configured to use DLRLinear mode you set only one IP address that is used on both ports

bull Control ports must use unique subnets

When ports A1 and A2 are configured to use DLRLinear mode however they use the same subnet because they are configured as one port

You can use one of the following to set the IP address on the controller when it is in the out-of-the-box condition

bull DHCP server

bull BOOTP DHCP EtherNetIP Commissioning tool version 30200 or later

bull RSLinx Classic software version 41000 or later

bull FactoryTalk Linx software version 61000 or later

bull Logix Designer application version 320100 or later

For more information on how to set or change the IP address on a CompactLogix 5480 controller see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

Connect the Controller to an EtherNetIP Network

Use an RJ45 cable to connect the controller to an EtherNetIP network

1 If needed wire the RJ45 connector as shown

2 Connect RJ45 cables to the controller Ethernet ports

IMPORTANT Before you can connect a CompactLogix 5480 controller to an

EtherNetIP network you must first install the network and

its components

This section assumes that the EtherNetIP network is

installed

Connector Number

Color

1585J 8-pin Cables with Support for 101001000 Mbps

1585J 8-pin Cables with Support for 10100 Mbps

1585J 4-pin Cables with Support for 10100 Mbps

1WhiteOrange

BI_DA+ TxData +

2 Orange BI_DA- TxData -

3WhiteGreen

BI_DB+ Recv Data +

4 Blue BI_DC+ Unused mdash

5 WhiteBlue BI_DC- Unused mdash

6 Green BI_DB- Recv Data -

7WhiteBrown

BI_DD+ Unused mdash

8 Brown BI_DD- Unused mdash

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 19

CompactLogix 5480 Controllers

Remove and Replace the Controller

1 Turn off power to the MOD power and the SA power RTBs

2 If there are local Compact 5000 IO modules in the system remove them If not skip to step 3

3 Disconnect wires from the RTBs

For more information see Disconnect Wires from the RTBs on page 18

4 Pull the RTB handles to remove the RTBs

IMPORTANT When you remove MOD power from the controller you shut down

power to all modules in the CompactLogix 5480 system That is

all system-side is removed When you remove SA power from the

controller all field-side power that is provided by the controller is

removed If SA power that is provided via a 5069-FPD field

potential distributor the system does not lose SA power to the

right of the field potential distributor

In this case you must use a separate power source for the SA

power RTB on the field potential distributor

We strongly recommend that before you remove MOD power or

SA power that you take the appropriate actions to help prevent

unintended consequences that can result from a system power

shutdown

Despite the removal of power from SA RTBs on the controller or

field potential distributor the 5069-OB16 and 5069-OB16F

modules continue to receive field-side power The modules

receive power from an external power source that is connected to

the LA (+) and LA (ndash) module terminals

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

UPS Control RTB

MOD Power RTB

SA Power RTB

20 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

5 Remove all cables from the controller

6 Push down on the front of the DIN rail latches

A click indicates that the DIN rail latches are open

If the DIN rail latches fail to remain in the open position hold them down

7 Pull the controller off the DIN rail

8 Repeat the installation steps that are described beginning at Install the Controller onto the DIN Rail on page 9

9 Apply MOD power and if necessary SA power to the system

Replace the FansThe CompactLogix 5480 controller uses fans at the top and bottom of the controller to help maintain lower operating temperatures when the controller is operating

Fan use includes speed control and monitoring Faults indicate fan operating conditions as follows

bull Minor faults - Triggered when a fan is not operating at the requested speed or if a fan fails to operate at all

In your Logix Designer application project you can use the Minor Faults tab on the Controller Properties dialog box to monitor for these faults

bull Major fault - Triggered if both fans fail and the controller goes over the maximum operating temperature

In this case the controller stops operating

You can order replacement fans Replacement fans come in pairs The fans are unique by position and keyed to help make sure that you install the correct fan in each position

The fans are labeled Fan 1 - Top and Fan 2 - Bottom

Consider the following

bull We recommend that you replace the fans in pairs That is if you replace the one fan we recommend that you replace the other fan too

bull You can replace fans during controller operation The fans support removal and insertion under power

bull Do not remove both fans at once if the controller is operating That is remove a fan and install the replacement fan before you remove the other fan

Remove the Top Fan

1 Push up on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

TIP In your Logix Designer application project you can

use the Major Faults tab on the Controller

Properties dialog box to monitor for this fault

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

R

B

F

Open Position

IMPORTANT If you replace fans while the controller is operating

do not touch live voltage components

TIP If the hinges do not disengage when you push up on the front of the

fan then use a screwdriver as a pry tool

5069-L4200ERMW

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 21

CompactLogix 5480 Controllers

2 Pull the fan out of the slot at the top of the controller

Install the Top Replacement Fan

1 Insert the top replacement fan into the slot at the top of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push down on the top replacement fan until it clicks in place

Remove the Bottom Fan

1 Push the down on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

2 Pull the fan out of the slot at the bottom of the controller

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

TIP If the hinges do not disengage when you push down on the front of

the fan then use a screwdriver as a pry tool

5069-L4200ERMW

5069-L4200ERMW

22 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Bottom Replacement Fan

1 Insert the bottom replacement fan into the slot at the bottom of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push up on the bottom replacement fan until it clicks in place

Use the COS For Windows-based ComputingThe COS on a CompactLogix 5480 controller runs in parallel with the Logix control engine You are not required to use the COS

You can use the following methods to install working controller firmware when the controller is in the out-of-box state

bull ControlFLASHtrade or ControlFLASH Plustrade softwarebull Secure Digital (SD) card

Use a Flash Programming Tool to Install Controller FirmwareYou can use ControlFLASH and ControlFLASH Plus software to install controller firmware

The following requirements apply when you use ControlFLASH or ControlFLASH Plus to install working controller firmware

bull You must use one of the followingndash ControlFLASH software version 150100 or laterndash ControlFLASH Plus version 20000 or later

bull You must use a Linx-based software application with your flash programming toolndash With ControlFLASH software you can use RSLinx

Classic Lite RSLinx Classic RSLinx Enterprise or FactoryTalk Linx

ndash With ControlFLASH Plus software you must use FactoryTalk Linx

Minimum software versions apply with Linx-based software For more information on the minimum software version requirements see the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

5069-L4200ERMW

5069-L4200ERMW

IMPORTANT Before you can use the COS you must install working controller firmware The requirement applies even if you

are not using the controller for real-time control If you do not

install working controller firmware the COS does not start

In the out-of-box state the controller uses firmware revision

1xxx On a CompactLogix 5480 controller the minimum

working controller firmware is revision 32012

TIP We recommend that you connect your peripherals to the

ports that are dedicated to COS use before you install

controller firmware

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 23

CompactLogix 5480 Controllers

Download the Flash Programming Tool

ControlFLASH and ControlFLASH Plus software are available from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

Download the installation files and install the software

Download the Controller Firmware

After the flash programming tool is installed download the controller firmware from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

The initial download is a exe file You use the Rockwell Automation Download Manager to extract a dmk from the downloaded file

Install the Controller Firmware

To install the controller firmware via a flash programming tool you complete the following steps

1 To start the tool click StartgtAll ProgramsgtFlashing Programming ToolsgtControlFLASH or ControlFLASH Plus

2 Follow the prompts to complete the following stepsa Choose the controllerb Select the firmware revisionc Install the controller firmware

A dialog box confirms that the installation was successful

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use a flash programming tool to install controller firmware see the following

bull ControlFLASH Firmware Upgrade Kit User Manual publication 1756-UM105

bull ControlFLASH Plus Quick Start Guide publication CFP-QS001

bull CompactLogix 5480 Controllers User Manual publication 5069-UM002

Use a Secure Digital Card to Install Controller FirmwareYou can use an SD card to install controller firmware CompactLogix 5480 controllers ship with an SD card installed behind the front door on the controller

To use an SD card to install controller firmware complete the following steps

1 Before you turn on power to the controller remove the SD card from the controller

2 Install the SD card into another working CompactLogix 5480 controller that has a Logix Designer application project on it

3 Save the project to the SD card

4 Remove the SD card from the working controller and reinstall it in the new controller

5 Turn on power to the new controller

When the new controller powers up it automatically updates the firmware to the revision that is stored on the SD card

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use the SD card with the controller after valid firmware is installed and the controller is powered see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

IMPORTANT These steps only highlight the major tasks that you

complete to install controller firmware with ControlFLASH

To successfully install controller firmware you must complete other tasks that are not described here

For complete information on how to install controller

firmware see the publications listed at the end of the section

IMPORTANT To install controller firmware on a new CompactLogix 5480

controller via an SD card you must have another controller of

the same type that is already working

The SD card method requires that you save the Logix Designer

application project from the working controller to the SD card

before you use it in the new controller

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

SD Card Slot

24 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpecificationsThis table lists a subset of controller specifications For a complete list of specifications see the CompactLogix 5380 Compact GuardLogixreg 5380 and CompactLogix 5480 Controllers Specifications Technical Data publication 5069-TD002

Environmental Specifications - CompactLogix 5480 Controllers

Attribute 5069-L430ERMW 5069-L450ERMW 5069-4100ERMW 5069-L4200ERMW

Temperature operating

IEC 60068-2-1 (Test Ad Operating Cold)

IEC 60068-2-2 (Test Bd Operating Dry Heat)

IEC 60068-2-14 (Test Na Operating Thermal Shock)

0 degC lt Ta lt +60 degC

(+32 degF lt Ta lt +140 degF)

Temperature surrounding air max 60 degC (140 degF)

Enclosure Type Rating None (open-style)

Voltage and current ratings

MOD Power voltage range 18hellip32V DC

MOD Power power max 72 W

MOD Power current typical 4 A

MOD Power inrush 4 A for 15 ms

MOD Power Passthrough(1) 6 A 18hellip32V DC

MOD Power current rating max10 A

Do not exceed 10 A current draw at the MOD power RTB(4)

SA Power voltage ranges(2) 0hellip32V DC

0hellip240V AC 47hellip63 Hz

SA Power current max (2) 10 mA (DC power)

25 mA (AC power)

SA Power Passthrough(2) (3) 999 A 0hellip32V DC

9975 A 0hellip240V AC 47hellip63 Hz

SA Power current rating max(2) Do not exceed 10 A current draw at the SA power RTB

Isolation voltage

300V (continuous) Basic Insulation Type SA and MOD Power to Backplane

300V (continuous) Basic Insulation Type SA to MOD Power

300V (continuous) Basic Insulation Type Ethernet to Backplane

300V (continuous) Double Insulation Type Ethernet to MOD Power

300V (continuous) Double Insulation Type Ethernet to SA Power

50V (continuous) Functional Insulation Type Ethernet to USB ports and DisplayPort

300V (continuous) Basic Insulation Type USB ports and DisplayPort to Backplane

300V (continuous) Double Insulation Type USB ports and DisplayPort to MOD Power

300V (continuous) Double Insulation Type USB ports and DisplayPort to SA Power

No isolation between Ethernet ports

Type tested at 1500V AC for 60 s

Wire size

5069-RTB4-SCREW 5069-RTB6-SCREW connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 35 mm (014 in) max diameter including insulation single wire connection only

5069-RTB4-UPS connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 29 mm (011 in) max diameter including insulation single wire connection only

Ethernet connections

Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2

Insulation-stripping length 5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 12 mm (047 in)

Terminal block torque5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 04 Nbullm (35 lbbullin)

ATTENTION Do not wire more than two conductors on one RTB terminal

(1) Maximum level of MOD power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(2) SA power specifications are based on the number and type of Compact 5000 IO modules that are used in the system If the set of IO modules that is used in the system require AC and DC voltage you must install a 5069-FPD field

potential distributor to separate the module types

(3) Maximum level of SA power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(4) Remember MOD power usage includes the total power that the controller and local Compact 5000 IO modules use If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000 IO

modules can draw a maximum of 10 A in addition to the current that the controller draws

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 25

CompactLogix 5480 Controllers

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation

You can view or download publications at httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage To order paper copies of technical documentation contact your local Allen-Bradley distributor or Rockwell Automationreg sales representative

Resource Description

CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069-TD002

Provides specifications and other technical data for CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 controllers

CompactLogix 5480 Controllers User Manual publication 5069-UM002 Describes how to configure operate and monitor CompactLogix 5480 controllers

Industrial Automation Wiring and Grounding Guidelines publication 1770-41 Provides general guidelines for installing a Rockwell Automationreg industrial system

Product Certifications website rokautocertifications Provides declarations of conformity certificates and other certification details

26 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 11: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

CompactLogix 5480 Controllers

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

The following diagram shows an external 24V DC power supply that is connected to the MOD power RTB when you are not using UPS control signals

Install the SA Power RTBInstall the SA power RTB even if you do not use SA power

1 Hook the bottom of the SA power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect SA DC Power

Before you connect an external DC power source to the SA power RTB make sure that the SA power source is properly sized

For more information o n SA power see SA Power on page 8

1 Confirm that MOD power and SA power sources are turned off

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the DC (+) connection on the external power supply into the first SA (+) terminal on the RTB

trade

NET B1

LINK B1

NET A1

LINK A1

NET A2

LINK A2

SPEED X1

LINK X1

OK

RUN

FORCE

FAN 1

SD

FAN 2

CompactLogix 5480

5069-L4200ERMW

CONTROLLER

UPS

MP

SA

R

B

F

R

B

F

24V DC

Power

Supply

+

ndashIMPORTANT SA power is only required if your application includes local

Compact 5000 IO modules that require SA power to operate

or are connected to field-side devices that are powered by

SA power

5069-L4200ERMW

SA Power RTB

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 11

CompactLogix 5480 Controllers

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the DC (mdash) connection on the external power supply into the first SA (mdash) terminal on the RTB

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

7 Insert the wire from an Earth Ground location into the first

Ground ( ) on the RTB

The Earth Ground location can be the external SA power supply the DIN rail or other Earth Ground location

8 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

The following diagram shows an external 24V DC power supply that is connected to the SA power RTB when you do not use UPS control signals

TIP

This symbol denotes a Functional Ground terminal that provides a

low impedance path between electric circuits and earth for functional

purposes and provides noise immunity improvement This connection

must be made for functional purposes

5069-L4200ERMW

24V DC

Power

Supply

+

ndash

24V DC

Power

Supply

+

ndash

MOD

Power

SA DC

Power

Functional Ground

12 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Connect SA AC Power

Before you connect an external AC power source to the SA power RTB make sure that the SA power source is properly sized

For more information o n SA power see SA Power on page 8

1 Verify that the SA power source is not powered on

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the L1AC (+) connection on the external power supply into the first SA (+) terminal on the RTB

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the L2NAC(mdash) connection on the external power supply into the first SA(mdash) terminal on the RTB

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

7 Insert the wire from an Earth Ground location into the first

Ground ( ) on the RTB

The Earth Ground location can be the external SA power supply the DIN rail or other Earth Ground location

8 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

This diagram shows an external 240V AC power supply that is connected to the SA power RTB when you do not use UPS control signals

IMPORTANT SA power is only required if your application includes local

Compact 5000 IO modules that require SA power to operate

or are connected to field-side devices that are powered by

SA power

TIP

This symbol denotes a Functional Ground terminal that provides a

low impedance path between electric circuits and earth for functional

purposes and provides noise immunity improvement This connection

must be made for functional purposes

5069-L4200ERMW

24V DC

Power

Supply

+

ndash

240V AC

Power

Supply

+

ndash

MOD

Power

SA AC

Power

Functional Ground

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 13

CompactLogix 5480 Controllers

Connect Control Signals Via UPS Control RTBThe CompactLogix 5480 controller does not have an internal energy storage module that lets the controller save the state of the program if system-side power is lost You must connect an external uninterruptible power supply (UPS) to the UPS control RTB to save the state of the program if power is lost

You connect control signals from an external power supply to the UPS control RTB to let the controller experience a controlled shutdown upon an incoming power loss

When a UPS connection is detected the CompactLogix 5480 controller defaults to initiate shutdown 1 minute after a power loss indication

We recommend that you use 1606 switched mode uninterruptible power supplies from Rockwell Automation with a CompactLogix 5480 controller for example the 1606-XLS240-UPS power supply

For more information on Bulletin 1606 uninterruptible power supplies see the following

bull Bulletin 1606 DC-UPS Uninterruptible Power Supply Installation Instructions publication 1606-IN025

bull Bulletin 1606 Switched Mode Power Supplies Reference Manual publication 1606-RM036

The switched mode uninterruptible power supplies use a 12-volt battery module to bridge power failures and voltage fluctuations We recommend that you use the 1606-XLSBATASSY1 battery module from Rockwell Automation

You can use other accessories such as replacement batteries mounting kits and panelwall mounting brackets with the battery module

For more information on and the battery module and accessories that you can use with them see the following

bull Bulletin 1606 12V 7Ah Battery Modules Installation Instructions publication 1606-IN011

bull Bulletin 1606 Switched Mode Power Supply Battery Modules (12V 7Ah) Reference Manual publication 1606-RM037

UPS Control SignalsThese control signals are used on the UPS Control RTB

UPS Control RTB Terminals

Signal Description

UPS Ready (R)

An input signal from the UPS to the controller that indicates the UPS is working and can buffer during a power failure

The charge level for a UPS to be ready to buffer during a power failure varies For example the 1606-XLS240-UPS power supply must be greater than 85 charged to be ready

The letter R indicates the RTB terminal for this signal

Buffering (B)

An input signal from the UPS to the controller that indicates the UPS battery is providing power because the external power has failed

After a preset time (typically 1 minute after power failure) the controller performs an orderly shutdown by stopping execution and saving the state of the controller

The letter B indicates the RTB terminal for this signal

Battery Fail (F)

An input from the UPS to the controller that indicates the UPS battery has failed and the controller cannot operate from stored energy

In this case the controller does not attempt to save the state of the program when the external power fails The controller issues an alarm if a UPS was previously attached and ready to buffer

The letter F indicates the RTB terminal for this signal

Inhibit (I)

An output signal from the controller to the UPS that disables the UPS signal output The INHIBIT signal is triggered after data is backed up and the system is ready to shut down

The letter I indicates the RTB terminal for this signal

14 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the UPS Control RTBInstall the UPS control RTB even if you do not intend to connect uninterruptible power to the controller

1 Hook the bottom of the UPS power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect UPS Control Signals

1 Verify that all sources of MOD power and SA power are turned off

2 Verify the followingbull A 24V DC power supply is connected to the 24V IN

terminals on the UPSbull A 12V DC battery is connected to the 12V BAT terminals

on the UPS

For more information see the example graphic on page 17

Connect to the MOD Power RTB from a UPS

1 Daisy chain the wires from these connections on the UPSbull 24V OUT (+)bull Ready (1)bull Buffering (3)bull Battery Fail (5)bull Inhibit (7)

2 Connect one wire to each (+) terminal on the MOD power RTB as shown in the example graphic on page 17a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Daisy chain a wire that is connected to the 24V OUT (ndash) terminal on the UPS and a second wire

4 Connect one wire to each (ndash) terminal on the MOD power RTB a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

IMPORTANT The UPS terminal labels in this section represent the labels on

a 1606-XLS240-UPS power supply Your UPS terminals can be

labeled differently

5069-L4200ERMW

UPS Control RTB

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 15

CompactLogix 5480 Controllers

Connect to the UPS Control RTB from a UPS

1 Connect a wire from the Ready (2) connection on the UPS to the UPS Ready terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

2 Connect a wire from the Buffering (4) connection on the UPS to the Buffering terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Connect a wire from the Battery Fail (6) connection on the UPS to the Battery Fail terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

4 Connect a wire from the Inhibit (8) connection on the UPS to the Inhibit terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

16 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

This diagram shows a 1606-XLS240-UPS power supply battery that is connected to a CompactLogix 5480 controller

5069-L4200ERMW

UPS Ready

Buffering

Battery Fail

Inhibit

(7) Inhibit +

(8) Inhibit ndash

24V DC

Power

Supply

Ready

(1) (2)

+ ndash + ndash + ndash + ndash

N L PE

Buffering

(3) (4)

Battery Fail

(5) (6)

12V DC Battery

(for example 1606-XLSBATASSY1)

+ ndash

DC-UPS

(1606-XLS240-UPS)

24V

IN

12V

BAT

24V

OUT

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 17

CompactLogix 5480 Controllers

Disconnect Wires from the RTBsIf necessary complete these tasks to disconnect wires from any RTB on the controller

1 Turn the screwdriver counter-clockwise to open the terminal

2 Remove the wire

Install Compact 5000 IO ModulesComplete one of the following

bull If you do not use local Compact 5000 IO modules in the system proceed to Install the End Cap on page 18

bull If you use local Compact 5000 IO modules in the system install the modules to the right side of the controller

After the IO modules are installed install the end cap on the right side of the last IO module in the system For more information on how to install the end cap see page 18

For more information on how to install Compact 5000IO modules see the installation instructions available with each Compact 5000 IO module catalog number

Install the End CapYou must install an end cap on the right side of the last module in a CompactLogix 5480 system The end cap covers the exposed interconnections on the last module in the system If you do not install the end cap before powering the system equipment damage or injury from electric shock can result

If you do not intend to install Compact 5000 IO modules to the system before you turn on power to the controller install the end cap

1 Align the end cap with the interlocking pieces on the controller

2 Push the end cap toward the DIN rail until it locks into place

Power the System

After the end cap is installed on the last module in the system turn on power to the MOD power RTB and the SA power RTB

IMPORTANT Consider the following before you power the system

bull Make sure to remove the debris shield from the controller before power-up

bull As noted previously you must install working controller firmware to use the COS on the controller There are two ways to install working firmware The ways are described beginning on page 23

One of the methods to install working controller firmware

uses the SD card that ships with the controller

ndash If you intend to use the SD card to install working

controller firmware go to Use a Secure Digital Card

to Install Controller Firmware on page 24

Complete the steps described in that section apply

power to the controller and return to the next

section that is Set the Network Internet Protocol

(IP) Addresses on page 19

ndash If you do not intend to use the SD card to install

working controller firmware turn on the power now

and proceed to the next section

Top Interlocking

Pieces

End Cap

Bottom Interlocking

Pieces

18 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Set the Network Internet Protocol (IP) AddressesYou must set an IP address on Ethernet ports for the controller to operate on an EtherNetIP network via that port

Out-of-the-box the following applies to Ethernet ports A1 A2 and B1

bull The ports are DHCP-enabled and the IP address is set automatically via a DHCP server

If there is no DHCP server available to set the IP address you must set the IP address manually

bull If ports A1 and A2 are configured to use DLRLinear mode you set only one IP address that is used on both ports

bull Control ports must use unique subnets

When ports A1 and A2 are configured to use DLRLinear mode however they use the same subnet because they are configured as one port

You can use one of the following to set the IP address on the controller when it is in the out-of-the-box condition

bull DHCP server

bull BOOTP DHCP EtherNetIP Commissioning tool version 30200 or later

bull RSLinx Classic software version 41000 or later

bull FactoryTalk Linx software version 61000 or later

bull Logix Designer application version 320100 or later

For more information on how to set or change the IP address on a CompactLogix 5480 controller see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

Connect the Controller to an EtherNetIP Network

Use an RJ45 cable to connect the controller to an EtherNetIP network

1 If needed wire the RJ45 connector as shown

2 Connect RJ45 cables to the controller Ethernet ports

IMPORTANT Before you can connect a CompactLogix 5480 controller to an

EtherNetIP network you must first install the network and

its components

This section assumes that the EtherNetIP network is

installed

Connector Number

Color

1585J 8-pin Cables with Support for 101001000 Mbps

1585J 8-pin Cables with Support for 10100 Mbps

1585J 4-pin Cables with Support for 10100 Mbps

1WhiteOrange

BI_DA+ TxData +

2 Orange BI_DA- TxData -

3WhiteGreen

BI_DB+ Recv Data +

4 Blue BI_DC+ Unused mdash

5 WhiteBlue BI_DC- Unused mdash

6 Green BI_DB- Recv Data -

7WhiteBrown

BI_DD+ Unused mdash

8 Brown BI_DD- Unused mdash

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 19

CompactLogix 5480 Controllers

Remove and Replace the Controller

1 Turn off power to the MOD power and the SA power RTBs

2 If there are local Compact 5000 IO modules in the system remove them If not skip to step 3

3 Disconnect wires from the RTBs

For more information see Disconnect Wires from the RTBs on page 18

4 Pull the RTB handles to remove the RTBs

IMPORTANT When you remove MOD power from the controller you shut down

power to all modules in the CompactLogix 5480 system That is

all system-side is removed When you remove SA power from the

controller all field-side power that is provided by the controller is

removed If SA power that is provided via a 5069-FPD field

potential distributor the system does not lose SA power to the

right of the field potential distributor

In this case you must use a separate power source for the SA

power RTB on the field potential distributor

We strongly recommend that before you remove MOD power or

SA power that you take the appropriate actions to help prevent

unintended consequences that can result from a system power

shutdown

Despite the removal of power from SA RTBs on the controller or

field potential distributor the 5069-OB16 and 5069-OB16F

modules continue to receive field-side power The modules

receive power from an external power source that is connected to

the LA (+) and LA (ndash) module terminals

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

UPS Control RTB

MOD Power RTB

SA Power RTB

20 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

5 Remove all cables from the controller

6 Push down on the front of the DIN rail latches

A click indicates that the DIN rail latches are open

If the DIN rail latches fail to remain in the open position hold them down

7 Pull the controller off the DIN rail

8 Repeat the installation steps that are described beginning at Install the Controller onto the DIN Rail on page 9

9 Apply MOD power and if necessary SA power to the system

Replace the FansThe CompactLogix 5480 controller uses fans at the top and bottom of the controller to help maintain lower operating temperatures when the controller is operating

Fan use includes speed control and monitoring Faults indicate fan operating conditions as follows

bull Minor faults - Triggered when a fan is not operating at the requested speed or if a fan fails to operate at all

In your Logix Designer application project you can use the Minor Faults tab on the Controller Properties dialog box to monitor for these faults

bull Major fault - Triggered if both fans fail and the controller goes over the maximum operating temperature

In this case the controller stops operating

You can order replacement fans Replacement fans come in pairs The fans are unique by position and keyed to help make sure that you install the correct fan in each position

The fans are labeled Fan 1 - Top and Fan 2 - Bottom

Consider the following

bull We recommend that you replace the fans in pairs That is if you replace the one fan we recommend that you replace the other fan too

bull You can replace fans during controller operation The fans support removal and insertion under power

bull Do not remove both fans at once if the controller is operating That is remove a fan and install the replacement fan before you remove the other fan

Remove the Top Fan

1 Push up on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

TIP In your Logix Designer application project you can

use the Major Faults tab on the Controller

Properties dialog box to monitor for this fault

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

R

B

F

Open Position

IMPORTANT If you replace fans while the controller is operating

do not touch live voltage components

TIP If the hinges do not disengage when you push up on the front of the

fan then use a screwdriver as a pry tool

5069-L4200ERMW

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 21

CompactLogix 5480 Controllers

2 Pull the fan out of the slot at the top of the controller

Install the Top Replacement Fan

1 Insert the top replacement fan into the slot at the top of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push down on the top replacement fan until it clicks in place

Remove the Bottom Fan

1 Push the down on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

2 Pull the fan out of the slot at the bottom of the controller

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

TIP If the hinges do not disengage when you push down on the front of

the fan then use a screwdriver as a pry tool

5069-L4200ERMW

5069-L4200ERMW

22 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Bottom Replacement Fan

1 Insert the bottom replacement fan into the slot at the bottom of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push up on the bottom replacement fan until it clicks in place

Use the COS For Windows-based ComputingThe COS on a CompactLogix 5480 controller runs in parallel with the Logix control engine You are not required to use the COS

You can use the following methods to install working controller firmware when the controller is in the out-of-box state

bull ControlFLASHtrade or ControlFLASH Plustrade softwarebull Secure Digital (SD) card

Use a Flash Programming Tool to Install Controller FirmwareYou can use ControlFLASH and ControlFLASH Plus software to install controller firmware

The following requirements apply when you use ControlFLASH or ControlFLASH Plus to install working controller firmware

bull You must use one of the followingndash ControlFLASH software version 150100 or laterndash ControlFLASH Plus version 20000 or later

bull You must use a Linx-based software application with your flash programming toolndash With ControlFLASH software you can use RSLinx

Classic Lite RSLinx Classic RSLinx Enterprise or FactoryTalk Linx

ndash With ControlFLASH Plus software you must use FactoryTalk Linx

Minimum software versions apply with Linx-based software For more information on the minimum software version requirements see the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

5069-L4200ERMW

5069-L4200ERMW

IMPORTANT Before you can use the COS you must install working controller firmware The requirement applies even if you

are not using the controller for real-time control If you do not

install working controller firmware the COS does not start

In the out-of-box state the controller uses firmware revision

1xxx On a CompactLogix 5480 controller the minimum

working controller firmware is revision 32012

TIP We recommend that you connect your peripherals to the

ports that are dedicated to COS use before you install

controller firmware

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 23

CompactLogix 5480 Controllers

Download the Flash Programming Tool

ControlFLASH and ControlFLASH Plus software are available from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

Download the installation files and install the software

Download the Controller Firmware

After the flash programming tool is installed download the controller firmware from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

The initial download is a exe file You use the Rockwell Automation Download Manager to extract a dmk from the downloaded file

Install the Controller Firmware

To install the controller firmware via a flash programming tool you complete the following steps

1 To start the tool click StartgtAll ProgramsgtFlashing Programming ToolsgtControlFLASH or ControlFLASH Plus

2 Follow the prompts to complete the following stepsa Choose the controllerb Select the firmware revisionc Install the controller firmware

A dialog box confirms that the installation was successful

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use a flash programming tool to install controller firmware see the following

bull ControlFLASH Firmware Upgrade Kit User Manual publication 1756-UM105

bull ControlFLASH Plus Quick Start Guide publication CFP-QS001

bull CompactLogix 5480 Controllers User Manual publication 5069-UM002

Use a Secure Digital Card to Install Controller FirmwareYou can use an SD card to install controller firmware CompactLogix 5480 controllers ship with an SD card installed behind the front door on the controller

To use an SD card to install controller firmware complete the following steps

1 Before you turn on power to the controller remove the SD card from the controller

2 Install the SD card into another working CompactLogix 5480 controller that has a Logix Designer application project on it

3 Save the project to the SD card

4 Remove the SD card from the working controller and reinstall it in the new controller

5 Turn on power to the new controller

When the new controller powers up it automatically updates the firmware to the revision that is stored on the SD card

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use the SD card with the controller after valid firmware is installed and the controller is powered see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

IMPORTANT These steps only highlight the major tasks that you

complete to install controller firmware with ControlFLASH

To successfully install controller firmware you must complete other tasks that are not described here

For complete information on how to install controller

firmware see the publications listed at the end of the section

IMPORTANT To install controller firmware on a new CompactLogix 5480

controller via an SD card you must have another controller of

the same type that is already working

The SD card method requires that you save the Logix Designer

application project from the working controller to the SD card

before you use it in the new controller

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

SD Card Slot

24 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpecificationsThis table lists a subset of controller specifications For a complete list of specifications see the CompactLogix 5380 Compact GuardLogixreg 5380 and CompactLogix 5480 Controllers Specifications Technical Data publication 5069-TD002

Environmental Specifications - CompactLogix 5480 Controllers

Attribute 5069-L430ERMW 5069-L450ERMW 5069-4100ERMW 5069-L4200ERMW

Temperature operating

IEC 60068-2-1 (Test Ad Operating Cold)

IEC 60068-2-2 (Test Bd Operating Dry Heat)

IEC 60068-2-14 (Test Na Operating Thermal Shock)

0 degC lt Ta lt +60 degC

(+32 degF lt Ta lt +140 degF)

Temperature surrounding air max 60 degC (140 degF)

Enclosure Type Rating None (open-style)

Voltage and current ratings

MOD Power voltage range 18hellip32V DC

MOD Power power max 72 W

MOD Power current typical 4 A

MOD Power inrush 4 A for 15 ms

MOD Power Passthrough(1) 6 A 18hellip32V DC

MOD Power current rating max10 A

Do not exceed 10 A current draw at the MOD power RTB(4)

SA Power voltage ranges(2) 0hellip32V DC

0hellip240V AC 47hellip63 Hz

SA Power current max (2) 10 mA (DC power)

25 mA (AC power)

SA Power Passthrough(2) (3) 999 A 0hellip32V DC

9975 A 0hellip240V AC 47hellip63 Hz

SA Power current rating max(2) Do not exceed 10 A current draw at the SA power RTB

Isolation voltage

300V (continuous) Basic Insulation Type SA and MOD Power to Backplane

300V (continuous) Basic Insulation Type SA to MOD Power

300V (continuous) Basic Insulation Type Ethernet to Backplane

300V (continuous) Double Insulation Type Ethernet to MOD Power

300V (continuous) Double Insulation Type Ethernet to SA Power

50V (continuous) Functional Insulation Type Ethernet to USB ports and DisplayPort

300V (continuous) Basic Insulation Type USB ports and DisplayPort to Backplane

300V (continuous) Double Insulation Type USB ports and DisplayPort to MOD Power

300V (continuous) Double Insulation Type USB ports and DisplayPort to SA Power

No isolation between Ethernet ports

Type tested at 1500V AC for 60 s

Wire size

5069-RTB4-SCREW 5069-RTB6-SCREW connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 35 mm (014 in) max diameter including insulation single wire connection only

5069-RTB4-UPS connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 29 mm (011 in) max diameter including insulation single wire connection only

Ethernet connections

Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2

Insulation-stripping length 5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 12 mm (047 in)

Terminal block torque5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 04 Nbullm (35 lbbullin)

ATTENTION Do not wire more than two conductors on one RTB terminal

(1) Maximum level of MOD power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(2) SA power specifications are based on the number and type of Compact 5000 IO modules that are used in the system If the set of IO modules that is used in the system require AC and DC voltage you must install a 5069-FPD field

potential distributor to separate the module types

(3) Maximum level of SA power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(4) Remember MOD power usage includes the total power that the controller and local Compact 5000 IO modules use If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000 IO

modules can draw a maximum of 10 A in addition to the current that the controller draws

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 25

CompactLogix 5480 Controllers

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation

You can view or download publications at httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage To order paper copies of technical documentation contact your local Allen-Bradley distributor or Rockwell Automationreg sales representative

Resource Description

CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069-TD002

Provides specifications and other technical data for CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 controllers

CompactLogix 5480 Controllers User Manual publication 5069-UM002 Describes how to configure operate and monitor CompactLogix 5480 controllers

Industrial Automation Wiring and Grounding Guidelines publication 1770-41 Provides general guidelines for installing a Rockwell Automationreg industrial system

Product Certifications website rokautocertifications Provides declarations of conformity certificates and other certification details

26 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP ltFEFF005500740069006c0069006300650020006500730074006100200063006f006e0066006900670075007200610063006900f3006e0020007000610072006100200063007200650061007200200064006f00630075006d0065006e0074006f0073002000640065002000410064006f0062006500200050004400460020007000610072006100200063006f006e00730065006700750069007200200069006d0070007200650073006900f3006e002000640065002000630061006c006900640061006400200065006e00200069006d0070007200650073006f0072006100730020006400650020006500730063007200690074006f00720069006f00200079002000680065007200720061006d00690065006e00740061007300200064006500200063006f00720072006500630063006900f3006e002e002000530065002000700075006500640065006e00200061006200720069007200200064006f00630075006d0065006e0074006f00730020005000440046002000630072006500610064006f007300200063006f006e0020004100630072006f006200610074002c002000410064006f00620065002000520065006100640065007200200035002e003000200079002000760065007200730069006f006e0065007300200070006f00730074006500720069006f007200650073002egt FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB ltFEFF005500740069006c0069007a006500200065007300730061007300200063006f006e00660069006700750072006100e700f50065007300200064006500200066006f0072006d00610020006100200063007200690061007200200064006f00630075006d0065006e0074006f0073002000410064006f0062006500200050004400460020007000610072006100200069006d0070007200650073007300f5006500730020006400650020007100750061006c0069006400610064006500200065006d00200069006d00700072006500730073006f0072006100730020006400650073006b0074006f00700020006500200064006900730070006f00730069007400690076006f0073002000640065002000700072006f00760061002e0020004f007300200064006f00630075006d0065006e0074006f00730020005000440046002000630072006900610064006f007300200070006f00640065006d0020007300650072002000610062006500720074006f007300200063006f006d0020006f0020004100630072006f006200610074002000650020006f002000410064006f00620065002000520065006100640065007200200035002e0030002000650020007600650072007300f50065007300200070006f00730074006500720069006f007200650073002egt SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 12: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

CompactLogix 5480 Controllers

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the DC (mdash) connection on the external power supply into the first SA (mdash) terminal on the RTB

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

7 Insert the wire from an Earth Ground location into the first

Ground ( ) on the RTB

The Earth Ground location can be the external SA power supply the DIN rail or other Earth Ground location

8 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

The following diagram shows an external 24V DC power supply that is connected to the SA power RTB when you do not use UPS control signals

TIP

This symbol denotes a Functional Ground terminal that provides a

low impedance path between electric circuits and earth for functional

purposes and provides noise immunity improvement This connection

must be made for functional purposes

5069-L4200ERMW

24V DC

Power

Supply

+

ndash

24V DC

Power

Supply

+

ndash

MOD

Power

SA DC

Power

Functional Ground

12 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Connect SA AC Power

Before you connect an external AC power source to the SA power RTB make sure that the SA power source is properly sized

For more information o n SA power see SA Power on page 8

1 Verify that the SA power source is not powered on

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the L1AC (+) connection on the external power supply into the first SA (+) terminal on the RTB

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the L2NAC(mdash) connection on the external power supply into the first SA(mdash) terminal on the RTB

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

7 Insert the wire from an Earth Ground location into the first

Ground ( ) on the RTB

The Earth Ground location can be the external SA power supply the DIN rail or other Earth Ground location

8 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

This diagram shows an external 240V AC power supply that is connected to the SA power RTB when you do not use UPS control signals

IMPORTANT SA power is only required if your application includes local

Compact 5000 IO modules that require SA power to operate

or are connected to field-side devices that are powered by

SA power

TIP

This symbol denotes a Functional Ground terminal that provides a

low impedance path between electric circuits and earth for functional

purposes and provides noise immunity improvement This connection

must be made for functional purposes

5069-L4200ERMW

24V DC

Power

Supply

+

ndash

240V AC

Power

Supply

+

ndash

MOD

Power

SA AC

Power

Functional Ground

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 13

CompactLogix 5480 Controllers

Connect Control Signals Via UPS Control RTBThe CompactLogix 5480 controller does not have an internal energy storage module that lets the controller save the state of the program if system-side power is lost You must connect an external uninterruptible power supply (UPS) to the UPS control RTB to save the state of the program if power is lost

You connect control signals from an external power supply to the UPS control RTB to let the controller experience a controlled shutdown upon an incoming power loss

When a UPS connection is detected the CompactLogix 5480 controller defaults to initiate shutdown 1 minute after a power loss indication

We recommend that you use 1606 switched mode uninterruptible power supplies from Rockwell Automation with a CompactLogix 5480 controller for example the 1606-XLS240-UPS power supply

For more information on Bulletin 1606 uninterruptible power supplies see the following

bull Bulletin 1606 DC-UPS Uninterruptible Power Supply Installation Instructions publication 1606-IN025

bull Bulletin 1606 Switched Mode Power Supplies Reference Manual publication 1606-RM036

The switched mode uninterruptible power supplies use a 12-volt battery module to bridge power failures and voltage fluctuations We recommend that you use the 1606-XLSBATASSY1 battery module from Rockwell Automation

You can use other accessories such as replacement batteries mounting kits and panelwall mounting brackets with the battery module

For more information on and the battery module and accessories that you can use with them see the following

bull Bulletin 1606 12V 7Ah Battery Modules Installation Instructions publication 1606-IN011

bull Bulletin 1606 Switched Mode Power Supply Battery Modules (12V 7Ah) Reference Manual publication 1606-RM037

UPS Control SignalsThese control signals are used on the UPS Control RTB

UPS Control RTB Terminals

Signal Description

UPS Ready (R)

An input signal from the UPS to the controller that indicates the UPS is working and can buffer during a power failure

The charge level for a UPS to be ready to buffer during a power failure varies For example the 1606-XLS240-UPS power supply must be greater than 85 charged to be ready

The letter R indicates the RTB terminal for this signal

Buffering (B)

An input signal from the UPS to the controller that indicates the UPS battery is providing power because the external power has failed

After a preset time (typically 1 minute after power failure) the controller performs an orderly shutdown by stopping execution and saving the state of the controller

The letter B indicates the RTB terminal for this signal

Battery Fail (F)

An input from the UPS to the controller that indicates the UPS battery has failed and the controller cannot operate from stored energy

In this case the controller does not attempt to save the state of the program when the external power fails The controller issues an alarm if a UPS was previously attached and ready to buffer

The letter F indicates the RTB terminal for this signal

Inhibit (I)

An output signal from the controller to the UPS that disables the UPS signal output The INHIBIT signal is triggered after data is backed up and the system is ready to shut down

The letter I indicates the RTB terminal for this signal

14 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the UPS Control RTBInstall the UPS control RTB even if you do not intend to connect uninterruptible power to the controller

1 Hook the bottom of the UPS power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect UPS Control Signals

1 Verify that all sources of MOD power and SA power are turned off

2 Verify the followingbull A 24V DC power supply is connected to the 24V IN

terminals on the UPSbull A 12V DC battery is connected to the 12V BAT terminals

on the UPS

For more information see the example graphic on page 17

Connect to the MOD Power RTB from a UPS

1 Daisy chain the wires from these connections on the UPSbull 24V OUT (+)bull Ready (1)bull Buffering (3)bull Battery Fail (5)bull Inhibit (7)

2 Connect one wire to each (+) terminal on the MOD power RTB as shown in the example graphic on page 17a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Daisy chain a wire that is connected to the 24V OUT (ndash) terminal on the UPS and a second wire

4 Connect one wire to each (ndash) terminal on the MOD power RTB a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

IMPORTANT The UPS terminal labels in this section represent the labels on

a 1606-XLS240-UPS power supply Your UPS terminals can be

labeled differently

5069-L4200ERMW

UPS Control RTB

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 15

CompactLogix 5480 Controllers

Connect to the UPS Control RTB from a UPS

1 Connect a wire from the Ready (2) connection on the UPS to the UPS Ready terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

2 Connect a wire from the Buffering (4) connection on the UPS to the Buffering terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Connect a wire from the Battery Fail (6) connection on the UPS to the Battery Fail terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

4 Connect a wire from the Inhibit (8) connection on the UPS to the Inhibit terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

16 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

This diagram shows a 1606-XLS240-UPS power supply battery that is connected to a CompactLogix 5480 controller

5069-L4200ERMW

UPS Ready

Buffering

Battery Fail

Inhibit

(7) Inhibit +

(8) Inhibit ndash

24V DC

Power

Supply

Ready

(1) (2)

+ ndash + ndash + ndash + ndash

N L PE

Buffering

(3) (4)

Battery Fail

(5) (6)

12V DC Battery

(for example 1606-XLSBATASSY1)

+ ndash

DC-UPS

(1606-XLS240-UPS)

24V

IN

12V

BAT

24V

OUT

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 17

CompactLogix 5480 Controllers

Disconnect Wires from the RTBsIf necessary complete these tasks to disconnect wires from any RTB on the controller

1 Turn the screwdriver counter-clockwise to open the terminal

2 Remove the wire

Install Compact 5000 IO ModulesComplete one of the following

bull If you do not use local Compact 5000 IO modules in the system proceed to Install the End Cap on page 18

bull If you use local Compact 5000 IO modules in the system install the modules to the right side of the controller

After the IO modules are installed install the end cap on the right side of the last IO module in the system For more information on how to install the end cap see page 18

For more information on how to install Compact 5000IO modules see the installation instructions available with each Compact 5000 IO module catalog number

Install the End CapYou must install an end cap on the right side of the last module in a CompactLogix 5480 system The end cap covers the exposed interconnections on the last module in the system If you do not install the end cap before powering the system equipment damage or injury from electric shock can result

If you do not intend to install Compact 5000 IO modules to the system before you turn on power to the controller install the end cap

1 Align the end cap with the interlocking pieces on the controller

2 Push the end cap toward the DIN rail until it locks into place

Power the System

After the end cap is installed on the last module in the system turn on power to the MOD power RTB and the SA power RTB

IMPORTANT Consider the following before you power the system

bull Make sure to remove the debris shield from the controller before power-up

bull As noted previously you must install working controller firmware to use the COS on the controller There are two ways to install working firmware The ways are described beginning on page 23

One of the methods to install working controller firmware

uses the SD card that ships with the controller

ndash If you intend to use the SD card to install working

controller firmware go to Use a Secure Digital Card

to Install Controller Firmware on page 24

Complete the steps described in that section apply

power to the controller and return to the next

section that is Set the Network Internet Protocol

(IP) Addresses on page 19

ndash If you do not intend to use the SD card to install

working controller firmware turn on the power now

and proceed to the next section

Top Interlocking

Pieces

End Cap

Bottom Interlocking

Pieces

18 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Set the Network Internet Protocol (IP) AddressesYou must set an IP address on Ethernet ports for the controller to operate on an EtherNetIP network via that port

Out-of-the-box the following applies to Ethernet ports A1 A2 and B1

bull The ports are DHCP-enabled and the IP address is set automatically via a DHCP server

If there is no DHCP server available to set the IP address you must set the IP address manually

bull If ports A1 and A2 are configured to use DLRLinear mode you set only one IP address that is used on both ports

bull Control ports must use unique subnets

When ports A1 and A2 are configured to use DLRLinear mode however they use the same subnet because they are configured as one port

You can use one of the following to set the IP address on the controller when it is in the out-of-the-box condition

bull DHCP server

bull BOOTP DHCP EtherNetIP Commissioning tool version 30200 or later

bull RSLinx Classic software version 41000 or later

bull FactoryTalk Linx software version 61000 or later

bull Logix Designer application version 320100 or later

For more information on how to set or change the IP address on a CompactLogix 5480 controller see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

Connect the Controller to an EtherNetIP Network

Use an RJ45 cable to connect the controller to an EtherNetIP network

1 If needed wire the RJ45 connector as shown

2 Connect RJ45 cables to the controller Ethernet ports

IMPORTANT Before you can connect a CompactLogix 5480 controller to an

EtherNetIP network you must first install the network and

its components

This section assumes that the EtherNetIP network is

installed

Connector Number

Color

1585J 8-pin Cables with Support for 101001000 Mbps

1585J 8-pin Cables with Support for 10100 Mbps

1585J 4-pin Cables with Support for 10100 Mbps

1WhiteOrange

BI_DA+ TxData +

2 Orange BI_DA- TxData -

3WhiteGreen

BI_DB+ Recv Data +

4 Blue BI_DC+ Unused mdash

5 WhiteBlue BI_DC- Unused mdash

6 Green BI_DB- Recv Data -

7WhiteBrown

BI_DD+ Unused mdash

8 Brown BI_DD- Unused mdash

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 19

CompactLogix 5480 Controllers

Remove and Replace the Controller

1 Turn off power to the MOD power and the SA power RTBs

2 If there are local Compact 5000 IO modules in the system remove them If not skip to step 3

3 Disconnect wires from the RTBs

For more information see Disconnect Wires from the RTBs on page 18

4 Pull the RTB handles to remove the RTBs

IMPORTANT When you remove MOD power from the controller you shut down

power to all modules in the CompactLogix 5480 system That is

all system-side is removed When you remove SA power from the

controller all field-side power that is provided by the controller is

removed If SA power that is provided via a 5069-FPD field

potential distributor the system does not lose SA power to the

right of the field potential distributor

In this case you must use a separate power source for the SA

power RTB on the field potential distributor

We strongly recommend that before you remove MOD power or

SA power that you take the appropriate actions to help prevent

unintended consequences that can result from a system power

shutdown

Despite the removal of power from SA RTBs on the controller or

field potential distributor the 5069-OB16 and 5069-OB16F

modules continue to receive field-side power The modules

receive power from an external power source that is connected to

the LA (+) and LA (ndash) module terminals

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

UPS Control RTB

MOD Power RTB

SA Power RTB

20 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

5 Remove all cables from the controller

6 Push down on the front of the DIN rail latches

A click indicates that the DIN rail latches are open

If the DIN rail latches fail to remain in the open position hold them down

7 Pull the controller off the DIN rail

8 Repeat the installation steps that are described beginning at Install the Controller onto the DIN Rail on page 9

9 Apply MOD power and if necessary SA power to the system

Replace the FansThe CompactLogix 5480 controller uses fans at the top and bottom of the controller to help maintain lower operating temperatures when the controller is operating

Fan use includes speed control and monitoring Faults indicate fan operating conditions as follows

bull Minor faults - Triggered when a fan is not operating at the requested speed or if a fan fails to operate at all

In your Logix Designer application project you can use the Minor Faults tab on the Controller Properties dialog box to monitor for these faults

bull Major fault - Triggered if both fans fail and the controller goes over the maximum operating temperature

In this case the controller stops operating

You can order replacement fans Replacement fans come in pairs The fans are unique by position and keyed to help make sure that you install the correct fan in each position

The fans are labeled Fan 1 - Top and Fan 2 - Bottom

Consider the following

bull We recommend that you replace the fans in pairs That is if you replace the one fan we recommend that you replace the other fan too

bull You can replace fans during controller operation The fans support removal and insertion under power

bull Do not remove both fans at once if the controller is operating That is remove a fan and install the replacement fan before you remove the other fan

Remove the Top Fan

1 Push up on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

TIP In your Logix Designer application project you can

use the Major Faults tab on the Controller

Properties dialog box to monitor for this fault

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

R

B

F

Open Position

IMPORTANT If you replace fans while the controller is operating

do not touch live voltage components

TIP If the hinges do not disengage when you push up on the front of the

fan then use a screwdriver as a pry tool

5069-L4200ERMW

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 21

CompactLogix 5480 Controllers

2 Pull the fan out of the slot at the top of the controller

Install the Top Replacement Fan

1 Insert the top replacement fan into the slot at the top of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push down on the top replacement fan until it clicks in place

Remove the Bottom Fan

1 Push the down on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

2 Pull the fan out of the slot at the bottom of the controller

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

TIP If the hinges do not disengage when you push down on the front of

the fan then use a screwdriver as a pry tool

5069-L4200ERMW

5069-L4200ERMW

22 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Bottom Replacement Fan

1 Insert the bottom replacement fan into the slot at the bottom of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push up on the bottom replacement fan until it clicks in place

Use the COS For Windows-based ComputingThe COS on a CompactLogix 5480 controller runs in parallel with the Logix control engine You are not required to use the COS

You can use the following methods to install working controller firmware when the controller is in the out-of-box state

bull ControlFLASHtrade or ControlFLASH Plustrade softwarebull Secure Digital (SD) card

Use a Flash Programming Tool to Install Controller FirmwareYou can use ControlFLASH and ControlFLASH Plus software to install controller firmware

The following requirements apply when you use ControlFLASH or ControlFLASH Plus to install working controller firmware

bull You must use one of the followingndash ControlFLASH software version 150100 or laterndash ControlFLASH Plus version 20000 or later

bull You must use a Linx-based software application with your flash programming toolndash With ControlFLASH software you can use RSLinx

Classic Lite RSLinx Classic RSLinx Enterprise or FactoryTalk Linx

ndash With ControlFLASH Plus software you must use FactoryTalk Linx

Minimum software versions apply with Linx-based software For more information on the minimum software version requirements see the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

5069-L4200ERMW

5069-L4200ERMW

IMPORTANT Before you can use the COS you must install working controller firmware The requirement applies even if you

are not using the controller for real-time control If you do not

install working controller firmware the COS does not start

In the out-of-box state the controller uses firmware revision

1xxx On a CompactLogix 5480 controller the minimum

working controller firmware is revision 32012

TIP We recommend that you connect your peripherals to the

ports that are dedicated to COS use before you install

controller firmware

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 23

CompactLogix 5480 Controllers

Download the Flash Programming Tool

ControlFLASH and ControlFLASH Plus software are available from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

Download the installation files and install the software

Download the Controller Firmware

After the flash programming tool is installed download the controller firmware from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

The initial download is a exe file You use the Rockwell Automation Download Manager to extract a dmk from the downloaded file

Install the Controller Firmware

To install the controller firmware via a flash programming tool you complete the following steps

1 To start the tool click StartgtAll ProgramsgtFlashing Programming ToolsgtControlFLASH or ControlFLASH Plus

2 Follow the prompts to complete the following stepsa Choose the controllerb Select the firmware revisionc Install the controller firmware

A dialog box confirms that the installation was successful

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use a flash programming tool to install controller firmware see the following

bull ControlFLASH Firmware Upgrade Kit User Manual publication 1756-UM105

bull ControlFLASH Plus Quick Start Guide publication CFP-QS001

bull CompactLogix 5480 Controllers User Manual publication 5069-UM002

Use a Secure Digital Card to Install Controller FirmwareYou can use an SD card to install controller firmware CompactLogix 5480 controllers ship with an SD card installed behind the front door on the controller

To use an SD card to install controller firmware complete the following steps

1 Before you turn on power to the controller remove the SD card from the controller

2 Install the SD card into another working CompactLogix 5480 controller that has a Logix Designer application project on it

3 Save the project to the SD card

4 Remove the SD card from the working controller and reinstall it in the new controller

5 Turn on power to the new controller

When the new controller powers up it automatically updates the firmware to the revision that is stored on the SD card

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use the SD card with the controller after valid firmware is installed and the controller is powered see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

IMPORTANT These steps only highlight the major tasks that you

complete to install controller firmware with ControlFLASH

To successfully install controller firmware you must complete other tasks that are not described here

For complete information on how to install controller

firmware see the publications listed at the end of the section

IMPORTANT To install controller firmware on a new CompactLogix 5480

controller via an SD card you must have another controller of

the same type that is already working

The SD card method requires that you save the Logix Designer

application project from the working controller to the SD card

before you use it in the new controller

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

SD Card Slot

24 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpecificationsThis table lists a subset of controller specifications For a complete list of specifications see the CompactLogix 5380 Compact GuardLogixreg 5380 and CompactLogix 5480 Controllers Specifications Technical Data publication 5069-TD002

Environmental Specifications - CompactLogix 5480 Controllers

Attribute 5069-L430ERMW 5069-L450ERMW 5069-4100ERMW 5069-L4200ERMW

Temperature operating

IEC 60068-2-1 (Test Ad Operating Cold)

IEC 60068-2-2 (Test Bd Operating Dry Heat)

IEC 60068-2-14 (Test Na Operating Thermal Shock)

0 degC lt Ta lt +60 degC

(+32 degF lt Ta lt +140 degF)

Temperature surrounding air max 60 degC (140 degF)

Enclosure Type Rating None (open-style)

Voltage and current ratings

MOD Power voltage range 18hellip32V DC

MOD Power power max 72 W

MOD Power current typical 4 A

MOD Power inrush 4 A for 15 ms

MOD Power Passthrough(1) 6 A 18hellip32V DC

MOD Power current rating max10 A

Do not exceed 10 A current draw at the MOD power RTB(4)

SA Power voltage ranges(2) 0hellip32V DC

0hellip240V AC 47hellip63 Hz

SA Power current max (2) 10 mA (DC power)

25 mA (AC power)

SA Power Passthrough(2) (3) 999 A 0hellip32V DC

9975 A 0hellip240V AC 47hellip63 Hz

SA Power current rating max(2) Do not exceed 10 A current draw at the SA power RTB

Isolation voltage

300V (continuous) Basic Insulation Type SA and MOD Power to Backplane

300V (continuous) Basic Insulation Type SA to MOD Power

300V (continuous) Basic Insulation Type Ethernet to Backplane

300V (continuous) Double Insulation Type Ethernet to MOD Power

300V (continuous) Double Insulation Type Ethernet to SA Power

50V (continuous) Functional Insulation Type Ethernet to USB ports and DisplayPort

300V (continuous) Basic Insulation Type USB ports and DisplayPort to Backplane

300V (continuous) Double Insulation Type USB ports and DisplayPort to MOD Power

300V (continuous) Double Insulation Type USB ports and DisplayPort to SA Power

No isolation between Ethernet ports

Type tested at 1500V AC for 60 s

Wire size

5069-RTB4-SCREW 5069-RTB6-SCREW connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 35 mm (014 in) max diameter including insulation single wire connection only

5069-RTB4-UPS connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 29 mm (011 in) max diameter including insulation single wire connection only

Ethernet connections

Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2

Insulation-stripping length 5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 12 mm (047 in)

Terminal block torque5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 04 Nbullm (35 lbbullin)

ATTENTION Do not wire more than two conductors on one RTB terminal

(1) Maximum level of MOD power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(2) SA power specifications are based on the number and type of Compact 5000 IO modules that are used in the system If the set of IO modules that is used in the system require AC and DC voltage you must install a 5069-FPD field

potential distributor to separate the module types

(3) Maximum level of SA power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(4) Remember MOD power usage includes the total power that the controller and local Compact 5000 IO modules use If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000 IO

modules can draw a maximum of 10 A in addition to the current that the controller draws

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 25

CompactLogix 5480 Controllers

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation

You can view or download publications at httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage To order paper copies of technical documentation contact your local Allen-Bradley distributor or Rockwell Automationreg sales representative

Resource Description

CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069-TD002

Provides specifications and other technical data for CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 controllers

CompactLogix 5480 Controllers User Manual publication 5069-UM002 Describes how to configure operate and monitor CompactLogix 5480 controllers

Industrial Automation Wiring and Grounding Guidelines publication 1770-41 Provides general guidelines for installing a Rockwell Automationreg industrial system

Product Certifications website rokautocertifications Provides declarations of conformity certificates and other certification details

26 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 13: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

CompactLogix 5480 Controllers

Connect SA AC Power

Before you connect an external AC power source to the SA power RTB make sure that the SA power source is properly sized

For more information o n SA power see SA Power on page 8

1 Verify that the SA power source is not powered on

2 Strip 12 mm (047 in) of insulation from the wires that you connect to the RTB

3 Insert the wire from the L1AC (+) connection on the external power supply into the first SA (+) terminal on the RTB

4 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

5 Insert the wire from the L2NAC(mdash) connection on the external power supply into the first SA(mdash) terminal on the RTB

6 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

7 Insert the wire from an Earth Ground location into the first

Ground ( ) on the RTB

The Earth Ground location can be the external SA power supply the DIN rail or other Earth Ground location

8 Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

This diagram shows an external 240V AC power supply that is connected to the SA power RTB when you do not use UPS control signals

IMPORTANT SA power is only required if your application includes local

Compact 5000 IO modules that require SA power to operate

or are connected to field-side devices that are powered by

SA power

TIP

This symbol denotes a Functional Ground terminal that provides a

low impedance path between electric circuits and earth for functional

purposes and provides noise immunity improvement This connection

must be made for functional purposes

5069-L4200ERMW

24V DC

Power

Supply

+

ndash

240V AC

Power

Supply

+

ndash

MOD

Power

SA AC

Power

Functional Ground

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 13

CompactLogix 5480 Controllers

Connect Control Signals Via UPS Control RTBThe CompactLogix 5480 controller does not have an internal energy storage module that lets the controller save the state of the program if system-side power is lost You must connect an external uninterruptible power supply (UPS) to the UPS control RTB to save the state of the program if power is lost

You connect control signals from an external power supply to the UPS control RTB to let the controller experience a controlled shutdown upon an incoming power loss

When a UPS connection is detected the CompactLogix 5480 controller defaults to initiate shutdown 1 minute after a power loss indication

We recommend that you use 1606 switched mode uninterruptible power supplies from Rockwell Automation with a CompactLogix 5480 controller for example the 1606-XLS240-UPS power supply

For more information on Bulletin 1606 uninterruptible power supplies see the following

bull Bulletin 1606 DC-UPS Uninterruptible Power Supply Installation Instructions publication 1606-IN025

bull Bulletin 1606 Switched Mode Power Supplies Reference Manual publication 1606-RM036

The switched mode uninterruptible power supplies use a 12-volt battery module to bridge power failures and voltage fluctuations We recommend that you use the 1606-XLSBATASSY1 battery module from Rockwell Automation

You can use other accessories such as replacement batteries mounting kits and panelwall mounting brackets with the battery module

For more information on and the battery module and accessories that you can use with them see the following

bull Bulletin 1606 12V 7Ah Battery Modules Installation Instructions publication 1606-IN011

bull Bulletin 1606 Switched Mode Power Supply Battery Modules (12V 7Ah) Reference Manual publication 1606-RM037

UPS Control SignalsThese control signals are used on the UPS Control RTB

UPS Control RTB Terminals

Signal Description

UPS Ready (R)

An input signal from the UPS to the controller that indicates the UPS is working and can buffer during a power failure

The charge level for a UPS to be ready to buffer during a power failure varies For example the 1606-XLS240-UPS power supply must be greater than 85 charged to be ready

The letter R indicates the RTB terminal for this signal

Buffering (B)

An input signal from the UPS to the controller that indicates the UPS battery is providing power because the external power has failed

After a preset time (typically 1 minute after power failure) the controller performs an orderly shutdown by stopping execution and saving the state of the controller

The letter B indicates the RTB terminal for this signal

Battery Fail (F)

An input from the UPS to the controller that indicates the UPS battery has failed and the controller cannot operate from stored energy

In this case the controller does not attempt to save the state of the program when the external power fails The controller issues an alarm if a UPS was previously attached and ready to buffer

The letter F indicates the RTB terminal for this signal

Inhibit (I)

An output signal from the controller to the UPS that disables the UPS signal output The INHIBIT signal is triggered after data is backed up and the system is ready to shut down

The letter I indicates the RTB terminal for this signal

14 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the UPS Control RTBInstall the UPS control RTB even if you do not intend to connect uninterruptible power to the controller

1 Hook the bottom of the UPS power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect UPS Control Signals

1 Verify that all sources of MOD power and SA power are turned off

2 Verify the followingbull A 24V DC power supply is connected to the 24V IN

terminals on the UPSbull A 12V DC battery is connected to the 12V BAT terminals

on the UPS

For more information see the example graphic on page 17

Connect to the MOD Power RTB from a UPS

1 Daisy chain the wires from these connections on the UPSbull 24V OUT (+)bull Ready (1)bull Buffering (3)bull Battery Fail (5)bull Inhibit (7)

2 Connect one wire to each (+) terminal on the MOD power RTB as shown in the example graphic on page 17a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Daisy chain a wire that is connected to the 24V OUT (ndash) terminal on the UPS and a second wire

4 Connect one wire to each (ndash) terminal on the MOD power RTB a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

IMPORTANT The UPS terminal labels in this section represent the labels on

a 1606-XLS240-UPS power supply Your UPS terminals can be

labeled differently

5069-L4200ERMW

UPS Control RTB

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 15

CompactLogix 5480 Controllers

Connect to the UPS Control RTB from a UPS

1 Connect a wire from the Ready (2) connection on the UPS to the UPS Ready terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

2 Connect a wire from the Buffering (4) connection on the UPS to the Buffering terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Connect a wire from the Battery Fail (6) connection on the UPS to the Battery Fail terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

4 Connect a wire from the Inhibit (8) connection on the UPS to the Inhibit terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

16 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

This diagram shows a 1606-XLS240-UPS power supply battery that is connected to a CompactLogix 5480 controller

5069-L4200ERMW

UPS Ready

Buffering

Battery Fail

Inhibit

(7) Inhibit +

(8) Inhibit ndash

24V DC

Power

Supply

Ready

(1) (2)

+ ndash + ndash + ndash + ndash

N L PE

Buffering

(3) (4)

Battery Fail

(5) (6)

12V DC Battery

(for example 1606-XLSBATASSY1)

+ ndash

DC-UPS

(1606-XLS240-UPS)

24V

IN

12V

BAT

24V

OUT

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 17

CompactLogix 5480 Controllers

Disconnect Wires from the RTBsIf necessary complete these tasks to disconnect wires from any RTB on the controller

1 Turn the screwdriver counter-clockwise to open the terminal

2 Remove the wire

Install Compact 5000 IO ModulesComplete one of the following

bull If you do not use local Compact 5000 IO modules in the system proceed to Install the End Cap on page 18

bull If you use local Compact 5000 IO modules in the system install the modules to the right side of the controller

After the IO modules are installed install the end cap on the right side of the last IO module in the system For more information on how to install the end cap see page 18

For more information on how to install Compact 5000IO modules see the installation instructions available with each Compact 5000 IO module catalog number

Install the End CapYou must install an end cap on the right side of the last module in a CompactLogix 5480 system The end cap covers the exposed interconnections on the last module in the system If you do not install the end cap before powering the system equipment damage or injury from electric shock can result

If you do not intend to install Compact 5000 IO modules to the system before you turn on power to the controller install the end cap

1 Align the end cap with the interlocking pieces on the controller

2 Push the end cap toward the DIN rail until it locks into place

Power the System

After the end cap is installed on the last module in the system turn on power to the MOD power RTB and the SA power RTB

IMPORTANT Consider the following before you power the system

bull Make sure to remove the debris shield from the controller before power-up

bull As noted previously you must install working controller firmware to use the COS on the controller There are two ways to install working firmware The ways are described beginning on page 23

One of the methods to install working controller firmware

uses the SD card that ships with the controller

ndash If you intend to use the SD card to install working

controller firmware go to Use a Secure Digital Card

to Install Controller Firmware on page 24

Complete the steps described in that section apply

power to the controller and return to the next

section that is Set the Network Internet Protocol

(IP) Addresses on page 19

ndash If you do not intend to use the SD card to install

working controller firmware turn on the power now

and proceed to the next section

Top Interlocking

Pieces

End Cap

Bottom Interlocking

Pieces

18 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Set the Network Internet Protocol (IP) AddressesYou must set an IP address on Ethernet ports for the controller to operate on an EtherNetIP network via that port

Out-of-the-box the following applies to Ethernet ports A1 A2 and B1

bull The ports are DHCP-enabled and the IP address is set automatically via a DHCP server

If there is no DHCP server available to set the IP address you must set the IP address manually

bull If ports A1 and A2 are configured to use DLRLinear mode you set only one IP address that is used on both ports

bull Control ports must use unique subnets

When ports A1 and A2 are configured to use DLRLinear mode however they use the same subnet because they are configured as one port

You can use one of the following to set the IP address on the controller when it is in the out-of-the-box condition

bull DHCP server

bull BOOTP DHCP EtherNetIP Commissioning tool version 30200 or later

bull RSLinx Classic software version 41000 or later

bull FactoryTalk Linx software version 61000 or later

bull Logix Designer application version 320100 or later

For more information on how to set or change the IP address on a CompactLogix 5480 controller see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

Connect the Controller to an EtherNetIP Network

Use an RJ45 cable to connect the controller to an EtherNetIP network

1 If needed wire the RJ45 connector as shown

2 Connect RJ45 cables to the controller Ethernet ports

IMPORTANT Before you can connect a CompactLogix 5480 controller to an

EtherNetIP network you must first install the network and

its components

This section assumes that the EtherNetIP network is

installed

Connector Number

Color

1585J 8-pin Cables with Support for 101001000 Mbps

1585J 8-pin Cables with Support for 10100 Mbps

1585J 4-pin Cables with Support for 10100 Mbps

1WhiteOrange

BI_DA+ TxData +

2 Orange BI_DA- TxData -

3WhiteGreen

BI_DB+ Recv Data +

4 Blue BI_DC+ Unused mdash

5 WhiteBlue BI_DC- Unused mdash

6 Green BI_DB- Recv Data -

7WhiteBrown

BI_DD+ Unused mdash

8 Brown BI_DD- Unused mdash

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 19

CompactLogix 5480 Controllers

Remove and Replace the Controller

1 Turn off power to the MOD power and the SA power RTBs

2 If there are local Compact 5000 IO modules in the system remove them If not skip to step 3

3 Disconnect wires from the RTBs

For more information see Disconnect Wires from the RTBs on page 18

4 Pull the RTB handles to remove the RTBs

IMPORTANT When you remove MOD power from the controller you shut down

power to all modules in the CompactLogix 5480 system That is

all system-side is removed When you remove SA power from the

controller all field-side power that is provided by the controller is

removed If SA power that is provided via a 5069-FPD field

potential distributor the system does not lose SA power to the

right of the field potential distributor

In this case you must use a separate power source for the SA

power RTB on the field potential distributor

We strongly recommend that before you remove MOD power or

SA power that you take the appropriate actions to help prevent

unintended consequences that can result from a system power

shutdown

Despite the removal of power from SA RTBs on the controller or

field potential distributor the 5069-OB16 and 5069-OB16F

modules continue to receive field-side power The modules

receive power from an external power source that is connected to

the LA (+) and LA (ndash) module terminals

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

UPS Control RTB

MOD Power RTB

SA Power RTB

20 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

5 Remove all cables from the controller

6 Push down on the front of the DIN rail latches

A click indicates that the DIN rail latches are open

If the DIN rail latches fail to remain in the open position hold them down

7 Pull the controller off the DIN rail

8 Repeat the installation steps that are described beginning at Install the Controller onto the DIN Rail on page 9

9 Apply MOD power and if necessary SA power to the system

Replace the FansThe CompactLogix 5480 controller uses fans at the top and bottom of the controller to help maintain lower operating temperatures when the controller is operating

Fan use includes speed control and monitoring Faults indicate fan operating conditions as follows

bull Minor faults - Triggered when a fan is not operating at the requested speed or if a fan fails to operate at all

In your Logix Designer application project you can use the Minor Faults tab on the Controller Properties dialog box to monitor for these faults

bull Major fault - Triggered if both fans fail and the controller goes over the maximum operating temperature

In this case the controller stops operating

You can order replacement fans Replacement fans come in pairs The fans are unique by position and keyed to help make sure that you install the correct fan in each position

The fans are labeled Fan 1 - Top and Fan 2 - Bottom

Consider the following

bull We recommend that you replace the fans in pairs That is if you replace the one fan we recommend that you replace the other fan too

bull You can replace fans during controller operation The fans support removal and insertion under power

bull Do not remove both fans at once if the controller is operating That is remove a fan and install the replacement fan before you remove the other fan

Remove the Top Fan

1 Push up on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

TIP In your Logix Designer application project you can

use the Major Faults tab on the Controller

Properties dialog box to monitor for this fault

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

R

B

F

Open Position

IMPORTANT If you replace fans while the controller is operating

do not touch live voltage components

TIP If the hinges do not disengage when you push up on the front of the

fan then use a screwdriver as a pry tool

5069-L4200ERMW

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 21

CompactLogix 5480 Controllers

2 Pull the fan out of the slot at the top of the controller

Install the Top Replacement Fan

1 Insert the top replacement fan into the slot at the top of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push down on the top replacement fan until it clicks in place

Remove the Bottom Fan

1 Push the down on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

2 Pull the fan out of the slot at the bottom of the controller

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

TIP If the hinges do not disengage when you push down on the front of

the fan then use a screwdriver as a pry tool

5069-L4200ERMW

5069-L4200ERMW

22 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Bottom Replacement Fan

1 Insert the bottom replacement fan into the slot at the bottom of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push up on the bottom replacement fan until it clicks in place

Use the COS For Windows-based ComputingThe COS on a CompactLogix 5480 controller runs in parallel with the Logix control engine You are not required to use the COS

You can use the following methods to install working controller firmware when the controller is in the out-of-box state

bull ControlFLASHtrade or ControlFLASH Plustrade softwarebull Secure Digital (SD) card

Use a Flash Programming Tool to Install Controller FirmwareYou can use ControlFLASH and ControlFLASH Plus software to install controller firmware

The following requirements apply when you use ControlFLASH or ControlFLASH Plus to install working controller firmware

bull You must use one of the followingndash ControlFLASH software version 150100 or laterndash ControlFLASH Plus version 20000 or later

bull You must use a Linx-based software application with your flash programming toolndash With ControlFLASH software you can use RSLinx

Classic Lite RSLinx Classic RSLinx Enterprise or FactoryTalk Linx

ndash With ControlFLASH Plus software you must use FactoryTalk Linx

Minimum software versions apply with Linx-based software For more information on the minimum software version requirements see the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

5069-L4200ERMW

5069-L4200ERMW

IMPORTANT Before you can use the COS you must install working controller firmware The requirement applies even if you

are not using the controller for real-time control If you do not

install working controller firmware the COS does not start

In the out-of-box state the controller uses firmware revision

1xxx On a CompactLogix 5480 controller the minimum

working controller firmware is revision 32012

TIP We recommend that you connect your peripherals to the

ports that are dedicated to COS use before you install

controller firmware

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 23

CompactLogix 5480 Controllers

Download the Flash Programming Tool

ControlFLASH and ControlFLASH Plus software are available from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

Download the installation files and install the software

Download the Controller Firmware

After the flash programming tool is installed download the controller firmware from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

The initial download is a exe file You use the Rockwell Automation Download Manager to extract a dmk from the downloaded file

Install the Controller Firmware

To install the controller firmware via a flash programming tool you complete the following steps

1 To start the tool click StartgtAll ProgramsgtFlashing Programming ToolsgtControlFLASH or ControlFLASH Plus

2 Follow the prompts to complete the following stepsa Choose the controllerb Select the firmware revisionc Install the controller firmware

A dialog box confirms that the installation was successful

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use a flash programming tool to install controller firmware see the following

bull ControlFLASH Firmware Upgrade Kit User Manual publication 1756-UM105

bull ControlFLASH Plus Quick Start Guide publication CFP-QS001

bull CompactLogix 5480 Controllers User Manual publication 5069-UM002

Use a Secure Digital Card to Install Controller FirmwareYou can use an SD card to install controller firmware CompactLogix 5480 controllers ship with an SD card installed behind the front door on the controller

To use an SD card to install controller firmware complete the following steps

1 Before you turn on power to the controller remove the SD card from the controller

2 Install the SD card into another working CompactLogix 5480 controller that has a Logix Designer application project on it

3 Save the project to the SD card

4 Remove the SD card from the working controller and reinstall it in the new controller

5 Turn on power to the new controller

When the new controller powers up it automatically updates the firmware to the revision that is stored on the SD card

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use the SD card with the controller after valid firmware is installed and the controller is powered see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

IMPORTANT These steps only highlight the major tasks that you

complete to install controller firmware with ControlFLASH

To successfully install controller firmware you must complete other tasks that are not described here

For complete information on how to install controller

firmware see the publications listed at the end of the section

IMPORTANT To install controller firmware on a new CompactLogix 5480

controller via an SD card you must have another controller of

the same type that is already working

The SD card method requires that you save the Logix Designer

application project from the working controller to the SD card

before you use it in the new controller

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

SD Card Slot

24 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpecificationsThis table lists a subset of controller specifications For a complete list of specifications see the CompactLogix 5380 Compact GuardLogixreg 5380 and CompactLogix 5480 Controllers Specifications Technical Data publication 5069-TD002

Environmental Specifications - CompactLogix 5480 Controllers

Attribute 5069-L430ERMW 5069-L450ERMW 5069-4100ERMW 5069-L4200ERMW

Temperature operating

IEC 60068-2-1 (Test Ad Operating Cold)

IEC 60068-2-2 (Test Bd Operating Dry Heat)

IEC 60068-2-14 (Test Na Operating Thermal Shock)

0 degC lt Ta lt +60 degC

(+32 degF lt Ta lt +140 degF)

Temperature surrounding air max 60 degC (140 degF)

Enclosure Type Rating None (open-style)

Voltage and current ratings

MOD Power voltage range 18hellip32V DC

MOD Power power max 72 W

MOD Power current typical 4 A

MOD Power inrush 4 A for 15 ms

MOD Power Passthrough(1) 6 A 18hellip32V DC

MOD Power current rating max10 A

Do not exceed 10 A current draw at the MOD power RTB(4)

SA Power voltage ranges(2) 0hellip32V DC

0hellip240V AC 47hellip63 Hz

SA Power current max (2) 10 mA (DC power)

25 mA (AC power)

SA Power Passthrough(2) (3) 999 A 0hellip32V DC

9975 A 0hellip240V AC 47hellip63 Hz

SA Power current rating max(2) Do not exceed 10 A current draw at the SA power RTB

Isolation voltage

300V (continuous) Basic Insulation Type SA and MOD Power to Backplane

300V (continuous) Basic Insulation Type SA to MOD Power

300V (continuous) Basic Insulation Type Ethernet to Backplane

300V (continuous) Double Insulation Type Ethernet to MOD Power

300V (continuous) Double Insulation Type Ethernet to SA Power

50V (continuous) Functional Insulation Type Ethernet to USB ports and DisplayPort

300V (continuous) Basic Insulation Type USB ports and DisplayPort to Backplane

300V (continuous) Double Insulation Type USB ports and DisplayPort to MOD Power

300V (continuous) Double Insulation Type USB ports and DisplayPort to SA Power

No isolation between Ethernet ports

Type tested at 1500V AC for 60 s

Wire size

5069-RTB4-SCREW 5069-RTB6-SCREW connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 35 mm (014 in) max diameter including insulation single wire connection only

5069-RTB4-UPS connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 29 mm (011 in) max diameter including insulation single wire connection only

Ethernet connections

Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2

Insulation-stripping length 5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 12 mm (047 in)

Terminal block torque5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 04 Nbullm (35 lbbullin)

ATTENTION Do not wire more than two conductors on one RTB terminal

(1) Maximum level of MOD power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(2) SA power specifications are based on the number and type of Compact 5000 IO modules that are used in the system If the set of IO modules that is used in the system require AC and DC voltage you must install a 5069-FPD field

potential distributor to separate the module types

(3) Maximum level of SA power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(4) Remember MOD power usage includes the total power that the controller and local Compact 5000 IO modules use If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000 IO

modules can draw a maximum of 10 A in addition to the current that the controller draws

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 25

CompactLogix 5480 Controllers

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation

You can view or download publications at httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage To order paper copies of technical documentation contact your local Allen-Bradley distributor or Rockwell Automationreg sales representative

Resource Description

CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069-TD002

Provides specifications and other technical data for CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 controllers

CompactLogix 5480 Controllers User Manual publication 5069-UM002 Describes how to configure operate and monitor CompactLogix 5480 controllers

Industrial Automation Wiring and Grounding Guidelines publication 1770-41 Provides general guidelines for installing a Rockwell Automationreg industrial system

Product Certifications website rokautocertifications Provides declarations of conformity certificates and other certification details

26 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA ltFEFF005500740069006c0069007a007a006100720065002000710075006500730074006500200069006d0070006f007300740061007a0069006f006e00690020007000650072002000630072006500610072006500200064006f00630075006d0065006e00740069002000410064006f006200650020005000440046002000700065007200200075006e00610020007300740061006d007000610020006400690020007100750061006c0069007400e00020007300750020007300740061006d00700061006e0074006900200065002000700072006f006f0066006500720020006400650073006b0074006f0070002e0020004900200064006f00630075006d0065006e007400690020005000440046002000630072006500610074006900200070006f00730073006f006e006f0020006500730073006500720065002000610070006500720074006900200063006f006e0020004100630072006f00620061007400200065002000410064006f00620065002000520065006100640065007200200035002e003000200065002000760065007200730069006f006e006900200073007500630063006500730073006900760065002egt JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 14: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

CompactLogix 5480 Controllers

Connect Control Signals Via UPS Control RTBThe CompactLogix 5480 controller does not have an internal energy storage module that lets the controller save the state of the program if system-side power is lost You must connect an external uninterruptible power supply (UPS) to the UPS control RTB to save the state of the program if power is lost

You connect control signals from an external power supply to the UPS control RTB to let the controller experience a controlled shutdown upon an incoming power loss

When a UPS connection is detected the CompactLogix 5480 controller defaults to initiate shutdown 1 minute after a power loss indication

We recommend that you use 1606 switched mode uninterruptible power supplies from Rockwell Automation with a CompactLogix 5480 controller for example the 1606-XLS240-UPS power supply

For more information on Bulletin 1606 uninterruptible power supplies see the following

bull Bulletin 1606 DC-UPS Uninterruptible Power Supply Installation Instructions publication 1606-IN025

bull Bulletin 1606 Switched Mode Power Supplies Reference Manual publication 1606-RM036

The switched mode uninterruptible power supplies use a 12-volt battery module to bridge power failures and voltage fluctuations We recommend that you use the 1606-XLSBATASSY1 battery module from Rockwell Automation

You can use other accessories such as replacement batteries mounting kits and panelwall mounting brackets with the battery module

For more information on and the battery module and accessories that you can use with them see the following

bull Bulletin 1606 12V 7Ah Battery Modules Installation Instructions publication 1606-IN011

bull Bulletin 1606 Switched Mode Power Supply Battery Modules (12V 7Ah) Reference Manual publication 1606-RM037

UPS Control SignalsThese control signals are used on the UPS Control RTB

UPS Control RTB Terminals

Signal Description

UPS Ready (R)

An input signal from the UPS to the controller that indicates the UPS is working and can buffer during a power failure

The charge level for a UPS to be ready to buffer during a power failure varies For example the 1606-XLS240-UPS power supply must be greater than 85 charged to be ready

The letter R indicates the RTB terminal for this signal

Buffering (B)

An input signal from the UPS to the controller that indicates the UPS battery is providing power because the external power has failed

After a preset time (typically 1 minute after power failure) the controller performs an orderly shutdown by stopping execution and saving the state of the controller

The letter B indicates the RTB terminal for this signal

Battery Fail (F)

An input from the UPS to the controller that indicates the UPS battery has failed and the controller cannot operate from stored energy

In this case the controller does not attempt to save the state of the program when the external power fails The controller issues an alarm if a UPS was previously attached and ready to buffer

The letter F indicates the RTB terminal for this signal

Inhibit (I)

An output signal from the controller to the UPS that disables the UPS signal output The INHIBIT signal is triggered after data is backed up and the system is ready to shut down

The letter I indicates the RTB terminal for this signal

14 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the UPS Control RTBInstall the UPS control RTB even if you do not intend to connect uninterruptible power to the controller

1 Hook the bottom of the UPS power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect UPS Control Signals

1 Verify that all sources of MOD power and SA power are turned off

2 Verify the followingbull A 24V DC power supply is connected to the 24V IN

terminals on the UPSbull A 12V DC battery is connected to the 12V BAT terminals

on the UPS

For more information see the example graphic on page 17

Connect to the MOD Power RTB from a UPS

1 Daisy chain the wires from these connections on the UPSbull 24V OUT (+)bull Ready (1)bull Buffering (3)bull Battery Fail (5)bull Inhibit (7)

2 Connect one wire to each (+) terminal on the MOD power RTB as shown in the example graphic on page 17a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Daisy chain a wire that is connected to the 24V OUT (ndash) terminal on the UPS and a second wire

4 Connect one wire to each (ndash) terminal on the MOD power RTB a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

IMPORTANT The UPS terminal labels in this section represent the labels on

a 1606-XLS240-UPS power supply Your UPS terminals can be

labeled differently

5069-L4200ERMW

UPS Control RTB

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 15

CompactLogix 5480 Controllers

Connect to the UPS Control RTB from a UPS

1 Connect a wire from the Ready (2) connection on the UPS to the UPS Ready terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

2 Connect a wire from the Buffering (4) connection on the UPS to the Buffering terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Connect a wire from the Battery Fail (6) connection on the UPS to the Battery Fail terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

4 Connect a wire from the Inhibit (8) connection on the UPS to the Inhibit terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

16 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

This diagram shows a 1606-XLS240-UPS power supply battery that is connected to a CompactLogix 5480 controller

5069-L4200ERMW

UPS Ready

Buffering

Battery Fail

Inhibit

(7) Inhibit +

(8) Inhibit ndash

24V DC

Power

Supply

Ready

(1) (2)

+ ndash + ndash + ndash + ndash

N L PE

Buffering

(3) (4)

Battery Fail

(5) (6)

12V DC Battery

(for example 1606-XLSBATASSY1)

+ ndash

DC-UPS

(1606-XLS240-UPS)

24V

IN

12V

BAT

24V

OUT

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 17

CompactLogix 5480 Controllers

Disconnect Wires from the RTBsIf necessary complete these tasks to disconnect wires from any RTB on the controller

1 Turn the screwdriver counter-clockwise to open the terminal

2 Remove the wire

Install Compact 5000 IO ModulesComplete one of the following

bull If you do not use local Compact 5000 IO modules in the system proceed to Install the End Cap on page 18

bull If you use local Compact 5000 IO modules in the system install the modules to the right side of the controller

After the IO modules are installed install the end cap on the right side of the last IO module in the system For more information on how to install the end cap see page 18

For more information on how to install Compact 5000IO modules see the installation instructions available with each Compact 5000 IO module catalog number

Install the End CapYou must install an end cap on the right side of the last module in a CompactLogix 5480 system The end cap covers the exposed interconnections on the last module in the system If you do not install the end cap before powering the system equipment damage or injury from electric shock can result

If you do not intend to install Compact 5000 IO modules to the system before you turn on power to the controller install the end cap

1 Align the end cap with the interlocking pieces on the controller

2 Push the end cap toward the DIN rail until it locks into place

Power the System

After the end cap is installed on the last module in the system turn on power to the MOD power RTB and the SA power RTB

IMPORTANT Consider the following before you power the system

bull Make sure to remove the debris shield from the controller before power-up

bull As noted previously you must install working controller firmware to use the COS on the controller There are two ways to install working firmware The ways are described beginning on page 23

One of the methods to install working controller firmware

uses the SD card that ships with the controller

ndash If you intend to use the SD card to install working

controller firmware go to Use a Secure Digital Card

to Install Controller Firmware on page 24

Complete the steps described in that section apply

power to the controller and return to the next

section that is Set the Network Internet Protocol

(IP) Addresses on page 19

ndash If you do not intend to use the SD card to install

working controller firmware turn on the power now

and proceed to the next section

Top Interlocking

Pieces

End Cap

Bottom Interlocking

Pieces

18 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Set the Network Internet Protocol (IP) AddressesYou must set an IP address on Ethernet ports for the controller to operate on an EtherNetIP network via that port

Out-of-the-box the following applies to Ethernet ports A1 A2 and B1

bull The ports are DHCP-enabled and the IP address is set automatically via a DHCP server

If there is no DHCP server available to set the IP address you must set the IP address manually

bull If ports A1 and A2 are configured to use DLRLinear mode you set only one IP address that is used on both ports

bull Control ports must use unique subnets

When ports A1 and A2 are configured to use DLRLinear mode however they use the same subnet because they are configured as one port

You can use one of the following to set the IP address on the controller when it is in the out-of-the-box condition

bull DHCP server

bull BOOTP DHCP EtherNetIP Commissioning tool version 30200 or later

bull RSLinx Classic software version 41000 or later

bull FactoryTalk Linx software version 61000 or later

bull Logix Designer application version 320100 or later

For more information on how to set or change the IP address on a CompactLogix 5480 controller see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

Connect the Controller to an EtherNetIP Network

Use an RJ45 cable to connect the controller to an EtherNetIP network

1 If needed wire the RJ45 connector as shown

2 Connect RJ45 cables to the controller Ethernet ports

IMPORTANT Before you can connect a CompactLogix 5480 controller to an

EtherNetIP network you must first install the network and

its components

This section assumes that the EtherNetIP network is

installed

Connector Number

Color

1585J 8-pin Cables with Support for 101001000 Mbps

1585J 8-pin Cables with Support for 10100 Mbps

1585J 4-pin Cables with Support for 10100 Mbps

1WhiteOrange

BI_DA+ TxData +

2 Orange BI_DA- TxData -

3WhiteGreen

BI_DB+ Recv Data +

4 Blue BI_DC+ Unused mdash

5 WhiteBlue BI_DC- Unused mdash

6 Green BI_DB- Recv Data -

7WhiteBrown

BI_DD+ Unused mdash

8 Brown BI_DD- Unused mdash

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 19

CompactLogix 5480 Controllers

Remove and Replace the Controller

1 Turn off power to the MOD power and the SA power RTBs

2 If there are local Compact 5000 IO modules in the system remove them If not skip to step 3

3 Disconnect wires from the RTBs

For more information see Disconnect Wires from the RTBs on page 18

4 Pull the RTB handles to remove the RTBs

IMPORTANT When you remove MOD power from the controller you shut down

power to all modules in the CompactLogix 5480 system That is

all system-side is removed When you remove SA power from the

controller all field-side power that is provided by the controller is

removed If SA power that is provided via a 5069-FPD field

potential distributor the system does not lose SA power to the

right of the field potential distributor

In this case you must use a separate power source for the SA

power RTB on the field potential distributor

We strongly recommend that before you remove MOD power or

SA power that you take the appropriate actions to help prevent

unintended consequences that can result from a system power

shutdown

Despite the removal of power from SA RTBs on the controller or

field potential distributor the 5069-OB16 and 5069-OB16F

modules continue to receive field-side power The modules

receive power from an external power source that is connected to

the LA (+) and LA (ndash) module terminals

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

UPS Control RTB

MOD Power RTB

SA Power RTB

20 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

5 Remove all cables from the controller

6 Push down on the front of the DIN rail latches

A click indicates that the DIN rail latches are open

If the DIN rail latches fail to remain in the open position hold them down

7 Pull the controller off the DIN rail

8 Repeat the installation steps that are described beginning at Install the Controller onto the DIN Rail on page 9

9 Apply MOD power and if necessary SA power to the system

Replace the FansThe CompactLogix 5480 controller uses fans at the top and bottom of the controller to help maintain lower operating temperatures when the controller is operating

Fan use includes speed control and monitoring Faults indicate fan operating conditions as follows

bull Minor faults - Triggered when a fan is not operating at the requested speed or if a fan fails to operate at all

In your Logix Designer application project you can use the Minor Faults tab on the Controller Properties dialog box to monitor for these faults

bull Major fault - Triggered if both fans fail and the controller goes over the maximum operating temperature

In this case the controller stops operating

You can order replacement fans Replacement fans come in pairs The fans are unique by position and keyed to help make sure that you install the correct fan in each position

The fans are labeled Fan 1 - Top and Fan 2 - Bottom

Consider the following

bull We recommend that you replace the fans in pairs That is if you replace the one fan we recommend that you replace the other fan too

bull You can replace fans during controller operation The fans support removal and insertion under power

bull Do not remove both fans at once if the controller is operating That is remove a fan and install the replacement fan before you remove the other fan

Remove the Top Fan

1 Push up on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

TIP In your Logix Designer application project you can

use the Major Faults tab on the Controller

Properties dialog box to monitor for this fault

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

R

B

F

Open Position

IMPORTANT If you replace fans while the controller is operating

do not touch live voltage components

TIP If the hinges do not disengage when you push up on the front of the

fan then use a screwdriver as a pry tool

5069-L4200ERMW

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 21

CompactLogix 5480 Controllers

2 Pull the fan out of the slot at the top of the controller

Install the Top Replacement Fan

1 Insert the top replacement fan into the slot at the top of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push down on the top replacement fan until it clicks in place

Remove the Bottom Fan

1 Push the down on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

2 Pull the fan out of the slot at the bottom of the controller

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

TIP If the hinges do not disengage when you push down on the front of

the fan then use a screwdriver as a pry tool

5069-L4200ERMW

5069-L4200ERMW

22 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Bottom Replacement Fan

1 Insert the bottom replacement fan into the slot at the bottom of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push up on the bottom replacement fan until it clicks in place

Use the COS For Windows-based ComputingThe COS on a CompactLogix 5480 controller runs in parallel with the Logix control engine You are not required to use the COS

You can use the following methods to install working controller firmware when the controller is in the out-of-box state

bull ControlFLASHtrade or ControlFLASH Plustrade softwarebull Secure Digital (SD) card

Use a Flash Programming Tool to Install Controller FirmwareYou can use ControlFLASH and ControlFLASH Plus software to install controller firmware

The following requirements apply when you use ControlFLASH or ControlFLASH Plus to install working controller firmware

bull You must use one of the followingndash ControlFLASH software version 150100 or laterndash ControlFLASH Plus version 20000 or later

bull You must use a Linx-based software application with your flash programming toolndash With ControlFLASH software you can use RSLinx

Classic Lite RSLinx Classic RSLinx Enterprise or FactoryTalk Linx

ndash With ControlFLASH Plus software you must use FactoryTalk Linx

Minimum software versions apply with Linx-based software For more information on the minimum software version requirements see the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

5069-L4200ERMW

5069-L4200ERMW

IMPORTANT Before you can use the COS you must install working controller firmware The requirement applies even if you

are not using the controller for real-time control If you do not

install working controller firmware the COS does not start

In the out-of-box state the controller uses firmware revision

1xxx On a CompactLogix 5480 controller the minimum

working controller firmware is revision 32012

TIP We recommend that you connect your peripherals to the

ports that are dedicated to COS use before you install

controller firmware

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 23

CompactLogix 5480 Controllers

Download the Flash Programming Tool

ControlFLASH and ControlFLASH Plus software are available from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

Download the installation files and install the software

Download the Controller Firmware

After the flash programming tool is installed download the controller firmware from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

The initial download is a exe file You use the Rockwell Automation Download Manager to extract a dmk from the downloaded file

Install the Controller Firmware

To install the controller firmware via a flash programming tool you complete the following steps

1 To start the tool click StartgtAll ProgramsgtFlashing Programming ToolsgtControlFLASH or ControlFLASH Plus

2 Follow the prompts to complete the following stepsa Choose the controllerb Select the firmware revisionc Install the controller firmware

A dialog box confirms that the installation was successful

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use a flash programming tool to install controller firmware see the following

bull ControlFLASH Firmware Upgrade Kit User Manual publication 1756-UM105

bull ControlFLASH Plus Quick Start Guide publication CFP-QS001

bull CompactLogix 5480 Controllers User Manual publication 5069-UM002

Use a Secure Digital Card to Install Controller FirmwareYou can use an SD card to install controller firmware CompactLogix 5480 controllers ship with an SD card installed behind the front door on the controller

To use an SD card to install controller firmware complete the following steps

1 Before you turn on power to the controller remove the SD card from the controller

2 Install the SD card into another working CompactLogix 5480 controller that has a Logix Designer application project on it

3 Save the project to the SD card

4 Remove the SD card from the working controller and reinstall it in the new controller

5 Turn on power to the new controller

When the new controller powers up it automatically updates the firmware to the revision that is stored on the SD card

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use the SD card with the controller after valid firmware is installed and the controller is powered see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

IMPORTANT These steps only highlight the major tasks that you

complete to install controller firmware with ControlFLASH

To successfully install controller firmware you must complete other tasks that are not described here

For complete information on how to install controller

firmware see the publications listed at the end of the section

IMPORTANT To install controller firmware on a new CompactLogix 5480

controller via an SD card you must have another controller of

the same type that is already working

The SD card method requires that you save the Logix Designer

application project from the working controller to the SD card

before you use it in the new controller

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

SD Card Slot

24 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpecificationsThis table lists a subset of controller specifications For a complete list of specifications see the CompactLogix 5380 Compact GuardLogixreg 5380 and CompactLogix 5480 Controllers Specifications Technical Data publication 5069-TD002

Environmental Specifications - CompactLogix 5480 Controllers

Attribute 5069-L430ERMW 5069-L450ERMW 5069-4100ERMW 5069-L4200ERMW

Temperature operating

IEC 60068-2-1 (Test Ad Operating Cold)

IEC 60068-2-2 (Test Bd Operating Dry Heat)

IEC 60068-2-14 (Test Na Operating Thermal Shock)

0 degC lt Ta lt +60 degC

(+32 degF lt Ta lt +140 degF)

Temperature surrounding air max 60 degC (140 degF)

Enclosure Type Rating None (open-style)

Voltage and current ratings

MOD Power voltage range 18hellip32V DC

MOD Power power max 72 W

MOD Power current typical 4 A

MOD Power inrush 4 A for 15 ms

MOD Power Passthrough(1) 6 A 18hellip32V DC

MOD Power current rating max10 A

Do not exceed 10 A current draw at the MOD power RTB(4)

SA Power voltage ranges(2) 0hellip32V DC

0hellip240V AC 47hellip63 Hz

SA Power current max (2) 10 mA (DC power)

25 mA (AC power)

SA Power Passthrough(2) (3) 999 A 0hellip32V DC

9975 A 0hellip240V AC 47hellip63 Hz

SA Power current rating max(2) Do not exceed 10 A current draw at the SA power RTB

Isolation voltage

300V (continuous) Basic Insulation Type SA and MOD Power to Backplane

300V (continuous) Basic Insulation Type SA to MOD Power

300V (continuous) Basic Insulation Type Ethernet to Backplane

300V (continuous) Double Insulation Type Ethernet to MOD Power

300V (continuous) Double Insulation Type Ethernet to SA Power

50V (continuous) Functional Insulation Type Ethernet to USB ports and DisplayPort

300V (continuous) Basic Insulation Type USB ports and DisplayPort to Backplane

300V (continuous) Double Insulation Type USB ports and DisplayPort to MOD Power

300V (continuous) Double Insulation Type USB ports and DisplayPort to SA Power

No isolation between Ethernet ports

Type tested at 1500V AC for 60 s

Wire size

5069-RTB4-SCREW 5069-RTB6-SCREW connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 35 mm (014 in) max diameter including insulation single wire connection only

5069-RTB4-UPS connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 29 mm (011 in) max diameter including insulation single wire connection only

Ethernet connections

Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2

Insulation-stripping length 5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 12 mm (047 in)

Terminal block torque5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 04 Nbullm (35 lbbullin)

ATTENTION Do not wire more than two conductors on one RTB terminal

(1) Maximum level of MOD power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(2) SA power specifications are based on the number and type of Compact 5000 IO modules that are used in the system If the set of IO modules that is used in the system require AC and DC voltage you must install a 5069-FPD field

potential distributor to separate the module types

(3) Maximum level of SA power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(4) Remember MOD power usage includes the total power that the controller and local Compact 5000 IO modules use If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000 IO

modules can draw a maximum of 10 A in addition to the current that the controller draws

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 25

CompactLogix 5480 Controllers

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation

You can view or download publications at httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage To order paper copies of technical documentation contact your local Allen-Bradley distributor or Rockwell Automationreg sales representative

Resource Description

CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069-TD002

Provides specifications and other technical data for CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 controllers

CompactLogix 5480 Controllers User Manual publication 5069-UM002 Describes how to configure operate and monitor CompactLogix 5480 controllers

Industrial Automation Wiring and Grounding Guidelines publication 1770-41 Provides general guidelines for installing a Rockwell Automationreg industrial system

Product Certifications website rokautocertifications Provides declarations of conformity certificates and other certification details

26 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB ltFEFF005500740069006c0069007a006500200065007300730061007300200063006f006e00660069006700750072006100e700f50065007300200064006500200066006f0072006d00610020006100200063007200690061007200200064006f00630075006d0065006e0074006f0073002000410064006f0062006500200050004400460020007000610072006100200069006d0070007200650073007300f5006500730020006400650020007100750061006c0069006400610064006500200065006d00200069006d00700072006500730073006f0072006100730020006400650073006b0074006f00700020006500200064006900730070006f00730069007400690076006f0073002000640065002000700072006f00760061002e0020004f007300200064006f00630075006d0065006e0074006f00730020005000440046002000630072006900610064006f007300200070006f00640065006d0020007300650072002000610062006500720074006f007300200063006f006d0020006f0020004100630072006f006200610074002000650020006f002000410064006f00620065002000520065006100640065007200200035002e0030002000650020007600650072007300f50065007300200070006f00730074006500720069006f007200650073002egt SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 15: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

CompactLogix 5480 Controllers

Install the UPS Control RTBInstall the UPS control RTB even if you do not intend to connect uninterruptible power to the controller

1 Hook the bottom of the UPS power RTB on the controller

2 Push the RTB against the controller until you hear a click

3 Push the RTB handle against the RTB until you hear a click

Connect UPS Control Signals

1 Verify that all sources of MOD power and SA power are turned off

2 Verify the followingbull A 24V DC power supply is connected to the 24V IN

terminals on the UPSbull A 12V DC battery is connected to the 12V BAT terminals

on the UPS

For more information see the example graphic on page 17

Connect to the MOD Power RTB from a UPS

1 Daisy chain the wires from these connections on the UPSbull 24V OUT (+)bull Ready (1)bull Buffering (3)bull Battery Fail (5)bull Inhibit (7)

2 Connect one wire to each (+) terminal on the MOD power RTB as shown in the example graphic on page 17a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Daisy chain a wire that is connected to the 24V OUT (ndash) terminal on the UPS and a second wire

4 Connect one wire to each (ndash) terminal on the MOD power RTB a Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

IMPORTANT The UPS terminal labels in this section represent the labels on

a 1606-XLS240-UPS power supply Your UPS terminals can be

labeled differently

5069-L4200ERMW

UPS Control RTB

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 15

CompactLogix 5480 Controllers

Connect to the UPS Control RTB from a UPS

1 Connect a wire from the Ready (2) connection on the UPS to the UPS Ready terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

2 Connect a wire from the Buffering (4) connection on the UPS to the Buffering terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Connect a wire from the Battery Fail (6) connection on the UPS to the Battery Fail terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

4 Connect a wire from the Inhibit (8) connection on the UPS to the Inhibit terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

16 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

This diagram shows a 1606-XLS240-UPS power supply battery that is connected to a CompactLogix 5480 controller

5069-L4200ERMW

UPS Ready

Buffering

Battery Fail

Inhibit

(7) Inhibit +

(8) Inhibit ndash

24V DC

Power

Supply

Ready

(1) (2)

+ ndash + ndash + ndash + ndash

N L PE

Buffering

(3) (4)

Battery Fail

(5) (6)

12V DC Battery

(for example 1606-XLSBATASSY1)

+ ndash

DC-UPS

(1606-XLS240-UPS)

24V

IN

12V

BAT

24V

OUT

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 17

CompactLogix 5480 Controllers

Disconnect Wires from the RTBsIf necessary complete these tasks to disconnect wires from any RTB on the controller

1 Turn the screwdriver counter-clockwise to open the terminal

2 Remove the wire

Install Compact 5000 IO ModulesComplete one of the following

bull If you do not use local Compact 5000 IO modules in the system proceed to Install the End Cap on page 18

bull If you use local Compact 5000 IO modules in the system install the modules to the right side of the controller

After the IO modules are installed install the end cap on the right side of the last IO module in the system For more information on how to install the end cap see page 18

For more information on how to install Compact 5000IO modules see the installation instructions available with each Compact 5000 IO module catalog number

Install the End CapYou must install an end cap on the right side of the last module in a CompactLogix 5480 system The end cap covers the exposed interconnections on the last module in the system If you do not install the end cap before powering the system equipment damage or injury from electric shock can result

If you do not intend to install Compact 5000 IO modules to the system before you turn on power to the controller install the end cap

1 Align the end cap with the interlocking pieces on the controller

2 Push the end cap toward the DIN rail until it locks into place

Power the System

After the end cap is installed on the last module in the system turn on power to the MOD power RTB and the SA power RTB

IMPORTANT Consider the following before you power the system

bull Make sure to remove the debris shield from the controller before power-up

bull As noted previously you must install working controller firmware to use the COS on the controller There are two ways to install working firmware The ways are described beginning on page 23

One of the methods to install working controller firmware

uses the SD card that ships with the controller

ndash If you intend to use the SD card to install working

controller firmware go to Use a Secure Digital Card

to Install Controller Firmware on page 24

Complete the steps described in that section apply

power to the controller and return to the next

section that is Set the Network Internet Protocol

(IP) Addresses on page 19

ndash If you do not intend to use the SD card to install

working controller firmware turn on the power now

and proceed to the next section

Top Interlocking

Pieces

End Cap

Bottom Interlocking

Pieces

18 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Set the Network Internet Protocol (IP) AddressesYou must set an IP address on Ethernet ports for the controller to operate on an EtherNetIP network via that port

Out-of-the-box the following applies to Ethernet ports A1 A2 and B1

bull The ports are DHCP-enabled and the IP address is set automatically via a DHCP server

If there is no DHCP server available to set the IP address you must set the IP address manually

bull If ports A1 and A2 are configured to use DLRLinear mode you set only one IP address that is used on both ports

bull Control ports must use unique subnets

When ports A1 and A2 are configured to use DLRLinear mode however they use the same subnet because they are configured as one port

You can use one of the following to set the IP address on the controller when it is in the out-of-the-box condition

bull DHCP server

bull BOOTP DHCP EtherNetIP Commissioning tool version 30200 or later

bull RSLinx Classic software version 41000 or later

bull FactoryTalk Linx software version 61000 or later

bull Logix Designer application version 320100 or later

For more information on how to set or change the IP address on a CompactLogix 5480 controller see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

Connect the Controller to an EtherNetIP Network

Use an RJ45 cable to connect the controller to an EtherNetIP network

1 If needed wire the RJ45 connector as shown

2 Connect RJ45 cables to the controller Ethernet ports

IMPORTANT Before you can connect a CompactLogix 5480 controller to an

EtherNetIP network you must first install the network and

its components

This section assumes that the EtherNetIP network is

installed

Connector Number

Color

1585J 8-pin Cables with Support for 101001000 Mbps

1585J 8-pin Cables with Support for 10100 Mbps

1585J 4-pin Cables with Support for 10100 Mbps

1WhiteOrange

BI_DA+ TxData +

2 Orange BI_DA- TxData -

3WhiteGreen

BI_DB+ Recv Data +

4 Blue BI_DC+ Unused mdash

5 WhiteBlue BI_DC- Unused mdash

6 Green BI_DB- Recv Data -

7WhiteBrown

BI_DD+ Unused mdash

8 Brown BI_DD- Unused mdash

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 19

CompactLogix 5480 Controllers

Remove and Replace the Controller

1 Turn off power to the MOD power and the SA power RTBs

2 If there are local Compact 5000 IO modules in the system remove them If not skip to step 3

3 Disconnect wires from the RTBs

For more information see Disconnect Wires from the RTBs on page 18

4 Pull the RTB handles to remove the RTBs

IMPORTANT When you remove MOD power from the controller you shut down

power to all modules in the CompactLogix 5480 system That is

all system-side is removed When you remove SA power from the

controller all field-side power that is provided by the controller is

removed If SA power that is provided via a 5069-FPD field

potential distributor the system does not lose SA power to the

right of the field potential distributor

In this case you must use a separate power source for the SA

power RTB on the field potential distributor

We strongly recommend that before you remove MOD power or

SA power that you take the appropriate actions to help prevent

unintended consequences that can result from a system power

shutdown

Despite the removal of power from SA RTBs on the controller or

field potential distributor the 5069-OB16 and 5069-OB16F

modules continue to receive field-side power The modules

receive power from an external power source that is connected to

the LA (+) and LA (ndash) module terminals

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

UPS Control RTB

MOD Power RTB

SA Power RTB

20 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

5 Remove all cables from the controller

6 Push down on the front of the DIN rail latches

A click indicates that the DIN rail latches are open

If the DIN rail latches fail to remain in the open position hold them down

7 Pull the controller off the DIN rail

8 Repeat the installation steps that are described beginning at Install the Controller onto the DIN Rail on page 9

9 Apply MOD power and if necessary SA power to the system

Replace the FansThe CompactLogix 5480 controller uses fans at the top and bottom of the controller to help maintain lower operating temperatures when the controller is operating

Fan use includes speed control and monitoring Faults indicate fan operating conditions as follows

bull Minor faults - Triggered when a fan is not operating at the requested speed or if a fan fails to operate at all

In your Logix Designer application project you can use the Minor Faults tab on the Controller Properties dialog box to monitor for these faults

bull Major fault - Triggered if both fans fail and the controller goes over the maximum operating temperature

In this case the controller stops operating

You can order replacement fans Replacement fans come in pairs The fans are unique by position and keyed to help make sure that you install the correct fan in each position

The fans are labeled Fan 1 - Top and Fan 2 - Bottom

Consider the following

bull We recommend that you replace the fans in pairs That is if you replace the one fan we recommend that you replace the other fan too

bull You can replace fans during controller operation The fans support removal and insertion under power

bull Do not remove both fans at once if the controller is operating That is remove a fan and install the replacement fan before you remove the other fan

Remove the Top Fan

1 Push up on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

TIP In your Logix Designer application project you can

use the Major Faults tab on the Controller

Properties dialog box to monitor for this fault

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

R

B

F

Open Position

IMPORTANT If you replace fans while the controller is operating

do not touch live voltage components

TIP If the hinges do not disengage when you push up on the front of the

fan then use a screwdriver as a pry tool

5069-L4200ERMW

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 21

CompactLogix 5480 Controllers

2 Pull the fan out of the slot at the top of the controller

Install the Top Replacement Fan

1 Insert the top replacement fan into the slot at the top of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push down on the top replacement fan until it clicks in place

Remove the Bottom Fan

1 Push the down on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

2 Pull the fan out of the slot at the bottom of the controller

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

TIP If the hinges do not disengage when you push down on the front of

the fan then use a screwdriver as a pry tool

5069-L4200ERMW

5069-L4200ERMW

22 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Bottom Replacement Fan

1 Insert the bottom replacement fan into the slot at the bottom of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push up on the bottom replacement fan until it clicks in place

Use the COS For Windows-based ComputingThe COS on a CompactLogix 5480 controller runs in parallel with the Logix control engine You are not required to use the COS

You can use the following methods to install working controller firmware when the controller is in the out-of-box state

bull ControlFLASHtrade or ControlFLASH Plustrade softwarebull Secure Digital (SD) card

Use a Flash Programming Tool to Install Controller FirmwareYou can use ControlFLASH and ControlFLASH Plus software to install controller firmware

The following requirements apply when you use ControlFLASH or ControlFLASH Plus to install working controller firmware

bull You must use one of the followingndash ControlFLASH software version 150100 or laterndash ControlFLASH Plus version 20000 or later

bull You must use a Linx-based software application with your flash programming toolndash With ControlFLASH software you can use RSLinx

Classic Lite RSLinx Classic RSLinx Enterprise or FactoryTalk Linx

ndash With ControlFLASH Plus software you must use FactoryTalk Linx

Minimum software versions apply with Linx-based software For more information on the minimum software version requirements see the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

5069-L4200ERMW

5069-L4200ERMW

IMPORTANT Before you can use the COS you must install working controller firmware The requirement applies even if you

are not using the controller for real-time control If you do not

install working controller firmware the COS does not start

In the out-of-box state the controller uses firmware revision

1xxx On a CompactLogix 5480 controller the minimum

working controller firmware is revision 32012

TIP We recommend that you connect your peripherals to the

ports that are dedicated to COS use before you install

controller firmware

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 23

CompactLogix 5480 Controllers

Download the Flash Programming Tool

ControlFLASH and ControlFLASH Plus software are available from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

Download the installation files and install the software

Download the Controller Firmware

After the flash programming tool is installed download the controller firmware from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

The initial download is a exe file You use the Rockwell Automation Download Manager to extract a dmk from the downloaded file

Install the Controller Firmware

To install the controller firmware via a flash programming tool you complete the following steps

1 To start the tool click StartgtAll ProgramsgtFlashing Programming ToolsgtControlFLASH or ControlFLASH Plus

2 Follow the prompts to complete the following stepsa Choose the controllerb Select the firmware revisionc Install the controller firmware

A dialog box confirms that the installation was successful

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use a flash programming tool to install controller firmware see the following

bull ControlFLASH Firmware Upgrade Kit User Manual publication 1756-UM105

bull ControlFLASH Plus Quick Start Guide publication CFP-QS001

bull CompactLogix 5480 Controllers User Manual publication 5069-UM002

Use a Secure Digital Card to Install Controller FirmwareYou can use an SD card to install controller firmware CompactLogix 5480 controllers ship with an SD card installed behind the front door on the controller

To use an SD card to install controller firmware complete the following steps

1 Before you turn on power to the controller remove the SD card from the controller

2 Install the SD card into another working CompactLogix 5480 controller that has a Logix Designer application project on it

3 Save the project to the SD card

4 Remove the SD card from the working controller and reinstall it in the new controller

5 Turn on power to the new controller

When the new controller powers up it automatically updates the firmware to the revision that is stored on the SD card

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use the SD card with the controller after valid firmware is installed and the controller is powered see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

IMPORTANT These steps only highlight the major tasks that you

complete to install controller firmware with ControlFLASH

To successfully install controller firmware you must complete other tasks that are not described here

For complete information on how to install controller

firmware see the publications listed at the end of the section

IMPORTANT To install controller firmware on a new CompactLogix 5480

controller via an SD card you must have another controller of

the same type that is already working

The SD card method requires that you save the Logix Designer

application project from the working controller to the SD card

before you use it in the new controller

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

SD Card Slot

24 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpecificationsThis table lists a subset of controller specifications For a complete list of specifications see the CompactLogix 5380 Compact GuardLogixreg 5380 and CompactLogix 5480 Controllers Specifications Technical Data publication 5069-TD002

Environmental Specifications - CompactLogix 5480 Controllers

Attribute 5069-L430ERMW 5069-L450ERMW 5069-4100ERMW 5069-L4200ERMW

Temperature operating

IEC 60068-2-1 (Test Ad Operating Cold)

IEC 60068-2-2 (Test Bd Operating Dry Heat)

IEC 60068-2-14 (Test Na Operating Thermal Shock)

0 degC lt Ta lt +60 degC

(+32 degF lt Ta lt +140 degF)

Temperature surrounding air max 60 degC (140 degF)

Enclosure Type Rating None (open-style)

Voltage and current ratings

MOD Power voltage range 18hellip32V DC

MOD Power power max 72 W

MOD Power current typical 4 A

MOD Power inrush 4 A for 15 ms

MOD Power Passthrough(1) 6 A 18hellip32V DC

MOD Power current rating max10 A

Do not exceed 10 A current draw at the MOD power RTB(4)

SA Power voltage ranges(2) 0hellip32V DC

0hellip240V AC 47hellip63 Hz

SA Power current max (2) 10 mA (DC power)

25 mA (AC power)

SA Power Passthrough(2) (3) 999 A 0hellip32V DC

9975 A 0hellip240V AC 47hellip63 Hz

SA Power current rating max(2) Do not exceed 10 A current draw at the SA power RTB

Isolation voltage

300V (continuous) Basic Insulation Type SA and MOD Power to Backplane

300V (continuous) Basic Insulation Type SA to MOD Power

300V (continuous) Basic Insulation Type Ethernet to Backplane

300V (continuous) Double Insulation Type Ethernet to MOD Power

300V (continuous) Double Insulation Type Ethernet to SA Power

50V (continuous) Functional Insulation Type Ethernet to USB ports and DisplayPort

300V (continuous) Basic Insulation Type USB ports and DisplayPort to Backplane

300V (continuous) Double Insulation Type USB ports and DisplayPort to MOD Power

300V (continuous) Double Insulation Type USB ports and DisplayPort to SA Power

No isolation between Ethernet ports

Type tested at 1500V AC for 60 s

Wire size

5069-RTB4-SCREW 5069-RTB6-SCREW connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 35 mm (014 in) max diameter including insulation single wire connection only

5069-RTB4-UPS connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 29 mm (011 in) max diameter including insulation single wire connection only

Ethernet connections

Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2

Insulation-stripping length 5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 12 mm (047 in)

Terminal block torque5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 04 Nbullm (35 lbbullin)

ATTENTION Do not wire more than two conductors on one RTB terminal

(1) Maximum level of MOD power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(2) SA power specifications are based on the number and type of Compact 5000 IO modules that are used in the system If the set of IO modules that is used in the system require AC and DC voltage you must install a 5069-FPD field

potential distributor to separate the module types

(3) Maximum level of SA power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(4) Remember MOD power usage includes the total power that the controller and local Compact 5000 IO modules use If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000 IO

modules can draw a maximum of 10 A in addition to the current that the controller draws

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 25

CompactLogix 5480 Controllers

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation

You can view or download publications at httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage To order paper copies of technical documentation contact your local Allen-Bradley distributor or Rockwell Automationreg sales representative

Resource Description

CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069-TD002

Provides specifications and other technical data for CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 controllers

CompactLogix 5480 Controllers User Manual publication 5069-UM002 Describes how to configure operate and monitor CompactLogix 5480 controllers

Industrial Automation Wiring and Grounding Guidelines publication 1770-41 Provides general guidelines for installing a Rockwell Automationreg industrial system

Product Certifications website rokautocertifications Provides declarations of conformity certificates and other certification details

26 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU ltFEFF00560065007200770065006e00640065006e0020005300690065002000640069006500730065002000450069006e007300740065006c006c0075006e00670065006e0020007a0075006d002000450072007300740065006c006c0065006e00200076006f006e002000410064006f006200650020005000440046002d0044006f006b0075006d0065006e00740065006e002c00200076006f006e002000640065006e0065006e002000530069006500200068006f00630068007700650072007400690067006500200044007200750063006b006500200061007500660020004400650073006b0074006f0070002d0044007200750063006b00650072006e00200075006e0064002000500072006f006f0066002d00470065007200e400740065006e002000650072007a0065007500670065006e0020006d00f60063006800740065006e002e002000450072007300740065006c006c007400650020005000440046002d0044006f006b0075006d0065006e007400650020006b00f6006e006e0065006e0020006d006900740020004100630072006f00620061007400200075006e0064002000410064006f00620065002000520065006100640065007200200035002e00300020006f0064006500720020006800f600680065007200200067006500f600660066006e00650074002000770065007200640065006e002egt ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 16: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

CompactLogix 5480 Controllers

Connect to the UPS Control RTB from a UPS

1 Connect a wire from the Ready (2) connection on the UPS to the UPS Ready terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

2 Connect a wire from the Buffering (4) connection on the UPS to the Buffering terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

3 Connect a wire from the Battery Fail (6) connection on the UPS to the Battery Fail terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

4 Connect a wire from the Inhibit (8) connection on the UPS to the Inhibit terminal on the UPS control RTBa Insert the wire into the terminalb Turn the screwdriver to close the terminal on the wire

The screw torque is 04 Nbullm (35 lbbullin)

16 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

This diagram shows a 1606-XLS240-UPS power supply battery that is connected to a CompactLogix 5480 controller

5069-L4200ERMW

UPS Ready

Buffering

Battery Fail

Inhibit

(7) Inhibit +

(8) Inhibit ndash

24V DC

Power

Supply

Ready

(1) (2)

+ ndash + ndash + ndash + ndash

N L PE

Buffering

(3) (4)

Battery Fail

(5) (6)

12V DC Battery

(for example 1606-XLSBATASSY1)

+ ndash

DC-UPS

(1606-XLS240-UPS)

24V

IN

12V

BAT

24V

OUT

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 17

CompactLogix 5480 Controllers

Disconnect Wires from the RTBsIf necessary complete these tasks to disconnect wires from any RTB on the controller

1 Turn the screwdriver counter-clockwise to open the terminal

2 Remove the wire

Install Compact 5000 IO ModulesComplete one of the following

bull If you do not use local Compact 5000 IO modules in the system proceed to Install the End Cap on page 18

bull If you use local Compact 5000 IO modules in the system install the modules to the right side of the controller

After the IO modules are installed install the end cap on the right side of the last IO module in the system For more information on how to install the end cap see page 18

For more information on how to install Compact 5000IO modules see the installation instructions available with each Compact 5000 IO module catalog number

Install the End CapYou must install an end cap on the right side of the last module in a CompactLogix 5480 system The end cap covers the exposed interconnections on the last module in the system If you do not install the end cap before powering the system equipment damage or injury from electric shock can result

If you do not intend to install Compact 5000 IO modules to the system before you turn on power to the controller install the end cap

1 Align the end cap with the interlocking pieces on the controller

2 Push the end cap toward the DIN rail until it locks into place

Power the System

After the end cap is installed on the last module in the system turn on power to the MOD power RTB and the SA power RTB

IMPORTANT Consider the following before you power the system

bull Make sure to remove the debris shield from the controller before power-up

bull As noted previously you must install working controller firmware to use the COS on the controller There are two ways to install working firmware The ways are described beginning on page 23

One of the methods to install working controller firmware

uses the SD card that ships with the controller

ndash If you intend to use the SD card to install working

controller firmware go to Use a Secure Digital Card

to Install Controller Firmware on page 24

Complete the steps described in that section apply

power to the controller and return to the next

section that is Set the Network Internet Protocol

(IP) Addresses on page 19

ndash If you do not intend to use the SD card to install

working controller firmware turn on the power now

and proceed to the next section

Top Interlocking

Pieces

End Cap

Bottom Interlocking

Pieces

18 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Set the Network Internet Protocol (IP) AddressesYou must set an IP address on Ethernet ports for the controller to operate on an EtherNetIP network via that port

Out-of-the-box the following applies to Ethernet ports A1 A2 and B1

bull The ports are DHCP-enabled and the IP address is set automatically via a DHCP server

If there is no DHCP server available to set the IP address you must set the IP address manually

bull If ports A1 and A2 are configured to use DLRLinear mode you set only one IP address that is used on both ports

bull Control ports must use unique subnets

When ports A1 and A2 are configured to use DLRLinear mode however they use the same subnet because they are configured as one port

You can use one of the following to set the IP address on the controller when it is in the out-of-the-box condition

bull DHCP server

bull BOOTP DHCP EtherNetIP Commissioning tool version 30200 or later

bull RSLinx Classic software version 41000 or later

bull FactoryTalk Linx software version 61000 or later

bull Logix Designer application version 320100 or later

For more information on how to set or change the IP address on a CompactLogix 5480 controller see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

Connect the Controller to an EtherNetIP Network

Use an RJ45 cable to connect the controller to an EtherNetIP network

1 If needed wire the RJ45 connector as shown

2 Connect RJ45 cables to the controller Ethernet ports

IMPORTANT Before you can connect a CompactLogix 5480 controller to an

EtherNetIP network you must first install the network and

its components

This section assumes that the EtherNetIP network is

installed

Connector Number

Color

1585J 8-pin Cables with Support for 101001000 Mbps

1585J 8-pin Cables with Support for 10100 Mbps

1585J 4-pin Cables with Support for 10100 Mbps

1WhiteOrange

BI_DA+ TxData +

2 Orange BI_DA- TxData -

3WhiteGreen

BI_DB+ Recv Data +

4 Blue BI_DC+ Unused mdash

5 WhiteBlue BI_DC- Unused mdash

6 Green BI_DB- Recv Data -

7WhiteBrown

BI_DD+ Unused mdash

8 Brown BI_DD- Unused mdash

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 19

CompactLogix 5480 Controllers

Remove and Replace the Controller

1 Turn off power to the MOD power and the SA power RTBs

2 If there are local Compact 5000 IO modules in the system remove them If not skip to step 3

3 Disconnect wires from the RTBs

For more information see Disconnect Wires from the RTBs on page 18

4 Pull the RTB handles to remove the RTBs

IMPORTANT When you remove MOD power from the controller you shut down

power to all modules in the CompactLogix 5480 system That is

all system-side is removed When you remove SA power from the

controller all field-side power that is provided by the controller is

removed If SA power that is provided via a 5069-FPD field

potential distributor the system does not lose SA power to the

right of the field potential distributor

In this case you must use a separate power source for the SA

power RTB on the field potential distributor

We strongly recommend that before you remove MOD power or

SA power that you take the appropriate actions to help prevent

unintended consequences that can result from a system power

shutdown

Despite the removal of power from SA RTBs on the controller or

field potential distributor the 5069-OB16 and 5069-OB16F

modules continue to receive field-side power The modules

receive power from an external power source that is connected to

the LA (+) and LA (ndash) module terminals

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

UPS Control RTB

MOD Power RTB

SA Power RTB

20 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

5 Remove all cables from the controller

6 Push down on the front of the DIN rail latches

A click indicates that the DIN rail latches are open

If the DIN rail latches fail to remain in the open position hold them down

7 Pull the controller off the DIN rail

8 Repeat the installation steps that are described beginning at Install the Controller onto the DIN Rail on page 9

9 Apply MOD power and if necessary SA power to the system

Replace the FansThe CompactLogix 5480 controller uses fans at the top and bottom of the controller to help maintain lower operating temperatures when the controller is operating

Fan use includes speed control and monitoring Faults indicate fan operating conditions as follows

bull Minor faults - Triggered when a fan is not operating at the requested speed or if a fan fails to operate at all

In your Logix Designer application project you can use the Minor Faults tab on the Controller Properties dialog box to monitor for these faults

bull Major fault - Triggered if both fans fail and the controller goes over the maximum operating temperature

In this case the controller stops operating

You can order replacement fans Replacement fans come in pairs The fans are unique by position and keyed to help make sure that you install the correct fan in each position

The fans are labeled Fan 1 - Top and Fan 2 - Bottom

Consider the following

bull We recommend that you replace the fans in pairs That is if you replace the one fan we recommend that you replace the other fan too

bull You can replace fans during controller operation The fans support removal and insertion under power

bull Do not remove both fans at once if the controller is operating That is remove a fan and install the replacement fan before you remove the other fan

Remove the Top Fan

1 Push up on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

TIP In your Logix Designer application project you can

use the Major Faults tab on the Controller

Properties dialog box to monitor for this fault

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

R

B

F

Open Position

IMPORTANT If you replace fans while the controller is operating

do not touch live voltage components

TIP If the hinges do not disengage when you push up on the front of the

fan then use a screwdriver as a pry tool

5069-L4200ERMW

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 21

CompactLogix 5480 Controllers

2 Pull the fan out of the slot at the top of the controller

Install the Top Replacement Fan

1 Insert the top replacement fan into the slot at the top of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push down on the top replacement fan until it clicks in place

Remove the Bottom Fan

1 Push the down on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

2 Pull the fan out of the slot at the bottom of the controller

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

TIP If the hinges do not disengage when you push down on the front of

the fan then use a screwdriver as a pry tool

5069-L4200ERMW

5069-L4200ERMW

22 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Bottom Replacement Fan

1 Insert the bottom replacement fan into the slot at the bottom of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push up on the bottom replacement fan until it clicks in place

Use the COS For Windows-based ComputingThe COS on a CompactLogix 5480 controller runs in parallel with the Logix control engine You are not required to use the COS

You can use the following methods to install working controller firmware when the controller is in the out-of-box state

bull ControlFLASHtrade or ControlFLASH Plustrade softwarebull Secure Digital (SD) card

Use a Flash Programming Tool to Install Controller FirmwareYou can use ControlFLASH and ControlFLASH Plus software to install controller firmware

The following requirements apply when you use ControlFLASH or ControlFLASH Plus to install working controller firmware

bull You must use one of the followingndash ControlFLASH software version 150100 or laterndash ControlFLASH Plus version 20000 or later

bull You must use a Linx-based software application with your flash programming toolndash With ControlFLASH software you can use RSLinx

Classic Lite RSLinx Classic RSLinx Enterprise or FactoryTalk Linx

ndash With ControlFLASH Plus software you must use FactoryTalk Linx

Minimum software versions apply with Linx-based software For more information on the minimum software version requirements see the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

5069-L4200ERMW

5069-L4200ERMW

IMPORTANT Before you can use the COS you must install working controller firmware The requirement applies even if you

are not using the controller for real-time control If you do not

install working controller firmware the COS does not start

In the out-of-box state the controller uses firmware revision

1xxx On a CompactLogix 5480 controller the minimum

working controller firmware is revision 32012

TIP We recommend that you connect your peripherals to the

ports that are dedicated to COS use before you install

controller firmware

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 23

CompactLogix 5480 Controllers

Download the Flash Programming Tool

ControlFLASH and ControlFLASH Plus software are available from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

Download the installation files and install the software

Download the Controller Firmware

After the flash programming tool is installed download the controller firmware from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

The initial download is a exe file You use the Rockwell Automation Download Manager to extract a dmk from the downloaded file

Install the Controller Firmware

To install the controller firmware via a flash programming tool you complete the following steps

1 To start the tool click StartgtAll ProgramsgtFlashing Programming ToolsgtControlFLASH or ControlFLASH Plus

2 Follow the prompts to complete the following stepsa Choose the controllerb Select the firmware revisionc Install the controller firmware

A dialog box confirms that the installation was successful

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use a flash programming tool to install controller firmware see the following

bull ControlFLASH Firmware Upgrade Kit User Manual publication 1756-UM105

bull ControlFLASH Plus Quick Start Guide publication CFP-QS001

bull CompactLogix 5480 Controllers User Manual publication 5069-UM002

Use a Secure Digital Card to Install Controller FirmwareYou can use an SD card to install controller firmware CompactLogix 5480 controllers ship with an SD card installed behind the front door on the controller

To use an SD card to install controller firmware complete the following steps

1 Before you turn on power to the controller remove the SD card from the controller

2 Install the SD card into another working CompactLogix 5480 controller that has a Logix Designer application project on it

3 Save the project to the SD card

4 Remove the SD card from the working controller and reinstall it in the new controller

5 Turn on power to the new controller

When the new controller powers up it automatically updates the firmware to the revision that is stored on the SD card

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use the SD card with the controller after valid firmware is installed and the controller is powered see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

IMPORTANT These steps only highlight the major tasks that you

complete to install controller firmware with ControlFLASH

To successfully install controller firmware you must complete other tasks that are not described here

For complete information on how to install controller

firmware see the publications listed at the end of the section

IMPORTANT To install controller firmware on a new CompactLogix 5480

controller via an SD card you must have another controller of

the same type that is already working

The SD card method requires that you save the Logix Designer

application project from the working controller to the SD card

before you use it in the new controller

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

SD Card Slot

24 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpecificationsThis table lists a subset of controller specifications For a complete list of specifications see the CompactLogix 5380 Compact GuardLogixreg 5380 and CompactLogix 5480 Controllers Specifications Technical Data publication 5069-TD002

Environmental Specifications - CompactLogix 5480 Controllers

Attribute 5069-L430ERMW 5069-L450ERMW 5069-4100ERMW 5069-L4200ERMW

Temperature operating

IEC 60068-2-1 (Test Ad Operating Cold)

IEC 60068-2-2 (Test Bd Operating Dry Heat)

IEC 60068-2-14 (Test Na Operating Thermal Shock)

0 degC lt Ta lt +60 degC

(+32 degF lt Ta lt +140 degF)

Temperature surrounding air max 60 degC (140 degF)

Enclosure Type Rating None (open-style)

Voltage and current ratings

MOD Power voltage range 18hellip32V DC

MOD Power power max 72 W

MOD Power current typical 4 A

MOD Power inrush 4 A for 15 ms

MOD Power Passthrough(1) 6 A 18hellip32V DC

MOD Power current rating max10 A

Do not exceed 10 A current draw at the MOD power RTB(4)

SA Power voltage ranges(2) 0hellip32V DC

0hellip240V AC 47hellip63 Hz

SA Power current max (2) 10 mA (DC power)

25 mA (AC power)

SA Power Passthrough(2) (3) 999 A 0hellip32V DC

9975 A 0hellip240V AC 47hellip63 Hz

SA Power current rating max(2) Do not exceed 10 A current draw at the SA power RTB

Isolation voltage

300V (continuous) Basic Insulation Type SA and MOD Power to Backplane

300V (continuous) Basic Insulation Type SA to MOD Power

300V (continuous) Basic Insulation Type Ethernet to Backplane

300V (continuous) Double Insulation Type Ethernet to MOD Power

300V (continuous) Double Insulation Type Ethernet to SA Power

50V (continuous) Functional Insulation Type Ethernet to USB ports and DisplayPort

300V (continuous) Basic Insulation Type USB ports and DisplayPort to Backplane

300V (continuous) Double Insulation Type USB ports and DisplayPort to MOD Power

300V (continuous) Double Insulation Type USB ports and DisplayPort to SA Power

No isolation between Ethernet ports

Type tested at 1500V AC for 60 s

Wire size

5069-RTB4-SCREW 5069-RTB6-SCREW connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 35 mm (014 in) max diameter including insulation single wire connection only

5069-RTB4-UPS connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 29 mm (011 in) max diameter including insulation single wire connection only

Ethernet connections

Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2

Insulation-stripping length 5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 12 mm (047 in)

Terminal block torque5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 04 Nbullm (35 lbbullin)

ATTENTION Do not wire more than two conductors on one RTB terminal

(1) Maximum level of MOD power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(2) SA power specifications are based on the number and type of Compact 5000 IO modules that are used in the system If the set of IO modules that is used in the system require AC and DC voltage you must install a 5069-FPD field

potential distributor to separate the module types

(3) Maximum level of SA power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(4) Remember MOD power usage includes the total power that the controller and local Compact 5000 IO modules use If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000 IO

modules can draw a maximum of 10 A in addition to the current that the controller draws

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 25

CompactLogix 5480 Controllers

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation

You can view or download publications at httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage To order paper copies of technical documentation contact your local Allen-Bradley distributor or Rockwell Automationreg sales representative

Resource Description

CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069-TD002

Provides specifications and other technical data for CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 controllers

CompactLogix 5480 Controllers User Manual publication 5069-UM002 Describes how to configure operate and monitor CompactLogix 5480 controllers

Industrial Automation Wiring and Grounding Guidelines publication 1770-41 Provides general guidelines for installing a Rockwell Automationreg industrial system

Product Certifications website rokautocertifications Provides declarations of conformity certificates and other certification details

26 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 17: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

CompactLogix 5480 Controllers

This diagram shows a 1606-XLS240-UPS power supply battery that is connected to a CompactLogix 5480 controller

5069-L4200ERMW

UPS Ready

Buffering

Battery Fail

Inhibit

(7) Inhibit +

(8) Inhibit ndash

24V DC

Power

Supply

Ready

(1) (2)

+ ndash + ndash + ndash + ndash

N L PE

Buffering

(3) (4)

Battery Fail

(5) (6)

12V DC Battery

(for example 1606-XLSBATASSY1)

+ ndash

DC-UPS

(1606-XLS240-UPS)

24V

IN

12V

BAT

24V

OUT

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 17

CompactLogix 5480 Controllers

Disconnect Wires from the RTBsIf necessary complete these tasks to disconnect wires from any RTB on the controller

1 Turn the screwdriver counter-clockwise to open the terminal

2 Remove the wire

Install Compact 5000 IO ModulesComplete one of the following

bull If you do not use local Compact 5000 IO modules in the system proceed to Install the End Cap on page 18

bull If you use local Compact 5000 IO modules in the system install the modules to the right side of the controller

After the IO modules are installed install the end cap on the right side of the last IO module in the system For more information on how to install the end cap see page 18

For more information on how to install Compact 5000IO modules see the installation instructions available with each Compact 5000 IO module catalog number

Install the End CapYou must install an end cap on the right side of the last module in a CompactLogix 5480 system The end cap covers the exposed interconnections on the last module in the system If you do not install the end cap before powering the system equipment damage or injury from electric shock can result

If you do not intend to install Compact 5000 IO modules to the system before you turn on power to the controller install the end cap

1 Align the end cap with the interlocking pieces on the controller

2 Push the end cap toward the DIN rail until it locks into place

Power the System

After the end cap is installed on the last module in the system turn on power to the MOD power RTB and the SA power RTB

IMPORTANT Consider the following before you power the system

bull Make sure to remove the debris shield from the controller before power-up

bull As noted previously you must install working controller firmware to use the COS on the controller There are two ways to install working firmware The ways are described beginning on page 23

One of the methods to install working controller firmware

uses the SD card that ships with the controller

ndash If you intend to use the SD card to install working

controller firmware go to Use a Secure Digital Card

to Install Controller Firmware on page 24

Complete the steps described in that section apply

power to the controller and return to the next

section that is Set the Network Internet Protocol

(IP) Addresses on page 19

ndash If you do not intend to use the SD card to install

working controller firmware turn on the power now

and proceed to the next section

Top Interlocking

Pieces

End Cap

Bottom Interlocking

Pieces

18 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Set the Network Internet Protocol (IP) AddressesYou must set an IP address on Ethernet ports for the controller to operate on an EtherNetIP network via that port

Out-of-the-box the following applies to Ethernet ports A1 A2 and B1

bull The ports are DHCP-enabled and the IP address is set automatically via a DHCP server

If there is no DHCP server available to set the IP address you must set the IP address manually

bull If ports A1 and A2 are configured to use DLRLinear mode you set only one IP address that is used on both ports

bull Control ports must use unique subnets

When ports A1 and A2 are configured to use DLRLinear mode however they use the same subnet because they are configured as one port

You can use one of the following to set the IP address on the controller when it is in the out-of-the-box condition

bull DHCP server

bull BOOTP DHCP EtherNetIP Commissioning tool version 30200 or later

bull RSLinx Classic software version 41000 or later

bull FactoryTalk Linx software version 61000 or later

bull Logix Designer application version 320100 or later

For more information on how to set or change the IP address on a CompactLogix 5480 controller see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

Connect the Controller to an EtherNetIP Network

Use an RJ45 cable to connect the controller to an EtherNetIP network

1 If needed wire the RJ45 connector as shown

2 Connect RJ45 cables to the controller Ethernet ports

IMPORTANT Before you can connect a CompactLogix 5480 controller to an

EtherNetIP network you must first install the network and

its components

This section assumes that the EtherNetIP network is

installed

Connector Number

Color

1585J 8-pin Cables with Support for 101001000 Mbps

1585J 8-pin Cables with Support for 10100 Mbps

1585J 4-pin Cables with Support for 10100 Mbps

1WhiteOrange

BI_DA+ TxData +

2 Orange BI_DA- TxData -

3WhiteGreen

BI_DB+ Recv Data +

4 Blue BI_DC+ Unused mdash

5 WhiteBlue BI_DC- Unused mdash

6 Green BI_DB- Recv Data -

7WhiteBrown

BI_DD+ Unused mdash

8 Brown BI_DD- Unused mdash

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 19

CompactLogix 5480 Controllers

Remove and Replace the Controller

1 Turn off power to the MOD power and the SA power RTBs

2 If there are local Compact 5000 IO modules in the system remove them If not skip to step 3

3 Disconnect wires from the RTBs

For more information see Disconnect Wires from the RTBs on page 18

4 Pull the RTB handles to remove the RTBs

IMPORTANT When you remove MOD power from the controller you shut down

power to all modules in the CompactLogix 5480 system That is

all system-side is removed When you remove SA power from the

controller all field-side power that is provided by the controller is

removed If SA power that is provided via a 5069-FPD field

potential distributor the system does not lose SA power to the

right of the field potential distributor

In this case you must use a separate power source for the SA

power RTB on the field potential distributor

We strongly recommend that before you remove MOD power or

SA power that you take the appropriate actions to help prevent

unintended consequences that can result from a system power

shutdown

Despite the removal of power from SA RTBs on the controller or

field potential distributor the 5069-OB16 and 5069-OB16F

modules continue to receive field-side power The modules

receive power from an external power source that is connected to

the LA (+) and LA (ndash) module terminals

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

UPS Control RTB

MOD Power RTB

SA Power RTB

20 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

5 Remove all cables from the controller

6 Push down on the front of the DIN rail latches

A click indicates that the DIN rail latches are open

If the DIN rail latches fail to remain in the open position hold them down

7 Pull the controller off the DIN rail

8 Repeat the installation steps that are described beginning at Install the Controller onto the DIN Rail on page 9

9 Apply MOD power and if necessary SA power to the system

Replace the FansThe CompactLogix 5480 controller uses fans at the top and bottom of the controller to help maintain lower operating temperatures when the controller is operating

Fan use includes speed control and monitoring Faults indicate fan operating conditions as follows

bull Minor faults - Triggered when a fan is not operating at the requested speed or if a fan fails to operate at all

In your Logix Designer application project you can use the Minor Faults tab on the Controller Properties dialog box to monitor for these faults

bull Major fault - Triggered if both fans fail and the controller goes over the maximum operating temperature

In this case the controller stops operating

You can order replacement fans Replacement fans come in pairs The fans are unique by position and keyed to help make sure that you install the correct fan in each position

The fans are labeled Fan 1 - Top and Fan 2 - Bottom

Consider the following

bull We recommend that you replace the fans in pairs That is if you replace the one fan we recommend that you replace the other fan too

bull You can replace fans during controller operation The fans support removal and insertion under power

bull Do not remove both fans at once if the controller is operating That is remove a fan and install the replacement fan before you remove the other fan

Remove the Top Fan

1 Push up on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

TIP In your Logix Designer application project you can

use the Major Faults tab on the Controller

Properties dialog box to monitor for this fault

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

R

B

F

Open Position

IMPORTANT If you replace fans while the controller is operating

do not touch live voltage components

TIP If the hinges do not disengage when you push up on the front of the

fan then use a screwdriver as a pry tool

5069-L4200ERMW

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 21

CompactLogix 5480 Controllers

2 Pull the fan out of the slot at the top of the controller

Install the Top Replacement Fan

1 Insert the top replacement fan into the slot at the top of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push down on the top replacement fan until it clicks in place

Remove the Bottom Fan

1 Push the down on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

2 Pull the fan out of the slot at the bottom of the controller

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

TIP If the hinges do not disengage when you push down on the front of

the fan then use a screwdriver as a pry tool

5069-L4200ERMW

5069-L4200ERMW

22 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Bottom Replacement Fan

1 Insert the bottom replacement fan into the slot at the bottom of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push up on the bottom replacement fan until it clicks in place

Use the COS For Windows-based ComputingThe COS on a CompactLogix 5480 controller runs in parallel with the Logix control engine You are not required to use the COS

You can use the following methods to install working controller firmware when the controller is in the out-of-box state

bull ControlFLASHtrade or ControlFLASH Plustrade softwarebull Secure Digital (SD) card

Use a Flash Programming Tool to Install Controller FirmwareYou can use ControlFLASH and ControlFLASH Plus software to install controller firmware

The following requirements apply when you use ControlFLASH or ControlFLASH Plus to install working controller firmware

bull You must use one of the followingndash ControlFLASH software version 150100 or laterndash ControlFLASH Plus version 20000 or later

bull You must use a Linx-based software application with your flash programming toolndash With ControlFLASH software you can use RSLinx

Classic Lite RSLinx Classic RSLinx Enterprise or FactoryTalk Linx

ndash With ControlFLASH Plus software you must use FactoryTalk Linx

Minimum software versions apply with Linx-based software For more information on the minimum software version requirements see the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

5069-L4200ERMW

5069-L4200ERMW

IMPORTANT Before you can use the COS you must install working controller firmware The requirement applies even if you

are not using the controller for real-time control If you do not

install working controller firmware the COS does not start

In the out-of-box state the controller uses firmware revision

1xxx On a CompactLogix 5480 controller the minimum

working controller firmware is revision 32012

TIP We recommend that you connect your peripherals to the

ports that are dedicated to COS use before you install

controller firmware

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 23

CompactLogix 5480 Controllers

Download the Flash Programming Tool

ControlFLASH and ControlFLASH Plus software are available from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

Download the installation files and install the software

Download the Controller Firmware

After the flash programming tool is installed download the controller firmware from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

The initial download is a exe file You use the Rockwell Automation Download Manager to extract a dmk from the downloaded file

Install the Controller Firmware

To install the controller firmware via a flash programming tool you complete the following steps

1 To start the tool click StartgtAll ProgramsgtFlashing Programming ToolsgtControlFLASH or ControlFLASH Plus

2 Follow the prompts to complete the following stepsa Choose the controllerb Select the firmware revisionc Install the controller firmware

A dialog box confirms that the installation was successful

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use a flash programming tool to install controller firmware see the following

bull ControlFLASH Firmware Upgrade Kit User Manual publication 1756-UM105

bull ControlFLASH Plus Quick Start Guide publication CFP-QS001

bull CompactLogix 5480 Controllers User Manual publication 5069-UM002

Use a Secure Digital Card to Install Controller FirmwareYou can use an SD card to install controller firmware CompactLogix 5480 controllers ship with an SD card installed behind the front door on the controller

To use an SD card to install controller firmware complete the following steps

1 Before you turn on power to the controller remove the SD card from the controller

2 Install the SD card into another working CompactLogix 5480 controller that has a Logix Designer application project on it

3 Save the project to the SD card

4 Remove the SD card from the working controller and reinstall it in the new controller

5 Turn on power to the new controller

When the new controller powers up it automatically updates the firmware to the revision that is stored on the SD card

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use the SD card with the controller after valid firmware is installed and the controller is powered see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

IMPORTANT These steps only highlight the major tasks that you

complete to install controller firmware with ControlFLASH

To successfully install controller firmware you must complete other tasks that are not described here

For complete information on how to install controller

firmware see the publications listed at the end of the section

IMPORTANT To install controller firmware on a new CompactLogix 5480

controller via an SD card you must have another controller of

the same type that is already working

The SD card method requires that you save the Logix Designer

application project from the working controller to the SD card

before you use it in the new controller

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

SD Card Slot

24 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpecificationsThis table lists a subset of controller specifications For a complete list of specifications see the CompactLogix 5380 Compact GuardLogixreg 5380 and CompactLogix 5480 Controllers Specifications Technical Data publication 5069-TD002

Environmental Specifications - CompactLogix 5480 Controllers

Attribute 5069-L430ERMW 5069-L450ERMW 5069-4100ERMW 5069-L4200ERMW

Temperature operating

IEC 60068-2-1 (Test Ad Operating Cold)

IEC 60068-2-2 (Test Bd Operating Dry Heat)

IEC 60068-2-14 (Test Na Operating Thermal Shock)

0 degC lt Ta lt +60 degC

(+32 degF lt Ta lt +140 degF)

Temperature surrounding air max 60 degC (140 degF)

Enclosure Type Rating None (open-style)

Voltage and current ratings

MOD Power voltage range 18hellip32V DC

MOD Power power max 72 W

MOD Power current typical 4 A

MOD Power inrush 4 A for 15 ms

MOD Power Passthrough(1) 6 A 18hellip32V DC

MOD Power current rating max10 A

Do not exceed 10 A current draw at the MOD power RTB(4)

SA Power voltage ranges(2) 0hellip32V DC

0hellip240V AC 47hellip63 Hz

SA Power current max (2) 10 mA (DC power)

25 mA (AC power)

SA Power Passthrough(2) (3) 999 A 0hellip32V DC

9975 A 0hellip240V AC 47hellip63 Hz

SA Power current rating max(2) Do not exceed 10 A current draw at the SA power RTB

Isolation voltage

300V (continuous) Basic Insulation Type SA and MOD Power to Backplane

300V (continuous) Basic Insulation Type SA to MOD Power

300V (continuous) Basic Insulation Type Ethernet to Backplane

300V (continuous) Double Insulation Type Ethernet to MOD Power

300V (continuous) Double Insulation Type Ethernet to SA Power

50V (continuous) Functional Insulation Type Ethernet to USB ports and DisplayPort

300V (continuous) Basic Insulation Type USB ports and DisplayPort to Backplane

300V (continuous) Double Insulation Type USB ports and DisplayPort to MOD Power

300V (continuous) Double Insulation Type USB ports and DisplayPort to SA Power

No isolation between Ethernet ports

Type tested at 1500V AC for 60 s

Wire size

5069-RTB4-SCREW 5069-RTB6-SCREW connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 35 mm (014 in) max diameter including insulation single wire connection only

5069-RTB4-UPS connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 29 mm (011 in) max diameter including insulation single wire connection only

Ethernet connections

Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2

Insulation-stripping length 5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 12 mm (047 in)

Terminal block torque5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 04 Nbullm (35 lbbullin)

ATTENTION Do not wire more than two conductors on one RTB terminal

(1) Maximum level of MOD power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(2) SA power specifications are based on the number and type of Compact 5000 IO modules that are used in the system If the set of IO modules that is used in the system require AC and DC voltage you must install a 5069-FPD field

potential distributor to separate the module types

(3) Maximum level of SA power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(4) Remember MOD power usage includes the total power that the controller and local Compact 5000 IO modules use If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000 IO

modules can draw a maximum of 10 A in addition to the current that the controller draws

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 25

CompactLogix 5480 Controllers

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation

You can view or download publications at httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage To order paper copies of technical documentation contact your local Allen-Bradley distributor or Rockwell Automationreg sales representative

Resource Description

CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069-TD002

Provides specifications and other technical data for CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 controllers

CompactLogix 5480 Controllers User Manual publication 5069-UM002 Describes how to configure operate and monitor CompactLogix 5480 controllers

Industrial Automation Wiring and Grounding Guidelines publication 1770-41 Provides general guidelines for installing a Rockwell Automationreg industrial system

Product Certifications website rokautocertifications Provides declarations of conformity certificates and other certification details

26 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE ltFEFF0041006e007600e4006e00640020006400650020006800e4007200200069006e0073007400e4006c006c006e0069006e006700610072006e00610020006f006d002000640075002000760069006c006c00200073006b006100700061002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740020006600f600720020006b00760061006c00690074006500740073007500740073006b0072006900660074006500720020007000e5002000760061006e006c00690067006100200073006b0072006900760061007200650020006f006300680020006600f600720020006b006f007200720065006b007400750072002e002000200053006b006100700061006400650020005000440046002d0064006f006b0075006d0065006e00740020006b0061006e002000f600700070006e00610073002000690020004100630072006f0062006100740020006f00630068002000410064006f00620065002000520065006100640065007200200035002e00300020006f00630068002000730065006e006100720065002egt ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 18: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

CompactLogix 5480 Controllers

Disconnect Wires from the RTBsIf necessary complete these tasks to disconnect wires from any RTB on the controller

1 Turn the screwdriver counter-clockwise to open the terminal

2 Remove the wire

Install Compact 5000 IO ModulesComplete one of the following

bull If you do not use local Compact 5000 IO modules in the system proceed to Install the End Cap on page 18

bull If you use local Compact 5000 IO modules in the system install the modules to the right side of the controller

After the IO modules are installed install the end cap on the right side of the last IO module in the system For more information on how to install the end cap see page 18

For more information on how to install Compact 5000IO modules see the installation instructions available with each Compact 5000 IO module catalog number

Install the End CapYou must install an end cap on the right side of the last module in a CompactLogix 5480 system The end cap covers the exposed interconnections on the last module in the system If you do not install the end cap before powering the system equipment damage or injury from electric shock can result

If you do not intend to install Compact 5000 IO modules to the system before you turn on power to the controller install the end cap

1 Align the end cap with the interlocking pieces on the controller

2 Push the end cap toward the DIN rail until it locks into place

Power the System

After the end cap is installed on the last module in the system turn on power to the MOD power RTB and the SA power RTB

IMPORTANT Consider the following before you power the system

bull Make sure to remove the debris shield from the controller before power-up

bull As noted previously you must install working controller firmware to use the COS on the controller There are two ways to install working firmware The ways are described beginning on page 23

One of the methods to install working controller firmware

uses the SD card that ships with the controller

ndash If you intend to use the SD card to install working

controller firmware go to Use a Secure Digital Card

to Install Controller Firmware on page 24

Complete the steps described in that section apply

power to the controller and return to the next

section that is Set the Network Internet Protocol

(IP) Addresses on page 19

ndash If you do not intend to use the SD card to install

working controller firmware turn on the power now

and proceed to the next section

Top Interlocking

Pieces

End Cap

Bottom Interlocking

Pieces

18 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Set the Network Internet Protocol (IP) AddressesYou must set an IP address on Ethernet ports for the controller to operate on an EtherNetIP network via that port

Out-of-the-box the following applies to Ethernet ports A1 A2 and B1

bull The ports are DHCP-enabled and the IP address is set automatically via a DHCP server

If there is no DHCP server available to set the IP address you must set the IP address manually

bull If ports A1 and A2 are configured to use DLRLinear mode you set only one IP address that is used on both ports

bull Control ports must use unique subnets

When ports A1 and A2 are configured to use DLRLinear mode however they use the same subnet because they are configured as one port

You can use one of the following to set the IP address on the controller when it is in the out-of-the-box condition

bull DHCP server

bull BOOTP DHCP EtherNetIP Commissioning tool version 30200 or later

bull RSLinx Classic software version 41000 or later

bull FactoryTalk Linx software version 61000 or later

bull Logix Designer application version 320100 or later

For more information on how to set or change the IP address on a CompactLogix 5480 controller see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

Connect the Controller to an EtherNetIP Network

Use an RJ45 cable to connect the controller to an EtherNetIP network

1 If needed wire the RJ45 connector as shown

2 Connect RJ45 cables to the controller Ethernet ports

IMPORTANT Before you can connect a CompactLogix 5480 controller to an

EtherNetIP network you must first install the network and

its components

This section assumes that the EtherNetIP network is

installed

Connector Number

Color

1585J 8-pin Cables with Support for 101001000 Mbps

1585J 8-pin Cables with Support for 10100 Mbps

1585J 4-pin Cables with Support for 10100 Mbps

1WhiteOrange

BI_DA+ TxData +

2 Orange BI_DA- TxData -

3WhiteGreen

BI_DB+ Recv Data +

4 Blue BI_DC+ Unused mdash

5 WhiteBlue BI_DC- Unused mdash

6 Green BI_DB- Recv Data -

7WhiteBrown

BI_DD+ Unused mdash

8 Brown BI_DD- Unused mdash

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 19

CompactLogix 5480 Controllers

Remove and Replace the Controller

1 Turn off power to the MOD power and the SA power RTBs

2 If there are local Compact 5000 IO modules in the system remove them If not skip to step 3

3 Disconnect wires from the RTBs

For more information see Disconnect Wires from the RTBs on page 18

4 Pull the RTB handles to remove the RTBs

IMPORTANT When you remove MOD power from the controller you shut down

power to all modules in the CompactLogix 5480 system That is

all system-side is removed When you remove SA power from the

controller all field-side power that is provided by the controller is

removed If SA power that is provided via a 5069-FPD field

potential distributor the system does not lose SA power to the

right of the field potential distributor

In this case you must use a separate power source for the SA

power RTB on the field potential distributor

We strongly recommend that before you remove MOD power or

SA power that you take the appropriate actions to help prevent

unintended consequences that can result from a system power

shutdown

Despite the removal of power from SA RTBs on the controller or

field potential distributor the 5069-OB16 and 5069-OB16F

modules continue to receive field-side power The modules

receive power from an external power source that is connected to

the LA (+) and LA (ndash) module terminals

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

UPS Control RTB

MOD Power RTB

SA Power RTB

20 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

5 Remove all cables from the controller

6 Push down on the front of the DIN rail latches

A click indicates that the DIN rail latches are open

If the DIN rail latches fail to remain in the open position hold them down

7 Pull the controller off the DIN rail

8 Repeat the installation steps that are described beginning at Install the Controller onto the DIN Rail on page 9

9 Apply MOD power and if necessary SA power to the system

Replace the FansThe CompactLogix 5480 controller uses fans at the top and bottom of the controller to help maintain lower operating temperatures when the controller is operating

Fan use includes speed control and monitoring Faults indicate fan operating conditions as follows

bull Minor faults - Triggered when a fan is not operating at the requested speed or if a fan fails to operate at all

In your Logix Designer application project you can use the Minor Faults tab on the Controller Properties dialog box to monitor for these faults

bull Major fault - Triggered if both fans fail and the controller goes over the maximum operating temperature

In this case the controller stops operating

You can order replacement fans Replacement fans come in pairs The fans are unique by position and keyed to help make sure that you install the correct fan in each position

The fans are labeled Fan 1 - Top and Fan 2 - Bottom

Consider the following

bull We recommend that you replace the fans in pairs That is if you replace the one fan we recommend that you replace the other fan too

bull You can replace fans during controller operation The fans support removal and insertion under power

bull Do not remove both fans at once if the controller is operating That is remove a fan and install the replacement fan before you remove the other fan

Remove the Top Fan

1 Push up on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

TIP In your Logix Designer application project you can

use the Major Faults tab on the Controller

Properties dialog box to monitor for this fault

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

R

B

F

Open Position

IMPORTANT If you replace fans while the controller is operating

do not touch live voltage components

TIP If the hinges do not disengage when you push up on the front of the

fan then use a screwdriver as a pry tool

5069-L4200ERMW

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 21

CompactLogix 5480 Controllers

2 Pull the fan out of the slot at the top of the controller

Install the Top Replacement Fan

1 Insert the top replacement fan into the slot at the top of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push down on the top replacement fan until it clicks in place

Remove the Bottom Fan

1 Push the down on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

2 Pull the fan out of the slot at the bottom of the controller

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

TIP If the hinges do not disengage when you push down on the front of

the fan then use a screwdriver as a pry tool

5069-L4200ERMW

5069-L4200ERMW

22 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Bottom Replacement Fan

1 Insert the bottom replacement fan into the slot at the bottom of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push up on the bottom replacement fan until it clicks in place

Use the COS For Windows-based ComputingThe COS on a CompactLogix 5480 controller runs in parallel with the Logix control engine You are not required to use the COS

You can use the following methods to install working controller firmware when the controller is in the out-of-box state

bull ControlFLASHtrade or ControlFLASH Plustrade softwarebull Secure Digital (SD) card

Use a Flash Programming Tool to Install Controller FirmwareYou can use ControlFLASH and ControlFLASH Plus software to install controller firmware

The following requirements apply when you use ControlFLASH or ControlFLASH Plus to install working controller firmware

bull You must use one of the followingndash ControlFLASH software version 150100 or laterndash ControlFLASH Plus version 20000 or later

bull You must use a Linx-based software application with your flash programming toolndash With ControlFLASH software you can use RSLinx

Classic Lite RSLinx Classic RSLinx Enterprise or FactoryTalk Linx

ndash With ControlFLASH Plus software you must use FactoryTalk Linx

Minimum software versions apply with Linx-based software For more information on the minimum software version requirements see the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

5069-L4200ERMW

5069-L4200ERMW

IMPORTANT Before you can use the COS you must install working controller firmware The requirement applies even if you

are not using the controller for real-time control If you do not

install working controller firmware the COS does not start

In the out-of-box state the controller uses firmware revision

1xxx On a CompactLogix 5480 controller the minimum

working controller firmware is revision 32012

TIP We recommend that you connect your peripherals to the

ports that are dedicated to COS use before you install

controller firmware

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 23

CompactLogix 5480 Controllers

Download the Flash Programming Tool

ControlFLASH and ControlFLASH Plus software are available from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

Download the installation files and install the software

Download the Controller Firmware

After the flash programming tool is installed download the controller firmware from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

The initial download is a exe file You use the Rockwell Automation Download Manager to extract a dmk from the downloaded file

Install the Controller Firmware

To install the controller firmware via a flash programming tool you complete the following steps

1 To start the tool click StartgtAll ProgramsgtFlashing Programming ToolsgtControlFLASH or ControlFLASH Plus

2 Follow the prompts to complete the following stepsa Choose the controllerb Select the firmware revisionc Install the controller firmware

A dialog box confirms that the installation was successful

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use a flash programming tool to install controller firmware see the following

bull ControlFLASH Firmware Upgrade Kit User Manual publication 1756-UM105

bull ControlFLASH Plus Quick Start Guide publication CFP-QS001

bull CompactLogix 5480 Controllers User Manual publication 5069-UM002

Use a Secure Digital Card to Install Controller FirmwareYou can use an SD card to install controller firmware CompactLogix 5480 controllers ship with an SD card installed behind the front door on the controller

To use an SD card to install controller firmware complete the following steps

1 Before you turn on power to the controller remove the SD card from the controller

2 Install the SD card into another working CompactLogix 5480 controller that has a Logix Designer application project on it

3 Save the project to the SD card

4 Remove the SD card from the working controller and reinstall it in the new controller

5 Turn on power to the new controller

When the new controller powers up it automatically updates the firmware to the revision that is stored on the SD card

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use the SD card with the controller after valid firmware is installed and the controller is powered see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

IMPORTANT These steps only highlight the major tasks that you

complete to install controller firmware with ControlFLASH

To successfully install controller firmware you must complete other tasks that are not described here

For complete information on how to install controller

firmware see the publications listed at the end of the section

IMPORTANT To install controller firmware on a new CompactLogix 5480

controller via an SD card you must have another controller of

the same type that is already working

The SD card method requires that you save the Logix Designer

application project from the working controller to the SD card

before you use it in the new controller

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

SD Card Slot

24 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpecificationsThis table lists a subset of controller specifications For a complete list of specifications see the CompactLogix 5380 Compact GuardLogixreg 5380 and CompactLogix 5480 Controllers Specifications Technical Data publication 5069-TD002

Environmental Specifications - CompactLogix 5480 Controllers

Attribute 5069-L430ERMW 5069-L450ERMW 5069-4100ERMW 5069-L4200ERMW

Temperature operating

IEC 60068-2-1 (Test Ad Operating Cold)

IEC 60068-2-2 (Test Bd Operating Dry Heat)

IEC 60068-2-14 (Test Na Operating Thermal Shock)

0 degC lt Ta lt +60 degC

(+32 degF lt Ta lt +140 degF)

Temperature surrounding air max 60 degC (140 degF)

Enclosure Type Rating None (open-style)

Voltage and current ratings

MOD Power voltage range 18hellip32V DC

MOD Power power max 72 W

MOD Power current typical 4 A

MOD Power inrush 4 A for 15 ms

MOD Power Passthrough(1) 6 A 18hellip32V DC

MOD Power current rating max10 A

Do not exceed 10 A current draw at the MOD power RTB(4)

SA Power voltage ranges(2) 0hellip32V DC

0hellip240V AC 47hellip63 Hz

SA Power current max (2) 10 mA (DC power)

25 mA (AC power)

SA Power Passthrough(2) (3) 999 A 0hellip32V DC

9975 A 0hellip240V AC 47hellip63 Hz

SA Power current rating max(2) Do not exceed 10 A current draw at the SA power RTB

Isolation voltage

300V (continuous) Basic Insulation Type SA and MOD Power to Backplane

300V (continuous) Basic Insulation Type SA to MOD Power

300V (continuous) Basic Insulation Type Ethernet to Backplane

300V (continuous) Double Insulation Type Ethernet to MOD Power

300V (continuous) Double Insulation Type Ethernet to SA Power

50V (continuous) Functional Insulation Type Ethernet to USB ports and DisplayPort

300V (continuous) Basic Insulation Type USB ports and DisplayPort to Backplane

300V (continuous) Double Insulation Type USB ports and DisplayPort to MOD Power

300V (continuous) Double Insulation Type USB ports and DisplayPort to SA Power

No isolation between Ethernet ports

Type tested at 1500V AC for 60 s

Wire size

5069-RTB4-SCREW 5069-RTB6-SCREW connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 35 mm (014 in) max diameter including insulation single wire connection only

5069-RTB4-UPS connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 29 mm (011 in) max diameter including insulation single wire connection only

Ethernet connections

Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2

Insulation-stripping length 5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 12 mm (047 in)

Terminal block torque5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 04 Nbullm (35 lbbullin)

ATTENTION Do not wire more than two conductors on one RTB terminal

(1) Maximum level of MOD power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(2) SA power specifications are based on the number and type of Compact 5000 IO modules that are used in the system If the set of IO modules that is used in the system require AC and DC voltage you must install a 5069-FPD field

potential distributor to separate the module types

(3) Maximum level of SA power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(4) Remember MOD power usage includes the total power that the controller and local Compact 5000 IO modules use If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000 IO

modules can draw a maximum of 10 A in addition to the current that the controller draws

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 25

CompactLogix 5480 Controllers

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation

You can view or download publications at httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage To order paper copies of technical documentation contact your local Allen-Bradley distributor or Rockwell Automationreg sales representative

Resource Description

CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069-TD002

Provides specifications and other technical data for CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 controllers

CompactLogix 5480 Controllers User Manual publication 5069-UM002 Describes how to configure operate and monitor CompactLogix 5480 controllers

Industrial Automation Wiring and Grounding Guidelines publication 1770-41 Provides general guidelines for installing a Rockwell Automationreg industrial system

Product Certifications website rokautocertifications Provides declarations of conformity certificates and other certification details

26 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 19: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

CompactLogix 5480 Controllers

Set the Network Internet Protocol (IP) AddressesYou must set an IP address on Ethernet ports for the controller to operate on an EtherNetIP network via that port

Out-of-the-box the following applies to Ethernet ports A1 A2 and B1

bull The ports are DHCP-enabled and the IP address is set automatically via a DHCP server

If there is no DHCP server available to set the IP address you must set the IP address manually

bull If ports A1 and A2 are configured to use DLRLinear mode you set only one IP address that is used on both ports

bull Control ports must use unique subnets

When ports A1 and A2 are configured to use DLRLinear mode however they use the same subnet because they are configured as one port

You can use one of the following to set the IP address on the controller when it is in the out-of-the-box condition

bull DHCP server

bull BOOTP DHCP EtherNetIP Commissioning tool version 30200 or later

bull RSLinx Classic software version 41000 or later

bull FactoryTalk Linx software version 61000 or later

bull Logix Designer application version 320100 or later

For more information on how to set or change the IP address on a CompactLogix 5480 controller see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

Connect the Controller to an EtherNetIP Network

Use an RJ45 cable to connect the controller to an EtherNetIP network

1 If needed wire the RJ45 connector as shown

2 Connect RJ45 cables to the controller Ethernet ports

IMPORTANT Before you can connect a CompactLogix 5480 controller to an

EtherNetIP network you must first install the network and

its components

This section assumes that the EtherNetIP network is

installed

Connector Number

Color

1585J 8-pin Cables with Support for 101001000 Mbps

1585J 8-pin Cables with Support for 10100 Mbps

1585J 4-pin Cables with Support for 10100 Mbps

1WhiteOrange

BI_DA+ TxData +

2 Orange BI_DA- TxData -

3WhiteGreen

BI_DB+ Recv Data +

4 Blue BI_DC+ Unused mdash

5 WhiteBlue BI_DC- Unused mdash

6 Green BI_DB- Recv Data -

7WhiteBrown

BI_DD+ Unused mdash

8 Brown BI_DD- Unused mdash

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 19

CompactLogix 5480 Controllers

Remove and Replace the Controller

1 Turn off power to the MOD power and the SA power RTBs

2 If there are local Compact 5000 IO modules in the system remove them If not skip to step 3

3 Disconnect wires from the RTBs

For more information see Disconnect Wires from the RTBs on page 18

4 Pull the RTB handles to remove the RTBs

IMPORTANT When you remove MOD power from the controller you shut down

power to all modules in the CompactLogix 5480 system That is

all system-side is removed When you remove SA power from the

controller all field-side power that is provided by the controller is

removed If SA power that is provided via a 5069-FPD field

potential distributor the system does not lose SA power to the

right of the field potential distributor

In this case you must use a separate power source for the SA

power RTB on the field potential distributor

We strongly recommend that before you remove MOD power or

SA power that you take the appropriate actions to help prevent

unintended consequences that can result from a system power

shutdown

Despite the removal of power from SA RTBs on the controller or

field potential distributor the 5069-OB16 and 5069-OB16F

modules continue to receive field-side power The modules

receive power from an external power source that is connected to

the LA (+) and LA (ndash) module terminals

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

UPS Control RTB

MOD Power RTB

SA Power RTB

20 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

5 Remove all cables from the controller

6 Push down on the front of the DIN rail latches

A click indicates that the DIN rail latches are open

If the DIN rail latches fail to remain in the open position hold them down

7 Pull the controller off the DIN rail

8 Repeat the installation steps that are described beginning at Install the Controller onto the DIN Rail on page 9

9 Apply MOD power and if necessary SA power to the system

Replace the FansThe CompactLogix 5480 controller uses fans at the top and bottom of the controller to help maintain lower operating temperatures when the controller is operating

Fan use includes speed control and monitoring Faults indicate fan operating conditions as follows

bull Minor faults - Triggered when a fan is not operating at the requested speed or if a fan fails to operate at all

In your Logix Designer application project you can use the Minor Faults tab on the Controller Properties dialog box to monitor for these faults

bull Major fault - Triggered if both fans fail and the controller goes over the maximum operating temperature

In this case the controller stops operating

You can order replacement fans Replacement fans come in pairs The fans are unique by position and keyed to help make sure that you install the correct fan in each position

The fans are labeled Fan 1 - Top and Fan 2 - Bottom

Consider the following

bull We recommend that you replace the fans in pairs That is if you replace the one fan we recommend that you replace the other fan too

bull You can replace fans during controller operation The fans support removal and insertion under power

bull Do not remove both fans at once if the controller is operating That is remove a fan and install the replacement fan before you remove the other fan

Remove the Top Fan

1 Push up on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

TIP In your Logix Designer application project you can

use the Major Faults tab on the Controller

Properties dialog box to monitor for this fault

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

R

B

F

Open Position

IMPORTANT If you replace fans while the controller is operating

do not touch live voltage components

TIP If the hinges do not disengage when you push up on the front of the

fan then use a screwdriver as a pry tool

5069-L4200ERMW

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 21

CompactLogix 5480 Controllers

2 Pull the fan out of the slot at the top of the controller

Install the Top Replacement Fan

1 Insert the top replacement fan into the slot at the top of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push down on the top replacement fan until it clicks in place

Remove the Bottom Fan

1 Push the down on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

2 Pull the fan out of the slot at the bottom of the controller

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

TIP If the hinges do not disengage when you push down on the front of

the fan then use a screwdriver as a pry tool

5069-L4200ERMW

5069-L4200ERMW

22 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Bottom Replacement Fan

1 Insert the bottom replacement fan into the slot at the bottom of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push up on the bottom replacement fan until it clicks in place

Use the COS For Windows-based ComputingThe COS on a CompactLogix 5480 controller runs in parallel with the Logix control engine You are not required to use the COS

You can use the following methods to install working controller firmware when the controller is in the out-of-box state

bull ControlFLASHtrade or ControlFLASH Plustrade softwarebull Secure Digital (SD) card

Use a Flash Programming Tool to Install Controller FirmwareYou can use ControlFLASH and ControlFLASH Plus software to install controller firmware

The following requirements apply when you use ControlFLASH or ControlFLASH Plus to install working controller firmware

bull You must use one of the followingndash ControlFLASH software version 150100 or laterndash ControlFLASH Plus version 20000 or later

bull You must use a Linx-based software application with your flash programming toolndash With ControlFLASH software you can use RSLinx

Classic Lite RSLinx Classic RSLinx Enterprise or FactoryTalk Linx

ndash With ControlFLASH Plus software you must use FactoryTalk Linx

Minimum software versions apply with Linx-based software For more information on the minimum software version requirements see the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

5069-L4200ERMW

5069-L4200ERMW

IMPORTANT Before you can use the COS you must install working controller firmware The requirement applies even if you

are not using the controller for real-time control If you do not

install working controller firmware the COS does not start

In the out-of-box state the controller uses firmware revision

1xxx On a CompactLogix 5480 controller the minimum

working controller firmware is revision 32012

TIP We recommend that you connect your peripherals to the

ports that are dedicated to COS use before you install

controller firmware

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 23

CompactLogix 5480 Controllers

Download the Flash Programming Tool

ControlFLASH and ControlFLASH Plus software are available from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

Download the installation files and install the software

Download the Controller Firmware

After the flash programming tool is installed download the controller firmware from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

The initial download is a exe file You use the Rockwell Automation Download Manager to extract a dmk from the downloaded file

Install the Controller Firmware

To install the controller firmware via a flash programming tool you complete the following steps

1 To start the tool click StartgtAll ProgramsgtFlashing Programming ToolsgtControlFLASH or ControlFLASH Plus

2 Follow the prompts to complete the following stepsa Choose the controllerb Select the firmware revisionc Install the controller firmware

A dialog box confirms that the installation was successful

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use a flash programming tool to install controller firmware see the following

bull ControlFLASH Firmware Upgrade Kit User Manual publication 1756-UM105

bull ControlFLASH Plus Quick Start Guide publication CFP-QS001

bull CompactLogix 5480 Controllers User Manual publication 5069-UM002

Use a Secure Digital Card to Install Controller FirmwareYou can use an SD card to install controller firmware CompactLogix 5480 controllers ship with an SD card installed behind the front door on the controller

To use an SD card to install controller firmware complete the following steps

1 Before you turn on power to the controller remove the SD card from the controller

2 Install the SD card into another working CompactLogix 5480 controller that has a Logix Designer application project on it

3 Save the project to the SD card

4 Remove the SD card from the working controller and reinstall it in the new controller

5 Turn on power to the new controller

When the new controller powers up it automatically updates the firmware to the revision that is stored on the SD card

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use the SD card with the controller after valid firmware is installed and the controller is powered see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

IMPORTANT These steps only highlight the major tasks that you

complete to install controller firmware with ControlFLASH

To successfully install controller firmware you must complete other tasks that are not described here

For complete information on how to install controller

firmware see the publications listed at the end of the section

IMPORTANT To install controller firmware on a new CompactLogix 5480

controller via an SD card you must have another controller of

the same type that is already working

The SD card method requires that you save the Logix Designer

application project from the working controller to the SD card

before you use it in the new controller

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

SD Card Slot

24 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpecificationsThis table lists a subset of controller specifications For a complete list of specifications see the CompactLogix 5380 Compact GuardLogixreg 5380 and CompactLogix 5480 Controllers Specifications Technical Data publication 5069-TD002

Environmental Specifications - CompactLogix 5480 Controllers

Attribute 5069-L430ERMW 5069-L450ERMW 5069-4100ERMW 5069-L4200ERMW

Temperature operating

IEC 60068-2-1 (Test Ad Operating Cold)

IEC 60068-2-2 (Test Bd Operating Dry Heat)

IEC 60068-2-14 (Test Na Operating Thermal Shock)

0 degC lt Ta lt +60 degC

(+32 degF lt Ta lt +140 degF)

Temperature surrounding air max 60 degC (140 degF)

Enclosure Type Rating None (open-style)

Voltage and current ratings

MOD Power voltage range 18hellip32V DC

MOD Power power max 72 W

MOD Power current typical 4 A

MOD Power inrush 4 A for 15 ms

MOD Power Passthrough(1) 6 A 18hellip32V DC

MOD Power current rating max10 A

Do not exceed 10 A current draw at the MOD power RTB(4)

SA Power voltage ranges(2) 0hellip32V DC

0hellip240V AC 47hellip63 Hz

SA Power current max (2) 10 mA (DC power)

25 mA (AC power)

SA Power Passthrough(2) (3) 999 A 0hellip32V DC

9975 A 0hellip240V AC 47hellip63 Hz

SA Power current rating max(2) Do not exceed 10 A current draw at the SA power RTB

Isolation voltage

300V (continuous) Basic Insulation Type SA and MOD Power to Backplane

300V (continuous) Basic Insulation Type SA to MOD Power

300V (continuous) Basic Insulation Type Ethernet to Backplane

300V (continuous) Double Insulation Type Ethernet to MOD Power

300V (continuous) Double Insulation Type Ethernet to SA Power

50V (continuous) Functional Insulation Type Ethernet to USB ports and DisplayPort

300V (continuous) Basic Insulation Type USB ports and DisplayPort to Backplane

300V (continuous) Double Insulation Type USB ports and DisplayPort to MOD Power

300V (continuous) Double Insulation Type USB ports and DisplayPort to SA Power

No isolation between Ethernet ports

Type tested at 1500V AC for 60 s

Wire size

5069-RTB4-SCREW 5069-RTB6-SCREW connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 35 mm (014 in) max diameter including insulation single wire connection only

5069-RTB4-UPS connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 29 mm (011 in) max diameter including insulation single wire connection only

Ethernet connections

Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2

Insulation-stripping length 5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 12 mm (047 in)

Terminal block torque5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 04 Nbullm (35 lbbullin)

ATTENTION Do not wire more than two conductors on one RTB terminal

(1) Maximum level of MOD power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(2) SA power specifications are based on the number and type of Compact 5000 IO modules that are used in the system If the set of IO modules that is used in the system require AC and DC voltage you must install a 5069-FPD field

potential distributor to separate the module types

(3) Maximum level of SA power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(4) Remember MOD power usage includes the total power that the controller and local Compact 5000 IO modules use If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000 IO

modules can draw a maximum of 10 A in addition to the current that the controller draws

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 25

CompactLogix 5480 Controllers

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation

You can view or download publications at httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage To order paper copies of technical documentation contact your local Allen-Bradley distributor or Rockwell Automationreg sales representative

Resource Description

CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069-TD002

Provides specifications and other technical data for CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 controllers

CompactLogix 5480 Controllers User Manual publication 5069-UM002 Describes how to configure operate and monitor CompactLogix 5480 controllers

Industrial Automation Wiring and Grounding Guidelines publication 1770-41 Provides general guidelines for installing a Rockwell Automationreg industrial system

Product Certifications website rokautocertifications Provides declarations of conformity certificates and other certification details

26 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE ltFEFF0041006e007600e4006e00640020006400650020006800e4007200200069006e0073007400e4006c006c006e0069006e006700610072006e00610020006f006d002000640075002000760069006c006c00200073006b006100700061002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740020006600f600720020006b00760061006c00690074006500740073007500740073006b0072006900660074006500720020007000e5002000760061006e006c00690067006100200073006b0072006900760061007200650020006f006300680020006600f600720020006b006f007200720065006b007400750072002e002000200053006b006100700061006400650020005000440046002d0064006f006b0075006d0065006e00740020006b0061006e002000f600700070006e00610073002000690020004100630072006f0062006100740020006f00630068002000410064006f00620065002000520065006100640065007200200035002e00300020006f00630068002000730065006e006100720065002egt ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 20: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

CompactLogix 5480 Controllers

Remove and Replace the Controller

1 Turn off power to the MOD power and the SA power RTBs

2 If there are local Compact 5000 IO modules in the system remove them If not skip to step 3

3 Disconnect wires from the RTBs

For more information see Disconnect Wires from the RTBs on page 18

4 Pull the RTB handles to remove the RTBs

IMPORTANT When you remove MOD power from the controller you shut down

power to all modules in the CompactLogix 5480 system That is

all system-side is removed When you remove SA power from the

controller all field-side power that is provided by the controller is

removed If SA power that is provided via a 5069-FPD field

potential distributor the system does not lose SA power to the

right of the field potential distributor

In this case you must use a separate power source for the SA

power RTB on the field potential distributor

We strongly recommend that before you remove MOD power or

SA power that you take the appropriate actions to help prevent

unintended consequences that can result from a system power

shutdown

Despite the removal of power from SA RTBs on the controller or

field potential distributor the 5069-OB16 and 5069-OB16F

modules continue to receive field-side power The modules

receive power from an external power source that is connected to

the LA (+) and LA (ndash) module terminals

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

UPS Control RTB

MOD Power RTB

SA Power RTB

20 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

5 Remove all cables from the controller

6 Push down on the front of the DIN rail latches

A click indicates that the DIN rail latches are open

If the DIN rail latches fail to remain in the open position hold them down

7 Pull the controller off the DIN rail

8 Repeat the installation steps that are described beginning at Install the Controller onto the DIN Rail on page 9

9 Apply MOD power and if necessary SA power to the system

Replace the FansThe CompactLogix 5480 controller uses fans at the top and bottom of the controller to help maintain lower operating temperatures when the controller is operating

Fan use includes speed control and monitoring Faults indicate fan operating conditions as follows

bull Minor faults - Triggered when a fan is not operating at the requested speed or if a fan fails to operate at all

In your Logix Designer application project you can use the Minor Faults tab on the Controller Properties dialog box to monitor for these faults

bull Major fault - Triggered if both fans fail and the controller goes over the maximum operating temperature

In this case the controller stops operating

You can order replacement fans Replacement fans come in pairs The fans are unique by position and keyed to help make sure that you install the correct fan in each position

The fans are labeled Fan 1 - Top and Fan 2 - Bottom

Consider the following

bull We recommend that you replace the fans in pairs That is if you replace the one fan we recommend that you replace the other fan too

bull You can replace fans during controller operation The fans support removal and insertion under power

bull Do not remove both fans at once if the controller is operating That is remove a fan and install the replacement fan before you remove the other fan

Remove the Top Fan

1 Push up on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

TIP In your Logix Designer application project you can

use the Major Faults tab on the Controller

Properties dialog box to monitor for this fault

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

R

B

F

Open Position

IMPORTANT If you replace fans while the controller is operating

do not touch live voltage components

TIP If the hinges do not disengage when you push up on the front of the

fan then use a screwdriver as a pry tool

5069-L4200ERMW

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 21

CompactLogix 5480 Controllers

2 Pull the fan out of the slot at the top of the controller

Install the Top Replacement Fan

1 Insert the top replacement fan into the slot at the top of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push down on the top replacement fan until it clicks in place

Remove the Bottom Fan

1 Push the down on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

2 Pull the fan out of the slot at the bottom of the controller

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

TIP If the hinges do not disengage when you push down on the front of

the fan then use a screwdriver as a pry tool

5069-L4200ERMW

5069-L4200ERMW

22 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Bottom Replacement Fan

1 Insert the bottom replacement fan into the slot at the bottom of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push up on the bottom replacement fan until it clicks in place

Use the COS For Windows-based ComputingThe COS on a CompactLogix 5480 controller runs in parallel with the Logix control engine You are not required to use the COS

You can use the following methods to install working controller firmware when the controller is in the out-of-box state

bull ControlFLASHtrade or ControlFLASH Plustrade softwarebull Secure Digital (SD) card

Use a Flash Programming Tool to Install Controller FirmwareYou can use ControlFLASH and ControlFLASH Plus software to install controller firmware

The following requirements apply when you use ControlFLASH or ControlFLASH Plus to install working controller firmware

bull You must use one of the followingndash ControlFLASH software version 150100 or laterndash ControlFLASH Plus version 20000 or later

bull You must use a Linx-based software application with your flash programming toolndash With ControlFLASH software you can use RSLinx

Classic Lite RSLinx Classic RSLinx Enterprise or FactoryTalk Linx

ndash With ControlFLASH Plus software you must use FactoryTalk Linx

Minimum software versions apply with Linx-based software For more information on the minimum software version requirements see the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

5069-L4200ERMW

5069-L4200ERMW

IMPORTANT Before you can use the COS you must install working controller firmware The requirement applies even if you

are not using the controller for real-time control If you do not

install working controller firmware the COS does not start

In the out-of-box state the controller uses firmware revision

1xxx On a CompactLogix 5480 controller the minimum

working controller firmware is revision 32012

TIP We recommend that you connect your peripherals to the

ports that are dedicated to COS use before you install

controller firmware

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 23

CompactLogix 5480 Controllers

Download the Flash Programming Tool

ControlFLASH and ControlFLASH Plus software are available from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

Download the installation files and install the software

Download the Controller Firmware

After the flash programming tool is installed download the controller firmware from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

The initial download is a exe file You use the Rockwell Automation Download Manager to extract a dmk from the downloaded file

Install the Controller Firmware

To install the controller firmware via a flash programming tool you complete the following steps

1 To start the tool click StartgtAll ProgramsgtFlashing Programming ToolsgtControlFLASH or ControlFLASH Plus

2 Follow the prompts to complete the following stepsa Choose the controllerb Select the firmware revisionc Install the controller firmware

A dialog box confirms that the installation was successful

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use a flash programming tool to install controller firmware see the following

bull ControlFLASH Firmware Upgrade Kit User Manual publication 1756-UM105

bull ControlFLASH Plus Quick Start Guide publication CFP-QS001

bull CompactLogix 5480 Controllers User Manual publication 5069-UM002

Use a Secure Digital Card to Install Controller FirmwareYou can use an SD card to install controller firmware CompactLogix 5480 controllers ship with an SD card installed behind the front door on the controller

To use an SD card to install controller firmware complete the following steps

1 Before you turn on power to the controller remove the SD card from the controller

2 Install the SD card into another working CompactLogix 5480 controller that has a Logix Designer application project on it

3 Save the project to the SD card

4 Remove the SD card from the working controller and reinstall it in the new controller

5 Turn on power to the new controller

When the new controller powers up it automatically updates the firmware to the revision that is stored on the SD card

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use the SD card with the controller after valid firmware is installed and the controller is powered see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

IMPORTANT These steps only highlight the major tasks that you

complete to install controller firmware with ControlFLASH

To successfully install controller firmware you must complete other tasks that are not described here

For complete information on how to install controller

firmware see the publications listed at the end of the section

IMPORTANT To install controller firmware on a new CompactLogix 5480

controller via an SD card you must have another controller of

the same type that is already working

The SD card method requires that you save the Logix Designer

application project from the working controller to the SD card

before you use it in the new controller

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

SD Card Slot

24 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpecificationsThis table lists a subset of controller specifications For a complete list of specifications see the CompactLogix 5380 Compact GuardLogixreg 5380 and CompactLogix 5480 Controllers Specifications Technical Data publication 5069-TD002

Environmental Specifications - CompactLogix 5480 Controllers

Attribute 5069-L430ERMW 5069-L450ERMW 5069-4100ERMW 5069-L4200ERMW

Temperature operating

IEC 60068-2-1 (Test Ad Operating Cold)

IEC 60068-2-2 (Test Bd Operating Dry Heat)

IEC 60068-2-14 (Test Na Operating Thermal Shock)

0 degC lt Ta lt +60 degC

(+32 degF lt Ta lt +140 degF)

Temperature surrounding air max 60 degC (140 degF)

Enclosure Type Rating None (open-style)

Voltage and current ratings

MOD Power voltage range 18hellip32V DC

MOD Power power max 72 W

MOD Power current typical 4 A

MOD Power inrush 4 A for 15 ms

MOD Power Passthrough(1) 6 A 18hellip32V DC

MOD Power current rating max10 A

Do not exceed 10 A current draw at the MOD power RTB(4)

SA Power voltage ranges(2) 0hellip32V DC

0hellip240V AC 47hellip63 Hz

SA Power current max (2) 10 mA (DC power)

25 mA (AC power)

SA Power Passthrough(2) (3) 999 A 0hellip32V DC

9975 A 0hellip240V AC 47hellip63 Hz

SA Power current rating max(2) Do not exceed 10 A current draw at the SA power RTB

Isolation voltage

300V (continuous) Basic Insulation Type SA and MOD Power to Backplane

300V (continuous) Basic Insulation Type SA to MOD Power

300V (continuous) Basic Insulation Type Ethernet to Backplane

300V (continuous) Double Insulation Type Ethernet to MOD Power

300V (continuous) Double Insulation Type Ethernet to SA Power

50V (continuous) Functional Insulation Type Ethernet to USB ports and DisplayPort

300V (continuous) Basic Insulation Type USB ports and DisplayPort to Backplane

300V (continuous) Double Insulation Type USB ports and DisplayPort to MOD Power

300V (continuous) Double Insulation Type USB ports and DisplayPort to SA Power

No isolation between Ethernet ports

Type tested at 1500V AC for 60 s

Wire size

5069-RTB4-SCREW 5069-RTB6-SCREW connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 35 mm (014 in) max diameter including insulation single wire connection only

5069-RTB4-UPS connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 29 mm (011 in) max diameter including insulation single wire connection only

Ethernet connections

Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2

Insulation-stripping length 5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 12 mm (047 in)

Terminal block torque5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 04 Nbullm (35 lbbullin)

ATTENTION Do not wire more than two conductors on one RTB terminal

(1) Maximum level of MOD power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(2) SA power specifications are based on the number and type of Compact 5000 IO modules that are used in the system If the set of IO modules that is used in the system require AC and DC voltage you must install a 5069-FPD field

potential distributor to separate the module types

(3) Maximum level of SA power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(4) Remember MOD power usage includes the total power that the controller and local Compact 5000 IO modules use If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000 IO

modules can draw a maximum of 10 A in addition to the current that the controller draws

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 25

CompactLogix 5480 Controllers

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation

You can view or download publications at httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage To order paper copies of technical documentation contact your local Allen-Bradley distributor or Rockwell Automationreg sales representative

Resource Description

CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069-TD002

Provides specifications and other technical data for CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 controllers

CompactLogix 5480 Controllers User Manual publication 5069-UM002 Describes how to configure operate and monitor CompactLogix 5480 controllers

Industrial Automation Wiring and Grounding Guidelines publication 1770-41 Provides general guidelines for installing a Rockwell Automationreg industrial system

Product Certifications website rokautocertifications Provides declarations of conformity certificates and other certification details

26 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP ltFEFF005500740069006c0069006300650020006500730074006100200063006f006e0066006900670075007200610063006900f3006e0020007000610072006100200063007200650061007200200064006f00630075006d0065006e0074006f0073002000640065002000410064006f0062006500200050004400460020007000610072006100200063006f006e00730065006700750069007200200069006d0070007200650073006900f3006e002000640065002000630061006c006900640061006400200065006e00200069006d0070007200650073006f0072006100730020006400650020006500730063007200690074006f00720069006f00200079002000680065007200720061006d00690065006e00740061007300200064006500200063006f00720072006500630063006900f3006e002e002000530065002000700075006500640065006e00200061006200720069007200200064006f00630075006d0065006e0074006f00730020005000440046002000630072006500610064006f007300200063006f006e0020004100630072006f006200610074002c002000410064006f00620065002000520065006100640065007200200035002e003000200079002000760065007200730069006f006e0065007300200070006f00730074006500720069006f007200650073002egt FRA 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 ITA ltFEFF005500740069006c0069007a007a006100720065002000710075006500730074006500200069006d0070006f007300740061007a0069006f006e00690020007000650072002000630072006500610072006500200064006f00630075006d0065006e00740069002000410064006f006200650020005000440046002000700065007200200075006e00610020007300740061006d007000610020006400690020007100750061006c0069007400e00020007300750020007300740061006d00700061006e0074006900200065002000700072006f006f0066006500720020006400650073006b0074006f0070002e0020004900200064006f00630075006d0065006e007400690020005000440046002000630072006500610074006900200070006f00730073006f006e006f0020006500730073006500720065002000610070006500720074006900200063006f006e0020004100630072006f00620061007400200065002000410064006f00620065002000520065006100640065007200200035002e003000200065002000760065007200730069006f006e006900200073007500630063006500730073006900760065002egt JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 21: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

CompactLogix 5480 Controllers

5 Remove all cables from the controller

6 Push down on the front of the DIN rail latches

A click indicates that the DIN rail latches are open

If the DIN rail latches fail to remain in the open position hold them down

7 Pull the controller off the DIN rail

8 Repeat the installation steps that are described beginning at Install the Controller onto the DIN Rail on page 9

9 Apply MOD power and if necessary SA power to the system

Replace the FansThe CompactLogix 5480 controller uses fans at the top and bottom of the controller to help maintain lower operating temperatures when the controller is operating

Fan use includes speed control and monitoring Faults indicate fan operating conditions as follows

bull Minor faults - Triggered when a fan is not operating at the requested speed or if a fan fails to operate at all

In your Logix Designer application project you can use the Minor Faults tab on the Controller Properties dialog box to monitor for these faults

bull Major fault - Triggered if both fans fail and the controller goes over the maximum operating temperature

In this case the controller stops operating

You can order replacement fans Replacement fans come in pairs The fans are unique by position and keyed to help make sure that you install the correct fan in each position

The fans are labeled Fan 1 - Top and Fan 2 - Bottom

Consider the following

bull We recommend that you replace the fans in pairs That is if you replace the one fan we recommend that you replace the other fan too

bull You can replace fans during controller operation The fans support removal and insertion under power

bull Do not remove both fans at once if the controller is operating That is remove a fan and install the replacement fan before you remove the other fan

Remove the Top Fan

1 Push up on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

TIP In your Logix Designer application project you can

use the Major Faults tab on the Controller

Properties dialog box to monitor for this fault

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

R

B

F

Open Position

IMPORTANT If you replace fans while the controller is operating

do not touch live voltage components

TIP If the hinges do not disengage when you push up on the front of the

fan then use a screwdriver as a pry tool

5069-L4200ERMW

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 21

CompactLogix 5480 Controllers

2 Pull the fan out of the slot at the top of the controller

Install the Top Replacement Fan

1 Insert the top replacement fan into the slot at the top of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push down on the top replacement fan until it clicks in place

Remove the Bottom Fan

1 Push the down on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

2 Pull the fan out of the slot at the bottom of the controller

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

TIP If the hinges do not disengage when you push down on the front of

the fan then use a screwdriver as a pry tool

5069-L4200ERMW

5069-L4200ERMW

22 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Bottom Replacement Fan

1 Insert the bottom replacement fan into the slot at the bottom of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push up on the bottom replacement fan until it clicks in place

Use the COS For Windows-based ComputingThe COS on a CompactLogix 5480 controller runs in parallel with the Logix control engine You are not required to use the COS

You can use the following methods to install working controller firmware when the controller is in the out-of-box state

bull ControlFLASHtrade or ControlFLASH Plustrade softwarebull Secure Digital (SD) card

Use a Flash Programming Tool to Install Controller FirmwareYou can use ControlFLASH and ControlFLASH Plus software to install controller firmware

The following requirements apply when you use ControlFLASH or ControlFLASH Plus to install working controller firmware

bull You must use one of the followingndash ControlFLASH software version 150100 or laterndash ControlFLASH Plus version 20000 or later

bull You must use a Linx-based software application with your flash programming toolndash With ControlFLASH software you can use RSLinx

Classic Lite RSLinx Classic RSLinx Enterprise or FactoryTalk Linx

ndash With ControlFLASH Plus software you must use FactoryTalk Linx

Minimum software versions apply with Linx-based software For more information on the minimum software version requirements see the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

5069-L4200ERMW

5069-L4200ERMW

IMPORTANT Before you can use the COS you must install working controller firmware The requirement applies even if you

are not using the controller for real-time control If you do not

install working controller firmware the COS does not start

In the out-of-box state the controller uses firmware revision

1xxx On a CompactLogix 5480 controller the minimum

working controller firmware is revision 32012

TIP We recommend that you connect your peripherals to the

ports that are dedicated to COS use before you install

controller firmware

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 23

CompactLogix 5480 Controllers

Download the Flash Programming Tool

ControlFLASH and ControlFLASH Plus software are available from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

Download the installation files and install the software

Download the Controller Firmware

After the flash programming tool is installed download the controller firmware from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

The initial download is a exe file You use the Rockwell Automation Download Manager to extract a dmk from the downloaded file

Install the Controller Firmware

To install the controller firmware via a flash programming tool you complete the following steps

1 To start the tool click StartgtAll ProgramsgtFlashing Programming ToolsgtControlFLASH or ControlFLASH Plus

2 Follow the prompts to complete the following stepsa Choose the controllerb Select the firmware revisionc Install the controller firmware

A dialog box confirms that the installation was successful

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use a flash programming tool to install controller firmware see the following

bull ControlFLASH Firmware Upgrade Kit User Manual publication 1756-UM105

bull ControlFLASH Plus Quick Start Guide publication CFP-QS001

bull CompactLogix 5480 Controllers User Manual publication 5069-UM002

Use a Secure Digital Card to Install Controller FirmwareYou can use an SD card to install controller firmware CompactLogix 5480 controllers ship with an SD card installed behind the front door on the controller

To use an SD card to install controller firmware complete the following steps

1 Before you turn on power to the controller remove the SD card from the controller

2 Install the SD card into another working CompactLogix 5480 controller that has a Logix Designer application project on it

3 Save the project to the SD card

4 Remove the SD card from the working controller and reinstall it in the new controller

5 Turn on power to the new controller

When the new controller powers up it automatically updates the firmware to the revision that is stored on the SD card

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use the SD card with the controller after valid firmware is installed and the controller is powered see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

IMPORTANT These steps only highlight the major tasks that you

complete to install controller firmware with ControlFLASH

To successfully install controller firmware you must complete other tasks that are not described here

For complete information on how to install controller

firmware see the publications listed at the end of the section

IMPORTANT To install controller firmware on a new CompactLogix 5480

controller via an SD card you must have another controller of

the same type that is already working

The SD card method requires that you save the Logix Designer

application project from the working controller to the SD card

before you use it in the new controller

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

SD Card Slot

24 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpecificationsThis table lists a subset of controller specifications For a complete list of specifications see the CompactLogix 5380 Compact GuardLogixreg 5380 and CompactLogix 5480 Controllers Specifications Technical Data publication 5069-TD002

Environmental Specifications - CompactLogix 5480 Controllers

Attribute 5069-L430ERMW 5069-L450ERMW 5069-4100ERMW 5069-L4200ERMW

Temperature operating

IEC 60068-2-1 (Test Ad Operating Cold)

IEC 60068-2-2 (Test Bd Operating Dry Heat)

IEC 60068-2-14 (Test Na Operating Thermal Shock)

0 degC lt Ta lt +60 degC

(+32 degF lt Ta lt +140 degF)

Temperature surrounding air max 60 degC (140 degF)

Enclosure Type Rating None (open-style)

Voltage and current ratings

MOD Power voltage range 18hellip32V DC

MOD Power power max 72 W

MOD Power current typical 4 A

MOD Power inrush 4 A for 15 ms

MOD Power Passthrough(1) 6 A 18hellip32V DC

MOD Power current rating max10 A

Do not exceed 10 A current draw at the MOD power RTB(4)

SA Power voltage ranges(2) 0hellip32V DC

0hellip240V AC 47hellip63 Hz

SA Power current max (2) 10 mA (DC power)

25 mA (AC power)

SA Power Passthrough(2) (3) 999 A 0hellip32V DC

9975 A 0hellip240V AC 47hellip63 Hz

SA Power current rating max(2) Do not exceed 10 A current draw at the SA power RTB

Isolation voltage

300V (continuous) Basic Insulation Type SA and MOD Power to Backplane

300V (continuous) Basic Insulation Type SA to MOD Power

300V (continuous) Basic Insulation Type Ethernet to Backplane

300V (continuous) Double Insulation Type Ethernet to MOD Power

300V (continuous) Double Insulation Type Ethernet to SA Power

50V (continuous) Functional Insulation Type Ethernet to USB ports and DisplayPort

300V (continuous) Basic Insulation Type USB ports and DisplayPort to Backplane

300V (continuous) Double Insulation Type USB ports and DisplayPort to MOD Power

300V (continuous) Double Insulation Type USB ports and DisplayPort to SA Power

No isolation between Ethernet ports

Type tested at 1500V AC for 60 s

Wire size

5069-RTB4-SCREW 5069-RTB6-SCREW connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 35 mm (014 in) max diameter including insulation single wire connection only

5069-RTB4-UPS connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 29 mm (011 in) max diameter including insulation single wire connection only

Ethernet connections

Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2

Insulation-stripping length 5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 12 mm (047 in)

Terminal block torque5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 04 Nbullm (35 lbbullin)

ATTENTION Do not wire more than two conductors on one RTB terminal

(1) Maximum level of MOD power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(2) SA power specifications are based on the number and type of Compact 5000 IO modules that are used in the system If the set of IO modules that is used in the system require AC and DC voltage you must install a 5069-FPD field

potential distributor to separate the module types

(3) Maximum level of SA power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(4) Remember MOD power usage includes the total power that the controller and local Compact 5000 IO modules use If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000 IO

modules can draw a maximum of 10 A in addition to the current that the controller draws

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 25

CompactLogix 5480 Controllers

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation

You can view or download publications at httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage To order paper copies of technical documentation contact your local Allen-Bradley distributor or Rockwell Automationreg sales representative

Resource Description

CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069-TD002

Provides specifications and other technical data for CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 controllers

CompactLogix 5480 Controllers User Manual publication 5069-UM002 Describes how to configure operate and monitor CompactLogix 5480 controllers

Industrial Automation Wiring and Grounding Guidelines publication 1770-41 Provides general guidelines for installing a Rockwell Automationreg industrial system

Product Certifications website rokautocertifications Provides declarations of conformity certificates and other certification details

26 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP ltFEFF005500740069006c0069006300650020006500730074006100200063006f006e0066006900670075007200610063006900f3006e0020007000610072006100200063007200650061007200200064006f00630075006d0065006e0074006f0073002000640065002000410064006f0062006500200050004400460020007000610072006100200063006f006e00730065006700750069007200200069006d0070007200650073006900f3006e002000640065002000630061006c006900640061006400200065006e00200069006d0070007200650073006f0072006100730020006400650020006500730063007200690074006f00720069006f00200079002000680065007200720061006d00690065006e00740061007300200064006500200063006f00720072006500630063006900f3006e002e002000530065002000700075006500640065006e00200061006200720069007200200064006f00630075006d0065006e0074006f00730020005000440046002000630072006500610064006f007300200063006f006e0020004100630072006f006200610074002c002000410064006f00620065002000520065006100640065007200200035002e003000200079002000760065007200730069006f006e0065007300200070006f00730074006500720069006f007200650073002egt FRA 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 ITA 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 JPN ltFEFF9ad854c18cea51fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e30593002537052376642306e753b8cea3092670059279650306b4fdd306430533068304c3067304d307e3059300230c730b930af30c830c330d730d730ea30f330bf3067306e53705237307e305f306f30d730eb30fc30d57528306b9069305730663044307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e30593002gt KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 22: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

CompactLogix 5480 Controllers

2 Pull the fan out of the slot at the top of the controller

Install the Top Replacement Fan

1 Insert the top replacement fan into the slot at the top of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push down on the top replacement fan until it clicks in place

Remove the Bottom Fan

1 Push the down on the front of the fan

Make sure that the fan is fully disengaged before you try to pull it out

2 Pull the fan out of the slot at the bottom of the controller

5069-L4200ERMW

5069-L4200ERMW

5069-L4200ERMW

TIP If the hinges do not disengage when you push down on the front of

the fan then use a screwdriver as a pry tool

5069-L4200ERMW

5069-L4200ERMW

22 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Install the Bottom Replacement Fan

1 Insert the bottom replacement fan into the slot at the bottom of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push up on the bottom replacement fan until it clicks in place

Use the COS For Windows-based ComputingThe COS on a CompactLogix 5480 controller runs in parallel with the Logix control engine You are not required to use the COS

You can use the following methods to install working controller firmware when the controller is in the out-of-box state

bull ControlFLASHtrade or ControlFLASH Plustrade softwarebull Secure Digital (SD) card

Use a Flash Programming Tool to Install Controller FirmwareYou can use ControlFLASH and ControlFLASH Plus software to install controller firmware

The following requirements apply when you use ControlFLASH or ControlFLASH Plus to install working controller firmware

bull You must use one of the followingndash ControlFLASH software version 150100 or laterndash ControlFLASH Plus version 20000 or later

bull You must use a Linx-based software application with your flash programming toolndash With ControlFLASH software you can use RSLinx

Classic Lite RSLinx Classic RSLinx Enterprise or FactoryTalk Linx

ndash With ControlFLASH Plus software you must use FactoryTalk Linx

Minimum software versions apply with Linx-based software For more information on the minimum software version requirements see the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

5069-L4200ERMW

5069-L4200ERMW

IMPORTANT Before you can use the COS you must install working controller firmware The requirement applies even if you

are not using the controller for real-time control If you do not

install working controller firmware the COS does not start

In the out-of-box state the controller uses firmware revision

1xxx On a CompactLogix 5480 controller the minimum

working controller firmware is revision 32012

TIP We recommend that you connect your peripherals to the

ports that are dedicated to COS use before you install

controller firmware

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 23

CompactLogix 5480 Controllers

Download the Flash Programming Tool

ControlFLASH and ControlFLASH Plus software are available from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

Download the installation files and install the software

Download the Controller Firmware

After the flash programming tool is installed download the controller firmware from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

The initial download is a exe file You use the Rockwell Automation Download Manager to extract a dmk from the downloaded file

Install the Controller Firmware

To install the controller firmware via a flash programming tool you complete the following steps

1 To start the tool click StartgtAll ProgramsgtFlashing Programming ToolsgtControlFLASH or ControlFLASH Plus

2 Follow the prompts to complete the following stepsa Choose the controllerb Select the firmware revisionc Install the controller firmware

A dialog box confirms that the installation was successful

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use a flash programming tool to install controller firmware see the following

bull ControlFLASH Firmware Upgrade Kit User Manual publication 1756-UM105

bull ControlFLASH Plus Quick Start Guide publication CFP-QS001

bull CompactLogix 5480 Controllers User Manual publication 5069-UM002

Use a Secure Digital Card to Install Controller FirmwareYou can use an SD card to install controller firmware CompactLogix 5480 controllers ship with an SD card installed behind the front door on the controller

To use an SD card to install controller firmware complete the following steps

1 Before you turn on power to the controller remove the SD card from the controller

2 Install the SD card into another working CompactLogix 5480 controller that has a Logix Designer application project on it

3 Save the project to the SD card

4 Remove the SD card from the working controller and reinstall it in the new controller

5 Turn on power to the new controller

When the new controller powers up it automatically updates the firmware to the revision that is stored on the SD card

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use the SD card with the controller after valid firmware is installed and the controller is powered see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

IMPORTANT These steps only highlight the major tasks that you

complete to install controller firmware with ControlFLASH

To successfully install controller firmware you must complete other tasks that are not described here

For complete information on how to install controller

firmware see the publications listed at the end of the section

IMPORTANT To install controller firmware on a new CompactLogix 5480

controller via an SD card you must have another controller of

the same type that is already working

The SD card method requires that you save the Logix Designer

application project from the working controller to the SD card

before you use it in the new controller

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

SD Card Slot

24 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpecificationsThis table lists a subset of controller specifications For a complete list of specifications see the CompactLogix 5380 Compact GuardLogixreg 5380 and CompactLogix 5480 Controllers Specifications Technical Data publication 5069-TD002

Environmental Specifications - CompactLogix 5480 Controllers

Attribute 5069-L430ERMW 5069-L450ERMW 5069-4100ERMW 5069-L4200ERMW

Temperature operating

IEC 60068-2-1 (Test Ad Operating Cold)

IEC 60068-2-2 (Test Bd Operating Dry Heat)

IEC 60068-2-14 (Test Na Operating Thermal Shock)

0 degC lt Ta lt +60 degC

(+32 degF lt Ta lt +140 degF)

Temperature surrounding air max 60 degC (140 degF)

Enclosure Type Rating None (open-style)

Voltage and current ratings

MOD Power voltage range 18hellip32V DC

MOD Power power max 72 W

MOD Power current typical 4 A

MOD Power inrush 4 A for 15 ms

MOD Power Passthrough(1) 6 A 18hellip32V DC

MOD Power current rating max10 A

Do not exceed 10 A current draw at the MOD power RTB(4)

SA Power voltage ranges(2) 0hellip32V DC

0hellip240V AC 47hellip63 Hz

SA Power current max (2) 10 mA (DC power)

25 mA (AC power)

SA Power Passthrough(2) (3) 999 A 0hellip32V DC

9975 A 0hellip240V AC 47hellip63 Hz

SA Power current rating max(2) Do not exceed 10 A current draw at the SA power RTB

Isolation voltage

300V (continuous) Basic Insulation Type SA and MOD Power to Backplane

300V (continuous) Basic Insulation Type SA to MOD Power

300V (continuous) Basic Insulation Type Ethernet to Backplane

300V (continuous) Double Insulation Type Ethernet to MOD Power

300V (continuous) Double Insulation Type Ethernet to SA Power

50V (continuous) Functional Insulation Type Ethernet to USB ports and DisplayPort

300V (continuous) Basic Insulation Type USB ports and DisplayPort to Backplane

300V (continuous) Double Insulation Type USB ports and DisplayPort to MOD Power

300V (continuous) Double Insulation Type USB ports and DisplayPort to SA Power

No isolation between Ethernet ports

Type tested at 1500V AC for 60 s

Wire size

5069-RTB4-SCREW 5069-RTB6-SCREW connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 35 mm (014 in) max diameter including insulation single wire connection only

5069-RTB4-UPS connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 29 mm (011 in) max diameter including insulation single wire connection only

Ethernet connections

Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2

Insulation-stripping length 5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 12 mm (047 in)

Terminal block torque5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 04 Nbullm (35 lbbullin)

ATTENTION Do not wire more than two conductors on one RTB terminal

(1) Maximum level of MOD power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(2) SA power specifications are based on the number and type of Compact 5000 IO modules that are used in the system If the set of IO modules that is used in the system require AC and DC voltage you must install a 5069-FPD field

potential distributor to separate the module types

(3) Maximum level of SA power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(4) Remember MOD power usage includes the total power that the controller and local Compact 5000 IO modules use If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000 IO

modules can draw a maximum of 10 A in addition to the current that the controller draws

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 25

CompactLogix 5480 Controllers

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation

You can view or download publications at httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage To order paper copies of technical documentation contact your local Allen-Bradley distributor or Rockwell Automationreg sales representative

Resource Description

CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069-TD002

Provides specifications and other technical data for CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 controllers

CompactLogix 5480 Controllers User Manual publication 5069-UM002 Describes how to configure operate and monitor CompactLogix 5480 controllers

Industrial Automation Wiring and Grounding Guidelines publication 1770-41 Provides general guidelines for installing a Rockwell Automationreg industrial system

Product Certifications website rokautocertifications Provides declarations of conformity certificates and other certification details

26 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU ltFEFF00560065007200770065006e00640065006e0020005300690065002000640069006500730065002000450069006e007300740065006c006c0075006e00670065006e0020007a0075006d002000450072007300740065006c006c0065006e00200076006f006e002000410064006f006200650020005000440046002d0044006f006b0075006d0065006e00740065006e002c00200076006f006e002000640065006e0065006e002000530069006500200068006f00630068007700650072007400690067006500200044007200750063006b006500200061007500660020004400650073006b0074006f0070002d0044007200750063006b00650072006e00200075006e0064002000500072006f006f0066002d00470065007200e400740065006e002000650072007a0065007500670065006e0020006d00f60063006800740065006e002e002000450072007300740065006c006c007400650020005000440046002d0044006f006b0075006d0065006e007400650020006b00f6006e006e0065006e0020006d006900740020004100630072006f00620061007400200075006e0064002000410064006f00620065002000520065006100640065007200200035002e00300020006f0064006500720020006800f600680065007200200067006500f600660066006e00650074002000770065007200640065006e002egt ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE ltFEFF0041006e007600e4006e00640020006400650020006800e4007200200069006e0073007400e4006c006c006e0069006e006700610072006e00610020006f006d002000640075002000760069006c006c00200073006b006100700061002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740020006600f600720020006b00760061006c00690074006500740073007500740073006b0072006900660074006500720020007000e5002000760061006e006c00690067006100200073006b0072006900760061007200650020006f006300680020006600f600720020006b006f007200720065006b007400750072002e002000200053006b006100700061006400650020005000440046002d0064006f006b0075006d0065006e00740020006b0061006e002000f600700070006e00610073002000690020004100630072006f0062006100740020006f00630068002000410064006f00620065002000520065006100640065007200200035002e00300020006f00630068002000730065006e006100720065002egt ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 23: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

CompactLogix 5480 Controllers

Install the Bottom Replacement Fan

1 Insert the bottom replacement fan into the slot at the bottom of the controller

Make sure the tabs at the back of the fan are inserted in the holes at the back of the slot

2 Push up on the bottom replacement fan until it clicks in place

Use the COS For Windows-based ComputingThe COS on a CompactLogix 5480 controller runs in parallel with the Logix control engine You are not required to use the COS

You can use the following methods to install working controller firmware when the controller is in the out-of-box state

bull ControlFLASHtrade or ControlFLASH Plustrade softwarebull Secure Digital (SD) card

Use a Flash Programming Tool to Install Controller FirmwareYou can use ControlFLASH and ControlFLASH Plus software to install controller firmware

The following requirements apply when you use ControlFLASH or ControlFLASH Plus to install working controller firmware

bull You must use one of the followingndash ControlFLASH software version 150100 or laterndash ControlFLASH Plus version 20000 or later

bull You must use a Linx-based software application with your flash programming toolndash With ControlFLASH software you can use RSLinx

Classic Lite RSLinx Classic RSLinx Enterprise or FactoryTalk Linx

ndash With ControlFLASH Plus software you must use FactoryTalk Linx

Minimum software versions apply with Linx-based software For more information on the minimum software version requirements see the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

5069-L4200ERMW

5069-L4200ERMW

IMPORTANT Before you can use the COS you must install working controller firmware The requirement applies even if you

are not using the controller for real-time control If you do not

install working controller firmware the COS does not start

In the out-of-box state the controller uses firmware revision

1xxx On a CompactLogix 5480 controller the minimum

working controller firmware is revision 32012

TIP We recommend that you connect your peripherals to the

ports that are dedicated to COS use before you install

controller firmware

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 23

CompactLogix 5480 Controllers

Download the Flash Programming Tool

ControlFLASH and ControlFLASH Plus software are available from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

Download the installation files and install the software

Download the Controller Firmware

After the flash programming tool is installed download the controller firmware from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

The initial download is a exe file You use the Rockwell Automation Download Manager to extract a dmk from the downloaded file

Install the Controller Firmware

To install the controller firmware via a flash programming tool you complete the following steps

1 To start the tool click StartgtAll ProgramsgtFlashing Programming ToolsgtControlFLASH or ControlFLASH Plus

2 Follow the prompts to complete the following stepsa Choose the controllerb Select the firmware revisionc Install the controller firmware

A dialog box confirms that the installation was successful

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use a flash programming tool to install controller firmware see the following

bull ControlFLASH Firmware Upgrade Kit User Manual publication 1756-UM105

bull ControlFLASH Plus Quick Start Guide publication CFP-QS001

bull CompactLogix 5480 Controllers User Manual publication 5069-UM002

Use a Secure Digital Card to Install Controller FirmwareYou can use an SD card to install controller firmware CompactLogix 5480 controllers ship with an SD card installed behind the front door on the controller

To use an SD card to install controller firmware complete the following steps

1 Before you turn on power to the controller remove the SD card from the controller

2 Install the SD card into another working CompactLogix 5480 controller that has a Logix Designer application project on it

3 Save the project to the SD card

4 Remove the SD card from the working controller and reinstall it in the new controller

5 Turn on power to the new controller

When the new controller powers up it automatically updates the firmware to the revision that is stored on the SD card

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use the SD card with the controller after valid firmware is installed and the controller is powered see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

IMPORTANT These steps only highlight the major tasks that you

complete to install controller firmware with ControlFLASH

To successfully install controller firmware you must complete other tasks that are not described here

For complete information on how to install controller

firmware see the publications listed at the end of the section

IMPORTANT To install controller firmware on a new CompactLogix 5480

controller via an SD card you must have another controller of

the same type that is already working

The SD card method requires that you save the Logix Designer

application project from the working controller to the SD card

before you use it in the new controller

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

SD Card Slot

24 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpecificationsThis table lists a subset of controller specifications For a complete list of specifications see the CompactLogix 5380 Compact GuardLogixreg 5380 and CompactLogix 5480 Controllers Specifications Technical Data publication 5069-TD002

Environmental Specifications - CompactLogix 5480 Controllers

Attribute 5069-L430ERMW 5069-L450ERMW 5069-4100ERMW 5069-L4200ERMW

Temperature operating

IEC 60068-2-1 (Test Ad Operating Cold)

IEC 60068-2-2 (Test Bd Operating Dry Heat)

IEC 60068-2-14 (Test Na Operating Thermal Shock)

0 degC lt Ta lt +60 degC

(+32 degF lt Ta lt +140 degF)

Temperature surrounding air max 60 degC (140 degF)

Enclosure Type Rating None (open-style)

Voltage and current ratings

MOD Power voltage range 18hellip32V DC

MOD Power power max 72 W

MOD Power current typical 4 A

MOD Power inrush 4 A for 15 ms

MOD Power Passthrough(1) 6 A 18hellip32V DC

MOD Power current rating max10 A

Do not exceed 10 A current draw at the MOD power RTB(4)

SA Power voltage ranges(2) 0hellip32V DC

0hellip240V AC 47hellip63 Hz

SA Power current max (2) 10 mA (DC power)

25 mA (AC power)

SA Power Passthrough(2) (3) 999 A 0hellip32V DC

9975 A 0hellip240V AC 47hellip63 Hz

SA Power current rating max(2) Do not exceed 10 A current draw at the SA power RTB

Isolation voltage

300V (continuous) Basic Insulation Type SA and MOD Power to Backplane

300V (continuous) Basic Insulation Type SA to MOD Power

300V (continuous) Basic Insulation Type Ethernet to Backplane

300V (continuous) Double Insulation Type Ethernet to MOD Power

300V (continuous) Double Insulation Type Ethernet to SA Power

50V (continuous) Functional Insulation Type Ethernet to USB ports and DisplayPort

300V (continuous) Basic Insulation Type USB ports and DisplayPort to Backplane

300V (continuous) Double Insulation Type USB ports and DisplayPort to MOD Power

300V (continuous) Double Insulation Type USB ports and DisplayPort to SA Power

No isolation between Ethernet ports

Type tested at 1500V AC for 60 s

Wire size

5069-RTB4-SCREW 5069-RTB6-SCREW connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 35 mm (014 in) max diameter including insulation single wire connection only

5069-RTB4-UPS connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 29 mm (011 in) max diameter including insulation single wire connection only

Ethernet connections

Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2

Insulation-stripping length 5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 12 mm (047 in)

Terminal block torque5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 04 Nbullm (35 lbbullin)

ATTENTION Do not wire more than two conductors on one RTB terminal

(1) Maximum level of MOD power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(2) SA power specifications are based on the number and type of Compact 5000 IO modules that are used in the system If the set of IO modules that is used in the system require AC and DC voltage you must install a 5069-FPD field

potential distributor to separate the module types

(3) Maximum level of SA power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(4) Remember MOD power usage includes the total power that the controller and local Compact 5000 IO modules use If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000 IO

modules can draw a maximum of 10 A in addition to the current that the controller draws

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 25

CompactLogix 5480 Controllers

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation

You can view or download publications at httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage To order paper copies of technical documentation contact your local Allen-Bradley distributor or Rockwell Automationreg sales representative

Resource Description

CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069-TD002

Provides specifications and other technical data for CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 controllers

CompactLogix 5480 Controllers User Manual publication 5069-UM002 Describes how to configure operate and monitor CompactLogix 5480 controllers

Industrial Automation Wiring and Grounding Guidelines publication 1770-41 Provides general guidelines for installing a Rockwell Automationreg industrial system

Product Certifications website rokautocertifications Provides declarations of conformity certificates and other certification details

26 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA ltFEFF005500740069006c006900730065007a00200063006500730020006f007000740069006f006e00730020006100660069006e00200064006500200063007200e900650072002000640065007300200064006f00630075006d0065006e00740073002000410064006f00620065002000500044004600200070006f007500720020006400650073002000e90070007200650075007600650073002000650074002000640065007300200069006d007000720065007300730069006f006e00730020006400650020006800610075007400650020007100750061006c0069007400e90020007300750072002000640065007300200069006d007000720069006d0061006e0074006500730020006400650020006200750072006500610075002e0020004c0065007300200064006f00630075006d0065006e00740073002000500044004600200063007200e900e90073002000700065007500760065006e0074002000ea0074007200650020006f007500760065007200740073002000640061006e00730020004100630072006f006200610074002c002000610069006e00730069002000710075002700410064006f00620065002000520065006100640065007200200035002e0030002000650074002000760065007200730069006f006e007300200075006c007400e90072006900650075007200650073002egt ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 24: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

CompactLogix 5480 Controllers

Download the Flash Programming Tool

ControlFLASH and ControlFLASH Plus software are available from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

Download the installation files and install the software

Download the Controller Firmware

After the flash programming tool is installed download the controller firmware from the PCDC at httpscompatibilityrockwellautomationcomPageshomeaspx

The initial download is a exe file You use the Rockwell Automation Download Manager to extract a dmk from the downloaded file

Install the Controller Firmware

To install the controller firmware via a flash programming tool you complete the following steps

1 To start the tool click StartgtAll ProgramsgtFlashing Programming ToolsgtControlFLASH or ControlFLASH Plus

2 Follow the prompts to complete the following stepsa Choose the controllerb Select the firmware revisionc Install the controller firmware

A dialog box confirms that the installation was successful

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use a flash programming tool to install controller firmware see the following

bull ControlFLASH Firmware Upgrade Kit User Manual publication 1756-UM105

bull ControlFLASH Plus Quick Start Guide publication CFP-QS001

bull CompactLogix 5480 Controllers User Manual publication 5069-UM002

Use a Secure Digital Card to Install Controller FirmwareYou can use an SD card to install controller firmware CompactLogix 5480 controllers ship with an SD card installed behind the front door on the controller

To use an SD card to install controller firmware complete the following steps

1 Before you turn on power to the controller remove the SD card from the controller

2 Install the SD card into another working CompactLogix 5480 controller that has a Logix Designer application project on it

3 Save the project to the SD card

4 Remove the SD card from the working controller and reinstall it in the new controller

5 Turn on power to the new controller

When the new controller powers up it automatically updates the firmware to the revision that is stored on the SD card

Power is automatically cycled on the controller as part of the firmware installation process After the power-up completes the COS starts automatically

For more information on how to use the SD card with the controller after valid firmware is installed and the controller is powered see the CompactLogix 5480 Controllers User Manual publication 5069-UM002

IMPORTANT These steps only highlight the major tasks that you

complete to install controller firmware with ControlFLASH

To successfully install controller firmware you must complete other tasks that are not described here

For complete information on how to install controller

firmware see the publications listed at the end of the section

IMPORTANT To install controller firmware on a new CompactLogix 5480

controller via an SD card you must have another controller of

the same type that is already working

The SD card method requires that you save the Logix Designer

application project from the working controller to the SD card

before you use it in the new controller

OK

RUN

FORCE

FAN 1

SD

FAN 2

5069-L4200ERMW

CONTROLLER

UPS

MP

R

B

F

SD Card Slot

24 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

SpecificationsThis table lists a subset of controller specifications For a complete list of specifications see the CompactLogix 5380 Compact GuardLogixreg 5380 and CompactLogix 5480 Controllers Specifications Technical Data publication 5069-TD002

Environmental Specifications - CompactLogix 5480 Controllers

Attribute 5069-L430ERMW 5069-L450ERMW 5069-4100ERMW 5069-L4200ERMW

Temperature operating

IEC 60068-2-1 (Test Ad Operating Cold)

IEC 60068-2-2 (Test Bd Operating Dry Heat)

IEC 60068-2-14 (Test Na Operating Thermal Shock)

0 degC lt Ta lt +60 degC

(+32 degF lt Ta lt +140 degF)

Temperature surrounding air max 60 degC (140 degF)

Enclosure Type Rating None (open-style)

Voltage and current ratings

MOD Power voltage range 18hellip32V DC

MOD Power power max 72 W

MOD Power current typical 4 A

MOD Power inrush 4 A for 15 ms

MOD Power Passthrough(1) 6 A 18hellip32V DC

MOD Power current rating max10 A

Do not exceed 10 A current draw at the MOD power RTB(4)

SA Power voltage ranges(2) 0hellip32V DC

0hellip240V AC 47hellip63 Hz

SA Power current max (2) 10 mA (DC power)

25 mA (AC power)

SA Power Passthrough(2) (3) 999 A 0hellip32V DC

9975 A 0hellip240V AC 47hellip63 Hz

SA Power current rating max(2) Do not exceed 10 A current draw at the SA power RTB

Isolation voltage

300V (continuous) Basic Insulation Type SA and MOD Power to Backplane

300V (continuous) Basic Insulation Type SA to MOD Power

300V (continuous) Basic Insulation Type Ethernet to Backplane

300V (continuous) Double Insulation Type Ethernet to MOD Power

300V (continuous) Double Insulation Type Ethernet to SA Power

50V (continuous) Functional Insulation Type Ethernet to USB ports and DisplayPort

300V (continuous) Basic Insulation Type USB ports and DisplayPort to Backplane

300V (continuous) Double Insulation Type USB ports and DisplayPort to MOD Power

300V (continuous) Double Insulation Type USB ports and DisplayPort to SA Power

No isolation between Ethernet ports

Type tested at 1500V AC for 60 s

Wire size

5069-RTB4-SCREW 5069-RTB6-SCREW connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 35 mm (014 in) max diameter including insulation single wire connection only

5069-RTB4-UPS connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 29 mm (011 in) max diameter including insulation single wire connection only

Ethernet connections

Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2

Insulation-stripping length 5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 12 mm (047 in)

Terminal block torque5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 04 Nbullm (35 lbbullin)

ATTENTION Do not wire more than two conductors on one RTB terminal

(1) Maximum level of MOD power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(2) SA power specifications are based on the number and type of Compact 5000 IO modules that are used in the system If the set of IO modules that is used in the system require AC and DC voltage you must install a 5069-FPD field

potential distributor to separate the module types

(3) Maximum level of SA power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(4) Remember MOD power usage includes the total power that the controller and local Compact 5000 IO modules use If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000 IO

modules can draw a maximum of 10 A in addition to the current that the controller draws

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 25

CompactLogix 5480 Controllers

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation

You can view or download publications at httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage To order paper copies of technical documentation contact your local Allen-Bradley distributor or Rockwell Automationreg sales representative

Resource Description

CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069-TD002

Provides specifications and other technical data for CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 controllers

CompactLogix 5480 Controllers User Manual publication 5069-UM002 Describes how to configure operate and monitor CompactLogix 5480 controllers

Industrial Automation Wiring and Grounding Guidelines publication 1770-41 Provides general guidelines for installing a Rockwell Automationreg industrial system

Product Certifications website rokautocertifications Provides declarations of conformity certificates and other certification details

26 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR ltFEFF004200720075006b00200064006900730073006500200069006e006e007300740069006c006c0069006e00670065006e0065002000740069006c002000e50020006f0070007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740065007200200066006f00720020007500740073006b00720069006600740020006100760020006800f800790020006b00760061006c00690074006500740020007000e500200062006f007200640073006b0072006900760065007200200065006c006c00650072002000700072006f006f006600650072002e0020005000440046002d0064006f006b0075006d0065006e00740065006e00650020006b0061006e002000e50070006e00650073002000690020004100630072006f00620061007400200065006c006c00650072002000410064006f00620065002000520065006100640065007200200035002e003000200065006c006c00650072002000730065006e006500720065002egt PTB ltFEFF005500740069006c0069007a006500200065007300730061007300200063006f006e00660069006700750072006100e700f50065007300200064006500200066006f0072006d00610020006100200063007200690061007200200064006f00630075006d0065006e0074006f0073002000410064006f0062006500200050004400460020007000610072006100200069006d0070007200650073007300f5006500730020006400650020007100750061006c0069006400610064006500200065006d00200069006d00700072006500730073006f0072006100730020006400650073006b0074006f00700020006500200064006900730070006f00730069007400690076006f0073002000640065002000700072006f00760061002e0020004f007300200064006f00630075006d0065006e0074006f00730020005000440046002000630072006900610064006f007300200070006f00640065006d0020007300650072002000610062006500720074006f007300200063006f006d0020006f0020004100630072006f006200610074002000650020006f002000410064006f00620065002000520065006100640065007200200035002e0030002000650020007600650072007300f50065007300200070006f00730074006500720069006f007200650073002egt SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 25: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

CompactLogix 5480 Controllers

SpecificationsThis table lists a subset of controller specifications For a complete list of specifications see the CompactLogix 5380 Compact GuardLogixreg 5380 and CompactLogix 5480 Controllers Specifications Technical Data publication 5069-TD002

Environmental Specifications - CompactLogix 5480 Controllers

Attribute 5069-L430ERMW 5069-L450ERMW 5069-4100ERMW 5069-L4200ERMW

Temperature operating

IEC 60068-2-1 (Test Ad Operating Cold)

IEC 60068-2-2 (Test Bd Operating Dry Heat)

IEC 60068-2-14 (Test Na Operating Thermal Shock)

0 degC lt Ta lt +60 degC

(+32 degF lt Ta lt +140 degF)

Temperature surrounding air max 60 degC (140 degF)

Enclosure Type Rating None (open-style)

Voltage and current ratings

MOD Power voltage range 18hellip32V DC

MOD Power power max 72 W

MOD Power current typical 4 A

MOD Power inrush 4 A for 15 ms

MOD Power Passthrough(1) 6 A 18hellip32V DC

MOD Power current rating max10 A

Do not exceed 10 A current draw at the MOD power RTB(4)

SA Power voltage ranges(2) 0hellip32V DC

0hellip240V AC 47hellip63 Hz

SA Power current max (2) 10 mA (DC power)

25 mA (AC power)

SA Power Passthrough(2) (3) 999 A 0hellip32V DC

9975 A 0hellip240V AC 47hellip63 Hz

SA Power current rating max(2) Do not exceed 10 A current draw at the SA power RTB

Isolation voltage

300V (continuous) Basic Insulation Type SA and MOD Power to Backplane

300V (continuous) Basic Insulation Type SA to MOD Power

300V (continuous) Basic Insulation Type Ethernet to Backplane

300V (continuous) Double Insulation Type Ethernet to MOD Power

300V (continuous) Double Insulation Type Ethernet to SA Power

50V (continuous) Functional Insulation Type Ethernet to USB ports and DisplayPort

300V (continuous) Basic Insulation Type USB ports and DisplayPort to Backplane

300V (continuous) Double Insulation Type USB ports and DisplayPort to MOD Power

300V (continuous) Double Insulation Type USB ports and DisplayPort to SA Power

No isolation between Ethernet ports

Type tested at 1500V AC for 60 s

Wire size

5069-RTB4-SCREW 5069-RTB6-SCREW connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 35 mm (014 in) max diameter including insulation single wire connection only

5069-RTB4-UPS connections

0515 mm2 (22hellip16 AWG) solid or stranded copper wire rated at 105 degC (221 degF) or greater 29 mm (011 in) max diameter including insulation single wire connection only

Ethernet connections

Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2

Insulation-stripping length 5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 12 mm (047 in)

Terminal block torque5069-RTB4-SCREW 5069-RTB6-SCREW and 5069-L4UPSRTB connections 04 Nbullm (35 lbbullin)

ATTENTION Do not wire more than two conductors on one RTB terminal

(1) Maximum level of MOD power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(2) SA power specifications are based on the number and type of Compact 5000 IO modules that are used in the system If the set of IO modules that is used in the system require AC and DC voltage you must install a 5069-FPD field

potential distributor to separate the module types

(3) Maximum level of SA power current that the controller can pass through to the next module in the system The specific level of current passed through varies based on system configuration

(4) Remember MOD power usage includes the total power that the controller and local Compact 5000 IO modules use If you connect external power to both sets of MOD power RTB terminals however the local Compact 5000 IO

modules can draw a maximum of 10 A in addition to the current that the controller draws

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 25

CompactLogix 5480 Controllers

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation

You can view or download publications at httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage To order paper copies of technical documentation contact your local Allen-Bradley distributor or Rockwell Automationreg sales representative

Resource Description

CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069-TD002

Provides specifications and other technical data for CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 controllers

CompactLogix 5480 Controllers User Manual publication 5069-UM002 Describes how to configure operate and monitor CompactLogix 5480 controllers

Industrial Automation Wiring and Grounding Guidelines publication 1770-41 Provides general guidelines for installing a Rockwell Automationreg industrial system

Product Certifications website rokautocertifications Provides declarations of conformity certificates and other certification details

26 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 26: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

CompactLogix 5480 Controllers

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation

You can view or download publications at httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage To order paper copies of technical documentation contact your local Allen-Bradley distributor or Rockwell Automationreg sales representative

Resource Description

CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069-TD002

Provides specifications and other technical data for CompactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 controllers

CompactLogix 5480 Controllers User Manual publication 5069-UM002 Describes how to configure operate and monitor CompactLogix 5480 controllers

Industrial Automation Wiring and Grounding Guidelines publication 1770-41 Provides general guidelines for installing a Rockwell Automationreg industrial system

Product Certifications website rokautocertifications Provides declarations of conformity certificates and other certification details

26 Rockwell Automation Publication 5069-IN019D-EN-P - July 2019

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA ltFEFF005500740069006c0069007a007a006100720065002000710075006500730074006500200069006d0070006f007300740061007a0069006f006e00690020007000650072002000630072006500610072006500200064006f00630075006d0065006e00740069002000410064006f006200650020005000440046002000700065007200200075006e00610020007300740061006d007000610020006400690020007100750061006c0069007400e00020007300750020007300740061006d00700061006e0074006900200065002000700072006f006f0066006500720020006400650073006b0074006f0070002e0020004900200064006f00630075006d0065006e007400690020005000440046002000630072006500610074006900200070006f00730073006f006e006f0020006500730073006500720065002000610070006500720074006900200063006f006e0020004100630072006f00620061007400200065002000410064006f00620065002000520065006100640065007200200035002e003000200065002000760065007200730069006f006e006900200073007500630063006500730073006900760065002egt JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 27: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

CompactLogix 5480 Controllers

Notes

Rockwell Automation Publication 5069-IN019D-EN-P - July 2019 27

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR ltFEFF004200720075006b00200064006900730073006500200069006e006e007300740069006c006c0069006e00670065006e0065002000740069006c002000e50020006f0070007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740065007200200066006f00720020007500740073006b00720069006600740020006100760020006800f800790020006b00760061006c00690074006500740020007000e500200062006f007200640073006b0072006900760065007200200065006c006c00650072002000700072006f006f006600650072002e0020005000440046002d0064006f006b0075006d0065006e00740065006e00650020006b0061006e002000e50070006e00650073002000690020004100630072006f00620061007400200065006c006c00650072002000410064006f00620065002000520065006100640065007200200035002e003000200065006c006c00650072002000730065006e006500720065002egt PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 28: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

Rockwell Automation SupportUse the following resources to access support information

Documentation FeedbackYour comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at httpliteraturerockwellautomationcomidcgroupsliteraturedocumentsdura-du002_-en-epdf

Technical Support Center Knowledgebase Articles How-to Videos FAQs Chat User Forums and Product Notification Updates

httpsrockwellautomationcusthelpcom

Local Technical Support Phone Numbers Locate the phone number for your country httpwwwrockwellautomationcomglobalsupportget-support-nowpage

Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer

httpwwwrockwellautomationcomglobalsupportdirect-dialpage

Literature Library Installation Instructions Manuals Brochures and Technical Data

httpwwwrockwellautomationcomgloballiterature-libraryoverviewpage

Product Compatibility and Download Center (PCDC)

Get help determining how products interact check features and capabilities and find associated firmware

httpwwwrockwellautomationcomglobalsupportpcdcpage

Allen-Bradley Compact 5000 CompactLogix ControlFLASH ControlFLASH Plus FactoryTalk GuardLogix Logix 5000 Rockwell Automation Rockwell Software and Studio 5000 Logix Designer are trademarks of Rockwell Automation

Inc

EtherNetIP is a trademark of ODVA Inc

Trademarks not belonging to Rockwell Automation are property of their respective companies

Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at httpwwwrockwellautomationcomrockwellautomationabout-ussustainability-ethicsproduct-environmental-compliancepage

Publication 5069-IN019D-EN-P - July 2019 PN-543655Supersedes Publication 5069-IN019C-EN-P - October 2018 Copyright copy 2019 Rockwell Automation Inc All rights reserved Printed in the USA

  • CompactLogix 5480 Controllers Installation Instructions
    • Summary of Changes
    • About the Controller
    • Required System Components
      • System Planning
      • Spacing
      • Enclosure Selection
      • Dimensions
      • Ground Considerations
      • System Power Considerations
        • Install the Controller onto the DIN Rail
        • Connect External Power Supplies to the Controller
          • Install the MOD Power RTB
          • Connect MOD Power
          • Install the SA Power RTB
          • Connect SA DC Power
          • Connect SA AC Power
            • Connect Control Signals Via UPS Control RTB
              • UPS Control Signals
              • Install the UPS Control RTB
              • Connect UPS Control Signals
              • Disconnect Wires from the RTBs
                • Install Compact 5000 IO Modules
                • Install the End Cap
                • Power the System
                • Set the Network Internet Protocol (IP) Addresses
                • Connect the Controller to an EtherNetIP Network
                • Remove and Replace the Controller
                • Replace the Fans
                  • Remove the Top Fan
                  • Install the Top Replacement Fan
                  • Remove the Bottom Fan
                  • Install the Bottom Replacement Fan
                    • Use the COS For Windows-based Computing
                      • Use a Flash Programming Tool to Install Controller Firmware
                        • Use a Secure Digital Card to Install Controller Firmware
                        • Specifications
                        • Additional Resources
                          • Back Cover
                            • Print Spec Sheet

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              Introduction_Category Types

                              ampLPrint Specifications
                              ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

                              ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

                              This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                              Publication Type and Print Category
                              Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
                              AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                              AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                              AR NA NA ArticleEditorialByline NA NA Presale Internal
                              (press releases should not be checked into DocMan or printed)
                              AT B3 B4 D5 Application techniques 5 100 Presale External
                              BR A2 Primary A1 NA Brochures 5 100 Presale External
                              CA C2 Primary C1 NA Catalogue 1 50 Presale External
                              CG NA NA Catalogue Guide 1 50 Presale External
                              CL NA NA Collection 5 50 Presale External
                              CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                              CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                              DC E-only E-only Discount Schedules NA NA Presale Internal
                              DI A1 A3 NA Direct Mail 5 100 Presale Internal
                              DM NA NA Product Demo 5 50 Presale Internal
                              DS B3 D5 Dimensions Sheet 1 5 Post External
                              DU B3 D5 Document Update 1 5 Post External
                              GR B2 D6 Getting Results 1 5 Post External
                              IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
                              LM NA NA Launch Materials 5 50 Presale Internal
                              PC B3 D5 Packaging Contents
                              PL E-only primary B3 E-only Price List 5 50 Presale Internal
                              PM B2 D6 Programming Manual 1 5 Post External
                              PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                              QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                              QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
                              RM B2 D5 D6 Reference Manual 1 5 Post External
                              RN B3 D5 Release Notes 1 5 Post External
                              SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
                              SG B2 D5 D6 Selection Guide BW 5 50 Presale External
                              SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                              SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                              TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
                              TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                              UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                              WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                              WP B3 Primary B5 D5 White Paper 5 50 Presale External
                              Minimum order quantities on all POD items are based on the publication length
                              Publication length Minimum Order Quantity
                              77 or more pages 1 (no shrink wrap required)
                              33 to 76 pages 25
                              3 to 32 pages 50
                              1 or 2 pages 100
                              Pre-sale Marketing
                              All paper in this category is White Brightness 90 or better Opacity 90 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
                              A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
                              A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
                              A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
                              A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                              A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
                              A8 4 color cover Category being deleted 50 matte sheet text self cover
                              2 color text
                              Selection Guide
                              A9 2 color 100gsm bond 50 matte sheet text self cover
                              Selection Guide
                              Gray shading indicates Obsolete Print Catagories
                              Post Sale Technical Communication
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                              2 color text 50 matte sheet text
                              B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B3 1 color 100gsm bond 50 matte sheet text self cover
                              B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
                              B5 2 color 100gsm bond 50 matte sheet text self cover
                              Catalogs
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                              4 color text 45 Coated Sheet
                              C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                              2 color text 32-33 Coated Sheet
                              Print on Demand by Print Vendor (POD)
                              All paper in this category is White Brightness 82 or better Opacity 88 or better
                              Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                              D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                              D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                              D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                              D4 1 color 160gsm tab 90 index
                              D5 1 color 80gsm bond 20 bond self cover
                              D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D7 2 color 160gsm tab 90 index
                              D8 2 color 80gsm bond 20 bond self cover
                              D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                              D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
                              Gray shading indicates Obsolete Print Catagories
                              Print on Demand By Print Vendor (POD) or Off Set (OS)
                              Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
                              RA-QR005K-EN-P | 12019
                              Printing Specification YOUR DATA HERE Instructions NO
                              (required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                              Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                              Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
                              Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                              Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
                              Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
                              (required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
                              Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
                              Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                              (required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
                              (required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
                              Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
                              Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
                              BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
                              Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
                              Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
                              Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
                              Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
                              Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
                              Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
                              Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
                              D4
                              D5
                              D6
                              D7
                              D8
                              D9
Page 29: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

Print Spec Sheet

ampLPrint Specifications
ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

Introduction_Category Types

ampLPrint Specifications
ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
Publication Type and Print Category
Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
AR NA NA ArticleEditorialByline NA NA Presale Internal
(press releases should not be checked into DocMan or printed)
AT B3 B4 D5 Application techniques 5 100 Presale External
BR A2 Primary A1 NA Brochures 5 100 Presale External
CA C2 Primary C1 NA Catalogue 1 50 Presale External
CG NA NA Catalogue Guide 1 50 Presale External
CL NA NA Collection 5 50 Presale External
CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
CP E-only E-only D5 Competitive Information 5 50 NA Confidential
DC E-only E-only Discount Schedules NA NA Presale Internal
DI A1 A3 NA Direct Mail 5 100 Presale Internal
DM NA NA Product Demo 5 50 Presale Internal
DS B3 D5 Dimensions Sheet 1 5 Post External
DU B3 D5 Document Update 1 5 Post External
GR B2 D6 Getting Results 1 5 Post External
IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
LM NA NA Launch Materials 5 50 Presale Internal
PC B3 D5 Packaging Contents
PL E-only primary B3 E-only Price List 5 50 Presale Internal
PM B2 D6 Programming Manual 1 5 Post External
PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
RM B2 D5 D6 Reference Manual 1 5 Post External
RN B3 D5 Release Notes 1 5 Post External
SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
SG B2 D5 D6 Selection Guide BW 5 50 Presale External
SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
UM B2 Primary B4 D6 User Manual BW 1 5 Post External
WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
WP B3 Primary B5 D5 White Paper 5 50 Presale External
Minimum order quantities on all POD items are based on the publication length
Publication length Minimum Order Quantity
77 or more pages 1 (no shrink wrap required)
33 to 76 pages 25
3 to 32 pages 50
1 or 2 pages 100
Pre-sale Marketing
All paper in this category is White Brightness 90 or better Opacity 90 or better
Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
A8 4 color cover Category being deleted 50 matte sheet text self cover
2 color text
Selection Guide
A9 2 color 100gsm bond 50 matte sheet text self cover
Selection Guide
Gray shading indicates Obsolete Print Catagories
Post Sale Technical Communication
Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
2 color text 50 matte sheet text
B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
B3 1 color 100gsm bond 50 matte sheet text self cover
B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
B5 2 color 100gsm bond 50 matte sheet text self cover
Catalogs
Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
4 color text 45 Coated Sheet
C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
2 color text 32-33 Coated Sheet
Print on Demand by Print Vendor (POD)
All paper in this category is White Brightness 82 or better Opacity 88 or better
Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
D4 1 color 160gsm tab 90 index
D5 1 color 80gsm bond 20 bond self cover
D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
D7 2 color 160gsm tab 90 index
D8 2 color 80gsm bond 20 bond self cover
D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Gray shading indicates Obsolete Print Catagories
Print on Demand By Print Vendor (POD) or Off Set (OS)
Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables
RA-QR005K-EN-P | 12019
Printing Specification YOUR DATA HERE Instructions NO
(required) Publication Number 5069-IN019D-EN-P Sample 2030-SP001B-EN-P 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
Use Legacy Number YES or NO 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
Legacy Number if applicable Sample Legacy Number 0160-533 8375rdquo x 10875 SADDLE - Saddle Stitch A2 RIGHT CORNER
Publication Title CompactLogix 5480 Controller Installation Instructions Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title 825rdquo x 11rdquo (RA product profile std) PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
Used in Manufacturing YES YES or NO - If Yes must have Part No listed below 825rdquo x 10875rdquo STAPLED1 -1 position A3
Part Number PN-543655 If SAP Part Number be sure to enter PN- before the number 7385rdquo x 9rdquo (RSI Std) STAPLED1B - bottom 1 position A5
(required) Category D5 Select Print Category ABC or D from category list on Introduction_Category Types tab 6rdquo x 4rdquo STAPLED2 - 2 positions A6
Paper Stock Color White is assumed For color options contact your vendor 55rdquo x 85rdquo (half-size) THERMAL - Thermal bound (Tape bound) A7
Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number here 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
(required) Page Count ofPublication 28 Total page count including cover Enter PAGE count not SHEET count 475rdquo x 7rdquo (slightly smaller half-size) A9
(required) Finished Trim Size Width 85rdquo x 11rdquo This is sheet size before folding 425 x 550 Post Sale Technical Communication
Fold Review key below Leave blank if folded for saddle stitching 4rdquo x 6rdquo B1
Finished Fold Size 425 x 55 This is size after folding is completed 3rdquo x 5rdquo B2
BindingStitching SADDLE - Saddle Stitch Review key below 9rdquo x 12rdquo (Folder) B3 None
Stitching Location SIDE Blank Corner or Side A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) B4 Half or V or Single Fold
Drill Hole (YesNo) NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border A5 (583rdquo x 826rdquo) (148 x 210 mm) B5 C or Tri-Fold
Number of Tabs Needed 5 tab in stock at RR Donnelley 36rdquo x 24rdquo Poster Catalogs DbleParll
Number of Pages per Pad Average sheets of paper 25 50 75100 Max 24rdquo x 36rdquo Poster C1 Sample
Glue Location on Pad Glue location on pads 18rdquo x 24rdquo Poster C2 Short (must specify dimensions between folds in Comments)
Comments After publication is printed and stapled it should be folded twice Once from top to bottom and once from left to right When folding is done the PN should appear in the lower right corner D2 Double Gate
Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastic Coil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) D3
D4
D5
D6
D7
D8
D9
Page 30: CompactLogix 5480 Controllers Installation Instructions · DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın

Introduction_Category Types

ampLPrint Specifications
ampLRockwell Automation Publication RA-QR005K-EN-PampRJanuary 2019

ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Error CompatibilityLevel 15 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams true MaxSubsetPct 1 Optimize true OPM 1 ParseDSCComments false ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts false TransferFunctionInfo Apply UCRandBGInfo Remove UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Average ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 200000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages false ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Average GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 200000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages false GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Average MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile (None) PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released print on demand or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
Publication Type and Print Category
Publication Type Off Set Print Category Spec (See tables below) Print on Demand Spec (See tables below) Description Order Min Order Max Life Cycle Usage Release Option
AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
AR NA NA ArticleEditorialByline NA NA Presale Internal
(press releases should not be checked into DocMan or printed)
AT B3 B4 D5 Application techniques 5 100 Presale External
BR A2 Primary A1 NA Brochures 5 100 Presale External
CA C2 Primary C1 NA Catalogue 1 50 Presale External
CG NA NA Catalogue Guide 1 50 Presale External
CL NA NA Collection 5 50 Presale External
CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
CP E-only E-only D5 Competitive Information 5 50 NA Confidential
DC E-only E-only Discount Schedules NA NA Presale Internal
DI A1 A3 NA Direct Mail 5 100 Presale Internal
DM NA NA Product Demo 5 50 Presale Internal
DS B3 D5 Dimensions Sheet 1 5 Post External
DU B3 D5 Document Update 1 5 Post External
GR B2 D6 Getting Results 1 5 Post External
IN B3 Primary B2 D5 D6 Installation instructions 1 5 Post External
LM NA NA Launch Materials 5 50 Presale Internal
PC B3 D5 Packaging Contents
PL E-only primary B3 E-only Price List 5 50 Presale Internal
PM B2 D6 Programming Manual 1 5 Post External
PP A3 D1 Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
QR B2 primary B3 B5 D5 D6 Quick Reference 1 5 Post External
QS B2 primary B3 B5 D5 D6 Quick Start 1 5 Post External
RM B2 D5 D6 Reference Manual 1 5 Post External
RN B3 D5 Release Notes 1 5 Post External
SG B1 Primary B4 D5 D6 Selection Guide Colour 5 50 Presale External
SG B2 D5 D6 Selection Guide BW 5 50 Presale External
SP A1 A2 A3 A4 NA Sales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 50 Presale External
TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
UM B2 Primary B4 D6 User Manual BW 1 5 Post External
WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
WP B3 Primary B5 D5 White Paper 5 50 Presale External
Minimum order quantities on all POD items are based on the publication length
Publication length Minimum Order Quantity
77 or more pages 1 (no shrink wrap required)
33 to 76 pages 25
3 to 32 pages 50
1 or 2 pages 100
Pre-sale Marketing
All paper in this category is White Brightness 90 or better Opacity 90 or better
Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
A1 4 color 170 gsm 2pp 100 gloss cover 100 gloss text
A2 4 color 170 gsm folded 4pp 100 gloss cover 80 gloss text
A3 4 color Cover 170 gsm with Body 120 gsm gt 4pp 80 gloss cover 80 gloss text
A4 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 gloss text
A5 2 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
A7 4 color cover2 color textSelection Guide Category being deleted 10 Point Cover C2S50 matte sheet text
A8 4 color cover Category being deleted 50 matte sheet text self cover
2 color text
Selection Guide
A9 2 color 100gsm bond 50 matte sheet text self cover
Selection Guide
Gray shading indicates Obsolete Print Catagories
Post Sale Technical Communication
Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
2 color text 50 matte sheet text
B2 1 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
B3 1 color 100gsm bond 50 matte sheet text self cover
B4 2 color 160gsm Colortech amp 100gsm Bond 90 Cover50 matte sheet text
B5 2 color 100gsm bond 50 matte sheet text self cover
Catalogs
Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
4 color text 45 Coated Sheet
C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
2 color text 32-33 Coated Sheet
Print on Demand by Print Vendor (POD)
All paper in this category is White Brightness 82 or better Opacity 88 or better
Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
D4 1 color 160gsm tab 90 index
D5 1 color 80gsm bond 20 bond self cover
D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
D7 2 color 160gsm tab 90 index
D8 2 color 80gsm bond 20 bond self cover
D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Gray shading indicates Obsolete Print Catagories
Print on Demand By Print Vendor (POD) or Off Set (OS)
Use these guidelines to determine if your publication should be print on demand by print vendor (POD) or if it would be more economical to print ffseton a press (OS) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the POD category Guidelines differ for black amp white and color printing so be sure to check the correct tables