Ventilation of the E4 Stockholm BypassHBI Haerter
www.hbi.ch
COMISSIONING OF THE VENTILATION CONTROL OF THE E4 STOCKHOLM BYPASS
1
Commissioning of the Ventilation Control of the E4
Stockholm Bypass
Rune BRANDT HBI Haerter, Zurich, Switzerland, www.hbi.ch
Lars ELERTSONSwedish Transport Administration, Stockholm, Sweden,
www.trafikverket.se
Swedish Transport Administration
Ventilation of the E4 Stockholm BypassHBI Haerter
www.hbi.ch
COMISSIONING OF THE VENTILATION CONTROL OF THE E4 STOCKHOLM BYPASS
2
Agenda
Background and earlier experience
Overview of Bypass Stockholm
Ventilation strategies and modes:
• Normal operation (air quality)
• Smoke management
Tunnel-ventilation Simulator
Testing
Benefits
18km
Swedish Transport Administration
Ventilation of the E4 Stockholm BypassHBI Haerter
www.hbi.ch
COMISSIONING OF THE VENTILATION CONTROL OF THE E4 STOCKHOLM BYPASS
3
• The Swedish Transport Administration makes contracts with functional requirements in major projects for technical systems.
• As the ventilation control system is required to cover all possible scenarios from fire operation, normal operation, maintenance and incident modes to partial tunnel closures, numerous operational modes and levels have to be taken into account.
• Tests have to cover all possible transitions between operational modes and levels.
• Tests have to be performed based on finding faults in the beginning, which results in saving time in the end.
• In previous tunnel projects, the time for testing tunnel ventilation has been shortened because of pressure to open early considering the economic advantages for the public.
• Therefore, the Swedish Transport Administration wants to be prepared for this kind of request.
• If everything has been verified and debugged in an early stage, we can accept this challenge to open early.
Background and earlier experiences
Swedish Transport Administration
Ventilation of the E4 Stockholm BypassHBI Haerter
www.hbi.ch
COMISSIONING OF THE VENTILATION CONTROL OF THE E4 STOCKHOLM BYPASS
4
SMART = Save Money And Reduce Time
How, in this particular project ?
Use a simulator to find faults and save time.
BE SMART
Swedish Transport Administration
Ventilation of the E4 Stockholm BypassHBI Haerter
www.hbi.ch
COMISSIONING OF THE VENTILATION CONTROL OF THE E4 STOCKHOLM BYPASS
5
Safety features• Emergency exits:
@100 to 150 m
• Fixed fire fighting system
• Longitudinal ventilation
Tunnel ventilation• Jet fans: 250
• Air-exchange stations: 6
• Smoke-extraction station (serves both tubes)
• Portal-air extractions: 4
Sensors
• Air velocity sensors: 190
• Air quality sensors: 54
• Smoke detectors: 250
• Linear heat detector
Facts (opening 2026)
• Length: 21 km
• Length of main tunnel: 18 km
• Total length of all tubes: 56 km
• Number of lanes: 3 lanes in each direction in two separate tunnel tubes
• Maximum speed:80/100 km/h
• Estimated traffic:140 000 vehicles/day (year 2035)
• Construction costs:3.1bn Euro (2009 prices)
Overview of The E4 Stockholm Bypass
Swedish Transport Administration
Ventilation of the E4 Stockholm BypassHBI Haerter
www.hbi.ch
COMISSIONING OF THE VENTILATION CONTROL OF THE E4 STOCKHOLM BYPASS
6
279 373371 375 377 471 473 571
374372 376 472378 474272
279
Schematic overview of tunnel-ventilation system
Jet fans (250) Smoke-extraction station Air-exchange stations (6) Portal-air extractions (6)(serves both tubes)
Air velocity sensors (190) Smoke detectors (250) Air-quality sensors (54)
Swedish Transport Administration
Ventilation of the E4 Stockholm BypassHBI Haerter
www.hbi.ch
COMISSIONING OF THE VENTILATION CONTROL OF THE E4 STOCKHOLM BYPASS
7
Normal ventilation at maximum capacity northbound tunnels
0.0: 1 (9620 - 11770)
2150.0: 2 (11770 - 12237)
2617.0: 3 (12237 - 15378)
5758.0: 4 (15378 - 15955)
6335.0: 5 (15955 - 16055)
6435.0: 6 (16055 - 16312)
6692.0: 7 (16312 - 19737)
10117.0: 8 (19737 - 19833)
Sections [m]
Path: South - North Add/Remove variables
Double click a variable in legend to view the 3D plot
m 0. 2000. 4000. 6000. 8000. 10000. 12000. 14000. 16000.
0.
50.
100.
150.
200.
250.
300.
350.
400.
450.
500.
550.
Fraction NO2, µg/m3
Entry 211 Entry
314
AES371/373
AES471/473
279 373371 375 377 471 473 571
NO
x[m
g/m
3]
AES375/377
Entry 414
500
0
Swedish Transport Administration
Ventilation of the E4 Stockholm BypassHBI Haerter
www.hbi.ch
COMISSIONING OF THE VENTILATION CONTROL OF THE E4 STOCKHOLM BYPASS
8
Step-wise controller for in-tunnel air quality: principle
AQV+AQV-
Step
tcsg
time
time
Air quality
An air-quality target value (AQV) is specified, which is assessed for each sensor:1) Air-quality level > AQV+: Ventilation stepped up2) Air-quality level < AQV- and operation time > tcsg: Ventilation stepped down
Swedish Transport Administration
Ventilation of the E4 Stockholm BypassHBI Haerter
www.hbi.ch
COMISSIONING OF THE VENTILATION CONTROL OF THE E4 STOCKHOLM BYPASS
9
Air-quality sensor
Control Step generator
Max value
AQVAir-quality
target value
Control matrixnormal operation
Defines for each sub-controller:• Sensors comprised in the
control loop• Fans assigned to sub
controller• Capacity of fans for each step
Step to activate(1-5)
An air-quality target value (AQV) is specified, which is assessed for each sensor:1) Air-quality level > AQV+: Ventilation stepped up2) Air-quality level < AQV- and operation time > tcsg: Ventilation stepped down
Step-wise controller for in-tunnel air quality: principle
Swedish Transport Administration
Ventilation of the E4 Stockholm BypassHBI Haerter
www.hbi.ch
COMISSIONING OF THE VENTILATION CONTROL OF THE E4 STOCKHOLM BYPASS
10
Step-wise controller for in-tunnel air quality: application
373371 375 377 471 473 571
374372 376 472378 474272
279
279
Ctr.1 1 1 1
1
3 2 1
NOS (normal operation sections):- at least one air-quality sensor- Ventilation equipment also in other sections (NOS) at disposition- Selection of ventilation equipment according to pre-specified priorities
Dilemma: the ventilation equipment can receive conflicting instructions
Swedish Transport Administration
Ventilation of the E4 Stockholm BypassHBI Haerter
www.hbi.ch
COMISSIONING OF THE VENTILATION CONTROL OF THE E4 STOCKHOLM BYPASS
11
Step-wise controller for in-tunnel air quality: example
373371 375 377 471 473 571
374372 376 472378 474272
279
279
Ctr.1 1 1 1
1
3 2 1
Several air-quality sensors devoted to one Normal Operation Section (NOS)
1Ventilation equipment in several sections selected according priorities
Only portal-air extraction if inside air quality is worse than ambient air quality
Increase air-exchange in main tunnel or flow in ramp according to analytic rules
Swedish Transport Administration
Ventilation of the E4 Stockholm BypassHBI Haerter
www.hbi.ch
COMISSIONING OF THE VENTILATION CONTROL OF THE E4 STOCKHOLM BYPASS
12
279 373371 375 377 471 473 571
Control-Step
Generator
(Ramp 313)
Control-Step
Generator
(Ramp 314) Control-Step
Generator
(Ramp 411)
Control-Step
Generator
(Ramp 414)
Control-Step
Generator
(Station 371/373)
Control-Step
Generator
(Station 375/377)
Control-Step
Generator
(Station 471/473)
Air-Exchange
Regulator
(Station 371/373)
Air-Exchange
Regulator
(Station 375/377)
Air-Exchange
Regulator
(Station 471/473)
Jet-Fan Regulator
(Ramp 211/213)
Jet-Fan Regulator
(Ramp 313)Jet-Fan Regulator
(Ramp 314)Jet-Fan Regulator
(Ramp 411)
Jet-Fan Regulator
(Ramp 414)
Environmental
Station Controller
(Station 475)
Control-Step
Generator
(Main tunnel)
Jet-Fan Regulator
(Main tunnel)
Environmental
Station Controller
(Station 571)
Control-Step
Generator
(Ramp 211/213)
Sub-Controller Ramp 314
Sub-Controller Ramp 313
Sub-Controller Ramp 411
Sub-Controller Ramp 211/213
Sub-Controller Ramp 414
Sub-Controller Station 475
Sub-Controller Station 475
Sub-Controller Station 471/473
Sub-Controller Station 375/377
Sub-Controller Station 371/373
Sub-Controller Main tunnel
Air-Quality
Main/Entrance Ramps
Checker
11 controllers for normal ventilation of northbound tunnels
Swedish Transport Administration
Ventilation of the E4 Stockholm BypassHBI Haerter
www.hbi.ch
COMISSIONING OF THE VENTILATION CONTROL OF THE E4 STOCKHOLM BYPASS
13
Smoke management: example northbound tube
Control
PI-CtrPI-Ctr PI-Ctr PI-Ctr
PI-Ctr
u = 3m/s
373371 375 377 471 473 571
374372 376 472378 474272
600m3/s
279
279
• Longitudinal ventilation at specified velocity with active feedback control– 3m/s if FFFS functions
– 1 m/s if FFFS doesn't function and there is traffic congestion (<10 km/h)
• Smoke extraction at all ventilation stations
• 1 m/s at tunnel sections to protect
• => always active flow control
• Plausibility checks of air-velocity sensors (anemometers)
• Ventilation sections not the same as for normal operation
Controller
Swedish Transport Administration
Ventilation of the E4 Stockholm BypassHBI Haerter
www.hbi.ch
COMISSIONING OF THE VENTILATION CONTROL OF THE E4 STOCKHOLM BYPASS
14
Ventilation strategies with Operation modes
1. Stopped Ventilation
• Fire ventilation2. Fixed settings
3. Variable settings (to enable modification by intervention services)
4. Maximum (about 5 m/s towards fire)
5. Minimal (about 1 m/s towards fire)
6. Standard (about 3 m/s towards fire)
• Normal operation (internal and external air quality)7. Maximum (all fans at full capacity)
8. Normal (According to air-quality measurements)
9. Time schedule (fan, time and day schedule)
10. Maintenance according to air quality measurements
Hie
rarc
hy
Swedish Transport Administration
Ventilation of the E4 Stockholm BypassHBI Haerter
www.hbi.ch
COMISSIONING OF THE VENTILATION CONTROL OF THE E4 STOCKHOLM BYPASS
15
• Tunnel-ventilation simulator consists of a mathematical simulation model of tunnel ventilation and logic for generating the operating status of the items covered by the tunnel ventilation.
• The simulation model is created to mimic the natural response of the tunnel with its sensors.
• Software is based on Road Tunnel Ventilation (IDA RTV) from the company EQUA (www.equa.se).
• The Tunnel-ventilation simulator will be connected and integrated to be an Real-time simulator witch interacts with the application logic running in an environment for Control Systems. With it’s software solution applications and hardware for PLC and SCADA-Servers.
• In the process of preparation tender documents, a simulation model is constructed and it will be used as a testing tool in the Factory Acceptance Test.
Simulator
Swedish Transport Administration
Ventilation of the E4 Stockholm BypassHBI Haerter
www.hbi.ch
COMISSIONING OF THE VENTILATION CONTROL OF THE E4 STOCKHOLM BYPASS
16Swedish Transport Administration
Ventilation of the E4 Stockholm BypassHBI Haerter
www.hbi.ch
COMISSIONING OF THE VENTILATION CONTROL OF THE E4 STOCKHOLM BYPASS
17
Systems Layout for Factory Acceptans Test
Windows PC
Control
Software
Developer
Environment
Ethernet
PLC
Windows PC
IDA RTV
Interface
OPC
Control System-Server
HMI
Swedish Transport Administration
Ventilation of the E4 Stockholm BypassHBI Haerter
www.hbi.ch
COMISSIONING OF THE VENTILATION CONTROL OF THE E4 STOCKHOLM BYPASS
18
Systems Layout for Factory Acceptans Test
Operator
interface
Tunnel
Simulator
development
environment
PLC (hidden
under desk)
Foto from tests in Cross City Tunnel, Sydney
Swedish Transport Administration
Ventilation of the E4 Stockholm BypassHBI Haerter
www.hbi.ch
COMISSIONING OF THE VENTILATION CONTROL OF THE E4 STOCKHOLM BYPASS
19
Ventilation control
Swedish Transport Administration
Workflow for the Tunnel Simulator
Ventilation of the E4 Stockholm BypassHBI Haerter
www.hbi.ch
COMISSIONING OF THE VENTILATION CONTROL OF THE E4 STOCKHOLM BYPASS
20
Testing of the control system are divided in three steps:• Factory Acceptance Test, FAT. This is a very intensive period where all Type-
objects with it’s systems are connected to the Control System. It includes objects and systems for; Electricity, Tunnel ventilation, Traffic, Communication, Fire, Waste water, Lightning and Tunnel sensors).
• Site Acceptance Test, SAT. After the FAT is accepted by TRV, then the next test phase starts with all objects and all systems which are installed on site and connected to the Control System. (Approx. 50.000 objects in Stockholm Bypass).
• Operation Acceptance Test, OAT. Where all objects and systems which are controlled and supervised by the Control System are now connected and tested to the Traffic Central.
FAT refers to acceptance testing during factory testing, i.e. before delivery to and installation of the plant. SAT refers to testing at the plant site. OAT relates to trial operation and takes place before the opening for traffic. Trial operation of the installation and operation of the regional systems in “Trafik Stockholm”. Commissioning and operator training before opening to traffic.
Swedish Transport Administration
Ventilation of the E4 Stockholm BypassHBI Haerter
www.hbi.ch
COMISSIONING OF THE VENTILATION CONTROL OF THE E4 STOCKHOLM BYPASS
21
• Benefits for all, the public, Transport admin. and contractors.
• During the Factory Acceptance Tests, the contractor verifies using the tunnel ventilation simulator that the implemented functions in the control system for tunnel ventilation meet the requirements in the contract.
• In this way, application logic for tunnel ventilation is tested cost-effectively in an office environment.
• By doing this systems design errors, deviations and risks of application logic can be identified and corrected before the Site Acceptant Tests begins.
• Application logic that is used for simulation is executed in the same hardware (PLC and HMI) which will be present in the actual tunnel. Here simulations will provide the beneficial results and that tests should not have to be repeated unnecessarily.
• The simulator can be used as a tool for the Swedish Transport Agency for the final approval for Stockholm Bypass.
• As mentioned before in previous tunnel projects, the time for testing tunnel ventilation has been shortened because of pressure to open early considering the economic advantages for the public.
• We have to accept the money spent on a simulator to reduce time, that’s our goal and that is why we want to be smart.
Benefits
Swedish Transport Administration
Ventilation of the E4 Stockholm BypassHBI Haerter
www.hbi.ch
COMISSIONING OF THE VENTILATION CONTROL OF THE E4 STOCKHOLM BYPASS
22
SMART = Save Money And Reduce Time
Use a simulator to reduce time and faults.
SMART
Swedish Transport Administration
Simulation
Ventilation of the E4 Stockholm BypassHBI Haerter
www.hbi.ch
COMISSIONING OF THE VENTILATION CONTROL OF THE E4 STOCKHOLM BYPASS
23
COMMISSIONING OF THE VENTILATION CONTROLOF THE E4 STOCKHOLM BYPASS
Lars ElertsonSpecialist Control and Monitoring [email protected]: +46 70 587 67 34Swedish Transport Administration
Rune BrandtSpecialist Tunnel Ventilation and [email protected]: +41 79 341 30 65HBI Haerter
Thank You!
Questions?
Swedish Transport Administration