clean air act and chimneys
TRANSCRIPT
!
A guide to chimney design
and installation legislation£10
CHIMNEYDISCHARGEHEIGHTS
CHIMNEYDISCHARGEHEIGHTS
What you need to know about . . . .
T H E C L E A N A I R A C T
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 3
The Clean Air Act
Chimney Discharge Heights
Selkirk are very much aware that their chimney, flue and exhaust systems handle waste gases
and combustion products that are discharged into an already sensitive atmosphere.
Consequently, we are conscious of the need for the environment to be protected particularly
where legislation demands.
The chimney height requirement of the Clean Air Act is an area, particularly in relation to commercial
heating boilers, that is often abused, misunderstood and on many occasions blatantly ignored. As
Europe’s largest manufacturer of prefabricated residential / commercial chimney and exhaust
systems, we are often asked to advise on this subject, inquiries emanating from a broad spectrum of
the construction industry, including architects consulting engineers and heating contractors.
For global ecological reasons, air quality is now a subject being treated with high priority by many
countries. Within the UK, legislation on this subject has been with us since the 1800s. The first Clean
Air Act was enacted in 1956 and was subsequently extended and amended by the Clean Air Act
1968. Both these Acts were repealed in 1993 and consolidated into the Clean Air Act 1993. The
Environmental Protection Act 1990 regulates the emission of certain substances to air, land or water,
from various processes. The 1995 Environment [not Environmental] Act provides for the preparation
of a National Air Quality Strategy by the Secretary of State and for local authorities to review and
assess local air quality on the basis of health-based objectives for eight pollutants. The National Air
Quality Strategy was published by The Stationary Office (formely HMSO), CM3587 in March 1997;
Regulations putting the air quality objectives on a statutory basis are expected before the end of
1997. The results of local authority reviews and assessments of local air quality and the requirement
for them to take action to ensure air quality objectives are not breached may well affect the
guidelines on chimney discharge heights. Those who believe that they can circumnavigate
legislation on chimney discharge heights will find that they will contravene other environmental
legislation.
This publication has been prepared to identify the current UK Statutory Requirements for the
discharge height for chimneys serving boiler plant, diesel generators and incinerators. There are
many references within the text to the Clean Air Act, the Clean Air Act Memorandum, the
Environmental Protection Act and Technical Guidance Note (Dispersion) D1. The reader is advised
to obtain and peruse copies of these documents, and will find additional useful information on each
in the annual NSCA* Pollution Hand Book. (*National Society for Clean Air)
We have set out this booklet in a question and answer format, as it was felt this would best answer
most of the queries raised. To assist, there is an index at the back of this booklet to enable particular
subjects to be more easily found.
What you need to know!!
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 5
1
Q3 What would be defined as “very largeplant”, and who would be the approvingauthority?
A3 Within the Environmental Protection Act
there are a number of Prescribed Processes,
each of which are sub-divided into
Part A processes and Part B processes.
Part A Processes
These require an Integrated Pollution
Control (IPC) operating permit and this is
controlled by the EA (Environment Agency)
or the SEPA (Scottish Environmental
Protection Agency) as appropriate.
Processes include boilers, furnaces, gas
turbines or compression ignition engines of
a total of 50MW thermal input or greater at
one location, waste oil/recovered oil burners
of 3 MW or more, incinerators having an
aggregated works capacity of one tonne per
hour or more, and most chemical process
plants. The approving authority for chimney
discharge heights would be the EA or SEPA
as applicable.
Part B Processes
These require an Air Pollution Control (APC)
operating permit and this is controlled by the
Local Authority.
Part B. processes include boilers, furnaces,
gas turbines and compression ignition
engines having a thermal input from 20-50
MW, and waste oil /recovered oil burners
under 3 MW. The approving authority for
chimney discharge heights would be the
Local Authority in England & Wales and
SEPA in Scotland.
For a full schedule of all Part A & B processes,
see the Environmental Protection Prescribed
Processes & Substances Regulations 1991
(and subsequent amendments), or the current
National Society for Clean Air -
“Pollution Handbook”.
Q1 What legislation within the UK controlsthe emissions from commercial /industrial boiler house chimneys, dieselgenerator and incinerator exhausts etc. ?
A1 There are two main items of legislation
within the UK (excluding N. Ireland), which
control the emission of waste gases etc. into
the atmosphere . They are the Clean Air Act
1993 and the Environmental Protection Act
1990. In N. Ireland the relevant legislation is
the Clean Air (Northern Ireland) Order 1981.
An Industrial Pollution Order for N. Ireland
has been issued in draft form and is now
expected to be enacted during 1997. This
order will enforce controls in N. Ireland
similar to the Environmental Protection Act in
the rest of the UK. There is also a
requirement under the Clean Air Act to
control the emission of grit and dust from a
furnace and to avoid nuisance from odours
for example, which is covered by the
Environmental Protection Act, Part III
(Statutory nuisances and clean air), as well
as other legislation.
Q2 Do any of the Acts set a discharge heightat which waste gas emissions arepermissible ?
A2 Yes. Under sections 14-16 of the Clean Air
Act and to the requirements for BATNEEC* in
section 7(2) of the Environmental Protection
Act, the discharge height is defined as the
height, approved by the approving authority,
at which the emissions are rendered
harmless and are prevented from being a
nuisance or prejudicial to health. The
approving authority is normally, except in the
case of very large plant, the Environmental
Health Department for the Local Authority
area where the installation is located.
*(Best Available Technology Not Entailing
Excessive Cost)
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 6
2
Q4 We are primarily concerned with smallercommercial / industrial boilers,incinerators and diesel generators. Do any of the Acts set a lower limit forthe rating of equipment to be consideredunder the Act ?
A4 Yes. In the case of the Clean Air Act, which
covers England, Scotland & Wales, under
clause 14 it is an offence to operate a furnace
that burns:-
● Pulverized fuel
● Solid fuel at a rate of 45.4 kg/hr or more
● Liquid or gaseous fuel at a rate
equivalent to 366.4 kW or more
unless the height of the chimney serving
the furnace has been approved by the local
authority.
A lower limit of 150kW gross heat input is
specified in the introduction to the Clean Air
Act Memorandum, and there appears to be
no explanation as to why this variance
between the Act and the Memorandum
should exist. However, since the
Memorandum is advisory only, the figure of
366.4kW specified in the actual Clean Air Act
should be taken as the lower limit.
In the case of N. Ireland, the Clean Air Order
1981 does not set any lower limit and each
case is considered on its merits by the local
authority officer.
Q5 Why is chimney height so important andhow does it contribute to pollutioncontrol?
A5 Chimney heights offer a means of local
control of pollutants discharge into the
atmosphere from combustion plant
(including diesel generators), incineration
plant and industrial process. They are used
to control the deposition of pollutants to the
ground or their ambient concentrations over
either long or short time scales, for a variety
of purposes including health effects and
nuisance (due to odour for example). There
may also be the necessity for additional
abatement controls on the discharges from a
particular source ,e.g. the requirement of
BATNEEC* to minimize the discharge where
practically possible. However, even when
there are high levels of abatement, there is
likely to be a residual discharge that must be
effectively dispersed by means of an
adequate chimney height.
*(Best Available Technology Not Entailing
Excessive Cost)
Chimneys act as a means of control over
local pollution levels by discharging the
polluting source to a height sufficient to
ensure that the dispersion of the initial
discharge plume, where the pollutants are
most concentrated, is high above ground
level. The chimney height is arranged so that
the eventual contact of the plume with the
ground results in pollutant concentrations
Figure 1
Chimneydiscarge height
A
B
50 to 100 x discharge height
Increasing the chimney discharge height, A, makes little, if any difference to pollutantconcentration, characteristics, if B is increasedbeyond 50 to 100 x A
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 7
Memorandum take into account the type of
fuel burned, and in the case of fuels with a
sulphur content greater than 0.04%, the
geographical location, (area category) in
which the plant operates. (See clause 17 of
the Clean Air Act Memorandum and the
calculation Process on page x of this
document).
More recently there has been a need to deal
with newer types of combustion plant (e.g.
combined cycle), and with the requirements
for adequate discharge stack height for a
wide variety of smaller process plant etc. This
has been met with the Technical Guidance
Note D1.
Each of these documents is advisory rather
than mandatory so as to allow for some
variation in unusual circumstances, but a
discharge height derived from either method
would normally be considered a minimumacceptable figure. However, it should be
noted that clause 25 of the Memorandum as
well as clauses 6.2 & 6.5 of the Technical
Guidance Note D1, both set overidingminimum requirements.
There is also specific advice on minimum
chimney heights for discharge stacks in the
Process Guidance Notes issued by the DOE
Local Authority Unit dealing with the
requirements for authorization of various Part
B processes. These also contain maximum
pollutant emission limits for the process.
Q7 When calculating the chimney dischargeheight what plant rating is to be used?
A7 The maximum rated input of the plant, not
its normal operational load, is to be used when
calculating the chimney discharge height. This
applies to both the Clean Air Act Memorandum
and Technical Guidance Note D1.
In relation to Technical Guidance Note D1
reference should be made to the various
Guidance Notes issued by either the
3
being within a prescribed limit value. This
process is only effective within distances of
about 50-100 chimney heights, much
beyond which the effects of discharge height
are no longer distinguishable. The highest
pollutant concentrations usually occur within
this range. Figure 1 illustrates the point.
Q6 How then is the discharge height of achimney actually set?
A6 The calculation of effective chimney height is
a matter of great practical importance. There
are a variety of methods of doing this, either
by direct dispersion modeling or by using
one of a number of guides for this purpose.
For large plant of the type defined as Part A
Processes, (see Q3), it is common for
individual dispersion modeling studies to be
requested as part of the authorization
process. Direct dispersion modeling may
also be used for calculating chimney heights
for smaller plant where there are complex
problems due to the character of the
dispersion or the nature of the discharge.
However, for the great majority of smaller
polluting discharges chimney heights are
determined using the published guides for
this purpose namely:-
i Third Edition of the 1956 Clean Air
Memorandum “Chimney Heights”.
Published by the Department of the
Environment.
ii Technical Guidance Note D1
(Dispersion). Published by The
Environment Agency
Both documents are available from
The Stationary Office (formerly HMSO)
The Clean Air Act Memorandum “Chimney
Heights” has been used for many years for
conventional combustion plant (mainly
heating and steam raising plant burning coal,
fuel oil or gas), and is still recommended for
this purpose. The calculations to the
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 8
A10 No. Although reference is made in the
“Scope of Memorandum”, (paragraph 3),
that it is suitable for diesel generator
exhausts, this was added some what as an
afterthought and is not strictly correct. See
paper by D J Hall, “Pollutant discharges from
stationary diesel engine exhausts”. Clean
Air; Vol. 17 No 1, 1987, pp. 9 - 20. This paper
gives a method by which the Clean Air Act
can be adapted to deal with diesel engine
exhausts, but this advice has now been
superseded by the issue of Technical
Guidance Note ‘D1’.
The discharge height for a diesel engine
exhaust should be determined using
Technical Guidance Note D1, as this method
takes account of the various pollutants
directly, and also the high discharge velocity
associated with such exhausts.
The levels of pollutants can vary significantly
from engine to engine. At present, whilst
there are no maximum limits defined in the
UK for the various pollutants, other European
Countries do impose limits, and we can
asume that some guidance will be issued by
The Environment Agency in due course. In
the meantime, for the best results, details of
the pollutant discharge in each case should
be obtained directly from the equipment
manufacturer. If this is information is not
readily available, then the break down of
pollutants given in Appendix ‘A’ of this
booklet could be used.
Q11 Does the act relate to all fuels?
A11 Yes. No fuel type is exempt. The Clean Air
Act applies to furnaces burning pulverized
fuel, solid fuel, liquid or gaseous fuel. These
are dealt with in the Clean Air Act
Memorandum under two headings namely:-
● VLS (Very low sulphur) content fuel -
defined as a fuel with less than
0.04% sulphur by mass.
Environment Agency (IPR notes) or the
Secretary of State (PG notes) which contain
guidance on emission concentration limits. A
list of these notes is given in Appendix ‘E’ of
D1. When calculating a chimney/exhaust
discharge height to D1 it can normally be
assumed that the concentrations of the
emitted pollutants are at the limit values
contained in the IPR or PG note unless the
operator has been authorized to operate
with lower limits in which case the lower
values would be used.
Q8 What if the plant operates with a highturndown ratio or a wide range ofdischarge conditions?
A8 In the case of the Memorandum this is not
considered. The chimney height is
calculated on the maximum emission and
target velocities are set at full load operation.
In the case of the Guidance Note, this is dealt
with under section 6.3 where it is
recommended that a discharge stack height
is calculated for both maximum and
minimum capacity and the highest calculated
height used.
Q9 Can the Clean Air Act Memorandum beused to determine the discharge heightfor an incinerator exhaust.?
A9 No. This is clearly stated in the introduction
to the “Scope of Memorandum” (Par. 3.).
Incinerator, as well as gas turbine exhaust
discharge heights, are best determined using
Technical Guidance Note D1. Reference
should be made to the appropriate IPR or PG
guidance note for emission concentration
limits. (see A7)
Q10 Can the Clean Air Act Memorandum beused to determine the discharge heightfor diesel generator exhausts.?
4
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 9
In normal practice this refers to Natural
Gas, LP Gas, or Premium Kerosene
(class C1 BS2869).
● Other Fuels - defined as a fuel with
greater than 0.04% sulphur by mass.
In normal practice this refers to Solid
fuel, Gas Fuel Oil, and Heavy Fuel Oil.
Q12 What fuel pollutants are considered whencalculating a chimney discharge height?
A12 In the case of boiler plant where the chimney
height is calculated via the Clean Air Act
Memorandum the major pollutants
considered are :-
● VLS fuels . . . . . . Nitric Oxide (NO)
● Other fuels . . . . Sulphur Dioxide (SO2)
When using the Technical Guidance Note D1
to calculate a chimney discharge height, all
major pollutants are taken into account.
Some typical pollutant values will be found in
tables on page 17.
Q13 Is the discharge velocity of the emissionfrom a chimney important?
A13 Yes, very important. The higher the
discharge velocity, the better the dispersion
of the pollutants. In the case of the Clean Air
Act Memorandum, the calculations assume
that an adequate exit velocity will be
achieved to prevent the plume of gas flowing
down the outside of the chimney. Target
velocities for a range of boiler ratings are
listed in the memorandum under clause 7 of
the introduction “Efflux Velocity”. All
velocities are at the equipment full load
rating. and are based on a separate
flue/chimney per boiler.
In the case of Technical Guidance Note D1,
5
the discharge velocity is part of the
calculation and will therefore have a direct
influence on the calculated discharge height.
Minimum discharge velocities are set under
clause 6.1.1 of the Guidance Note, and are
typically between 10 and 15m/s. Again, these
values are based on a separate flue/exhaust
for each discharge outlet on the equipment.
A high discharge velocity is also important
for another reason as it prevents cold air
entering the top of the chimney/exhaust,
flowing downwards and cooling the rising hot
gas and the inner surface of the chimney
wall. This can cause the formation of
condensation on the chimney wall, and in turn
lead to corrosion of the chimney construction.
In the case of high sulphur fuels, it will also
lead to the formation and emission of acid
smut from the chimney outlet.
The maintenance of an adequate discharge
velocity at all times is very difficult where
more than one item of equipment is
served by one chimney, in view of the
turndown involved.
To achieve the recommended minimum
discharge velocity, it is often necessary,
particularly with boiler plant to reduce the
internal diameter of the chimney exit by
means of a tapered cone. The correct size of
tapered cone will increase the discharge
velocity as required, but at the same time
will have, in most cases, only a limited effect
on the chimney system’s overall pressure
drop. The outlet diameter of the tapered
cone can be calculated by either of the
expressions in figure 2 opposite.
From the above, it can be seen that bothfrom an environmental as well as plantservice life viewpoint, it is highlypreferable to provide an individualexhaust/chimney from each exhaustoutlet on the equipment.
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 10
6
Q14 In some cases, particularly with naturaldraught atmospheric gas boilers, it is notpossible to achieve the recommendeddischarge velocity. What can be done inthis case?
A14 As far as boiler plant is concerned, every
effort should be made to design the
flue/chimney system so as to provide the
stated minimum exit velocity. (See Q13) This
is best achieved by providing a separate
flue and chimney system for each item of
equipment. For aesthetics, the flue pipes
could be collected in a common shroud or
cupola above roof level.
Alternatively, if a common header and
chimney system is to be provided, then the
system should be designed, incorporating
an induced draught fan if necessary, so as to
provide the required exit velocity.
By incorporating a fan, the chimney internal
diameter can be significantly reduced. The
fan motor speed can in turn be controlled by
a pressure sensing probe, so as to maintain
a constant level of draught at each boiler flue
outlet connection, irrespective of the number
of boilers operating. This will enable a high
level of boiler operating efficiency to be
achieved at all loads.
If neither of the above options are possible,
then the chimney height, C, calculated to the
Memorandum, should be further corrected
using the following expression.
H* = C + Hd where Hd = 2(W/U - 1.5)D
H* = the final corrected chimney height
in metres
C = the chimney height calculated to the
memorandum in metres
Hd = the effective reduction in stack height
due to low velocity in metres
W = the stack actual discharge velocity in m/s
U = the windspeed at the top of the stack
(normally taken as 5 m/s)
D = the stack outside diameter in metres
For discharge heights calculated to
Technical Guidance Note D1, reference
should be made to the Building Research
Establishment Report CR. 103/95 which was
prepared for the Local Authority Unit of Air
Quality Division, Department of the
Environment.
Section 4 of this report contains a
qualification to Guidance Note D1 with
reference to low efflux velocities.
4Vo
πVe
V1
V2
x 1000 = Cone outlet diameter (mm)
x D, = Cone outlet diameter (mm)
Where:- Vo = Waste gas volume @ operating temperature (m3/s)Ve = Required exit velocity (m/s)
Where:- V1 = Exit cone inlet velocity m/sV2 = Target exit velocity m/sD1 = Chimnet diameter (mm)
Note that the sides of the cone shouldtaper at an angle no greater than 30°from the vertical
30°
or
Figure 2
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 11
would be required of any other flue design.
Stack heights should continue to be calculated
by reference to the Chimney Heights
Memorandum irrespective of the details of the
flue or termination design.”
Q16 When determining a building height,from what datum is the height measured?
A16 Building height is measured to the ridge or
other highest point of a building above the
datum of general ground level as illustrated
in Figure 3. The height of a lift or tank room
etc., or any other protrusions less than 1% of
the roof area can be ignored. See also
Figures 8 & 9 related to the calculation
example on page 15.
This applies to areas around the discharge
stack where the ground slope is not greater
than 1 in 10, and the topographic effects on
dispersion are not significant. Specialist
advice may be needed in other cases where
topography is a problem.
SD
H
C
GL
SD
H
C
GL
SD
H
C
GL
SD
H
C
GL
Basementboiler Room
7
Q15 Do the special characteristics of a room-sealed balance draught flue system andterminal, enable a lower dischargeheight than the height calculated via theMemorandum to be acceptable.
A15 No. This is fully dealt with in a paper by
Dr. D J Hall in “CLEAN AIR”, Volume 17,
Number 3/4, 1987 and is obtainable either
from the National Society for Clean Air -
136 North Street - Brighton BN1 1RG.
or direct from Selkirk’s Marketing
Services Department.
The conclusions to the above paper state
the following:-
“ Whatever the benefits conferred by the
room-sealed balanced flue approach may be,
they are enjoyed only in the context of the
avoidance of fluctuating pressure differences
between combustion air inlet and flue outlet.
As far as the control of pollution is concerned,
the room-sealed flue does NOT enable lower
stack heights or less constrained location than
Figure 3
H = building height
C = chimney discharge height
GL = ground level
SD = separation distance
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 12
ridge of the building roof is outsidedistance 5 U, how is the building heightto be determined?
A18 This is best illustrated in Figure 4. If the ridge
of the roof is beyond the distance 5 U, (Fig 4
a) the building height is taken as the height
of the eaves. If the ridge is within the
distance 5 U , (Fig. 4b), then the building
height is taken to the ridge.
Q19 Some buildings are rather complex inshape and can have various sections ofdiffering heights and widths. How is thisdealt with?
A19 Large buildings of this type are broken up
into two or more parts, and each part treated
as a separate building. (See also Fig. 3 on
page 9 of the Memorandum, and Fig. 5 on
page 35 of Technical Guidance Note D1). In
addition, on page 16 of Technical Guidance
Note D1, clause 5.4.3 provides information
on the effective height and width of trees,
lattice towers and other porous structures,
which can influence chimney height. This
data can be equally applied to calculations
according to the Memorandum.
8
Q17 When considering the correction ofchimney height relevant to buildings,how is the distance 5 U and the buildingwidth and height measured
A17 The distance 5 U is really a radial dimension
with the chimney at the centre. All buildings
falling within this radius are to be considered
when correcting the chimney height for
building effect. In practice, it will be relatively
easy to discount a number of smaller
buildings within this radius, and commonly
one building will be obvious as the single
dominant structure.
The building width “B”, is measured at right
angles to a line connecting the centre of the
chimney to the nearest point of the building.
This can be seen more clearly in the
illustrations used in the Calculation Processes
described on page 15. (Defined also in
Figure 2 on page 8 of the Memorandum, and
Figure 8 on page 36 of Technical Guidance
Note D1).
Q18 In cases where a chimney serving a small gas fired boiler is locatedclose to or on the outside wall of thebuilding, where the highest point or the
Figure 4
(a) (b)
5U
HC
5U
HC
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 13
9
Q20 In some instances, a chimneytermination can be located close to atank / plant-room, the height of whichhas not been included in the calculationsbecause the area is less than 1% of theroof area. The termination could then bean undesirable lower height than the tank/ plant-room. Within what separationdistance should the chimney terminationbe raised above the tank / plant-roomroof, and by how much?
A20 This situation is covered in section 25.c of
the Memorandum which states that a
“chimney should never be less than the
height of any part of an attached building
with a distance 5 U. In the circumstances
described in the question therefore, if the
chimney is within a distance of 5 U from a
tank/plant-room, then it should extend to a
height of 0.6 U above the tank/plant-room
roof. (See “common case” in clause 23 of the
Memorandum). However, if the plant-room
has ventilation air inlet louvres, the chimney
should extend to a height of 3m above the top
of the louvres in accordance with section 25.a.
Q21 1n a boiler room containg more than one boiler, how is the chimney height determined?
A21 The Clean Air Act Memorandum did not
envisage multiple discharges in close
proximity being treated separately. In terms
of building down-wash effects, it is the
NB : 5U is calculated on the combineddischarge of ALL chimneys
5U
cumulative discharge that is important. As a
general rule, if the discharges are contained
within a distance 5 U, based on the
combined discharge, they should be treated
collectively, see Figure 5. Outside this
distance, they can be treated individually.
Q22 In some cases, dependent on the building design and application, andparticularly with small boiler plant, itmay be more practical to provideindividual vertical chimney for eachappliance, rather than to provide acommon chimney or cluster. Within whatseparation distance between chimneyscan each boiler chimney discharge beconsidered separately?
A22 If practical, the flues from all boilers should
be collected together in a common multi-
flued chimney system/s, the discharge
height being calculated on the combined
emission of all boilers. If this is not practical,
and a separate chimney system is to be
provided for each boiler, then the 5 U rule as
described previously in A21 would apply.
However, if one of the discharges is
significantly smaller than the others, and is
separated by less than 5 U, it may
considered separately, subject to Local
Authority approval.
Q23 What if there are boilers at more than onelocation on the same site?
A23 If possible, the flues from all boilers should
be collected together in a common multi-
flued chimney system, the discharge height
being calculated on the combined emission
of all boilers. (See A21). However, if this is
not practical a chimney system, multi-flued if
necessary, should be provided at each
location. When calculating the discharge
height for each location, the 5 U rule
previously described in A21 will apply.
See Figure 6 overleaf.
Figure 5
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 14
'x'
1 2 3 4 5
10
Q24 What if an Incinerator and/or Generatorexhaust/s is to be included with boilerflues in a multi-flued chimney system?
A24 In this case the chimney height would be
calculated using Technical Guidance Note
D1, because the introduction of the
incinerator/ generator exhaust takes it
outside the scope of the Memorandum. Again
the total combined emission is important but
this is treated differently depending on the
spacing of the individual flues. (See section
6.4 of Guidance Note D1).
Q25 How should Stand-by plant beconsidered?
A25 Stand-by plant should be included in the
chimney discharge height calculation, if its
inclusion would significantly increase the
rate of emission or significantly change the
type/level of the various pollutants. In cases
where multiple boiler plant is used, one of
which is a stand-by in case of failure of one
of the others, its capacity may be omitted
from the chimney height calculations. Where
there is a standby fuel, (for example, gas-oil
in case of interrupted gas supply), the
chimney stack height should be based on
that for the most polluting fuel.
Q26 When considering the height of thevarious buildings, if a building has noopenable windows can it be ignored, orits height effectively reduced?
A26 Most definitely not. The object of the
exercise is to place the chimney discharge
at a height were the discharge plume can be
dissipated safely over a large area as
described earlier in A5. If the discharge
plume strikes a building shortly after leaving
the chimney exit then the pollutants will be
brought to ground level in a greater
concentration than is desirable.
Q27 Is it permissible under anycircumstances to discharge flue gas at alow level from commercial boiler plant?
A27 Yes. Under clause 26 of the Clean Air Act
Memorandum provision is made, subject to
certain conditions, for certain fan diluted
emissions to be installed to discharge at a
height above ground that is below the roof
level of the building. Note, however, that
there remains a minimum height of 3m, (2m
if input is less than 1MW), above the ground,
elevated walkways, openable windows or
ventilation air intake grills in such
installations. (See sections 27 & 28 of the
If ‘x’ is less than 5U, based on the combined emission of stacks 1 to 5, then the dischargeheight for all 5 is based on the combined emission of stacks 1 to 5.
If ‘x’ is greater than 5U, based on the combined emission of stacks 1 to 5, then two individualsystems would apply, one based on the combined emission of stacks 1 to 3, and the other onthe combined emission of stacks 4 and 5.
Figure 6
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 15
11
Chimney Heights Memorandum). This
arrangement applies principally to gas fired
equipment and is restricted to relatively low
ratings because as the input rating increases
the size of intake and exhaust louvre can
become very large and impractical.
A common fault with such systems is
that the exhaust louvre is NOT set to
discharge at an angle of about 30° above the
horizontal as recommended in clause 27.f. of
the Memorandum. Failure to meet this
requirement means that the flue gas can be
entrained down the wall surface thus
preventing the dispersal of the pollutants and
increasing their concentration in the local
area, which defeats the intention of the
relaxation. See Figure 7.
Fan diluted flue systems should never be
permitted to discharge into an enclosed, or
almost enclosed, ‘well’ or courtyard.
Q28 Finally, are the calculations to determinea chimney discharge height difficult?
A28 Whilst the text so far may not give such an
impression, the calculations required for the
Clean Air Act Memorandum are actually
quite simple and straightforward. In addition
most of the results can be found by using the
alignment charts at the end of the
Memorandum, and we have included our
own simple tables at the end of this booklet,
which enable the chimney height to be
determined for 95% of Clean Air Act
Memorandum applications, i.e., where only
one building is to be considered.
The calculations required for the
Technical Guidance Note are more
complicated mathematically, but the results
can again be simply obtained from a set of
charts at the end of that booklet.
The final calculated discharge height should
be rounded to the nearest metre, always
rounded up in the case of D1.
At the end of each of the guides,
worked examples are given which are
also very helpful in determining the
calculation procedure.
In each case, the discharge heights
calculated using either of the above
methods, should be regarded as a guide,
rather than a mathematically precise
definition of the discharge stack height. The
conclusion may need to be modified in the
light of particular local circumstances or of
practical experience. (See clauses 29 & 30
of the Clean Air Act Memorandum).
Figure 7Louvre orientation on fan dilution systems
Diluted combustiongases
Drainage
Louvres should slope upwards atan angle of not less than 30° fromthe horizontal
Unobstructeddischargee.g. clear ofoverhang
Figure 7
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 16
The final chimney discharge height MUST always be approved by the approving authoritywhich in most cases is the local Environmental Health Department.
When carrying out calculations to either the Clean Air Act Memorandum or GuidanceNote D1, the various separation distances and building measurements should not betaken as exact or precise dimensions, but rather as a guide in each case.
It should always be borne in mind that the object of the exercise is to obtain an effectiveand safe chimney discharge height, rather than a minimum discharge height.
!
12
COMPUTER DISK
To accompany this booklet, Selkirk have a computer
disk which contains simple to use programs for all of
the calculations required in determining the
discharge height of a chimney.
Copies of the disk are available to consulting design
engineers free of charge direct from Selkirk’s
Marketing Services Department at Barnstaple.
Telephone 01271 334332.
Acknowledgments
Thanks are due to Dr. David Hall of the Building
Research Establishment for discussions on the
content of this document, and for his comments on
the draft.
Dr. Hall was involved with the Third Edition of the
Memorandum on Chimney Heights, was
responsible for the New Guidance Note D1 and
acts in an advisory capacity to both Environmental
Health Officers on behalf of the Air Quality Division,
DETR (Department of the Environment, Transport &
the Regions), and to the Environment Agency.
Thanks are also due to Barrie Meridew and Ken
Jess of Selkirk Ltd for the formulation and technical
supervision of this booklet.
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 17
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 18
1213
CALCULATION PROCESS(Clean Air Act Memorandum only)
For the majority of cases, (95%), where one
building is to be considered which is wider than
it is high, the tables on pages 18 to 25 can be
used to calculate the final chimney height.
1 Determine the uncorrected chimney height,
“U” from the appropriate fuel table,
bearing in mind that the appropriate area
category, (geographical location), should
be used where applicable. (See also A6 as
well as the area category list opposite).
2 If the uncorrected height, “U”, is less than
2.5 times the height of the building to which
it is attached or any other building within
5 U of the chimney, then the chimney
height should be increased as follows.
Otherwise the final chimney height remains
as “U”, and as is acceptable.
3 Consider all buildings within a radius 5 U
from the chimney position. If there is only
one obvious building to be considered as
described above, then the corrected
height, “C”, can be obtained from the
appropriate “corrected height” column in
the appropriate table. If there is more than
one building, then refer to the calculation
procedure in the Memorandum. If in any
doubt as to whether more than one
building should be considered, it is
preferable to complete the calculation for
more than one building as per the
Memorandum, as this may result in a lesser
chimney height than if only one building is
considered.
4 Consider the following overriding minimum
requirements and increase the chimney
height if appropriate.
● A chimney should terminate at least 3m
above the level of any adjacent area to
which there is general access, i.e.,
ground level, roof area, openable
window or ventilation intake grill.
(See also A20).
● A chimney should never be less than the
calculated uncorrected chimney height.
● A chimney should never be less than the
height of any part of an attached building
within a distance of 5 U. (See also A20).
The tables on page x are Selkirk copyrightand have been prepared using the followingdata:-
■ All Output ratings are 85% of input rating
■ Fuel Specification
35sec Oil - Cv (gross) = 45.6Mj/kg
Sulphur % = 0.3*
Heavy Oil- Cv (gross) = 42.9Mj/kg
Sulphur % = 3.5*
*maximum allowable by BS 2869
Area Categories (geographical location) as taken from Clause 17 of the Memorandum.
A an undeveloped area where development is
unlikely;
B a partially developed area with scattered
houses;
C a built-up residential area;
D an urban area of mixed industrial and
residential development;
E a large city or an urban area, of mixed
heavy industrial and dense residential
development;
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 19
14
Calculation examples
Example 1
55m
90º
18m
10mhigh
Figure 8
Chimney system comprisingthree individual chimneys ona triangular support mast, (or it could be one commonchimney serving all boilerplant).
Roof tank room 3m x 3mby 2,5m high.
Roof area is 1020m2
Illustration is not to scale.
Building height is always the highest point of the buildingmeasured from a datum of the ground level (see Q & A16).In this example the building height is 25m.
Building width is always thewidest face of the building at rightangles to the separation distance.In this example, the buildingwidth is 55m.
Chimneydischargeheightmeasured fromdatum of thegeneral groundlevel.See also theillustration for Q & A16.
Building separation distance is always a horizontal lineconnecting the closest point of the building to the centre ofthe chimney position. See also the illustration for Q & A16.In this example, the building separation distance is 18m.
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 20
15
1a Fuel - Natural Gas
Total output of three boilers = 5000kW
Efficiency ≅ 85%
∴ Total input = 5882kW
From Table A, the uncorrected height U = 3.9m
∴ 5 x U = 19.7m
The uncorrected height is less than 2.5 times the
building to which it is attached, (in this case the
boiler house), and any other building within 5 x U.
The chimney height will therefore require to be
corrected for building effect.
The separation distance from the centre of the
chimney to the closest point of the office block
= 18m.
As this separation distance is less than 5 x U and
the office block is the tallest building within a radius
of 5 x U from the chimney centre, the chimney
height will need to be corrected to take into
account the height of the office block.
The office block height is 25m. The additional
height of the of the roof tank room can be ignored,
as its area, (9m2), is less than 1% of the total office
block roof area, (1020 m2).
The office block width is measured along a line
which extends to capture the widest frontage facing
the chimney, (55m in this case), and which is
determined at right angles to another line drawn
from the centre of the chimney to the closest point
of the building. This other line denotes the
separation distance, which in this case is 18m.
As there is only one building to be considered; the
office block, and it is wider than it is high, then the
corrected height can be interpolated from Table D
as 27m.
Check that the overriding requirements of note 4
above, (Clause 25 of the Memorandum), are
satisfied. If no further adjustment is required, then
the Corrected Discharge Height = 27m above
ground level.
1b Fuel - 35sec. Oil
Total input as previous calculation = 5882kW.
From the Area Categories on page 13, select an
area type that best describes the location where
the boiler plant will be installed. For this example,
the Area Category is “D”.
From Table B, and Category “D”,
the uncorrected height U = 11.4m.
∴ 5 x U = 57.1m.
The uncorrected height is less than 2.5 times the
height of the building to which it is attached and
any other building within 5U. The chimney height
will therefore need “correction” for building effect.
The office block is still the tallest and most obvious
building within a radius of 5U from the centre of the
chimney.
The office block height, (25m), and width, (55m),
remain as previous, and the corrected height can
be interpolated from Table D as 32m.
Check overriding minimum requirements as
previous, and if further adjustment is not required,
the Corrected Discharge Height
= 32m above ground level.
The shaded sections in the tables on pages 18, 20
and 23, represent the data extracted for the above
sample calculations.
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 21
16
H20m
90º SDii
SDi
BuildingNo. 2
BuildingNo. 1
H15m
BW
CH
Example 2
This calculation is an example in which two
buildings are considered where two boilers are
served by individual chimneys on a common mast.
The example is best read step by step in
conjunction with the procedure set out in within the
Memorandum, as this will explain some of the
variable inputs used in the calculation, e.g. “D” ,
which is just one of the Area Categories.
Data
Total output = 20,466kW
Efficiency = 80%
Total input = 25,582kW
Fuel = 42.9Mj/kg
Sulphur content = 3.5%
Fuel usage - W = 25582 x 3600 = 2,146kg/hr
42.9 x 1000
SO2 Emission - R = 0.02 x 2146 x 3.5 = 150kg/hr
Figure 9
See Figures 3, 4 and 8 formore explanation of heightsand separating distances.
CH = Chimney Discharge Height.
BW = Building width of 58m.
SD i = Separating distance to Building No.1 of 45m.
SD ii = Separating distance to Building No.2 of 32m.
Illustration is not to scale.
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 22
17
1st Example
Area Category = “D” (Mixed industrial /residential)
Adjusted SO2 emission- Ra = 150 x 1.3 = 195 kg/hr
Uncorrected height = U x 1950.5 - 0.9 x 1950.67 = 39m
Two buildings within a radius of 5U to be
considered.
Building No. H W K T
1 20 6 6 29
2 15 58 15 37.5
Tm = 37.5
Hm = 20
U > Tm ∴ C = U
Chimney discharge height = 39m
Fuel Oil (0.3 and 3.5% Sulphur)
Pollutant Discharge rate (g/kg of fuel burned)
Generator Boiler
3.5% 0.3% 3.5% 0.3%
Sulphur Sulphur Sulphur Sulphur
Sulphur Dioxide (S02) 70 6 70 6
Nitric Oxide (NO) 22 3.2
Nitrogen Dioxide (NO2) 3 0.23
2nd Example
Area Category = “C” (Residential area)
Adjusted SO2 emission - Ra = 150 x 1 = 150 kg/hr
U = 5 x 1500.5 - 0.9 x 1500.67 = 35.4m
Building No. H W K T
1 20 6 6 29
2 15 58 15 37.5
Tm = 37.5
Hm = 20
C = Hm + U 1 -
C = 20 + 35.4 1 - = 36.5m
Chimney discharge height = 37m
Typical Pollutant Values for generators and boilers.
Gas
Pollutant Discharge rate (g/m3 of fuel burned)
Generator Boiler
Sulphur Dioxide (S02) N/A N/A
Nitric Oxide (NO) 9 3
Nitrogen Dioxide (NO2) 1 0.02
Hm
Tm( )20
37.5( )
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 23
18
Table D Uncorrected Chimney Height (U) for a range of Input/Output ratingsTable
Natural Gas
A
Shaded area relates to input for sample calculation 1a
Output Kw Input Kw U 5 x U Output Kw Input Kw U 5 x U
125 147 0.4 2.2 4,800 5,647 3.8 19.2150 176 0.5 2.4 4.900 5,765 3.9 19.5200 235 0.6 2.9 5,000 5,882 3.9 19.7250 294 0.7 3.3 5,100 6,000 4.0 19.9300 353 0.7 3.6 5,200 6,118 4.0 20.2350 412 0.8 4.0 5,300 6,235 4.1 20.4400 471 0.9 4.3 5,400 6,353 4.1 20.6450 529 0.9 4.6 5,500 6,471 4.2 20.8500 588 1.0 4.9 5,600 6,588 4.2 21.1600 706 1.1 5.5 5,700 6,706 4.3 21.3700 824 1.2 6.1 5,800 6,824 4.3 21.5800 941 1.3 6.6 5,900 6,941 4.3 21.7900 1,059 1.4 7.0 6,000 7,059 4.4 22.0
1,000 1,176 1.5 7.5 6,100 7,176 4.4 22.21,100 1,294 1.6 7.9 6,200 7,294 4.5 22.41,200 1,412 1.7 8.4 6,300 7,412 4.5 22.61,300 1,529 1.8 8.8 6,400 7,529 4.6 22.81,400 1,647 1.8 9.2 6,500 7,647 4.6 23.01,500 1,765 1.9 9.6 6,600 7,765 4.7 23.31,600 1,882 2.0 9.9 6,700 7,882 4.7 23.51,700 2,000 2.1 10.3 6,800 8,000 4.7 23.71,800 2,118 2.1 10.7 6,900 8,118 4.8 23.91,900 2,235 2.2 11.0 7,000 8,235 4.8 24.12,000 2,353 2.3 11.4 7,100 8,353 4.9 24.32,100 2,471 2.3 11.7 7,200 8,471 4.9 24.52,200 2,588 2.4 12.0 7,300 8,588 4.9 24.72,300 2,706 2.5 12.4 7,400 8,706 5.0 24.92,400 2,824 2.5 12.7 7,500 8,824 5.0 25.12,500 2,941 2.6 13.0 7,600 8,941 5.1 25.32,600 3,059 2.7 13.3 7,700 9,059 5.1 25.52,700 3,176 2.7 13.6 7,800 9,176 5.1 25.72,800 3,294 2.8 13.9 7,900 9,294 5.2 25.92,900 3,412 2.8 14.2 8,000 9,412 5.2 26.13,000 3,529 2.9 14.5 8,100 9,529 5.3 26.33,100 3,647 3.0 14.8 8,200 9,647 5.3 26.53,200 3,765 3.0 15.1 8,300 9,765 5.3 26.73,300 3,882 3.1 15.3 8,400 9,882 5.4 26.93,400 4,000 3.1 15.6 8,500 10,000 5.4 27.13,500 4,118 3.2 15.9 8,600 10,118 5.5 27.33,600 4,235 3.2 16.2 8,700 10,235 5.5 27.53,700 4,353 3.3 16.4 8,900 10,353 5.5 27.63,800 4,471 3.3 16.7 9,000 10,588 5.6 28.03,900 4,588 3.4 17.0 9,100 10,706 5.6 28.24,000 4,706 3.4 17.2 9,200 10,824 5.7 28.44,100 4,824 3.5 17.5 9,300 10,941 5.7 28.64,200 4,941 3.5 17.7 9,400 11,059 5.8 28.84,300 5,059 3.6 18.0 9,500 11,176 5.8 28.94,400 5,176 3.6 18.2 9,600 11,294 5.8 29.14,500 5,294 3.7 18.5 9,700 11,412 5.9 29.34,600 5,412 3.7 18.7 9,800 11,529 5.9 29.54,700 5,529 3.8 19.0 10,000 11,765 6.0 29.8
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 24
Area Category A B C D E
Output InputkW kW U 5 x U U 5 x U U 5 x U U 5 x U U 5 x U
125 147 1.2 5.9 1.4 7.0 1.6 7.9 1.8 9.0 2.0 10.0150 176 1.3 6.4 1.5 7.7 1.7 8.7 2.0 9.9 2.2 11.0200 235 1.5 7.4 1.8 8.8 2.0 10.0 2.3 11.4 2.5 12.7250 294 1.7 8.3 2.0 9.9 2.2 11.2 2.6 12.8 2.8 14.2300 353 1.8 9.1 2.2 10.8 2.5 12.3 2.8 14.0 3.1 15.5350 412 2.0 9.8 2.3 11.7 2.6 13.2 3.0 15.1 3.4 16.8400 471 2.1 10.5 2.5 12.5 2.8 14.2 3.2 16.1 3.6 17.9450 529 2.2 11.1 2.7 13.3 3.0 15.0 3.4 17.1 3.8 19.0500 588 2.3 11.7 2.8 14.0 3.2 15.8 3.6 18.1 4.0 20.0600 706 2.6 12.9 3.1 15.3 3.5 17.3 4.0 19.8 4.4 21.9700 824 2.8 13.9 3.3 16.5 3.7 18.7 4.3 21.4 4.7 23.7800 941 3.0 14.9 3.5 17.7 4.0 20.0 4.6 22.8 5.1 25.3900 1,059 3.2 15.8 3.8 18.8 4.2 21.2 4.8 24.2 5.4 26.9
1,000 1,176 3.3 16.6 4.0 19.8 4.5 22.4 5.1 25.5 5.7 28.31,100 1,294 3.5 17.4 4.1 20.7 4.7 23.5 5.4 26.8 5.9 29.71,200 1,412 3.6 18.2 4.3 21.7 4.9 24.5 5.6 28.0 6.2 31.01,300 1,529 3.8 18.9 4.5 22.6 5.1 25.5 5.8 29.1 6.5 32.31,400 1,647 3.9 19.7 4.7 23.4 5.3 26.5 6.0 30.2 6.7 33.51,500 1,765 4.1 20.3 4.8 24.2 5.5 27.4 6.3 31.3 6.9 34.71,600 1,882 4.2 21.0 5.0 25.0 5.7 28.3 6.5 32.3 7.2 35.81,700 2,000 4.3 21.7 5.2 25.8 5.8 29.2 6.7 33.3 7.4 36.91,800 2,118 4.5 22.3 5.3 26.5 6.0 30.0 6.9 34.3 7.6 38.01,900 2,235 4.6 22.9 5.5 27.3 6.2 30.9 7.0 35.2 7.8 39.02,000 2,353 4.7 23.5 5.6 28.0 6.3 31.7 7.2 36.1 8.0 40.12,100 2,471 4.8 24.1 5.7 28.7 6.5 32.5 7.4 37.0 8.2 41.12,200 2,588 4.9 24.6 5.9 29.3 6.6 33.2 7.6 37.9 8.4 42.02,300 2,706 5.0 25.2 6.0 30.0 6.8 34.0 7.7 38.7 8.6 43.02,400 2,824 5.1 25.7 6.1 30.6 6.9 34.7 7.9 39.6 8.8 43.92,500 2,941 5.3 26.3 6.3 31.3 7.1 35.4 8.1 40.4 9.0 44.82,600 3,059 5.4 26.8 6.4 31.9 7.2 36.1 8.2 41.2 9.1 45.72,700 3,176 5.5 27.3 6.5 32.5 7.4 36.8 8.4 42.0 9.3 46.52,800 3,294 5.6 27.8 6.6 33.1 7.5 37.5 8.5 42.7 9.5 47.42,900 3,412 5.7 28.3 6.7 33.7 7.6 38.1 8.7 43.5 9.6 48.23,000 3,529 5.8 28.8 6.9 34.3 7.8 38.8 8.8 44.2 9.8 49.13,100 3,647 5.8 29.2 7.0 34.8 7.9 39.4 9.0 45.0 10.0 49.93,200 3,765 5.9 29.7 7.1 35.4 8.0 40.1 9.1 45.7 10.1 50.73,300 3,882 6.0 30.2 7.2 35.9 8.1 40.7 9.3 46.4 10.3 51.53,400 4,000 6.1 30.6 7.3 36.5 8.3 41.3 9.4 47.1 10.4 52.23,500 4,118 6.2 31.1 7.4 37.0 8.4 41.9 9.6 47.8 10.6 53.03,600 4,235 6.3 31.5 7.5 37.5 8.5 42.5 9.7 48.4 10.7 53.73,700 4,353 6.4 31.9 7.6 38.0 8.6 43.1 9.8 49.1 10.9 54.53,800 4,471 6.5 32.4 7.7 38.6 8.7 43.7 10.0 49.8 11.0 55.23,900 4,588 6.6 32.8 7.8 39.1 8.8 44.2 10.1 50.4 11.2 55.94,000 4,706 6.6 33.2 7.9 39.6 9.0 44.8 10.2 51.1 11.3 56.74,100 4,824 6.7 33.6 8.0 40.0 9.1 45.3 10.3 51.7 11.5 57.44,200 4,941 6.8 34.0 8.1 40.5 9.2 45.9 10.5 52.3 11.6 58.14,300 5,059 6.9 34.4 8.2 41.0 9.3 46.4 10.6 52.9 11.7 58.74,400 5,176 7.0 34.8 8.3 41.5 9.4 47.0 10.7 53.6 11.9 59.44,500 5,294 7.0 35.2 8.4 42.0 9.5 47.5 10.8 54.2 12.0 60.14,600 5,412 7.1 35.6 8.5 42.4 9.6 48.0 11.0 54.8 12.2 60.84,700 5,529 7.2 36.0 8.6 42.9 9.7 48.6 11.1 55.4 12.3 61.4
19
Table D Uncorrected Chimney Height (U) for a range of Input/Output ratings
35sec. Oil CV (gross) 45.6Mj/kg Sulphur % = 0.31st of 2 pages
U and 5 U by Area Category
Table B
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 25
Area Category A B C D E
Output InputkW kW U 5 x U U 5 x U U 5 x U U 5 x U U 5 x U
4,800 5,647 7.3 36.4 8.7 43.3 9.8 49.1 11.2 55.9 12.4 62.14,900 5,765 7.4 36.8 8.8 43.8 9.9 49.6 11.3 56.5 12.5 62.75,000 5,882 7.4 37.1 8.8 44.2 10.0 50.1 11.4 57.1 12.7 63.35,100 6,000 7.5 37.5 8.9 44.7 10.1 50.6 11.5 57.7 12.8 64.05,200 6,118 7.6 37.9 9.0 45.1 10.2 51.1 11.6 58.2 12.9 64.65,300 6,235 7.6 38.2 9.1 45.5 10.3 51.6 11.8 58.8 13.0 65.25,400 6,353 7.7 38.6 9.2 46.0 10.4 52.0 11.9 59.3 13.2 65.85,500 6,471 7.8 39.0 9.3 46.4 10.5 52.5 12.0 59.9 13.3 66.45,600 6,588 7.9 39.3 9.4 46.8 10.6 53.0 12.1 60.4 13.4 67.05,700 6,706 7.9 39.7 9.4 47.2 10.7 53.5 12.2 61.0 13.5 67.65,800 6,824 8.0 40.0 9.5 47.6 10.8 53.9 12.3 61.5 13.6 68.25,900 6,941 8.1 40.3 9.6 48.0 10.9 54.4 12.4 62.0 13.8 68.86,000 7,059 8.1 40.7 9.7 48.4 11.0 54.9 12.5 62.5 13.9 69.46,100 7,176 8.2 41.0 9.8 48.9 11.1 55.3 12.6 63.1 14.0 70.06,200 7,294 8.3 41.4 9.8 49.2 11.2 55.8 12.7 63.6 14.1 70.56,300 7,412 8.3 41.7 9.9 49.6 11.2 56.2 12.8 64.1 14.2 71.16,400 7,529 8.4 42.0 10.0 50.0 11.3 56.7 12.9 64.6 14.3 71.76,500 7,647 8.5 42.3 10.1 50.4 11.4 57.1 13.0 65.1 14.4 72.26,600 7,765 8.5 42.7 10.2 50.8 11.5 57.5 13.1 65.6 14.6 72.86,700 7,882 8.6 43.0 10.2 51.2 11.6 58.0 13.2 66.1 14.7 73.36,800 8,000 8.7 43.3 10.3 51.6 11.7 58.4 13.3 66.6 14.8 73.96,900 8,118 8.7 43.6 10.4 52.0 11.8 58.8 13.4 67.1 14.9 74.47,000 8,235 8.8 43.9 10.5 52.3 11.9 59.3 13.5 67.6 15.0 74.97,100 8,353 8.9 44.3 10.5 52.7 11.9 59.7 13.6 68.0 15.1 75.57,200 8,471 8.9 44.6 10.6 53.1 12.0 60.1 13.7 68.5 15.2 76.07,300 8,588 9.0 44.9 10.7 53.4 12.1 60.5 13.8 69.0 15.3 76.57,400 8,706 9.0 45.2 10.8 53.8 12.2 60.9 13.9 69.5 15.4 77.17,500 8,824 9.1 45.5 10.8 54.2 12.3 61.3 14.0 69.9 15.5 77.67,600 8,941 9.2 45.8 10.9 54.5 12.3 61.7 14.1 70.4 15.6 78.17,700 9,059 9.2 46.1 11.0 54.9 12.4 62.1 14.2 70.9 15.7 78.67,800 9,176 9.3 46.4 11.0 55.2 12.5 62.5 14.3 71.3 15.8 79.17,900 9,294 9.3 46.7 11.1 55.6 12.6 62.9 14.4 71.8 15.9 79.68,000 9,412 9.4 47.0 11.2 55.9 12.7 63.3 14.4 72.2 16.0 80.18,100 9,529 9.5 47.3 11.3 56.3 12.7 63.7 14.5 72.7 16.1 80.68,200 9,647 9.5 47.6 11.3 56.6 12.8 64.1 14.6 73.1 16.2 81.18,300 9,765 9.6 47.8 11.4 57.0 12.9 64.5 14.7 73.6 16.3 81.68,400 9,882 9.6 48.1 11.5 57.3 13.0 64.9 14.8 74.0 16.4 82.18,500 10,000 9.7 48.4 11.5 57.7 13.1 65.3 14.9 74.4 16.5 82.68,600 10,118 9.7 48.7 11.6 58.0 13.1 65.7 15.0 74.9 16.6 83.18,700 10,235 9.8 49.0 11.7 58.3 13.2 66.1 15.1 75.3 16.7 83.68,800 10,353 9.9 49.3 11.7 58.7 13.3 66.4 15.1 75.7 16.8 84.09,000 10,588 10.0 49.8 11.9 59.3 13.4 67.2 15.3 76.6 17.0 85.09,100 10,706 10.0 50.1 11.9 59.7 13.5 67.6 15.4 77.0 17.1 85.59,200 10,824 10.1 50.4 12.0 60.0 13.6 67.9 15.5 77.5 17.2 85.99,300 10,941 10.1 50.6 12.1 60.3 13.7 68.3 15.6 77.9 17.3 86.49,400 11,059 10.2 50.9 12.1 60.6 13.7 68.7 15.7 78.3 17.4 86.99,500 11,176 10.2 51.2 12.2 61.0 13.8 69.0 15.7 78.7 17.5 87.39,600 11,294 10.3 51.5 12.3 61.3 13.9 69.4 15.8 79.1 17.6 87.89,700 11,412 10.3 51.7 12.3 61.6 13.9 69.7 15.9 79.5 17.6 88.29,800 11,529 10.4 52.0 12.4 61.9 14.0 70.1 16.0 79.9 17.7 88.7
10,000 11,765 10.5 52.5 12.5 62.5 14.2 70.8 16.1 80.7 17.9 89.6
Shaded area relates to input for sample calculation 1b
35sec. Oil CV (gross) 45.6Mj/kg Sulphur % = 0.3
20
Table D Uncorrected Chimney Height (U) for a range of Input/Output ratings
2nd of 2 pages
Table B
U and 5 U by Area Category
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 26
Area Category A B C D E
Output InputkW kW U 5 x U U 5 x U U 5 x U U 5 x U U 5 x U
5,000 5,882 21.6 108.1 23.2 115.9 24.4 121.9 25.7 128.4 26.8 133.9
5,200 6,118 21.8 109.0 23.4 116.9 24.6 122.8 25.9 129.4 27.0 134.9
5,400 6,353 22.0 109.8 23.5 117.7 24.7 123.7 26.1 130.4 27.2 135.9
5,600 6,588 22.1 110.6 23.7 118.6 24.9 124.7 26.3 131.4 27.4 136.9
5,800 6,824 22.3 111.4 23.9 119.4 25.1 125.5 26.5 132.3 27.6 137.9
6,000 7,059 22.4 112.1 24.1 120.3 25.3 126.4 26.6 133.2 27.8 138.8
6,200 7,294 22.6 112.9 24.2 121.0 25.4 127.2 26.8 134.1 28.0 139.8
6,400 7,529 22.7 113.6 24.4 121.8 25.6 128.0 27.0 134.9 28.1 140.6
6,600 7,765 22.9 114.3 24.5 122.6 25.8 128.8 27.2 135.8 28.3 141.5
6,800 8,000 23.0 115.0 24.7 123.3 25.9 129.6 27.3 136.6 28.5 142.4
7,000 8,235 23.1 115.7 24.8 124.0 26.1 130.3 27.5 137.4 28.6 143.2
7,200 8,471 23.3 116.3 24.9 124.7 26.2 131.1 27.6 138.1 28.8 144.0
7,400 8,706 23.4 116.9 25.1 125.4 26.4 131.8 27.8 138.9 29.0 144.8
7,600 8,941 23.5 117.6 25.2 126.1 26.5 132.5 27.9 139.6 29.1 145.6
7,800 9,176 23.6 118.2 25.3 126.7 26.6 133.2 28.1 140.4 29.3 146.3
8,000 9,412 23.8 118.8 25.5 127.4 26.8 133.9 28.2 141.1 29.4 147.1
8,200 9,647 23.9 119.4 25.6 128.0 26.9 134.5 28.4 141.8 29.6 147.8
8,400 9,882 24.0 119.9 25.7 128.6 27.0 135.2 28.5 142.5 29.7 148.5
8,600 10,118 24.1 120.5 25.8 129.2 27.2 135.8 28.6 143.1 29.8 149.2
8,800 10,353 24.2 121.1 26.0 129.8 27.3 136.4 28.8 143.8 30.0 149.9
9,000 10,588 24.3 121.6 26.1 130.4 27.4 137.1 28.9 144.4 30.1 150.6
9,200 10,824 24.4 122.1 26.2 131.0 27.5 137.7 29.0 145.1 30.5 152.6
9,400 11,059 24.5 122.7 26.3 131.6 27.7 138.3 29.1 145.7 30.8 153.8
9,600 11,294 24.6 123.2 26.4 132.1 27.8 138.8 29.3 146.3 31.0 155.1
9,800 11,529 24.7 123.7 26.5 132.7 27.9 139.4 29.4 146.9 31.3 156.4
10,000 11,765 24.8 124.2 26.6 133.2 28.0 140.0 29.5 147.5 31.5 157.6
10,200 12,000 24.9 124.7 26.7 133.7 28.1 140.5 29.6 148.1 31.8 158.8
10,400 12,235 25.0 125.2 26.8 134.2 28.2 141.1 29.7 148.7 32.0 160.0
10,600 12,471 25.1 125.7 27.0 134.8 28.3 141.6 29.8 149.2 32.2 161.2
10,800 12,706 25.2 126.1 27.1 135.3 28.4 142.1 30.0 149.8 32.5 162.3
11,000 12,941 25.3 126.6 27.2 135.8 28.5 142.7 30.1 150.4 32.7 163.5
11,200 13,176 25.4 127.0 27.2 136.2 28.6 143.2 30.4 151.9 32.9 164.6
11,400 13,412 25.5 127.5 27.3 136.7 28.7 143.7 30.6 153.0 33.1 165.7
11,600 13,647 25.6 127.9 27.4 137.2 28.8 144.2 30.8 154.0 33.4 166.8
11,800 13,882 25.7 128.4 27.5 137.7 28.9 144.7 31.0 155.0 33.6 167.9
12,000 14,118 25.8 128.8 27.6 138.1 29.0 145.2 31.2 156.0 33.8 169.0
12,200 14,353 25.8 129.2 27.7 138.6 29.1 145.7 31.4 157.0 34.0 170.0
12,400 14,588 25.9 129.7 27.8 139.0 29.2 146.1 31.6 158.0 34.2 171.1
12,600 14,824 26.0 130.1 27.9 139.5 29.3 146.6 31.8 159.0 34.4 172.1
12,800 15,059 26.1 130.5 28.0 139.9 29.4 147.1 32.0 160.0 34.6 173.2
13,000 15,294 26.2 130.9 28.1 140.4 29.5 147.5 32.2 160.9 34.8 174.2
13,200 15,529 26.3 131.3 28.2 140.8 29.6 148.0 32.4 161.9 35.0 175.2
13,400 15,765 26.3 131.7 28.2 141.2 29.7 148.4 32.6 162.8 35.2 176.2
13,600 16,000 26.4 132.1 28.3 141.6 29.8 148.9 32.7 163.7 35.4 177.2
13,800 16,235 26.5 132.5 28.4 142.1 29.9 149.3 32.9 164.7 35.6 178.1
14,000 16,471 26.6 132.8 28.5 142.5 29.9 149.7 33.1 165.6 35.8 179.1
14,200 16,706 26.6 133.2 28.6 142.9 30.0 150.1 33.3 166.5 36.0 180.1
14,400 16,941 26.7 133.6 28.7 143.3 30.1 150.6 33.5 167.4 36.2 181.0
14,600 17,176 26.8 134.0 28.7 143.7 30.4 152.1 33.6 168.2 36.4 181.9
14,800 17,412 26.9 134.3 28.8 144.1 30.6 152.9 33.8 169.1 36.6 182.9
15,000 17,647 26.9 134.7 28.9 144.4 30.7 153.7 34.0 170.0 36.8 183.8
21
Table D Uncorrected Chimney Height (U) for a range of Input/Output ratings
1st of 2 pages Heavy Oil CV (gross) 42.9Mj/kg Sulphur % = 3.5
U and 5 U by Area Category
Table C
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 27
Area Category A B C D E
Output InputkW kW U 5 x U U 5 x U U 5 x U U 5 x U U 5 x U
15,200 17882 27.0 135.1 29.0 144.8 30.9 154.5 34.2 170.8 36.9 184.715,400 18118 27.1 135.4 29.0 145.2 31.1 155.3 34.3 171.7 37.1 185.615,600 18353 27.2 135.8 29.1 145.6 31.2 156.0 34.5 172.5 37.3 186.515,800 18588 27.2 136.1 29.2 146.0 31.4 156.8 34.7 173.4 37.5 187.416,000 18824 27.3 136.4 29.3 146.3 31.5 157.6 34.8 174.2 37.6 188.216,200 19059 27.4 136.8 29.3 146.7 31.7 158.3 35.0 175.0 37.8 189.116,400 19294 27.4 137.1 29.4 147.0 31.8 159.1 35.2 175.8 38.0 190.016,600 19529 27.5 137.5 29.5 147.4 32.0 159.8 35.3 176.6 38.2 190.816,800 19765 27.6 137.8 29.6 147.8 32.1 160.6 35.5 177.4 38.3 191.717,000 20000 27.6 138.1 29.6 148.1 32.3 161.3 35.6 178.2 38.5 192.517,200 20235 27.7 138.4 29.7 148.5 32.4 162.0 35.8 179.0 38.7 193.317,400 20471 27.8 138.8 29.8 148.8 32.5 162.7 36.0 179.8 38.8 194.117,600 20706 27.8 139.1 29.8 149.1 32.7 163.5 36.1 180.5 39.0 195.017,800 20941 27.9 139.4 29.9 149.5 32.8 164.2 36.3 181.3 39.2 195.818,000 21176 27.9 139.7 30.0 149.8 33.0 164.9 36.4 182.1 39.3 196.618,200 21412 28.0 140.0 30.0 150.1 33.1 165.6 36.6 182.8 39.5 197.418,400 21647 28.1 140.3 30.1 150.5 33.3 166.3 36.7 183.6 39.6 198.118,600 21882 28.1 140.6 30.3 151.7 33.4 167.0 36.9 184.3 39.8 198.919,000 22353 28.2 141.2 30.6 153.0 33.7 168.3 37.2 185.8 40.1 200.519,200 22588 28.3 141.5 30.7 153.6 33.8 169.0 37.3 186.5 40.2 201.219,400 22824 28.4 141.8 30.8 154.2 33.9 169.7 37.4 187.2 40.4 202.019,600 23059 28.4 142.1 31.0 154.8 34.1 170.3 37.6 187.9 40.5 202.719,800 23294 28.5 142.4 31.1 155.4 34.2 171.0 37.7 188.6 40.7 203.520,000 23529 28.5 142.7 31.2 156.0 34.3 171.6 37.9 189.3 40.8 204.220,200 23765 28.6 143.0 31.3 156.6 34.5 172.3 38.0 190.0 41.0 205.020,400 24000 28.6 143.2 31.4 157.2 34.6 172.9 38.1 190.7 41.1 205.720,600 24235 28.7 143.5 31.6 157.8 34.7 173.6 38.3 191.4 41.3 206.420,800 24471 28.8 143.8 31.7 158.4 34.8 174.2 38.4 192.1 41.4 207.121,000 24706 28.8 144.1 31.8 159.0 35.0 174.8 38.6 192.8 41.6 207.821,200 24941 28.9 144.3 31.9 159.6 35.1 175.4 38.7 193.4 41.7 208.521,400 25176 28.9 144.6 32.0 160.2 35.2 176.1 38.8 194.1 41.8 209.221,600 25412 29.0 144.9 32.1 160.7 35.3 176.7 39.0 194.8 42.0 209.921,800 25647 29.0 145.2 32.3 161.3 35.5 177.3 39.1 195.4 42.1 210.622,000 25882 29.1 145.4 32.4 161.9 35.6 177.9 39.2 196.1 42.3 211.322,200 26118 29.1 145.7 32.5 162.4 35.7 178.5 39.3 196.7 42.4 212.022,400 26353 29.2 145.9 32.6 163.0 35.8 179.1 39.5 197.4 42.5 212.722,600 26588 29.2 146.2 32.7 163.6 35.9 179.7 39.6 198.0 42.7 213.423,000 27059 29.3 146.7 32.9 164.7 36.2 180.9 39.9 199.3 42.9 214.723,200 27294 29.4 147.0 33.0 165.2 36.3 181.5 40.0 199.9 43.1 215.323,400 27529 29.4 147.2 33.2 165.8 36.4 182.1 40.1 200.5 43.2 216.023,600 27765 29.5 147.5 33.3 166.3 36.5 182.6 40.2 201.1 43.3 216.623,800 28000 29.5 147.7 33.4 166.8 36.6 183.2 40.4 201.8 43.5 217.324,000 28235 29.6 148.0 33.5 167.4 36.8 183.8 40.5 202.4 43.6 217.924,200 28471 29.6 148.2 33.6 167.9 36.9 184.4 40.6 203.0 43.7 218.624,400 28706 29.7 148.5 33.7 168.4 37.0 184.9 40.7 203.6 43.8 219.224,600 28941 29.7 148.7 33.8 168.9 37.1 185.5 40.8 204.2 44.0 219.824,800 29176 29.8 148.9 33.9 169.5 37.2 186.0 41.0 204.8 44.1 220.525,000 29412 29.8 149.2 34.0 170.0 37.3 186.6 41.1 205.4 44.2 221.126,200 30824 30.1 150.6 34.6 173.0 38.0 189.9 41.8 208.9 44.9 224.725,400 29882 29.9 149.7 34.2 171.0 37.5 187.7 41.3 206.5 44.5 222.325,600 30118 30.0 149.9 34.3 171.5 37.6 188.2 41.4 207.1 44.6 222.925,800 30353 30.0 150.1 34.4 172.0 37.8 188.8 41.5 207.7 44.7 223.526,000 30588 30.1 150.4 34.5 172.5 37.9 189.3 41.7 208.3 44.8 224.1
22
2nd of 2 pages
Table D Uncorrected Chimney Height (U) for a range of Input/Output ratings
Heavy Oil CV (gross) 42.9Mj/kg Sulphur % = 3.5
U and 5 U by Area Category
Table C
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 28
0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 8 8.5 9 9.5 10 10.5 11 11.5 12 12.5 13 13.5 14 14.5 15
H
6 7 7 7 8 8 8 8 9 9 9 10 10 10 11 11 11 11 12
8 9 9 9 10 10 10 10 11 11 11 12 12 12 13 13 13 13 14
10 11 11 11 12 12 12 12 13 13 13 14 14 14 15 15 15 15 16
12 13 13 13 14 14 14 14 15 15 15 16 16 16 17 17 17 17 18
14 15 15 15 16 16 16 16 17 17 17 18 18 18 19 19 19 19 20
16 17 17 17 18 18 18 18 19 19 19 20 20 20 21 21 21 21 22
18 19 19 19 20 20 20 20 21 21 21 22 22 22 23 23 23 23 24
20 21 21 21 22 22 22 22 23 23 23 24 24 24 25 25 25 25 26
22 23 23 23 24 24 24 24 25 25 25 26 26 26 27 27 27 27 28
24 25 25 25 26 26 26 26 27 27 27 28 28 28 29 29 29 29 30
26 27 27 27 28 28 28 28 29 29 29 30 30 30 31 31 31 31 32
28 29 29 29 30 30 30 30 31 31 31 32 32 32 33 33 33 33 34
30 31 31 31 32 32 32 32 33 33 33 34 34 34 35 35 35 35 36
32 33 33 33 34 34 34 34 35 35 35 36 36 36 37 37 37 37 38
34 35 35 35 36 36 36 36 37 37 37 38 38 38 39 39 39 39 40
36 37 37 37 38 38 38 38 39 39 39 40 40 40 41 41 41 41 42
38 39 39 39 40 40 40 40 41 41 41 42 42 42 43 43 43 43 44
40 41 41 41 42 42 42 42 43 43 43 44 44 44 45 45 45 45 46
42 43 43 43 44 44 44 44 45 45 45 46 46 46 47 47 47 47 48
44 45 45 45 46 46 46 46 47 47 47 48 48 48 49 49 49 49 50
46 47 47 47 48 48 48 48 49 49 49 50 50 50 51 51 51 51 52
48 49 49 49 50 50 50 50 51 51 51 52 52 52 53 53 53 53 54
50 51 51 51 52 52 52 52 53 53 53 54 54 54 55 55 55 55 56
12 12 13 13 13 14 14 14 14 15 15
14 14 15 15 15 16 16 16 16 17 17
16 16 17 17 17 18 18 18 18 19 19
18 18 19 19 19 20 20 20 20 21 21
20 20 21 21 21 22 22 22 22 23 23
22 22 23 23 23 24 24 24 24 25 25
24 24 25 25 25 26 26 26 26 27 27
26 26 27 27 27 28 28 28 28 29 29
28 28 29 29 29 30 30 30 30 31 31
30 30 31 31 31 32 32 32 32 33 33
32 32 33 33 33 34 34 34 34 35 35
34 34 35 35 35 36 36 36 36 37 37
36 36 37 37 37 38 38 38 38 39 39
38 38 39 39 39 40 40 40 40 41 41
40 40 41 41 41 42 42 42 42 43 43
42 42 43 43 43 44 44 44 44 45 45
44 44 45 45 45 46 46 46 46 47 47
46 46 47 47 47 48 48 48 48 49 49
48 48 49 49 49 50 50 50 50 51 51
50 50 51 51 51 52 52 52 52 53 53
52 52 53 53 53 54 54 54 54 55 55
54 54 55 55 55 56 56 56 56 57 57
56 56 57 57 57 58 58 58 58 59 59
23
Uncorrected height ‘U’
Table D Corrected height (c) for a range of U and building height (H)
Based on C = H + 0.6 x U (See clause 23 of Memorandum)
Shaded area relates to inputfor sample calculation 1a
Shaded area relatesto input for samplecalculation 1b
H = the building height in metres measured to its ridge or highest point, ignoring lift or tank rooms, or any other projection having an area of less than 1% of the roof area
Table D
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 29
25 25.5 26 26.5 27 27.5 28 28.5 29 29.5 30
25 25.5 26 26.5 27 27.5 28 28.5 29 29.5 30
25 25.5 26 26.5 27 27.5 28 28.5 29 29.5 30
27 27 28 28 28 29 29 29 29 30 30
29 29 30 30 30 31 31 31 31 32 32
31 31 32 32 32 33 33 33 33 34 34
33 33 34 34 34 35 35 35 35 36 36
35 35 36 36 36 37 37 37 37 38 38
37 37 38 38 38 39 39 39 39 40 40
39 39 40 40 40 41 41 41 41 42 42
41 41 42 42 42 43 43 43 43 44 44
43 43 44 44 44 45 45 45 45 46 46
45 45 46 46 46 47 47 47 47 48 48
47 47 48 48 48 49 49 49 49 50 50
49 49 50 50 50 51 51 51 51 52 52
51 51 52 52 52 53 53 53 53 54 54
53 53 54 54 54 55 55 55 55 56 56
55 55 56 56 56 57 57 57 57 58 58
57 57 58 58 58 59 59 59 59 60 60
59 59 60 60 60 61 61 61 61 62 62
61 61 62 62 62 63 63 63 63 64 64
63 63 64 64 64 65 65 65 65 66 66
65 65 66 66 66 67 67 67 67 68 68
H
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
24
15.5 16 16.5 17 17.5 18 18.5 19 19.5 20 20.5 21 21.5 22 22.5 23 23.5 24 24.5
17 18 18 18 19 19 19 19 20 20 20.5 21 21.5 22 22.5 23 23.5 24 24.5
19 20 20 20 21 21 21 21 22 22 22 23 23 23 24 24 24 24 25
21 22 22 22 23 23 23 23 24 24 24 25 25 25 26 26 26 26 27
23 24 24 24 25 25 25 25 26 26 26 27 27 27 28 28 28 28 29
25 26 26 26 27 27 27 27 28 28 28 29 29 29 30 30 30 30 31
27 28 28 28 29 29 29 29 30 30 30 31 31 31 32 32 32 32 33
29 30 30 30 31 31 31 31 32 32 32 33 33 33 34 34 34 34 35
31 32 32 32 33 33 33 33 34 34 34 35 35 35 36 36 36 36 37
33 34 34 34 35 35 35 35 36 36 36 37 37 37 38 38 38 38 39
35 36 36 36 37 37 37 37 38 38 38 39 39 39 40 40 40 40 41
37 38 38 38 39 39 39 39 40 40 40 41 41 41 42 42 42 42 43
39 40 40 40 41 41 41 41 42 42 42 43 43 43 44 44 44 44 45
41 42 42 42 43 43 43 43 44 44 44 45 45 45 46 46 46 46 47
43 44 44 44 45 45 45 45 46 46 46 47 47 47 48 48 48 48 49
45 46 46 46 47 47 47 47 48 48 48 49 49 49 50 50 50 50 51
47 48 48 48 49 49 49 49 50 50 50 51 51 51 52 52 52 52 53
49 50 50 50 51 51 51 51 52 52 52 53 53 53 54 54 54 54 55
51 52 52 52 53 53 53 53 54 54 54 55 55 55 56 56 56 56 57
53 54 54 54 55 55 55 55 56 56 56 57 57 57 58 58 58 58 59
55 56 56 56 57 57 57 57 58 58 58 59 59 59 60 60 60 60 61
57 58 58 58 59 59 59 59 60 60 60 61 61 61 62 62 62 62 63
59 60 60 60 61 61 61 61 62 62 62 63 63 63 64 64 64 64 65
15.5 16 16.5 17 17.5 18 18.5 19 19.5 20 20.5 21 21.5 22 22.5 23 23.5 24 24.5 25 25.5 26 26.5 27 27.5 28 28.5 29 29.5 30
In the shaded area, C = U because U>2.5 x H(See clause 21 and 25b of the Memorandum)
H = the building height in metres measured to its ridge or highest point, ignoring lift or tank rooms, or any other projection having an area of less than 1% of the roof area
Table D Corrected height (c) for a range of U and building height (H)
Based on C = H + 0.6 x U (See clause 23 of Memorandum)
Table E
Uncorrected height ‘U’
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 30
30.5 31 31.5 32 32.5 33 33.5 34 34.5 35 35.5 36 36.5 37 37.5 38 38.5 39 39.5 40
25
In the shaded area, C = U because U>2.5 x H(See clause 21 and 25b of the Memorandum)
H = the building height in metres measured to its ridge or highest point, ignoring lift or tank rooms, or any other projection having an area of less than 1% of the roof area
30.5 31 31.5 32 32.5 33 33.5 34 34.5 35 35.5 36 36.5 37 37.5 38 38.5 39 39.5 40
30.5 31 31.5 32 32.5 33 33.5 34 34.5 35 35.5 36 36.5 37 37.5 38 38.5 39 39.5 40
30.5 31 31.5 32 32.5 33 33.5 34 34.5 35 35.5 36 36.5 37 37.5 38 38.5 39 39.5 40
30.5 31 31.5 32 32.5 33 33.5 34 34.5 35 35.5 36 36.5 37 37.5 38 38.5 39 39.5 40
32 33 33 33 34 34 34 34 35 35 35.5 36 36.5 37 37.5 38 38.5 39 39.5 40
34 35 35 35 36 36 36 36 37 37 37 38 38 38 39 39 39 39 40 40
36 37 37 37 38 38 38 38 39 39 39 40 40 40 41 41 41 41 42 42
38 39 39 39 40 40 40 40 41 41 41 42 42 42 43 43 43 43 44 44
40 41 41 41 42 42 42 42 43 43 43 44 44 44 45 45 45 45 46 46
42 43 43 43 44 44 44 44 45 45 45 46 46 46 47 47 47 47 48 48
44 45 45 45 46 46 46 46 47 47 47 48 48 48 49 49 49 49 50 50
46 47 47 47 48 48 48 48 49 49 49 50 50 50 51 51 51 51 52 52
48 49 49 49 50 50 50 50 51 51 51 52 52 52 53 53 53 53 54 54
50 51 51 51 52 52 52 52 53 53 53 54 54 54 55 55 55 55 56 56
52 53 53 53 54 54 54 54 55 55 55 56 56 56 57 57 57 57 58 58
54 55 55 55 56 56 56 56 57 57 57 58 58 58 59 59 59 59 60 60
56 57 57 57 58 58 58 58 59 59 59 60 60 60 61 61 61 61 62 62
58 59 59 59 60 60 60 60 61 61 61 62 62 62 63 63 63 63 64 64
60 61 61 61 62 62 62 62 63 63 63 64 64 64 65 65 65 65 66 66
62 63 63 63 64 64 64 64 65 65 65 66 66 66 67 67 67 67 68 68
64 65 65 65 66 66 66 66 67 67 67 68 68 68 69 69 69 69 70 70
66 67 67 67 68 68 68 68 69 69 69 70 70 70 71 71 71 71 72 72
68 69 69 69 70 70 70 70 71 71 71 72 72 72 73 73 73 73 74 74
Uncorrected height ‘U’
H
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
Table D Corrected height (c) for a range of U and building height (H)
Based on C = H + 0.6 x U (See clause 23 of Memorandum)
Table F
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 31
A
additional chimney height In calculation process on page 13
approval 2, 3, 4
area category 6 and in calculation process on page 13
B
balanced flue 15
building height 16, 17, 18, 19,
building width 17, 19,
C
calculations 28 and page 13
chemical process plants 3
chimney height 5, 6, 21, 23, 16
clean air act memorandum 1, 2, 4, 5, 6, 7, 9, 10, 11, 12, 13, 21, 27, 28
combined cycle 6
combined emission 21, 22
common flue 21, 22
common header 14, 21
complex building 19
cone 13 and Figure 2
corrected height In sample calculation on page 13
D
diesel generator exhausts 4, 10, 24
discharge height 2, 3, 6
discharge plume 26
discharge velocity 13
dispersion 6
dispersion modeling 6
dust 1
E
effective chimney height 6
engines 3
equipment rating 4, 7, 13
exhaust louvre 27
exhausts 1
exit cone 13
exit velocity (efflux velocity) 13, 14
F
fan (induced draught) 14
fan dilution 27
final discharge height 14
fuels 11
full load 8
G
gas turbine exhaust 3, 9
gas-oil 25
gaseous fuel 4
generator exhaust 4, 10, 24
geographical location 6 and in calculation process on page 13
grit 1
ground level 16
guidance note 8
guides (published) 6
I
incinerator 1, 3, 9, 24
individual chimney 22
induced draught fan 14
initial discharge plume 5
L
large plant 6, 3
lattice tower 19
legislation 1
lift room 16,20
lift room area 16, and in sample calculation on page 13
liquid fuel 4
26
IndexSubject Location
(No’s. = Q & A paragraphs)Subject Location
(No’s. = Q & A paragraphs)
local authority 4
location 3, 6, 15, 21, 23
louvres 20, 27
low discharge velocity 14
low level discharge 27
lower limit 4
M
maximum emission 8
minimum chimney height 6
multi-flued chimney 23, 24
N
nitric oxide 12
normal operating load 7
Northern Ireland 1, 4
nuisance 2
O
odours 1
P
plant location 3, 6, 15, 21, 23
plant room 18, 20
plume 5, 13, 26
pollutant concentration 5
pollutants 3, 5, 12, 25 Also tables on page 17
pollution 1, 5, 6, 15
porous structure 19
prescribed processes 3
process guidance notes 6
pulverized fuel 4
R
rated input 7
rating 13
reduced load 7, 8
roof 20
roof area In sample calculation on page 13
roof buildings 16,20
roof level 27
room-sealed balanced
flue system 15
S
solid fuel 4
stand-by plant 25
sulphur 11
sulphur dioxide 12
T
tank room 16, 20
tank room area 16, and in sample calculation on page 13
tapered cone 13
target velocities 8
technical guidance note D1 6, 13, 18, 24
trees 19
turndown ratio 8
U
“U” 17, 18, 19 and in sample
calculation on page 13
uncorrected height In sample calculation on page 13
V
velocities 8, 13
ventilation air intake 27
very large plant 3
VLS 11
VLS fuels 12
W
waste oil 3
windows 26
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 32
27
Notes
The information, tables and sample calculations in this document are intended to
provide guidance on the correct application of chimney system discharge dictated by
the Clean Air Act Legislation. Whilst we consider the information contained to be
accurate, users are advised where necessary to check any calculations and clear all
applications with an appropriate authority
Clean Air Act Booklet A/W 10/1/01 3:50 pm Page 33