class 15 control action and controllers

21
ICE401: PROCESS INSTRUMENTATION AND CONTROL Class 15 Control Action and Controllers Dr. S. Meenatchisundaram Email: [email protected] Process Instrumentation and Control (ICE 401) Dr. S.Meenatchisundaram, MIT, Manipal, Aug Nov 2015

Upload: manipal-institute-of-technology

Post on 12-Apr-2017

830 views

Category:

Engineering


1 download

TRANSCRIPT

Page 1: Class 15   control action and controllers

ICE401: PROCESS INSTRUMENTATION

AND CONTROL

Class 15

Control Action and Controllers

Dr. S. Meenatchisundaram

Email: [email protected]

Process Instrumentation and Control (ICE 401)

Dr. S.Meenatchisundaram, MIT, Manipal, Aug – Nov 2015

Page 2: Class 15   control action and controllers

Control System Parameters:

Process Instrumentation and Control (ICE 401)

Dr. S.Meenatchisundaram, MIT, Manipal, Aug – Nov 2015

• Let us now examine the general properties of the controller

shown in Figure.

To review:

1. Inputs to the controller are a measured indication of both the

controlled variable and a setpoint representing the desired

value of the variable, expressed in the same fashion as the

measurement;

Page 3: Class 15   control action and controllers

Control System Parameters:

Process Instrumentation and Control (ICE 401)

Dr. S.Meenatchisundaram, MIT, Manipal, Aug – Nov 2015

2. The controller output is a signal representing action to be

taken when the measured value of the controlled variable

deviates from the setpoint.

3. The measured indication of a variable is denoted by b, and

the actual variable is denoted by c. Thus, if a sensor measures

temperature by conversion to resistance, the actual variable is

temperature in degrees Celsius, but the measured indication

is resistance in ohms.

4. Further conversion may be performed by transducers or

transmitters to provide a current in mA, for example. In such

a case, the current becomes the measured indication of the

variable.

Page 4: Class 15   control action and controllers

Control System Parameters:

Process Instrumentation and Control (ICE 401)

Dr. S.Meenatchisundaram, MIT, Manipal, Aug – Nov 2015

Error:

• The deviation or error of the controlled variable from the

setpoint is given by

e = r – b (15.1)

where

r = setpoint of variable (reference)

b = measured indication of variable

e = error

• Equation (15.1) expresses error in an absolute sense, or in

units of the measured analog of the control signal. Thus, if

the setpoint in a 4 to 20 mA range corresponds to 9.9 mA and

the measured value is 10.7 mA, we have an error of – 0.8mA.

Page 5: Class 15   control action and controllers

Control System Parameters:

Process Instrumentation and Control (ICE 401)

Dr. S.Meenatchisundaram, MIT, Manipal, Aug – Nov 2015

• To describe controller operation in a general way, it is better

to express the error as percent of the measured variable range

(i.e., the span).

• The measured value of a variable can be expressed as percent

of span over a range of measurement by the equation

(15.2)

where cp = measured value as percent of measurement range

c = actual measured value

cmin = minimum of measured value

cmax = maximum of measured value

min

max min

100p

c cc

c c

−= ×

Page 6: Class 15   control action and controllers

Control System Parameters:

Process Instrumentation and Control (ICE 401)

Dr. S.Meenatchisundaram, MIT, Manipal, Aug – Nov 2015

Cycling:

• One of the most important modes is an oscillation of the

error about zero. This means the variable is cycling above

and below the setpoint value.

• Such cycling may continue indefinitely, in which case we

have steady-state cycling. Here we are interested in both the

peak amplitude of the error and the period of the oscillation.

• If the cycling amplitude decays to zero, however, we have a

cyclic transient error. Here we are interested in the initial

error, the period of the cyclic oscillation, and decay time for

the error to reach zero.

Page 7: Class 15   control action and controllers

Control System Parameters:

Process Instrumentation and Control (ICE 401)

Dr. S.Meenatchisundaram, MIT, Manipal, Aug – Nov 2015

Reverse and Direct Action:

• The error that results from measurement of the controlled

variable may be positive or negative, because the value may

be greater or less than the setpoint.

• How this polarity of the error changes the controller output

can be selected according to the nature of the process.

• A controller operates with direct action when an increasing

value of the controlled variable causes an increasing value of

the controller output. An example would be a level-control

system that outputs a signal to an output valve.

• Clearly, if the level rises (increases), the valve should be

opened (i.e., its drive signal should be increased).

Page 8: Class 15   control action and controllers

Control System Parameters:

Process Instrumentation and Control (ICE 401)

Dr. S.Meenatchisundaram, MIT, Manipal, Aug – Nov 2015

Reverse and Direct Action:

• Reverse action is the opposite case, where an increase in a

controlled variable causes a decrease in controller output.

• An example of this would be a simple temperature control

from a heater. If the temperature increases, the drive to the

heater should be decreased.

Page 9: Class 15   control action and controllers

Classification of Controller Modes:

Process Instrumentation and Control (ICE 401)

Dr. S.Meenatchisundaram, MIT, Manipal, Aug – Nov 2015

Page 10: Class 15   control action and controllers

Discontinuous Controller Modes:

Process Instrumentation and Control (ICE 401)

Dr. S.Meenatchisundaram, MIT, Manipal, Aug – Nov 2015

Two-Position Mode:

• The most elementary controller mode is the ON/OFF, or two-

position, mode. This is an example of a discontinuous mode.

• It is the simplest and the cheapest. Although an analytic

equation cannot be written, we can, in general, write

• When the measured value is less than the setpoint, full

controller output results. When it is more than the setpoint,

the controller output is zero. A heater is a common example.

If the temperature drops below a setpoint, the heater is turned

ON. If the temperature rises above the setpoint, it turns OFF.

00%

0100%

p

p

ep

e

<=

>

Page 11: Class 15   control action and controllers

Discontinuous Controller Modes:

Process Instrumentation and Control (ICE 401)

Dr. S.Meenatchisundaram, MIT, Manipal, Aug – Nov 2015

Neutral Zone:

• Any practical implementation of the two-position controller,

there is an overlap as increases through zero or decreases

through zero. In this span, no change in controller output

occurs.

• This is best shown in Figure 15.1, which plots p versus ep for

a two-position controller.

Figure 15.1 Two-position controller action with neutral zone

Page 12: Class 15   control action and controllers

Discontinuous Controller Modes:

Process Instrumentation and Control (ICE 401)

Dr. S.Meenatchisundaram, MIT, Manipal, Aug – Nov 2015

Neutral Zone:

• We see that until an increasing error changes by ∆ep above

zero, the controller output will not change state.

• In decreasing, it must fall ∆ep below zero before the controller

changes to the 0% rating.

• The range 2∆ep, which is referred to as the neutral zone or

differential gap, is often purposely designed above a certain

minimum quantity to prevent excessive cycling.

• The existence of such a neutral zone is an example of

desirable hysteresis in a system.

Page 13: Class 15   control action and controllers

Discontinuous Controller Modes:

Process Instrumentation and Control (ICE 401)

Dr. S.Meenatchisundaram, MIT, Manipal, Aug – Nov 2015

Figure 15.2 On–off controller response

Page 14: Class 15   control action and controllers

Discontinuous Controller Modes:

Process Instrumentation and Control (ICE 401)

Dr. S.Meenatchisundaram, MIT, Manipal, Aug – Nov 2015

Figure 15.3 On–off controller response with dead band

Page 15: Class 15   control action and controllers

Discontinuous Controller Modes:

Process Instrumentation and Control (ICE 401)

Dr. S.Meenatchisundaram, MIT, Manipal, Aug – Nov 2015

Example:

15.1 A liquid-level control system linearly converts a

displacement of 2 to 3 m into a 4 to 20-mA control signal. A

relay serves as the two-position controller to open or close an

inlet valve. The relay closes at 12 mA and opens at 10 mA. Find

(a) the relation between displacement level and current,

(b) the neutral zone or displacement gap in meters.

Solution: The relation between level and a current is a linear

equation such as H = K I + H0

Solving yields: K=0.0625 m/mA, H0=1.75m, HH=2.5m, and

HL=2.375m.

Neutral zone is 2.5 – 2.375 = 0.125m

Page 16: Class 15   control action and controllers

Discontinuous Controller Modes:

Process Instrumentation and Control (ICE 401)

Dr. S.Meenatchisundaram, MIT, Manipal, Aug – Nov 2015

Assignment 2.1:

The temperature of water in a tank is controlled by a two-

position controller. When the heater is off the temperature drops

at 2 K per minute. When the heater is on the temperature rises at

4 K per minute. The setpoint is 323 K and the neutral zone is

±4% of the setpoint. There is a 0.5-min lag at both the on and off

switch points. Find the period of oscillation and plot the water

temperature versus time.

Page 17: Class 15   control action and controllers

Discontinuous Controller Modes:

Process Instrumentation and Control (ICE 401)

Dr. S.Meenatchisundaram, MIT, Manipal, Aug – Nov 2015

Multi-Position Mode:

• A logical extension of the previous two-position control

mode is to provide several intermediate, rather than only two,

settings of the controller output.

• This discontinuous control mode is used in an attempt to

reduce the cycling behavior and overshoot and undershoot

inherent in the two-position mode.

• As an example, a three position controller can be

represented as1

1 1

1

100%

50%

0%

p

p

p

e e

p e e e

e e

>

= − < <

< −

Page 18: Class 15   control action and controllers

Discontinuous Controller Modes:

Process Instrumentation and Control (ICE 401)

Dr. S.Meenatchisundaram, MIT, Manipal, Aug – Nov 2015

Multi-Position Mode:

• As long as the error is between and of the setpoint, the

controller stays at some nominal setting indicated by a

controller output of 50%.

• If the error exceeds the setpoint by or more, then the output

is increased by 100%. If it is less than the setpoint by or

more, the controller output is reduced to zero.

• Figure 15.4 illustrates this mode graphically. Some small

neutral zone usually exists about the change points, but not

by design; thus, it is not shown. This type of control mode

usually requires a more complicated final control element,

because it must have more than two settings.

Page 19: Class 15   control action and controllers

Discontinuous Controller Modes:

Process Instrumentation and Control (ICE 401)

Dr. S.Meenatchisundaram, MIT, Manipal, Aug – Nov 2015

Figure 15.4 Three-position controller action

Page 20: Class 15   control action and controllers

Discontinuous Controller Modes:

Process Instrumentation and Control (ICE 401)

Dr. S.Meenatchisundaram, MIT, Manipal, Aug – Nov 2015

Figure 15.5 Relationship between error and three-position controller action, including

the effects of lag

Page 21: Class 15   control action and controllers

References:

• Process Control Instrumentation Technology, by Curtis D.

Johnson, Eighth Edition, Pearson Education Limited.

Process Instrumentation and Control (ICE 401)

Dr. S.Meenatchisundaram, MIT, Manipal, Aug – Nov 2015