North Hills Junior High SchoolPittsburgh, PA
Senior Thesis Final Presentation 2005
Chris RushLighting / Electrical
Faculty Consultant: Dr. Mistrick
• Building Introduction• Lighting
– Entrance Canopy– Main Lobby– Auditorium– Typical Classroom
• System Comparison• Daylight Study
• Construction Management– Classroom Lighting Estimates– Classroom Lighting Lifecycle Costs
• Mechanical– Auditorium HVAC Evaluation
• Electrical• Conclusion
Presentation Outline
• Site: Hilltop campus with Senior High and athletics• Occupants: North Hills 7th, 8th, and 9th grades• Size: 220,000 sq.ft., 3 stories• Architect & MEP: Burt Hill Kosar Rittelmann• Renovation: 1997-1999
Building Introduction
• Building Introduction• Lighting
– Entrance Canopy– Main Lobby– Auditorium– Typical Classroom
• System Comparison• Daylight Study
• Construction Management– Classroom Lighting Estimates– Classroom Lighting Lifecycle Costs
• Mechanical– Auditorium HVAC Evaluation
• Electrical• Conclusion
Presentation Outline
Entrance Canopy
Main Lobby
Auditorium
Omitted Designs Lighting Depth
• Building Introduction• Lighting
– Entrance Canopy– Main Lobby– Auditorium– Typical Classroom
• System Comparison• Daylight Study
• Construction Management– Classroom Lighting Estimates– Classroom Lighting Lifecycle Costs
• Mechanical– Auditorium HVAC Evaluation
• Electrical• Conclusion
Presentation Outline
Classroom Lighting Depth
• Concepts– Clear– Stimulating
• Considerations– Illuminance
• 50 fc on workplane• 50 fc on chalkboards
– Limited VDT use– Daylight– Power Density
• 1.4 W / sq.ft.
Classroom Lighting Depth
• Option 1 - Recessed– 9” x 4’ parabolic– 2 T8 lamps– 4 Symmetric– 11 Asymmetric
• Option 2 - Pendant– 12” x 4’ Direct / Indirect– 2 T8 lamps– 12 luminaires
Classroom Lighting Depth
Recessed Pendant
Classroom Lighting Depth
• Recessed– 61.5 fc Workplane– 62.6 fc Long Chalkboard– 49.9 fc Short Chalkboard– 1.29 W/sf
• Pendant– 56.7 fc Workplane– 26.9 fc Long Chalkboard– 27.0 fc Short Chalkboard– 1.03 W/sf
• Building Introduction• Lighting
– Entrance Canopy– Main Lobby– Auditorium– Typical Classroom
• System Comparison• Daylight Study
• Construction Management– Classroom Lighting Estimates– Classroom Lighting Lifecycle Costs
• Mechanical– Auditorium HVAC Evaluation
• Electrical• Conclusion
Presentation Outline
Classroom Daylighting Lighting Depth• Daylight Analysis, Radiance
– Daylight conditions• 5 days
– Two-month intervals– June/July omitted
• 3 times– 2.5 hour intervals– 7:30 – 3:00 school day
• 3 sky conditions– Clear, overcast, intermediate– Weighted by weather data
– Electric lighting• 2 lighting systems• 2 zones each
Classroom Daylighting Lighting Depth
36 84 132 180 228 276 324 372 42012
60
108
156
204
X (inches)
Y (in
ches
)
Yearly Average Daylight Illuminance on Workplane (Lux)
0-200200-400400-600600-800800-10001000-12001200-1400
Average: 238 lux Max: 1218 lux Min: 63 lux
Classroom Daylighting Lighting Depth
• Yearly Energy Use Process– Critical point– Dimming %– Power input– Energy per year
• Two situations– Entire room dimmed as one– Only zone nearest window dimmed
Classroom Daylighting Lighting Depth
97711941368Option 2 - Pendant
110714921710Option 1 - Recessed
Partially DimmedAll DimmedUndimmed
Yearly Energy Use (kWh)
• Recessed– 9 undimmed– 6 dimmed
• Pendant– 8 undimmed– 4 dimmed
• Building Introduction• Lighting
– Entrance Canopy– Main Lobby– Auditorium– Typical Classroom
• System Comparison• Daylight Study
• Construction Management– Classroom Lighting Estimates– Classroom Lighting Lifecycle Costs
• Mechanical– Auditorium HVAC Evaluation
• Electrical• Conclusion
Presentation Outline
Classroom Estimates CM Breadth
• Cost considerations– Ceiling construction
• Recessed / Pendant• Irregular layout
– Fixture costs– Wiring runs– Dimming system cost
• Control wiring• Dimming ballasts• Photosensor and controls
Classroom Estimates CM Breadth
52.980.7total hours$6,262$6,043total cost
UNDIMMED
12.117.8wiring time
12.621.1fixture time
28.241.9ceiling time
$688$928wiring cost
$3,993$3,030fixture cost
$1,581$2,085ceiling cost
PENDANTRECESSED
UNDIMMED SUMMARIES
54.082.3total hours$7,750$7,754total cost
DIMMED
1.081.59control wire time
$780$975dimming ballast cost
$650$650daylight controls
$59$86control wire cost
PENDANTRECESSED
ADDITIONAL DIMMING COSTS
• Building Introduction• Lighting
– Entrance Canopy– Main Lobby– Auditorium– Typical Classroom
• System Comparison• Daylight Study
• Construction Management– Classroom Lighting Estimates– Classroom Lighting Lifecycle Costs
• Mechanical– Auditorium HVAC Evaluation
• Electrical• Conclusion
Presentation Outline
Classroom Lifecycle Cost CM Breadth
• Building Life Cycle Cost 5.3 (NIST)– FEMP energy analysis– 25 year lifecycle– Pendant / Recessed, Dimmed / Undimmed
• First costs• Energy use ($0.08375 per kWh)
– Maintenance and replacement omitted• Assumed constant between systems• Comparison only
Classroom Lifecycle Cost CM Breadth
Recessed DimmedRecessed Undimmed
$9,938$2,184 $7,754 $9,417$3,374 $6,043 TotalEnergyFirst CostTotalEnergyFirst Cost
Pendant DimmedPendant Undimmed
$9,678$1,928 $7,750 $8,961$2,699 $6,262 TotalEnergyFirst CostTotalEnergyFirst Cost
25 year lifecycle
• Building Introduction• Lighting
– Entrance Canopy– Main Lobby– Auditorium– Typical Classroom
• System Comparison• Daylight Study
• Construction Management– Classroom Lighting Estimates– Classroom Lighting Lifecycle Costs
• Mechanical– Auditorium HVAC Evaluation
• Electrical• Conclusion
Presentation Outline
Classroom Comparison Conclusion
$9,678$8,961$9,938$9,41725 Yr. Total Cost$1,928$2,699$2,184$3,37425 Yr. Energy Cost54.052.982.380.7Labor Time$7750$6262$7754$6043First Cost977136811071710Yearly Energy (kWh)
26.9, 27.062.6, 49.9Chalkboard Illuminance (fc)56.761.5Workplane Illuminance (fc)
DimmedUndimmedDimmedUndimmed
PendantRecessed
• Other factors– Aesthetics– Suspension height– Daylight dimming reliability
Classroom Comparison Conclusion
• Recommendations– Recessed
• Superior chalkboard lighting• Minimal cost difference• Preferred appearance• No height issues
– Undimmed• Lack of savings• Potential unreliability
Thank You
• Faculty– Dr. Mistrick– Dr. Moeck– Professor Parfitt
• Industry consultants– Ed Wunderley– Discussion board members
• Family and Friends
Questions
0.114$6.791" conduit per LF
0.00889$0.48control wiring per LF
0.00727$0.33#12 wiring per LF
0.017variescarrier channels per SF
0.016$0.52ceiling labor per SF
time in labor$0.82ceiling material per SF
pre-installed$65.00added cost of Mark VII ballast
timecost
1.5LF of wire per LF conduit
(with 5% waste)854.7area
CONSTANTS
1.0531.404hours per fixture
$0.51$0.58cost of carrier channels per SF
$42.75$57.00labor cost per fixture
$290$145material cost per fixture
12ceiling labor multiplier
121.3125178.875feet of control wire
242.625357.75feet of wire
80.875119.25feet of conduit
1215# of fixtures
PENDANTRECESSED
QUANTITIES AND COSTS
52.980.7total hours
$6,262$6,043total cost
UNDIMMED
12.117.8wiring time
12.621.1fixture time
28.241.9ceiling time
$688$928wiring cost
$3,993$3,030fixture cost
$1,581$2,085ceiling cost
PENDANTRECESSED
UNDIMMED SUMMARIES
54.082.3total hours
$7,750$7,754total cost
DIMMED
1.081.59control wire time
$780$975dimming ballast cost
$650$650Wattstopper controls
$59$86control wire cost
PENDANTRECESSED
ADDITIONAL DIMMING COSTS