AP-MSM-08All Product Catalogue
Chilled Water System Solution
CONTENTS:
Chilled Water System SolutionMcQuay Offers ; Comprehensive Solution ........................ 2 In Air Conditioning Needs
Features Of McQuay Chilled Water Products ................... 3
Smart Manager ................................................................. 4
McQuay Air Cooled Mini Chiller Series ............................. 7
Tandem Compressors Air-Cooled Mini Chiller ................ 12
Inverter Mini Chiller ......................................................... 13
McQuay Chilled Water Fan Coil Units ..............................15
NIM & NIM PC Networking Control System .....................16
McQuay Chilled Water Fan Coil Units Range ..................17
SpecificationsMini Chiller Specifications ............................................... S1
Chilled Water Fan Coil Unit Specifications ..................... S6
MinneapolisMinneapolis
FaribaultFaribaultOwatonnaOwatonna
StauntanStauntan
Mexico CityMexico City
AuburnAuburn
CramlingtonCramlington
CecchinaCecchina SuZhouSuZhou
WuhanWuhan
ShenZhenShenZhen
Sungai BulohSungai Buloh
CikarangCikarang
Manufacturing Plant
GLOBAL DISTRIBUTION NETWORK
Americas• USA • Puerto Rico • Mexico • Paraguay • Uruguay • Guadaloupe •
Oceania• Australia • New Zealand •
Middle East & Africa• Jordan • Lebanon • Oman • Qatar • Saudi Arabia • Bahrain • Morocco • Iraq • U.A.E. •
• Mauritius • South Africa • Kenya • Madagascar • Ghana • Nigeria • Tanzania •
Europe• England • Greece • Hungary • Italy • Norway • Poland • Portugal • Russia • Spain •
• Belgium • Tunisia • Croatia • Cyprus • Lithuania • Malta • Slovenia • Ukraine •
• Turkey • Finland • Czech Republic • Romania •
Asia• Cambodia • China • Hong Kong • Indonesia • Maldives •
• Malaysia • Singapore • Thailand • Vietnam • Pakistan •
Product Overview
Model Range
Cooling Capacity (kW)
Heating Capacity (kW)
Electrical Supply
R22 MAC 020/025/030 C/CR
5.0 - 8.1
MAC 040/050/060 C/CR
M4AC 020/025/030 C/CR M4AC 040/050/060 C/CR
M5ACV 030 CR M5ACV 055/075 CR
MWM 007/010/015/020 GWMWM 301W MCK 020/025/030/040/050 AW
2.34-5.28
3.02-6.74
6.62-10.80
8.40-12.90
M5AC 020/025 CR
11.7 - 15.5
5.9 - 9.5 12.6 - 17.5
R407C
R410A
R410A Inverter
50Hz
60Hz
Model Range
Cooling Capacity (kW)
Heating Capacity (kW)
Electrical Supply
Model Range
Cooling Capacity (kW)
Heating Capacity (kW)
Electrical Supply50Hz
50Hz
60Hz
60Hz
MCM 007/010/015 CBW MCM 020/025/030/040/050 DW
1.90-3.08 5.19-13.19
2.28-4.19 6.45-15.10
MAC 080/100/120/150/210 C/CR
M4AC 080/100/120/150/210 C/CR
M5ACV 100/135/210 CR
MCK 020/025/030/040/050 AWH
3.81-5.16
MCK 015/020/025 BW MCK 010/015/020 CW
3.66-5.27 2.34-4.25
10.55-13.77 4.69-6.15 3.22-5.42
M5AC 030/040/050/055 CR
21.6 - 58.6 7.3 - 14.9
26.4 - 61.5 9.8 - 18.0
MCC 010/015/020/025/028 CWMCC 030/038/040/050/060 CW MDB 075/100/125/150 BWMCW 200/300/400/600 C/H
MCW 800/1000/1200 C/H
2.9-15.8 2.1-4.6
5.6-32.2 4.7-9.6
INTRODUCTION
McQuay is committed to offer you with the better solution in
your air conditioning needs. In the new series of chilled water
products, McQuay is not just offering you with wide range of
chilled water air conditioning equipments, but a better solution
from selecting the equipments, designing the water piping
systems to provide easy control of the complete chilled water
system. This is facilitated by the user friendly computer
selection programs and remote monitoring of the operation of
complete system through the Smart Manager.
The series of chilled water product has incorporated the technology of advanced communicating controls,
microprocessor controlled chillers with a wide range and variety of fan coil unit that offers total flexibility.
McQuay Offers ;Chilled Water System
2
McQuay Chilled Water Series Of Products
FEATURES
Year Round Comfort
Can be used in variety of climates with systems that
are available in two versions, cooling only and heat
pump.
Reliable and More Efficient
The refrigerant of the system is confined to within
the chiller itself and therefore no refrigerant is
circulating throughout the building. This will be no
risk of refrigerant leakages in building or risk of poor
oil return that will damage compressor caused by
poor installation.
Multiple compressors in McQuay chiller series offers
stages capacity control that will offer better
efficiency.
Long Piping Applications
McQuay chilled water system avoids the limitation
of piping lengths and bends that exist in Direct
Expansion refrigerant system. The chiller can be
installed far away from the fan coil units, thus
offering flexibility and creativity in the installation.
Quality, Innovative and Compact Design
McQuay chiller is equipped with reliable and quality
components.
Multiple Temperature Zone Control
The operation of the fan coil units can be managed
independently by zones according to similar air
conditioning comfort needs.
3
By adopting the McQuay chilled water system, the comfort in
residential and light commercial buildings such as offices, hospital,
restaurant, hotel and shopping complex can be controlled and
managed from just one point, that is through the Smart Manager.
The Smart Manager is acting as a center to manage the operation of
both the chilled water fan coil units and the chillers.
Besides allowing the user to have customized control for each
connected unit, the Smart Manager is also able to manage the overall
system operating mode of all units based on the air conditioning
system load demand of the building.
Chiller Network BUS Fan Coil Network BUS
Through the versatile Smart Manager controller, the operation of
each equipments in the McQuay chilled water system connected
through the chiller Bus and McQuay own proprietary NIM BUS can
be managed and controlled.
Supported Up To 50 Chillers & 120 Fan Coil Units
FEATURES
Controller
4
Alarm 1
(Ch 0)
Comp 1 overload
01/01/00 12.00am
Display Up To 46 Types Of Chiller Fault/Alarm And 6 Types Of FCU Fault/Alarm
Whenever a fault occurred in either the chiller or fan coil unit, a signal will be
sent to Smart Manager and an alarm message will appear on the LCD,
showing type of alarm, alarm occurred time, date and unit.
This will greatly ease the troubleshooting process and thus reduce the
valuable time of service technicians.
As soon as the fault is being solved, the alarm will automatically dissolve from
the LCD.
Priority Settings
Depending on the application requirement, the Smart Manager offers the flexibility to allow user to set the priority on
the operation of fan coil unit and chiller in a complete McQuay chilled water product system.
If priority is set to Fan Coil Unit, the chiller will be forced to OFF if all fan coil units are OFF. If Chiller Priority is being
set, all fan coil units will be OFF if chillers are OFF.
Threshold Value Setting
If the priority setting is being preset to fan coil unit, the operating mode of the complete McQuay chilled water system
can be synchronized to operate under one same mode. This is achievable through the unique feature called
“Threshold Value Setting”
Smart Manager can command chiller operating mode to switch from current operating mode if the threshold value is meet.
Example,
In a network of 10 fan coil units that is currently operating in COOL mode and a threshold of 60% was set for COOL
mode and threshold of 50% was set for HEAT mode. Should 6 of the fan coil units are requesting for HEAT mode then
the threshold for HEAT is crossed. Signal will be sent by Smart Manager to chiller BUS to switch the operating mode
of all chillers to HEAT mode. Requirement of users will be met.
• Heat Treshold •
Chiller to operate at Heat Mode
Chiller to operate at Cool Mode
0 1 2 3 4 5 6 7 8 9 10
• Cool Treshold •
5
HOLIDAY SETTINGS
Holiday 1Holiday 2Holiday 3Holiday 4Holiday 5
MWM
MCM 2MCK
MCC
MCM 1
Energy Saving Programmable Timer
The operation of the chiller and each fan coil unit
can be preset to operate and to stop at different
time schedule and at different day of a week. Taking
consideration of the fact that certain rooms in a
building will be empty at certain period of the day,
setting timer to On and to Off the operation of units
in those areas will greatly reduce the energy cost of
the building.
At the same time, Smart Manager allows setting up to
five sets of 7 days programmable operating schedules
(2 On/Off timer per day) for each fan coil unit.
Holiday Setting
While designing the Smart Manager, the practical
aspects of equipment application were always the
key points to be considered. Thus resulting in the
creation of “Holiday Setting” feature.
In this feature, users are allowed to set up to 10
holiday timers with each timer can last for duration
of 99 days.
During the duration of Holiday Timer set earlier, all fan
coil units and chiller will automatically be turned Off.
Set Holiday 1
Month : 1Day : 1Duration : Disable
8.00am
9.00am
10.00am
11.00am
12.00am
1.00pm
2.00pm
3.00pm
4.00pm
5.00pm
6.00pm
7.00pm
8.00am
9.00am
10.00am
11.00am
12.00am
1.00pm
2.00pm
3.00pm
4.00pm
5.00pm
6.00pm
7.00pm
Time
MCC
MCK
MCM2
MCM1
MWM
Un
it
6
Memory Backup (EEPROM), Alarm Memory for Chiller and FCU
When there is power failure occurs during
operation, Smart Manager will load the last state
memory from EEPROM after power On reset.
Besides, extra memory space inside the Smart
Manager will allow user to view the previous alarm
records even though its have been dissolved. This
useful information will benefit the service
technician to view the history of maintenance
record done to the unit.
Password Protection For Advanced Parameter Settings (Chiller)
A McQuay chilled water product system with key
parameters that were set by personal to optimize
operating conditions will need to be protected
against any unauthorized disturbance or changes.
The built in “Password Settings” feature will prevent
the losing of key parameter settings in the Smart
Manager.
Low Power Mode (Chiller + FCU)
Smart Manager will turn into low power mode during
electricity power breakdown. It will operate based
on the built in backup battery and only one timer
and interrupt is active. CPU operation is Off and no
display on LCD as well for energy saving purpose.
Key Parameter Display
For easy serviceability and maintenance, Smart
Manager is able to display the key parameter such
as defrost and compressor discharge sensor
temperature, water in/out temperature, status of
compressor On/Off, Cool/Heat mode water in
temperature, etc. Thus, it reduces the cumbersome
of requiring the service technicians to physically go
to site of chiller installation to do the
troubleshooting process.
Accumulative Compressor Run Time
User can also check the compressor run time of
chiller in Smart Manager. It will provide a guideline
as well as posting a reminder for requirement of
routine system service.
Multiple Temperature Zone Control
The operation of the fan coil units can be managed
independently by zones according to similar air
conditioning comfort needs.
Real Time Clock (RTC)
RTC will always appear at the summary pages and
the user is able to set the time and date.
7
McQuay offering you the range of air cooled chiller that is suitable for many applications from residential to
commercial.
McQuay Air Cooled Mini Chiller Series
The McQuay chiller is incorporated with the basic
necessary components such as circulating water
pump, expansion tank, compact brazed plate heat
exchanger, differential pressure switch and the
microprocessor controller and wired control panel.
In addition, the selection of the McQuay chiller could
not be more easy than the user friendly yet versatile
selection softwares for chiller as well as connecting
piping.
In short, Smart Manager Chilled Water Product Range
offers you the better solution to your chilled water
product needs.
8
Model :MAC 040/050/060 C/CRM4AC 040/050/060 C/CRM5ACV 055/075 CR Capacity :Cooling : 11.7 kW to 15.5 kWHeating : 12.6 kW to 17.5 kW
Refrigerant : R22, R407C, R410A
Model :MAC 020/025/030 C/CRM4AC 020/025/030 C/CRM5AC 020/025 CRM5ACV 030 CR Capacity :Cooling : 5 kW to 8.1 kWHeating : 5.9 kW to 9.5 kW
Refrigerant : R22, R407C, R410A
PRODUCT RANGE
Model :M5AC 030/040/050/055 CR Capacity :Cooling: 7.3 kW to 14.9 kWHeating: 9.8 kW to 18.0 kW
Refrigerant : R410A
9
Model :MAC 080/100/120/150 C/CRM4AC 080/100/120/150 C/CRM5ACV 100/135/210 CR Capacity :Cooling : 21.6 kW to 58.6 kWHeating : 26.4 kW to 61.5 kW
Refrigerant : R22, R407C, R410A
Compactness
The MAC/M4AC 020~030 C/CR is such a compact
unit that it can be integrated perfectly with any
architectural design, making it an ideal choice for
house, offices, restaurant and shop.
Scroll Compressor
Scroll Compressors are used for the units to offer a
quieter and more reliable performance over a wide
operating temperature range. (Except MAC/M4AC
020 C/CR which uses rotary compressor).
For MAC/M4AC 030, 040, 050, 060, 080, 100, 120,
150 CR, phase protector is provided to prevent the
compressor from rotating in the wrong directions.
Microprocessor Control
McQuay chillers are equipped with microprocessor
controller that will control and regulate the operation
of the unit.
Besides, the controller that contains the well
developed algorithm will provide protection to the
chiller by accurately sensing the key temperatures
in both the water and refrigerant circuit. Should
there be any abnormal reading received by
controller, an alarm signal will be sent to chiller
panel, followed by protection action plans such as
to stop the operation of compressor, condenser fan
motor or circulating water pump.
Partial Loading
Models MAC/M4AC 080~150 C/CR has been
designed with two separate refrigerant circuits, i.e.
it has two compressors. By doing so, the unit has
part loading capabilities, i.e. 0-50-100% of rated
capacity. This will improve the reliability and energy
efficiency of the unit, especially during low loading
operations.
Fully Equipped Chillers
McQuay chiller is fully integrated and equipped with
key hydronic components such as expansion tank,
water tank, brazed plate heat exchanger and water
circulating pump. The all in one concept will ease
the job of installer.
Brazed Plate Heat Exchanger
The heat exchanger is made of AISI 316 stainless
steel plates closely arranged and brazed together to
maximize possible heat exchange efficiency.
FEATURES
10
Availability Of Connection To Boiler
The microprocessor controller has a built in control
algorithms that allowed the chiller to be connected
to the boiler. By adding a boiler to the system, it can
either work as the sole heating water source in a
Cooling only unit or it can act as the booster heat
source to the Heat Pump chiller.
Safety Protection
The safety protections provided for the McQuay
chiller are:
• High & Low Pressure Switches
• Anti-Freeze Protection Sensor
• Discharge Temperature Sensor
• Over Pressure Relief Valve
• Water Pressure Differential Switch
• Anti-Freeze Heater on BPHE
• Compressor Water Pump &
Fan Motor Overload Protector
Anti-Freeze Protection
The chiller unit has several anti-freeze protection
features:
1. Built-in heater in BPHE
The BPHE has a strip heater around it to
prevent water freezing inside.
2. Anti-Freeze sensor
BPHE can avoid the frosting as the anti-
freeze sensor will send the signal to cut out
the compressor if the water temperature
becomes too cold.
3. Water pressure differential switch
This protection feature will ensure there is
water flow in pipings when the chiller is in
operation. Otherwise, the compressor will
cut out immediately.
Water In Water Out
Up to 50Chillers
Chiller Bus
11
Sequencing Control
For MAC/M4AC 080~150 C/CR, both compressors
will cut in and cut out depending on their
accumulative operating time. This sequencing
control feature will ensure no single compressor is
overload in operation as well as to ensure longer
reliability of compressors.
Modular Installation
The mini chillers are available for modular
connection. A network of up to 50 chillers in a
system is possible. Control on the operation of the
chillers will be done through the microprocessor
controller. The external water piping connection can
be made either from the left or right side of the unit.
FEATURES
Easy Installation And Maintenance
As a chiller, all hydronic components are assembled
and wiring jobs on chillers are done and tested in the
factory. Installation of additional component on site
can be eliminated.
In addition, unit operation is user friendly and
maintenance is simple. By opening the front panel,
you would have immediate assess to all
components.
Factory Precharged Refrigerant
Each heat exchanger in the chiller is brazed and
tested against leakages through dried air at 30 bars.
After that, another process to vacuum the system
before accurately charged with refrigerant to ensure
optimum performance. Thus, it saves the hustles of
field charging by installers.
Anti Corrosion Heat Exchanger
The condenser heat exchanger of chiller, heat pump
specification, utilize the special anti corrosion gold
aluminum fin.
R407C & R410A
In line with Montreal Protocol, the Smart Manager is
available in R407C & R410A refrigerant.
* R407C & R410A is having Zero Ozone Depletion
Potential (O.D.P). However it is gas whose Global
Warming Potential (GWP) is similiar to the high
GWP for R22.
Brazed Plate Heat Exchanger
The heat exchanger is made of AISI 316 stainless
steel plates closely arranged and brazed together to
ensure high heat exchange efficiency.
Chiller Control Panel
The chiller panel controller is designed to control the
chiller operation. This device allows the user to have
customized control for each connected unit.
Each chiller will have a chiller control panel that
comes as a standard accessory. At the same time,
the chiller control panel is able to be installed
remotely through the cable up to a distance of 100
meters. Example, the chiller panel can be installed in
a centralized plant control room for the building.
The chiller control
panel has been
designed taking
into consideration
of the user friendly
and yet versatile
control features.
Features:
• Whole system configuration.
• Unique parameter settings.
• Operation status display.
• Tracing fault record (offer quick troubleshooting
solutions).
• The display is shown in an 8-lines graphical LCD
display. There are 8 dedicated keys available in
the panel.
• Menu selection.
• Navigation on the screen.
• Modification of the selected value.
12
Air - Cooled Mini Chiller
This new line of innovative air cooled chiller by McQuay was designed with one purpose in mind, which is to offer user
with cost and energy saving for users.
Better Performance
• Usage of higher efficient R410A rotary compressors
in tandem configuration
• Tight tolerances between moving parts resulting
in high compressor volumetric efficiency
• Minimize mechanical losses
• Minimize gas flow losses and turbulence
• Optimize compressor oil return
Capacity Step Control
• 3 steps compressor loading (0%-40%-60%-100%)
for M5AC 040 CR & M5AC 050 CR
• 2 steps compressor loading (0%-50%-100%) for
M5AC 030 CR & M5AC 055 CR
Sequential Control
• Both compressors will cut in cut out depending
on water temperature. This is possibly improving
the compressor life cycle as well as the
compressor reliability. Elimination of Water Tank
• Combining the Tandem Compressors
technology with the algorithm of the
microprocessor control, water tank can be
eliminated in most instances.
Choices of Single Phase and 3 Phase Power Supply Connection
• Usage of single phase power supply compressors
and circulating water pump.
• Offers flexibility to field installation.
TANDEM COMPRESSORS
13
The new series of Inverter Mini Chillers are specially designed / developed to achieve better system energy saving
as well as towards perfect control during part load condition.
Built In Fan Speed
Fan speed is now controlled by the built in
algorithm, resulting in cost saving since installation
of external FSC (Fan Speed Controller) can be
exempted. It is regulated at 100%, 70% and 50%
based on the ambient and outdoor condensing
temperature.
Safety Protection
• High & Low Pressure Switches
• Anti-Freeze Protection Sensor
• Discharge Temperature Sensor
• Over Pressure Relief Valve
• Water Pressure Differential Switch
• Anti-Freeze Heater on BPHE
• Compressor, Water Pump Overload Protector
Anti Corrosion Heat Exchanger
Gold Aluminum fin is offered as the standard
material of the condenser heat exchanger of this
series of chiller.
True Dual Circuits BPHE
Apply sophisticated technology of true dual circuit
BPHE.
The true dual BPHE puts the secondary circuit
(water) in contact with 2 primary circuits
(refrigerant). So even if one primary circuit is shut
off, each secondary channel is still in contact with a
primary channel. These advantages have made the
product the natural choice for flexible chillers,
climate control applications and high-precision
systems food cooling cabinets in supermarkets.
Inverter Compressor
Inverter compressor is programmed to run at the
optimum speed, which is regulated by the input
frequency as it can varies according to the heat
load requirement.
water
Ref.1 Ref.2 Ref.1 Ref.1Ref.2
waterwater water
PrimaryCircuit 1
PrimaryCircuit 2
Water In
Water Out
14
Modular Installation
A network up to 50 chillers in a system is possible.
Control on the operation of the chillers will be done
through the microprocessor controller. The external
water piping connection can be made either from the
left or right side of the unit.
Chiller Panel Comes AsThe Standard Controller
Compatible WithSmart Manager
Inverter System Conventional System
Precise & Stable Temperature Control
Fast Cooling
RoomTemperature
SetTemperature
SetTemperature
RoomTemperature
Time
Time
Advantages of inverter compressor applications are:
LESS START & STOP
Frequency regulated compressorresulting in lesser
in the sense of start and stop of compressor, which
is greatly reduce the energy consumption.
FAST COOLING / HEATING
Unlike the other conventional systems, inverter
compressor has the ability to produce faster cooling /
heating capacity at the frequency higher than the
dominant capacity frequency.
BETTER COMPRESSOR RELIABILITY
Reliability of inverter compressor is always better
since there is lesser ON/OFF of the system
especially during the low load condition.
LOW STARTING SURGE
Inverter compressor require lower starting torque
and thus, resulting in lower starting current.
Elimination Of Water Tank
Inverter system provide constant water temperature
band, or much lesser water temperature fluctuation.
With this, water tank of the mini chiller system can
be eliminated.
15
McQuay Chilled Water Fan Coil Units
To complement the new innovative Smart Manager range of air cooled chillers, McQuay is offering an extensive
range of chilled water fan coil units that will meet most of indoor application requirements covering residential, light
commercial and commercial.
The aesthetically attractive decorative fan coil units such as Wall Mounted models, Ceiling Cassette and Ceiling
Convertible is compact and ergonomic, the ranges can blend in easily to any interior designs whether it is
residential houses, office, restaurant or shops.
In addition, the McQuay chilled water fan coil units are designed with easy installation and easy servicing in mind.
The fan coil units also include the microprocessor controller that has built in algorithm to control the operation of the
fan coil unit as well as to provide protection to the unit.
16
For NIM PC only
NIM
NIM
NIM NIM NIM NIM
NIM NIM
NIM
NIM PC for Global Control HubWith NIM PC, a personal computer will act as a centralised unit for both controlling and monitoring of all the air
conditioning units in the HydroNIM network.
For controlling, settings can be set from the PC and send out to the system for execution. While for monitoring,
there is a graphical user interface for displaying the status of each unit.
The NIM PC provides a Global Control Hub that offers control for better system management:
• Easy to operate full graphical user interface.
• Control units globally, as a group,
or as individual units.
• Configure a super master unit.
• Support up to 42 On/Off timers per week.
• Real time monitoring of online units.
• Error diagnostic and alerting features for all units.
• Data logging and printing ability.
• Database to store unit location.
• Login protected by password.
NIM Networking Control System (optional)
For multiple fan coil unit installation in an office, a centralised controlled operation can be achieved through the
McQuay proprietary NIM networking system.
Network Interface Module (NIM) is a networking system which enables communication among McQuay air
conditioners.
With the NIM, all your air conditioning systems can be controlled with just a single controller giving you boundless
benefits:
BENEFITS
• Ultimate convenience. No more individually controlling air conditioning units
• Quick and easy zone control from the master control unit
• Better control of air conditioning systems operating conditions
NIM utilizes master-slave type system whereby the master node will issue commands to each of the slave nodes.
17
McQuay Chilled Water Fan Coil Units Range
MWM 07/10/15/20/25 GW
MWM 301 W
• Slim and compact• Wide capacity range • Wide air flow range• Incorporated with NanoGuard.• Able to communicate with the versatile NIM for fan coil
units networking • Light weight• Detachable and washable air intake grille• Microprocessor control• Self diagnosis features• Automatic air swing• Wireless Control as standard• Mode selection, fan speed, 24 hours real timers• Optional wired controller
Wall Mounted Range
Features :
SLM Wired Controller
AC-5300WirelessController
OPTIONAL
G17 WirelessController
STANDARD
2 Pipes System:MCK 020/025/030/040/050 AW
4 Pipes System:MCK 020/025/030/040/050 AWH
MCK 015/020/025 BW
Ceiling Cassette Range
Features :
• 3 range of ceiling cassette to be chosen from. - MCK-CW - 570mm (w) x 570mm (l)- MCK-BW - 650mm (w) x 650mm (l)- MCK-AW - 820mm (w) x 820mm (I)
• Aesthetically attractive and slim front panel• 4 way air discharge to provide better air distribution to room• Automatic air swing• 4 pipes system is available for model
MCK020/025/030/040/050AWH • Easy servicing and maintenance• Built in high pressure head drain pump
- Ability to pump up condensate water to 700mm high• Built in water float switch to protect the unit from problems
of condensate water overflow• Microprocessor control• Able to communicate with the versatile NIM for fan coil
units networking• Self diagnosis feature• Wireless Control as standard
- Mode selection, fan speed, 24 hours real timers• Optional wired controller
OPTIONAL
Netware III Wired Controller
18
MCK 010/015/020 CW
STANDARD
G17 Wireless Controller
MCC 010/015/020/025/030/040/050/060 CW
MCC 028/038 CW
Ceiling Concealed Range
Features :
• Wide capacity range• 4 speed fan motor offers flexibility for installation to suit
application- Each speed will offer different external static pressure and
air flow• High External Static Pressure is available up to 18mm • Extra secondary drain pan to provide protection against
condensate water leaking• Availability of various optional duct accessories specially
designed to fit to MCC-CW range• Microprocessor control• Filter adaptor kit of 1 inch is available as optional accessory • Able to communicate with the versatile NIM for fan coil units
networking• Self diagnosis feature• Wired Control as standard
- Mode selection, fan speed selection
OPTIONAL
Netware III Wired ControllerSLM Wired Controller
STANDARD
MCM 020/025/040/050 DW
MCM 15/20/25 EW
• Ceiling Convertible feature offers flexibility on installation- Installation method of under ceiling or floor standing
• 2 way air discharge ensure better air distribution- Horizontal air throw and bottom air throw
• Automatic Air swing• Aesthetically attractive with round profile outlook fits into to
any indoor architectural• Strong air flow volume and strong air throw distance makes it
a perfect choice for light commercial such as restaurant and shop
• Microprocessor control• Able to communicate with the versatile NIM for fan coil units
networking• Self diagnosis feature• Wireless Control as standard
- Mode selection, fan speed, 24 hours real timers• Optional wired controller
Ceiling Convertible Range
Features :
19
MCM 007/010/015 CBW
SLM Wired Controller
AC-5300WirelessController
OPTIONAL
G17 WirelessController
STANDARD
20
Optional Accessories (MCC010CW~MCC025CW)
• Wide capacity range• Multiple rooms can be cooled by just 1 unit of MCW• Simple design with easy serviceability feature• Extremely low height of unit – 251mm for complete range• Water piping connection can be easily converted from one
side to the other• Fan motor assembly is not cased, allowing free return or back
return or bottom return with optional return plenum• Availability of optional extended drain to receive the
condensate water dripping from the water piping connection • Availability of 4 pipes MCW series• Other optional accessory available:
- Wired thermostat- Choice of external static pressure (ESP)- Four types of ESP are available: 0Pa, 30Pa, 60Pa, 80Pa.- PTC (Positive Temperature Coefficient) electric heater- 2 way & 3 way valves
Features :
2 Pipes System:MCW 200/300/400/600/800/1000/1200 C
4 Pipes System:MCW 200/300/400/600/800/1000/1200 CH
Features :
• These units are design with high air flow and high external static pressure, enables adequate distribution of air to the desired space
• Multiple rooms can be cooled by just 1 unit of MDB• Simple design with easy serviceability feature• The robust unit is designed with durability and reliability in
mind• MDB125/150BW is using the belt driven fan motor and
blower fan thus it offers flexibility for upgrading should higher air flow is required
• MDB150BW is designed to cater for either horizontal air discharge or vertical air discharge
MDB 075/100/125/150 BW
Return Bracket Assembly come with Adaptor(MCC 010CW - 1 outlet; MCC 015~020CW - 2 outlets)
Y-JointAdaptorDischarge and Return
Supply Grille Assembly come with Adaptor
(Front View)(Side View)
Return Grille Assemblycome with Adaptor
(Front View)
Ceiling Concealed Range
Ducted Blower Range
21
A new developed thermostat series, AC8000 is now available to be ordered as Chilled Water Fan Coil unit controller, inclusive of AC8000A and AC8000C. Its adopt micro-computer technology and is designed for the easier of installation.
AC8000A practises the most simple and conventional installation method where it consists of a wired controller and a power board. Both of its are attached together while being installed.
Same with AC8000A, AC8000C also consist of a wired controller and a power board, but the power board is attached to the fan coil unit while the wired controller will be installed away from it. Moreover AC8000C has the networking capability, with compatibility to the Network Interface Module (NIM); better control over whole operating system can be achieved as it offers quick and easy zone control from the master operating unit.
Features :• Four Operating Modes
COOL/ FAN/ HEAT/ AUTO• Variable Indoor Fan Speed Selection
High/ Medium/ Low/ Auto• Selectable Function
Cooling Only, Cooling and Heating (2 pipes), Cooling and Heating (4 pipes)• LCD display• LED Indication of Power Supply• 7 days Programmable Timer• Real Timer• Selectable Room Temperature/ Set Temperature Display• Temperature Control Precision up to +/- 1°C• High, Low Voltage Separated for Safety• Last State Memory Backup• Networking Capability (Only Applicable for AC8000C)
AC8000C is compatible with Smart Manager and NIM PC. By using a RS485 cable, it can easily form a NIM bus as described in schematic diagram.
RS485More FCUs
NIM PC
OR
Smart Manager
AC8000CFCU AC8000CFCU AC8000CFCU
LCD Panel LCD Panel LCD Panel
AC80000A AC80000C
AC8000C Series
S1
Mini Chiller Specifications
MAC020C - MAC060C (Cooling Only, R22)
MAC020C MAC025C MAC030C MAC040C MAC050C MAC060C
Btu/h 18000 23500 27500 40000 50000 53000
W 5275 6887 8059 11723 14654 15533
W 2669 2730 3491 4470 5245 6361
V/Ph/Hz
HEIGHT mm/in
WIDTH mm/in
DEPTH mm/in
kg/lb 116 / 256 123 / 271 128 / 282 195 / 430 196 / 432 203 / 448
dBA 57 57 58 60 60 61
l/s/m3/hr 0.25 / 0.9 0.33 / 1.2 0.39 / 1.4 0.56 / 2.0 0.70 / 2.5 0.74 / 2.7
MAX. WATER OPER. PRESSURE kPa/psi
l/s/m3/hr 0.25 / 0.9 0.33 / 1.2 0.39 / 1.4 0.56 / 2.0 0.70 / 2.5 0.74 / 2.7
INSTALLATION PIPE CONNECITON mm/in
m 8.4 9.7 8.8 9.2 6.8 6.6
L/ft3
1410 / 55.5
1160 / 45.7
460 / 18.1
40 / 1.41
MATERIAL
HEAD
220-240 / 1 / 50 380-415 / 3 / 50
CAPILLARY TUBE
1000 / 145
R22
WATER FLOW RATE
25.4 / 1
0 - 100%
CAPACITY/VOLUME
CAST IRON / STAINLESS STEEL
22 / 0.78
800 / 31.5
1160 / 45.7
460 / 18.1
CONTROL
POWER SOURCE
REFRIGERANT TYPE
MODEL
NOMINAL COOLING CAPACITY
NOMINAL TOTAL INPUT POWER
EVAPORATOR
NOMINAL WATER FLOW
UNIT DIMENSION
TANK
PIPING
HYDRAULIC KIT
PUMP
UNIT WEIGHT
SOUND PRESSURE LEVEL
COMPRESSOR
STAGE OF CAPACITY CONTROL (Btu/h)
MAC020CR - MAC060CR (Heatpump, R22)
Notes:1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 12ºC / 7ºC ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35ºC AIR AMBIENT TEMPERATURE.b) HEATING - 40ºC / 45ºC ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 7ºC AIR AMBIENT TEMPERATURE.
4) SOUND PRESSURE LEVEL ARE MEASURED IN AN ANECHOIC CHAMBER ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND1m BELOW THE UNIT.
MAC020CR MAC025CR MAC030CR MAC040CR MAC050CR MAC060CR
Btu/h 18000 23000 27500 40000 46000 53000
W 5275 6740 8060 11723 13481 15533
Btu/h 22000 25000 31500 43000 52000 59000
W 6448 7327 9232 12602 15240 17292
COOLING W 2599 2779 3541 4560 5046 6551
HEATING W 2770 2614 3561 4629 4999 6247
V/Ph/Hz
HEIGHT mm/in
WIDTH mm/in
DEPTH mm/in
kg/lb 116 / 256 123 / 271 128 / 282 195 / 430 196 / 432 203 / 448
dBA 57 57 58 60 60 61
COOLING l/s/m3/hr 0.25 / 0.9 0.32 / 1.2 0.39 / 1.4 0.56 / 2.0 0.64 / 2.3 0.74 / 2.7
HEATING l/s/m3/hr 0.31 / 1.1 0.35 / 1.3 0.44 / 1.6 0.60 / 2.2 0.73 / 2.6 0.83 / 3.0
MAX. WATER OPER. PRESSURE kPa/psi
COOLING l/s/m3/hr 0.25 / 0.9 0.32 / 1.2 0.39 / 1.4 0.56 / 2.0 0.64 / 2.3 0.74 / 2.7
HEATING l/s/m3/hr 0.31 / 1.1 0.35 / 1.3 0.44 / 1.6 0.60 / 2.2 0.73 / 2.6 0.83 / 3.0
INSTALLATION PIPE CONNECITON mm/in
COOLING m 8.4 9.9 8.8 9.2 8.2 6.6
HEATING m 6.9 9.4 7.9 8.1 6.0 4.0
L/ft3
220-240 / 1 / 50 380-415 / 3 / 50
CAPILLARY TUBE
0 - 100%
MATERIAL
CAPACITY/VOLUME
CAST IRON / STAINLESS STEEL
22 / 0.78 40 / 1.41
HEAD
WATER FLOW RATE
25.4 / 1
1000 / 145
460 / 18.1
800 / 31.5 1410 / 55.5
1160 / 45.7 1160 / 45.7
460 / 18.1
R22
UNIT WEIGHT
SOUND PRESSURE LEVEL
EVAPORATOR
NOMINAL WATER FLOW
POWER SOURCE
COMPRESSOR
STAGE OF CAPACITY CONTROL (Btu/h)
TANK
PIPING
HYDRAULIC KIT
PUMP
NOMINAL TOTAL INPUT POWER
REFRIGERANT TYPE
CONTROL
UNIT DIMENSION
MODEL
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
S2
Mini Chiller Specifications
M4AC020C - M4AC060C (Cooling Only, R407C)
M4AC060C
52000
15240
6859
203 / 448
61
0.73 / 2.6
0.73 / 2.6
7.0
M4AC050C
50000
14654
5955
196 / 432
60
0.70 / 2.5
0.70 / 2.5
6.8
380-415 / 3 / 50
1410 / 55.5
1160 / 45.7
460 / 18.1
40 / 1.41
M4AC020C M4AC025C M4AC030C M4AC040C
Btu/h 21000 23000 27000 40000
W 6154 6740 7912 11723
W 2617 2949 3679 4910
V/Ph/Hz
HEIGHT mm/in
WIDTH mm/in
DEPTH mm/in
kg/lb 116 / 256 123 / 271 128 / 282 195 / 430
dBA 57 57 58 60
l/s/m3/hr 0.29 / 1.0 0.32 / 1.2 0.38 / 1.4 0.56 / 2.0
MAX. WATER OPER. PRESSURE kPa/psi
l/s/m3/hr 0.29 / 1.0 0.32 / 1.2 0.38 / 1.4 0.56 / 2.0
INSTALLATION PIPE CONNECITON mm/in
m 7.3 9.9 8.9 9.2
L/ft3
800 / 31.5
1160 / 45.7
460 / 18.1
25.4 / 1
0 - 100%
CAPACITY/VOLUME
CAST IRON / STAINLESS STEEL
22 / 0.78
220-240 / 1 / 50
CAPILLARY TUBE
1000 / 145
R407C
MATERIAL
HEAD
WATER FLOW RATE
COMPRESSOR
STAGE OF CAPACITY CONTROL (Btu/h)
TANK
EVAPORATOR
NOMINAL WATER FLOW
PIPING
HYDRAULIC KIT
PUMP
MODEL
NOMINAL COOLING CAPACITY
NOMINAL TOTAL INPUT POWER
UNIT DIMENSION
CONTROL
POWER SOURCE
REFRIGERANT TYPE
UNIT WEIGHT
SOUND PRESSURE LEVEL
Notes:1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 12ºC / 7ºC ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35ºC AIR AMBIENT TEMPERATURE.b) HEATING - 40ºC / 45ºC ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 7ºC AIR AMBIENT TEMPERATURE.
4) SOUND PRESSURE LEVEL ARE MEASURED IN AN ANECHOIC CHAMBER ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND1m BELOW THE UNIT.
M4AC020CR - M4AC060CR (Heatpump, R407C)
CAST IRON / STAINLESS STEEL
M4AC060CR
51000
14947
60000
17584
6507
6268
203 / 448
61
0.71 / 2.6
0.84 / 3.0
0.71 / 2.6
0.84 / 3.0
7.5
3.5
M4AC050CR
46000
13481
51000
14947
5446
5647
196 / 432
60
0.64 / 2.3
0.71 / 2.6
0.64 / 2.3
0.71 / 2.6
8.2
6.4
460 / 18.1
1410 / 55.5
1160 / 45.7
40 / 1.41
380-415 / 3 / 50
M4AC020CR M4AC025CR M4AC030CR M4AC040CR
Btu/h 17000 22000 25000 40000
W 4982 6448 7327 11723
Btu/h 20000 25500 32500 45000
W 5861 7474 9525 13188
COOLING W 2597 3076 3804 4820
HEATING W 2685 2745 4004 4994
V/Ph/Hz
HEIGHT mm/in
WIDTH mm/in
DEPTH mm/in
kg/lb 116 / 256 123 / 271 128 / 282 195 / 430
dBA 57 57 58 60
COOLING l/s/m3/hr 0.24 / 0.9 0.31 / 1.1 0.35 / 1.3 0.56 / 2.0
HEATING l/s/m3/hr 0.28 / 1.0 0.36 / 1.3 0.46 / 1.7 0.63 / 2.3
MAX. WATER OPER. PRESSURE kPa / psi
COOLING l/s/m3/hr
l/s/m3/hr
0.25 / 0.9 0.32 / 1.2 0.35 / 1.3 0.56 / 2.0
HEATING 0.31 / 1.1 0.35 / 1.3 0.46 / 1.7 0.63 / 2.3
INSTALLATION PIPE CONNECITON mm/in
COOLING m 8.7 10.1 9.4 9.2
HEATING m 7.7 9.3 7.6 7.5
L/ft3
800 / 31.5
1160 / 45.7
460 / 18.1
R407C
HEAD
WATER FLOW RATE
25.4 / 1
1000 / 145
0 - 100%
MATERIAL
CAPACITY/VOLUME 22 / 0.78
CAST IRON / STAINLESS STEEL CAST IRON / STAINLESS STEEL
220-240 / 1 / 50
CAPILLARY TUBE
MODEL
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
NOMINAL TOTAL INPUT POWER
REFRIGERANT TYPE
CONTROL
UNIT DIMENSION
PIPING
HYDRAULIC KIT
PUMP
COMPRESSOR
STAGE OF CAPACITY CONTROL (Btu/h)
TANK
POWER SOURCE
UNIT WEIGHT
SOUND PRESSURE LEVEL
EVAPORATOR
NOMINAL WATER FLOW
S3
Mini Chiller Specifications
MAC080C - MAC150C (Cooling Only, R22)
MAC150C
138000
40445
13779
540 / 1190
69
2.00 / 7.2
2.00 / 7.2
23.0
HEIGHT
WIDTH
DEPTH
MAX. WATER OPER. PRESSURE
INSTALLATION PIPE CONNECITON
WATER FLOW RATE
UNIT WEIGHT
SOUND PRESSURE LEVEL
MODEL
NOMINAL COOLING CAPACITY
NOMINAL TOTAL INPUT POWER
UNIT DIMENSION
CONTROL
POWER SOURCE
REFRIGERANT TYPE
TANKMATERIAL
CAPACITY/VOLUME
1150 / 45.3
HYDRAULIC KIT
PUMP
EVAPORATOR
NOMINAL WATER FLOW
COMPRESSOR
STAGE OF CAPACITY CONTROL (Btu/h)
PIPINGHEAD
1800 / 70.9
MAC120C
116000
33998
11005
460 / 1014
67
1.67 / 6.0
1.67 / 6.0
25.0
NA
0 - 50 - 100%
380-415 / 3 / 50
TXV
1245 / 49.0
NA
42 / 1 1/4"
1000 / 145
R22
MAC100C
93000
27257
10175
350 / 772
66
1.31 / 4.7
1.31 / 4.7
23.5
900 / 35.4
1500 / 59.1
MAC080C
78000
22860
8667
340 / 750
65
1.08 / 3.9
1.08 / 3.9
26.0
Btu/h
W
W
V/Ph/Hz
mm/in
mm/in
mm/in
kg/lb
dBA
l/s/m3/hr
kPa/psi
l/s/m3/hr
mm/in
m
L/ft3
MAC080CR - MAC150CR (Heatpump, R22)
Notes:1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 12ºC / 7ºC ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35ºC AIR AMBIENT TEMPERATURE.b) HEATING - 40ºC / 45ºC ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 7ºC AIR AMBIENT TEMPERATURE.
4) SOUND PRESSURE LEVEL ARE MEASURED IN AN ANECHOIC CHAMBER ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND1m BELOW THE UNIT.
MAC150CR
138000
40445
132000
38686
13881
14572
560 / 1235
69
2.00 / 7.2
2.10 / 7.6
2.00 / 7.2
2.10 / 7.6
23.0
22.5
COOLING
HEATING
HEIGHT
WIDTH
DEPTH
COOLING
HEATING
MAX. WATER OPER. PRESSURE
COOLING
HEATING
INSTALLATION PIPE CONNECITON
COOLING
HEATING
EVAPORATOR
NOMINAL WATER FLOW
UNIT DIMENSION
UNIT WEIGHT
SOUND PRESSURE LEVEL
NOMINAL TOTAL INPUT POWER
REFRIGERANT TYPE
COMPRESSOR
STAGE OF CAPACITY CONTROL (Btu/h)
TANKMATERIAL
CAPACITY/VOLUME
PIPINGHEAD
WATER FLOW RATE
HYDRAULIC KIT
PUMP
CONTROL
POWER SOURCE
MODEL
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
1150 / 45.3
1800 / 70.9
MAC120CR
113000
33118
120000
35169
11714
11948
480 / 1058
67
1.67 / 6.0
1.79 / 6.4
1.67 / 6.0
1.79 / 6.4
25.0
24.5
NA
0 - 50 - 100%
NA
1000 / 145
42 / 1 1/4"
CAPILLARY TUBE
1245 / 49.0
380-415 / 3 / 50
R22
MAC100CR
94000
27549
110000
32239
11255
10759
360 / 794
66
1.31 / 4.7
1.37 / 4.9
1.31 / 4.7
1.37 / 4.9
23.5
22.5
1500 / 59.1
900 / 35.4
MAC080CR
77000
22567
90000
26376
9577
9329
350 / 772
65
1.08 / 3.9
1.14 / 4.1
1.08 / 3.9
1.14 / 4.1
26.0
25.0
Btu/h
W
Btu/h
W
W
W
V/Ph/Hz
mm/in
mm/in
mm/in
kg/lb
dBA
l/s/m
l/s/m
kPa/psi
l/s/m3/hr
l/s/m3/hr
mm/in
m
m
L/ft3
S4
Mini Chiller Specifications
M4AC080C - M4AC150C (Cooling Only, R407C)
Notes:1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 12ºC / 7ºC ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35ºC AIR AMBIENT TEMPERATURE. b) HEATING - 40ºC / 45ºC ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 7ºC AIR AMBIENT TEMPERATURE.4) SOUND PRESSURE LEVEL ARE MEASURED IN AN ANECHOIC CHAMBER ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
M4AC080CR - M4AC150CR (Heatpump, R407C)
M4AC150CR
Btu/h 130000
W 38101
Btu/h 144000
W 42204
COOLING W 15151
HEATING W 15824
V/Ph/Hz
HEIGHT mm/in
WIDTH mm/in
DEPTH mm/in
kg/lb 540 / 1190
dBA 69
COOLING l/s/m3/hr 2.00 / 7.2
HEATING l/s/m3/hr 2.10 / 7.6
MAX. WATER OPER. PRESSURE kPa/psi
COOLING l/s/m3/hr 2.00 / 7.2
HEATING l/s/m3/hr 2.10 / 7.6
INSTALLATION PIPE CONNECITON mm/in
COOLING m 23.0
HEATING m 22.5
L/ft3
CONTROL
POWER SOURCE
MODEL
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
PIPINGHEAD
WATER FLOW RATE
HYDRAULIC KIT
PUMP
COMPRESSOR
STAGE OF CAPACITY CONTROL (Btu/h)
TANKMATERIAL
CAPACITY/VOLUME
EVAPORATOR
NOMINAL WATER FLOW
UNIT DIMENSION
UNIT WEIGHT
SOUND PRESSURE LEVEL
NOMINAL TOTAL INPUT POWER
REFRIGERANT TYPE
1150 / 45.3
1800 / 70.9
M4AC120CR
110000
32239
118000
34583
12273
12386
460 / 1014
67
1.67 / 6.0
1.79 / 6.4
1.67 / 6.0
1.79 / 6.4
25.0
24.5
380-415 / 3 / 50
R407C
TXV
1245 / 49.0
1000 / 145
42 / 1 1/4"
NA
0 - 50 - 100%
NA
M4AC100CR
88000
25791
98000
28722
11028
11134
350 / 772
66
1.31 / 4.7
1.37 / 4.9
1.31 / 4.7
1.37 / 4.9
23.5
22.5
1500 / 59.1
900 / 35.4
M4AC080CR
74000
21688
90000
26377
9946
9975
340 / 750
65
1.08 / 3.9
1.14 / 4.1
1.08 / 3.9
1.14 / 4.1
26.0
25.0
M4AC150C
Btu/h 13700
W 40152
W 14531
V/Ph/Hz
HEIGHT mm/in
WIDTH mm/in
DEPTH mm/in
kg/lb 540 / 1190
dBA 69
l/s/m3/hr 2.00 / 7.2
MAX. WATER OPER. PRESSURE kPa/psi
l/s/m3/hr 2.00 / 7.2
INSTALLATION PIPE CONNECITON mm/in
m 23.0
L/ft3
EVAPORATOR
NOMINAL WATER FLOW
COMPRESSOR
STAGE OF CAPACITY CONTROL (Btu/h)
PIPINGHEAD
HYDRAULIC KIT
PUMP
TANKMATERIAL
CAPACITY/VOLUME
WATER FLOW RATE
UNIT WEIGHT
SOUND PRESSURE LEVEL
MODEL
NOMINAL COOLING CAPACITY
NOMINAL TOTAL INPUT POWER
UNIT DIMENSION
CONTROL
POWER SOURCE
REFRIGERANT TYPE
1800 / 70.9
1150 / 45.3
M4AC120C
115000
33705
11805
460 / 1014
67
1.67 / 6.0
1.67 / 6.0
25.0
380-415 / 3 / 50
TXV
1245 / 49.0
NA
42 / 1 1/4"
1000 / 145
R407C
NA
0 - 50 - 100%
M4AC100C
88000
25791
10771
350 / 772
66
1.31 / 4.7
1.31 / 4.7
23.5
1500 / 59.1
900 / 35.4
M4AC080C
74000
21688
9463
340 / 750
65
1.08 / 3.9
1.08 / 3.9
26.0
M5ACV030CR - M5ACV135CR (Inverter Heatpump, R410A)
S5
Mini Chiller Specifications
M5AC020CR - M5AC055CR (Heatpump, R410A)
Notes:1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 12ºC / 7ºC ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35ºC AIR AMBIENT TEMPERATURE.b) HEATING - 40ºC / 45ºC ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 7ºC AIR AMBIENT TEMPERATURE.
4) SOUND PRESSURE LEVEL ARE MEASURED IN AN ANECHOIC CHAMBER ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND1m BELOW THE UNIT.
COOLING
HEATING
HEIGHT
WIDTH
DEPTH
COOLING
HEATING
MAX. WATER OPER. PRESSURE
COOLING
HEATING
INSTALLATION PIPE CONNECITON
COOLING
HEATING
MATERIAL
CAPACITY/VOLUME
HEAD
WATER FLOW RATE
M5ACV210CR
200000
58617
210000
61548
22300
21800
1786 / 70.31
2093 / 82.4
1192 / 46.9
682
85
2.67 (9.8)
2.86 (10.5)
2.7 (9.6)
2.9 (10.3)
38.0 / 1.5
25
25
0 - 210000
M5ACV135CR
131500
38540
141500
41470
15750
16250
1260 / 49.6
1800 / 70.9
1150 / 45.3
560 / 1235
67
1.8 ( 6.6 )
2.0 ( 7.1 )
1.8 ( 6.6 )
2.0 ( 7.1 )
16.5
14.5
0 - 149000
EXV / CAPILLARY TUBE
M5ACV100CR
95000
27800
100000
29300
12000
11400
1260 / 49.6
1500 / 59.1
900 / 35.4
360 / 794
63
1.3 ( 4.8 )
1.4 ( 5.0 )
1.3 ( 4.8 )
1.4 ( 5.0 )
17.3
15.7
0 - 122000
380-415 / 3 / 50
R410A
1000 / 145
NA
NA
M5ACV075CR
70000
20515
75000
21980
9050
7900
1460 / 57.5
1150 / 45.3
550 / 21.7
200 / 440
65
0.9 ( 3.4 )
1.0 ( 3.7 )
0.9 ( 3.4 )
1.0 ( 3.7 )
22.3
21.3
0 - 75000
25.4 / 1
M5ACV055CR
50000
14654
55000
16119
7600
6100
1410 / 55.5
1010 / 39.8
460 / 18.1
195 / 430
62
0.7 ( 2.5 )
0.8 ( 2.7 )
0.7 ( 2.5 )
0.8 ( 2.7 )
12.7
11.5
0 - 55000
ELECTRONIC EXPANSION VALVE (EXV)
M5ACV030CR
27000
7913
33000
9663
5279
4418
220-240 / 1 / 50
790 / 31.1
1010 / 39.8
460 / 18.1
128 / 282
59
0.3 ( 1.3 )
0.4 ( 1.5 )
0.3 ( 1.3 )
0.4 ( 1.5 )
7.7
7.0
0 - 28700
Btu/h
W
Btu/h
W
W
W
V/Ph/Hz
mm/in
mm/in
mm/in
kg/lb
dBA
l/s/m3/hr
l/s/m3/hr
kPa/psi
l/s/m3/hr
l/s/m3/hr
mm/in
m
m
L/ft3
MODEL
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
NOMINAL TOTAL INPUT POWER
REFRIGERANT TYPE
CONTROL
UNIT DIMENSION
POWER SOURCE
COMPRESSOR
STAGE OF CAPACITY CONTROL (Btu/h)
TANK
PIPING
HYDRAULIC KIT
UNIT WEIGHT
SOUND PRESSURE LEVEL
EVAPORATOR
NOMINAL WATER FLOW
COOLING
HEATING
HEIGHT
WIDTH
DEPTH
COOLING
HEATING
MAX. WATER OPER. PRESSURE
COOLING
HEATING
INSTALLATION PIPE CONNECITON
COOLING
HEATINGHEAD
MATERIAL
WATER FLOW RATE
CAPACITY/VOLUME
1410 / 55.5
1010 / 39.8
460 / 18.1
M5AC055CR
50000
14641
55000
16105
5890
5990
173 / 381
60
0.72 / 2.6
0.72 / 2.6
0.72 / 2.6
7.9
5.7
0 - 50 - 100%
M5AC050CR
47000
13763
51000
14934
5090
5130
167 / 368
60
0.64 / 2.3
0.64 / 2.3
0.64 / 2.3
7.9
6.4
220-240 / 1 / 50 or 380-415 / 3 / 50
NA
CAPILLARY TUBE & TXV
0 - 40 - 60 - 100%
NA
M5AC040CR
37500
10981
40800
11947
4330
4490
1410 / 55.5
1010 / 39.8
460 / 18.1
165 / 364
60
0.53 / 1.9
0.53 / 1.9
0.53 / 1.9
10.0
8.9
R410A
1000 / 145
25.4 / 1
M5AC030CR
26800
7848
32500
9517
3720
3630
790 / 31.1
1010 / 39.8
460 / 18.1
125 / 276
58
0.42 / 1.5
0.42 / 1.5
0.42 / 1.5
9.0
7.7
0 - 50 - 100%
M5AC025CR
21000
6150
25000
7330
2760
2790
165 / 364
57
0.28 / 1.00
0.35 / 1.25
0.28 / 1.00
0.35 / 1.25
10.1
9.3
220-240 / 1 / 50
CAST IRON / STAINLESS STEEL
CAPILLARY TUBE
800 / 31.5
1160 / 45.7
460 / 18.1
0 - 100%
22 / 0.78
M5AC020CR
17000
4980
21500
6300
2550
2590
125 / 276
57
0.23 / 0.84
0.32 / 1.16
0.23 / 0.84
0.32 / 1.16
8.7
7.7
Btu/h
W
Btu/h
W
W
W
V/Ph/Hz
mm/in
mm/in
mm/in
kg/lb
dBA
l/s/m3/hr
l/s/m3/hr
kPa/psi
l/s/m3/hr
l/s/m3/hr
mm/in
m
m
L/ft3
POWER SOURCE
PIPING
TANK
REFRIGERANT TYPE
MODEL
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
NOMINAL TOTAL INPUT POWER
CONTROL
UNIT DIMENSION
UNIT WEIGHT
SOUND PRESSURE LEVEL
EVAPORATOR
NOMINAL WATER FLOW
HYDRAULIC KIT
PUMP
STAGE OF CAPACITY CONTROL (Btu/h)
COMPRESSOR
S6
Chilled Water Fan Coil Unit Specifications
MCK020AW - MCK050AW (Ceilling Cassette A Series)
HIGH
HEIGHT
WIDTH
DEPTH
MODEL
NOMINAL TOTAL COOLING CAPACITY
NOMINAL SENSIBLE COOLING CAPACITY
NOMINAL TOTAL HEATING CAPACITY (ENTERING
WATER TEMP. = 50°C)
NOMINAL AIR FLOW
UNIT DIMENSION - ( ) WITH PANEL
UNIT WEIGHT ( UNIT + PANEL )
CONNECTION
SOUND PRESSURE LEVEL ( H/M/L )
NOMINAL WATER FLOW RATE
HEAD LOSS (COOLING)
HEAD LOSS (HEATING) : 50°C
MCK050AW
36500
10800
26300
7700
44000
12900
511 / 1083
( 40+4 ) / ( 88+8.8 )
53 / 52 / 50
8.20
31.00
69.3 / 10.05
64.1 / 9.29
MCK040AW
33500
9950
24200
7100
40500
12000
483 / 1024
( 38+4 ) / (83.6+8.8 )
51 / 48 / 46
7.50
28.35
52.2 / 7.57
45.2 / 6.55
MCK030AW
30000
8800
21800
6400
37500
11000
433 / 918
( 35+4 ) / ( 77+8.8 )
49 / 45 / 43
6.70
25.33
41.6 / 6.03
35.3 / 5.12
335 / 13.2 ( 363 / 14.3 )
820 / 32.3 ( 930 / 36.6 )
821 / 32.3 ( 930 / 36.6 )
3/4" BSP FEMALE UNION
MCK025AW
25500
7500
18400
5400
32000
9500
383 / 812
( 32+4 ) / ( 70.4+0.44 )
45 / 42 / 40
5.70
21.55
30.8 / 4.47
26.8 / 3.89
MCK020AW
22500
6620
16700
4900
28500
8400
364 / 771
( 31+4 ) / ( 68.2+8.8 )
42 / 39 / 37
5.00
18.90
24.8 / 3.6
21.4 / 3.1
Btu/h
W
Btu/h
W
Btu/h
W
l/s / CFM
mm/in
mm/in
mm/in
kg/lb
dBA
USGPM
LITRES/M
kPa / psi
kPa / psi
Notes:1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - ENTERING AIR TEMP. : 27°C (80.6°F) DB / 19°C (66.2°F) WB, ENTERING WATER TEMP. : 7°C (44.6°F), LEAVING WATER TEMP. : 12°C (53.6°F)b) HEATING - ENTERING AIR TEMP.: 20°C (68°F) DB, ENTERING WATER TEMP. : 70°C (158°F), LEAVING WATER TEMP. : 65°C (149°F)
4) SOUND PRESSURE LEVEL IS MEASURE IN ANECHOIC CHAMBER, AND ACCORDING TO JIS C 9612 STANDARD. MCK020/025AW/AWH : POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE FACIA. MCK030/040/050AW/AWH : 1.5m BELOW THE FACIA (JIS B 8615).
MCK020AWH - MCK050AWH (4 Pipies Ceilling Cassette)
HIGH
MEDIUM
LOW
HEIGHT
WIDTH
DEPTH
MODEL
NOMINAL TOTAL COOLING CAPACITY
NOMINAL SENSIBLE COOLING CAPACITY
NOMINAL TOTAL HEATING CAPACITY (ENTERING
WATER TEMP. = 50°C)
NOMINAL AIR FLOW
UNIT DIMENSION - ( ) WITH PANEL
Cooling
Add.Heat
Exch
UNIT WEIGHT ( UNIT + PANEL )
SOUND PRESSURE LEVEL ( H/M/L )
HEAD LOSS (COOLING)
CONNECTION
HEAD LOSS (HEATING) : 50°C
NOMINAL WATER FLOW RATE
MCK050AWH
17600
5160
15500
4540
47000
13770
491 / 1040
448 / 950
411 / 870
( 40+4 ) / ( 88+8.8 )
53 / 52 / 50
3.90
14.74
5.20
19.67
5.96 / 0.86
8.8 / 1.28
MCK040AWH
17100
5010
15000
4400
46000
13480
467 / 990
406 / 860
359 / 760
( 38+4 ) / (83.6+8.8 )
51 / 48 / 46
3.80
14.36
5.11
19.3
5.7 / 0.83
8.6 / 1.23
MCK030AWH
15800
4630
13900
4070
42700
12510
415 / 880
349 / 740
321 / 680
( 35+4 ) / ( 77+8.8 )
49 / 45 / 43
3.50
13.23
4.76
18
4.94 / 0.72
7.2 / 1.04
335 / 13.2 ( 363 / 14.3 )
820 / 32.3 ( 930 / 36.6 )
821 / 32.3 ( 930 / 36.6 )
3/4" BSP FEMALE UNION
MCK025AWH
13500
3960
12000
3520
37500
10990
368 / 780
312 / 660
283 / 600
( 32+4 ) / ( 70.4+0.44 )
45 / 42 / 40
3.00
11.34
4.19
15.83
3.78 / 0.55
5.5 / 0.8
MCK020AWH
13000
3810
11600
3400
36000
10550
349 / 740
297 / 630
283 / 600
( 31+4 ) / ( 68.2+8.8 )
42 / 39 / 37
2.90
10.96
4.00
15.1
3.56 / 0.52
4.8 / 0.7
Btu/h
W
Btu/h
W
Btu/h
W
l/s / CFM
l/s / CFM
l/s / CFM
mm/in
mm/in
mm/in
kg/lb
dBA
USGPM
LITRES/M
USGPM
LITRES/M
kPa / psi
kPa / psi
S7
HIGH
HEIGHT
WIDTH
DEPTH
CONNECTION
NOMINAL AIR FLOW
UNIT DIMENSION - ( ) WITH PANEL
UNIT WEIGHT ( UNIT + PANEL )
HEAD LOSS (COOLING)
HEAD LOSS (HEATING) : 50°C
SOUND PRESSURE LEVEL ( H/M/L )
NOMINAL WATER FLOW RATE
MODEL
NOMINAL TOTAL COOLING CAPACITY
NOMINAL SENSIBLE COOLING CAPACITY
NOMINAL TOTAL HEATING CAPACITY (ENTERING
WATER TEMP. = 50°C)
MCK025BW
18000
5270
13300
3900
21000
6150
226 / 480
( 31+3 ) / (68.2+6.6 )
43 / 41 / 37
4.00
15.20
10.3 / 1.50
15.9 / 2.30
MCK020BW
17000
4980
11330
3320
18000
5270
40 / 36 / 30
3.79
14.30
9.70 / 1.41
7.6 / 1.10
293 / 11.5 ( 345 / 13.6 )
650 / 25.6 ( 727 / 28.6 )
650 / 25.6 ( 727 / 28.6 )
3/4" BSP FEMALE UNION
194 / 410
( 30+3 ) / ( 66+6.6)
MCK015BW
12500
3660
9250
2710
16000
4690
36 / 33 / 29
2.78
10.50
39.3 / 5.70
33 / 4.78
Btu/h
W
Btu/h
W
Btu/h
W
l/s / CFM
mm/in
mm/in
mm/in
kg/lb
dBA
USGPM
LITRES/M
kPa / psi
kPa / psi
Chilled Water Fan Coil Unit Specifications
MCK015BW - MCK025BW (Ceilling Cassette B Series)
HIGH
HEIGHT
WIDTH
DEPTH
HEAD LOSS (COOLING)
NOMINAL WATER FLOW RATE
CONNECTION
UNIT DIMENSION - ( ) WITH PANEL
MODEL
NOMINAL TOTAL COOLING CAPACITY
NOMINAL SENSIBLE COOLING CAPACITY
NOMINAL TOTAL HEATING CAPACITY (ENTERING
WATER TEMP. = 50°C)
HEAD LOSS (HEATING) : 50°C
UNIT WEIGHT ( UNIT + PANEL ) ( 23+2 ) / ( 50.6+4.4 )
SOUND PRESSURE LEVEL ( H/M/L )
NOMINAL AIR FLOW
MCK020CW
14500
4250
11100
3240
18500
5420
203 / 430
47 / 46 / 44
3.22
12.17
68.8 / 9.98
71.2 / 10.32
MCK015CW
14000
4100
10400
3060
17500
5120
44 / 42 / 41
3.10
11.83
68.6 / 9.95
70.5 / 10.22
250 / 9.8 ( 295 / 11.6 )
570 / 22.4 ( 640 / 25.2 )
3/4" BSP FEMALE UNION
570 / 22.4 ( 640 / 25.2 )
184 / 390
MCK010CW
8000
2340
6700
1970
10900
3200
( 22+2 ) / (48.5+4.4)
44 / 43 / 42
1.76
6.67
67.3 / 9.76
61.9 / 8.98
Btu/h
W
Btu/h
W
Btu/h
W
l/s / CFM
mm/in
mm/in
mm/in
kg/lb
dBA
USGPM
LITRES/M
kPa / psi
kPa / psi
MCK010CW - MCK020CW (Ceilling Cassette C Series)
Notes:1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - ENTERING AIR TEMP. : 27°C (80.6°F) DB / 19°C (66.2°F) WB, ENTERING WATER TEMP. : 7°C (44.6°F), LEAVING WATER TEMP. : 12°C (53.6°F)b) HEATING - ENTERING AIR TEMP.: 20°C (68°F) DB, ENTERING WATER TEMP. : 70°C (158°F), LEAVING WATER TEMP. : 65°C (149°F)
4) SOUND PRESSURE LEVEL ARE MEASURED IN ANECHOIC TEST ROOM & ACCORDING TO JIS C 9612 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE FACIA.
S8
3/4" BSP FEMALE ADAPTOR
MCM007CBW MCM010CBW MCM015CBW MCM020DW
6500 8600 10500 17700
1910 2500 3080 5190
5000 6660 8570 13650
1460 1950 2510 4000
7800 10600 14300 22000
2280 3100 4190 6450
95 / 200 142/ 300 190 / 400 264 / 660
214 / 8.4
1214 / 47.8
1174 / 46.2 670 / 26.4
35 / 77.2 43 / 94.8
45 / 42 / 37 46 / 43 / 38 47 / 44 / 39 50 / 47 / 40
1.45 1.89 2.33 3.92
5.50 7.17 8.83 14.83
9.30 / 1.35 15.4 / 2.23 4.5 / 0.65 45.6 / 6.61
7.0 / 1.01 12.7 / 1.84 3.6 / 0.52 39.2 / 5.68
235 / 9.3
666 / 26.2
33 / 72.8
824 / 32.4
Chilled Water Fan Coil Unit Specifications
MCM007CBW - MCM020DW (Ceilling Convertible)
Btu/h
W
Btu/h
W
Btu/h
W
HIGH l/s/CFM
HEIGHT mm/in
WIDTH mm/in
DEPTH mm/in
kg/lb
dBA
USGPM
LITRES/M
kPa/psi
kPa/psi
NOMINAL AIR FLOW
UNIT DIMENSION
UNIT WEIGHT
MODEL
NOMINAL TOTAL COOLING CAPACITY
NOMINAL SENSIBLE COOLING CAPACITY
NOMINAL TOTAL HEATING CAPACITY (ENTERINGWATER TEMP. = 70ºC)
CONNECTION
SOUND PRESSURE LEVEL ( H/M/L )
NOMINAL WATER FLOW RATE
HEAD LOSS (COOLING)
HEAD LOSS (HEATING) : 70ºC
Notes:1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :a) COOLING - ENTERING AIR TEMP. : 27ºC (80.6ºF) DB / 19ºC (66.2ºF) WB, ENTERING WATER TEMP. : 7ºC (44.6ºF), LEAVING WATER TEMP. : 12ºC (53.6ºF)b) HEATING - ENTERING AIR TEMP.: 20ºC (68ºF) DB, ENTERING WATER TEMP. : 70ºC (158ºF), LEAVING WATER TEMP. : 65ºC (149ºF)c) MCM025DW-MCM050DW: HEATING - ENTERING AIR TEMP.: 20ºC (68ºF) DB, ENTERING WATER TEMP. : 60ºC (140ºF), LEAVING WATER TEMP. : 55ºC (131ºF)4) SOUND PRESSURE LEVEL ARE MEASURED IN AN ANECHOIC CHAMBER ACCORDING TO JIS C 9612 STANDARD. MCM020/025DW : POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT
AND 0.8m BELOW THE UNIT. MCM030/040/050DW : 1 m IN FRONT OF THE UNIT AND 1m BELOW THE AIR DISCHARGE OPENING. (JIS B 8615) MCE007-015CBW: 1m IN FRONT AND 0.8m BELOW THE VERTICAL CENTRE LINE OF THE UNIT.
MCM025DW - MCM050DW (Ceilling Convertible)
MCM025DW MCM030DW MCM040DW MCM050DW
Btu/h 20800 24600 31200 45000
W 6100 4210 9140 13190
Btu/h 15000 17700 25600 31400
W 4400 5190 7500 9200
Btu/h 25900 28000 42300 51500
W 7590 8210 12400 15100
HIGH l/s/CFM 297 / 630 329 / 697 449 / 949 500 / 1058
HEIGHT mm/in 214 / 8.4
WIDTH mm/in
DEPTH mm/in
kg/lb 43 / 94.8 45 / 99.2
dBA 54 / 53 / 50 51 / 50 / 48 54 / 53 / 52 54 / 53 / 52
USGPM 4.63 5.46 6.91 10.00
LITRES/M 17.50 20.67 26.17 37.83
kPa/psi 55.7 / 8.07 49.4 / 7.16 124.0 / 3.48 37.7 / 5.46
kPa/psi 48.1 / 6.97 43.0 / 6.23 21.5 / 3.11 31.6 / 4.58
249 / 9.8
1214 / 47.8 1714 / 67.5
3/4" BSP FEMALE ADAPTOR
70 / 154.3
670 / 26.4
CONNECTION
SOUND PRESSURE LEVEL ( H/M/L )
NOMINAL WATER FLOW RATE
HEAD LOSS (COOLING)
HEAD LOSS (HEATING) : 60ºC
NOMINAL SENSIBLE COOLING CAPACITY
NOMINAL TOTAL HEATING CAPACITY (ENTERINGWATER TEMP. = 60ºC)
NOMINAL AIR FLOW
UNIT WEIGHT
MODEL
UNIT DIMENSION
NOMINAL TOTAL COOLING CAPACITY
S9
Chilled Water Fan Coil Unit Specifications
MCC010CW - MCC028CW (Ceiling Concealed)
SUPER HIGH
HIGH
MEDIUM
LOW
HEIGHT
WIDTH
DEPTH
NOMINAL AIR FLOW
EXTERNAL STATIC ( H/M/L )
UNIT DIMENSION
UNIT WEIGHT
SOUND PRESSURE LEVEL ( H/M/L )
NOMINAL WATER FLOW RATE
HEAD LOSS (COOLING)
MODEL
NOMINAL TOTAL COOLING CAPACITY
NOMINAL SENSIBLE COOLING CAPACITY
NOMINAL TOTAL HEATING CAPACITY (ENTERINGWATER TEMP. = 60ºC)
CONNECTION
HEAD LOSS (HEATING) : 60ºC
MCC028CW
26000
7620
19500
5715
55000
16120
401 / 850
382 / 810
363 / 770
335 / 710
10 / 8 / 7 / 6
290 / 11.4
942 / 37.1
600 / 23.6
38 / 83.8
44 / 41 / 38 / 34
5.70
21.58
14.69 / 2.13
11.38 / 1.65
MCC025CW
22500
6594
17900
5246
48000
14068
NA
345 / 730
340 / 720
274 / 580
5 / 4 / 3
261 / 10.3
1200 / 47.2
411 / 16.2
25 / 55.1
40 / 39 / 36
4.70
17.79
24.12 / 3.50
18.96 / 2.75
MCC020CW
18000
5275
13600
3986
38000
11137
NA
330 / 700
321 / 680
293 / 620
5 / 4 / 3
263 / 10.3
1065 / 41.9
413 / 16.2
22 / 48.5
38 / 36 / 34
4.20
15.90
18.28 / 2.65
14.20 / 2.06
3/4" BSP FEMALE ADAPTOR
MCC015CW
15000
4396
10000
2931
25500
7474
NA
241 / 510
208 / 440
170 / 360
5 / 4 / 3
262 / 10.3
905 / 35.6
412 / 16.2
21 / 46.3
37 / 34 / 29
2.58
9.77
13.97 / 2.03
10.76 / 1.56
MCC010CW
9900
2902
7000
2052
19000
5569
NA
142 / 300
123 / 260
104 / 220
5 / 4 / 3
261 / 10.3
765 / 30.1
411 / 16.2
17 / 37.5
33 / 30 / 26
2.00
7.57
8.83 / 1.28
6.69 / 0.97
Btu/h
W
Btu/h
W
Btu/h
W
l/s/CFM
l/s/CFM
l/s/CFM
l/s/CFM
mmAq
mm/in
mm/in
mm/in
kg/lb
dBA
USGPM
LITRES/M
kPa/psi
kPa/psi
Notes:1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - ENTERING AIR TEMP. : 27ºC (80.6ºF) DB / 19ºC (66.2ºF) WB, ENTERING WATER TEMP. : 7ºC (44.6ºF), LEAVING WATER TEMP. : 12ºC (53.6ºF)b) HEATING - ENTERING AIR TEMP.: 20°C (68°F) DB, ENTERING WATER TEMP. : 60°C (140°F), LEAVING WATER TEMP. : 55°C (131°F)
4) SOUND PRESSURE LEVEL ARE ACCORDING TO GB STD - GB/D17758. POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE CENTRE OF THE UNIT. TESTED WITH 2m LENGTH DUCT AT THE AIR DISCHARGE OUTLET ANS AIR RETURN INLET.
MCC030CW - MCC060CW (Ceiling Concealed)
SUPER HIGH
HIGH
MEDIUM
LOW
HEIGHT
WIDTH
DEPTH
HEAD LOSS (COOLING)
UNIT DIMENSION
NOMINAL WATER FLOW RATE
7/8" BSP FEMALE ADAPTOR
MODEL
NOMINAL TOTAL COOLING CAPACITY
NOMINAL SENSIBLE COOLING CAPACITY
NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 60ºC)
EXTERNAL STATIC ( SH/H/M/L )
UNIT WEIGHT
SOUND PRESSURE LEVEL ( SH/H/M/L )
NOMINAL AIR FLOW
CONNECTION
HEAD LOSS (HEATING) : 60ºC
MCC060CW
54000
15826
39900
11694
110000
32239
779 / 1650
722 / 1530
675 / 1430
609 / 1290
18 / 16 / 14 / 10
379 / 14.9
1499 / 59.0
542 / 21.3
62 / 136.7
55 / 53 / 50 / 47
10.80
40.88
7.01 / 1.02
5.38 / 0.78
MCC050CW
47000
13775
34700
10170
95000
27843
750 / 1590
651 / 1380
604 / 1280
571 / 1210
18 / 16 / 14 / 11
378 / 14.9
1299 / 51.1
541 / 21.3
54 / 119.0
53 / 52 / 50 / 47
10.00
37.85
37.08 / 5.38
29.65 / 4.30
MCC040CW
38000
11137
34000
9965
75000
21981
519 / 1100
500 / 1060
467 / 990
425 / 900
21/ 18 / 13 / 9
378 / 14.9
1045 / 41.1
541 / 21.3
42 / 92.6
51 / 49 / 45 / 41
7.40
28.01
18.86 / 2.74
14.69 / 2.13
MCC038CW
35000
10258
27600
8089
65000
19050
727 / 1540
694 / 1470
670 / 1420
637 / 1350
14 / 12 / 11 / 9
310 / 12.2
1247 / 49.1
638 / 25.1
41 / 90.4
55 / 51 / 48 / 45
9.60
36.34
44.24 / 6.42
35.78 / 5.19
3/4" BSP FEMALE ADAPTOR
MCC030CW
28000
8206
21800
6389
60000
17585
425 / 900
392 / 830
359 / 760
335 / 710
21 / 17 / 13 / 9
378 / 14.9
929 / 36.6
541 / 21.3
39 / 86.0
49 / 46 / 42 / 38
6.20
23.47
12.82 / 1.89
9.86 / 1.43
Btu/h
W
Btu/h
W
Btu/h
W
l/s/CFM
l/s/CFM
l/s/CFM
l/s/CFM
mmAq
mm/in
mm/in
mm/in
kg/lb
dBA
USGPM
LITRES/M
kPa/psi
kPa/psi
S10
Chilled Water Fan Coil Unit Specifications
MCW200C - MCW1200C (Ceilling Concealed)
SUPER HIGH
HIGH
MEDIUM
LOW
HEIGHT
WIDTH
DEPTH
CONNECTION
EXTERNAL STATIC ( H/M/L )
UNIT DIMENSION
SOUND PRESSURE LEVEL ( H/M/L ) AT 60Pa
NOMINAL AIR FLOW
HEAD LOSS (HEATING) : 60ºC
UNIT WEIGHT
HEAD LOSS (COOLING)
NOMINAL WATER FLOW RATE
MODEL
NOMINAL TOTAL COOLING CAPACITY
NOMINAL SENSIBLE COOLING CAPACITY
NOMINAL TOTAL HEATING CAPACITY(ENTERING WATER TEMP. = 60ºC)
MCW1200C
40650
11914
27340
8013
69810
20460
NA
575 / 1218
489 / 1036
419 / 888
251 / 9.9
1824 / 71.8
490 / 19.3
46
52.4 / 50.6 / 47.4
10.04
38.00
32.7 / 4.74
32.7 / 4.74
MCW1000C
31360
9191
21290
6240
53970
15818
NA
455 / 965
378 / 800
305 / 647
251 / 9.9
1564 / 61.6
490 / 19.3
44
53.1 / 52.0 / 51.1
7.66
29.00
21 / 3.05
21 / 3.05
MCW800C
27880
8171
18470
5413
48510
14217
NA
403 / 853
328 / 695
256 / 542
251 / 9.9
1464 / 57.6
490 / 19.3
41
53.1 / 51.5 / 49.7
6.34
24.00
18.4 / 2.67
18.4 / 2.67
MCW600C
22260
6524
15020
4402
38640
11325
NA
295 / 624
236 / 500
197 / 418
251 / 9.9
1214 / 47.8
490 / 19.3
30
49.0 / 47.2 / 43.3
4.76
18.00
38.2 / 5.54
38.2 / 5.54
Up to 8.13 mmAq
3/4" BSP FEMALE ADAPTOR
MCW400C
14450
4235
9740
2855
25740
7544
NA
214 / 453
144 / 306
109 / 230
251 / 9.9
1014 / 39.9
490 / 19.3
26
48.7 / 46.3 / 46.4
3.43
13.00
21.6 / 3.13
21.6 / 3.13
MCW300C
11460
3359
7850
2301
19510
5718
NA
153 / 324
129 / 274
97 / 206
251 / 9.9
884 / 34.8
490 / 19.3
22
48.3 / 44.7 / 37.8
2.64
10.00
12 / 1.74
12 / 1.74
MCW200C
7710
2260
5120
1501
13440
3939
NA
114 / 241
94 / 200
64 / 135
251 / 9.9
714 / 28.1
490 / 19.3
19
40.1 / 37.2 / 34.9
1.85
7.00
14.6 / 2.12
14.6 / 2.12
Btu/h
W
Btu/h
W
Btu/h
W
l/s/CFM
l/s/CFM
l/s/CFM
l/s/CFM
mmAq
mm/in
mm/in
mm/in
kg/lb
dBA
USGPM
LITRES/M
kPa/psi
kPa/psi
Notes:1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - ENTERING AIR TEMP. : 27ºC (80.6ºF) DB / 19.5ºC (67.1ºF) WB, ENTERING WATER TEMP. : 7ºC (44.6ºF), LEAVING WATER TEMP. : 12ºC (53.6ºF)b) HEATING - ENTERING AIR TEMP.: 21ºC (69.8ºF) DB, ENTERING WATER TEMP. : 60ºC (140ºF), LEAVING WATER TEMP. : 55ºC (131ºF)
3) SOUND PRESSURE LEVEL ARE MEASURED IN AN ANECHOIC CHAMBER ACCORDING TO JIS C 9612 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE FACIA.
MCW200H - MCW1200H (Ceilling Concealed)
SUPER HIGH
HIGH
MEDIUM
LOW
HEIGHT
WIDTH
DEPTH
NOMINAL AIR FLOW
UNIT DIMENSION
MODEL
NOMINAL TOTAL COOLING CAPACITY
NOMINAL TOTAL HEATING CAPACITY(ENTERING WATER TEMP. = 60ºC) - 1 ROW
NOMINAL WATER FLOW RATE - 3 ROWS
NOMINAL WATER FLOW RATE - 1 ROW
CONNECTION
NOMINAL SENSIBLE COOLING CAPACITY
NOMINAL TOTAL HEATING CAPACITY(ENTERING WATER TEMP. = 60ºC) - 3 ROWS
EXTERNAL STATIC ( SH/H/M/L )
UNIT WEIGHT
SOUND PRESSURE LEVEL ( H/M/L ) AT 60Pa
HEAD LOSS (COOLING) - 3 ROWS
HEAD LOSS (HEATING) : 60ºC - 3 ROWs
HEAD LOSS (COOLING) - 1 ROW
HEAD LOSS (HEATING) : 60ºC - 1 ROW
MCW1200H
34800
10200
26410
7740
64110
18790
29240
8570
NA
604 / 1280
519 / 1100
425 / 900
251 / 9.9
1824 / 71.8
490 / 19.3
49
52.4 / 50.6 / 47.4
8.45
32.00
3.72
14.10
45 / 6.53
45 / 6.53
20 / 2.9
20 / 2.9
MCW1000H
28320
8300
20130
5900
49300
14450
23920
7010
NA
472 / 1000
415 / 880
302 / 640
251 / 9.9
1564 / 61.6
490 / 19.3
47
53.1 / 52.0 / 51.1
6.87
26.00
3.20
12.10
26 / 3.77
26 / 3.77
18 / 2.61
18 / 2.61
MCW800H
26100
7650
18080
5300
43670
12800
17740
5200
NA
396 / 840
345 / 730
288 / 610
251 / 9.9
1464 / 57.6
490 / 19.3
44
53.1 / 51.5 / 49.7
6.13
23.20
2.38
9.00
33 / 4.79
33 / 4.79
21 / 3.05
21 / 3.05
MCW600H
20810
6100
14330
4200
33300
9760
15120
4430
NA
316 / 670
307 / 650
212 / 450
251 / 9.9
1214 / 47.8
490 / 19.3
32
49.0 / 47.2 / 43.3
4.76
18.00
2.11
8.00
47 / 6.82
47 / 6.82
17 / 2.47
17 / 2.47
3/4" BSP FEMALE ADAPTOR
Up to 8.13 mmAq
MCW400H
14330
4200
9900
2900
24670
7230
11430
3350
NA
212 / 450
189 / 400
165 / 350
251 / 9.9
1014 / 39.9
490 / 19.3
28
48.7 / 46.3 / 46.4
3.43
13.00
1.74
6.60
22 / 3.19
22 / 3.19
15 / 2.18
15 / 2.18
MCW300H
10240
3000
6960
2040
17200
5040
7850
2300
NA
165 / 350
142 / 300
94 / 200
251 / 9.9
884 / 34.8
490 / 19.3
24
48.3 / 44.7 / 37.8
2.51
9.50
1.22
4.60
13 / 1.89
13 / 1.89
8 / 1.16
8 / 1.16
MCW200H
7710
2260
5220
1530
12180
3570
4810
1410
NA
113 / 240
94 / 200
76 / 160
251 / 9.9
714 / 28.1
490 / 19.3
20
40.1 / 37.2 / 34.9
1.80
6.80
0.87
3.30
16 / 2.32
16 / 2.32
8 / 1.16
8 / 1.16
Btu/h
W
Btu/h
W
Btu/h
W
Btu/h
W
l/s/CFM
l/s/CFM
l/s/CFM
l/s/CFM
mmAq
mm/in
mm/in
mm/in
kg/lb
dBA
USGPM
LITRES/M
USGPM
LITRES/M
kPa/psi
kPa/psi
kPa/psi
kPa/psi
S11
Chilled Water Fan Coil Unit Specifications
MWM007GW - MWM025GW (Wall Mount)
MODEL
HIGH
HEIGHT
WIDTH
DEPTH
NOMINAL TOTAL COOLING CAPACITY - 1
NOMINAL SENSIBLE COOLING CAPACITY
NOMINAL TOTAL HEATING CAPACITY(ENTERING WATER TEMP. = 50°C)
NOMINAL AIR FLOW
NOMINAL TOTAL COOLING CAPACITY - 1Ø <3Ø>
HEAD LOSS (COOLING)
HEAD LOSS (HEATING) : 50°C
CONNECTION
UNIT WEIGHT
SOUND PRESSURE LEVEL ( H/M/L )
NOMINAL SENSIBLE COOLING CAPACITY
NOMINAL TOTAL HEATING CAPACITY(ENTERING WATER TEMP. = 50°C)
NOMINAL WATER FLOW RATE
UNIT DIMENSION
NOMINAL WATER FLOW RATE
HEAD LOSS (COOLING)
HEAD LOSS (HEATING) : 50°C
MWM025GW
18000
5280
14800
4330
23000
6740
18000
5275
13680
4009
23000
6741
312 / 660
16 / 35.3
50 / 48 / 44
4.00
15.12
69.3 / 10.05
70.6 / 10.243.65
13.82
41.7 / 6.04
35.8 / 5.19
304 / 12.0
1062 / 41.8
222 / 8.7
MWM020GW
15500
4540
12500
3650
20500
6010
15500
4543
11780
3453
20500
6008
297 / 630
16 / 35.3
49 / 43 / 40
3.40
12.85
50.3 / 7.29
50.6 / 7.343.43
12.98
50.4 / 7.31
50.9 / 7.38
MWM015GW
11000
3220
8000
2350
14000
4100
11000
3224
8360
2450
14000
4103
163 / 345
42 / 36 / 29
2.40
9.07
69.3 / 10.05
60.6 / 8.792.42
9.16
67.8 / 9.83
61.8 / 8.95
12 / 26.5
899 / 35.4
198 / 7.8
260 / 10.2
MWM010GW
9500
2780
6900
2030
12800
3750
9500
2784
7220
2116
12800
3751
142 / 300
39 / 34 / 28
2.10
7.94
64.7 / 9.38
58.6 / 8.52.16
8.18
54.9 / 7.95
47.0 / 6.81
1/2" BSP FEMALE ADAPTOR
MWM007GW
8000
2340
5900
1740
10300
3020
130 / 275
260 / 10.2
799 / 31.5
198 / 7.8
10 / 22.1
40 / 35 / 29
1.80
6.80
48.3 / 7
42 / 6.09
NA
NA
Btu/h
W
Btu/h
W
Btu/h
W
Btu/h
W
Btu/h
W
Btu/h
W
USGPM
LITRES/M
kPa / psi
kPa / psi
USGPM
LITRES/M
kPa / psi
kPa / psi
l/s / CFM
mm/in
mm/in
mm/in
kg/lb
dBA
60Hz
50Hz
50Hz
60Hz
Notes:1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - ENTERING AIR TEMP. : 27°C (80.6°F) DB / 19°C (66.2°F) WB, ENTERING WATER TEMP. : 7°C (44.6°F), LEAVING WATER TEMP. : 12°C (53.6°F)b) HEATING - ENTERING AIR TEMP.: 20°C (68°F) DB, ENTERING WATER TEMP. : 70°C (158°F), LEAVING WATER TEMP. : 65°C (149°F)
4) a) MDB: SOUND PRESSURE LEVEL ARE TESTED IN ANECHOIC CHAMBER AT 1.4m BELOW THE UNIT (FREE RETURN AND THE DISCHARGE AIR WAS DUCTED TO ADJACENT ROOM) b) MWM:SOUND PRESSURE LEVEL ARE TESTED IN ANECHOIC CHAMBER AND ACCORDING TO JIS C 9612 STANDARD. MWMFW : POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 0.8m BELOW THE UNIT. MWM301W : 1m IN FRONT AND 1 m BELOW THE DISCHARGE OPENING OF THE UNIT (JIS B 8615)
MDB075BW - MDB0150BW (Ducted Blower)
HEIGHT
WIDTH
DEPTH
1 1/8" BRAZING
10
NOMINAL AIR FLOW
15
HEAD LOSS (HEATING) : 70°C
HEAD LOSS (COOLING)
UNIT DIMENSION
UNIT WEIGHT
NOMINAL WATER FLOW RATE
NOMINAL SENSIBLE COOLING CAPACITY
SOUND PRESSURE LEVEL
EXTERNAL STATIC
CONNECTION
NOMINAL TOTAL HEATING CAPACITY(ENTERING WATER TEMP. = 70°C)
NOMINAL TOTAL COOLING CAPACITY
MODEL MDB075BW
73000
21395
57200
16764
160000
46893
1128 / 2390
572 / 22.5
1502 / 59.1
761 / 30.0
96 / 211.6
56
16.30
61.70
20.13 / 2.92
15.89 / 2.30
MDB0100BW
95000
27843
71400
20926
200000
58617
1444 / 3060
572 / 22.5
1502 / 59.1
761 / 30.0
100 / 220.5
57
20.00
75.71
16.27 / 2.36
12.69 / 1.84
MDB0125BW
122500
35903
94500
27696
265000
77667
1897 / 4020
885 / 34.8
1640 / 64.6
1040 / 40.9
140 / 308.6
58
27.10
102.58
22.75 / 3.30
17.93 / 2.60
MDB0150BW
157800
46249
118000
34584
329000
96424
2077 / 4400
885 / 34.8
1640 / 64.6
1040 / 40.9
145 / 319.7
59
35.00
132.50
18.96 / 2.75
14.89 / 2.16
Btu/h
W
Btu/h
W
Btu/h
W
l/s / CFM
mmAq
mm/in
mm/in
mm/in
kg/lb
dBA
USGPM
LITRES/M
kPa / psi
kPa / psi
S12
Chilled Water Fan Coil Unit Specifications
MCE015EW - MCE025EW (Ceiling Convertible)
Notes:1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - ENTERING AIR TEMP. : 27ºC (80.6ºF) DB / 19ºC (66.2ºF) WB, ENTERING WATER TEMP. : 7ºC (44.6ºF), LEAVING WATER TEMP. : 12ºC (53.6ºF)b) HEATING - ENTERING AIR TEMP.: 20ºC (68ºF) DB, ENTERING WATER TEMP. : 70ºC (158ºF), LEAVING WATER TEMP. : 65ºC (149ºF)
4) SOUND PRESSURE LEVEL ARE TESTED IN ANECHOIC CHAMBER AND ACCORDING TO JIS C 9612 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT
MCE015EW MCE020EW MCE025EW
15500 20300 21000
4540 5950 6160
12700 15400 16200
3720 4520 4740
19500 25000 28000
5720 7330 8210
HIGH 245 / 519 273 / 579 293 / 619
MEDIUM 217 / 460 250 / 530 269 / 570
LOW 192 / 406 231 / 490 245 / 520
HEIGHT
WIDTH
DEPTH
27 / 59.7 27 / 59.7 28 / 61.9
48 / 46 / 43 50 / 47 / 46 51 / 48 / 47
3.43 4.49 4.67
13.00 17.00 17.67
28 / 4.0 48 / 7.0 57 / 8.3
24 / 3.5 42 / 6.1 50 / 7.3HEAD LOSS (HEATING) : 50ºC
CONNECTION 1/2" BSP FEMALE ADAPTOR
UNIT WEIGHT
SOUND PRESSURE LEVEL ( H/M/L )
NOMINAL WATER FLOW RATE
HEAD LOSS (COOLING)
NOMINAL AIR FLOW
UNIT DIMENSION
212.5 / 8.4
1090 / 42.9
630 / 24.8
MODEL
NOMINAL TOTAL COOLING CAPACITY
NOMINAL SENSIBLE COOLING CAPACITY
NOMINAL TOTAL HEATING CAPACITY (ENTERINGWATER TEMP. = 70ºC)
Btu/h
W
Btu/h
W
Btu/h
W
l/s/CFM
l/s/CFM
l/s/CFM
mm/in
mm/in
mm/in
kg/lb
dBA
USGPM
LITRES/M
kPa/psi
kPa/psi
A Global Leader in System Solutions for Air Conditioning, Heating, Ventilating and Refrigeration.
Products manufactured in an ISO certified facility.This document contains the most current product information as of this printing.
For the most up-to-date product information, please go to www.mcquay.com.
© 2008 McQuay International +1 (800) 432-1342 www.mcquay.com