check list for protection audit (1)

Upload: govindappa-ramappa

Post on 04-Apr-2018

221 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/29/2019 Check List for Protection Audit (1)

    1/14

    Check List for Transmission Line

    Name/Details:

    Sl. No Protection Scheme Status ** Remarks

    1. Main I-Distance Protection Yes/No

    2. Main II-Distance Protection of directionalcomparison protection or phase segregated

    line differential protection

    Yes/No

    3. Directional instantaneous definite

    minimum time (IDMT) type earth fault

    relay

    Yes/No

    4. Directional IDMT over current and earth

    fault back up protection

    Yes/No

    5. Two stage over voltage protection Yes/No

    6. Auto Reclosing Yes/No

    7. Carrier aided inter-tripping/blocking

    feature

    Yes/No

    8. Are Power Line Carrier Communication

    (PLCC) equipment with Protection

    Coupler complete for speech transmission,

    line protection and data channels

    provided?

    Yes/No

    Yes/No

    Yes/No

    9. Are 100% back up Communication

    Channels provided for transmission line &

    line compensating equipment?

    Yes/No

    10. Disturbance Recorder Yes/No

    11. Distance to Fault Locator Yes/No

    12. Event Logger:i) Stand Alone

    ii) Part of S/S or switchyard

    automation system

    13. Are Time Synchronizing Equipment (TSE)

    complete with antenna, all cables,

    processing equipments etc. provided to

    receive synchronizing pulse through Global

    Yes/No

  • 7/29/2019 Check List for Protection Audit (1)

    2/14

    Positioning System (GPS) compatible for

    synchronization of event logger,

    disturbance recorder and

    SCADA/automation system ?

    14. Are all protection employed Numerical

    type?

    Yes/No

    15. Are two protection channels in addition to

    one speech plus data channel provided for

    each direction?

    Yes/No

    16. Local Breaker Backup Protection (LBB) Yes/No

    17. Any other Protection

    ** Check the availability & functional healthiness.

    Note:

    a) Sl No.2 is optional at voltage level 220KV & not required at voltage level 132KV;

    b) Sl No.3 is required at 220 KV if both Main-I & Main-II are distance protections,

    otherwise not required. At 132 KV level it is not required;

    c) Sl No.4 is required at 220 KV level if Main-II is not provided, otherwise not.

    d) Sl No.14 is required at 220KV and above;

  • 7/29/2019 Check List for Protection Audit (1)

    3/14

    Check List for Transformer

    Name/Details:

    Sl. No Protection Scheme Status ** Remarks

    1. Differential Protection Yes/No

    2. Over Fluxing Yes/No

    3. Restricted Earth Fault Yes/No

    4. Backup directional over current and earth

    fault protection (HV & LV side) or

    impedance protection

    Yes/No

    5. Buchholz Yes/No

    6. Winding Temperature Indicator (WTI) Yes/No

    7. Oil Temperature Indicator (OTI) Yes/No

    8. Magnetic Oil Gauge (MOG) with low oil

    level alarm

    Yes/No

    9. Oil Surge Relay (OSR) for On Load Tap

    Changer (OLTC)

    Yes/No

    10. Pressure Relieve Device (PRD) Yes/No

    11. Surge Arrester (SA) on both primary and

    secondary sides of transformers located

    outdoors and connected to over head lines

    Yes/No

    12. Tertiary winding protection Yes/No

    13. Over load alarm Yes/No

    14. Cooling

    15. Any other protection

    ** Check the availability & functional healthiness.

    Note:

    a) Sl No.6 is required at voltage level 220KV for 100MVA & above rating ;

    b) OTI is required for 1 MVA and above;

  • 7/29/2019 Check List for Protection Audit (1)

    4/14

    Check List for Reactor

    Name/Details:

    Sl. No Protection Scheme Status ** Remarks

    1. Differential Yes/No

    2. Restricted Earth Fault (REF) Yes/No

    3. Reactor backup protection (impedance

    type or definite time over current (O/C)

    and earth fault (E/F) protection)

    Yes/No

    4. Buchholz Yes/No5. Winding Temperature Indicator (WTI) Yes/No

    6. Magnetic Oil Gauge (MOG) Yes/No

    7. Oil Temperature Indicator (OTI) Yes/No

    8. Surge Arrestor (SA) Yes/No

    9. Cooling

    10. Any other Protection

    ** Check the availability & functional healthiness.

  • 7/29/2019 Check List for Protection Audit (1)

    5/14

    Check List for Sub-Station/Switchyard

    Name/Details:

    Sl. No Protection Scheme Status ** Remarks

    1. Local Breaker Backup (LBB) Yes/No

    2. Event Logger (EL) Yes/No

    3. Synchronizing Facility Yes/No

    4. Are Synchro Check Relay provided with requisite

    settings? Yes/No

    5. DC supply:i) 48V

    ii) 110V

    iii) 220V

    Yes/No

    Yes/No

    Yes/No

    6. DG set Yes/No

    7. Auxiliary Supply Yes/No

    8. Special Protection Scheme (SPS) Yes/No

    9. Under Frequency Relay(UFR):

    i) Stage I

    ii) Stage II

    iii) Stage III

    Yes/No

    Yes/No

    Yes/No

    10. Has the Fault level Increased since connected togrid? Yes/No

    11. If status at Sl.No 1 isYes, then whether

    Sectionalisation of the bus/ Series Reactor on the

    line or bus provided to limit the fault level? Yes/No

    12. Has the size and number of ICT in the S/S been

    planned in a way that the outage of any single unit

    does not overload the remaining ICTs or the

    underlying transmission system

    Yes/No

    13. SCADA:i) Voice

    ii) Data

    Yes/No

    Yes/No

    14. Switching Schemes Yes/No

    15. Are Circuit Breakers suitable for single-phase and

    three-phase auto reclosing? Yes/No

  • 7/29/2019 Check List for Protection Audit (1)

    6/14

    16. Are Circuit Breakers provided with two trip coils? Yes/No

    17. Are Circuit Breakers provided with Pre Insertion

    Resistors?

    Yes/No

    18. Are Earthing Switches provided at appropriate

    locations to facilitate earthing of outgoingtransmission lines to enable maintenance?

    Yes/No

    19. Are all main protection relays of numerical type? Yes/No

    20. Are protection functions subdivided into two

    independent groups & capable of providing

    uninterrupted protection even in the event of one

    protection groups failing?

    Yes/No

    21. Are two sets of DC sources available? Yes/No

    22. If status to Sl.No 21 is Yes, then whether relays are

    electrically and physically segregated into two

    groups to obtain redundancy and to take

    protection systems out for maintenance while theequipment remains in service?

    Yes/No

    23. If status to Sl.No 21 is No, then whether relays are

    electrically and physically segregated into two

    groups by giving DC supplies through separate

    fuses?

    Yes/No

    24. Bus Bar Protection Yes/No

    25. Bus Bar Protection scheme has provision for future

    expansion Yes/No

    26. Any other Protection

    ** Check the availability & functional healthiness.

    Note:

    a) Requirements for Sl No.14 are:

    Switching Scheme Voltage level

    Main & Transfer Bus or Double bus 66KV & 132 KV

    Double Main & Transfer Bus or Double bus 220KV

    Breaker & a half or Double Main and

    Transfer bus

    400KV

  • 7/29/2019 Check List for Protection Audit (1)

    7/14

    Check List for Generator

    Name/Details:

    Sl. No Protection Scheme Status ** Remarks

    1. Is Power System Stabiliser (PSS)

    provided in AVR for the generator? Yes/No

    2. Is it possible to use the Generator

    Transformer to provide start up power

    from the grid?

    Yes/No

    3. Cooling of GT , UAT & ST Yes/No

    4. Neutral Earthing

    5. Are protection systems for Generator,

    Generator Transformers, Unit

    Auxiliary Transformers connected to

    two independent channels/groups?

    Yes/No

    6. Generator Differential Yes/No

    7. 100% Stator Earth Fault Yes/No

    8. 95% Stator Earth Fault Yes/No

    9. Standby Stator Earth Fault Yes/No10. Interturn Fault Protection Yes/No

    11. Loss of field Yes/No

    12. Negative phase sequence Yes/No

    13. Low Forward power & Reverse power

    interlock for steam turbine generator

    Yes/No

    14. Rotor Earth Fault Yes/No

    15. Definite Time overvoltage Yes/No

    16. Generator Under Frequency Yes/No

    17. Over Fluxing for generator Yes/No

    18. Overload Yes/No

    19. Back up Impedance Yes/No20. Overheating (winding and/or bearing) Yes/No

  • 7/29/2019 Check List for Protection Audit (1)

    8/14

  • 7/29/2019 Check List for Protection Audit (1)

    9/14

    Check List for Generator Transformer

    Name/Details:

    Sl. No Protection Scheme Status ** Remarks

    1. Overall Differential Yes/No

    2. Rstricted Earth Fault Yes/No3. Overhead line connection Differential Yes/No

    4. Back up Earth Fault on GT HV Neutral Yes/No

    5. Over Fluxing Yes/No

    6. Back up non directional over current in

    all phases of on HV side of GT Yes/No

    7. Oil Temperature Indicator (OTI) trip Yes/No

    8. Winding Temperature Indicator (WTI)

    trip

    Yes/No

    9. Buchholz Yes/No

    10. Pressure Relief Valve Yes/No

    11. Pole Discrepancy of GT breaker Yes/No12. Breaker failure of GT breaker Yes/No

    13. Start-up Earth fault of LV and HV

    winding of GT and UAT Yes/No

    14. Any other Protection

    ** Check the availability & functional healthiness.

  • 7/29/2019 Check List for Protection Audit (1)

    10/14

    Check List for Unit Auxiliary Transformer

    Name/Details:

    Sl. No Protection Scheme Status ** Remarks1. Differential Yes/No

    2. LV back up Earth Fault Yes/No

    3. LV Restricted Earth Fault Yes/No

    4. Back up Over current Yes/No

    5. Oil Temperature Indicator (OTI) trip Yes/No

    6. Winding Temperature Indicator (WTI)

    trip

    Yes/No

    7. Buchholz Yes/No

    8. Pressure Relief Valve Yes/No

    9. Any other Protection Yes/No

    ** Check the availability & functional healthiness.

  • 7/29/2019 Check List for Protection Audit (1)

    11/14

    Check List for Station Transformer

    Name/Details:

    Sl. No Protection Scheme Status ** Remarks

    1. Differential current Yes/No

    2. Restricted Earth Fault for LV winding Yes/No3. Restricted Earth Fault for HV winding Yes/No

    4. Back up over current on HV side Yes/No

    5. Back up Earth Fault Yes/No

    6. Over Fluxing Yes/No

    7. Oil Temperature Indicator (OTI) Yes/No

    8. Winding Temperature Indicator (WTI) Yes/No

    9. Buchholz Yes/No

    10. Pressure Relief Valve trip Yes/No

    11. Breaker failure of GT breaker Yes/No

    12. Any other Protection

    ** Check the availability & functional healthiness.

  • 7/29/2019 Check List for Protection Audit (1)

    12/14

    Check List for HVDC

    Name/Details:

    Sl. No Protection Scheme Status ** Remarks

    1. Are DC Converter Terminals-

    i) Manned by Operator

    ii) Controlled by Remote Operation of

    SCADA system

    Yes/No

    Yes/No

    2. Is control system hierarchy followed? Yes/No

    3. Has HVDC Bipole the needed control

    features as given in note (b) Yes/No

    4. Are modules for pole control, converter

    control and valve control provided?

    Yes/No

    5. Does AC side protection function cover the

    zone for converter transformer, AC filters,

    shunt capacitors, shunt reactors and bus

    bars?

    Yes/No

    6. Does AC protection follow the same

    philosophy as in a typical substation i.e.

    detection of fault by relay and tripping of

    circuit breaker?

    Yes/No

    7. Does DC side protection function cover thezones consisting of valve hall, DC

    switchyard including smoothing reactor &

    DC filters, DC line, electrode line and

    ground electrode?

    Yes/No

    8. Do AC & DC protection system each have

    two identical independent electrical and

    mechanical systems with following

    protections----

    i) Converter differential

    ii) DC over current

    iii) DC differentialiv) AC conductor ground fault

    v) Commutation failure

    vi) DC filter protection

    vii)DC smoothing reactor

    viii) DC line ground fault

    ix) DC line differential

    x) DC under voltage

    Yes/No

    Yes/No

    Yes/NoYes/No

    Yes/No

    Yes/No

    Yes/No

    Yes/No

    Yes/No

    Yes/No

  • 7/29/2019 Check List for Protection Audit (1)

    13/14

    xi) DC overvoltage

    xii)Electrode line monitoring &

    protection

    Yes/No

    Yes/No

    9. For requirements of reliability and fast

    controllability of the HVDC system isprotection provided by numerical relays?

    Yes/No

    10. Are HVDC terminals provided with

    reliable communication system?

    i) Through Optical fibers

    ii) Through PLCC

    iii) Through PLCC & Optical fiber

    both

    Yes/No

    Yes/No

    Yes/No

    ** Check the availability & functional healthiness.

    Note:

    a) The control system hierarchy in Sl. No. 2 shall be as follows:

    (A)Bipole Control;

    (B) Pole Control;

    (C)Converter Control;

    (D)Valve Control;

    (E) VDCOL;

    b) The HVDC Bipole shall have control features including but not limited to the

    following:

    (A)Reactive Power Controller;

  • 7/29/2019 Check List for Protection Audit (1)

    14/14

    (B) Current & Power Controller;

    (C)Frequency Controller;

    (D)Power Modulator, Pole Power Compensation;

    (E) Sub-Synchronous Resonance Damping Controller;

    (F) Load Frequency Controller;

    (G)Current Margin Controller;

    (H)Excessive reactive power consumption Controller;

    (I) AC system stability function, such as power swing damping function;

    (J) NGH damping;

    c) Sl No.8(vi) not required for back to back schemes;