check list for protection audit (1)
TRANSCRIPT
-
7/29/2019 Check List for Protection Audit (1)
1/14
Check List for Transmission Line
Name/Details:
Sl. No Protection Scheme Status ** Remarks
1. Main I-Distance Protection Yes/No
2. Main II-Distance Protection of directionalcomparison protection or phase segregated
line differential protection
Yes/No
3. Directional instantaneous definite
minimum time (IDMT) type earth fault
relay
Yes/No
4. Directional IDMT over current and earth
fault back up protection
Yes/No
5. Two stage over voltage protection Yes/No
6. Auto Reclosing Yes/No
7. Carrier aided inter-tripping/blocking
feature
Yes/No
8. Are Power Line Carrier Communication
(PLCC) equipment with Protection
Coupler complete for speech transmission,
line protection and data channels
provided?
Yes/No
Yes/No
Yes/No
9. Are 100% back up Communication
Channels provided for transmission line &
line compensating equipment?
Yes/No
10. Disturbance Recorder Yes/No
11. Distance to Fault Locator Yes/No
12. Event Logger:i) Stand Alone
ii) Part of S/S or switchyard
automation system
13. Are Time Synchronizing Equipment (TSE)
complete with antenna, all cables,
processing equipments etc. provided to
receive synchronizing pulse through Global
Yes/No
-
7/29/2019 Check List for Protection Audit (1)
2/14
Positioning System (GPS) compatible for
synchronization of event logger,
disturbance recorder and
SCADA/automation system ?
14. Are all protection employed Numerical
type?
Yes/No
15. Are two protection channels in addition to
one speech plus data channel provided for
each direction?
Yes/No
16. Local Breaker Backup Protection (LBB) Yes/No
17. Any other Protection
** Check the availability & functional healthiness.
Note:
a) Sl No.2 is optional at voltage level 220KV & not required at voltage level 132KV;
b) Sl No.3 is required at 220 KV if both Main-I & Main-II are distance protections,
otherwise not required. At 132 KV level it is not required;
c) Sl No.4 is required at 220 KV level if Main-II is not provided, otherwise not.
d) Sl No.14 is required at 220KV and above;
-
7/29/2019 Check List for Protection Audit (1)
3/14
Check List for Transformer
Name/Details:
Sl. No Protection Scheme Status ** Remarks
1. Differential Protection Yes/No
2. Over Fluxing Yes/No
3. Restricted Earth Fault Yes/No
4. Backup directional over current and earth
fault protection (HV & LV side) or
impedance protection
Yes/No
5. Buchholz Yes/No
6. Winding Temperature Indicator (WTI) Yes/No
7. Oil Temperature Indicator (OTI) Yes/No
8. Magnetic Oil Gauge (MOG) with low oil
level alarm
Yes/No
9. Oil Surge Relay (OSR) for On Load Tap
Changer (OLTC)
Yes/No
10. Pressure Relieve Device (PRD) Yes/No
11. Surge Arrester (SA) on both primary and
secondary sides of transformers located
outdoors and connected to over head lines
Yes/No
12. Tertiary winding protection Yes/No
13. Over load alarm Yes/No
14. Cooling
15. Any other protection
** Check the availability & functional healthiness.
Note:
a) Sl No.6 is required at voltage level 220KV for 100MVA & above rating ;
b) OTI is required for 1 MVA and above;
-
7/29/2019 Check List for Protection Audit (1)
4/14
Check List for Reactor
Name/Details:
Sl. No Protection Scheme Status ** Remarks
1. Differential Yes/No
2. Restricted Earth Fault (REF) Yes/No
3. Reactor backup protection (impedance
type or definite time over current (O/C)
and earth fault (E/F) protection)
Yes/No
4. Buchholz Yes/No5. Winding Temperature Indicator (WTI) Yes/No
6. Magnetic Oil Gauge (MOG) Yes/No
7. Oil Temperature Indicator (OTI) Yes/No
8. Surge Arrestor (SA) Yes/No
9. Cooling
10. Any other Protection
** Check the availability & functional healthiness.
-
7/29/2019 Check List for Protection Audit (1)
5/14
Check List for Sub-Station/Switchyard
Name/Details:
Sl. No Protection Scheme Status ** Remarks
1. Local Breaker Backup (LBB) Yes/No
2. Event Logger (EL) Yes/No
3. Synchronizing Facility Yes/No
4. Are Synchro Check Relay provided with requisite
settings? Yes/No
5. DC supply:i) 48V
ii) 110V
iii) 220V
Yes/No
Yes/No
Yes/No
6. DG set Yes/No
7. Auxiliary Supply Yes/No
8. Special Protection Scheme (SPS) Yes/No
9. Under Frequency Relay(UFR):
i) Stage I
ii) Stage II
iii) Stage III
Yes/No
Yes/No
Yes/No
10. Has the Fault level Increased since connected togrid? Yes/No
11. If status at Sl.No 1 isYes, then whether
Sectionalisation of the bus/ Series Reactor on the
line or bus provided to limit the fault level? Yes/No
12. Has the size and number of ICT in the S/S been
planned in a way that the outage of any single unit
does not overload the remaining ICTs or the
underlying transmission system
Yes/No
13. SCADA:i) Voice
ii) Data
Yes/No
Yes/No
14. Switching Schemes Yes/No
15. Are Circuit Breakers suitable for single-phase and
three-phase auto reclosing? Yes/No
-
7/29/2019 Check List for Protection Audit (1)
6/14
16. Are Circuit Breakers provided with two trip coils? Yes/No
17. Are Circuit Breakers provided with Pre Insertion
Resistors?
Yes/No
18. Are Earthing Switches provided at appropriate
locations to facilitate earthing of outgoingtransmission lines to enable maintenance?
Yes/No
19. Are all main protection relays of numerical type? Yes/No
20. Are protection functions subdivided into two
independent groups & capable of providing
uninterrupted protection even in the event of one
protection groups failing?
Yes/No
21. Are two sets of DC sources available? Yes/No
22. If status to Sl.No 21 is Yes, then whether relays are
electrically and physically segregated into two
groups to obtain redundancy and to take
protection systems out for maintenance while theequipment remains in service?
Yes/No
23. If status to Sl.No 21 is No, then whether relays are
electrically and physically segregated into two
groups by giving DC supplies through separate
fuses?
Yes/No
24. Bus Bar Protection Yes/No
25. Bus Bar Protection scheme has provision for future
expansion Yes/No
26. Any other Protection
** Check the availability & functional healthiness.
Note:
a) Requirements for Sl No.14 are:
Switching Scheme Voltage level
Main & Transfer Bus or Double bus 66KV & 132 KV
Double Main & Transfer Bus or Double bus 220KV
Breaker & a half or Double Main and
Transfer bus
400KV
-
7/29/2019 Check List for Protection Audit (1)
7/14
Check List for Generator
Name/Details:
Sl. No Protection Scheme Status ** Remarks
1. Is Power System Stabiliser (PSS)
provided in AVR for the generator? Yes/No
2. Is it possible to use the Generator
Transformer to provide start up power
from the grid?
Yes/No
3. Cooling of GT , UAT & ST Yes/No
4. Neutral Earthing
5. Are protection systems for Generator,
Generator Transformers, Unit
Auxiliary Transformers connected to
two independent channels/groups?
Yes/No
6. Generator Differential Yes/No
7. 100% Stator Earth Fault Yes/No
8. 95% Stator Earth Fault Yes/No
9. Standby Stator Earth Fault Yes/No10. Interturn Fault Protection Yes/No
11. Loss of field Yes/No
12. Negative phase sequence Yes/No
13. Low Forward power & Reverse power
interlock for steam turbine generator
Yes/No
14. Rotor Earth Fault Yes/No
15. Definite Time overvoltage Yes/No
16. Generator Under Frequency Yes/No
17. Over Fluxing for generator Yes/No
18. Overload Yes/No
19. Back up Impedance Yes/No20. Overheating (winding and/or bearing) Yes/No
-
7/29/2019 Check List for Protection Audit (1)
8/14
-
7/29/2019 Check List for Protection Audit (1)
9/14
Check List for Generator Transformer
Name/Details:
Sl. No Protection Scheme Status ** Remarks
1. Overall Differential Yes/No
2. Rstricted Earth Fault Yes/No3. Overhead line connection Differential Yes/No
4. Back up Earth Fault on GT HV Neutral Yes/No
5. Over Fluxing Yes/No
6. Back up non directional over current in
all phases of on HV side of GT Yes/No
7. Oil Temperature Indicator (OTI) trip Yes/No
8. Winding Temperature Indicator (WTI)
trip
Yes/No
9. Buchholz Yes/No
10. Pressure Relief Valve Yes/No
11. Pole Discrepancy of GT breaker Yes/No12. Breaker failure of GT breaker Yes/No
13. Start-up Earth fault of LV and HV
winding of GT and UAT Yes/No
14. Any other Protection
** Check the availability & functional healthiness.
-
7/29/2019 Check List for Protection Audit (1)
10/14
Check List for Unit Auxiliary Transformer
Name/Details:
Sl. No Protection Scheme Status ** Remarks1. Differential Yes/No
2. LV back up Earth Fault Yes/No
3. LV Restricted Earth Fault Yes/No
4. Back up Over current Yes/No
5. Oil Temperature Indicator (OTI) trip Yes/No
6. Winding Temperature Indicator (WTI)
trip
Yes/No
7. Buchholz Yes/No
8. Pressure Relief Valve Yes/No
9. Any other Protection Yes/No
** Check the availability & functional healthiness.
-
7/29/2019 Check List for Protection Audit (1)
11/14
Check List for Station Transformer
Name/Details:
Sl. No Protection Scheme Status ** Remarks
1. Differential current Yes/No
2. Restricted Earth Fault for LV winding Yes/No3. Restricted Earth Fault for HV winding Yes/No
4. Back up over current on HV side Yes/No
5. Back up Earth Fault Yes/No
6. Over Fluxing Yes/No
7. Oil Temperature Indicator (OTI) Yes/No
8. Winding Temperature Indicator (WTI) Yes/No
9. Buchholz Yes/No
10. Pressure Relief Valve trip Yes/No
11. Breaker failure of GT breaker Yes/No
12. Any other Protection
** Check the availability & functional healthiness.
-
7/29/2019 Check List for Protection Audit (1)
12/14
Check List for HVDC
Name/Details:
Sl. No Protection Scheme Status ** Remarks
1. Are DC Converter Terminals-
i) Manned by Operator
ii) Controlled by Remote Operation of
SCADA system
Yes/No
Yes/No
2. Is control system hierarchy followed? Yes/No
3. Has HVDC Bipole the needed control
features as given in note (b) Yes/No
4. Are modules for pole control, converter
control and valve control provided?
Yes/No
5. Does AC side protection function cover the
zone for converter transformer, AC filters,
shunt capacitors, shunt reactors and bus
bars?
Yes/No
6. Does AC protection follow the same
philosophy as in a typical substation i.e.
detection of fault by relay and tripping of
circuit breaker?
Yes/No
7. Does DC side protection function cover thezones consisting of valve hall, DC
switchyard including smoothing reactor &
DC filters, DC line, electrode line and
ground electrode?
Yes/No
8. Do AC & DC protection system each have
two identical independent electrical and
mechanical systems with following
protections----
i) Converter differential
ii) DC over current
iii) DC differentialiv) AC conductor ground fault
v) Commutation failure
vi) DC filter protection
vii)DC smoothing reactor
viii) DC line ground fault
ix) DC line differential
x) DC under voltage
Yes/No
Yes/No
Yes/NoYes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
-
7/29/2019 Check List for Protection Audit (1)
13/14
xi) DC overvoltage
xii)Electrode line monitoring &
protection
Yes/No
Yes/No
9. For requirements of reliability and fast
controllability of the HVDC system isprotection provided by numerical relays?
Yes/No
10. Are HVDC terminals provided with
reliable communication system?
i) Through Optical fibers
ii) Through PLCC
iii) Through PLCC & Optical fiber
both
Yes/No
Yes/No
Yes/No
** Check the availability & functional healthiness.
Note:
a) The control system hierarchy in Sl. No. 2 shall be as follows:
(A)Bipole Control;
(B) Pole Control;
(C)Converter Control;
(D)Valve Control;
(E) VDCOL;
b) The HVDC Bipole shall have control features including but not limited to the
following:
(A)Reactive Power Controller;
-
7/29/2019 Check List for Protection Audit (1)
14/14
(B) Current & Power Controller;
(C)Frequency Controller;
(D)Power Modulator, Pole Power Compensation;
(E) Sub-Synchronous Resonance Damping Controller;
(F) Load Frequency Controller;
(G)Current Margin Controller;
(H)Excessive reactive power consumption Controller;
(I) AC system stability function, such as power swing damping function;
(J) NGH damping;
c) Sl No.8(vi) not required for back to back schemes;