chapter 7 matrix converter as a multilevel...

22
132 CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL INVERTER FOR DSTATCOM APPLICATION 7.1 INTRODUCTION The traditional way of maintaining power quality in a power system is to use banks of inductors and capacitors. Due to the development of technology, fast acting voltage source and current source converters based compensating devices have replaced the inductor and capacitor banks. The converter-based devices operate very fast but have high switching losses due to a number of power electronic switches in them. One such converter-based compensator in the transmission level is the STATCOM and in the distribution level is the DSTATCOM. In general, a DSTATCOM uses a two-level VSCs. The literature reports that the Total Harmonic Distortion (THD) of the two-level inverter’s output current is more than that of three- level inverter or the multilevel inverter (Rodriguez et al 2002, Yu et al 2004, Munoz et al 2010 and Zaveri et al 2012). For reducing the THD, some researchers have proposed multilevel inverters like diode-clamped multilevel inverters and cascaded multilevel inverters for the DSTATCOM application (Wen et al 2007, Sirisukprasert 2004 and Munoz et al 2012). Although the multilevel inverter reduces the THD as compared to the two level inverters, it requires complicated switching algorithms and has capacitor voltage balancing problems and increased switching losses. In this thesis, the Matrix Converter (MC) is used as a multilevel inverter for the DSTATCOM

Upload: vukiet

Post on 15-May-2018

231 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL …shodhganga.inflibnet.ac.in/bitstream/10603/49376/12/12_chapter7.pdf · 132 CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL INVERTER FOR DSTATCOM

132

CHAPTER 7

MATRIX CONVERTER AS A MULTILEVEL INVERTER

FOR DSTATCOM APPLICATION

7.1 INTRODUCTION

The traditional way of maintaining power quality in a power system

is to use banks of inductors and capacitors. Due to the development of

technology, fast acting voltage source and current source converters based

compensating devices have replaced the inductor and capacitor banks. The

converter-based devices operate very fast but have high switching losses due

to a number of power electronic switches in them. One such converter-based

compensator in the transmission level is the STATCOM and in the

distribution level is the DSTATCOM. In general, a DSTATCOM uses a

two-level VSCs. The literature reports that the Total Harmonic Distortion

(THD) of the two-level inverter’s output current is more than that of three-

level inverter or the multilevel inverter (Rodriguez et al 2002, Yu et al 2004,

Munoz et al 2010 and Zaveri et al 2012). For reducing the THD, some

researchers have proposed multilevel inverters like diode-clamped multilevel

inverters and cascaded multilevel inverters for the DSTATCOM application

(Wen et al 2007, Sirisukprasert 2004 and Munoz et al 2012). Although the

multilevel inverter reduces the THD as compared to the two level inverters, it

requires complicated switching algorithms and has capacitor voltage

balancing problems and increased switching losses. In this thesis, the Matrix

Converter (MC) is used as a multilevel inverter for the DSTATCOM

Page 2: CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL …shodhganga.inflibnet.ac.in/bitstream/10603/49376/12/12_chapter7.pdf · 132 CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL INVERTER FOR DSTATCOM

133

application. The MC is an AC-to-AC converter, which has low-complexity

switching scheme. This chapter investigates the matrix converter based

DSTATCOM for reactive power compensation in the MATLAB /

SIMULINK environment.

7.2 PROBLEM FORMULATION

A DSTATCOM is a fast acting shunt connected custom power

device used in the distribution system. The VSC or current source converter is

the important element in it. For high-voltage distribution system, the

DSTATCOMs are designed using a two-level VSC and the transformer at the

output side to meet the desired voltage profile. For high power application,

the VSCs are connected in parallel to the DC bus. This type of connection

requires a transformer with multiple secondary windings, which increases the

complexity of the power system. Further, the transformer increases the overall

cost and losses in the system and may saturate when the load draws any DC

current. The efficiency of the system is also low due to the increased

switching losses. Generally, the use of a two-level inverter requires a filter

circuit for reducing the THD at the output.

The use of multilevel inverters like the diode-clamped, the

cascaded and the flying capacitor types reduces the THD at the output without

the use of bulk filters. The flexibility of the multilevel inverter is improved by

increasing the number of possible operating states; consequently, all the

devices are controlled individually. Use of a multilevel inverter reduces the

transformer voltage ratio and it may be possible to connect the DSTATCOM

directly to a higher voltage system. When the diode-clamped multilevel

inverter is used for the DSTATCOM application, it gives rise to capacitor

unbalancing problem. In addition, it requires a clamping diode to clamp the

voltage across the switches (Sirisukprasert 2004, Xu et al 2008). When a

cascaded multilevel inverter is used with a single DC-link capacitor for the

Page 3: CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL …shodhganga.inflibnet.ac.in/bitstream/10603/49376/12/12_chapter7.pdf · 132 CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL INVERTER FOR DSTATCOM

134

DSTATCOM application, a transformer is required for connecting the

cascaded inverter structure to the distribution systems. Alternatively, a

separate cascaded multilevel inverter module with separate DC-link

capacitors for each phase can be used without the transformer. However, this

arrangement requires a complex DC-link voltage regulation loop whose

complexity increases with the increase in the number of H-bridge modules.

Further, connecting separate DC sources between the two converters in a

back-to-back arrangement such as in the UPFC and the UPQC is not possible

as a short-circuit occurs when the two back-to-back converters are not

switched ON. In addition to the reactive power exchange, the power pulsation

takes place at twice the output frequency for each H-bridge inverter. This

necessitates the over-sizing of the DC-link capacitors (Peng et al 1998 &

Shukla et al 2007). On the other hand, the use of a flying capacitor multilevel

inverter requires the simplest DC-link voltage regulation loop as compared to

other multilevel inverters. Further, it does not require a number of isolated

power supplies as required in the case of the cascaded H-bridge multilevel

inverters. Its DC-link capacitor control loop is as simple as the conventional

two-level inverter and is independent of the number of output voltage levels.

The main limitation of the flying capacitor multilevel inverter is that it

requires a large number of capacitors and the control is inefficient. To make

voltage control more efficient a simple DC-link is used (Shukla et al 2005,

Shukla et al 2007). However, multilevel inverter topologies for the

DSTATCOM applications require more number of switches, which increases

the switching losses and complexity of the switching algorithm.

To overcome these drawbacks in the multilevel inverter, a matrix

converter based DSTATCOM is proposed. The performance of this

DSTATCOM is studied for a simple switching algorithm. The HCC switching

algorithm is used in which the number of switches conducting at any time is

Page 4: CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL …shodhganga.inflibnet.ac.in/bitstream/10603/49376/12/12_chapter7.pdf · 132 CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL INVERTER FOR DSTATCOM

135

three and is less than the number of switches conducting at any time in a

multilevel inverter.

7.3 SYSTEM CONFIGURATION USING MATRIX

CONVERTER TOPOLOGY

Figure 7.1 shows the single line diagram of a DSTATCOM using

the matrix converter as a multilevel inverter.

Figure 7.1 Single line diagram of the DSTATCOM using the matrix converter as the multilevel inverter

The matrix converter topology for the three-level operation uses 18

switches whereas the diode clamped and the cascaded multilevel inverters for

the same level require 12 switches. However, the number of switches

conducting at any point of time in the matrix converter is less than the number

of switches conducting in the multilevel inverter. Thus, the matrix converter

as a multilevel inverter has reduced switching losses. It is also to be noted that

two capacitors are used in this type of inverter topology to achieve the three-

level of operation. It is a challenge to balance the voltage across these two

C1

Matrix Converter as Multilevel Inverter

Line Vs

LOAD1

LOAD2

C2

Bus

SW

Page 5: CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL …shodhganga.inflibnet.ac.in/bitstream/10603/49376/12/12_chapter7.pdf · 132 CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL INVERTER FOR DSTATCOM

136

capacitors. The proposed switching strategy overcomes this challenge.

Figure 7.2 shows the matrix converter having three arms, with each arm

having three sets of back-to-back connected switches (Cha 2004).

Figure 7.2 Matrix converter

The space vector based HCC switching algorithm is used. The

DSTATCOM is connected to the grid through a coupling transformer, as in

the case of a two-level inverter based DSTATCOM. The robustness of the

DSTATCOM controller is studied for load variations.

7.4 CONVENTIONAL HCC FOR THE PROPOSED MATRIX

CONVERTER TOPOLOGY

Section 4.4 had discussed the fundamentals of the Hysteresis

Current Control (HCC) technique for a two-level inverter. To apply the

LLc

Vc

Power Circuit

C1

C2

SC1A

SC2A

SNA SNC

SC1C

SC2C

SC1B

SC2B

SNB

LLa LLb

RLa RLb

Va Vb

3-ph Load

RLc

Page 6: CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL …shodhganga.inflibnet.ac.in/bitstream/10603/49376/12/12_chapter7.pdf · 132 CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL INVERTER FOR DSTATCOM

137

conventional HCC for the proposed matrix converter topology, two hysteresis

bands are used to maintain the error in the current to lie within the band,

whereas in the two-level inverter only one band was used. The outer and inner

bandwidths are selected as and /2 respectively. If the error in current,

( = ), crosses the upper limit of the outer band, + /2, the lower

switch of the respective phase is turned ON, such that the phase is connected

to the neutral and hence the current in the phase starts decreasing. When the

error in current, , crosses the lower limit of the outer band, /2, the

upper switch of the respective phase is turned ON, such that the phase get

connected to the capacitor C1 and the current in the phase starts to build up

rapidly resulting in the slope of the error in current, , being high. If the error

in current, , crosses the upper limit of the inner band, + /4, the middle

switch of the respective phase is turned ON so that the respective phase is

connected to the capacitor C2. At this instant, only half of the total voltage is

applied to the phase and hence the slope of the error in current will be low. By

doing so, the actual current is made to follow the reference current and hence

maintain the errors within the band limits. It should be noted that at any instant

of time, only one switch is conducting in any phase.

7.5 SPACE VECTORS FOR THE PROPOSED MATRIX

CONVERTER TOPOLOGY

Figure 7.3 shows the matrix converter based DSTATCOM

connected to the grid. Equations (4.7) to (4.10), given in section 4.5, that

govern the VSC based DSTATCOM are applicable for the matrix converter

based DSTATCOM too. However, the technique for applying the switching

vectors differs from the two-level VSC based DSTATCOM.

Page 7: CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL …shodhganga.inflibnet.ac.in/bitstream/10603/49376/12/12_chapter7.pdf · 132 CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL INVERTER FOR DSTATCOM

138

Figure 7.3 Grid connected matrix converter based DSTATCOM configuration

For an N-level inverter, switching vectors are possible. Hence,

for a three-level inverter, 27 switching vectors are possible. For these

switching states, the space vector diagram will be a concentric hexagon, as

shown in Figure 7.4. It is to be noted that the outer hexagon represents 12

active switching vectors; the inner hexagon represents 12 active switching

vectors and the origin represents 3 zero vectors. When the switching vectors

from the outer hexagon are used, voltage across both the capacitors C1 and C2

are applied to the load. Hence, there is no need to balance the capacitors in

this case. In the inner hexagon, each corner represents two active vectors. If a

particular switching vector is applied from the inner hexagon, it charges one

capacitor say C1 and discharges the other capacitor say C2. To charge the

capacitor C2 and discharge capacitor C1, the other switching vector from the

same corner of the inner hexagon is applied. A reference voltage of Vdc/2 is

set for each capacitor along with a tolerance bandwidth of Vdc/2. When the

actual capacitor voltage exceeds the tolerance band limit, the other switching

vector from the same corner of the inner hexagon is applied to keep the

capacitor voltage within the tolerance band. This technique helps in balancing

the capacitor voltages.

ica

icb

icc

Lf

Lf

LfRf

Rf

Rf

isa isb isc

vsa

vsc

vsb

iLa iLb iLc

C1

C2

MATRIX CONVERTER GRID

A

B

C

Page 8: CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL …shodhganga.inflibnet.ac.in/bitstream/10603/49376/12/12_chapter7.pdf · 132 CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL INVERTER FOR DSTATCOM

139

Figure 7.4 Space vector diagram for the matrix converter

7.6 SPACE VECTORS BASED HCC FOR THE MATRIX

CONVERTER BASED DSTATCOM

When the conventional method of hysteresis current control is used,

each phase of the inverter leg is controlled independently and hence the

switching frequency of the inverter goes abnormally high, which is not

desirable. Hence, in this section, a new vector based HCC is proposed to

overcome the problem of high switching frequency. If the actual current

crosses the tolerance region along a particular axis, a vector with an opposite

component along the same axis is applied, so that the actual current is brought

back into the tolerance region. Figure 7.5 shows the error region represented

in the frame around the actual current. For instance, if the actual current

hits the tolerance region on the top side (or bottom side), a vector with smaller

(or larger) component is applied, thus bringing back the actual current into

the tolerance region and maintaining a minimum slope in current error.

Similarly, if the actual current hits the tolerance region on the right (or left)

side, a vector with larger (or smaller) component is applied. In the

remaining cases, zero vectors are applied to reduce the switching losses.

( )

( )

( )

V(2)

V(2)

V(2)

V(2)

Page 9: CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL …shodhganga.inflibnet.ac.in/bitstream/10603/49376/12/12_chapter7.pdf · 132 CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL INVERTER FOR DSTATCOM

140

Figure 7.5 Error regions in the frame

It can be observed from Figure 7.6 that there are nine discrete levels

along the -axis and five discrete levels along the -axis. Hence, to identify

the region of the error in the current vector, an eight-level hysteresis

comparator HC in the -axis and a four level hysteresis comparator HC in

the -axis are used. Based on the output of the comparators HC and HC ,

optimal switching vectors are selected, as shown in Table 7.1. The switching

states corresponding to these vectors are given in Appendix 4. Figure 7.7a

shows the five discrete levels along the -axis and Figure 7.7b shows the

implementation of four level hysteresis comparator in the -axis. In the same

way, the eight-level hysteresis comparator is implemented along the -axis.

iref io

ie

BW

/6

BW

/3

Page 10: CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL …shodhganga.inflibnet.ac.in/bitstream/10603/49376/12/12_chapter7.pdf · 132 CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL INVERTER FOR DSTATCOM

141

Figure 7.6 Discrete levels in the frames

Table 7.1 Selection of the switching vectors based on the output of the comparators

DD 0 1 2 3 4

0 17 16 13 12 91 17 16 13 12 92 17 16 14,15 12 93 20 18,19 14,15 10,11 8 4 20 18,19 25,26,27 10,11 8 5 20 22,23 25,26,27 6,7 86 21 22,23 2,3 6,7 57 21 24 1 4 58 21 24 1 4 5

D =1 D =2 D =3 D =4 D =5 D =6 D =7 D =8

D =3

D =2

D =1

D =0

D =4

D =0

Page 11: CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL …shodhganga.inflibnet.ac.in/bitstream/10603/49376/12/12_chapter7.pdf · 132 CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL INVERTER FOR DSTATCOM

142

(a) Five discrete levels in the -axis

(b) Four hysteresis comparators in the -axis

Figure 7.7 Implementation of the hysteresis comparator in the -axis

The switching vectors are chosen such that the applied vector is

nearer to the error in current. Hence, as per Equation (7.1), which is derived

from Equation (4.15), the slope of the error in the current vector will be

minimized.

= (7.1)

10

23

4

{ }

1

2

3

401

01

01

01

D{ }

1 > 2 > 3 > 4

Page 12: CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL …shodhganga.inflibnet.ac.in/bitstream/10603/49376/12/12_chapter7.pdf · 132 CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL INVERTER FOR DSTATCOM

143

It should be noted that a small change in the error in current vector,

, is maintained to follow the reference current to achieve the minimum

switching frequency and hence reduce the losses. An optimal bandwidth is

selected considering the switching frequency and ripple in the output current.

The use of the matrix converter as a three-level inverter for

DSTATCOM application has many advantages. In the case of a two-level

inverter, if the reference voltage vector, Vn*, is in a particular sector, two

active vectors and one zero vector are to be used to bring the error in current

back to the tolerance region. In such a case, when the switching changes from

the active vector to the zero vector, a voltage stress of (Vdc – 0) is experienced

by the switch. However, in the case of a three-level inverter, if the reference

voltage vector Vn* is in a particular sector say sector I (S-I) as shown in

Figure 7.8, two active vectors of length Vdc, one active vector of length 3/2

Vdc from the outer hexagon and two active vectors of length Vdc/2 from the

inner hexagon and one zero vector out of the three zero vectors are used to

bring the error in the current back to the tolerance region. When the switching

state varies from the outer hexagon vector to the zero vector, a voltage stress

of ( 0) and ( 32 0)are experienced by the switches. When the

switching state varies from the inner hexagon vector to the zero vector, a

voltage stress of ( /2 0) is experienced by the switches. When the

switching state varies from the outer hexagon vector to the inner hexagon

vector, a voltage stress of ( 2 ) and ( 32 2) are

experienced by the switches. When the switching state varies from one outer

hexagon vector to another outer hexagon vector, a voltage stress of

( 32 ) is experienced by the switches.

Page 13: CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL …shodhganga.inflibnet.ac.in/bitstream/10603/49376/12/12_chapter7.pdf · 132 CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL INVERTER FOR DSTATCOM

144

Figure 7.8 Magnitude of the voltage vectors in sector I

Hence, except for the first change in the magnitude, all other

changes in the magnitude of the voltages are considerably less when

compared to a two-level inverter. The zero vector V0A (AAA) is chosen if the

previous active vector is any one of the vectors AAB, AAC, CAA, BAA,

ABA, ACA; zero vector V0B (BBB) is chosen if the previous active vector is

any one of the vectors ABB, BBC, BAB, CBB, BBA, BCB; zero vector V0C

(CCC) is chosen if the previous active vector is any one of the vectors BCC,

ACC, CBC, CAC, CCB, CCA.

7.7 SIMULATION STUDIES

The performance of the matrix converter based DSTATCOM for

load variation is studied with MATLAB simulation. The system consists of a

distribution bus modeled as a Thevinin’s equivalent voltage source, two RL

loads and a DSTATCOM. Load 1 is connected to the system permanently

whereas Load 2 is removed from the system at time t = 1 s and again

connected to the system at time t = 2 s. As both the loads are of RL type, the

system requires both real and reactive powers. When the DSTATCOM is

( )

( )

( )

Vdc/2

Vdc/2

Vdc

Vdc

3/2 Vdc

S-I

Page 14: CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL …shodhganga.inflibnet.ac.in/bitstream/10603/49376/12/12_chapter7.pdf · 132 CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL INVERTER FOR DSTATCOM

145

used, the source supplies only the real power to the load and the DSTATCOM

supplies the reactive power to the load. If the load draws the reactive power

from the source in addition to the real power, the source has to supply more

reactive component of current, which reduces the power factor on the source

side. To overcome this issue, the matrix converter based DSTATCOM is used

to supply the reactive power to the load and its performance is studied in

simulation for the above said load variation.

Figures 7.9 to 7.21 show the simulation results. Figure 7.9 shows

the real and reactive power supplied by the DSTATCOM. It is noted that the

DSTATCOM supplies only reactive power of 5 kVAR from the time t = 1 s to

t = 2 s and the rest of the time it supplies reactive power of 10 kVAR.

Figure 7.10 shows the real and reactive power supplied by the source. It is

clear that the source does not supply any reactive power to the system.

However, it supplies the real power of 15 kW when both the loads are

connected to the system and supplies the real power of 1 kW when only the

Load-1 is connected to the system. As the source supplies the entire real

power to the load, its current is in phase with its voltage, as shown in Figure

7.11. For a clearer view, Figure 7.12 shows the variation of source voltage

and current for a reduced time scale. As the source supplies the load active

power, the DSTATCOM should supply the load reactive power. Figure 7.13

shows the reactive power requirement of the load and the reactive power

supplied by the DSTATCOM. It is found that the load demand of reactive

power is fully supplied by the DSTATCOM. When the DSTATCOM

supplies the reactive power to the load, it injects the current in quadrature

with its voltage, as shown in Figure 7.14. Figures 7.15 and 7.16 respectively

show the variations of the phase A current in the DSTATCOM and in the

source. Figure 7.17 shows the variations of the three-phase voltages and

currents of the DSTATCOM. For improved visibility, the time scale is

reduced in Figure 7.18 for observing the variations of the three-phase voltages

Page 15: CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL …shodhganga.inflibnet.ac.in/bitstream/10603/49376/12/12_chapter7.pdf · 132 CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL INVERTER FOR DSTATCOM

146

and currents of the DSTATCOM. When the DSTATCOM is operated to

exchange only the reactive power with the system, its DC bus voltage should

be maintained constant. Figure 7.19 shows that the actual DC bus (made up of

two capacitors) voltage (Vdc) follows the reference voltage Vdc Ref = 1300 V

and hence the DC bus voltage is constant. This is achieved by maintaining

each capacitor voltage at its reference voltage of 650 V. Figures 7.20 and 7.21

show the variation of the voltage across the capacitors C1 and C2 respectively.

Hence, the space vector based HCC for the matrix converter based

DSTATCOM achieves its control objective.

Table 7.2 Simulation parameters for the matrix converter based DSTATCOM

Line voltage (V) 400

Source Resistance ( ) 0.01

Source Inductance (mH) 3

VSC Filter Inductance (mH) 5

Load-1 ( ) 1 + j34.55

Load-2 ( ) 10+ j3.14

Capacitance of DC Capacitors (C1, C2) (µF) 330

DC Capacitor Reference Voltage (V) 1300

Eight-level Hysteresis Comparator

1 0.02

2 0.04

3 0.06

4 0.08

5 0.10

6 0.12

7 0.14

8 0.16

Page 16: CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL …shodhganga.inflibnet.ac.in/bitstream/10603/49376/12/12_chapter7.pdf · 132 CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL INVERTER FOR DSTATCOM

147

Figure 7.9 Real and reactive powers supplied by the DSTATCOM

Figure 7.10 Real and reactive powers supplied by the source

0 0.5 1 1.5 2 2.5 3-2

-1.5

-1

-0.5

0

0.5

1

1.5x 10

4

Time (S)

P

Q

0 0.5 1 1.5 2 2.5 3-0.5

0

0.5

1

1.5

2

2.5

3

3.5x 10

4

Time (S)

P source

Q sourcs

Page 17: CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL …shodhganga.inflibnet.ac.in/bitstream/10603/49376/12/12_chapter7.pdf · 132 CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL INVERTER FOR DSTATCOM

148

Figure 7.11 Source voltage and current variations

Figure 7.12 Source voltage and current variations with reduced time

scale

0 0.5 1 1.5 2 2.5 3-400

-300

-200

-100

0

100

200

300

400

Time (S)

V source

I source

0.8 0.85 0.9 0.95 1 1.05 1.1

-300

-200

-100

0

100

200

300

Time (S)

I source

V source

Page 18: CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL …shodhganga.inflibnet.ac.in/bitstream/10603/49376/12/12_chapter7.pdf · 132 CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL INVERTER FOR DSTATCOM

149

Figure 7.13 Reactive power variation of the load and the DSTATCOM

Figure 7.14 Voltage and current variations of the DSTATCOM

0 0.5 1 1.5 2 2.5 3-1.5

-1

-0.5

0

0.5

1

1.5

2 x 104

Time (S)

Q L = QS

0.8 0.85 0.9 0.95 1 1.05 1.1 1.15 1.2

-300

-200

-100

0

100

200

300

Time (S)

I dstatcom

V dstatcom

Page 19: CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL …shodhganga.inflibnet.ac.in/bitstream/10603/49376/12/12_chapter7.pdf · 132 CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL INVERTER FOR DSTATCOM

150

Figure 7.15 Current variation in phase A of the DSTATCOM

Figure 7.16 Variation of the source current in phase A

0 0.5 1 1.5 2 2.5 3-40

-30

-20

-10

0

10

20

30

Time (S)

0 0.5 1 1.5 2 2.5 3-60

-40

-20

0

20

40

60

80

Time (S)

Page 20: CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL …shodhganga.inflibnet.ac.in/bitstream/10603/49376/12/12_chapter7.pdf · 132 CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL INVERTER FOR DSTATCOM

151

Figure 7.17 Three-phase voltage and current variations in the DSTATCOM

Figure 7.18 Three-phase voltage and current variations in the DSTATCOM with reduced time scale

1 1.2 1.4 1.6 1.8 2 2.2-400

-300

-200

-100

0

100

200

300

400

Time (S)

Iabc dstatcom Vabc dsta tcom

0.8 0.85 0.9 0.95 1 1.05 1.1

-300

-200

-100

0

100

200

300

Time (S)

Vabc dstatcomIabc dstatcom

Page 21: CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL …shodhganga.inflibnet.ac.in/bitstream/10603/49376/12/12_chapter7.pdf · 132 CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL INVERTER FOR DSTATCOM

152

Figure 7.19 DC bus (Vdc1+Vdc2) voltage

Figure 7.20 DC Capacitor-1 voltage

0 0.5 1 1.5 2 2.5 3-200

0

200

400

600

800

1000

1200

1400

1600

Time (s)

Vdc Ref

Vdc

0 0.5 1 1.5 2 2.5 3-100

0

100

200

300

400

500

600

700

800

Time (s)

Vdc1 Ref Vdc1

Page 22: CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL …shodhganga.inflibnet.ac.in/bitstream/10603/49376/12/12_chapter7.pdf · 132 CHAPTER 7 MATRIX CONVERTER AS A MULTILEVEL INVERTER FOR DSTATCOM

153

Figure 7.21 DC Capacitor-2 voltage

7.8 SUMMARY

In this chapter, a new converter topology with the matrix converter

is proposed for the DSTATCOM. This matrix converter is operated as a

multilevel inverter and is used in the DSTATCOM application instead of the

two-level VSC. The SVM based hysteresis current control scheme is

proposed for the matrix converter based DSTATCOM operating in reactive

power compensation mode. In this method, the switching vectors are selected

based on the output from the multilevel hysteresis comparators. Hence, for

any sector, five non-zero active vectors and a zero vector adjacent to the

reference vector are utilized. The non-zero vectors limit the error in the

current to lie within the error band. The zero vectors reduce the rate of change

of error in the current vector. This technique results in reduced stress on the

switches when compared to the two-level inverter. The SVM based HCC

results in faster transient response. The control scheme for power quality

improvement is robust especially for reactive power compensation.

0 0.5 1 1.5 2 2.5 3-100

0

100

200

300

400

500

600

700

800

Time (s)

Vdc2 Ref Vdc2