CHAPTER
4 Wiring Systems
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Objectives
• Know where to find codes and authorities for an installation.
• Recognize the marks of the most popular testing agencies.
• List the different conductor systems used in residential and light commercial wiring.
• Explain the basics of conduit bending.• Become familiar with the many different
types of raceway systems.
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
National Electrical Code (NEC)
• Rules, regulations, and criteria for installation of electrical equipment
• Revised every three years• Compliance typically mandated by state or
local building codes• “Authority having jurisdiction”—person
responsible for approving electrical installations
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Code Alert
• Article 90 defines what is and is not covered by the NEC
• Article 100 provides definitions of essential terms used throughout the NEC
• Article 110 provides general requirements for electrical installations
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
State and Local Codes
• All electrical construction governed by state or local building codes
• Be aware of specific codes based on location and type of construction
• Codes generally require– Licensing– Permits– Inspection/approval
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Additional Organizations
• Nationally recognized testing laboratories– Test materials and equipment– Underwriters Laboratories
• Occupational Safety and Health Administration (OSHA)– Agency of US federal government– Required safe practices
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Wiring Systems
• Wiring system—Wiring and related components used in an electrical system
• Two primary classifications:– Cables– Raceways
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Armored Cable (AC)
• Also called “BX”• Components:
– Armor (outer covering)– Insulated conductors– Bonding strip (for equipment grounding
system)
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Armored Cable (AC) (cont.)
• Requires anti-short bushings to protect conductors from sharp edges of armor
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Armored Cable Connectors
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Nonmetallic Sheathed Cable (NM)• Also called “Romex”
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Stripping Nonmetallic Sheathed Cable
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Service Entrance Cable (SE)
• Service Entrance Cable (SE)– Overhead cable– Connects utility company transformer to home’s
service panel
• Underground service entrance cable (USE)– Below-grade service connections
• Underground feeder and branch-circuit cable (UF)– Similar to NM but designed for below-grade use
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Code Alert
Typical requirements for cable support• Cable must be supported within 12 of a box• Maximum distance between cable supports is
4-6• Always check support requirements for
specific cable type being used
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Raceways
• Protective tubing installed to house conductors
• Conduit—tubing connecting boxes and devices in a wiring system
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Common Raceway Systems• Electrical metallic tubing (EMT)• Electrical nonmetallic tubing (ENT)• Rigid metal conduit (RMC)• Rigid PVC conduit (PVC)• Intermediate metal conduit (IMC)• Flexible metal conduit (FMC)• Liquidtight flexible metal conduit (LFMC)• Surface-mount raceways
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Electrical Metallic Tubing (EMT)
• Also called “thin-wall” conduit• Not threaded• Tubing serves as equipment grounding
conductor—proper connections are critical
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
EMT Connections
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Cutting Metal Conduit
• Cutting tools:– Hacksaw– Reciprocating saw– Pipe cutter
• After cutting, use reamer, file, or deburring tool to eliminate sharp edges
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Bending Metal Conduit
• Field bend—Conduit bend made on the construction site
• Generally, bending is easier and less costly than using fitting
• Always use the correct size conduit bender• Always know the minimum bend radius
allowed by code
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Stub Bend
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Back-to-Back Bend
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Offset Bend
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Offset Bend (cont.)
Preparation1. Measure distance to obstruction2. Measure height of obstruction3. Use offset bend chart to determine
• Angle of offset• Distance between bends• Shrink
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Offset Bend (cont.)
Marking conduit1. Add shrink to the distance to the
obstruction, and mark conduit at this distance
2. Measure back the distance between bends
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Offset Bend (cont.)
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Box Offset
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Saddle Bend• Two 22 1/2 bends and one 45 bend• Preparation
1. Measure height of obstruction2. Find distance from start of conduit to
center of obstruction, then add 3/16 for every inch of obstruction height (for 1/2 conduit). Mark this location (center of bend)
3. On each side of center mark, measure and mark a distance equal to 2 1/2 times the height of the obstruction
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Saddle Bend (cont.)
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Electrical Nonmetallic Tubing (ENT)• Often called “smurf tube” or “smurf”• Corrugated, flexible plastic• Easy to install• Cannot be buried or left exposed
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Rigid Metal Conduit (RMC)
• Galvanized pipe, similar to water pipe• Threaded connectors and fittings• Conduit part of equipment grounding
system• RMC has thicker walls than EMT has
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
RMC Connectors and Fittings
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Rigid PVC Conduit (PVC)
• Hard plastic conduit• Lighter than metal conduit• Can be heated and bent• Conduit joined to fittings with glue
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
PVC Connections
Permission granted to reproduce for educational use only.© Goodheart-Willcox Co., Inc.
Other Raceway Systems
• Intermediate metal conduit (IMC)– Walls thicker than EMT and thinner than
RMC• Flexible metal conduit (FMC)
– Also called “Greenfield”– Similar to armored cable casing
• Liquidtight Flexible Metal Conduit (LFMC)– Similar to FMC with a plastic sheath
• Surface-mount raceways