ch 11 - generator protection

Upload: sotany

Post on 10-Apr-2018

213 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/8/2019 Ch 11 - Generator Protection

    1/71

    GENERATOR CONTROL AND PROTECTION

    Generator Protection

  • 8/8/2019 Ch 11 - Generator Protection

    2/71

    GENERATOR CONTROL AND PROTECTION

    Generator Protection Introduction

    Device Numbers Symmetrical Components

    Fault Current Behavior

    Generator Grounding

    Stator Phase Fault (87G)

    Field Ground Fault (64F)

    Stator Ground Fault (87N, 51N, 59N, 27-3N)

  • 8/8/2019 Ch 11 - Generator Protection

    3/71

    GENERATOR CONTROL AND PROTECTION

    Generator Protection Loss of Field (40Q, 40Z)

    Over/Under Frequency (81O/81U)

    Overexcitation and Overvoltage (24, 59)

    Out of Step (78)

    Negative Sequence (Current Unbalance) (46)

    Inadvertent Energization (27, 50, 60, 81, 62, 86) Loss of Voltage Transformer (60)

    System Backup (51V, 21)

    Conclusion

  • 8/8/2019 Ch 11 - Generator Protection

    4/71

    GENERATOR CONTROL AND PROTECTION

    Generator Protection

    G

    64F

    60

    51N

    87T24

    81U

    47

    2762

    87G

    59 81O

    32-1

    59N

    51-GN

    32-2

    27-3N

    40 51V50

    EI46

    6349

    REG

    51

    51

    25

  • 8/8/2019 Ch 11 - Generator Protection

    5/71

    GENERATOR CONTROL AND PROTECTION

    Steam Generator Stator Windings

  • 8/8/2019 Ch 11 - Generator Protection

    6/71

    GENERATOR CONTROL AND PROTECTION

    Hydraulic Generator Stator / Rotor

  • 8/8/2019 Ch 11 - Generator Protection

    7/71

    GENERATOR CONTROL AND PROTECTION

    Hydraulic Generator Stator Core

  • 8/8/2019 Ch 11 - Generator Protection

    8/71

    GENERATOR CONTROL AND PROTECTION

    Generator Protection

  • 8/8/2019 Ch 11 - Generator Protection

    9/71

    GENERATOR CONTROL AND PROTECTION

    Split Phase Relaying CT

  • 8/8/2019 Ch 11 - Generator Protection

    10/71

    GENERATOR CONTROL AND PROTECTION

    Cylindrical Rotor in Need of Repair

  • 8/8/2019 Ch 11 - Generator Protection

    11/71

    GENERATOR CONTROL AND PROTECTION

    Generator Protection

  • 8/8/2019 Ch 11 - Generator Protection

    12/71

    GENERATOR CONTROL AND PROTECTION

    Generator Protection

  • 8/8/2019 Ch 11 - Generator Protection

    13/71

    GENERATOR CONTROL AND PROTECTION

    Symmetrical Components Positive Sequence

    A set of three phasors that have the same magnitude, are equally

    displaced from each other by 120, and have the same phasesequence as the system under study (ex ABC)

    Negative Sequence A set of three phasors that have the same magnitude, are equally

    displaced from each other by 120, and have the opposite phasesequence as the system under study (ex ACB)

    Zero Sequence A set of three phasors of equal magnitude that are all in phase or

    have zero displacement from each other

  • 8/8/2019 Ch 11 - Generator Protection

    14/71

  • 8/8/2019 Ch 11 - Generator Protection

    15/71

    GENERATOR CONTROL AND PROTECTION

    Symmetrical Components

  • 8/8/2019 Ch 11 - Generator Protection

    16/71

    GENERATOR CONTROL AND PROTECTION

    Symmetrical Components

  • 8/8/2019 Ch 11 - Generator Protection

    17/71

    GENERATOR CONTROL AND PROTECTION

    Symmetrical Components

  • 8/8/2019 Ch 11 - Generator Protection

    18/71

    GENERATOR CONTROL AND PROTECTION

    Symmetrical Components

  • 8/8/2019 Ch 11 - Generator Protection

    19/71

    GENERATOR CONTROL AND PROTECTION

    Symmetrical ComponentsExample Problem

    One conductor of a three phase line is

    open. The current flowing to the delta

    connected load thru line a is 10A. With

    the current in linea

    as reference andassuming that line c is open, find the

    symmetrical components of the line

    currents.

  • 8/8/2019 Ch 11 - Generator Protection

    20/71

    GENERATOR CONTROL AND PROTECTION

    Symmetrical ComponentsExample Problem

    Ia = 10/0 A, Ib = 10/180 A, Ic = 0 A

    Ia0

    = (1/3)(Ia

    + Ib

    + Ic

    )

    Ia0 = (1/3)(10/0 + 10/180 + 0) = 0

    Ia1 = (1/3)(Ia + Ib + 2 Ic )

    Ia1 = (1/3)(10/0 + 10/180+120 + 0)

    Ia1 = 5.78 /-30 Ia2 = (1/3)(Ia +

    2 Ib + Ic )

    Ia2 = (1/3)(10/0 + 10/180+240 + 0)

    Ia2 = 5.78 /30

  • 8/8/2019 Ch 11 - Generator Protection

    21/71

    GENERATOR CONTROL AND PROTECTION

    Symmetrical ComponentsExample Problem

    Ib0 = 0

    Ib1 = 5.78 /-150

    Ib2 = 5.78 /150

    Ic0 = 0

    Ic1 = 5.78 /90

    Ic2 = 5.78 /-90

  • 8/8/2019 Ch 11 - Generator Protection

    22/71

  • 8/8/2019 Ch 11 - Generator Protection

    23/71

    GENERATOR CONTROL AND PROTECTION

    Symmetrical ComponentsExample Problem

    Note: the components Ic1 and Ic2 have

    definite values although line c is open and

    can carry no net current. As expected, the

    sum of these currents is zero.

    The sum of the currents in line a is 10/0

    The sum of the currents in line b is 10/180

  • 8/8/2019 Ch 11 - Generator Protection

    24/71

    GENERATOR CONTROL AND PROTECTION

    Symmetrical Components

    Single Phase Line to Ground Fault

  • 8/8/2019 Ch 11 - Generator Protection

    25/71

    GENERATOR CONTROL AND PROTECTION

    Symmetrical Components

    Generator Sequence Networks

  • 8/8/2019 Ch 11 - Generator Protection

    26/71

    GENERATOR CONTROL AND PROTECTION

    Symmetrical Components

  • 8/8/2019 Ch 11 - Generator Protection

    27/71

    GENERATOR CONTROL AND PROTECTION

    Symmetrical Components

  • 8/8/2019 Ch 11 - Generator Protection

    28/71

    GENERATOR CONTROL AND PROTECTION

    Symmetrical Components

  • 8/8/2019 Ch 11 - Generator Protection

    29/71

    GENERATOR CONTROL AND PROTECTION

    Fault Current Behavior of a

    Synchronous Generator

  • 8/8/2019 Ch 11 - Generator Protection

    30/71

    GENERATOR CONTROL AND PROTECTION

    Fault Current Behavior of a

    Synchronous Generator

  • 8/8/2019 Ch 11 - Generator Protection

    31/71

    GENERATOR CONTROL AND PROTECTION

    Fault Current Behavior of a

    Synchronous Generator

  • 8/8/2019 Ch 11 - Generator Protection

    32/71

    GENERATOR CONTROL AND PROTECTION

    Fault Current Behavior of a

    Synchronous Generator

    Max DC Offset

    No DC Offset

  • 8/8/2019 Ch 11 - Generator Protection

    33/71

    GENERATOR CONTROL AND PROTECTION

    Fault Current Behavior of a

    Synchronous Generator

  • 8/8/2019 Ch 11 - Generator Protection

    34/71

    GENERATOR CONTROL AND PROTECTION

    Fault Current Behavior of a

    Synchronous Generator

  • 8/8/2019 Ch 11 - Generator Protection

    35/71

    GENERATOR CONTROL AND PROTECTION

    Generator Grounding

  • 8/8/2019 Ch 11 - Generator Protection

    36/71

    GENERATOR CONTROL AND PROTECTION

    Generator Grounding

    Low Impedance Grounding

    Single phase to ground fault current between 200A and 150%

    High Impedance Grounding

    Single phase to ground fault current between 5 and 20A

  • 8/8/2019 Ch 11 - Generator Protection

    37/71

    GENERATOR CONTROL AND PROTECTION

    Generator Stator Phase Fault

    Protection (87G)

  • 8/8/2019 Ch 11 - Generator Protection

    38/71

    GENERATOR CONTROL AND PROTECTION

    Generator Stator Phase Fault

    Protection (87G)

    87G used to protect for:

    3 phase line to line1 phase line to line

    multi-phase line to ground

    May not be able to detect a 1 phase to ground fault on high

    impedance grounded generatorsRestraint or Percentage Differential Trip Characteristic

    Used to improve sensitivity for detecting small levels of

    fault current

    Also maintains security against inadvertent tripping due

    to thru faults

  • 8/8/2019 Ch 11 - Generator Protection

    39/71

    GENERATOR CONTROL AND PROTECTION

    Generator Stator Phase Fault

    Protection (87G)

  • 8/8/2019 Ch 11 - Generator Protection

    40/71

    GENERATOR CONTROL AND PROTECTION

    Generator Stator Phase Fault

    Protection (87G)

  • 8/8/2019 Ch 11 - Generator Protection

    41/71

    GENERATOR CONTROL AND PROTECTION

    Generator Stator Phase Fault

    Protection (87G)

    Split-phase protection scheme

    Able to detect turn-turn faultsWindings for each phase split into equal groups

    Individual winding currents are vector summed

    Any difference in winding current results in a output from CT

    Overcurrent relay (50/51) can be used to monitor differencecurrent

    Setting must be above any normal unbalances that may exist

  • 8/8/2019 Ch 11 - Generator Protection

    42/71

    GENERATOR CONTROL AND PROTECTION

    Generator Stator Phase Fault

    Protection (87G)

  • 8/8/2019 Ch 11 - Generator Protection

    43/71

    GENERATOR CONTROL AND PROTECTION

    Generator Field Ground Fault

    Protection (64F)

  • 8/8/2019 Ch 11 - Generator Protection

    44/71

    GENERATOR CONTROL AND PROTECTION

    Generator Stator Ground Fault

    Protection (87N, 51N, 59N & 27-3N)

    For Low Impedance Grounded Generators

  • 8/8/2019 Ch 11 - Generator Protection

    45/71

    GENERATOR CONTROL AND PROTECTION

    Generator Stator Ground Fault

    Protection (87N, 51N, 59N & 27-3N)

    For Low Impedance Grounded Generators

  • 8/8/2019 Ch 11 - Generator Protection

    46/71

    GENERATOR CONTROL AND PROTECTION

    Generator Stator Ground Fault

    Protection (87N, 51N, 59N & 27-3N)

    External Generator Phase-Ground Fault

    G S G d F l

  • 8/8/2019 Ch 11 - Generator Protection

    47/71

    GENERATOR CONTROL AND PROTECTION

    Generator Stator Ground Fault

    Protection (87N, 51N, 59N & 27-3N)

    External Generator Phase-Ground Fault

    G S G d F l

  • 8/8/2019 Ch 11 - Generator Protection

    48/71

    GENERATOR CONTROL AND PROTECTION

    Generator Stator Ground Fault

    Protection (87N, 51N, 59N & 27-3N)

    Internal Generator Phase-Ground Fault

    G t St t G d F lt

  • 8/8/2019 Ch 11 - Generator Protection

    49/71

    GENERATOR CONTROL AND PROTECTION

    Generator Stator Ground Fault

    Protection (87N, 51N, 59N & 27-3N)

    Internal Generator Phase-Ground Fault

    G t St t G d F lt

  • 8/8/2019 Ch 11 - Generator Protection

    50/71

    GENERATOR CONTROL AND PROTECTION

    Generator Stator Ground Fault

    Protection (87N, 51N, 59N & 27-3N)

    High Impedance Grounded

    50MVA, 13.2kV Generator

    Xc = 10,610 for 0.25uf @ 60Hz

    Rpri = 10,610/3 = 3537

  • 8/8/2019 Ch 11 - Generator Protection

    51/71

    GENERATOR CONTROL AND PROTECTION

    Loss of Field Protection (40Q, 40Z)

  • 8/8/2019 Ch 11 - Generator Protection

    52/71

    GENERATOR CONTROL AND PROTECTION

    Loss of Field Protection (40Q, 40Z)

  • 8/8/2019 Ch 11 - Generator Protection

    53/71

    GENERATOR CONTROL AND PROTECTION

    Loss of Field Protection (40Q, 40Z)

    Over/Under Frequency Protection

  • 8/8/2019 Ch 11 - Generator Protection

    54/71

    GENERATOR CONTROL AND PROTECTION

    Over/Under Frequency Protection

    (81O/U)

    Causes:

    Significant load additionSudden reduction in mechanical input power

    Loss of generation

    Loss of load

    Underfrequency can cause:Higher generator load currents

    Overexcitation

    Turbine blade fatigue

    Overfrequency can cause:Overvoltage on hydro turbines

    Overexcitation and Overvoltage

  • 8/8/2019 Ch 11 - Generator Protection

    55/71

    GENERATOR CONTROL AND PROTECTION

    Overexcitation and Overvoltage

    Protection (24, 59)

    Modern Excitation Systems include over excitation limiting

    and protection, but it may take several seconds to limitOverexcitation occurs when the V/Hz ratio exceeds 105% at

    FL and 110% at no load

    V/Hz relays set at 110% with a 5 10 sec delay

    Generator overvoltage can occur without exceeding V/Hzrelay setting due to large over speed on hydro generator

    Generator overvoltage relay, 59 may be used

  • 8/8/2019 Ch 11 - Generator Protection

    56/71

  • 8/8/2019 Ch 11 - Generator Protection

    57/71

    GENERATOR CONTROL AND PROTECTION

    Out of Step Protection (78)BA

    EA EB

    ZBZTZA

    Generator SystemTransformer

    +R

    +X

    -R

    EA/EB>1

    Q

    P

    EA/EB=1

    EA/EB

  • 8/8/2019 Ch 11 - Generator Protection

    58/71

    GENERATOR CONTROL AND PROTECTION

    Out of Step Protection (78)

    R

    X

    BA

    M

    B

    Element

    Pickup

    A

    Element

    Pickup

    Blinder

    Elements

    Mho

    Element

    Gen X'd

    Trans

    System

    P

  • 8/8/2019 Ch 11 - Generator Protection

    59/71

    GENERATOR CONTROL AND PROTECTION

    Negative Sequence Protection (46)

    Protects generator from excessive heating in the rotor due to

    unbalanced stator currentsNegative sequence component of stator current induces

    double frequency current in rotor, causing heating

    Rotor temperature rise proportion to I22t

    Negative sequence relays provide settings for this relationshipin the form of a constant, k = I2

    2t

    Minimum permissible continuous unbalance currents are

    specified (ANSI/IEEE C50.13)

    Inadvertent Energization Protection

  • 8/8/2019 Ch 11 - Generator Protection

    60/71

    GENERATOR CONTROL AND PROTECTION

    Inadvertent Energization Protection

    (27, 50, 60, 81U, 62 and 86)

    Protects against closing of the generator breaker while

    machine is not spinning / on turning gearCaused by operator error, breaker flash-over, control circuit

    malfunction

    Two schemes illustrated:

    Frequency supervised overcurrentVoltage supervised overcurrent

    Inadvertent Energization Protection

  • 8/8/2019 Ch 11 - Generator Protection

    61/71

    GENERATOR CONTROL AND PROTECTION

    Inadvertent Energization Protection

    Frequency Supervised Overcurrent

    G

    50

    81U

    60

    62

    81U

    60

    86

    50 (3-phase)

    86

    62

    +DC

    -DC

    0.5sec Pickup

    0.1sec Dropout

    Inadvertent Energization Protection

  • 8/8/2019 Ch 11 - Generator Protection

    62/71

    GENERATOR CONTROL AND PROTECTION

    Inadvertent Energization Protection

    Frequency Supervised Overcurrent

    Uses an underfrequency relay (81U) to enable a sensitive

    instantaneous overcurrent relay (50)

    Overcurrent relay picks up at 50% or less of expected

    inadvertent energizing current

    Frequency relay contacts must remain closed if sensingvoltage goes to zero

    Voltage balance relay (60) protects against loss of sensing

    Time delay relay (62) protects against sudden application

    of nominal voltage during inadvertent energization,allowing overcurrent to trip lockout relay (86)

    Lockout relay must be manually reset

    Inadvertent Energization Protection

  • 8/8/2019 Ch 11 - Generator Protection

    63/71

    GENERATOR CONTROL AND PROTECTION

    Inadvertent Energization Protection

    Voltage Supervised Overcurrent

    Same illustration as frequency supervised overcurrent except

    81U replaced by 27Undervoltage setpoint of 85% of the lowest expected

    emergency operating level

    Loss of Voltage Transformer

  • 8/8/2019 Ch 11 - Generator Protection

    64/71

    GENERATOR CONTROL AND PROTECTION

    V ag a

    Protection (60)

    Common practice on large systems to use two or more VTs

    One used for relays and metering

    The other used for AVR

    VTs normally fused

    Most common cause of failure is fuse failure

    Loss of VT protection blocks voltage based protective

    functions (21, 32, 40 etc)

    Loss of VT protection measure voltage unbalance, typical

    setting is 15%

    Loss of Voltage Transformer

  • 8/8/2019 Ch 11 - Generator Protection

    65/71

    GENERATOR CONTROL AND PROTECTION

    g

    Protection (60)

    G

    60

    vt

    To

    Excitation

    Controller

    To

    Protective

    Relays

  • 8/8/2019 Ch 11 - Generator Protection

    66/71

    GENERATOR CONTROL AND PROTECTION

    System Backup Protection (51V, 21)

    Common practice to provide protection for faults outside

    of the generator zone of protection

    Voltage supervised time-overcurrent (51V) or distance

    relaying (21) may be used

    Distance relay set to include generator step up transformer

    and reach beyond, into the system

    Time delays must be coordinated with those of the system

    protection to assure that system protection will operate

    before back up CTs on neutral side of generator will also provide backup

    protection for the generator

  • 8/8/2019 Ch 11 - Generator Protection

    67/71

    GENERATOR CONTROL AND PROTECTION

    System Backup Protection (51V, 21)

    G

    21

    51V

    a.) Neutral Connected ct's

  • 8/8/2019 Ch 11 - Generator Protection

    68/71

    GENERATOR CONTROL AND PROTECTION

    System Backup Protection (51V, 21)

  • 8/8/2019 Ch 11 - Generator Protection

    69/71

    GENERATOR CONTROL AND PROTECTION

    System Backup Protection (51V, 21)

    For medium and small sized generators, voltage-restrained

    or voltage controlled time overcurrent relays (51V) areoften applied

    Control or restraining function used to prevent or

    desensitize the overcurrent relay from tripping until the

    generator voltage is reduced by a fault

  • 8/8/2019 Ch 11 - Generator Protection

    70/71

    GENERATOR CONTROL AND PROTECTION

    System Backup Protection (51V, 21)

    Percent Nominal Volts25% 100%

    25%

    100%

    a.) Voltage-Restrained Overcurrent

    PercentSetValueforPickup

    Percent Nominal Volts

    Enable

    Inhibit

    b.) Voltage-Contolled Overcurrent

    Pickup

    Inhibit/Enable

    80% 100%

  • 8/8/2019 Ch 11 - Generator Protection

    71/71

    GENERATOR CONTROL AND PROTECTION

    Conclusion

    Generators must be protected from electrical faults,

    mechanical problem and adverse system conditions Some faults require immediate attention (shutdown) while

    others just require alarming or transfer to redundant

    controllers

    Design of these systems requires extensive understanding

    of generator protection

    Further study IEEE C37.102 Guide for AC Generator

    Protective Relaying