ch 11 - generator protection
TRANSCRIPT
-
8/8/2019 Ch 11 - Generator Protection
1/71
GENERATOR CONTROL AND PROTECTION
Generator Protection
-
8/8/2019 Ch 11 - Generator Protection
2/71
GENERATOR CONTROL AND PROTECTION
Generator Protection Introduction
Device Numbers Symmetrical Components
Fault Current Behavior
Generator Grounding
Stator Phase Fault (87G)
Field Ground Fault (64F)
Stator Ground Fault (87N, 51N, 59N, 27-3N)
-
8/8/2019 Ch 11 - Generator Protection
3/71
GENERATOR CONTROL AND PROTECTION
Generator Protection Loss of Field (40Q, 40Z)
Over/Under Frequency (81O/81U)
Overexcitation and Overvoltage (24, 59)
Out of Step (78)
Negative Sequence (Current Unbalance) (46)
Inadvertent Energization (27, 50, 60, 81, 62, 86) Loss of Voltage Transformer (60)
System Backup (51V, 21)
Conclusion
-
8/8/2019 Ch 11 - Generator Protection
4/71
GENERATOR CONTROL AND PROTECTION
Generator Protection
G
64F
60
51N
87T24
81U
47
2762
87G
59 81O
32-1
59N
51-GN
32-2
27-3N
40 51V50
EI46
6349
REG
51
51
25
-
8/8/2019 Ch 11 - Generator Protection
5/71
GENERATOR CONTROL AND PROTECTION
Steam Generator Stator Windings
-
8/8/2019 Ch 11 - Generator Protection
6/71
GENERATOR CONTROL AND PROTECTION
Hydraulic Generator Stator / Rotor
-
8/8/2019 Ch 11 - Generator Protection
7/71
GENERATOR CONTROL AND PROTECTION
Hydraulic Generator Stator Core
-
8/8/2019 Ch 11 - Generator Protection
8/71
GENERATOR CONTROL AND PROTECTION
Generator Protection
-
8/8/2019 Ch 11 - Generator Protection
9/71
GENERATOR CONTROL AND PROTECTION
Split Phase Relaying CT
-
8/8/2019 Ch 11 - Generator Protection
10/71
GENERATOR CONTROL AND PROTECTION
Cylindrical Rotor in Need of Repair
-
8/8/2019 Ch 11 - Generator Protection
11/71
GENERATOR CONTROL AND PROTECTION
Generator Protection
-
8/8/2019 Ch 11 - Generator Protection
12/71
GENERATOR CONTROL AND PROTECTION
Generator Protection
-
8/8/2019 Ch 11 - Generator Protection
13/71
GENERATOR CONTROL AND PROTECTION
Symmetrical Components Positive Sequence
A set of three phasors that have the same magnitude, are equally
displaced from each other by 120, and have the same phasesequence as the system under study (ex ABC)
Negative Sequence A set of three phasors that have the same magnitude, are equally
displaced from each other by 120, and have the opposite phasesequence as the system under study (ex ACB)
Zero Sequence A set of three phasors of equal magnitude that are all in phase or
have zero displacement from each other
-
8/8/2019 Ch 11 - Generator Protection
14/71
-
8/8/2019 Ch 11 - Generator Protection
15/71
GENERATOR CONTROL AND PROTECTION
Symmetrical Components
-
8/8/2019 Ch 11 - Generator Protection
16/71
GENERATOR CONTROL AND PROTECTION
Symmetrical Components
-
8/8/2019 Ch 11 - Generator Protection
17/71
GENERATOR CONTROL AND PROTECTION
Symmetrical Components
-
8/8/2019 Ch 11 - Generator Protection
18/71
GENERATOR CONTROL AND PROTECTION
Symmetrical Components
-
8/8/2019 Ch 11 - Generator Protection
19/71
GENERATOR CONTROL AND PROTECTION
Symmetrical ComponentsExample Problem
One conductor of a three phase line is
open. The current flowing to the delta
connected load thru line a is 10A. With
the current in linea
as reference andassuming that line c is open, find the
symmetrical components of the line
currents.
-
8/8/2019 Ch 11 - Generator Protection
20/71
GENERATOR CONTROL AND PROTECTION
Symmetrical ComponentsExample Problem
Ia = 10/0 A, Ib = 10/180 A, Ic = 0 A
Ia0
= (1/3)(Ia
+ Ib
+ Ic
)
Ia0 = (1/3)(10/0 + 10/180 + 0) = 0
Ia1 = (1/3)(Ia + Ib + 2 Ic )
Ia1 = (1/3)(10/0 + 10/180+120 + 0)
Ia1 = 5.78 /-30 Ia2 = (1/3)(Ia +
2 Ib + Ic )
Ia2 = (1/3)(10/0 + 10/180+240 + 0)
Ia2 = 5.78 /30
-
8/8/2019 Ch 11 - Generator Protection
21/71
GENERATOR CONTROL AND PROTECTION
Symmetrical ComponentsExample Problem
Ib0 = 0
Ib1 = 5.78 /-150
Ib2 = 5.78 /150
Ic0 = 0
Ic1 = 5.78 /90
Ic2 = 5.78 /-90
-
8/8/2019 Ch 11 - Generator Protection
22/71
-
8/8/2019 Ch 11 - Generator Protection
23/71
GENERATOR CONTROL AND PROTECTION
Symmetrical ComponentsExample Problem
Note: the components Ic1 and Ic2 have
definite values although line c is open and
can carry no net current. As expected, the
sum of these currents is zero.
The sum of the currents in line a is 10/0
The sum of the currents in line b is 10/180
-
8/8/2019 Ch 11 - Generator Protection
24/71
GENERATOR CONTROL AND PROTECTION
Symmetrical Components
Single Phase Line to Ground Fault
-
8/8/2019 Ch 11 - Generator Protection
25/71
GENERATOR CONTROL AND PROTECTION
Symmetrical Components
Generator Sequence Networks
-
8/8/2019 Ch 11 - Generator Protection
26/71
GENERATOR CONTROL AND PROTECTION
Symmetrical Components
-
8/8/2019 Ch 11 - Generator Protection
27/71
GENERATOR CONTROL AND PROTECTION
Symmetrical Components
-
8/8/2019 Ch 11 - Generator Protection
28/71
GENERATOR CONTROL AND PROTECTION
Symmetrical Components
-
8/8/2019 Ch 11 - Generator Protection
29/71
GENERATOR CONTROL AND PROTECTION
Fault Current Behavior of a
Synchronous Generator
-
8/8/2019 Ch 11 - Generator Protection
30/71
GENERATOR CONTROL AND PROTECTION
Fault Current Behavior of a
Synchronous Generator
-
8/8/2019 Ch 11 - Generator Protection
31/71
GENERATOR CONTROL AND PROTECTION
Fault Current Behavior of a
Synchronous Generator
-
8/8/2019 Ch 11 - Generator Protection
32/71
GENERATOR CONTROL AND PROTECTION
Fault Current Behavior of a
Synchronous Generator
Max DC Offset
No DC Offset
-
8/8/2019 Ch 11 - Generator Protection
33/71
GENERATOR CONTROL AND PROTECTION
Fault Current Behavior of a
Synchronous Generator
-
8/8/2019 Ch 11 - Generator Protection
34/71
GENERATOR CONTROL AND PROTECTION
Fault Current Behavior of a
Synchronous Generator
-
8/8/2019 Ch 11 - Generator Protection
35/71
GENERATOR CONTROL AND PROTECTION
Generator Grounding
-
8/8/2019 Ch 11 - Generator Protection
36/71
GENERATOR CONTROL AND PROTECTION
Generator Grounding
Low Impedance Grounding
Single phase to ground fault current between 200A and 150%
High Impedance Grounding
Single phase to ground fault current between 5 and 20A
-
8/8/2019 Ch 11 - Generator Protection
37/71
GENERATOR CONTROL AND PROTECTION
Generator Stator Phase Fault
Protection (87G)
-
8/8/2019 Ch 11 - Generator Protection
38/71
GENERATOR CONTROL AND PROTECTION
Generator Stator Phase Fault
Protection (87G)
87G used to protect for:
3 phase line to line1 phase line to line
multi-phase line to ground
May not be able to detect a 1 phase to ground fault on high
impedance grounded generatorsRestraint or Percentage Differential Trip Characteristic
Used to improve sensitivity for detecting small levels of
fault current
Also maintains security against inadvertent tripping due
to thru faults
-
8/8/2019 Ch 11 - Generator Protection
39/71
GENERATOR CONTROL AND PROTECTION
Generator Stator Phase Fault
Protection (87G)
-
8/8/2019 Ch 11 - Generator Protection
40/71
GENERATOR CONTROL AND PROTECTION
Generator Stator Phase Fault
Protection (87G)
-
8/8/2019 Ch 11 - Generator Protection
41/71
GENERATOR CONTROL AND PROTECTION
Generator Stator Phase Fault
Protection (87G)
Split-phase protection scheme
Able to detect turn-turn faultsWindings for each phase split into equal groups
Individual winding currents are vector summed
Any difference in winding current results in a output from CT
Overcurrent relay (50/51) can be used to monitor differencecurrent
Setting must be above any normal unbalances that may exist
-
8/8/2019 Ch 11 - Generator Protection
42/71
GENERATOR CONTROL AND PROTECTION
Generator Stator Phase Fault
Protection (87G)
-
8/8/2019 Ch 11 - Generator Protection
43/71
GENERATOR CONTROL AND PROTECTION
Generator Field Ground Fault
Protection (64F)
-
8/8/2019 Ch 11 - Generator Protection
44/71
GENERATOR CONTROL AND PROTECTION
Generator Stator Ground Fault
Protection (87N, 51N, 59N & 27-3N)
For Low Impedance Grounded Generators
-
8/8/2019 Ch 11 - Generator Protection
45/71
GENERATOR CONTROL AND PROTECTION
Generator Stator Ground Fault
Protection (87N, 51N, 59N & 27-3N)
For Low Impedance Grounded Generators
-
8/8/2019 Ch 11 - Generator Protection
46/71
GENERATOR CONTROL AND PROTECTION
Generator Stator Ground Fault
Protection (87N, 51N, 59N & 27-3N)
External Generator Phase-Ground Fault
G S G d F l
-
8/8/2019 Ch 11 - Generator Protection
47/71
GENERATOR CONTROL AND PROTECTION
Generator Stator Ground Fault
Protection (87N, 51N, 59N & 27-3N)
External Generator Phase-Ground Fault
G S G d F l
-
8/8/2019 Ch 11 - Generator Protection
48/71
GENERATOR CONTROL AND PROTECTION
Generator Stator Ground Fault
Protection (87N, 51N, 59N & 27-3N)
Internal Generator Phase-Ground Fault
G t St t G d F lt
-
8/8/2019 Ch 11 - Generator Protection
49/71
GENERATOR CONTROL AND PROTECTION
Generator Stator Ground Fault
Protection (87N, 51N, 59N & 27-3N)
Internal Generator Phase-Ground Fault
G t St t G d F lt
-
8/8/2019 Ch 11 - Generator Protection
50/71
GENERATOR CONTROL AND PROTECTION
Generator Stator Ground Fault
Protection (87N, 51N, 59N & 27-3N)
High Impedance Grounded
50MVA, 13.2kV Generator
Xc = 10,610 for 0.25uf @ 60Hz
Rpri = 10,610/3 = 3537
-
8/8/2019 Ch 11 - Generator Protection
51/71
GENERATOR CONTROL AND PROTECTION
Loss of Field Protection (40Q, 40Z)
-
8/8/2019 Ch 11 - Generator Protection
52/71
GENERATOR CONTROL AND PROTECTION
Loss of Field Protection (40Q, 40Z)
-
8/8/2019 Ch 11 - Generator Protection
53/71
GENERATOR CONTROL AND PROTECTION
Loss of Field Protection (40Q, 40Z)
Over/Under Frequency Protection
-
8/8/2019 Ch 11 - Generator Protection
54/71
GENERATOR CONTROL AND PROTECTION
Over/Under Frequency Protection
(81O/U)
Causes:
Significant load additionSudden reduction in mechanical input power
Loss of generation
Loss of load
Underfrequency can cause:Higher generator load currents
Overexcitation
Turbine blade fatigue
Overfrequency can cause:Overvoltage on hydro turbines
Overexcitation and Overvoltage
-
8/8/2019 Ch 11 - Generator Protection
55/71
GENERATOR CONTROL AND PROTECTION
Overexcitation and Overvoltage
Protection (24, 59)
Modern Excitation Systems include over excitation limiting
and protection, but it may take several seconds to limitOverexcitation occurs when the V/Hz ratio exceeds 105% at
FL and 110% at no load
V/Hz relays set at 110% with a 5 10 sec delay
Generator overvoltage can occur without exceeding V/Hzrelay setting due to large over speed on hydro generator
Generator overvoltage relay, 59 may be used
-
8/8/2019 Ch 11 - Generator Protection
56/71
-
8/8/2019 Ch 11 - Generator Protection
57/71
GENERATOR CONTROL AND PROTECTION
Out of Step Protection (78)BA
EA EB
ZBZTZA
Generator SystemTransformer
+R
+X
-R
EA/EB>1
Q
P
EA/EB=1
EA/EB
-
8/8/2019 Ch 11 - Generator Protection
58/71
GENERATOR CONTROL AND PROTECTION
Out of Step Protection (78)
R
X
BA
M
B
Element
Pickup
A
Element
Pickup
Blinder
Elements
Mho
Element
Gen X'd
Trans
System
P
-
8/8/2019 Ch 11 - Generator Protection
59/71
GENERATOR CONTROL AND PROTECTION
Negative Sequence Protection (46)
Protects generator from excessive heating in the rotor due to
unbalanced stator currentsNegative sequence component of stator current induces
double frequency current in rotor, causing heating
Rotor temperature rise proportion to I22t
Negative sequence relays provide settings for this relationshipin the form of a constant, k = I2
2t
Minimum permissible continuous unbalance currents are
specified (ANSI/IEEE C50.13)
Inadvertent Energization Protection
-
8/8/2019 Ch 11 - Generator Protection
60/71
GENERATOR CONTROL AND PROTECTION
Inadvertent Energization Protection
(27, 50, 60, 81U, 62 and 86)
Protects against closing of the generator breaker while
machine is not spinning / on turning gearCaused by operator error, breaker flash-over, control circuit
malfunction
Two schemes illustrated:
Frequency supervised overcurrentVoltage supervised overcurrent
Inadvertent Energization Protection
-
8/8/2019 Ch 11 - Generator Protection
61/71
GENERATOR CONTROL AND PROTECTION
Inadvertent Energization Protection
Frequency Supervised Overcurrent
G
50
81U
60
62
81U
60
86
50 (3-phase)
86
62
+DC
-DC
0.5sec Pickup
0.1sec Dropout
Inadvertent Energization Protection
-
8/8/2019 Ch 11 - Generator Protection
62/71
GENERATOR CONTROL AND PROTECTION
Inadvertent Energization Protection
Frequency Supervised Overcurrent
Uses an underfrequency relay (81U) to enable a sensitive
instantaneous overcurrent relay (50)
Overcurrent relay picks up at 50% or less of expected
inadvertent energizing current
Frequency relay contacts must remain closed if sensingvoltage goes to zero
Voltage balance relay (60) protects against loss of sensing
Time delay relay (62) protects against sudden application
of nominal voltage during inadvertent energization,allowing overcurrent to trip lockout relay (86)
Lockout relay must be manually reset
Inadvertent Energization Protection
-
8/8/2019 Ch 11 - Generator Protection
63/71
GENERATOR CONTROL AND PROTECTION
Inadvertent Energization Protection
Voltage Supervised Overcurrent
Same illustration as frequency supervised overcurrent except
81U replaced by 27Undervoltage setpoint of 85% of the lowest expected
emergency operating level
Loss of Voltage Transformer
-
8/8/2019 Ch 11 - Generator Protection
64/71
GENERATOR CONTROL AND PROTECTION
V ag a
Protection (60)
Common practice on large systems to use two or more VTs
One used for relays and metering
The other used for AVR
VTs normally fused
Most common cause of failure is fuse failure
Loss of VT protection blocks voltage based protective
functions (21, 32, 40 etc)
Loss of VT protection measure voltage unbalance, typical
setting is 15%
Loss of Voltage Transformer
-
8/8/2019 Ch 11 - Generator Protection
65/71
GENERATOR CONTROL AND PROTECTION
g
Protection (60)
G
60
vt
To
Excitation
Controller
To
Protective
Relays
-
8/8/2019 Ch 11 - Generator Protection
66/71
GENERATOR CONTROL AND PROTECTION
System Backup Protection (51V, 21)
Common practice to provide protection for faults outside
of the generator zone of protection
Voltage supervised time-overcurrent (51V) or distance
relaying (21) may be used
Distance relay set to include generator step up transformer
and reach beyond, into the system
Time delays must be coordinated with those of the system
protection to assure that system protection will operate
before back up CTs on neutral side of generator will also provide backup
protection for the generator
-
8/8/2019 Ch 11 - Generator Protection
67/71
GENERATOR CONTROL AND PROTECTION
System Backup Protection (51V, 21)
G
21
51V
a.) Neutral Connected ct's
-
8/8/2019 Ch 11 - Generator Protection
68/71
GENERATOR CONTROL AND PROTECTION
System Backup Protection (51V, 21)
-
8/8/2019 Ch 11 - Generator Protection
69/71
GENERATOR CONTROL AND PROTECTION
System Backup Protection (51V, 21)
For medium and small sized generators, voltage-restrained
or voltage controlled time overcurrent relays (51V) areoften applied
Control or restraining function used to prevent or
desensitize the overcurrent relay from tripping until the
generator voltage is reduced by a fault
-
8/8/2019 Ch 11 - Generator Protection
70/71
GENERATOR CONTROL AND PROTECTION
System Backup Protection (51V, 21)
Percent Nominal Volts25% 100%
25%
100%
a.) Voltage-Restrained Overcurrent
PercentSetValueforPickup
Percent Nominal Volts
Enable
Inhibit
b.) Voltage-Contolled Overcurrent
Pickup
Inhibit/Enable
80% 100%
-
8/8/2019 Ch 11 - Generator Protection
71/71
GENERATOR CONTROL AND PROTECTION
Conclusion
Generators must be protected from electrical faults,
mechanical problem and adverse system conditions Some faults require immediate attention (shutdown) while
others just require alarming or transfer to redundant
controllers
Design of these systems requires extensive understanding
of generator protection
Further study IEEE C37.102 Guide for AC Generator
Protective Relaying