certificado cnas
DESCRIPTION
CNAS Test Report regarding Safety Productos ULTRATRANSCRIPT
Serial number:2008131
Sample name:ULTRASample type:U-304Manufacturer:KESECO CO.,LTDConsignment organization:KESECO CO., LTDExperiment classification: Experiment consignment
The address of research organization: 22 Soyeongdongru Cheongha Beijing ChinaThe zip code of research orgnization: 100132The telephone number of research organization: 010-6293-1468The fax number of research organization : 010-62913139The website of research organization: http://www.epri.ac.com
The eletrical engineering equipment & meter mesurement experiment Center
July 4th. 2008
Experiment report
Report serial number:2008131 The first page out of 9
Product name ULTRAproduction release number
KEU-14080632k022N
Model size U-304 Manufaturer address
Consignment organizatioKESECO CO., LTDSample number 08-012-011 Experiment date From June 18th 2008 to July 2nd 2008manufacturing organizat KESECO CO., LTD Regulated voltage ;AC380VExperiment type Consigned experiment Regulated capacity:30KVAExperiment list 6th listManufacturing date June 10th 2008
GB4208-1993<<The external case safety level(IP number) & technical conditions of the products
Based on standards and technical products condition , the electricity saver,Ultra U-304 produced by Keseco.Inc has been proceeded with six lists.The experiment results meet the needs
for related criteria & corporation product technicExperiment conclusion
Experiment basiscriteria
GB/T2421.2-2001<<The condition experiment of eletrical engineering & eletrical product, The second part :experiment measurement Experiment A:low temperature
GB/T2423.2-2001<<The condition experiment of eletrical engineering & eletrical product, The second part :experiment measurement Experiment B:High temperature
Receiving method
GB/T2423.3-2006<<The condition experiment of eletrical engineering & eletrical product, The second part :experiment measurement Experiment, Cab:Unchangable high humid and temperature experiment
GB/T2423.52-1995<< The condition experiment of eletrical engineering & eletrical product, The second part :Experiment method-Crash experiment
The eletrical engineering equipment & meter mesuring experiment Center
Experiment report
8F Namyoung Bldg Sungsudong-2ga Sungdong-Gu,Seoul, Korea
Experiment conditions
Report serial number:2008131The second page out of 9
Experiment item & Experiment conclusion
Order Experiment item Experiment conclusion Page number Order Experiment item Experiment conclusioPage number
1 Insulator intensity experimentSatisfied with corporation product technical condition
3
2 Safety level experiment pass 43 Unchangable high humidity&heat experiment pass 54 Shock experiment pass 65 Crash experiment pass 76 Experiment preserved under extremely low temperaturepass 87 Experiment picture pass 9
below filled with blanks
The equipment of major experiment meter
Interior voltage tester High & low temperature test box Shock & Crash test box
below filled with blanks
The eletrical engineering equipment & meter mesurement experiment Center
Experiment Report
Insulation tester ZC-7
Reguated number Serial number
DH2793ESS-SDJ 605
CP-100
110662000125200700110104
Report serial number:2008131
The third page out of 9
Insulation resistance(MΩ) (V) (S)
Main electric route among A,B,C,N
5 2500 60
Between Main electric route A,B,C,N and products exterior
5 2000 60
below filled with blanks / / / /
Experiment serial number
Pattern Experiment part Insulation resistance(MΩ) Pressure frequency
Main eletric route A and B phase 10Main eletric route B and C phase 10Main eletric route A and C phase 10Main eletric route A,B,Cand N phase 10Between main route A,B,C,N and outside 10below filled with blanks
Experiment pattern :The technical condition of productsExperiment conclusion:Satisfied with technical conditions of corporation product Experiment date:June 18 2008
28,0 68,5 46,0
Insulator intensity experiment
1. Experiment condition & requirement
Pressure frequency Environment temperature©
Description
08-021-011
금속안장기기유무 여부Whether or not there is a metal installment stand
Yes
2.Experiment results
Whether or not there is external sample
2500V pass
Relative temperature(%)
Temperature above sea level(m)
2500V pass2500V pass2500V pass2500V pass
Report serial number: 2008131
The fourth page out of 9
Experiment serial number 08-012-011 Environment temperature© 28,0 relative temperature(% 68,5
1. Experiment condition & requirement
1.Complying with GB 4208-1993 standard requiremen, as to insurance of solid material, solid alien substances of less than 1.0mm in diameter are not allowed to enter products inwoard
2.It has to have a waterproof function
2.Experiment resultsBased on GB 4208-1993 standard requirement, this experiment inspect safety action for absorbing solid alien substances of less than 1.0mm in diameter to comply with design requirements for protecting action installation, testing products.This study follow an inspection of test design with non water proof function, GB 4208-1993 medium level protection number.
The reason of experiment method : GB 4208-1993Experiment conclusion: PassExperiment date: June 18th. 2008
Safety level experiment
Description
Report serial number:2008131
Unchangable high humidity&heat experiment
08-012-011 Environment temperature(℃) 28.0~28.1 Relative temperature(%) 68.5~68.9
1.Experiment condition & requirement
Test with unpacked and not flowing current
After keeping 40C(+-2) Leave it for 48 hours meeting 93%(+- 3 ℃) condition again.
If insulation resistance surely has to be less than 5MΩ, this experiment has to be done in 80% permitted frequancy errors of voltage.
2.Experiment result
After getting study results, process nonconductor intensity experiment.
Experiment serial number Experiment list Insulation resistance(MΩ) Frequency of pressure08-012-011 Main eletric route A and B phase 7 2000V pass
Main eletric route B and C phase 7 2000V passMain eletric route A and C phase 7 2000V passMain eletric route A,B,Cand N phase 7 2000V passBetween main eletric route A,B,C,N and outside 7 1600V pass
The reason of experiment metho:GB/T 2423.3-2006
Experiment conclusion :Pass
Experiment date : From June 18th 2008 to June 20th 2008
Unchangable high humidity&heat experiment
Description
The Fifth page out of 9
This experiment doesn't have any weird changes in appearance like mold after lowering 75% humidity within 30 minutes and after 30 minutes and having recovery time for 4 hours with normal temperature and normal humid condition
After being stored for 48 hours in the high humid and heat experiement box, the mentioned experiment condition test has to be clean in appearance and doesn't have any moldswhen normal temperature and humidity is low
Report serial number:2008131
Experiment serial number 08-012-011 Environment temperature 28,7 Relative temperature( 69,4
1.Experiment condition & requirementAccelation :500m/s2
pulse keeping time :(11+-1)ms
Shock number :6 sides,each side 3 times(total18 times)
Shape of the waves Sine curve
Working condition Processed before products are setted
2.Experiment result
Description The experiment test device like the above is processed with packed.
The reason of experiment method :GB/T 2423.5-1995
Experiment conclusion :Pass
Experiment date June 30th 2008
Shock experiment The Sixth page out of 9
Meething needs for experiment conditions, experiment results don't have any damage at all in appearance and they comply to the requirement for GB/t 2423.5-1995 standard.
Report serial number:2008131
Experiment serial number 08-012-011 Environment temperature/C 29,0 Relative temperature(% 70,4
1.Experiment condition & requirement
The highest soaring accelation :400m/s2Average pulse유자기간 :6msShocking frequency :6 sides, 3 times for each side(total 18 times)Velocity variation :1.5m/sCrashing frequency : Each side(4000+-10회)Working condition : Processed before products are setted
Experiment result
Processed before products are setted
The reason of experiment method GB/T 2423.6-1995Experiment conclusion PassExperiment date July 2nd 2008
Crash experimentThe Seventh page out of 9
Description
Experiment result meets the requirement for GB/T 2423.6-1995 standard
It doesn't have any exterior distortions, screws' loosing and tightening phenomenon. This proves to comply with requirements for GB/T 2423.6-1995 standard
Report serial number 2008131
Experiment serial number 08-012-011 Environment temperature28.1~25.6 Relative temperature(
1.Experiment condition & requirement
1.Experiment keeping low temperature
The appearance of products definitely dosen't have any deform and air bubble phenomenon.
2.Experiment keeping high temperature
2.Experiment result
The reason of experiment metho : GB/T 2423.1-2001 & GB/T 2423.2-2001
Experiment conclusion : Pass
Experiment date :From June 20th 2008 to June 23rd
Description
Experiment keeping low& high temperatureThe 8th out of 9
68.9~67.9
First, products keep in a low temperature box(+70+-2) for 24 hours in a row. and then pick them up from the box and process appearance study after recovering it suitable for room temperature gradually.
First, products keep in a high temperature box(+70+-2) for 24 hours in a row. and then pick them up from the box and process appearance study afterrecovering it suitable for room temperature gradually. The appearance of products definitely dosen't have any deform and air bubble phenomenon.
Proceed a product test keeping in low and high temperature several times as meeting study requirements & conditions. An appearance research is gone ahead adjusting to room temperature. From the study results, this study has to prove that there are not any deforms or bubbling phenomenon on the appearance of the products.