ceiling cassette(60hz,r22) 6cst2-01a 08.pdf20080904
TRANSCRIPT
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
1/178
6CST2-01A
Ceiling Cassette(60Hz/R22)
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
2/178
2 Ceiling Cassette
Ceiling CassetteIntroduction
Part 1 General information
1. Model line up .....................................................................................10
1.1 Indoor units ............................................................................................................10
2.2 Outdoor units..........................................................................................................11
2. Nomenclature ....................................................................................12
2.1 Global standard......................................................................................................12
2.2 Decoration panel(For ceiling cassette models) ......................................................12
3. List of functions ................................................................................13
4. Features .............................................................................................15
5. Control system(accessory)..............................................................18
5.1 Individual control system........................................................................................18
5.2 Central control system............................................................................................18
5.3 Control device ........................................................................................................18
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
3/178
3Ceiling Cassette
Part 2 Product data
1. Indoor units.......................................................................................21
1.1 Ceiling cassette 4-way............................................................................................21
2. Outdoor units....................................................................................52
2.1 Single piping type ...................................................................................................52
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
4/178
4 Ceiling Cassette
Part 3 Design and installation
1. General installation guidelines......................................................102
1.1 Installation process & guidelines .................................................................102
1.2 Checking the drawing ...................................................................................103
1.3 Application guidelines...................................................................................104
2. Guideline for each installation process........................................107
2.1 Sleeve and inserting work.............................................................................107
2.2 Refrigerant piping work.................................................................................109
2.3 Drain piping work .........................................................................................119
2.4 Insulation work..............................................................................................125
2.5 Electrical work ..............................................................................................1292.6 Air tight test...................................................................................................131
2.7 Vacuum drying ..............................................................................................135
2.8 Additional charge of refrigerant.....................................................................140
2.9 Trial test run operation ..................................................................................141
3. Installation of indoor unit ..............................................................143
3.1 Safety precautions ........................................................................................143
3.2 Ceiling cassette 4-way..................................................................................148
4. Installation of outdoor Unit ...........................................................1584.1 Safety precautions ........................................................................................158
4.2 Introduction...................................................................................................164
4.3 Foundation....................................................................................................165
4.4 Settlement of the outdoor unit.......................................................................166
4.5 Selection of the best location........................................................................167
4.6 Clearance space...........................................................................................168
4.7 Outdoor unit piping .......................................................................................171
4.8 Outdoor unit installation requirements ..........................................................172
4.9 Outdoor unit cabin ........................................................................................175
4.10 Installation guide at the seaside .................................................................177
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
5/178
General information 5
Introduction6CST2-01A
Ceiling Cassette
Introduction
Preface
LG Electronics Inc.
Air Conditioning Division
New era brings more sophisticated and advanced buildings which in turn demands for specialized and optimized direct
expansion air conditioning systems. Also energy efficiency, environment friendliness, low noise and low maintenance are
the features which are essential for these systems.
As a part of vertical integration LG makes all the key components in house, which gives us an edge to make better and lat-
est technology products with best quality in optimized time.
Ceiling cassette installed in the ceiling is popularly used for various places. It has nice outlook and is equipped with many
special features.
This engineering product data book incorporates information about the product itself, and installation, designing for ceiling
cassette.The comprehensive study of this book will improve your knowledge about the system and its application in detail.
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
6/178
6 General information
Introduction 6CST2-01A
Ceiling Cassette
Publication history
Pub. No. Frequency Category Type Product name Refrigerant Models Notes Published in
6CST2-01A 60Hz CAC Single Ceiling cassette R22
LT-C182QLE0LT-C242PLE0LT-C302PLE0
LT-C362NLE0LT-C482MLE0LT-C602MLE0LT-H182QLE0LT-H242PLE0LT-H302PLE0LT-H362NLE0LT-H482MLE0LT-H602MLE0
New edition Jun.2008
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
7/178
General information 7
Introduction6CST2-01A
Ceiling Cassette
Step by step air conditioner selection process (reference)
(1) Calculate or obtain the maximum heat load for the area(s) to be air conditioned
(2)
(3)
(4)
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas
Make referene to the Multi PDB (P/No. 3828A20576B)
or alkaline gas, are produced.2. If the outdoor unit is installed close to the sea shore, direct exposure to the sea breeze
should be avoided and choose an outdoor unit with anti-corrosion treatment.
CAUTION
Selection of the control system
Control wiring method
Electrical wiring
Electrical characteristics
Field wiring
.....................................................................................p. 98
..........................................................................................................p. 156
Indoor unit specifications .......................................................................................p. 30
....................................................................................p. 59
......................................................................................p. 96
....................................................................p. 48
......................................................................................p. 174
Outdoor unit specifications
Capacity coefficient factor
Air flow and temperature distribution
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
8/178
8 General information
6CST2-01A
Ceiling Cassette
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
9/178
General information 9 Ceiling Cassette
Part 1 General information
1. Model line up.........................................................................................10
1.1 Indoor units .................................................................................................................102.2 Outdoor units...............................................................................................................11
2. Nomenclature ........................................................................................12
2.1 Global standard...........................................................................................................12
2.2 Decoration panel(For ceiling cassette models) ...........................................................12
3. List of functions....................................................................................13
4. Features.................................................................................................15
5. Control system(accessory)..................................................................185.1 Individual control system.............................................................................................18
5.2 Central control system ................................................................................................18
5.3 Control device .............................................................................................................18
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
10/178
10 General information
6CST2-01A
Ceiling Cassette
1. Model line up1.1 Indoor Units
Model line up
Model names
Category Type Chassis Capacity, kW(kBtu/h)
7.06(24.1) 8.79(30)
Ceiling
cassette 4-way
LT-C242PLE0
LT-H242PLE0
LT-C302PLE0
LT-H302PLE0TP
Model names
Category Type Chassis Capacity, kW(kBtu/h)14.06(48) 17.58(60)
Ceiling
cassette 4-way
LT-C482MLE0
LT-H482MLE0
LT-C602MLE0
LT-H602MLE0TM
Model names
Category Type Chassis Capacity, kW(kBtu/h)
10.55(36)
Ceiling
cassette 4-way
LT-C362NLE0
LT-H362NLE0TN
Model names
Category Type Chassis Capacity, kW(kBtu/h)
5.28(18)
Ceiling
cassette 4-way
LT-C182QLE0
LT-H182QLE0TQ
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
11/178
General information 11
Model line up6CST2-01A
Ceiling Cassette
1.2 Outdoor Units
Model name LT-C182QLE0
LT-H182QLE0 LT-C242PLE0 LT-H242PLE0
LT-C302PLE0
LT-H302PLE0
No. of connectable indoor units
Total capacity index of connectable kW
indoor units kBtu/h
Power supply
Chassis
1
5.28 7.06 7.06 8.79
18 24.1 24.1 30
1, 220V, 60Hz
Model name LT-C362NLE0
LT-H362NLE0 LT-C482MLE0 LT-H482MLE0
LT-C602MLE0
LT-H602MLE0
No. of connectable indoor units
Total capacity index of connectable kW
indoor units kBtu/h
Power supply
Chassis
1
10.55 14.06 14.06 17.58
36 48 48 60
1, 220V, 60Hz
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
12/178
12 General information
Nomenclature 6CST2-01A
Ceiling Cassette
2. Nomenclature2.1 Global standard
2.2 Decoration panel(For ceiling cassette models)
- C 2 4LT 2 P L E 0
Serial number
Decoration PanelL : Basic panel
Electric rating2 : 220V, 60Hz, 1
Cooling/heating capacityEx) 24,000 Btu/h'24'
34,000 Btu/h
'34'
Model typeC : Cooling only
H : Heat Pump
Type of air conditionerLT : Ceiling cassette using R22
Function
E : Elevation Grille
Chassis nameP : TP Chassis N : TN Chassis M : TM Chassis Q:TQ Chassis
P T - U M C
Functions
Indoor unit chassis
Model type
Decoration panel of ceiling cassette type indoor unit
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
13/178
General information 13
6CST2-01A
Ceiling Cassette
3. List of functions3.1 Indoor Units
FunctionCategory Ceiling Cassette4-way
Air supply outlet
Airflow direction control(left & right)
Airflow direction control(up & down)Auto swing(left & right)
Auto swing(up & down)
Airflow steps(fan/cool/heat)
Chaos swing
Chaos wind(auto wind)
Jet cool(Power wind)
Swirl wind
Deodorizing filter
Plasma air purifier
Prefilter(washable / anti-fungus)
Drain pump
E.S.P. control
Electric heater(operation)
High ceiling operation
Hot start
Self diagnosis
Soft dry operation
Auto changeover
Auto cleaning
Auto operation(artificial intelligence)
Auto restart operation
Child lock
Forced operation
Group control
Sleep mode
Timer(on/off)
Timer(weekly)Two thermistor control
Standard wired remote controller
Wide Character wired remote controllerPicto wired remote controller
Deluxe wired remote controller
Simple wired remote controller
Wired remote controller(for hotel use)
Wireless remote controller(simple)
Wireless LCD remote control
General central controller (Non LGAP)
Dry contact
Network Soluation(LGAP)
PDI(power distribution indicator)
PI 485
Zone control
CTIE
Electro thermostat
Thermistor
Test function
Vane Control
Auto Elevation grille
List of functions
O : Applied, X : Not applied, : No relationOption: Model name & price are different according to options, and assembled in factory with main unit.Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.*: except for LT-C182QLE0/LT-H182QLE0/LT-H602MLE0
Air flow
Air purifying
Installation
Reliability
Convenience
Individualcontrol
Specialfunction kit
Others
CAC network
function
4
-
Auto-
O
4 / 5 / 4(Cooling Only Models : 4 / 5 / -)
X
O
O
O
X
*O
O
O
O
X
O
O(Heat Pump Model Only)
O
O
O(Heat Pump Model Only)
X
O(Cooling Only)
O
O
O
O
O
O
OO
PCRCUSZ0
PQRCUSA0
PQRCUDS0/PQRCUDS0B/PQRCUDS0S
PQRCUCA0
PQRCFCS0
X
PQWRCSF0
X
PQDSB/PQDSBC
O
X
PSNFP14A0
-
-
-
-
O
O
PTEGM0
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
14/178
14 General information
List of functions 6CST2-01A
Ceiling Cassette
3.2 Outdoor Units
FunctionCategory Ceiling Cassette4-way
Defrost / Deicing
High Pressure Switch
Low Pressure SwitchPhase protection
Restart Delay (3-minutes)
Self Diagnosis
Soft Start
Test Function
Auto Changeover
Auto Restart Operation
Central control(LGAP)
PDI(Power Distribution Indicator)
PI485
Low Ambient Kit
Thermistor
O : Applied, X : Not applied, : No relationOption: Model name & price are different according to options, and assembled in factory with main unit.Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
Reliability
Convenience
Special function kit
Others
CAC networkfunction
O(Heat Pump Model Only)
O
XX
O
O
X
X
O(Heat Pump Model Only)
O
Accessory
X
Accessory
X
-
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
15/178
General information 15
Features6CST2-01A
Ceiling Cassette
4. Features
Ceiling Cassette 4-way
Compact Size
The indoor unit with slim and compact size enables
successful installation in various spaces.
Convenient Installation
Easy installation with corner detachable decoration panel.
One touch type Panel
It provides easy installation with a one-touch detachable
Compact design and easy installation
Low noise
Hygienic and easy-to-clean filter
2-thermistor(unit body and remote controller) Jet cool
High head drain pump(800mm(18k : 700mm))
High-ceiling corresponding operation
LCD wired remote controller
Wireless remote controller(accessory)
Hygienic and easy to clean filter
Washable filter is adopted.
It is easy to open grille and clean filter.
Drain leakagecheck
Hanger adjustHanger adjust
(PQRCUSA0)
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
16/178
16 General information
Features 6CST2-01A
Ceiling Cassette
Wide Jet Air Flow
Improved wide and narrow vane will provide comfortable
temperature distribution without air flow dead zone.
High head drain pump(800mm)
Built-in drain pump drains out water automatically.
A standard drain-head height of up to 800 mm is pos-
sible, providing an ideal solution for perfect water
drainage.
Function to Control the Air Volume by
Ceiling Height
Control of the air intensity has been made possible by
employing a height-control algorithm for the interior fan.
Two Thermistor Control
There may be a significant difference between the tempera-
ture taken at the installed product and indoor temperature.Two thermistor control provides option to control tempera-
ture by referring any of the two temperatures.With the help
of the slide switch at the back of the LCD wired remote con-
troller,selection of the desired thermistor for controlling the
unit can be done.One thermistor is in the Indoor unit &the
other one is in the LCD wired remote.
Flexible hose
Drain pump
PVC elbow
PVC
PVC
Ma
x.
800
(18k:
Max.
700)
300mm or less
[Unit : mm]Common
drain pipe
Current
New Cassette
Air flow dead zone
Even air distribution
New
Current
567mm
80mm Wider!!
Installation on thenormal-height ceiling
installation on thehigher ceiling
(PQRCUSA0)
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
17/178
General information 17
Features6CST2-01A
Ceiling Cassette
Swirl Swing
Swirl swing distributes air evenly throughout the room to ensure a more comfortable conditioned environment by adjusting
the movement of the louvers.
Company A
LG New Cassette
Vertical Temp. Differences Horizontal Temp. Differences
Vane 2
Vane 1
Vane 3
Vane 4
Time
Open
Open
Open
Open
OpenOpen
Time
Vane 1
Vane 2
Vane 3
Vane 4
Open
Close
Open
Close
Close
Open
Close
Open
Close
Open
Close
Close
Open
Close
OpenOpen
Close
Open
Close
Open
Comparison of Air Flow Types (UT12~18)
4-Open(Conventional)
Swirl Swing (New)
Vane 2
Vane 1 Vane 3
Vane 4
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
18/178
18 General information
Control system(accessory) 6CST2-01A
Ceiling Cassette
5.2 Central control system
5. Control system(accessory)
5.1 Individual control system
Not available
Simple central controller
Simple central controller
(function controller
available)
Function controller
PQCSA101S0
PQCSB101S0
PQCSC101S0
Deluxe central controller
(without schedule
function)
PQCSW501A0
Ceiling cassette
Deluxe central controller
(with schedule
function)
PQCSW502A0
PC based central controller
(without schedule
function)PQCSS501A0
PC based central controller
(with schedule
function)
PQCSS502A0
Item Model name Image Applicable model
Central controller
For detail information, refer to the "Part 4 Network solution of Multi F/FDX PDB".
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
19/178
General information 19
Combination6CST2-01A
Ceiling Cassette
5.3 Control device
Item Image Application modelModel name
Product
interface units
PI485
CNU
Dry_contact
PMNFP14A0
PQNFG00A0
PQDSB
PQDSA
BNU_LWLonWorks
for BMS PQNFB16A0
PDI
(Power distributor indicator) PQNUD1S00
Ceiling cassette
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
20/178
20 General information
6CST2-01A
Ceiling Cassette
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
21/178
Ceiling CassetteProduct data 21
Part 2 Product data
1. Indoor units............................................................................................22
1.1 Ceiling cassette 4-way.................................................................................................22
2. Outdoor units.........................................................................................52
2.1 Single piping type ........................................................................................................52
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
22/178
22 Ceiling cassette 4 way
Features 6CST0-01A
Ceiling Cassette
1. Indoor unit1.1 Ceiling cassette 4-way1.1.1 Features
Models : LT-C182QLE0, LT-C242PLE0, LT-C302PLE0, LT-C362NLE0, LT-C482MLE0, LT-C602MLE0,
LT-H182QLE0, LT-H242PLE0, LT-H302PLE0, LT-H362NLE0, LT-H482MLE0, LT-H602MLE0
4 Vane Independent Operation
Vane angle control satisfies both users who like direct wind
or indirect wind.And also it prevents cold air draft.
- This function can be controled with new wired remote con-troller
Group control
1) Operation summary
- Where several products are linked, one specific control
device can control a specific number of products.
2) Specific operation
- Connecting line is linked to each of the indoor equipments
for communication. A specific control device is connected
to each of them and this control device can control the
same function.
- Group control function is enabled by cutting an optional
jump wire in the wired remote control. At this time, themain system will not respond in order to prevent data colli-
sion.
- While executing group control command, use the random
data(0-3minutes) in the main body of indoor equipment for
limiting starting current.
- Control device can control up to 16 indoor equipments.
1 2 16
RemoteController
Air flow rate control
All vane operation Individual vane operation
(PQRCUSA0)
Direct air flow Indirect air flow
Individual vane anglecontrol
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
23/178
Ceiling cassette 4 way 23
Features6CST0-01A
Ceiling Cassette
Zero power consumption in standby modeby adopting SMPS (Switching mode power
supply)
Power waste due to standby mode
- Power is wasted if a plug is connected to an outlet even
though the appliance is turned off.
Development of super power-saving SMPS(Switching Mode Power Supply)
- Zero standby power by reducing 90% of standby power.
- No need to pull out every plug when system is not in use.
Low noise with 3-dimensional turbo fan
The most advanced low-noise design.The adoption ofturbo-fan and round type give the most quiet operation.
Built-in drain pump
A standard drain-head height of up to 800mm is possible,
creating the ideal solution for perfect water drainage.
High ceiling operation
According to the height of the installation, it provides vari-
ability of indoor fan motor speed.
If the height of installation is low then you can adjust low
rpm of indoor fan motor. On the other hand if the height of
the installation is high you can adjust high speed of indoorfan motor. Selection of speed can be done by slide switch
at the back of the LCD wired remote controller.
ex: If ceiling height of 2.7-3m(taken as standard for the product) is
exceeded, then the slide switch is iperated in the high mode discharg-ing air at a high volume rate and when below 2.7m, the switch isadjusted to discharge at a lower volume rate.
Noise output measured in anechoic testroom
Drain Pump
Mount Pump Switch assembly,Float
Flexible hose
Drain pump
PVC elbow
PVC
PVC
Max.
800
(18k:Max.7
00)
300mm or less
[Unit : mm]Commondrain pipe
Air velocity distribution
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
24/178
1.1.2 List of functions
Air supply outlet
Airflow direction control(left & right)
Airflow direction control(up & down)
Auto swing(left & right)
Air flow Auto swing(up & down)
Airflow steps(fan/cool/heat)
Chaos swing
Chaos wind(auto wind)
Jet cool(Power wind)
Swirl wind
Deodorizing filter
Air purifying Plasma air purifier
Prefilter(washable / anti-fungus)
Drain pump
InstallationE.S.P. control
Electric heater(operation)
High ceiling operation
Hot startReliability Self diagnosis
Soft dry operation
Auto changeover
Auto cleaning
Auto operation(artificial intelligence)
Auto restart operation
Child lock
Convenience Forced operation
Group control
Sleep mode
Timer(on/off)
Timer(weekly)
Two thermistor control
Standard wired remote controller
Wide Character wired remote controller
Picto wired remote controller
Individual controlDeluxe wired remote controller
Simple wired remote controller
Wired remote controller(for hotel use)
Wireless remote controller(simple)
Wireless LCD remote control
General central controller (Non LGAP)
Dry contact
CAC network function Network Soluation(LGAP)
PDI(power distribution indicator)
PI 485
Zone controlSpecial function kit CTIE
Electro thermostat
Thermistor
OthersTest Function
Vane Control
Auto Elevation Grille
4 4
- -
Auto Auto
- -
O O
4 / 5 / - 4 / 5 / 4
X X
O O
O O
O O
- -
PTPKQ0 PTPKQ0
O O
O O
O O
X X
O O
X OO O
O O
- O
X X
O X
O O
O O
O O
O O
O O
O O
O O
O O
PCRCUSZ0 PCRCUSZ0
PQRCUSA0 PQRCUSA0
PQRCUDS0/PQRCUDS0B/PQRCUDS0S PQRCUDS0/PQRCUDS0B/PQRCUDS0S
PQRCUCA0 PQRCUDA0
X X
X X
PQWRCSF0 PQWRHSF0
X X
PQDSB/PQDSB1/PQDSBC PQDSB / PQDSB1 / PQDSBC
O O
X X
PSNFP14A0 PSNFP14A0
- -- -
- -
- -
O O
O O
- -
FunctionCategory LT-C182QLE0 LT-H182QLE0
Note :
O : Applied, X : Not applied, : No relationOption: Model name & price are different according to options, and assembled in factory with main unit.Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
24 Ceiling cassette 4 way
List of functions 6CST0-01A
Ceiling Cassette
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
25/178
Ceiling cassette 4 way 25
List of functions6CST0-01A
Ceiling Cassette
Air supply outlet
Airflow direction control(left & right)
Airflow direction control(up & down)
Auto swing(left & right)
Air flow Auto swing(up & down)
Airflow steps(fan/cool/heat)
Chaos swing
Chaos wind(auto wind)
Jet cool(Power wind)
Swirl wind
Deodorizing filter
Air purifying Plasma air purifier
Prefilter(washable / anti-fungus)
Drain pump
InstallationE.S.P. control
Electric heater(operation)
High ceiling operation
Hot startReliability Self diagnosis
Soft dry operation
Auto changeover
Auto cleaning
Auto operation(artificial intelligence)
Auto restart operation
Child lock
Convenience Forced operation
Group control
Sleep mode
Timer(on/off)
Timer(weekly)
Two thermistor control
Standard wired remote controller
Wide Character wired remote controller
Picto wired remote controller
Individual controlDeluxe wired remote controller
Simple wired remote controller
Wired remote controller(for hotel use)
Wireless remote controller(simple)
Wireless LCD remote control
General central controller (Non LGAP)
Dry contact
CAC network function Network Soluation(LGAP)
PDI(power distribution indicator)
PI 485
Zone controlSpecial function kit CTIE
Electro thermostat
Thermistor
OthersTest Function
Vane Control
Auto Elevation Grille
4 4
- -
Auto Auto
- -
O O
4 / 5 / - 4 / 5 / 4
X X
O O
O O
O O
X X
PTPKM0 PTPKM0
O O
O O
O O
X X
O O
X OO O
O O
- O
X X
O -
O O
O O
O O
O O
O O
O O
O O
O O
PCRCUSZ0 PCRCUSZ0
PQRCUSA0 PQRCUSA0
PQRCUDS0/PQRCUDS0B/PQRCUDS0S PQRCUDS0/PQRCUDS0B/PQRCUDS0S
PQRCUCA0 PQRCUCA0
- -
X X
PQWRCSF0 PQWRHSF0
X X
PQDSB/PQDSBC PQDSB/PQDSBC
O O
X X
PSNFP14A0 PSNFP14A0
- -- -
- -
- -
O O
O O
PTEGM0 PTEGM0
FunctionCategory LT-C242PLE0 LT-H242PLE0
Note :
O : Applied, X : Not applied, : No relationOption: Model name & price are different according to options, and assembled in factory with main unit.Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
26/178
26 Ceiling cassette 4 way
List of functions 6CST0-01A
Ceiling Cassette
Air supply outlet
Airflow direction control(left & right)
Airflow direction control(up & down)
Auto swing(left & right)
Air flow Auto swing(up & down)
Airflow steps(fan/cool/heat)
Chaos swing
Chaos wind(auto wind)
Jet cool(Power wind)
Swirl wind
Deodorizing filter
Air purifying Plasma air purifier
Prefilter(washable / anti-fungus)
Drain pump
InstallationE.S.P. control
Electric heater(operation)
High ceiling operation
Hot startReliability Self diagnosis
Soft dry operation
Auto changeover
Auto cleaning
Auto operation(artificial intelligence)
Auto restart operation
Child lock
Convenience Forced operation
Group control
Sleep mode
Timer(on/off)
Timer(weekly)
Two thermistor control
Standard wired remote controller
Wide Character wired remote controller
Picto wired remote controller
Individual controlDeluxe wired remote controller
Simple wired remote controller
Wired remote controller(for hotel use)
Wireless remote controller(simple)
Wireless LCD remote control
General central controller (Non LGAP)
Dry contact
CAC network function Network Soluation(LGAP)
PDI(power distribution indicator)
PI 485
Zone controlSpecial function kit CTIE
Electro thermostat
Thermistor
OthersTest Function
Vane Control
Auto Elevation Grille
4 4
- -
Auto Auto
- -
O O
4 / 5 / - 4 / 5 / 4
X X
O O
O O
O O
X X
PTPKM0 PTPKM0
O O
O O
O O
X X
O O
X OO O
O O
- O
X X
O -
O O
O O
O O
O O
O O
O O
O O
O O
PCRCUSZ0 PCRCUSZ0
PQRCUSA0 PQRCUSA0
PQRCUDS0/PQRCUDS0B/PQRCUDS0S PQRCUDS0/PQRCUDS0B/PQRCUDS0S
PQRCUCA0 PQRCUCA0
- -
X X
PQWRCSF0 PQWRHSF0
X X
PQDSB/PQDSBC PQDSB/PQDSBC
O O
X X
PSNFP14A0 PSNFP14A0
- -- -
- -
- -
O O
O O
PTEGM0 PTEGM0
FunctionCategory LT-C302PLE0 LT-H302PLE0
Note :
O : Applied, X : Not applied, : No relationOption: Model name & price are different according to options, and assembled in factory with main unit.Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
27/178
Ceiling cassette 4 way 27
List of functions6CST0-01A
Ceiling Cassette
Note :
O : Applied, X : Not applied, : No relationOption: Model name & price are different according to options, and assembled in factory with main unit.Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
Air supply outlet
Airflow direction control(left & right)
Airflow direction control(up & down)
Auto swing(left & right)
Air flow Auto swing(up & down)
Airflow steps(fan/cool/heat)
Chaos swing
Chaos wind(auto wind)
Jet cool(Power wind)
Swirl wind
Deodorizing filter
Air purifying Plasma air purifier
Prefilter(washable / anti-fungus)
Drain pump
InstallationE.S.P. control
Electric heater(operation)
High ceiling operation
Hot startReliability Self diagnosis
Soft dry operation
Auto changeover
Auto cleaning
Auto operation(artificial intelligence)
Auto restart operation
Child lock
Convenience Forced operation
Group control
Sleep mode
Timer(on/off)
Timer(weekly)
Two thermistor control
Standard wired remote controller
Wide Character wired remote controller
Picto wired remote controller
Individual controlDeluxe wired remote controller
Simple wired remote controller
Wired remote controller(for hotel use)
Wireless remote controller(simple)
Wireless LCD remote control
General central controller (Non LGAP)
Dry contact
CAC network function Network Soluation(LGAP)
PDI(power distribution indicator)
PI 485
Zone controlSpecial function kit CTIE
Electro thermostat
Thermistor
OthersTest Function
Vane Control
Auto Elevation Grille
4 4
- -
Auto Auto
- -
O O
4 / 5 / - 4 / 5 / 4
X X
O O
O O
O O
X X
PTPKM0 PTPKM0
O O
O O
O O
X X
O O
X OO O
O O
- O
X X
O -
O O
O O
O O
O O
O O
O O
O O
O O
PCRCUSZ0 PCRCUSZ0
PQRCUSA0 PQRCUSA0
PQRCUDS0/PQRCUDS0B/PQRCUDS0S PQRCUDS0/PQRCUDS0B/PQRCUDS0S
PQRCUCA0 PQRCUCA0
- -
X X
PQWRCSF0 PQWRHSF0
X X
PQDSB/PQDSBC PQDSB/PQDSBC
O O
X X
PSNFP14A0 PSNFP14A0
- -- -
- -
- -
O O
O O
PTEGM0 PTEGM0
FunctionCategory LT-C362NLE0 LT-H362NLE0
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
28/178
28 Ceiling cassette 4 way
List of functions 6CST0-01A
Ceiling Cassette
Note :
O : Applied, X : Not applied, : No relationOption: Model name & price are different according to options, and assembled in factory with main unit.Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
Air supply outlet
Airflow direction control(left & right)
Airflow direction control(up & down)
Auto swing(left & right)
Air flow Auto swing(up & down)
Airflow steps(fan/cool/heat)
Chaos swing
Chaos wind(auto wind)
Jet cool(Power wind)
Swirl wind
Deodorizing filter
Air purifying Plasma air purifier
Prefilter(washable / anti-fungus)
Drain pump
InstallationE.S.P. control
Electric heater(operation)
High ceiling operation
Hot startReliability Self diagnosis
Soft dry operation
Auto changeover
Auto cleaning
Auto operation(artificial intelligence)
Auto restart operation
Child lock
Convenience Forced operation
Group control
Sleep mode
Timer(on/off)
Timer(weekly)
Two thermistor control
Standard wired remote controller
Wide Character wired remote controller
Picto wired remote controller
Individual controlDeluxe wired remote controller
Simple wired remote controller
Wired remote controller(for hotel use)
Wireless remote controller(simple)
Wireless LCD remote control
General central controller (Non LGAP)
Dry contact
CAC network function Network Soluation(LGAP)
PDI(power distribution indicator)
PI 485
Zone controlSpecial function kit CTIE
Electro thermostat
Thermistor
OthersTest Function
Vane Control
Auto Elevation Grille
4 4
- -
Auto Auto
- -
O O
4 / 5 / - 4 / 5 / 4
X X
O O
O O
O O
X X
PTPKM0 PTPKM0
O O
O O
O O
X X
O O
X OO O
O O
- O
X X
O -
O O
O O
O O
O O
O O
O O
O O
O O
PCRCUSZ0 PCRCUSZ0
PQRCUSA0 PQRCUSA0
PQRCUDS0/PQRCUDS0B/PQRCUDS0S PQRCUDS0/PQRCUDS0B/PQRCUDS0S
PQRCUCA0 PQRCUCA0
- -
X X
PQWRCSF0 PQWRHSF0
X X
PQDSB/PQDSBC PQDSB/PQDSBC
O O
X X
PSNFP14A0 PSNFP14A0
- -- -
- -
- -
O O
O O
PTEGM0 PTEGM0
FunctionCategory LT-C482MLE0 LT-H482MLE0
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
29/178
Ceiling cassette 4 way 29
List of functions6CST0-01A
Ceiling Cassette
Note :
O : Applied, X : Not applied, : No relationOption: Model name & price are different according to options, and assembled in factory with main unit.
Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
Air supply outlet
Airflow direction control(left & right)
Airflow direction control(up & down)
Auto swing(left & right)
Air flow Auto swing(up & down)
Airflow steps(fan/cool/heat)
Chaos swing
Chaos wind(auto wind)
Jet cool(Power wind)
Swirl wind
Deodorizing filter
Air purifying Plasma air purifier
Prefilter(washable / anti-fungus)
Drain pump
InstallationE.S.P. control
Electric heater(operation)
High ceiling operation
Hot startReliability Self diagnosis
Soft dry operation
Auto changeover
Auto cleaning
Auto operation(artificial intelligence)
Auto restart operation
Child lock
Convenience Forced operation
Group control
Sleep mode
Timer(on/off)
Timer(weekly)
Two thermistor control
Standard wired remote controller
Wide Character wired remote controller
Picto wired remote controller
Individual controlDeluxe wired remote controller
Simple wired remote controller
Wired remote controller(for hotel use)
Wireless remote controller(simple)
Wireless LCD remote control
General central controller (Non LGAP)
Dry contact
CAC network function Network Soluation(LGAP)
PDI(power distribution indicator)
PI 485
Zone controlSpecial function kit CTIE
Electro thermostat
Thermistor
OthersTest Function
Vane Control
Auto Elevation Grille
4 4
- -
Auto Auto
- -
O O
4 / 5 / - 4 / 5 / 4
X X
O O
O O
O O
X X
PTPKM0 PTPKM0
O O
O O
O O
X X
O O
X OO O
O O
- O
X X
O -
O O
O O
O O
O O
O O
O O
O O
O O
PCRCUSZ0 PCRCUSZ0
PQRCUSA0 PQRCUSA0
PQRCUDS0/PQRCUDS0B/PQRCUDS0S PQRCUDS0/PQRCUDS0B/PQRCUDS0S
PQRCUCA0 PQRCUCA0
- -
X X
PQWRCSF0 PQWRHSF0
X X
PQDSB/PQDSBC PQDSB/PQDSBC
O O
X X
PSNFP14A0 PSNFP14A0
- -- -
- -
- -
O O
O O
PTEGM0 PTEGM0
FunctionCategory LT-C602MLE0 LT-H602MLE0
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
30/178
1.1.3 Specifications
Note :
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27C(81F) DB /19C(66F) WB- Outdoor Temperature 35C(95F) DB /24C(75F) WB
Heating: - Indoor Temperature 20C(68F) DB/15C(59F) WB
- Outdoor Temperature 7C(44.6F) DB/6C(42.8F) WB
Piping Length - Interconnecting Piping Length 7.5m
- Level Difference of Zero.
Conversion Formula
kW = Btu/h
0.0002931CFM = CMM 35.3
Decorative Panel Model
Power Supply / V / Hz
Cooling Capacity kW
Btu/h
Heating Capacity kW
Btu/h
Current Nominal Running Current A
Fan Motor Type
Fan Type
Motor Output(W) x No. of Unit
Air Flow Rate CMM
(H / M / L) cfm
External Static Pressure mmAqCapacitor F / Vac
Drive
Coil Row x Column x FPI
Dimensions Body mm(inch)
(W x H x D) Decorative Panel mm(inch)
Net Weight Body kg (lbs)
Decorative Panel kg (lbs)
Air Filter
Sound Level (H / M / L) dB(A)+3
Piping Liquid mm (inch)
Connections Gas mm (inch)Drain(OD/ID) mm
Dehumidification Rate l/h
Safety Devices
Temperature Sensor
Referigerant
Referigerant Control
Connectable Outdoor Unit
Power and Transmission Interunit Cable No. x mm2
Model LT-C182QLE0 LT-H182QLE0
Indoor unit type Ceilling Cassette - 4way
PT-UQC PT-UQC
1 / 220 / 60 1 / 220 / 60
5.28 5.28
18,000 18,000
- 5.28
- 18,000
8.4 8.4
BLDC BLDC
Turbo Fan Turbo Fan
43 x 1 43 x 1
12 / 11 / 10 12 / 11 / 10
424 / 388 / 353 424 / 388 / 353
- -220 / 450 220 / 450
Direct Direct
2 x 10 x 18 2 x 10 x 18
570 x 570 x 256 (22.4 x 22.4 x 10.0) 570 x 570 x 256 (22.4 x 22.4 x 10.0)
700 x 700 x 30 (27.6 x 27.6 x 1.2) 700 x 700 x 30 (27.6 x 27.6 x 1.2)
15.5(34.2) 15.5(34.2)
3(6.6) 3(6.6)
Long life filter Long life filter
38 / 36 / 33 38 / 36 / 33
6.35 (1/4) 6.35 (1/4)
12.7 (1/2) 12.7 (1/2)32 / 25 32 / 25
2.4 2.4
Fuse, Thermal Protcector
Thermistor Thermistor
R22 R22
Capillary Tube Capillary Tube
LTUC182QLE0 LTUH182QLE0
4 x 0.75 (Including Earth) 5 x 0.75 (Including Earth)
30 Ceiling cassette 4 way
Specifications 6CST0-01A
Ceiling Cassette
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
31/178
Ceiling cassette 4 way 31
6CST0-01A
Ceiling Cassette
Note :
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27C(81F) DB /19C(66F) WB- Outdoor Temperature 35C(95F) DB /24C(75F) WB
Heating: - Indoor Temperature 20C(68F) DB/15C(59F) WB
- Outdoor Temperature 7C(44.6F) DB/6C(42.8F) WB
Piping Length - Interconnecting Piping Length 7.5m
- Level Difference of Zero.
Conversion Formula
kW = Btu/h
0.0002931CFM = CMM 35.3
Decorative Panel Model
Power Supply / V / Hz
Cooling Capacity kW
Btu/h
Heating Capacity kW
Btu/h
Current Nominal Running Current A
Fan Motor Type
Fan Type
Motor Output(W) x No. of Unit
Air Flow Rate CMM
(H / M / L) cfm
External Static Pressure mmAqCapacitor F / Vac
Drive
Coil Row x Column x FPI
Dimensions Body mm(inch)
(W x H x D) Decorative Panel mm(inch)
Net Weight Body kg (lbs)
Decorative Panel kg (lbs)
Air Filter
Sound Level (H / M / L) dB(A)+3
Piping Liquid mm (inch)
Connections Gas mm (inch)Drain(OD/ID) mm
Dehumidification Rate l/h
Safety Devices
Temperature Sensor
Referigerant
Referigerant Control
Connectable Outdoor Unit
Power and Transmission Interunit Cable No. x mm2
Model LT-C242PLE0 LT-H242PLE0
Indoor unit type Ceilling Cassette - 4way
PT-UMC PT-UMC
1 / 220 / 60 1 / 220 / 60
7.06 7.06
24,100 24,100
- 7.06
- 24,100
0.5 0.5
BLDC BLDC
Turbo fan Turbo fan
90 x 1 90 x 1
18.7 / 17.0 / 14.3 18.7 / 17.0 / 14.3
636 / 600 / 495 636 / 600 / 495
- -220 / 450 220 / 450
Direct Direct
2Rx8Cx19FPI 2Rx8Cx19FPI
840 x 204 x 840 (33.1 x 8.0 x 33.1) 840 x 204 x 840 (33.1 x 8.0 x 33.1)
950 x 25 x 950 (37.4 x 1.0 x 37.4) 950 x 25 x 950 (37.4 x 1.0 x 37.4)
20.8(45.9) 20.8(45.9)
5(11.0) 5(11.0)
Long life filter Long life filter
39 / 37 / 33 39 / 37 / 33
6.35(1/4) 6.35(1/4)
15.88(5/8) 15.88(5/8)32 / 25 32 / 25
3.3 3.3
Fuse, thermal protector for fan motor
Thermistor Thermistor
R22 R22
Cappilary Tube Cappilary Tube
1 1
4 x 0.75(Including earth) 5 x 0.75(Including earth)
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
32/178
32 Ceiling cassette 4 way
6CST0-01A
Ceiling Cassette
Specifications
Note :
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27C(81F) DB /19C(66F) WB- Outdoor Temperature 35C(95F) DB /24C(75F) WB
Heating: - Indoor Temperature 20C(68F) DB/15C(59F) WB
- Outdoor Temperature 7C(44.6F) DB/6C(42.8F) WB
Piping Length - Interconnecting Piping Length 7.5m
- Level Difference of Zero.
Conversion Formula
kW = Btu/h
0.0002931CFM = CMM 35.3
Decorative Panel Model
Power Supply / V / Hz
Cooling Capacity kW
Btu/h
Heating Capacity kW
Btu/h
Current Nominal Running Current A
Fan Motor Type
Fan Type
Motor Output(W) x No. of Unit
Air Flow Rate CMM
(H / M / L) cfm
External Static Pressure mmAq
Capacitor F / Vac
Drive
Coil Row x Column x FPI
Dimensions Body mm(inch)
(W x H x D) Decorative Panel mm(inch)
Net Weight Body kg (lbs)
Decorative Panel kg (lbs)
Air Filter
Sound Level (H / M / L) dB(A)+3
Piping Liquid mm (inch)
Connections Gas mm (inch)Drain(OD/ID) mm
Dehumidification Rate l/h
Safety Devices
Temperature Sensor
Referigerant
Referigerant Control
Connectable Outdoor Unit
Power and Transmission Interunit Cable No. x mm2
Model LT-C302PLE0 LT-H302PLE0
Indoor unit type Ceilling Cassette - 4way
PT-UMC PT-UMC
1 / 220 / 60 1 / 220 / 60
8.79 8.79
30,000 30,000
- 8.79
- 30,000
0.5 0.5
BLDC BLDC
Turbo fan Turbo fan
90 x 1 90 x 1
23.0 / 20.0 / 16.0 23.0 / 20.0 / 16.0
812 / 706 / 565 812 / 706 / 565
- -
220 / 450 220 / 450
Direct Direct
2Rx8Cx19FPI 2R x 8C x 19FPI
840 x 204 x 840 (33.1 x 8.0 x 33.1) 840 x 204 x 840 (33.1 x 8.0 x 33.1)
950 x 25 x 950 (37.4 x 1.0 x 37.4) 950 x 25 x 950 (37.4 x 1.0 x 37.4)
20.8(45.9) 20.8(45.9)
5(11.0) 5(11.0)
Long life filter Long life filter
44 / 41 / 38 44 / 41 / 38
6.35(1/4) 6.35(1/4)
15.88(5/8) 15.88(5/8)32 / 25 32 / 25
3.5 3.5
Fuse, thermal protector for fan motor
Thermistor Thermistor
R22 R22
Cappilary Tube Cappilary Tube
1 1
4 x 0.75(Including earth) 5 x 0.75(Including earth)
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
33/178
Ceiling cassette 4 way 33
6CST0-01A
Ceiling Cassette
Specifications
Note :
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27C(81F) DB /19C(66F) WB- Outdoor Temperature 35C(95F) DB /24C(75F) WB
Heating: - Indoor Temperature 20C(68F) DB/15C(59F) WB
- Outdoor Temperature 7C(44.6F) DB/6C(42.8F) WB
Piping Length - Interconnecting Piping Length 7.5m
- Level Difference of Zero.
Conversion Formula
kW = Btu/h
0.0002931CFM = CMM 35.3
Decorative Panel Model
Power Supply / V / Hz
Cooling Capacity kW
Btu/h
Heating Capacity kW
Btu/h
Current Nominal Running Current A
Fan Motor Type
Fan Type
Motor Output(W) x No. of Unit
Air Flow Rate CMM
(H / M / L) cfm
External Static Pressure mmAqCapacitor F / Vac
Drive
Coil Row x Column x FPI
Dimensions Body mm(inch)
(W x H x D) Decorative Panel mm(inch)
Net Weight Body kg (lbs)
Decorative Panel kg (lbs)
Air Filter
Sound Level (H / M / L) dB(A)+3
Piping Liquid mm (inch)
Connections Gas mm (inch)Drain(OD/ID) mm
Dehumidification Rate l/h
Safety Devices
Temperature Sensor
Referigerant
Referigerant Control
Connectable Outdoor Unit
Power and Transmission Interunit Cable No. x mm2
Model LT-C362NLE0 LT-H362NLE0
Indoor unit type Ceilling Cassette - 4way
PT-UMC PT-UMC
1 / 220 / 60 1 / 220 / 60
10.55 10.55
36,000 36,000
- 10.55
- 36,000
0.7 0.7
BLDC BLDC
Turbo fan Turbo fan
100 x 1 100 x 1
25.0 / 23.0 / 21.0 25.0 / 23.0 /21.0
883 / 812 / 742 883 / 812 / 742
- -220 / 450 220 / 450
Direct Direct
2Rx10Cx19FPI 2R x 10C x 19FPI
840 x 246 x 840 (33.1 x 9.7 x 33.1) 840 x 246 x 840 (33.1 x 9.7 x 33.1)
950 x 25 x 950 (37.4 x 1.0 x 37.4) 950 x 25 x 950 (37.4 x 1.0 x 37.4)
23.5(51.8) 23.5(51.8)
5(11.0) 5(11.0)
Long life filter Long life filter
42 / 40 / 37 42 / 40 / 37
6.35(1/4) 6.35(1/4)
15.88(5/8) 15.88(5/8)32 / 25 32 / 25
4.5 4.5
Fuse, thermal protector for fan motor
Thermistor Thermistor
R22 R22
Cappilary Tube Cappilary Tube
1 1
4 x 0.75(Including earth) 5 x 0.75(Including earth)
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
34/178
34 Ceiling cassette 4 way
6CST0-01A
Ceiling Cassette
Specifications
Decorative Panel Model
Power Supply / V / Hz
Cooling Capacity kW
Btu/h
Heating Capacity kW
Btu/h
Current Nominal Running Current A
Fan Motor Type
Fan Type
Motor Output(W) x No. of Unit
Air Flow Rate CMM
(H / M / L) cfm
External Static Pressure mmAqCapacitor F / Vac
Drive
Coil Row x Column x FPI
Dimensions Body mm(inch)
(W x H x D) Decorative Panel mm(inch)
Net Weight Body kg (lbs)
Decorative Panel kg (lbs)
Air Filter
Sound Level (H / M / L) dB(A)+3
Piping Liquid mm (inch)
Connections Gas mm (inch)Drain(OD/ID) mm
Dehumidification Rate l/h
Safety Devices
Temperature Sensor
Referigerant
Referigerant Control
Connectable Outdoor Unit
Power and Transmission Interunit Cable No. x mm2
Model LT-C482MLE0 LT-H482MLE0
Indoor unit type Ceilling Cassette - 4way
PT-UMC PT-UMC
1 / 220 / 60 1/220/60
14.06 14.06
48,000 48,000
- 14.06
- 48,000
1.0 1.0
BLDC BLDC
Turbo fan Turbo fan
124 x 1 124x1
33.0 / 30.0 / 26.0 33.0 / 30.0 / 26.0
1,165 / 1,060 / 918 1,165 / 1,060 / 918
- -220 / 450 220 / 450
Direct Direct
2Rx12Cx19FPI 2R x 12C x 19FPI
840 x 288 x 840 (33.1 x 11.3 x 33.1) 840 x 288 x 840 (33.1 x 11.3 x 33.1)
950 x 25 x 950 (37.4 x 1.0 x 37.4) 950 x 25 x 950 (37.4 x 1.0 x 37.4)
25.6(56.4) 25.6(56.4)
5(11.0) 5(11.0)
Long life filter Long life filter
47 / 44 / 41 47 / 44 / 41
9.52(3/8) 9.52(3/8)
19.05(3/4) 19.05(3/4)32 / 25 32 / 25
5.5 5.5
Fuse, thermal protector for fan motor
Thermistor Thermistor
R22 R22
Cappilary Tube Cappilary Tube
1 1
4 x 1.0(Including earth) 5 x 1.0(Including earth)
Note :
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27C(81F) DB /19C(66F) WB
- Outdoor Temperature 35C(95F) DB /24C(75F) WB
Heating: - Indoor Temperature 20C(68F) DB/15C(59F) WB
- Outdoor Temperature 7C(44.6F) DB/6C(42.8F) WB
Piping Length - Interconnecting Piping Length 7.5m
- Level Difference of Zero.
Conversion Formula
kW = Btu/h 0.0002931CFM = CMM 35.3
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
35/178
Ceiling cassette 4 way 35
6CST0-01A
Ceiling Cassette
Specifications
Decorative Panel Model
Power Supply / V / Hz
Cooling Capacity kW
Btu/h
Heating Capacity kW
Btu/h
Current Nominal Running Current A
Fan Motor Type
Fan Type
Motor Output(W) x No. of Unit
Air Flow Rate CMM
(H / M / L) cfm
External Static Pressure mmAqCapacitor F / Vac
Drive
Coil Row x Column x FPI
Dimensions Body mm(inch)
(W x H x D) Decorative Panel mm(inch)
Net Weight Body kg (lbs)
Decorative Panel kg (lbs)
Air Filter
Sound Level (H / M / L) dB(A)+3
Piping Liquid mm (inch)
Connections Gas mm (inch)Drain(OD/ID) mm
Dehumidification Rate l/h
Safety Devices
Temperature Sensor
Referigerant
Referigerant Control
Connectable Outdoor Unit
Power and Transmission Interunit Cable No. x mm2
Model LT-C602MLE0 LT-H602MLE0
Indoor unit type Ceilling Cassette - 4way
PT-UMC PT-UMC
1 / 220 / 60 1 / 220 / 60
17.58 17.58
60,000 60,000
- 17.58
- 60,000
1.0 1.0
BLDC BLDC
Turbo fan Turbo fan
124 x 1 124 x 1
34.0 / 31.0 /28.0 34.0 / 31.0 / 28.0
1,200 / 1,090 / 989 1,200 / 1,095 / 989
- -220 / 450 220 / 450
Direct Direct
2Rx12Cx19FPI 2Rx12Cx19FPI
840 x 288 x 840 (33.1 x 11.3 x 33.1) 840 x 288 x 840 (33.1 x 11.3 x 33.1)
950 x 25 x 950 (37.4 x 1.0 x 37.4) 950 x 25 x 950 (37.4 x 1.0 x 37.4)
25.6(56.4) 25.6(56.4)
5(11.0) 5(11.0)
Long life filter Long life filter
49 / 46 / 43 49 / 46 / 43
9.52(3/8) 9.52(3/8)
19.05(3/4) 19.05(3/4)32 / 25 32 / 25
6.3 6.3
Fuse, thermal protector for fan motor
Thermistor Thermistor
R22 R22
Cappilary Tube Cappilary Tube
1 1
4 x 1.0(Including earth) 5 x 1.0(Including earth)
Note :
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27C(81F) DB /19C(66F) WB- Outdoor Temperature 35C(95F) DB /24C(75F) WB
Heating: - Indoor Temperature 20C(68F) DB/15C(59F) WB
- Outdoor Temperature 7C(44.6F) DB/6C(42.8F) WB
Piping Length - Interconnecting Piping Length 7.5m
- Level Difference of Zero.
Conversion Formula
kW = Btu/h
0.0002931CFM = CMM 35.3
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
36/178
1.1.4 Dimensions
36 Ceiling cassette 4 way
Dimensions 6CST0-01A
Ceiling Cassette
1.Unitshouldbeinstalledincompliancewiththeinstallationmanual
inthe
productbox.
2.Unitshallbegroundedinaccordancewiththelocalregulationsor
applicablenationalcodes.
3.TheU
nitispoweredfromt
heoutdoorunit.Therefore
powercable
shouldbeconnectedwiththeoutdoorunit.
76,Seongsan-don
g,ChangwonCity,Gyeongnam,
641-713,Korea
www.lge.com/airco
nditioner
CHASSISCODE:TQ
Drainpipeconnection
Airsuctiongrille
PartName
Decorationpanel
Airdischargegrille
Liquidpipeconnection
Gaspipeconnection
65
No. 2 431
Remark
TechnicalSpecification
LT-C182QLE0+PT-UQC
LT-H182QLE0+PT-UQC
Ce
ilingCassette4-way+DecorationPanel
Note
7
Powersupplyconnection
HeatingCapacity
CoolingCapacity
Powersupply
Model
LT-C182QLE
0
1/
220V/60
Hz
5.2
8
18,0
00
- -
6.3
5(1/4)
12.7
(1/2)
32/25
LT-H182QLE0
1/
220V/60Hz
5.2
8
18,0
00
5.2
8
18,0
00
6.3
5(1/4)
12.7
(1/2)
32/25
Liquid()
Gas()
Drain(OD/ID)
Piping
Co
nnections
mm(inch)
mm
mm(inch)
kW
/V/Hz
kW
Btu/h
Btu/h
700
473
55
380(Airoutlethole)
700
378.6380(Airoutlethole)
172
378.6
4-R2
0 22.5
570
570
517
517
461
523
3019142.5
95.512559.5
570
7694
256
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
37/178
Ceiling cassette 4 way 37
Dimensions6CST0-01A
Ceiling Cassette
1.Unitshouldbeinstalledincompliancewiththeinstallationmanual
inthe
productbox.
2.Unitshallbegroundedinaccordancewiththelocalregulationsor
applicablenationalcodes.
3.TheU
nitispoweredfromtheoutdoorunit.Therefore
powercable
shouldbeconnectedwiththeoutdoorunit.
76,Seongsan-dong,ChangwonCity,Gyeongnam,
641-713,Korea
www.lge.com/airco
nditioner
CHASSISCODE:TP
Drainpipeconnection
Airsuctiongrille
PartName
Decorationpanel
Airdischargegrille
Liquidpipeconnection
Gaspipeconnection
65
No. 2 431
Remark
HeatingCapacity
CoolingCapacity
Powersupply
Model
LT-C242PLE
0
1/
220V/60
Hz
7.0
6
24,1
00
- -
6.3
5(1/4)
15.8
8(5/8)
32/25
LT-C302PLE0
1/
220V/60Hz
8.7
9
30,0
00
- -
6.3
5(1/4)
15.8
8(5/8)
32/25
Liquid()
Gas()
Drain(OD/ID)
Piping
Co
nnections
mm(inch)
mm
mm(inch)
kW
/V/Hz
kW
Btu/h
Btu/h
TechnicalSpecification
LT-C242PLE0+PT-UMC
LT-C302PLE0+PT-UMC
Ce
ilingCassette4-way+DecorationPanel
Note7
Powersupplyconnection
618
950
618
684
840
671
7
87
500(Airoutlethole)
998260
500(Airoutlethole)
4-R2
0
292
734
787
840
840
60
80
108
54
950
25
204
40 65
6
7
5
4
3 1 2
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
38/178
38 Ceiling cassette 4 way
Dimensions 6CST0-01A
Ceiling Cassette
1.Unitshouldbeinstalledincompliancewiththeinstallationmanual
inthe
productbox.
2.Unitshallbegroundedinaccordancewiththelocalregulationsor
applicablenationalcodes.
3.TheU
nitispoweredfromtheoutdoorunit.Therefore
powercable
shouldbeconnectedwiththeoutdoorunit.
76,Seongsan-dong,ChangwonCity,Gyeongnam,
641-713,Korea
www.lge.com/airco
nditioner
CHASSISCODE:TP
Drainpipeconnection
Airsuctiongrille
PartName
Decorationpanel
Airdischargegrille
Liquidpipeconnection
Gaspipeconnection
65
No. 2 431
Remark
HeatingCapacity
CoolingCapacity
Powersupply
Model
LT-H242PLE
0
1/
220V/60
Hz
7.0
6
24,1
00
7.0
6
24,1
00
6.3
5(1/4)
15.8
8(5/8)
32/25
LT-H302PLE0
1/
220V/60Hz
8.7
9
30,0
00
8.7
9
30,0
00
6.3
5(1/4)
15.8
8(5/8)
32/25
Liquid()
Gas()
Drain(OD/ID)
Piping
Co
nnections
mm(inch)
mm
mm(inch)
kW
/V/Hz
kW
Btu/h
Btu/h
TechnicalSpecification
LT-H242PLE0+PT-UMC
LT-H302PLE0+PT-UMC
Ce
ilingCassette4-way+DecorationPanel
Note7
Powersupplyconnection
618
950
618
684
840
671
7
87
500(Airoutlethole)
998260
500(Airoutlethole)
4-R2
0
292
734
787
840
840
60
80
108
54
950
25
204
40 65
6
7
5
4
3 1 2
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
39/178
Ceiling cassette 4 way 39
Dimensions6CST0-01A
Ceiling Cassette
1.Unitshouldbeinstalledincompliancewiththeinstallationmanual
inthe
productbox.
2.Unitshallbegroundedinaccordancewiththelocalregulationsor
applicablenationalcodes.
3.TheU
nitispoweredfromtheoutdoorunit.Therefore
powercable
shouldbeconnectedwiththeoutdoorunit.
76,Seongsan-dong,ChangwonCity,Gyeongnam,
641-713,Korea
www.lge.com/airco
nditioner
CHASSISCODE:TN
Drainpipeconnection
Airsuctiongrille
PartName
Decorationpanel
Airdischargegrille
Liquidpipeconnection
Gaspipeconnection
65
No. 2 431
Remark
TechnicalSpecification
LT-C362NLE0+PT-UMC
LT-H362NLE0+PT-UMC
Ce
ilingCassette4-way+DecorationPanel
Note7
Powersupplyconnection
HeatingCapacity
CoolingCapacity
Powersupply
Model
LT-C362NLE
0
1/
220V/60
Hz
10.5
5
36,0
00
- -
6.3
5(1/4)
15.8
8(5/8)
32/25
LT-H362NLE0
1/
220V/60Hz
10.5
5
36,0
00
10.5
5
36,0
00
6.3
5(1/4)
15.8
8(5/8)
32/25
Liquid()
Gas()
Drain(OD/ID)
Piping
Co
nnections
mm(inch)
mm
mm(inch)
kW
/V/Hz
kW
Btu/h
Btu/h
6
7
5
4
3 1 2
618
292
4-R
20500(Airoutlethole)
618950
671
500(Airoutlethole)
734950
54
25
787
787
840
684
840
6540
10860
840
80
608299
246
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
40/178
40 Ceiling cassette 4 way
Dimensions 6CST0-01A
Ceiling Cassette
1.Unitshouldbeinstalledincompliancewiththeinstallationmanual
inthe
productbox.
2.Unitshallbegroundedinaccordancewiththelocalregulationsor
applicablenationalcodes.
3.TheU
nitispoweredfromtheoutdoorunit.Therefore
powercable
shouldbeconnectedwiththeoutdoorunit.
76,Seongsan-dong,ChangwonCity,Gyeongnam,
641-713,Korea
www.lge.com/airco
nditioner
CHASSISCODE:TM
Drainpipeconnection
Airsuctiongrille
PartName
Decorationpanel
Airdischargegrille
Liquidpipeconnection
Gaspipeconnection
65
No. 2 431
Remark
TechnicalSpecification
LT-C482MLE0+PT-UMC
LT-C602MLE0+PT-UMC
Ce
ilingCassette4-way+DecorationPanel
Note7
Powersupplyconnection
HeatingCapacity
CoolingCapacity
Powersupply
Model
LT-C482MLE
0
1/
220V/60
Hz
14.0
6
48,0
00
- -
9.5
2(3/8)
19.0
5(3/4
)
32/25
LT-C602MLE0
1/
220V/60Hz
17.5
8
60,0
00
- -
9.5
2(3/8)
19.0
5(3/4)
32/25
Liquid()
Gas()
Drain(OD/ID)
Piping
Co
nnections
mm(inch)
mm
mm(inch)
kW
/V/Hz
kW
Btu/h
Btu/h
6
7
5
4
3 1 2
618
292
4-R
20500(Airoutlethole)
500(Airoutlethole)
734950
618
950
671
54
25
787
840
78684
840
787
110
60
840
80
14840
70135183
288
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
41/178
Ceiling cassette 4 way 41
Dimensions6CST0-01A
Ceiling Cassette
1.Unitshouldbeinstalledincompliancewiththeinstallationmanual
inthe
productbox.
2.Unitshallbegroundedinaccordancewiththelocalregulationsor
applicablenationalcodes.
3.TheU
nitispoweredfromtheoutdoorunit.Therefore
powercable
shouldbeconnectedwiththeoutdoorunit.
76,Seongsan-dong,ChangwonCity,Gyeongnam,
641-713,Korea
www.lge.com/airco
nditioner
CHASSISCODE:TM
Drainpipeconnection
Airsuctiongrille
PartName
Decorationpanel
Airdischargegrille
Liquidpipeconnection
Gaspipeconnection
65
No. 2 431
Remark
TechnicalSpecification
LT-H482MLE0+PT-UMC
LT-H602MLE0+PT-UMC
Ce
ilingCassette4-way+DecorationPanel
Note7
Powersupplyconnection
HeatingCapacity
CoolingCapacity
Powersupply
Model
LT-H482MLE
0
1/
220V/60
Hz
14.0
6
48,0
00
14.0
6
48,0
00
9.5
2(3/8)
19.0
5(3/4)
32/25
LT-H602MLE0
1/
220V/60Hz
17.5
8
60,0
00
17.5
8
60,0
00
9.5
2(3/8)
19.0
5(3/4)
32/25
Liquid()
Gas()
Drain(OD/ID)
Piping
Co
nnections
mm(inch)
mm
mm(inch)
kW
/V/Hz
kW
Btu/h
Btu/h
6
7
5
4
3 1 2
618
292
4-R
20500(Airoutlethole)
500(Airoutlethole)
734950
618
950
671
54
25
787
840
78684
840
787
110
60
840
80
14840
70135183
288
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
42/178
1.1.5 Piping diagrams
Models : LT-C182QLE0, LT-H182QLE0
42 Ceiling cassette 4 way
Piping diagrams 6CST0-01A
Ceiling Cassette
Indoor Unit
Heat
Exchanger(Evaporator)
Gas Side
Cooling
Heating
Liquid SideCapillary Tube
Th1
Th2
LOC. Description PCB Connector
Th1 Thermistor for indoor air temperature CN_ROOM
Th2 Thermistor for evaporating temperature CN_PIPE/IN
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
43/178
Ceiling cassette 4 way 43
Piping diagrams6CST0-01A
Ceiling Cassette
HeatE
xchanger
(Eva
porator)
Gas Side
Liquid SideCapillary Tube
Th1
Th2
LOC. Description PCB Connector
Th1 Thermistor for indoor air temperature CN_ROOM
Th2 Thermistor for evaporating temperature CN_PIPE1
CoolingHeating
Models : LT-C242PLE0, LT-C302PLE0, LT-C362NLE0, LT-C482MLE0, LT-C602MLE0,
LT-H242PLE0, LT-H302PLE0, LT-H362NLE0, LT-H482MLE0, LT-H602MLE0
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
44/178
44 Ceiling cassette 4 way
Wiring diagrams 6CST0-01A
Ceiling Cassette
1.1.6 Wiring diagrams
1) Wiring diagrams
Models : LT-C182QLE0
CN-D/PUMP
CN-POWER CN-VANE2 CN-VANE1
CN-DISPLAY
CN-MOTOR1
CN-REMO
CN-FLOATCN-ROOM
CN-OPTION
CN-PIPE/IN
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
45/178
Ceiling cassette 4 way 45
Wiring diagrams6CST0-01A
Ceiling Cassette
Models : LT-H182QLE0
CN-D/PUMP
CN-POWER CN-VANE2 CN-VANE1
CN-DISPLAY
CN-MOTOR1
CN-REMO
CN-FLOATCN-ROOM
CN-OPTION
CN-PIPE/IN
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
46/178
46 Ceiling cassette 4 way
Wiring diagrams 6CST0-01A
Ceiling Cassette
Models : LT-C242PLE0, LT-C302PLE0, LT-C362NLE0, LT-C482MLE0, LT-C602MLE0
CN-D/PUMP
CN-POWER CN-VANE2 CN-VANE1
CN-DISPLAY
CN-MOTOR1
CN-REMO
CN-FLOATCN-ROOM
CN-OPTION
CN-PIPE/IN
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
47/178
Ceiling cassette 4 way 47
6CST0-01A
Ceiling Cassette
Wiring diagrams
Models : LT-H242PLE0, LT-H302PLE0, LT-H362NLE0, LT-H482MLE0, LT-H602MLE0
CN-POWER
CN-ROOMCN-FLOAT
CN-MOTORCN-DPUMPCN-DISPLAY
CN-PIPE1CN-REMOCN-VANE1CN-VANE2
CN-OPTION
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
48/178
48 Ceiling cassette 4 way
Air flow and temperature distributions (reference data) 6CST0-01A
Ceiling Cassette
1.1.7 Air flow and temperature distribution (reference data)
Model : 24kBtu/h
Cooling Heating
Air velocity [m/s]
2.7m
2m
1m
0m4m3m3m 2m2m 1m0m1m4m
Temperature [C]
2.7m
2m
1m
0m4m3m3m 2m2m 1m0m1m4m
Air velocity [m/s]
2.7m
2m
1m
0m4m3m3m 2m2m 1m0m1m4m
Temperature [C]
2.7m
2m
1m
0m4m3m3m 2m2m 1m0m1m4m
2.0
1833 33
30 30
27 2724 2421 21
1820 20
22 22
24 24
2.0 2.02.0
1.5 1.5 1.51.5
1.0 1.0 1.01.0
0.5 0.5 0.50.5
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
49/178
Ceiling cassette 4 way 49
Sound levels6CST0-01A
Ceiling Cassette
1.1.8 Sound levels
Overall
Sound pressure level
Notes:
- Sound measured at 1.5m away from the center of the unit.- Data is valid at free field condition.- Data is valid at nominal operation condition.
- Reference accoustic pressure 0dB=20Pa.- Sound level will vary depending on a range of factors such asthe construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.- The operating conditions are assumed to be standard.
1.5m
Ceiling
Model
LT-C182PLE0
LT-C242PLE0
LT-C302PLE0
LT-C362NLE0
LT-C482MLE0
LT-C602MLE0
Sound levels[dB(A)]
H M L
38
39
44
42
47
49
36
37
41
40
44
46
33
33
38
37
41
43
Model
LT-H182PLE0
LT-H242PLE0
LT-H302PLE0
LT-H362NLE0
LT-H482MLE0
LT-H602MLE0
Sound levels[dB(A)]
H M L
38
39
44
42
47
49
36
37
41
40
44
46
33
33
38
37
41
43
OctaveBandSoundPressureLevel(dB
re20Pa)
Octave Band Center Frequency (Hz)
Octave
BandSoundPressureLevel(dBre20Pa)
Octave Band Center Frequency (Hz)
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000 8000
OctaveBandSoundPressureLevel(dBre20Pa)
Octave Band Center Frequency (Hz)
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
Approximate
Hearing
Threshold
High
MiddleLow
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000 8000
OctaveBandSoundPressureLevel(dBre20Pa)
Octave Band Center Frequency (Hz)
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
Approximate
Hearing
Threshold
High
MiddleLow
125 500 2000 8000
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
10
20
30
40
50
60
70
80
HighMiddleLow
ApproximateHearingThreshold
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000 8000
Octave
BandSoundPressureLevel(dBre20Pa)
Octave Band Center Frequency (Hz)
HighMiddleLow
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
ApproximateHearingThreshold
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000 8000
Octave
BandSoundPressureLevel(dBre20Pa)
Octave Band Center Frequency (Hz)
HighMiddleLow
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
ApproximateHearingThreshold
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000 8000
HighMid
Low
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
ApproximateHearingThreshold
HighMiddleLow
LT-C182QLE0 LT-H182QLE0LT-C242PLE0LT-H242PLE0
LT-C306PLE0
LT-H306PLE0
LT-C362NLE0
LT-H362NLE0
LT-C482MLE0
LT-H482MLE0
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
50/178
50 Ceiling cassette 4 way
Sound levels 6CST0-01A
Ceiling Cassette
LT-C602MLE0
LT-H602MLE0
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000 8000
OctaveBandSoundPressureLevel(dBre20Pa)
Octave Band Center Frequency (Hz)
High
MiddleLow
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
Approximate
Hearing
Threshold
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
51/178
Ceiling cassette 4 way 51
Controller6CST0-01A
Ceiling Cassette
1.1.9 Controller
Operation indication screen
Set temperature button
Wireless remote controllerReceiver
Some kind of product could not
receive wireless signal.
Ventilation button
Operation mode selection
button
Sub-function button
Function setting button
Exit utton
On/ Off buttonRoom temperature button
Fan speed button
Air flow button
Reservation/ Time setting
button
Setting/ Cancel button
Up, Down, Left, Right
1
9
11
12
3
5
6
2
4 10
13
14
7
8
15
2
6
8
1
1
1
15
Some functions may not be operated and displayed depending on the product type.
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
52/178
52 Outdoor unit
Power supply 6CST0-01A
Ceiling Cassette
2. Outdoor units2.1 Single piping type2.1.1. Power supply
Outdoor unitIndoor unitEarth wire
Power supply
Circuit breaker
Type Outdoor unit Capacity [kBtu/h(kW)] Circuit breaker capacity Power supply
LT-C182QLE0 18(5.28) 20A
LT-C242PLE0 24.1(7.06) 30A
LT-C302PLE0 30(8.79) 30A1, 220V, 60HzCooling only
LT-C362NLE0 36(10.55) 30A
LT-C482MLE0 48(14.06) 50A
LT-C602MLE0 60(17.58) 50A
LT-H182QLE0 18(5.28) 20A
LT-H242PLE0 24.1(7.06) 30A
LT-H302PLE0 30(8.79) 30AHeat Pump
LT-H362NLE0 36(10.55) 30A1, 220V, 60Hz
LT-H482MLE0 48(14.06) 50A
LT-H602MLE0 60(17.58) 50A
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
53/178
Outdoor unit 53
List of functions6CST0-01A
Ceiling Cassette
Defrost / Deicing
High Pressure Switch
Low Pressure Switch
Reliability Phase protectionRestart Delay (3-minutes)
Self Diagnosis
Soft Start
Test Function
ConvenienceAuto Changeover
Auto Restart Operation
CAC NetworkCentral control(LGAP)
FunctionPDI(Power Distribution Indicator)
PI485
Special Function Kit Low Ambient Kit
Others Thermistor
FunctionCategory LT-C182QLE0 LT-H182QLE0
X O
O O
X X
X XO O
O O
X X
X X
X O
O O
Accessory Accessory
X X
Accessory Accessory
X X
- -
2.1.2 List of functions
Note :
O : Applied, X : Not applied, : No relation
Option: Model name & price are different according to options, and assembled in factory with main unit.
Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
54/178
54 Outdoor unit
List of functions 6CST0-01A
Ceiling Cassette
Defrost / Deicing
High Pressure Switch
Low Pressure Switch
Reliability Phase protectionRestart Delay (3-minutes)
Self Diagnosis
Soft Start
Test Function
ConvenienceAuto Changeover
Auto Restart Operation
CAC NetworkCentral control(LGAP)
FunctionPDI(Power Distribution Indicator)
PI485
Special Function Kit Low Ambient Kit
Others Thermistor
FunctionCategory LT-C242PLE0 LT-H242PLE0
X O
O O
X X
X XO O
O O
X X
X X
X O
O O
Accessory Accessory
X X
Accessory Accessory
X X
- -
Note :
O : Applied, X : Not applied, : No relation
Option: Model name & price are different according to options, and assembled in factory with main unit.
Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
55/178
Outdoor unit 55
List of functions6CST0-01A
Ceiling Cassette
Defrost / Deicing
High Pressure Switch
Low Pressure Switch
Reliability Phase protectionRestart Delay (3-minutes)
Self Diagnosis
Soft Start
Test Function
ConvenienceAuto Changeover
Auto Restart Operation
CAC NetworkCentral control(LGAP)
FunctionPDI(Power Distribution Indicator)
PI485
Special Function Kit Low Ambient Kit
Others Thermistor
FunctionCategory LT-C302PLE0 LT-H302PLE0
X O
O O
X X
X XO O
O O
X X
X X
X O
O O
Accessory Accessory
X X
Accessory Accessory
X X
- -
Note :
O : Applied, X : Not applied, : No relation
Option: Model name & price are different according to options, and assembled in factory with main unit.
Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
56/178
56 Outdoor unit
List of functions 6CST0-01A
Ceiling Cassette
Defrost / Deicing
High Pressure Switch
Low Pressure Switch
Reliability Phase protectionRestart Delay (3-minutes)
Self Diagnosis
Soft Start
Test Function
ConvenienceAuto Changeover
Auto Restart Operation
CAC NetworkCentral control(LGAP)
FunctionPDI(Power Distribution Indicator)
PI485
Special Function Kit Low Ambient Kit
Others Thermistor
FunctionCategory LT-C362NLE0 LT-H362NLE0
X O
O O
X X
X XO O
O O
X X
X X
X O
O O
Accessory Accessory
X X
Accessory Accessory
X X
- -
Note :
O : Applied, X : Not applied, : No relation
Option: Model name & price are different according to options, and assembled in factory with main unit.
Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
57/178
Outdoor unit 57
List of functions6CST0-01A
Ceiling Cassette
Defrost / Deicing
High Pressure Switch
Low Pressure Switch
Reliability Phase protectionRestart Delay (3-minutes)
Self Diagnosis
Soft Start
Test Function
ConvenienceAuto Changeover
Auto Restart Operation
CAC NetworkCentral control(LGAP)
FunctionPDI(Power Distribution Indicator)
PI485
Special Function Kit Low Ambient Kit
Others Thermistor
FunctionCategory LT-C482MLE0 LT-H482MLE0
X O
O O
X X
X XO O
O O
X X
X X
X O
O O
Accessory Accessory
X X
Accessory Accessory
X X
- -
Note :
O : Applied, X : Not applied, : No relation
Option: Model name & price are different according to options, and assembled in factory with main unit.
Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
58/178
58 Outdoor unit
List of functions 6CST0-01A
Ceiling Cassette
Defrost / Deicing
High Pressure Switch
Low Pressure Switch
Reliability Phase protectionRestart Delay (3-minutes)
Self Diagnosis
Soft Start
Test Function
ConvenienceAuto Changeover
Auto Restart Operation
CAC NetworkCentral control(LGAP)
FunctionPDI(Power Distribution Indicator)
PI485
Special Function Kit Low Ambient Kit
Others Thermistor
FunctionCategory LT-C602MLE0 LT-H602MLE0
X O
O O
X X
X XO O
O O
X X
X X
X O
O O
Accessory Accessory
X X
Accessory Accessory
X X
- -
Note :
O : Applied, X : Not applied, : No relation
Option: Model name & price are different according to options, and assembled in factory with main unit.
Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
-
8/10/2019 Ceiling Cassette(60Hz,R22) 6CST2-01A 08.Pdf20080904
59/178
Outdoor unit 59
Specifications6CST0-01A
Ceiling Cassette
2.1.3 Specifications
Nominal Capacity Cooling kW(Min~Rating~Max) Btu/h
Heating kWBtu/h
Nominal Input Cooling kW(Min~Rating~Max) Heating kWTesting CombinationRunning Current Cooling A(Rating) Heating AStarting Current Cooling/Heating APower Supply / V / Hz
Power Supply Cable(Outdoor) No. x mm2
Power and Transmission CableNo. x mm2
(Outdoor to Indoor or Outdoor to BD)Power and Transmission Cable(BD to Indoor) No. x mm2
Dimensions W x H x D mm(inch)Net Weight kg(lbs)Max. Number of Connectable Indoor UnitsCompressor (#1) Type
Qty x ModelMotor type
Oil charge volume ccOil Type
Compressor (#2) TypeQty x ModelMotor typeOil charge volume ccOil type
Compressor (#3) TypeQty x ModelMotor typeOil charge volume cc
Oil typeRefrigerant Cycle A Charge (at 7.5m) g(oz)
Cycle B Charge (at 7.5m) g(oz)
TypeControlAdditional Refrigerant Charge g/m(oz/ft)Heat Exchanger (Rows x Column x FPI(FPDM)) x No.
Defrosting MethodFan Capacitor F/Vac
DriveDischarge Direction(Side/Top)
Air Flow Rate x No. of Fan CMM(cfm)Sound Level(H/L) Sound Pressure dB(A)+3Piping Connections Liquid(Cycle A) mm(inch)
Gas(Cycle A) mm(inch)Liquid(Cycle B) mm(inch)Gas(Cycle B) mm(inch)High Pressure Gas mm(inch)
Max. Interunit Total Piping m
Piping Length Main Piping mTotal Branch Piping m
Each Branch Piping mMax. Elevation Outdoor Unit~Indoor Unit mDifference Indoor Unit~Indoor Unit mOperation Range Cooling C(F)(Outdoor) Heating C(F)
5.28 5.28
18,000 18,000
- 5.28
- 18,000
1.86 1.86
- 1.78
- -
8.4 8.4
- 8.1
52 52
1 / 220 / 60 1/220/60
3 x 2.1 3 x 2.1
4x0.75 (Including earth) 5 x 0.75 (Including earth)
- -
840 x 575 x 275 (33.