calculating variable transfer limits fordynamic transfers.ppt

18
CALCULATING VARIABLE TRANSFER LIMITS FOR DYNAMIC TRANSFERS LIMITS FOR DYNAMIC TRANSFERS RAMU RAMANATHAN(*), BRIAN TUCK, STEVEN C. PAI ORLANDO CINIGLIO JAMES PRICE GORDON DOBSON MACK ORLANDO CINIGLIO, JAMES PRICE, GORDON DOBSON-MACK Maxisys Inc., Bonneville Power Administration, BC Hydro & Power Authority, Idaho Power Corporation, California Independent System Operator, Powerex Corp. USA, Canada

Upload: others

Post on 07-Jun-2022

10 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Calculating Variable Transfer Limits forDynamic Transfers.ppt

CALCULATING VARIABLE TRANSFER LIMITS FOR DYNAMIC TRANSFERSLIMITS FOR DYNAMIC TRANSFERS

RAMU RAMANATHAN(*), BRIAN TUCK, STEVEN C. PAIORLANDO CINIGLIO JAMES PRICE GORDON DOBSON MACKORLANDO CINIGLIO, JAMES PRICE, GORDON DOBSON-MACK

Maxisys Inc., Bonneville Power Administration, BC Hydro & Power Authority, Idaho Power Corporation, California Independent System Operator, Powerex Corp.

USA, Canada

Page 2: Calculating Variable Transfer Limits forDynamic Transfers.ppt

DTC Task Force Participants

2

Page 3: Calculating Variable Transfer Limits forDynamic Transfers.ppt

NWPP Wind Generation Levels

2010 Coincident Peak Load = 60,200 MW

Dec 2010 Installed Wind Gen = 7,800 MW

Dec 2012 Installed Wind Gen = 13,200 MW

2010 Spring Min Load (HE04) = 32,745 MW

3

Page 4: Calculating Variable Transfer Limits forDynamic Transfers.ppt

Variable Transfer ExampleStep 3

BCH ACE = 0 MW

1. Initial state - all ACE’s = 0

Real-time Operating Hour

Step 2

BC Hydro

2. CAISO requests 50 MW of Regulation BCH ACE = - 50 MW

4 BCH and CAISO’s AGC respond

3. BCH sends official Dynamic Schedule to BPA & CAISO.

BPA ACE = 0 MW

BPA ACE = 0 MW

4. BCH and CAISO s AGC respondto new Dynamic Schedule.

BPA

CAISO

4CAISO ACE = 0 MW

CAISO ACE = + 50 MW

Page 5: Calculating Variable Transfer Limits forDynamic Transfers.ppt

Are Variable Transfer Limits Needed?

5

Page 6: Calculating Variable Transfer Limits forDynamic Transfers.ppt

Wh W th I f T f V i bilitWhy Was the Issue of Transfer Variability Limits Studied?

- Additional large and frequently varying Dynamic Transfers on top of stressed static conditions raised concerns for System Operators in 2005;Operators in 2005;

- TOPs concerned about increasing Dynamic Transfers to facilitate wind integration without assessing impact on transmission gridtransmission grid.

- How much and how frequently can transfers vary over 15 minute intervals outside of ramp periods?minute intervals outside of ramp periods?

6

Page 7: Calculating Variable Transfer Limits forDynamic Transfers.ppt

What Was Found?

Increasing the magnitude and frequency ofIncreasing the magnitude and frequency of Transfer Variability can results in potential:

Impacts to system reliability;- Impacts to system reliability;- Impacts to system equipment;- Impacts to customers.

Customer Impact Acceptable?

Equipment Impact Acceptable?

Operating Point Reliable?Acceptable? Acceptable? Reliable?

77

Page 8: Calculating Variable Transfer Limits forDynamic Transfers.ppt

Static vs. Variable Transfer

• Sum of the variable transfers plus the static transfers on a path must be less than or equal to the SOL; ST + VT <= SOL

8

Page 9: Calculating Variable Transfer Limits forDynamic Transfers.ppt

OOptimization Formulation:

Objective:Objective:

Max ∑ Abs( Transferi (z) ) for i = 1 to m source / sink pairs

Subject to

H(z) <= 0H(z) < 0

Where

z = is the vector of decision variables that includes both control and state variablesH(z) = is vector of operating conditions that cannot be violated

9

violated

Page 10: Calculating Variable Transfer Limits forDynamic Transfers.ppt

Factors Influencing Variable Transfers

Amount of static transfer Allowed Voltage variationAllowed Voltage variationReliability criteria Location of balancing resources Location of balancing resourcesAutomatic voltage control devicesSystem conditions such as topology RemedialSystem conditions such as topology, Remedial

Action Schemes (RAS), Load/Generation patterns etc.patterns etc.

10

Page 11: Calculating Variable Transfer Limits forDynamic Transfers.ppt

Impact on Customer vs. Operating Point

Path 3 TVL TVL V lt Chat 3Flow N to S1348 MW 400 MW

TVL vs Voltage Change

1000120014001600

W)

1348

1941 MW 379 MW

2561 MW 295 MW200

0200400600800

1000

30 25 20 15 10 5 0 5 10

TVL

(MW

2902

2561

1941

2902 MW 257 MW-200-30 -25 -20 -15 -10 -5 0 5 10

Voltage Change (KV)

11

Page 12: Calculating Variable Transfer Limits forDynamic Transfers.ppt

R li bilitReliabilityVoltage Stability Analysis

No COI flow Collapse point

Margin2.5 % n-25% n-1

VoltageStabilityLimit

1 4796 MW 5190 MW 130 MW 5060 MW

2 4670 MW 5140 MW 128 MW 5012 MW

3 4467 MW 5080 MW 127 MW 4953 MW

4 4050 MW 4980 MW 125 MW 4855 MW

• Voltage stability limit is decreasing as the “modified point” moved further from the initial cases.• TVL limit is taking the margin out of point at path rating

12

Page 13: Calculating Variable Transfer Limits forDynamic Transfers.ppt

R li bilitReliabilityTransient Stability Analysis

13

Page 14: Calculating Variable Transfer Limits forDynamic Transfers.ppt

L ti f B l i RLocation of Balancing Resources Economic Benefits

14

Page 15: Calculating Variable Transfer Limits forDynamic Transfers.ppt

Id l CIdeal Case

VT

STST

• VT is maximum when the slope is 45 degrees

15

Page 16: Calculating Variable Transfer Limits forDynamic Transfers.ppt

C W A hi Id l C ?Can We Achieve Ideal Case ?

VT 1

ST

Tran

sfer VT 2

MW

T

• VT increases voltage variation will increase • VT variation can be decreased by automatic voltage control devices• T f V i bilit Li it (TVL) SOL

Time

16

Transfer Variability Limit (TVL) <= SOL• Reliability issues due to MW change

Page 17: Calculating Variable Transfer Limits forDynamic Transfers.ppt

ObservationsObservations

Variable transfer (VT) cost higher than static ( ) gtransfer. The VT cost needs to account for loss in static

transfer revenuetransfer revenue. The best cost for variable transfer is same as

static transfer. Variable transfer cost cannot go gbelow the static transfer.Many factors influence DT Limit

M ki d i t t d ill i DTMaking more devices automated will increase DT Limit

17

Page 18: Calculating Variable Transfer Limits forDynamic Transfers.ppt

??