bus-vt
TRANSCRIPT
-
8/7/2019 Bus-VT
1/6
CUSTOMER:
CONTRACT NO. :
SUBSTATION:
TYPE FORM:
BAYNo.
SAUDI ELECTRICITY COMPANY. SEC. EOA.
30733178/00
380/115kV BSP ABU HADRIYAH
420kV GIS
C4. BUS 1 VOLTAGE TRANSFORMER
ABU HAORIYAH - 380/115kV BSP GIS
EXPANSION PROJECT.
NATIONAL CONTRACTING COMPANY
LTO. AL KHOBAR.
Type
Standard
Rated primary voltage
Rated secondary voltage
Rated output
Accuracy class
Highest system voltage
Rated insulation level
Rated voltage factorRated frequency
Rated SF6 gas pressure
Construction No.
VZR-AM400CFS3
IEC 60044-2
380143
110-110/43 1110-110143
100 1100
O.2&3P 1 0.2&3P
4 2 0
630/1425
1.5130 s60
600 kPa-abs at 20'C
3387061-4
kV
V
VA
Serial No. Phase
1 0 9 1 0 0 1 5 A
1 0 9 1 0 0 1 6 B
1 0 9 1 0 0 1 7 C
-
8/7/2019 Bus-VT
2/6
CUSTOMER:
CONTRACT NO. :
SUBSTATION:
TYPE FORM :
BAYNo.
SAUDI ELECTRICITY COMPANY. SEC. EOA.
30733178/00
380/115kV BSP ABU HADRIYAH
420kV GIS
C4. BUS 1 VOLTAGE TRANSFORMER
ABU HADRIYAH 380/115kV BSP GIS
EXPANSION PROJECT.
NATIONAL CONTRACTING COMPANY
LTD. AL KHOBAR.
MANUFACTURER
TYPE
: TOSHIBA JAPAN.
: VZR - AM400CFS3
: 380kV
" 3110 - 110V
F110 - 110V
73
SERIAL. No. CHECKS TO BE PERFORMEDCRITERIA OF
RESULTACCEPTANCE
1 INSPECT PHYSICAL DAMAGE IDEFECTS NO DAMAGE IDEFECTS OK
2 CHECK NAME PLATE CORRECTNESS AS PER APPROWED DWGS. OK
3 CHECK TIGHTNESS O F ALL BO LTED CONNECTI ONS SATI SFACTORY OK
4CHECK ALL GROUNDING CONNECTIONS
ARE SECURLY CONNECTEDAS PER APPROWED DWGS. OK
5CHECK ALL SECONDARY WIRING IS CORRECTLY
AS PER APPROWED DWGS. OKCOLOUR CODED AND SIZE OF WIRE AS SPECIFIED
6 CHECK VT. LOCATION AND SECONDARY TERMINAL AS PER APPROWED DWGS. OKLABELING AS PER DRAWING.
Signature:
Date: VI
WITNESSED BY
Name: MUHAMMAD KASHIF
Signature: / / /;)
Date: B Ill m o v~1tTOSHIBA CORPORATION SAUDI ELECTRICTY COMPANY. CSD. EOA
TOSHIBA CORPORATION
-
8/7/2019 Bus-VT
3/6
CUSTOMER:
CONTRACT NO. :
SUBSTATION:
TYPE FORM :
BAYNo.
SAUDI ELECTRICITY COMPANY. SEC. EOA.
30733178/00
380/115kV BSP ABU HADRIYAH
420kVGIS
C4. BUS 1 VOLTAGE TRANSFORMER
FIELD TEST PROCEDURE & RECORD
ABU HAORIYAH 380/115kV BSP GIS
EXPANSION PROJECT.
CONTRACTOR: NATIONAL CONTRACTING COMPANYLTD. AL KHOBAR.
VOLTAGE TRANSFORMER.
Insulation resistance measurement.
VTNo. PHASE SERIAL No.
A 10910015BUS 1.VT. B 10910016
C 10910017
Primary Circuit : > 1000 MO
Secondary Circuit: > 2 MO (Toshiba standard)
Measurement circuitInsulation resistance (GO) Ambient
ResultPhase A Phase B Phase C Temp. 0 C
PRIMARY - GROUND 100 GO 100 GO 100 GO 23.1 OK
SECONDARY1-GROUND 40GO 30 GO 25 GO 23.1 OK
SECONDARY 2- GROUND 40GO 40 GO 30 GO 23.1 OK
SECONDARY 1- PRIMARY 40 GO 40 GO 30 GO 23.1 OK
SECONDARY 2 - PRIMARY 40GO 40 GO 25GO 23.1 OK
SECONDARY1-SECONDARY2 16GO 15GO 17 GO 23.1 OK
WITNESSED BY
Name: MUHAMMAD KASHIF
Signature:
Date: 6f
Signature:
Date: e J I
-
8/7/2019 Bus-VT
4/6
CUSTOMER:
CONTRACT NO. :
SUBSTATION:
TYPE FORM :
BAYNo.
SAUDI ELECTRICITY COMPANY. SEC. EOA.
30733178/00
380/115kV BSP ABU HADRIYAH
420kVGIS
C4. BUS 1 VOLTAGE TRANSFORMER
FIELD TEST PROCEDURE & RECORDABU HADRIYAH - 380/115kV BSP GIS
EXPANSION PROJECT.
NATIONAL CONTRACTING COMPANYCONTRACTOR : LTD. AL KHOBAR.
VOLTAGE TRANSFORMER.
Polarity check.Check the polarity by inductive kick method for both taps.
Earthing
conductor
Removed
PrimaryPhase Terminal No.
IndicationResult
Injection point ON OFF1a1 - 1n X2A:1-3 + - OK1a2 - 1n X2A:2-3
A2a1 - 2n X2B: 1 - 3 + - OK2a2 - 2n X2B: 2 - 31a1 - 1n X2A:4-6 + - OK1a2 - 1n X2A:5-6
K835 B2a1 - 2n X2B: 4-6
+- OK
2a2 - 2n X2B: 5 - 61a1-1n X2A:7-9 +
-
OK
C1a2 - 1n X2A:8-92a1 - 2n X2B: 7 - 9 + - OK2a2 - 2n X2B: 8-9
Criteria : Subtractive polarity [Toshiba standard]
At the moment of making the switch, voltmeter should be indicated positive.
At the moment of breaking the switch, voltmeter should be indicated negative.
Signature:
Date: 0 1
Signature:
Date: 01 IJ/?-OIDTOSHIBA CORPORATION SAUDI ELECTRICTY COMPANY. CSD. EOA
TOSHIBA CORPORATION
-
8/7/2019 Bus-VT
5/6
CUSTOMER: I SAUDI ELECTRICITY COMPANY. SEC. EOA. PROJECT:ABU HAORIYAH 380/115kV BSP GIS
EXPANSION PROJECT.
CONTRACT NO. : 30733178/00CONTRACTOR:
NATIONAL CONTRACTING COMPANY
SUBSTATION: 380/115kV BSP ABU HADRIYAH LTD. AL KHOBAR.
TYPE FORM : 420kVGISIBAY NO. IC4. BUS 1 vnl Tar-", RATING: ~RnI
-
8/7/2019 Bus-VT
6/6
CUSTOMER: SAUDI ELECTRICITY COMPANY. SEC. EOA. PROJECT:ABU HAORIYAH 380/115kVBSP GIS
EXPANSION PROJECT.
CONTRACT NO. : 30733178/00CONTRACTOR:
NATIONAL CONTRACTING COMPANY
SUBSTATION: 380/115kV BSP ABU HADRIYAH LTO. AL KHOBAR.
TYPE FORM : 420kV GIS
BAYNo. C4. BUS 1 VOLTAGE TRANSFORMER RATING: I380kV, 3150A. 63kA 1sec. 60Hz
V O L T A G E T R A N S F O R M E R .
Ratio test.-
Earthing Voltage
conductor Source
Removed - - - ~-
f = : T T-E---"
~():ES VT
Cloee
A
B
C
Phase Rated Ratio Terminal No.Primary Voltage Secondan Voltaae (mV )
Result{V} Calculated Meassured
380kV 110V VT1.JB:X2A : 1 - 3 2000 V 1002.77 V 999.40 OK. .J3
380k'l/ 110V VT1.JB:X2A : 2 - 3 2000 V 578.95 V 577.70 OK
A..J 3 ..J 3
380kV 110V VT1.JB:X2B: 1 - 3 2000 V 1002.77 V 999.40 OK. .J3
380kY 110V VT1.JB:X2B : 2 - 3 2000 V 578.95 V 578.20 OK..J 3 ..J 3
380kY 110V VT1.JB:X2A : 4 - 6 2000 V 1002.77 V 1000.10 OK. .J3
380k'l/
..11ll VT1.JB:X2A : 5 - 6 2000 V 578.95 V 578.20 OKB
. .J 3 ..J 3
380kV 110V VT1.JB:X2B : 4 - 6 2000 V 1002.77 V 1000.10 OK. .J3
380kY 110V VT.JB:X2B : 5 - 6 2000 V 578.95 V 577.90 OK. .J 3 ..J 3
380kV 110V VT1.JB:X2A : 7 - 9 2000 V 1002.77 V 1000.40 OK. .J3
380kV 110V VT1.JB:X2A : 8 9 2000 V 578.95 V 578.50 OK
C. .J 3 ..J 3
380k'l/ 110V VT1.JB:X2B : 7 - 9 2000 V 1002.77 V 1000.80 OK. .J3
380kV 110V VT1.JB:X2B : 8 - 9 2000 V 578.95 V 578.10 OK. .J 3 ..J 3
Criteria: Rated ratio O.5%
TEST EQUIPMENT USED: FLUKE 187 MULTI METER & MAGNUS.
TESTED BY WITNESS ED BY
Name: BENNY JACOB
~
Name: MUHAMMAD KASHIF
Signature: Signature:
~Date: Or! (I /