    CUSTOMER:

    CONTRACT NO. :

    SUBSTATION:

    TYPE FORM:

    BAYNo.

    SAUDI ELECTRICITY COMPANY. SEC. EOA.

    30733178/00

    380/115kV BSP ABU HADRIYAH

    420kV GIS

    C4. BUS 1 VOLTAGE TRANSFORMER

    ABU HAORIYAH - 380/115kV BSP GIS

    EXPANSION PROJECT.

    NATIONAL CONTRACTING COMPANY

    LTO. AL KHOBAR.

    Type

    Standard

    Rated primary voltage

    Rated secondary voltage

    Rated output

    Accuracy class

    Highest system voltage

    Rated insulation level

    Rated voltage factorRated frequency

    Rated SF6 gas pressure

    Construction No.

    VZR-AM400CFS3

    IEC 60044-2

    380143

    110-110/43 1110-110143

    100 1100

    O.2&3P 1 0.2&3P

    4 2 0

    630/1425

    1.5130 s60

    600 kPa-abs at 20'C

    3387061-4

    kV

    V

    VA

    Serial No. Phase

    1 0 9 1 0 0 1 5 A

    1 0 9 1 0 0 1 6 B

    1 0 9 1 0 0 1 7 C

  • 8/7/2019 Bus-VT

    2/6

    CUSTOMER:

    CONTRACT NO. :

    SUBSTATION:

    TYPE FORM :

    BAYNo.

    SAUDI ELECTRICITY COMPANY. SEC. EOA.

    30733178/00

    380/115kV BSP ABU HADRIYAH

    420kV GIS

    C4. BUS 1 VOLTAGE TRANSFORMER

    ABU HADRIYAH 380/115kV BSP GIS

    EXPANSION PROJECT.

    NATIONAL CONTRACTING COMPANY

    LTD. AL KHOBAR.

    MANUFACTURER

    TYPE

    : TOSHIBA JAPAN.

    : VZR - AM400CFS3

    : 380kV

    " 3110 - 110V

    F110 - 110V

    73

    SERIAL. No. CHECKS TO BE PERFORMEDCRITERIA OF

    RESULTACCEPTANCE

    1 INSPECT PHYSICAL DAMAGE IDEFECTS NO DAMAGE IDEFECTS OK

    2 CHECK NAME PLATE CORRECTNESS AS PER APPROWED DWGS. OK

    3 CHECK TIGHTNESS O F ALL BO LTED CONNECTI ONS SATI SFACTORY OK

    4CHECK ALL GROUNDING CONNECTIONS

    ARE SECURLY CONNECTEDAS PER APPROWED DWGS. OK

    5CHECK ALL SECONDARY WIRING IS CORRECTLY

    AS PER APPROWED DWGS. OKCOLOUR CODED AND SIZE OF WIRE AS SPECIFIED

    6 CHECK VT. LOCATION AND SECONDARY TERMINAL AS PER APPROWED DWGS. OKLABELING AS PER DRAWING.

    Signature:

    Date: VI

    WITNESSED BY

    Name: MUHAMMAD KASHIF

    Signature: / / /;)

    Date: B Ill m o v~1tTOSHIBA CORPORATION SAUDI ELECTRICTY COMPANY. CSD. EOA

    TOSHIBA CORPORATION

  • 8/7/2019 Bus-VT

    3/6

    CUSTOMER:

    CONTRACT NO. :

    SUBSTATION:

    TYPE FORM :

    BAYNo.

    SAUDI ELECTRICITY COMPANY. SEC. EOA.

    30733178/00

    380/115kV BSP ABU HADRIYAH

    420kVGIS

    C4. BUS 1 VOLTAGE TRANSFORMER

    FIELD TEST PROCEDURE & RECORD

    ABU HAORIYAH 380/115kV BSP GIS

    EXPANSION PROJECT.

    CONTRACTOR: NATIONAL CONTRACTING COMPANYLTD. AL KHOBAR.

    VOLTAGE TRANSFORMER.

    Insulation resistance measurement.

    VTNo. PHASE SERIAL No.

    A 10910015BUS 1.VT. B 10910016

    C 10910017

    Primary Circuit : > 1000 MO

    Secondary Circuit: > 2 MO (Toshiba standard)

    Measurement circuitInsulation resistance (GO) Ambient

    ResultPhase A Phase B Phase C Temp. 0 C

    PRIMARY - GROUND 100 GO 100 GO 100 GO 23.1 OK

    SECONDARY1-GROUND 40GO 30 GO 25 GO 23.1 OK

    SECONDARY 2- GROUND 40GO 40 GO 30 GO 23.1 OK

    SECONDARY 1- PRIMARY 40 GO 40 GO 30 GO 23.1 OK

    SECONDARY 2 - PRIMARY 40GO 40 GO 25GO 23.1 OK

    SECONDARY1-SECONDARY2 16GO 15GO 17 GO 23.1 OK

    WITNESSED BY

    Name: MUHAMMAD KASHIF

    Signature:

    Date: 6f

    Signature:

    Date: e J I

  • 8/7/2019 Bus-VT

    4/6

    CUSTOMER:

    CONTRACT NO. :

    SUBSTATION:

    TYPE FORM :

    BAYNo.

    SAUDI ELECTRICITY COMPANY. SEC. EOA.

    30733178/00

    380/115kV BSP ABU HADRIYAH

    420kVGIS

    C4. BUS 1 VOLTAGE TRANSFORMER

    FIELD TEST PROCEDURE & RECORDABU HADRIYAH - 380/115kV BSP GIS

    EXPANSION PROJECT.

    NATIONAL CONTRACTING COMPANYCONTRACTOR : LTD. AL KHOBAR.

    VOLTAGE TRANSFORMER.

    Polarity check.Check the polarity by inductive kick method for both taps.

    Earthing

    conductor

    Removed

    PrimaryPhase Terminal No.

    IndicationResult

    Injection point ON OFF1a1 - 1n X2A:1-3 + - OK1a2 - 1n X2A:2-3

    A2a1 - 2n X2B: 1 - 3 + - OK2a2 - 2n X2B: 2 - 31a1 - 1n X2A:4-6 + - OK1a2 - 1n X2A:5-6

    K835 B2a1 - 2n X2B: 4-6

    +- OK

    2a2 - 2n X2B: 5 - 61a1-1n X2A:7-9 +

    -

    OK

    C1a2 - 1n X2A:8-92a1 - 2n X2B: 7 - 9 + - OK2a2 - 2n X2B: 8-9

    Criteria : Subtractive polarity [Toshiba standard]

    At the moment of making the switch, voltmeter should be indicated positive.

    At the moment of breaking the switch, voltmeter should be indicated negative.

    Signature:

    Date: 0 1

    Signature:

    Date: 01 IJ/?-OIDTOSHIBA CORPORATION SAUDI ELECTRICTY COMPANY. CSD. EOA

    TOSHIBA CORPORATION

  • 8/7/2019 Bus-VT

    5/6

    CUSTOMER: I SAUDI ELECTRICITY COMPANY. SEC. EOA. PROJECT:ABU HAORIYAH 380/115kV BSP GIS

    EXPANSION PROJECT.

    CONTRACT NO. : 30733178/00CONTRACTOR:

    NATIONAL CONTRACTING COMPANY

    SUBSTATION: 380/115kV BSP ABU HADRIYAH LTD. AL KHOBAR.

    TYPE FORM : 420kVGISIBAY NO. IC4. BUS 1 vnl Tar-", RATING: ~RnI

  • 8/7/2019 Bus-VT

    6/6

    CUSTOMER: SAUDI ELECTRICITY COMPANY. SEC. EOA. PROJECT:ABU HAORIYAH 380/115kVBSP GIS

    EXPANSION PROJECT.

    CONTRACT NO. : 30733178/00CONTRACTOR:

    NATIONAL CONTRACTING COMPANY

    SUBSTATION: 380/115kV BSP ABU HADRIYAH LTO. AL KHOBAR.

    TYPE FORM : 420kV GIS

    BAYNo. C4. BUS 1 VOLTAGE TRANSFORMER RATING: I380kV, 3150A. 63kA 1sec. 60Hz

    V O L T A G E T R A N S F O R M E R .

    Ratio test.-

    Earthing Voltage

    conductor Source

    Removed - - - ~-

    f = : T T-E---"

    ~():ES VT

    Cloee

    A

    B

    C

    Phase Rated Ratio Terminal No.Primary Voltage Secondan Voltaae (mV )

    Result{V} Calculated Meassured

    380kV 110V VT1.JB:X2A : 1 - 3 2000 V 1002.77 V 999.40 OK. .J3

    380k'l/ 110V VT1.JB:X2A : 2 - 3 2000 V 578.95 V 577.70 OK

    A..J 3 ..J 3

    380kV 110V VT1.JB:X2B: 1 - 3 2000 V 1002.77 V 999.40 OK. .J3

    380kY 110V VT1.JB:X2B : 2 - 3 2000 V 578.95 V 578.20 OK..J 3 ..J 3

    380kY 110V VT1.JB:X2A : 4 - 6 2000 V 1002.77 V 1000.10 OK. .J3

    380k'l/

    ..11ll VT1.JB:X2A : 5 - 6 2000 V 578.95 V 578.20 OKB

    . .J 3 ..J 3

    380kV 110V VT1.JB:X2B : 4 - 6 2000 V 1002.77 V 1000.10 OK. .J3

    380kY 110V VT.JB:X2B : 5 - 6 2000 V 578.95 V 577.90 OK. .J 3 ..J 3

    380kV 110V VT1.JB:X2A : 7 - 9 2000 V 1002.77 V 1000.40 OK. .J3

    380kV 110V VT1.JB:X2A : 8 9 2000 V 578.95 V 578.50 OK

    C. .J 3 ..J 3

    380k'l/ 110V VT1.JB:X2B : 7 - 9 2000 V 1002.77 V 1000.80 OK. .J3

    380kV 110V VT1.JB:X2B : 8 - 9 2000 V 578.95 V 578.10 OK. .J 3 ..J 3

    Criteria: Rated ratio O.5%

    TEST EQUIPMENT USED: FLUKE 187 MULTI METER & MAGNUS.

    TESTED BY WITNESS ED BY

    Name: BENNY JACOB

    ~

    Name: MUHAMMAD KASHIF

    Signature: Signature:

    ~Date: Or! (I /