building control system, aplication guide cibse guide

195

Upload: aym1979

Post on 16-Aug-2015

118 views

Category:

Design


21 download

TRANSCRIPT

Page 1: Building control system, aplication guide   cibse guide
Page 2: Building control system, aplication guide   cibse guide

Building control systems

CIBSE Guide H

Oxford Auckland Boston Johannesburg Melbourne New Delhi

Page 3: Building control system, aplication guide   cibse guide

Butterworth-HeinemannLinacre House, Jordan Hill, Oxford OX2 8DP225 Wildwood Avenue, Woburn, MA 01801-2041A division of Reed Educational and Professional PublishingLtd

© July 2000 The Chartered Institution of Building ServicesEngineers London

All rights reserved. No part of this publication may bereproduced or transmitted in any form or by any means,electronically or mechanically, including photocopying,recording or any information storage or retrieval system,without either prior permission in writing from the publisheror a licence permitting restricted copying. In the UnitedKingdom such licences are issued by the Copyright LicensingAgency: 90 Tottenham Court Road, London W1P 0LP.

Whilst the advice and information in this book are believedto be true and accurate at the date of going to press, neitherthe Chartered Institution of Building Services Engineers northe publisher can accept any legal responsibility or liabilityfor any errors or omissions that may be made.

British Library Cataloguing in Publication DataA catalogue record for this book is available from the BritishLibrary

ISBN 07506 504 78

1 2 3 4 5 6 7 8 9 10

Typeset in Great Britain by Phoenix Photosetting,Chatham, KentPrinted and bound in Great Britain by Bath Press,Bath, Avon

Page 4: Building control system, aplication guide   cibse guide

Contents

Foreword v

Preface vii

Acknowledgements viii

1 Introduction: the need for controls 1-1

1.1 Overview of the Guide 1-11.2 The modern control system 1-21.3 The global environment 1-21.4 The indoor environment 1-31.5 Energy conservation 1-31.6 Information technology and systems integration 1-41.7 Building operation 1-51.8 The benefits of a BMS 1-51.9 Summary 1-6References 1-6

2 Control fundamentals 2-1

2.0 General 2-12.1 Control modes 2-12.2 Optimum start 2-72.3 Weather compensation 2-82.4 Stability and tuning 2-92.5 Artificial intelligence 2-132.6 Summary 2-14References 2-14

3 Components and devices 3-1

3.1 Sensors 3-13.2 Actuators 3-73.3 Valves 3-83.4 Dampers 3-173.5 Motors 3-203.6 Pumps and fans 3-233.7 Control panels and motor control centres 3-233.8 The intelligent outstation 3-243.9 Summary 3-26References 3-26

4 Systems, networks and integration 4-1

4.0 General 4-14.1 BMS architecture 4-14.2 Networks 4-54.3 Electromagnetic compatibility (EMC) 4-124.4 Systems integration 4-154.5 User interface 4-174.6 Summary 4-18References 4-19

5 Control strategies for subsystems 5-1

5.1 Safety 5-15.2 Boilers 5-35.3 Chillers 5-75.4 Control of hydraulic circuits 5-145.5 Central air handling plant 5-285.6 Energy recovery 5-325.7 Mechanical ventilation 5-345.8 Variable air volume 5-415.9 Constant-volume room terminal units 5-46

Page 5: Building control system, aplication guide   cibse guide

5.10 Fan coil units 5-465.11 Dual duct systems 5-485.12 Chilled ceilings 5-495.13 Heat pumps 5-515.14 Natural ventilation 5-535.15 Lighting controls 5-565.16 Summary 5-61References 5-62

6 Control strategies for buildings 6-1

6.0 General 6-16.1 Operating modes 6-16.2 Design techniques 6-26.3 Whole-building HVAC systems 6-46.4 Case studies 6-76.5 Summary 6-10References 6-10

7 Information technology 7-1

7.1 Energy monitoring 7-17.2 Fault reports and maintenance scheduling 7-67.3 Summary 7-7References 7-7

8 Management issues 8-1

8.1 Procurement options 8-18.2 Design and specification of a controls system 8-48.3 Tendering process 8-78.4 Commissioning 8-88.5 Operation 8-138.6 Occupant surveys 8-148.7 Cost issues 8-158.8 Summary 8-16References 8-17

Appendix A1: Bibliography A1-1

Appendix A2: Tuning rules A2-1

A2.1 The PID control loop A2-1A2.2 Digital control A2-1A2.3 Tuning A2-2A2.4 Step-by-step tuning procedure A2-3

Appendix A3: Glossary A3-1

Page 6: Building control system, aplication guide   cibse guide

Foreword

The CIBSE Applications Manual Automatic Controls and their implication for systems designwas published in 1985 with the stated aim ‘to provide building services engineers generallywith the detailed guidance required to ensure that automatic controls are considered as anintegral part of the design philosophy’. The technology, both hardware and software, ofautomatic control systems has advanced greatly since then and the need for a new edition isclear. The Department of the Environment, Transport and the Regions granted an awardfor the production of a new edition of the manual under the Partners in Technologyscheme. The DETR provided 50% of the funding for the project; the Partners provided thebalance, with the initial publishing costs met by CIBSE. A contact for the preparation of thedraft was placed with the Department of Building Engineering at UMIST, and the work hasbeen supervised by a Task Group, drawn initially from the CIBSE IT and Controls specialinterest group.

Partners Ken Butcher CIBSEGerald McGilley Landis and Staefa Division of Siemens Building

Technologies LtdGraham Nicholls E SquaredMartyn Harrold Ove Arup

Task Group Geoff Levermore Dept of Building Engineering, UMIST, Chair

Brian Flude ConsultantDavid Lush ConsultantSteve Loughney Landis and Staefa Division of Siemens Building

Technologies LtdAndrew Martin BSRIANick Skemp Building Design PartnershipJeremy Warren AspenTSCRoger Poole British AirwaysColin Ashford BRECSUTom Edge Brian Clancy PartnershipPeter Tunnell Landis and Staefa Division of Siemens Building

Technologies LtdAlistair Cameron R W GregoryStuart Aynsley Cylon ControlsIan Shuttleworth Johnson ControlsPeter McDermott E SquaredPeter Day E SquaredMalcolm Clapp Consultant

George Henderson DETR Representative

Contract Donald McIntyre Consultantauthor

CIBSE Ken ButcherRobert Yarham

Page 7: Building control system, aplication guide   cibse guide

This Page Intentionally Left Blank

Page 8: Building control system, aplication guide   cibse guide

Preface

Controls are poorly understood in our industry. The subject is also disliked in university courses as it can become highlymathematical. It is probably partly due to this lack of appreciation of controls and their commissioning that I have yet tofind a building that works properly and satisfies the occupants after it has been commissioned. This Guide is an attempt toredress some of these problems. It explains the topic of controls with the minimum of mathematics. It builds on and updatesthe earlier 1985 Applications Manual Automatic Building Controls.

Some points did come up a number of times in the Task Group discussions that could not be quantified in the body of theGuide but are worth mentioning here;

● Adequate time should be allowed for the commissioning process. It can take between 1 day and 6 months to commission acontrol system, depending on the size and complexity of the system. Another general and difficult-to-define quantity isthe time to commission a BMS point, but figures between 8 minutes and 60 minutes are often mentioned.

● The form of contracts and subcontracts can have major implications for controls and especially the time forcommissioning; slippages and cost cutting can end with the design and commissioning being done poorly. Partneringmay help this.

● Part-load performance details of the HVAC system to be controlled will aid the design and commissioning of the controlsystem. Rarely do systems operate at, or get commissioned at, the near-extreme conditions of design.

● The controls should be considered from the earliest stages of the design process.

● Occupant feedback, via a self-assessed questionnaire, can be a useful design and commissioning tool.

● In many new buildings occupants need to be involved in the control process and also informed of the control process.

I would like to give my sincere thanks to the Task Group, which has provided many useful comments and much guidance,to Donald McIntyre for helping to get them into a coherent, easy to read document, and to Ken Butcher for his helpthroughout the preparation process.

Geoff Levermore July 1999

Page 9: Building control system, aplication guide   cibse guide

Acknowledgements

Preparation of the manual would not have been possible without the generous help of the many people who providedinformation and literature, and gave their time to discuss the project and read the many drafts. While it is not possible tomention them all by name, their contributions were highly valued.

Page 10: Building control system, aplication guide   cibse guide

1.1 Overview of the GuideThe first edition of this Guide was published in 1985 as anApplications Manual, under the title Automatic BuildingControls and Their Implications for Systems Design. The manydevelopments since then, particularly in the fields ofmicroprocessor control and communications networks,have necessitated the production of an entirely new edition.The aim of the Guide has been restated since the first editionto reflect the growing importance of IT, and now reads: toprovide the building services engineer with a sufficientunderstanding of modern control systems and relevant informationtechnology to ensure that the best form of control system for thebuilding is specified and that proper provision is made for itsinstallation, commissioning, operation and maintenance.

The structure of the Guide is indicated in Table 1.1. Thisintroductory section sets out the benefits to be gained froma modern building control system and will be of value inmaking the case that adequate provision be made at an earlystage for a proper control system. The following sectiondeals with the different types of control mode and theirapplication in different situations; advice is given on thesetting up and tuning of controllers to ensure stableoperation.

Sections 3–6 deal with the practical design of controlsystems, starting with the hardware components, then theirincorporation into control systems by linking them intonetworks, and then two sections on control strategies forHVAC systems and whole buildings. The Guide thus starts

1-1

1 Introduction: the need for controls

1.1 Overview of the Guide

1.2 The modern control system

1.3 The global environment

1.4 The indoor environment

1.5 Energy conservation

1.6 Information technology and systems integration

1.7 Building operation

1.8 The benefits of a BMS

1.9 Summary

This introductory section provides an overview of the Guide and will be of value when preparing the general case for a controlsystem. It demonstrates the importance of controls in ensuring effective and efficient control of a building in order to:

— provide comfortable and productive working conditions

— provide the proper environment for industrial processes

— operate in an energy efficient manner

— be environment friendly.

Table 1.1 Organisation of the Guide

1 Introduction The contribution that a modern building management system can make to the efficient and economical operation of a building

2 Control The basic types of control operation that are found in practice, ranging from the simple thermostat to microprocessor controlledfundamentals self-learning algorithms. Guidance on the application of different control types and their tuning for optimum operation

3 Components and The whole range of hardware components that constitute a control system, including sensors, valves, dampers, actuators, motors devices and basic controllers

4 Systems, networks The means by which components are brought together to form an operating control system. The various BMS architectures and and integration the major standard protocols for bus systems. Characteristics of networks and the extension to full systems integration

5 Control strategies Control strategies for the fundamental parts of HVAC systems: safety interlocks, boilers, chillers, water and air systems, lightingfor subsystems

6 Control strategies Control strategies for whole buildings. Avoiding conflict between subsystems. Illustrations of successful control installationsfor buildings

7 Information The relation between BMS and IT. Energy monitoring and targeting, maintenance scheduling, facilities managementtechnology

8 Management issues The importance of the procurement method on the BMS design process. Commissioning, CDM requirements and cost issues

Page 11: Building control system, aplication guide   cibse guide

with the constituent components and moves up to completesystems. The user may prefer to consult the controlstrategies for systems of interest and then refer back in theGuide to obtain a fuller understanding of the componentparts.

Section 7 deals with the relation between buildingmanagement systems and information technology. The BMSand IT systems may share a communications network andthe information gathered by the BMS can be used by the ITsystem for further purposes, enhancing the value of bothsystems. The final section shows the importance of thebuilding procurement process in determining whetheradequate resources are devoted to the design andinstallation of a suitable BMS and emphasises the necessityof taking control requirements into consideration at anearly stage in the design process.

1.2 The modern controlsystem

Good controls are essential for the safe and efficientoperation of a modern building. The control system doesmore than keep the inside of a building comfortable for theoccupants. It is required to keep the HVAC plant operatingefficiently, to ensure that all plant operates safely in theevent of any unforeseen circumstances, and it must becapable of two-way communication with the personnelcharged with its operation. While it may be self-evidentthat modern highly serviced buildings require asophisticated control system, it should be realised thatsimpler buildings relying on a boiler system and naturalventilation can still benefit from a modern BMS. Theincreasing emphasis on energy conservation and reductionof greenhouse gas emissions serves to increase theimportance of efficient controls.

The late 1970s saw the introduction of digital datatechnology, in which information is transmitted not as ananalogue electrical value, but as a number. Digital datatransmission is less susceptible to error than analoguetransmission and it is standard practice to construct thesignal protocol in such a way that it is possible to detectwhether an error has occurred during transmission. Thiswas the beginning of direct digital control (DDC). Itrequired the codification of rules by which values areconverted to numerical messages for sending; suchmessages have to contain not only the value of the variableunder consideration, but additional information such asthe origin and destination of the message and error-checking information. Such conventions on the structureof the messages are the basis of data communicationprotocols. At the early stage of DDC, data handling wascentralised and multiplexing circuits were used so that thecentral unit could contact each remote unit as required. Ascomputing power rapidly increased, the functionality of thecentral control unit became more and more sophisticated,with the ability to handle increasing amounts of data and toperform additional functions such as the monitoring ofenergy consumption and the printing or reports.

The advent of the microprocessor allowed considerablecomputing power to be incorporated in a small device andmeant that it was now no longer necessary for all controland monitoring functions to be carried out by a largecentralised computer. Intelligent outstations placed round

the building became capable of carrying out local controlfunctions, while communicating with a central supervisorwhich could oversee their actions, receive any alarm signalsand alter set points or operating times as required. Therehas been enormous progress in the field of datacommunication and the application of local area networks(LANs), which allow microprocessors and computers tocommunicate with each other over standardised networks.Communication may be extended to link together theoperation of several buildings, which may be located milesapart, or even in different countries.

All these have contributed to the modern buildingmanagement system. In this Guide the term ‘controlsystem’ or ‘building control system’ is used to cover allcontrol elements, including hardware, controllers, anylinking network and central controllers. The term BMSrefers to a system where components may communicatewith each other and generally implies some form of centralsupervisor, which permits monitoring and control of thebuilding from a single point. The period that saw thedevelopment of the BMS has also seen the rise ininformation technology (IT). A modern operation, whetherit is office or factory, is likely to distribute and process largeamounts of information dealing with the operation of thebusiness. There may be advantages in linking IT and BMS,either for the economy of using shared networks or for themore efficient integration of management control over themany activities taking place in a building.

1.3 The global environmentThe building industry is implicated in two major concernsabout the possibility of global environmental change:global warming and damage to the ozone layer. Buildingsare a major source of carbon dioxide emissions, whetherdirectly by the consumption of fuel for space and waterheating, or indirectly by the consumption of electricity forlighting, air conditioning and other uses. It is estimatedthat energy use in buildings in the UK accounts for abouthalf of the total carbon dioxide emissions.

The destruction of the ozone layer is a distinct problem fromclimate warming, but the causes are linked. Chlorinatedfluorocarbons (CFCs) are stable compounds which for yearshave been the most commonly used refrigerant in airconditioning applications. If released, CFCs interact withozone in the upper atmosphere leading to a thinning of theozone layer, which normally provides an effective barrier toexcessive ultraviolet radiation from the sun. Aninternational agreement has been reached to restrict the useof CFCs. The Montreal protocol allows the use of alternativerefrigerants (HCFCs) with a much lower ozone depletioncapacity than CFCs for an interim period, after which theywould be banned as well(1). Proposed EU legislation willfurther restrict the use of refrigerants. In summary:

— Any use of CFCs for new or existing systems is to beprohibited from 2001, including recovered andstockpiled CFCs.

— The use of HCFCs in new air conditioning plant willbe phased out between 2001 and 2004, dependingon the type of plant.

— The use of new HCFCs for maintaining existingsystems is to be banned after 2010, though it will bepossible to use recovered and recycled refrigerant.

1-2 Building control systems

Page 12: Building control system, aplication guide   cibse guide

— Recovery of CFCs and HCFCs on plant servicing ordecommissioning will become mandatory andannual leak checks for larger systems will becompulsory.

There is therefore strong pressure to reduce energyconsumption in buildings and to avoid the use of airconditioning wherever possible. This pressure may takeseveral forms: further legislation can be expected, the priceof fuel may be increased and responsible clients willincorporate environmental goals in the design brief. TheCIBSE Code of Professional Conduct places a general duty onmembers to ‘have due regard to environmental issues’(2)

and the CIBSE Policy Statement on Global Warmingrecommends that members take positive steps to reduceglobal warming(3).

Any major reduction in energy use by buildings requirescommitment by the client expressed in the design brief,followed by action at the design stage, where fundamentaldecisions on the form of the building and the use of airconditioning are made. Correct design and operation ofbuilding controls is essential to avoid waste of energy.Reduction in the use of air conditioning and the applicationof natural ventilation bring new challenges for effectivebuilding control and the maintenance of satisfactoryinternal conditions coupled with low energy use. TheCIBSE Guide to Energy Efficiency in Buildings(4) has theobjective of showing how to improve the energyperformance of buildings. While primarily targeted atbuilding services engineers, it is of use to all members of thebuilding team.

1.4 The indoor environmentThe function of the building services and their associatedcontrol system is to provide an environment within thebuilding appropriate to the activities taking place therein.Several factors contribute to feelings of thermal comfortand their incorporation into the predicted mean vote (PMV)index is set out in European Standard BS EN 7730(5).Recent research(6) strongly suggests that people adapt totheir environment, allowing temperature settings to fall inwinter and rise in summer. This has importantimplications for the design of naturally ventilatedbuildings. Guidance on the required conditions for a rangeof occupations and activities is given in CIBSE Guide A1(7).Decisions on allowable excursions of the conditions outsidethe recommended comfort bands, e.g. during a summerheatwave, will have important repercussions on plantsizing. The specified control tolerances will affect thedesign and cost of the control system. The indoorenvironment affects not only comfort, but also productivityand health. Relevant legislation is referred to as appropriatein the text. The Control of Fuel and Electricity, StatutoryInstrument(8), specifies a maximum heating level of 19ºC innon-domestic buildings. The law has not been rigorouslyenforced. While it is difficult to substantiate precise claimsof productivity gains, there is little doubt that comfortableconditions will have a beneficial effect. Surveys haveconsistently shown that the speed with which managementattends to complaints is very important. Those companieswhere management attends promptly to problems arehighly rated by the occupants(9). The client’s point of viewfor the specification of offices is represented in Best Practicein the Specification for Offices(10).

While the primary function of a building control systemhas been the control of temperature and humidity, theincreased awareness of sick building syndrome (SBS) andother building related illnesses has emphasised therequirement to ensure good indoor air quality. Thedemands of energy conservation and healthy ventilation aresometimes in conflict, necessitating better attention to thecontrol of ventilation to ensure a satisfactory compromise.More attention is being given to the quality as well asquantity of ventilation.

There are many buildings which house processes andoperations which have their own special requirements forenvironmental control. Examples are low temperature forfood preparation, high and controlled humidity for paperfabrication, clean rooms for electronic assembly. Thepharmaceutical industry has its own special regulationsfor control of the environment, both for drug productionand for animal housing. Companies producing goods forexport may need to meet the requirements set down bythe customer’s country. It is outside the scope of thisGuide to give the many regulations; it is the respons-ibility of the client or his representative to ensure thatthey are taken into account at an early stage in thedesign.

1.5 Energy conservationBuilding controls have a vital role to play in preventingwaste of energy. The amount of energy required to run abuilding is determined by:

— thermal efficiency of the building envelope

— thermal insulation

— airtightness

— provision for passive solar gains

— requirements of the indoor environment

— temperature schedule

— ventilation needs

— humidity control

— indoor air quality

— lighting requirement

— hot water requirements

— lifts and mechanical services

— processes within the building

— IT equipment

— industrial processes.

The above requirements taken together demand a level ofbase energy, which is the energy required to meet thebusiness needs of the building operation. This provides aminimum level of energy expenditure. Any reduction inbase energy requirement implies a change in buildingconstruction or use. The difference between actual energyexpenditure and the base requirement represents avoidablewaste. Examination of data from a number of UK buildingsshows avoidable waste levels in the range 25 to 50%; in awell-managed building, avoidable waste levels of below15% are achieved(11).

Introduction: the need for controls 1-3

Page 13: Building control system, aplication guide   cibse guide

Avoidable waste has many causes, including:

— poor time and temperature control of the buildinginterior

— ineffective utilisation of internal heat gains

— plant oversizing

— excessive ventilation

— low operating efficiency of the HVAC system

— poor system design and installation

— standing losses

— unnecessary use of artificial lighting and airconditioning.

The control system affects most of the above. Detailedapplications will be found in the body of the Guide. Majorcontributions of the control system in reducing waste are:

— the limitation of heating and cooling to theminimum period necessary; this usually includesthe use of optimum start controllers and some formof occupancy detection to avoid excessive out-of-hours use

— prevention of unnecessary plant operation andboiler idling

— monitoring to give early warning of malfunction orinefficient operation.

The establishment of a figure for base energy provides aclear figure to aim at and allows the performance of thebuilding to be clearly and unambiguously stated in terms ofavoidable waste. The base energy requirement must be

estimated by a sound method, which is understood andrespected by all parties involved. As far as possible, itshould be broken down into components, to allowidentification of areas which require action.

Fuel Efficiency Booklet 10(12) gives clear advice on theselection of an appropriate control system for energy savingpurposes. It categorises control systems into four bands ofascending cost and complexity, shown in Table 1.2. Thehighest band gives the greatest potential energy savings,but may not be appropriate for all buildings or operatingstaff.

Band 0 is the minimum level of control required under the1995 Building Regulations. Achieving this level of control ina building that has poor or non-existent controls will makeconsiderable savings, and further savings of up to 20% maybe made by the use of more sophisticated systems. Table1.3, taken from the fuel efficiency booklet, gives rule-of-thumb assessments of cost savings that may be achieved.This table represents only a crude starting point. Thedecision on the type of control system to be installed in abuilding depends on more factors than simple energypayback savings and must be made on a deeper analysis ofthe costs and benefits to be expected.

1.6 Information technologyand systems integration

A modern building contains several technical services inaddition to heating and ventilation, such as lighting, liftcontrol, security and access control, closed circuit television

1-4 Building control systems

Table 1.2 Banding classification of heating control systems, after Energy Efficiency Office(12)

Band Time Boiler Distribution Space heating Hot water system

Output greater than 100 kW

2 Optimiser plus time Boiler loading Compensated with All emitters with Local gas fired control of zones. control. space temperature individual control, water heaters or Time control of HW Off-line boilers reset and separate zone modulating where point of use storage isolated. circuits. Interaction appropriate electric units

Interaction with with space control space control

1 Optimiser plus time Effective boiler Compensated with TRVs and room Segregated HWS

control of zones. sequencing and space temperature thermostats except system, or top Time control of HW control strategies. reset and separate zone in room with space located or dual storage High efficiency circuits reset sensor thermostats on

boilers calorifiers

0 Optimiser plus time Effective boiler Compensated with None, or on Effective control of HW storage sequence control space temperature emitters designed thermostats on

reset for separate control calorifiers

–1 Timeswitch None No compensator None or TRVs Basic thermostat

Output less than 100 kW

1 Optimiser plus time Effective boiler Compensated with TRVs and room Segregated HWS

control of zones where sequencing and space temperature thermostats except system, or top appropriate. Time control strategies. reset and separate zone in room with space located or dualcontrol of HW storage High efficiency circuits reset sensor thermostats on

boilers calorifiers

0 Effective time control Effective boiler Compensated with None or on emitters Effective plus time control of HW thermostat space temperature designed for thermostats on storage reset separate control calorifiers

–1 Timeswitch Boiler thermostat Not compensated None or TRVs Thermostat

Page 14: Building control system, aplication guide   cibse guide

(CCTV) systems, as well as the information technologynetwork necessary for the user’s business operation. Allthese services communicate within their own system usingsome form of network. There are major potential benefits ifthe various systems can communicate with each other, usingthe same communications network or a limited number ofcompatible networks:

— the reduction in cabling and infrastructure cost

— the ability of the systems to share information witheach other.

This process is known as systems integration. At its most basiclevel, it means that devices from different manufacturers mayuse the same communications network, communicating withtheir peers and not interfering with other equipment. At themost advanced level, all systems within a building use thesame communications network, exchange information witheach other and are controlled from a single supervisor. Forinstance, the presence detectors of a lighting control systemmay feed information on out-of-hours occupancy to thesecurity and access control systems. Full integration is alsoknown as the intelligent building concept.

HVAC control systems operate in real time, ensuring properoperation of the environmental control system. Theinformation generated may be fed into the informationtechnology system where it can be used for the productionof reports, energy monitoring and targeting and thepreparation of maintenance schedules.

1.7 Building operationA well-planned control system offers improved man-agement of building services and can form the core of anintegrated facilities management system, covering otherbuilding-related services such as access control, security,energy monitoring and targeting, information technologyand maintenance. The amount of direct involvement bystaff in the day-to-day running of an HVAC system hassteadily reduced over recent years. However, it would be amistake to assume that the control system can be left to takecare of itself from the moment of handover. The client mustchoose from a range of options, from running the buildingservices in-house with the client organisation’s own staff, tooutsourcing to a service bureau who may supervise efficientoperation, deal with occupant requests and organisemaintenance, all from a remote supervisor. Whichever formof organisation is chosen, there should be clear ownershipof the control system with unambiguous responsibility forits successful operation. This requires a commitment by theclient to ensure adequate resources for the operation and

maintenance of the building control system; part of thiscommitment is the provision of proper training for staff.The organisation should ensure prompt and effectiveresponse to requests or complaints from the buildingoccupants; several studies have confirmed the importanceof rapid response in ensuring occupant satisfaction withtheir place of work.

The software which has been developed for BMS supervisorshas greatly simplified the day-to-day management of evenlarge BMSs and will show savings in operating staff costscompared with a simpler system which requires frequentattention. With the development of wide area networks, it ispossible to have remote supervision. This enables skilledpersonnel to be located at a single site and able to monitorthe performance of several BMSs in scattered buildings,leaving less qualified staff to carry out the daily operationon site. There will also be a saving in maintenance costs asthe BMS is able to keep run-time records of all equipment,allowing maintenance to be planned effectively. Earlywarning of failure is available from monitoring. Plant life isextended by the reduction in hours of use that is obtainedby scheduling, by reducing unnecessary device operation orunstable hunting and by reducing fan and pump speeds.

1.8 The benefits of a BMSWhen deciding on the appropriate type of control system tospecify for a building, it is necessary to remember that the

Introduction: the need for controls 1-5

Table 1.3 Rule-of-thumb costs and benefits of control bands(12)

Control Capital cost increase Energy usage, Payback, over Commentsband over Band 0 (%) compared with Band 0 base (years)

Band 0 (%)

2 100–200 –20 2–4 Highly recommended for minimum energy usage

1 50–100 –10 1–2 Recommended for costeffective energy savings

0 0 0 N/A Minimum

–1 N/A ≤ +50 N/A Does not meet BuildingRegulations since 1985

Table 1.4 Benefits of a BMS

Building owner Higher rental valueFlexibility on change of building useIndividual tenant billing for services

Building tenant Reduced energy consumptionEffective monitoring and targeting of energyconsumptionGood control of internal comfort conditionsIncreased staff productivityImproved plant reliability and life

Occupants Better comfort and lightingPossibility of individual room controlEffective response to HVAC-related complaints

Facilities manager Control from central supervisorRemote monitoring possibleRapid alarm indication and fault diagnosisComputerised maintenance schedulingGood plant schematics and documentation

Controls contractor Bus systems simplify installationSupervisor aids setting up and commissioningInteroperability enlarges supplier choice

Page 15: Building control system, aplication guide   cibse guide

benefits of a modern control system are enjoyed variouslyby the different groups of users involved with the building.Table 1.4 lists some of the benefits to be achieved with aneffective modern BMS. It goes without saying that thesebenefits will only be obtained if the system is properlyspecified, installed, commissioned, operated andmaintained. It is the function of this guide to assist inachieving that goal.

1.9 SummaryEffective control of the heating, ventilating and airconditioning systems in a building is essential to provide aproductive, healthy and safe working environment for theoccupants. Without a properly functioning BMS theactivities carried out in the building will be disadvantaged.Along with good building design and efficient HVAC plant,the BMS plays a vital role in the prevention of energy wasteand reducing the environmental impact of the building.

Modern BMSs are based on intelligent controllers whichmay be programmed to carry out a wide range of controlfunctions. Typically, a number of controllers are employed,each controlling an item of plant or an HVAC subsystem.The controllers communicate with each other and with acentral supervisor over a local area network (LAN). Thesystem manager is able to monitor and control the entireBMS from one point.

The scale and complexity of the control system should beappropriate to the building and its operation; highlyeffective and reliable control may be achieved withrelatively simple control systems. However, whenconsidering the cost effectiveness of a BMS, all theoperational benefits that flow from a well-managed facilityshould be taken into account: not only energy saving butalso the reductions in staffing cost, improved maintenancescheduling and the benefits of system integration withother building facilities. Such facilities as access control,security and lighting may be integrated with the BMS,

giving total building management from one point. There issteady progress towards compatibility between products, sothat devices from different manufacturers may share thesame LAN and event interact directly with each other. Thegoal of freely interchangeable devices is termedinteroperability.

References1 Butler D J G Phase-out of CFCs and HCFCs: options for owners and

operators of air-conditioning systems BRE IP 14/95 (Watford:Building Research Establishment) (1995)

2 CIBSE code of professional conduct (London: CharteredInstitution of Building Services Engineers) (1995)

3 CIBSE policy statement on global warming (London: CharteredInstitution of Building Services Engineers) (1990)

4 Energy efficiency in buildings CIBSE Guide F (London: CharteredInstitution of Building Services Engineers) (1998)

5 European Standard BS EN 7730: Moderate thermal environments— determination of the PMV and PPD indices and specification ofthe conditions for thermal comfort (London: British StandardsInstitution) (1994)

6 Nicol F, Humphreys M A, Sykes O and Roaf S Indoor air temperaturestandards for the 21st century (London: E & F N Spon) (1995)

7 Environmental design, CIBSE Guide A (London: CharteredInstitution of Building Services Engineers) (1999)

8 Statutory Instrument 1980/1013: control of fuel and electricity(amended) Order 1984 (London: Stationery Office) (1984)

9 Leaman A PROBE 10 occupancy survey analysis BuildingServices Journal 19(5) 37–41 (1997)

10 Best practice in the specification for offices (Reading: BritishCouncil for Offices) (1997)

11 Ashford C J. Avoidable waste/base energy budgeting BRESCUWorkshop Document (Watford: Building ResearchEstablishment (1997)

12 Controls and energy savings Fuel Efficiency Booklet 10 (Harwell:Building Research Energy Conservation Support Unit) (1995)

1-6 Building control systems

Page 16: Building control system, aplication guide   cibse guide

2.0 GeneralA control system consists of three basic elements: asensor, a controller and a controlled device (see Figure2.1). The sensor measures some variable such astemperature and transmits its value to the controller. Thecontroller uses this value to compute an output signal,which is transmitted to the controlled device, which thenacts to change the output of the load, which acts on thecontrolled system. In the majority of cases relevant to thisGuide we are dealing with closed loop systems, where thecontroller is attempting to control the variable whosevalue is being measured by the sensor. The results of itsactions are fed back to the controller input and the systemis said to have feedback. In the example shown in Figure2.1, the controller is attempting to maintain roomtemperature at a set point. A low room temperatureresults in increased output from the heater, which thenraises the room temperature. This increase is detected bythe sensor and transmitted to the controller, which altersits output accordingly to reduce the difference betweenset point and the measured value of the controlledvariable. In the discussion of control modes that follows,it is implicitly assumed that the system is inherentlycontrollable. Poor design may result in a system that ispractically impossible to control; this will be discussedfurther below.

Open loop or feedforward systems operate withoutfeedback. As before, the operation of the controlled deviceis a function of the value measured by the sensor, but this

does not result in a change to the measured variable. Aweather compensator is an example of open loop control,where an external air temperature sensor is used tocontrol the flow temperature in a heating circuit used toheat a building. The control system has no way ofknowing if the desired internal temperature has beenachieved.

In practice, a control loop may have more than one inputsignal and more than one output signal. Groups of controlloops can be chained together to create control sequences.The simple description above implies that the input andoutput of the controller are continuous variables and this isso for such variables as temperature. An important part ofpractical control systems is a set of complex interlocks,where the operation of one part of the system is contingenton the operating state of several other variables andsystems. Many inputs and outputs are thus binary (on/off)in nature. When preparing a points list, it is conventional torefer to them as digital inputs and digital outputs (DI andDO); this does not imply DDC.

2.1 Control modesConsider again the simple closed loop system of Figure 2.1.The way in which the control system responds to a changein the controlled variable is described by the control mode.Several control modes are in use and it is important to selectthe appropriate mode for the job in hand.

2-1

2 Control fundamentals

2.0 General

2.1 Control modes

2.2 Optimum start

2.3 Weather compensation

2.4 Stability and tuning

2.5 Artificial intelligence

2.6 Summary

This section introduces the concept of feedback and the control loop. It describes the basic control modes used in HVAC

controls, including:

— simple on/off control

— proportional, integral and derivative control

— optimisers and compensators

— intelligent controls.

Issues of stability are dealt with and methods of tuning control loops for the best combination of response speed and stabilityare given. The section goes on to discuss advances in adaptive controls, which learn by experience how to optimise operationof a controller.

Page 17: Building control system, aplication guide   cibse guide

2.1.1 Two-position (on/off) control

In this mode, the controlled device gives either maximumor minimum output, typically on and off. Figure 2.2illustrates two-position control for a simple heating system.It is desired to control temperature at the set point. Forreasons that will become clear, it is necessary for there to bea temperature differential between switching on andswitching off of the controlled device. With the heating on,the space temperature rises until the sensor output exceedsthe set point. The heating then switches off and stays offuntil the temperature falls through the differential andreaches the lower limit, whereupon it comes back on andthe cycle repeats. The temperature interval between theupper and lower limits is termed the differential gap ordifferential band; in American usage it may be referred toas the deadband. Within the differential gap the output maybe either on or off, depending on the last switchingoperation. In accordance with present convention, the setpoint is taken to be the upper point of the differential gap;earlier conventions take it to be the centre point. The roomtemperature continues to increase for a time after theheating system has been switched off; this is caused by, forexample, hot water present in the radiators. Two-positioncontrol results in a swing of temperature about the set pointand a mean temperature that normally lies below the setpoint; some systems when operating under light loads maygive a mean temperature above the set point. The swingmay be reduced by reducing the differential, but at the costof increased frequency of switching, with attendant wear onthe system. The peak-to-peak variation in space tem-perature is termed the swing or operating differential andthe differential of the controller itself, i.e. the differentialthat becomes apparent by turning the dial of thethermostat, is known as the mechanical or manualdifferential.

2-2 Building control systems

Figure 2.1 The components of a control system. In practice, somecomponents may be combined

Set point

Differential

Figure 2.2 Two-position (on/off)control

Page 18: Building control system, aplication guide   cibse guide

The common domestic room thermostat is an example of atwo-position controller. The inherent differential of thethermostat is of the order of 3 K, for mechanical reasonsnecessary to provide a snap action operation of the contactsto avoid arcing. The operating differential may be reducedby incorporating an accelerator heater in the thermostat. Alow-powered heater within the body of the thermostat iswired in parallel with the load and comes on with theheating system. This has the result of increasing thetemperature seen by the thermostat, resulting in earlierclosure. The frequency of switching therefore increases,giving a lower operating differential and reducedtemperature swings in the room. The effect of theaccelerator is to reduce the mean room temperatureachieved in practice below the set temperature and thiscontrol offset increases with load. This is equivalent to theload error found with proportional control and the action ofthe accelerated thermostat may be described as pseudo-proportional.

Floating control is a form of two-position control whichrequires that the controlled device can have its outputincreased or decreased by a slow-moving actuator. It is alsoknown as three-position or tristate control. A typicalexample would be a motorised valve controlling flow of hotwater. The valve moves slowly towards open or closedposition during the application of a signal from thecontroller; with no signal, the valve stays where it is andholds its position. The output of the controller is now threerather than two position: increasing, decreasing and off (i.e.no change). Figure 2.3 illustrates this mode of control.When the room temperature exceeds the upper tem-perature limit, the controller signals the valve to startclosing. The valve slowly moves towards the closedposition, reducing the heat supply to the room. When theroom temperature falls to the upper limit, the controllerswitches off and the valve stays where it is. The roomtemperature now floats within the neutral zone, until itcrosses either the upper or lower temperature limit,whereupon the valve is driven in the appropriate direction.Such a system is designed to have a long operating time

between fully open and closed positions of the controlleddevice; with a short operating time the action behaves likesimple on/off control. Floating control is used for systemswhere the sensor is immediately downstream from the coil,damper or other device that it controls. It is not suitable forsystems with a long dead time. A variant is proportional-speed floating control, where the further the value of thecontrolled variable moves outside the neutral zone, thefaster the actuator moves to correct the disturbance. This isin fact very similar to integral action.

2.1.2 Proportional control

Proportional control requires a continuously variableoutput of the controlled device. The control systemproduces an output which is proportional to the errorsignal, i.e. the difference between the value of thecontrolled variable and the set point. For the controller toproduce an output to match the load on the system, it isnecessary that there be an offset between the controlledvariable and the set point. In steady-state conditions, aproportional controller produces an offset or load error,which increases with the load on the system. Figure 2.4shows the operation of a proportional controller for aheating system. The control output increases from 0 to100% as the input falls from the set point through theproportional band, also known as the throttling range. Itcan be seen that in steady-state conditions the equilibriumvalue of the control point will be below the set point andthat this offset will increase with load, e.g. in colder weatherwhen the heating load is greater. For cooling systems, theequilibrium value will be above the set point.

The proportional band may be expressed in units of thephysical quantity being controlled, e.g. ºC, %RH, pascal, oras a percentage of the controller scale range. If, for instance,the controller has a scale range of 0–80ºC and a proportionalband of width 20 K, the proportional band is 25%. The gainof a proportional controller is the reciprocal of theproportional band, expressed either in physical units, e.g.K–1 or non-dimensionally, e.g. a proportional band of 50%is equivalent to a gain of 2.

Control fundamentals 2-3

Figure 2.3 Floating control

Figure 2.4 Proportional control. Diagram shows steady-state conditionswith the controlled variable at Tc with a controller output Yc. Tc is at anoffset or load error below set point. (Sometimes the set point is in themiddle of the proportional band)

Page 19: Building control system, aplication guide   cibse guide

Figure 2.5 shows the response of a proportional controlsystem to a change in demand. The value of the controlledvariable follows a damped oscillation before settling downto the steady offset temperature. The amount of offset maybe reduced by narrowing the proportional band, but at therisk of introducing instability; as the proportional band isreduced, the control action approaches on/off.

A form of proportional control known as timeproportioning may be achieved even if the output device isonly capable of a two-position output, e.g. high/low oron/off. The output from the controller varies the ratio ofon/off times within a constant cycle period, e.g. if the cycletime is 10 minutes and the controller calls for 40% output,the output device will be switched on for 4 minutes and offfor 6 minutes. The cycle time may be set independently; itshould be sufficiently long to avoid any problems of wearcaused by too frequent switching of the controlled device,but shorter than the response time of the overall system.The method is suitable for systems with long responsetimes, where it will give much lower temperature swingsthan simple on/off control. The control behaviour is similarto a proportional system and will show a load error. Timeproportioning control may be used for the control ofelectric resistive heaters where the switching frequency islimited by the requirement to avoid electrical disturbanceson the supply(1).

2.1.3 Integral control

Integral control is not often found on its own, but isnormally combined with proportional control in a PIcontroller. In its pure form it produces a rate of change ofthe output of the controller proportional to the deviationfrom the set point, or in other words, the output is afunction of the integral over time of the deviation from theset point. When the controlled variable is at the set point,the rate of change of output is zero. The system shouldtherefore settle to a steady-state condition, with steadyoutput and zero offset. The control mode is similar tofloating control, but with a zero width neutral zone andvariable rate of change of output: compare withproportional-speed floating control. It is illustrated inFigure 2.6.

When integral control is used by itself, it must be used insystems with short time constants and fast reaction rates. It

is not suitable for a system with slow responses or long timelags, where it will over-correct. A typical controlled deviceis a valve driven by a variable-speed actuator, which givesthe required variable rate of change of control response. Aconstant-speed actuator may be used where the controllerprovides a variable duration pulsed current to give effectivevariable speed. The speed of closure of the valve must beslow compared to the speed of response of the controlledsystem. The more common combination of proportionaland integral control is discussed below.

2.1.4 PI — Proportional plus integralcontrol

Adding integral control to a proportional controllercompensates for the load error. This is probably the mostwidely used mode in HVAC control and when correctly setup is capable of providing stable control with zero offset.The controller integrates the deviation from set point overtime and uses this value to adjust the control output tobring the controlled value back towards the set point. Theproportional band may therefore be increased to give stablecontrol; the load offset that would otherwise be introducedis eliminated over time by the integral action. The integralsetting is characterised by the integral action time, which isthe time it takes for the integral term of the control outputequation to match the output change due to theproportional term on a step change in error. Alternatively,the integral setting may be characterised as the reset rate,which is the inverse of the integral time, and measured inresets per minute. Most PI controllers are interactive, wherethe integral gain is multiplied internally by the gain settingof the proportional action (see Appendix A2). The practicalimplication is that the proportional band may be adjustedwithout affecting the integral time. A non-interactivecontroller has independently adjustable gains for theproportional and integral actions, and so adjusting the

2-4 Building control systems

Figure 2.5 Response of a proportional controller to a sudden change inload

Figure 2.6 Pure integral control action. System is initially in steady state.Figure shows response to a step decrease in set point

Page 20: Building control system, aplication guide   cibse guide

proportional gain will alter the integral action time asdefined above. A long integral time will increase the steady-state load error; in the limit of infinite integral action timethe PI controller becomes a simple proportional controller.However, if the integral time is reduced to a valuecomparable to or less than the time constant of thecontrolled system, instability will result.

The output of the integral term depends on the pasthistory of the controlled variable, and problems may resulton start-up where the controller treats the preceding offperiod as a long-term error. This is known as wind-up.Wind-up will also occur if the controller output is 100%and the error remains positive; in this situation theintegral action will continue to increase to a huge positivevalue. When the system becomes controllable again, a longperiod of negative error will be required to unwind theintegral term and return to normal operation. Controllersincorporate anti-wind-up features to prevent this, either bylocking the integrator at the pre-existing value wheneverthe controller output is at either extreme, or by limitingthe integrator to some maximum value, typically 50% offull output. Similar problems can occur on starting up asystem and some systems disable the integral action onstart-up until the system is controlling within theproportional band.

2.1.5 PID — Proportional plus integralplus derivative

Derivative action provides a control signal proportional tothe rate of change of the controlled variable. This has theeffect of reducing control action if the controlled variable israpidly approaching the set point, anticipating that thevariable is about to reach the desired value and so reducingovershoot. It is therefore of value in systems with highinertia. Derivative action can cause problems in practice. Ifthe measured variable is subject to rapidly varying randomchanges, the derivative action of the controller will producean erratic output, even if the amplitude of the changes issmall. See the note on derivative kick in Appendix A2.Derivative action is never used on its own, but is combinedwith proportional and integral action to produce PIDcontrol, also known as three-term control. A three-termcontroller is capable of maintaining a zero offset understeady conditions, while being able to respond to suddenload changes.

The gain setting of the derivative action is defined as thederivative action time, which is the time, usually measuredin minutes, taken for the proportional term to match thederivative term when the error changes linearly with time.Derivative action is not normally required in HVACapplications and setting the derivative time of a PIDcontroller to zero results in PI action. Three-term PID actionis used mainly in process control applications.

Figure 2.7 shows the ideal characteristics of PID control onthe behaviour of the controlled variable on start-up. Withproportional control only, the output is a function of thedeviation of the controlled variable from the set point. Asthe controlled variable stabilises, a residual load errorresults. With the addition of integral control, the controlledvariable eventually returns to the set point, but there is stillsome overshoot before stable operation is achieved. Addingderivative control reduces the overshoot and the final setpoint is achieved in a shorter time.

2.1.6 Digital control

Microprocessor controllers operate by sampling values ofthe controlled variable at discrete intervals of time. Themicroprocessor then calculates the required controlleroutput. For the most part, the processor mimics theanalogue control modes described above. The controller isable to store past values of the controlled variable, which areneeded to calculate derivative and integral terms.Programmable controllers are described in more detail in3.8. One important difference between analogue and digital

Control fundamentals 2-5

Proportional control

Proportional–integral control

Proportional–integral–derivativecontrol

Figure 2.7 Illustration of PID control modes

Page 21: Building control system, aplication guide   cibse guide

controllers is the effect of sampling rate. The frequency ofsampling is limited by the speed of the processor and anymultiplexing of the controller input, plus the ability of thenetwork to transmit frequent messages. If the sampling rateis too low, instability may result if the controller is delayedin taking appropriate control action. Where there is asufficiently fast sampling time, some controllers update thecontrol output at intervals which are longer than thesampling interval; the interval between changes in outputis known as the loop reschedule interval. Some controllersallow the loop reschedule interval to be adjustedindependently from the sampling interval of the controller.

The control equations described in Appendix A2 aretransformed in a digital controller into discrete timealgorithms. The standard PID equation is called theposition algorithm, since the position of the controlelement is related to the output signal. An alternative isthe velocity or incremental algorithm. At each time step,the controller makes an adjustment to the position of thecontrolled device which is proportional to the change inthe deviation of the controlled variable from the set pointsince the last sample, plus a term proportional to thedeviation. Incremental control usually employs a slowmoving actuator. At each time step, the controllercalculates the required change in actuator position andsends a timed pulse to the actuator to move it the requiredamount. This control mode is similar to the floatingcontrol mode described in 2.1.1. It is found to work welland has the advantage of avoiding integral wind-up. Thedisadvantage is that the controller has no information onthe actual position of the controlled device. If knowledgeof the position is required, the controller can integrate thecontroller output and calculate the position of thecontrolled device. This integration calculation requires tobe re-zeroed at intervals. This may be done by driving theactuator to a limit stop to provide a fix of its position. Thismay be done automatically each day during out-of-hoursoperation. The mathematical treatment of incrementalcontrol is given in Appendix A2.

2.1.7 Cascade control

For some applications it is an advantage to divide thecontroller into two subsystems: a submaster controllerwhich controls an intermediate part of the controlledsystem, and a master controller which adjusts the set pointof the submaster loop. A typical application is fortemperature control of a large space, where the mastercontroller controls the supply air temperature set point as afunction of space temperature, and a submaster controllercontrols the supply air temperature by modulating theheating coil valve (Figure 2.8).

In its standard form, the submaster controller providescontrol of the supply air temperature against variations inincoming air temperature or fluctuating heating coil watertemperature. The master controller resets the supply airtemperature set point as a function of the space temperatureusing PI control. Care may be necessary to avoid instabilityif both loops use integral action. Some confusion interminology may be found. An unambiguous term for thissystem of control is cascade control, and is used in thisGuide. Cascade control is also commonly known in the UKas reset control. In the USA simple integral control may bereferred to as reset, and a cascade controller is commonlyreferred to as master–submaster. The terms master–slave

and primary–secondary are also used to refer to the twocontrol loops. Cascade control is used when PI control aloneis not suitable or will not provide stability, for instancewhere the space temperature responds slowly to variationsin supply air temperature.

2.1.8 Time lags

In any feedback control loop, the response of the controlledsystem, as seen by a change in the sensor output, does nothappen instantaneously upon a change in the controlledoutput. Two types of delay may be identified. A transportdelay, also known as a distance–velocity lag, represents the time it takes for the heating orother medium to travel from its source to the point whereits heat begins to be transferred to the controlled space. Inlarge installations, distances can be very long and it cantake some minutes for a change in water temperature atthe boilerhouse to reach distant points in the building. Thesecond type of delay, termed a transfer lag, depends on thetime taken to increase the temperature of a component dueto its thermal capacity. Consider the simple heating circuitof Figure 2.9. When the controller gives the signal to openthe valve, hot water flows towards the heating coil, taking atime equal to the distance velocity lag to reach it. A series offirst-order transfers then take place: primary water toheating coil, heating coil to calorifier water, water tocylinder material and finally cylinder metal to the sensor.The resultant response of the temperature sensor is shown.This is typical of a higher-order response, and may beapproximated by a combination of dead time and first-order response as shown.

All lags contribute to poor control. Integral or floatingcontrol is unsuitable for systems with a significant deadtime, since the controller will continue to change theoutput during the dead time, resulting in overshoot. PIcontrol is then more suitable. The proportional control,with adequately wide proportional band, provides a stablecontrol, and the integral action, with suitably long integraltime, removes the load error.

2.1.9 Logic control

The use of microprocessor-based DDC controllers offersenormous freedom to the controls designer, since virtuallyany control strategy may be programmed into thecontroller software. In practice, digital controllers are basedon the well-understood control modes described in this

2-6 Building control systems

Figure 2.8 Cascade control. The room temperature is used to reset the setpoint of the controller controlling the supply air temperature

Page 22: Building control system, aplication guide   cibse guide

section. The widely used universal controller, whichincorporates pre-programmed control modules in itssoftware is described in 3.8. The controller may beconfigured to meet the requirements of the actual controlstrategy to be implemented. Some examples of logic controlare given in 5.8.2 and 5.14.3.2.

The controllers incorporate a number of logic controlfunctions which may be used to improve control operation.Some examples are:

— Hysteresis. The hysteresis module only passes achange in input which is greater than a presetamount. It can be used to stop the control systemresponding to small fluctuations in the controlledvariable, so reducing control action and wear.

— Averaging. The averaging module is used to producea mean value of a number of inputs. For example,the system may be set up to control mean zonetemperature, averaged over several temperaturesensors. Sophisticated versions may beprogrammed to ignore extreme values.

— Logic operators. Logic modules provide the fullrange of Boolean AND, NOT, OR and XOR gates. Theyare used to provide software interlocks, e.g.preventing operation of a heating system whenwindows are open. Safety-critical interlocks shouldbe hardwired.

— Look-up tables. Functional relationships can beprovided in the form of look-up tables. Examplesare the conversion of a thermistor resistance to atemperature or the software linearisation of acontrolled element characteristic.

The full range of available modules is too great to list here.The range of modules is sufficient to cover most controlrequirements and the controller manufacturers provideexamples of control strategies to assist in configuration. Ifrequired for special situations, it is possible to write controlstrategies using a high level programming language, such asBASIC or C.

2.1.10 Choice of control mode

When selecting the appropriate control mode, the followingconsiderations should be taken into account:

— the degree of accuracy required and the amount ofoffset that is acceptable

— the type of load changes expected, includingamplitude, frequency and duration

— the system characteristics, such as the number andduration of time lags and speed of response ofsubsystems

— the expected start-up situation.

In general, use the simplest mode that will meet therequirements. Using a complicated mode may result indifficulties in setting up and lead to poorer rather thanbetter control. Derivative control is not normally requiredin HVAC systems. Its function is to avoid overshoot in a highinertia system by measuring the rate of approach to setpoint and reducing control action in advance. It is used insome boiler sequencers, where it will inhibit bringing anadditional boiler on line if the rate of rise of watertemperature shows that the operating boilers will achievethe required temperature on their own. Table 2.1 liststypical applications.

2.2 Optimum startOne of the most important functions of a building controlsystem is time control, ensuring that plant is switched offwhen not needed. Substantial energy savings may be madeby intermittent heating or cooling of a building comparedwith continuous operation. The savings achievable from

Control fundamentals 2-7

Figure 2.9 Response of system with dead time. On opening the valve at t = 0 there is a distance–velocity lag DV before the primary hot waterreaches the heating coil. The coil then heats up with a first-order response.The sensor has a higher-order response, which may be approximated by afirst-order response with dead time

Table 2.1 Recommended control modes

Application Recommended control mode

Space temperature P

Mixed air temperature PI

Coil discharge temperature PI

Chiller discharge temperature PI

Air flow PI. Use wide proportional band andshort integral time. PID may be required

Fan static pressure PI. Some applications may require PID

Humidity P, possibly PI for tight control

Dewpoint P, possibly PI for tight control

Page 23: Building control system, aplication guide   cibse guide

intermittent heating compared with continuous heatingdepend on several factors. The savings will be greater in alightweight building which cools and heats up quickly; anyestimation of overall running costs must take into accountall relevant factors. Heavyweight buildings are able toabsorb peak gains and benefit from night cooling, whichmay outweigh any savings from intermittent heating. Ingeneral, intermittent heating and cooling will be morebeneficial in the following situations:

— lightweight building (low thermal mass)

— short occupancy period

— generously sized plant.

Simple timeswitch control can be effective and is suitable forheating systems with a heat output of up to about 30 kW.Above this figure, an optimum start controller isrecommended; above an output of 100 kW, optimum startcontrol is required by the Building Regulations(2). The time ofswitching on prior to occupancy is selected to ensure that theheating system has time to achieve a comfortabletemperature at the start of the occupancy period. If this iscorrect in cold weather, the system will come onunnecessarily early in mild weather, giving higher energyconsumption than necessary. Nor will a simple timeswitchbe able to cope with the longer preheat period necessary aftera weekend or holiday. An optimum start controller, oroptimiser, is designed to calculate the latest switch on timeunder a range of operating conditions. Figure 2.10 illustratesthe required control characteristic. During the unoccupiedperiod, the plant normally operates to provide a minimumtemperature to provide protection for the building fabric andcontents. This is typically 10ºC but may be lower. Separatefrost protection must be provided for the heating system.

The primary function of the optimiser is to calculate thelatest switch on time. Several algorithms have beenproposed. The most widely used is BRESTART(3). Thiscalculates the switch-on time as a function of both internalspace temperature and external air temperature. Mostcontrollers incorporate a self-learning or adaptive feature.By following the building performance over a few weeks,the controller sets its internal parameters to match thecharacteristics of the actual combination of building andheating system. The optimiser also selects maximum heatoutput from the heating system during the warm-up periodby disabling any weather compensator that may be fitted.The boost is terminated and compensation restored whenthe building reaches the desired temperature.

An optimum stop function may be fitted, whereby heatingor cooling is switched off before the end of the occupancyperiod, at a switch-off time calculated to ensure that thespace temperature does not drift outside predeterminedcomfort limits by the end of the occupancy period. Withair-handling systems, the zone air temperature willapproach the building fabric temperature within about 15minutes after switch-off. This may not provide comfortableconditions and so limits the usefulness of optimum stopstrategies. Optimum stop is used less often than optimumstart and the potential savings are less.

2.3 Weather compensationA building heating system is designed to provide fullheating on a design day; in practice an additional margin is

allowed to provide extra power during the boost period ofintermittent heating. The capacity of the heating system istherefore greater than required for operation in all but thecoldest condition. For buildings heated by a conventionalradiator system, operation during mild weather with theflow temperature at the full design value, typically 80ºC,results in control problems, high temperature swings andconsequent discomfort; it also results in wasteful heat lossfrom the hot water circuit. For buildings larger thandomestic or the smallest commercial, it is required by theBuilding Regulations that weather compensation beprovided to adjust the flow temperature in accordance withthe outside temperature.

Compensation control allows the whole building to becontrolled as one unit, or as a limited number of zones,thus eliminating the need to provide a large number ofseparate space temperature controls. It has the addedadvantage of limiting heat loss in the event of increasedload, e.g. if windows are opened. If used as the only form oftemperature control, it requires the radiator size to becarefully matched to the heat requirement of the building;since this is virtually impossible to do in advance,provision must be made for balancing the system andadjustment of the compensator control characteristic. Apractical solution is to use weather compensation and trimlocal temperatures by the use of thermostatic radiatorvalves.

2-8 Building control systems

Figure 2.10 Optimum start control

Page 24: Building control system, aplication guide   cibse guide

The form of the weather compensator control characteristicis shown in Figure 2.11. The controller allows adjustmentof the minimum and maximum flow temperatures and theslope of the characteristic curve. The heat output from aradiator is proportional to the 1.3 power of the differencebetween mean radiator temperature and room temperatureand so the linear characteristic shown in the figure willtend to overheat in cold weather. Some controllers providea two-slope or curved line to allow for this. This isdiscussed in detail in Levermore(4).

Figure 2.12 shows a common method used in smallerbuildings of providing a compensated flow temperature.Water from the boiler is blended with cooler water from thesecondary circuit return in a three-port mixing valve. Thetemperature sensor is downstream of the valve andresponds quickly to temperature changes in the flow. Forlarger buildings or special circumstances, more complexcontrol arrangements may be needed. Where different partsof the building respond differently to external climaticconditions, it will be necessary to subdivide operation intozones, and perhaps add additional external sensors, e.g. asolar detector to aid control of the southern side of thebuilding.

The simple weather compensator described above is anexample of open loop control; there is no feedback fromzone temperature and the achievement of satisfactorytemperature depends on the accuracy of setting up thecharacteristic relationship between outside temperatureand flow temperature. The setting of the characteristic

curve should be reviewed whenever there is a change inbuilding use, which may affect the level of internal gains, ormodification such as fitting insulation. Variations in solargain with season or changes in shading due to foliage mayalso affect the settings. There are two modifications to thesimple weather-compensated circuit which give improvedcontrol and are becoming more commonly used.

— Zone trim. The standard weather-compensatedcircuit is used, with a zone trim applied to thecompensated water flow temperature. The trimmodifies the set point by a margin proportional tothe difference between the measured zonetemperature and the desired set point.

— Cascade control of zone temperature. The outsidetemperature sensor is not used, but replaced by aninternal zone sensor. This provides the input to a PIcontroller which resets the water flow temperature.This gives stable effective control of indoortemperature with no offset.

2.4 Stability and tuningThe stability of a control system is concerned with itsresponse to a disturbance. The disturbance may be a changein the external load, e.g. an increase in solar gain though thewindows of a building. The HVAC system is required to reactto bring the controlled variable (room temperature) backtowards the desired value. For practical reasons, thestability of a system is usually considered in terms of itsreaction to a sudden change in set point:

— Stable. After the change in set point, the controlledvariable sooner or later settles down to a new steadyvalue. On the way, there may be oscillations aboutthe eventual steady-state value. All the systemsshown in Figure 2.7 are characterised as stable; thepresence of an offset from the set point (load error)is no disqualification.

— Unstable. The system does not achieve a steady statefollowing a disturbance. There are two types ofunstable response:

— Oscillatory. The controlled variablecontinues to oscillate or hunt about the setpoint.

— Non-oscillatory. The controlled variablecontinues to increase or decrease until itreaches a limiting value.

Non-oscillatory instability is unlikely to be produced in anHVAC system except by a design or installation error. Forexample, confusing the connection of room temperaturesensors in different rooms will produce unstable control: anincrease in heat load in Room A will reduce the heat inputto Room B; the sensor in Room B will then demand moreheat for Room A. Instability may be produced by theintervention of the occupants. If an occupant opens awindow because the room is too warm and this results incool outdoor air blowing over a poorly placed thermostat,heat input to the room may be increased.

On/off control inevitably produces an oscillating value ofthe controlled variable. If the proportional band of aproportional controller is reduced below a critical value, thecontrol system goes into oscillation. When considering the

Control fundamentals 2-9

Figure 2.11 Weather compensation control characteristic with twoadjustable slopes

Figure 2.12 Weather compensator controlling flow temperature

Page 25: Building control system, aplication guide   cibse guide

effects of oscillation, it is necessary to distinguish variationsin the controlled variable from changes in the position ofthe controlled device and the associated system output. Thesystem output in an on/off system necessarily swings from 0to 100%. However, the swing in the controlled variable mayonly be a fraction of a degree where an acceleratedthermostat is used. A large variation in system output doesnot therefore necessarily imply unsatisfactory controlledconditions.

Most buildings and their HVAC systems have a high thermalmass and in consequence change temperature fairly slowly.As a result, building control systems may be relativelyinsensitive to poor setting up of the control system, and acontrol system that is hunting may produce conditions thatare acceptable to the occupants. Hunting behaviour mayonly be evident on directly observing movement of theactuators or by detailed logging of system behaviour by theBMS. A control system which hunts is unsatisfactory forseveral reasons:

— It produces excessive wear on valves and actuators.

— Temperature cycling may produce undesirableeffects on plant and equipment.

— It may produce instabilities in other parts of thesystem.

Some variation of control output and movement of thecontrolled device is inevitable as the system responds tosmall changes occurring within the building. Theopportunity should be taken to observe the action of thecontrolled devices at a time when the HVAC system iscontrolling in a steady state. Any movement should be slowand of small amplitude. It is difficult to give figures whichare of general application. However, as a rule of thumb,action should be taken to investigate the stability of thesystem if any controlled device is cycling with an amplitudegreater than 20% of its full range, or is changing position bymore than 20% in a period of 10 minutes.

The following factors must be taken into account to ensurea stable operating control system:

— correct tuning of controllers

— interactions between control loops

— stable operation must be ensured over all operatingconditions, e.g. variation of system gain with load

— the influence of sampling period.

Interaction between control loops. An HVAC system may containmany control loops, the actions of which interact with eachother. Consider, for instance a network of heat emitterscontrolled by two-port valves, being fed from a commonsecondary circuit. Each two-port valve is controlled by alocal control loop which maintains a zone temperature. Themovement of one valve in response to a change in load willalter the pressure seen by the other circuits, causing a changein flow, with a resultant alteration in the controlled variableand consequent movement of the vales. This in turn willchange the pressure seen by the original two-port valve. It ispossible for the circuits to interact in such a way that thevalves do not achieve a steady equilibrium position, butcontinue to hunt.

A general principle that applies to any feedback controlloop is that the sensor must measure the response of the

controlled variable relevant to that loop and not any other.The effects of interchanging the connection of sensors inadjacent rooms is an obvious example. If one room is belowits set point, additional heat will be supplied to the otherroom. This will result in a reduction in heat supply to thefirst room, giving maximum heating to one room and nonein the other.

A more subtle variation of this problem occurs when thetwo controlled zones overlap. Consider the example ofadjacent VAV boxes supplying a common space. Each boxhas its own temperature sensor, but the nature of thespace and the air flow patterns is such that the twotemperature sensors show the same value. If the set pointsof the two VAV boxes are not identical, one will show asmall positive error and the other a small negative error.Since it is impossible for both to have zero errorsimultaneously, the effect of PI control will be to produceintegral wind-up, which over time will result in one boxbeing driven to maximum output and the other tominimum. This effect may be mitigated by usingproportional-only control where there is a danger ofadjacent boxes interacting. The use of intelligent VAVboxes or fan coil units allows groups to be programmedwith a common set point, with one unit acting as amaster, controlling the others as slaves.

Operating conditions. An HVAC system is designed to operateover a wide range of conditions. Most design work is doneat design conditions, where the system is required toproduce maximum output. For most of the year, thesystem operates at part load where control behaviour maybe different from design conditions. Consider for instancea VAV system. The supply air is cooled by a cooling coil,which is modulated to control the air temperature. If theair flow is half the design maximum, then the change invalve position to produce a given change in airtemperature will be about half that required at full flow,i.e. the gain of the system has doubled. There is thereforea risk of instability if the control loop is tuned at designconditions. To ensure stability, tuning should be done inconditions which produce a high system gain.

Sampling time. Digital control systems measure thecontrolled variables at intervals known as the samplingtime. The sampling time is determined by:

— the time period required by the A/D converter

— any multiplexing between sensor inputs

— density of traffic on a bus system.

Too fast a sampling time will require an unnecessaryamount of data handling by the BMS. However, too slow asampling time may be inadequate to detect changes in thesystem in time to take appropriate control action. Wherethe sampled values are stored for evaluation, too slow asampling rate can produce unsatisfactory or misleadinginformation; a high frequency variation sampled at too lowa frequency may be interpreted incorrectly as a lowfrequency variation; this is known as aliasing. The correctsampling frequency may be selected by reference toShannon’s sampling theorem, which states that provided asignal contains no component with a frequency higher thanfmax, the signal may be reconstituted from a set of samplestaken with frequency at least twice fmax. In practice,sampling frequencies of 10 times the theoretical value areused(4).

2-10 Building control systems

Page 26: Building control system, aplication guide   cibse guide

2.4.1 Tuning

The behaviour of a control loop under changing conditionsis affected by the controller settings. Incorrect settings ofthe controller parameters may lead to unstable behaviour,resulting in large output swings, or else sluggish responseand a deviation from the desired set point. Optimumperformance from a controller depends on the correctsettings for the control parameters. Two forms of responsemay be considered to represent the acceptable boundariesof sensitive and sluggish behaviour:

— Quarter wave response. Following a disturbance, thesystem response overshoots the new equilibriumvalue and approaches equilibrium in a series ofdamped oscillations. The amplitude of the firstovershooting wave is four times that of the second.

— Critically damped. This response is the fastestapproach to the new equilibrium value that can beachieved without any overshoot.

Values of the parameters may be found by carrying out insitu tests on the control loop. There are two commontechniques used in estimation.

— closed loop ultimate cycling method (oscillationtest)

— open loop reaction curve method (transientresponse).

Both require the behaviour of the control loop to berecorded; parameter settings may then be calculated fromthe measured response. Several calculation methods areavailable and may be selected to give the desired behaviour;they are summarised in Appendix A2. It must beemphasised that the parameters calculated in this wayshould be regarded as guide values. Since system gain oftenvaries with operating conditions, control loop behaviourwill also vary. To ensure stable operation under allconditions, tuning should ideally be done under conditionsof high system gain. Where there is doubt, the parametersshould be adjusted as follows to reduce risk of instability:

— proportional band increased

— integral action time increased

— derivative action time decreased.

2.4.2 Practical tuning

Before starting formal tuning procedures, it is advisable tocheck the system manually. If manual operation isunsatisfactory, the problems should be rectified beforetuning the loop. Adjust the set point manually betweenseveral positions and observe:

— Is the process noisy: are there rapid fluctuations inthe controlled variable?

— Is there appreciable hysteresis or backlash in theactuator?

— Is it easy to maintain and change a set point?

— In which operating region is the process mostsensitive?

Some general principles should be borne in mind beforestarting to tune a control loop.

— In order for tuning procedures to work properly,the final output to the controlled device shouldhave a proportional action. An on/off controllercannot be tuned satisfactorily.

— The controlled device should be within itsoperating range, i.e. not driven to fully open orclosed, nor operating in a region where movementof the final actuator has little effect on the processoutput.

— Where cascade control is being tuned, tune theinner (submaster) loop first. Where a control loopdepends on the stability of some other part of thesystem, tune the primary service first, e.g. tune aprimary water circuit to ensure flow temperaturestability before tuning any of the secondary loops.

— Some controllers operate more than one controlleddevice, e.g. a temperature controller may operateboth heating and cooling coils. It may be necessaryto disable operation of one of the outputs to preventit being brought into operation during tuning if thecontrolled variable overshoots.

Determining the controller settings by the formal methodsdetailed in Appendix A2 may not always be practicable.Experience has shown the following adjustments will oftengive suitable settings.

— Proportional band. A conservative starting point forthe proportional band is a value equal to the changein the controlled variable produced by a 50%change in plant output.

— Integral time. A conservative initial value for theintegral time is to set it equal to the open loop timeconstant, estimated as the sum of the componenttime constants, e.g. actuator, sensor and HVACprocess.

— Derivative time. Derivative control is applied whenthere are significant delays in the control loop. Tryan initial value of derivative time equal to 50% ofthe loop dead time.

— Sampling time. Set to no more than 25% of the openloop time constant; greater sampling times mayresult in unstable control.

Guidance on typical initial controller settings will generallybe provided by the manufacturer. Table 2.2 shows suitablesettings for some common applications, which may be usedif no better information is available.

2.4.3 Self-tuning controllers

The methods described above for tuning PID controllers arebased on standard control theory, which makes assumptionsabout the linearity of the controlled system. In practice, theformal tuning methods may have disadvantages:

— Effort. Tuning control loops during commissioningis time consuming and it may be difficult to allocatethe skilled effort required when under pressure oftime. There is a temptation to leave the controllersat factory preset values, which are unlikely to beoptimum.

— Non-linearity. The tuning methods assume that thecontrol system is linear and that the system gain

Control fundamentals 2-11

Page 27: Building control system, aplication guide   cibse guide

remains constant. System gains vary with load andare likely to vary both over the day and over the year.Correct choice of valve or damper authority andcharacterisation helps to improve system linearity,but it is not always possible to achieve good linearityover the range of operations encountered.

Several means of automatic tuning of controllers havetherefore been developed. There are different approaches:

— Autotuning. Autotuning software automates thetuning procedure by exciting a controlled responseand calculating the optimum control settings. It isinitiated by a controls engineer during commission-ing or when required. Autotuning is applicablewhen the system characteristics are constant.

— Adaptive techniques. Where the operatingcharacteristics of the control system varysubstantially, it is desirable to use a form of self-tuning that acts continually to optimise the controlsettings. The different approaches are:

— Gain scheduling. If the variation of optimumsettings of controller parameters with plantoperating condition can be established,then the parameters are automaticallyadjusted as a function of plant operation.Gain scheduling is effective when theoperating dynamics of the system are wellunderstood.

— Adaptive control. Where the changes in plantdynamics are large and unpredictable, acontroller which continuously tunes itselfis desirable. Adaptive controllers use someform of plant model or pattern recognition.A commonly found form of adaptivecontrol is to be found in optimum startcontrollers, which are described below.

2.4.3.1 Autotuning

Several manufacturers market controllers with an inbuiltautotuning facility. Software within the controllerautomates the tuning procedure by exciting a response

from the plant and calculating the control parameters fromthe observed response. The controller is then set to the newparameters; the engineer may be required to accept thembefore they are applied. Before tuning, the process must bein a steady-state condition. The tuning action is initiated bythe controls engineer, normally by simply pressing abutton. The controller parameters remain fixed betweentuning sessions. An autotuner is therefore unable tocompensate for variations in system gain and the tuningprocess should therefore take place under representativeoperating conditions. In many HVAC systems there isinteraction between different control loops. When using anautotuner it is important to select the order in which theloops are tuned to minimise any interactions. Start withfast-responding local control loops; when these have beentuned move to larger slower loops. The use of autotuningcan give significant improvements in performance coupledwith a substantial reduction in commissioning timecompared with conventional PID controllers. Furtherdetails are to be found in Wallenborg(5) and Astrom et al.(6).

2.4.3.2 Adaptive techniques

The control characteristics of an HVAC system may varywith operating conditions. The characteristics andauthority of valves and dampers affect linearity of responseof a system and the achievement of a linear characteristic ofa complex system over its whole operating range is difficult.The gain of a system will also change with operatingconditions, e.g. the change in flow temperature producedby an optimiser or the change in inlet air temperature withseason will produce changes in system gain. Since a highsystem gain tends to produce control instability, controllersmust be tuned when the plant gain is high. This will ensurestability, but control performance may be sluggish in lowgain conditions. There is therefore an advantage to using acontroller which will retune itself automatically in responseto changing conditions.

If the performance of the control system is well understood,it is possible to monitor the operating conditions of theplant and adjust the control parameters in accordance witha data table which relates control parameters to operatingconditions. This process is known as gain scheduling,though it is not limited to adjusting the controller gain;derivative and integral times may be adjusted as required.Gain scheduling is not strictly a form of adaptive control,since no learning is involved. The relation between plantoperating conditions and optimum controller settings mustbe known in advance. It is possible to build up a schedule ofcontrol parameters by initiating autotuning under a rangeof operating conditions.

If the changes in plant dynamics are large and unpredictablethen a controller which continuously tunes itself has greatadvantages. Adaptive controllers learn the operatingconditions of the plant and control system by observing theresponse to changes in set point or external disturbances. Inorder to protect the system against unreliable parameterestimates, additional software is used to supervise thesystem to prevent poor control performance in unpredict-able situations; this is known as jacketing software. Thereare two basic approaches to adaptive control:

— Pattern recognition methods analyse the controlledresponse and recalculate new values of controlparameters. Oscillations and offsets are measuredand new control gains calculated when significant

2-12 Building control systems

Table 2.2 Typical settings for a PI controller

Controlled Controlled quantity Proportional Integral timedevice band (min)

Heating coil Zone temperature 2 K 0

Preheat coil Duct temperature 3 K 4

ChW coil Duct temperature 8 K 4

Humidifier Zone RH 15% RH 15

Dehumidifier Duct RH 15% RH 4coil

Thermal wheel Duct air temperature 4 K 4

Run around coil Supply air temperature 6 K 4

Recirculation Mixed air temperature 4 K 4damper

Ventilation Zone CO2 100 ppm 10supply concentration

Room terminal Zone temperature 3 K 4unit

Supply fan Static pressure 1000 Pa 1

Page 28: Building control system, aplication guide   cibse guide

adjustments are required. A pattern recognitionadaptive controller (PRAC) is described in Seem(7).The method was developed for systems that can bemodelled as a first-order plus dead-time response,which includes most HVAC systems. The controlleris claimed to be easy to use and provide nearoptimal control. It has been used successfully in anumber of HVAC situations.

— Indirect methods employ a model of the processwhich is continually updated by comparison withbehaviour of the real plant. The model is then used tocalculate updated values of the control parameters.This method may be combined with neural networks.

Adaptive controllers and self-tuning controllers have yet tofind wide application in the HVAC industry, though theyoffer potential benefits in reduction in commissioningtime, increased actuator life and improved environmentalcontrol. Their operation may be adversely affected if tuningis attempted in the presence of plant failure or periodicdisturbances. An adaptive controller which continuouslyseeks to optimise its operation may act to compensate forplant degradation and so delay needed maintenance action.

2.5 Artificial intelligenceConventional controllers, whether analogue or digital, relyon a precise mathematical relation between input andoutput. For a well-behaved system operating in a consistentenvironment, a well-tuned PID controller will givesatisfactory control. However, many real systems involveuncertainties, non-linearities and variations in theiroperating environment. There may be multiple inputswhich affect the desired control output. Such complicationsmay be difficult to incorporate in a conventional controller.Advances in artificial intelligence and the availability ofimproved processing power are leading to the developmentof new types of controller. Fuzzy logic and neural networksshow great promise in dealing with some aspects of HVACcontrol and their application is certain to grow.

Fuzzy logic is a means of decision making based on a set ofrules of the type IF (A is true) THEN (take action B). Therules are written based on knowledge and experience of thesystem to be controlled and are expressed in near naturallanguage(8). Fuzzy logic differs from conventional logic inthat a statement may have degrees of truth. To put it moreformally, a point can have simultaneous degrees ofmembership of several fuzzy sets. This represents the waywe deal with situations in real life; there is, for instance, no

abrupt transition between ‘comfortable’ and ‘cool’. Figure2.13 illustrates the chain of operations in a fuzzy logiccontroller, for the simple example of a single-input, single-output controller; one of the advantages of fuzzy logic is itsability to deal with multiple inputs and outputs. Thecontroller accepts a crisp input; crisp means an exactnumerical value, such as the deviation of a measuredtemperature from the set point. The controller thenfuzzifies the input, by establishing the degree ofmembership of the several fuzzy sets which have beendefined in the controller. For instance, a measured roomtemperature may have 80% membership of the set‘comfortable’ and 20% membership of the set ‘cool’. Thecontroller then applies the inference rules, which are of theform IF (the room is cool) THEN (set heating to half power).This results in an output which has membership of severalfuzzy output sets; this output is then defuzzified to producea crisp output value which is used to control the plant. Thedefuzzification process is analogous to the fuzzificationprocess, where the degree of membership of several outputsets is combined to produce a crisp output.

The main advantages of fuzzy control are that it does notrequire a model of the process to be controlled and that it ispossible to incorporate the results of operational experienceinto the set of rules. These would be otherwise difficult toincorporate into a conventional control algorithm. Fuzzycontrollers have been developed for HVAC systems and it hasbeen found that they offer advantages of robustness, energysaving and fast response, compared with conventional PIDcontrol(9). Simple fuzzy controllers are often found toexhibit undesirable oscillation when the system iscontrolling near the set point. It is possible to use the rate ofchange of the controlled variable as additional input to thecontroller. Extra fuzzy rules are added to modify thecontroller output according to the rate of change; this helpsprovide smooth control at conditions near the set point andis a common feature in fuzzy controller designs.

Neural networks attempt to reproduce the way the humanbrain learns by experience. In brief, a neural network deviceaccepts data from a number of inputs, processes the datausing a series of non-linear processing elements andproduces a set of output data. What distinguishes a neuralnetwork from other types of processor is that it does notdepend on a model or even an understanding of the process,but is capable of learning by experience. Learningalgorithms are employed which adjust the internalparameters to optimise the performance of the network.Accordingly, a period of training is necessary before a neuralnetwork can achieve satisfactory performance. Neuralnetworks are applicable where a high degree of non-linearity

Control fundamentals 2-13

Figure 2.13 Components of a fuzzycontroller

Page 29: Building control system, aplication guide   cibse guide

exists and there is a large amount of data available fortraining the network. Both these criteria apply to a BMS. Anumber of promising applications to HVAC systems havebeen identified(10):

— Condition monitoring. Incipient plant failure may bedetected by changes in performance. This requiresknowledge of how the plant operates under a widerange of conditions and the ability to detectvariations; a neural network can be trained to dothis.

— Optimisation. The operation of a complete HVACsystem is highly non-linear, making it difficult tooptimise performance under a range of loadconditions. A neural network can be applied tolearn the system behaviour and then used off-line toinvestigate optimum control strategy.

— Energy monitoring. Neural networks have thepotential to learn the consumption patterns againstkey variables such as occupancy, time of day,weather and process activity. Deviations from theexpected pattern can then be detected, giving earlywarning of increased energy consumption.

2.6 Summary The section sets out the basic concepts of open loop andfeedback control loops. The fundamental control modesused in feedback control are:

— proportional control, which produces a controloutput proportional to the deviation of thecontrolled variable from the desired set point

— integral control, which produces a control signalproportional to the time integral of the deviationfrom the set point

— derivative control, which produces a control signalproportional to the rate of change of the controlledvariable.

Proportional control can be used by itself to produce stable,effective control, but produces a load error, i.e. an offsetfrom the set point. Integral action may be added toproportional control to give PI control, which eliminatesthe load error over time. Derivative control is used toanticipate overshoot in systems of high inertia. PID controlcan produce rapid response to changes in load with littleoffset, but is rarely used in building control systems.

Controllers need to be tuned to avoid the problems ofinstability on the one hand, or sluggish response on theother. Formal methods of estimating the optimumparameter settings are summarised. In addition, practicalrecommendations are given of values which are likely to befound satisfactory in practice.

Optimum start control is an algorithm that has beendeveloped to turn on heating or cooling at the latest possibletime to ensure that comfort conditions are achieved at thestart of the occupancy period. The controllers are capable oflearning the behaviour of the building and heating systemand adjusting the settings accordingly; this is an example ofadaptive control. The control of compensated heatingcircuits is described; flow temperature may be related toeither outside weather in internal zone temperature.Developments in intelligent controls are described whichare leading to the introduction of adaptive controllerswhich are capable of continuously retuning themselves togive optimum operation.

References1 BS 5839: Fire detection and alarm systems for buildings: Part 1 1988.

Code of practice for system design, installation and servicing (London:British Standards Institution) (1988)

2 Conservation of fuel and power 1995 Approved Document L1(London: Stationery Office) (1994)

3 Birtles A and John R A new optimum start algorithm BuildingServices Engineering Research and Technology 6(3) 117–122 (1985)

4 Levermore G J Building energy management systems 2nd ed(London: E & F N Spon) (2000)

5 Wallenborg A O A new self-tuning controller for HVAC systemsASHRAE Transactions 97(1) 19–25 (1991)

6 Astrom K J, Hagglund T, Hang C C and Ho W K Automatictuning and adaptation for PID controllers – a survey ControlEngineering Practice 1(4) 699–714 (1993)

7 Seem J E Implementation of a new pattern recognition adaptivecontroller developed through optimisation ASHRAETransactions 103(1) 494–506 (1997)

8 Wang L A course in fuzzy systems and control (Englewood Cliffs,NJ: Prentice Hall) (1997)

9 Underwood C P HVAC control systems: modelling, analysis anddesign (Andover: E & F N Spon) (1998)

10 Barnard N I Neural networks: potential areas of application inbuilding services Building Services Engineering Research andTechnology 14(3) B15–B18 (1993)

2-14 Building control systems

Page 30: Building control system, aplication guide   cibse guide

3.1 SensorsSensors form a vital component of any control system.Sophistication in the computing and software functionscannot compensate for inaccurate information provided bypoor-quality or inappropriately mounted sensors. Thetypes of sensor available for use in building control systemsare reviewed and guidance on selection and installation isgiven.

3.1.1 General categories

The word sensor is generally used rather loosely to cover allprocesses between the measured variable and the input to thecontrol module. The functions may be broken down into:

— Sensing element: a component that undergoes ameasurable change in response to a change in thevariable to be measured.

— Transducer: an active device that produces anelectrical signal which is a function of the change inthe sensing element.

— Transmitter: a device that produces an electricalsignal that is a standardised function of the changein the physical variable and which can be used as aninput to the control module.

In practice the function of the transducer and transmitterare often combined. Their function may be referred to assignal conditioning, which may include filtering to removenoise, averaging over time, or linearisation. In somesystems the sensing element may be connected directly intothe controller, e.g. thermocouple input, where the signalconditioning now takes place inside the controller module.The various combinations are categorised as follows.

Status sensors produce a binary (on/off) output dependingon whether the measured variable is above or below a set

point. The sensors are normally mechanical devices, wherea physical movement of the sensing element causes switchcontacts to open or close. Typical devices are thermostats,humidistats and pressure switches. The output may beconnected to a digital input of a controller for statusreporting or software interlock purposes. Safety-criticalinterlocks are usually hardwired directly to the item ofplant which is to be switched off.

Where the condition being monitored is critical, it isimportant that it be measured directly. For instance, whereit is important to shut down part of a system in the event ofno air flow, the air flow in the duct should be monitored bya pressure sensitive switch; if the flow is non-critical it maybe satisfactory to simply monitor the presence of anelectrical input to the fan motor. The general form ofoutput from a status sensor is the provision of voltage-freecontacts.

Analogue sensors convert the value of the measuredvariable into an electrical signal which is input to otherdevices for measurement and control purposes. Analoguesensors may be subdivided into:

— Passive devices which consist of the sensingelement only and do not contain a transducer. Allsignal conditioning is carried out in the controllerto which it is connected. Examples includeresistance type temperature sensors. No powersupplies are required and the sensor is connectedvia field wiring directly to an analogue input on acontroller.

— Active devices which incorporate signalconditioning within the sensor device and include atransmitter which converts the measured value toan industry standard electrical signal forconnection via field wiring to an analogue input onthe controller. The output of the transmittercommonly takes one of several standard formsshown in Table 3.1. Signal transmission employing

3-1

3 Components and devices

3.1 Sensors

3.2 Actuators

3.3 Valves

3.4 Dampers

3.5 Motors

3.6 Pumps and fans

3.7 Control panels and motor control centres

3.8 The intelligent outstation

3.9 Summary

This section deals with the hardware components that make up a control system. Guidance is given on the choice of suitablesensors and the importance of correct installation is stressed. Valve sizing and characterisation is covered together with choiceof dampers. The use of variable-speed drives for pumps and fans is covered.

Page 31: Building control system, aplication guide   cibse guide

a 4–20 mA signal requires only a two-wireconnection and is suitable for use in hostileenvironments. It is commonly used in processcontrol applications. A 0–10 V transducer requiresboth a power supply and a signal output, needing athree or four-wire connection. The lower cost of0–10V systems leads to its widespread applicationin HVAC systems.

Intelligent sensors contain a microprocessor whichconverts the measured value or status of the measuredvariable into a digitally encoded signal for directcommunication over a network for onward transmission toother intelligent devices for control and measurementpurposes. In addition, an intelligent sensor may carry outadditional data processing before transmitting the value,such as:

— checking upper and lower bounds

— calibration and compensation functions

— calculating derived values, e.g. enthalpy.

3.1.2 Selection requirements

The correct selection and location of sensors is vital toachieving the required performance from any controlsystem. Sensor problems are the most frequent cause ofcontrol system malfunctions. A poor-quality sensor maysuffer from drift or early failure, resulting in poor controland high maintenance costs.

3.1.2.1 General requirements

The requirements that must be borne in mind whenselecting any type of sensor are set out in Table 3.2.

Sensor inaccuracy or failure is a major cause of problems inbuilding management systems. Experience shows that theproblems are usually caused by incorrect installation,rather than an intrinsic problem with the sensor itself.

3.1.2.2 Accuracy

The claimed accuracy for a sensor does not guarantee thatthe same accuracy will be achieved at the controller or BMSsupervisor, nor that it will be maintained over the operatinglife of the sensor. The accuracy of the overall measurementsystem depends on several factors:

— Accuracy of the sensing element. The claimed accuracyof the element may not be available over the wholeoperating range or may be quoted under ideal con-ditions.

— Sensitivity. This is the smallest change in themeasured variable that can be detected by thesystem.

— Interacting variables. The condition of the sensormay be affected by other environmental variables,e.g. an air temperature sensor will be affected bythermal radiation or an RH sensor by localvariations in air temperature.

— Stability. Sensors may drift with time and requirechecking. Stability is likely to be affected byoperating conditions.

— Hysteresis. The sensor reading may be affected by itspast history and speed and direction of change ofthe measured variable.

— Mounting. The mounting and location of the sensorwill affect the reading.

— Signal conditioning. Associated transducers willintroduce their own limitations to the accuracyachievable. Some systems ‘filter’ readings first andonly transmit when the measured variable haschanged by a specified ‘filter factor’. This is used tominimise network traffic.

— A/D conversion. The discrimination of any analogueto digital conversion will set a limit to theachievable accuracy. Eight-bit conversion dividesthe range into 256 steps, 12-bit into 4096 steps. Inthe latter case, a measurement range of –50 to 150ºCwould have a step size of 0.05K.

3.1.2.3 Speed of response

Sensors need to respond sufficiently fast to changes in themeasured variable so that stable and accurate control canbe maintained. The speed of response is characterised bythe time constant τ, which is the time taken for the signaloutput to change by 63% of the final change. The timeconstant of a sensor in practice includes the effects of itshousing, the manner of mounting and the nature of themedium being measured. There may be additional delaysintroduced by the measurement system; the scan rate ofthe controller limits the speed of response of the system to

2 Building control systems

Table 3.1 Standard signals for transmission of sensor readings

Signal Application

0–10 V DC Standard for HVAC applications

4–20 mA Common in process control

Voltage-free contact For status indication

Pulse Energy and flow measurement

Table 3.2 Sensor requirements

Sensor requirement Checklist

Type Status, analogue, intelligent

Sensed medium Air, water, gas, oil

Sensed quantity Temperature, pressure, velocity, humidity

Location Space, duct, pipe

Housing Accessibility, effect on accuracy and speed

Accuracy Accuracy, resolution, hysteresis, repeatability

Operating range The range over which the sensor performsaccurately

Overload range The range to which the sensor may be subjectedwithout damage

Response time Affected by sensor, housing and medium

Protection Is protection required from a damagingenvironment?

Maintenance Calibration requirements, ease of servicing andreplacement

Interchangeability Can sensor be replaced by another from the sameor different manufacturer?

Cost Initial cost and total ownership cost over lifecycle

Page 32: Building control system, aplication guide   cibse guide

a change in the measured variable. Increasing the relativespeed of the fluid flowing past the sensor reduces the timeconstant, up to a speed of about 0.3 m/s for water and 2 m/sfor air. Above these speeds there is little reduction in timeconstant. For accurate and rapid measurement it ispossible to measure air temperature with an aspiratedthermometer, where air is drawn past the sensing elementby a small fan.

The time constant of the sensor should be considered inrelation to the rest of the controlled system. Too low a timeconstant may give problems if short term fluctuations in themeasured variable give rise to unwanted control action.This may be dealt with in the controller software, typicallyby incorporating an averaging function to extend the timeconstant. Too high a time constant may mean that thecontrol system will respond too slowly to changes in thecontrolled variable; this cannot satisfactorily becompensated by the control software. The time constant ofthe sensor is only one part of the time lags involved in aheating and control system; the general problem will bediscussed below.

3.1.3 Types of sensor

The following deals with the selection of sensors which areused in control systems. It does not cover more specialisedsensors which are used in safety systems, such as gas orrefrigerant leak detection. Nor does it include safety sensorswhich are normally included in plant, such as the fusiblelinks used to detect over-temperature above boilers. Energymetering is covered in 7.1.3.1 and the use of occupancydetectors in lighting control systems is dealt with in5.15.1.3.

3.1.3.1 Temperature sensors

Temperature is the most widely measured variable in HVACapplications and several types of sensor are available.Mechanical devices are in general cheap and reliable. Theoutput is a physical displacement which is used to directlyoperate a switch; the most common example is the domestic

room thermostat. The set point may be varied by physicaladjustment. They are not used in automatic controlsystems, except for limit switches. The most widely usedsensing elements are listed in Table 3.3; elements usedprimarily for specialist or technical purposes have not beenincluded.

The specification of a temperature sensor reflects itsapplication. An accuracy of 0.6 K achieved over a 15 to 25°Crange is suitable for zone air temperature measurement,while an accuracy of 0.25 K is needed for control of chilledwater temperature. There is little point in specifyinggreater accuracy than is realistically required; reliability isoften more important in practice.

3.1.3.2 Humidity sensors

The measurement of humidity is important in airconditioning control, but presents practical problems ofdrift and contamination. Simple mechanical sensors areavailable based on the expansion of hair or a nylon film withincreasing atmospheric relative humidity. These elementscan be incorporated in humidistats, comparable in operationand application to mechanical thermostats. They aregenerally reliable and resistant to contamination, but havelow accuracy, which worsens outside the range of 20 to 80%RH. While many types of humidity sensor exist, two typeshave come to dominate in HVAC applications (Table 3.4); thetraditional wet and dry bulb psychrometer is not included asit is no longer used in automatic control applications. Thecapacitative polymer film sensor provides a direct measure ofrelative humidity and is in widespread use. The sensingelement is normally protected by a membrane or nettingfilter; a sintered metal filter permits the use of an RH probe inair speeds of up to 40 m/s. Where an accurate measurement ofdewpoint is required, particularly at low humidities or lowtemperature, the chilled mirror dewpoint sensor providesthe most accurate measurement(1,2). This detects theformation of condensation droplets on a small mirror surfacewhich is cooled by the Peltier effect; the temperature atwhich condensation is detected provides a direct measure ofdewpoint. A recent development detects the onset ofcondensation using electromagnetic means.

Components and devices 3-3

Table 3.3 Temperature sensors

Sensor Element Description Types Advantages Disadvantages Applications

Platinum resistance Thin metal film Electrical resistance Pt100 and Pt1000, Industry standard. Cost. Lead wire Widespreadthermometer (PRT) on substrate increases as a available as Interchangeable resistance and

linear function passive sensors elements, high self-heating canof temperature. or with inbuilt accuracy, reliable, introduce errorsThree- or four-wire transmitter stableconnection required

Thermistor Semiconducting Electrical resistance Various standards Cheap, high Accuracy and Widespread.metallic oxides changes with exist; some are sensitivity, small drift. Short life Differentialin bead, rod or temperature; supplier specific. size, wide unless protected temperaturedisc format highly non-linear Usually negative range available against moisture.

temperature Signal conditioningcoefficient (NTC) required; may not

be interchangeable

Nickel resistance Wound coil of Near linear change Standards exist for Moderate to good May need signal Widespreadthermometer nickel or nickel in resistance with Ni100 and Ni1000 accuracy. Field conditioning. May

alloy wire temperature. elements. Alloy wiring has little not beHigher coefficient elements may be effect on accuracy interchangeablethan platinum supplier specific.

Available in specialformats, e.g. ductaveraging

Page 33: Building control system, aplication guide   cibse guide

Where RH is measured and a measure of absolute humidityor enthalpy is required, it is necessary to take asimultaneous measurement of air temperature. The airtemperature sensor should experience the sameenvironment as the humidity sensor and ideally should beenclosed in the same housing. Sensors are available whichincorporate both temperature and RH measurement withinthe same head and may have enthalpy and dewpoint outputoptions, in addition to the direct measurement oftemperature and RH. Measurement of humidity is subject tomany uncertainties and it is unreasonable to expect anaccuracy in practice of better than 2.5%. Furtherinformation on a wide range of sensor types, their errorsand calibration methods are given in a guide published bythe Institute of Measurement and Control(3).

In some applications, such as the control of chilled ceilings,it is necessary to anticipate the formation of condensation ona chilled surface. Two major types of sensor are used. One isa dedicated form of humidity meter. The sensing element iscontained in a small metal housing which is held in goodthermal contact with the cold surface. The attached controlunit provides a digital signal output when the RH at thesensor reaches a preset level of 97% and so anticipates theformation of condensation. The other type detects the initialformation of condensation by monitoring the electrical

resistance across an array of conducting tracks on a substrateheld in good thermal contact with the cold surface.

3.1.3.3 Pressure sensors

Pressure is the most commonly measured quantity aftertemperature. Most pressure sensors consist of a diaphragmor bellows, which moves under the influence of the pressureapplied across it. The movement is a function of the appliedpressure and the measurement problem is fundamentally ameasure of displacement.

Pressure may measured relative to atmospheric pressure,when it is termed gauge pressure, or else as a differentialpressure across two points in a system. Building staticpressure may vary appreciably over a building and thereference atmospheric pressure against which gaugepressure is measured must be carefully considered. Pressurewithin a building is affected by mechanical ventilation,door and window opening and the stack effect. An outsidestatic pressure sensor should be mounted in free air at least2 m above a surface and fitted with a wind shield. Thebellows or diaphragm construction depends more on theworking pressure than on the medium and most pressuresensors may be used with air, water or other media. Thetypes of pressure sensor listed in Table 3-5 are classified by

3-4 Building control systems

Table 3.4 Humidity sensors

Type Element Description Types Advantages Disadvantages Applications

Capacitive sensor Thin polymer film Film expands with Supplier specific, Accurate, reliable High cost. Drift, Widespreadacts as dielectric increasing RH, range of and stable particularly if

changing mountings exposed to highcapacitance of available RH. Annualsensor. Dedicated recalibration advisedsignal conditioninggives linear outputwith RH

Dewpoint Chilled mirror Detects dew Supplier specific Direct measurement Size, expense. High accuracyformation on of dewpoint, Maintenance controlmirror chilled by high accuracy requirementsPeltier effect.Measurement headincorporates lightsource, detector andchilled mirror.Sophisticated controlgear required

Table 3.5 Pressure sensors, classified by transducer

Sensor Element Description Advantages Disadvantages Applications

Capacitive Diaphragm or bellows Movement of Low cost Low output, Low pressure air.with capacitive bellows alters signal conditioning Duct static ortransducer capacity required filter differential

pressure

Inductive Diaphragm or bellows Movement of bellows Rugged construction Expensive; temperature As for capacitativewith inductive operates a linear compensation maytransducer variable differential be difficult

transformer

Strain gauge Diaphragm or bellows Strain gauge bonded Rugged, linear output Low output signal High pressure,with strain gauge to pressure sensing chilled water,transducer element steam

Potentiometer Diaphragm or bellows Movement of Inexpensive, Low accuracy,connected directly pressure sensing high output large size, wearto variable resistor element operates may shorten life

a variable resistor

Page 34: Building control system, aplication guide   cibse guide

transducer, rather than the pressure sensing element.Where fluctuating pressures or vibration are to bemeasured, use may be made of piezoelectric transducers,which can respond to sonic frequencies. A wide range ofmechanical pressure switches is also available, whichoperate as status sensors and are used where safetyinterlocks are required, e.g. to detect fan operation.

3.1.3.4 Velocity and flow

Strictly, velocity implies both speed and direction. Inpractice, the direction of flow is determined by the duct orpipe and a speed measurement is all that is required. Theflow in a duct may be measured directly or derived from avelocity measurement and knowledge of the cross-sectionalarea of the duct; corrections for temperature and pressuremay be required. For well-developed flow in a straight pipe,it is possible to assume the velocity distribution over thecross-section of the duct. This requirement is generallysatisfied by positioning the sensor so that there is a distancebetween the sensor and any disturbance of 10 pipediameters before the sensor and five after. If this is notpossible, multiple measurements will be required toprovide some form of averaging. Several methods ofvelocity and flow measurement are available (Table 3.6).For control purposes it may be possible to monitor

differential pressure across a fixed restriction, such as aheating coil or louvre; devices which have a variableresistance, such as filters or cooling coils, must not be usedfor this purpose.

3.1.3.5 Air quality

The use of demand-controlled ventilation (DCV) requires ameasure of the condition of the indoor air. Carbon dioxideconcentration is becoming the most generally acceptedmeasure (Table 3.7). While it does not give a completeindication of the various contaminants, it gives an overallmeasure of the relation between occupancy and ventilation.Multi-gas sensors, based on a tin oxide layer, respond to anumber of possible contaminants, but the integratedresponse does not necessarily reflect the air quality asperceived by occupants. They are therefore not generallyrecommended for DCV.(4,5). Multi-gas sensors haveapplications in areas where there is a low concentration ofpeople, but smells are a potential problem, for examplerestaurants and bars. Sensors sensitive to particular gasesare required for specialised ventilation control applications,such as car parks. Indirect methods, such as counting thetotal building occupancy or predicting it from a workschedule, may be used instead of air quality measurementfor ventilation control.

Components and devices 3-5

Table 3.6 Velocity and flow sensors

Sensor Element Description Types Advantages Disadvantages Applications

Pitot tube Tube with opening The stagnation Can be obtained Inexpensive, but Requires Air speed whenat upstream end pressure of the in the form of duct averaging unidirectional direction is

air brought to arrays which sensor may be air flow above determined. Airrest in the tube is perform an expensive 3 m/s. Can become flow rate forproportional to averaging function blocked with dirt VAV unitsthe square of the over the areaair speed. The of the duct, e.g.difference between Wilson gridstagnation andstatic pressures ismeasured by asuitable pressure gauge

Hot wire Heated fine wire The sensor element Available as grid Measures mass Fragile, expensive Air flow.anemometer or thermistor bead is heated by an for measuring flow, resistant to Available in

electric current to flow rate in duct contamination, arrays. Usea constant short time thermistor typetemperature. The constant. Can for non-directionalcurrent is a function measure low flowof the fluid speed flow rates

Orifice plate A plate with a The pressure drop Calibrated plates Robust, no Erosion of orifice Can be used forprecisely defined across the plate is with integral moving parts will affect accuracy. air, water or steamhole is inserted proportional to pressure tapping Has to be fittedinto the duct the square of the are available. in straight section.

velocity. Venturi devices Not suitable forTransducer may operate on a low flows. Highsense mass or similar principle; pressure lossvolume flow rate they have a

lower pressure lossbut are bulkier

Turbine flow Bladed turbine The speed of May be full bore, Moderate cost. Susceptible to Metering of watermeter immersed in the rotation is mounted between Good accuracy. damage when and natural gas.

fluid proportional to flanges, or a small Wide range of used with water Heat meteringflow. A magnetic insertion device velocities and lowdetector produces mounted in the pressure lossa pulse train with centre of the pipefrequencyproportional to rotor speed

Page 35: Building control system, aplication guide   cibse guide

3.1.4 Sensor mounting

A sensor can only measure the state of its own sensingelement. Care must be taken to ensure that this isrepresentative of the physical quantity being measured.The following general guidelines should be borne inmind:

— Ensure that the sensor is in a positionrepresentative of the variable to be measured.

— Take care that temperature and humidity sensorsare screened from direct radiation, particularlysunlight.

— Take account of the active and inactive sections ofthe sensor probe.

— Ensure adequate immersion of the sensor in themedium. Heat conduction along a sheath can affectreadings.

— Provide a tight sealing hole adjacent to every ductmounted sensor for the insertion of a test sensor.

— For pipe sensors use a separable pocket. Ensure thatthe sensor is a close fit in the pocket and use athermal conductive paste.

— Use flexible cable. A rigid cable could disturb theposition of the sensor.

— Sensor cables should be provided with a ‘drip loop’to prevent water running into the sensor housing.

— Allow sufficient spare cable to allow for removal.

— Record the location of all concealed sensors.

— Fix a labelling plate next to every sensor, not on thedevice itself.

— Allow for stratification and use more than onesensor or an averaging sensor if necessary.

— Position duct temperature sensors downstream ofsupply fans.

A booklet on control sensor installation published by theBuildings Controls Group(6) gives excellent practical adviceon the choice and installation of sensors.

3.1.5 Calibration

Sensors should be routinely checked and recalibrated. Thefrequency of checking depends on the nature of the sensor;it will be greatest for sensors in challenging environmentsand those subject to drift. Exposure to extreme conditionsmay affect calibration; this is a problem with RH sensorsexposed to high humidities.

Sensor calibration may be performed by using the sensor tomeasure a standard condition, or to compare the sensorreading with that of a standard instrument. The former ismore common in the laboratory that in the field. Standardrelative humidities may be produced using saturatedsolutions of salts and it is possible to obtain a set ofcalibration vessels into which humidity probes can beinserted for checking. It is more common to check sensorsby comparison against a reference standard. This should bea good quality instrument reserved for this purpose whichhas itself a certificate to prove that its calibration istraceable to a national standard(7). The accreditation ofcalibration and testing laboratories in the UK is carried outby the United Kingdom Accreditation Service, whichincorporates NAMAS (National Accreditation of Measure-ment and Sampling). Care must be taken to ensure that thesensor under test and the reference standard are in factexperiencing the same environment. Provision of testmounting points adjacent to pipe- and duct-mountedsensors is good practice and enables a rapid check to becarried out.

3-6 Building control systems

Table 3.7 Gas sensors

Sensor Element Description Types Advantages Disadvantages Applications

CO2 sensor NDIR optical cell Measures the Wall-mounted Small size, Cost Demand-(non-dispersive absorption of housing with insensitive to controlledinfra-red) infra-red radiation CO2-permeable humidity or ventilation for

by CO2 in air membrane for other vapours occupied spacesDCV applications

Multi-gas sensor Tin oxide film Detects oxidation Various wall and Sensitive to wide Relative rather Multi-contaminanton a heated tin duct housings range of than absolute situations. Carbondioxide surface. available contaminants measure of dioxide controlSensitive to contamination preferred forheavy odours, occupied spacessmoke andsolvent gases

Specified pollutant Non-dispersive Uses IR absorption Available for High accuracy High cost Car parkinfra-red Sensor is specific several gases and stability ventilation control

to pollutant (carbonmonoxide andnitrogen dioxide);swimming pools(chlorine); airpollutionmonitoring(sulphur dioxide)

Obscuration Optical cell Detects absorption High accuracy High cost Roadway andof light beam by and stability tunnel ventilationsuspended particles control

Page 36: Building control system, aplication guide   cibse guide

3.2 ActuatorsAn actuator responds to the output signal from a controllerand provides the mechanical action to operate the finalcontrol device, which is typically a valve or damper. A widerange of actuators is available and the chosen actuatormust:

— match the mechanical requirements of thecontrolled device

— match the characteristics of the control system,especially the output signal of the controller

— be suitable for its operating environment.

The major mechanical division is between linear and rotaryactuators. Linear actuators are required for use with lift andlay valves. Rotary actuators tend to be used on shoe valvesand butterfly valves. Actuator and valve are selected to bedimensionally compatible, so that the actuator spindleconnects directly to the valve stem; many manufacturersprovide matched combinations. Linear actuators may beused to operate dampers using a linkage to provide therequired rotary movement. Movement is provided by anelectric motor operating through a reduction gear train,producing relatively high torque at low speed. Wherespecified, a spring return mechanism is incorporated,which is wound as the motor operates. In the event of powerfailure, the actuator is returned to the specified position. Itis now possible to obtain microprocessor-controlled devicesfor particular applications, e.g. a unit which combinesdifferential pressure sensor, controller and damper actuatorfor the control of VAV boxes.

The actuator must be suitable for its operatingenvironment. The manufacturer’s data gives safe operatingranges of temperature and humidity and often the IPprotection number (see Table 3.13). Where the operatingenvironment is likely to be corrosive, as in a swimmingpool or industrial setting, advice should be obtained fromthe manufacturer.

A range of modulating magnetic valves is obtainable, wherea movable magnetic core moves in a solenoid and transfersthe linear stroke directly to the integral valve. The valvesare reliable and fast, capable of precise regulation, resultingin a high rangeability, coupled with a fast response time ofonly 1 s. The solenoid itself is operated by a 0–20 V phasecut signal, but in-built electronics allow operation from astandard 0–10 V DC signal input. The high rangeability andprecise control makes these valves suitable for demandingsituations and installations where the valve may berequired to operate at low authority, requiring stablecontrol at low valve openings.

Thermic actuators contain a solid expansion mediumwhich is heated by an electrical resistance heater. Whenpower is applied to the actuator, the heating effect causesthe medium to expand, producing a linear motion of thespindle. On cooling, the spindle retracts by pressure of abuilt-in spring. Thermic actuators are robust and silent.Full stroke is about 3 mm and stroke time is a few minutes.Modulating control can be achieved with pulse widthmodulation; some models use a standard 0–10 V signal.Models are available designed to operate radiator valves.

Some gas valve applications use electro-hydraulic actuators,where a motor pumps hydraulic oil against a rolling

diaphragm and piston. The piston then drives open thevalve against the force of a spring. Once the valve is fullyopen, an internal relief valve is closed, the pump is switchedoff and the valve remains open without further applicationof power. To close the valve, the relief valve is opened andthe spring forces the oil back into the reservoir.

3.2.1 Mechanical characteristics

A linear actuator requires the following quantities to bespecified:

— Thrust. The thrust is measured in newtons and mustbe sufficient to close the valve against thedifferential pressure acting across the valve plug. Insome hydraulic systems employing two-port valves,closing forces may be considerable, up to the fullpump head. Manufacturers supply tables ofmaximum differential pressures for valve/actuatorcombinations.

— Stroke. The stroke of the actuator spindle must besufficient to provide full operation of the valve. Thestroke is normally adjustable to suit the valve; inmany actuators this is self-set automatically.

— Running time or stroke time. This is the time taken forthe actuator to travel over the full operating range.The low gearing of the electric motor used to drivethe actuator spindle produces low operating speedsand the actuator operates at several seconds per mmtravel, giving a stroke time of the order of minutes.This speed of movement may be an integral part ofthe control loop and is required to be input to thecontroller during configuration. Depending on thetype of actuator motor and its control, the runningtime may be invariant or else dependent on theload.

Rotary actuators are used to operate dampers and butterflyor ball valves. The actuator produces a rotary movementwhich is coupled directly to the control element. Theactuator has the following specification:

— Torque. The operating force is given as the torque inN m. Damper manufacturers supply tables of therequired torque for their dampers as a function ofdamper area and air velocity in the duct.

— Angle of rotation. Rotary actuators typically have amaximum angle of rotation of just over a rightangle. This angle may be adjusted to suit therequired rotation of the valve or damper.

— Running time. As for linear actuators.

3.2.2 Electrical connections

An actuator requires some or all of the following connections:

— Power to power the drive. May be 230 or 240 V AC, 24V AC, 24 V DC; 230 V is becoming an EU standard.

— Control signal from the controller. 0–10 V and 2–10 VDC are the most common. 4–20 mA is used inprocess control applications. 0–20 V phase cut maybe used for magnetic actuators. A 24 V AC pulsed isalso found.

— 135 Ω potentiometer. Used by the Honeywell 90 seriesfor both control input and positional feedback.

Components and devices 3-7

Page 37: Building control system, aplication guide   cibse guide

— Position indication. A 2–10 V DC signal to providepositional feedback or indication. Positionfeedback may also be provided by a potentiometer.End switches are used to provide positiveopen/close position indication.

The actuator may be fully modulating, where the positionof the actuator is proportional to the control signal, ortristate, used for floating control, where the motor may bedriven in either direction or stopped. Many actuatorsexhibit some degree of hysteresis and the relation betweencontrol signal and actuator position depends on thedirection of travel. Most actuators have the facility toprovide a positional feedback signal, indicating the actualposition of the actuator. This may be used to drive a remoteposition indicator, or be incorporated in a control loop toprovide positive positioning of the actuator; this overcomesany problems caused by hysteresis. In some cases wherepositive positioning is required, the position indicator maybe mounted on the controlled device itself, e.g. damper.End switches may also be used in simple sequencingapplications to divert a signal to another device when thefirst device is fully closed. The actuator may be configuredso that either end of the travel is corresponds to a zerocontrol signal. The spring return which operates on powerfailure may return the actuator to either the spindleextended or spindle retracted position. All actuators arefitted with a manual override, to allow for manualpositioning of the actuator and control device duringcommissioning or maintenance.

3.2.3 Pneumatic actuators

Pneumatic actuators comprise a piston or diaphragm towhich air pressure is applied to provide a lineardisplacement. A mechanical linkage is required where it isdesired to produce a rotary movement, e.g. for dampercontrol. The construction of the actuator and its method ofconnection to the valve or damper determines the directionof operation, i.e. whether increasing control air pressureresults in opening or closing of the valve or damper. Mostpneumatic actuators are of the single-action type where theforce on the diaphragm is opposed by a spring and the netforce applied to the valve or damper is the differencebetween them. When the air pressure is removed the springwill return the valve to the selected extreme position andthis may be used for fail-safe requirements.

When a straightforward pneumatic actuator operatesagainst large or variable forces the position of the actuatorspindle may not be proportional to the signal pressure fromthe controller. To overcome this a pneumatic relay, knownas a positioner, is fitted to the actuator; this uses main airline pressure to power the actuator and provide theoperating force, but incorporates an all-pneumatic controlto ensure that the actuator is correctly positioned for agiven signal pressure. To do this a positive feedback ofactuator position is used.

Pneumatic controllers provide reliable and fast operationand are still used extensively in the HVAC industry. For newinstallations they have been largely supplanted by DDC andpneumatic systems are now installed only in specialsituations. The necessity to provide a clean dry air supplycan lead to maintenance problems. Where an existingpneumatic control system is being upgraded to electronicDDC control, it is possible to retain pneumatic operation of

the actuators by using hybrid electro-pneumatictransducers which use pneumatic power to provide theoperating force, but whose position is controlled by astandard electronic signal.

3.3 Valves

3.3.1 Hydraulic flow

Fluid temperatures used in commercial buildings areclassified into five broad ranges (Table 3.8).

In SI units, pressure is measured in pascals. The bar iscommonly used, where

1 bar = 100 kPa

It is sometimes helpful to visualise pressure in terms ofhead of water:

1 bar = 10.5 m head of water

Flow is properly measured in m3/s in SI units. This resultsin small values which are awkward to handle and it iscommon to quote flow rates in litres per second (l/s) orm3/h, where

1 l/s = 3.6 m3/h

A control valve is subject to three types of pressure:

— Static pressure. This is the maximum internalpressure of the hydraulic system and for opensystems will usually be governed by the height ofthe cold water tank in the roof above the lowestpoint of the system. The body of the valve and thegland through which the spindle moves must beable to withstand the maximum pressure of thesystem, which is equal to the static head of thesystem plus the pump pressure.

— Differential pressure. Valves should always beinstalled so that the plug closes against the flow;installation in the wrong direction could result inunstable operation with a danger of the valvesnapping shut. The pressure produced by the pumpin a circuit has to be capable of meeting the pressuredrops at design flow rate produced by the resistanceof all fittings, pipes, boilers valves etc. However, insome circuits using two-port valves, it is possiblefor a large differential pressure to be developedacross a single valve under part load conditions;three-port valves nominally have the same pressuredrop for all positions of the valve. The actuatormust therefore be capable of driving the valve

3-8 Building control systems

Table 3.8 Working fluid temperature ranges

Classification Temperature range (ºC)

Chilled water (CW) 5–10

Low temperature hot water (LTHW) 20–90

Medium temperature hot water (MTHW) 95–120

High temperature hot water (HTHW) 120–200

Steam < 16 bar

Page 38: Building control system, aplication guide   cibse guide

against a differential pressure equal to themaximum pump head. By the same token, themaximum differential pressure rating (MDP) of thevalve must be greater than the maximum pumphead.

— Pressure drop. There is a pressure drop across valvein normal operation. This is an important part ofvalve selection and is discussed below under valveauthority.

3.3.2 Types of valve

Valves may be classified by their function into:

— Regulating: a valve which is adjusted duringcommissioning to provide a fixed resistance in afluid circuit to give the design flow rate and ensurea correct balance. The adjustment is normallymanual. A double regulating valve is provided withindicated positions of the valve opening and has anadjustable stop, so that the valve can be closed toisolate a circuit and reopened to the previously setposition.

— Commissioning: a regulating valve which incorporatesa calibrated orifice and pressure tappings for flowmeasurement during commissioning.

— Flow limiting (also known as automatic or dynamicbalancing valves): valves which maintain a constantflow independently of the differential pressure acrossthem. This constant flow is maintained over theregulation range of differential pressure, which istypically 10:1 or more. Valves are available with presetcontrol cartridges for a predetermined flow rate, orcan be externally adjustable for commissioning.

— Differential pressure control: a valve whichautomatically adjusts to maintain a constantdifferential pressure across part of a circuit.

— Modulating: a valve which is adjusted by the controlsystem via an actuator to regulate hydraulic flow.

— Safety shut-off: a valve that is designed to close underspring pressure on power failure, critical condition(e.g. fire) or out-of-range process variable.

Modulating valves form the main subject of interest in thisGuide. The complete valve assembly consists of:

— actuator, which converts the output signal from thecontroller into mechanical movement

— spindle, which transmits the actuator movement tothe moving part of the valve

— valve body, containing the flow control device.

Components and devices 3-9

Figure 3.1 Common valve types: (a) plug and seatvalve: three-port mixing valve, single seat; (b) plugand seat valve, three-port mixing valve, double seat;(c) two-part plug and seat valve; (d) rotary shoe valve;(e) butterfly valve

Page 39: Building control system, aplication guide   cibse guide

Several types of valve body are used and are illustrated inFigure 3.1:

— The butterfly valve is the simplest form of valve.The internal disc is aligned either in line or acrossthe flow and is used for on/off control.

— Rotary shoe valves are used commonly on chilledand LPHW systems because of their compact size. Inaction, a rotating shoe is moved over the ports by arotary actuator and provides modulatingregulation, which may be characterised.

— Plug and seat valves are the most common and areavailable in a wide range of sizes and can be used forall heat transfer media. The valve plug is moved onand off the valve seat by linear movement of thespindle. The spindle moves through a gland, whichmust allow free movement and yet not leak underthe static pressure of the system. The shape of thevalve and seat determine the characteristic of thevalve. They are also known as lift and lay or globevalves.

Valves are available in two-, three- or four-portconfigurations. Three-port valves have found widespread

application in HVAC systems. Used with constant-speedcirculation pumps they offer a range of well-established andtrouble-free control solutions. A four-port valve performsthe control function of a three-port valve but includes aninternal bypass to produce compact connections; see Figure3.2.

A three-port valve is provided with two inlet ports and oneoutlet port, when it is described as a mixing valve, or, lesscommonly, with one inlet and two outlet ports, when it isdescribed as a diverting valve. Both mixing and divertingvalves may be incorporated in a circuit for either mixingor diverting application. These terms may cause confusionand Figure 3.3 illustrates the meaning of the terms. Ingeneral, three-port valves available in the building servicesindustry are designed to be used as mixing valves and arenot suitable for use as diverting valves. Where a divertingvalve is required, i.e. one inlet and two outlets, a double-seated or shoe type valve should be used to avoid the out-of-balance forces which would occur with a single-seatedglobe valve. Connecting a mixing valve as a divertingvalve is likely to lead to unstable operation, since waterpressure acts to slam the plug against the valve seat.Mixing applications are typically constant-flow, variable-temperature loads, such as a compensated heating circuit;diverting applications are typically variable-flow,constant-temperature circuits, such as heater batteries.Correct connection of a valve is important and may becrucial. There is not a consistent terminology foridentifying valve ports. Figure 3.4 illustrates the morecommon conventions. This Guide refers to the ports ascontrol, bypass and common and describes a three-wayvalve as open when the flow is between control andcommon ports, with the bypass shut. This applies to bothmixing and diverting valves.

Two-port valves are used to throttle flow in a circuit. In acomplex circuit the independent modulation of two-portvalves can produce balancing problems and pressurevariations throughout the system. However, when usedwith a variable-speed pump and with proper attention tosystem design, two-port valves offer reductions in both firstcost and the cost of pumping. Suitable hydraulic controlcircuits are given in section 5.

3-10 Building control systems

32

41

+Figure 3.2 Four-port valve. Afour-port valve incorporates thebypass and tee connections in thevalve body giving compactinstallation

Figure 3.3 Three-port valves inmixing and diverting applications

Page 40: Building control system, aplication guide   cibse guide

3.3.3 Valve design

3.3.3.1 Characteristic

A control valve is one link in a chain of control, runningfrom the error signal which is input to the controller to thechange in output of the emitter; an example is shown inFigure 2.1. While not essential, a linear relation betweenthe change in output from the controller and change in heatoutput from the emitter makes for a well-behaved andstable system. For most heat emitters, there is a stronglynon-linear relation between the flow rate of the heattransfer fluid and heat output from the emitter, with outputrising rapidly as the flow increases from zero, thenflattening out at higher flow rates. For example, heat outputfrom a radiator rises rapidly as hot water is admitted at lowflow rates, but once the body of the radiator is hot,increasing the water flow rate will produce little increase inheat output. This is illustrated in Figure 3.5; the curves fora heating or cooling coil are similar. A valve which

produced a flow rate proportional to spindle lift wouldtherefore result in a non-linear system, operating over anarrow range of spindle movement and possibly resultingin unstable operation.

Valves are therefore often designed so that the resultantheat output from the emitter is approximately proportionalto the spindle movement. This is done by shaping the plugso that the free area, and hence flow rate, is a definedfunction of spindle lift. This relationship is termed thevalve characteristic. The most commonly encounteredcharacteristics are:

— linear, where the orifice area is directlyproportional to the valve spindle movement andthe flow varies linearly with spindle lift

— characterised V-port, with a characteristic fallingbetween linear and equal percentage

— equal percentage, or similar modified parabolic,where equal increments of valve spindle lift providean equal percentage change of the area

— quick opening, where the flow increases veryrapidly from zero for a small spindle movement,with a fairly linear relationship between flow andspindle movement. Such valves are used primarilyfor on/off service.

Figure 3.6 shows in stylised form the basic characteristiccurves for the four types described above. The staticcharacteristics are measured by measuring the flow as afunction of valve position for a constant pressure dropacross the valve. In a real circuit, the characteristic ismodified by the authority of the valve; this is discussedfurther below.

Equal percentage valves have a theoretical characteristicwhich may be expressed as an equation relating flowthrough the valve to the degree of opening, measured atconstant pressure drop. The degree of opening of a valve isvariously referred to as the spindle lift, stem position, orpercentage of full stroke:

Q = Q0 exp (Sn)

Components and devices 3-11

Figure 3.4 Three-port valve terminology, showing designation of ports

Flow rate (%)

Figure 3.5 Radiator heat output as a function of flow rate, withtemperature drop as parameter. Heating and cooling coils show a similarrelationship Figure 3.6 Stylised static valve characteristics

Page 41: Building control system, aplication guide   cibse guide

where

Q flow through valve (nominal units)

Q0 theoretical flow though valve at S = 0

n valve sensitivity

S spindle lift (1 = fully open).

The sensitivity n is the percentage change in flow throughthe valve produced by a 1% change in stem position. Atypical value is about 4. The theoretical flow Q0 though thevalve at zero opening is a mathematical convenience anddoes not represent the actual flow when the valve is closed.Real equal percentage valves can be made to follow thetheoretical characteristic reasonably well, but depart fromit at low openings. A practical equal percentage valve has acharacteristic of the form shown in Figure 3.7. Qminrepresents the minimum flow at which the valve stillprovides reasonable control. Below this flow, the flow fallsoff rapidly and cannot be controlled reliably. Valves arenormally designed to shut down rapidly below theminimum controllable flow. If the valve does not provide atight shutoff, the residual flow is termed let-by. The ratio ofthe maximum controllable flow to the maximum flow isknown as the rangeability R, sometimes referred to as thepractical rangeability to distinguish it from the theoreticalrangeability. A rangeability of 25 indicates a valve whichwill control according to its defined characteristic down to4% of its maximum flow. The practical rangeabilitydefinition holds for all types of valve. For equal percentagevalves it is possible to define an ideal rangeability

Rideal = Qmax/Q0 = exp(n)

The ideal rangeability is directly related to the sensitivity.

Good rangeability is required when valves are required tocontrol at low flow rates. This occurs in some circuits usingtwo-port valves. Situations where valve authority is low willrequire operation at low spindle lifts. It is conventional toregard valves as having ‘good’ rangeability as follows:

— terminal unit valves: rangeability of 25:1

— screwed plant valves: rangeability of 50:1

— flanged plant valves: rangeability of 50:1

— magnetic solenoid valves: rangeability of 500:1.

Good control at low strokes requires an actuator that canposition the valve accurately.

3.3.3.2 Flow coefficient

The size of a valve is described by the flow coefficient,which determines the rate of flow of fluid through the valveas a function of the pressure drop across it. The flow of fluidthrough a constriction is proportional to the square root ofthe pressure drop across the constriction. The flowcoefficient of a valve is defined in SI units by the equation:

Vm = Av

0.5

where:

Vm volume flow rate (m3/s)

Pm pressure drop across valve (Pa)

�fm fluid density (kg/m3)

Av flow coefficient of valve (m2).

Manufacturers often quote the capacity of a valve as thecapacity index Kv. This is equivalent to the flow coefficient,but applied to water flow, with the flow rate measured in theso-called continental units of m3/h and pressure drop inbars. The flow equation becomes

Vm = KvPm0.5

where:

Vm volume flow rate of water (m3/h)

Pm pressure drop across valve (bar)

Kv flow coefficient of valve.

The older imperial unit Cv (equivalent to Av ) may also bemet. The conversion factors and units are summarised inTable 3.9. It may be noted that 1 bar ≅ 1 kgf/cm2.Manufacturers usually produce a range of valves with Kvvalues rising in geometrical progression, with each value ofKv 60% greater than the preceding one in the series.

3.3.3.3 Steam valves

Valves used for steam are a specialist application of two-port valves for compressible fluid flow. If a smallconstriction is introduced into a pipe-carrying steam, it hasthe effect of increasing the velocity of the steam passingthrough the constriction and reducing the steam pressuredownstream of the constriction. The net result is that thereis little effect on the overall flow of steam in the pipe. As thesize of the opening is decreased, this effect is maintaineduntil a maximum critical steam velocity is reached, when,for dry steam, the downstream absolute pressure is 58% ofthe inlet pressure. Further reduction of the area of theconstriction results in reduced flow of steam. Thus, insizing steam valves, the valve pressure drop may beassumed to be 40% of the absolute pressure at full load,

Pm��fm�

3-12 Building control systems

Figure 3.7 Valve rangeability. The dotted line shows a theoretical equalpercentage valve characteristic. The solid line shows a practical valve,controlling over the range Qmin to Qmax. The practical rangeability R =Qmin/Qmax. The theoretical rangeability Rideal = Q0/Qmax. The residual flowQlet is termed the let-by

Page 42: Building control system, aplication guide   cibse guide

immediately upstream of the valve. Using this figure andthe given duty, the valve may be sized from manufacturers’tables. If the inlet pressure is below 100 kPa, applying the40% rule gives unsatisfactory conditions downstream and,in such cases only, it is necessary to assume a smallerpressure drop, ignoring any possible loss in degree ofcontrol. Guidance on these reduced pressure drops isnormally given in manufacturers’ literature. Additionalpressure drops due to pipe runs, isolating valves etc., meanthat control valves must be sized on their inlet pressure atfull load and not on the boiler pressure.

It is important to ensure that the heat exchange surfacewhich is supplied by the valve is adequate to handle the fulldesign load when the pressure at the inlet of the heatexchanger is 60% of the of the absolute pressure at the inletof the control valve; any other pressure losses in pipeworkand fittings need to be taken into account. Care must betaken to ensure that suitable stream traps are incorporated.Failure to do so will result in unacceptably poor controlunder light conditions.

3.3.4 Valve selection

3.3.4.1 Authority

To provide good control, a control valve must be sized inrelation to the circuit it controls so that the pressure dropacross the valve is of the same order as that round the rest ofthe circuit. If the valve is too large when open, theresistance to flow in the circuit is dominated by theresistance of the rest of the circuit. Throttling the valvewould initially have little effect on flow; control would thenonly be obtained over a small range of spindle lift when thevalve is nearly closed. The control system is then operatingunder high gain conditions and instability may result.Conversely, too small a valve may have an unnecessarilyhigh resistance and additional pump head would berequired to maintain flow.

The relation of the valve size to the circuit is expressedquantitatively in terms of the valve authority. The conceptof authority is first discussed with relation to two-portvalves. In the simple circuit of Figure 3.8, a constant-headpump circulates water though a load and the flow rate iscontrolled by a two-port valve. At design conditions, thevalve is fully open and the pump pressure is distributedbetween the differential pressure across the valve P1 and thepressure drop round the rest of the circuit. The relationbetween valve lift and flow in the circuit depends on theresistance of the valve in relation to that of the rest of thecircuit. This is expressed quantitatively by the authorityNdes. The subscript ‘des’ emphasises that the authority isdefined at design flow conditions; this is of significance inmore complex circuits.

Ndes = P1/Pclose

where:

P1 pressure drop across the valve in the fullyopen position at design flow

Pclose pressure drop across the valve in its fullyclosed position.

For the simple circuit shown, Pclose is the pump pressure.Figure 3.9 shows the relation between flow in the circuitand valve lift for both linear and equal percentage valves.Reducing the valve authority distorts the valvecharacteristic, making control more difficult at low flowrates. A minimum authority of 0.5 is acceptable. Below anauthority of 0.5 the characteristic is increasingly distortedaway from the required shape. In other words, at designconditions the pressure drop across the fully open controlvalve should be about half the total locally availabledifferential pressure.

Where the hydronic circuit has several branches, it isnecessary to take into account the influence of controlaction taking place in other branches. Figure 3.10 showsseveral branches controlled by two-port valves, arranged ina ladder circuit. The valve authority of a single branch iscalculated as described above, but with an extension to thedefinition of Pclose:

Pclose is the pressure drop across the valve in its fullyclosed position, with all other branches remainingat design settings.

However, when the circuit is actively controlling, the valvesin all branches act independently under the influence oftheir own control loops. In the worst case, all otherbranches may close down and the pressure across thebranch under consideration rises towards the full pumppressure. In practice the pump head is a function of flow

Components and devices 3-13

Table 3.9 Valve flow coefficients

Notation Flow Pressure Fluid Avdensity

SI (BS 4740) Av m3/s Pa kg/m3

Continental Kv m3/h bar Water 28.0 × 10–6Kv

Imperial Cv gal/min psi Specific 28.8 × 10–6Cvgravity

US Cv US gal/min psi Specific 24.0 × 10–6Cvgravity

Figure 3.8 Valve authority in simple throttling circuit. Diagram showspressure drop round a simple throttling circuit at design flow. The circuithas been drawn with a zero pressure drop in the return leg. The valveauthority Ndes = P1/Pclose

Page 43: Building control system, aplication guide   cibse guide

rate; the consequences of this for control are discussed insection 5. This increase in pressure at the branch has theeffect of reducing the valve authority. To reflect this, theminimum authority is defined as

Nmin = P1/Pmax

where:

P1 pressure drop across valve in the fully openposition at design flow

Pmax maximum pressure drop across the valve inits fully closed position, obtainable withany combination of valve positions in therest of the circuit.

In general with all other valves shut, flow through thesystem drops towards zero and the pressure across the

control valve under consideration rises towards the pumphead Ppump. If automatic valves are fitted, Pmax may be lessthan the pump head.

Valves should be selected so that

Ndes ≥ 0.5

Nmin ≥ 0.25

The treatment of three-port valves follows that of two-portvalves. Figure 3.11 shows a three-port mixing valve in acircuit which is balanced to provide a constant flow thoughthe heat exchanger as the valve modulates. The valve is saidto be open when the flow is across the top of the tee, whenthe pump delivers water directly from the heat source to the

3-14 Building control systems

N = 0

.1

N = 0

.1

Figure 3.9 Flow through a control valve as a function of spindle lift,showing the effect of valve authority

Figure 3.10 Authority in a multi-branch throttling circuit. Schematicthree-branch throttling circuit, showing authority of valve in branch 3,which has a design pressure drop of P1. Design authority Ndes = P1/Pclose,minimum authority Nmin = P1/Pmax

Figure 3.11 Authority of three-port valve in mixing circuit. N = P1/(P1 +P2) = P1/P3, where P3 is measured with the valve closed, i.e. in bypassposition

Page 44: Building control system, aplication guide   cibse guide

heat emitter without recirculation through the bypass leg.The pressure drop across the valve in the closed position(i.e. full bypass flow) is denoted by P3 and the authority isdefined in the same way as for the two-port valve.

Ndes = P1 / P3 = P1 / (P1 + P2)

P3 is constant because of the constant flow through the heatemitter. P2 is the pressure drop round the variable flow partof the circuit, including the heat generator and associatedpipework, but not the bypass or balancing valve.

The authority is equal to 0.5 if the pressure drop across thethree-way valve when fully open is equal to the pressuredrop in the variable flow part of the circuit, excluding thebypass.

The circuit of Figure 3.11 gives a variable flow through theheat generator which reduces to zero if there is no demandfrom the heat emitter. This has obvious practical problemswhich may be obviated by employing a separate pump inthe primary circuit as shown in Figure 3.12. The bypassforms a virtual heat generator with almost no pressure drop.The authority of the three-way valve is now

N = P1 /(P1 + P4)

where P4 is the pressure drop round the variable part of thecircuit, i.e. round the bypass pipework. P4 is therefore smalland the valve has an authority close to unity.

Where a three-port valve is used in a diverting application,as in Figure 3.13, the authority is defined in the same way.As before, it is the pressure drop round the controlled, i.e.variable-flow, section of the circuit that is used in thecalculation of authority.

The above definitions of authority and therecommendation that the designer should aim at a designauthority of 0.5 and a minimum authority of 0.25 will assistin the selection of an appropriately sized valve. It will notguarantee good control, especially where a number ofvariable flow branches interact. Where there is uncertaintya network analysis is recommended. Further details aregiven in the literature(8–10).

A three-port mixing valve is commonly used to provide aconstant flow through the load in a circuit such as the oneshown in Figure 3.11. The incorporation of a balancingvalve in the bypass leg allows the resistance of the bypass

leg to be set equal to the resistance of the heat generatorcircuit. In this way, the resistance seen by the pump is equalwhether the three-port valve is fully open or fully shut andthe flow is the same in both positions. However, to ensureconstant flow at all positions of the valve, a further designparameter associated with three-port valves must beconsidered, the symmetry of the internal ports. Sym-metrical design means that both control and bypass ports ina mixing valve have the same characteristic and the controland bypass connections may be reversed without affectingthe control behaviour of the valve. However, when the portsboth have an equal percentage characteristic, the totalvolume flow through the valve is not constant at all openingpositions. This is illustrated in Figure 3.14, where it is seenthat the common flow is reduced at intermediate openingpositions. This is unsatisfactory for some situations and thesolution is to use an asymmetrical valve to achieve constantflow. An asymmetrical valve has its internal ports designedso that the control port provides the desired operatingcharacteristic, while the port connected to the bypass isdesigned to compensate to maintain a constant total flowthrough the valve independent of valve opening; see Figure3.15. The ports of an asymmetrical valve are notinterchangeable.

3.3.4.2 Sizing

The relationship between valve position and heat outputmay be illustrated using the graphical construction shownin Figure 3.16. The upper right quadrant shows the relation

Components and devices 3-15

Figure 3.12 Mixing circuit with primary pump and bypass. The authorityof the three-way mixing valve N = P1/(P1 + P4) and is close to unity

Figure 3.13 Authority of three-port valve in diverting circuit. N = P1/(P1+ P2) = P1/P3, where P3 is measured with the valve closed, i.e. in bypassposition

Figure 3.14Curves forsymmetricalthree-port valveselected forpower linearoutput

Page 45: Building control system, aplication guide   cibse guide

between valve stroke position and flow for two types of valvecharacteristic for different authorities. The valve authoritymodifies the characteristic curves shown in Figure 3.6,which are drawn for a constant pressure drop across thevalve, i.e. for an authority of unity. The bottom rightquadrant shows the relation between flow through theheater emitter and heat output. Together, these allow theconstruction of the curve in the bottom left quadrant, whichshows the relation between valve position and heat output.Two example curves are shown. Curve 2, representing anequal percentage characteristic with authority N = 0.7, givesan almost linear change of heat output with valve position.Curve 5, a linear characteristic valve with authority N = 0.8,is highly non-linear and shows why this type of valve isunsuitable in this application.

It is the task of the controls specialist to size and selectcontrol valves suitable for the HVAC system under

consideration. Once the circuit has been designed and thevalve authority decided, the valve size can be selected fromthe pressure drop across the valve and the flow rate throughit, both when the valve is fully open. Valve sizes arespecified as the Kv value, see 3.3.3.2. The required valve sizeis given by the equation:

Kv = Vm/Pm0.5

where:

Vm flow through open valve (m3/h)

Pm pressure drop across open valve (bar).

This may be rewritten as

Kv = 36Vml/PmkP0.5

where:

Vml flow through open valve (l/s)

PmkP pressure drop across open valve (kPa).

The required valve with the nearest Kv value may beselected from a manufacturer’s list. Choosing a valve with alower Kv value will increase the authority. It must beemphasised yet again that the system design has a greatinfluence on the possibility of designing effective controls.System design and controls should be considered togetherfrom the concept stage of the project. The design ofhydraulic circuits is considered in more detail in section 5.

3.3.4.3 Cavitation

When a fluid flows through a restriction, its velocityincreases and in consequence the static pressure decreases.The reduction in pressure may be sufficient to cause theformation of vapour bubbles. When these bubbles collapse,they create noise in the system. In addition, intensemicrojets of liquid are formed which can damage thesurface of the valve and pipework. The condition forcavitation to occur is defined in terms of the pressure dropacross the valve:

Pmax = Km(Pin – Pv)

where:

Pmax maximum allowable pressure drop acrossopen valve (kPa)

Km valve recovery coefficient

Pin absolute inlet pressure (kPa)

Pv fluid vapour pressure at inlet temperature(kPa).

Values for Km are a function of the valve construction, butare typically between 0.6 and 0.9. Values of water vapourpressure as a function of temperature are shown in Table3.10. In general, cavitation problems are unlikely to beencountered if the pressure drop across the valve is lessthan 70 kPa, or if the fluid velocity is below 3 m/s.

3.3.4.4 Valve selection checklist

On water circuits, first decide whether two- or three-portvalves are the most suitable and select a reliable control

3-16 Building control systems

Figure 3.15Curves forasymmetricalthree-port valveselected forpower linearoutput

Figure 3.16 Stylised valve authority and power output characteristics

Page 46: Building control system, aplication guide   cibse guide

strategy. The following points should be taken intoconsideration when selecting a valve:

— Is the valve body suitable for the temperature andpressure of the fluid system? Remember thepressure is the sum of static and dynamic head.

— Ensure that the valve will pass the required flow at apressure drop within the maximum differentialpressure rating of the valve.

— Check for out-of-balance forces, particularly duringclosure of a two-port valve.

— Check whether tight shutoff is required; this is notusually possible with a double seated valve

— Check there is sufficient pump head to providethe pressure drop across the valve at the specificduty.

The above rules apply to all valves, including two-positionon/off. For modulating valves, the following additionalconsiderations apply:

— Select an equal percentage valve characteristicunless there is good reason to select an alternative.

— Ensure pressure drops though heat exchangers andassociated pipework are known before controlvalves are selected.

— Select valves to provide an authority of at least 0.5for diverting applications and 0.3 for mixingapplications.

— Where possible, use heat transfer curves of flowagainst output to check possible anomalies andconfirm the correct characteristic has been chosen.

— Ensure that the rangeability of the selected valves islarge enough to provide stable control under lowload conditions.

— Three-port valves with asymmetrical port charac-teristics should be used to maintain flow conditions.

Before finalising the selection:

— Check whether there have been changes to thespecification of heat exchangers and pipework sincethe original design.

3.4 Dampers

3.4.1 Damper selection

Dampers are used to control air flow in ducts in a manneranalogous to the use of valves in hydraulic circuits. Thedamper chosen for a particular situation must satisfy boththe physical requirements of the application and alsoprovide suitable control characteristics. The practice ofsimply selecting a damper to fit the available ductdimensions can lead to unsatisfactory control operation.The majority of dampers used for modulating control havea rectangular cross-section and provide control by rotatinga set of blades. The blades may move in parallel oropposition to each other. Figure 3.17 shows different typesof damper. Round dampers normally have a butterfly typeblade and are used to control flow in ducts that have highstatic pressure and high velocity characteristics. Dampers

Components and devices 3-17

Table 3.10 Vapour pressure of water

Water temperature (ºC) Vapour pressure (kPa)

10 1.220 2.330 4.240 7.450 12.360 19.970 31.180 47.390 70.1

100 101110 143120 199130 270140 361150 476160 618170 792180 1003190 1255200 1555

Figure 3.17 Types of damper

Page 47: Building control system, aplication guide   cibse guide

may be installed for the control of fire and smoke. Smokedampers have to meet relevant criteria and are normallyinstalled and operated independently of the HVAC controlsystem; they are not considered further in this Guide. It ispossible to obtain smoke and control dampers, which arecapable of operating as modulating dampers, whileretaining the necessary smoke control criteria after manyoperations. Damper sizing is covered in more detail below.Other factors to be taken into account when selecting adamper are:

— Leakage rating. Leakage through the damper in theclosed position may be critical in such applicationsas fresh air intakes in cold climates and the designshould specify the maximum acceptable leakage. Itis difficult to achieve good shutoff with a damperand it is necessary to specify low leakageconstruction where required. Different classes ofleakage are available and leakage is specified interms of leakage volumetric flow per unit damperarea at a specified pressure difference. Low leakageis obtained by the provision of seals and the use ofstiffer blades; this may require a higher closingforce from the actuator.

— Velocity and turbulence. As the air velocity in a ductincreases, the damper blades experience higherforces, which may be sufficient to bend or twist theblade, or cause problems with the bearings andlinkage. Dampers are given a velocity rating toindicate the maximum velocity in the duct; ratingsmay need to be reduced in turbulent conditions.Moderate turbulence may be found downstream ofduct transitions or elbows. Severe turbulence canbe found near the discharge of a fan and this can besufficient to prevent satisfactory operation of adamper.

— Pressure. The maximum static pressure that can bedeveloped across a damper occurs when the bladesare closed. Dampers are given a maximum staticpressure differential; operation above this valuemay give rise to excessive leakage and possibledamage.

— Torque requirements. Two conditions must beconsidered when establishing minimum torquerequirement of a damper. One is the closing torquewhich is needed to achieve the required maximumleakage rate. The other is the dynamic torqueneeded to overcome the effect of high velocity airflow over the blades. This will affect actuatorselection.

— Mixing. Parallel blade dampers alter the flowdirection of air passing through them. By directingthe air flow to one side of the duct, they may causestratification. In some cases, the change in directionof the air stream may be used to promote mixingwhere it joins another air stream.

3.4.2 Modulating dampers

The most common type of modulating damper has arectangular cross-section, with a set of blades that may berotated by a linkage connected to an actuator, to restrict theflow of air through the damper. The blades are linked toeach other and may have parallel or opposed motion; seeFigure 3.18.

The relationship between damper blade rotation and flowthrough the damper for a constant pressure drop across thedamper is shown in Figure 3.19. This is termed theinherent characteristic of the damper.

The ‘ideal’ damper characteristic would result in a linearrelation between actuator movement and heat delivered tothe conditioned space. The distribution of heat by airdiffers from that by water in that air systems are essentiallyopen and all the energy in the air stream can be consideredas delivered to the conditioned space. A linear dampercharacteristic is therefore desirable. Systems controlled bymodulating dampers normally have a fan running atconstant speed with a constant pressure drop across thesystem. In the simple ducted air system of Figure 3.20,where air is supplied by a fan running at constant pressure,the total pressure drop across damper and plant is constant

3-18 Building control systems

Figure 3.18 Parallel and opposed operation of damper blades

Figure 3.19 Inherent characteristics of damper types

Page 48: Building control system, aplication guide   cibse guide

and so the pressure drop across the damper increases as thedamper is closed; when fully closed it is equal to the staticpressure of the fan.

The changing partition of pressure drop across damper andload as the flow changes results in dampers having aninstalled characteristic different from the inherentcharacteristic. The installed characteristic is affected by thesize of the damper, described by the damper authority. Thisis defined in a similar way to that of valves, where theauthority is given by

N = P1/(P1 + P2)

where:

P1 pressure drop across the damper in the fullyopen position

P2 pressure drop across the rest of the circuit.

In many cases (P1 + P2) is constant and equal to thepressure developed by the fan. American usage may refer tothe damper characteristic ratio (α or sometimes δ) definedas

� = P2/P1

The installed damper characteristic curves may be derivedfrom a knowledge of the inherent curve and the authority.The pressure drop developed across a fitting is proportionalto the square of the air flow through it and it isstraightforward to show that for any intermediate openingposition

(1/Fa)2 – 1

N =(1/Fi)

2 – 1

where:

Fa ratio of actual flow in the intermediateposition to actual flow at the fully openposition

Fi ratio of flow in the intermediate position toflow through the fully open damper for theinherent characteristic.

Damper characteristic curves are supplied by dampermanufacturers and typical examples of installedcharacteristics are shown in Figure 3.21 and Figure 3.22.

It can be seen that for an opposed blade damper the closestapproach to linearity occurs with an authority N = 5 to10%, while for parallel blade dampers it occurs when N =20%. The implication is that for a given pressure dropacross the damper and system, the pressure drop across aparallel blade damper will be four times that across anopposed blade damper, with correspondingly higher energyconsumption. Opposed blade dampers are therefore

recommended in general for control purposes.

It is poor practice to choose a damper size based on duct sizeand convenience of location. This frequently results inoversized dampers with inadequate authority to provideproper control. The correct damper will often have smallerdimensions than the duct, giving additional benefits inreduced damper and actuator costs, together with lowerleakage in the closed position. Where the damper is smallerthan the cross-section of the ductwork, it may be installedwith a baffle or blanking plate to take up the additional area.If the blanked off area exceeds about 30% of the total cross-section, it may be advisable to use a reducing section of

Components and devices 3-19

Figure 3.20 Damper authority N = P1/(P1 + P2)

Figure 3.21 Installed characteristic of parallel blade damper

Figure 3.22 Installed characteristic of opposed blade damper

Page 49: Building control system, aplication guide   cibse guide

ductwork to avoid turbulence caused by the suddenrestriction at the baffle.

3.4.3 Applications

In general, parallel blade dampers are used where there islittle resistance to flow in series with the damper, and opposedblade dampers where the controlled section containsrestrictions of any sort (Table 3.11). Useful treatments ofdamper applications are to be found in the literature(11,12).

3.4.3.1 Return air mixing

A common application is the control of return air shown inFigure 3.23. The system delivers a constant flow of air to theconditioned space; the dampers are used to vary theproportion of air that is recycled. The pressures at Ps and Peare therefore constant and so for sizing purposes eachdamper may be considered separately in its own subsystem.The inlet and exhaust subsystems include the seriesresistance of weather louvres and bird screens and anopposed blade damper should therefore be chosen to give anauthority of between 5 and 10%; Figure 3.22 shows that thiswill produce an approximately linear installed charac-teristic. Where louvres and screens are absent at inlet andexhaust, the lack of their resistance increases the authority ofthe damper and it may be appropriate to select a parallelblade damper to give a more linear characteristic. The returnair path has little resistance other than the damper itself, andso the damper operates at a high authority. The correctchoice here would be a parallel blade damper.

3.4.3.2 Face and bypass control

A common application of dampers controlling the flow ofoutside air uses two dampers in a face and bypass

configuration, as shown in Figure 3.24. The system isdesigned to provide a constant pressure drop and henceconstant combined flow rate, while the proportion of airflowing through the coil is varied by operating a linked pairof dampers. Since the pressure drop across the bypassdamper is constant, a parallel blade damper is used toprovide a linear characteristic with minimum pressure dropat full flow. Since the face damper has the resistance of thecoil in series, an opposed blade damper is used of theappropriate authority to provide a linear characteristic.Starting with the known resistance of the coil, the facedamper will be sized to give an authority of between 5 and10% and the bypass damper then sized so that its resistanceis equal to that of the combination of face damper and coil;this will give an approximately constant flow though thesystem at all operating positions. Consideration may begiven to the use of parallel blade dampers for both sets toaid downstream mixing, as shown in the diagram.

3.5 Motors

3.5.1 Energy efficiency

Motors are major users of electricity and account for almosthalf the total electricity use in the UK. Recentdevelopments in higher efficiency motors and variable-speed drives are described in the DETR Good Practice Guide2(13), which offers good advice on the energy efficient use ofmotors, shown in Table 3.12. By far the most common typeof motor used in HVAC applications is the three-phasesquirrel cage induction motor. Three-phase power issupplied to the field windings in the stator, the fixed part ofthe motor which encloses the rotating rotor. The current in

3-20 Building control systems

Table 3.11 Damper applications

Control application Damper type

Return air Parallel

Outdoor air or exhaust air— with weather louvre or bird screen Opposed— without louvre or screen Parallel

Coil face Opposed

Bypass— with perforated baffle Opposed— without perforated baffle Parallel

Two-position (all applications) Parallel

Figure 3.23 Damper selection for arecirculated air mixing circuit

Figure 3.24 Face and bypass damper system, showing use of parallel bladedampers to assist mixing

Page 50: Building control system, aplication guide   cibse guide

the field windings produces a rotating magnetic field whichinduces currents in the rotor conductors and pulls the rotorround with it. There are no electric connections to therotor. The speed of rotation of the rotor is somewhat slowerthan the frequency of the applied field by an amount knownas slip, expressed as a percentage of the synchronous speed,hence the description of the motor as asynchronous.Within the operating range of the motor, speed isapproximately constant. The treatment here refers to three-phase induction motors, unless otherwise stated.

3.5.2 Starting

The low ohmic resistance of the field windings of aninduction motor means that if a stationary motor isconnected directly to the supply, it will draw a heavystarting current until the motor develops sufficient speed toproduce a balancing back EMF. This starting current may beup to eight times the full load current and can produceproblems for the electrical services within the building.Several methods have been developed to limit the startingcurrent and provide controlled start-up of motors. Theassociated topic of variable-frequency drives is covered in3.5.3.

3.5.2.1 Direct on-line (DOL)

In some situations it may be possible to simply connect themotor to the supply. This will produce a high peak startingcurrent and in most cases a high starting torque. Thecontrol gear and contactors must accommodate the startingcurrent. Switchgear designed to BS EN 60947-4-1(14) isbased on a starting current of 7.2 times normal full loadcurrent. DOL starting is simple, but it use is limited toapplications where:

— Low power motors are used and the supply can copewith the start current.

— The load driven by the motor can cope with mechanicalshock produced by the high starting torque.

— A high starting torque is needed.

3.5.2.2 Star–delta starter

With this form of starter, the three-phase supply voltage tothe stator windings can be switched between star and deltaconfigurations. On starting, the supply is connected in starconfiguration, when the starting current is typicallybetween 1.5 and 2.6 times the normal full load current andthe peak starting torque is between 0.2 and 0.5 times thenominal operating torque. Under this condition the motorwill accelerate to about 75% of full speed, when theconnections are switched to delta configuration, allowingthe motor to achieve full performance. The switchover iscontrolled by a timer, whose operating time is set duringcommissioning. It is normal to introduce a small delaybefore the delta connection, to avoid any arcing or transientcurrents. Its features are:

— low starting torque

— access to both ends of stator windings required.

3.5.2.3 Primary resistance starter

Starting current is limited by connecting a resistance bank inseries with the motor windings. Once the motor has run up,the resistance is switched out and the motor is directlyconnected; the changeover is normally controlled by a timer.Starting current and torque are controlled by the choice ofresistance; typically a peak starting current of 4.5 times fullload and a peak starting torque of 0.75 operating torque. Thisform of starter is suitable for applications such as ventilatorfans, where the load torque increases with speed.

3.5.2.4 Autotransformer

The motor is started at reduced voltage supplied from anautotransformer. This is a specialised solution, used forlarge motors above 100 kW.

3.5.2.5 Electronic soft start

Introduced relatively recently, this form of starter is rapidlygrowing in use. An electronic circuit is used to produce agradually increasing voltage to the motor to produce asteady smooth acceleration. The units employ a thyristorbridge and by varying the firing angle of each set ofthyristors, it is possible to control the output voltage. Thesupply frequency is unchanged and soft starters do notbehave like inverter drives.

3.5.3 Speed control

The use of variable-speed drives (VSD) on motors forpumping fluids or moving air can lead to substantial energysavings(15). The recent development of variable-frequencyinverter drives has expanded the application of variable-flow systems, with attendant changes in control systemdesign. This section summarises the main methods ofmotor speed control, concentrating on inverter drives.

3.5.3.1 Eddy current coupling

The eddy current coupling is an electromagnetic couplingwhich fits between a standard constant-speed AC inductionmotor and the load. The relative rotation of the motor andload generates the eddy currents to provide the couplingand so the maximum output speed is less than the motor

Components and devices 3-21

Table 3.12 Energy saving checklist for motors

1 Is the equipment still needed?— Check that changing requirements have not eliminated the

need

2 Switching the motor off— Time the switching according to a schedule— Monitor system conditions and switch off when motor is not

needed— Sense the motor load and switch off when idling

3 Reducing the load on the motor— Is the transmission efficient?— Is the driven equipment efficient, e.g. gearboxes and belt

drives?— Is the control system effective?

4 Minimising motor losses— Specify higher efficiency motors where feasible— Avoid oversized motors— Check power quality

5 Slowing down the load— Use variable speed drives where possible, for both control and

regulation— Use multiple-speed motors where 2, 3 or 4 distinct duties exist— Check pulley ratios for belt drives

Page 51: Building control system, aplication guide   cibse guide

speed. This form of speed control is well proven andreliable. It can produce high torque at low speed, thoughthis is not often a requirement for HVAC applications.

3.5.3.2 Switched reluctance drive

This system requires a special motor with more stator thanrotor poles. It is powered by a solid-state switchedreluctance drive controller, which provides controlled DCpulses to the motor. While the components are similar tothose used in inverter drives, the principle of operation isdifferent. Sophisticated motor control is possible, withcontrol of maximum and minimum speeds and accelerationrates. Control of starting conditions is available, making theuse of a separate starter unnecessary. The number ofsuppliers is more limited than for inverter drives; themaximum motor size is about 75 kW.

3.5.3.3 Variable-voltage control

Speed control by varying the input voltage by a transformer isnot normally recommended. The range of speed regulation islimited and efficiency is poor. Electronic variable-voltagedrives are available which use phase angle control thyristorsto provide a variable-voltage input to the motor. The cost ofthe drive is lower than an inverter drive, but the control andefficiency is poorer. A special motor matched to the controlleris used and this form of control is only recommended forsmall pumps with built-in variable-speed drive.

3.5.3.4 Multi-speed motor

Multi-speed motors are available which are basicallystandard induction motors with additional windings whichmay be switched in or out, effectively changing the numberof poles of the motor. The motor speed will thereforechange in coarse steps, from 3000 rpm for a two-poleconfiguration to 750 rpm as an eight-pole configuration,less slippage. Two- or three-speed motors are common,with four-speed available. Multi-speed motors are simpleand low cost and are found incorporated in small multi-speed pumps and fans. They are normally only available infractional kilowatt sizes.

3.5.3.5 Inverter drive

Variable-speed inverter drives supply power of controlledfrequency and voltage to the motor. Standard inductionmotors are used without modification and with recentdevelopments and cost reductions this is now the mostpopular method for fan and pump speed control. Theinverters produce a limited starting current for a soft start,making the use of a separate starting circuit unnecessary.Various types of speed control are available. There are threemain types of inverter:

— pulse width modulation (PWM)

— pulse amplitude modulation (PAM)

— current source inverter (CSI).

Pulse width modulation inverters

The principle of the inverter is shown in Figure 3.25.Three-phase mains current is rectified and fed to a DC linkcircuit, which provides some smoothing. The rectifier may

be either uncontrolled, using diodes, or controlled, usingthyristors. Uncontrolled rectifiers produce largedisturbances and losses in the mains and the use ofcontrolled rectifiers is generally recommended. The DC linkcontains induction coils and capacitors to provide areservoir of smoothed current for the output stage. Recentdevelopments have allowed the elimination of the DC linkby the employment of a matrix inverter in the rectifier,which is a combination of power transistors controlled insuch a way as to give a smooth output and eliminate theneed for the DC link. This reduces the space requirementand also reduces the size of the EMC filter(16). The outputbridge circuit uses transistors to supply a train of pulses.The output bridge operates at a switching frequency whichmust be substantially higher than mains frequency. Bycontrolling the width and spacing of the pulses it is possibleto produce a near sinusoidal supply to the motor ofcontrolled frequency and amplitude; the frequency variesfrom a minimum of a few hertz to a maximum of mainsfrequency to give maximum rated motor speed. The higherthe operating frequency of the output bridge, the moreclosely will the motor current approximate to a sine wave.With a low switching frequency (<5 kHz) the motorcurrent waveform will not be smooth and the result may beundesirable motor noise. A higher switching frequency,now available up to 20 kHz, produces smoother runningbut requires more attention to EMC performance.

The inverter is controlled by driver and control circuits.The control circuit of the variable-speed drive ensures thatthe amplitude of the output is matched to the frequency;the output voltage is reduced at low frequencies to preventexcessive winding currents being drawn. Highestefficiencies are achieved when the voltage–frequencycharacteristic is matched to the type of load. The controlgear also provides a soft start capability.

The processor may also incorporate localised controlfunctions. The processor takes overall control of the invertersuch as up/down ramping of the frequency, start/stop signal,motor protection and error handling. At the same time theprocessor may also take care of the control task, e.g. pumpingapplication. The processor controls the inverter using abuilt-in PID regulator and a signal from a pressure sensor, toproduce a constant pressure to the system. All adjustments toand communications with the surroundings are controlledby the processor, which also collects the data to becommunicated to the user.

Open loop control. Open loop control operates withoutfeedback. The inverter supplies the voltage and frequencywhich is expected to produce the desired speed. Whileadequate for many applications, this form of control is notsuitable for sustained low speed operation, nor withfluctuating loads.

3-22 Building control systems

Figure 3.25 Principle of PWM inverter for motor speed control

Page 52: Building control system, aplication guide   cibse guide

Voltage vector control (VVC). This is a sophisticated form ofPWM inverter, in which the control circuit of the invertermonitors the output to the motor and digitally controls thetiming of the output pulses to produce a high quality sinewave output matched to the motor type and load. It claimsbetter speed control and efficiency than a simple PWMinverter.

Flux vector control. By obtaining information about thespeed and position of the rotor, it is possible to calculate thetorque and flux demand of the motor instant by instant andcontrol the output bridge accordingly. This makes for avery accurate control of speed with rapid response to inputsignals. However, it is more expensive than the othervarieties of PWM controller and requires some form oftachometer or position encoder on the motor, obviating theadvantage of being usable with standard motors. It is notnormally justified for building services applications.Sensorless vector control is a form of flux vector controlwhich dispenses with the need for speed feedback from themotor by deducing the rotor behaviour from the windingcurrent.

Pulse amplitude modulation inverters

The pulse amplitude inverter is similar to the PWM inverterin its basic principle, except that the output waveform isconstructed from pulses of varied amplitude. With pulseamplitude modulation the output bridge of the inverterconstructs an approximately sinusoidal voltage output ofvariable frequency. The output is made up from either sixor 18 pulses per period; the six-pulse inverter gives a ratherpoor output waveform.

Current source inverter (CSI)

This is a simple low cost inverter, but has the disadvantagesof producing harmonic disturbances on the mains and is oflower efficiency than other types of inverter. CSIs are notnormally recommended for building services applications.

3.5.4 Variable-speed motors

The frequency inverter has become the standard form ofvariable-speed drive. Inverters are available as stand-aloneunits and extend up to the megawatt range. A stand-aloneinverter drive offers the greatest choice of drive and speedcontrol system, and when used with a feedback encodergives great accuracy of torque and speed control. This isimportant for some process control, but not required inHVAC applications. The term ‘variable-speed motor’ is nowgenerally used to imply a motor with integrated inverterdrive. Such motors are available up to about 10 kW, thoughthe upper limit is increasing. The choice between avariable-speed motor with built-in VSD and a separateinverter will be based on the following considerations:

— Variable-speed motor

— Inverter and EMC filters built in, givinglower installation cost and reduced wiringruns.

— Suitable for fan and pump speed control,less suitable for constant torqueapplications.

— Simple product selection.

— Inverter may be top or non-drive endmounted.

— PID controller for pressure or temperaturecontrol can be incorporated.

— Stand-alone inverter(16)

— More accurate control possible with use offeedback encoder.

— Available in large sizes, up to megawatts.

— Smaller bulk of motor may suit availableinstallation space.

— Suitable for all types of load.

3.6 Pumps and fansThe specification of pumps and fans is outside theresponsibility of the controls engineer. A single pump maynot be able to satisfy the full design flow and yet provideeconomical operation at part loads. The designer must alsoensure that the pump motor is not overloaded under anypossible operating condition. Several possible pumparrangements are available to the designer:

— multiple pumps in parallel or series

— provision of a standby pump

— pumps with two-speed motors

— variable-speed pumps

— distributed pumping, including primary, secondaryand tertiary circuits.

This brief discussion is included to emphasise theimportance of the chosen method of flow control to overallenergy consumption. For a fan or pump operating in a fixedsystem with flow of constant density:

— Volume rate of flow is proportional to speed ofrotation.

— Pressure varies as the square of the speed.

— Absorbed power varies as the cube of the speed.

Regulation of flow by the use of dampers or valves willtherefore in general be less efficient than by the use ofvariable-speed drives. This topic is treated in detail in aBRECSU publication(15), from which Figure 3.26 is taken.The use of VSD in control applications will be considered inmore detail in section 5.

3.7 Control panels and motorcontrol centres

It is standard practice to group together low and mediumvoltage (e.g. 240 V single-phase and 415 V three-phase)control equipment and mount it in an enclosed cabinet.This gives protection for the equipment and operating staffand allows convenient connection of hardwired interlocks.Thus the cabinet will contain such equipment as relays,contactors, isolators, fuses, starters and motor speedcontrollers. Meters may be mounted in the surface of thecabinet as required. Control panels are classified asfollows(17):

Components and devices 3-23

Page 53: Building control system, aplication guide   cibse guide

— Form 2. This is a conventional cupboard type box,with an isolator linked to the door. Opening thedoor of the cabinet isolates all components, whichare commonly mounted on a DIN rail. There is norequirement to shroud connections.

— Form 3. The door of the cabinet is lockable but notinterlocked to an isolator. All connections areshrouded and individual items of equipment, suchas motor starters, have their own covers andisolators. This type of panel is used where severalitems of plant are served from the same controlpanel. One item may be isolated and servicedwithout switching off the rest.

— Form 4. The control centre consists of severalseparate cubicles, each serving a separate item ofplant and with its own door and interlockedisolator. The construction serves to contain anexplosion and allows work on individual plantitems. The separation of electrical equipment alsoreduces EMC problems; see 4.3. The cubicleconstruction tends to restrict access for work. Analternative version mounts the equipment onwithdrawable racks. This allows the equipment tobe withdrawn for servicing or exchange.

With the increased use of inverter drives, there is a move todecentralise motor control, placing the inverter andassociated control gear adjacent to the motor beingcontrolled. Several variable-speed drives incorporate theirown local controller, which may be connected to the BMS.Inverters require to be air cooled and placing severalinverters in a control cabinet will require fan cooling.

Control panels usually have a separate section with its owndoor for the extra-low voltage (ELV) (e.g. 24 V) controlsystem, which is not isolated. It is therefore possible toobtain access to the control wiring while the plant is inoperation. There is normally a facility for plugging in alaptop PC or other interface for diagnosis and servicing. It isgood practice to allow only ELV control cables to enter orleave the control centre. In particular, LV interlock cablesshould not enter the box, since they could remain live evenwhen the box was nominally isolated. Some plant provides240 V interlock signals, e.g. for boiler lockout. A relay at theplant should be fitted to provide a voltage-free contact foruse by the control system.

Control panels and motor control centres are normallyconstructed by specialist subcontractors and delivered tosite with internal wiring complete. Further informationmay be obtained from the regulations set out in BS CEN60439(17).

3.8 The intelligent outstationThe intelligent outstation, or universal controller, is at theheart of the contemporary building management system(BMS). Known variously as a field processing unit,distributed processing unit, freely programmablecontroller or simply as a controller, it combines a stand-alone control capability with the ability to communicateover a network with the head end supervisor. Controllersare available from many manufacturers and share thecharacteristic of being highly versatile, able to accept arange of inputs, to drive different output devices and to beprogrammed to carry out most common control tasks.Where the controller is dedicated to suit a particular pieceof plant, such as a VAV box or chiller unit, it is termed aunitary controller or dedicated function controller.

Controllers incorporate all or most of the followingcomponents and can usually accept additional modules asplug in units.

— inputs: a module accepting a range of different typesof input

— outputs: voltage and current outputs, plus relay closures

— communications: the ability to communicate withthe supervisor and other controllers

— processor: a microprocessor to perform the controloperations

— configuration modules: a range of software moduleswhich can be linked to carry out the requiredcontrol functions

— clock

— power supply

— local display: either a built in display or provisionfor a plug in display unit

— local supervisor: provision to plug in a supervisor.

The components are housed in a case which is normallydesigned to be tamper proof. Protection against harshenvironments is categorised by the ingress protectionsystem. The degree of protection is categorised by the two-digit IP number(18) (Table 3.13). The first indicates the

3-24 Building control systems

Figure 3.26 Comparative efficiencies of variable-flow methods

Page 54: Building control system, aplication guide   cibse guide

degree of protection from dust, running from 0 (noprotection) to 6 (dust tight). The second digit indicateswater protection, running from 0 (no protection) to 8(submersible). Controllers may operate in an electricallynoisy environment and electromagnetic compatibility(EMC) is discussed in 4.3.

3.8.1 Configuration

The controller must be configured before it can be put intooperation. This may be divided into:

— system configuration

— hardware configuration

— strategy configuration.

3.8.1.1 System configuration

The controller is part of a larger system, communicatingwith the supervisor and other controllers. Other devicesmay communicate with the controller, either to interrogateit for information or to download software or alter controlparameters:

— local display panel

— remote display panel

— local or central supervisor

— another controller.

In addition, the controller can originate messages which aretransmitted to other devices:

— alarms which can be received by the supervisor,printer or display

— communications transmitted to another controller.

A supervisor is a computer which allows an operator accessto data held within controllers and also allows modificationto the software held inside the controller. On a large BMS,there is a head end supervisor, which has access to theentire BMS network. It is normally possible to use a portablePC connected locally to a controller, which may berestricted to communicate with that controller alone. Thesupervisor may communicate in four modes, to restrictunauthorised access to the BMS configuration.

— Read only. The supervisor may be used tointerrogate controllers and to display values andproduce reports. No changes may be made to anysystem parameters.

— Supervisor mode. This mode enables the operator tochange set points and operating times. It isnormally password protected.

— Configuration mode. This mode enables the engineerto change parameters or set up and fundamentallymodify the control strategy resident in the controller.

— Upload/download. This mode enables the operatorto take a copy (i.e. upload) of the strategy definingfile from the controller memory and then store onfloppy disc. In the unlikely case of loss of memoryin the controller, it is possible to download the filefrom the supervisor to the controller.

3.8.1.2 Hardware configuration

Typically, a controller is hardwired to a number of inputsand outputs, and communicates with the rest of the BMS oversome form of network. These have to be set up correctly.

Inputs. Controllers can accept a range of analogue anddigital inputs. Each input channel must be configured tomatch the connected input. Depending on the type ofcontroller, this may be done by physically changing inputmodules, changing links or components. A universal inputchannel may accept any form of input, but still requiresconfiguration by changing internal links. The range ofanalogue inputs includes:

— Voltage. This is usually 0–10 V DC to match thestandard output of a sensor transducer.

— Current. This is usually 4–20 mA DC to match thestandard.

— Passive. Some controllers can be configured toaccept thermistors or resistance thermometerswired in directly to the input channel. Measurementcircuitry is incorporated in the controller.

— Digital. This operates on a voltage-free contactclosure and is used to monitor plant status. Thecontroller provides a 24 V DC supply to energise theinput signal.

— Pulse. This accepts pulses from pulsing energymeters, with defined minimum pulse width.

Outputs. Controllers provide a range of analogue and relayoutputs, including:

— Analogue voltage. Usually 0–10 V. This signal may beused to control most actuators without furtheramplification. In some cases an intermediate drivermodule may be required.

— Relay output: changeover relays, used to energisecontrolled plant.

— Time proportioning: a relay output with variablemark/space ratio.

— Pulsed: 24 V AC pulsed operation, required by someactuators.

— Resistive: 0–135 Ω potentiometer output.

— Network address. The network node address of thecontroller must be identified by a by a uniquenumber. This may be set either by a switch withinthe controller or during software configuration.

— Communications. Setting up the communicationsinterface depends on the network.

Components and devices 3-25

Table 3.13 IP protection numbers IEC 144

IP Foreign body protection against: Water protection against:

0 None None

1 Large foreign bodies Vertical dripping water

2 Medium sized foreign bodies Angled dripping water

3 Small foreign bodies Fine water spray

4 Granular foreign bodies Heavy water spray

5 Dust deposit Water jet

6 Dust ingress Water flow

7 Immersion

8 Submersion

Page 55: Building control system, aplication guide   cibse guide

3.8.1.3 Strategy configuration

Controllers are pre-programmed with a number of softwaremodules. The modules exist as ‘firmware’ within thecontroller memory and are not re-programmable. In orderfor the controller to perform the desired function, themodules are brought into action by linking them togetherby so-called ‘soft wiring’. In addition to the firmware,advanced controllers allow the writing of custom controlroutines in the controller’s own programming language.The whole process is known as strategy configuration.Configuration is carried out using a proprietary programrunning on a PC. Each controller manufacturer has its ownhigh level programming tool, which normally consists of apictorial representation of the firmware modules containedin the controller, which may be linked on screen by ‘softwiring’. In addition to the interconnections of the modules,values of control parameters may be keyed in at this stage.The complete configuration may be downloaded into thecontroller. The program remains available for use in othercontrollers. A controller contains some or all of the softwaremodules listed in Table 3.14.

3.9 SummaryThe selection and correct use of appropriate components isessential to produce a reliable and satisfactory controlsystem. The types of sensor available are summarised andadvice given on selection. Sensors must be mounted in aposition that is representative of the quantity beingmeasured and which gives access for maintenance andcalibration. Experience shows that incorrect installation isthe major cause of problems with sensors.

Actuators convert the output from a controller into themechanical movement of a valve or damper. The actuatorchosen must have sufficient force to operate the controlleddevice; it is important to select an actuator with therequired degree of positioning accuracy, particularly if thecontrolled device has to operate over its whole range.Modern actuators incorporate microprocessor controlwhich gives accurate positioning and feedback of positionto the control system.

Control valves for hydraulic circuits should be chosen togive adequate authority and a characterisation appropriatefor the output device. The aim is to provide a finalcontrolled output which is nearly linear with valveposition; this will assist in providing satisfactory control.

The same considerations apply to dampers. The sectiongives guidance on the choice between parallel and opposeddampers and emphasises the need to provide sufficientdamper authority; this may require the damper area to besmaller than the duct. It is now possible to use standardinduction motors with variable-speed drives. The use ofVSD and two-port valves can lead to substantial savings inpump and fan energy consumption. The design ofhydraulic systems incorporating two-port valves demandscare to avoid problems at part load.

Lastly, the intelligent controller is described. This is theworkhorse of most control systems. It provides local controlof subsystems while communicating over a network withthe building management system. Controllers contain acomprehensive range of pre-programmed controlfunctions, which require to be configured for particularapplications, using proprietary programming softwareprovided by the controller manufacturer.

References1 Carotenuto A, Dell’Isola M, Crovini L and Actis A Accuracy of

commercial dew point hygrometer ASHRAE Transactions 101(2)252–259 (1995)

2 Carotenuto A, Dell’Isola A J and Vigo P A comparison betweenthe metrological performances of humidity sensors Transactionsof Measurement and Control 17(1) 21–32 (1994)

3 A guide to the measurement of humidity (London: Institute ofMeasurement and Control) (1996)

4 Potter I N and Booth W B CO2 controlled mechanical ventilationsystems TN 12/94.1 (Bracknell: Building Services Research andInformation Association) (1994)

5 Martin A J and Booth W B Indoor air quality sensors TN 1/96(Bracknell: Building Services Research and InformationAssociation) (1996)

6 Control sensor installation (London: Building Controls Group)(1996)

7 UKAS Traceability of measurement: general policy M50 (Feltham:United Kingdom Accreditation Service) (1996)

8 Petitjean R Total hydronic balancing 2nd ed (Ljung, Sweden:Tour and Andersson) (1997)

9 Parsloe C J The design of variable speed pumping systems Draft79000/2 (Bracknell: Building Services Research andInformation Association) (1999)

10 Levermore G J Building Energy Management Systems, 2nd ed(London: E & F N Spon) (2000)

11 Honeywell Engineering manual of automatic control SI ed(Minneapolis: Honeywell Inc.) (1995)

12 Johnson Damper application engineering. Engineering ReportH352 H352 (Milwaukee: Johnson Controls Inc.) (1991)

13 DETR Good Practice Guide 2. Energy savings with electric motorsand drives Updated 1998 (Harwell: ETSU) (1998)

14 BS EN 60947-4-1 Electromechanical contactors and motor starters(London: British Standards Institution) (1995)

15 Variable flow control GIR 41 (Watford: Building Research EnergyConservation Support Unit) (1996)

16 ABB Getting it together Electrical Review 230(12) 31–33 (1997)

17 BS EN 60439-1 Specification for low-voltage switchgear and controlgear assemblies (London: British Standards Institution) (1994)

18 BS EN 60 529 Specification for degrees of protection provided byenclosures (IP code) (London: British Standards Institution) (1991)

3-26 Building control systems

Table 3.14 Typical controller software modules

Module Example

Timer functions Scheduling, time zonesOptimum start stop Self-adaptivePID control Self-tuning control loopData logging Stores input and output dataMetering Utility energy metering from pulsed meterLoad management Load cycling and maximum demand controlActuator drivers Time proportioningLighting Presence or absence detection, dimmingMaths functions Log, square root, enthalpy, sensor scalingKnob Input settingsLogic Timers, counters, hours runPulse counting Energy measurementSequencing Controls module operation sequence

Page 56: Building control system, aplication guide   cibse guide

4.0 GeneralThe term building management system encompasses awide range of control systems, ranging from dedicatedcontrollers hardwired to the equipment they control, tolarge-scale distributed systems, extending over several sitesor even countries. The development of larger integratedsystems depends on the existence of communicationprotocols which allow devices from different sources tocommunicate with each other. The organisation of buildingmanagement systems and the networks on which theydepend is the subject of this section.

4.1 BMS architectureThe organisation of the various control elements into acomprehensive BMS is termed the system architecture.

4.1.1 Conventional controls

Electronic control systems were first developed usinganalogue signals to carry information between parts of thesystem and to provide the control action. Controllers werebased on operational amplifiers, now replaced bymicroprocessors. The sensor could be connected directly tothe controller, in which case the controller required theappropriate input circuitry to handle the signal input.Greater flexibility could be achieved by using a transducerto convert the sensor output to one of the several standardsignal forms. This has the additional advantage ofproviding a stronger signal where transmission over adistance is required, where a small signal such as athermocouple EMF might become corrupted. Outputs from

the controller are standardised and are connected directlyto the required actuator. Voltage-to-pressure and pressure-to-voltage transducers allow the use of pneumatic actuatorswith electronic controllers.

Controllers based on analogue inputs and outputs still formthe basis of control systems for smaller buildings. Eachcontroller is linked by direct connection to the controlledoutput device and performs a single function, i.e. a singlecontrol loop. Several independent control systems maycoexist within a building, e.g. a boiler control incorporatingtime switch and flow temperature control plus independentzone temperature controllers. Conventional controllersshare the following characteristics:

— single function controller, hardwired to sensor andactuator

— analogue inputs and outputs

— sensor signal conditioning required for long cablelengths

— standardised controller output

— no central supervision

— cost-effective for simple buildings.

4.1.2 Centralised intelligence

The advent of the microprocessor allowed the developmentof direct digital control (DDC) systems. The controllerfunction is carried by a software program, which can bewritten to execute any desired control characteristic. Manycontrol loops can be handled by the same processor.Changes to the control function can be made by changes tosoftware alone, without any requirement to change

4-1

4 Systems, networks and integration

4.0 General

4.1 BMS architecture

4.2 Networks

4.3 Electromagnetic compatibility (EMC)

4.4 Systems integration

4.5 User interface

4.6 Summary

Section 4 deals with the ways in which components are linked together to form a complete building management system.Large networks are divided into management, automation and field levels, each with their own communications protocols.The attributes of the major standard protocols are described. Systems integration allows communication between differentbuilding services systems, with consequent advantages of more efficient operation; the principles of integration are described,along with ways of avoiding possible contractual problems. Recommended installation practices to avoid problems ofelectromagnetic interference are described and good cabling practices set out. The principles of good user interface design aredescribed.

Page 57: Building control system, aplication guide   cibse guide

hardware. The development of adaptive and self-learningcontrol algorithms becomes possible.

The first systems using DDC employed a centralisedcontroller (Figure 4.1) incorporating all the processingcapability in one unit, known as the central processing unit(CPU). The CPU is connected to some form of user interfaceknown as a supervisor, which allows the operator to viewthe status of the system and change control parameters. Allsensors are brought back to the central unit. Where thepath lengths are long this will normally require signalconditioning at the sensor. The signal conditionercombines a transducer, which converts the sensor output toa standard form, and the transmitter which amplifies thesignal for transmission over long distances of wire. At thecentral controller, the incoming signal is conditioned by aninput card, and converted to a digital form by an analogue-to-digital converter before being sent to the microprocessorfor processing. The treatment of the output signal from thecontroller follows the same pattern in reverse. The outputfrom the microprocessor is converted to analogue form, andconverted to a standard form before being sent to thetransducer at the controlled device.

In control systems with centralised intelligence:

— All sensor inputs are wired to central controller(CPU).

— Control functions are executed digitally.

— Software may be changed without hardware change.

— Reporting and parameter changes are made via thesupervisor.

— The wiring cost is high.

— The system is vulnerable to controller malfunction.

— They have been superseded by the intelligentoutstation, i.e. distributed intelligence.

4.1.2.1 Dumb outstation

The provision of separate wiring for each sensor andactuator is expensive and this has led to the introduction oflocal outstations, also known as data-gathering panels.Sensors are connected into the outstation which performssignal processing and communications functions. A so-called dumb outstation (Figure 4.2) does not carry out anycontrol function. Connection to the central controller is bya data transmission cable. The CPU is required to addresseach point in turn; this is known as polling and in a largesystem results in slow operation. The features of a dumboutstation are:

— Sensors and actuators are connected to localoutstation.

— Outstation contains signal conditioning andcommunication circuits.

— Outstation performs no control function.

— CPU polls each point in turn.

— Outstations vulnerable to CPU failure.

— CPU has to handle large amounts of data.

— They have been superseded by intelligentoutstations.

4.1.3 Programmable controllers

While the use of dumb outstations reduces the wiringrequirements for a large BMS, it is vulnerable to a failure inthe CPU. It is now the general rule to use programmablecontrollers or intelligent outstations (Figure 4.3) whichincorporate their own microprocessor and carry out localcontrol functions, which will operate in the event of a CPUproblem. Communication with the central supervisor is forthe purpose of supervision, fault reporting, data collection

4-2 Building control systems

Figure 4.1 DDC with centralised controller and hardwiring

Figure 4.2 Centralised controller with dumb outstations

Figure 4.3 BMS with intelligent outstations

Page 58: Building control system, aplication guide   cibse guide

and the ability to change control parameters as necessary.Communication between outstation and supervisor isnormally using some form of local area network; this mayemploy a proprietary protocol or one of the standardsystems discussed further below. The intelligent outstation,also known as the universal or freely programmablecontroller, is the main building block of the modern BMSand is described in detail in 3.8. The main features are:

— Control function is incorporated in outstations.

— Outstations function independently of CPU.

— Central station accepts reports and fault alarms.

— Central station may alter set points and otherparameters.

— Devices communicate via a local area network orbus.

— It is the basic component of a modern controlsystem.

A unitary controller is distinguished from a generalcontroller in that it is designed to control a specific type ofplant, e.g. a VAV box or air handling unit. Sensors andactuators may be hardwired or communicate with theunitary controller over a field bus. Unitary controllers arefound supplied with packaged systems; see 4.1.6.

4.1.4 Bus systems

Decentralisation is carried further using a bus system(Figure 4.4). Intelligent devices in the control systemincorporate their own microprocessor and communicationsability. Devices are connected to a bus which allowscommunication between all devices using a well-definedprotocol. Each device is individually addressable andprogrammable. For instance, an intelligent temperaturesensor at the field bus level will transmit a message onto thenetwork identifying itself as well as including atemperature value. Any controller or other device on thebus may then use this message. In order to limit total trafficon a network, a bus network may be divided into segmentsconnected by bridges, which can transmit only messagesdestined for outside the segment. Connection betweenbuses at different levels is via gateways or protocol interfaceunits, which can perform translation where the controllevels employ different protocols, as well as filtering. Someof the major bus systems used in BMS are discussed below.The characteristics of a bus system are:

— All devices communicate using standard protocol.

— All devices are individually addressable.

— Devices communicate directly with each other asrequired.

— The system is decentralised.

— Interoperability between different manufacturers isa possibility.

4.1.5 Modular systems

A particular example of a bus system is based on the conceptof modular controls. The system uses a range of modularunits, each of which is programmed to control a specificitem of plant. In addition, there is a range of zonecontrollers which perform the function of a local userinterface. All the modules communicate on the sametwisted-pair bus system, using the LonTalk protocol.Installation and configuration are simple; the controlmodules are pre-programmed and are self-tuning, sovirtually all the installation that is required is hardwiring tothe plant that is to be controlled and the setting of themodule’s address. Adjustment of set points and timeschedules is done at the zone controller, which is normallymounted in the controlled space and available foradjustment by the user. The system is suitable for situationswhere the services of a controls specialist is not available forinstallation or commissioning. Systems can be builtincorporating several hundred modules and remotesupervision is possible.

4.1.6 Packaged systems

HVAC plant, such as multiple boilers or chillers, may besupplied as a packaged unit complete with factoryinstalled unitary control system (Figure 4.5). In theexample of a multiple boiler unit, the fitted controllerwould incorporate all safety cutouts, ignition procedures,boiler sequencing and the control of ancillary devices suchas flue dilution fans. Such a unit will control itselfindependently. Typically, the required flow temperature isset directly at the local controller, but it may be desirableto connect it to the main BMS for the purpose of timescheduling and transmitting a general alarm to thesupervisor. It will be necessary to check the compatibilityof the manufacturer’s controller with the main BMS. Themain features are:

— packaged plant with factory-installed unitarycontroller

— often an economical solution

— limited interface with BMS

— sometimes compatibility problems.

Systems, networks and integration 4-3

Figure 4.4 Bus system Figure 4.5 Factory-fitted unitary controller

Page 59: Building control system, aplication guide   cibse guide

4.1.7 Three-level model

The BMS of a large modern building may be arranged in ahierarchical structure. A useful concept is that ofcommunication level. The European Committee forStandardisation (CEN) divides communications within abuilding into three levels(20) (Figure 4.6):

— management level, e.g. supervisor to supervisor

— automation level, e.g. DDC controllers

— field level, e.g. sensors and actuators.

Information which is needed locally is not passedupwards to higher levels, reducing the traffic on thesystem. Communication with sensors and actuators takesplace at the field level. Intelligent controllers sit at theautomation level, as does the head end supervisor, whichhas access to all systems at this level. The managementlevel accesses information from the automation level andhas access to a wide area network, so that it can exchangemanagement information with independent systems inthe same or other buildings. The control function atmanagement level is limited. Interfaces between levels areused to:

— restrict low level traffic from passing to the levelabove

— translate from one protocol to another.

The three-layer structure has the advantage of organisingnetwork traffic efficiently, but requires the additionalcomplication of linking the three levels. A single networkcarrying all communications may be sufficient for manyapplications.

4.1.8 Utilisation of IT network

Modern organisations usually have an extensive ITsystem, which necessarily incorporates a networkcovering the building. IT networks are designed to carryvery large amounts of information and it may be possibleto use the network for the purposes of the BMS (Figure4.7). This can save infrastructure costs by the eliminationof a separate BMS network, but places increased demandson the installation to ensure that the BMS is operational intime for building commissioning. Anyone with access tothe IT system has potential access to the BMS, which couldallow staff to monitor or reset local temperatures. A BMSrequires real-time operation and there are potentialproblems over sharing the network with other IT traffic,which may involve transmission of large files with thepossibility of delays. Using the IT system for BMSpurposes:

— presupposes an extensive IT network

— reduces infrastructure cost

— high speed data transmission

— ready access to BMS by staff via workstations

— BMS may be disrupted during modifications to theIT system

— controls commissioning dependent on IT network.

The term ‘systems integration’ implies that several, or all,building services systems are brought together into a singlecooperative management system and are able tocommunicate with each other and act accordingly. Forexample, information on occupation level derived from theaccess control system can be used as an input to the

4-4 Building control systems

Figure 4.6 The three-layer model of BMS architecture

Page 60: Building control system, aplication guide   cibse guide

ventilation controller. The increasing use of standardprotocols makes communication between systems easier;gateways can be used where it is necessary to bridgebetween different protocols. The concept is also known asthe intelligent building system (IBS). All building servicesmay be controlled from a single supervisor. Systemsintegration is discussed further in 4.4.

4.2 NetworksNetwork implies that a number of devices are connectedwith each other via a communications system. A com-munications network is characterised by two essentialparts:

— physical medium, which is used to transport thesignals, e.g. wire, optical fibre, radio

— protocol, which is the set of common language rulesfor the communication signals.

Devices communicating over a segment of the physicalmedium and using the same protocol form a local areanetwork (LAN). Separate LANs, which may employ a range ofphysical media and protocols, can communicate with eachother with the help of routers, forming a wide area network(WAN). The components of a WAN may be widely separated,communicating via satellite. An internetwork is analternative name for a WAN. The manner in which networksare arranged and interconnected is termed the networktopology, discussed further below.

4.2.1 Topology

The manner in which devices and their interconnections arelaid out is termed the topology of the network. The chosentopology will affect the amount of cabling required and theflexibility of layout. It will also have an influence on thetechnical aspects of communication, such as signalling rateand reliability. Figure 4.8 illustrates the main topologies.

— Point to point. Devices are connected directly to eachother. Features are:

— Only one connection affected by a fault.

— Simultaneous transmissions are possible.

— Wiring cost is high.

— There is no automatic interconnectionbetween devices.

— Star structure. Each device is directly connected to acentral unit. Features are:

— Failure of one device does not affect others.

— Failure of central unit gives system failure.

— Cabling cost is high.

— Ring structure. Bus devices are interconnected in aring structure. Each device communicates with itsneighbours and passes messages on. It is possible toincorporate watchdog relays, which bypassindividual nodes when a device is powered down;this retains the integrity of the ring. Features are:

— Cabling cost is modest and expansion iseasy.

Systems, networks and integration 4-5

Figure 4.7 BMS and IT shared network

Page 61: Building control system, aplication guide   cibse guide

— Failure of one device leads to system failure.

Example: Arcnet.

— Bus structure. All bus devices communicate over thesame transmission path. Features are:

— Any device can communicate with any other.

— Failure of one device does not affectcommunication between other devices.

— Cabling cost is low and expansion is simple.

— Bus can only handle one message at a time.

Example: Ethernet.

— Tree structure. The tree structure is a combination ofthe structures described above. Information sent toa root is passed upwards to all devices sitting on therelevant branches, which are connected as a busstructure. The devices at the roots of the networkserve to amplify and send on messages receivedfrom other branches, or may act as gateways,converting messages from one transmissionmedium to another. Features are:

— Aids organisation of subsystems.

— No direct connection between all bus devices.

— Failure of the root leads to system failure.

— Examples: LonWorks, EIBus.

The most common topology used in the major fieldnetwork systems is a form of tree structure, whereby localbus topologies may be connected together using couplers orrouters at each root. By this means, subsystems usingdifferent communication media may be coupled togetherand operate using the same protocol.

4.2.2 Communication media

Communication between devices takes place over a localarea network (LAN). This has two aspects, the networkprotocol and the physical embodiment in thecommunications medium. Several communication mediaare available for BMS purposes (Table 4.1). Achievabletransmission rates are steadily increasing.

Coaxial cable and fibre optic cable have very high data-carrying capability and can transmit data over long

4-6 Building control systems

Figure 4.8 Network topologies

Table 4.1 Communication media

Communication medium Transmission Applicationrate (bits/s)

Power line carrier 5 k Limited data-carrying capacity. Application is primarily domestic or retrofit

Telephone line 56 k Useful for communicating between physically separated LANs. Unsuitable for real-timecontinuous control

ISDN telephone line 128 k High capacity

Unshielded twisted pair (UTP) 1 M The most common medium for voice and data communication. Four-core cable may be used fordigital signalling

Shielded twisted pair 16 M Offers higher capacity than UTP but bulkier and more expensive

Coaxial cable 10 M High capacity data transmission. Basis of the older Ethernet systems

Optical fibre 1000 M The highest data transmission capacity. Immune from EMC problems. Unsuitable for multiplelocal connections

Radio 10 k Short range licence-exempt radio provides flexible operation

Page 62: Building control system, aplication guide   cibse guide

distances. They require specialist installation and are usedin many IT systems. While a BMS can well share the use ofsuch a network, the high specification is not necessary for aBMS. The most widely used medium for a BMS bus is twisted-pair copper wire. Restricting the transmission rate to 10kbit/s makes the medium resistant to interference and thecable may share trunking with power cables; no specialistinstallation is required. Where it is difficult to run cables, itis possible to use power line carrier or radio systems. Powerlines are susceptible to much electrical noise, but thedevelopment of spread spectrum techniques has madepower line carrier systems more resistance to interferenceand good signal rates are possible.

Low power radio systems operating in the UHF band may beused without a licence for telemetry and datatransmission(1). They have the advantage of lowinfrastructure cost, low installation cost and flexibility inuse. National authorities have issued specifications forlicence-exempt radio transmission, which define themaximum permissible RF power, the frequency andbandwidth of the transmission and the number of channels.Standards differ between continental Europe and the UK.In the UK there are two relevant specifications:

— MPT1340 defines a single-channel low powersystem with a range of tens of meters. Unit costs arelow.

— MPT1329 allows up to 31-channel operation andcan achieve a range of several kilometres with goodpenetration within buildings. Data transmissionrates of up to 10 kbit/s are possible.

Table 4.2 gives the classification of data cables(2). Category 6cabling is the current standard for data cabling.

Several protocols have been developed, not all of whichhave been exploited for use in BMSs. Table 4.3 summarisessome of the bus protocols that are in use.

4.2.3 Structured cabling

The increasing use of IT in business operations hasrequired developments in the cabling infrastructure thatinterconnects the many terminal devices. Networksrequire sufficient capacity to deal with demands such asvideo conferencing; network loads of 1 Gbit/s have beenreached and are projected to increase. The consequence isthat the IT cabling in a building may rapidly becomeinadequate, with the consequent expense and disruptionof upgrading.

The concept of structured cabling, also known as universalcabling, aims to install a cabling infrastructure in abuilding or group of buildings which will meet therequirements of all potential users of the building during itslifetime, without the need for re-cabling. PCs and otherterminal devices, including BMS components, are pluggedinto local terminal outlets. The initial installation aims toprovide sufficient terminal outlets to accommodate futureinternal rearrangements and variations of work require-ments.

The cabling topology is illustrated in Figure 4.9. Threelevels of installed cabling are involved, plus a patch cable toconnect each device to the local terminal.

— Horizontal cabling. Each work area of the building,typically a floor or part floor, has a floor distributor,also known as the patch frame, mounted in thetelecommunications closet. Direct cabling,normally Category 5, runs from the floordistributor to each of the local terminal outlets inthe work area. The outlets are typically floor boxescontaining an RJ45 socket, installed at sufficientdensity to allow for future needs. The length ofhorizontal cabling is limited to 90 m.

— Building backbone cabling. Within a building, eachfloor distributor is connected to the buildingdistributor via building backbone cabling. Thiscabling is also termed building riser cabling, sinceit commonly interconnects floors of a building.

Systems, networks and integration 4-7

Table 4.2 Data cable classification

Category Description

1 Basic telephone cable for voice

2 Data cable for use to 4 Mbit/s

3 LAN cable characterised up to 16 MHz (Class C link)

4 LAN cable characterised to 20 MHz

5 LAN cable characterised up to 100 MHz (Class D link)

6 LAN cable characterised up to 250 MHz

Table 4.3 Some network protocols

Protocol Standard Comment

Ethernet ISO 8802-3 Data transmission up to 10 Mbit/s. The most common IT medium(3)

ARCNET ANSI 878.1 High performance LAN with data exchange up to 2.5 Mbit/s. Used widely in industrial applications(4)

BACnet MS/TP Master Slave/Token Passing serial communications using an EIA-485 signal. Provides adequate performance atreasonable cost

Point to point EIA 232 Serial communication between two devices. Typically used for dial-up communication using modems

LonWorks The Lon network is based on the proprietary Neuron chip and can be applied to a wide variety of physicalmedia

Batibus ISO JTC 1 SC25 Uses twisted pair at 4.8 kbit/s

TCP/IP Transmission Control Protocol/Internet Protocol. It encompasses media access, packet transport, sessioncommunications etc. TCP/IP is supported by a large number of hardware and software vendors. SeveralInternet protocols deal with aspects of TCP/IP. The most important have been collected into a three-volumeset, the DDN Protocol Handbook(5)

European Uses twisted pair at 9.6 kbit/sInstallation Bus

Page 63: Building control system, aplication guide   cibse guide

— Campus backbone cabling. Where several buildingsshare the same network, campus backbone cablingis used to connect building distributors with thecampus distributor. Fibre optic cable is commonlyused for this purpose.

— Work area cabling. Individual devices, such as PCs,printers, telephones and BMS components, areconnected to the terminal outlets via work areacabling, also known as patch cabling. Each devicewhich is to be connected to the network is providedwith a jack plug compatible with the terminaloutlets.

For BMS purposes, use of an 8-pin RJ45 plug and socket isrecommended. Thus, where a BMS system is to share astructured cabling system, it would be specified that allcontrol components, e.g. actuators, controllers, VAV boxes,would be provided with a fly lead terminated by a standardjack plug. The structured cabling system must be specifiedto provide a large number of sockets in suitable locations, inservice ducts and plant rooms, which will be adequate forpresent and future needs.

Where structured cabling is specified, the cabling system isdesigned as a complete system to incorporate all datatransmission needs. The wiring is then installed by a singlecontractor. This eliminates many problems of coordinationand commissioning and is claimed to lead to cost savings.However, any decision to incorporate the BMS with astructured cabling system should be considered carefully.Flexibility is not normally a high priority with HVAC andBMS systems, since major repositioning of plant is anunusual event and is likely to be associated with a majorrefurbishment in the building. Sharing communicationsnetworks may introduce contractual problems overinstallation, commissioning and maintenance, whichshould be resolved at an early stage. For some BMSapplications, the current-carrying capacity of the cable usedin an IT network may be inadequate; again, this problemmust be resolved in good time.

4.2.4 Standardisation

Components of a network communicate with each otherusing a common communication protocol. The com-munication medium itself may take a number of physicalforms, but is typically a low voltage twisted-pair cable.Communication normally takes the form of a message ortelegram. When required to do so, a device transmits atelegram onto the bus, containing such information as theidentification of the sending device, the information to betransmitted, e.g. a temperature value, the address of thedevice for which the message is intended and additionalinformation needed for error checking. Each devicetherefore requires a microprocessor to handle messagecoding and the transmission and reception of messages tothe bus; this must include procedures to deal with messageprioritisation and the avoidance of message collision whenseveral devices are attempting to transmit at the same time.The rules for message formation form the protocol.

Historically, manufacturers have developed their ownproprietary protocols, but there is now a strong move to theadoption of standard protocols. A major advantage of usinga BMS network with a standard operating protocol is thedegree of compatibility that may be achieved betweendifferent pieces of control equipment. Three levels ofcompatibility can be distinguished:

— Compatibility or coexistence. Devices from differentmanufacturers may use the same communicationsnetwork without interfering with each other, butcan only communicate within their own subgroupof devices.

— Interoperability. All devices on the network share thesame communications protocol and so maycommunicate with each other, e.g. one maker’slight switch will operate another’s light fitting.

— Interchangeability. Devices are completely standard-ised, both physically and operationally, so that devicesfrom different sources may be freely interchanged.

4-8 Building control systems

Figure 4.9 Topology of structuredcabling installation

Page 64: Building control system, aplication guide   cibse guide

Substantial progress has been made towards the goal ofproducing networks with interoperability. This implies thatdevices from different manufacturers which conform to therequired standard can be plugged into to the BMS networkand operate with devices from other manufacturers. Thisdevelopment has depended on the development andacceptance of the necessary protocols, which are well-defined sets of rules by which devices identify themselvesand transmit and receive messages. Several protocols havebeen developed by national and international bodies and bymanufacturers. Full interchangeability is rare. It wouldbenefit users in that more than one source of supply wouldbe available, offering the benefits of competition. However,the requirement that the devices should be operationallyidentical would hold back developments.

4.2.4.1 Standardising bodies

A well-defined protocol is essential for a bus system if it isto find wide application and allow devices from differentmanufacturers to operate together. A bus system requiresthe following properties:

— a governing association

— a sufficient range of published standard protocols

— a testing procedure

— a certification procedure.

The European Committee for Standardisation (CEN) tookon the task of defining norms for BMS protocols and startedby classifying communications within a building into threelevels (Table 4.4).

The management network exists to allow data to be collectedfor the management of facilities and energy and financialreporting. It can be used to connect complete systemstogether. The automation network operates at the level ofcontrollers and user interfaces. This is the level at whichmost BMSs operate, e.g. the connection between an intelligentoutstation and the head end supervisor. Interfaces to relatedservices such as lighting, fire or security, take place at thislevel. FND (Firm Neutral Data Transmission) is a GermanDIN standard intended for linking BMS central stations anduptake outside Germany and Switzerland is low. At theautomation net level, FIP (Field Instrumentation Protocol)is a French standard, which has not become established inbuilding services applications. The field network is the lowlevel network used to connect small devices such as unitarycontrollers, sensors and actuators. EHS (European HomeSystems) was developed with EU funding for domesticapplications; this is expected to become incorporated into anew common standard, mentioned in 4.2.5.5. The othermajor standards are considered in more detail below.

The International Organisation for Standardisation (ISO)has developed a design model which all protocoldevelopment should reference. It is called the Open

Systems Interconnection (OSI) Basic Reference Model,ISO 7498(6), and is also known as the seven-layer model(Table 4.5). The model represents an effort to make thecommunication problem manageable by breaking it downinto a series of smaller problems, each of which can then betackled independently of the others. This has been done bydefining a hierarchy of functions arranged one on top of theother in seven layers where each layer deals with one ormore of the issues. The seven-layer model is independent ofthe CEN 3 level hierarchy; each of the CEN levels containsa protocol which can be analysed in terms of the OSI model.

For example, the bottom two layers of the stack are thephysical and data link layers. According to the OSI model,these layers concern the type of physical interconnection ofcomputers, the electrical signalling, addressing, errordetection scheme, and medium access method. Theselection of these characteristics, taken together,constitutes what is commonly referred to as a local areanetwork or LAN. The next layer up is called the networklayer and describes the characteristics of protocols designedto allow multiple LANs to be connected together. Thetransport layer optimises the actions of the network leveland represents a link between the lower and higher layers.The session and presentation layers deal with wide areanetworks. The presentation layer provides for a commonlanguage for the entire network, so that devices usingdifferent protocols may communicate with each other.Finally, at the top, is the application layer which addressesthe communication requirements of specific applications,for example, building automation and control. Anapplication layer protocol defines the specific format andcontent of the messages that two or more computers, eachcooperating in a particular application, will use inconversing about their common activities.

Several bus networks are in widespread use for buildingmanagement systems. Major systems are described in thefollowing sections. The systems share many concepts,though may use different words to describe them. Thisguide uses the term device to describe a whole physicalpiece of equipment that is connected to the net; the devicecontains the necessary communications processing poweras well as the hardware necessary for it to carry out itsfunction. The term object may have slightly differentmeanings in different systems, but is normally defined interms of the software function of a component or a device.

4.2.5 Standard systems

4.2.5.1 BACnet

BACnet, an acronym for Building Automation and ControlNetwork, was developed under the aegis of the American

Systems, networks and integration 4-9

Table 4.4 Levels of communication within a building (CEN TC247,WG4)

Level Example Proposed draft standards

Management Supervisor to supervisor BACnet, FND

Automation DDC controllers BACnet, FIP, Profibus

Field Sensors, actuators LON, EIB, Batibus, EHS

Table 4.5 Open Systems Interconnection Basic Reference Model

Layer 7 Application User interface

Layer 6 Presentation Common language User

Layer 5 Session Opens and closes dialogue sessions

Layer 4 Transport Network optimisation

Layer 3 Network Data packet transport round network

Layer 2 Data link Message structure Transport

Layer 1 Physical Communication medium and signalling

Page 65: Building control system, aplication guide   cibse guide

Society of Heating, Refrigerating and Air ConditioningEngineers (ASHRAE) to provide on open systemspecifically designed for the requirements of BMSs. It is nowformally defined in ANSI/ASHRAE standard 135-1995(7).BACnet focused on defining a method for communicationsfor the functions commonly found in building automation.BACnet is administered by a standing committee and isdesigned as a high level protocol which may use a numberof transmission protocols at the field bus level. Table 4.6shows the organisation of BACnet in terms of the OSImodel; the commonly used media are in bold type.

In terms of the OSI model, therefore, BACnet is a four-layerprotocol stack consisting of an application layer protocol, anetwork layer protocol, and several data link and physicallayer protocols. BACnet’s simple network layer allowsmultiple BACnet networks to be connected in order tocreate a BACnet internetwork. This capability is most oftenused in order to allow networks employing different datalink layer technologies to be linked together throughrouting devices. For example, a large building could havemultiple programmable controllers and operatorworkstations connected by an Ethernet network, and eachprogrammable controller could be connected to low costapplication-specific controllers using a master–slave RS 485bus or other low cost bus.

BACnet was defined from the start for use with buildingservices. BACnet defines 18 standard object types, where anobject is an abstract representation of a control systemelement. Object types are defined for analogue and binaryinputs and outputs, control loops, schedules and so on,chosen to facilitate the modelling of DDC systems; furtherobjects will be added to deal with other buildingmanagement functions such as fire and security. Eachobject consists of a set of properties, where each propertycontains a value of some specified data. All objects have theproperties of an object identifier, and object name and anobject type. In addition, there are other properties such aspresent value, status and so on. BACnet carries outoperations by invoking a set of standard services whichgovern the rules by which messages are constructed andtasks performed.

4.2.5.2 LonWorks

LonWorks is the general name for field bus systems basedon the LonTalk protocol, which is physically implementedin the Neuron chip. This is a programmable integratedcircuit developed to handle network and input/outputfunctions. The aim of LonWorks is the establishment ofinteroperable systems, whereby devices using the LonTalk

protocol, from different manufacturers, can freelycommunicate with each other over the LonWorks network.To this end, an independent association, the LonMarkInteroperability Association, has been set up, which isresponsible for establishing standard specifications for thefunctionality of devices which are to be connected to thenetwork. In the language of LonWorks, a device such as asensor, controller or actuator has an abstract representationas an object. Each object has a strictly defined functionalprofile, which sets out the inputs and outputs that thedevice exchanges with the rest of the network. As well asissuing functional profiles, the LonMark InteroperabilityAssociation offers means for conformance testing ofproducts. Products conforming to the guidelines are issuedwith a LonMark logo as a warranty for interoperability.

LonWorks is capable of employing several differentcommunication media. It is possible to build a fullydistributed HVAC control system in which the componentsof a control loop exist as physically separate objects, fromdifferent manufacturers, communicating with each otherover the building’s field bus network.

Figure 4.10 illustrates the components of a LonWorksnetwork. Individual devices are connected to the bus atnodes. The term device is used to imply a physical devicesuch as a controller or sensor. The protocol treats thesystem as a collection of objects. Objects are well-definedbuilding blocks of the system, with a defined set ofproperties. For instance, a sensor object has propertieswhich identify its type, its individual identity and itsoutput, e.g. temperature, together with several otheroptional properties. A physical device, such as a controller,may consist of several objects. Each device must contain theprocessing power necessary for it to communicateaccording to the protocol. Each device must contain atransceiver, which sits between the Neuron chip and thebus. Transceivers are available for several media, includingtwisted pair, power line carrier, wireless and infra red.Figure 4.11 illustrates the components of a temperaturesensor. The A/D converter conditions the temperaturesignal from the temperature sensor into a form that can berecognised by the processor. The function of the processoris to generate a signal which will follow the strict protocol ofthe network, identifying the sensor and transmitting atemperature value that can be accessed anywhere else on thenetwork. This signal is then converted to a form appro-priate to the local communication medium. Depending onthe application, the device may be powered from thenetwork or from an external supply.

The nature of the system is such that each object performs awell-defined function. For instance, a sensor, controller andactuator driver may be physically separate devices andattached to the bus at different points, but bound togetherby addressable software and operating as a single controller.The various protocols define a large number of objectswhich together cover most requirements of a BMS. It is notnecessary that the operation of a device be transparent tothe network and in many cases it is more practical to have acomplex device, such as a VAV controller, built in aconventional way with hardwired sensors and actuators.Such a unitary device may be connected to the net using alimited protocol which allows the supervisor to know theoperational status of the controller and alter the set point ifnecessary; however, the supervisor has no knowledge of theinner workings of the controller.

4-10 Building control systems

Table 4.6 OSI model of BACnet protocols

Layer Examples

Application BACnet applicationOSI 7

Simple BACnet Network LayernetworkOSI 3

Data link ISO 8802-2 Type 1 MS/TP Dial-up LONOSI 2

Physical Ethernet Arcnet RS 485 RS 232 LONOSI 1

Layers 4–6 refer to wide area networks. Layers 1 and 2 constitute the LAN.

Page 66: Building control system, aplication guide   cibse guide

Different communication media may be used within thesame network by the application of routers. Routers alsoserve the function of partitioning sections of the networkfrom traffic in another area, so that information which isonly required within one area is confined to that area andnot transmitted over the entire network. In addition,interfaces are available which allow a LonWorksapplication to run on a non-Neuron host. Thus a PC canbecome a node on the network. The use of an interoperablenetwork for BMS allows information to be exchangedbetween subsystems that might otherwise present problemsof intercommunication. For instance, an IR presencedetector could send output to lighting, security and HVACsubsystems over the network.

The application of fully interoperable LonWorks systems islimited by the range of functional profiles which have been

defined and their incorporation into products. Even whereprofiles have been defined, there are situations where it maybe more practical to use a conventional intelligentcontroller hardwired into the unit which it controls; this islikely to be the case for factory-fitted controllers. It ispossible to design an interface with a LonWorks fieldnetwork so that the controller may communicate with therest of the system, allowing monitoring of performance andthe resetting of parameters at the head end. This representsa compromise with full interoperability, but may often be apractical solution.

4.2.5.3 EIBus

EIBus is a European standard administered by the Euro-pean Installation Bus Association, with its headquarters inBrussels. The EIBA has members drawn from the majormanufacturers of electrical installation equipment inEurope and has as its aim of guiding development of ahighly reliable bus system for BMS which will be availableall over Europe. The EIBA is independent of individualcompanies; it sets out the technical directives for the EIBussystem and lays down quality requirements. Members whopass its tests may use the EIB mark. The EIBus has beendeveloped as a simple and reliable system which may beinstalled without special skills by an electrical fitter. Thebus itself consists of an unshielded twisted pair, which isnormally installed adjacent to the power supply cables,sharing the same trunking. Devices sitting on the buscommunicate by sending event-driven telegrams. Arelatively low information rate of 9.6 kbit/s is used. The

Systems, networks and integration 4-11

Figure 4.10 Components of aLonWorks network

Transceiver

Sensor

Neuronchip Memory

Network

Figure 4.11 Components of a LonWorks temperature sensor

Page 67: Building control system, aplication guide   cibse guide

choice of frequency makes installation less critical. Thereare no restrictions on the layout; branching and looping arepermitted.

Each device on the system comprises a bus coupling unit(BCU) and an application unit (AU). The AU may be someform of sensor or actuator. In the case of a sensor, the AUsends information to the BCU, which encodes it andtransmits a message onto the bus. In the case of an actuator,the BCU receives a message destined for the AU, decodes itand instructs the AU on the action to perform. The BCU isprogrammed during the set-up phase of the installation.This is done using a PC plugged into the system using EIBTool Software.

The smallest EIBus system (Figure 4.12) consists of a busline, some bus devices and a power supply, which provides 28V DC to the line. Up to 64 bus devices may be connected to asingle bus line, which has a maximum length of 1000 m. Upto 12 lines may be interconnected using line couplers to forman area. If further expansion is required, up to 15 areas may beconnected to a backbone line. Each device is characterised byits physical address of area, line and device number.

Line couplers act to control traffic. When setting up thesystem, devices are bound together by giving the source andtarget address. The coupler will pass line-crossing tele-grams but all other messages are confined within the lineboundary, thus reducing the amount of traffic on thenetwork. A PC may be connected to the bus by a gateway, toprovide head end supervision. A PC is also used during thecommissioning period with appropriate software.

4.2.5.4 Batibus

Batibus originated in France as an open field bus systemdesigned specifically for use in buildings. The protocol isdefined in French and international standards andadministered by the Batibus Club International, based inFrance. It is designed to be an interoperable system andproduct certification is carried out by an independent

company. Batibus finds its main applications in small tomedium buildings and has been incorporated in productsfrom several manufacturers.

The communication medium is an unshielded twisted pair,operating at 4.8 kbit/s; it may be installed next to powercables if a shielded insulated twisted pair is used. The cablemay be installed in a free topology and carries the powersupply for the devices. Devices are connected to the bus viaa communications module. The address of each device is setphysically at the device by setting a drum wheel or dipswitches; in some cases the device carries a display andkeypad for the purpose.

Each network can accommodate 240 separate addresses.The actual number of devices may be greater, since devicesof the same type which are required to operate together mayshare the same address. Depending on the cable size used,the total network length may extend over 2 km. The buscable operates at 15 V and network devices may be powereddirectly from the bus up to a total consumption of 150 mA,typically 75 devices. Up to 1000 externally powered devicesmay be connected to the bus.

4.2.5.5 HBES

At the time of writing, the EIB Association, Batibus ClubInternational and the European Home Systems Associationhave announced a programme of convergence to produce acommon standard to be known as Home and BuildingElectronic Systems (HBES).

4.3 Electromagneticcompatibility (EMC)

The extensive wiring of a control system makes itsusceptible to interference from the many sources ofelectrical noise present in and around buildings. The effects

4-12 Building control systems

Figure 4.12 Topology of EIBus

Page 68: Building control system, aplication guide   cibse guide

of interference can range from minor errors in atemperature reading to complete system failure andequipment damage. Since the control system operatescontinuously in real time, it is vulnerable to interference. Amalfunction that may be tolerable if it involves a temporarydeviation in HVAC performance, becomes intolerable if itrepresents a threat to safety or security. The requirementthat a system has a satisfactory EMC standard may bespecified using a standard clause from Section A64 of theNational Engineering Specification(8). Two alternatives aregiven: Clause 7080 states the general requirements ofcompatibility and is recommended for general use; where itis essential to identify specific EMC standards to be met,Clause 7090 may be used.

The chance that a BMS will suffer from interference dependson:

— the levels of conducted and radiated electro-magnetic disturbances in the building

— the immunity that has been designed into theindividual components that make up the BMS

— the way that the BMS, as a networked system ofcontrollers, has been installed.

Ambient electromagnetic noise levels can be high inmodern commercial buildings with their high densities ofelectrical and electronic equipment, and in HVAC plantrooms containing heavy electrical plant. Industrialprocesses can produce substantial interference and theremay be sources of noise external to the building. As far aspossible, these problems should be tackled at source at anearly stage. The prime responsibility of the controlsspecialist is to select equipment that complies with theimmunity and emissions limits in the EMC productstandards and to install them in accordance with goodpractice. The BMS installation should then have satisfactoryreliability and comply with the UK regulations. Thefollowing draws on BRE Digest 424(9), which should bereferred to for more detailed advice.

4.3.1 The ElectromagneticCompatibility Directive

The EMC Directive(10) sets out the two requirements, thatequipment should neither suffer from, nor cause, electricalinterference. Compliant equipment carries a CE mark andit is now a criminal offence to sell or bring into service non-compliant equipment. It should therefore be possible toassume that control products meet the essentialrequirements of the EMC Directive. At the moment therequirements are generic; product-specific standards forbuilding control products are in preparation. Mostproducts are self-certified by the manufacturer, based ontests in their own or third-party test house. For a bespokeproduct, such as a control panel, where the expense oftesting would not be justified, it is possible to meet theregulations by the preparation of a technical constructionfile, where an approved third party certifies that theconstruction complies with the objectives of the Directive.

4.3.2 Installation

The use of approved components is not sufficient toguarantee freedom from interference. The EMC of an

installation depends also on the degree of coupling to noisesources; BMS, with their extensive signal cabling, areespecially vulnerable. There is a balance to be madebetween the costs of providing protection by using highimmunity components or by using lower immunityproducts which may require special installation measuresto prevent interference.

4.3.2.1 Location

EMC should be a major consideration, along with ease ofaccess, in the location of controllers and other componentsof a control system. While placing control componentsclose to the equipment being controlled has advantages, itmay expose them to high levels of disturbance. Controllersand cabling should be placed as far away as practicable fromsources of electrical noise; these include switched loadssuch as relays and contactors, lifts, air-handling units,chillers and variable-speed drives. Transformers, busbarsand lift control equipment can be strong sources of 50 Hzmagnetic fields, which can cause disturbance to computerdisplay screens; a separation of up to 5 m may be necessaryto avoid wobbling images.

There may be sources of interference external to thebuilding. It is advisable to carry out an EMC survey inadvance of construction if the planned site is near to radars,radio transmitters, electrified railway lines or heavyindustrial plant. It may be necessary to install specialmains-conditioning units to provide clean power to theBMS. In extreme situations, it is possible to incorporatearchitectural screening to screen rooms or even the entirebuilding against interference(11).

4.3.2.2 Power supply and earthing

Power supplies in HVAC plant rooms should normally beadequate for BMS controllers that comply with the relevantimmunity standards. However, power supplies may sufferfrom a wide range of disturbances and the risk ofinterference will be minimised if supplies from electricallynoisy circuits are avoided. If practicable, field controllersshould be supplied via a separate ring or spur circuit fromthe local distribution board.

The earthing of electronic equipment and signal cablingcan introduce problems. Earth systems in a buildingprovide the functions of:

— safety

— lightning protection

— EMC.

Safety earthing provides protection against electric shockby connecting exposed metalwork to the earth lead inmains wiring. Lightning protection for a structure isprovided by lightning conductors mounted at the top of thestructure, connected by down leads to earth electrodes.Transients induced in external cables, lightningconductors and other metalwork can propagate throughouta building; remote strikes to power and data cables cangenerate transients that propagate by conduction down thecable before entering the building. Lightning protection ofbuildings is covered by BS 6651 and is discussed byJohansson(12). With a properly designed lightningprotection system, the risk to components conforming tothe EMC Directive should be low. BMS cables running

Systems, networks and integration 4-13

Page 69: Building control system, aplication guide   cibse guide

outside the building should be buried; screened twisted-pair cable in metal conduit may be used for short distances.To improve reliability, surge protection devices may beinstalled where external cables enter the building. Foradvice on earthing practice, see Earthing Practice(13).

4.3.2.3 Cabling

The cabling that connects components of a control systemis susceptible to interference from adjacent power cablesand from radio frequency interference. Techniques foravoiding interference include the use of screened cables,care with routing cables, segregation of power and signalcables and correct earthing practices.

Many types of screened cable are available. A compre-hensive treatment of data and other types of cabling is givenin Electric Cables Handbook(14). Table 4.7 gives an indicationof the performance of different types of cable in attenuatingmagnetic and electric fields. It is important to rememberthat screening with a conductive material, such as copper, iseffective at attenuating high frequency electromagneticfields, but has little effect on power frequency magneticfields. To attenuate 50 Hz magnetic fields it is necessary toshield with a magnetic material such as steel, or to usetwisted-pair cables.

In practice, a low cost, foil-screened twisted pair cable issuitable for most BMS applications for frequencies below 1MHz. For IT and data communication circuits operating atfrequencies above 1 MHz, such as Ethernet, the cable typewill normally be specified by the equipment supplier. Itmay be coaxial cable or suitable twisted pair. The use ofcoaxial cable is not recommended for low frequency use asnoise induced in the screen will be added to the signal.

BMS signal cables should be kept as far away as practicablefrom sources of interference. In particular, untwisted cablesshould not be exposed to magnetic fields from high currentequipment such as transformers. The IEE WiringRegulations permit signal and power cables to share the sameconduit, providing the signal cable has adequate insulation.The regulations are written from the point of view ofelectrical safety, and do not concern interference. Sharing aconduit or trunking makes for economical installation andsome field bus systems, e.g. EIBus, are designed so that thiswill not introduce any EMC problems. However, in general itis recommended that signal cables without screening shouldbe separated from power cables by a minimum distance of150 mm. Ideally signal and power cables should be routed in

separate trays or trunking, and cross at right angles wherethey meet. Table 4.8 presents general recommendations fordifferent types of screened signal and power cables;manufacturers’ recommendations should be followed whereappropriate. The control system specification should laydown what standard of installation is required.

The earthing of circuits and cable screens can presentproblems. Correct earthing depends on the type of cable,the signal frequency and whether the signal is single endedor differential. In a differential circuit, neither of the pair ofsignal wires is at earth potential; induced potentials frominterference are induced onto both wires, and the input of adifferential amplifier is able to reject common-modedisturbances. Most BMS analogue and digital circuits arelow frequency and single ended, with the ground line atearth potential. For such cables, both the ground line andthe screen of the cable should be connected together andearthed at the controller end of the cable only. Earthing thescreen at both ends of the cable creates an earth loop, whichcan cause large 50 Hz currents to be induced, which in turncan induce unwanted noise in the signal cable. Somecommunication circuits employ differential amplifiers.Neither signal lead is earthed and the screen should beconnected to earth at one end only. Cabling for a standardsystem should follow manufacturer’s advice. Highfrequency cables above 1 MHz behave rather differentlyand the outer screen is earthed at both ends and perhaps atseveral points along its length.

4.3.2.4 Control panels

Control panels must comply with the EMC Directive. Thismay be achieved by constructing the panel entirely fromCE-marked components, in which case each componentmust be installed in accordance with instructions suppliedwith the component. Alternatively, the complete panel maybe tested as a unit for compliance with the relevantstandards, in which case the panel itself will have a CEmark. Unauthorised modifications made after installationcould invalidate the CE mark.

BRE Digest 424(9) summarises good practice in the design ofcontrol panels, including the following points:

— Sources of broadband electrical noise, such ascontactor solenoid coils and switch contacts forexternal inductive loads, may need suppressors.

— Metal cabinets with low impedance bondingbetween separate parts provide good screeningagainst radiated electromagnetic disturbances.Mild steel cabinets give good protection, whilemetal-coated plastic enclosures may be inadequateagainst low frequency magnetic fields. Conductivegaskets may be required where a high level ofinterference is expected, such as near a transmitteror radar installation.

4-14 Building control systems

Table 4.7 Screening cables against 50 Hz magnetic and radio frequency(RF) electromagnetic fields

Code Cable type Noise reduction50 Hz RF

Plain Plain, no screen, no twists None NonePlain in steel conduit or trunking Good GoodPlain with braid or metal tape screen None Good

UTP Plain two-core unscreened twisted pair Good None

STP Braid-screened twisted pair Good Good

FTP Foil-screened twisted pair Good Good

MICC Mineral-insulated copper clad None GoodTwisted-pair MICC Good Good

SWA Steel wire armoured Good Good

Table 4.8 Minimum separation (mm) between BMS signal cables andpower cables(15)

Signal cable Power cable

Twin and earth SWA MICC

Plain untwisted 150 125 Touching

UTP 75 50 Touching

All screened Touching Touching Touching

Page 70: Building control system, aplication guide   cibse guide

— Use a Form 4 control panel cabinet, which isdivided into cubicles with each motor drive in aseparate cubicle.

— Interfacing relays may be mounted in either thedrive or controller section. If in the controllersection, they should be in a separate area from thecontroller or separated by a metal screen.

— Cables entering the panel should preferably be ledto a termination strip mounted on the cabinet,rather than to the controller itself. Connectionswithin the cabinet should be routed whereverpossible along a metal surface.

— Variable-speed motor drives should be carefullyinstalled in accordance with the manufacturer’sinstructions, which may require the use of adesignated VSD enclosure and screened powercables.

4.4 Systems integrationA modern building incorporates a range of buildingservices other than HVAC. Such systems have in the pastbeen developed by different manufacturers and inoperation they worked completely independently of eachother. There are great potential benefits if the differentsystems can be brought together so that they cancommunicate with each other and work cooperatively. Theterm systems integration is used to describe the bringingtogether of equipment from different sources and thecombined working of different building services systems,bringing about some or all of the following benefits:

— Savings in installation costs. The integrated systemsmay share the same physical network forcommunication.

— Greater choice for the designer. Devices from differentmanufacturers use the same protocols and can beused with the same network.

— Simpler building operation. All building servicessystems can be supervised from the same centralinterface. Where appropriate, systems can beaccessed from other points in the network.

— Integrated operation. Where fully implemented,systems integration allows systems to interact,giving intelligent operation of the whole building.

From the point of view of the user, a major benefit ofsystems integration is that the entire BMS may be operatedfrom a single head end PC, so that operating staff haveonly to learn one set of operating software. This benefitcan be achieved by the use of a neutral head end; seebelow.

4.4.1 Implementation

Systems integration can be implemented at different levels:

— Within a system. The term systems integration issometimes used to describe the ability of devicesfrom different manufacturers to use the samecommunications network. This is better describedas interoperability rather than as full systemsintegration.

— At the head end supervisor. The separate systems actindependently of each other, but are all brought to acommon supervisor, known as a neutral head end,which incorporates gateways allowing it tocommunicate with all the systems. Thus all systemsmay be controlled using a common interface with aconsistent look and feel. Information from thedifferent systems may be combined into reportsand operating schedules may be set in common. Itdiffers from full integration in that there is nodirect communication between different systems; ifdata is to be passed from one system to another, ithas to be sent via the supervisor.

— Full integration. Information is exchanged betweenall systems, which are programmed to respondappropriately. This produces the intelligentbuilding.

A modern building will have many networked systemsrunning in parallel:

— IT network

— telephone network, paging and fax

— security and access control

— fire and emergency systems

— closed circuit television (CCTV)

— lifts

— lighting

— HVAC

— energy management.

It is possible for all systems to share a common IT networkfor communication with evident savings in cabling costs;the practical considerations are dealt with further in 4.1.8.Intelligent building operation comes when the differentsystems are able to communicate with each other directlyand take appropriate control decisions. Some examples willmake this clear (Table 4.9).

The availability of comprehensive information allowspowerful reporting applications to be provided. Energymetering may be combined with temperature andoccupancy information for M&T analysis, as well asproviding the information for tenant utility billing. Runtime or fault data may be fed to a maintenance schedulingprogram, which will provide the facilities manager withnotice of required actions.

Systems, networks and integration 4-15

Table 4.9 Examples of integration between systems

Integrated systems Features

Access and HVAC Access control system informs the HVAC systemof the number of occupants in an auditorium,which adjusts ventilation rate accordingly

Security and CCTV If a visitor is denied access, CCTV and PA systemsare activated, allowing the supervisor to see andspeak to the person and take appropriate action

Energy management The energy metering system reports thatand HVAC maximum demand limit may be exceeded, so that

the HVAC controls may shed load

Lighting and security Occupancy detectors in the lighting controlsystem inform the security system of the positionof occupants during out-of-hours working

Page 71: Building control system, aplication guide   cibse guide

4.4.2 Problems with integration

A fully integrated building management system offersconsiderable advantages to the building user. However,there are difficulties in achieving this, which may beclassified as technical and contractual.

4.4.2.1 Technical

The technical difficulties are real, but being overcome. Atthe field level, interoperability requires that all devicesconform to the protocol standard being used. An example isLonWorks set of definitions of Standard Network VariableTypes, which defines the protocol for devices ranging fromtemperature sensor to VAV controller. In situations wherethe required device either does not match the standard, orthe standard has not yet been defined, it will be necessary toprovide a customised solution, both for the device inquestion and any other devices on the network that need toreceive the message.

Network technicalities are discussed elsewhere, but theremay be problems with widely different systems sharing thesame communications medium. Most building servicesoperate in real time, sending relatively small amounts ofinformation at frequent intervals. The building user’s ITsystem, however, is designed for the needs of the businessand is likely to transmit very large files at irregularintervals. There are difficulties in ensuring that all systemsachieve their required traffic access. This situation can beimproved by confining control traffic to a segment of thenetwork, or sub-LAN, by the use of a bridge or router toconnect it to the rest of the internetwork. Local traffic isconfined to the segment and only information which isdestined elsewhere is allowed out via the bridge.

4.4.2.2 Fire protection system (FPS)

While at first sight the fire alarm system would seem to bean ideal candidate for integration, there are a number ofobstacles to allowing the fire system to share the samenetwork as other building services. Fire protection requiresthe monitoring of fire and smoke detectors throughout thebuilding, the transmission of information to and from thefire alarm system, and the initiation of appropriate controlactions.

Integration of the FPSs and BMSs for monitoring purposes isfairly straightforward. Autonomous subsystems, e.g. fire,security and BMSs, are linked together at the managementlevel: see Figure 4.6. Each of the systems is capable ofoperation on its own. The fire detection system is completeand contains all the fire alarm components such as firepanels. The fire detection system can pass informationupwards to the central supervisor, e.g. alarm annunciationsand associated display of fire locations. The centralsupervisor may or may not be able to pass commands to thefire alarm system. If so, the commands would be for non-critical functions, which would not affect operation in anemergency. Many parts of the fire alarm network must becapable of prolonged operation during a fire, which inpractice means wiring in MICC (mineral-insulated copper-sheathed cable). MICC is not suitable for general purpose datacabling, on account of its expense and limited bandwidth.

In the event of a fire being raised, the BMS is required to takeappropriate actions, and the control strategy for each plant

should contain settings for a fire alarm mode (see 5.1.5). Indiscussion with the Building Control and Fire Officers, thefunctions may be divided into primary or supplementarysafety operations. Primary, safety-critical operations arenormally controlled directly from the FPS, leaving thesupplementary operations to be controlled via the BMS. Fireand smoke control dampers are generally classed as safety-critical and are not part of the BMS.

Code of Practice BS 7807(16) sets requirements for design,installation and servicing of integrated fire detectionsystems. It does in principle allow a considerable degree ofintegration between fire and other systems, providing therequirements of BS 5389 are met(17). In practice, the limitingfactor for integrating systems is the high cost of suitablecabling. Any integrated system requires the approval of theBuilding Control Officer and the Fire Prevention Officer,with the likely involvement of the building insurers. Whereit is desired to achieve the flexibility and sophistication of anintegrated fire detection system, the potential difficulties ofobtaining approval and any possible contractual problemsshould be tackled at the earliest possible stage. The generalof fire engineering and the provision of safety systems iscovered by CIBSE Guide E(18).

4.4.2.3 Contractual

Systems integration requires the bringing together ofequipment and systems which have in the past beenhandled as independent contracts. Where an integratednetwork is planned care must be taken to ensure that clearlines of responsibility are laid down. It may be that a singlecompany, possibly a systems integrator or one of thesuppliers, should be responsible for providing thecommunications network and coordinating all othercompanies that are to use it. Not only must there be clearresponsibility for design, installation and commissioning,but there must be a responsibility that extends throughoutthe operating life of the integrated system. Some standardsrequire a central database to hold all information on thenetwork topology and linking software. There must be clearownership of the database and arrangements for its upkeep.

There are technical advantages to be gained by theintegration of security systems with the BMS; for instance thepresence detectors used for lighting control can feedinformation to the security system. Such integration maycontravene security standards and not be acceptable to theinsurance company involved. Potential conflicts ofresponsibility may be avoided as far as possible by creatingsub-networks for primary systems so that each can be fullyinstalled and tested for independent functionality beforeadding the interoperable functions. Any problemsoccurring on integration will overlap two or more networksand be the responsibility of the systems integrator to resolve.

4.4.3 Integration with IT systems

Systems integration moves the BMS closer to the IT system.The term information technology is used to cover a numberof meanings. The CIBSE Applications Manual InformationTechnology and Buildings(19) classifies information systemsas belonging to three generic areas:

— user information systems: voice, text, image anddata networks used by the occupants of the buildingfor business purposes

4-16 Building control systems

Page 72: Building control system, aplication guide   cibse guide

— building information systems: for the control andsupervision of building management, energy, fireand security systems

— miscellaneous information systems: public address,closed circuit TV, paging and signage, which spanor fall between the first two categories.

The spread of IT types from user IT to building informationsystems is illustrated in Figure 4.13. The more fullyintegrated the building systems, the greater the interactionbetween types, e.g. the telephone network may by used toallow building occupants to change temperature set points,or the paging system employed to give an automatic calloutto a maintenance engineer in the event of a malfunction.

4.5 User interfaceModern building management systems are controlled bymeans of software operations. Control is no longer by knobsand switches, hardwired to the device to be operated. Theuse of computers as central supervisors gives the designeralmost total freedom to design the operator interface. Theability to control and monitor every aspect of the building’soperation has in turn increased the amount of informationto be handled by the supervisor with a correspondingincrease in complexity. Since a building service installationwill be operated by a range of users with disparateresponsibilities, qualifications and experience, it is vital todesign operator controls which can be used at theappropriate level by a wide range of users.

4.5.1 Levels of operation

Interaction with the BMS may take place at all levels of thesystem and at each level there may be differentrequirements for different classes of operator (Table 4.10).Large systems contain all levels of operation. Managementlevel activities are primarily information gathering anddata analysis, without active control of the system. Themanagement level computer can communicate withseveral remote sites or even countries. In many system,the management and operations level functions arehoused within the same computer; some supervisoryprograms will carry out both management and controlfunctions.

4.5.2 Hardware

4.5.2.1 Zone level: stand-alone controllers

Small HVAC systems may operate without a BMS, using anumber of dedicated controllers which are designed toperform a particular function. Each controller is hardwiredto the relevant plant and does not communicate with othercontrollers. Examples are compensators, optimisers andthree-term temperature controllers. Such controllers aresmall in size and incorporate their own user interface.Typically, this consists of a liquid crystal display plus akeypad or a number of multifunction knobs and buttons.They are capable of sophisticated control functions andrequire careful setting up by a trained operator. It may bepossible to disable the set-up functions, leaving the mainset point, e.g. room temperature, available for change byunskilled staff. Alternatively, the setting knob may bemounted remotely from the controller in the occupiedspace, with the controller itself in a protected space such asthe plant room.

The limited size of the display puts great demands on theergonomic design of the interface. Much use is made ofsymbols and menus. However, it is rarely possible to makethe full range of user adjustments self-explanatory. It isadvantageous if abbreviated instructions be kept with thecontroller behind a drop-down cover or elsewhere. It isessential that the instruction book is kept in a place where itwill be found when required at a later date.

4.5.2.2 Operations level: plug-in keypad

A simple keypad may be plugged into a BMS outstation toreview point values, receive alarms and provide someparameter adjustment. The keypads have a small LCDdisplay and a limited number of keys. The device may bepermanently mounted on an outstation or be used as aportable readout. Alarms may be directed to the keypad,which contains a built-in buzzer. Some types of keypad maybe mounted on a motor control panel and be used to viewdata and make changes to parameters for all the controlsmounted within the panel.

Systems, networks and integration 4-17

Table 4.10 User interaction with BMS

Level Operator Function

Management level Facilities manager ReportingSystem administrator Energy M&T

Off-line data analysis

Operations level Non-technical personnel Response to alarm central supervisor (security, caretaker) messages and instructions

System operator Rescheduling, parameter adjustment, monitoring

Specialist engineer Reprogramming, fault finding, expansion

Service tools Specialist engineer Monitoring, reconfiguration, fault finding

System level Non-technical personnel Some local control ofoutstation conditions

Specialist engineer Parameter adjustment, reprogramming, fault finding

Zone level Occupants Set point adjustmentlocal control

Figure 4.13 The range of information types found in a modern building

Page 73: Building control system, aplication guide   cibse guide

4.5.2.3 Systems level: touchscreen

A touchscreen can sit on the network, providing reducedinput and output capacity compared with the mainsupervisor. However, subject to access control, it can haveaccess to the entire network. The user communicates withthe display by touching the screen display, which mayconsist of pictures, graphs, knobs, dials and text. The screentakes up less space than a PC. It has no movable parts and issuitable for wall or panel mounting. A typical use is toprovide limited control of local plant operation by aminimally trained user. The display screens can bespecially designed for the intended function.

4.5.2.4 Operations level: supervisor

The central supervisor, also known as the head endsupervisor, commonly consists of a PC together with aprinter. By the use of appropriate gateways and interfaces,the PC can communicate with control and bus systemsemploying a variety of communications protocols, and ifdesired, with other building management systems such asfire, lighting, security etc. The head end supervisor is theprime interface between the system operator and the BMS.Where the BMS operates over a LAN or bus system, it willnormally be possible to access the system from anywhere onthe network using a PC and appropriate software. The use ofa portable supervisor is of great value when performingcommissioning or maintenance. Use is of course dependenton access control.

4.5.3 Users

The enormous power and flexibility of the PC-basedsupervisor means that the software must be carefullychosen to allow appropriate operation by different levels ofuser. There are three levels of operation:

— Operation by unskilled personnel. When the buildingis unoccupied, or the operator is absent, unskilledpersonnel such as a caretaker or security guard canmonitor critical alarms from the BMS. Thesupervisor should display or forward only alarmsrequiring action and also give instructions to allowthe action to be carried out.

— Operation by trained personnel. In a large system, thesupervisor will be operated by a person trained inits use, but who will not necessarily be a buildingservices engineer. The operator’s responsibilitiesinclude monitoring the plant for satisfactoryoperation, resetting parameters or time schedules asrequired. All alarms must be responded to; a well-designed supervisor requires confirmation of theaction taken before allowing an alarm to be turnedoff.

— Operation by the controls engineer. The supervisor mayincorporate software which allows reconfiguring ofthe control system, and uploading and down-loading of software to outstations.

4.5.4 Software

Several software packages for supervisors are available andmay be expected to include some or all of the followingfeatures:

— Graphics. Graphic displays of plant operationcontain diagrams of the plant with live point valuesdisplayed, giving on-screen displays of tem-peratures, flows etc. plus the operating state ofitems of plant. Set points may be adjusted directlyand plant items switched on and off.

— Data logging. Point values, both analogue anddigital, are routinely recorded in the systemdatabase. Data may be displayed graphically, eitheras a real-time trend graph of the present situation ora review of historical data.

— Alarms. Certain points may be assigned alarm levelsand alarm priorities. When an alarm event occurs,the supervisor software takes appropriate action,typically:

— displaying an alarm message on screen

— sending an alarm message to another nodeon the BMS

— relaying an alarm message via email, pageror fax

— updating the alarm log, which includesacknowledgement and action taken.

— Reports. Reports are predefined summaries ofhistorical data, which may be printed automaticallyor on demand. They may also be transferred to aspreadsheet for off-line analysis.

— Time scheduling. Time schedules determine theoperation of building services on working days,weekends, holidays and maintenance periods. Thesupervisor software incorporates a calendarfunction which allows advance time scheduling in auser friendly manner.

— Security. Access to the supervisor must be controlledto prevent unauthorised use. Each user is assigned apassword which has an access level associated withit. Typical access levels are:

(1) Alarms only. Allows viewing and printing ofalarms.

(2) View. Allows viewing of all graphics.

(3) Read/write. As view, but allows changing setpoints and time schedules.

(4) Supervisor. As read/write, plus changingsystem parameters and passwords.

For additional security, all accesses to the supervisor arelogged. In addition, the supervisor may contain additionalsoftware relevant to the operation of the BMS, such asmonitoring and targeting or maintenance management. Asuitable drawing package will allow the production of thesystem graphics.

4.6 SummaryConventional controllers are hardwired to the systems theycontrol and do not communicate with each other. They canprovide satisfactory and economical control of smallbuildings. The modern programmable controller contains amicroprocessor and performs local control of a piece of

4-18 Building control systems

Page 74: Building control system, aplication guide   cibse guide

plant or subsystem and exchanges information with the restof the building management system. The programmablecontroller is the workhorse of most BMSs and can beconfigured to perform a wide range of control functions.Packaged plant is usually supplied with its own hardwireddedicated controller, which has limited communicationswith the main BMS.

Communications within a BMS take place at three levels: themanagement level for supervisors, automation level forcontrollers and field level for sensors and actuators. Localarea networks may be organised in a variety of topologies.The most common is the tree structure. Devices on thesame branch communicate freely with each other over afield bus. Gateways at the root of the branch filter messagesand translate to a different protocol or communicationsmedium as required. A BMS network may therefore includedifferent communications media and protocols.

The most common medium used by a BMS is the unshieldedtwisted pair, which is cheap and simple to install. Wherethe BMS shares a network with IT and high datatransmission rates are required, coaxial cable is used.Telephone lines or radio links may be used to linkphysically separated parts of a wide area network.

The use of standard communications protocols allowsdevices from different manufacturers to communicate witheach other, and the major protocols are described,including BACnet and LonTalk. The use of extensivenetworks risks problems of electromagnetic compatibility.Components and installation practices should meet therequirements of the EMC Directive to prevent problemsarising.

The philosophy of systems integration brings buildingservices systems together, so that such systems as HVAC,lifts, lighting, security may share information and becontrolled from a common supervisor. This leads toimproved efficiency of operation, but integration requirescareful planning to ensure clear lines of responsibility.

The complexity of a large system places demands on theuser interface design. The supervisor should be arrangedso that access is possible at several controlled levels,from simple supervision to fault location and recon-figuration.

References1 Simms R How far will it go? Electronics World (September)

780–781 (1998)

2 BS EN 50173 Information technology — generic cablingsystems (London: Stationery Office) (1996)

3 ISO/IEC 8802-3 Information processing systems — Local areanetworks — Part 3 Carrier sense multiple access with collisiondetection (CSMA/CD) access method and physical layer specifications(Geneva: ISO) (1993)

4 ARCNET local area network standard ANSI/ATA 878.1 (NewYork: American National Standards Institute) (1992)

5 DDN protocol handbook (Menlo Park CA: SRI International)(1989)

6 ISO 7498 Information processing systems. Open systemsinterconnection Basic reference model (Geneva: ISO) (1984)

7 BACnet — A data communication protocol for building automationand control networks ANSI/ASHRAE 135-1995 (Atlanta, GA:American Society of Heating, Refrigeration and AirConditioning Engineers) (1995)

8 NES National engineering specification (London: CharteredInstitution of Building Services Engineers) (1997)

9 Installing BMS to meet electromagnetic compatibility requirementsBRE Digest 424 (Watford: Building Research Establishment)(1997)

10 EMC Directive EEC Statutory Instrument No 2372 89/336(Brussels: EEC) (1989)

11 Bromley A K R Electromagnetic screening of offices forprotection against electrical interference and security againstelectronic eavesdropping CIBSE 1991 National Conference,Canterbury, 7–9 April 1991 (London: Chartered Institution ofBuilding Services Engineers) (1991)

12 Johansson M Lightning protection of buildings and their contents: areview of current practice TN 1/94 (Bracknell: Building ServicesResearch and Information Association) (1994)

13 Earthing practice (Potters Bar: Copper Development Association)(1997)

14 BICC Electric cables handbook 3rd ed (Oxford: Blackwell Science)(1997)

15 ECA Recommended cable separations to achieve EMC in buildings(London: Electrical Contractors’ Association) (1993)

16 BS 7807 Code of practice for design, installation and servicing ofintegrated systems incorporating fire detection and alarm systemsand/or other security systems for buildings other than dwellings(London: British Standards Institution) (1995)

17 BS 5839: Fire detection and alarm systems for buildings: Part 1 1988.Code of practice for system design, installation and servicing (London:British Standards Institution) (1988)

18 Fire engineering CIBSE Guide E (London: Chartered Institutionof Building Services Engineers) (1997)

19 Information technology and buildings Applications Manual AM7(London: Chartered Institution of Building Services Engineers)(1992)

20 ISO Building control systems ISO 16484 (Geneva: ISO) (2000)

Systems, networks and integration 4-19

Page 75: Building control system, aplication guide   cibse guide

This Page Intentionally Left Blank

Page 76: Building control system, aplication guide   cibse guide

5.1 SafetyA control system must ensure safe operation of the system itcontrols, give adequate warning of any malfunction and ifnecessary take appropriate action in the event of equipmentfailure. A BMS employs a variety of alarms, interlocks andcontrol strategies to do this. These strategies are found overa wide range of different HVAC systems and are treatedtogether below to avoid repetition.

The operations considered may be classified as:

— alarms

— interlocks

— safety strategies.

5.1.1 Alarms

Alarms are installed to indicate to the operator that asystem variable has exceeded a pre-determined limit. Thismay simply be a warning that some maintenance action isrequired, e.g. a filter is becoming blocked or a piece of planthas exceeded its run-time limit, or be a statement that afailure has occurred requiring immediate attention. At thedesign stage it must be decided how the alarm is to bedisplayed and what action must be taken. Alarmenunciators are available which give visual and audibleindication that a fault has occurred; they may be placedadjacent to the plant in question or where they will be seen

by the operator. Otherwise they are displayed on the centralsupervisor. Alarms may be given priority grades whichdetermine how the alarm is to be handled. To ensure thatthe alarm is not ignored or cancelled without action beingtaken, the alarms should ‘lock on’ until cleared; theappropriate operator identification should be requiredbefore the clearance is accepted, together with anacknowledgement of the action taken.

Alarms may be classified as:

— digital alarms, assigned to the open or closedposition of a contact

— analogue alarms, initiated when a value falls outsidethe high or low alarm limits

— status alarm, initiated when the status of a contactdiffers from the expected value, e.g. a device has notresponded appropriately to a control signal

— totaliser alarm, initiated when the accumulatedvalue of a variable exceeds its high limit value

— hours run alarm, initiated when the total hours runof an item of plant exceeds the set limit.

5.1.2 Interlocks

Interlocks ensure that particular items of plant may onlyoperate together, or are prohibited from operatingsimultaneously. While this could be programmed into theBMS, the use of the term interlock implies that correct

5-1

5 Control strategies for subsystems

5.1 Safety

5.2 Boilers

5.3 Chillers

5.4 Control of hydraulic circuits

5.5 Central air handling plant

5.6 Energy recovery

5.7 Mechanical ventilation

5.8 Variable air volume

5.9 Constant-volume room terminal units

5.10 Fan coil units

5.11 Dual duct systems

5.12 Chilled ceilings

5.13 Heat pumps

5.14 Natural ventilation

5.15 Lighting controls

5.16 Summary

A large HVAC system may be broken down into subsystems, each with its own control strategy for effective operation. Thissection sets out the major strategies for the basic HVAC subsystems, which can subsequently be put together to form acomplete application.

Page 77: Building control system, aplication guide   cibse guide

operation is sufficiently important for the functions to behardwired. An example would be the requirement that aminimum water flow through a boiler exists before theboiler can be fired. Hardwired interlocks may be providedfor the following:

— Boilers, interlocked to:

— pumps and primary loop flow

— plant room ventilation and flow dilutionproving

— gas detection and gas valve

— panic buttons.

— Chillers interlocked to:

— primary pumps and chiller flow

— motorised valve end switches

— dedicated high and low pressure switches.

— Plant shutdown interlocked to fire alarm.

— Start-up and shut-down sequences may behardwired where this is important for safety orplant protection

5.1.3 Safety strategies

Safety switches override normal plant operation to preventharm to plant or personnel and are normally incorporatedin the BMS software. This does not necessarily imply anymalfunction. For a large system, the logical hierarchy of themany interlinked safety switches becomes complicated andis best set out as a decision tree. The use of complexcomputer systems may serve to conceal potential problemsor unexpected control actions in alarm situations. Advice isgiven by the Health and Safety Executive(1).

Hot or chilled water systems

For systems dependent on the circulation of hot or chilledwater, the presence of water circulation enables the wholeHVAC system and:

— In the event of flow failure, the system is shut downand the boilers or chillers are turned off.

— Frost protection is normally provided during offperiods. If the outside temperature or the interior ofan exposed boiler house falls below say 3ºC, thecirculation pumps are turned on to prevent freezingin exposed pipework. If the water circulationtemperature falls below say 20ºC, the heat source isenabled to provide warm water. In addition, thespace temperature in the most exposed part of thebuilding should be maintained above 10ºC.

— If the system is operating under optimum startcontrol, the compensator is disabled and the flowtemperature set to maximum.

Air handling systems

A minimum value of differential pressure across the supplyfan is normally required to enable the whole system. If thepressure fails, the controller shuts down supply and exhaustfans and sets dampers to required positions. The followingactions should be carried out:

— Interlock supply and extract fans so that both comeon together.

— In the event of fire or smoke signal, stop supply andextract fans, close intake and recirculation dampersand open extract damper; details to be agreed withfire officer.

— Frost protection is required to prevent cold outsideair freezing the coil. Operate water pumps toprovide flow though coils when the outside air fallsbelow 2ºC. Open valves to ensure flow throughcoils. Frost precautions may include closing out-door air dampers and starting air recirculation fans.

— The measurement of differential pressure acrossfilters will give warning of a blocked filter requiringreplacement. This is displayed as an alarm.

Boilers

— Protection against catastrophic failure willnormally be provided by the inbuilt controls, e.g.flame failure and over-temperature cutouts and lowwater level provided as part of boiler package.Boiler firing is inhibited unless flow is proved.

— Boilers may suffer damage from thermal shock ifreturn water is supplied at too low a temperature toa hot boiler. A minimum return temperature to ahot boiler is required to prevent damage from boilershock and condensation within the boiler.Temperature limits are advised by the boilermanufacturer.

Package controls. Items of plant such as boilers and chillersare factory fitted with safety switches such as over-temperature cutouts or flame failure devices, which operatethrough the unitary controller. In most cases, these may bewired to the BMS which will display an alarm and indicatethe failure mode to the operator.

Many of the system variables monitored for alarm andsafety reasons are part of the control system. However, it isbad practice to use the same sensor and signal processor forboth control and alarm functions. The two should bephysically distinct.

A related function of a BMS is to ensure correct sequencingof operations during start-up and shut-down. During start-up, plant may be switched on in sequence to ensure thatmaximum demand is not exceeded. During the run-up timeof fans and pumps, it will be necessary to inhibit the actionof various alarms and switches, so that they do not interpretthe initial period as a fan or pump failure. The alarm inhibittime has to be set to a suitable value. On close-down of thesystem, whether routine or due to a failure warning, valves,actuators and other devices should be driven to appropriatepositions. Typically for an air system with recirculation,the intake and exhaust dampers are closed and therecirculation damper is opened.

5.1.4 Selection switches

It is normal practice for each item of plant to be providedwith a Hand/Off/Auto selection switch. This switch isoperated manually and allows the plant item to be switchedoff or operated independently of the BMS for such tasks asmaintenance or commissioning. When the switch is in the

5-2 Building control systems

Page 78: Building control system, aplication guide   cibse guide

Off position, the plant is shut down regardless of the BMSoperating signal. The Hand position activates the plant as ifit were receiving a ‘normal operation’ signal from the BMS.Safety features and interlocks remain in operation. Thestatus of the selection switch is monitored by the BMS.

5.1.5 Fire and smoke control

The design, installation and operation of the fire controlsystem is separate from that of the HVAC and BMS. The firesystem is subject to approval by the fire control officer andit is unusual for approval to be given to integrate the firesystems with other building systems. The operation of fireand smoke control dampers is therefore not the function ofthe BMS. The BMS receives fire alarm signals and must actaccordingly. The control strategy for each subsystem of theHVAC plant should set out the control action to be taken inthe event of receiving a fire alarm signal. For much of theplant, the response to a fire alarm is plant shut-down.Where there is a central air handling unit, the response to afire alarm may be either of:

— plant shut-down, including supply and extract fanswith inlet and exhaust dampers closed

— plant shut-down with the extract fan continuing torun with the exhaust damper open

In all cases a fireman’s override switch must be availableallowing the fire officer to manually control the ventilationplant when arriving on site. CIBSE Guide E(2) discusses thefire precautions relevant to a BMS and CIBSE TechnicalMemorandum TM16(3) gives the legislative background.

5.2 BoilersA great range of boilers for the production of steam and hotwater is available. Most burn gas or oil and available sizes ofboilers range from small domestic units with simple on/offcontrol to multiple boiler units delivering over 10 MW ofheat. Electrode boilers, which pass electric current directlythrough the water to be heated, are available in sizes up to 2MW and can be used for hot water or steam generation,often taking advantage of off-peak supplies. The principlesof boiler control remain the same for all sizes. Boilercontrols may be classified as:

— Operating controls, which undertake routineoperations, such as firing and shutting down theburners and controlling the water leaving tempera-ture. In multiple boiler systems, the operatingcontrols sequence the firing of the separate units.

— Limiting controls, which ensure that systemvariables do not exceed any preset limits, whichmay have safety implications. The limiting controlsmay link to safety interlocks, which shut downboiler operation in the event of a malfunction ofboiler or related equipment. Safety controls andoperating controls should be separate.

There is a wide range of available boilers and installationarrangements and this is reflected in the variety of installedcircuits and control strategies. Many are unsatisfactory,giving inefficient or unstable operation in practice.Recommendations for good practice have been broughttogether by BRECSU(4) which sets out a number of

recommended circuits and control strategies (Table 5.1).The following sets out the principles of control of the boilercontrol and primary water circuit. Control of secondarycircuits is dealt with in 5.3.3.

5.2.1 Types of boiler

New boilers must comply with the Boiler (Efficiency)Regulations 1993(5) and have some or all of the followingcharacteristics:

— low water content and low thermal mass

— high part load efficiencies

— improved heat exchangers and insulation

— low standing losses

— packaged modular arrangements for larger outputs.

One result of the improved design is that it is not usuallyworthwhile to isolate boilers when heat output is notrequired, leading to simpler and more reliable multipleboiler installations, compared with earlier installationswhich required isolation of unused boilers.

Condensing boilers achieve high efficiency by condensingwater vapour in the flue gases and so extracting additionallatent heat.

Control strategies for subsystems 5-3

Table 5.1 Classification of boiler controls

Control type Description

Operating controls:— Leaving water Controls water temperature by burner — thermostat on/off, high/low or modulation

— Pump overrun Pump runs after burner turns off to dissipateheat and prevent boiler overheating andlocking out

— Flue gas Monitor oxygen in flue gas and regulate airsupply for maximum efficiency

— Ignition and shut Automatic burner ignition sequence— down

— Sequencer Controls the operation of multiple boilers

— Sequence selection Rotates the order of operation of multipleboilers

Limiting controls:

— High limit stat Locks out boiler if leaving water temperatureexceeds limit

— Water pressure High and low limits in pressurised systems

— Water flow Check water flow in boiler

Safety interlocks:

— Flame safeguard Check before and after ignition. Shut fuelsupply and purge if no flame

— Burner fan Check for forced draught burners

— Gas detection Check for gas in plant room and close gas valveif detected

— Flue gas dilution Check fan operation

— Water level Checks water level

— Fuel-oil temperature Closes fuel supply valve if heavy oil outsidetemperature limits

— Fusible link above Closes fuel supply valve if high — boiler temperature detected

Page 79: Building control system, aplication guide   cibse guide

Condensing boilers:

— Have an additional heat exchanger in the fluegases.

— Are efficient when not condensing, but require awater return temperature of less than 55ºC forcondensing operation. Maximum efficiency isachieved with a return temperature of 35ºC.

— Can achieve efficiencies in the range 85–95%.

— Are generally higher first cost than non-condensing.

Space heating requirements vary over the season and thereare advantages in using multiple boilers operating undercontrol of a sequencer. As the heat load increases,individual boilers are progressively turned on. Each boilerperforms at or near design conditions, giving highefficiency and reduced wear. The multiple boiler systemmay comprise independent boilers or an integrated unitconsisting of several identical modules. Some modularboilers have several burners firing into a single combustionchamber. The use of multiple boilers provides safety in theevent of a boiler failure; if two boilers are installed, eachwith an output of one half of the design maximum, one ofthem will be capable of heating the building for more than90% of the heating season. Boilers are now available whichmaintain high efficiency when operating at low loads andthe potential improvement in seasonal efficiency fromusing multiple boilers must be carefully weighed againstthe increased complexity of the installation.

Hot water service requirements, i.e. hot water for washing,catering and other purposes, may be supplied in four ways:

— central calorifier, supplied by main heating boiler

— central dedicated HWS boiler

— local storage, heated by gas or electricity

— local point of use, usually electric.

In general, it is more efficient to separate space heating andhot water service systems. A self-contained central hotwater system is normally much more efficient than usingthe main central heating boiler to provide hot water,particularly in summer. One solution is to use electricimmersion heating combined with off peak storage insummer and retaining use of the main boiler in winter.Small decentralised gas-fired storage water heaters close tothe point of use can significantly improve efficiency,especially in an extensive building where distributionlosses associated with a central plant would be high. Wherehot water demand is low, local instantaneous point of usewater heating is economical.

5.2.2 Boiler controls

Boilers are supplied by the manufacturer with built-incontrols. These controls must meet the provisions of HSEPM5(6), which sets out safety requirements for boilercontrols and these will normally be met by themanufacturer’s control panel. Many manufacturers offer afull controls package controlling all the relevant aspects ofboiler operation set out in Table 5.1, which themanufacturer will supply and commission. The controlunit will normally interface with the BMS, giving the BMSaccess to alarms and status information and allowingadjustment of set points.

5.2.2.1 Burner controls

The controls on the burner are linked to a thermostatwhich senses the leaving water temperature. The burnercontrol may be:

— on/off

— two-stage (high/low), giving typically 40% output atthe low setting

— modulating, giving an output range from 20 to100% output at good efficiency.

5.2.2.2 Boiler protection

Some boilers risk corrosion damage if condensation occurson the heat exchanger and so the system design andoperation must ensure that the return temperature to theboiler must exceed a minimum value, typically between 25and 55ºC. This is termed back end protection. The boilermay also require a minimum flow rate during firing. Atypical weather compensation circuit using a mixing valve,shown in Figure 2.12, results in a constant flow through thesecondary circuit at the variable compensated temperature.The variable return flow to the boiler will be at a lowtemperature during mild weather. It may be necessary toemploy a boiler protection circuit, which uses an additionalpump to maintain flow temperature in the boiler (anexample is shown in Figure 5.22).

A particular example is a condensing boiler with split heatexchanger. This requires a low water temperature flowingthrough the secondary heat exchanger to producecondensation in the flue gas, while maintaining back endprotection in the primary heat exchanger. This may resultin connecting the two heat exchanger sections to differentparts of the system. An example is shown in Figure 5.1 for atypical weather-compensated circuit. The cool return waterfrom the secondary circuit passes through the secondaryheat exchanger and a standard boiler protection circuit isprovided in the primary.

The boiler protection circuit finds application for older,high water content boilers operating with variable flow inthe primary circuit. The control of heating circuits isdiscussed in BRECSU General Information Report GIR40(4), which strongly recommends that with modern highefficiency boilers a constant primary flow circuit should be

5-4 Building control systems

Figure 5.1 Condensing boiler fitted with a two-part heat exchanger in acompensation circuit. Boiler protection for the primary heat exchanger isprovided

Page 80: Building control system, aplication guide   cibse guide

used, with a system header to decouple the flows in primaryand secondary circuits. This obviates the need for back endprotection and gives simple effective control (see Figure5.23).

If the burner and primary circulation pump are switched offsimultaneously in a lightweight boiler, there may besufficient residual heat to cause local boiling, with the riskof damage to the boiler. It is therefore usual to provide apump overrun function; the pump runs for a short period,up to 5 minutes, after the burner switches off, to dissipatethe residual heat. The situation is different for high watercontent boilers. Here, the residual heat represents aworthwhile amount of energy. The function of the pumpoverrun function is to move this useful heat into thesecondary heating circuit, rather than allow it to contributeto the boiler standing loss. Circulation is maintained for ashort period until flow and return temperatures are roughlyequal.

5.2.2.3 Water heating plant

A recommended water heating plant for general use utilisesseparate primary and secondary water circuits, linked by acommon header which acts as a hydraulic decoupler. Aprimary pump maintains water flow round the primarycircuit and through the boiler. The primary pump isnormally positioned in the return pipework to the boiler,particularly when open non-pressurised systems are used.Hot water is drawn from the common header to supplysecondary circuits and HWS calorifiers as required. Withthis layout, compensation control adjusts the flowtemperature of the secondary water flow temperature anddoes not influence the boiler. It is important to ensurecompatible flows where the primary and secondary circuitsinteract; see 5.4.1. The use of a hydraulic decoupler isrecommended as the constant flow of water through theboiler allows stable control to be achieved. Figure 5.2 showsa simple primary circuit; the boiler is protected by a highlimit thermostat on the flow water and a flow switch on theprimary return. Other boiler protection controls werediscussed above. There are many variations of watercircuit, the most important of which are discussed furtherin 5.4.

For smaller systems where there is only one secondarycircuit it is possible to use the same circulation pump todrive both primary and secondary circuits. Figure 2.12illustrates a simple weather compensation circuit where theprimary flow is compensated. This has the disadvantage ofreducing the return temperature to the boiler at low loads,with the attendant risk of condensation and corrosion.

5.2.2.4 Multiple boilers

Multiple boilers are used with some form of sequencecontrol, which switches units on or off to match the heatdemand. Separate boilers, not necessarily identical, may becontrolled by a sequencer. A modular boiler can be used,consisting of a group of similar modules that are broughtinto use as required. The unit may have separatecombustion chambers or a common combustion chamber.In order to share operating duty equally between allcomponents of a multiple boiler system, boiler sequenceselection is employed. This changes the order of operationof the boilers in rotation, either on a time or usage basis.Control is simplest where all components of the boilersystem are identical. Circumstances where non-identicalboilers are used include:

— The use of a small boiler for summer hot waterservice.

— The use of a single condensing boiler, where thecost of specifying all condensing units is notjustified. The condensing boiler should always bethe lead boiler to ensure maximum utilisation.

Poor control of boiler operation can add 15 to 30% to fuelconsumption(4) compared to a well-controlled system. Theuse of modern boilers, with good efficiency and lowstanding losses, has simplified some aspects of boilercontrol. With a multiple boiler installation, heat lossesfrom an unused boiler are reduced if that boiler is cold orcooling; when the heat output from a unit is not required itis more efficient to isolate the unit and prevent hot waterflowing through it. However, experience has shown that theuse of individual boiler pumps and isolation valves cancause many problems. The low standing losses of modernboilers allow simple sequencing control of multiple boilerswithout the necessity for isolation.

These low losses also enable a multiple boiler unit to operatewith constant flow through all boilers without significantheat loss. This allows a simplified hydraulic layout, givingeffective control without the use of individual boiler pumpsor isolation valves. The use of separate primary andsecondary circulation pumps combined with a low lossheader ensures that a constant flow is maintained throughthe boilers, irrespective of any control action in thesecondary circuit; this enables effective boiler sequencingcontrol based on the return temperature.

Figure 5.3 shows the control principle for multiple parallelconnected low water content boilers. This is recommendedby BRECSU(4) for simple effective and reliable control. Thelead boiler is enabled at all times heating is required. As theheating demand in the secondary circuit increases, thereturn water temperature drops and subsequent boilers areenabled according to the change in return temperature.Individual boiler temperature is controlled by thermostatson the boiler leaving water temperature. Integral controlshould not be used, since the fall in return temperature with

Control strategies for subsystems 5-5

Figure 5.2 Simple boiler primary circuit. The boiler feeds a commonheader and primary flow is maintained by a pump. The boiler firing iscontrolled to give the desired flow temperature; a low primary returnsignal will enable the boiler

Page 81: Building control system, aplication guide   cibse guide

increased heat load is part of the strategy and is not to betreated as a load error.

In conditions of low load, the return water temperatureentering the boilers is higher than at design conditions.The return temperature controls the number of boilers inservice, and takes boilers off-line as the return temperaturerises. The leaving water temperature of the operatingboilers will be higher than the design temperature;however, this flow is then diluted by water flowing thoughthe non-operating boilers; this is the phenomenon of flowdilution. The flow temperature of primary water enteringthe common header is the mean of the leaving temperaturesof the multiple boilers. Individual boiler thermostats mustbe set higher than the design flow temperature to obviatethe risk of lockout at low loads. Due regard must be paid tothe provisions of PM5(6) on allowable temperatures andpressures.

Some designs of boilers, particularly older models withlarge water content, have an unacceptably high standingloss when warm. Overall efficiency in a multiple boilersystem is therefore improved if boilers can be isolatedfrom the primary water circulation and allowed to coolwhen not required. This adds to the complexity of thecontrol system and can lead to control problems; inaddition, some manufacturers do not recommend isolationvalves because of concern about the effects of repeatedheating and cooling of the boiler. If isolation is to be used,it must be engineered properly, as inadequate isolationgives rise to inefficiencies and control problems. Tightshut-off is required, as even a residual flow of 1% ofnominal flow rate can give a heat loss equal to 40% of thatobtaining at 100% flow(7).

Figure 5.4 shows a suitable control circuit for multipleparallel connected large boilers which need to be isolated.The lead boiler is enabled at all times heating is requiredand subsequent boilers and pumps are enabled accordingto the total heat load of the system, which is measured asthe product of the primary circulation flow and thedifference between flow and return temperature in andout of the common header. During boiler warm-up, thevalve is in the recirculation position to prevent corrosionand cold slugs of water being delivered to the header. Aseparate control is required during system start-up, sincethere is then no temperature differential across theheader. Outside air temperature can be used as anindication of system load. Individual boiler firing iscontrolled as normal by a thermostat on the boiler outlet.Control by heat load requires more instrumentation thancontrol by temperature differential, but is required sincethe use of separate boiler pumps makes it difficult toensure a constant primary flow. This circuit is moreexpensive to install than the simpler system shown inFigure 5.3 and has to be justified by the reduction in heatloss from off-line boilers.

5-6 Building control systems

Sequence controller

Co

mm

on

hea

der

Figure 5.3 Multiple parallel boilers operating under control of asequencer. Individual boiler firing is controlled by boiler thermostat

Figure 5.4 Multiple parallel highwater content boilers. The sequencecontrol enables additional boilersaccording to measured heat load

Page 82: Building control system, aplication guide   cibse guide

Series connection of boilers has the practical disadvantagethat it is more difficult to isolate a unit for maintenancethan with parallel connection. The resistance to flow in theprimary circuit is also greater, resulting in higher pumpinghead. Nevertheless, this system gives simple effective andreliable control, without any of the possible problems ofhigh boiler leaving temperatures caused by flow dilution.Figure 5.5 shows series-connected boilers feeding acommon header. Constant flow in the primary circuit ismaintained at all times. The lead boiler is enabled at alltimes heating is required. Subsequent boilers are enabled asthe return temperature drops in a manner proportional totemperature. Individual boiler firing is controlled by theboiler’s own thermostat.

5.2.3 System pressurisation

Pressurising a hot water system allows higher operatingtemperatures. Simple systems rely on the static headprovided by a feed and expansion (F&E) tank; note that therelevant measurement when calculating pressure andallowable working temperature is the height of the feed andexpansion tank above the highest point of the circulatingsystem. The F&E tank is open to atmosphere and so willabsorb oxygen and may also become contaminated. The useof a sealed system eliminates absorption of air and theattendant corrosion risk; higher working pressures may beobtained in buildings where it is impossible to mount anF&E tank at sufficient height. Pressurisation may also beapplied to chilled water systems. A pressurised system mustmeet the requirements of PM5(6). This details a number ofcontrol interlocks to ensure safe working and specifies thatthe temperature of the water leaving the boiler must be atleast 17 K below the temperature of saturated steam at apressure equal to the pressure at the highest point of thecirculating system. It is necessary to monitor pressure toensure that systems do not over- or under-pressurise.

5.2.3.1 Sealed expansion vessel pressurisation

This system uses a sealed expansion vessel incorporating aflexible diaphragm. The space above the diaphragm ischarged with air or nitrogen to the required pressure andprovides system pressurisation during normal operation.The movement of the diaphragm accommodates expansionof the water in heating. If system pressure falls due to water

loss, the pressurisation pump is activated; this adds water tothe vessel to bring the pressure back to the working level.An anti-gravity tank acts as a buffer between the hot watercirculation and the expansion vessel to prevent hot waterreaching the vessel during expansion (see Figure 5.6).

In addition to the pressure sensor which controls thepressurisation pump, high and low pressure switches areinstalled to act as interlocks. Activation of the high pressureswitch disables the boiler and closes the fuel supply;circulation pumps continue for the run-on period.Activation of the low pressure switch disables the boilerand turns off circulation pumps. These interlocks arenormally hardwired and require a manual reset.

5.2.3.2 Pump pressurisation

An alternative system uses a pump to maintain systempressure. Figure 5.7 illustrates the system. When thesystem is below pressure, the pressurisation pumps operateto restore pressure. If the system pressure is high, a spillvalve opens and relieves any excess pressure by allowingwater to pass to the expansion vessel. The pumps do not runcontinuously, but operate more often than is the case withthe sealed system above and it is therefore common practiceto provide duplicate pumps. The system can be provided asa packaged pressurisation unit with controls incorporated.High and low pressure interlocks should be provided, as forthe sealed system.

5.3 ChillersThe basic components of an air conditioning system usingchilled water as a distribution medium are:

— chiller, which contains the refrigeration unit

— heat rejection system, e.g. air cooled condenser orcooling tower

— chilled water distribution system.

The control of the distribution system is considered indetail in other sections. The chiller is the heart of thechilled water system and is classified by the type ofrefrigeration cycle:

— Vapour compression. This is the most common type,using an electrically driven compressor

— Absorption. Absorption chillers use heat to drive therefrigeration cycle. They are used where heat ischeaply available; they have some advantages inlarge systems.

Vapour compression units are classified by the type ofcompressor, which are shown in Table 5.2 together withtypical applications and capacity control methods.

Control strategies for subsystems 5-7

Figure 5.5 Series-connected boilers operating under control of asequencer

Table 5.2 Compressor types

Compressor Application Capacity control

Centrifugal Inlet vane and VSD

Reciprocating All sizes Cylinder unloading

Screw > 200 kW Slide valve and VSD

Scroll >50 kW and < 200 kW VSD

Page 83: Building control system, aplication guide   cibse guide

5.3.1 Chiller control

All types of compressor are capable of some form of capacitycontrol. Reciprocating chillers are still the most commonlyused, and consist of multi-cylinder units. Capacity controlis by unloading one or more cylinders, i.e. by letting thesuction valve open so that the unloaded cylinder does notpump refrigerant. Depending on the number of cylinders,this gives four or more stage capacity control. Rotarycompressors using a combination of variable-speed drives(VSD) and mechanical control can give smoothlymodulating control of chilling capacity; in most cases theoutput may be modulated down to about 10% of full output.The efficiency of operation is strongly affected by theoperating temperatures and pressure of the chiller unit.The primary factor affecting compressor efficiency is thepressure difference across the compressor, known as therefrigerant pressure. Reducing the refrigerant pressureincreases efficiency. Refrigerant pressure is reduced by thefollowing:

— reducing condenser water temperature (but there isa minimum temperature for safe operation)

— raising the chilled water temperature

— reducing load (but overall chiller efficiency falls offat loads below about 30% full load).

Improved efficiency will be achieved by resetting thechilled water flow temperature upwards when the buildingcooling demand is light. Where variable-speed pumping ofthe chilled water is employed, the necessary flow rate andhence pumping energy consumption will be increased if the

chilled water flow temperature is increased, compared withthe alternative of maintaining flow temperature andreducing flow rate. It is possible that this will negate anyimprovement in chiller efficiency. Each system has to beconsidered independently to decide whether chilled watertemperature reset is energy efficient.

Heat rejection from the chiller is commonly either by usinga separate cooling tower or an integral air-cooled condenser.Air-cooled condensers are used in most small self-containedor split package systems up to about 1 MW capacity. Suchunits have the advantage of being self-contained, requiringno additional water supply and obviating any risk ofLegionnaires’ disease. The refrigerant gas leaving thecompressor is circulated through a heat exchanger which iscooled by ambient air drawn over it by a fan. Fan speed iscontrolled as a function of load and ambient conditions tominimise overall energy consumption. Fan control for apackaged unit containing an air-cooled condenser isprovided as part of the unitary controller provided with theunit and is not regarded as part of the BMS. The control ofcooling towers is considered separately below.

It is universal practice that the chiller manufacturerprovides a factory-fitted controller which is programmed toensure safe and efficient operation over a wide range ofloads. The dedicated controller looks after capacity controland condenser water temperature, plus other items such asthermal expansion valves or hot gas bypass. For multiplechillers, it will take care of sequencing. The controlsspecialist is therefore not required to configure the chillercontrols for optimum efficiency. For many systems, thechilled water temperature is set at a constant value at the

5-8 Building control systems

Anti-gravityvesselPressurisation

pumpMake

up

Expansionvessel

Limit switch FlowFigure 5.6 Sealed expansion vesselpressurisation. Pump runs whenrequired to replace water and make uppressure. High and low limit pressureswitch fitted

Figure 5.7 Pump pressurisation. Thepump runs to maintain system pressureon receipt of low pressure signal.Excess water passes to the expansionvessel via the spill valve. High and lowpressure limit switch is fitted

Page 84: Building control system, aplication guide   cibse guide

chiller controller, leaving the only function of the BMS toturn the chiller on and off at appropriate times. However,the more comprehensive chiller controllers are designed tocommunicate with a BMS. This provides for control of thesupply of chilled water and monitoring of operation, whileleaving the detailed control and optimisation of theworking of the chiller to the fitted controller.

Table 5.3 summarises an interface between a chillercontroller and the BMS. The example shown is for areciprocating chiller and the controller allows the BMSdirect control of capacity by loading or unloading thecompressor cylinders. In general, it is sufficient for the BMSto supply the chilled water temperature set point and allowthe chiller controller to optimise operation. Several pointsare available to the BMS which may be used for conditionmonitoring and maintenance.

5.3.2 Multiple chillers

The use of multiple chillers offers standby capacity andimproved efficiency at part loads. A typical arrangement isshown in Figure 5.8, where two multi-cylinder compressorsare mounted in parallel. The lead compressor runspreferentially; the lag compressor is activated when thelead compressor can no longer meet the load.

This arrangement can provide good control of the leavingtemperature of the chilled water. In the example, thechillers have a design capacity to produce a leavingtemperature of 6ºC when the return temperature is 10.5ºC.In the example, each chiller control is set at 4.5ºC. This setpoint has to be lower than the leaving temperature set pointsince if only one chiller is in operation, the water leavingthe operating machine will be mixed with the warmer waterpassing through the inactive machine; this is termed flowdilution. If the chilled water temperature leaving a chillerfalls below the lower limit of the operating differential, thatchiller is unloaded one step. The sequence control sensor ismounted in the mixed chilled water flow. If the mixed flowfalls below the lower limit of the operating differential, achiller step is unloaded. The sequencer unloads the lagchiller in preference to the lead. It is also necessary to set atime delay, known as the load/unload time; this is the timeallowed for the chiller to bring the water temperature under

control after a load change. If the water temperature has notbeen brought within the differential band within this time,a further step is loaded or unloaded. There can becircumstances where one chiller has sufficient capacity tomeet the building load, but would need to cool to a flowtemperature below its set point; this is a consequence offlow dilution. In this situation, both chillers run at partload. The operating differential of the sequence controllermust be greater than the change in leaving temperatureproduce by loading or unloading one step; this is necessaryfor stable operation. This method of step control can givegood control of the mixed leaving temperature.

Multiple chillers are not necessarily of the same size ortype. There are advantages in using a mixture of sizes, e.g.

Control strategies for subsystems 5-9

Table 5.3 Chiller control interface for reciprocating chiller

Point Type

Controlled points:

— Water temperature set point AO

— % load limit (10–100%) AO

— Lead unit No AO

— Start/stop command DO

— Load the chiller DO

— Unload the chiller DO

Monitored points:

— Chilled water temperature AI

— Condenser water temperature AI

— Compressor oil temperature AI

— Compressor oil pressure AI

— Compressor suction pressure AI

— Compressor discharge temperature AI

— Compressor full load current AI

— Compressor run hours AI

— Compressor number of starts AI

— Compressor anti-recycle timer AI

AO: analogue output; AI: analogue input; DO: digital output.

Figure 5.8 Two chillers in paralleloperating under sequence controller

Page 85: Building control system, aplication guide   cibse guide

chillers in the ratio 30/50/70. This allows better matching ofcapacity to load than the use of equal-sized chillers; thechiller management controller assesses the load and selectsthe combination of chillers which best matches it. In somesituations, a combination of vapour compression andabsorption chillers may be economical, either because ofthe availability of a source of cheap heat or a requirement toavoid peak electrical loads. The optimisation of a multiplechiller system requires knowledge of the efficiency curvesof each chiller at all temperature differentials. A typicalcalculation sequence, starting at minimum load, would beto select and start the most efficient chiller for that load. Asthe load increases, the data is constantly checked. When theoptimum load for adding a second chiller occurs, based oncurrent load, temperature differences and efficiency curves,the selected chiller is started and the loading of each chilleris adjusted for maximum system efficiency. If the decisionis made to add or drop a chiller, minimum on and off timeconsiderations must be considered.

5.3.3 Cooling towers

A cooling tower (Figure 5.9) employs evaporative coolingand can cool the condenser water to within 3 K of theambient wet bulb temperature. By comparison, an air-cooled heat exchanger can achieve cooling of condenserwater to within about 11 K of ambient dry bulbtemperature. The use of poorly maintained cooling towershas been associated with outbreaks of legionellosis and thishas restricted their application in recent years(8,9). However,the greater efficiency of the evaporative cooling towerensures its continued use in appropriate situations.

The performance of a cooling tower is characterised by twotemperature differences:

— range: the difference between entering and leavingwater temperatures

— approach: the temperature difference between thewater leaving the cooling tower and the ambientwet bulb temperature (ambient dry bulb tem-perature in the case of a ‘dry’ cooling system).

A schematic diagram of an open cooling tower and itscontrols is shown in Figure 5.9. In an open cooling towerthe condenser water itself is sprayed in the tower to achievemaximum evaporative cooling. As shown above, themaximum working efficiency of the chiller is achieved atthe lowest possible condensing water temperature, subjectto a minimum temperature, typically 18ºC, below whichthere is a risk of damage to the compressor. Figure 5.10shows the lowest possible condenser water temperatureleaving a cooling tower as a function of ambient wet bulbtemperature and this should give the maximum possiblechiller efficiency. The condenser water is subject to low andhigh temperature limits to avoid damage to the chiller. Asshown in Figure 5.9, control of condenser watertemperature is by a combination of fan speed control andvariable bypass of the flow of condenser water though thetower. Where multiple fans are employed, sequentialswitching of fans may be used instead of fan speed control.The range, i.e. the amount of cooling produced in the tower,may be increased by increasing the cooling tower fan speedand reduced by turning the fan off and using the bypassvalve to reduce the flow of condenser water through thetower. The bypass valve is always fully open to the towerwhen the fan is on.

There are three major control strategies for cooling toweroperation:

— fixed set point

— variable set point (fixed approach)

— near optimal control.

With fixed set point control, the condenser temperature iscontrolled at a constant set point, typically about 26 to28ºC, by the use of the modulating bypass valve and thecooling tower fan. For simple systems, the fan control ison/off. This has the advantage of simplicity, but in part loadconditions the condensing water temperature isunnecessarily high, resulting in high chiller powerconsumption. Variable set point control adjusts the setpoint of the condenser water temperature in accordancewith a characteristic curve of the form shown in Figure

5-10 Building control systems

Figure 5.9 Open circuit coolingtower with bypass circuit

Page 86: Building control system, aplication guide   cibse guide

5.10. Restricting the set point to the minimum approachvalue means that the fan speed will not be increased in avain attempt to reach an impossibly low temperature.

Variable set point control does not necessarily result inminimum energy consumption, since the saving in chillerpower consumption is to some extent offset by an increasedcooling tower fan consumption. A control strategydeveloped in the USA(10) and since applied to the UKsituation(11) achieves low combined energy consumptions.The strategy is termed near optimal control and consists ofa simple control algorithm that regulates the fan speed inproportion to the part load ratio, i.e. the ratio of the actualload to the maximum system load. Upper and lowercondenser water temperature limits are incorporated toprevent damage to the chiller. This is an open loop controland it is necessary to calculate in advance the systemparameters of the control algorithm from performance dataof the cooling tower and chiller. The controller requiresthree inputs: chilled water flow and return temperaturesand the condenser water supply temperature. A value forchilled water flow is also necessary to calculate the chillerload; this value can be supplied from commissioning dataor measured directly. The control output is a signal to runthe tower fans at a speed proportional to the cooling load.Near optimal control is particularly suited to installationswith large centrifugal compressors that are operatedthroughout the year over a range of ambient temperatures.

As well as control of condensing water temperature, acooling tower requires other controls for safe operation:

— Freeze protection. Water in the tower is at risk offreezing in cold weather; the danger is increased bythe use of a bypass valve or when the chiller is out ofaction. An immersion heater controlled by athermostat in the tower pond is used to preventfreezing. Alternatively, the pond may be drained toa sump located in a warm space when a risk ispresent.

— Bleeding. The concentration of dissolved andsuspended solids increases over time due toevaporation and the collection of airborne dirt. Thepond requires to be bled periodically and topped up

with fresh water. This may be on a time schedule orcontrolled by monitoring water conductivity. Thebleeding program may be combined with chemicaltreatment of the water. A water meter is ofteninstalled in the supply pipe to the pond, which maybe used to control chemical dosing equipment.

— Interlocks. A flow switch is positioned in thecondenser water circuit. If flow is not proved, bothchiller and cooling tower fan are switched off. Adifferential pressure switch may be used to provecooling tower fan operation.

In a closed circuit (indirect) cooling tower, the condenserwater is circulated though a heat exchanger within thetower. Condenser water and cooling tower water are thuskept separate, which has the advantage of preventingpossibly dirty water passing through the condenser.Control strategies are the same for the open tower. Theclosed circuit tower still involves the use of sprayed waterwith the attendant risk of the dispersal of contaminateddroplets. Where it is necessary to use a dry system, it may bedesirable to use a dry cooling tower. Condenser water iscirculated through a water–air heat exchanger which iscooled by fans. This differs from an air-cooled condenserwhere the refrigerant itself is circulated through an air-cooled heat exchanger. The use of a dry cooling toweravoids the use of long refrigerant lines where the heatrejection unit is remote from the compressor. It has thedisadvantage compared with an air-cooled condenser ofintroducing an extra heat exchanger, with the associatedloss of efficiency. The minimum approach for the cooledwater is about 11 K of the ambient dry bulb temperature.Otherwise, the control principles are the same as for anevaporative cooling tower.

5.3.4 Free cooling

For systems which depend on the circulation of chilledwater, it may be possible to dispense with the chiller whenthe outdoor conditions are such that the condenser watertemperature from the cooling tower is lower than therequired chilled water temperature. Three methods areavailable for the provision of free cooling:

— Refrigerant vapour migration. A special chiller designincorporates extra refrigerant paths which bypassthe compressor. Heat exchange between condenserand evaporator takes place by gravity circulation ofrefrigerant. This is also known as the thermo-syphonic method of free cooling.

— Auxiliary heat exchanger. The condenser water andchilled water circuits are diverted to an auxiliaryheat exchanger, where the cool condenser waterextracts heat from the chilled water circuit.

— Interconnected circuits. The two circuits are directlyconnected, so that the condenser water flows in thechilled water circuit. This risks circulating dirtywater to fan coil units or other terminals with riskof fouling and blockage. Water treatment andfiltration assume great importance.

The term free cooling in this context is to be distinguishedfrom the situation in air handling systems usingeconomiser control, where cold outdoor air is circulateddirectly to the conditioned space. This is also termed freecooling and is treated in 5.7.5.

Control strategies for subsystems 5-11

Figure 5.10 Minimum condenser water temperature for an open circuitcooling tower

Page 87: Building control system, aplication guide   cibse guide

5.3.5 Ice storage

Ice storage systems run chillers overnight to produce ice;during the subsequent day the ice is melted to providechilled water for cooling and dehumidification. While it ispossible to size the ice store to be of sufficient size to copewith the next day demand, it is more common to opt forpartial storage, where the ice store is not sufficient in itselfto provide all cooling needs on a design day. Peak loads aremet by discharging the ice store and running the chiller atthe same time. Ice storage has several advantages over anon-storage system:

— Smaller chiller size. The chiller does not have to meetthe instantaneous maximum design load,potentially giving reduced capital costs.

— Lower running costs. It may be possible to takeadvantage of reduced electricity prices at night orexploit the potential for reducing maximumdemand charges.

— More efficient chiller operation. The chiller runssteadily at design load for extended periods andbenefits from lower ambient temperatures, whichresults in reduced condenser water temperatures.

The two major types of ice store are classified as:

— Direct storage. This type of store is also known as anice builder. Refrigerant coils are immersed in thestorage tank and ice forms on the outside of thecoils. When cooling is required in the main system,chilled water is passed through the tank and thismelts the ice.

— Indirect storage. The most common form of indirectstore is the ice bank. The primary chilled circuituses a glycol mix. During charging, this is chilledand circulated through a cooling coil immersed inthe ice store to freeze it. During discharge thesame glycol mix is circulated through the coil inthe now frozen ice store and then to a heatexchanger to cool the secondary chilled water. It ispossible to dispense with the heat exchanger andcirculate the glycol mix throughout the secondarysystem.

5.3.5.1 System configuration

Partial storage systems can be configured in different ways,the names reflecting the relative positions of the chiller andice store. Chiller upstream configuration represents thegreat majority of installed systems.

— Chiller upstream. The chiller, ice store and load arepiped in series. Chilled coolant leaving the chillerflows directly to the coil in the ice store. When bothchiller and store discharge are operatingsimultaneously, the chiller receives water from theload at relatively warm temperature, allowing thechiller to operate at a high COP.

— Chiller downstream. The chiller receives waterleaving the ice store and it is possible to modulatethe flow and bypass round the store to achievealmost constant operating conditions for thechiller. This arrangement allows low coolant flowtemperatures to the load if required, but requiresthat the chiller operate at low temperatures with alower COP.

— Parallel system. The piping arrangement allows thechiller or ice store to operate independently of eachother, or in a variety of arrangements. It ispotentially more efficient, but requires morepipework, valves and controls.

Figure 5.11 shows a chiller upstream ice storage system.The system is arranged so that it can provide some coolingto the building during the night-time charging period. Thecircuit shown is suitable for a night-time cooling load of upto about 20% of the peak load. Larger night-time coolingloads require a separate chiller which is available 24 h perday but does not contribute to ice store charging. The figureshows an injection circuit used to modulate the supply ofcoolant to the secondary heat exchanger. If simultaneousbuilding cooling and store charging is required during thenight, use of the injection circuit avoids supplying coolantat below zero temperature to the heat exchanger. Ifsimultaneous cooling and charging is never required, theextra pump and three-port valve may be dispensed with.The various operating modes are tabulated in the figure.The daytime cooling load is met by chiller, ice store or acombination of the two. Temperature control of the coolantflow to the load is modulated using the three-way mixing atthe exit of the ice store. The temperature drop across thesecondary heat exchanger must equal the sum of thetemperature drops across the chiller and ice store. This mayrequire a larger temperature differential than usual withconsequent attention to design. The design and control ofice storage systems is dealt with in CIBSE TM18(12).

5.3.5.2 Control techniques

It is important that the controller be able to monitor theamount of ice in the store, both to terminate charging whenthe maximum capacity has been reached and to estimate the

5-12 Building control systems

P1 P2 V1 V2 V3 T1 T2 T3V4

Figure 5.11 Ice storage: series configuration chiller, upstream. Ifsimultaneous charging of the store and building cooling is not required,the injection circuit with P1 and V4 may be dispensed with. The tableshows settings for chiller priority operation. Set points are illustrative only

Page 88: Building control system, aplication guide   cibse guide

available capacity remaining during discharge. Severaltypes of ice inventory estimation are used:

— Volumetric devices. These detect the pressure changeproduced by the increase in depth of the storecaused by water expansion on freezing.

— Heat flow monitoring. These methods calculate theheat entering and leaving the store by measuringflow rate and temperature difference across the coiland so estimate the quantity of ice melted. Thismethod estimates the quantity of ice remainingduring discharge and requires that the store starteach day fully charged to give a datum.

— Store exit temperature. During charging, coolant leavesthe store at an initial temperature of about –0.5ºC.When charging is complete, this temperature fallsrapidly and the chiller is switched off when the exittemperature reaches –4ºC. In practice, the fall intemperature may not give a clear endpoint, since thelayer of ice on the coil inhibits heat transfer.

Charging strategy for a partial storage system. The ice storeis charged each night during the low rate tariff period.Three levels of control are possible:

— Charge to full. The charge period is initiated by atime switch or signal that the low rate tariff periodhas started. The chiller then operates at full loaduntil the charge control device indicates that thestore is fully charged, irrespective of the level ofdaytime demand. The control is reset to preventcycling.

— Skipped charge. If only a small amount of the icestore has been depleted during the day, thesubsequent night’s charge may be omitted.

— Optimum charge. Each night, the controller mustcalculate the total expected cooling required for thefollowing day, together with an estimate of the iceremaining in the store after the previous day’soperation. The difference, plus an allowance of 10%or so, is the required overnight charge.

Standing losses from an ice store are small and the energypenalty from charging fully each night may not be enoughto justify a complex control system. For many buildingsduring the British winter, free cooling will be sufficient toprovide enough chilled water and it will not be necessary torun the ice store. As the weather warms up in spring, thefirst day that chiller operation is required during the daymarks the start of the ice storage season. The moresophisticated controllers use an estimate of the coolingdemand profile during the day, both to estimate the totalcharge required and to optimise the discharge pattern. Thisis done by averaging the hourly figures over the previousthree days, taking due account of weekends or holidays.

Control of the discharge cycle. Two main methods ofcontrol are available:

— Store priority. This treats the ice store as an extrachiller and modulates the supply of chilled waterfrom the store to the rate that it can supply for therest of the occupied period. If this is insufficient tomeet the instantaneous demand, the chiller is runas well.

— Chiller priority. The chiller provides the base load,with the ice store being used to provide additional

capacity as required. The chiller is turned off whenthe ice store is sufficient to meet the remainingdemand for the day.

The store priority control may result in inadequate coolingability to meet peak demands towards the end of theworking day and the potential reduction in operating costby exploiting lower cost stored energy may be nullified byincreased capital cost and inefficient part load operation ofthe chiller. The chiller priority method results in bothsmaller chiller and ice store sizes and allows full advantageof the ability of the ice store to provide high cooling powerwhen required for peak demands at the end of the day or fordemand management. Figure 5.12 compares dischargepattern of the two strategies.

Achieving optimum discharge control is complicated bythe fact that the available rate of chilled water supply fromstore falls off as the store is depleted. The aim of thedischarge control is to run the chiller at maximum capacityduring the day until the remaining demand can be met bythe ice store alone. Maximum cooling demand occursduring the afternoon and the controller makes use of anestimate of demand profile obtained by averaging theprevious three days demand. At hourly intervals during theday, the controller compares the estimated demand for therest of the day with the remaining store capacity. If the storecapacity exceeds the demand, the store is used alone.Otherwise, the chiller runs at full rate for 1 h, after whichthe comparison is repeated(13).

Control strategies for subsystems 5-13

Time of day

Time of day

Figure 5.12 Comparison of store priority and chiller priority operation atpart load

Page 89: Building control system, aplication guide   cibse guide

5-14 Building control systems

5.4 Control of hydraulic circuitsThe variety of hydraulic circuits used in heating andcooling applications is very great. The following sets outsome of the basic hydraulic circuits which are used for bothprimary and secondary systems and gives the maincharacteristics which are relevant to their control. Primarycircuit implies the main distribution circuit of hot orchilled water, which supplies secondary circuits. Secondarycircuit implies the hydraulic circuit which circulates fluidthrough a heat exchanger, which is typically a coil in a ductor fan coil unit, but may be a radiator, chilled ceiling orother device. In addition, there may be a circuit with itsown pump ensuring the required circulation through theboiler or chiller. The discussion below is set out usingboilers, but most applies equally to chilled water circuits.

5.4.1 Network design

It is essential that hydraulic circuits are properly designedand balanced if the control system is to be able to operate ina stable and effective manner. Sufficient flow of water mustbe available at each terminal and it must be controllableunder all operating conditions; it is not sufficient to achievedesign conditions alone. The problem of achievingcontrollability under part load conditions is greater whentwo-port variable flow circuits are used, compared withcircuits using three-port valves. Three-port valves used inmixing circuits give more or less constant flow conditions,so that modulation of one valve does not disturb flow rateselsewhere in the system. In contrast, modulation of a two-port valve causes variations of flow and pressure elsewhere,which can lead to overflow or starvation of other terminals.This is discussed in more detail in 5.4.5.

While the detailed theory of hydraulic circuits is outsidethe scope of this Guide, three simple principles may bestated for good controllability(7):

— The design flow must be available at all terminals.

— The control valves must have sufficient authority.

— Flows must be compatible at system interfaces.

These conditions may be achieved by a combination ofsatisfactory circuit design in the first place and propersystem balancing on commissioning.

Availability of design flow

Consider a system which has a number of heating terminalscontrolled by two-port valves. Under steady operatingconditions the valves modulate to provide the required flowthrough each terminal and the need for balancing valvesmay not be apparent. However, in boost or optimum startmode, all valves open fully. If the system is not properlybalanced, some circuits will receive an overflow, with acorresponding underflow in less favoured circuits. The lessfavoured circuits will only receive their required flow whenthe favoured zones have reached their set temperature andtheir valves start closing. Since the output from a heatemitter is not a linear function of flow, the increased flow inthe favoured circuits does not produce a correspondingincrease in heat emission, with the result that the fulloutput of the boiler is not available during start-up, when itis most needed. Mistaken attempts to cure the under-heating by increasing the pump pressure are unsatisfactory.

Correct balancing is required to achieve design flow in allsecondary circuits with the control valves fully open.

Valve authority

Valve authority was defined in 3.3.4.1. An alternativedefinition, which is more readily applicable to systems withtwo-port valves is

N =

where ΔPmin is the minimum pressure drop across thecontrol valve in its fully open position and ΔPmax is thepressure drop across the valve in its fully closed position.The authority can therefore be envisaged as a measure ofthe variation of the differential pressure across the controlvalve as the valve modulates. An authority of N = 1 impliesno variation of pressure; an authority of N = 0.25 means apressure variation over a range of 4:1 as the valve modulatesfrom closed to open. An authority of N ≥ 0.25 should beaimed at. A valve with a low authority will give poor controland may give rise to hunting operation. Satisfactoryauthority is achieved by selecting a valve with the requiredpressure drop at design flow rate and balancing the systemto achieve the design flow rates. In some systems using two-port valves it is difficult to achieve the required authorityand a differential control valve may be used to give aconstant pressure drop across the control valve. Thisachieves an authority of N = 1 and is discussed further in5.4.5.5.

Compatibility of flow

Where two circuits share a common section, the systemmust be balanced to ensure that the two flows do notinteract in such a way as to prevent the desired performancebeing achieved. Figure 5.13 shows a boiler feeding asecondary circuit though a hydraulic decoupler; decouplersare discussed further in 5.4.3.3. If the flow in the secondarycircuit is greater than that in the primary circuit, water willflow upward in the decoupler, with the result that coolreturn water mixes with the hot boiler flow, reducing theflow temperature in the secondary circuit. This can preventthe design boiler heat output being delivered to the heatemitters. The total pump flow on the primary side must beat least equal to that on the secondary and this must beestablished during balancing. The diagram shows a verysimple layout. In practice, problems of incompatible floware likely to arise with multiple boiler or chillerinstallations feeding a variable-flow secondary circuit.

ΔPmin

ΔPmax

Figure 5.13 Incompatible flows. Reverse flow in the decoupler dilutes theflow temperature

Page 90: Building control system, aplication guide   cibse guide

Hydraulic circuits may be designed and analysed using theprinciples of network analysis(14). Resistances of pipeworkand components may be estimated from dimensions ormanufacturer’s data; see CIBSE Guide C4(15). Flow rates arecalculated from the fundamental equation

ΔP = RM2

where:

M is the mass flow rate (kg/s)

R is the resistance (Pa s2/kg2)

ΔP is the pressure differential (Pa).

This differs from the familiar Ohm’s law. In a hydrauliccircuit the pressure drop is proportional to the square of themass flow; this has the consequence that resistances inseries are simply added, but two resistances in parallel arecombined according to the relation

R =

Thus if two resistances of value R are connected in parallel,the combined resistance is only 0.25R. Using the basicequation and the requirement that mass flow is conservedgoing round the circuit, it is possible to calculate flows andpressure drops at all parts of a circuit. Various tools areavailable to perform this(14). A network analysis should becarried out at the design stage whenever possible, payingattention to the behaviour of the system at part load. As willbe seen in later sections, modulation of individual two-portvalves may result in over or underflow in other sectionswhich cannot be corrected.

5.4.2 Basic circuits

Four basic types of secondary circuit are described in thefollowing sections. A fuller analysis may be found inPetitjean(16) and Seyfert(7). Valve selection and sizing followthe general principles set out above. In general, severalsecondary circuits may be fed off a single primary circuit,each of which is independently controlled by the demandsof the zone or space being conditioned. The manner inwhich the circuits interact under part load conditions is ofgreat importance to the design and successful operation ofthe system. Variable-flow systems present their owndifficulties, which are considered separately.

5.4.2.1 Diverting circuit

Figure 5.14 shows a mixing valve installed in a divertingcircuit. Several similar secondary circuits may be fed fromthe primary circuit, and the flow of fluid through each ofheat exchangers under full flow conditions may bebalanced by positioning a regulating valve as shown. Theuse of a three-port valve ensures that the total flowthrough the secondary circuit, i.e. heat exchanger andbypass, remains approximately constant at all valvepositions. Note that the regulating valve is in a constant-flow section of the circuit. The control valve is selectedand sized as described in 3.3.4 above, aiming at a valveauthority of 0.5. The diverting circuit has the followingcharacteristics:

— Flow is constant in the primary circuit.

— There is constant temperature, variable flow in theheat exchanger.

— Variable flow in the heat exchanger may give pooroperation, e.g. stratification.

— System remains balanced as individual loads vary.

— Full pumping load is maintained at low demand.

— Use of a diverting valve possible: a mixing valve indiverting application is usually preferred.

— A secondary pump is not always required.

5.4.2.2 Mixing circuit

In this circuit, the entire volume of water in the secondarycircuit is pumped through the heat exchanger, and controloccurs by mixing the water to modulate the temperature inthe heat exchanger. The advantage of a mixing circuit overa diverting circuit is the even emission of heat over theentire surface of the heat exchanger, resulting in a smalltemperature gradient in the secondary medium; thecontinuous movement also reduces the risk of freezing inan air coil. The simple circuit shown in Figure 5.15 worksbest when there is little or no pressure drop between theflow and return pipes of the mixing circuit. A primarypump is not always necessary on small systems, providedthat the requirements for minimum flow in the boiler aremet; boiler protection can be provided by switching off theboiler when heating demand is satisfied, in conjunctionwith pump overrun and temperature interlocks. If aregulating valve is required to balance the secondarycircuits it should be placed in the constant flow section asshown. The simple mixing circuit has the followingcharacteristics:

— There is variable flow in the primary circuit.

— Constant flow through heat exchanger gives eventemperature distribution.

— Can provide secondary circuits operating atdifferent temperatures.

— Primary pump may not be necessary in smallsystems.

R1R2

R1 + R2 + 2 R1R2

Control strategies for subsystems 5-15

����

Figure 5.14 Diverting circuit with mixing valve

Page 91: Building control system, aplication guide   cibse guide

— There is full pumping load at part demand.

— There is an extra cost of secondary circulatingpumps.

— Boiler protection at low demand is required.

In some heating systems, there is a requirement that themaximum flow temperature in the secondary circuit shouldbe limited to a value below that of the primary flowtemperature. This can be done by installing an internalbypass to the mixing circuit, as shown in Figure 5.16; thistype of circuit is sometimes known as a dual mixing circuit.The regulating valve in the secondary circuit limits theflow through the heat emitter. The valve in the internalbypass is adjusted with the three-port mixing valve fullyopen to provide the required mixing of primary andsecondary bypass flows which will provide the desiredmaximum secondary flow temperature. An application ofthis circuit is given in 5.4.6 on underfloor heating.

The mixing circuit works best where the primary flow andreturn pipes are at approximately the same pressure. Wherea primary circulation pump is used, this situation may be

achieved by the use of a hydraulic decoupler. If a pumpedprimary loop with a pressure drop between flow and returnis required, then an injection circuit may be used, asdescribed in 5.4.2.3 below. Otherwise, a local low-lossheader can be incorporated as shown in Figure 5.17. Thisresults in a constant flow in the primary circuit. Anotherapproach is to use a differential pressure control valve(DPCV) across the secondary circuit to limit the pressuredrop seen by the three-port mixing valve. The action ofDPCVs is discussed in more detail below in 5.4.5.5.

5.4.2.3 Injection circuit

The use of an injection circuit gives greater separationbetween primary and secondary circuits (Figure 5.18). Itrequires sufficient pressure difference between the primaryflow and return pipes to provide flow through the controlvalve. The secondary circulation pump pumps watercontinuously through the load. When there is no demandfor heat, the control valve is closed and primary water flowsvia the bypass circuit through the control valve and back tothe connection point on the primary return. When thecontrol valve opens, a volume of water is injected into thesecondary circuit and the equivalent amount leaves thesecondary circuit via the control valve. Both primary andsecondary circuits have constant flow rates. A regulatingvalve should be placed at every branching point in theprimary circuit; a regulating valve may also be used in thesecondary circuit to achieve the desired flow rate. The sizeof the control valve is determined from the nominal flow inthe secondary circuit, calculated from the nominal heatoutput of the heat exchanger and the temperature dropacross it, and the available differential pressure between theconnection points on the primary flow and return legs.The variable-flow section, which is normally relevant to thecalculation of valve authority, is the section between theprimary and secondary bypasses; these resistances arelikely to be negligible and valve authority will be high.With this form of circuit, correct hydraulic layout isimportant to avoid parasitic or single pipe circulation in theconnection between primary and secondary circuits.Injection circuits are not suitable where it is important toavoid cross-contamination between primary and secondary

5-16 Building control systems

Figure 5.15 Mixing circuit

Figure 5.16 Mixing circuit with internal bypass. Used to providetemperature gradient between primary and secondary circuits

Figure 5.17 Mixing circuit incorporating low loss header. Suitable for usewith constant flow pumped primary circuit

Page 92: Building control system, aplication guide   cibse guide

circuits, or where the primary circuit uses mediumtemperature hot water (MTHW) or high temperature hotwater (HTHW) and the consequences of valve failure wouldbe unacceptable. In these situations a heat exchangershould be used to separate primary and secondary water.

Injection circuits have the following characteristics:

— Flow in both primary and secondary circuits isconstant.

— Primary and secondary circuits are independent.

— Require sufficient pressure differential betweenprimary flow and return.

— Suitable for district heating.

5.4.2.4 Throttling circuit

The use of two-port valves offers a cost saving over divertingor mixing valves. In Figure 5.19, the two-port valve controlsthe flow of water in the secondary circuit. Flow in the heatexchanger is at constant temperature, variable flow, withthe possible problems of stratification. There are someproblems in providing suitable valve authorities inthrottling circuits. Figure 5.20 shows a ladder arrangementof multiple secondary circuits controlled by two-portvalves, with illustrative pressures shown to demonstrate theregulation problem. The figures are based on a pump

producing 100 units of pressure, loads requiring a pressuredrop of 10 units at design flow and connecting pipeworkproducing a pressure drop of 10 units between legs. In orderto equalise conditions between the secondary circuits it isnecessary to add regulating valves as shown. The regulatingvalve in the index leg, i.e. the leg furthest from the source,remains fully open while the others are adjusted to giveequal flow in all legs. Valve authority is calculated as theratio of pressure drop across the control valve (10 units) tothe pressure drop across the part of the circuit with variableflow (100 units). In this case, the entire primary circuit flowis variable, resulting in low valve authorities of 0.1, wellbelow that recommended for good control. The reversereturn arrangement shown in Figure 5.21 has the advantageof using the flow and return pipework itself to balance theflows, but results in similar low authorities. Authoritiescould be increased by installing smaller valves, but with aconsequent rise in pump head and energy consumption.Since the flow in the primary circuit is controlled by thethrottling valves, provision must be made to ensure thatadequate flow through the boiler is maintained or someother form of boiler protection provided. The use ofvariable-speed pumping overcomes some of the problemsassociated with the use of two-port valves and is consideredseparately in 5.4.5 below.

The characteristics of throttling circuits are:

— Flow in both primary and secondary circuits isvariable.

Control strategies for subsystems 5-17

Figure 5.18 Injection circuit Figure 5.19 Throttling circuit with two-port valve

Figure 5.20 Throttling circuits inladder configuration. Pump develops100 units of pressure

Page 93: Building control system, aplication guide   cibse guide

— Hydraulic balancing of circuits is required.

— Secondary circulation pumps not necessary.

— There is low valve authority.

— Pumping cost is possibly high.

— Cost of valves is lower compared with three-port.

— Boiler protection is required.

— Consider variable-speed pumping.

5.4.3 Primary circuits: boiler andchiller connections

A hydraulic heating or cooling system typically consists of acentral source of hot or chilled water which is circulated ina primary system. A number of separately controlledsecondary circuits obtain the necessary hot or chilled waterfrom the primary circulation main. Secondary circuitsusually fall into one of the main categories described above.Here we deal with some aspects of the primary circuits,which are described in terms of boilers. Chillers follow thesame basic principles.

5.4.3.1 Central heating without primarypump

A central heating system employing secondary mixingcircuits fitted with their own circulation pumps candispense with the need for a primary pump; see Figure 5.22.The secondary pumps provide the pressure required tocirculate water through the boiler circuit. This layoutproduces a variable flow in the boiler circuit and at times oflow demand the water returned to the boiler will fall involume and temperature. Some boilers require a minimumboiler return temperature to prevent condensation. This isknown as back-end protection and can be achieved by theincorporation of a boiler circulation pump. A non-returnvalve is incorporated to prevent reverse flow when theboiler circulation pump is off.

5.4.3.2 Low pressure header system

All secondary circuits are connected to a distributionheader. The header may be at some distance from the boilerbut the header itself is of sufficient size to ensure that thereis little pressure drop over its length; there should benegligible pressure difference (<500 Pa) between theconnection points of the secondary circuits. The flow and

return headers are connected at the far end by a hydraulicshort circuit. A secondary circulation pump is required foreach secondary circuit. Figure 5.23 shows connections for aradiator zone and a calorifier. The low resistance of theheader means that only the resistance of the secondarycircuits beyond the connection points need to be taken intoaccount when calculating valve authorities; it is notnecessary to include the resistance of the boiler andprimary piping. The resistance in the primary circuit mustbe matched to the capacity of the primary pump byinstalling a regulating valve close to the primary pump;alternatively a variable-speed drive may be used forregulation. The flow rates in the primary and secondaryloops must be set to avoid problems with incompatibleflows; see 5.4.1 above. An example of a potentialincompatibility is illustrated in Figure 5.24(17). If the right-hand secondary circuit has too great a flow rate, there willbe a reverse circulation between the connection points Band A, with the results that the right hand secondary circuitis supplied by its own return.

5.4.3.3 Hydraulic decoupling

Higher operating efficiencies may be obtained bydistributing heating loads over several boilers; this allows

5-18 Building control systems

Figure 5.21 Throttling circuits inreverse return configuration

Figure 5.22 Boiler protection circuit

Page 94: Building control system, aplication guide   cibse guide

some boilers to be switched off at part load operation.Boiler sequencing is considered in more detail in 5.2.2. Theuse of multiple boilers with a variable-volume primarycircuit produces a need to decouple primary and secondarycircuits. This is achieved with a hydraulic decoupler, orbuffer vessel, which is basically an upright pipe with fourconnections. The boiler pumps deliver water to thedecoupler; in the absence of heating demand the entirevolume passes down through the decoupler, which acts as abypass. The decoupler consists of an upright pipe, whosebore should be about three times that of the connectedsupply pipes. This ensures a low flow rate and negligiblepressure drop in the decoupler; the upright mounting, withflow entering at the top, prevents internal thermalcirculation. The design should be such as to minimise anyturbulence which might induce mixing between flow andreturn. To prevent dilution of the flow by return water theprimary flow must be greater than the secondary flow; see5.4.1 on compatible flow rates. Boiler operation iscontrolled from a temperature sensor which is located nearthe top of the decoupler. A variety of secondary circuits may

be used. Figure 5.25 shows simple mixing circuits on thesecondary. The decoupler is applicable to primary circuitswith variable-speed pumping (see 5.2.2.4).

5.4.4 Calorifiers

Calorifiers are devices by which secondary hot water isheated by higher temperature primary water or steam.Storage calorifiers are in widespread domestic andcommercial use for hot water services. A non-storagecalorifier acts as a heat exchanger and is used to transferheat from a high temperature circuit to a lower temperaturesecondary water circuit. Injection circuits provide analternative to the use of a non-storage calorifier and areincreasingly used for this purpose. A non-storage calorifieris essential where the high temperature source is steam orwhere it is necessary to separate the primary and secondarywater circuits, such as swimming pool applications.

The circuit for a non-storage calorifier is shown in Figure5.26. The secondary circuit may be for the provision of hotwater services or an LTHW heating circuit. Where a non-storage calorifier is used for HWS, the secondary circuit willalways be of the pumped circulation type, where hot wateris pumped continuously round the distribution circuit, tomake hot water instantaneously available at the taps. Thetemperature of the secondary flow leaving the calorifier iscontrolled by modulating the primary flow in the heatexchanger using a three-port mixing valve in divertingapplication; where the primary circuit uses steam, a two-port valve in the primary flow is used. An additional two-port isolating valve is fitted to the primary flow to providetight shut off of flow to the calorifier. This ensures thatthere is no overheating or boiling in the calorifier, whichmight otherwise be caused by a control valve which did notclose tightly.

The calorifier control is initiated by a demand signal fromthe secondary circuit. The origin of this signal depends onthe application. It is likely to be a time schedule signal forHWS, or a heating demand for LTHW application. On receiptof the signal, the secondary pump is started and when flowhas been proved, the primary circuit isolating valve opensand the control valve modulates to control the secondarywater flow temperature at the required set point. If the highlimit thermostat is activated, the three-port valve bypasses

Control strategies for subsystems 5-19

Figure 5.23 Low pressure header system

Figure 5.24 Incompatibility in a lowloss header. Mismatch of flows mayresult in circulation from B to A

Page 95: Building control system, aplication guide   cibse guide

the calorifier and the isolating valve is shut. The high limitthermostat requires manual resetting. The same actions aretaken by the control system if a failure signal is receivedfrom the secondary pump. When the demand signal ceases,the isolating valve is closed and the three-port control valveset to bypass the calorifier. The secondary pump continuesto run during the pump overrun period and then is turnedoff; this minimises any risk of boiling due to residual heat.

The primary heat generator which supplies the primary hotwater may also supply heat to other systems in the building.The secondary demand signal enables the heat generator.During start-up conditions, the heat load on the secondary

circuit may be such that the calorifier remains cool,resulting in a return of cool water in the primary circuit;this may pose a risk to the boiler. In this case, it is possibleto control valves in the circuits supplied by the secondaryloop to remain in full bypass until the primary returntemperature has reached an adequate temperature,whereupon the system switches to normal operation. Thisallows the primary circuit and boiler to reach operatingtemperature as quickly as possible.

Storage calorifiers are generally used for the provision ofhot water services and a typical circuit is shown Figure 5.26,using LPHW in the primary circuit. Control of the stored

5-20 Building control systems

Figure 5.25 Two-boiler system withhydraulic decoupling

Figure 5.26 Control of calorifiers

Page 96: Building control system, aplication guide   cibse guide

water temperature uses on/off control, with a widedifferential of up to 10 K. The heating demand is activatedwhen the stored water temperature is below the lowertemperature limit and the HWS time schedule is on. Theisolating valve opens and the three-port valve opens fully tosend primary water though the heating coil. This continuesuntil the stored water has been heated to the uppertemperature limit, when the valves close. The three-portvalve does not modulate and operates fully open or closed.A high limit thermostat is fitted at high level in the storedwater and is typically set to 90ºC. If this temperature isexceeded, the isolating valve is closed to prevent primarywater entering the calorifier. If a secondary circulationpump is fitted, it should overrun for 5 minutes. Thethermostat requires manual resetting. Stored water systemsshould always be designed to reduce the risk ofLegionnaires’ disease and the matter is dealt with in CIBSETM13(8) and HSG 70(9). One requirement is that the storedwater should be heated to a minimum of 60ºC . HWS areoften a major source of energy wastage, particularly withlarge centralised systems. BRESCU GIR 40(4) givesrecommendations for efficient design and operation.

5.4.5 Variable-volume systems

5.4.5.1 Pumping energy requirements

For a conventional heating system using pumpedcirculation of heating water, it has been estimated thatenergy used in the pumps represents some 2% of the totalheating energy consumption and 7% of the energy cost(18).Constant-volume systems operate the pumps at constantspeed irrespective of system load requirement and usethree-port valves to control the flow of fluid through theheat emitters. This has advantages in simplifying controland balancing problems at part load, but means that there isno reduction in pumping energy at part load. A variable-volume system, where the pump speed is reduced at lowdemand, offers the opportunity to save a substantialamount of pumping energy. With zero static delivery head,the power input to a pump varies as the cube of the flow. Inpractice, efficiency variations of pump and drive will affectthis, but there are still substantial energy savings to bemade.

Figure 5.27 illustrates the difference in controlling flow bythrottling valve or by variable speed. Full flow of the system

under consideration occurs at point A where the pumpcurve and system curve intersect. In a properly designedsystem, this occurs at a position where the pump isoperating at near maximum efficiency. A reduction insystem flow may be achieved by increasing the resistance inthe circuit using a two-port throttling valve. The systemcurve becomes steeper and a new operating point B isachieved. The same reduction in flow can be achieved byreducing the speed of the pump. The pump curve ischanged to the lower dotted line and now intersects theoriginal system curve at C. The two operating positions Band C have the same system flow, but require differentpower inputs to the pump. The pump power is given by

pump power = (pump head × flow rate)/(pump efficiency × drive efficiency)

Pump efficiency is a function of pump speed and flow. Itshows little reduction over the upper portion of the speedrange, but rapidly decreases as the speed falls below about60% of the design value. The efficiency of the variable-speed drive also varies with speed. The overall relationbetween power consumption and flow is shown in Figure5.28. With fixed-speed pumping and a throttling circuitthere is some reduction in power consumption at reducedflow rates, while substantial reductions may be achievedwith a variable-speed pump motor. With constant-flowthree-port regulation there is no reduction in pumpingpower consumption.

The above considerations apply to system regulation as wellas control. A variable-speed drive can be used whencommissioning the system to provide design flowconditions at reduced pump speed, without the use of aregulating valve. This solution will use less pumping powerthan using a regulating valve with the pump running at fullspeed.

The selection of the optimum system for reducing energycosts is a function of several parameters. The extent of thesavings will vary with:

— the degree of pump turn-down

— the gradient of the pump pressure/flowcharacteristic curve

— the gradient of the system curve

— reduction in static delivery head

— run time at different speeds

— energy costs

— variation in pump and drive efficiencies.

More information on estimation of savings in running costsis given by ETSU Good Practice Guide No.2(19) andBower(20).

5.4.5.2 Parallel pumping

Two or more pumps in parallel may be used where lightload conditions could overload a single pump and as analternative to fully variable-speed pumping. For any givenpump head, two pumps in parallel provide twice the flow ofa single pump. However, single-pump operation in a systemproduces more than half the flow of dual-pump operation;this is shown by the intersection of the system curve withthe pump curves in Figure 5.29. Typically, a single pump

Control strategies for subsystems 5-21

Figure 5.27 Flow control by throttling and speed reduction

Page 97: Building control system, aplication guide   cibse guide

produces about 80% of the flow with both pumps operating.Operation of the pumps is controlled by measuring thedifferential pressure across supply and return near themidpoint of the circuit. A control with large operatingdifferential or built in time delay may be required toprevent rapid cycling between single and dual operation.

The pumps are connected so that each may be valved off forrepair or replacement. The use of parallel pumps providesprotection against failure of one pump. The remainingpump provides sufficient flow to maintain adequateoperation until the failed pump is replaced. A non-returnvalve is fitted in the discharge of each pump to preventbackflow when one pump is shut down. Parallel pumps aresometimes used where the hydronic circuit is used for bothheating and cooling. Both pumps operate during thecooling season to provide maximum design flow, but onlyone is required during the heating season, since the flowrequirements are then lower.

To ensure satisfactory operation, the pumps should beidentical. If for any reason it is decided to use different

pumps, the composite pump curve should be constructedwith care and all operating conditions examined to avoidpossible undesirable interactions between the pumps(21).Packaged twin pump sets are available which have built-incheck valves; some have unequal-sized pumps to suitdifferent operating modes.

5.4.5.3 Fixed-speed circulating pump

Figure 5.30 shows a heating system consisting of boiler,pump, mains distribution pipes and a number ofsubcircuits. The subcircuits are controlled by two-portcontrol valves which are modulated to satisfy local demand.The circuit is typical of those found in hospitals, schoolsand similar public buildings. The same circuit may be

5-22 Building control systems

Figure 5.28 Pumping power consumption as a function of flow, showing saving from variable speed

Figure 5.29 Parallel pump operation: identical pumps. System operatingpoint with two pumps is at A; each pump operates at B with equal flow.With one pump in operation, flow reduces to point C

Figure 5.30 Fixed-speed circulating pump. Pressure distribution atmaximum (ABDEA) and low demand (ACFGA). Balancing valves notshown.

Page 98: Building control system, aplication guide   cibse guide

applied for chilled water circulation. The subcircuits areconnected in ladder configuration and a pressure–distancediagram can be drawn up to show the pressure distributionat maximum and minimum demand conditions. Atmaximum demand, AB represents the pump head at designflow rate, BD the frictional pressure loss in the flow pipe,DE the pressure loss in the furthest subcircuit and EA thefrictional pressure loss in the return circuit. The circuitfurthest from the boiler and pump is known as the indexcircuit. As heating demand decreases, the two-port valvesin the subcircuits modulate towards the closed position andthe system flow falls towards zero. At conditions of low flowthe pipe pressure drops tend to zero, giving the pressuredistribution ACFG. The pressure drop available acrosseach subcircuit varies with the overall demand on thesystem. The variation is greatest for the index circuit,where the pressure differential varies from the full pumphead to a small amount. This variation makes it impossibleto balance the circuit at all loads.

5.4.5.4 Variable-speed circulating pump

The typical pump characteristics shown in Figure 5.27results in the pressure head across the pump increasing asthe flow though the circuit falls when the throttling valvesmodulate towards the closed position. Savings in pumpingenergy may be achieved if the speed of the pump is reducedat low loads. A common form of control is to reduce thepump speed so as to maintain a constant pressuredifferential across the pump as the flow in the circuitreduces. Circulating pumps are available which incorporatedifferential pressure measurement and variable-speeddrive, providing constant pressure control in a single unit.Figure 5.31 shows the pressure distribution round thecircuit at maximum and low demand. Savings in pumpingenergy are achieved compared with a constant speed pump,but the pressures across the branches are higher thannecessary to achieve the required flows at low loads.

An alternative strategy is to control the pump speed tomaintain a constant differential pressure across the index

circuit. This produces the pressure distribution shown inFigure 5.32. At low loads, pressure across distant branchesis maintained, but branches near to the pump riskstarvation. In neither case is it possible to balance thebranches in such a way that they remain in balance at allloads. The situation is worse when branches modulateindependently. Figure 5.33 compares the two methods ofpump speed control when a single branch modulates shut,for the case of a simple three-branch circuit(22). With pumpdifferential pressure control, a constant pressure ismaintained at the pump. If a branch closes, flow in thecircuit is reduced, giving lower pressure drops round thepipework. The result is higher pressures at the downstreambranches, giving excess flow. The converse takes placewhen differential pressure control at the index circuit isused. Closure of the furthest branch results in reducedpressure and starvation of upstream branches.

Control by pump differential pressure control gives greaterpump energy consumption, but is less likely to producecontrol problems. The recommended practice is to controlthe pump speed by differential pressure measured betweenflow and return, about two thirds of the way between pumpand index circuit. The best position is difficult to predictand is best determined by trial and error. It is good practiceto install additional pressure tappings along the pipeworkso that the effect of different measuring positions may beevaluated.

The difficulties in balancing the systems are caused by thepressure drop round the circuit; without this, all brancheswould operate at the same differential pressure withoutproblem. It follows that the control problems will bereduced by sizing the pipework to give as low a pressuredrop as possible. For systems of any significant size,designers would have to size pipes at less than 100 Pa/mpressure drop to achieve any real benefit(22). This wouldsignificantly increase the pipe diameter and the increase incost is unlikely to be acceptable.

Control strategies for subsystems 5-23

Figure 5.31 Pump differential pressure control. Pressure distribution atmaximum and low demand when the branches throttle evenly

Figure 5.32 Control of differential pressure at index circuit. Pressuredistribution at maximum and low demand

Page 99: Building control system, aplication guide   cibse guide

It is inevitable that modulation of an individual two-portvalve will produce flow variations elsewhere in the circuitand perfect balancing of the system is not possible. Thistopic is discussed by Rishel(23) who recommends thatbalancing valves are not used in such circuits; he states thatbalancing valves will interfere with proper control in someflow conditions and will cause additional consumption ofpump energy. However, this technique produces its ownproblems of unbalanced flow during start-up conditions, asdescribed in 5.4.1. The use of valves with high rangeabilityto cope with the variable conditions is required.

The main advantage in the use of variable-speed pumpingis the saving in electrical energy, but it can introduceproblems of control instability. The interaction of pumpspeed control and the two-port valves may produceinstabilities. The response of the pump speed controlshould be faster than that of the two-port valves; this is nota problem in practice, since the two-port valves aretypically in a control loop which involves a roomtemperature response and is therefore relatively slow. Theuse of automatic differential pressure control valves canavoid many of the problems of balancing or authority andis described below.

5.4.5.5 Differential pressure control valves

A differential pressure control valve is a mechanical devicewhich can automatically control the flow of fluid in a circuitto maintain a constant differential pressure between twopoints in the circuit. Figure 5.34 shows a schematicdrawing of such a valve. It is basically a two-port valvewhose valve spindle movement is operated by a diaphragm.Pressure tappings from the circuit positions whosedifferential pressure is to be controlled are led to oppositesides of the diaphragm, and the out-of-balance force moves

the spindle against the force of a spring until anequilibrium position is established.

Figure 5.35 shows a simple heating circuit with a number ofsecondary circuits connected to the primary circulationsystem in a ladder arrangement. As discussed above, thepressure drop round the primary circuit produces differentpressure drops across each secondary circuit, which willvary with load. By using a differential pressure control

5-24 Building control systems

Figure 5.33 Control of three-branch circuit, showing effect of valve closures

Figure 5.34Differential pressurecontrol valve

Page 100: Building control system, aplication guide   cibse guide

valve in each circuit, it is possible to maintain the pressuredrop across two-port valve and heat emitter at a constantvalue for each secondary circuit. Each two-port valve nowoperates under constant conditions at high authority. Itmay not be necessary to install a differential pressurecontrol valve for each secondary circuit; it is often possibleto install valves at strategic positions where they canprovide suitable control for more than one circuit. Thisarrangement is to be found in large systems and districtheating schemes.

5.4.5.6 Automatic flow-limiting valve

By incorporating a metering orifice into a differentialpressure control valve, the device can be used as a flowlimiter. The differential pressure across the orifice iscommunicated to the diaphragm of a control valve asshown in Figure 5.36. The diagram shows a separatemetering orifice, but in a practical valve the meteringorifice takes the form of an adjustable plug on the oppositeside of the valve seat from the operating plug. If the flow inthe valve rises above the preset limit, the increased pressuredrop across the orifice causes the valve to close, controllingthe flow at the limiting value. At flows below the setamount, the valve is fully open and does not exert a controlfunction. Flow-limiting valves are used where it is requiredto ensure that no secondary circuit can deprive othercircuits of their allocation of circulating water.

In some circuits it is desirable or even necessary to controlboth the maximum flow rate and the differential pressure ineach subcircuit. The reasons for this are:

— Limiting the maximum flow to each subcircuitensures that no circuit can take more water fromthe distribution network than has been designed.

— Temperature control valves in subcircuits requireto work below a maximum pressure differential.This is particularly important for thermostaticradiator valves.

— Subcircuit control valves should not be subjected towildly fluctuating pressure differentials tomaintain reasonable control authority.

The combination of a differential pressure control valveand an automatic flow limiting valve in each subcircuit willachieve the above requirements. However, this will befound too expensive for many applications. It is possible toobtain a valve which combines both functions in a singlebody. Another solution is to incorporate a flow-measuringorifice into the subcircuit together with an adjustabledifferential pressure control valve (Figure 5.37). Duringcommissioning, the differential pressure control valve setpoint is set to a value which is just high enough to producethe design flow rate in the subcircuit, as measured at theflow measuring orifice. This adjustment is performed withany automatic control valves in the subcircuit fully open.The circuit thus operates with the minimum pressure dropacross the load and control valve and the control valveoperates under optimum conditions at all times.

5.4.5.7 Control of minimum flow rate

There is often a requirement to maintain a minimum flowrate through the boilers or chillers. This is usually achievedby the use of separate primary and secondary circuits or theprovision of boiler protection circuits, which werediscussed in 5.2 and 5.3. For the simple circuits describedbelow, there is a single circulation loop. If all the throttlingvalves in the branches close down, the flow falls towardszero. Maintenance of the flow though the boiler may beobtained using a differential pressure control valve as abypass. The DPCV valve operates in an opposite sense to that

Control strategies for subsystems 5-25

Figure 5.35 Differential pressure control valves installed in throttlingcircuits

Figure 5.36 Automatic flow-limiting valve (principle)Figure 5.37 Use of a measuring orifice to set differential pressure controlvalve during commissioning

Page 101: Building control system, aplication guide   cibse guide

described in 5.4.5.5 and opens with increasing pressuredifferential. The valve is installed as a bypass, with thepressure tappings connected across the circulation pump asshown in Figure 5.38. As the throttling valves in thecontrolled circuits close down and reduce flow though thepump, the pump pressure rises and acts to open the DPCV. Itis necessary to use a circulation pump with a relatively steepcharacteristic near the design operating point.

An alternative method is to use a three-port valve indiverting application at the furthest branch (Figure 5.39).This gives a constant flow through the furthest branch,which becomes the minimum circuit flow. As well asproviding a minimum flow through the circuit and boiler,this solution has the advantage in ensuring that there are nodead legs in the system. Another important advantage isthat it helps to reduce pressure variations in the rest of thecircuit when the furthest branch closes down, since this isotherwise the worst case for producing underflows in otherbranches.

5.4.5.8 Design recommendations

The use of variable-speed pumping offers considerableeconomies, both in energy consumption and in the cost ofvalves and associated gear. However, the above discussionhas shown that there are difficulties in achieving suitablevalve authority and maintaining system balance at varyingloads. Further information may be found in theliterature(7,18,.22). Manufacturer’s literature is also a usefulsource of practical advice.

— Control by differential pressure across the pumpdoes not give minimum pumping power and maygive excess flow in downstream branches.

— Control by differential pressure at the index circuitgives least pumping power but risks starvation ofupstream branches.

— Control by differential pressure about two thirds ofthe way between pump and index circuit is a goodcompromise. The best position may be found bytrial and error.

— Balance the system to ensure that the design flow isavailable at all terminals during start-up con-ditions.

— Valves of high rangeability are recommended.

— Size pipework for minimum pressure dropcompatible with cost.

— Valves must be capable of closing against maximumpressure, which may be full pump pressure.

— Network analysis of flows at part load conditions isrecommended.

— The use of differential pressure control valveseliminates balancing problems and gives good valveauthority, but increases costs.

— Use a differential pressure control valve as a bypassor use a diverting circuit in the furthest branch toprovide flow in the circuit when all branches shut.

5.4.6 Underfloor heating

Underfloor heating systems circulate hot water in coilsembedded in the screed of a concrete floor. Systemsemploying heat spreader plates are available for use withtimber floors, but are less common. Comfort considerationsand restrictions on materials limit the flow temperature to amaximum of about 60ºC and the floor surface temperatureto about 30ºC. The normal practice is to design for amaximum floor temperature of 26ºC in the main body ofthe space; higher temperatures may be used in circulationspaces or zones of high heat loss, such as next to large glazedareas. The combination of low floor temperature and thehigh thermal mass of the floor produces a system that isslow to respond to changes in demand. This is compensatedto some extent by the small temperature differentialbetween floor surface and room temperature, whichproduces a degree of self-regulation.

An underfloor heating circuit suitable for general use isshown in Figure 5.40. This employs a primary heatingcircuit which circulates water from a conventional boilerthrough a low loss header. This primary circuit may be usedto provide water for a variety of secondary circuits, such asother heating circuits or an HWS calorifier. The underfloorheating secondary circuit uses constant flow, variabletemperature in the floor coils; this ensures an eventemperature over the heated surface.

5-26 Building control systems

Figure 5.38 Automatic bypass. The DPCV opens to allow flow through thebypass leg as the differential pressure across the pump rises. Thismaintains flow through the boiler as the throttling valves close down

Figure 5.39 Constant flow at furthest branch. Replacing the two-portvalve by a three-port diverting circuit at the furthest branch maintainscircuit flow and reduces pressure fluctuations

Page 102: Building control system, aplication guide   cibse guide

Weather-compensated flow control is used; the flowtemperature is controlled over the range of typically 30 to50ºC as a function of the outside temperature. Control is bya standard weather compensator using PI control tomodulate the three-port mixing valve. The bypass in thesecondary circuit maintains some mixing flow when thethree-port valve is fully open to the high temperatureprimary flow, limiting the secondary flow temperature tothe required maximum value. A room temperature sensorin the occupied space acts as a high limit thermostat todisable the secondary circulating pump. If desired,additional protection can be provided by a high limitthermostat acting on either the floor surface temperature orthe flow temperature. In practice, there may be difficultiesin providing a suitable sensor for use as a floor limitthermostat. If a high limit temperature is exceeded, analarm should be raised by the BMS, since the circuitbalancing or weather compensation characteristic mayneed to be adjusted. Cascade control based on zonetemperature may be used to reset the flow temperature as analternative strategy to the use of weather compensation.This is a higher cost option. The long time constant of theunderfloor heating systems makes them a suitablecandidate for optimum start and stop control.Alternatively, night setback control may be used; for slowresponding systems a setback of 5 K is adequate.

The low flow and return temperatures employed inunderfloor heating makes it suitable for use with a lowtemperature heat source such as a condensing boiler. In thiscase, the heating circuit may form part of the boiler primarycircuit. A simple control strategy can be used, with thecirculating pump running continuously and the boilerswitched on and off or modulated to control the zonetemperature. Where several zones are to be controlled, it iscommon practice to use an outside compensator to providecontrol of flow temperature, plus separate room thermostatsand valves to limit zone temperature.

5.4.7 Thermostatic radiator valves

Thermostatic radiator valves are widely used to providelocal control of heating systems. The valves are self-actingand require no external source of power. The TRV is a two-port throttling valve which fits directly onto the flow orreturn connection of a conventional LPHW radiator. Thehead contains a liquid- or wax-filled capsule, which

expands on a rise of ambient temperature and closes thevalve against spring pressure. The manufacturer’smounting recommendations should be followed to ensurethat the sensing head is properly exposed to roomtemperature. Incorrect positioning will result in the valveresponding to heat from the radiator itself rather than toroom temperature. The valve closes over a proportionalband of about 3 K. However, the lack of valvecharacterisation, the highly non-linear relation betweenflow and radiator heat output and the difficulties ofachieving suitable valve authority mean that the controlcharacteristics are inferior to those obtainable with amotorised valve. The differential pressure against whichthe valve has to close and the flow temperature of thecirculating water both have a small influence on theoperating temperature. Most TRVs are self-contained andcan be fitted as direct replacements for a conventionalradiator valve; variations are available with remote sensingor adjustment. TRVs are also available which may beenabled or disabled by an electrical signal; the headcontains a small heating element which acts to close thevalve when energised. This system may be used for timescheduling or to provide a night setback facility. Heatingcircuits in most commercial buildings are required to useweather compensation under the present BuildingRegulations. In this situations, TRVs act as trimmingdevices, providing local temperature control. They alsoprevent overheating and make effective use of anyincidental heat gains.

A heating system incorporating radiators fitted with TRVsfalls within the category of throttling circuits described in5.4.2.4. However, radiator circuits have characteristics oftheir own and the widespread application of TRV heatingcircuits fitted with TRVs demands special consideration.System balancing is important; without a properlybalanced system it will be impossible to achieve propercontrol. During the warm-up period, all TRVs are likely tobe fully open. If the system is not balanced, the flow thoughthe radiators will be determined by pressure drops in thepipework, since the pressure drop in the radiators is lowand virtually independent of their heat output rating.Favoured parts of the system will receive excessive flow andunfavoured parts insufficient flow. Since heat output from aradiator does not increase significantly at above design flowrates, the overall heat output from the system is belowdesign output. The unfavoured parts of the system will onlystart delivering heat when the TRVs start closing in the

Control strategies for subsystems 5-27

Figure 5.40 Underfloor heating.Water is circulated through the floorcoil at constant flow rate, variabletemperature. Flow temperature iscontrolled by a weather compensator;a floor limit thermostat disables thecirculation pump

Page 103: Building control system, aplication guide   cibse guide

favoured parts. It is therefore important to balance thesystem so that the design flow is available at all radiatorswhen the TRVs are fully open.

TRV systems must be designed to operate successfully underpart load conditions. This may be done by the use of variable-speed circulation pumps, or, if a constant-speed pump is used,by the use of differential pressure control valves. Thesemethods avoid the production of noise in TRVs when subjectedto a high differential pressure, and the difficulties in operationas the pump head increases at restricted flow rates.

Where a constant-speed circulation pump is used, a bypassis provided to provide a circulation loop as the TRVs closeoff. This has the advantage of providing nearly constantflow through the boiler, and is illustrated in Figure 5.41.Flow through the bypass leg is controlled by a differentialpressure control valve, which opens as the pump head risesto maintain a nearly constant pressure differential betweenflow and return to the heating circuit. DPCVs were discussedin more detail in 5.4.5.5. This method of control requires apump with a relatively steep characteristic near the designoperating point.

Where the secondary heating circuit is fed from a primarycirculation circuit with a differential pressure between flowand return of greater than 50 kPa, the circuit of Figure 5.42can be used. The excess pressure is dropped across a DPCVwhich is controlled by the differential pressure across thesecondary heating circuit. This circuit is an example of theuse of automatic throttling valves in series; in general, thisis not advisable because of the risk of instability. However,TRVs have a response time of 15 minutes or more, while aDPCV responds in a much shorter time, resulting in stableoperation.

In both the circuits described, it will be generally be foundsuitable to set the DPCV to control between 10 and 20 kPa;

the setting should be consistent with the design flowthough the radiators and the Kv value of the TRV to ensurethat full flow is available at design conditions. There is arisk of noise being created in radiator valves at differentialpressures of over 30 kPa.

The use of variable-speed pumps has several advantages,including reduction in pumping energy. A radiator systemcontrolled by TRVs is a common example of a variable-volume system. The control of variable-volume systemswas considered at length in 5.4.5. For a large or complexsystem involving TRVs and variable-speed pumping, thissection should be consulted. However, for most simple TRVsystems, it is sufficient to use a circulator pump withintegral differential pressure variable-speed control. Themotor speed is varied to maintain the pump head at thepreset value. The circulators are designed to cope withthe zero flow situation should all TRVs close simultaneouslyand there is therefore no need to provide a bypass valve.The effect on boiler operation of low flow rates must beconsidered.

5.5 Central air handling plantFigure 5.43 illustrates a generalised air handling systemwith recirculation. Not all the components may be presentin any actual system. The basic system is to be found withmodifications in many HVAC systems.

Outside air is filtered, after which it passes to a preheaterwhich serves to protect the rest of the system against lowoutside air temperatures. The air then goes to a mixing box,where it is mixed with a controlled quantity of recirculatedair before being conditioned in the air handling unit. TheAHU contains heating and cooling coils, humidification andthe ability to dehumidify the air. It also contains the mainsupply fan which distributes air to the room terminal units.Supply air at the required temperature and humidity isdistributed into the conditioned zone by room terminalunits. Air is extracted from the occupied zone by the extractfan; the recirculation damper allows a proportion of the airto be recirculated; exhaust air is discharged to atmosphere.There may be supplementary direct extraction from thespace where it is necessary to remove contaminated airdirectly to outside, such as from a kitchen or industrialprocess.

The air handling unit is the heart of a central airconditioning system. Its function is to supply conditionedair at the appropriate temperature and humidity, at therequired flow rate and containing the correct proportion of

5-28 Building control systems

Figure 5.41 Control of radiators by TRVs. Constant-speed circulator. Thedifferential pressure control valve acts as a bypass to control the pressureacross the radiator circuit

Figure 5.42 Control of radiators by TRVs. Pumped primary loop. Thiscircuit is suitable for a mains differential of greater than 50 kPa

Page 104: Building control system, aplication guide   cibse guide

outside air for ventilation. This section deals with thecontrol of temperature and humidity plus the mixing ofrecirculated and outdoor air. The overall control strategywill depend on the type of air conditioning system, mostimportantly whether it is a constant volume or variablevolume system. Control strategies for complete buildingsystems are described in the next section.

5.5.1 Preheat coil

The preheat coil, when fitted, serves to preheat outside airto a minimum temperature before it passes to the rest of theplant. It also provides frost protection against cold airentering the air handling system.

— Protection against freezing. A frost thermostatdownstream of the preheater prevents the supplyfan from operating if it senses a temperaturebelow its set point, typically 3ºC. This overridesany other fan operation signal and raises an alarm.

— Protection of the preheat coil. During periods whenthe air handling plant is not in operation, thepreheat coil is protected against freezing bycirculating water through it. On receipt of a lowoutside air temperature signal or low primarywater return temperature signal, the preheat coilcontrol valve is opened to allow water to circulate.

— Normal operation. During normal operation, thecontrol valve operates under PI control to maintainan off coil temperature at the set point, typically8ºC. In the event of a fan failure, the control valvemoves to full bypass.

Control of preheat may alternatively be by using a face andbypass damper on the preheat coil. Where a preheat coil isnot fitted, it will be necessary to transfer the protectionfunctions to the first coil in the system.

5.5.2 Heating coil

Air heating is typically by an LTHW coil. Figure 5.45shows the coil controlled by a three-way mixing valve indiverting application. In normal operation during theheating season, the valve modulates under PI control. Thecontrolled variable depends on the air conditioning type,and is typically supply air temperature for a VAV systemand zone air temperature for a constant volume system.Cascade control is common, where the deviation from thezone set point is used to reset the supply air temperatureset point, which is controlled by the heating coil. If there is no preheat coil fitted to the intake air duct, thefirst heating coil in the AHU fulfils this function and freeze protection is installed, following the description in5.5.1.

Control strategies for subsystems 5-29

EhA

Figure 5.43 Major components of acentral air conditioning system

Figure 5.44 LTHW preheating coil. Normal mode: three-port LTHW valve ismodulated under PI control to achieve the off-coil set point. Valve closed(full bypass): plant shut-down, OSC or night cooling, cooling operation,economiser cycle. Valve open: low outside temperature, low primary returntemperature, boost, OSH heating, freeze protection

POA

Page 105: Building control system, aplication guide   cibse guide

5.5.3 Cooling coil

Cooling of the supply air is achieved by a chilled water coil,whose operation is basically similar to the heating coildescribed above. Figure 5.46 shows a three-way valvemodulating the flow of chilled water though the coil andalso shows the cooling process on a psychrometric chart.The composition of the air approaching the coil isdetermined by the type of air conditioning system and istypically a mixture of exhaust air and outside air, controlledby mixing dampers described in 5.7.5. At high coolingloads, line 1, the cooling coil is required to cool the on-coilair to below its dewpoint, so that both sensible and latentcooling take place. The coil therefore acts as adehumidifier. In practice, the air leaving the coil will be alittle above the coil temperature and less than 100%saturation. At lighter cooling loads, line 2, sensible coolingonly may be sufficient. The use of cooling coils fordehumidification and the implications of enthalpy controlwill be considered below. Here we treat temperaturecontrol only.

The flow of water in the coil is modulated using the controlvalve, controlled by a PI controller with either supplytemperature (VAV system) or zone temperature (CV system)as the controlled variable. The valve remains in bypassposition if free cooling from an economiser cycle or energyrecovery device is sufficient to provide the cooling needs.

Direct expansion (DX) cooling coils may be used. The coilserves as the evaporator of a refrigeration circuit.Refrigerant flow to the coil is controlled by a two-positionsolenoid valve, which is opened when cooling is required.The thermostatic expansion valve is throttled to maintain aminimum refrigerant suction temperature; the expansionvalve is normally supplied as part of the packaged controlsupplied with the coil. In normal operation the solenoidvalve opens when the controlled air temperature, whichmay be supply or zone temperature, rises above the desiredset point. The thermal expansion valve opens under self-acting control to maintain the refrigerant suctiontemperature set point (see Figure 5.47).

DX cooling differs from that provided by a chilled water coilin that the DX coil temperature is largely determined by therate of heat transfer from the air flow to the coil. In theabsence of sufficient air flow, the coil temperature may

5-30 Building control systems

Figure 5.45 LTHW heating coil. Diagram shows cascade control of supplytemperature reset from zone temperature. Normal mode: three-port LTHW

valve is modulated under PI control to achieve the supply air temperatureset point. Valve closed (full bypass): plant shut-down, OSC cooling, nightcooling, cooling operation, economiser cycle. Variations: the heating coilcontrols zone temperature directly. Freeze protection if no preheat coil

Air temperature (°C)

Figure 5.46 Chilled water cooling coil. (a) Control of zone temperature;there is no dehumidification control. Normal operation: three-port chilledwater valve is modulated under PI control to achieve the desired set pointtemperature in the controlled zone. Valve closed (full bypass): plant shut-down, OSH or boost heating, night cooling. Valve open: OSC cooling.Variations: control of supply air temperature is required for VAV systems.Existence of cooling demand from zone may be used to enable mainchilled water plant. (b) Cooling coil psychrometrics. Line 1: high coolingload: both sensible and latent cooling. Line 2: low cooling load: sensiblecooling only

Figure 5.47 Direct expansion (DX) cooling coil. Refrigerant flow iscontrolled by a two-position refrigerant solenoid valve; the thermostaticexpansion valve (TEV) controls the suction temperature Trefrig directly. Thelow limit thermostat prevents the off-coil temperature falling too low.Normal operation: refrigerant valve opens when the controlled airtemperature rises above the set point. Valve shut: plant shut-down, OSH orboost heating, night cooling, low limit. Valve open: OSC cooling (low limitstat remains operative)

Page 106: Building control system, aplication guide   cibse guide

reach excessively low levels. The use of face and bypassdampers with a DX coil is not recommended because of thedanger of ice formation. In general, a DX coil is capable ofcooling to low temperatures and an off-coil air temperaturelow limit interlock prevents the supply air from becomingtoo cold.

5.5.4 Humidification

Indoor air humidities may fall to low levels during theheating season, when the moisture content of the intake airis low. If considered necessary, zone air humidity may beraised by:

— Direct humidification. Moisture is introduceddirectly into the controlled space. This method ismost commonly found in industrial andhorticultural applications. It may be used where asingle zone requires control, such as a computersuite. Portable room humidifiers operating undertheir own humidistat are readily available.Independent humidifying units designed forceiling installation can be used; these have a formsimilar to a fan coil unit and are designed forinstallation above a suspended ceiling.

— Indirect humidification. Moisture is introduced intothe supply air at the AHU or elsewhere in the supplyductwork. This is the most common system for airconditioned buildings.

Some humidifiers, known as storage type, utilise a reservoirof water whose level is maintained using a ball valve orsimilar. The water is circulated in the supply air streamusing a washer or sprayed coil to assist evaporation;unevaporated water is returned to the reservoir and re-used.Storage type humidifiers have been associated with healthrisks and their use is generally not recommended(24). Non-storage humidifiers operate so that all the water isevaporated in the air stream and there is no reservoir whichcould harbour contamination. The major types ofhumidifier are:

— Steam injection. Steam from a local generator isinjected into the supply air duct. It is possible to usesteam from a central plant, but this is less common.

— Atomised spray. Fine droplets are generated fromclean cold water and injected into the supply air,where they evaporate rapidly. Droplet generation isby an ultrasonic nebuliser or by using an airpressurised nozzle. Any dissolved solids present inthe water supply will become airborne and waterpretreatment may be advisable.

The two systems are compared on the psychrometric chartin Figure 5.48. Steam injection increases humidity withlittle or no warming effect (line 1). In contrast, the atomisedspray humidifier is an adiabatic process and moves thesupply air along a line of constant wet bulb temperature,thus producing a cooling effect. The direct operating cost ofan atomising humidifier is much less than that of a steamhumidifier, but adiabatic humidification reduces thetemperature of the supply air and in most situationssensible heat must be added to restore the temperature (seeline 2).

Figure 5.49 shows a steam humidifier controlling humidityin the occupied space. Steam is injected in the supply air

downstream of the rest of the main AHU. The humidifiermay be modulated continuously or in stages. Control of thehumidity is achieved via a sensor which is positioned eitherin the controlled zone itself or in the extract air stream. PIcontrol is used to modulate the humidifier. Response of thehumidity in the zone to changes in output is slow; theabsorption and release of moisture by the building fabricimposes a substantial inertia on the system. The settings ofthe PI controller must reflect this. A relative humiditysensor is used, with control on relative humidity. Toprevent any risk of condensation in the supply ducting ahigh limit humidity sensor is positioned in the supply duct.This limits the humidifier if the supply RH rises above ahigh limit, typically 80% RH. The steam humidifier isenabled during normal operation provided that operationof the supply fan is proved. At all other times it is disabled.

The control strategy for an atomising humidifier isessentially the same as for the steam humidifier. The air iscooled by the humidifying process; this represents anadditional heating load on the system and should be

Control strategies for subsystems 5-31

Air temperature (°C)

Figure 5.48 Humidification processes. It is required to humidify air frompoint A to B. Steam injection increases moisture content with littleincrease in dry bulb temperature, line 1. An atomising device humidifiesalong a line of constant wet bulb temperature, requiring the addition ofsensible heat, line 2

Figure 5.49 Steam humidification. Control of the humidifier is by PI

control on the RH in the controlled zone. A high limit stat in the supplyduct prevents condensation. Normal operation: supply of steam ismodulated by a PI controller which controls RH in the occupied space.Humidifier disabled: at all times other than during normal operation withthe supply fan proved. Variations: control may be on return air RH from thecontrolled zone

Page 107: Building control system, aplication guide   cibse guide

automatically dealt with by the temperature control system.A low limit thermostat may be installed in the ductdownstream of the humidifier to bring in extra heating ifthe temperature falls too low; this is in addition to the highlimit humidistat which is designed to prevent condensationin the ductwork.

5.6 Energy recoveryIt is possible to recover energy from the exhaust air streamwhich would otherwise be discharged to atmosphere andtransfer it to the intake air stream. Such devices may beused on full fresh air systems or between the exhaust andintake air streams of a recirculating system. Use of a heatrecovery system makes it possible to use a full fresh airsystem without serious energy penalty, in situations whereit is required to avoid recirculated air for hygienic or otherreasons. Three major types of heat recovery system are inuse and are listed in Table 5.4 with their characteristics.Energy recovery devices can be used during both heatingand cooling modes of building operation. However, in theUK climate the periods during which exhaust air isdischarged at a temperature appreciably below ambient arerare and so the application of energy recovery duringcooling is limited. The table shows temperature efficienciesduring heating operation; temperature efficiency is ameasure of the effectiveness of the heat exchanger inrecovering sensible heat. The energy recovery depends onthe relative mass flows in the two air streams as well as onthe temperature efficiency of the device. The efficienciesmust be regarded as approximate and will vary with themake and model of the equipment. Efficiencies willgenerally be lower for cooling operation and lower again ifenthalpy recovery is considered. When considering theoverall cost benefit of a heat recovery installation, therunning cost as well as capital cost must be considered. Inaddition to the operating cost of the pump or wheel motor,the devices introduce an extra resistance to flow in the airsystem, thus increasing fan costs. A comprehensivetreatment of air to air heat recovery is given in an ASHRAEHandbook(25).

Another, the regenerative heat exchanger, operates byperiodically reversing the two air flows over a heatabsorbing mass. This type of device can achieve highoperating efficiencies, but is more often found in processindustries than in HVAC systems. Units are available whichcombine a plate heat exchanger with a heat pump; a smallheat pump is used to transfer additional heat from theexhaust air, downstream of the heat exchanger, to thesupply air. Such a unit is capable of discharging exhaust airat below outdoor ambient temperature and thus acts as a netsupplier of heat to the supply air.

The thermal wheel and run around coil devices both requirea power input for their operation (and supply and extract fansmay use more power to maintain the design supply flow) and,for it to be worthwhile switching the unit on, the cost ofoperating the device must not exceed the worth of the energytransferred. This equation must be evaluated in financialterms, since the unit costs of the input power to the device andof the heat energy are unlikely to be the same. From this, atemperature differential, both positive and negative, betweenextract and intake air streams is calculated, below which it isnot worthwhile operating the energy recovery device. Whenin operation, the rate of heat transfer between the two airstreams may be controlled up to the maximum value of whichthe device is capable. There is a limited range of temperaturedifference between the air streams where the energy recoverycan be varied to control the supply temperature without anyadditional heating or cooling. Outside this range, when thewheel has either reached maximum speed or stopped, themain plant is brought into play for temperature control. Thecontrol strategy for a variable-rate heat recovery device issimply summarised in Table 5.5.

5.6.1 Thermal wheel

The thermal wheel is a type of regenerative heat exchangerconsisting of a shallow drum which contains a matrixcapable of absorbing and releasing heat. The opposing airstreams pass through the slowly rotating drum in an axialdirection. Thus the packing absorbs heat as it passesthrough the exhaust air stream and subsequently releases itto the cooler intake air. Figure 5.50 shows a thermal wheel

5-32 Building control systems

Table 5.4 Energy recovery devices

Type Temperature Contiguous Control Cross-efficiency air streams contamination

Thermal wheel < 80% Yes Speed Possible

Plate heat < 70% Yes Face and Noexchanger bypass

damper

Run-around < 65% No Pump speed Nocoil or valve

Table 5.5 Control strategy for heat recovery devices

ΔT betweenair streams Control mode

Large Energy recovery device operates to give maximum heatrecovery. Control of supply temperature by HVAC plant

Medium Control of supply air temperature achieved by modulatingrate of heat recovery. No heating or cooling by HVAC plant

Small Energy recovery not viable. Device remains off and controlof supply air temperature is by HVAC plant as required

SA

Figure 5.50 Thermal wheel heat recovery, variable speed. The wheel isenabled when the temperature differential (TEtA – TOA) is sufficient tojustify operation. Normal operation: rotation of speed wheel is modulated tocontrol supply or zone air temperature. Further temperature control in theAHU is enabled when wheel is at zero or maximum speed. Normaloperation also during OSH heating or cooling or boost. Wheel disabled: plantshut-down or night cooling

Page 108: Building control system, aplication guide   cibse guide

used to transfer energy between extract and intake airstreams. The wheel may be constructed so as to transferlatent as well as sensible heat, by coating the heat absorbingmatrix with a hygroscopic substance. The wheel is drivenby a variable-speed motor and to be effective, the cost ofoperating the wheel must not exceed the worth of theenergy transferred. When in operation, the rate of heattransfer between the two air streams is an increasingfunction of the rotational speed of the wheel, up to amaximum speed above which there is only a negligibleincrease. When the wheel is in operation, there is a limitedrange of temperature difference between the air streamswhere the rotational speed of the wheel can be varied tocontrol the supply temperature without any additionalheating or cooling. This is realised using a PI controller tomodulate the speed of the wheel, with either the supply orzone temperature as controlled variable. Outside this range,when the wheel has either reached maximum speed orstopped, the main plant is brought into play fortemperature control.

Control interlocks follow the expected pattern:

— The wheel only operates when the main supply fanis running.

— The wheel is enabled when the BMS is signallingnormal operation, optimum start heating orcooling, or boost operation.

— The wheel is disabled during night cooling or whenthe air handling system is shut down.

An alternative configuration for a thermal wheel uses aconstant speed of operation of the wheel and varies the rateof heat transfer between air streams by use of a face andbypass damper. The control strategy is the same as forvariable-speed operation.

5.6.2 Run-around coils

Run-around coils may be used when the intake and exhaustducts are not adjacent to each other and when the potentialenergy recovery is sufficient to justify the extra initial andrunning cost. It has the additional advantage of preventingany possibility of cross-contamination. Figure 5.51 illus-trates the control set-up of a pair of run-around coils. Thetwo coils are connected with counterflow piping, with apump circulating water, glycol or other thermal fluidaround the circuit. There is a risk of icing on the exhaustcoil if the solution entering falls to freezing point; thecontroller ensures that the solution entering the coil doesnot fall below a minimum temperature set point, typically2ºC. Control of the rate of energy recovery may be by abypass valve, as shown, or by variable-speed pump. Thecontrol strategy follows the same lines as that described forthe thermal wheel. The pump only operates if thetemperature differential between intake and extract air isgreater than a predetermined amount. The rate of heattransfer is modulated to control the supply air temperatureup to the maximum possible, when the plant is brought into provide the necessary heating or cooling.

5.6.3 Fixed plate heat exchanger

Fixed plate heat exchangers are available in a number ofconfigurations. They require the two air streams to be

brought together. Apart from any penalty due to thepressure drop though the heat exchanger, no externalpower is required for operation, so the minimum viabletemperature difference described above is not relevant. Ifcontrol of the rate of heat transfer is required, this may beobtained using a face and bypass damper system as shownin Figure 5.52. The control strategy for modulating the rateof heat transfer is exactly as described above for the thermalwheel with face and damper bypass. A pressure differentialswitch across the plates is used to provide an alarm in thecase of a blocked or frozen heat exchanger.

Control strategies for subsystems 5-33

Figure 5.51 Run-around coil. Heat is transferred from the warmer to thecooler air stream. Normal operation: the pump is enabled when thetemperature difference (TEtA – TOA) is sufficient to justify operation. Thethree-way valve is modulated to control the supply air temperature.Further temperature control by the AHU is enabled only if the pump is offor the valve is fully closed to the bypass. Normal operation also during OSH

and boost heating, OSC cooling. Pump off, valve to bypass: plant shut-downor night cooling

Figure 5.52 Fixed plate heat exchanger with face and bypass dampers.Heat recovery from warmer to cooler air stream via a fixed plate heatexchanger. Control is shown using face and bypass dampers in the intakeair stream. A differential pressure sensor across the exhaust section warnsof blockage due to icing. Normal operation: dampers modulate the flow ofair through the HEX to obtain the supply air set point; the face and bypassdampers move in opposition. Further temperature control by the AHU isenabled when the face damper is fully open or closed. Dampers modulateduring OSH or boost heating and OSC cooling. Face damper open: plant shut-down. Face damper closed: night cooling

Page 109: Building control system, aplication guide   cibse guide

5.7 Mechanical ventilationAll occupied buildings require a supply of outside air forventilation purposes. A minimum supply of air is necessaryfor the removal of odour, carbon dioxide and any othercontaminants produced by human occupation and otheractivities. The build-up of carbon dioxide and water vapourare normally the two most important determinants of thenecessary ventilation rate. Other contaminants havereceived a great deal of attention in the context of sickbuilding syndrome but as yet there is no reliablemeasurement which would allow automatic control ofventilation for indoor air quality. Minimum outdoor airrequirements are set out in the CIBSE Guide Part A1(26);international legislation is reviewed by Olesen(27). In theabsence of smoking, an outside air supply of 8 l/s per personis found sufficient to maintain acceptable air quality. Insituations of low occupancy, emission of volatile organiccompounds (VOCs) from building materials becomes thedominant air pollutant and it is good practice to set aminimum outside air supply rate of about 20% of themaximum value; this will provide acceptable air quality inconditions of low occupancy. Where ventilation withoutside air is closed down during unoccupied hours to saveenergy, ventilation should be restarted before thebeginning of the occupied period. The pattern of airmovement in the ventilated space affects the ventilationefficiency, which may be defined as the ratio of contam-inants in the extract air to that in the occupied region(28). Afully mixing ventilation system has an efficiency of unity. Apoor system, where the supply air short circuits the roomand moves directly towards the extract, has an efficiency ofless than one. A displacement ventilation system, where theincoming air moves over the occupants before picking upcontaminants and removing them via the extract, can havean efficiency of greater than one.

Ventilation also has an important part to play intemperature control. In the absence of heating, indoor airtemperatures are generally higher than outdoor ambienttemperature as a result of solar gains and heat-generatingactivities in the building. Increasing the ventilation ratetherefore dissipates heat gains and can reduce indoor airtemperature towards a limiting value equal to the outdoortemperature.

Ventilation in domestic and small commercial buildingshas traditionally been by natural methods, typicallyopenable windows operated by the occupants. This does notguarantee adequate ventilation and the Building RegulationsPart F(29) require the use of mechanical extract fans orpassive stack ventilation. In recent years, the use of naturalventilation has been extended to large commercialbuildings. Such systems must be integrated carefully withthe design of the building itself to ensure that ventilation isachieved to extract heat gains in warm weather, thusachieving the goal of avoiding the requirement for airconditioning. The control of natural ventilation isdiscussed in 5.14.

The following deals with aspects of the control ofmechanical ventilation. Where a central AHU is employed, itis normal to incorporate outside air ventilation. Figure 5.43illustrates a generalised air handling system withrecirculation. The basic system is to be found withmodifications in many HVAC systems; a general descriptionis given in BRECSU GPG 257(30). A general description is

given here, followed by a more detailed treatment ofcomponents.

Where the air supply is used to heat or cool the occupiedzones, the volume flow of conditioned air is several timesthat of the outside air necessary for ventilation purposes. Itis therefore normal practice to recirculate a proportion ofthe air which has been extracted from the conditioned spaceand mix it with the required outdoor air supply; this leadsto economies in operation. A full fresh air system, with norecirculation, may be found in the following circumstances:

— The extract air is contaminated and should not berecirculated. In this situation, consider heat recovery.

— Non-air systems are used for heating or cooling, e.g.radiators, heated floors, chilled ceilings.

— Local air recirculation is used, e.g. fan coil units.

In these circumstances there is no recirculation at thecentral plant. Outside air supply rate may be fixed at therequired minimum ventilation rate or controlled as afunction of ventilation demand or cooling requirement.

5.7.1 Demand-controlled ventilation

Subsequent sections deal with the control of ventilationsystems which, in general, provide the required minimumamount of outside air for ventilation purposes, plus avariable amount of recirculated air and further outside airas required for temperature and humidity control. For mostpurposes, it is sufficient to calculate the required minimumoutside air supply from a knowledge of typical buildingoccupancy, plus any further requirements to removeadditional contaminants. Where the building has a largeand unpredictable occupancy, there are potential energysavings in matching the outside air supply to theventilation demand; this is termed demand-controlledventilation (DCV)(31,32).

Carbon dioxide level is the usual controlled variable foroccupied spaces. Carbon monoxide monitors can be usedfor controlling the ventilation of enclosed car parks. Otherair quality sensors are available which respond to a mixtureof pollutants, but have not found widespread applications;see 3.1.3.5. As an alternative to direct measurement of CO2it may be possible to estimate the number of occupants inthe controlled space and adjust the ventilation rateaccordingly. This has the advantage of providing therequired outdoor air supply immediately, without waitingfor CO2 levels to build up. Occupancy may be obtainedfrom the access control system in an integrated BMS.

The control system for DCV should always ensure aminimum outdoor air supply, regardless of CO2 level, todeal with outgassing from building materials. Set pointcontrol, where outdoor ventilation rate is switched betweenmaximum and minimum rates, is suitable for situationswhere the occupancy is either high or low, but atunpredictable times; examples are meeting rooms, lecturetheatres. A set point of between 600–1000 ppm CO2 will befound suitable, with a differential band of about 100 ppm.Proportional control is more suitable where the occupantdensity is variable. Where outdoor ambient CO2 levels arevariable, which is often found in urban locations, it is betterto control on the difference between outdoor and indoorconcentration. The lower limit of the proportional band

5-34 Building control systems

Page 110: Building control system, aplication guide   cibse guide

should be set at a level 100 ppm above outdoor, with aproportional band of about 500 ppm.

5.7.2 Poor outdoor air quality

Effective ventilation requires that outdoor air is cleanerthan the indoor air which it replaces. This is not always thecase and it may be necessary to take precautions to ensurethat polluted air does not enter the building. The first lineof defence is to ensure that air intakes are placed in clean airand away from any likely sources of pollution, such as carparks or loading bays. Outdoor air ducts incorporate filtersto remove particulate matter; the increased fan energy costassociated with better filtration must be evaluated at thedesign stage. However, filters will not remove gaseouscontaminants, such as carbon monoxide or oxides ofnitrogen.

Where demand-controlled ventilation is used, there is adanger that the indoor air quality (IAQ) sensor which controlsventilation rate may react to any ingress of pollutants byincreasing the ventilation rate and so making the situationworse. Outdoor air quality (OAQ) is often variable over theday, at its worst during peak traffic or at some other timeassociated with the generation of pollution. This provides anopportunity for control. Air handling systems with recircu-lation can vary the balance between recirculated and outdoorair, and it is advantageous to reduce the outdoor air contri-bution during times of high pollution, increasing it tocompensate at other times. Such a solution can only operatesatisfactorily where the pollution episodes are of relativelyshort duration. Two strategies may be used(33):

— Where the OAQ is known to be poor at the same timeeach day, a timeswitch can be used to set outdoor airsupply to its minimum level during these times.

— Where OAQ is variable, an OAQ sensor can be used toreduce outdoor air supply during pollution episodes.

A carbon monoxide sensor is recommended for as a sensor. COis found to show a high correlation with other urban pollutantssuch as oxides of nitrogen and other compounds and reliablesensors are available. The recommended strategy is

— Use a set point of 5 ppm CO for ventilation control.

— Use CO values averaged over 5 minutes to avoidresponding to short term spikes.

— If the set point is exceeded, switch the ventilationsystem to full recirculation for a short period, say 15minutes. Maintain the required average minimumoutdoor ventilation rate over periods of 1 h. Do notallow reduced ventilation rates to compromisethermal comfort.

— When the building is unoccupied and OAQ issatisfactory, purge with outside air for a timeequivalent to four full air changes in the building.

The above strategy will reduce intake of polluted air, whilegiving priority to sufficient ventilation to remove indoorpollutants.

5.7.3 Full outside air damper system

Figure 5.53 shows a simple full outside air system. Theexhaust and intake dampers move together. Both move

fully open when the plant is operating and close duringperiods of non-operation or when a fan-failure signal isreceived. An interlock prevents fan operation if therespective damper fails to prove open.

5.7.4 Variable-volume extract fan

It is normal practice to run a building at a slightoverpressure to prevent ingress of outside air through leaksin the fabric. This is done by ensuring that the supply airflow is greater than the extract flow; the balance is made upby exfiltration through the building envelope. The volumeflow rates of the supply fan and extract fan are normallylinked to prevent excessive over- or under-pressurisation ofthe building. For constant volume systems this is simplydone by linking the operation of the two fans, but for avariable-volume system it is necessary to control the speedof the extract fan to follow the supply air volume. Control ofsupply and extract flows is linked with the control ofoutdoor air supply and 5.7.6 should be read in conjunctionwith this discussion. There are four techniques which maybe used to control the operation of the extract fan: openloop, building static pressure, duct static pressure and airflow tracking.

Open loop control

Open loop controls the speed of the extract fan in step withthat of the supply fan, but without any feedback from theresult (Figure 5.54). Open loop control requires supply and

Control strategies for subsystems 5-35

Figure 5.53 Full outside air damper system. Exhaust and intake dampersmove together to maintain system balance. Normal operation: both dampersare fully open to admit outside air and discharge exhaust air. Dampers areproven open by end switches to enable supply fan. Dampers open: normaloperation, OSC heating and cooling, boost heating, night cooling. Dampersclosed: plant shut-down, fan failure

Figure 5.54 Open loop control of extract fan: a VAV system with supply fancontrolled by duct pressure. Extract fan is controlled in tandem withsupply fan

Page 111: Building control system, aplication guide   cibse guide

extract fans with similar operating characteristics.Balancing the two air flows is done during commissioning,but the balance will be affected by changes in buildingoperation in an unpredictable way. This form of controlmay be acceptable in small systems which are tolerant ofvariations in building pressurisation.

Building static pressure control

The speed of the extract fan is varied to control the buildingstatic pressure (Figure 5.55). The pressure is comparedwith the static pressure outside the building and may be setto a slight over- or under-pressure. Careful location of thepressure sensors is important; the indoor sensor should bedistant from opening external doors or liftshaft, while theoutdoor sensor should be mounted at least 5 m above thebuilding and shielded from wind. A hallway on an upperfloor is usually suitable for the indoor location.

Duct static pressure control

Where individual returns from the space are dampercontrolled, it is preferable to control the extract fan by thereturn duct static pressure (Figure 5.56). This is similar inprinciple to the control of a VAV supply fan by ductpressure; in the case of the extract fan the pressure isnegative.

Air flow tracking

Velocity sensors, or other flow-measuring devices, arepositioned after the supply fan and before the extract fanand the measures converted to volumetric supply rates(Figure 5.57). The supply and extract volume flow rates arecompared and the extract fan speed is modulatedaccordingly. The fan speed may be controlled so that theextract flow rate is a fixed proportion of the supply flow rate.In a typical VAV system, the supply fan speed is controlledusing a measure of the static duct pressure and the extractfan using a measure of the difference in supply and extractflow rates. The sampling rate for the latter must be slowerthan the former to ensure stability. The extract fan isdisabled in the event of plant shut-down or supply fanfailure; in all other situations the extract fan is modulatedto follow the supply flow rate. Where there is asupplementary exhaust system, it may be necessary to

measure the supplementary exhaust flow and subtract thisfrom the supply flow to find the desired extract rate. Airflow tracking presents some problems in control in practiceand improved techniques are discussed in 5.7.6.

5.7.5 Mixing damper systems

Many air handling systems employ some form of mixingdamper system, in which a proportion of the return air fromthe occupied space is recirculated and mixed with outsideair. The three sets of dampers work in unison with eachother so that the proportion of recirculated air and outsideair may be varied while keeping the air flows in balance.

The principles governing the control of mixing dampersystems are:

— At least the minimum outside air requirement issupplied during occupied hours.

— Dampers are controlled to give minimum energydemand from the HVAC system.

Details of control strategy vary between systems. Wherehumidity control is provided, control is more energyefficient using enthalpy control rather than simple dry bulbtemperature. VAV systems require a minimum outside airsupply to be maintained against variations in supply airvolume flow. Figure 5.58 shows the basic mixing dampersystem. During part of the year it may be possible to satisfy

5-36 Building control systems

Figure 5.55 Control of extract fan by building static pressure. The extractfan is controlled to maintain building pressure at a fixed set point. Supplyfan control not shown

Figure 5.56 Control of extract fan by extract duct static pressure. Theextract fan speed is controlled to ensure that there is sufficient negativepressure in the extract duct. Applicable for systems with multiple dampercontrolled extract terminals

Figure 5.57 Control of extract fan by air flow tracking. Extract fan speed iscontrolled so that the exact flow rate balances the supply flow, less anysupplementary exhaust flows

Page 112: Building control system, aplication guide   cibse guide

the requirements of temperature control by mixingrecirculated air and outdoor air in suitable proportions.When this is not possible, the outside air supply rate is setto either minimum or maximum value, depending on theconditions.

The minimum outside air damper position is set duringcommissioning; it may be set physically at the damper or,more commonly, within the controller software. Forconstant volume systems, where the supply fan runs atconstant speed during normal operation, the minimumdamper position is fixed. For variable-volume systems, theoutside air damper position needs to be controlled as afunction of the supply air flow rate. The outside air damperopening is increased at low supply flow rates to maintainthe required minimum volume of outside air. This may beachieved in two ways:

— linking the outside air damper position to the fanspeed control signal

— controlling the outside air damper position using alocal control loop which utilises a flow sensor in theoutside air duct. More details are given in 5.7.6.

The operation of the mixing dampers to provide the mostenergy efficient recirculated air supply is termed theeconomiser cycle. The principle is illustrated on thepsychrometric chart in Figure 5.59; this shows control ondry bulb temperature only. The diagram shows a situationwhere extract air from the controlled space is at atemperature TEtA and air is to be supplied at a temperatureTSA. For near steady state, four operating modes may bedistinguished:

— At low outside temperatures the air is cold enoughto bring the mixed air temperature to below therequired supply temperature even at the minimumoutside air supply rate; at these temperatures,below TOAmin, the outside air damper is set to itsminimum position and heating is required to bringthe supply air temperature up to TSA.

— When the outside air is within the range TOAmin <TOA < TSA the mixed air can be controlled at therequired supply temperature by modulating thedampers, up to 100% outside air when TOA = TSA.In this range the system is operating in free coolingmode.

— Within the range TSA < TOA < T EtA the outside airis maintained at 100% to give the lowesttemperature of the recirculated air entering the airhandling unit for cooling.

— As the outdoor air temperature rises above thereturn air temperature, the outside air dampermoves to its minimum position to give the lowestpossible mixed air temperature.

The figure shows control of outdoor air flow as a function ofsupply and extract temperatures; in practice these will varywith cooling load.

Thus in the free cooling mode, temperature control can beachieved without the need for heating or cooling from theAHU. The simple example assumes a fixed supply airtemperature. For a constant volume system, the mixingdampers may be operated by a PI controller with input fromthe controlled zone air temperature; the zone set point maybe changed according to season. For a VAV system, it is thesupply air temperature that is controlled, but there isadditional control of the outside air damper to ensure thatthe required minimum outside air flow is maintained. Thecontrol of the dampers may be generalised:

The dampers modulate towards the open position underthe following circumstances:

(1) The return air temperature is greater than theoutside air temperature and cooling is required(TSA < TEtA) (free cooling mode).

(2) The return air temperature is less than outside airtemperature and heating is required (non-steadystate situation).

Control strategies for subsystems 5-37

Figure 5.58 Mixing damper control. The dampers are moved together toprovide a balanced supply. The proportion of outside air is varied to giveeconomic operation, subject to minimum ventilation requirements

,

Figure 5.59 Principle of economiser control

Page 113: Building control system, aplication guide   cibse guide

The dampers modulate to the minimum outside airposition under the following circumstances:

(3) The return air temperature is greater than theoutside air temperature and heating is required(TSA > TEtA).

(4) The return air temperature is less than the outsideair temperature and cooling is required. (non-steady-state mode).

Situations 2 and 4 would only be met during changingtemperatures and are not usual.

Where the humidity as well as the temperature of thesupply air is controlled, account must be taken of the totalenergy content of the air streams if maximum efficiency isto be obtained. This is known as enthalpy control. This isillustrated on a psychrometric diagram in Figure 5.60,which shows an all air system where the extract air from theoccupied space has a temperature and humidity defined bythe point A on the diagram. The normal operating situationis considered where the supply air to the space requires dryand wet bulb temperatures which are both below that of thereturn air, i.e. the supply air condition lies somewhere inregion 1 of the diagram. This applies in virtually allsituations, whether heating or cooling, since the sensibleand latent loads in the occupied space raise the dry and wetbulb temperature of the extract air above that of the supplyair, whether the building is in heating or cooling mode.Two lines are shown on the diagram: a line of constant airtemperature a–a and one of constant enthalpy e–e; this ispractically indistinguishable from a line of constant wetbulb temperature. In region 4 of the diagram, the enthalpyof the outside air is less than that of the return air andeconomies will be obtained by opening the outside airdamper, even though the dry bulb temperature is greaterthan that of the extract air. Conversely, in region 2 of thediagram, the high humidity of the outside air would createan energy penalty on dehumidification and the outside air

supply should be set to minimum. The principle ofenthalpy control, during normal operating conditionswhere the return air wet and dry bulb temperature areabove those of the required supply air condition, is asfollows:

— When the outside air has a lower enthalpy than theextract air but a higher temperature (region 4), use100% outdoor air with no recirculation.

— When the outside air has a lower enthalpy andtemperature than the extract air (region 1), use theoptimum mix of outdoor and recirculated air.

— When the outside air enthalpy is more than theextract air enthalpy (regions 2 and 3), the dampersprovide the minimum outdoor air supply requiredfor ventilation.

Note that the temperature and humidity of the supply airdo not appear in Figure 5.60, but simply the relationshipbetween the return air and outside air. Examples of thedifferent situations are shown in Figure 5.61. There is nosingle sensor for the measurement of enthalpy, which has tobe calculated from separate measurements of temperatureand humidity. Sensors are available which combine bothsensors and carry out the necessary computation.

5.7.6 Outdoor air supply

The general air handling system shown in Figure 5.43supplies air to the occupied space; the supply air is amixture of outdoor air and recirculated air. The proportionof outdoor air varies with the quantity of extract air that isrecirculated. Since the volume flow of supply air is itselfvariable in a VAV system, there can be problems in ensuringthat the required minimum volume of outdoor air forventilation purposes is always provided.

In a constant volume system, the supply fan provides aconstant volume of air. Where economiser control isemployed, the proportions of outdoor and recirculated airare varied for optimum energy efficiency. The outdoor airdamper has its minimum opening position set duringcommissioning, so that when the economiser control is inthe maximum recirculation position, the required amountof outdoor air is supplied. After the initial balancing, nofurther control is required. The system will always provideat least the minimum outdoor air ventilation requirement,rising to 100% outdoor air during maximum free cooling.

In a VAV system, the supply fan is modulated according tothe load requirement of the building and a control strategyis required to ensure that the minimum ventilationrequirement is met. The difficulties of ensuring reliablecontrol of outdoor air supply are discussed by Kettler(34),who surveys the available strategies:

(1) Limiting the outside air damper to a minimum openingposition. This must be set during commissioning togive the required outdoor air flow with the supplyfan at minimum speed and with maximumrecirculation if an economiser control is fitted. Thissolution is the simplest, but does not giveminimum energy consumption, since outdoor airflow may be excessive at high supply flows.

(2) Limiting the outside air damper to a minimum openingposition which is a function of fan speed. The

5-38 Building control systems

Figure 5.60 Principle of enthalpy control. Point A is the extract aircondition and the required supply air condition is somewhere in region 1.Minimum outside air is used when the outdoor conditions are in regions 2and 3; enthalpy economiser control mixes outdoor and extract air whenoutdoor conditions are in regions 1 and 4

Page 114: Building control system, aplication guide   cibse guide

relationship is established during commissioningand must provide the required ventilation supply atall combinations of supply fan speed andrecirculated air proportion.

(3) Modulating the outside air damper to provide the desiredair flow as measured in the outdoor air intake. An airflow sensor in the intake duct is used with a PIcontroller in a separate control loop.

(4) Modulating the extract fan speed in a technique knownas volume matching or air flow tracking. 5.7.4 describesthe air flow tracking technique, whereby the extractfan speed in a VAV system may be controlled tofollow the supply fan. If the extract fan is controlledto maintain constant difference between extractand supply air flows, the difference is made up bythe outdoor air intake flow; the difference is set tobe equal to the ventilation requirement.

(5) Injection fan method. An extra fan is fitted to run inparallel with the main intake duct. This fan runscontinuously and injects the required minimumoutdoor air flow downstream of the mixing box; seeFigure 5.62. The injection fan controls the air flowin the duct with its own PI control loop, whichensures that the required volume flow of air isdelivered irrespective of wind effects or backpressures. It is especially suitable where theoutdoor air supply has to be reset, as in demand-controlled ventilation. It has the disadvantage ofrequiring additional ductwork.

(6) Plenum-pressure method. The basis of the plenum-pressure method is shown in Figure 5.63. A

differential pressure sensor is fitted across theoutdoor air louvre and intake damper. With therecirculation damper open and the supply fangiving maximum air flow, the outdoor air damper isset during commissioning to give the requiredminimum outdoor air supply. The combination oflouvre and minimum damper setting is now treatedas a fixed orifice for air flow control. The plenum-

Control strategies for subsystems 5-39

0 10 20 30

0 10 20 30

0 10 20 30

0 10 20 30

Figure 5.61 Examples of enthalpycontrol. (a) 100% outdoor air(region 4); (b) minimum outdoorair (region 3); (c) economisercontrol, heating required (region1); (d) economiser control,humidification required (region1). EtA, extract air; SA, supply air;OA, outside air; MA, mixed air

Figure 5.62 Injection fan system. The required outdoor air volume isinjected into the supply duct by a separately controlled fan. Control ofdampers is not shown

Page 115: Building control system, aplication guide   cibse guide

pressure strategy operates in conditions whereminimum outdoor air is required. As the supply fanreduces air flow in response to reduced demandfrom the VAV boxes, the controller modulates therecirculation damper towards the closed position tomaintain the pressure drop and hence required flowthrough the outdoor air damper. This ensures thatthe required ventilation flow is maintained insituations of maximum recirculation. When themixed air control requires more than minimumoutside air, the outdoor air damper is allowed toopen further and the plenum pressure control loopis deactivated, since the dampers are nowpositioning to bring in more than the minimumflow required for ventilation. This system isclaimed to give reliable and simple control with asmall energy penalty(35).

The first two strategies have the advantage of simplicity.The first will provide excess outdoor air in all butconditions of minimum supply fan speed. The second is asimple open loop control and should be recommissioned atsuitable intervals. While apparently offering direct controlof the outdoor air supply, the third and fourth strategies canpresent problems in practice. Measurement of air flow inthe outdoor air intake duct presents practical problemsarising from turbulence and the low face velocitiesdemanded by filters. Inaccuracies in flow measurement canalso produce problems with the volume matching method.Normally acceptable errors in flow measurement maytranslate into unacceptable error in the difference betweenextract and supply. It can be shown that a 5% error in flowmeasurement may produce an unacceptable 50% error inoutdoor air supply(35).

Where volume-matching control is used in conjunctionwith recirculation, there can be situations where outdoorair is drawn in via the exhaust air outlet. This tends tooccur in situations of high recirculation, when the intakeand exhaust dampers are modulated towards closed. Airentering the system via this route bypasses any intakefilters and risks introducing poor quality air to thesystem, especially if the exhaust is situated in a dirty area,such as a vehicle loading bay. The problem may beavoided by leaving the outdoor intake damper wide openduring normal occupancy; the speed of the extract fan iscontrolled using the volume matching technique and

the exhaust and recirculation dampers are linkedconventionally(36).

5.7.7 Dehumidification with mixingdamper control

A typical air handling plant will use a combination ofmixing damper control and a chilled waterdehumidification coil to provide air at controlledtemperature and humidity; humidification is consideredseparately. The control strategy ensures that cooling anddehumidification are provided by the most economicalmethod; this is a practical application of the principle ofenthalpy control described above. The arrangement of thesystem is shown in Figure 5.64. A heating coil is shown inaddition to the cooling coil, since reheat is required toprovide independent control of both air temperature andhumidity.

The use of mixed recirculated and outside air offerseconomies in the dehumidification process in a wayanalogous to the economiser cycle. The process isillustrated on a psychrometric chart in Figure 5.61. It isdesired to condition the supply air to the temperature andmaximum moisture content indicated by the point SA onthe chart; humidification is considered elsewhere. If thedesired moisture content of the supply air lies between thatof the extract air EtA and the outside air OA, then themixing dampers are modulated to produce mixed air of thedesired moisture content.

Proper dehumidification requires a heating coil to be inoperation downstream of the cooling coil. In someinstallations it is the practice to place the only heating coilupstream of the cooling coil. By this means it is possible todispense with a separate preheating coil by combining thefunctions of pre and main heating coils. In this case, duringoperating conditions when dehumidification is required,air leaves the cooling coil just above saturation. This createsa risk of condensation in the ductwork and also createsproblems with control. Fully independent control oftemperature and humidity in the controlled space is notpossible with this arrangement. However, for situationswhere dehumidification is seldom required during a year, itmay provide acceptable conditions.

5-40 Building control systems

Figure 5.63 Plenum-pressure control of outside air. When the economisercircuit calls for minimum outside air, the intake damper moves tominimum open position. The recirculation damper modulates to maintainpressure differential across louvre and damper. Other controls not shown

Figure 5.64 Chilled water dehumidification with mixed air control. Thedampers are moved together to provide economic operation. Furtherdehumidification and reheat provided by the heating and cooling coils

Page 116: Building control system, aplication guide   cibse guide

5.7.8 Displacement ventilation

Conventional mixing ventilation aims to mix supply airwith room air; both temperature and the concentration ofcontaminants are approximately uniform over thecontrolled space. The extract air also has a similartemperature and composition to the air in the occupiedzone. This is not the most efficient way of ventilating aspace and ignores the general rule that heat and pollutantsshould be extracted at source, before they mix with thegeneral air. Displacement ventilation aims to supply cleanair directly into the occupied zone (Figure 5.65). As the airmakes its way towards the extract, it picks up heat andcontaminants, so that the extract air is significantly hotterand dirtier than the air experienced by the occupants. Inthis way, it is possible to provide effective ventilation atlower supply volumes compared with a mixing system, withresulting economies. Various geometries are possible andare applied in special situations. The use of downflowsystems is general in clean rooms and operating theatres.For open office spaces, an upward air flow is employed. Airis introduced through floor diffusers and is extracted atceiling level. Sources of heat, such as people or officemachinery, produce a rising plume of warm air. Manypollutant sources are warm, so the dirty air will rise towardsthe ceiling without entering the breathing zone.

The result is a vertical temperature gradient in the occupiedspace. There may be a shallow layer of cool air where thesupply air is produced at floor level, termed the pool zone.The occupied zone extends to a height of 1.5 m or so, abovewhich the temperature rises towards the ceiling. Thecooling power of a displacement system is limited. It is notpossible to reduce supply temperature or increase supplyvolumes because of the risk of local discomfort. Ifadditional heating or cooling is required it must beprovided by a separate system. The common combinationof chilled ceiling and displacement ventilation is discussedin 5.12.

It is normal to run a displacement system at constant flowrate with the supply temperature controlled as a function ofoutdoor temperature. Supply flow rates are typically 2.5 airchanges per hour. These flow rates are low compared with amixing system and the fresh air requirement represents alarge part, or even all, of the supply flow. The systemtherefore lends itself to a full fresh air system, with a heatexchanger for energy efficiency. Figure 5.65 shows adisplacement ventilation system. The system shown offersfull control of temperature and humidity of the supply air.

Dehumidification is required if the ventilation system isused with any form of chilled panel cooling system, toprevent the formation of condensation on cold surfaces.This is discussed in 5.12. A full specification and points listof the displacement system shown in the figure is given inSection 3.16.4 of the BSRIA Library of System ControlStrategies(37). The main points of the strategy are:

— Fan and extract fan run at constant speed duringnormal occupancy. The volume flow must besufficient to meet outdoor air requirements atmaximum occupancy; it is typically 2.5 air changesper hour.

— Supply air temperature is linked to outdoortemperature. The supply air set point is at itsmaximum of 22ºC when outside temperature is12ºC or below; the set point is at a minimum of18ºC when the outside temperature is 21ºC orabove, with linear interpolation between thesepoints.

Control of the thermal wheel, humidification anddehumidification follows the strategies detailed elsewherein this Guide.

The minimum supply air temperature is primarilygoverned by comfort considerations, since the air isintroduced at floor level over the occupied area. Theminimum acceptable temperature depends on the designand location of the air inlets and in some cases may be lowerthan 18ºC. Some installations link the supply airtemperature to zone temperature, rather than outsidetemperature as described above. A master–submastercontroller is used, which resets the supply air temperatureset point according to the zone temperature. Carefulconsideration must be given to the placement of the zoneair temperature sensor, bearing in mind the verticaltemperature gradient produced by displacement systems.

5.8 Variable air volumeVariable air volume (VAV) was probably the most widelyinstalled type of air conditioning system during the last twodecades. Conditioned air is supplied by a central plant toseveral zones; the air supply is controlled independently toeach zone by one or more room terminal units (RTU) whichcontrol zone temperature by modulating the volume flow ofair to the zone. The main air handling unit supplies

Control strategies for subsystems 5-41

Figure 5.65 Displacementventilation. Diagram shows resetof supply air temperature as afunction of outside temperature

Page 117: Building control system, aplication guide   cibse guide

conditioned cool air to all room terminal units; this supplycontains the necessary proportion of make-up outside airfor ventilation. The air is supplied at constant temperature,though the set point may be varied with season. The roomunits vary the air flow to each controlled space to providethe necessary temperature control. The units may beprovided with reheat coils or heater batteries, in which casethey provide all heating and cooling requirements. It is,however, common to use VAV systems for cooling only andto provide any necessary heating by the use of a separateheating system such as perimeter radiators. The diversity indemand between different zones means that part loadeconomies are achieved in both fan power and coolingpower when using a VAV system. The air supply from theterminals to the conditioned space varies with cooling orheating demand and a variable-volume extract fan may beused to ensure a constant building pressure. In this case thetotal measured flow from the VAV units is summed andmade available to the extract fan controller. The controllercan scale the signal, so that the space operates underpositive or negative pressure as desired. As an alternative,the building pressure may be measured directly and used tocontrol the extract fan.

5.8.1 Room terminal units for VAV

systems

VAV terminal units are fitted with their own localcontroller; the control functions for the various types ofVAV terminal are described below. The term intelligent VAVterminal has no precise definition. At the very least, itimplies that the controller is connected to the main BMSnetwork, allowing common reset of temperature set pointfor groups of terminals and the linking of the terminaldamper control to the operation of the central AHU.However, the term intelligent is better reserved forcontrollers which have full exchange of information withthe BMS, including feedback of damper position.

5.8.1.1 Pressure dependent VAV unit

A simple VAV unit is shown in Figure 5.66. Flow throughthe unit is controlled by a throttling damper, whoseposition is controlled by a proportional controller as afunction of room temperature. If a reheat coil is fitted, it isbrought into action when the room temperature falls belowthe heating set point, using a PI controller to modulate thevalve controlling the hot water supply to the coil. Anelectric heater battery may be fitted in place of the reheatcoil. The control characteristic is shown in Figure 5.66.When the room temperature is below the cooling set point,the damper is held at a minimum opening position toensure sufficient air supply for ventilation and room airdistribution. The air supply to the space at a given damperposition is a function of the static air pressure in the supplyduct, which varies with the state of the system. A signal maybe provided to the BMS when the damper is open.

5.8.1.2 Pressure independent VAV terminal

The static air pressure in the supply duct to the VAVterminal will in general vary with the operation of otherterminal units in the system and any consequent control ofthe main supply fan. A pressure independent VAV terminal,also known as variable constant volume, delivers a supply ofair to the conditioned space which is a function of space

temperature only and not of the supply air pressure. Thecontrol characteristic is shown in Figure 5.67. Proportionalcontrol of air supply as a function of space temperature isachieved using a cascade controller. The first stage of thecontroller resets the air flow set point as a function of themeasured space temperature using a P or PI controller. A

5-42 Building control systems

Zone temperature

Figure 5.66 Pressure dependent VAV terminal unit. Unit shown withoptional reheat coil fitted. Normal operation is shown in the diagram.Additional modes are: primary supply damper and reheat valve open — boostand OSH heating; supply damper open, reheat valve to bypass — OSC and nightcooling, plant shut-down

Zone temperature

Figure 5.67 Pressure independent VAV terminal unit. A cascade controlleris used to reset the air flow as a function of zone temperature. Normaloperation shown in diagram. Damper and reheat valve open: boost and OSH

heating. Damper open, reheat valve to bypass: plant shut-down, OSC or nightcooling

Page 118: Building control system, aplication guide   cibse guide

second PI controller is then used to operate the damper toproduce the required air flow. The VAV box incorporates adifferential pressure sensor for the measurement of air flow.Intelligent damper actuators are available whichincorporate a differential pressure sensor, controller andactuator in a single unit.

5.8.1.3 Induction VAV terminal unit

The induction unit combines cool air supply from thecentral AHU (primary air) with warm return air from theconditioned space (secondary air). The VAV box is located inthe ceiling plenum of the zone, where an adequate supply ofreturn air is available for recirculation. A diagram of aninduction unit is shown in Figure 5.68. A pressureindependent type controller is shown. The flow rate of theprimary air is controlled as a function of zone temperatureby operating the primary inlet damper, as described for thestandard pressure independent VAV unit. The inductiondampers are moved simultaneously in the oppositedirection, so that as the primary air supply is reduced theamount of recirculated air is increased. The total volume ofair discharged to the room is roughly constant with load,giving improved room circulation compared with a simpleVAV terminal. Induction systems require increased mainduct pressure to accomplish effective entrainment and soresult in higher operating costs compared with the basicVAV unit.

5.8.1.4 Fan-assisted VAV unit: series fan

The fan-assisted VAV box also mixes cool supply air withrecirculated air from the conditioned space. A smallcontinuously operating fan in the VAV box is used to mix

the primary and secondary air and to ensure good airdistribution in the zone. The improved circulation is ofvalue at low cooling loads and during heating duty if areheat coil is fitted. The air supply to the space is at constantvolume and at a temperature which varies with load. Adiagram of a unit is shown in Figure 5.69; the fan serves todraw air in from the return plenum, mix the two airsupplies and overcome any downstream pressure drop. Thecontrol characteristic is shown for the example of a pressureindependent unit, where the primary inlet damper ismodulated to maintain the primary air flow set point,which is reset as a function of room temperature by acascade controller.

5.8.1.5 Fan-assisted VAV unit: parallel fan

A parallel fan box is sometimes used where heatingperformance is of importance. A diagram of the unit isshown in Figure 5.70. Parallel boxes rely on the primarycooling air supply for effective distribution during thecooling season, when the fan is switched off. When heatingis required, or when cooling needs are low, the fan operatesto recirculate secondary air from the room and to providebetter air distribution.

5.8.2 Supply fan control for VAV

systems

The central fan in a VAV system supplies conditioned air to anumber of VAV room terminal units. Each room terminal

Control strategies for subsystems 5-43

Zone temperature

Figure 5.68 Induction VAV terminal unit, pressure independent. Nooptional reheat coil shown. Normal operation shown in the diagram. Theprimary damper is modulated to control the primary supply at the setpoint, which is reset from room temperature. Where a reheat coil is fitted,control is as for simple pressure independent VAV box. Other modes:Primary damper open, heating valve open: OSH and boost heating. Primarydamper open, heating valve closed: plant shut-down, fan failure, OSC andnight cooling

Zone temperature

,

Figure 5.69 Fan-assisted VAV terminal unit — series fan, pressureindependent. Fan runs continuously. Normal operation shown indiagram, other modes in table

Page 119: Building control system, aplication guide   cibse guide

unit (RTU) supplies air to a room or zone and controls thetemperature in the zone by modulating the supply of air thatit delivers. The central supply fan is therefore required tosupply a varying volume of air, whose quantity isdetermined by the independent actions of a number of roomterminal units. The use of a constant-speed supply fan wouldproduce an increase in duct pressure as room unitsmodulated towards closed, resulting in an increase in energyconsumption and a risk of damage. It is therefore universalpractice to modulate the supply fan in a VAV system to matchthe demand of the terminal units. The supply fan may becontrolled by a number of methods. Variable-speed drive isthe most efficient and its use is becoming widespread.

Several control strategies for fan speed control are in use.For simple layouts, a single measure of duct static pressuremay be used to control the supply fan. As the complexity ofthe duct layout increases, it is necessary to use severalsensors to ensure that all branches receive adequate airsupply and do not suffer starvation in some part loadconditions. Where intelligent VAV boxes are used, it ispossible to monitor the condition of all room terminal unitsand modulate the fan for optimum operation.

Single pressure sensor

The supply fan speed is controlled using a static pressuresensor positioned in the supply duct (Figure 5.71). Fanspeed is controlled using a PI controller to maintain ductstatic pressure at the set point. The room terminal unitsmodulate towards closed as the cooling load lessens; thiscauses the duct pressure to rise and the fan speed is then

reduced to maintain the pressure. Choosing the bestposition for the pressure sensor presents some difficulties.Where the terminal units are positioned along a single duct,it is possible to use a single sensor. Positioning the sensortowards the end of the duct remote from the supply fangives the most efficient control. The pressure set point ischosen to give sufficient pressure at the RTU in designconditions to overcome the pressure drop in the terminaland air diffuser; because of the pressure drop down the ductdue to duct loss, terminal units upstream will alwaysoperate at a higher pressure. However, placing the sensor atthe far end of the duct may give rise to excessive variationsin pressure following disturbance by events such asopening and closing doors, and a position about two-thirdsof the way along the main duct is conventionally adopted asa satisfactory compromise. Where the main duct feedsbranches and a single pressure sensor is to be used, thesensor should be placed just before the branch which hasthe highest pressure drop in design conditions.

Multiple pressure sensors

In general, however, a single pressure sensor is inadequatefor a branched duct layout. If the independent operation ofthe RTUs causes the relative pressure drop in the branches todiffer notably from design conditions, a branch upstream ofthe sensor may risk starvation. The problem may beovercome by using a pressure sensor for each branch(Figure 5.72). The pressure sensors are placed about two-thirds of the way down each duct; placing the sensors at thehead of the branches will often produce satisfactory results.The controller is programmed to adjust the fan speed sothat all pressure set points are reached or exceeded; thisensures that all branches receive an adequate air supply.

Intelligent VAV boxes

Where intelligent pressure independent VAV room terminalunits are used, it is possible for the BMS to obtain

5-44 Building control systems

Fan on

Zone temperature

Returnplenum

osc

osc

Figure 5.70 Fan-assisted VAV terminal unit — parallel fan, pressureindependent. Normal operation is shown in the diagram. Fan operatesduring heating only. Other modes shown in table

Figure 5.71 Control of VAV supply fan using single duct static pressuresensor. (a) Single main duct. Supply fan speed is controlled to maintain aconstant static duct pressure at a position two thirds of the way down theduct. (b) Several branch ducts. The single sensor is positioned at the headof the branch with the largest pressure drop along it

Page 120: Building control system, aplication guide   cibse guide

information on the setting of each individual RTU and to usethis information to calculate the required fan speed setting(Figure 5.73). The pressure sensors are positioned at thehead of each branch. The controller uses a pre-programmedknowledge of the duct layout and the position of thepressure sensors. The RTU setting gives the required air flowat each terminal, from which it is possible to calculate ductpressure drops and find the static pressure at the sensorpositions which are necessary to feed each branch. To avoidoverloading the communications net, the pressure setpoints are reset every 15 minutes. The PI controller thencontrols the fan speed to satisfy these requirements.

An alternative approach is possible where intelligent VAVboxes are used, whereby the fan speed is controlled so thatthe terminal units operate towards the middle of theirrange. The controller employs a form of floating control,which increases fan speed if the controller finds too manyboxes open and reduces fan speed if it finds too manyclosed. More precisely, the strategy is(18):

— The controller reviews the positions of the dampersin all the VAV boxes.

— If any box has a damper position of more than 90%open, the fan speed is gradually increased until alldampers are below 80% open.

— Else if every box damper is below 60% open and atleast one VAV damper is at or below its minimum

setting, then gradually reduce the fan speed until atleast one VAV damper opens to 70%.

— Else leave the fan speed unchanged.

Whichever sensor mounting position is used to controlfan speed, it is necessary to mount a high limit pressuresensor in the supply fan discharge. This providesprotection against the development of high pressures inthe duct, which could result from a duct blockage. Onreceipt of a high pressure signal, the supply fan is disabledand a warning sent to the BMS. For all the above controlsystems, the supply fan is disabled on plant shut-down.The dampers in the RTUs should be left open when thesystem shuts down, so that they are open when the supplyfan is started; intake and exhaust dampers should be openon start-up.

5.8.3 Supply air temperature controlfor VAV systems

Several levels of control are available for VAV systems. Themost straightforward is the provision of cooling only; theroom terminal units modulate to provide room cooling andany necessary heating is provided by a separate system,typically water radiators. In all but the simplest of systems,the speed of the main supply fan is linked to demand; thisprovides economic fan operation at times of low demand.Additional energy savings can be achieved by resetting thetemperature of the supply air according to load, e.g. byraising the supply air temperature at times of low coolingload. Two major control strategies are available. The firstrequires the use of intelligent room terminal units whichcan signal the position of their dampers to the BMS; thesecond links supply air temperature to fan speed.

5.8.3.1 VAV supply air temperature reset withintelligent terminal units (BSRIA3.14.2)

The control strategy supplies air from the central airhandling plant at an optimum supply temperature, aimed atminimising the supply air flow rate and the amount ofterminal reheating; the strategy is described in Martin andBanyard(37), Section 3.14.2. The room terminal units act tocontrol room temperature in the normal way, employing alocal control loop to modulate the damper positions and touse reheat where room heating is required. The intelligentterminal units signal damper positions to the BMS; inparticular, they signal when any dampers have reachedpredefined maximum or minimum opening positions.Control of the supply fan speed is by one of the standardmethods, such as duct static pressure. The supply airtemperature is to be controlled between predefinedmaximum and minimum temperatures, typically 22ºC and12ºC. The basis of the control strategy is as follows:

— All, or nearly all, zones require heating: the supplyair temperature set point is gradually raised untilone damper has closed to its minimum openingposition.

— All, or nearly all, zones require cooling: the supplyair temperature set point is gradually reduced untilone damper has closed to its minimum openingposition. The set point is reduced further if anydampers are at maximum opening position.

Control strategies for subsystems 5-45

Figure 5.72 VAV supply fan control: multiple branches and sensors.Supply fan speed is controlled to ensure that all pressure sensors achieve atleast the set point pressure. The signal to the PI controller is the largestnegative deviation from set point

Figure 5.73 VAV supply fan control: intelligent VAV boxes. The controllersums the demand from all individual room units and resets the duct staticpressure set point

Page 121: Building control system, aplication guide   cibse guide

— Zones require a mixture of heating and cooling: inthis situation, control of the cooling set point takesprecedence over that of heating. The airtemperature set point is adjusted so that theterminal units supplying the greatest cooling loadare at the maximum open position.

The interaction of the RTU dampers, supply fan speedcontrol and supply air temperature reset presents a risk ofinstability. The control of supply air temperature should beslow acting and should follow changes in the other twocontrol subsystems.

5.8.3.2 VAV supply air temperature resetscheduled to fan speed (BSRIA 3.14.3)

This strategy can be used where information on the RTUdamper positions is not available. It is generally applicableand can be used where the RTUs incorporate reheat coils.However, in this situation the control strategy of the RTUshould maintain the dampers at the minimum open positionwhen the unit is supplying heating; some strategies increasethe air flow though the RTU during reheating to ensureadequate air circulation. The object of the strategy is toadjust the primary air supply temperature so that the mainsupply fan operates within its efficient speed range, betweenpredetermined high and low set points.

During normal operation, the supply fan speed is comparedwith the upper and lower speed limits and adjusted ifoutside the desired operating range.

— If the fan speed is above the upper limit, the systemis having difficulty meeting the cooling load. Thesupply air temperature is gradually reduced. Thishas the effect of reducing damper opening in theRTUs with a consequent reduction in supply fanspeed. The reduction in supply air temperaturecontinues until the fan speed falls below the highlimit or the minimum air temperature set point isreached.

— If the fan speed is below the lower speed limit, thesupply air temperature is gradually increased untileither the fan speed is above the lower limit or thesupply air temperature set point reaches itsmaximum value.

The interaction of the RTU dampers, supply fan speedcontrol and supply air temperature reset presents a risk ofinstability. The control of supply air temperature should beslow acting and should follow changes in the other twocontrol subsystems. The following rules will assist stability:

— On starting the main supply fan, or changing tonormal operation following optimum start, nightcooling or boost operation, a period of at least 15minutes should be allowed for the system to settlebefore initiating supply temperature set pointcontrol.

— Before initiating a change in set point, the fan speedshould have been above or below the limits for apredetermined time delay period.

— The change in set point should be gradual. Steps of0.5 K every 10 minutes is typical.

— Control of the high and low speed limits shouldincorporate a differential to avoid undue cycling.

5.9 Constant-volume roomterminal units

The central plant of a constant-volume air conditioningsystem supplies conditioned air to all terminal units. Theconstant-volume RTUs supply a constant volume of air toindividual zones. Correct balancing of the air supply of theRTUs during commissioning ensures that the zones remainin balance. Control of conditions as the overall load changesis performed at the central plant. The RTUs may beequipped with reheat coils for the adjustment of individualzone temperatures.

Individual RTUs therefore require adjustment to balance thesystem and to ensure that they deliver the required constantair supply. Self-adjusting mechanical volume regulatorsmay be used but is generally better to use positive controlusing an air flow sensor and damper. A schematic diagramof a constant-volume RTU is shown in Figure 5.74. Airsupply is maintained constant by a PI controller operatingthe damper, irrespective of pressure variations in the mainsupply duct. If fitted, a reheat coil comes into action whenthe room temperature falls below the heating set point.There is no local control of cooling or humidity, which iscarried out at the central plant. Separate controllers areshown in the diagram to emphasise that there is no input ofzone temperature to the air supply controller, in contrast toa VAV unit. The controllers are connected to the main BMSfor such functions as optimum start, boost heating andshut-down.

5.10 Fan coil unitsThe use of water as a distribution medium for heating andcooling offers considerable economies of space comparedwith the use of air. Fan coil units provide local temperaturecontrol, using a fan to recirculate room air over water/air

5-46 Building control systems

-

Figure 5.74 Constant-volume air terminal unit, pressure independent.Normal operation: damper modulates to provide constant design air flow.Heating valve modulated to maintain space temperature. Other modes intable

Page 122: Building control system, aplication guide   cibse guide

heat exchange coils. A wide range of units is available,typically fitted under windows or in a suspended ceiling;other variations are possible. Fan coil units (FCUs) controlspace temperature by recirculating room air and provisionmust be made to ensure a supply of outside air forventilation. This may be done independently of the FCUs.For more sophisticated systems, a central unit conditionsoutside air to suitable temperature and humidity andsupplies it to the FCUs, where it is mixed with therecirculated air. The necessary distribution ducts are muchsmaller than those required for an all air system. Fan coilunits are not suitable for accurate humidity control. Somecontrol of latent load can be achieved by dehumidifying thesupply of outside ventilation air and the cooling coil in theunit can handle some latent load, in which case provisionmust be made to drain the condensate.

Control of the output of a fan coil unit may be by:

— Fan speed control. Water is circulated at a constanttemperature in the coil of the heat exchangers andthe fan speed modulated according to demand.This method may cause disturbance to occupants,since changes in noise level are more noticeablethan the noise from a fan running at constantspeed; there may also be noticeable changes in localair movement. If variable fan speed control is used,the controlling temperature sensor should bemounted in the controlled space, since a sensormounted in the return air path in the unit will givean unsatisfactory indication at low or zero fanspeeds. A manual boost fan speed may be providedfor rapid temperature change.

— Waterside control. The rate of flow of hot or chilledwater is controlled using a two- or three-way valve.

— Airside control. Water is circulated through theheating and cooling coils in the unit. The air flowpath through the unit is controlled by internal flapswhich direct the air over the coils according todemand.

The water circuits may be classified into two groups:

— Two-pipe water systems. A single supply of water isavailable at the FCU. This may be either hot or colddepending on season, but it is not possible fordifferent units within the same zone to heat andcool simultaneously.

— Four-pipe systems. Both hot and chilled water areavailable to the FCU. The unit may employ separateheat exchangers for heating and cooling, or a singleheat exchanger coupled with the use of achangeover valve. The type of heat exchanger willhave implications for the selection of water supplytemperature.

5.10.1 Fan coil units. Waterside control

Figure 5.75 shows a four-pipe unit which incorporatesventilation air supply from a central AHU. The fan runscontinuously during normal operation. Zone temperature iscontrolled by modulating the supply of hot or chilled waterto the coils using three-port valves; heating and cooling arenever provided at the same time. Multi-speed fans arecommonly fitted to fan coil units, with the appropriate speedfor each unit selected during commissioning. A higher

speed may be selected by the controller during boostoperation or to supply a high demand.

There are several variations in the type and control of FCUs.Control of a four-pipe unit may be by a simpleheating/cooling thermostat with central deadband, whichoperates an on/off solenoid valve to the coils. Fan coil unitsare in widespread use and can operate successfully underlocal control. Locally controlled fan coils have foundwidespread use in such applications as hotels and multi-cellular offices, where the units are accessible and localcontrol by occupants is satisfactory. The effective control offan coil units in large buildings and spaces is greatlyfacilitated by the use of intelligent fan coil units, fitted withcontrollers that communicate via the BMS network. This hasadditional practical advantages where units are not readilyaccessible, e.g. when mounted behind a suspended ceiling,since adjustments to set points and balancing may becarried out from the head end without requiring access tothe unit. The use of fan coil units controlled via thenetwork allows:

— incorporation of the FCUs in optimum startprograms

— remote adjustment of set points, individually or ingroups

— flexible time scheduling of operation

— linking to occupancy detection

— simple adjustment of control parameters.

Control strategies for subsystems 5-47

Low/high

Figure 5.75 Fan coil unit, four-pipe waterside control. Fan runscontinuously and coils modulate to control room temperature. Optionalventilation air from central AHU. Other modes in table

Page 123: Building control system, aplication guide   cibse guide

Since heating and cooling are never employedsimultaneously within a single FCU, it is possible to use asingle coil which is used for both heating and coolingduty. Such four-pipe single-coil fan coil units require theuse of special three-way valves on both the supply waterside and return water side of the single coil. When thethermostat calls for heat, the valves to the chilled watersupply and return circuits remain closed, while the supplyvalve hot water port is throttled to provide heatingcontrol. There is a deadband between heating and coolingoperation.

Two-pipe fan control units are supplied with either LTHWor chilled water; the selection is made centrally and it is notpossible for different units to provide simultaneous heatingand cooling. Operation of the two-pipe FCU is controlled byan air thermostat, mounted in the return air path of the unitor else mounted remotely in the room. The thermostat is aheating/cooling type and requires a changeover signal. Thismay be provided remotely or from a pipe-mountedthermostat on the supply water pipe, which is used tochange the operational mode from heating to cooling. Thethermostat controls a motorised two- or three-port valveadmitting water to the coil. The fan runs continuouslyduring operation; the fan may be switched by central timeswitch or locally.

5.10.2 Fan coil units. Airside control

The operation of a four-pipe FCU with air side control isshown in Figure 5.76. Outside air for ventilation can besupplied directly to the room or, less commonly, fordistribution via the FCU. Water supply to the coils is notmodulated and the coils use two-port valves withopen/close control. Output from the FCU is modulated byvarying the air path over the coils by the use of dampers,which adjust the proportion of air flowing across each coil.The dampers are interlinked so that the air does not flowacross both coils at the same time. Airside FCUs may bechosen in preference to waterside units where it is desiredto avoid the large number of small water control valvesrequired for waterside units. Where waterside units areinstalled, it is important to take care over the flushingprocedures to ensure that no debris is left which couldlodge in the valves; isolation of the valves during flushingis recommended.

5.11 Dual duct systemsBoth heated and cooled air are circulated throughout thebuilding in separate ducts. The air streams are combined atthe room terminal to provide the required temperaturecontrol. Dual duct systems require a substantial amount ofspace within the building to accommodate the two ductsand in their simple forms have poor energy economy, sinceheated and cooled air streams are mixed to provide control.They have fallen out of favour and new systems are nolonger specified. However, many examples of dual ductsystems are still to be found and some possible controlstrategies are described below. By using variable-volumecontrol of the supply fans and temperature reset of the twosupply temperatures to match demand, substantialeconomies in energy consumption may be made over asimple constant-volume system. The major types of dualduct system are described below; many variations arepossible. Control strategies for the extract fan and airrecirculation follow normal practice.

5.11.1 Constant volume, dual duct,single supply fan

The central air handling unit uses a single supply fan whichruns at constant speed, supplying air to the two supplyducts. The hot duct, often known as the hot deck, has itsown heating coil and the cold deck an independent coolingcoil. Each coil is controlled by its own temperaturecontroller. Each room or zone to be controlled has aterminal unit consisting of a mixing box and coupleddampers, which control the proportion of hot and cold airadmitted to the box from the supply ducts. The dampers aremodulated by a zone controller and are coupled to provide aconstant mixed air flow into the room, at the temperaturerequired to maintain the zone set point. The supply fanruns at constant speed. This system has high energyconsumption; some improvement may be made byresetting the hot and cold duct temperatures to match therequired demand.

5.11.2 Variable volume, dual duct,single supply fan

With this type of dual duct system, the room terminal unitshave independent dampers on the heated and cooled airsupplies. The RTUs provide a variable air flow to thecontrolled zones and at conditions of low load, both airflows are reduced to the minimum level required forventilation supply. The main supply fan speed is controlledvia pressure sensors in the two supply ducts. This operatesin a manner similar to that used for VAV systems. Acomparator control is used, giving priority to the lowerpressure in the two ducts, to ensure that each duct has thesufficient pressure to deliver air to all zones.

5.11.3 Variable volume, dual duct, dualsupply fans

This variation of the dual duct system offers the mostcontrol and greatest potential economy. Separate fans areused for the two ducts together with room terminal unitsthat give independent control of the heated and cooled air

5-48 Building control systems

Ceiling

Controller

θ Room sensor

+

M Tocooling

coilTodampers

Figure 5.76 Fan coil unit, four-pipe airside control. Fan runscontinuously. Dampers are connected to provide air path for heating,bypass or cooling; heating mode shown. Room temperature control is bymodulating dampers and on/off control of coils

Page 124: Building control system, aplication guide   cibse guide

supply to the room. The room terminal units control thezone temperature by providing the requisite amount of hotor cold air. The most energy efficient units do not mix theair supplies, but supply either hot or cold air as required. Adiagram of the unit is shown in Figure 5.77. The units aretermed variable constant volume. This implies that the airsupply rate is varied under proportional control to meet theroom temperature control requirements, but that the airflow is independent of variation in supply duct pressure.

The twin supply fans are controlled to give a fixed staticpressure in their respective supply ducts, in exactly the sameway as a VAV system (Figure 5.78). If all the room terminalunits call for heating, the cold air dampers in the units closedown and the cold deck supply fan reduces in speed tomaintain the supply duct pressure at the set point. This givessavings in fan energy compared with a simple constantvolume system. Further economies are made by resettingthe hot and cold supply temperatures. The aim is to heat andcool the two air streams just enough to provide the heatingand cooling required by the controlled zones. For thismethod of control intelligent room units are required whichsignal their damper positions back to the supply aircontroller via the BMS. The hot air supply temperature isreset so that just one hot air damper in the RTUs is fully open;if more than one damper is open the supply temperature isincreased to provide the required heat. The equivalentstrategy is used for the cold deck temperature. This controlstrategy is capable of providing the greatest economy inoperation. However, in practice it is sensitive to sensormalfunctions; a single sensor error or a faulty thermostatwill confuse the whole system. An alternative is to predictthe required supply duct temperatures from parameterssuch as outside air and mean indoor air temperatures.

5.12 Chilled ceilingsChilled ceilings provide cooling by a mixture of radiationand convection. Panels present a large surface area to theroom and have a substantial radiant component. Chilled

beams employ natural convection to cool room air, whichslowly descends into the occupied space. While some beamsare available which combine cooling, heating andventilation air supply, generally beams and ceiling panelsprovide cooling only and ventilation must be providedseparately. The control strategy for chilled ceilings isgoverned by their limited cooling capacity and thenecessity to avoid condensation occurring on the coldsurface(38). The ceiling panel and associated pipework run

Control strategies for subsystems 5-49

Zone temperature

Figure 5.77 Dual duct variable constant volume room terminal unit. Thecontroller modulates the hot and cold air flows to maintain zonetemperature. No mixing of the air flows is allowed. Damper positions aremade available to supply fan controller

Figure 5.78 Variable volume,dual duct, dual supply fan. Fanspeeds controlled to give constantduct static pressure. Duct heatingand cooling controlled to satisfyroom demands. Control of extractfan and recirculation followsconventional practice

Page 125: Building control system, aplication guide   cibse guide

several degrees below room temperature and condensationwill form if the coldest surface, typically the incomingchilled water flow pipe, falls below the local air dewpoint.Unlike fan coil units, chilled ceilings have no provision forthe collection or removal of condensate and the controlsystem must ensure that no condensation is formed whichcould drip into the occupied space. Condensation isprevented either by:

— control of the zone air dewpoint by dehumidifica-tion of ventilation air

— reset of the chilled water flow temperature tomaintain it above room air dewpoint by a smalltemperature differential, typically 2 K.

Dewpoint is measured using a RH and temperature sensorin the same enclosure and calculating the dewpoint withthe appropriate algorithm. Whichever method ofcondensation control is used, there should be an additionalsensor to detect the initiation of any condensation and stopthe chilled water flow.

For systems using mechanical ventilation that incorporatedehumidification of the supply air, the dewpoint of thesupply air is controlled so that the dewpoint of the zone airremains below the ceiling temperature. The minimumchilled water flow temperature for a ceiling is typically14ºC and the dewpoint of the zone air needs to be limitedto 12ºC. The energy implications of dehumidificationshould be considered at the design stage by estimating thefrequency of high outdoor dewpoints during hot weather.Consider whether comfort criteria may be relaxed byallowing the chilled water flow temperature to rise onthose occasions when the dehumidification plant is atmaximum capacity and unable to meet the 12ºC target. Useof a single internal dewpoint measurement position isnormally suitable for mechanically ventilated buildingswhere latent loads are similar throughout the building.The sensor is normally situated in the extract air duct. Ifone part of the building is known to have a high latentload, that area should be used as the reference location.Where sensible and latent loads are non-uniform over thebuilding and maximum cooling power is needed from theceiling, zoning is required. The dewpoint should bemeasured in each independently controlled zone and thechilled water temperature adjusted accordingly. This willensure that each zone receives the maximum potentialcooling.

Where no dehumidification of ventilation air is available,the ceiling flow temperature must be controlled to be atleast 2 K above the zone dewpoint. Where naturalventilation is employed, it is sufficient to control onexternal dewpoint, since the internal dewpoint will be closeto the external dewpoint, unless there are significantsources of moisture vapour in the building. The chilledwater flow temperature is controlled typically at 14ºC, orreset to 2 K above the external dewpoint, whichever ishigher. This will give relatively high ceiling temperaturesin summer, with correspondingly reduced cooling power.The same strategy for controlling flow temperature is usedfor mechanical ventilation without dehumidification;dewpoint may be measured in the zone air or in the extractduct.

The small temperature differential of 2 K between dew-point and water temperature is sensitive to measurementerror; three sensors are involved in its computation. Good

quality sensors must be used and be recalibrated at regularintervals. It is strongly advisable that a condensationdetector be used which will disable the secondarycirculation pump in the event of condensation beingdetected. This should be regarded as a safety mechanismand not used as a control method. The condensationdetector is mounted near the flow connection of theceiling panel, since this presents the greatest condensationrisk.

The flow of chilled water in the ceiling is of courseprimarily used to control the temperature of the occupiedspace; the above paragraphs deal with the necessity to avoidcondensation and emphasise the limited cooling poweravailable from a chilled ceiling. Chilled ceilings are notsuitable for rooms with high sensible or latent loads. Nightcooling or optimum start cooling may be used to supportthe limited cooling capacity. Chilled ceilings are to someextent self-regulating, since the cooling power increases asthe room temperature rises. The generally recommendedmethod for zone temperature control is by on/off control ofthe chilled water flow to the ceiling panel, either by controlof the circulation pump or by a two-port on/off valve. Bettercomfort control is achieved by modulating the flowtemperature of the chilled water, subject to the aboveprovisions of condensation prevention. Where chilledceilings are used to cool individual rooms which havevariable occupancy, a presence detector may be used toenable the circulation pump for each room; this iscombined with separate dewpoint measurement for eachcontrolled space.

Figure 5.79 illustrates the control strategy for a chilledceiling system that does not employ dehumidification ofventilation air. It shows individual zone control, withcontrol of chilled water flow temperature using a three-portvalve mixing circuit. The cooling circuit is enabled whenthe space temperature rises above the cooling set point,typically 23ºC. It is normally sufficient to use simple on/offcontrol of the secondary pump for cooling control, since thesystem is partially self-regulating. Flow temperature iscontrolled at a fixed interval of 2 K above the zonedewpoint and the circulation pump is disabled ifcondensation is detected. Where both mechanical andnatural ventilation are available, natural ventilation shouldbe restricted or prevented while the chilled ceiling isenabled.

5-50 Building control systems

Figure 5.79 Chilled ceiling, with control of flow temperature on zone dewpoint. Secondary circulation pump is enabled when zone air temperaturerises above cooling set point. Flow temperature is controlled at 2 K abovezone dew point. If condensation is detected, pump is switched off

Page 126: Building control system, aplication guide   cibse guide

5.13 Heat pumps

5.13.1 VRF split systems

This type of system is characterised by a type of fan coil unitmounted indoors, containing a direct expansion coolingcoil. The unit is connected by refrigerant lines to anoutdoor unit containing the compressor, condenser andcooling fans. Many systems operate as a reversible heatpump and so can provide heating or cooling from theindoor unit as required. No air treatment other thanheating or cooling is involved, so the system cannot strictlybe described as air conditioning. Split systems come in arange of sizes and may be classified as:

— Packaged split units. These comprise a single roomunit and outdoor unit. The simpler units providecooling only; heating and cooling are available ifthe unit can operate as a reversible heat pump.

— Multi-split unit. Several room units are connected toa single outdoor unit. Individual room temperaturecontrol is possible, but not simultaneous heatingand cooling from the same outdoor unit.

— Variable refrigerant flow (VRF) systems. Several roomunits are connected to a single outdoor unit, whichhas a variable-speed compressor to give variableload. In the more advanced systems, it is possiblefor different room units connected to the sameoutdoor unit to heat and cool simultaneously.

The distinction between multi-split and VRF systems is notclear cut and is one of size and sophistication. Large VRFsystems may contain several hundred indoor units and beconnected to the BMS. VRF systems have the advantage ofrequiring no central plant room and needing little space forinstallation; the room units are compact and are connectedby refrigerant lines to the outdoor unit. A single outdoorunit can typically serve up to 16 indoor units; extendedruns of refrigerant piping are possible and large buildingsmay be served by the appropriate number of outdoor units.Consideration must be given to the safety implications ofthe use of long runs of refrigerant pipework in occupiedspaces. Refrigerant vapours are neither toxic norinflammable, but permissible exposure limits are laiddown. The design of the installation and use of the buildingmust pose minimum risk of damage to the pipework. Eachgroup of units served by one outdoor unit operates as anindependently controlled system, but groups can be linkedtogether as described below. Energy efficient operationoccurs when indoor units within a group provide heatingand cooling at the same time. This depends on the unitsbeing served by the same outdoor unit, so the design of alarge system should take this into account, e.g. by groupingcore and periphery, or north and south zones within thesame group. Due regard must be paid to ventilationrequirements, which have to be provided independently.

Controls for split units are provided by the manufacturerand can provide a hierarchy of control levels, from occupantcontrol of individual indoor units up to full BMS capability(Figure 5.80). The outdoor unit of a multi-split unit isrequired to operate over a wide range of loads and normallyincorporates a variable-speed drive compressor. Theoutdoor unit contains its own controller to adjust therefrigerant flow to the indoor units in response to demand.The modular nature of the system means that that an

outdoor unit and its associated group of indoor units cancontinue operating under local control in the event of ahigh level control failure. While the details vary frommanufacturer to manufacturer, the general principles arethe same and are identified by the different controllersavailable.

Individual room unit controller

This is a simple unit designed for use by the room occupantand may be wall mounted, or hand held operating via an IRlink. It gives control of room temperature and fan speedonly, plus on/off. It may be overridden by a higher-levelcontroller.

Group remote controller

This provides control for a group of units connected to asingle outdoor unit. If required, it can override individualroom controller settings. The room units can be controlledtogether as a group or individually addressed. The groupcontroller provides the following control functions:

— mode: on/off, heating, cooling

— time scheduling

— room temperature set point

— fan speed

— air direction.

Control strategies for subsystems 5-51

Figure 5.80 Control hierarchy of a VRF multi-split system. Large systemsmay be built up while retaining occupant control of individual units. (a)Group of VRF room units, showing individual room controllers and groupremote controller. (b) Several groups of units under the control of a centralcontroller. (c) Large system with PC-based control, interfaced with BMS

Page 127: Building control system, aplication guide   cibse guide

In addition, the controller provides various checkingfunctions, information displays and fault diagnoses. Agroup remote controller can operate as a stand-alone unit orbe incorporated into a higher level system.

Central controller

This provides central control of up to a few hundred units.The units may be organised into groups and be operatedfrom the central controller, which allows group settings ofset points and time schedules. The individual room unitsretain their own local controllers, which may be used by theoccupants unless overridden by the central controller. Thecentral controller provides monitoring and fault diagnosisfor all the units under its control.

PC-based controller

For large systems, the central controller is replaced by a PC-based operating system which can interface with thousandsof individual indoor units. This provides the ability toorganise the units into groups, set flexible time schedulingand set points and monitor performance and faultreporting. Functions such as optimum start may beincorporated. The PC-based system connects via interfaceunits to the indoor units, or can operate via a layer of centralcontrollers if it is desired to retain some redundancy. Thissupervisor may be linked to the BMS via a suitable interface.This provides the BMS with the information to monitorfaults and temperatures and to carry out limited control ofset points and on/off switching. Alternatively, for somesystems it is now possible to obtain an interface which willprovide full integration with the BMS.

5.13.2 Reverse cycle heat pump units

This system consists of a number of room units which areinterconnected by an uninsulated two-pipe water loop.Each room unit contains a reversible heat pump, which canaccept heat from or reject heat to the water loop. An integralfan recirculates room air to provide local heating or coolingas required.

Each room unit is supplied by the manufacturer completewith a control unit, which has a thermostat and fan speedselector. The thermostat selects the heating or coolingmode of the heat pump; there is a deadband betweenheating and cooling set points of about 3 K, within whichthe compressor does not operate. The units may beindividually controlled by the occupants or arranged in amaster–slave configuration where several units serve thesame space. Central control of temperature setting and timescheduling is possible via the BMS. Damage to the units mayresult if they are operated with water loop temperaturesoutside prescribed limits and interlock switches are fittedto prevent this. Ventilation must be providedindependently of the heat pump units. This can be by acentral AHU, which filters and tempers the air beforedistributing it to the occupied space. Where possible, theventilation air may be supplied near the inlets of the heatpump units, so that it will mix with the recirculated air; thisis practical in the case of units mounted in the ceiling void.

The units must be provided with a circulating loop of waterof controlled temperature. Figure 5.81 shows the basiccontrol of the loop. The control system is required to ensure

that there is a flow of water maintained between limits oftypically 20 and 43ºC at all times that the room units areoperating. Heat rejection from the loop is performed by adry cooler or evaporative closed circuit cooler; an opencooling tower is unsuitable, since it is important tomaintain high water quality in the circulating loop. For thesame reason, heat injection to the loop is preferably via aheat exchanger, though direct injection from a boilerprimary circuit is permissible. Heat injection and rejectionnever occur at the same time. The water loop is fitted withconventional pressurisation and make-up control; these arenot shown in the figure. During normal operation, theheating and cooling valves are modulated to maintain a flowset point of 33 ± 2ºC; this temperature gives efficientoperation of the heat pump units, particularly in buildingswith year round heat gains. In conditions of high heating orcooling demand, the flow temperature may move outsidethis control band. High and low limit thermostats areinstalled which switch off the heat pump units if the flowtemperature falls below 18ºC or rises above 45ºC. Operationis restored at 22 and 41ºC respectively.

The control sequence on start-up is as follows:

(1) Start water pumps.

(2) Energise heat injection circuit.

(3) Energise reverse cycle heat pump units.

Step 3 may only take place when the water loop is up totemperature. It is recommended that a limit thermostat beplaced in the return of the water loop circuit. When thistemperature reaches the required limit, of at least 20ºC, theheat pump units are enabled and the limit thermostat is

5-52 Building control systems

Protection

Figure 5.81 Unitary water to air reverse cycle heat pump system.Circulating water flow temperature is controlled at about 33°C; room heatpump units are switched off if water goes outside range 20°–43°C

Page 128: Building control system, aplication guide   cibse guide

switched out of circuit. Alternatively, the control systemmay impose a time delay between energising the heatinjection circuit and enabling the heat pump units. Whenoperating the system under a time schedule control, thisdelay must be allowed for to ensure that the room units areenabled by the start of the occupied period. Where a centraltime switch is used, each unit should have a random timedelay to prevent high start currents resulting from all unitsbeing switched simultaneously. When individual time-switches are used, there will normally be sufficient variation.

The control sequence on shut-down is:

(1) De-energise the heat pump units.

(2) De-energise the heat injection circuit.

(3) Turn off the water pumps.

5.14 Natural ventilationThis section deals with buildings where natural ventilationis an integral part of the environmental control system. Oneof the goals of natural ventilation design is avoidance of theneed for air conditioning and such buildings are likely tofeature:

— solar shading and fenestration design to reducesolar gains

— use of daylighting and high efficiency lamps toreduce internal gains from lighting

— high thermal mass construction with exposedinternal mass to give a thermal flywheel effect

— design features to enhance natural ventilation flow,such as atria and ventilation stacks

— user involvement, often by openable windows.

The forces driving natural ventilation are low and variable,and the design of successful buildings presents someproblems. The CIBSE Applications Manual AM10(39) setsout the principles of successful design; a summary is givenin BRECSU GPG 237(40). Complete control of naturalventilation by manual window opening under control ofthe occupants is possible only in small buildings. For largerbuildings some form of automatic control is essential, withat least some of the ventilation control devices beingoperated according to the appropriate control strategy viathe BMS. It is common for the occupants to have somemanually operated vents at their disposal. Experienceshows that occupants in naturally ventilated buildings aremore tolerant of temperature variations than theircounterparts in air conditioned buildings, particularly ifthere is some form of user control in the form of openablewindows. Variation of internal temperature with externalclimatic conditions must be expected. Further informationon natural ventilation and passive cooling may be found inKolokotroni(41), Limb(42) and Allard(43).

5.14.1 Controlled devices

Controlled devices for natural ventilation consist primarilyof modulating inlet and outlet ventilation openings(39).Natural fluctuations in wind speed and direction give riseto variations in ventilation rate and make precise controldifficult. When the ventilation devices have a large area

relative to the space being ventilated, some form ofmodulating control will be required. For smaller openingsit may be possible to use open/shut control, particularly if anumber of openings may be operated in sequence.Consideration must be given to the performance of theopenings in rain and wind. If adequate protection is notprovided by some form of baffle or cowl, it will be necessaryto restrict the opening position in bad weather, to avoiddamage or rain ingress. Where natural ventilation is usedduring unoccupied hours for night cooling, considerationmust be given to any compromise of building securitypresented by the open air inlets. It is common to provideopening windows under occupant control in addition to thevents operated by the BMS.

5.14.2 Measurement devices

Technical aspects of sensors are covered in section 3. Naturalventilation control has its own measurement requirementsand some or all of the following may be required:

— External air temperature. This forms an essentialinput for natural ventilation control systems. Thesensor should be mounted on the north face of thebuilding and be provided with a radiation shieldagainst solar and sky radiation.

— Rain intensity sensors. These are fitted so thatwindows and vents may be shut automatically toprevent rain ingress. For a large building it may beadvisable to mount sensors at opposite ends todetect approaching rain.

— Wind speed. Windows and vents may be shut orpartially closed at high wind speeds to avoiddamage or to control over-ventilation. If combinedwith a rain sensor, wind speed sensors can be usedto give protection against driving rain ingress.

— Wind direction. This can be used to select windwardor leeward vents as appropriate.

— Solar radiation. A solar radiation sensor may be usedto increase ventilation rates at times of high solargain or to automatically control the operation ofsolar screens or window blinds.

— Slab temperature. The building fabric plays anessential part in passive temperature control andsome natural ventilation control strategies use ameasure of fabric temperature rather than internalair temperature. The sensor should be inserted to adepth of approximately 25 to 50 mm into the slab,packed with thermal paste and cemented in. As aless satisfactory alternative, a surface mountedsensor may be used which is covered withinsulation. A position should be chosen on aninternal wall or ceiling remote from temperaturedisturbances.

— CO2 concentration. This can be used as a set point forventilation control in addition to internal airtemperature and is of value in buildings with a largebut variable occupancy.

— Occupation. The number of people in the controlledspace may be used to set the target ventilation rate.This is feasible where the building has controlledentry and exit; in an integrated system it may bepossible to obtain information from the securitysystem.

Control strategies for subsystems 5-53

Page 129: Building control system, aplication guide   cibse guide

The low driving forces for natural ventilation preclude theuse of mechanical filtration. It is therefore important thatthe air intakes are positioned in clean areas. In somesituations, there may be times of day when externalpollution is unavoidable, and the inlets should becontrolled during these periods.

5.14.3 Control strategies

The aim of ventilation control is to provide sufficientoutdoor air for ventilation purposes and to remove anyexcess heat gains. For any given ventilation opening, therate of supply of outside air is greatly affected by externalambient conditions of wind and temperature and so theprovision of a minimum ventilation opening does notguarantee adequate ventilation; on the other hand, inwindy conditions, there may be excessive ventilation. Manynaturally ventilated buildings have a large but variableoccupancy and hence a changing need for ventilation. It istherefore common to use some form of demand controlledventilation (DCV), normally employing CO2 as the measuredvariable. Other air quality sensors have not foundwidespread application. The level of occupation may beused to estimate the rate of CO2 production and hence therequired ventilation.

In naturally ventilated buildings, heating is provided by anindependent system, typically LTHW radiators. Naturalventilation is used to maintain satisfactory levels of CO2 atall times and to provide cooling when required. Permanenttrickle ventilation is provided so that the legal minimumopenings are maintained when the ventilation controlsystem has closed all controlled ventilation openings. AnApproved Document (AD Part F1) of the BuildingRegulations sets the minimum size for the opening area inoffice rooms as 4000 mm2 in rooms of up to 10 m2 floor area,and 400 mm2 per m2 of floor area in larger rooms. The airflow through the ventilators is subject to wind pressure andsome means of control is desirable. Hit and miss ventilatorsunder occupant control may be provided, or automaticventilators which self-regulate under different pressureconditions. Alternatively, background mechanical ventila-tion may be used to provide the minimum ventilation airsupply. The use of night ventilation to dissipate heat gainsacquired during the heat of the day and to precool thebuilding fabric is an important strategy in avoiding the useof mechanical cooling and it is possible to keep the internaltemperature below daytime external ambient temperatureby this means.

Ventilation rates will inevitably fluctuate under theinfluence of changes in wind speed. Where modulatingcontrol of natural ventilation openings is provided, it willnot be possible to use fast acting control loops to try andachieve more accurate control. Large differential bandsshould be used and it is not normally necessary to use PID orPI control loops(44). Control of natural ventilation systemcan be described in terms of two strategies(45,46), one whichoperates during normal occupation periods the other whichprovides night-time cooling of the structure.

5.14.3.1 Occupation period

During warm weather when no heating is required, theventilation openings are modulated by the control systemto control the internal air temperature. During colder

weather, when the internal zone temperature falls below theheating set point and the heating system is activated, thevents are set to their minimum position, providingsufficient air for ventilation only. When demand controlventilation is present, ventilation to maintain air qualitytakes precedence. The target air quality is typically a CO2concentration below a set point of 1000 ppm. The decisiontree is shown in Figure 5.82. Depending on the complexityof the installed system, vent opening may be determined bywind direction to select the optimum choice of windwardand leeward openings.

The decision tree does not show any special action to betaken when the outside temperature rises above the internalset point, other than to open all vents to the maximum.Bringing in outside air at a higher temperature than theinternal zone temperature will result in a heat gain, and thereis an argument that vents should be closed to minimise theingress of warm outside air. However, this does not allow forthe effect of internal heat gains which will tend to increasethe inside temperature to a level above that outside. Ingeneral it will be more effective to use warm outside air forventilation than to allow the gains to build up inside withoutventilation. Where the building has openable windowsunder occupant control, users will usually open windows tothe maximum in hot weather, nullifying any attempt toreduce ventilation. This will aid comfort by increasing localair movement. In practice it will be generally found adequateto maintain maximum ventilation in hot weather; this mayhave to be reconsidered in climates other than the UK(45).

5.14.3.2 Night cooling

The aim of night cooling is to use ventilation during theunoccupied period to dissipate heat gains absorbed by thebuilding during the day. Buildings designed for naturalventilation typically have high thermal mass with exposedconcrete slabs. These have a flywheel effect ontemperatures, absorbing heat during the day and sopreventing air temperature from rising too high. It istherefore advantageous to ensure that the slabs are cooledduring the night. The design of a natural ventilation systemis integral with the architectural design of the building.This extends to the control system and there are few off-the-shelf systems for general application. Therecommended control strategy simply uses ventilation tobring the zone temperature down to the lower limit of thecomfort band, i.e. as low as possible without bringing theheating system into action. More complex control strategieswhich bring the zone temperature below the comfort bandin an attempt to maximise cooling have not provedworthwhile in practice(46); see also Kolokotroni(41).

The night cooling system is enabled if:

— the mean outside air temperature over theperiod 1200 to 1700 > the night cooling(mean ambient) set point (typically 20ºC)

or the average daytime internal temperatureover the period 0900 to 1700 > the nightcooling (mean zone) set point (typically22ºC)

or the slab temperature > the slab cooling setpoint (typically 23ºC)

or peak zone temperature > peak set point(typically 23ºC).

5-54 Building control systems

Page 130: Building control system, aplication guide   cibse guide

If night-time cooling is enabled, during the non-occupiedperiod the vents are opened for cooling if:

— zone temperature > outside air temperature

and zone temperature > heating set point(typically 19ºC)

and minimum outside air temperature > 12ºC

and no bad weather interlock.

The heating system should not be operated when nightcooling is enabled. Night cooling should be availablethroughout the whole non-occupied period and for sevendays per week. Because of the long time constant of thebuilding structure, when the night cooling has been appliedfor a period of five days or more, it should be continued for afurther two nights after the afternoon outside temperaturehas fallen below the night cooling set point.

5.14.4 Mixed mode

The term mixed mode implies a combination of naturalventilation with mechanical ventilation and possiblymechanical cooling. The general philosophy is that naturalventilation should be used to the greatest possible extent,with mechanical services employed only when necessary.By these means it should be possible to minimise energyconsumption. Mixed mode has no precise definition anddifferent types have been classified(45,47):

— Contingency. This describes a building that has beendesigned primarily for natural ventilation, with theprovision for the addition of mechanical serviceslater if found necessary.

— Zoned. Some zones of the building are providedwith mechanical services where there is a specificrequirement. An example might be a building with

Control strategies for subsystems 5-55

Figure 5.82 Decision tree fornatural ventilation duringoccupied period

Page 131: Building control system, aplication guide   cibse guide

naturally ventilated office spaces, a mechanicallyventilated kitchen area and an air conditionedcomputer room.

— Complementary. Both natural ventilation andmechanical services serve the same zone. Thesystems may be operated in either changeover orconcurrent mode. Concurrent systems oftenprovide a basic level of mechanical ventilation toensure a permanent draught free ventilation airsupply, while allowing occupants to open windowsas they choose. Changeover systems operate indistinct modes to satisfy different requirements.For example, windows may be openable in mildweather, but locked shut when mechanical plant isused for either heating or cooling. Changeoversystems present practical problems of producingeffective control strategies and ensuring thatoccupants are fully conversant with the differentrequirements of the various modes of operation.

The use of mechanical services to complement naturalventilation has two main functions:

— Winter ventilation. During the heating season, it maybe difficult to control a natural ventilation systemto provide a supply of ventilation air which issufficient for ventilation purposes, but not so largethat it causes excessive heat loss or uncomfortabledraughts. It may be preferable to close the naturalventilation system and employ mechanicalventilation during the heating season.

— Summer cooling. The use of natural ventilation tocontrol summer temperatures was described above.In some conditions of warm still weather, thenatural driving forces may be insufficient toprovide the required level of natural ventilationand this is supplemented by the use of mechanicalventilation. The same ventilation paths my beutilised, e.g. by positioning a fan in an extract stack.

The control strategy for mixed mode operation is thereforefundamentally the same as for natural ventilation. Duringnight cooling, the strategy set out in 5.14.3.2 is adopted;mechanical ventilation is not used during night cooling.During winter heating, the natural ventilation system isclosed and mechanical ventilation is used to provide therequired ventilation supply. During summer daytimeventilation, the natural system operates preferentially asdescribed in 5.14.3.1 above. Only if the zone temperaturerises more than a predetermined amount above the coolingset point and all natural inlets and outlets are driven fullyopen is the mechanical ventilation brought in tosupplement natural ventilation. In situations where theexternal temperature is significantly above internal airtemperature, increased ventilation may result in additionalheating of both the space air temperature and the buildingfabric, so reducing the beneficial radiant cooling fromexposed ceiling slabs. If any zones are fitted withmechanical cooling, it will be necessary to shut down thenatural ventilation openings and revert to mechanicalventilation before enabling the cooling system.

5.15 Lighting controlsLighting is often the largest consumer of electricity in abuilding. In a naturally ventilated building lighting may

account for 40% or more of the total electricity cost. Theoverall lighting design together with the choice of lampsand fittings pays the major part in determining the energycost of the lighting system; further reductions can beachieved by the use of an effective lighting controlsystem(48). Part L of the Building Regulations(49) requires theuse of efficient light sources and specifically requires theuse of controls, stating:

where it is practical, the aim of lighting controlsshould be to encourage the maximum use ofdaylight and to avoid the unnecessary use oflighting when spaces are unoccupied.

The lighting conditions produced by the controls systemmust at all times provide satisfactory illumination for theoccupants of the building. Safety aspects are dealt with byLighting at Work(50). The CIBSE Code for Interior Lighting(51)

states ‘Any control system must ensure that acceptableconditions are always provided for the occupants. Safetyand visual effectiveness and comfort must take priority overenergy saving’. The control system must default to a safecondition if a fault develops and return to the pre-faultcondition after the fault has been rectified. The emergencylighting system must not be connected to the lightingcontrol system. While the major benefit of lighting controlis usually seen in terms of energy saving, a good controlsystem brings other important benefits:

— Occupant satisfaction and productivity. A goodworking environment is essential for comfort andproductivity. The widespread use of display screenequipment has made lighting design more critical.

— Planning flexibility. The use of electronic controlsallows redesign or reallocation of work layoutswithout alteration to fixed luminaires or wiring.Increased controllability allows for shift workingand unpredictable work patterns.

— Better management information. A centralisedlighting control system can provide information onlighting use by different zones, assist withmaintenance and can assist in security when linkedto presence detectors.

5.15.1 Control methods

Four basic methods of lighting control may be described,which may be used separately or in combination with eachother. Not all types of lamp are suitable for dimming orfrequent switching; this will be considered below.

5.15.1.1 Localised manual controls

Local switches and dimmers can either be permanentlyhardwired as wall-mounted switches or ceiling-mountedpull switches, or may be operated by remote control.Remote control devices are similar to the handsets used tooperate television sets and are based on infra red orultrasonic signals. The receiver may be ceiling mountednear to the luminaires being controlled, so that walls orpartitions may be moved without the need for rewiring. In alarge space, the luminaires should be switchable in groups.Luminaires controlled by a single switch should cover anarea with roughly constant daylight factor; in a large spacethis would mean that rows of luminaires parallel to thewindows would each have their own switch. In other

5-56 Building control systems

Page 132: Building control system, aplication guide   cibse guide

situations, it would be appropriate for luminaires related toa particular activity or work group to be controlledtogether. The manual switches should be placed as near aspossible to the area being controlled. The BuildingRegulations(49) require that the distance from the lightswitch to the furthest fitting that it controls is no more than8 m, or three times the height of the height of the floor levelof the fitting, whichever is greater. Where multiple switchesare located together, clear labelling is of benefit.

5.15.1.2 Timeswitches

For buildings with fixed occupancy times a simpletimeswitch can be effective, set to switch lights on shortlybefore work commences and to switch the full lighting offafter working hours. Sufficient lights may need to be left onfor security and safety, and some form of override should beprovided for people working late; this should incorporatean extension timer to prevent the lights being left on allnight. Timeswitches are effective for external lighting, butrequire adjustment with season.

Reset control is an extension of a timeswitch, relying on thefact that people are motivated to switch lights on ratherthan off. A time control switches the whole lighting systemoff at predetermined times. Occupants are provided withlocal controls to reset individual luminaires or small groupsof luminaires back on as required. Typical switch-off timesare lunch time, shortly after the end of the working day andafter the cleaning period. A variety of local reset switchingmeans is possible, including pull cords and infra redtransmitters.

5.15.1.3 Occupancy detection

Occupancy or presence sensors can be used to switch onlights as a person enters the controlled area. The lights areswitched off again when no occupancy has been detected fora set interval; the interval is chosen to avoid frequentswitching, which can shorten lamp life. A minimum onperiod of 10 minutes should be set; general practice is to useon-times of up to 30 minutes. An alternative strategy is touse a manual switch to switch the lights on; the presencesensor switches the light off when no occupancy has beendetected for a set time. This is sometimes known as absencesensing. Presence sensing finds application in infrequentlyused areas such as store rooms or spaces where people mayhave their hands full when entering.

The most common detectors are passive infra red (PIR),which detect the movement of a warm body across theirfield of view. The range of operation of a PIR is up to about10 m. For larger spaces a microwave detector may be used,which operates by the Doppler shift of radiation reflectedfrom a moving body; operating ranges of 50 m are possible.Acoustic sensors are available which respond to noise.Presence detectors are normally combined with a photocell,which prevents operation of the lighting when there issufficient ambient light.

5.15.1.4 Lighting level

For continuously occupied spaces which have a substantialproportion of daylighting, it is possible to control theartificial lighting so that it is turned off when daylight issufficient and on again to produce the required amount of

light as the daylight contribution falls. Photocells are usedto monitor the light level in the space and regulate thelighting accordingly. Where simple on/off switching isused, there is a danger that switching will cause noticeableand annoying changes in light level. To avoid complaints,the switching levels need to be set fairly high; a switch-onoccurs when the daylight illuminance is about twice therequired task illuminance and switch-off takes place whenthe combined artificial and daylight illuminance is three orfour times the required task illuminance. It is also necessaryto incorporate a time delay into the control system to avoidrapid switching caused by rapidly varying light levels,caused, for instance, by passing clouds.

More effective control can be effected by the use ofdimmers. Suitable lamps can be smoothly dimmed down to10% of their maximum light output before becomingunstable. A ceiling-mounted photocell looking downwardsresponds to the combined daylight and artificialillumination and the control system is set to provide aconstant level of illumination. This system not only takesaccount of varying daylight, but also the fall-off in lightoutput during the maintenance cycle of the lamp andfitting. Since it is necessary to design an installation toprovide the required illumination at the end of the cycle,lamps are oversized when new. The use of an automaticcontrol system will show a saving in energy at thebeginning of the maintenance cycle, when the lamps arenew and the luminaires clean.

5.15.1.5 Scene set control

The use of lighting is an important part of interior design.In commercial applications such as restaurants, hotels etc.different lighting schemes may be required at differenttimes of day. Other examples would include multi-functionrooms requiring a range of lighting scenes to suit differentactivities. A scene-set controller can be used to store theindividual luminaire settings and to switch or cross-fadebetween settings as desired. Such a controller is unlikely tobe combined with other automatic control systems and thedifferent scenes are manually selected as required. Displaylighting is excused from some of the provisions of Part L ofthe Building Regulations.

5.15.2 Systems and components

5.15.2.1 System selection

Factors influencing the selection of a lighting controlsystem include:

— the expected occupancy pattern

— the availability of daylight

— the desired level of control sophistication

— the capital cost of the system versus potential savings

— need to accommodate changes in the building oruse patterns.

A building with little daylight and a workforce workingregular hours will require little more than a simpletimeswitch to turn off the lights at the end of the workingday and a provision to ensure that they are not all turned onagain and left on by the cleaners or security staff. Figure 5.83

Control strategies for subsystems 5-57

Page 133: Building control system, aplication guide   cibse guide

shows an initial decision tree for selecting suitable forms oflighting control for a number of applications.

An additional factor to be considered is the interactionbetween the lighting and HVAC systems. In some buildingsconstructed on the principles known as integratedenvironmental design (IED), heat recovered from lightsplayed an important part in the thermal control of thebuilding; a refurbishment in such a building whichproduced a lower and fluctuating heat gain from thelighting system could create problems with the HVACcontrol system.

5.15.2.2 Lamps and control gear

The selection of lamp type for a lighting installation willdepend on may factors, such as efficiency, colourrendering, physical dimensions and appearance. TheBuilding Regulations(52) require that at least 95% of theinstalled capacity measured as circuit watts should berestricted to the lamp types indicated in Table 5.6;display and emergency lighting are excluded. Further

information on lamp types is available in the LIF LampGuide(53). Lamp types differ greatly in their suitability forcontrol applications. High intensity discharge (HID)lamps, while offering high luminous efficacy, offer only alimited range of dimming possibilities and are unsuitablefor control by presence detection, since restart of a warmlamp may take several minutes. Conventional tungstenfilament lamps (GLS) are easily dimmed and offerimmediate switching with no penalty in lamp life.However, their low luminous efficacy prevents their beingused as the main light source in commercial buildings.The same is true for tungsten halogen lamps, which havethe additional disadvantage of requiring special controlgear for the dimming of low voltage lamps.

Tubular and compact fluorescent lamps form the mainstayof most lighting schemes in commercial buildings.Fluorescent lamps require electrical control circuits fortheir operation, which may be classified as follows.

— Switch start. The simplest and cheapest option, withpenalties in lamp efficiency and life where frequentswitching occurs.

5-58 Building control systems

Figure 5.83 Selection of lightingcontrol strategy

Table 5.6 Principal lamp types and their suitability for control applications

Lamp Control gear Dimming Frequent Part switching L ?

GLS Tungsten filament None *** *** No

LV tungsten halogen None ** *** No

Compact fluorescent Yes Yes

Tubular fluorescent Switch start * * Yes

Cold start electronic * * Yes

Warm start * ** Yes

High frequency * ** Yes

High frequency regulating *** *** Yes

SOX Low pressure sodium Yes * * No

HPS High pressure sodium Yes ** * Yes

MBI Metal halide Yes ** * Yes

***Suitable; **possible; *unsuitable.

Page 134: Building control system, aplication guide   cibse guide

— Electronic start. The electronic circuit givesinstantaneous and flicker-free starting. The warmstart version warms the cathode for up to 2 s beforestarting, giving improved lamp life.

— High frequency. The lamp is run at a frequency ofabout 30 kHz instead of mains frequency. Thiseliminates flicker and improves the luminousefficacy by up to 20%. In addition, the power factorof the lighting load is improved.

— High frequency regulating. As for high frequency,with the added advantage of being smoothlydimmable down to about 10% power. This is thecontrol gear of choice for lighting control systems.

The life of a fluorescent lamp is adversely affected byfrequent switching. Neither conventional starter switchcircuits nor cold start electronic circuits are suitable foruse with presence detection. Warm start electronicballasts preheat the cathode for a period ranging from aminimum of 0.4 s to about 2 s. The Lighting IndustryFederation(54) recommends that where fluorescent lampsare to be switched frequently, the longer warm-up timeshould be considered and that a minimum on-time of 20minutes should be employed to ensure that both lampsand ballast reach normal operating temperature beforerecycling.

5.15.2.3 Lighting Control Systems

A lighting control system may be as simple as alightswitch by the door, which may be entirelysatisfactory in some situations. At the other end of thescale of sophistication, it is possible to have eachluminaire individually addressable and controlled via theBMS. Such a system allows the full range of controlpossibilities. Luminaires may be individually controlledby permitted users over the telephone system or from aPC. The BMS can record lamp burning hours for plannedmaintenance or detect lamp failure. The energy ofindividual or groups of luminaires may be recorded,making individual billing possible in multi-occupiedbuildings. Since all control is via a low voltage bussystem, there is no need for rewiring if the buildinglayout is altered. Several manufacturers provide lightingcontrol equipment which is compatible with one or moreof the major field network protocols.

The four basic control methods described in 5.15.1 arebrought together in a lighting control system using the so-called intelligent luminaire. The luminaire incorporates apresence detector and a downward-looking photocell,which measures the level of illumination in the area servedby the luminaire. The built-in controller ensures thatillumination is only provided when the space is occupiedand provides a constant level of illumination in varyingambient light levels. In addition, individual luminairesmay be controlled directly by the appropriate user, whohas control over dimming and brightening, typically withan infra red controller or over the telephone network. Inaddition, the luminaires can communicate with each otherover a bus system. This makes it possible to program theluminaires to act cooperatively so that, for instance, agroup of luminaires is switched on if a presence is detectedby any one of them. This has application in the lighting ofcirculation spaces or when it is desired to anticipate

movement; for example, it is possible to switch the lightson in a room as a person approaches the door, avoiding theproblem of walking into an unlit area. Where a person maybe working after hours in a large office, the luminaires canbe programmed to provide general background illumina-tion to avoid the person working in an isolated pool oflight.

The communications receiver in the intelligent luminairemay also be used to receive information from other sensors,such as a wall mounted temperature sensor. The multi-sensor can therefore serve as a communications point forthe entire BMS. With the logic of lighting control strategiesbecoming more complex, it is important that the systemdesign should be tested in advance, using a ‘what if ’approach to indicate the operation under all possible userscenarios.

5.15.2.4 Human factors

The operation of lighting controls is immediately apparentto the building occupant and for this reason it is essentialthat the needs and behaviour of the users is taken intoaccount from the start. Surveys have shown that whereusers had little or no control of the lights in their own workspace, or low awareness of the proper use of controls, lowsatisfaction and energy wastage were common. Highsatisfaction and energy efficiency were generally associatedwith high levels of local control plus high awareness, byboth end-users and facilities managers, of how the controlsoperated.

Occupant surveys have suggested some general points to beborne in mind.

— People are good at judging whether they need the lightson. Do not switch lights on or increase brightnessautomatically unless this is essential for safety, orappropriate for managed areas.

— People are not good at switching lights off. Try toprovide automatic switch-off, but . . .

— People do not like being plunged into darkness. Wherepossible lights should be dimmed down, or awarning given. There should be readily accessiblelocal override switches.

— People dislike automatic systems which distract them ordo not do what they want. Automatic switching orstepped dimming is best done at fixed times ratherthan at seemingly random intervals. Occupancydetectors should be positioned to avoid nuisancetriggering.

— Local controls should be accessible and their operationintuitive. Switches should be close to the point ofdecision and their operation clear.

— Individual requirements differ. Given the choice, usersselect a wide range of illuminance levels. Lowerlevels are often chosen for work with computerscreens; people with less acute eyesight or moreexacting work may need additional task lighting.

Six categories of space have been identified and classified interms of their perceived ownership?, i.e. the person orgroup who are de facto in control of the lighting of thatspace(55). Each of these types of space has differentrequirements, which are summarised in Table 5.7.

Control strategies for subsystems 5-59

Page 135: Building control system, aplication guide   cibse guide

5-60 Building control systems

Table 5.7 Lighting controls for different categories of occupied space(55)

Space type Characteristics Examples Issues and problems Suitable approaches

Owned Occupants regard the Small offices, Occupants need to Avoid automatic switch-on, space as their own and particularly for one or two switch both on and off and except possibly in small want to make all their persons. Residential greatly object to ‘Big windowless rooms. own decisions about the homes Brother’ controls. Any Lightswitches by the door status of the lights. A automatic adjustments can be used effectively. close relationship should be imperceptible, Consider absence sensing between user, space and e.g. absence sensing and photoelectric dimming control makes this once the room is vacated, to avoid waste. Always possible or gradual dimming provide local override

Shared Occupants regard their Open plan offices. Some Systems default to Separate control circuits part of the space as their production, maintenance convenient but of lighting for own, but cannot be in and laboratory areas inefficient states, circulation, decoration full control of typically with all the and safety avoids the environmental systems lights on. The status then first arrival switching on which have to suit others only changes if the everything. Ideally have as well. Ideally there situation becomes local switching and should be some lighting undesirable or at the end adjustment at individual control, or task lighting of the day. Security staff work stations. available on request and cleaners may need Consider ‘last out,

different controls lights off ’ facility

Temporarily Occupants are usually Meeting rooms, Controls not easy to find Highly visible easy-to-owned present for a few hours at interview rooms, quiet or understand. In meeting understand local

a time. They can be in rooms, study carrels, rooms presence detection controls are required in individual or consensus laboratory writing up must include local obvious places. Absence control while they are areas, classrooms, lecture override for slide sensing is desirable, there, but may not be rooms presentation etc. preferably with ‘last out, very familiar with the Nuisance triggering of lights off’ facility at the controls. Lights left on presence detectors. exit. Teaching and when the room is Manual ‘on’ often presentation rooms may vacated; nobody feels preferable require dimming and responsible control from lectern

Occasionally Occupants visit Toilets, store rooms, Lights get left on for Consider occupancy visited occasionally. There may equipment and machine long periods unnecessarily. sensors or time-delay

be long vacant periods in rooms, garages, cleaners’ Occupancy sensors may switches if there are no between. People may cupboards, bookstacks, not see people in remote safety implications, e.g. sometimes have their warehouse aisles parts of the space or may in bookstacks where the hands full or be be triggered by passers by main aisles are lit. For manoeuvring trolleys. small rooms a switch by Safety lighting may be the door and an indicator needed in larger spaces light may be enough

Unowned Spaces though which Corridors, circulation Lights are often left on Presence-detecting or people pass. People will areas, stairs, lobbies, unnecessarily, either in time-delay switches expect their path to be lit lifts, loading bays, car daylight or when the area allow lights to be off adequately. They may be parks. Lighting should is empty. Difficult to when people are absent. prepared to operate well- be well-structured to suit find lightswitches; these Avoid sudden darkness placed light switches, but the route, and be low need to be in obvious by dim-out, sequenced they may not switch energy places, well-marked and switch-off of background them off afterwards perhaps with safety lighting. In daylit

locator/indicator lights. areas, photoelectric Too many lights controls can give switched on at once excellent energy savings

Managed The larger public spaces Restaurants, libraries, Lights are often left on Arrange circuits in which occupants concourse etc. Often unnecessarily, either according to usage and would not normally have well-determined use when there is sufficient daylight. Consider expect to operate lights. hours, so systems can be daylight or when there photoelectric daylight Ambient light levels can programmed are no people about. linking and low energy often be allowed to vary Management are often safety or utility lighting within quite a wide range too busy with other out of hours. Where

things to make fine added sparkle is adjustment to lighting required, try to use low

energy decorative lighting

Page 136: Building control system, aplication guide   cibse guide

5.16 SummaryControl strategies for entire systems can be broken downinto strategies for component subsystems. A fundamentalrequirement of a building control system is that it ensuressafe operation of the plant under its control. All strategiesmust provide for alarms which give warning of a variableout of limits or plant requiring attention interlocks, whichautomatically prevent or shut down operation of plantwhen necessary. In addition, the strategy must include theaction to be taken on receipt of a fire alarm.

Unsuitable control strategies for boilers can lead toinefficient and problematic operation. A primary watercircuit using a constant-flow circulation pump andcommon header is recommended for effective and reliablecontrol. Multiple boilers are used with sequencing controlto match a variable load. For modern low loss boilers, it isnot necessary to isolate off-line boilers and sequencecontrol is provided on the return temperature from acommon header. For high water content boilers it may benecessary to provide individual circulation pumps and toisolate off-line boilers. Boiler protection circuits arenecessary where the return flow to the boiler is of variableflow and temperature.

Chiller controls are normally provided as part of a packagedunit. Where a separate cooling tower is employed, efficiencymay be improved by controlling the condenser watertemperature. The technique of near optimal controloperates by modulating cooling tower fan speed as afunction of chiller load and leads to operating efficiencies.In cool ambient conditions it may be possible to dispensewith chiller operation and operate in free cooling mode,where the cooling tower alone is able to meet the buildingcooling load.

In secondary water circuits the use of variable-speed pumpsand two-port valves offers savings in pumping energy andinitial cost but care is required if the system is to remain inbalance and under control under varying load conditions.Where throttling circuits are used to vary output, speedcontrol of the circulation pump is recommended, coupledwith the use of high rangeability two-port valves. The use ofdifferential pressure control valves can be valuable inmaintaining system balance.

HVAC systems using a central air handling unit normallyemploy some air recirculation. Return air and outside airare mixed to produce the required supply air temperature ifpossible; otherwise the outside air proportion is set at aminimum or maximum value as determined by the outsideconditions. Where supply air humidity is controlled, it isbetter to use enthalpy control of the recirculation dampersfor greatest efficiency. Heat recovery may be used instead ofor in addition to recirculation. Where a variable rate heatrecovery device is used, it is modulated to control thesupply air temperature as far as possible.

Provision of the necessary amount of outside air forventilation purposes must always be ensured. Where avariable air volume system is used in association withrecirculation, it is not sufficient to simply provide aminimum proportion of outside air, since this will beinadequate at low volumes. Several techniques areavailable. The outdoor air damper position may becontrolled as a function of fan supply speed, so that it opens

further to compensate for reduced supply volume. Theoutdoor air supply may be measured directly and the valueused to modulate the intake damper. Where both extractand supply flow rates are available, the extract fan can bemodulated, so that the extract flow exceeds the supply flowby the required amount; the balance is the outdoor airintake.

VAV systems consist of a central air handling unit whichsupplies conditioned air to a number of VAV room terminalunits. The RTUs control room temperature by modulatingdampers to vary the air supply to the room. Variable-speedcontrol of the main supply fan is required for energyefficiency. The fan speed may be controlled as a function ofthe static pressure in the main supply duct. Positioning ofthe pressure sensor two thirds of the distance down the ductwill normally be found suitable. Where intelligent VAVboxes are used, which are capable of signalling their damperposition, it is possible to match the air supply to aggregatedemand. Further efficiency may be achieved by resettingthe air supply temperature set point as a function of totalload.

Fan coil units provide room temperature control underlocal control, but can be linked to a BMS for functions suchas time scheduling, group reset of set points or optimumstart heating and cooling.

Variable refrigerant flow systems consist of a number ofroom units, connected to an outdoor unit containing acompressor, connected by refrigerant lines. Simultaneousheating and cooling among units powered by a singleoutside unit is possible, giving efficient operation. VRFsystems are supplied with packaged control systems, whichhave limited interconnection possibilities with a BMS;control of time scheduling and set points is normallypossible, together with alarm transmission.

Chilled ceilings are to some extent self-regulating and two-position control of chilled water flow to panels or beam isadequate. Prevention of condensation on the cold surface isimportant. Where central air handling plant is used, themost effective method is to control the room temperaturedewpoint to at least 2 K below the chilled watertemperature; otherwise the chilled water flow temperatureshould be maintained 2 K above room air dewpoint. In bothcases, an additional condensation detector should be usedas a precaution.

Lighting is often the largest consumer of electricity in abuilding. There are four basic methods of lighting control.

— Localised manual controls. Switches must be readilyaccessible; the use of pull cords or remote controlhandsets can be advantageous. Groups ofluminaires switched together should be grouped byactivity or daylight factor.

— Timeswitches. These can be effective for set workschedules. Systems where lights are switched off bytimeswitch and switched on manually are effective.

— Occupancy detection. This is useful in zones whichare used occasionally. The lights come on when anoccupant is detected and go off when no occupancyhas been detected for an interval of at least 10minutes.

— Lighting level. For continuously occupied spaceswith some daylight, the artificial lighting can be

Control strategies for subsystems 5-61

Page 137: Building control system, aplication guide   cibse guide

modulated to provide a constant level ofillumination. Dimming preferable to on/offswitching and rapid fluctuations in level should beavoided. Intelligent luminaires are available,incorporating their own presence detector andphotocell; luminaires communicate via a bus andare individually addressable, allowing the lightingsystem to be integrated with the BMS.

References1 HSE Out of control — why control systems go wrong and how to

prevent failure (Sudbury: HSE Books) (1995)

2 Fire engineering CIBSE Guide E (London: Chartered Institutionof Building Services Engineers) (1997)

3 CIBSE Fire precautions: sources of information on legal and otherrequirements Technical Memorandum TM16 (London:Chartered Institution of Building Services Engineers) (1990)

4 Heating systems and their control GIR 40 (Garston: BuildingResearch Energy Conservation Support Unit) (1996)

5 Boiler (Efficiency) Regulations 1993. Statutory Instrument 3083(London: The Stationery Office) (1993)

6 HSE Automatically controlled steam and hot water PM5 (Sudbury,Suffolk: HSE Books) (1989)

7 Petitjean R Total hydronic balancing 2nd ed (Ljung, Sweden:Tour and Andersson) (1997)

8 Minimising the risk of Legionnaires’ disease CIBSE TM13(London: Chartered Institution of Building ServicesEngineers) (1991)

9 HSE The control of legionellosis including legionnaires’ disease HSG70 (London: HSE Books) (1993)

10 Braun J E and Didderich G T Near optimal control of coolingtowers for chilled water systems ASHRAE Transactions 96(2)806–813 (1990)

11 De Saulles T and Pearson C Set-point and near optimal controlfor cooling towers Building Services Journal 20(6) 47–48 (1998)

12 Ice storage systems CIBSE TM18 (London: Chartered Institutionof Building Services Engineers) (1994)

13 Trend Ice storage. Monitoring and control for optimum performance(Horsham: Caradon Trend) (1995)

14 Levermore G J BEMS II (working title) 2nd ed (London: E & FN Spon) (1999)

15 Flow of fluids in pipes and ducts CIBSE Guide C4 (London:Chartered Institution of Building Services Engineers) (1977)

16 Seyfert H The control device in water circulation 450/en/95-06(Switzerland: Staefa Control System) (1995)

17 Petitjean R The case for hydronic balancing Journal of theChartered Institute of Building Services 15(5) 43–44 (1993)

18 Variable flow control GIR 41 (Watford: Building Research EnergyConservation Support Unit) (1996)

19 ETSU Guidance notes for reducing energy consumption costs of electricmotor and drive systems Good Practice Guide No 2, 2nd ed(Harwell: ETSU) (1990)

20 Bower J R The economics of operating centrifugal pumps with variablespeed drives C108/81 (London: I Mech E) (1981)

21 Centrifugal pumps ASHRAE Handbook: HVAC systems andequipment Chapter 38 (Atlanta, GA: American Society ofHeating, Refrigeration and Air Conditioning Engineers)(1996)

22 Parsloe C J The design of variable speed pumping systems AG 14/99

(Bracknell: Building Services Research and InformationAssociation) (1999)

23 Rishel J B Use of balance valves in chilled water systemsASHRAE Journal 39(6) 45–51 (1997)

24 Pickering C A C and Jones W P Health and hygienichumidification. BSRIA TN 13/86 (Bracknell: Building ServicesResearch and Information Association) (1998)

25 Air to air energy recovery ASHRAE Handbook: HVAC Systemsand Equipment Chapter 42 (Atlanta, GA: American Society ofHeating, Refrigeration and Air Conditioning Engineers) (1996)

26 Environmental Design CIBSE Guide A (London: CharteredInstitution of Building Services Engineers) (1999)

27 Olesen B W International development of standards forventilation of buildings ASHRAE Journal (4) 31–39 (1997)

28 Liddament M A review of ventilation efficiency Technical Note 39(Coventry: Air Infiltration and Ventilation Centre) (1993)

29 Building Regulations 1991 (1995 ed) Approved Documents F1, F2(London: Department of the Environment and the WelshOffice; Stationery Office) (1994)

30 Energy efficient mechanical ventilation systems. Good PracticeGuide GPG 257 (Watford: Building Research EnergyConservation Support Unit) (1998)

31 Potter I N and Booth W B CO2 controlled mechanical ventilationsystems TN 12/94.1 (Bracknell: Building Services Research andInformation Association) (1994)

32 IEA Demand controlled ventilating systems: a summary of IEAAnnex 18 (Coventry: IEA) (1998)

33 Fletcher J Ventilation control and traffic pollution Technical NoteTN 5/98 (Bracknell: Building Services Research andInformation Association) (1998)

34 Kettler J P Minimum ventilation control for VAV systems: fantracking vs workable solutions ASHRAE Transactions 101(2)625–630 (1995)

35 Kettler J P Controlling minimum ventilation volume in VAVsystems ASHRAE Journal 40(5) 45–50 (1998)

36 Seem J E, House J M and Klaassen C J Leave the outdoor airdamper wide open ASHRAE Journal 40(2) 58–60 (1998)

37 Martin A J and Banyard C P Library of system control strategiesApplications Guide AG 7/98 1st ed (Bracknell: BuildingServices Research and Information Association) (1998)

38 Martin A Condensation control for chilled ceilings BuildingServices and Environmental Engineer 21 (9 May) 9(1998)

39 Natural ventilation in non-domestic buildings CIBSE ApplicationsManual AM10 (London: Chartered Institution of BuildingServices Engineers) (1997)

40 BRECSU Natural ventilation in non-domestic buildings — a guidefor designers, developers and owners Good Practice Guide GPG 237(Watford: Building Research Energy Conservation SupportUnit) (1998)

41 Kolokotroni M Night ventilation for cooling office buildings IP 4/98(Watford: Building Research Establishment) (1998)

42 Limb M J Passive cooling technology for office buildings — anannotated bibliography (Coventry: Air Infiltration and VentilationCentre) (1998)

43 Allard F Natural ventilation in buildings: a design handbook(London: James and James) (1998)

44 Mixed mode ventilation systems CIBSE Applications ManualAM13 (London: Chartered Institution of Building ServicesEngineers) (2000)

45 Martin A J Control of natural ventilation TN11/95 (Bracknell:Building Services Research and Information Association) (1995)

5-62 Building control systems

Page 138: Building control system, aplication guide   cibse guide

46 Fletcher J Night cooling control strategies TA 14/96 (Bracknell:Building Services Research and Information Association) (1996)

47 Bordass W T and Jaunzens J Mixed mode: the ultimate optionBuilding Services Journal 18(11) 27–29 (1996)

48 BRECSU Electric lighting controls — a guide for designers, installersand users Good Practice Guide 160 (Garston: Building ResearchEnergy Conservation Support Unit) (1997)

49 Building Regulations Part L (London: Stationery Office) (1995)

50 HSE Lighting at work (London: HSE) (1998)

51 CIBSE code for interior lighting (London: Chartered Institution ofBuilding Services Engineers) (1994)

52 Lighting requirements of Building Regulations Part L GuidanceNote GN4 (London: Chartered Institution of Building ServicesEngineers) (1996)

53 LIF lamp guide 2nd ed (London: Lighting Industry Federation)(1994)

54 Use of PIR detectors with electronic ballasts and fluorescent lampsLIF Technical Statement No 17 (London: Lighting IndustryFederation) (1995)

55 Slater A I, Bordass W T and Heasman T A People and lightingcontrols BRE Information Paper IP6/96 (Garston: BuildingResearch Establishment) (1996)

Control strategies for subsystems 5-63

Page 139: Building control system, aplication guide   cibse guide

This Page Intentionally Left Blank

Page 140: Building control system, aplication guide   cibse guide

6.0 GeneralA complete HVAC system consists of an assembly of plantmodules, many of which interact with each other. Similarly,the control strategy for a whole building includes thestrategies of individual plant modules and must take intoaccount all the possible interactions between subsystems.Failure to consider these interactions may result in:

— system instabilities

— high energy consumption

— compromise of safe operation.

6.1 Operating modesThe descriptions of subsystem control strategies in theprevious section indicated many of the interactions whichshould be included in control strategies. In the design of theHVAC and control system for a new building, there areinevitably combinations of subsystems that have notpreviously been documented and it is essential that thedesign is theoretically challenged with a range of ‘what if ’scenarios. A variety of possible, likely and unlikely situationsshould be drawn up and predicted responses of the controlsystem followed through, to ensure that there are nounexpected effects. The BSRIA Library of Control Strategies(1)

uses a number of operating modes in which a HVAC plantcould operate at different times. Possible modes are listed inTable 6.1. The number of modes will depend on the nature ofthe HVAC system. A mixed mode system involving heatingand cooling, plus mechanical and natural ventilation mayhave several distinct operating modes during occupancy.The operation of all control strategies in these modes shouldalways be specified unambiguously.

Documentation of a complete control strategy consists ofthe following:

— schematic diagram of plant

— description of plant

— control strategy

— specification clauses

— BMS points list

— summary of plant operation

— control flowchart.

6-1

6 Control strategies for buildings

6.0 General

6.1 Operating modes

6.2 Design techniques

6.3 Whole-building HVAC systems

6.4 Case studies

6.5 Summary

This section deals with control strategies for whole buildings. The strategy for a complete HVAC system must take into accountthe interaction between subsystems. The system may operate in several different modes and the condition of each subsystemin every possible mode must be specified. Practical and theoretical design techniques are described which may be used topredict control performance under a range of conditions. The major HVAC systems are summarised with advice on avoidingconflict between subsystems and the successful incorporation of user control. The section ends with some case studies toillustrate successful applications.

Table 6.1 Operating modes for an HVAC system

Low outside air temperature interlock (for plant protection)

Low return water temperature interlock (for plant protection)

Low zone temperature in the conditioned zone (for building fabric andcontents protection)

Plant shut-down

Fan overrun for air systems, pump overrun for water systems

Optimum start heating (OSH), boost heating

Optimum start cooling (OSC)

Night cooling

Fire

Normal operation during the occupied period, subdivided into:

— heating

— cooling

— natural or mechanical ventilation (mixed mode)

— thermal storage operation

Page 141: Building control system, aplication guide   cibse guide

For reasons of space it is not possible to present a range offull control strategies in this manual. Control strategiesmay be obtained from a number of sources. Largeconsultancies maintain their own libraries of strategieswhich have been found reliable in practice and which maybe modified to meet the needs of new design projects. Someof the major manufacturers publish control strategies,which are often of general application(2,3). The majorpublished source of strategies in the UK is the BSRIALibrary of System Control Strategies(1). This is a compre-hensive document, presenting a large number of controlsolutions with descriptions of plant operation and controlstrategy. A standard specification clause is provided witheach strategy, together with a full points list. Theexpectation is that the Library will provide a set ofstandardised solutions that will enable control systems tobe designed, configured and tested in less time than wouldbe required designing from scratch. This Guide has drawnheavily on the Library for the control strategies summarisedin the previous section and BSRIA references have beengiven where applicable.

It is important to choose an HVAC system and controlsystem that are appropriate for the requirements of thebuilding and the operations it supports. There is noadvantage in having a sophisticated BMS nor inaccumulating information that is not needed and will notbe used. Where simple controls, perhaps packagedcontrollers supplied by plant manufacturers, will performadequately, they should be used unless there is good reasonto install a customised control system. Large modernbuildings benefit from a full BMS; the various options forsystem architecture are dealt with in section 4. The powerand flexibility of a modern BMS allows virtually any controlstrategy to be implemented, and later modified. Changes inuser requirements, developments in HVAC technology andevolving policies on energy conservation ensure thatinnovation and change in building design is a continuingprocess. Few buildings are identical in their needs toothers. This has the consequence that the controls designeris faced with buildings that cannot be satisfied by off-the-shelf solutions. The control strategies for subsystems setout in section 5 have been chosen to be representative ofbest current practice, but must always be evaluated forsuitability for any given building and environmentalcontrol system.

The requirements of energy conservation and the desire toreduce or eliminate the need for air conditioning have ledto building designs which are intended to operate at thelimit of their capabilities during conditions of designweather conditions; it is no longer acceptable to insureagainst problems by oversizing the plant. This has led to awide range of buildings, ranging from fully airconditioned sealed buildings to full natural ventilation. Inmany cases, however, it has been found necessary tointroduce ancillary equipment to deal with particularweather or operational conditions. This gives rise topotential control problems in operating the varioussystems and avoiding conflicts. Practical examples aregiven in the case studies.

6.2 Design techniquesVarious techniques are available which will assist thedesigner in assessing the performance of possible HVAC

plant designs and associated control strategies. The varioustechniques differ in their methods and application and aredescribed below. The information that may be expectedfrom their use includes:

— performance of building under different operatingconditions, especially hot weather

— information on practical problems of installationand operation

— energy consumption

— evaluation of control strategies

— prediction of control performance.

6.2.1 Full scale mock-up

A full scale mock-up of a representative section of thebuilding is constructed. As far as possible it should usethe actual materials and items of plant that will beemployed in the actual building. The mock-up is placedin a large environmental chamber that can simulateexternal conditions, including the effects of solarradiation; several such chambers exist in the UK. Theeffects of indoor activities are reproduced by placingsuitable heat sources in the mock-up room. Suitableinstrumentation has to be provided to monitor theinternal conditions produced. The mock-up is thensubjected to a range of external conditions, representingextreme design conditions and a number of intermediateconditions. The HVAC installation is used to control theindoor conditions, which are recorded and evaluated. Theprocedure allows the designer to:

— show the visual appearance of the finished internalspace

— investigate the performance of the HVAC system

— evaluate the control system and its strategy

— ensure that all components can be installed asplanned and so obviate problems on site.

Where the cost of a mock-up can be justified, it hasproved beneficial to all parties involved in the buildingproject. The use of mock-ups is usually restricted inpractice to room-height sections. Where it is required topredict the performance of tall atrium type structures,recourse must be made to analogue or mathematicalmodelling.

6.2.2 Analogue modelling

Air movement in convective flow may be modelled in awater tank, using salt solutions of varying concentrationto represent air at different temperatures(4,5). The model isoperated upside down; dense salt solution moves downthrough water in a way analogous to the upwardmovement of warm air. A scale model of a section of thebuilding is constructed out of Perspex and mountedupside down in the test tank. Coloured salt solution isinjected to represented heat sources and its movementunder convective flow is recorded. The technique hasbeen used successfully to evaluate the performance of

6-2 Building control systems

Page 142: Building control system, aplication guide   cibse guide

natural ventilation systems and their control by openingand closing vents(6) but has not received widespreadapplication.

6.2.3 Mathematical modelling

Computer-based mathematical modelling may be used tosimulate the performance of a building in considerabledetail. Several software applications are available and maybe purchased or used via a bureau. General advice on theapplication of models is given in CIBSE AM11(7). The firststep is to input a geometrical model of the building. Thisincludes the building dimensions, thermal properties of theconstructional elements, and the orientation and location ofthe building. The HVAC plant is added; separate modulesexist which model the performance of common plant andcontrol systems. Internal heat production and occupancyschedules over the year are set up. The model may then berun to produce predictions of temperatures and energyflows, using detailed weather data for the location andseason of interest. Air movement is modelled using thetechnique of computer fluid dynamics (CFD). This hasfound considerable application in the investigation ofnaturally ventilated buildings. The models usually operatein time steps of 1 h and so cannot be used to investigate thefiner points of control dynamics. The models are mostuseful in predicting building performance in extremeweather conditions and establishing whether internalconditions will be found acceptable in hot weather. Theability of the models to allow for the effects of thermal masson peak temperature is of particular value in this context.

Control strategies may be evaluated using mathematicalmodels. It is sometimes found that control criteria may berelaxed without causing any appreciable discomfort, due tothe stabilising effects of the building thermal mass. Thiscan lead to worthwhile savings in energy consumption.Models have also been found of real value in establishingeffective night cooling strategies and the operation ofmixed mode systems.

6.2.4 Emulation

An emulator for a building energy management systemconsists of a simulation of a building and its HVAC systemwhich may be connected to a real BMS. The real BMS controlsthe simulated building as if it were real, transmitting controlsignals and receiving simulated information back as thesimulated building responds to its actions. Since an actualBMS controller is used, with its own time characteristics, it isnecessary that the simulated building responds at the samerate as the real building. An emulation run thereforeoperates in real time, e.g. it will take a week to emulate aweek’s building operation. An emulator can be used for:

— evaluating the performance of a BMS

— training of BMS operators

— assisting in the development of new controlalgorithms

— fine tuning the control parameters.

An advantage of using an emulator is that a BMS may betested with any type of building and HVAC system for whicha simulation model is available, and tests can be run ondifferent BMS under identical conditions. Since a real BMS is

used, it is not necessary to know the algorithms employed,so that products from different manufacturers may becompared without compromising any proprietaryinformation about the control strategies. The buildingsimulation model is of fundamental importance for theemulation technique. As well as modelling the thermalresponse of the building, the dynamic behaviour of thecontrols and actuators must be modelled realistically; thisis a more stringent requirement than is found with themathematical models described in 6.2.3 above. Operation ofplant is described in great detail and the emulation exercisemay be used to predict reversals and travel of actuators as anindicator of potential maintenance costs. Six emulatorswere developed for an IEA exercise and are described byLebrun and Wang(8). They worked well but have not yetfound widespread application.

6.3 Whole-building HVACsystems

Table 6.2 lists some major types of HVAC system used inmodern buildings with some of their characteristics. Manyvariations on the basic systems are possible. Controlstrategies for the subsystems involved have been dealt within section 5. The designer must consider how the differentcomponents of the HVAC system may interact underdifferent operating conditions and ensure that the controlsystem will maintain economic and effective operationunder all conditions.

6.3.1 VAV and perimeter heating

This is a widely used combination. Conditioned air issupplied to all parts of the space via the VAV boxes. Theproportion of recirculated to outdoor air in the air supply iscontrolled to ensure that the correct amount of ventilationair is maintained against variations in supply air volume.Temperature control in the zone supplied by a group ofterminal units is provided by varying the air flow thougheach box. Heating may be provided via the terminal unit byfitting the box with a reheat coil, which is supplied withLTHW. The relevant control strategies are set out in Section5. It is common to provide heating by conventional LTHWradiators or other room heat emitters. This has advantages:

— There is no water supply in the ceiling.

— The heat is supplied where required to counteractperimeter heat loss, especially under windows.

— There is better heat distribution from radiatorsthan from the ceiling, especially at low air flowrates.

The control strategies for the combined system present nogreat problems. The perimeter heating LTHW flow shouldbe weather compensated. It may be necessary to fit separatecontrols on different facades where there are largedifferences in heat loss or insolation. Thermostatic radiatorvalves will give extra control if required; they may be fittedin addition to, but not instead of, compensated flowtemperature. Given effective control of the perimeterheating, it is not necessary to interlock the VAV cooling andthe heating to prevent simultaneous operation. With a deepbuilding, perimeter heating may be necessary to maintaincomfort in the perimeter zone while the central zones

Control strategies for buildings 6-3

Page 143: Building control system, aplication guide   cibse guide

require cooling. Boost heating during optimum start isprovided by setting the perimeter heating flow temperatureto maximum, with the VAV system off or on fullrecirculation.

6.3.2 Fan coil units

Fan coil units are available in a wide range ofconfigurations, including underfloor units, console unitsdesigned to go on the wall or under windows, to thecommon type installed in a ceiling void. Units areconnected to a supply of hot and chilled water. Thedistribution of water round a building is simpler and takesless space than the distribution of conditioned air. Thismakes the installation of fan coil units more flexible thanthat of a VAV system. FCUs are to be found in all types ofbuilding and control systems range from a local thermostatcontrolling fan operation to a fully integrated whole-building system. Control of individual FCUs was dealt within 5.10; here, we consider the implications of integration.

The FCUs themselves recirculate room air, heating orcooling as required to maintain the room air set point.Ventilation air is provided by a central air handling unitwhich supplies 100% outdoor air at controlled temperatureand usually controlled humidity. Incorporating thetemperature of the primary supply air in the controlstrategy allows energy savings to be made by controlling theoperation of the heat exchanger to exploit free cooling. Fancoil units have no provision for dehumidification otherthan moisture condensing on the cooling coil. Fan coilunits must therefore always be provided with a condensatetray and a means to remove any condensate. In general, it isbest to avoid running an FCU with a wet coil, especiallywhen the unit is mounted above a false ceiling where theresults of any failure of the condensate removal will be aproblem. The preferred method is to deal with the latentload by dehumidifying the primary outdoor air to controlroom humidity at the desired level; this will normally besufficient to prevent condensation on the FCU cooling coil.The usual practice is to duct the primary supply air to eachFCU, where it is mixed with the recirculated room air by the

unit fan. It is also possible to distribute ventilation airthrough independent terminals. This may have advantageswhere it is required to maintain maximum flexibility forpossible repositioning of the FCUs at a later date, or wherethe FCUs are only used during the cooling season.

In an integrated system, each intelligent fan coil unitincorporates its own controller which communicates withthe BMS. Room temperature set points and time schedulesmay be set remotely for each unit or group of units actingtogether. Once of the disadvantages of fan coil units is thepotential degree of maintenance required and thedisruption involved in identifying and servicing faultyunits which are distributed throughout the occupied space.The BMS is used to give warning of any failures or routinemaintenance needed, such as the need for a filter change. Afan coil system incorporates many small water controlvalves, which are susceptible to sticking or blockage. It ispossible to incorporate checking routines in the BMS. Eachvalve is driven fully open and closed in turn, and theappropriate response of the discharge air temperature ischecked.

Figure 6.1 shows an air handling unit for a fan coil system,which supplies 100% outdoor air to all room units. A heatexchanger is incorporated to transfer heat between exhaustand outdoor intake air. The air is supplied at constant flowrate during the occupancy period; the extract fan isinterlocked to operate at the same time. The supply airhumidity is controlled to maintain the zone humidity at alevel which will provide comfort and prevent, or at leastminimise, condensation on the fan coils. This is typicallycontrolled using an RH sensor in the extract. Supply airtemperature may be controlled to be near the desired zonetemperature, or scheduled to the outside air temperature;this will allow full advantage to be taken of any free cooling.A suitable schedule is that the supply air temperatureshould have a maximum temperature of 22ºC when theoutside air is at 12ºC or below, and a minimum temperatureof 14ºC when the outside air is above 21ºC, with a linearrelation in between these values. The heat recovery isoperated according to the strategy in Table 5.5 formaximum efficiency.

6-4 Building control systems

Table 6.2 Major HVAC systems

Feature VAV and Fan coil units, Chilled ceiling Natural VRF

perimeter heating four-pipe displacement vent ventilation

ComponentHeating LTHW radiators FCU Perimeter radiators Radiators Indoor unitCooling VAV box FCU Ceiling or beam None Indoor unitVentilation Central AHU, Central AHU, Central AHU, full Natural Mechanical

mixed air full fresh air fresh air ventilationSpatial impact

Plant space High Average Average High GoodRiser shafts High Average Average High GoodFloor space High Average Low High HighCeiling depth High Average High High Average

PerformanceTemperature Good Good Satisfactory Poor SatisfactoryAir distribution Adequate Adequate Good Adequate PoorNoise Good Adequate Excellent Good Adequate

CostCapital High Average High Average LowOperating Low Average Average Low AverageMaintenance Average High Average Low High

FlexibilityRearrangement of partitions Good Good Good Poor Poor

Page 144: Building control system, aplication guide   cibse guide

Further economies may be made by resetting the flowtemperatures of the LTHW and CW to the coils. This strategyrequires information to be made available to the BMS on theposition of the heating and cooling valves on each FCU. Thetemperature of the LTHW is reset so that at least one heatingvalve is fully open while maintaining the required roomtemperature in all zones. Similarly, the chilled water flowtemperature is reset so that at least one cooling valve is fullyopen. This strategy ensures that the water being circulatedto the coils is neither hotter nor cooler than required tomaintain the desired conditions. Some care must beexercised when employing this type of strategy, whichdepends on a large number of logical criteria all beingsatisfied. A single sensor failure or incorrectly adjusted setpoint will prevent satisfactory operation. A full controlstrategy for a fan coil unit system is given in BSRIA Libraryof System Control Strategies, 3.16.3(1).

6.3.3 VRF systems

Variable refrigerant flow systems provide zone heating andcooling by means of indoor units which are connected viarefrigerant lines to the group outdoor unit. Controlstrategies for VRF systems were set out in 5.13.1. The VRFindoor units do not provide ventilation air and this has tobe provided separately. For some applications, such as hotelrooms, it may be adequate to use simple extract ventilation.In general it is better to provide full mechanical ventilationwith controlled supply and extract. Manufacturers of VRFsystems provide mechanical ventilation with heat recovery(MVHR) systems which may be used in conjunction with theindoor units to provide both temperature control andventilation. The MVHR unit contains supply and exhaustfans, a cross-flow heat exchanger, filter and a bypass damperwhich can allow the air to flow straight through and bypassthe heat exchanger. The unit is fully ducted and the supplyair may be led to conventional diffusers or connected to theindoor units, where it mixes with the recirculated room airbeing heated or cooled. Each MVHR unit provides sufficientair for several indoor units.

When operating as an independent ventilation system, theunit has its own controller, offering a selection of fan speedsand heat exchange or bypass operating modes. The modemay be selected manually or automatically, based on theoutdoor air and extract temperatures. Where the unit isconnected to the indoor VRF units, the control may beintegrated with the VRF control system, using themanufacturer’s proprietary network. The modular natureof VRF systems means that the system may be extended toprovide temperature control and ventilation for a largebuilding. Humidity control is not provided in theventilation units; some dehumidification is provided by theroom units when cooling in conditions of high humidity.

6.3.4 Chilled ceiling and displacementventilation

The range of systems coming under the general descriptionof chilled ceilings can be divided into three groups, withdifferent operating characteristics:

— Chilled panels. A chilled ceiling panel presents a flatsurface to the room below. The rear surface of thepanel is insulated and there is no requirement forair circulation behind the panel. Cooling is over50% by radiation.

— Passive chilled beam. The chilled beam contains acooling coil designed to cool air flowing downthrough it. Room air circulates up behind the beamand down through it by natural convection. Highercooling loads are possible than with chilled panelsand cooling is about 80% convection. Some beamsare designed to present a cool surface to the room,enhancing the radiant proportion.

— Ventilated chilled beam. The beam contains an airduct which supplies the room ventilation air. Thesupply is 100% outdoor air and is cooled andpossibly dehumidified. High velocity nozzles injectair into the beam, which induces additional room

Control strategies for buildings 6-5

Figure 6.1 Integrated fan coil unit system. The supply air temperature is scheduled to outside temperature. Control connections not shown

Page 145: Building control system, aplication guide   cibse guide

air flow thorough the cooling coil. This increasesthe cooling capacity of the beam over that of apassive beam.

Chilled ceilings and beams provide an effective way ofproducing comfort cooling in buildings with modest heatloads. Ventilation air is provided independently and thisgives the opportunity of introducing mixed modeventilation, where natural ventilation can be used atappropriate times. Mechanical ventilation withconditioned outdoor air is provided in the heating andcooling seasons; natural ventilation may be used if desiredwhen the outside conditions are suitable. The usual form ofmechanical ventilation is a form of displacementventilation, where the air is introduced at floor level; theuse of swirl diffusers ensures that air velocities fall rapidlyaway from the diffusers and do not cause draughts. In anideal displacement ventilation system, the air movessteadily up through the occupied zone, taking heat andpollutants with it, to be extracted at high level. By thismeans, a high ventilation efficiency, potentially greaterthan one, can be achieved. An air temperature and airquality gradient can be achieved, whereby the occupants arein the clean cool part of the gradient, with air qualityworsening at high level. This is in contrast to mixing airdistribution, which gives average conditions over the wholespace.

In practice, true displacement ventilation is difficult toachieve with a radiant ceiling and impossible with a chilledbeam. The chilled beam provides convective cooling, withcooled air falling back into the occupied zone and mixingwith the incoming ventilation air. The effect is less markedwith a radiant ceiling, which cools largely by radiantexchange with the warmer surfaces in the room(9,10). Sometypical chilled ceiling combinations are shown in Table 6.3,with relevant outline strategies.

Chilled ceilings are normally arranged with a separatelycontrolled perimeter zone. Perimeter heating usingconventional LTHW radiators is used to counteractperimeter heat loss and any downdraught from windowsand is controlled using weather-compensated flowtemperature as described in 6.3.1 for VAV systems. A largespace will require perimeter heating at the same time ascentral zone cooling to maintain comfort near windows.

Where the radiators are compensated, it will not always benecessary to interlock the perimeter ceiling and radiator toprevent simultaneous heating and cooling. Where aventilated beam is used incorporating heating coils, aninterlock must be present.

6.3.5 Natural and mixed modesystems

The design of mixed mode and naturally ventilatedbuildings is closely integrated with that of the buildingitself. Provision of air flow paths, control of solar gain andthe need to provide adequate thermal mass, all influence thebuilding shape and layout. Mixed mode and naturallyventilated buildings tend to be one-off designs, with uniquecontrol solutions. Such buildings are likely to include anumber of controlled devices, relating to solar control,lighting, heating and mechanical ventilation and perhapscooling. These controlled devices are operated by acombination of automatic and occupant control. There is adanger, borne out by experience, that subsystems mayinteract in such a way to give unsatisfactory control andexcessive energy consumption. Every attempt must bemade to anticipate and design out potential problems.

Full occupant control is only feasible in small cellularoffices, where the control choices have limited effect on therest of the building. The use of a weather-compensatedheating circuit will avoid the worst excesses of the window-open/heating-on problem, and simple timeswitches andpresence detection will limit excessive use of lighting. Mostnaturally ventilated buildings incorporate openablewindows and other forms of occupant control. Directcontrol is appreciated by occupants and should lead togreater satisfaction. However, not too much should beexpected of occupant control as regards optimum operationof a large building. Operation of a controlled device mayhave an effect remote from the occupant who, by reasons ofproximity, has ‘ownership’ of the controlled device. Forinstance, the opening of leeward windows is necessary forcross-ventilation in a large building, but will have littleeffect on comfort nearby. There is therefore little incentivefor anyone near the window to open it. While it is desirableto delegate as much control as is practical to occupants, it is

6-6 Building control systems

Table 6.3 Chilled ceiling systems

Chilled panel Passive beam Ventilated beam

Cooling System Chilled panel Coil in beam Coil in beam

Chilled water 14°C 14°C 14°C

Control Water flow on/off Water flow on/off Modulate water flow

Heating System Radiators Radiators Coil in beam

Control Compensated flow Compensated flow Modulated flow

Ventilation System Floor diffusers Floor diffusers Duct in beam

Air supply 18–22°C 18–22°C 14–18°C

Control Constant volume Constant volume Constant volume

Interlocks Heat/cool No No Yes

Windows or presence If desired If desired If desired

Condensation All systems Raise chilled water temperature above dewpoint orprevention dehumidify ventilation air. Plus condensation detection

Page 146: Building control system, aplication guide   cibse guide

not reasonable to expect them to take responsibility for theefficient operation of the whole building. The ability to takean action in response to discomfort, perhaps by opening awindow, is valued. The requirement to operate windows forthe benefit of staff in a remote part of the zone is unlikely tobe carried out efficiently.

Most mixed mode buildings are of complementary designand are designed to operate under a concurrent orchangeover strategy(11). A concurrent system usespermanent mechanical ventilation which runs con-tinuously to provide sufficient outdoor air for ventilationpurposes. Occupants are free to open windows to provideadditional cooling when needed. The natural andmechanical systems complement each other and simul-taneous use is possible without conflict. A changeovermixed mode strategy aims to operate the building using themost efficient combination of available systems. The BMSselects the appropriate operating mode and enables orinhibits the relevant systems. There may be several modes,depending on season, use of building or time of day. TheBMS must change from one operating mode to another insuch a way that continuous control is provided and withoutbeing obvious to the occupant. Control of particular devicesmay be passed from manual occupant control to automaticcontrol and this must be done without antagonising thebuilding users. Control decisions made by the BMS must beacceptable to the occupants and appear sensible; if not, thebuilding users may expend considerable ingenuity inoutwitting the BMS. Locking windows which shut whenexternal air temperature exceeds internal temperature maynot be acceptable to the occupants in the building.Situations where the BMS promptly overrides an actiontaken by an occupant will be disliked and lead either to theabandonment of any involvement in environmental controlor an antagonism to the building and the organisationwhich it represents(12).

6.4 Case studiesThe control solution adopted for any individual building islikely to have its own particular characteristics. Choices aremade by the designer to resolve problems or take advantageof opportunities presented by the project. It is thereforeimpossible for this Guide to list a comprehensive selectionof whole-building control strategies that would cover all, oreven most, BMSs. The remainder of the chapter presentssome case studies of building management systems thathave been successfully applied to actual buildings. Thestudies cover a range of building types and HVAC systems.The description of the control systems, while brief, serve todemonstrate the wide range of BMS applied in practice andserve to bring out some useful lessons.

6.4.1 Retrofit using a modular controlsystem

Building Greenway School, HorshamType Junior School

Greenway School in Horsham teaches 400 7–11-year-oldchildren in a group of buildings, comprising a mainbuilding and six classroom huts. Heating and hot water to

the main building are provided by three gas-fired boilersand independent gas-fired convectors are used to heat theclassroom huts. It was decided to keep the existing heatingsystem and upgrade the controls to provide overall controlfrom a single position, but allow individual teachers someflexibility in setting temperatures.

A modular control system was installed, consisting of onemaster and eight-slave zone controllers, plus a boilersequence controller and the necessary sensors andactuators. All components are interconnected via a simpletwo-wire bus, employing the LonWorks protocol. Themaster zone controller is located in the school secretary’soffice and is used to set the time schedule and temperaturesfor all zones. In addition, the controller provides optimumstart and weather compensation. The individual zonecontrollers in each classroom give a temperature displayand allow limited alteration of set point.

The control system provides central control of timescheduling, bringing the entire system under central controland preventing any individual heaters being left on bymistake. No specialist knowledge is required for operation.

The modular controls chosen proved easy to install usingthe bus system. The straightforward interface allowedoperation by non-technical staff.

6.4.2 Remote control of a group ofhomes for the elderly

Building 10 elderly people’s homes, ClwydType Residential homes

Clwyd Council operates a centralised BMS bureau andenergy monitoring and targeting service, which has beensuccessful in producing an overall reduction of 25% inenergy consumption in buildings serviced. It was decidedthat a group of elderly people’s homes operated by the socialservices department offered scope for improved control andmonitoring. The ten homes are of modern construction andheated by a conventional boiler serving radiators and hotwater services.

The energy conservation unit applies a three-year paybackcriterion for improvement schemes, which required a lowcost solution. Each home was retrofitted with a stand-aloneenergy management system. This provided time andtemperature scheduling, optimum start and weathercompensation, including room reset control. Boileroperation includes sequencing control and improvement ofefficiency by variable minimum off-time control, whichincreases the off-time during cycling as the flow and returntemperatures get closer together, i.e. at light loads. Controlof hot water services is also provided. Water heating periodsare matched to kitchen operating times and the boiler flowtemperature is adjusted as the duty moves between spaceand water heating. The controllers contain their own data-logging features and a modem, which allows com-munication between the controller and the BMS bureau overthe public service telephone network. The controller cansend routine data files automatically to the central PC andinitiate alarms messages if required. If desired, alarms canbe sent automatically to a fax machine. Staff at the centralbureau may remotely view plant status or take directcontrol of operation.

Control strategies for buildings 6-7

Page 147: Building control system, aplication guide   cibse guide

The previous heating systems were poorly controlled andinstallation of the improved controllers producedreductions in gas consumption of between 20 and 30%. Inaddition to the savings produced by improved controllerperformance, the information provided by the monitoringand targeting service allowed other energy savings to beidentified.

Lesson. The use of stand-alone controllers with built-incommunication facilities allowed professional energymanagement of a number of dispersed buildings to beinstalled at low cost.

6.4.3 Low energy university buildingwith fabric storage

Building Elizabeth Fry Building, University of EastAnglia

Type Two floors of cellular offices and two floorsof lecture and seminar rooms, plus kitchenand dining room

The building is highly insulated and well sealed. Nomechanical cooling is provided. Supply ventilation air istempered by passing though hollow core floor and ceilingslabs. A highly simplified diagram of the system as appliedto the office area is shown in Figure 6.2. Gas-fired boilersprovide heat to the AHU when required and a high efficiencyregenerative heat exchanger is employed for heat recovery.Full fresh air ventilation is used during occupied hours. Allwindows are openable without restriction on their use.Ventilation to the lecture theatres is by variable speed fancontrolled by the CO2 concentration of the extract air. Thiscompensates for the variable occupancy and givessubstantial savings in fan running costs.

The building is thermally very stable and control of zonetemperature is achieved by controlling the core tem-perature (Table 6.4), measured near the air outlets.

The Elizabeth Fry Building has successfully achieved acombination of very low energy consumption and highoccupant satisfaction. The hollow core slab system achieves

very steady temperatures and comfortable summerconditions without the use of air conditioning.

There were initial teething problems caused by inadequatecontrols and the lack of a proper BMS, which did not allowthe maintenance staff to understand the operation of thevarious systems. Subsequently, new controls were fitted andintegrated into the campus-wide BMS system. Theavailability of performance data was vital in allowing thecontrol strategy and settings to be fine tuned andsimplified. The commissioning and handover periodextended over the first two years of occupancy. Cooperationbetween the building manager, controls specialist and thedesign team resulted in a well-configured system with asimple control strategy(10,13).

6.4.4 Mixed mode R&D facility usingchilled beams

Building Hewlett Packard, Building 3, BristolType Three-storey open plan building housing

offices and computing laboratories

This building provides a research and development facilityfor up to 450 staff and was completed during 1998(14). Thethree storeys provide two floors of open plan flexible spacefor offices and laboratories (Figure 6.3). The ground floorcontains a presentation area, meeting rooms and a largecoffee shop, which provides a centre of social interaction. Acentral atrium forms a central street; on the upper floors,glazed balustrades surround the central space, giving afeeling of light and openness.

The nature of the business activity produces a relativelyhigh small power load of about 40 W/m2. This demandsmechanical cooling, which is provided by chilled beams.There is no natural ventilation. The building is well sealed,achieving a low leakage value with the assistance of concretefloor and ceiling slabs, which also provide thermal mass.Supply air is provided as 100% outside air through floordiffusers; extract is via air handling luminaires. The supplyair is conditioned in the central AHU and delivered to thezones at a constant temperature of 19ºC, though this may be

6-8 Building control systems

Figure 6.2 Hollow core slab system used in Elizabeth Fry Building. Full fresh air ventilation is used at all times during occupancy. Heat recovery may bedeactivated

Page 148: Building control system, aplication guide   cibse guide

reset over the range 19–21ºC if required in hot or coldweather. Full recirculation is used during warm-up. Supplyair can be dehumidified to maintain the dewpoint below12ºC, to avoid condensation forming on the chilled beams;in this building no facility for humidification is provided.Perimeter heating to offset losses at the windows is providedby LTHW radiators. Additional radiators are fitted at highlevel in the atrium to prevent cold downdraughts in winterfrom the atrium roof. There is no external solar shading.Internal venetian blinds are fitted and a central blindcontroller sets the position and angle of the blinds. In strongsunshine, the blinds heat up and produce a convectiveupdraught of warm air. To prevent this causing problems forthe chilled beams, the perimeter is decoupled from theinternal zone by drawing the air through a grille circling theperimeter. The air passes over a large cooling coil andreturns to the occupied space. In hot weather, it is possiblefor hot air to accumulate under the atrium roof and work itsway down into the second-floor offices. To prevent this,chilled water can be passed through the high level radiators.

The building has an advanced IT network. This is designedto be innovative and is subject to change. It was thereforedecided to maintain the control network entirelyindependent of the IT system. The innovative nature of thesystem decided the consultants to construct a full scalemock-up of the perimeter zone to evaluate the controlsystem under a range of operating conditions. These testsdemonstrated a potential instability, where the perimeterradiators and chilled beams oscillated between heating and

cooling. This was resolved by altering the control setpoints. Air movement in the atrium was investigated usingCFD modelling, which demonstrated the need to use highlevel radiators, both to prevent downdraughts in winter andto limit overheating in summer. The thoroughinvestigation of control behaviour at the design stageproved invaluable in resolving potential problems.

6.4.5 Terminal 2, Manchester Airport

Building Terminal 2, Manchester AirportType Large airport terminal

Manchester Airport’s second terminal was completed in1994. It was decided to use an integrated BMS which wouldprovide a facilities management system which, in additionto controlling the extensive HVAC system, would interfacewith many other systems and provide the following controland monitoring:

— Control— HVAC: VAV systems in terminal, shops and

offices— lighting— airport services: telephone system, baggage

handling, escalators— runway drainage— access control: to plant rooms.

Control strategies for buildings 6-9

Table 6.4

Mode Core Outside Heat recovery Heating coil Recirculationtemperature temperature

Stage 2 heating Tc < 21.5 for 15 min Yes Yes No

Stage 1 heating Tc < 21.5 Yes No No

Ventilation only 21.5 < Tc < 22.5 No No No

Stage 1 cooling Tc > 22.5 To < Tz No No No

Stage 2 cooling Tc > 22.5 To > Tz Yes No No

Night cooling Tc < 23 To < (Tc – 2) No No No

Night heating N/A Yes Yes

Tc = Core temperature; To = Outside temperature; T2 = Zone temperature.

Figure 6.3 Cross-section of HewlettPackard Building 3, showing chilledceiling and displacementventilation(14)

Page 149: Building control system, aplication guide   cibse guide

— Monitor— energy: electricity, water, gas and provide

billing— life safety: fire fighting, smoke detection— apron services: ground power, battery

charging.

The system is designed to provide full multi-userfunctionality and operate using the airport’s existing fibreoptic structured wiring system. It utilises a two-tiernetwork topology. The top tier sits on the ManchesterAirport fibre optic network; master controllers are locatedin plant rooms and workstations in various control roomsare connected directly to the network. The lower tier is thenrun locally to pick up controllers located in motor controlcentres, substations or VAV boxes, using coaxial cable or UTPas appropriate.

As far as possible, control systems were designed as genericcopies of existing systems, allowing the use of existingreliable software. Commissioning was facilitated bypositioning the site team’s temporary buildings so thatconnections could be made to the structured wiring systemat an early stage. This provision of a temporary location forthe supervisor allowed programs to be downloaded into thecontrollers as soon as the network was complete. Thesystem has proved capable of expansion. It now comprisesover 8000 points and 1000 graphics panels. It can cope withmulti-users. Touchscreen display panels are installed inshop and office areas, allowing adjustment of a restrictedrange of set points and variables.

6.5 SummaryEfficient operation of a building requires that thesubsystems do not interact wastefully. All possibleoperating modes of the building should be listedsystematically together with the operating states of thecomponent subsystems. This will assist in identifyingunsatisfactory situations, e.g. where heating and coolingmay be operating simultaneously. The involvement of thebuilding occupant in the operation of control devices canbring benefits in increased comfort and satisfaction withthe environment. However, concurrent operation ofautomatic control systems and occupant action mayproduce dissatisfaction if the user is overridden by theautomatic system. Careful attention is required to produce acombination of user and automatic control that is neitherwasteful nor over-complex and self-defeating.

Several techniques are available to predict buildingperformance, either analogue modelling, full scale mock-

up, or various mathematical modelling techniques.Modelling can anticipate potential control problems andallow them to be corrected at the design stage. The sectionsummarises the more common combinations of heating,cooling and ventilation and discusses the requirements forthem to work together satisfactorily.

Design lessons are illustrated by a range of case studies,which range from simple heating-only classrooms to largecomplex integrated buildings. The choice of theappropriate system and strategy for the task in hand isemphasised.

References1 Martin A J and Banyard C P Library of system control strategies

Applications Guide AG 7/98 1st ed (Bracknell: BuildingServices Research and Information Association) (1998)

2 Honeywell Engineering manual of automatic control SI ed(Minneapolis: Honeywell Inc.) (1995)

3 Siemens MSR Planungshandbuch (CD-ROM) (Karlsruhe:Siemens AG) (1997)

4 Lane-Serff G F, Linden P F et al. Laboratory and mathematicalmodels of natural ventilation Roomvent’90 Proc. 2nd InternationalConf. Paper A2-7 (Oslo, Norway: Norsk VVS) (1990)

5 Etheridge D and Sandberg M Building ventilation theory andmeasurement (Chichester: Wiley) (1998)

6 Brister A Cable Talk Building Services. CIBSE Journal 15(11)22–26 (1993)

7 Building energy and environmental modelling CIBSE ApplicationsManual AM11 (London: Chartered Institution of BuildingServices Engineers) (1998)

8 Lebrun J and Wang S Evaluation and emulation of building energymanagement systems Synthesis report AN17-SR1 (Liege,Belgium: University of Liege) (1993)

9 Alamdari F and Eagles N Displacement ventilation and chilledceilings TN 2/96 (Bracknell UK: Building Services Research andInformation Association) (1996)

10 Bunn R Chilling lessons Journal of the Chartered Institute ofBuilding Services 17(5) 37–38 (1995)

11 Mixed mode ventilation systems: CIBSE Applications Manual(London: CIBSE) (1999)

12 Probe 18: Portland Building Building Services Journal 21(1)35–40 (1999)

13 Probe 14: Elizabeth Fry Building Building Services Journal 20(4)37–43 (1998)

14 Pearson A HP sourced Building Services Journal 19(12) 12–16(1997)

6-10 Building control systems

Page 150: Building control system, aplication guide   cibse guide

7.1 Energy monitoringA major justification for the installation of a BMS is theprevention of energy waste. Correct and efficient control ofHVAC plant will itself contribute to efficient use of energybut in addition it is necessary that the energy managerreceive accurate and up-to-date information on energy usein the buildings for which he is responsible. The approachgenerally adopted in the UK is termed energy monitoringand targeting (M&T), which is vigorously promoted by theDETR. The term monitoring and targeting does not in itselfimply the use of a BMS or indeed any hardware for datacollection and analysis. M&T requires that data on energyconsumption be regularly collected, summarised andcompared with target consumption figures. Computerisedcollection and analysis of data makes M&T a powerful toolfor the control and reduction of energy consumption(1).

7.1.1 Monitoring and targeting

M&T has two major functions:

— the control of current energy use, by monitoringconsumption and comparing it against historicaldata and benchmarks for similar buildings

— improvements in the efficiency of energy use by thesetting of future targets.

In large buildings or complexes, effective energymanagement requires that areas of accountability beestablished, termed energy account centres (EAC).Accountability implies both responsibility for the energyconsumed and the authority to control the consumption.The energy consumption of an EAC should be

— measurable

— manageable

— reconcilable against a measured activity.

An EAC could be a department, an energy intensiveproduction process, a sublet part of a building or anindividual building on a site. A standard energyperformance is initially established for each EAC, whichrelates energy consumption to appropriate variables, suchas degree-days or production output. The standardperformance provides a benchmark against which energyconsumption may be compared, prior to the setting oftargets for future improvements. The targets must berealistic and achievable and agreed with the managersresponsible for each EAC. BRECSU have published anumber of Energy Consumption Guides, e.g. Guide 19(2),and consumption data for a wide range of non-domesticbuildings is summarised by Jones and Cheshire(3).Additional information is to be found in CIBSEApplications Manual AM5(4).

The monitoring part of the M&T process involves four stages:

(1) Data collection. Energy consumption data iscollected. A comprehensive system will includeelectricity, gas and water meters located in eachEAC, capable of sending data to a central collectionpoint. The availability of other relevant data mustbe taken into account, e.g. degree-day data orproduction figures.

(2) Data analysis. The data received by the computer ischecked for errors and then stored in a formsuitable for further analysis. Data analysis is carriedout according to the needs of the system; this islikely to include weekly and monthly totals. Anyresults which indicate a problem or malfunctionshould generate an immediate warning.

(3) Reporting. Management reports produced by thesystem which show the energy consumption of eachEAC compared with targets.

7-1

7 Information technology

7.1 Energy monitoring

7.2 Fault reports and maintenance scheduling

7.3 Summary

The building management system provides an important source of information, which may be exported to other applications.Building performance and energy consumption are analysed by energy monitoring and targeting software, to assist ineffective energy management. Information from the BMS is employed as part of facilities management, including theadministration of planned maintenance.

Page 151: Building control system, aplication guide   cibse guide

(4) Action. It is essential that a management structureexists to make effective use of the reports generatedby the M&T system.

For an M&T system to be effective, all four stages must beimplemented. The collection of data, however accurate,which is not looked at and which prompts no action servesno purpose. Effective M&T requires full managementsupport. As a rule-of-thumb, M&T may be expected toreduce energy bill by about 5%; larger savings are possiblewhere equipment malfunction or gross control failures areidentified as the result of metering information. This figureallows an appropriate level of M&T to be chosen in relationto the total energy bill. Energy management systems sharemany of the characteristics of a BMS. In a building thesystem installed for energy monitoring and targeting mayshare hardware with the BMS and may be operated from thesame terminal by the same staff. However, the they are notthe same. The BMS provides real-time control of thebuilding services, while the M&T system is concerned withdata collection and historical analysis.

7.1.2 Planning an M&T system

Energy M&T may be instituted at a simple level, usinginvoices or manual meter readings and simple manual orspreadsheet analysis. The major factors to be taken intoaccount at an early stage are summarised below. The mostimportant is the total energy bill to be monitored, since it isthe potential savings on this bill that fund the M&T system.M&T systems may be classified according to their level ofcoverage and sophistication.

7.1.2.1 Level of coverage

— Single site, utility based. The site is treated as a singleEAC and monitored using only utility meters andinvoices. Here, a site implies a building or group ofbuildings served by a single utility meter. It may bepossible to aggregate physically separate buildingsinto a single site for supply and metering purposes.

— Single site with submeters. Energy is monitored foreach of the EACs within a single site by means ofsubmetering.

— Multi-site, utility based. A number of sites aremonitored using the main utility meters. Each siteis treated as a single EAC.

— Multi-site with submeters. Several sites, each of whichis subdivided into EACs and submetered.

7.1.2.2 Level of sophistication

— Manual system. Meters are read manually andtabulated on paper.

— Keyboard input system. Meters are read individually,and readings recorded by hand or by a data captureunit. Readings are then entered into a computer foranalysis.

— Automatic input system. The meters are connected viadata loggers or other system to the computer andenergy consumption is collected and monitoredautomatically.

— Advanced system. Implies more sophisticated datahandling, combining energy data with data from

other systems or sites. May include automaticcontrol or provide warning messages. Sophisticatedbureau services are available using neural networkanalysis of consumption data to detect energywaste, coupled with an expert system to identifycauses.

7.1.2.3 Choice of system

It is important not to choose an oversophisticated system.Not only will such a system cost more to install, but it willdemand staff time to maintain it in an operational state andto take action on the results. If the requisite support is notavailable the system will not fulfil any purpose. Thefollowing points should be considered at an early stage inthe planning:

— Cost effectiveness. Any proposed system will berequired to meet the organisation’s criteria forreturn on investment. The cost of a system issensitive to the number of meters installed. Notonly does this affect the installed cost, but theanalysis, reporting and storage of the increasedamount of data will add to the running costs. Therule-of-thumb that M&T should save 5% of energycosts may be used to provide indication of a viablelevel of investment.

— Number of meters. Each EAC requires its own meters.Electricity meters will always be required, togetherwith gas meters where appropriate. Water metersare recommended, particularly if there are anywater intensive processes. Further submeteringmay be desirable for particular processes orequipment. The consumption of some areas may becalculated using the concept of a virtual meter, i.e.the difference between a main and submeter.

— Monitoring period. This is the period between meterreadings. For a fully automated system this shouldbe half-hourly. The use of time-of-day electricitypricing is spreading from large customers tosmaller or even domestic customers and half-hourly information will be necessary whenconsidering the optimum policy for electricitytariffs. The additional information given by half-hourly metering is useful for diagnostic purposes,helping to identify reasons for anomalousconsumption.

— Reporting. The M&T system should produce regularstandardised reports, showing performance againsttarget. Weekly and monthly periods arecommonplace. There is no point in producingreports more frequently than they will be read. It isimportant that the information is usable by theintended audience of the report. Ideallymanagement reports should highlight anyavoidable waste and define responsibility forimprovement.

— Management organisation. Figure 7.1(5) shows howM&T operates within the management structure.Each EAC requires a manager responsible for energyperformance within the centre, and who willreceive routine reports. It is essential that sufficientstaff are trained in the operation of the system and aminimum of two staff should be able to operate it. Ifthis is not practicable, the use of a bureau serviceshould be considered. Metered data is read

7-2 Building control systems

Page 152: Building control system, aplication guide   cibse guide

remotely via modem or the Internet and the bureauproduces the required analysis, reporting andbilling as required.

7.1.2.4 Electricity Tariff

The choice of electricity tariff has its own relevance to thedesign of a M&T system. Since 1994, customers with a totaldemand of over 100 kW have been able to negotiate a supplyfrom any electricity supplier; the freedom has since beenextended to all customers. The type of tariff negotiated willhave a bearing on the design of submetering and the energymanagement system. The major factors to be consideredare:

— aggregation of sites

— choice of tariff.

It may be advantageous to group separate buildings orsites together so that they are supplied as a single unitthrough one main meter. The Office of Gas andElectricity Markets (OFGEM) has set out requirementsfor the main meter. It must comply with the PoolingSettlement Agreement document known as Code ofPractice 5 and it must be maintained by an approvedmeter operator. The meter must record all units used eachhalf hour and transmit the stored readings once per day tothe UK Data Collection Service, which then passes theinformation on to the interested parties. The readings willnormally be made available to the building operator.Users with a demand of less than 100 kW may continue touse a conventional meter.

The customer may install further meters downstream of themain meter; this is known as secondary metering orsubmetering. Secondary metering is installed for:

— tenant billing

— cost centre accounting

— energy management.

Secondary metering is not constrained by the same level ofregulation as primary metering, though any meter used fortenant billing has to be OFFER approved.

With the growth in the number of competing electricitysuppliers, there are several types of tariff available. Themajor classifications are:

— Two-rate. Separate rates are charged for day andnight.

— Six-rate STOD. The unit rate varies by season andtime of day.

— Disaggregated. This identifies the components ofelectricity use which contribute to the total charge,e.g. energy used, maximum demand, power factor.

— Pool pricing. The unit charge is based on the half-hourly spot price of electricity.

— Tariffs requiring the measurement of reactive power.These are mostly found in industry.

It is outside the scope of this guide to deal with the choice oftariffs. The price of electricity in the pool can varysubstantially from half hour to half hour and pool pricing isonly suitable for large users where the necessary activemanagement of load can be supported. A disaggregatedtariff will be suitable for sites where demand can bemanaged to reduce costs; this is likely to be true wherethere are energy intensive processes that can be controlledto contain the maximum demand. The tariff chosen willaffect the level of submetering and type of energymanagement. Half-hourly metering is almost alwaysworthwhile as detailed demand patterns can assist in theidentification of problems or identification of excessiveelectricity consumption. Management of a disaggregatedtariff requires information on maximum demand availablein real time with some form of warning to enable action tobe taken.

7.1.3 Metering equipment

Energy metering hardware in an energy managementsystem consists of some or all of the following components:

— meter module, which measures the desired quantityand converts the value to an electrical output,typically pulses

Information technology 7-3

Figure 7.1 Monitoring andtargeting management structure

Page 153: Building control system, aplication guide   cibse guide

— display module, which displays the present value ofthe rate of energy consumption, plus other derivedquantities

— data logger, which accepts pulses from the meter,processes and stores data on energy consumptionand transmits data on demand to the centralcomputer containing the M&T software

— data transmission system, connecting one or moredata loggers to the central computer

— computer, containing the analysis software.

Meter module

An electric meter module (Figure 7.2) requiressimultaneous inputs of current and voltage. In a wholecurrent meter, the entire current is wired to pass though themeter. They are suitable for single-phase applications, up toa current of about 80 A. Otherwise, a current transformer(CT) is used which is fitted around each phase conductor.Standard ring type CTs require the cable to be isolated anddisconnected for installation, while split core CTs can beinstalled without disturbance. Clamp-on CTs are used fortemporary connections with portable equipment. Thesecondary current output of the CT is measured by a lowimpedance meter; the resistance of the connection betweenCT and meter must be kept low or an appreciable error maybe introduced. Simultaneous measurement of voltage andcurrent is required to give an accurate measurement ofpower consumption, and is essential for the calculation ofkW, kVA, kVAr and power factor. The harmonic contentand reactive component of many modern electrical loadscan give rise to substantial measurement errors if currentonly metering is used. However, on sites where the powerfactor is high and the voltage stable it may be sufficient toemploy only a current connection to the meter. Where theaim of energy management is the partition of energyconsumption between EACs and the detection of excessconsumption, this will normally be sufficient.

Most meters provide a pulsed output in the form of voltage-free contact closures. This is true for gas, water and othermeters as well as electricity meters. A defined pulse,

typically about 100 ms in duration, is provided each timethe meter records an equal increment of energyconsumption. The scaling is chosen to give a pulsefrequency of around 1 Hz at maximum power. It is possibleto fit optical meter readers to existing utility meters withoutany disturbance to their connections. The reader employs aphotoelectric device to detect the rotation of the meter discor dial needle and provides an output pulse which may behandled in the same way as a conventional pulse output.

For most purposes it is sufficient to measure kWh alone.Where more detail is required, a dual meter modulemeasuring kVA and kVAr may be employed. From thesequantities kWh, power factor and maximum demand maybe derived. It is unlikely that automatic logging of anyother electrical parameters will be required unless there areconcerns over the quality of supply. If necessary, a portablepower analyser may be used to give detailed measurementsof power quality. The measurement and display oninstantaneous power (kW) can be useful for diagnosticpurposes, such as identifying loads in the building andtracking down any ‘hidden loads’.

Display module

The meter may incorporate a display or be connected to alocal display module. At its simplest, this shows a real-timedisplay of the rate of energy consumption, e.g. kW. Morecomplex displays can select kVA, kVAr and have sufficientmemory to show maximum demand and cumulative energyconsumption.

Data logger

The output pulses from the meter are summed in a datalogger module. This will typically have several inputchannels for different meters. The data logger may be partof a separate energy management system. Alternatively,where the energy management system is an integral part ofthe main BMS, intelligent BMS outstations are able to acceptpulsed inputs for energy measurement purposes (Figure7.3). The pulses are counted, scaled and stored to givevalues of energy consumption per half hour for each

7-4 Building control systems

Figure 7.2 Components of an automaticelectricity meter

Page 154: Building control system, aplication guide   cibse guide

channel. There must be a real-time connection between themeter and the data logger. Hardwiring is the most common,being simple and reliable. Where the meters are dispersedover a large site, it is possible to use a radio link between themeters and logger. Where the energy management system isseparate from the BMS, it may be advisable for the EMS datalogger to accept temperature inputs. This makes possibleanalysis of energy consumption as a function oftemperature without any additional data from sourcesoutside the system. Meters are available with built-incommunications systems such as RS 485, typically usingthe MODBUS communications protocol. This is preferredto pulsed output where it is required to measure variablesother than simple kW h.

Computer

The central computer receives and processes the metereddata. The computer may be a separate machine dedicated toM&T or the software may reside in the main BMS supervisor.Where a bureau service is used, the computer is situated offsite and communicates via modem or Internet. Thesoftware can carry out some or all of the followingfunctions:

— retrieval, checking and collation of metered data

— acceptance of data from other sources

— instant access on demand to data from individualmeters

— review of data in flexible format, allowingcomparison between different time periods andmeter locations

— display of additional electrical data such as powerfactor, frequency, reactive power

— comprehensive input of tariff definitions

— automatic production of sub-billing

— automatic production of routine reports

— immediate warning of exceptions, such asparameters exceeding preset limits

— historical analysis of energy consumptions, e.g.regression or cusum.

7.1.4 Data analysis and reporting

For a simple system it may be sufficient to use a spreadsheetfor data analysis. However, once there are several meters

with half-hourly energy readings, it will almost certainly bebetter to employ a commercial software package foranalysis.

7.1.4.1 Data input

The analysis software can only operate properly given acomplete set of accurate data. During commissioning of thesystem, it is important to check that each meter channel iscorrectly identified and that all scaling factors have beencorrectly set. During routine operation, the software can beset to carry out routine checks on the incoming data:

— Is the data within preset limits?

— Is any data missing?

— Is the new reading higher than the previousreading?

Invalid readings should be flagged for the operator’sattention. If the analysis proceeds with dubious input data,the subsequent reports should be so annotated. Subsequentenergy analysis may involve data from other sources, suchas degree-days or production figures. This data has to beprovided reliably and in a form which is compatible withthe metered data, e.g. the periods over which productionoutput and energy consumption are measured mustcoincide. At some stage the measured energy consumptionsshould be compared with the fuel invoices. Where an M&Tsystem is installed in an existing building, it is desirable toinput historical consumption data to provide a basis forcomparison. It may be difficult to provide data in a suitableformat to match the new EAC organisation.

7.1.4.2 Routine analysis

The analysis package will be programmed to produceroutine analysis every reporting period. The type ofanalysis will be tailored to individual needs:

— attribution of energy costs to each EAC, including tenantbilling

— comparison of energy consumption with target figures.

In addition, further analysis can be undertaken which willbe used in reviewing performance and setting futuretargets. Energy consumption often shows a simple linearrelationship with an independent variable such as degree-days or production. A linear regression analysis establishesthe slope of the line and intercept on the consumption axis.This can be used to estimate base consumption such as hot

Information technology 7-5

Figure 7.3 Incorporation of meteringinto a BMS

Page 155: Building control system, aplication guide   cibse guide

water loads, which do not vary with external temperature(see Figure 7.4). Once a historical regression has beenestablished, any new point which falls off the regressionline demands attention. A degree-day regression is subjectto a scatter of around 10%; the analysis may be improved byrefining the choice of base temperature used in compilingthe degree-day figures.

CUSUM

The CUSUM technique(6) compares actual performance withtarget performance for each measurement period anddisplays cumulative savings. It is necessary to be able tocalculate a target consumption for each analysis period; thismay be a function of other variables, such as outsidetemperature. By calculating the cumulative sum of thedifferences from the target, a trend line can be plotted thatgives a clear indication of performance and changes inperformance. The value of the cusum gives total saving todate and the slope gives the performance trend. A change inperformance of the building system will be shown by achange in slope (see Figure 7.5).

7.2 Fault reports andmaintenance scheduling

The BMS can be used to provide information on the total runtime and condition of HVAC components, which can beintegrated into maintenance operations. Ideally, amaintenance policy should be decided for each componentof the HVAC system, taking into account risk, technical andcost issues. Five maintenance categories may be classified:

— run to fail

— install redundant units

— preventive maintenance program

— condition-based maintenance

— redesign to reduce maintenance.

The appropriate maintenance policy for each componentcan be chosen on the basis of the decision tree shown inFigure 7.6.

Preventive maintenance tasks are carried out either atregular calendar intervals or at intervals based onequipment run time. Preventive maintenance ranges fromsimple lubrication to complete tear down and rebuild ofequipment. Selection of the maintenance period is of greateconomic significance and is usually based onmanufacturers’ recommendations. Planned maintenancesoftware is available which is used to:

— catalogue maintenance tasks for various plant items

— generate and manage work orders

— manage inventory for spare parts

— store maintenance history

— generate management reports.

7-6 Building control systemsM

on

thly

oil

con

sum

pti

on

(10

3 l)

Figure 7.4 Linear regression of energy consumption against monthlydegree days, showing the summer base load(4)

0

–1000

–2000

1983 1984 1985

780 x 103 litres

560 x 103 litres

CU

SUM

(10

3 litr

es o

f o

il)

Figure 7.5 Example of a CUSUM plot showing cumulative energy savings(7)

-

Figure 7.6 Selection of maintenance strategy

Page 156: Building control system, aplication guide   cibse guide

The BMS is used to provide information on equipmentruntime, which is fed directly to the planned maintenanceprogram.

Condition-based maintenance

In some situations it is possible to monitor the condition ofan item of plant. This provides valuable information onsystem performance and reliability and can detect earlysigns of trouble in an item of plant, allowing maintenanceto be carried out before the plant progresses to failure orwhen it begins to operate with reduced efficiency. Thistechnique will normally provide greater intervals betweenmaintenance than preventive maintenance carried out atfixed intervals. The economic justification is based on therelation between the increased cost of CBM balanced againstthe saving from increased maintenance periods.

CBM encompasses a set of techniques used to monitor plantcondition. Some may be carried out automatically via theBMS; others require a physical inspection or measurement.Examples of direct monitoring include:

— Pressure drop across filters. This indicates when theyneed to be changed. The analysis algorithm willdepend on whether the system is constant orvariable flow.

— Efficiency of heat exchangers. This may be monitoredby measuring temperatures and flows, and so detectdegradation of performance caused by fouling.

— Operating variables. A selection of plant variables,such as temperature and pressure, is logged. A longterm change in operating conditions may indicatedegradation in the equipment.

Other monitoring techniques are not yet suitable forintegration into the BMS, though this may become possiblein special situations:

— Vibration analysis. Used to detect wear in rotatingmachinery.

— Infra-red thermography. Can detect high resistanceconnections in electrical equipment, high frictionin rotating machinery and failing thermalinsulation.

— Analysis of lubricants. Used to detect wear of gearsand other mechanical parts.

— Motor current analysis. Used in large electricalmotors ( > 20 kW).

7.3 SummaryThe building management system can be used to supportenergy management and targeting by measuringcomponents of energy consumption and exporting the datato a EM&T applications package. The use of EM&T can save 5%of energy costs; this yardstick may be used to supportdecisions on the level of investment in metering. Secondarymeters may be used for tenant billing as well as energymanagement. Monitoring via the BMS may be used to supportmaintenance management. Information on plant run timesand condition monitoring is fed into a planned maintenanceprogram which produces maintenance schedules.

References1 ETSU Computer-aided monitoring and targeting for industry Good

Practice Guide 31 (Harwell: ETSU) (1991)

2 BRECSU Energy use in offices Energy Consumption Guide 19.(Watford: Building Research Energy Conservation SupportUnit) (1998)

3 Jones P G and Cheshire D Bulk data for benchmarking non-domestic building energy consumption CIBSE/ASHRAE JointNational Conference, Harrogate: 29 Sep–1 Oct 1996 1. 203-213(London: Chartered Institution of Building Services Engineers)(1996)

4 CIBSE Energy audits and surveys Applications manual AM5(London: Chartered Institution of Building Services Engineers)(1991)

5 Energy efficiency in buildings CIBSE Guide F (London: CharteredInstitution of Building Services Engineers) (1998)

6 Harris P Energy monitoring and target setting using CUSUM(Cheriton: Technology Publications) (1989)

7 Degree days Fuel Efficiency Booklet No. 7 (London: Departmentof the Environment, Transport and Regions) (1993)

Information technology 7-7

Page 157: Building control system, aplication guide   cibse guide

8 Building control systems

This Page Intentionally Left Blank

Page 158: Building control system, aplication guide   cibse guide

8.1 Procurement optionsThe form of procurement chosen by the client can have animportant influence on the way in which the controls aredesigned and installed. Irrespective of the procurementmethod, we may define the main parties involved in thebuilding process as:

— Client: the customer for whom the building isprocured and who pays the cost.

— Contractors: companies that construct the building.There may be firms that manufacture and installspecialist subsystems and work as subcontractors tothe main contractors.

— Consultants: firms that offer design and cost controlservices and are independent of any commercialinterest in construction companies.

The procurement of a large building is a complex processand over the years different forms of organisation andmanagement have developed. Thinking About Building(1)

identifies four main procurement options. Many variationsof these basic structures are possible, and are discussed atlength in Turner(2). The major systems may be classified asfollows:

— Design combined with construction

— design and build

— design and manage.

— Design separate from construction

— traditional

— management methods.

The structure of the options is shown in Figure 8.1 in

simplified form. The following describes their maincharacteristics that are relevant to control systems.

8.1.1 Design and build

With design and build, the client places a contract with asingle contractor who has responsibility for both designand construction. The client may appoint an adviser to actas employer’s agent, to advise on the preparation of theclient’s brief, evaluation of tenders and to provideindependent advice throughout the project. Design andbuild has advantages:

— The client has single point responsibility from oneorganisation.

— Because the contractor has responsibility for bothdesign and construction, economies should bepossible.

A well-written client’s brief is essential to the achievementof a satisfactory controls solution in the final building; aninadequately detailed initial brief may lead to thecontractor providing an absolute minimum specification. Avariation is known as develop and construct, where theclient uses a design consultant to produce a scope design,before obtaining tenders from contractors who develop andcomplete the design and then construct the building.

8.1.2 Design and manage

A single firm is appointed to design, manage and deliver aproject. This is similar to design and build, except that thedesign and management contractor does not carry out theconstruction, but places this with a construction con-tractor. The common variations of design and manage are:

8-1

8 Management issues

8.1 Procurement options

8.2 Design and specification of a controls system

8.3 Tendering process

8.4 Commissioning

8.5 Operation

8.6 Occupant surveys

8.7 Cost issues

8.8 Summary

Effective planning is essential to ensure that the final building is properly controlled. This section describes different variationsof the building procurement process, setting out the responsibilities of the parties involved, with emphasis on the part playedby the controls specialist. The importance of good planning is emphasised in ensuring that the control system is properlyspecified, installed and commissioned. Operation and maintenance of the control system subsequent to handover is also dealtwith. The financial benefits of the investment in a BMS may be analysed using the life cycle costing methods described in thesection.

Page 159: Building control system, aplication guide   cibse guide

— Contractor. A project design and managementorganisation designs and manages the work,generally for a fee, and delivers the project byemploying works contractors to design and orconstruct.

— Consultant. An organisation that is the client’sagent designs and manages the work andobtains subcontracts from works contractors whothen each enter into a direct contract with theclient.

8.1.3 Traditional

The traditional procurement method separates design fromconstruction. The client appoints design consultants whoprepare a detailed design of the building. The design is putout to tender, following which a main contractor,responsible to the client, is appointed. The main contractormay appoint subcontractors. During construction, thedesign consultants exercise a supervisory role. This methodis well understood in the UK and has the advantages of:

8-2 Building control systems

Figure 8.1 Major procurementoptions. (a) Traditional (lump sum)contracting relationships. (b) Designand build. (c) Constructionmanagement. (d) Design and manage

Page 160: Building control system, aplication guide   cibse guide

— providing clear contractual responsibility for eachaspect of the work

— a well-understood procedure.

From the controls point of view, it has disadvantages:

— There is no involvement of specialist subcontractorat the design stage.

— Modifications to the design during construction areexpensive.

8.1.4 Management methods

Management methods separate to a greater or lesser extentthe function of management from those of design andconstruction. They have become associated with projectswhich are large and complex, and where early completion isrequired. Management methods give more flexibility tomodify requirements during the course of the project anddesign and construction may overlap. Reduced projecttimes are generally possible by continual re-evaluation ofoptions and reallocation of resources. This allowsvariations to be introduced more easily than the traditionalmethod but can result in increased costs. This flexibilitymay make it difficult to assign responsibility in case ofdispute. There are two main variations of managementmethods:

— Construction management. Design and constructionare still separate functions, but a constructionmanager is appointed to manage the whole process.The manager is appointed by the client;consultants and contractors have a directcontractual agreement with the client.

— Management contracting. The appointedmanagement contractor provides the services ofmanaging for a fee all the works contractors byemploying them as subcontractors.

8.1.5 Relations between parties

There are many variations of the above, which aresummarised in Turner(2). The traditional organisation stillaccounts for the majority of new buildings, particularly forthe smaller operations. Construction management is stillrelatively uncommon, except for large complex projects.Design and build is increasing. The form of organisationcan affect the process of designing and installing a controlsystem. In the traditional system, the controls specialistsubcontractor is at the end of a contract chain, which maymean that available money and time are insufficient toproduce the required quality of installation. The exclusionof the specialist contractor from the design process maymean that their experience is not taken into account.Fragmentation of the design consultancy can mean thatcontrols consultants do not have an input into the design ofthe HVAC system itself, leading to the common complaintamong controls consultants that the systems they arepresented with are inherently uncontrollable.

The general awareness that procurement practices could beimproved led to a review being set up under thechairmanship of Sir Michael Latham to consider:

— current procurement and contractual arrangements

— current roles, responsibilities and performance ofparticipants, including the client.

The Latham report Constructing the Team(3) recognised thatthe efficiency of the British building industry could beincreased by improving the interrelationship of the manyparties involved. Many of the report’s recommendationshave been implemented, or are in the process of being setup. However, a subsequent report(4) found that the UK M&Econtracting industry lagged well behind that of othercountries. Among a number of factors, the report identifiedthe following which are relevant to controlssubcontracting:

— lack of project planning and organisation

— poor quality design of services

— lack of approved installation drawings

— inadequate use of prefabrication and pre-assembly.

Further recommendations for improvement in both qualityand efficiency were contained in the Egan report RethinkingConstruction(5), which proposed a target of a cost reductionof 10% per year plus a reduction in defects. The reportstrongly favoured the use of partnering methods, which aredescribed further below.

8.1.6 Partnering

Partnering is not a different form of procurementorganisation, but rather a cooperative approach which hasbeen defined as an arrangement whereby people are encouragedto work more efficiently together, including shared problemresolution, continuous improvement, continuity of work, fastconstruction, completion on time and improved profits. Twotypes of partnering are in common use — projectpartnering, where one-off development is undertaken usinga team that agrees to work in partnership, and strategicpartnership, where the same team is involved over a seriesof construction projects. A study by Reading University(6)

calculates that savings of up to 10% may be achieved withone-off partnerships, and up to 30% for strategic partner-ships. Partnering aims to replace the confrontationalsystem of watertight contracts with a more open approachto resolving problems as they arise. This often involvespartnering workshops, where all parties meet on neutralterritory to set goals and resolve problems. The workshopsmay be conducted by a facilitator, a third party skilled inteam building and group dynamics.

Since partnering requires a shared approach to problems itis often linked to some form of profit sharing. Whilepartnering may be applied to almost any form ofprocurement, it is best suited to a situation where thepartners learn to work together over a series of projects in astable market. The client has also an important part to playin creating the conditions where partnering can flourish.Table 8.1 indicates the situations where the partneringapproach may be most useful.

The controls specialist will be expected to contribute to thedesign at an early stage and to take part in partneringworkshops to increase the effectiveness of all members ofthe construction team. This will help contribute to thedesign of an effective, controllable HVAC system. In returnthe controls specialist is entitled to expect the maincontractor to(7):

Management issues 8-3

Page 161: Building control system, aplication guide   cibse guide

— offer greater predictability of work

— use standard forms of subcontract

— refrain from rebidding to help reducesubcontractor’s bid costs

— draw up a preferred list of subcontractors

— honour tender commitments

— reimburse the costs of design.

Partnering does not normally involve a legally bindingagreement, though it is common for everyone to sign up to apartnering charter setting out the declared aims. Care needsto be taken to ensure that a partnering agreement does notfall foul of the laws on restrictive practices or faircompetition, which may prevent exclusion of potentialbidders or demand that contracts must be awarded onlowest price. Partnering is by no means a panacea and itcannot compensate for other inefficiencies.

8.2 Design and specificationof a controls system

8.2.1 Sequence of events

Table 8.2 illustrates the steps involved from design tocompletion of a building control system. The procedure isbased on the traditional building procurement method, butit applies to all methods, with some variations inresponsibility. The first step is for the client to set out therequirements for the building as a design concept. Themore clearly the client’s requirements are set out in theproject brief, the better controlled will be the wholeprocess. The outline design process should includeconsideration of the end user’s operational requirementsand the general level of control and IT systems. The clientmay appoint a principal adviser at this stage to supplyindependent advice now and later in the project. The use ofa principal adviser may be crucial to the success of a projectwhere the client has little in-house experience.

Once the brief has been agreed, the design work is passedover to consultants, whose job it is to produce the finaldesign which will form the basis of the building contract.For a complex building, the controls design is likely to bedone by a specialist consultant, either an independent firmor a specialist group within an M&E consultancy. The levelof detail varies from project to project; it may be a completespecification, or a simple performance specification, whichleaves the controls specialist to do the detailed design work

and select the supplier. It is possible to place the controlsdesign with a manufacturer, who will provide design,supply and installation to the project. Large buildingprojects will be constructed by several contractors andsubcontractors and it is important that theirresponsibilities be clearly allocated. Some level of designresponsibility is normally allocated to the installingcontractor, for instance by an instruction that they producedrawings. The division of responsibilities betweencontractors must also be made clear in the specification. Anexample relevant to controls is the provision of cabling.Power and signal cabling may be provided by differentcontractors and BMS signals may be partially carried by ashared IT network. The specification must detailresponsibilities, including the routing of cabling to satisfyEMC requirements.

Potential contractors bid for the contract to construct thebuilding. The successful bidder, the main contractor, isunlikely to provide all necessary specialists in-house, andmay appoint specialist subcontractors to supply and installthe control system. This subcontractor may need to providedetail design work, depending on the completeness of the

8-4 Building control systems

Table 8.1 Situations where partnering can be used(7)

Partnering may Good for partnering Ideal for partneringprovide benefits

Form of contract Traditional Management contracting Construction management

Initiator Consultant, contractor Client

Programme of work One-off Regular Programme of similar projects

Project type High value, high risk

Market conditions Boom/bust Stable

Table 8.2 Sequence of events in building procurement

Activity Responsible

Concept and design brief of building, Client, architect, principal including control and associated adviserrequirements

Place contract for design with consultants Client

Produce detailed design of building, HVAC Architect, consultants, and control systems, which becomes basis controls specialistfor tender document

Estimate costs and prepare bid Contractors

Place contract with main contractor Client

Main contractor may subcontract controls Main contractorinstallation

Prepare and agree description of operation Controls specialist

Prepare detailed installation drawings

Obtain items from suppliers and installcontrols systemCheck operationPrepare documentation

Test and commissioning Commissioning sub-contractor, with consultantsupervision

Staff training Controls specialist

Acceptance and handover Client

Fine tuning and maintenance of controls Separate contract

Page 162: Building control system, aplication guide   cibse guide

Management issues 8-5

controls specification. When the specialist subcontract hasbeen appointed, they may prepare a description ofoperation. This document sets out how the subcontractorintends to interpret the controls specification and realise itas a practical operating control system. The description ofoperation is referred back through the contract chain to beagreed by the client and the consultant responsible for thecontrols specification. This ensures that the specificationhas been interpreted properly and that the client is clear asto the controls system that will be provided; the procedurealso gives some protection to the controls specialist againstlater disputes arising from any misunderstanding.Commissioning of the HVAC and controls systems may becarried out by an independent specialist subcontractor,witnessed by the controls specialist and the controlconsultant. Provision of full documentation and trainingfor the staff who will operate the systems is an essential partof the process and is completed before handover of thesystem to the client.

8.2.2 Design brief

The first stage is for the client to set out the requirements ina way that can be interpreted by the design team. Thecontrol system of a complex building is essential to theproper functioning of the building. It represents asubstantial cost and the design of a BMS should beconsidered from the start. The design brief produced by theclient should include any particular requirements andrestrictions on the cost and scope of the controls. The clientshould consider carefully the intended function of thebuilding and its occupants together with future control andIT requirements. This should include discussions betweencontrols companies and the end user. Experience showsthat the best building management systems result fromsituations where controls specialists and the end user havehad direct contact with each other. It is never too early toinclude the end users, including operators of the BMS andthe building occupants. The client, in association with adesign consultant, produces a design brief, which forms thebasis for the specification. The Building Control Group haspublished a pre-specification checklist, which isreproduced in Figure 8.2.

Where installation of a BMS is being considered for anexisting building, planning should start with a thoroughsurvey of the building and its operation. An energy auditwill reveal sources of avoidable energy waste, which shouldbe rectified before starting work on the control system. Theneed for centralised control should be considered critically;for smaller installations, the use of stand-alone controlsmay be a cheaper alternative compared with BMS.

8.2.3 Specification

The specification forms the basis of bids by contractors andis the basis of the eventual contractual agreement. It istherefore essential that the specification provides acomplete and unambiguous definition of the buildingcontrol system. Changes made to the specification afterwork has started are likely to be expensive. It is alsoimportant that the specification should set out clearly theallocation of design responsibilities to avoid subsequentdisagreements(8). A comprehensive treatment of the issueswhich should be considered when specifying a BMS is givenby Pennycook and Hamilton(9). To simplify the process of

drawing up a specification and to reduce the chance ofimportant items being overlooked, various bodies havedrawn up outline specifications which may be used with theminimum of modification. Teekeram and Gray(10) reviewedthe situation over several countries. The mostcomprehensive and widely used is the National EngineeringSpecification (NES), which is structured in accordance withthe CPI Common Arrangement of Works Sections forBuilding Works(11). The Controls and BMS sections of theNational Engineering Specification refer to the UK standardspecification for BMS which was drawn up by the BEMSCentre(12). It is in turn based on the Standard Specification(M&E)(13).

The aim is to set out the specification in functional terms,rather than prescribing the hardware and software to beused. In a time of rapidly changing technology, functionalobjectives may be achieved by different hardware andsoftware strategies for different systems. The functionalapproach should encourage suppliers to offer the mostsuitable systems on a competitive basis.

A project specification compiled using the NES has threemain sections:

— Preliminaries, referring to the whole project.

— System specifications, one for each relevant worksection.

— Reference specifications, relevant specificationsdrawn from Group Y, where Group Y is acollection of specifications of component partsand materials. These may be relevant to severalsections in the system specification, so it iscommon practice to bind them in a separatevolume for easy reference.

The Preliminaries section is drawn from Group A of theNES and contains an overall description of the project,together with information on organisation and contractualmatters. Specification for the controls system must take itsplace and be compatible with the specification for the wholeproject. The preliminaries for the controls systemspecification must not conflict with the main contractpreliminaries, which is the governing document for thewhole project.

Each of the systems specifications is subdivided into threeparts:

— Part 1. System objectives. The system objectives aredescriptive clauses to be written by the specifier,using the following headings:

— performance objectives

— design parameters

— system description

— control requirements

— system schematics

— system drawings.

The system objectives should provide a completereference package so that the ideas behind thedesign are passed on in an intelligible and logicalformat. The first three parts should start as soon asthe client’s brief has been received, and kept up todate as the design proceeds. In the absence of a

Page 163: Building control system, aplication guide   cibse guide

8-6 Building control systems

BUILDING CONTROLS GROUP PRE SPECIFICATION CHECK LIST1 GENERAL DETAILS1.1 Have the detailed operational needs of the End User been fully considered?1.2 Will the envisaged Form of Contract allow for the needs of the Client/User to be met?1.3 Is there to be scope for integrating other functions/elements into the BMS?

If YES which:a) Access/Security b) CCTV c) Lighting controld) Chillers e) Boilers f) Variable speed drivesg) Others, please specify

1.4 Will any elements of the system need to be Acceptance Tested at manufacturers works?1.5 Will the system be required to be expanded and/or upgraded over the next 5 to 10 years?1.6 Will the BMS supplier have a minimum 4 week tendering?

Section 2 OUTSTATION DETAILS2.1 Will the Motor Control Units (MCC s) contain the outstations?

If YES outstations should be contained in a separate control sectionIf NO please state the distance between MCC and outstation

2.2 What form of MCC will you be specifying?2.3 Are the MCC s to be a special colour? If YES please specify2.4 What IP ratings are the MCCs?2.5 If OUTSIDE the MCCs what IP rating is required for outstations?2.6 Have you specified the number of points (inputs/outputs) to be covered by the system

If YES please indicate:)a) Analogue (resistance b) Digital (open or closed c) Pulse (metering)voltage or current) contacts)d) Hardware e) Software f) Other (please specify)

2.7 Are the outstations to have any special features? If YES please indicate:Memory battery back-up I/O battery back-up Special cardsIndividual I/O override UPS Other features

2.8 Are the outstations to have displays/keypads?If NO please state which are not required. Is a fully functional laptop PC required?If YES please indicate: a) Door mounted b) Within MCC c) Portable device d) Specially protected e) on all outstations If NO please specify how many, which and what functionality

Section 3 CENTRAL SUPERVISOR SOFTWARE & HARDWARE3.1 Is there to be a Central Supervisory Computer on the project?3.2 Is the Central Supervisor dedicated to BMS or also running other programmes?3.3 Have you specified the hardware and can it cope with the project?3.4 What size monitor have you specified?3.5 Have you specified ALL the software that you require for this project?3.6 Is the Central Supervisor to be networked?

If YES please indicate the type of network.3.7 Do you require extra computer terminals? If YES how many3.8 Have you specified how these terminals are to be configured?3.9 Have you indicated where these terminals are to be located?3.10 Will remote telephone modem communication be required?

4 INSTALLATION4.1 Will the BMS Contractor be required to supply

a) Computer hardware b) sensors/actuators c) MCC sd) Install all the above e) Cable all the above f) Engineer BMS softwareg) Supervisor software h) Power wiring i) Commission the above

4.2 Will Tendering Information accord with the Building Controls Standard Method of Measurement?4.3 Will you be applying special conditions to the contract installation? If YES please specify

5 TRAININGWhat Training will the BMS Contractor be required to provide?Off site On site Other

6 WARRANTY AND MAINTENANCE6.1 Have you Included for a system service & maintenance contract in your tender documentation?

If YES have you specified the type of cover you require a) 24 hour callout b) Guaranteed response time c) 6 monthly maintenance check-up d) Annual maintenancecheck up e) Dedicated spares holding e) Other requirements

6.2 Have you specified the period during which you require maintenance to be provided ?IS THERE ANYTHING ELSE YOU OUGHT TO HAVE THOUGHT ABOUT?

Figure 8.2 Pre-specification checklist (courtesy Building Controls Group)

Page 164: Building control system, aplication guide   cibse guide

central control system, the control requirementsare listed in the system specification for the relevantwork section. Where a central control system is tobe used, the control requirements may either belisted in the relevant system specification, or else alldetails of the control system can be listed in theCentral Controls Work Section, with appropriatecross-references from the systems being controlled.

— Part 2. Selection schedules. This part contains a list ofreferences to the relevant Y Group ReferenceSpecifications that are relevant to this work section.As well as invoking the relevant specification, theschedule invokes required clauses from Group Y,deleting irrelevant options; additional text may beinserted as required.

— Part 3. Clauses specific to the system. This containsinformation specific to the work section. The NEScontains a large number of clauses and Part 3 isconstructed by deleting clauses and options that arenot required.

The NES is designed to aid production of specifications byproviding a standard logical structure, which is amenable toincorporation in computer programs. As far as BMSs areconcerned, it is complementary to the material presented inthe BSRIA documents(12) and indeed Work Section W62 ofthe NES makes frequent reference to the BSRIApublication.

8.2.4 Conditions and tolerances

The specification of the required controlled conditions andpermissible tolerances must be considered carefully.Setting unrealistically tight tolerances may result in eitheran unnecessarily expensive design solution to meet them,or a system which fails to meet the specification, with theattendant risk of legislation.

General comfort criteria are covered in Section A1 of theCIBSE Guide(14) and by ASHRAE-ANSI Standard 55(15).The most important variable is the temperature in theoccupied space. This may be specified in terms of airtemperature, environmental temperature or one of anumber of comfort indices. The adaptive model of thermalcomfort(16) states that it is permissible to allow spacetemperatures to rise in summer, since the occupants learnto adapt and minimise discomfort. This has importance forthe design of HVAC systems, since it may be possible toreduce or even eliminate the need for air conditioning.Where this principle is adopted, the acceptable limits ofbuilding performance must be understood and accepted byall parties.

Where full air conditioning is employed, the required rangeof air temperature and humidity is specified. Theinteraction of air temperature, relative humidity andmoisture content must be remembered. In general, themoisture content of the air in a building is less subject tovariation than the air temperature. Changes in airtemperature at constant moisture content may cause therelative humidity to go outside the specified range. Peopleare not very sensitive to the level of ambient humidity and arange of 40 to 70% RH is normally found acceptable. If closercontrol is required, then the tolerances must be specified insuch a manner that they can be realistically met by the HVACsystem. Where central control of humidity is used, it may

be better to specify humidity in terms of moisture contentrather than relative humidity.

Similar considerations apply to plant operation. Controllimits must be within the capability of the plant and itsmeasurement and control system. When specifying thetolerances for system variables there is no point inspecifying unnecessarily narrow limits, even if they can bemet. The heat output from a heat emitter may be littleaffected by a 20% variation in water flow; however, anarrower specification is required for chilled watersystems(17).

8.3 Tendering process

8.3.1 Pre-tendering

In many cases it is advantageous to draw up a short list ofpotential suppliers who will be asked to tender for theproject. The use of a pre-tender brief allows selection ofsuitable tenderers to be produced, avoiding wasted effort. Apre-tender brief is given to possible suppliers, who areasked to return a questionnaire and are then interviewed todiscuss the project in outline. The pre-tender brief containsenough information to indicate the size and complexity ofthe project, the available budget and the proposed timescale. The brief should contain the following:

— objective of the brief

— project description

— an indication of cost

— project management and form of contract

— building and plant schedules

— questionnaire.

8.3.2 Tendering

The usual documents required for the tendering process areshown in Table 8.3. More detail, together with examples oftender documentation, is given in BSRIA(12). If the pre-tendering process has produced a suitable short list and thespecification has been properly drawn up, assessment ofthe tenders should be straightforward. To protect

Management issues 8-7

Table 8.3 Tender documents

Document Purpose

Instructions to tenderers How to complete the tender documents

Form of tender On which the tender bid is returned

Tender details and summary Cost breakdown of the tender price. Willprovide the basis for any negotiation ofvariations

Form of contract and specialconditions

Full specification Full set of standard and particularspecifications, together with relevantplans and drawings

Information required from Additional requirements needed totenderer confirm details of the tender

Page 165: Building control system, aplication guide   cibse guide

subcontractors against possible bad practices, a Code ofPractice for the Selection of Subcontractors(18) has beenpublished by the Construction Industry Board.

8.4 CommissioningCommissioning is defined by CIBSE as ‘the advancementof an installation from static completion to working orderto specified requirements (as envisaged by the designer)’.Correct commissioning is vital to the satisfactoryoperation of the HVAC system and it is essential thatsufficient time and resources be allocated to the task.Since commissioning is the last major operation in thebuilding process and the control system is the last systemto be commissioned, there is every danger thatcommissioning the control system will take place undergreat time pressure or even continue after the building isoccupied. Experience has shown only too well that thiscan create many problems, with an unacceptably highproportion of buildings failing to operate properly, withconsequences of high energy consumption and occupantdissatisfaction. This section emphasises the importance ofensuring that commissioning takes its proper place in theprocurement process from the start of planning theproject.

Commissioning of the control systems is dependent onsatisfactory operation of the electrical and mechanicalservices. The control system may also interact withspecialist services such as security, access control and theIT system. The greater the degree of integration, the moreplanning is necessary and the more care required todefine areas of responsibility(19). Sequential records of allstages of pre-commissioning and commissioning of allother aspects of the building must be issued prior tocommencement of the commissioning of the automaticcontrol system.

Table 8.4 summarises the stages of the procurement processand the activities which are relevant to the commissioningof the controls system.

8.4.1 Commissioning management

For the traditional UK procurement organisation, theresponsibilities for commissioning the BMS are shown inTable 8.5. This arrangement has the advantage of clearlydefined responsibilities. However, it does not necessarilyproduce the most effective commissioning. The controlsspecialist, who is responsible for installation andcommissioning, has little or no input into the design of theBMS, nor the design and commissioning of the plant whichwill be controlled by the BMS.

8.4.1.1 Project management

The organisation and management of commissioning isdescribed in detail by Pike and Pennycook(20), whichgives examples of matrices of responsibilities forcommissioning. Good project management is essentialfor large and complex projects and the subject iscovered in the Guide to the BEMS Centre StandardSpecification(12).

— A detailed commissioning programme should bewritten and agreed with the main contractor.

— There must be a means of monitoring progress.

— Checklists should be used to monitor progress.

— The controls specialist must have a documentationsystem in place for dealing with variations tocontract.

Project management guidance(21) and BSRIA’sCommissioning Guides define responsibilities for thepersonnel involved in the commissioning process. Dutieswill vary between projects depending on assignedresponsibility. Example roles are detailed below.

The project manager has a coordinating, monitoring andcontrolling role for the project. The responsibilities includethe following:

— aiding the client selecting the design team andother appropriate consultants and negotiating theirterms and conditions of employment

— setting up the management and administrativestructure for the project.

Table 8.5 Commissioning responsibilities for traditional procurement

Party Responsibility

Client Write design brief

Appoint design consultant

Design consultant Write BMS functional specification

Review tenders from BMS contractors

Appoint BMS contractor

Witness commissioning

Approve completion

BMS contractor Prepare tender

Design BMS to meet specification

Install BMS

Commission BMS

8-8 Building control systems

Table 8.4 Commissioning activities during theprocurement process

Stage Commissioning activity

Brief Commissioning objectives

Appoint commissioning manager

Design Minimise need for commissioning

Design for commissionability

Installation Pre-commissioning

Commissioning

Handover Witnessing

O&M documentation

User training

Operation Monitoring and feedback

System proving

Fine tuning

Recommissioning

Page 166: Building control system, aplication guide   cibse guide

The client’s commissioning manager provides the controlpoint for commissioning for the client. The manager will beresponsible for:

— arranging the appointment of the commissioningteam

— establishing the commissioning objectives

— developing a comprehensive commissioningprogramme and preparing the roles and jobdescriptions for each member of the team

— arranging the sessions for user training at the end ofthe project.

The professional consultants must identify the services tobe commissioned and define the responsibilities splitbetween the contractor, manufacturer and client. They arealso responsible for inspecting the work for which theyhave design responsibility (including inspecting the workat the end of the contract defects liability period) anddefining the performance testing criteria to be adopted.

The site commissioning manager may be a member of themain contractor’s team and provides the focus for themanagement of all the commissioning activities. The tasksmay include the following:

— coordinating the professional team members andthe client’s involvement in commissioning

— ensuring that the contractors’ programmes includecommissioning activities and that these coordinatewith the main construction activity

— acquiring appropriate information from therelevant parties to ensure that the systems can becommissioned in accordance with relevant codes ofpractice

— witnessing works and site testing of plant, cleaningand commissioning

— demonstrating safety systems to the local authority,fire officer, district surveyor and the building insurer

— providing a focus to collect all handoverdocumentation.

8.4.2 The brief

The original brief will lay down the foundation for theorganisation of commissioning. This is the stage at whichthe organisation of the whole building procurement processis decided. For large projects, the appointment of acommissioning manager should be considered, with theresponsibility of ensuring that the requirements ofcommissioning are considered at all stages. The managerwill be responsible for appointing the commissioning teamand ensuring that adequate resources for commissioningare built into the specification. Decisions should be taken atthis stage whether commissioning should extend beyondthe handover of the building and whether provision is to bemade for system proving and post occupancy feedbackwhen the building is in operation.

8.4.3 The design stage

Commissioning should be borne in mind at the initialdesign stage; this applies to both the HVAC system and the

control system itself. Two complementary approaches arerelevant:

— designing to minimise commissioning

— designing to make commissioning easier.

The amount of commissioning needed can be reduced byappropriate design:

— Design for self-balancing wherever possible.

— Balance pressure drops across sub-branches andterminal units.

— Avoid using different terminal units on same branch.

— Use reverse return pipework layouts.

— Use automatic balancing valves.

— Use variable-speed drives for fan and pumpregulation.

— Use computer analysis to give settings for presetvalves.

Attention to the needs of commissioning at the design stagewill make it easier. Conversely, failing to provide thenecessary facilities for commissioning may make itimpossible. The following items will assist commissioning:

— Include regulating valves where appropriate.

— Include isolation valves and test points.

— Include flow measurement devices at mainbranches and major heat exchangers.

— Ensure that the system may be cleaned and vented.

— Ensure access for commissioning andmaintenance(22).

— Provide items of plant with a ‘manual–off–auto’switch. The switch can be set to ‘manual’ forcommissioning the plant itself, prior tocommissioning the BMS.

— Agree at an early stage a common procedure forallocating mnemonics to identify points uniquely.

— Obtain mid and full load design values fromconsultant.

The design consultants are responsible for writing thesystem specification, which includes the commissioningspecification. At this stage a commissioning specialistshould review the specification.

8.4.4 Installation

Satisfactory commissioning of the BMS is of coursedependent on the correct installation and commissioningof the HVAC plant. The commissioning manager will ensurethat plant is in a suitable condition before commissioningof the BMS commences and is certified as such. Above all, allwater systems must be flushed clean; the presence of debrisin water systems is a common cause of problems in thecommissioning of valves.

8.4.4.1 Pre-commissioning the BMS

Pre-commissioning is the checking of all the components ofthe controls system, both on the bench and on site, before

Management issues 8-9

Page 167: Building control system, aplication guide   cibse guide

putting the system into operation for commissioningproper. As much checking should be done off site beforeinstallation; this will normally be faster and allow rapidrectification of any problems that are found. Checking ofsensors for accuracy is best done off site under controlledconditions. The on-site pre-commissioning consists inchecking that all items have been installed in the rightplace, the right way round and are wired correctly. Pre-commissioning tasks include:

— maximisation of off-site testing and pre-commissioning of control panels, applicationsoftware etc.

— the checking of all wiring for short circuits,continuity, identification and termination

— the checking of all sensors for correct installation

— proving of all actuators

— proving the presence of outputs and devices on thenetwork bus system.

8.4.4.2 Commissioning the BMS

Before commissioning can start, all control hardware mustbe installed and pre-commissioned. Any unitary controlson plant which is to be connected to the BMS should havebeen commissioned, or be commissioned in parallel withthe BMS. The HVAC plant itself must have beencommissioned; all plant items under control of the BMSmust have been commissioned and the system flushed cleanand vented. All electro-mechanical safety interlocks andfail safe conditions should be implemented andoperational.

Commissioning the BMS consists of two major activities:

— checking that the control system works

— setting all parameters and switches to appropriatevalues, including tuning control loops.

Checking the system

Both the head end supervisor and the controls of particularbuilding services plants have to be commissioned. Thesupervisor requires commissioning after installation. It

may be commissioned in parallel with the outstationswhich control specific items of plant, when it can itself beused as an aid to commissioning. Full commissioning of thecentral supervisor requires previous completion of plantcommissioning. For specific plant commissioning, theCode of Practice(20) sets out five basic items, to which hasbeen added the relation with the supervisor:

— panel controls

— hardware points

— interlocks

— control loops

— alarms

— supervisor.

This procedure is illustrated by the example of an airhandling unit shown in Figure 8.3. Table 8.6 summarisesthe tasks of the commissioning process; the example issummarised from Pike and Pennycook(20).

Setting the values

An important function of a BMS is its operation as atimeswitch, controlling the start and stop operation ofmany systems throughout the building, includingoptimisers. All BMS supervisors allow time schedules to bereadily altered at the head end. However, experience showsthat the initial settings may remain unaltered. Accordingly,the client should supply as much information as possible onrequired time and temperature schedules, to allow thecorrect values to be input during commissioning. It isrecommended that the controls specialist sends aquestionnaire to the client asking for relevant information.A sample questionnaire is given in the commissioning Codeof Practice(20).

All control loops require to be tuned. While the goal isminimum response time consistent with stability, it mustbe remembered that the operating gain of a control loop islikely to vary with operating conditions, so that the gainwill vary with season. Where possible, the loop should betuned under conditions of maximum gain; this will ensurestability under all conditions. Various ways of tuning loopsincluding the use of automatic tuning are discussed in 2.4.1.

8-10 Building control systems

Figure 8.3 Air handling system to becommissioned

Page 168: Building control system, aplication guide   cibse guide

8.4.5 Handover

Once commissioning of the control system has beencompleted, it is demonstrated in front of witnesses and acompletion certificate issued; the client’s representativemay attend. The witnessing officer will require acompletion method statement which details thearrangements, methods and a list of items to bedemonstrated in front of witnesses. Witnessing is just onepart of completion. Documentation and trainingarrangements are also required. Table 8.7 summarises theitems to be covered during completion. When all itemshave been completed to the satisfaction of the testers andwitnesses, a certificate to that effect is signed off by bothparties and handover takes place. Handover representschange of ownership from contractor to client.

8.4.5.1 Witnessing

The organisation of witnessing will depend on the natureof the system and is decided by the witnessing officer. Forlarge projects, there are advantages in a phased approach,so that witnessing of completed subsystems can beginbefore final completion of the whole system. It is notessential that every point be checked. A sufficient numbershould be checked to give the witnesses confidence in the

overall reliability, using a quality control approach. Themethod suggested in the BEMS commissioning Code ofPractice(20) is:

Management issues 8-11

Table 8.6 Commissioning an air handling unit

Step Function Check

Panel controls Power Phases healthy, panel live, BMS power on

Fire alarm Reset button, lamp test

Supply fan Run, trip, test/off/auto switch, overload range and set

Extract fan Run, trip, test/off/auto switch, overload range and set

Fuses Correct size, spares in panel

Hardware points Sensors Outputs, correct connections

(at pre-commissioning) Actuators Full stroke travel

Connections Continuity and polarity

Interlocks Fans Supply and extract fan interlock

Dampers Supply, extract and recirculation dampers synchronised

Coils Heater and cooler batteries move to default position on shut-down

Fire Appropriate action on fire signal, e.g. close supply and recirculationdampers, open exhaust damper, stop fans

Control loops Optimiser Set parameters

Frost Set and test frost protection and morning boost

Control loop Set proportional and integral constants

Operation of valves and dampers

Enthalpy control if fitted

Run-time totalisation

Software Check application software

Timeswitches Run through time schedules

Alarms General Operation, labelling

Filter block Set pressure switch and check operation

Supply fan Set pressure switch and inhibit time. Check operation

Extract fan Set pressure switch and inhibit time. Check operation

Supervisor Graphics Points labelling, plant depiction

Control functions, correct values

Table 8.7 Completion checklist(20)

Item Description

1 Audit of cabling and hardware installation

2 Demonstration that sensors and actuators are correctlyconnected and addressed

3 Demonstration of the physical and logical integrity of thesystem

4 Demonstration of the sensor calibrations

5 Demonstration of all control actions

6 Demonstration of successful system software commissioning.(This should include loading and subsequent operation)

7 Verification of specified graphics

8 Verification of specified training arrangements

9 Verification of handover of all specified manuals,documentation and drawings

10 Verification of handover of back-up copies of software

11 Verification of handover of consumable spares

Page 169: Building control system, aplication guide   cibse guide

— The BMS controlling the main plant (e.g. boilers andchillers) and other important points should bewitnessed completely.

— The proportion of other points to be witnesseddepends on the size of the system, e.g. if fewer than300 points, witness all the points, between 300 and1000 points, witness 50%, and if more than 1000points, witness 20%.

— If the failure rate is greater than 15%, thesupervising officer should have the right to witness100% of the points.

— Where there are several similar plants, one can bewitnessed in detail and the others on a samplingbasis.

8.4.5.2 Documentation

Good operations and maintenance (O&M) documentation isnecessary for successful:

— day-to-day operation of the system

— effective maintenance

— system refurbishment.

There is a statutory requirement under the CDMRegulations(23,24) to provide proper documentation. Theclient is required to appoint a planning supervisor, whosefunction is to ensure that a health and safety plan isprepared, to advise the client on the necessary resourcesrequired to implement the plan, and to prepare the healthand safety file. The health and safety file is a record ofinformation for the end user, which tells those who mightbe responsible for the building in the future of the risks thathave to be managed during maintenance, repair orrenovation. Operation, maintenance and commissioningdocumentation make up part of the health and safety file.The file must include details of hazards and risks, and thesafety certificates collected during construction. Thedocumentation must be presented in the format required bythe regulations(25).

While all building services require proper O&Mdocumentation, the complex nature of a BMS, which mayhave control strategies and other information stored incomputer memories, makes it essential to provide writtendetails of what function the BMS performs and how itachieves them. Advice on the preparation of O&M manualsis given in Armstrong(26). The documentation shouldinclude:

— written description of plant operation

— control strategy or logic diagrams recording thefinal version of installed software

— details of system application software configuration

— points list, including hard and soft points

— copies of certificate of compliance with relevantstandards

— data sheets for all control components andequipment

— instructions for switching on, operation andswitching off, isolation, fault finding and fordealing with emergency conditions

— instructions for any necessary precautionarymeasures

— instructions for servicing

— instructions in the use of software routines forcreating procedures, graphics reports etc., whereapplicable

— description of user adjustable points

— provision for updates and modifications.

The file may be in two parts: operating manuals for day-to-day use and sets of drawings for use during alterations.Copies of manufacturers’ data may be incorporated, but arenot a substitute for proper instructions. Details of sparesand sources of supply should be included. In addition, thereshould be a complete set of record documents supplied athandover, containing records of all the commissioningvalues and the checklists completed during commissioningand witnessing.

8.4.5.3 Training

The successful operation of a BMS depends on the skill andknowledge of the operator. The installation of a modernBMS represents a substantial investment and properoperator training is necessary to realise the full value of thisinvestment. The client has to decide who will operate theBMS. In many cases this will be staff, but the contracting outof facilities management services is becoming morecommon. Training is often part of the contract and socontract completion is not possible until the training hasbeen carried out. This may result in financial pressure toperform the training too early, before the end user is readyor staff have been appointed. It is recommended thattraining costs should be determined and held as a PC sumoutside the main contract, to be paid when the training iscompleted.

It is recommended that:

— at least two BMS operators attend an ‘in-house’training course run by the controls specialist beforecompletion of the BMS

— the BMS operators are invited to attend thecommissioning of the BMS

— the BMS operators should be present during thehandover period to learn about the system

— all new operators who may subsequently beappointed should also receive proper training.

8.4.6 Costing

The importance of commissioning to the satisfactoryoperation of the plant and control system has beenemphasised. It therefore requires proper provision of timeand cost to enable the process to be carried outsatisfactorily; allowing commissioning to absorb time andcost overruns is not satisfactory. Effective commissioninghas long lasting benefits, which need to be given full valuewhen making out a business case for expenditure;inadequate commissioning is sure to prove expensive overthe long run. The benefits of effective commissioning maybe summarised:

— increased building value

8-12 Building control systems

Page 170: Building control system, aplication guide   cibse guide

— improved occupant satisfaction and productivity

— reduced energy costs

— reduced maintenance requirements and longerplant life

— sound database for future refurbishment.

When costing proposals, all activities should be taken intoaccount, including provision for post-occupancy evaluationand fine tuning.

8.5 Operation

8.5.1 Fine tuning

After handover, the building operates under control of theappropriate staff, whether in-house staff, a contractfacilities management team or other form of organisation.It is rare that a new building works perfectly withoutfurther attention; it would be unreasonable to expect this,since the manner of building use by the occupants cannotalways be predicted and it will not have been possibleduring commissioning to experience the full range ofweather conditions. It is therefore to be expected that theBMS will require attention and tuning over a period of atleast a year after occupation. Proper provision should bemade for this, in terms of effort and cost. This shouldinclude an allowance for a return visit at least twice duringthe first year. In most cases, it will be of great benefit for allconcerned if the client installs a dedicated telephone line toallow remote monitoring of the BMS by the controlsspecialist. As well as assisting in fault diagnosis, the linkcan be used for training and other purposes.

8.5.2 Maintenance

While the microelectronics components in a BMS are ingeneral very reliable, a controls systems contains movingparts which are subject to wear and devices such as sensorswhich may be subject to physical damage or degradationfrom their environment. Maintenance is therefore essentialto ensure that a BMS stays in efficient working orderthroughout its life. Maintenance includes updating andmaintenance of software and documentation.

Maintenance may be obtained from different types ofprovider:

— In-house staff. Only large organisations with asophisticated building are likely to carry thenecessary technical staff to provide BMSmaintenance. In-house staff may be used to providethe first line of investigation into failures and carryout simple repairs, calling on specialist contractorsfor more complex work.

— Maintenance divisions of M&E companies. Many M&Econtractors operate specialist maintenancedivisions that will undertake maintenance of BMSsystems, whether installed by the parent companyor not. The maintenance companies are generallyautonomous companies, so it should not beassumed that there is a continuity of responsibilitybetween installer and maintenance company.

— Systems integrators. Many of the larger systemsintegrators provide comprehensive maintenanceand 24 hour bureau services. This may includeremote monitoring of plant condition.

— Specialised maintenance companies. There is a largenumber of small specialised maintenancecompanies, often specialising in a particular rangeof equipment. Although not having the resources ofthe large M&E companies, they can supply a servicetailored to the customer’s needs.

— Consultants. An increasing number of engineeringconsultants offer maintenance services, includingtraining or documentation production, and themanagement of maintenance on behalf of thebuilding operator.

— Controls manufacturers. Several major manufacturersoffer maintenance contracts of systems using theirequipment.

Whichever method is chosen, it is important that themaintenance is specified carefully(9). As a minimum, amaintenance specification should include requirementsfor:

— software upgrades

— data back-up and archiving

— checking of sensors and actuators

— arrangements for emergency callout

— performance standard for the building controlsystem, including delivered conditions andoperating efficiency.

As with commissioning, it is advantageous if the needs ofmaintenance are considered at an early stage; the severalapproaches to the organisation of maintenance are reviewedin Smith(27) and CIBSE TM17(28). Plant and equipmentshould be designed and installed in a manner to assistfuture maintenance; recommendations are given byMoD(22) and Parsloe(29). Advice on specification andcontracts is to be found in Smith(30) and StandardMaintenance Specification(31). Experience shows that the bestresults are obtained in situations where the BMS is ‘owned’by someone in the building operator’s organisation. Thereshould be an individual who feels responsible for the properoperation of the BMS and will take whatever initiative isnecessary to ensure its successful working.

8.5.3 Recommissioning

Existing buildings may operate below optimumperformance and recommissioning the building servicesmay represent the most effective way to bring operation upto the required standard. Recommissioning can often bejustified by:

— evidence of occupant dissatisfaction

— high operating costs or energy consumption

— high maintenance costs

— a change in building use

— major plant overhaul or replacement

— repeated system failures.

Management issues 8-13

Page 171: Building control system, aplication guide   cibse guide

8.6 Occupant surveysThe experience of the building occupants plays animportant part in the evaluation of the performance of abuilding control system. Building users consistently placegood environmental control at the top of the list ofdesirable features in a workplace. A well-controlledenvironment not only produces comfort, but contributes toproductivity and health as well as influencing theoccupants’ general opinion of other facilities. The series ofPROBE post-occupancy studies of buildings hasemphasised the importance of a well-controlledenvironment and emphasised that the occupantsthemselves are part of the system. Disregarding theresponses of the users will itself create problems, even if themechanical system is performing adequately. Thepublished summary of the first PROBE series produced aset of key design lessons about the requirements of theoccupant(32).

— Rapid response to changes. There should be a rapidresponse to the need for a change, whether this isprovided automatically by the BMS or bymanagement intervention.

— Offer choices and trade-offs. If ideal conditions cannotbe provided, the occupants should be offered achoice of trade-offs, e.g. in hot conditions, openablewindows allow a choice between being hot orsuffering from external noise.

— Good feedback mechanisms. These are essential sothat action can be taken quickly. Complaints orproblems need to receive rapid attention. The trendtowards contracting out services such as facilitiesmanagement can work against rapid response.

— Management resources. These are vital; complicatedbuildings can outstrip the limited capabilities ofthe occupiers to run them effectively.

— Ownership of some problems by the occupants. This is sothat they may participate in the solution withoutsuffering a sense of alienation.

— Perception of good control. This is important tooccupants, who require simple effective controls orelse rapid and effective management response torequests.

The above design lessons emphasise that the users mustperceive that they are part of the control system. Howevergood the control system may be in technical terms, if themanner in which it is operated ignores the feelings andresponses of the building occupants, then it will not befound satisfactory. The application of the above lessons willresult in working methods whereby early indications ofunsatisfactory operation of the building control systemcome to the attention of the building operator. Otherindications may come from the energy monitoring andtargeting procedures. In any case, it may be advantageous toinitiate a regular review of system performance, say oneyear after installation and at longer intervals thereafter.When it is desired to initiate a proactive review of theoperation of the building services operation, BRECSUpropose a three-level strategy to review buildingperformance, which can be initiated at any stage of thebuilding’s life.

— Level 1. Review performance, using a help desk orfocus groups to obtain the views of occupants.

Assess energy performance against targets orbenchmarks and ensure that health and safetyrequirements are met. If there is cause for concern,move on to Level 2.

— Level 2. Use a more formal procedure to identify anyproblems. Use occupation satisfaction surveys andenergy surveys. If performance problems areestablished, go to Level 3.

— Level 3. Employ plant-focused troubleshootingprocedures to find the cause of troubles. Systemscan then be fine tuned, recommissioned orrefurbished as required.

The relation between building controls and complaints ofpoor indoor environmental quality is set out by Fletcher(33).Reports of poor conditions are classified into 16 divisionsand an action checklist for each is given. The suggestedactions only apply if the problem is controls related or canbe mitigated by modifying the control set-up.

A detailed occupant satisfaction survey demands a formalapproach. The use of a standardised questionnaire willprovide a satisfaction score for the building that will enableits performance to be compared with national benchmarks,as well as identifying areas of control and management thatrequire attention. The PROBE standard questionnaire iscopyright and may be used under licence; this ensures thatit is applied according to standard procedures. Formaloccupant surveys should be undertaken with caution, bothto ensure results that can be compared with benchmarksand to avoid possible staff-related problems.

— The questionnaire should be short and easy toanswer in at most 10 minutes.

— In large buildings, a representative sample ofoccupants should be surveyed, aiming at as high aresponse rate as possible.

— The provisions of the Data Protection Act must beborne in mind.

— The staff association or other relevant body shouldbe kept fully informed.

— Make the goal of the survey clear to respondents; donot raise unrealistic expectations of improvementin conditions.

— Resolve any questions of confidentiality in advance.

— If the survey is to be conducted by externalresearchers, resolve questions of ownership of dataand possible publication in advance.

One type of questionnaire provides a visual fingerprint ofoccupants’ response to their working environment as wellas an overall building score. Respondents are asked to rateup to 24 factors on a double Likert scale. This asks for tworesponses for each factor. One is a seven-point scalerunning from ‘like’ to ‘dislike’; the other is a seven-pointscale describing how important that factor is. The factorscover physical aspects of the indoor environment such astemperature and humidity, but also include someorganisational factors. The responses from all respondentsmay be combined to give an overall liking score (OLS) forthe building. The use of the importance scale means thatappropriate weighting is given to each factor whencomputing the OLS. The overall liking score is expressed asa percentage, running from +100% to –100%. The

8-14 Building control systems

Page 172: Building control system, aplication guide   cibse guide

questionnaire has been evaluated in several surveys andhas been found to differentiate well between buildings(34).In practice, OLS scores range from about +20% for a well-liked building, down to –20% or worse for one disliked byits occupants. Total scores for the individual factors maybe displayed as a bar chart, termed the buildingfingerprint; an example is shown in Figure 8.4. This givesan immediate picture of the good and bad features of thebuilding and can be a useful tool in ascertaining whichaspects of a building require attention during a post-occupancy survey.

8.7 Cost issues

8.7.1 Cost benefit analysis

A comprehensive BMS represents a substantial investment,which is expected to bring a variety of benefits to the client.In order to make a rational investment decision, it isnecessary to have some method of comparison betweenalternative systems. Cost benefit methods of analysis havebeen developed by economists, which aim to express allcosts and benefits associated with a plan of action in acommon unit, i.e. money, and to make rationalcomparisons between plans which may have different sizeand time scales. One important principle is that the benefitsand costs must be expressed from a single point of view, e.g.better indoor air quality may be beneficial to the officeworker in terms of health and comfort and it may produce abenefit for the office tenant in terms of increasedproductivity. However, neither is a direct benefit for thebuilding owner, who may be able to achieve the benefit as

an increased rent. Cost benefit analysis is moststraightforward where the building owner, operator andemployer are the same. Where they are not, it must be bornein mind that the organisation receiving the benefit, e.g. of areduction in energy consumption, may not be theorganisation that paid for the BMS.

The IEA Annex 16 task, Cost Benefit Assessment Methods forBEMS(35) set out to produce a coherent analysis procedurewhich could be used to calculate savings from BMS andassist in making investment decisions. The reportconcluded that no single model would become accepted;the more common methods of analysis are given in thereport and summarised below. More important than themethod chosen is the ability to provide good quality inputdata, particularly where it is necessary to compare differenttypes of costs and savings, e.g. investment cost versusproductivity gain. It is recommended that a detailed listingis prepared of the costs incurred and the benefits expectedfrom the BMS. Table 8.8 summarises the suggestedheadings, which may be expanded into considerably moredetail.

In a modern office building, staffing costs are much greaterthan energy costs. The benefits of improved staff utilisationmay therefore be as much or more than the savings inenergy consumption. The IEA report quotes estimateswhich state that the benefits of an intelligent building interms of energy savings, increased productivity andreduction in building management costs are roughly equal;put another way, this means that the overall benefits of agood BMS may be three times the direct saving in energyconsumption. Another rule-of-thumb quoted is that anoverall productivity improvement of 2.5% would be enoughto pay for the entire BMS.

Management issues 8-15

Figure 8.4 Fingerprint of a deep plan, modern, naturally ventilated building. (OLS –15%; C/ = control of)

Page 173: Building control system, aplication guide   cibse guide

8.7.2 Life cycle costing

Life cycle costing is an emerging technique that seeks toextend the cost benefit analysis over the whole life of theproject, including final disposal. It has been defined as amethod that collects together all tax allowances, capital andrevenue costs for each system from original installation toabandonment. As with all such analyses, the quality of thedata is of vital importance. For life cycle costing to takeplace, the tender invitation should include separate pricebreakdowns as follows:

— installation cost

— annual maintenance cost of components

— cost and rate of increase of maintenance contracts

— cost of replacement items

— economic life of system and components

— minimum guaranteed period that spares will beavailable

— system training costs.

The relation between BMS lifetime and the lifetime ofrelated systems may be important. IT systems in generalhave a shorter life than BMS. If the BMS is to be closelyintegrated with the IT system, there may be implications forthe BMS if the IT system is renewed. Similarly, replacementcycles for the BMS should be related to the likely lifetime ofthe HVAC system.

8.7.3 Assessment methods

There are several assessment methods available which areto be found in standard economic texts, e.g. Thuesen etal.(36) and ETSU(37). It is emphasised again that good qualitydata is important, and that the costs and benefits should beassessed from the same standpoint. The main methods aresummarised as follows.

8.7.3.1 Net cash flow

Cash flow analysis is the basis for all cost benefit analyses.For a number of periods, typically yearly, the costs andbenefits of the investment opportunity are written down.The total period may extend up to the expected life of theinvestment, including disposal costs for full life cyclecosting. Thus the cash flow table shows both the total costsand benefits and when they are expected to be achieved.

8.7.3.2 Payback method

The payback period is commonly defined as the length oftime to recover the initial investment from the benefitsproduced by that investment; no account is taken ofinterest rates. Using the cash flow table described above, thenet cash flow is accumulated. The year in which the totalbenefits equal the total cost is the simple payback period,i.e. it is the time after which the investment cost is repaid.There are several variants on the payback period and it isimportant to state which one is used when makingcomparisons. For instance, the payback period calculatedby dividing the initial cost by the annual benefits does nottake into account the initial period, e.g. construction phase,during which no benefits are received.

In general the payback period fails to consider the timevalue of money, i.e. the value of money to be received in thefuture is less than that of money received now, nor does itconsider what happens after the payback period, e.g. themagnitude and timing of the cash flows. The paybackmethod tends to favour shorter lived investments.Acceptable values of payback period vary with the type oforganisation. Typically, payback period of three years orless are required by industry and up to 10 years byGovernment projects.

8.7.3.3 Discount techniques

There are several techniques based on discounted cash flow(DCF), all of which use a discount rate in the calculations,reflecting the time value of money(38,39). The present worthmethod, also known as net present value, is typical. Allfuture amounts in the cash flow table are discounted back tothe start of the project. The discount rate may be thought ofas the return available on money from other investments;10% is typically used. With this method of analysis, it ispossible that an investment which shows a positive net cashflow after a few years may show a negative present worth;the implication is that it would be more profitable to investthe money elsewhere. The techniques can be used for lifecycle costing; the effect of the discount rate is to reduce thepresent value of costs and benefits which will occur morethan a few years in the future.

8.8 SummaryThe procurement process chosen by the client stronglyinfluences the way in which the control system is designedand installed. The traditional procurement processseparates design from construction. This provides for clearcontractual responsibilities, but means that the controlsspecialist may be appointed late in the process and havelittle opportunity to contribute to the design. Design andbuild brings design and construction together in the same

8-16 Building control systems

Table 8.8 Listing of costs and benefits of a BMS

First cost Specification and design

Hardware

Software

Installation, commissioning

Training

On-going costs Maintenance

Communication costs

Staffing

Benefits Reduction in avoidable waste

Savings in staffing costs

Better maintenance and fault detection

Improved productivity

Tax implications

Life cycle factors Replacement cost

Scrap value

System economic life

Life of related systems

Page 174: Building control system, aplication guide   cibse guide

organisation. Partnering methods aim to build a stablerelationship between those involved in the procurementprocess, enabling all parties involved to make a fullcontribution.

The initial project brief produced by the client is of greatimportance and the type of control system and theorganisation of commissioning should be considered fromthe start. The manual includes a pre-specification check listto assist in clarifying ideas about the required buildingmanagement system.

It is helpful if the specification follows a standard form,such as the National Engineering Specification. Once theHVAC and control system has been installed, effectivecommissioning is crucial. In modern complex buildings,the controls system interacts with other systems and care isnecessary in planning the commissioning process andassigning areas of responsibility. The original specificationshould be designed both to reduce the amount ofcommissioning required and to make that commissioningeasier. The design should be reviewed at an early stage by acommissioning specialist.

There are statutory requirements for the preparation ofproper documentation, which is necessary for systemoperation, maintenance and refurbishment.

After the building is occupied, it must be run to provide asatisfactory working environment for its occupants.Prompt response to any user problems is important inproducing satisfaction. Where there appear to be problemsa survey of the building users can be helpful; standardquestionnaires can be used to provide comparison withother buildings.

Decisions on how much to spend on control systems shouldinvolve the concept of life cycle costing, taking futurerunning costs, maintenance expenditure and energy savinginto account. Standard discounted cash flow techniques canbe used to evaluate proposals.

References

1 Thinking about building (Business Round Table) (1995)

2 Turner A E Building procurement 2nd ed (London: MacMillan)(1997)

3 Latham M Constructing the team. Final report of theGovernment/industry review of procurement and contractualarrangements in the UK construction industry (London: StationeryOffice) (1994)

4 Hawkins G Improving M&E site productivity TN 14/97(Bracknell: Building Services Research and InformationAssociation) (1997)

5 Egan J Rethinking construction (London: Department ofEnvironment, Transport and Regions) (1998)

6 RCF Trusting the team — the best practice guide to partnering inconstruction (University of Reading: Centre for Strategic Studiesin Construction) (1995)

7 Anderson D Partnering: all together now Journal of the CharteredInstitution of Building Services 17(11) 31–34 (1995)

8 Parsloe CJ Allocation of design responsibility TN21/97 (Bracknell:Building Services Research and Information Association) (1997)

9 Pennycook K and Hamilton G Specifying building managementsystems BSRIA TN 6/98 (Bracknell: Building Services Researchand Information Association) (1998)

10 Teekeram A J H and Grey R W Specifications and standards forBEMS (St Albans: Oscar Faber) (1991)

11 NES National engineering specification (London: BuildingServices Research and Information Association) (1997)

12 BSRIA Guide to BEMS Centre Standard Specification AH1/90 Vol1 (Bracknell: Building Services Research and InformationAssociation) (1990)

13 PSA Building management systems, Standard Specification (M&E)No 15 (London: Property Services Agency) (1986)

14 Environmental Design CIBSE Guide A (London: CharteredInstitution of Building Services Engineers) (1999)

15 Thermal environmental conditions for human occupancyANSI/ASHRAE Standard 55 (Atlanta, GA: American Society ofHeating, Refrigeration and Air Conditioning Engineers) (1992)

16 Nicol F, Humphreys M A, Sykes O and Roaf S Indoor airtemperature standards for the 21st century (London: E & F N Spon)(1995)

17 Parsloe C J and Spencer A W Design and commissioning ofpipework systems TN 20/95 (Bracknell: Building ServicesResearch and Information Association) (1995)

18 Sneath C Code of practice for the selection of subcontractors (London:Thomas Telford Publishing) (1997)

19 Wild L J Commissioning HVAC systems. Division of responsibilitiesAG 3/89 (Bracknell: Building Services Research andInformation Association) (1989)

20 Pike P G and Pennycook K Commissioning BEMS — a code ofpractice AH 2/92 (Bracknell: Building Services Research andInformation Association) (1992)

21 Chartered Institution of Building Code of practice for projectmanagement for construction and development (Chase ProductionServices) (1992)

22 MoD Space requirements for plant access, operation and maintenance.Defence Works Functional Standard: Design andMaintenenance Guide 08 (London: Stationery Office) (1996)

23 The Construction (Design and Management) Regulations 1994(London: Stationery Office) (1994)

24 Managing construction for health and safety. Construction (Designand Management) Regulations 1994 Approved Code of Practice(L54) (Sudbury, Suffolk: HSE Books) (1995)

25 Nanayakkara R Standard specification for the CDM RegulationsHealth and Safety File AG 9/97 (1997)

26 Armstrong J H Operation and maintenance manuals for buildingservices installations. Application Guide 1/87.1 2nd ed (Bracknell:Building Services Research and Information Association) (1990)

27 Smith M H Decisions in maintenance TN 14/92 (Bracknell:Building Services Research and Information Association) (1992)

28 Maintenance management for building services TM 17 (London:Chartered Institution of Building Services Engineers) (1994)

29 Parsloe C J Design for maintainability AG 11/92 (Bracknell:Building Services Research and Information Association) (1992)

30 Smith M H Maintenance contracts for building engineering services.A guide to management and documentation AG 4/89.1 (Bracknell:Building Services Research and Information Association) (1991)

31 Standard maintenance specification for mechanical services inbuildings. Volume 3: Control, energy and BMS (London: Heatingand Ventilating Contractors Association) (1992)

32 Leaman A PROBE 10 occupancy survey analysis BuildingServices Journal 19(5) 37–41 (1997)

Management issues 8-17

Page 175: Building control system, aplication guide   cibse guide

33 Fletcher J Building control and indoor environmental quality — abest practice guide (Bracknell: Building Services Research andInformation Association) (1998)

34 Leventis M and Levermore G J Occupant feedback — importantfactors for occupants in office design Chartered Institution ofBuilding Services Engineers/ASHRAE Joint National ConferencePart Two Harrogate UK 1996 II. 192–200 (London. CharteredInstitution of Building Services Engineers) (1996)

35 Hyvärinen J Cost benefit assessment methods for BEMS (St Albans:Oscar Faber) (1992)

36 Thuesen H G, Fabrycky W J and Thuesen G J Engineeringeconomy 5th ed (New Jersey: Prentice Hall) (1977)

37 ETSU Economic evaluation of energy efficiency projects (Harwell:ETSU) (1994)

38 Wright M G Using discounted cash flow in investment appraisal 3rded McGraw-Hill) (1990)

39 Dixon R Investment appraisal. A guide for managers Revised ed(Kogan Page) (1994)

8-18 Building control systems

Page 176: Building control system, aplication guide   cibse guide

Relevant references are listed as they occur in the text. Thefollowing publications contain a great deal of usefulinformation.

A1.1 Control theoryLevermore G J Building energy management systems 2nd ed (London: E & FN Spon) (2000)

Underwood C P HVAC control systems: modelling, analysis and design(Andover: E & F N Spon) (1998)

A1.2 Control strategiesLevenhagen J I HVAC controls system design diagrams (New York: McGrawHill) (1998)

Martin A J and Banyard C P Library of system control strategies. ApplicationsGuide AG 7/98. (Bracknell: Building Services Research and InformationAssociation) (1998)

MSR Planungshandbuch (CD-ROM) (Karlsruhe: Siemens AG) (1997)

A1.3 GeneralEngineering manual of automatic control SI edition (Minneapolis: HoneywellInc.) (1995)

A1.4 Control valvesPetitjean R Total hydronic balancing (Ljung, Sweden: Tour and AnderssonAB) (1997)

A1-1

Appendix A1: Bibliography

Page 177: Building control system, aplication guide   cibse guide

This Page Intentionally Left Blank

Page 178: Building control system, aplication guide   cibse guide

A2.1 The PID control loopThe basic feedback controller is illustrated in Figure A2.1.The error signal xe is processed by a controller whichproduces an output signal Y, which in turn drives thecontrolled device, e.g. actuator and fan coil, resulting in achange in the controlled variable x. In 3.3.3.1 a descriptionwas given of how the components of the controlled device,e.g. valve and heat emitter, may be matched to linearise theheat output, resulting in an approximately linear relationbetween the controller output Y and the heat output to theconditioned space. However, even if the change in theoutput is roughly linear with controller output, the gain ofthe system can change with operating conditions.

When a controlled system running in a steady state isdisturbed by a change in load, a change in set point or someother disturbance, the system will react. If the system isoperating in a stable manner, it will sooner or later settledown in a new stable state. If the system is unstable, it willgo into indefinite oscillations of increasing amplitude; inpractice the size of the oscillation will be limited by thecomponents of the system and the system will continueoscillating or hunting.

The high thermal inertia of most buildings, coupled withthe slow response of traditional heating systems, hasusually meant that reasonably stable temperatureconditions can be achieved with simple control systems. Insome circumstances, it is possible for satisfactorily steadyconditions to be achieved in the controlled space even whenthe HVAC system itself is hunting in an unstable manner.This is bad practice, leading to excess wear of components.The trend towards lighter buildings and the use of airhandling systems has increased the responsiveness ofsystems and so increased the possibility of unstableoperation.

The general equation for the output of a three-termcontroller is

(A2.1)

where:

Y output from controller (ND, 0–1)

Y0 constant controller output (bias) (ND)

xe error i.e. difference between set point and measured value (K)

Kp proportional gain constant= (1/proportional band) (1/K)

Ki integral gain constant (1/(Ks))

Kd derivative gain constant (s/K).

The equation has been written in terms of the controlleroutput as a non-dimensional (ND) quantity scaled from 0 to1. In practice, the output would be a standard voltage orcurrent output, or else a digital value for DDC. Thecontrolled variable is illustrated as a temperature, but couldbe any other controlled variable.

The equation may be rewritten

(A2.2)

where:

Ti = Kp/Ki integral action time (s)

Td = Kd/Kp derivative action time (s)

Most controllers are set up this way, with independentadjustments for Ti and Td, which are usually calibrated inminutes.

The stability of a simple system may be analysed by settingup the differential equations which describe its dynamicbehaviour(1). Standard analysis methods, based on Laplacetransforms, are then used to check for stable operation.However, most systems are too complex for this analysis tobe practical and empirical rules have been derived to assistin setting up a three-term controller to achieve the desiredcompromise between stability and speed of response. Forcompleteness, the general case of a three-term controller isgiven. However, in most HVAC applications the derivativeterm is not required and is disabled by setting thederivative time to zero.

A2.2 Digital controlThe above equations are written in terms of continuousanalogue quantities. Digital control systems, whichconstitute the majority of modern systems, operate with

Y Y K x T x t Tx

t

T

= + + +⎛

⎝⎜

⎠⎟∫0 p e i e d

e

0

(1/ ) dd

d

Y Y K x Kx

t

T

= + + +∫0 p e i e de

0K d

d

dx t

A2-1

Appendix A2: Tuning rules

(Zone temperature)

Setpoint (Actuator

anddamper)

(Zonecontrol)

Figure A2.1 Feedback control loop

Page 179: Building control system, aplication guide   cibse guide

discrete sample values of the measured quantities. Thegeneral equation for a three-term PID controller becomes

(A2.3)

which is similar to Equation A2.2, but with the followingchanges in symbols:

Yk output from controller at time step k(ND, 0–1)

Y0 controller offset (ND)

xk deviation from set point at time step k (K)

Δt sampling interval (s).

The discrete sampling of the controlled variable producessome effects not found with analogue controllers. Noise orinterference can cause sudden changes in the controlleroutput. Noise affecting a single sampled value will producea sudden change in controller output due to thephenomenon known as derivative kick; this is caused bythe change in value of the derivative term (xk+1 – xk)/Δt. Achange in set point will also produce a derivative kick,together with the associated proportional kick; the kicklasts for only one time step but can cause unwantedmovement in the controlled device. While in general ashort sampling time increases the accuracy of control, itincreases the effect of derivative kick.

Software techniques may be used to reduce the effect ofderivative kick. A moving average of the last four sensorvalues may be used to reduce the effects of noise; logicalfilters can also be beneficial. It is possible to set an errordeadband around the set point. Control action is only takenwhen the controlled variable moves outside the deadband;this prevents operation of the controlled device due tominor noise signals in a system that is controllingsatisfactorily near the set point. Another technique is toapply the derivative calculation to the change in value ofthe controlled variable, rather than the change in deviationof the controlled variable from the set point as shownabove; this avoids any derivative kick when the set pointchanges. In practice, derivative control is not implementedin most BMS controllers, since the benefits are not sufficientto justify the extra effort of setting up the controller and therisk of introducing instabilities.

Equation A2.3 is termed the position algorithm. Theposition of the controlled device is related directly to theoutput signal Y from the controller; a constant positionoffset Y0 can be used if required. There may be situationswhere the error x is large for an extended period of time;this can easily arise during a long warm-up period. Theintegral term may then become very large. This will causethe controller to overshoot the set point and propercontrol is not established until the integral term hasbecome dissipated. This phenomenon is known as integralwind-up and may be prevented in software by limiting theintegral term to a maximum value, typically that whichwill produce between 50 and 100% output from thecontroller.

The problem of wind-up may be avoided by using theincremental control algorithm. This is based on the changebetween successive values of the controlled variable.

(A2.4)

Equation A2.4 has been written without a derivative term,which is not normally used in incremental control. Thechange in output ΔYk+1 is used to reposition the controlleddevice, e.g. by holding on an actuator motor for a timeinterval proportional to ΔYk+1 or by controlling a steppermotor. There is no positional feedback from the actuator.The algorithm has the advantage of avoiding integral wind-up.

A2.3 TuningThe aim of tuning a controller is to restore controlfollowing a disturbance as quickly as possible and toachieve stable control with a small or zero offset from theset point. These criteria interact; increasing the speed ofresponse risks introducing instability. The controllerparameters must be set to values appropriate to the system.A full analysis of the dynamic response of a controlledsystem is complex(2) and not often attempted in practice.Several methods have been developed to estimate suitablevalues of the control constants.

The ultimate cycling method, also known as the ultimatefrequency method, can be carried out on the intact controlsystem. To use this method, the integral and derivativeactions of the controller to be tuned are first disabled. Theproportional gain setting is then increased (i.e. the band isreduced) in small steps from a low value; at each value of theband, the system is given a small disturbance by adjustingthe set point. At low values of the proportional gain thecontrolled variable will settle down to a stable value whenthe set point is changed; as the gain is increased, a value willbe reached when the system starts hunting. The oscillationsshould be steady, with neither increasing nor decreasingamplitude. The value of the proportional gain Kp

* at whichthis happens is noted, together with the period of oscillationT*. The settings of the controller may then be obtainedusing the Ziegler–Nichols method set out in Table A2.1.This method produces a response to a step change in the setpoint similar to that shown in Figure A2.2. This is alsoknown as the quarter wave method, because the amplitudeof the first overshooting wave is four times that of thesecond.

Reaction curve methods depend on measuring the openloop response. This requires the controller to be taken outof the control loop and the response of the controlledvariable to an artificial step change ΔY in controller outputto be measured. Most systems will respond with acombination of time delay and first-order response. FigureA2.3 shows how the time delay Tt , time constant Tg andfinal change in controlled variable x∞ may be estimated

Δ ΔY Y Y K x x

t

Txk k k k k k+ + += − = − +

⎧⎨⎩

⎫⎬⎭

1 1 p 1i

Y Y K xT

x t Tx x

tk k jk k

j

k

+ ++

=

= + + + −⎧⎨⎪

⎩⎪

⎫⎬⎪

⎭⎪∑1 0 p 1

id

1

1

1 ΔΔ

A2-2 Building control systems

Table A2.1 Ultimate frequency method controller settingsto produce a quarter-wave response (Ziegler and Nichols).Kp

* is the gain which just produces hunting with period T*

Controller mode Kp Ti Td

P 0.5Kp*

PI 0.45Kp* 0.8T*

PID 0.6Kp* 0.5T* 0.125T*

Page 180: Building control system, aplication guide   cibse guide

from the reaction curve. These values may then be used tocalculate the optimum controller settings. Table A2.2shows values calculated according to a method developedby Cohen and Coon(3) quoted by Kreider and Rabl(4), whichproduces a quarter-wave response.

The quarter-wave response produced by the Ziegler–Nicholsor Cohen–Coon methods may be considered too oscillatoryand a more damped response is often more appropriate inpractice. Control settings to produce a critically dampedresponse may be estimated from the open loop response by amethod due to Bekker(5) and are set out in Table A2.2. It waspointed out at the beginning of the section that the gain of acontrolled system is likely to vary with operating conditions.Control settings should be established with the system in ahigh gain condition. Setting the controller in conditions oflow gain could result in system instability when theconditions move to high gain.

Digital controllers add a fourth setting, the computationtime step, which is the interval between digital controllerupdates. The sensitivity of the integral term increases and

the sensitivity of the derivative term decreases as thesampling time interval increases. A long sampling intervalmeans that the controller does not receive information at asufficient rate to operate properly and may result inunstable control; on the other hand, a very short samplinginterval may waste execution time resources.

A2.4 Step-by-step tuningprocedure

The procedure given below, to be followed for tuning acontroller by either of the two methods analysed above, hasbeen adapted from a controller manual. Settings have beenquantified in terms of the proportional band, rather thangain, since this corresponds to the settings on mostcontrollers. This description should be read in conjunctionwith the advice given in section 2. An alternative simplifiedprocedure is given by Borresen(6).

A2.4.1 Closed loop ultimate cycling

This tuning method is carried out on the intact controlloop.

Appendix A2: Tuning rules A2-3

Table A2.2 Controller settings: open loop reaction curve method. Themeasured variables are defined in Figure A2.3

Controller mode Kp Ti Td

Quarter-wave response(4)

P AB(1 + R/3)

PI AB(1.1 + R/12) Tt

PID AB(1.33 + R/4) Tt Tt

Critically damped response(5)

PI 0.37AB Tg

A = ΔY/x∞ , B = Tg/Tt, R = 1/B.

411 + 2R

32 + 6R13 + 8R

30 + 3R9 + 20R

-

Figure A2.2 Response to a change in set point, showing underdamped and critically damped responses

Figure A2.3 Reaction curve. Curve shows open loop response of a systemto a step change in controller output ΔY applied at time t = 0. The values oftime delay Tt, time constant Tg and final change in output x∞ are estimatedas shown

Page 181: Building control system, aplication guide   cibse guide

(1) Connect a chart recorder to measure the controlledvariable.

(2) Set the controller to give proportional action only,by the selector switch if fitted, or by setting theintegral time to maximum and the derivative timeto zero.

(3) Start with a wide proportional band, i.e. low gainsetting.

(4) Reduce the proportional band in steps. After eachreduction, make a small adjustment to the set pointand observe the response. To start with the loopwill stabilise with the controlled variable at a steadyvalue.

(5) Note the proportional band setting Xp* when the

response to a set point change is for the loop to gointo oscillation with a steady amplitude. Measurethe period of the oscillation T*.

(6) Calculate the control parameters from Table A2.3.

(7) Set the parameters on the controller and check howthe control loop behaves in response to a change inset point. Adjust the parameters if necessary.

A2.4.2 Open loop response(1) Connect a chart recorder to measure the controlled

variable.

(2) Open the control loop by disconnecting thecontroller from the controlled device.

(3) Make a sudden change ΔY in the position of thecontrolled device, either by hand or by applying a

constant voltage to the device input to simulate thecontroller output. ΔY is measured as a fraction offull output.

(4) Record the change in controlled variable with time,which will have the form shown in Figure A2.3.Calculate the time lag Tt, the time constant Tg andthe final change in controlled variable .

(5) Calculate the parameter settings from Table A2.4.

(6) Reconnect the controller and observe the reactionof the control loop to changes in set point. Adjustparameters if necessary.

References1 Underwood C P HVAC control systems: modelling, analysis and

design (Andover: E & F N Spon) (1998)

2 Levermore G J Building energy management systems 1st ed(London: E & F N Spon) (1992)

3 Cohen G H and Coon G A Theoretical considerations forretarded control Trans ASME 75 827–834 (1953)

4 Kreider J F and Rabl A Heating and cooling of buildings. Design forefficiency International ed (New York: McGraw Hill) (1994)

5 Bekker J, Meckl P and Hittle D C A tuning method for firstorder processes with PI controllers ASHRAE Transactions 97(2)19–23 (1991)

6 Borresen B A Controllability — back to basics ASHRAETransactions 96(2) 817–819 (1990)

A2-4 Building control systems

Table A2.3 Control parameters, ultimate cycling method

Controller mode Xp Ti Td

P 2Xp*

PI 2.2Xp* 0.9T*

PID 1.7Xp* 0.75T* 0.15T*

Table 10.4 Control parameters, reaction curve method

Controller mode Xp Ti Td

P

PI 1.1 3.5Tt

PID 0.9 2.5Tt 0.5Tt

x∞ TtΔY Tg

x∞ TtΔY Tg

x∞ TtΔY Tg

Page 182: Building control system, aplication guide   cibse guide

Adaptive control A system in which automatic means system are used to adjust system parameters

to achieve optimum performance

ANSI American National Standards Insti-tute

ASHRAE American Society of Heating,Refrigeration and Air ConditioningEngineers

Authority The authority of a valve or damperdescribes the degree of control itexerts when installed in a circuit

BACnet The Building Automation andControl networking communicationprotocol: ANSI/ASHRAE Standard135-1995. Provides a means by whichbuilding automation devices fromvarious manufacturers can share dataand work together

Baud rate A measure of rate of transmission ofdata in bits per second

BMS Building management system. Abuilding-wide network which allowscommunication with and control ofitems of HVAC plant. May also includeother systems such as lighting

Boost period The period when plant is operatedat full capacity, normally in thepreheat period before occupancy

Bridge A device that connects two or moreLAN segments at the physical anddata link layers. This device mayalso perform message filtering ifprogrammed to do so

Bus A common communications linkwhich carries messages betweendevices (nodes) which are connectedto the bus. The term field bus refers tolow level communications

Cascade control A control system consisting of aslave controller controlling asystem variable and a mastercontroller controlling the set pointof the slave. Also known as resetcontrol or master–submaster (US)

CDM Construction (Design and Manage-ment) Regulations, 1994

CEN European Committee for Standard-isation

Clean contact A contact not connected to anyvoltage source. Also called a voltagefree contact

Client The person who commissions thedesign and construction of a build-ing. May not be the end user

Compensator Normally implies weather compen-sation: a control device whosefunction is to vary flow temperatureas a function of external temperature

Control function A term used to describe type ofcontrol, e.g. compensation, night setback etc.

Control parameter A preset variable used in a controlalgorithm, e.g. width of the propor-tional band

Controlled variable The physical quantity being control-led by the system, e.g. air temperature

CPU Central processing unit

Deadband (1) The range of values of thecontrolled variable within which afloating controller produces nochange in control action, also calledneutral zone(2) The range of values of thecontrolled variable in which HVACplant is off, e.g. the interval betweenheating and cooling operation(3) The range between upper andlower switching values for a two-position controller. Better termedthe differential

Dead time The time required for a response inthe controlled variable to beobserved following a step change ininput to the controller

Dead zone See deadband, sense 2

Default value Stored value of a control parameteror other system variable to whichthe system reverts in the absence ofan instruction

Derivative action Time taken for the proportionaltime term to match the derivative term of

a PID controller when the errorchanges linearly with time

Derivative control A control method in which thecontrol output signal is proportionalto the rate of change of the control-led variable. Normally used in con-junction with other modes, e.g. PID

Desired value The desired value of the controlledvariable. Not necessarily the same asthe set point

A3-1

Appendix A3: Glossary

Page 183: Building control system, aplication guide   cibse guide

Deviation The difference between the set pointand the actual value of thecontrolled variable

Differential The difference between the higherand lower operating levels of anon/off controller

Direct digital control Implies that the control algorithms (DDC) are in the form of software.

Analogue inputs or outputs maycoexist with digital control

Distance–velocity lag The time taken for a heating orcooling medium to travel from itscontrolled source to the point ofdelivery

Distributed A system where data processing is intelligence carried out at local controllers or

outstations as well as at the centralstation

Distributed See universal controllerprocessing unit (DPU)

Double regulating A valve for the regulation of flow valve rate having an established valve

characteristic and provided withindicated positions of the valveopening and an adjustable stop suchthat the valve can be closed forisolation purposes and reopened tothe previously determined setposition

Duty cycling A control method which alternatesor cycles the sequence of plant use toensure standby plant is brought intouse. See also sequencer

EAC Energy account centre. An area ofenergy accountability, used inenergy monitoring

Economiser control Controlled mixing of recirculatedand outdoor air to give economy inheating or cooling costs. See freecooling

EMC Electromagnetic compatibility

Emulation Representation of a building systemby a computer simulation, in such away that a real BMS may be con-nected to the emulator as if it were areal system

Enthalpy control Controlled mixing of recirculatedand outside air based on theirenthalpies. Only used in associationwith humidity control of supply air

Events (BACnet) Changes in the state of an object,typically between normal, off-normaland fault condition. Events may bereported to other BACnet devices

Exhaust air Air which is discharged to outside

Extract air Air which is extracted from anoccupied zone

Feedback control Also called closed loop control,where a measure of the controlledvariable is fed back to the controller

Feedforward control See open loop control

Field processing unit See universal controller

Floating action A control mode where the outputsignal changes at a steady rate whenthe input signal falls outside theneutral zone

Flow coefficient Kv: The flow of water through a flow (valve) measurement device or double

regulating valve at a temperaturebetween 5 and 40°C and measured incubic metres per hour, that willinduce a pressure loss of 1 barKvs: The flow of water through aflow measurement device, of eitherfixed or variable orifice types, at atemperature between 5 and 40ºC andmeasured in cubic metres per hour,that will induce a differentialpressure, or signal, of 1 bar acrossthe pressure tapping points

FND Firmenneutrales Datenuebertrag-ungssystem (FND non-proprietarydata communications system).German DIN standard designed forBMS communication. Low uptakeoutside Germany

Free cooling (1) The use of outside air in aneconomiser control system to mini-mise or avoid the use of chillerplant(2) The provision of chilled waterfrom a cooling tower or dry cooler,without the use of chiller plant

Gateway A device that connects two or moredissimilar networks by messagetranslation and signal conditioning,permitting information exchangebetween them. A gateway would benecessary to translate LonWorksmessages to the BACnet format

Head end Another term for the supervisor of aBMS

Health and safety file Documentation prepared under theCDM regulations and handed to theclient on completion of construc-tion. Includes operating manuals ofbuilding services

HTHW High temperature hot water (used inheating systems; water temperatureover 120ºC)

Hunting A control state where the systemdoes not settle to a steady value butoscillates about the set point

HWS Hot water services, i.e. hot water totaps

Integral action time The time it takes for the integralterm of the control output equationto match the offset caused by theproportional term on a step changein error

Integral control A control mode where the outputsignal changes at a rate which is

A3-2 Building control systems

Page 184: Building control system, aplication guide   cibse guide

proportional to the deviation of theinput from the set point. Usuallyfound combined with proportionalcontrol

Internetwork Two or more networks connected byrouters

Interoperability The coordinated operation ofvarious pieces of equipment fromvarious manufacturers on the basisof standardised interfaces andservices

Jacketing software Software used in conjunction withadaptive controllers to prevent out-of-range operation

JCT Joint Contracts Tribunal

Let-by Residual flow through a valve whenclosed

Load error The difference between the set pointand the steady state value of thecontrolled variable of a proportionalor other controller

Local area network An arrangement that enables com- (LAN) puter or processor based equipment

to be linked so that they may com-municate with each other. Impliesboth hardware, e.g. cabling, andsoftware

LON Local operating network using theLonWorks protocol

LonTalk Protocol using a neuron chip forcommunications. It covers a varietyof physical media including twistedpair, power line carrier, and wirelesstransfers

LonWorks LonWorks is a registered trade markand is the generic term for bus systemsbased on the LonTalk protocol

LPHW Low pressure hot water (used inheating systems; water at approxi-mately atmospheric pressure)

LTHW Low temperature hot water (used inheating systems; water temperature70–100ºC)

M&T Monitoring and targeting. Used torefer to energy management inform-ation systems

Modem A device which converts data into aform suitable form transmissionover a telephone or other network

MS/TP Master–Slave/Token-Passing EIA-485 LAN developed for BACnet byASHRAE.

MTHW Medium temperature hot water(used in heating systems; watertemperature 100–120ºC)

NBS National Building Specification

NES National Engineering Specification

Neutral zone See deadband

Night set back The reduction in set point of aheating system during unoccupiedhours

NIST National Institute for Standards andTechnology, which is located inWashington DC. The NIST wassubstantially involved with thedevelopment of BACnet

Node A computer or digital deviceconnected to a network, with anaddress on that network

Object (BACnet) BACnet ‘Objects’ represent in astandardised way the informationrequired for a building automationcontrol system. The ‘analogue input’object, for example, represents sensorinputs such as temperature sensors

Open communication A term used for the exchange ofdata between various pieces ofequipment on the basis of open orstandardised protocols

Open loop control A control system where the control-ler does not receive information onthe results of its actions cf. feedbackcontrol

Open protocol A protocol available for use byanyone. It may be protected bycopyright and licence fees may becharged for its use. Changes in anopen protocol may be made at anytime by the original author

Open system Apart from open communications,an open system requires standard-ised formats, services and interfacesin order to transfer software simplyto other platforms and to achieve auniform operation philosophy.Open communication is also aprerequisite for an open system

Optimiser A control system employing anoptimum start algorithm

Optimum start A control system or algorithmwhich starts plant operation at thelatest time possible to achievedspecified conditions at the start ofthe occupancy period

Optimum stop A control system or algorithmwhich stops plant operation at theearliest possible time such thatinternal conditions will notdeteriorate beyond preset limits bythe end of the occupancy period

Outstation A device connected to sensors andactuators which can perform localcontrol and other functions. It canexchange information with thecentral station

PID Control incorporating proportional,integral and derivative actions

Planning supervisor Person appointed by the clientunder the CDM regulations tooversee safety of construction

Glossary A3-3

Page 185: Building control system, aplication guide   cibse guide

PLC Programmable logic controller

Point Generic name for a source of data(input) or control output in a controlsystem. May be analogue or digital.A virtual point is computed fromreal points

Points schedule The list of all points in a controlsystem

Pressure tapping Normally two pressure tapping point points are provided on a flow

measurement device either side of afixed or variable orifice to enable thepressure differential to be measured

Principal adviser Person or organisation that canimpartially advise a client on theneed to build and how to go aboutprocurement

Proportional band The range of input values corres-ponding to the full range of outputvariation of a proportional control-ler. May be expressed in actualunits (e.g. temperature) or as apercentage of the full input range ofthe controller

Proportional control Control action where the controloutput is proportional to the devia-tion of the deviation of the inputfrom the set point

Proportional gain Reciprocal of proportional band

PSDN Public switched data network. Adata communications network setup by a public telephone service

PSTN Public switched telephone network:the normal telephone service

PTP Point-to-point protocol. Providesserial communications between twoBACnet half-router devices, typic-ally for dial-up communicationsover phone modems. It may also beapplied as a hard-wired interface.For the duration of the con-nections, messages may be passedbetween networks on either side ofthe PTP connections

PWM Pulse width modulation, used infrequency inverters for motor speedcontrol

Rangeability Operating range of a valve,expressed as the ratio of maximumand minimum controllable flows

Recirculated air Air which has been extracted froma zone and which is mixed withoutdoor air to make up the supplyair

Regulating valve A valve which is set during com-missioning to achieve the requireddesign flow

Repeater A device that connects two or morephysical segments of a LAN at thephysical layer and exactly reproducesthe electrical signal on either side so

that nodes either side of the repeaterare considered to be on the samenetwork

Reset action Integral control action (US usage)

Reset control Non-standard term for cascadecontrol

Reset rate Inverse of integral action time

Resolution The smallest change in input signalthat can be discriminated in a device

Return air Air extracted from a zone andreturned to the main air handlingplant. Not necessarily the same asrecirculated air. Extract air ispreferred term

Router A device which connects two ormore networks, of same or differenttypes, so that a message may betransferred across the appropriatenetworks to reach its destination.The router translates betweenprotocols where required

SCADA Supervisory control and dataacquisition

Self-optimising See adaptive control systemcontrol system

Sequencer A controller which controls theoperation of multiple boilers orchillers, both for modulation andduty cycling

Set point The value to which a controller is setto achieve the desired value of thecontrolled variable

Shoe valve Rotating shoe that slides overinternal ports. Normally three-way

Slipper valve See shoe valve

Soft point See virtual point

Standardised protocol A standardised protocol is putforward by a national or inter-national standardisation committee.Member countries are obliged toaccept these standards. Any changesto the standards must be approvedby the standardisation committee.The certification procedure is oftenstandardised at the same time.Examples are BACnet, FND,PROFIBUS etc.

Stroke The range of movement of a linearactuator

Supervisor The user interface for a BMS. Alsocalled head end

Supply air Air supplied by a central air hand-ling unit to the occupied zones

TCP/IP Transmission Control Protocol/Internet Protocol. It encompassesmedia access, packet transport,session communications, etc. TCP/IPis supported by a large number ofhardware and software vendors

A3-4 Building control systems

Page 186: Building control system, aplication guide   cibse guide

Three term control Another term for PID control

Throttling range See proportional band

Time constant The time required for a quantity toreach 63% of its new final equili-brium value following a change ordisturbance.

Unitary controller Device which controls and/or moni-tors a single piece of equipment. Seededicated function controller

UTP Unshielded twisted pair

Virtual point A variable which is computed ratherthan directly measured, e.g. enthalpy

Voltage Circuits are classified as:(1) Extra-low voltage (ELV). Notexceeding 50 V between conductors

and not exceeding 30 V AC or 50 V DCbetween any conductor and earth(2) Low voltage. Between 50 and 250V(3) Medium voltage. Over 250 V andnot exceeding 650 V

Weather The control of heating medium compensation temperature as a function of external

temperature

Wind-up An excessive or out-of-range controlaction produced by an integralaction controller following start upor other period when there has beena deviation from the set point

Zone A part of a building which is con-trolled independently of other zones

Glossary A3-5

Page 187: Building control system, aplication guide   cibse guide

This Page Intentionally Left Blank

Page 188: Building control system, aplication guide   cibse guide

IndexAbsence sensing, 5-57

see also OccupancyAbsorption chillers, 5-7Accelerator heater, 2-3Accuracy of sensors, 3-2Active analogue sensors, 3-1–2Actuators, 3-7, 3-9

electrical connections, 3-7–8mechanical characteristics, 3-7pneumatic, 3-8valves, 3-12

Adaptive control, 2-12–13Adaptive tuning techniques, 2-12–13A/D conversion, 3-2Air-cooled condensers, 5-8Air flow tracking (volume matching), 5-39,

5-40variable-volume extract fans, 5-36

Air handling systems, see Central air handlingplant

Air handling units (AHUs), 5-28–9Air quality, 1-3

poor outdoor, 5-35sensors, 3-5–6

Airside fan coil units, 5-47, 5-48Alarms, 5-1

user interface, 4-18American Society of Heating, Refrigerating

and Air Conditioning Engineers(ASHRAE), 4-9–10

Analogue alarms, 5-1Analogue modelling, 6-2–3Analogue sensors, 3-1–2Angle of rotation, rotary actuators, 3-7Architecture, building management systems,

4-1bus systems, 4-3centralised intelligence, 4-1–2conventional controls, 4-1modular systems, 4-3packaged systems, 4-3programmable controllers, 4-2–3three-level model, 4-4utilisation of IT network, 4-4–5

Arcnet, 4-6, 4-7Artificial intelligence, 2-13–14Atomised spray humidifiers, 5-31–2Authority

damper, 3-19valve, 3-13–15, 5-14

Automatic balancing valves, 3-9Automatic flow-limiting valves, 5-25Autotransformers, 3-21Autotuning, 2-12Auxiliary heat exchanger, free cooling, 5-11Averaging, 2-7

Back end protection of boilers, 5-4, 5-18BACnet, 4-7, 4-9–10Baffles, 3-19Base energy requirement, 1-3, 1-4Batibus, 4-7, 4-12Batibus Club International, 4-12Bekker tuning method, A2-3Best Practice in the Specification for Offices, 1-3Blanking plates, 3-19Bleeding, cooling towers, 5-11Boiler (Efficiency) Regulations 1993, 5-3Boilers, 5-3

controls, 5-4boiler protection, 5-4–5burner controls, 5-4

multiple boilers, 5-5–7water heating plant, 5-5

primary hydraulic circuits, 5-18–19safety strategies, 5-2system pressurisation, 5-7types, 5-3–4

BRE Digest 424, 4-13, 4-14BRESTART, 2-8Brief

commissioning, 8-9design, 8-5, 8-6

BS 5389, 4-16BS 6651, 4-13BS 7807, 4-16BS CEN 60439, 3-24BS EN60947-4-1, 3-21BS EN7730, 1-3Buffer vessels, see Decoupling, hydraulicBuilding Automation and Control Network

(BACnet), 4-7, 4-9–10Building backbone cabling, 4-7, 4-8Building management systems (BMSs)

architecture, 4-1bus systems, 4-3centralised intelligence, 4-1–2conventional controls, 4-1modular systems, 4-3packaged systems, 4-3programmable controllers, 4-2–3three-level model, 4-4utilisation of IT network, 4-4–5

benefits, 1-5–6commissioning, 8-10–11definition, 1-2pre-commissioning, 8-9–10

Building operation, see OperationBuilding Regulations (1995)

energy conservation, 1-4lighting controls, 5-56, 5-57, 5-58natural ventilation, 5-54optimum start, 2-8ventilation, 5-34weather compensation, 2-8, 5-27

Burner controls, boilers, 5-4Bus network topology, 4-6Bus systems

BMS architecture, 4-3standardising bodies, 4-9

Butterfly valves, 3-9, 3-10actuators, 3-7

Bypass ports, valves, 3-10, 3-11authority, 3-15

Cablingclassification, 4-7electromagnetic compatibility, 4-14sensors, 3-6specification, 8-4structured, 4-7–8

Calibration of sensors, 3-6Calorifiers, 5-19–21Campus backbone cabling, 4-8Capacitative humidity sensors, 3-3, 3-4Capacitative pressure sensors, 3-4Capacity index, 3-12Carbon dioxide

concentrationair quality sensors, 3-5, 3-6mechanical ventilation, 5-34natural ventilation, 5-53, 5-54

emissions, 1-2Carbon monoxide

sensors, 3-6, 5-35ventilation, 5-34, 5-35

Cascade control (reset control), 2-6

central air handling plant, 5-29lighting, 5-57tuning, 2-11underfloor heating, 5-27zone temperature, 2-9

Case studies, 6-7low energy university building with fabric

storage, 6-8mixed mode R&D facility using chilled

beams, 6-8–9remote control of elderly people’s homes,

6-7–8retrofit using a modular control system, 6-7Terminal 2, Manchester Airport, 6-9–10

Cash flow analysis, 8-16Cavitation, valves, 3-16Ceilings, see Chilled ceilingsCentral air handling plant, 5-28–9

cooling coil, 5-30–1heating coil, 5-29–30humidification, 5-31–2preheat coil, 5-29safety strategies, 5-2

Central heating system, 5-18Centralised intelligence, 4-1–2Central processing unit (CPU), 4-2Centrifugal compressors, 5-7Characterised V-port valves, 3-11Characteristics

damper, 3-18–19valve, 3-11–12

Charge to full, ice storage, 5-13Chilled ceiling panels, 6-5Chilled ceilings, 5-49–50

case study, 6-8–9and displacement ventilation, 6-5–6

Chilled mirror dewpoint sensors, 3-3, 3-4Chilled water systems, 5-2Chiller downstream ice storage system, 5-12Chiller priority control, ice storage, 5-13Chillers, 5-7

control, 5-8–9cooling towers, 5-10–11free cooling, 5-11ice storage, 5-12–13multiple, 5-9–10primary hydraulic circuits, 5-18–19

Chiller upstream ice storage system, 5-12Chlorinated fluorocarbons (CFCs), 1-2–3Chlorine sensors, 3-6CIBSE Code for Interior Lighting, 5-56CIBSE Code of Professional Conduct, 1-3CIBSE Guide A1, 1-3CIBSE Guide to Energy Efficiency in Buildings,

1-3CIBSE Policy Statement on Global Warming, 1-3Closed loop systems, 2-1

cooling towers, 5-11Closed loop ultimate cycling method, 2-11,

A2-2, A2-3–4Close-down, see Shut-down periodClosing torque, dampers, 3-18Coaxial cable

electromagnetic compatibility, 4-14networks, 4-6–7

Code of Practice for the Selection ofSubcontractors, 8-8

Coexistence, networks, 4-8Cohen–Coon tuning method, A2-3Commissioning, 8-8

brief, 8-9costing, 8-12–13design stage, 8-9handover, 8-11–12installation, 8-9–11

Index I-1

Page 189: Building control system, aplication guide   cibse guide

management, 8-8–9Commissioning valves, 3-9Common ports, valves, 3-10, 3-11

authority, 3-15Communication media, networks, 4-6–7Compatibility, networks, 4-8Complementary ventilation, 5-56Components of a control system, 2-1, 2-2Computer fluid dynamics (CFD), 6-3Computers, see Information technologyCondensation prevention, 5-50Condensing boilers, 5-3–4

multiple boiler systems, 5-5Condition-based maintenance (CBM), 7-7Conditions, 8-7

monitoring, 2-14Configuration mode, intelligent outstations,

3-25Constant volume, dual duct, single supply fan,

5-48Constant-volume room terminal units, 5-46Constructing the Team, 8-3Construction management, 8-3Contingency ventilation, 5-55Contractual problems with systems

integration, 4-16Controllers, see Intelligent outstationsControl loops, interaction between

autotuning, 2-12stability issues, 2-10

Control modes, see Modes of controlControl of Fuel and Electricity, 1-3Control panels, 3-23–4

electromagnetic compatibility, 4-14–15Control ports, valves, 301-, 3-11

authority, 3-15design, 3-11

Conventional controls, 4-1Cooling coils, 5-30–1Cooling towers, 5-8, 5-10–11Cost benefit analysis, 8-15–16Cost effectiveness, energy monitoring and

targeting, 7-2Costing, 8-12–13Cost issues

assessment methods, 8-16cost benefit analysis, 8-15–16life cycle costing, 8-16

Coverage, energy monitoring and targeting,7-2

Critically damped response, 2-11Current source inverters (CSIs), 3-23Current transformers (CTs), 7-4Cusum technique, 7-6

Damper authority, 3-19Damper characteristic, 3-18–19Damper ratio, 3-19Dampers

applications, 3-20face and bypass control, 3-20return air mixing, 3-20

fire protection system, 4-16modulating, 3-18–19selection, 3-17–18ventilation, 5-36–8, 5-40

Data analysis, energy monitoring andtargeting, 7-1, 7-5–6

Data collection, energy monitoring andtargeting, 7-1

Data-gathering panels, 4-2Data logging, 7-4–5

user interface, 4-18Deadband, see Differential gap/band

Decoupling, hydraulic, 5-18–19, 5-20incompatible flows, 5-14

Dedicated function controllers, see Unitarycontrollers

Dehumidificationchilled ceilings, 5-50cooling coils, 5-30displacement ventilation, 5-41with mixing damper control, 5-40VRF systems, 6-5see also Humidity control

Demand-controlled ventilation (DCV), 5-34–5,5-54

air quality sensors, 3-5Derivative action, 2-7

PID control, 2-5Derivative action time, 2-11Derivative kick, A2-2Design and build, 8-1, 8-2, 8-3Design and manage, 8-1–2Design and specification of a controls system

commissioning, 8-9conditions and tolerances, 8-7design brief, 8-5, 8-6sequence of events, 8-4–6specification, 8-6–7techniques, 6-2

analogue modelling, 6-2–3emulation, 6-3full scale mock-up, 6-2mathematical modelling, 6-3

Design brief, 8-5, 8-6Develop and construct, 8-1Dewpoint sensors, 3-3, 3-4

chilled ceilings, 5-50Differential gap/band (deadband), 2-2

fan control units, 5-48heat pumps, 5-52

Differential pressure, 3-4valves, 3-8–9

Differential pressure control valves (DPCVs),3-9

mixing circuits, 5-16thermostatic radiator valves, 5-28variable-volume systems, 5-24–5

Digital alarms, 5-1Digital control, 2-5–6

tuning, A2-1–2, A2-3Digital data technology, 1-2Digital inputs (DIs), 2-1Digital outputs (DOs), 2-1Dimmers, 5-56, 5-57Direct digital control (DDC), 2-1, 2-6–7

BMS architecture, 4-1–2origins, 1-2

Direct expansion (DX) cooling coils, 5-30–1Direct humidification, 5-31Direct ice storage, 5-12Direct on-line (DOL) starting, 3-21Discounted cash flow (DCF), 8-16Discount techniques, 8-16Displacement ventilation, 5-41

and chilled ceilings, 6-5–6Distance–velocity lag, 2-6Distributed processing units, see Intelligent

outstationsDiverting circuits, 5-15Diverting valves, 3-10Documentation

control strategy, 6-1operations and maintenance, 8-12

Drip loops, sensor cables, 3-6Dual duct systems, 5-48–9Dual mixing circuits, 5-16Dumb outstations, 4-2

Dynamic balancing valves, see Flow limitingvalves

Dynamic torque, dampers, 3-18

Earthing, 4-13–14Economiser cycle, 5-37, 5-38Eddy current coupling, 3-21–2Egan report, 8-3EHS, 4-9EIBus, 4-6, 4-7, 4-11–12Electrical connections, actuators, 3-7–8Electricity tariffs, 7-3Electro-hydraulic actuators, 3-7Electromagnetic compatibility (EMC), 4-12

EMC Directive, 4-13installation, 4-13

cabling, 4-14control panels, 4-14–15location, 4-13power supply and earthing, 4-13–14

Electromagnetic humidity sensors, 3-3Electronic soft start, 3-21Electronic start, fluorescent lamps, 5-59Elizabeth Fry Building, 6-8Emulation, 6-3Energy

conservation, 1-3–4, 1-5efficiency, motors, 3-20–1monitoring, 7-1

data analysis and reporting, 7-5–6metering equipment, 7-3–5neural networks, 2-14and targeting (M&T), 7-1–3

recovery, 5-32fixed plate heat exchangers, 5-33run-around coils, 5-33thermal wheel, 5-32–3

use, lighting, 5-56Energy account centres (EACs), 7-1, 7-2Enthalpy control

cooling coils, 5-30mechanical ventilation, 5-38, 5-39

Environmentglobal, 1-2–3indoor, 1-3

Equal percentage valves, 3-11–12Ethernet, 4-6, 4-7European Committee for Standardisation

(CEN), 4-4, 4-9European Home Systems (EHS), 4-9European Installation Bus (EIBus), 4-6, 4-7,

4-11–12European Installation Bus Association (EIBA),

4-11European Standards, 1-3External air supply, 5-38–40External air temperature, 5-53Extract fans, variable-volume, 5-35–6

Face and bypass control, dampers, 3-20Fan-assisted VAV units, 5-43, 5-44Fan coil units (FCUs), 5-46–7

airside control, 5-48interaction between control loops, 2-10waterside control, 5-47–8whole-building HVAC systems, 6-3–5

Fans, 3-23dual duct systems, 5-48–9VAV systems, 5-43–5, 5-46variable-volume extract, 5-35–6

Fan speed control, fan coil units, 5-47Fault reports, 7-6–7Feed and expansion (F&E) tanks, 5-7, 5-8Feedback mechanisms, 8-14Feedforward systems, see Open loop systems

I-2 Building control systems

Page 190: Building control system, aplication guide   cibse guide

Fibre optic cable, 4-6–7Field Instrumentation Protocol (FIP), 4-9Field processing units, see Intelligent

outstationsFilters, 5-35Fine tuning, 8-13Fingerprint, building, 8-15FIP, 4-9Fire protection system (FPS)

dampers, 3-18safety, 5-2, 5-3systems integration, 4-16

Firm Neutral Data Transmission (FND), 4-9Firmware, intelligent outstations, 3-26Fixed plate heat exchangers, 5-32, 5-33Fixed-speed circulating pumps, 5-22–3Floating control, 2-3

time lags, 2-6Flow, hydraulic, 3-8–9

sensors, 3-5Flow coefficient, 3-12, 3-13Flow dilution

multiple boilers, 5-6multiple chillers, 5-9

Flow limiting valves, 3-9Fluorescent lamps, 5-58–9Flux vector control, 3-23FND, 4-9Form 2 control panels, 3-24Form 3 control panels, 3-24Form 4 control panels, 3-24Four-pipe water systems, 5-47, 5-48Four-port valves, 3-10Free cooling, 5-11Freely programmable controllers, see

Intelligent outstationsFrost protection

air handling systems, 5-2central air handling plant, 5-29cooling towers, 5-11water systems, 5-2

Fuel Efficiency Booklet 10, 1-4Full outside air damper system, 5-35Full scale mock-ups, 6-2Full systems integration, 1-5, 4-15Fundamentals of control, 2-1, 2-14

artificial intelligence, 2-13–14modes of control, 2-1–7optimum start, 2-7–8stability and tuning, 2-9–13weather compensation, 2-8–9

Fuzzy logic, 2-13

Gain scheduling, 2-12Gas sensors, 3-5–6Gauge pressure, 3-4Global environment, 1-2–3Global warming, 1-2, 1-3Globe valves, see Plug and seat valvesGraphics, 4-18Greenway School, Horsham, 6-7Group remote controllers, heat pumps,

5-51–2

Handover, 8-11documentation, 8-12training, 8-12witnessing, 8-11–12

Hardwareconfiguration, intelligent outstations, 3-25user interface

plug-in keypad, 4-17stand-alone controllers, 4-17supervisor, 4-18touchscreen, 4-18

HBES, 4-12HCFCs, 1-2–3Health and safety file, 8-12Heat flow monitoring, IEE inventory

estimation, 5-13Heating coils, 5-29–30Heat pumps

reverse cycle units, 5-52–3VRF split systems, 5-51–2

Hewlett Packard, Building 3, Bristol, 6-8–9High frequency control, fluorescent lamps,

5-59High frequency regulating control, fluorescent

lamps, 5-59Home and Building Electronic System

(HBES), 4-12Horizontal cabling, 4-7, 4-8Hot water systems

floating control, 2-3pressurisation, 5-7safety strategies, 5-2see also Boilers

Hot wire anemometers, 3-5Hours run alarms, 5-1Humidification, 5-31–2Humidistats, 3-1, 3-3Humidity control, 1-3

conditions, 8-7sensors, 3-3–4VRF systems, 6-5see also Dehumidification

Hunting behaviour, 2-10Hydraulic circuits, control of, 5-14

basic circuits, 5-15–18calorifiers, 5-19–21network design, 5-14–15primary circuits, 5-18–19thermostatic radiator valves, 5-27–8underfloor heating, 5-26–7variable-volume systems, 5-21–6

Hydraulic flow, 3-8–9sensors, 3-5

Hysteresisactuators, 3-8logic control, 2-7sensors, 3-2

Ice bank, 5-12Ice builder, 5-12Ice storage, 5-12

control techniques, 5-12–13system configuration, 5-12

Ideal damper characteristics, 3-18IEE Wiring Regulations, 4-14Incremental algorithm, 2-6Index circuit, 5-23, 5-24Indirect humidification, 5-31Indirect ice storage, 5-12Individual room unit controllers, heat pumps,

5-51Indoor environment, 1-3Induction VAV terminal units, 5-43Inductive pressure sensors, 3-4Information technology (IT), 1-2, 1-4–5

energy monitoring, 7-1–6fault reports and maintenance scheduling,

7-6–7network, 4-4–5systems integration, 4-4–5, 4-15, 4-16–17

Infra-red thermography, 7-7Ingress protection system, 3-24–5Inherent characteristics of dampers, 3-18,

3-19Injection circuits, 5-16–17Injection fan system, 5-39

Installation, 8-9commissioning the BMS 8-10–11pre-commissioning the BMS, 8-9–10

Installed characteristics of dampers, 3-19Integral action time

PI control, 2-4, 2-5tuning, 2-11

Integral control, 2-4time lags, 2-6see also PI control; PID control

Integrated environmental design (IED), 5-58Integration, see Systems integrationIntelligent building system (IBS), see Full

systems integrationIntelligent fan coil units, 5-47

whole-building HVAC systems, 6-4Intelligent luminaires, 5-59Intelligent outstations (programmable

controllers; universal controllers), 2-7,3-24–5

BMS architecture, 4-3configuration, 3-25

hardware, 3-25strategy, 3-26system, 3-25

heat pumps, 5-52stand-alone controllers, 4-17

Intelligent sensors, 3-2Intelligent VAV boxes, 5-42, 5-44–5

interaction between control loops, 2-10supply air temperature control, 5-45–6

Interchangeability, networks, 4-8, 4-9Interconnected circuits, free cooling, 5-11Interference, A2-2Interlocks, 5-1–2

cooling towers, 5-11Internal bypass, 5-16International Organisation for Standardisation

(ISO), 4-9Internetworks, see Wide area networksInteroperability, 1-6, 4-15

networks, 4-8, 4-9Inverter drives, 3-22

current source inverter (CSI), 3-23motor control centres, 3-24pulse amplitude modulation (PAM), 3-23pulse width modulation (PWM), 3-22–3

IP protection numbers, 3-24–5ISDN telephone line, 4–6ISO, 4-9

Keypad, plug-in, 4-17

Lamps, 5-58–9see also Lighting control

Latham, Sir Michael, 8-3Leakage rating, dampers, 3-18Legionnaires’ disease, 5-8, 5-10, 5-21Let-by, 3-12Library of System Control Strategies, 6-2Life cycle costing, 8-16Lift and lay valves, see Plug and seat valvesLighting control, 5-56

methods, 5-56–7systems and components, 5-57–61

Lightning protection, 4-13–14Linear actuators, 3-7Linear regression analysis, 7-5–6Linear valves, 3-11Load error (offset), 2-3, 2-4Local area networks (LANs), 1-2, 4-5

communication, 4-6intelligent outstations, 4-3OSI Basic Reference Model, 4-9

Localised manual lighting controls, 5-56–7

Index I-3

Page 191: Building control system, aplication guide   cibse guide

Logic control, 2-6–7Logic operators, 2-7LonMark Interoperability Association, 4-10LonTalk protocol, 4-3, 4-10LonWorks, 4-6, 4-7, 4-10–11

case study, 6-7systems integration, 4-16

Look-up tables, 2-7Loop reschedule interval, 2-6Low-loss headers, 5-16Low pressure header systems, 5-18, 5-19Lubricant analysis, 7-7

Maintenance, 8-13remote operation, 1-5scheduling, 7-6–7

Managed space, and lighting controls, 5-60Management contracting, 8-3Management issues, 8-16–17

commissioning, 8-8–13cost issues, 8-15–16design and specification of a controls

system, 8-4–7occupant surveys, 8-14–15operation, 8-13procurement options, 8-1–4tendering process, 8-7–8

Management methods, procurement, 8-3Manchester Airport, Terminal 2, 6-9–10Manual differential, 2-2Master controller, 2-6Mathematical modelling, 6-3Mechanical differential, 2-2Mechanical ventilation, 5-34

chilled ceilings, 5-50, 6-6dehumidification with mixing damper

control, 5-40demand-controlled ventilation, 5-34–5displacement ventilation, 5-41full outside air damper system, 5-35mixing damper systems, 5-36–8outdoor air supply, 5-38–40poor outdoor air quality, 5-35variable-volume extract fan, 5-35–6see also Mixed mode ventilation

Mechanical ventilation with heat recovery(MVHR) systems, 6-5

Metering equipment, 7-2, 7-3–4computer, 7-4, 7-5data logger, 7-4–5data transmission system, 7-4display module, 7-4meter module, 7-3, 7-4

Mineral-insulated copper-sheathed cable(MICC), 4-16

Minimum flow rate control, 5-25–6Mixed mode ventilation, 5-55–6

and chilled ceilings, 6-6whole-building HVAC systems, 6-6–7

Mixingcircuits, 5-15–16dampers, 3-18

ventilation, 5-36–8, 5-40valves, 3-10

Mock-ups, full scale, 6-2Modelling

analogue, 6-2–3mathematical, 6-3

Modern control systems, 1-2Modes of control, 2-1

cascade control, 2-6choice of, 2-7digital control, 2-5–6integral control, 2-4logic control, 2-6–7

PI control, 2-4–5PID control, 2-5proportional control, 2-3–4time lags, 2-6two-position (on/off) control, 2-2–3

Modular systems, 4-3case study, 6-7

Modulating dampers, 3-18–19Modulating valves, 3-9

actuators, 3-7selection, 3-17

Montreal protocol, 1-2Motor control centres, 3-23–4Motor current analysis, 7-7Motors

energy efficiency, 3-20–1speed control, 3-21–3starting, 3-21variable-speed, 3-23

Mounting of sensors, 3-2, 3-6MPT1329, 4-7MPT1340, 4-7Multi-gas sensors, 3-5, 3-6Multiple boilers, 5-4, 5-5–7Multiple chillers, 5-8, 5-9–10Multiple pressure sensors, VAV supply fan

control, 5-44, 5-45Multi-speed motors, 3-22Multi-split systems, heat pumps, 5-51

National Accreditation of Measurement andSampling (NAMAS), 3-6

National Engineering Specification (NES), 4-13,8-6–7

Natural ventilation, 5-53chilled ceilings, 5-50, 6-6controlled devices, 5-53control strategies, 5-54

night cooling, 5-54–5occupation period, 5-54

measurement devices, 5-53–4whole-building HVAC systems, 6-6–7see also Mixed mode ventilation

Near optimal control, cooling towers, 5-11Need for controls, 1-2, 1-6

benefits of a BMS, 1-5–6building operation, 1-5energy conservation, 1-3–4global environment, 1-2–3indoor environment, 1-3information technology and systems

integration, 1-4–5Net cash flow, 8-16Net present value, 8-16Network analysis, 5-15Networks, 4-5

communication media, 4-6–7hydraulic circuits, 5-14–15IT, 4-4–5protocols, 4-7standardisation, 4-8–9standard systems, 4-9–12structured cabling, 4-7–8topology, 4-5–6

Neural networks, 2-13–14Neutral head end, 4-15Nickel resistance thermometer, 3-3Night cooling

chilled ceilings, 5-50mixed mode ventilation, 5-56natural ventilation, 5-54–5

Night setback control, 5-27Nitrogen dioxide sensors, 3-Noise, A2-2Non-oscillatory instability, 2-9

Obscuration, 3-6Occasionally visited space, and lighting

controls, 5-60Occupancy

calculation, 3-5lighting, 5-57mechanical ventilation, 5-34natural ventilation, 5-53, 5-54, 5-55

Occupant surveys, 8-14–15Offset, 2-3, 2-4On/off control, see Two-position (on/off)

controlOpen loop reaction curve method, 2-11, A2-3,

A2-4Open loop systems

components, 2-1cooling towers, 5-11motor speed control, 3-22variable-volume extract fans, 5-35–6weather compensator, 2-9

Open Systems Interconnection (OSI) BasicReference Model, 4-9

BACnet, 4-10Operating conditions, 2-10Operating differential, 2-2, 2-3Operating modes, 6-1–2Operation, 1-5

conditions, 8-7fine tuning, 8-13maintenance, 8-13recommissioning, 8-13

Opposed blade damper, 3-18, 3-19applications, 3-20

Optical fibre, 4-6–7Optimisation, 2-14Optimum charge, ice storage, 5-13Optimum start, 2-7–8

adaptive control, 2-12chilled ceilings, 5-50underfloor heating, 5-27water systems, 5-2

Optimum stop, 2-8underfloor heating, 5-27

Orifice plates, 3-5Oscillation test, see Closed loop ultimate

cycling methodOscillatory instability, 2-9–10Outdoor air supply, 5-38–40Outdoor air temperature, 5-53Overall liking scores (OLS), 8-14–15Overview of Guide, 1-1–2Owned space, and lighting controls, 5-60Ozone layer, damage to, 1-2

Packaged split units, heat pumps, 5-51Packaged systems, 4-3Parallel blade damper, 3-18, 3-19

applications, 3-20Parallel ice storage system, 5-12Parallel pumping, 5-21–2Partnering, 8-3–4Passive analogue sensors, 3-1Passive chilled beams, 6-5Patch cabling, 4-8Pattern recognition adaptive controller

(PRAC), 2-12–13Payback method, 8-16PC-based controllers, heat pumps, 5-52Peltier effect, 3-3Percentage of full stroke (spindle lift),

3-11–12Performance reviews, 8-14Perimeter heating

and chilled ceilings, 6-6and VAV, 6-3–4

I-4 Building control systems

Page 192: Building control system, aplication guide   cibse guide

PI control, 2-4–5choice of, 2-7interaction between control loops, 2-10time lags, 2-6tuning, 2-12, A2-1

PID control, 2-5choice of, 2-7digital control, 2-6tuning, A2-2

Piezoelectric transducers, 3-5Pitot tubes, 3-5Platinum resistance thermometer (PRT), 3-3Plenum-pressure system, 5-39–40Plug and seat valves (lift and lay valves), 3-9,

3-10actuators, 3-7

Plug and shoe valves, see Shoe valvesPneumatic actuators, 3-8Point to point network protocol, 4-7Point to point network topology, 4-5, 4-6Polling, 4-2Position algorithm, 2-6, A2-2Positioners, 3-8Position indication, actuators, 3-8Potentiometer pressure sensors, 3-4Power line carrier, 4-6, 4-7Power supplies, 4-13Practical tuning, 2-11Pre-commissioning the BMS, 8-9–10Predicted mean vote (PMV) index, 1-3Preheat coils, 5-29Presence sensing, 5-57

see also OccupancyPresent worth method, 8-16Pressure and dampers, 3-18Pressure dependent VAV units, 5-42Pressure drop, 3-9Pressure independent VAV terminals, 5-42–3Pressure sensors, 3-4–5Pressure switches, 3-1Pressurisation of hot water systems, 5-7, 5-8Pre-tendering, 8-7Primary hydraulic circuits, 5-14

boiler and chiller connections, 5-18–19Primary resistance starters, 3-21PROBE post-occupancy studies, 8-14Procurement options, 8-1

design and build, 8-1design and manage, 8-1–2management methods, 8-3partnering, 8-3–4relations between parties, 8-3traditional, 8-2–3

Programmable controllers, see Intelligentoutstations

Project management, 8-8–9Project patterning, 8-3Proportional band, 2-11Proportional control, 2-3–4

choice of, 2-7interaction between control loops, 2-10time lags, 2-6ventilation, 5-34–5

Proportional plus integral control, see PIcontrol

Proportional plug integral plus derivativecontrol, see PID control

Proportional-speed floating control, 2-3Protection of boilers, 5-4–5Pseudo-proportional control, 2-3Pulse amplitude modulation (PAM) inverters,

3-23Pulse width modulation (PWM) inverters,

3-22–3Pump differential pressure control, 5-23

Pumping energy requirements, 5-21Pump overrun function, 5-5Pump pressurisation, 5-7, 5-8Pumps, 3-23

heat, 5-51–3

Quality, air, see Air qualityQuarter wave response, 2-11Quarter wave tuning method, A2-2Questionnaires, occupant surveys, 8-14–15Quick opening valves, 3-11

Radiatorsand chilled ceilings, 6-6naturally ventilated buildings, 5-54thermostatic valves, 5-27–8, 6-3and VAV, 6-3–4

Radio, 4-6, 4-7Rain intensity sensors, 5-53Rangeability, valves, 3-12Read only mode, intelligent outstations, 3-25Reciprocating compressors, 5-7, 5-8, 5-9Recommissioning, 8-13Rectangular dampers, 3-17Reference standards, sensor calibration, 3-6Refrigerant pressure, 5-8Refrigerant vapour migration, 5-11Regenerative heat exchanger, 5-32Regulating valves, 3-9Remote control, 1-5

case study, 6-7–8heat pumps, 5-51–2lighting, 5-56

Reportingenergy monitoring and targeting, 7-1, 7-2faults, 7-6–7user interface, 4-18

Reset control, see Cascade controlReset rate, 2-4Response speed, 8-14

sensors, 3-2–3Rethinking Construction, 8-3Return air mixing, dampers, 3-20Reverse cycle heat pump units, 5-52–3Reviews of performance, 8-14Ring network topology, 4-5–6Room terminal units (RTUs)

constant-volume, 5-46dual duct systems, 5-48, 5-49variable air volume, 5-41, 5-42–3

Rotary actuators, 3-7Rotary compressors, 5-8Rotary shoe valves, see Shoe valvesRotation angle, rotary actuators, 3-7Round dampers, 3-17Run-around coils, 5-32, 5-33Running time, actuators, 3-7

Safety, 5-1alarms, 5-1documentation, 8-12earthing, 4-13fire and smoke control, 5-3interlocks, 5-1–2lighting, 5-56, 5-59selection switches, 5-2–3strategies, 5-2

Safety shut-off valves, 3-9Sampling time

digital control, 2-6stability issues, 2-10tuning, 2-11

Scene set lighting control, 5-57Screened cables, 4-14Screw compressors, 5-7

Scroll compressors, 5-7Sealed expansion vessel pressurisation, 5-7, 5-8Secondary hydraulic circuits, 5-14, 5-18Secondary metering, 7-3Security issues, 4-18Security systems, 4-16Selection switches, 5-2–3Self-tuning controllers, 2-11–12, 2-13

adaptive techniques, 2-12–13autotuning, 2-12

Sensing element, 3-1Sensitivity of sensors, 3-2Sensors

calibration, 3-6general categories, 3-1–2mounting, 3-6natural ventilation, 5-53selection requirements, 3-2

accuracy, 3-2response speed, 3-2–3

types, 3-3air quality sensors, 3-5–6humidity sensors, 3-3–4pressure sensors, 3-4–5temperature sensors, 3-3velocity and flow sensors, 3-5

Set point control, 5-34Seven-layer model, see Open Systems

Interconnection (OSI) Basic ReferenceModel

Shannon’s sampling theorem, 2-10Shared space, and lighting controls, 5-60Shielded twisted pair, 4-6Shoe valves, 3-9, 3-10

actuators, 3-7Shut-down period

fire and smoke control, 5-3heat pumps, 5-53sequencing of operations, 5-2

Sick building syndrome (SBS), 1-3, 5-34Signal conditioning, 3-1

accuracy, 3-2Similar modified parabolic (equal percentage)

valves, 3-11–12Single pressure sensors, VAV supply fan

control, 5-44Sizing

dampers, 3-19valves, 3-15–16

Skipped charge, ice storage, 5-13Slab temperature, 5-53Slip, 3-21Smoke protection

dampers, 3-18safety, 5-2, 5-3

Software, 4-18Soft wiring, intelligent outstations, 3-26Solar radiation, 5-53Sophistication, energy monitoring and

targeting, 7-2Space types and lighting controls, 5-59–60Specification, 8-4, 8-6–7Speed control, motors, 3-21–3Spindle lift, 3-11–12Spindles, 3-9Stability

of control systems, 2-9–10of sensors, 3-2

Standardisation, network, 4-8–9Standardising bodies, 4-9Standard Specification (M&E), 8-6Standard systems

BACnet, 4-9–10Batibus, 4-12EIBus, 4-11–12

Index I-5

Page 193: Building control system, aplication guide   cibse guide

HBES, 4-12LonWorks, 4-10–11

Star–delta starters, 3-21Star network topology, 4-5, 4-6Start

motors, 3-21optimum, see Optimum start

Start-up periodcalorifiers, 5-20sequencing of operations, 5-2

Static pressuredampers, 3-18valves, 3-8variable-volume extract fans, 5-36

Status alarms, 5-1Status sensors, 3-1Steam injection humidifiers, 5-31Steam valves, 3-12–13Stem position (spindle lift), 3-11–12Stop, see Optimum stopStorage type humidifiers, 5-31Store exit temperature, ice inventory

estimation, 5-13Store priority control, ice storage, 5-13Strain gauge pressure sensors, 3-4Strategic partnerships, 8-3Strategy configuration, intelligent outstations,

3-26Stroke, linear actuators, 3-7Stroke time, actuators, 3-7Structured cabling, 4-7–8Submaster controller, 2-6, 2-11Submetering, 7-3Sulphur dioxide sensors, 3-6Summer cooling, 5-56Supervisors, 3-25

centralised intelligence, 4-2programmable controllers, 4-2–3user interface, 4-18

Supply air temperature control for VAVsystems, 5-45–6

Supply fan control for VAV systems, 5-43–5Surveys, occupant, 8-14–15Swing (operating) differential, 2-2, 2-3Switched reluctance drive, 3-22Switch start, fluorescent lamps, 5-58System configuration, intelligent outstations,

3-25hardware, 3-25strategy, 3-26system, 3-25

Systems integration, 1-4–5, 4-15implementation, 4-15with IT systems, 4-4–5, 4-16–17problems, 4-16

TCP/IP, 4-7Technical problems with systems integration,

4-16Telephone line, 4-6, 4-7Temperature control, 1-3

components of control system, 2-1, 2-2conditions, 8-7modes

cascade control, 2-6two-position control, 2-2–3

sensors, 3-3ventilation, 5-34

Temporarily owned space, and lightingcontrols, 5-60

Tendering process, 8-7Terminal 2, Manchester Airport, 6-9–10Thermal wheels, 5-32–3Thermic actuators, 3-7Thermistors, 3-3

Thermometersnickel resistance, 3-3platinum resistance (PRT), 3-3

Thermostatic radiator valves (TRVs), 5-27–8,6-3

Thermostats, 2-3, 3-1, 3-3Thermosyphonic method, free cooling, 5-11Three-level model, BMS architecture, 4-4, 4-9Three-phase squirrel cage induction motor,

3-21Three-port valves, 3-9, 3-10

authority, 3-14–15terminology, 3-10, 3-11

Three-position control, 2-3Three-term control, see PID controlThrottling circuits, 5-17–18Throttling range, 2-3Thrust, linear actuators, 3-7Time constant, 3-2, 3-3Time lags, 2-6Time proportioning control, 2-4Time scheduling

thermostatic radiator valves, 5-27user interface, 4-18

Timeswitches, lighting, 5-57Tolerances, 8-7Topology

cabling, 4-7–8network, 4-5–6

Torquedampers, 3-18rotary actuators, 3-7

Totaliser alarms, 5-1Touchscreen, 4-18Traditional procurement option, 8-2–3Training, 1-5, 8-12, 8-13Transducers, 3-1Transfer lag, 2-6Transient response, see Open loop reaction

curve methodTransmitters, 3-1Transport delay, 2-6Tree network topology, 4-6Tristate control, 2-3Tuning, 2-10, 2-11, 8-13, A2-2–3

digital control, A2-1–2PID control loop, A2-1practical, 2-11self-tuning controllers, 2-11–13step-by-step procedure, A2-3–4

Turbine flow meters, 3-5Turbulence and dampers, 3-18Twisted-pair copper wire

electromagnetic compatibility, 4-14networks, 4-6, 4-7

Two-pipe water systems, 5-47, 5-48Two-port valves, 3-10

authority, 3-13–14design, 3-12

Two-position (on/off) control, 2-2–3stability, 2-9–10tuning, 2-11

Ultimate cycling/frequency method, see Closedloop ultimate cycling method

Underfloor heating, 5-26–7Unitary controllers, 3-24, 4-3United Kingdom Accreditation Service, 3-6Universal (structured) cabling, 4-7–8Universal controllers, see Intelligent

outstationsUniversity of East Anglia, 6-8Unowned space, and lighting controls, 5-60Unshielded twisted pair (UTP), 4-6Unstable control systems, 2-9–10

Upload/download mode, intelligentoutstations, 3-25

User interface, 4-17hardware, 4-17–18levels of operation, 4-17software, 4-18users, 4-18

Valve authority, 3-13–15hydraulic circuits, 5-14

Valve characteristic, 3-11–12Valves

actuators, 3-7design

characteristic, 3-11–12flow coefficient, 3-12steam valves, 3-12–13

hydraulic flow, 3-8–9selection

authority, 3-13–15cavitation, 3-16checklist, 3-16–17sizing, 3-15–16

thermostatic radiator, 5-27–8, 6-3types, 3-9–11

Vapour compression chillers, 5-7Vapour pressure of water, 3-16, 3-17Variable air volume (VAV), 5-41–2

intelligent, see Intelligent VAV boxesoperating conditions, 2-10overlapping controlled zones, 2-10and perimeter heating, 6-3–4room terminal units, 5-42–3supply air temperature control, 5-45–6supply fan control, 5-43–5ventilation, 5-37, 5-38, 5-39, 5-40

Variable constant volume (pressureindependent VAV terminals), 5-42–3

Variable refrigerant flow (VRF) systems,5-51–2, 6-5

Variable-speed circulating pumps, 5-23–4thermostatic radiator valves, 5-28

Variable-speed drives (VSDs), 3-21Variable-speed motors, 3-23Variable-voltage control, 3-22Variable volume, dual duct, dual supply fans,

5-48–9Variable volume, dual duct, single supply fan,

5-48Variable-volume extract fans, 5-35–6Variable-volume systems

automatic flow-limiting valve, 5-25control of minimum flow rate, 5-25–6design recommendations, 5-26differential pressure control valves, 5-24–5fixed-speed circulating pump, 5-22–3parallel pumping, 5-21–2pumping energy requirements, 5-21variable-speed circulating pump, 5-23–4

Velocity algorithm, 2-6Velocity ratings, dampers, 3-18Velocity sensors, 3-5Ventilated chilled beams, 6-5–6

case study, 6-8–9Ventilation, see Mechanical ventilation; Mixed

mode ventilation; Natural ventilationVibration analysis, 7-7Voltage vector control (VVC), 3-23Volume matching, see Air flow trackingVolumetric devices, ice inventory estimation,

5-13

Water, vapour pressure of, 3-16, 3-17Water heating plant, 5-5Waterside fan coil units, 5-47–8

I-6 Building control systems

Page 194: Building control system, aplication guide   cibse guide

Weather compensation, 2-1, 2-8–9boilers, 5-4, 5-5thermostatic radiator valves, 5-27underfloor heating, 5-27

Wet and dry bulb psychrometers, 3-3Whole-building HVAC systems, 6-3–4

chilled ceiling and displacement ventilation,6-5–6

fan coil units, 6-4–5natural and mixed mode systems, 6-6–7

VAV and perimeter heating, 6-3–4VRF systems, 6-5

Wide area networks (WANs), 4-5BMS architecture, 4-4OSI Basic Reference Model, 4-9remote supervision, 1-5

Wind direction, 5-53Windows, 5-53, 5-54, 6-6–7Wind speed, 5-53, 5-54Wind-up

digital control, 2-6, A2-2PI control, 2-5, 2-10

Winter ventilation, 5-56Witnessing, 8-11–12Work area cabling, 4-8

Ziegler–Nichols tuning method, A2-2Zoned ventilation, 5-55–6Zone trim, 2-9

Index I-7

Page 195: Building control system, aplication guide   cibse guide

This Page Intentionally Left Blank