bs5 - lecture 2 hvac systems
TRANSCRIPT
HVAC SYSTEMS
TYPES
HOW AS AN ARCHITECT TO MAKE A CHOICE FIT FOR THE
PROJECT TYPE
ARCHITECTURAL THUMB RULE1 TON IS THE AC LOAD REQUIREMENT FOR A SPACE OF
100 SFT.
10’0”
10’0”
PRICINPLES OF AIR CONDITIONINGTHE AIM IS TO KEEP IT MORE COMFORTABLE INSIDE
THE BUILDING THAN IT IS OUTSIDE
A simple stylized diagram of the refrigeration cycle: 1) condensing coil, 2) expansion valve, 3) evaporator coil, 4) compressor
The refrigeration cycle uses four essential elements to cool.The system refrigerant starts its cycle in a gaseous state. The compressor pumps the refrigerant gas up to a high pressure and temperature.From there it enters a heat exchanger (sometimes called a condensing coil or condenser) where it loses energy (heat) to the outside, cools, and condenses into its liquid phase.An expansion valve (also called metering device) regulates the refrigerant liquid to flow at the proper rate.The liquid refrigerant is returned to another heat exchanger where it is allowed to evaporate, hence the heat exchanger is often called an evaporating coil or evaporator. As the liquid refrigerant evaporates it absorbs energy (heat) from the inside air, returns to the compressor, and repeats the cycle. In the process, heat is absorbed from indoors and transferred outdoors, resulting in cooling of the building.
PRICINPLES OF AIR CONDITIONINGTHE AIM IS TO KEEP IT MORE COMFORTABLE INSIDE
THE BUILDING THAN IT IS OUTSIDE
TYPES OF AC SYSTEMS
TYPES OF AC SYSTEMS
WINDOW AC
SMALL SCALE PROJECTS
PROVIDES HIGH REDUDANCY DOESN’T LOOK GOOD AESTHATICALLY
WINDOW AC
SMALL SCALE PROJECTS
PROVIDES HIGH REDUDANCY DOESN’T LOOK GOOD AESTHATICALLY
WINDOW AC
HIGH WALL AC
SMALL SCALE PROJECTS
PROVIDES HIGH REDUDANCY LOOK’S BETTER AESTHATICALLY
HIGH WALL AC
CASSETE AC OR CEILING MOUNTED AC
SYSTEM COMPARISON FOR SERVICES APARTMENTS, RESTAURANTS AND FOOD COURT PROJECT: CONSCIENT ONE DATED: 15 JULY 2013
S No PARAMETER AIR COOLED SPLIT SYSTEM WATER COOLED SPLIT SYSTEM AIR COOLED VRV SYSTEM AIR COOLED SCREW CHILLER WATER COOLED SCREW CHILLER
1 COMPONENTS
Indoor unit. Indoor unit. Indoor unit. Aircooled screw chillers. Watercooled screw chillers.
Aircooled outdoor unit. Watercooled condensing unit. Aircooled outdoor unit. Chilled water pumps. Chilled water pumps.
Refrigerant piping. Refrigerant piping. Refrigerant piping. Chilled water piping. Condenser water pumps.
Cooling towers. Electronic controls. Airhandling units / Fan coil units. Chilled water piping.
Condenser water pumps.
Condenser water piping.
Condenser water piping. Cooling towers.
Air Handling units / Fan coil units.
2 PHASE WISE INSTALLATION Possible Possible Possible Not Possible Not Possible
3 CAPITAL COST L1 L2 H H L3
4POWER CONSUMPTION HIGH LOW LOW Higher at full load LOW
IKW [Full Load] 1.35 kW/TR 1.1 kW/TR 1.2kW/TR 1.6 kW/TR 1.1 kW/TR
5 OPERATING COST
ICooling Requirement at 80% diversity 382 Tons 382 Tons 382 Tons 382 Tons 382 Tons
IIPower consumption 516 420 459 611 420
6 SPACE REQUIREMENT
IOPEN SPACE for ODUs Required Not Required Required Not Required Not Required
IIOPEN SPACE for PLANT Not Required Not Required Not Required Required Not Required
IIIOPEN SPACE for COOLING TOWERS Not Required Required.[for condenser pumps
also] Not Required Not Required Required
IVBASEMENT SPACE for PLANT Not Required Not Required Not Required Not Required Required
7 REFRIGERANT PIPING Length less than 15 m. Required Length 50m-100m. NA NA
8 BILLING Easiest Easy, only cooling towers and pumps are common.
Easy, in case of separate system for each user. Difficult due to common plant Difficult due to common plant
9 DERATION High in peak ambient conditions Low in peak ambient conditions High in peak ambient conditions High in peak ambient conditions Low in peak ambient conditions
10
SOFT WATER REQUIREMENT NA 8LPH/TR NA NA 8LPH/TR
TOTAL WATER REQUIREMENT/DAY (12 HOURS)
NA 36710 LITRES/DAY NA NA 36710 LITRES/DAY
11 RECOMMENDATIONSNot recommended due to non availability of open spaces for ODUs
Recommended for best efficiency and low capex if water is not scarce.
Not recommended due to non availability of open spaces for ODUs
Recommended due to water scarcity and good performance on part loads.
Recommended for best efficiency and low capex if water is not scarce.
CENTRALISED AC SYSTEM
ROOM FITTED WITH
DUCTS
EACH ROOM HAS FCU
EACH FLOOR HAS AHU
EACH BUILDING HAS COOLING TOWERS MOSTLY ON ROOFS
EACH BUILDING HAS CHILLERS MOSTLY IN
BASEMENTS
CENTRALISED AC SYSTEM
ROOM FITTED WITH
DUCTS
EACH ROOM HAS FCU
EACH FLOOR HAS AHU
EACH BUILDING HAS COOLING TOWERS MOSTLY ON ROOFS
EACH BUILDING HAS CHILLERS MOSTLY IN
BASEMENTS