brisb`ane water june operating manual road client

22
Brisb`ane Water Engineering Services OPERATING MANUAL FOR: Electrical Mechanical Water Meters 5 Bunya Street Eagle Farm Q 4009 Ph. (07) 3403 1849 Fx. (07) 3403 1898 WITTON ROAD /LAMBERT ROAD INDOOROOPILLY 375/600 DIA. RISING SEWER MAIN. CATHODIC PROTECTION SYSTEM CLIENT: DEPARTMENT OF WATER SUPPLY AND SEWERAGE SEWERAGE OPERATIONS BRANCH. 24th June 1966. Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual Q-Pulse Id TMS1321 Active 21/07/2015 Page 1 of 22

Upload: others

Post on 14-Jan-2022

3 views

Category:

Documents


0 download

TRANSCRIPT

Brisb`ane Water Engineering Services

OPERATING MANUAL FOR:

Electrical Mechanical Water Meters 5 Bunya Street Eagle Farm Q 4009

Ph. (07) 3403 1849 Fx. (07) 3403 1898

WITTON ROAD /LAMBERT ROAD INDOOROOPILLY 375/600 DIA. RISING SEWER MAIN.

CATHODIC PROTECTION SYSTEM

CLIENT:

DEPARTMENT OF WATER SUPPLY AND SEWERAGE SEWERAGE OPERATIONS BRANCH.

24th June 1966.

Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual

Q-Pulse Id TMS1321 Active 21/07/2015 Page 1 of 22

(1.0) Introduction (2.0) Corrosion and Cathodic Protection (3.0) Mains Details (4.0) Cathodic Protection (4.1) Type of System (4.2) Rectifier (4.3) Cathode (4.4) Anodes (4.5) Test Points (4.6) Associated Drawings (4.7) Associated Standards (4.8) Government Regulations (5.0) Peformed Testing (6.0) Conclusion (7.0). Maintenance

DRAWINGS

486%6/25- AA1C0021E Standard Rectifier Wiring Diagram

(No Number) Monthly Maintenance Program

Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual

Q-Pulse Id TMS1321 Active 21/07/2015 Page 2 of 22

(1.0) -.INTRODUCTION'

Steel when immersed or covered in water has a tendency to corrode (or rust) as the oxidized form is more stable than the metal.

Because of this, precaution must be taken to stop or minimize the corrosion reaction to an acceptable level consistent with the design life of the structure. This is normally achieved by the ùse of protective coatings which control the corrosion reaction by isolating the steel from its surrounding environment.

However, it is not practical to achieve a perfect coating and coating damage will always occur with time. Because of this, corrosion may occur at imperfections in the paint coating, causing further deterioration in the coating as well as loss of metal.

As a result of this, the coating defects must be rectified by periodic maintenance or an additional method of protection used to prevent this deterioration and corrosion occurring. This additional protection is achieved by the cathodic protection system.

(2.0) CORROSION AND CATHODIC PROTECTION

Corrosion is an electrochemical process in that it is accompanied by a flow of electrical current.

Corrosion occurs on the surface of metals at active areas known as an9des, which are electrically continuous with less active or passive areas known as cathodes. The electric current flows from the anode through the electrolyte to the cathode, with the circuit being completed by the electrical continuity between the cathode and anode. In practice anodes and cathodes are generally part of the same metallic surface and individual anodic areas may be small.

In applying cathodic protection and external current is applied to the surface so that the entire surface to be protected acts as a cathode. This involves the use of an auxiliary anode and when the current flow from this anode is sufficient, no part of the structure acts as an anode.

An external source of direct current such as a transformer rectifier is used in conjunction with an anode consisting of material with a very slow corrosion rate.

While it is the flow of current which achieves the cathodic protection of the surface it is impractical to measure these currents over individual anodic areas to determine when cathodic protection has been achieved. However, with the flow of cathodic protection current, the structure becomes more negative with respect to the surrounding electrolyte. Because of this, it is possible to state values of metal /electrolyte potential at which corrosion does not occur. This metal/electrolyte potential is generally measured against a standard reference electrode which allows a reproducible potential at which corrosion does not occur to be quoted.

Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual

Q-Pulse Id TMS1321 Active 21/07/2015 Page 3 of 22

(3.0) MAINS DET I S

Size: Dia 375/600 mild steel cement lined.

Coating: Tar Epoxy

Length: 2.00 km

Location: Witton Road Pumping Station to Lambert Rd. near Carnarvon St.

Construction Drawings:

3028/1053375 Dia. Witton Rd. Rising Main.

486/7/6- KIT0004E Witton/Lambert Rd Cathodic Protection System.

486/7/8- KI1C0005E_ Witton Rd.375 Dia. Rising Main C.P System.

Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual

Q-Pulse Id TMS1321 Active 21/07/2015 Page 4 of 22

(4.0) CATHODIC PROTECTION DETAILS

(4.1) Type of Cathodic Protection: Impressed Current.

(4.2) Rectifier: Special 32 Volt, 10 amp direct current output enclosed in a stainless steel switchboard. Rectifier has a 240V supply from the nearby Witton Rd. Submersible Sewerage Pumping Station.. With this system, the 100mm cast iron main in Kinloch St, there is a bleed and a bond on to the 375mm main by a 1.5

ohm resistor at the rectifier.

(4.3) Cathode: The cathode point is located on the 375 dia main adjacent to the submersible pump station. The cathode point is where the cabling from the rectifier is attached to the structure under cathodic protection.

(4.4) Anodes: Two 1500 x 75mm silicone iron anodes were installed approximately 210 metres from the trunk mains in a vertical bed at the end of Kinloch St. approx. 10 metres from the river bank. The anodes were firstly packaged with cokebreeze thereby improving anode - ground resistance. The anodes are identified by a marker post and label.

(4.5) Test Points: Test points are installed on cathodically protected structures to enable testing to ensure full protection of the mains. On these mains five test points have been installed for details see dwg no. CE02 /136.

(4.6)

(4.7)

Associated Drawings: Cathodic Protection Details - 2/14.213 Cathodic Protection Test Point Details - 2/14.199 Standard Rectifier Wiring Diagram - 486/6/25- AA1C0021E Vertical Ground bed Details - 486/6/25- AA1C0024E

Associated Standards: AS 3000 1986 Australia Wiring Rules AS 2832.1 1985 Pipes, Cables, Ducts, Guide to Cathodic Protection,

Part One.

(4.8) Government Regulations: Queensland Electricity Acts and Regulations.

5

Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual

Q-Pulse Id TMS1321 Active 21/07/2015 Page 5 of 22

(5.0) PERFORMED TESTING

(1) Natural Potential Survey.

(2) Testing of Insulated Flanges, Joints. -

(3) Soil Resistance Testing.

(4) Current Drain Survey.

(5) Pipe Coating Anomaly Survey.

(6) Rectifier Loop Resistance.

(7) Foreign Structure Interference Survey and Mitigation.

(8) Final Potential Survey and Commissioning.

(6.0) CONCLUSION

Full Cathodic protection has been achieved on this section of trunk mains. The cathodic protection system is registered with the Queensland Electricity Commission and has approval to operate.

(7.0) MAINTENANCE

The cathodic protection system is maintained on a monthly basis after commissioning. These checks involve testing rectifier operation and recording of pipe to soil potentials.

Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual

Q-Pulse Id TMS1321 Active 21/07/2015 Page 6 of 22

12th October 1992 Electrical Workshop Cathodic Protection

CPS Monthly Maintenance Details.

Required:

1/ . Notify plant operator and/or sign entry logs where necessary. 2/ Have appropriate keying.

Labour:

One tradesperson, one vehicle. 20 minutes per site.

Procedure:

1/ .Identify installation. 2/ Check system for operation. 3/ Record voltmeter. 4/ Record ammeter. 5/ Comments. 6/ Log entry.

Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual

Q-Pulse Id TMS1321 Active 21/07/2015 Page 7 of 22

13th October 1992 Electrical Workshop Cathodic Protection

CPS 6 Monthly Maintenance Details.

Required:

1/ Notify plant operator and/or sign entry logs where necessary. 2/ Have appropriate keying. 3/ Set of tools. (Electricians) 4/ Multimeter. 5/ DC clampmeter. 6/ Copper sulphate reference cell and leads. 7/ Cleaning equipment. 8/ Gatic cover lifters.

Labour:

One tradesperson electrical, one laborer, one vehicle. Two hours per site.

Procedure:

1/ Identify system. 2/ Check system for operation. 3/ Record voltmeter. 4/ Record ammeter. 5/ Record "on" potentials for all test points. 6/ Record "instant off" potentials for all test points. 7/ Record "off" potentials for all test points. 8/ Perform loop resistance and record. 9/ Check and record anode string currents. 10/ Comments. 11/ Log entry.

Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual

Q-Pulse Id TMS1321 Active 21/07/2015 Page 8 of 22

13th October 1992 Electrical Workshop Cathodic Protection

CPS 60 Monthly Maintenance Details.

Required:

1/ Notify plant operator and/or sign entry logs where necessary. 2/ Have appropriate keying. 3/ Set of tools. (Electricians) 4/ Multimeter. 5/ DC clampmeter. 6/ Copper sulphate reference cell and leads. 7/ Cleaning equipment. 8/ Gatic cover lifters. 9/ Rectifier load bank. 10/ PCS2000 Detection Equipment.

Labour:

One tradesperson electrical, one laborer, one vehicle. Eight hours per site.

Procedure:

1/ Identify system. 2/ Check system for operation. 3/ Record voltmeter. 4/ Record ammeter. 5/ Record "on" potentials for all test points. 6/ Record "instant off" potentials for all test points. 7/ Record "off" potentials for all test points. 8/ . Perform loop resistance and record. 9/ Check and record anode string currents. 10/ Load test rectifier for 10 minutes. 11/ Check all switchboard and testpoint terminals for tightness. 12/ Check all switchboard and testpoints are labelled and I.D. tags attached. 13/ Check plans are correctly drawn and modify if necessary. 14/ Remove and inspect anodes. 15/ Recheck all interference (CPS) bleeds. 16/ Pipecamp structure if applicable. 17/ Apply for "continue to operate" permit if applicable.

Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual

Q-Pulse Id TMS1321 Active 21/07/2015 Page 9 of 22

Brisbane Water Engineering Services - Ph. 34031838 Fx. 34031839 5 Bunya Street

Eagle Farm Q 4009 Electrical Engineering Unit

Cathodic Protection System Loop Resistance

Date: 27th JUNE 1996 Cathodic Protection System: System Operating Volts:

12

10

8

4

2

o

Witton Rd.- Lambert Rd. Rising Sewer Main 14.5 System Operating amps 6.2

Test Voltage: Test Current: (volts) (amps)

2

4

8 10

< `° '.`. :

ti .

0.3 1.2' 2. 1

3.1 4

,,

Loop Resistance (ohms)

2.105263

Graph of System voltage vs current.

o 2

Current (amps) 3 4 5

06/20/96 LOOPWITT.WK4

Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual

Q-Pulse Id TMS1321 Active 21/07/2015 Page 10 of 22

Brisbane Water Engineering Services CP Form No. 23

Electrical Engineering Unit

Cathodic Protection System Potential Recording Form

Project Wilton Rd. /Lambert Rd. Rising Sewer Main Date 24th June 1996

o

-500

Test Point number

Distances to T.P.

Potentials to CuSO4 Resistivities at 2 metres Natural Off On

(metres) (mV) (mV) (mV) (ohm.metres) 1 0 -490 -590 -1136 13.81 2 300 -596 -605 -1295 9.92 3 700 -592 -627 -1026 10.06 4 1500 -471 -505 -850 16.32 5 0 2000 -475 -527 -865 11.49 6 7 8 9

10 11

12 13 .

14

Graph of potentials and resistivity vs pipelength

-1500

-2000 0 300 700 1500 2000

Distance (metres)

Natural Off

Rectifier located at OM,

A On 8 -850mV Resistivity

500

400

300

200

100

o

Revision 06/26/96

Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual

Q-Pulse Id TMS1321 Active 21/07/2015 Page 11 of 22

Brisbane Water Engineering Services

Electrical Engineering Unit

Cathodic Protection Interference Survey Results Form

CP Form No. 27

Project Unit Reading .L4. 3 .tl....6.:7- ct Date 2,9.-.5' tï,á.

Reading Test Point I. D.

Location Swing

On--54.3 SP /3 4-ui G St Off -3tT0

On -c;, b c. W c.4.a,". Off -5.40 )416:A0A., l-IOtxSt- I p tt.aiF St On - 472 weArker Off -4 3 0 >1 Ai h /4 o c.l. S t 12 -ro . I G+ S -f . On - /S (, $ ccr-c4.

- -

Off - G o-ie 144_4 Pok 3 I (..) i-4} or\ 1lú

On -7 3 / (Zoo-a Off _ 72 3 {lG.:. l tZoo-a tlt t ....) :kk on R J

On -'44e Ma,ul Off -4 o 2 (Rc.... l{-I aN a(l,o...l u.-M hall On -G 12 t,Jc.,A.t.v

Off - 55 o 1.4c.:tit l-Eor,c.S -e- I -h.) ì G S1-

On -4.g6 Se th Off - C. men Pc, - 11-g990 -t-c.. c.sr On --4- S 7 SeltiJ Off ,44 S r1t.tt- Pof1 l 544 44 7 fcJ14St- On -G 12- HgvcJ'

Off -G ! 3 (kck. l i3rìc,15 -e, St On -- 4444 ' IMtù,h / / Off -lÿ S`JCJ itl!G-ZQ- Schtl On - 32. g TYaKSfvrl J V

Off - 329 ?4 .e.,n. id e. St .

On - 3 4 Seq,..h _et

Off - 3 XU,. Pole- 316/0 8ri&15tSF

On

Off

On

Off

TESTED BY 1 s'in vil,/

Revision 09/28/95

Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual

Q-Pulse Id TMS1321 Active 21/07/2015 Page 12 of 22

Brisbane Water Engineering Services cP For, No.18

Electrical Engineering Unit

Standard Cathodic Protection Test Point Data Gathering Form

Project .. IA/ Ci-k" Ík a'

T P Location SAM11). StAk 4.Q W if 014 It

Mains Size

Date 2:7- ç

TP No i

T P Type C.o up ay,

POTENTIAL TESTING

CATHODE TO CATHODE RETURN (RESISTANCE) ZINC REFERENCE TO PIPE CuSo4 REFERENCE TO PIPE ZINC TO CuSo4

EARTH TESTING TEST NO. 1

PIN SPACING MEGGER READING

Itc R.. + rm. n pvd - . 4.4'10 w

qqo Mr/

RESISTIVITY i 3 p6

TEST NO 2 PIN SPACING Erh RESISTIVITY 2 °/ - 3 MEGGER READING - q' 3

TEST NO 3

PIN SPACING MEGGER READING

COMMENTS / LOCATION DRAWING

RESISTIVITY

v o 1vt +o f e,f + r(Ar.+ a.. o

Loc,ror. eS. Poì.f

RS l --5 161 4

INSTALLED BY

Revision 09/28/95

Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual

Q-Pulse Id TMS1321 Active 21/07/2015 Page 13 of 22

Brisbane Water Engineering Services CP Form No.18

Electrical Engineering Unit

Standard Cathodic Protection Test Point Data Gathering Form

Project ...l,t.t. ana. Íß vk Date 12-7

T P Location ....a.a.a.16.0 & Ç e-e-k T P No. 2. Mains Size T P Type ...1.

POTENTIAL TESTING

CATHODE TO CATHODE RETURN (RESISTANCE) ZINC REFERENCE TO PIPE CuSo4 REFERENCE TO PIPE ZINC TO CuSo4

EARTH TESTING TEST NO. 1

PIN SPACING 2.I44 MEGGER READING 7 go

TEST NO 2 PIN SPACING MEGGER READING

TEST NO 3 PIN SPACING MEGGER READING

1.- Golfs

A sì r.5 Matte. RESISTIVITY

-4 JL

RESISTIVITY ci "7 Z 2 JU

RESISTIVITY 2 1 ,5o of

COMMENTS / LOCATION DRAWING

C r

Ga}ko IAA. Poivt

fcs 4-

Po i n}

Ro..(1h0 - St

(kac.i1

( O O M 4- o

-rei t Po .,ft- 3 .

INSTALLED BY r S11191-14.

Revision 09/28/95

Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual

Q-Pulse Id TMS1321 Active 21/07/2015 Page 14 of 22

Brisbane Water Engineering Services CP Form No.18

Electrical Engineering Unit

Standard Cathodic Protection Test Point Data Gathering Form

Project ..hl iti Q.h......R

TP Location C 174Mbc.rt a- G rtc1voNt

Mains Size

Date 11- g - 16'

TPNo. 3

T P Type a

POTENTIAL TESTING

CATHODE TO CATHODE RETURN (RESISTANCE) ' Y.Sl., ZINC REFERENCE TO PIPE -I.4 99 s+

CuSo4 REFERENCE TO PIPE wt v ZINC TO CuSo4 g¡ rn

EARTH TESTING TEST NO. 1

PIN SPACING MEGGER READING

TEST NO 2 PIN SPACING MEGGER READING

TEST NO 3 PIN SPACING MEGGER READING

771

COMMENTS / LOCATION DRAWING

RESISTIVITY / c1 j(_,

RESISTIVITY ZLA 3' j RESISTIVITY

d.aim e vfi

te S+ Va\v-

once. A inct-1"twk .

C44kocte.._Po; hC

INSTALLED BY p. S7/911-1,

Revision 09/28/95

Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual

Q-Pulse Id TMS1321 Active 21/07/2015 Page 15 of 22

Brisbane Water Engineering Services

Electrical Engineering Unit

Cathodic Protection Interference Survey Results Form

CP Form No. 27

Project .(d. 4 0 Ni La) Unit Reading I'Ì Y 5.C4 Date Z.0 -10, ̀ l Ía.

Reading Test Point I. D.

Location Swing

On -367 Atm? c - e.- we kc,.

PìP-c Off -397 On - r 7 w -rl- o a sz.y

S ea, -c, P s 1-e.- ho I 2."5-W Off - 50-b On --5 o

INc. -c.vL YiaR. v.. II Off --- '5C9f On -33'3 wi...4 S Fil okN

w°' --t-c& r. Ahock L Off -355 On - 55 S ` Avlok

Fence 5M- 4--e_ter Pf,tui .2 Off - s s s On

Off

On

Off

On

Off

On

Off

On

Off

On

Off

On -

Off

On

Off

On

Off

On

Off

TESTED BY

Revision 09/28/95

Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual

Q-Pulse Id TMS1321 Active 21/07/2015 Page 16 of 22

Brisbane Water Engineering Services - cP Form No. 17

Electrical Engineering Unit

Cathodic Protection Anode Bed Testing _

Project V- tko ti cl Date i - 7-1(.7

ANODE MATERIAL: S'1 4 /e04' 144,2V BURIAL: 1, rr'ui4- 4v'Z c 1,-k

ANODE SIZE/WEIGHT: /5oox75;,,, G,vsr,.e j 7,rie- TEST POINT TYPE: P-r ANODE PACKAGING: SOIL RESISTIVITY:

ANODE DEPTH: .SAO ,vl SIGNAGE: r RESISTANCE TO GROUND: ANODE CURRENT

ANODE NO.1 2. G iL ANODE No.1 2 - 6 4. i. -. r s

ANODE No.2 2 t. f JL - -- - ANODE No.2 3 ,,,r a ,^^

ANODE No.3 ANODE No.3 ANODE No.4 ANODE No.4 ANODE No.5 ANODE No.5

TOTAL 3 o .1 i. TOTAL G i co ",, r s

LOCATION DRAWING

TESTED BY P 5 711.1 111

Revision 09/28/95

Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual

Q-Pulse Id TMS1321 Active 21/07/2015 Page 17 of 22

Brisbane Water Engineering Services CP Form No.18

Electrical Engineering Unit

Standard Cathodic Protection Test Point Data Gathering Form

Project W oh .cL Date ..l 3 94

T P Location 1Nht t+ c tci" y D Ort a/ 4- T P No. ..3

Mains Size T P Type 13

POTENTIAL TESTING

CATHODE TO CATHODE RETURN (RESISTANCE) ZINC REFERENCE TO PIPE CuSo4 REFERENCE TO PIPE ZINC TO CuSo4

EARTH TESTING TEST NO. 1

PIN SPACING MEGGER READING

TEST NO 2 PIN SPACING MEGGER READING

TEST NO 3 PIN SPACING MEGGER READING

gol

3+ 4vc9

COMMENTS / LOCATION DRAWING

RESISTIVITY U p ,JL_

RESISTIVITY I % -A_

RESISTIVITY

vo r ko ke(á- Poi-,+ 4

W al4-tfie 4'0,.¡fo R.

13i,a5

+ejf C-4ó0; } o Point IZi0%,

r1 te

INSTALLED BY r . 57-1 y n Revision 09/28/95

Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual

Q-Pulse Id TMS1321 Active 21/07/2015 Page 18 of 22

Brisbane Water Engineering Services CP Form No.18

Electrical Engineering Unit

Standard Cathodic Protection Test Point Data Gathering Form

Project ..b 1':fk4.I,....g,sL Date ...fit- r q 4

T P Location .Iroan% /14" T P No. if-

Mains Size T P Type ß.

POTENTIAL TESTING

CATHODE TO CATHODE RETURN (RESISTANCE) - '3 Jl. ZINC REFERENCE TO PIPE -?- 713 CuSo4 REFERENCE TO PIPE - ZINC TO CuSo4 gg6

EARTH TESTING TEST NO. 1

PIN SPACING MEGGER READING

TEST NO 2 PIN SPACING MEGGER READING

TEST NO 3 PIN SPACING MEGGER READING

+ RESISTIVITY /6.32 I.3

"S. kA. q COMMENTS / LOCATION DRAWING

RESISTIVITY Z G'l

RESISTIVITY

Fr,4c.c. pI«Ms`'1

L.A M g G-'t

}'GS+ Poh} Ca-il,oa4.-

7 p >trco-1 -t cJ- Pov.t T cA0oú4.. J

yv o M .I-o 4p-t 11- Pat -t

INSTALLED BY P. Sli i

Revision 09/28/95

Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual

Q-Pulse Id TMS1321 Active 21/07/2015 Page 19 of 22

WIT TON ROAD

PUMPING STATION

?

L" CI RISING MAIN

4" CI RISING MAIN RANOR. STREET

PUMPING STATION

KINLOCH STREET

PUMPING STATION

WALTER TAY! OR

ERIOCE

21," DIA LAMBERT RC

RISING MAIN

MANAGER DIRECTOR OF PLANNING & DESIGN

DESIGN J.SAY 2.9.94

DRAWN R.LIS TON 2.9.9 4

PROJECT

WITTON ROAD

PUMP STATION

0 31.10.94

No DATE

ISSUED FOR CONSTRUCTION

AMENDMENT

DATE:

DIRECTOR OF

CONSTRUCTION

R.L.

BY DATE:

DATE:

DIRECTOR OF

M & E SERVICES

DATE:

DIRECTOR OF SEW. OPERATIONS /W.S. DISTRIBUTION

DATE:

C i_CKED

ENGINEER IN CHARGE

TITLE

375mmDIA RISING MAIN

C.P. SYSTEM

Brisbane My

BRISBANE CITY COUNCIL

DEPARTMENT OF WATER SUPPLY

AND SEWERAGE

MECHANICAL & ELECTRICAL SERVICES

SCALE: NTS Nc. 1 OF i SHEETS

SUPERVISING ENGINEER

CADO FILE No. 78C0005-

DRAWING No.

486/7/8-KI1C0005E AMEND.

0

Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual

Q-Pulse Id TMS1321 Active 21/07/2015 Page 20 of 22

2 3

1

10 .

1

18

19

20

. 21

D

22

23

24

25

1111r-' 26

E

F

27

29

29

30

31

32

33.

34

36

37

38

M

timPotia, N\ \If ;

mat

/ 1 I

N -4

0

ttoeAS PPE MON-PtTALIU

--- ____ '

5 s 7 8

4»iaIIIIiiiir" - - --

LA `M-@ER-T

; $ ti

E

= tr fta. s ST

r

NOTES

0 4.96 ISSUED FOR APPROVAL O.L.P.

No DATE AMENDENT INITIALS

AMENDENT & ISSUE REGISTER MANAGER

DATE:

DIRECTOR OF

TECHNOLOGY SERVICES

DATE:

DIRECTOR CF

PLANNING & DESIGN

DATE:

DIRECTOR OF

WATER SUPPLY

DATE:

DIRECTOR OF

CONSTRUCTION

DATE:

DESIGN J.S. 72.496 ENGINEER IN CHARGE

DRAWN O.L.P. 23.4.96 SUPERVISING ENGINEER

TRACED

DECKED

REFERENCES

A2 REDUCED

CALO FLE No. 76T00040 THIS DRAWING WAS PRODUCED

USING QIImRAW

A

B

c

D

COPYRIGHT ® 1996 No repoduction is permitted in whole or in part without

the express consent of BRISBANE CITY COUNCIL.

BRISBANE WATER

Etfasete guuu

BRISBANE CITY COUNCIL

BRISBANE WATER TECHNOLOGY SERVICES BRANCH

INFORMATION TECHNOLOGY

PROJECT:

WITTON / LAMBERT RD. RISING MAIN C.P. SYSTEM

TITLE

CATHODIC PROTECTION TEST POINT DETAILS

SCALE: N.T.S. No. 2 OF 2 SHEETS

DRAWING No.

486/7/6-KIT0004E AMEND.

0 2 3 4 5 6 7

E

F

8

Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual

Q-Pulse Id TMS1321 Active 21/07/2015 Page 21 of 22

IIIIL11111

10 11 12 1 16 1 18 20 21 22 24 2

A

G.P.O. x ic RECTIFIER C/B 10A UNIT C/B

10A

VARISTOR TO DATA LOGGER

N

i

o N/L

NEON 11 W

Kl u u

REMOTE INTERUPT

2 ® Y

INTERUPT SWITCH

NOTES

14

Ls

14

a

VARIAC

TRANSFORMER GAYRAD (SEE NOTE 1)

u O Q) ih ti

DIODE FUSE 25A

TRANSFORMER OUTPUT CURRENT & VOLTAGE

TO SUIT APPLICATION PROVIDING SUITABLE

RESOLUTION I CONTROL

' AMMETER & VOLTMETER TO PROVIDE

SUITABLE RESOLUTION FOR SYSTEM

+ POSITIVE WIRING TO BE RED

- NEGATIVE WIRING TO BE BLACK

L.V. AC WIRING TO BE 4nn2 SLUE /WHITE

DC WIRING TO BE 4nn2

240V AC WIRING TO BE 1.5nn2- BROWN /BLACK REFERENCE.WIRING TO BE 1.5nn2 -GREY

LEGEND

BRIDGE

ti

3:

ECTIFIER UNIT

+VE

C ; - J -. -

VARISTOR

0 EVE OUTPUT SEE NOTE

AMMETER

-VE

-VE

31

50

30

VOLTMETER

TERMINALS WITH 4nn TEST PLUG SOCKETS

KI - 240V RELAY

K2,K3, & K4 - 24V DC RELAYS

RI - SHUNT RESISTOR (SIZED TO PRODUCE A VV DROP AT FULL LOAD)

R2,R3 - VOLTAGE DIVIDER (SIZED TO PRODUCE A VOLTAGE OF 10V ACROSS R2 AT MAX. OUTPUT VOLTAGE)

+VE AND -VE DC FUSES TO BE SIZED APPROX. 5AMPS ABOVE NORMAL OUTPUT CURRENT

a

K4.i. i COUPON DISCONNECT

n n m

\.K3.1

tR$R

Ii z W

w á. z O Ó Ó W + U U C W Z. UNN1_1Q

Z WJáJ U Q

O cc z çIYZUZ Z W W W <LI-1.1- WO WO Col CCdCVd

TO TELEMETRY EQUIPMEN-

íó

n

K2 K3

K4

C4T1R0: Ra EC TURN

=PON [LEO

IDe REF CCOLPnO

CuSe4 TEST CWRLTImt

BANANA PLUG SOCKETS ON FRONT PANEL

11111!MMIN

W J m

Zn

U c L./m

óU a \ U á>

Ua W > z d N

E U £ > 431 ZO J ZC- UW É Z E

ZU

ÓÓ 2 < cçn C-3

< C

W ~ Ú

Z ç z LI L IJ ._ Li W 0 Ú W r- <ú - W 01Y

LJ N U D GL

L. -- z ÿW Uv . N d , '

COUPON TNPE REFERENCE

R.L. 11B.1C.93 CHANGES AS SHOWN

D R:.. 25.8.93 ISSUED FOR CONSTRUCTION

BY DATE REVISION _HECK APPR

-`-;\! 1 C . SBn NL- CITY COUNCIL

DEPARTMENT OF WATER SUPPLY & SEWERAGE

_CHANICAL & ELECTRICAL SERVICES

P?O_:ECT

STANDARD CATHODIC PROTECTION

DRAWN µyç .lAic R.C. 3.8.53

T:ST POINT TERMINALS FOR REMOTE RECTIFIER SITES

SUPER ENG. NAME WIZ .SCAL M.-I. 213.8.93

. DESIGN J..1. 3.8 93

TIT¿!_ RECTIFIER UNIT WITH DATA LOGGING FACILITIES WIRING DIAGRAM

CHcCKcD, JS. 25.8.53

DRAWING Na.

-^. 86/6/25-AAIC0021E

SENIOR ENG.

ELECT. ENG.

4040212 FILE s

A625C21

Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual

Q-Pulse Id TMS1321 Active 21/07/2015 Page 22 of 22