brisb`ane water june operating manual road client
TRANSCRIPT
Brisb`ane Water Engineering Services
OPERATING MANUAL FOR:
Electrical Mechanical Water Meters 5 Bunya Street Eagle Farm Q 4009
Ph. (07) 3403 1849 Fx. (07) 3403 1898
WITTON ROAD /LAMBERT ROAD INDOOROOPILLY 375/600 DIA. RISING SEWER MAIN.
CATHODIC PROTECTION SYSTEM
CLIENT:
DEPARTMENT OF WATER SUPPLY AND SEWERAGE SEWERAGE OPERATIONS BRANCH.
24th June 1966.
Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual
Q-Pulse Id TMS1321 Active 21/07/2015 Page 1 of 22
(1.0) Introduction (2.0) Corrosion and Cathodic Protection (3.0) Mains Details (4.0) Cathodic Protection (4.1) Type of System (4.2) Rectifier (4.3) Cathode (4.4) Anodes (4.5) Test Points (4.6) Associated Drawings (4.7) Associated Standards (4.8) Government Regulations (5.0) Peformed Testing (6.0) Conclusion (7.0). Maintenance
DRAWINGS
486%6/25- AA1C0021E Standard Rectifier Wiring Diagram
(No Number) Monthly Maintenance Program
Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual
Q-Pulse Id TMS1321 Active 21/07/2015 Page 2 of 22
(1.0) -.INTRODUCTION'
Steel when immersed or covered in water has a tendency to corrode (or rust) as the oxidized form is more stable than the metal.
Because of this, precaution must be taken to stop or minimize the corrosion reaction to an acceptable level consistent with the design life of the structure. This is normally achieved by the ùse of protective coatings which control the corrosion reaction by isolating the steel from its surrounding environment.
However, it is not practical to achieve a perfect coating and coating damage will always occur with time. Because of this, corrosion may occur at imperfections in the paint coating, causing further deterioration in the coating as well as loss of metal.
As a result of this, the coating defects must be rectified by periodic maintenance or an additional method of protection used to prevent this deterioration and corrosion occurring. This additional protection is achieved by the cathodic protection system.
(2.0) CORROSION AND CATHODIC PROTECTION
Corrosion is an electrochemical process in that it is accompanied by a flow of electrical current.
Corrosion occurs on the surface of metals at active areas known as an9des, which are electrically continuous with less active or passive areas known as cathodes. The electric current flows from the anode through the electrolyte to the cathode, with the circuit being completed by the electrical continuity between the cathode and anode. In practice anodes and cathodes are generally part of the same metallic surface and individual anodic areas may be small.
In applying cathodic protection and external current is applied to the surface so that the entire surface to be protected acts as a cathode. This involves the use of an auxiliary anode and when the current flow from this anode is sufficient, no part of the structure acts as an anode.
An external source of direct current such as a transformer rectifier is used in conjunction with an anode consisting of material with a very slow corrosion rate.
While it is the flow of current which achieves the cathodic protection of the surface it is impractical to measure these currents over individual anodic areas to determine when cathodic protection has been achieved. However, with the flow of cathodic protection current, the structure becomes more negative with respect to the surrounding electrolyte. Because of this, it is possible to state values of metal /electrolyte potential at which corrosion does not occur. This metal/electrolyte potential is generally measured against a standard reference electrode which allows a reproducible potential at which corrosion does not occur to be quoted.
Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual
Q-Pulse Id TMS1321 Active 21/07/2015 Page 3 of 22
(3.0) MAINS DET I S
Size: Dia 375/600 mild steel cement lined.
Coating: Tar Epoxy
Length: 2.00 km
Location: Witton Road Pumping Station to Lambert Rd. near Carnarvon St.
Construction Drawings:
3028/1053375 Dia. Witton Rd. Rising Main.
486/7/6- KIT0004E Witton/Lambert Rd Cathodic Protection System.
486/7/8- KI1C0005E_ Witton Rd.375 Dia. Rising Main C.P System.
Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual
Q-Pulse Id TMS1321 Active 21/07/2015 Page 4 of 22
(4.0) CATHODIC PROTECTION DETAILS
(4.1) Type of Cathodic Protection: Impressed Current.
(4.2) Rectifier: Special 32 Volt, 10 amp direct current output enclosed in a stainless steel switchboard. Rectifier has a 240V supply from the nearby Witton Rd. Submersible Sewerage Pumping Station.. With this system, the 100mm cast iron main in Kinloch St, there is a bleed and a bond on to the 375mm main by a 1.5
ohm resistor at the rectifier.
(4.3) Cathode: The cathode point is located on the 375 dia main adjacent to the submersible pump station. The cathode point is where the cabling from the rectifier is attached to the structure under cathodic protection.
(4.4) Anodes: Two 1500 x 75mm silicone iron anodes were installed approximately 210 metres from the trunk mains in a vertical bed at the end of Kinloch St. approx. 10 metres from the river bank. The anodes were firstly packaged with cokebreeze thereby improving anode - ground resistance. The anodes are identified by a marker post and label.
(4.5) Test Points: Test points are installed on cathodically protected structures to enable testing to ensure full protection of the mains. On these mains five test points have been installed for details see dwg no. CE02 /136.
(4.6)
(4.7)
Associated Drawings: Cathodic Protection Details - 2/14.213 Cathodic Protection Test Point Details - 2/14.199 Standard Rectifier Wiring Diagram - 486/6/25- AA1C0021E Vertical Ground bed Details - 486/6/25- AA1C0024E
Associated Standards: AS 3000 1986 Australia Wiring Rules AS 2832.1 1985 Pipes, Cables, Ducts, Guide to Cathodic Protection,
Part One.
(4.8) Government Regulations: Queensland Electricity Acts and Regulations.
5
Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual
Q-Pulse Id TMS1321 Active 21/07/2015 Page 5 of 22
(5.0) PERFORMED TESTING
(1) Natural Potential Survey.
(2) Testing of Insulated Flanges, Joints. -
(3) Soil Resistance Testing.
(4) Current Drain Survey.
(5) Pipe Coating Anomaly Survey.
(6) Rectifier Loop Resistance.
(7) Foreign Structure Interference Survey and Mitigation.
(8) Final Potential Survey and Commissioning.
(6.0) CONCLUSION
Full Cathodic protection has been achieved on this section of trunk mains. The cathodic protection system is registered with the Queensland Electricity Commission and has approval to operate.
(7.0) MAINTENANCE
The cathodic protection system is maintained on a monthly basis after commissioning. These checks involve testing rectifier operation and recording of pipe to soil potentials.
Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual
Q-Pulse Id TMS1321 Active 21/07/2015 Page 6 of 22
12th October 1992 Electrical Workshop Cathodic Protection
CPS Monthly Maintenance Details.
Required:
1/ . Notify plant operator and/or sign entry logs where necessary. 2/ Have appropriate keying.
Labour:
One tradesperson, one vehicle. 20 minutes per site.
Procedure:
1/ .Identify installation. 2/ Check system for operation. 3/ Record voltmeter. 4/ Record ammeter. 5/ Comments. 6/ Log entry.
Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual
Q-Pulse Id TMS1321 Active 21/07/2015 Page 7 of 22
13th October 1992 Electrical Workshop Cathodic Protection
CPS 6 Monthly Maintenance Details.
Required:
1/ Notify plant operator and/or sign entry logs where necessary. 2/ Have appropriate keying. 3/ Set of tools. (Electricians) 4/ Multimeter. 5/ DC clampmeter. 6/ Copper sulphate reference cell and leads. 7/ Cleaning equipment. 8/ Gatic cover lifters.
Labour:
One tradesperson electrical, one laborer, one vehicle. Two hours per site.
Procedure:
1/ Identify system. 2/ Check system for operation. 3/ Record voltmeter. 4/ Record ammeter. 5/ Record "on" potentials for all test points. 6/ Record "instant off" potentials for all test points. 7/ Record "off" potentials for all test points. 8/ Perform loop resistance and record. 9/ Check and record anode string currents. 10/ Comments. 11/ Log entry.
Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual
Q-Pulse Id TMS1321 Active 21/07/2015 Page 8 of 22
13th October 1992 Electrical Workshop Cathodic Protection
CPS 60 Monthly Maintenance Details.
Required:
1/ Notify plant operator and/or sign entry logs where necessary. 2/ Have appropriate keying. 3/ Set of tools. (Electricians) 4/ Multimeter. 5/ DC clampmeter. 6/ Copper sulphate reference cell and leads. 7/ Cleaning equipment. 8/ Gatic cover lifters. 9/ Rectifier load bank. 10/ PCS2000 Detection Equipment.
Labour:
One tradesperson electrical, one laborer, one vehicle. Eight hours per site.
Procedure:
1/ Identify system. 2/ Check system for operation. 3/ Record voltmeter. 4/ Record ammeter. 5/ Record "on" potentials for all test points. 6/ Record "instant off" potentials for all test points. 7/ Record "off" potentials for all test points. 8/ . Perform loop resistance and record. 9/ Check and record anode string currents. 10/ Load test rectifier for 10 minutes. 11/ Check all switchboard and testpoint terminals for tightness. 12/ Check all switchboard and testpoints are labelled and I.D. tags attached. 13/ Check plans are correctly drawn and modify if necessary. 14/ Remove and inspect anodes. 15/ Recheck all interference (CPS) bleeds. 16/ Pipecamp structure if applicable. 17/ Apply for "continue to operate" permit if applicable.
Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual
Q-Pulse Id TMS1321 Active 21/07/2015 Page 9 of 22
Brisbane Water Engineering Services - Ph. 34031838 Fx. 34031839 5 Bunya Street
Eagle Farm Q 4009 Electrical Engineering Unit
Cathodic Protection System Loop Resistance
Date: 27th JUNE 1996 Cathodic Protection System: System Operating Volts:
12
10
8
4
2
o
Witton Rd.- Lambert Rd. Rising Sewer Main 14.5 System Operating amps 6.2
Test Voltage: Test Current: (volts) (amps)
2
4
8 10
< `° '.`. :
ti .
0.3 1.2' 2. 1
3.1 4
,,
Loop Resistance (ohms)
2.105263
Graph of System voltage vs current.
o 2
Current (amps) 3 4 5
06/20/96 LOOPWITT.WK4
Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual
Q-Pulse Id TMS1321 Active 21/07/2015 Page 10 of 22
Brisbane Water Engineering Services CP Form No. 23
Electrical Engineering Unit
Cathodic Protection System Potential Recording Form
Project Wilton Rd. /Lambert Rd. Rising Sewer Main Date 24th June 1996
o
-500
Test Point number
Distances to T.P.
Potentials to CuSO4 Resistivities at 2 metres Natural Off On
(metres) (mV) (mV) (mV) (ohm.metres) 1 0 -490 -590 -1136 13.81 2 300 -596 -605 -1295 9.92 3 700 -592 -627 -1026 10.06 4 1500 -471 -505 -850 16.32 5 0 2000 -475 -527 -865 11.49 6 7 8 9
10 11
12 13 .
14
Graph of potentials and resistivity vs pipelength
-1500
-2000 0 300 700 1500 2000
Distance (metres)
Natural Off
Rectifier located at OM,
A On 8 -850mV Resistivity
500
400
300
200
100
o
Revision 06/26/96
Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual
Q-Pulse Id TMS1321 Active 21/07/2015 Page 11 of 22
Brisbane Water Engineering Services
Electrical Engineering Unit
Cathodic Protection Interference Survey Results Form
CP Form No. 27
Project Unit Reading .L4. 3 .tl....6.:7- ct Date 2,9.-.5' tï,á.
Reading Test Point I. D.
Location Swing
On--54.3 SP /3 4-ui G St Off -3tT0
On -c;, b c. W c.4.a,". Off -5.40 )416:A0A., l-IOtxSt- I p tt.aiF St On - 472 weArker Off -4 3 0 >1 Ai h /4 o c.l. S t 12 -ro . I G+ S -f . On - /S (, $ ccr-c4.
- -
Off - G o-ie 144_4 Pok 3 I (..) i-4} or\ 1lú
On -7 3 / (Zoo-a Off _ 72 3 {lG.:. l tZoo-a tlt t ....) :kk on R J
On -'44e Ma,ul Off -4 o 2 (Rc.... l{-I aN a(l,o...l u.-M hall On -G 12 t,Jc.,A.t.v
Off - 55 o 1.4c.:tit l-Eor,c.S -e- I -h.) ì G S1-
On -4.g6 Se th Off - C. men Pc, - 11-g990 -t-c.. c.sr On --4- S 7 SeltiJ Off ,44 S r1t.tt- Pof1 l 544 44 7 fcJ14St- On -G 12- HgvcJ'
Off -G ! 3 (kck. l i3rìc,15 -e, St On -- 4444 ' IMtù,h / / Off -lÿ S`JCJ itl!G-ZQ- Schtl On - 32. g TYaKSfvrl J V
Off - 329 ?4 .e.,n. id e. St .
On - 3 4 Seq,..h _et
Off - 3 XU,. Pole- 316/0 8ri&15tSF
On
Off
On
Off
TESTED BY 1 s'in vil,/
Revision 09/28/95
Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual
Q-Pulse Id TMS1321 Active 21/07/2015 Page 12 of 22
Brisbane Water Engineering Services cP For, No.18
Electrical Engineering Unit
Standard Cathodic Protection Test Point Data Gathering Form
Project .. IA/ Ci-k" Ík a'
T P Location SAM11). StAk 4.Q W if 014 It
Mains Size
Date 2:7- ç
TP No i
T P Type C.o up ay,
POTENTIAL TESTING
CATHODE TO CATHODE RETURN (RESISTANCE) ZINC REFERENCE TO PIPE CuSo4 REFERENCE TO PIPE ZINC TO CuSo4
EARTH TESTING TEST NO. 1
PIN SPACING MEGGER READING
Itc R.. + rm. n pvd - . 4.4'10 w
qqo Mr/
RESISTIVITY i 3 p6
TEST NO 2 PIN SPACING Erh RESISTIVITY 2 °/ - 3 MEGGER READING - q' 3
TEST NO 3
PIN SPACING MEGGER READING
COMMENTS / LOCATION DRAWING
RESISTIVITY
v o 1vt +o f e,f + r(Ar.+ a.. o
Loc,ror. eS. Poì.f
RS l --5 161 4
INSTALLED BY
Revision 09/28/95
Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual
Q-Pulse Id TMS1321 Active 21/07/2015 Page 13 of 22
Brisbane Water Engineering Services CP Form No.18
Electrical Engineering Unit
Standard Cathodic Protection Test Point Data Gathering Form
Project ...l,t.t. ana. Íß vk Date 12-7
T P Location ....a.a.a.16.0 & Ç e-e-k T P No. 2. Mains Size T P Type ...1.
POTENTIAL TESTING
CATHODE TO CATHODE RETURN (RESISTANCE) ZINC REFERENCE TO PIPE CuSo4 REFERENCE TO PIPE ZINC TO CuSo4
EARTH TESTING TEST NO. 1
PIN SPACING 2.I44 MEGGER READING 7 go
TEST NO 2 PIN SPACING MEGGER READING
TEST NO 3 PIN SPACING MEGGER READING
1.- Golfs
A sì r.5 Matte. RESISTIVITY
-4 JL
RESISTIVITY ci "7 Z 2 JU
RESISTIVITY 2 1 ,5o of
COMMENTS / LOCATION DRAWING
C r
Ga}ko IAA. Poivt
fcs 4-
Po i n}
Ro..(1h0 - St
(kac.i1
( O O M 4- o
-rei t Po .,ft- 3 .
INSTALLED BY r S11191-14.
Revision 09/28/95
Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual
Q-Pulse Id TMS1321 Active 21/07/2015 Page 14 of 22
Brisbane Water Engineering Services CP Form No.18
Electrical Engineering Unit
Standard Cathodic Protection Test Point Data Gathering Form
Project ..hl iti Q.h......R
TP Location C 174Mbc.rt a- G rtc1voNt
Mains Size
Date 11- g - 16'
TPNo. 3
T P Type a
POTENTIAL TESTING
CATHODE TO CATHODE RETURN (RESISTANCE) ' Y.Sl., ZINC REFERENCE TO PIPE -I.4 99 s+
CuSo4 REFERENCE TO PIPE wt v ZINC TO CuSo4 g¡ rn
EARTH TESTING TEST NO. 1
PIN SPACING MEGGER READING
TEST NO 2 PIN SPACING MEGGER READING
TEST NO 3 PIN SPACING MEGGER READING
771
COMMENTS / LOCATION DRAWING
RESISTIVITY / c1 j(_,
RESISTIVITY ZLA 3' j RESISTIVITY
d.aim e vfi
te S+ Va\v-
once. A inct-1"twk .
C44kocte.._Po; hC
INSTALLED BY p. S7/911-1,
Revision 09/28/95
Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual
Q-Pulse Id TMS1321 Active 21/07/2015 Page 15 of 22
Brisbane Water Engineering Services
Electrical Engineering Unit
Cathodic Protection Interference Survey Results Form
CP Form No. 27
Project .(d. 4 0 Ni La) Unit Reading I'Ì Y 5.C4 Date Z.0 -10, ̀ l Ía.
Reading Test Point I. D.
Location Swing
On -367 Atm? c - e.- we kc,.
PìP-c Off -397 On - r 7 w -rl- o a sz.y
S ea, -c, P s 1-e.- ho I 2."5-W Off - 50-b On --5 o
INc. -c.vL YiaR. v.. II Off --- '5C9f On -33'3 wi...4 S Fil okN
w°' --t-c& r. Ahock L Off -355 On - 55 S ` Avlok
Fence 5M- 4--e_ter Pf,tui .2 Off - s s s On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On -
Off
On
Off
On
Off
On
Off
TESTED BY
Revision 09/28/95
Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual
Q-Pulse Id TMS1321 Active 21/07/2015 Page 16 of 22
Brisbane Water Engineering Services - cP Form No. 17
Electrical Engineering Unit
Cathodic Protection Anode Bed Testing _
Project V- tko ti cl Date i - 7-1(.7
ANODE MATERIAL: S'1 4 /e04' 144,2V BURIAL: 1, rr'ui4- 4v'Z c 1,-k
ANODE SIZE/WEIGHT: /5oox75;,,, G,vsr,.e j 7,rie- TEST POINT TYPE: P-r ANODE PACKAGING: SOIL RESISTIVITY:
ANODE DEPTH: .SAO ,vl SIGNAGE: r RESISTANCE TO GROUND: ANODE CURRENT
ANODE NO.1 2. G iL ANODE No.1 2 - 6 4. i. -. r s
ANODE No.2 2 t. f JL - -- - ANODE No.2 3 ,,,r a ,^^
ANODE No.3 ANODE No.3 ANODE No.4 ANODE No.4 ANODE No.5 ANODE No.5
TOTAL 3 o .1 i. TOTAL G i co ",, r s
LOCATION DRAWING
TESTED BY P 5 711.1 111
Revision 09/28/95
Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual
Q-Pulse Id TMS1321 Active 21/07/2015 Page 17 of 22
Brisbane Water Engineering Services CP Form No.18
Electrical Engineering Unit
Standard Cathodic Protection Test Point Data Gathering Form
Project W oh .cL Date ..l 3 94
T P Location 1Nht t+ c tci" y D Ort a/ 4- T P No. ..3
Mains Size T P Type 13
POTENTIAL TESTING
CATHODE TO CATHODE RETURN (RESISTANCE) ZINC REFERENCE TO PIPE CuSo4 REFERENCE TO PIPE ZINC TO CuSo4
EARTH TESTING TEST NO. 1
PIN SPACING MEGGER READING
TEST NO 2 PIN SPACING MEGGER READING
TEST NO 3 PIN SPACING MEGGER READING
gol
3+ 4vc9
COMMENTS / LOCATION DRAWING
RESISTIVITY U p ,JL_
RESISTIVITY I % -A_
RESISTIVITY
vo r ko ke(á- Poi-,+ 4
W al4-tfie 4'0,.¡fo R.
13i,a5
+ejf C-4ó0; } o Point IZi0%,
r1 te
INSTALLED BY r . 57-1 y n Revision 09/28/95
Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual
Q-Pulse Id TMS1321 Active 21/07/2015 Page 18 of 22
Brisbane Water Engineering Services CP Form No.18
Electrical Engineering Unit
Standard Cathodic Protection Test Point Data Gathering Form
Project ..b 1':fk4.I,....g,sL Date ...fit- r q 4
T P Location .Iroan% /14" T P No. if-
Mains Size T P Type ß.
POTENTIAL TESTING
CATHODE TO CATHODE RETURN (RESISTANCE) - '3 Jl. ZINC REFERENCE TO PIPE -?- 713 CuSo4 REFERENCE TO PIPE - ZINC TO CuSo4 gg6
EARTH TESTING TEST NO. 1
PIN SPACING MEGGER READING
TEST NO 2 PIN SPACING MEGGER READING
TEST NO 3 PIN SPACING MEGGER READING
+ RESISTIVITY /6.32 I.3
"S. kA. q COMMENTS / LOCATION DRAWING
RESISTIVITY Z G'l
RESISTIVITY
Fr,4c.c. pI«Ms`'1
L.A M g G-'t
}'GS+ Poh} Ca-il,oa4.-
7 p >trco-1 -t cJ- Pov.t T cA0oú4.. J
yv o M .I-o 4p-t 11- Pat -t
INSTALLED BY P. Sli i
Revision 09/28/95
Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual
Q-Pulse Id TMS1321 Active 21/07/2015 Page 19 of 22
WIT TON ROAD
PUMPING STATION
?
L" CI RISING MAIN
4" CI RISING MAIN RANOR. STREET
PUMPING STATION
KINLOCH STREET
PUMPING STATION
WALTER TAY! OR
ERIOCE
21," DIA LAMBERT RC
RISING MAIN
MANAGER DIRECTOR OF PLANNING & DESIGN
DESIGN J.SAY 2.9.94
DRAWN R.LIS TON 2.9.9 4
PROJECT
WITTON ROAD
PUMP STATION
0 31.10.94
No DATE
ISSUED FOR CONSTRUCTION
AMENDMENT
DATE:
DIRECTOR OF
CONSTRUCTION
R.L.
BY DATE:
DATE:
DIRECTOR OF
M & E SERVICES
DATE:
DIRECTOR OF SEW. OPERATIONS /W.S. DISTRIBUTION
DATE:
C i_CKED
ENGINEER IN CHARGE
TITLE
375mmDIA RISING MAIN
C.P. SYSTEM
Brisbane My
BRISBANE CITY COUNCIL
DEPARTMENT OF WATER SUPPLY
AND SEWERAGE
MECHANICAL & ELECTRICAL SERVICES
SCALE: NTS Nc. 1 OF i SHEETS
SUPERVISING ENGINEER
CADO FILE No. 78C0005-
DRAWING No.
486/7/8-KI1C0005E AMEND.
0
Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual
Q-Pulse Id TMS1321 Active 21/07/2015 Page 20 of 22
2 3
1
10 .
1
18
19
20
. 21
D
22
23
24
25
1111r-' 26
E
F
27
29
29
30
31
32
33.
34
36
37
38
M
timPotia, N\ \If ;
mat
/ 1 I
N -4
0
ttoeAS PPE MON-PtTALIU
--- ____ '
5 s 7 8
4»iaIIIIiiiir" - - --
LA `M-@ER-T
; $ ti
E
= tr fta. s ST
r
NOTES
0 4.96 ISSUED FOR APPROVAL O.L.P.
No DATE AMENDENT INITIALS
AMENDENT & ISSUE REGISTER MANAGER
DATE:
DIRECTOR OF
TECHNOLOGY SERVICES
DATE:
DIRECTOR CF
PLANNING & DESIGN
DATE:
DIRECTOR OF
WATER SUPPLY
DATE:
DIRECTOR OF
CONSTRUCTION
DATE:
DESIGN J.S. 72.496 ENGINEER IN CHARGE
DRAWN O.L.P. 23.4.96 SUPERVISING ENGINEER
TRACED
DECKED
REFERENCES
A2 REDUCED
CALO FLE No. 76T00040 THIS DRAWING WAS PRODUCED
USING QIImRAW
A
B
c
D
COPYRIGHT ® 1996 No repoduction is permitted in whole or in part without
the express consent of BRISBANE CITY COUNCIL.
BRISBANE WATER
Etfasete guuu
BRISBANE CITY COUNCIL
BRISBANE WATER TECHNOLOGY SERVICES BRANCH
INFORMATION TECHNOLOGY
PROJECT:
WITTON / LAMBERT RD. RISING MAIN C.P. SYSTEM
TITLE
CATHODIC PROTECTION TEST POINT DETAILS
SCALE: N.T.S. No. 2 OF 2 SHEETS
DRAWING No.
486/7/6-KIT0004E AMEND.
0 2 3 4 5 6 7
E
F
8
Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual
Q-Pulse Id TMS1321 Active 21/07/2015 Page 21 of 22
IIIIL11111
10 11 12 1 16 1 18 20 21 22 24 2
A
G.P.O. x ic RECTIFIER C/B 10A UNIT C/B
10A
VARISTOR TO DATA LOGGER
N
i
o N/L
NEON 11 W
Kl u u
REMOTE INTERUPT
2 ® Y
INTERUPT SWITCH
NOTES
14
Ls
14
a
VARIAC
TRANSFORMER GAYRAD (SEE NOTE 1)
u O Q) ih ti
DIODE FUSE 25A
TRANSFORMER OUTPUT CURRENT & VOLTAGE
TO SUIT APPLICATION PROVIDING SUITABLE
RESOLUTION I CONTROL
' AMMETER & VOLTMETER TO PROVIDE
SUITABLE RESOLUTION FOR SYSTEM
+ POSITIVE WIRING TO BE RED
- NEGATIVE WIRING TO BE BLACK
L.V. AC WIRING TO BE 4nn2 SLUE /WHITE
DC WIRING TO BE 4nn2
240V AC WIRING TO BE 1.5nn2- BROWN /BLACK REFERENCE.WIRING TO BE 1.5nn2 -GREY
LEGEND
BRIDGE
ti
3:
ECTIFIER UNIT
+VE
C ; - J -. -
VARISTOR
0 EVE OUTPUT SEE NOTE
AMMETER
-VE
-VE
31
50
30
VOLTMETER
TERMINALS WITH 4nn TEST PLUG SOCKETS
KI - 240V RELAY
K2,K3, & K4 - 24V DC RELAYS
RI - SHUNT RESISTOR (SIZED TO PRODUCE A VV DROP AT FULL LOAD)
R2,R3 - VOLTAGE DIVIDER (SIZED TO PRODUCE A VOLTAGE OF 10V ACROSS R2 AT MAX. OUTPUT VOLTAGE)
+VE AND -VE DC FUSES TO BE SIZED APPROX. 5AMPS ABOVE NORMAL OUTPUT CURRENT
a
K4.i. i COUPON DISCONNECT
n n m
\.K3.1
tR$R
Ii z W
w á. z O Ó Ó W + U U C W Z. UNN1_1Q
Z WJáJ U Q
O cc z çIYZUZ Z W W W <LI-1.1- WO WO Col CCdCVd
TO TELEMETRY EQUIPMEN-
íó
n
K2 K3
K4
C4T1R0: Ra EC TURN
=PON [LEO
IDe REF CCOLPnO
CuSe4 TEST CWRLTImt
BANANA PLUG SOCKETS ON FRONT PANEL
11111!MMIN
W J m
Zn
U c L./m
óU a \ U á>
Ua W > z d N
E U £ > 431 ZO J ZC- UW É Z E
ZU
ÓÓ 2 < cçn C-3
< C
W ~ Ú
Z ç z LI L IJ ._ Li W 0 Ú W r- <ú - W 01Y
LJ N U D GL
L. -- z ÿW Uv . N d , '
COUPON TNPE REFERENCE
R.L. 11B.1C.93 CHANGES AS SHOWN
D R:.. 25.8.93 ISSUED FOR CONSTRUCTION
BY DATE REVISION _HECK APPR
-`-;\! 1 C . SBn NL- CITY COUNCIL
DEPARTMENT OF WATER SUPPLY & SEWERAGE
_CHANICAL & ELECTRICAL SERVICES
P?O_:ECT
STANDARD CATHODIC PROTECTION
DRAWN µyç .lAic R.C. 3.8.53
T:ST POINT TERMINALS FOR REMOTE RECTIFIER SITES
SUPER ENG. NAME WIZ .SCAL M.-I. 213.8.93
. DESIGN J..1. 3.8 93
TIT¿!_ RECTIFIER UNIT WITH DATA LOGGING FACILITIES WIRING DIAGRAM
CHcCKcD, JS. 25.8.53
DRAWING Na.
-^. 86/6/25-AAIC0021E
SENIOR ENG.
ELECT. ENG.
4040212 FILE s
A625C21
Cathodic Protection System - Witton Road to Lambert Road Indooroopilly - Sewer Rising Main - 375 to 600 mm - OM Manual
Q-Pulse Id TMS1321 Active 21/07/2015 Page 22 of 22