    CODE OF PRACTICE

    OF ELECTRICAL SAFETYFOR

    WORK ON OR NEARHIGH VOLTAGE

    ELECTRICAL APPARATUS

    (THE BLUE BOOK)

    2005

    VICTORIA

  • 8/4/2019 BlueBook 2008

    2/151

    ISSUE SHEET

    Copy Number . . . . . . . . . . . . . . . . . . . . . .

    CONTROLLED COPY

    UNCONTROLLED COPY

    (Note: Uncontrolled copies will NOT be subject

    to automatic revision servicing)

    ISSUED TO: . . . . . . . . . . . . . . . . . . . . . . .

    COMPANY: . . . . . . . . . . . . . . . . . . . . . . .

    DATE: . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    This book to be returned to the issuer onrequest or on termination of employment.

    ISSUED BY: . . . . . . . . . . . . . . . . . . . . . . .

  • 8/4/2019 BlueBook 2008

    3/151

    Blue Book December 2005 Page 1 of 148

    NOTE TO USERS

    The Electrical Safety Committee (ESC) calls to the

    attention of users of this publication that the

    following important matters are applicable to its

    use:

    DISCLAIMER

    No person should act or rely on the contents of this

    publication before considering and, if appropriate,

    taking professional advice upon that persons own

    particular circumstances. The ESC believes that, to

    the best of its knowledge, the information in this

    publication is correct but no person gives any

    warranty of completeness, accuracy or reliability inrespect of the information or publication. This

    publication is sold or otherwise made available on

    the basis that the ESC and its respective

    representatives, members, employees and agents,

    the authors and the publishers:

    (1) are not responsible for any error in oromission from this publication, and

    (2) except for liability under statute which cannot

    be excluded, expressly disclaim all and any

  • 8/4/2019 BlueBook 2008

    4/151

    Page 2 of 148 Blue Book December 2005

    liability, including without limitation for

    negligence, to any person, whether a

    purchaser of this publication or not, in respectof anything and of the consequences of

    anything done or omitted to be done by any

    person in reliance, whether whole or partial,

    upon the whole or any part of the contents of

    this publication.

    This Code of Practice is regularly reviewed by theESC to ensure that it reflects current work

    requirements and evolving technologies.

    Suggestions or comments regarding possible

    amendments should be addressed to:

    Energy Safe Victoria

    P.O. Box 262,Collins St West,

    Melbourne, 8007

    Telephone: (03) 9203 9700

    Facsimile: (03) 9686 2197

    E mail address: [email protected] web site: http://www.esv.vic.gov.au

    Victorian Government web site:http://www.dms.dpc.vic.gov.au

  • 8/4/2019 BlueBook 2008

    5/151

    Blue Book December 2005 Page 3 of 148

    ELECTRICAL SAFETY COMMITTEEMEMBERSHIP

    Dennis Mason BlueScope Steel Limited

    (Chairperson)

    Greg Hollett ALCOA World Alumina Australia

    Jim Lean Agility Management Pty Ltd

    Garry Reeves Powercor Australia LtdDavid Just SP AusNet

    David Le Lievre ALCOA World Alumina Australia

    Peter Billsdon Southern Hydro

    Peter den Brinker Victorian WorkCover Authority

    Graeme Watson Electrical Trades Union

    Allan Driver Energy Safe Victoria

    Loc Vuong Energy Safe Victoria

    Paul Madden National Electrical andCommunications Association

    Mark Fowler Utility Asset Management

    SECRETARIAT

    John Batten Secretary

  • 8/4/2019 BlueBook 2008

    6/151

    Page 4 of 148 Blue Book December 2005

    STATEMENT FROM THE DIRECTOR OFENERGY SAFETY

    Energy Safe Victoria (ESV) is the regulator for

    Electrical and Gas Safety in Victoria, Australia. As

    part of its role, ESV sets the minimum standards for

    the design, construction, operation and

    maintenance of electricity network assets.

    The Code of Practice On Electrical Safety For Work

    on or Near High Voltage Electrical Apparatus (the

    2005 Blue Book) has been prepared by the

    Electrical Safety Committee established under

    Section 10 of the Electricity Safety Act 1998.

    The Electricity Safety (Network Assets) Regulations

    1999, and The Electricity Safety (Installations)

    Regulations 1999, invoke the Code as amended

    from time to time. The 2005 Blue Book will therefore

    supersede the Code of Practice On Electrical

    Safety For Work on or Near High Voltage Electrical

    Apparatus published in 1998 (the 1998 Blue Book).

    ESV has decided that the 2005 Blue Book will come

    into operation on 31 December 2005

    ESV recognises that the Victorian Electricity Supply

    Industry and high voltage customers need time to

    train and make workers under their control aware of

  • 8/4/2019 BlueBook 2008

    7/151

    Blue Book December 2005 Page 5 of 148

    the requirements of the 2005 Blue Book, It is

    therefore not necessary for a network operator or a

    person who owns or operates a high voltageelectrical installation to comply with the 2005 Blue

    Book before 31 December 2006 provided that the

    1998 Blue Book continues to be complied with up

    to that time.

    I endorse the 2005 Blue Book and commend the

    Committee members and those industryorganisations involved with the development of the

    2005 Blue Book.

    Ken Gardner

    Director of Energy Safety

    31 December 2005

  • 8/4/2019 BlueBook 2008

    8/151

    Page 6 of 148 Blue Book December 2005

    PREFACEVictorian legislation such as the Occupational

    Health & Safety Act, 2004 requires, in part, that:

    Sec. 21 Duties of employers to employees

    (1) An employer must, so far as is reasonablypracticable, provide and maintain for

    employees of the employer a working

    environment that is safe and without risks to

    health

    For the purposes of sub-section (1)

    (a) a reference to an employee includes a

    reference to an independent contractor

    engaged by an employer and any

    employees of the independent contractor:and

    (b) the duties of an employer under this sub-

    section extends to an independent

    contractor, engaged by the employer, and

    any employees of the independent

    contractor, in relation to matters overwhich the employer has control or would

    have control if not for any agreement

    purporting to limit or remove that control.

  • 8/4/2019 BlueBook 2008

    9/151

    Blue Book December 2005 Page 7 of 148

    Employers outside the scope of this document

    requiring additional information on HV safety

    should seek assistance from: Energy Safe Victoria;

    Local Distribution, Transmission or Generating

    Company; or

    Victorian WorkCover Authority.

  • 8/4/2019 BlueBook 2008

    10/151Blue Book December 2005 Page 8 of 142

    Contents

    CONTENTS PAGE

    Definitions 141 PURPOSE 26

    2 SCOPE 26

    3 GENERAL SAFETY REQUIREMENTS 28

    3.1 Hazard Identification, Risk Assessment

    And Control 28

    3.2 First Aid 293.3 Communications 29

    3.4 Forms 29

    3.5 Use And Testing Of Operating And

    Live-line Equipment 29

    3.6 Insulating Sticks 30

    3.7 Labelling Of Electrical Apparatus 31

    3.8 Ladders 31

    3.9 Personal Protective Equipment 31

    3.10 Tapes And Other Measuring Devices 33

    3.11 Use Of Safety Observers 33

    3.12 Fit State For Work 343.13 Work Within Electric And

    Magnetic Fields 35

  • 8/4/2019 BlueBook 2008

    11/151

    Contents

    Blue Book December 2005 Page 9 of 148

    PAGE

    4 TRAINING AND AUTHORISATION 39

    4.1 General 39

    4.2 Approved Training Standard 40

    4.3 Records 42

    5 WORK IN THE VICINITY OF ELECTRICAL

    APPARATUS 43

    5.1 General 43

    5.2 Handling Objects/loads 44

    5.3 Erection Or Dismantling Of Overhead Conductors 45

    5.4 Use Of Mobile Plant 45

    5.5 Work By Ordinary Persons 47

    5.6 Work Within Stations Or On Multi-circuit

    Overhead Lines With Multiple Asset 486 APPROACH TO ELECTRICAL APPARATUS 49

    6.1 General 49

    6.2 Safe Approach Distance Persons 52

    6.3 Safe Approach Distances - Vehicles 59

    6.4 Safe Approach Distances Uninsulated

    Mobile Plant 62

    6.5 Safe Approach Distance Insulated

    Mobile Plant 63

  • 8/4/2019 BlueBook 2008

    12/151

    Contents

    Page 10 of 148 Blue Book December 2005

    PAGE

    6.6 Emergency Approach 65

    6.7 Contact With Live High Voltage Conductors By

    Means Of Appliances 65

    6.8 Approach To Live High Voltage

    Insulated Cables 65

    6.9 Work In Stations 67

    6.10 Work Outside Of Stations 68

    7 OPERATION OF HIGH VOLTAGE ELECTRICAL

    APPARATUS 69

    7.1 Persons Authorised To Operate High Voltage

    Electrical Apparatus 69

    7.2 High Voltage Switching 708 EARTHING OF HIGH VOLTAGE

    ELECTRICAL APPARATUS 71

    8.1 General 71

    8.2 Earthing For Access To High Voltage Electrical

    Apparatus 72

    8.3 Removal Of Earth When Working

    Under An Access Authority 73

    8.4 Earthing Of Overhead Lines 74

  • 8/4/2019 BlueBook 2008

    13/151

    Contents

    Blue Book December 2005 Page 11 of 148

    PAGE

    8.5 High Voltage Metal-clad Switch Units 74

    8.6 High Voltage Capacitors 758.7 Overhead Lines Priority Earthing

    System 75

    9 ACCESS FOR WORK ON OR NEAR HIGH VOLTAGE

    ELECTRICAL APPARATUS 77

    9.1 General 77

    9.2 Electrical Access Permit Procedure 79

    9.3 Sanction For Testing Procedure 88

    9.4 Out Of Commission Electrical

    Apparatus 94

    9.5 Suspension Of An Access Authority 94

    9.6 Live Work - High Voltage 969.7 Preparing High Voltage Electrical Apparatus For

    Access 99

    9.8 Working On Insulated Power Or Supervisory

    Cables 108

    10 PLACING HIGH VOLTAGE ELECTRICAL

    APPARATUS IN SERVICE 111

    10.1 Clearance For Service 111

    10.2 Connections To New Or Out Of

    Commission Electrical Apparatus 111

  • 8/4/2019 BlueBook 2008

    14/151

    Contents

    Page 12 of 148 Blue Book December 2005

    PAGE

    11 LOW VOLTAGE NETWORK ASSETS 113

    11.1 General 113

    11.2 Work On Or Near Live Low Voltage

    Conductors 113

    11.3 Work On Or Near De-energised Low

    Voltage Exposed Conductors 114

    12 WORK BY PERSONS NOT UNDER THE CONTROL

    OF THE ASSET OWNER 116

    12.1 General 116

    12.2 Permits To Work Adjacent To Network

    Assets 117

    12.3 Work On Abandoned Underground

    Cables 118APPENDIX A INFORMATION TO BE

    CONTAINED IN FORMS 119

    Application for an Access Authority 119

    Application for Authority to Work in the Vicinity

    of Electrical Apparatus 120

    Personal Authorisations 121

    Authority to Work in the Vicinity of Electrical

    Apparatus 122

  • 8/4/2019 BlueBook 2008

    15/151

    Contents

    Blue Book December 2005 Page 13 of 148

    PAGE

    Clearance to Place Electrical Apparatus into

    Service (May also be Overhead Line Clearance and

    Underground Cable Clearance) 122

    Electrical Access Permit & Sanction For Testing 124

    Statement of Condition of Apparatus/Plant (SCAP) 125

  • 8/4/2019 BlueBook 2008

    16/151

    Definitions

    Page 14 of 148 Blue Book December 2005

    DEFINITIONS

    For the purpose of this Code of Practice, thefollowing definitions shall apply:

    Note: For definitions of barriers and signs referClause 9.7.2.4

    1 Access Authority means any form ofauthorisation which allows access to, work on

    or near, or testing of electrical apparatus.Examples used in this Code are:

    Electrical Access Permit means a formof authorisation which allows access to,and work upon, electrical apparatus.

    Sanction for Testing means a form ofauthorisation to allow energisation ofelectrical apparatusfor testing purposes.

    Permit to Work Adjacent to Network

    Assets means a document providingwritten permission to persons, other thanemployees or contractors of the networkoperator, to work within safe approachdistancesor nearor in the vicinityof thenetwork operators electrical apparatus.

    2 Alive see Live

  • 8/4/2019 BlueBook 2008

    17/151

    Definitions

    Blue Book December 2005 Page 15 of 148

    3 Appliance means any instrument or devicedesigned for the use nearor in direct contact

    with live high voltage conductors. 4 Approvedmeans having appropriate

    organisation endorsement in writing for aspecific function.

    5 Authorised Personmeans a person withtechnical knowledge or sufficient experience

    who has been approved, or has the delegatedauthority to act on behalf of the organisation, toperform the duty concerned

    Examples used in this Code are:

    Authorised Applicant means anapproved person who has been assessedas competent against an approvedtraining standard to make application forspecified types of access authorities.

    Authorised Electrical Operator(Electrical Operator) means anapproved person who has been assessed

    as competent against an approvedtraining standard to carry out switchingoperations on high voltage electricalapparatus.

    Authorised Live HV Workermeans an

  • 8/4/2019 BlueBook 2008

    18/151

    Definitions

    Page 16 of 148 Blue Book December 2005

    approved person who has beenassessed as competent against an

    approved training standard to carry outparticular work on or near exposed livehigh voltage conductors.

    Authorised Recipient means anapproved person who has been assessedas competent against an approved

    training standard to receive an electricalaccess permit.

    Authorised Testermeans an AuthorisedRecipient who has been assessed ascompetent against an approved trainingstandard, and is approved to receive asanction for testing.

    6 Authority to Receive Electrical Access

    Permitsmeans a form of authorisation held byan authorisedrecipient.

    7 Authority to Receive Sanctions for Testing

    means a form of authorisation held by an

    authorisedtester.8 Authority to Work in the Vicinity of

    Electrical Apparatusmeans a form ofauthorisation to be used where applicable to

  • 8/4/2019 BlueBook 2008

    19/151

    Definitions

    Blue Book December 2005 Page 17 of 148

    allow work in the vicinityof electricalapparatus.

    9 Bonded means connected together in such amanner as to ensure that all connected partsare maintained at the same potential

    10 Cablemeans an insulated conductoror twoor more such conductorslaid together,whether with or without fillings, reinforcements

    or protective coverings.

    11 Circuit Breakermeans a device capable ofmaking, carrying and breaking currents undernormal and abnormal circuit conditions, suchas short circuit.

    12 Competentmeans having the skills,knowledge and attributes a person needs tocomplete a task.

    13 Conductormeans a wire, cable or form ofmetal designed for carrying electric current.

    14 Connectedmeans joined together by a

    conductor capable of carrying electricalcurrent for its required function or purpose byeither physically clamping or boltingconductors together or closing a circuitbreaker, switch or similar device.

  • 8/4/2019 BlueBook 2008

    20/151

    Definitions

    Page 18 of 148 Blue Book December 2005

    15 De-energisedmeans not connected to anysource of electrical supply but not necessarily

    isolated.16 Discharged means having been connected

    to the general mass of earth in such a manneras to remove any residual electrical energy ina conductor.

    17 Earthed means directly electrically

    connected to the general mass of earth so asto ensure and maintain the effective dissipationof electrical energy.

    18 Earthing Devicemeans an approveddeviceused for the earthing of conductors.

    19 Electrical Apparatus means any electricalequipment, including overhead lines andunderground cables, the conductors of whichare liveor can be made live.

    20 Energisedmeans connected to a source ofelectrical supply.

    21 Exposed conductormeans an electricalconductor, approach to which is not preventedby a barrier of rigid material or by insulationwhich is adequate under a relevant AustralianStandard specification for the voltage

  • 8/4/2019 BlueBook 2008

    21/151

    Definitions

    Blue Book December 2005 Page 19 of 148

    concerned.

    22 High voltage or HVmeans a nominal voltage

    exceeding 1000 volts a.c. or exceeding 1500 voltsd.c.

    23 High Voltage Customermeans any user ofelectricity (excluding the VESI) directlyconnected at high voltageto the Transmissionor Distribution Networks.

    24 Instructed personmeans a personadequately advised or supervised by anauthorised person to enable them to avoid thedangers which electricity may create.

    25 Insulated Mobile Plantmeans mobile plantapprovedand tested for carrying out work onor near electrical apparatus.

    26 Insulatedmeans separated from adjoiningconducting material by a non-conductingsubstance which provides resistance to thepassage of current, or to disruptive dischargesthrough or over the surface of the substance atthe operating voltage, and to mitigate thedanger of shock or injurious leakage of current.

    27 Insulating Stickmeans a stick approvedandtested for carrying out operating and livework

  • 8/4/2019 BlueBook 2008

    22/151

    Definitions

    Page 20 of 148 Blue Book December 2005

    on live electrical apparatus.

    28 Isolatedmeans not connected to any

    possible sources of electricity supply bymeans which will prevent unintentional re-energisation of the electrical apparatusandwhich is assessed as a suitable step in theprocess of making safe for access purposes.

    29 Livemeans energised or subject to

    hazardous induced or capacitive voltages

    30 Live workmeans all work performed oncomponents of electrical apparatusnotisolated, proved de-energisedand earthed.

    31 Low voltage or LVmeans nominal voltageexceeding 50 V a.c./120 V d.c. but notexceeding 1000 V a.c./1500 V d.c.

    32 Mobile Plantmeans cranes, elevating workplatforms, tip trucks or similar plant, anyequipment fitted with a jib or boom and anydevice capable of raising or lowering a load.

    Mobile plant can only be considered as avehiclewhen in the normal travelling mode andnot in the working mode when determiningsafe approach distances.

  • 8/4/2019 BlueBook 2008

    23/151

    Definitions

    Blue Book December 2005 Page 21 of 148

    Helicopters used for bare hand live-line workare excluded from this definition of mobile

    plant.33 Near means a situation where there is a

    reasonable possibility of a person, eitherdirectly or through any conducting medium,coming within the relevant safe approachdistances.

    34 Network Assetmeans any asset that isowned or operated by a network operatorforthe purposes of generating, transmitting,distributing or supplying electricity of thenetwork operator.

    35 Network Operatormeans the owner,

    controller or operator of an electricity network.

    36 Nominal voltagemeans the AC (phase tophase RMS) or DC voltage by which a systemof supply is designated.

    37 Not Electrically Connectedmeansdisconnected from all sources of supply by theremoval or absence of conductors,appropriate to the voltage and insulatingmedium and not able to be made live bynormal operating means and identified in

  • 8/4/2019 BlueBook 2008

    24/151

    Definitions

    Page 22 of 148 Blue Book December 2005

    accordance with approvedprocedures.

    38 Operating Authoritymeans an appropriate

    representative of an organisation, who isresponsible for the control of electricalapparatusconcerned.

    39 Ordinary Personmeans a person withoutsufficient training or experience to enable themto avoid the dangers which electrical

    apparatusmay create.

    Note: Ordinary Person in this Code refers to aperson under the control of a Network Operatoror HV Customer.

    40 Organisationmeans a business, enterprise,company, or corporation.

    41 Out of Commissionmeans the condition ofelectrical apparatuswhich is not electricallyconnectedand declared to be so in writing tothe operating authorityresponsible for theelectrical apparatus.

    42 Personal Protective Equipmentmeansclothing, equipment and/or substances, whichwhen worn or correctly used, protect parts orall of the body from foreseeable risk of injury ordisease at work or in the workplace.

  • 8/4/2019 BlueBook 2008

    25/151

    Definitions

    Blue Book December 2005 Page 23 of 148

    43 Practicable means having regard to (a) the severity of the hazard or risk in

    question;(b) the state of knowledge about that hazard

    or risk and any ways of removing ormitigating that hazard or risk;

    (c) the availability and suitability of ways toremove or mitigate that hazard or risk; and

    (d) the cost of removing or mitigating thathazard or risk.

    44 Proceduremeans the documentation of asystematic series of actions (or activities)directed to achieve a desired result.

    45 Recipientmeans a person who has signed

    on an access authority.

    46 Recipient in Chargemeans an authorisedrecipientto whom an access authorityhasbeen issued and who is in charge of allrecipientssigned on that access authority.

    47 Resumption of (Resume) an Access

    Authoritymeans the re-commencement of allwork under an access authoritythat had beensuspended.

    48 Safe Approach Distancemeans the

  • 8/4/2019 BlueBook 2008

    26/151

    Definitions

    Page 24 of 148 Blue Book December 2005

    minimum distance that shall be maintained bya person, vehicleor mobile plant(including its

    load, controlling ropes and any otheraccessories) when approaching electricalapparatusother than for work in accordancewith an access authority.

    49 Safety Observermeans a person withsufficient knowledge of the task being

    performed and competent for the duty ofobserving and warning against unsafeapproach to electrical apparatus.

    50 Shall is to be interpreted as mandatory.

    51 Should- is to be interpreted as advisory ordiscretionary.

    52 Stationmeans any enclosed or fencedlocation in which high voltagesupply isgenerated, converted, controlled ortransformed.

    53 Suspension of an Access Authoritymeansthe cessation of all work under an issuedaccess authoritywhere all persons workingunder that authority have signed off.

  • 8/4/2019 BlueBook 2008

    27/151

    Definitions

    Blue Book December 2005 Page 25 of 148

    54 Tester in Chargemeans an authorised testerto whom a sanction for testinghas been issued

    and who is in charge of all members of thework party signed on that sanction for testing.

    55 Vehiclemeans a truck (non tipping), car,utility, or other general purpose conveyanceused for the carriage of persons or goods. (seealso mobile plant).

    56 Vicinitymeans a situation where it is unlikelythat a person will, either directly or through anyconducting medium (e.g. via mobile plant),come within the relevant safe approachdistances.

    57 Victorian Electricity Supply Industry(VESI)

    means the Organisations which are licensedunder the Electricity Industry Act 2000 toparticipate in the generation, transmission,distribution, and supply of electricity in Victoria.

    58 Written (in Writing)means recorded onpaper or in electronic form.

  • 8/4/2019 BlueBook 2008

    28/151

    Purpose and Scope

    Page 26 of 148 Blue Book December 2005

    1 PURPOSE

    The purpose of this Code of Practice is to provide

    practical guidance in maintaining safe systems of

    work in relation to control of risks associated with

    work on or near or in the vicinity of high voltage

    electrical apparatusin Victoria.

    2 SCOPEThis Code of Practice defines:

    Principles; and

    Electrical Safety Procedures

    The Principles apply to all persons working on, near

    or in the vicinityof high voltage electrical apparatuswhich is capable of being energised.

    The Electrical Safety Procedures defined in this

    Code apply within the VESI. HV Customers shall

    apply those procedures required by regulations

    and may use the remaining procedures.

    This Code is also applicable to not electricallyconnected apparatus in situations where the

    required level of isolation, as defined, cannot be

    confirmed prior to work commencing, for example,

    on abandoned underground cables.

  • 8/4/2019 BlueBook 2008

    29/151

    Scope

    Blue Book December 2005 Page 27 of 148

    Organisationsshall follow the principles contained

    within this Code.

    In order to comply with the electrical safety

    procedure requirements of this Code a VESIorganisation shall either:

    (a) Apply the procedures contained within thisCode; or

    (b) Vary the procedures by:

    completing a hazard identification and risk

    assessment documenting the process

    advising the Electrical Safety Committee in

    writing

    Figure 1 - Hierarchy of documentation for electrical safety

    This Code sets a minimum standard and may be

    enhanced by Organisational procedures. These

    procedures may utilise other industry standards.

  • 8/4/2019 BlueBook 2008

    30/151

    General Safety Requirements

    Page 28 of 148 Blue Book December 2005

    3 GENERAL SAFETYREQUIREMENTS

    PRINCIPLE - Consideration shall be given toprovide additional procedures covering mattersidentified relevant to providing a comprehensivesafe working environment.

    3.1 HAZARD IDENTIFICATION, RISKASSESSMENT AND CONTROL

    An organisations safe system of work shall includeappropriate risk management processes to ensurehazards associated with work within safe approachdistances or near electrical apparatus areidentified, assessed and controlled.

    Prior to working within safe approach distancesornear any electrical apparatus, the personsconducting the work shall identify, assess andcontrol the associated hazards and risks.

    The hazard identification and risk assessmentprocess shall be regularly reviewed and audited toensure compliance.

  • 8/4/2019 BlueBook 2008

    31/151

    General Safety Requirements

    Blue Book December 2005 Page 29 of 148

    3.2 FIRST AID

    Persons who are required to work where there is a

    risk of inadvertent contact with live electricalconductors shall be given appropriate first aidtraining on commencement, and thereafter subjectto annual competency assessment. Training shallcover skills in expired air resuscitation, externalcardiac compressions, shock, burns and incidentassessment and management.

    3.3 COMMUNICATIONS

    All communications relating to the operation of, oraccess to, electrical apparatus shall be clear anddefinite. Electrical apparatusshall be referred to byname and sufficient detail to give positiveidentification. Verbal instructions and statements

    shall be confirmed by repeating back to avoidmisunderstanding.

    3.4 FORMS

    Guidance for minimum requirement on forms isgiven in Appendix A.

    3.5 USE AND TESTING OF OPERATING ANDLIVE-LINE EQUIPMENT

    All sticks, gloves, sleeves, mats, protective barriersor covers, earthing trucks, portable earthing

  • 8/4/2019 BlueBook 2008

    32/151

    General Safety Requirements

    Page 30 of 148 Blue Book December 2005

    devices, insulating platforms, insulated elevatingwork platforms or other equipment used for

    operating high voltage electrical apparatus orperforming live-line work shall be specificallyapproved for the particular application. Visualinspection shall be made for physical damage orcontamination immediately prior to use.

    All equipment including protective equipment usedon high voltage electrical apparatus and whichrequires regular testing to prove the effectivenessof insulation shall be tested at specific intervals asper Organisational procedures and marked to showthe date of the next routine test.

    Gloves, sleeves, mats and protective barriers orcovers used for operating high voltage electrical

    apparatusor for performing Glove and Barrier Live-Line Work shall not be relied upon as the solemeans of insulation.

    Equipment shall not be used after the marked dateuntil retested.

    3.6 INSULATING STICKS

    3.6.1 Insulating sticks shall have a length whichprovides appropriate insulation from live parts andenables a person using the stick to maintain theapplicable safe approach distance(refer 6.2) at all

  • 8/4/2019 BlueBook 2008

    33/151

    General Safety Requirements

    Blue Book December 2005 Page 31 of 148

    times.

    3.6.2 When an insulating stickis to be used in wet

    conditions consideration shall be given to thepotential for hazardous surface leakage currents.

    3.7 LABELLING OF ELECTRICALAPPARATUS

    For the purposes of identification and description,electrical apparatus shall, wherever practicable, beclearly labelled.

    3.8 LADDERS

    Metallic or wire-reinforced ladders, shall not beused on, or near exposed live electrical apparatus;unless approved for use in accordance with

    organisational procedures.3.9 PERSONAL PROTECTIVE EQUIPMENT

    All persons who may be exposed to possibleelectric shock, flash or other injury from electricalapparatusshall use approved personal protectiveequipment. Personal protective equipment shall

    include clothing with wrist to ankle cover and fullyenclosed footwear.

    Additional personal protective equipmentshall beused in accordance with the type of work and therisks involved.

  • 8/4/2019 BlueBook 2008

    34/151

    General Safety Requirements

    Page 32 of 148 Blue Book December 2005

    GENERAL PPE REQUIREMENTS

    1 Working on, near or in the vicinity ofelectrical apparatus approved safety:

    headwear

    natural fibre clothing

    footwear

    2 Operating electrical apparatus approvedsafety:

    headwear

    footwear

    natural fibre clothing

    hand protection

    face/eye protection

    3 Supervised visit to a station with no

    involvement in any work at that station and

    movements confined to normal access ways,

    e.g. roads, paths and stairs:

    The person responsible for organising or

    supervising such visitors to ensure that they

    are suitably clothed or covered, and

    supplied with approved safety headwear.

  • 8/4/2019 BlueBook 2008

    35/151

    General Safety Requirements

    Blue Book December 2005 Page 33 of 148

    3.10 TAPES AND OTHER MEASURING

    DEVICES

    Only approved non-conducting tapes and rulesshould be used in the vicinity of live electrical

    apparatus. Conductive tapes shall not be used

    near exposed live electrical apparatus unless

    approvedfor use in accordance with organisational

    procedures.

    3.11 USE OF SAFETY OBSERVERS

    Where it is considered after a risk assessment that

    a person, equipment or mobile plant might

    inadvertently infringe Safe Approach Distances, a

    safety observershall be posted.

    For work near electrical apparatus, use of a safetyobserverto warn against inadvertent infringement

    of safe approach distancesmay be required under

    this code, under organisational procedures or

    under precautions determined appropriate under

    the hazard identification, risk assessment and

    control procedures used by the persons

    conducting the work.

  • 8/4/2019 BlueBook 2008

    36/151

    General Safety Requirements

    Page 34 of 148 Blue Book December 2005

    A safety observer shall:

    monitor the work and warn against potential

    infringement of safe approach distances;

    be positioned to effectively observe andimmediately communicate with personsperforming the work;

    have the authority to temporarily suspend therelevant work at any time;

    not perform any other work while acting assafety observer; and

    be specifically instructed in the duties andworkplace hazards applicable.

    3.12 FIT STATE FOR WORK

    Alcohol, drugs, mental alertness and physicalcondition of a person may impede their ability to

    work safely in an electrical environment.

    Persons who are required to work on, nearor in the

    vicinityof electrical apparatusshall not consume or

    be under the influence of alcohol or drugs that

    diminish work skills during work hours. This shall betaken to include meal or rest breaks.

    Appropriate policies shall be implemented by

    organisations.

  • 8/4/2019 BlueBook 2008

    37/151

    General Safety Requirements

    Blue Book December 2005 Page 35 of 148

    3.13 WORK WITHIN ELECTRIC AND

    MAGNETIC FIELDS

    3.13.1 General

    Persons working within electric and magnetic fields

    shall be appropriately protected from the

    annoyance due to electric discharge effects of

    strong electric fields and the possible biological

    effects associated with extremely strong electric

    and magnetic fields.

    Persons using medical implantable devices

    including cardiac pacemakers should consult their

    doctors and the relevant organisation Health &

    Safety Officer for information on possible

    electromagnetic interferences with the medical

    devices prior to entering areas of strong electricand magnetic fields.

    The electric fields and magnetic field exposure

    limits given below are based upon National Health

    and Medical Research Council (NHMRC)

    Guidelines. An ongoing review of these guidelines

    is presently being carried out by the AustralianRadiation Protection and Nuclear Safety Agency

    (ARPANSA), and information on the activity is

    available from ARPANSA. Expected publication

  • 8/4/2019 BlueBook 2008

    38/151

    General Safety Requirements

    Page 36 of 148 Blue Book December 2005

    date for the new ARPANSA Standard is 2006.

    Organisations should apply appropriate exposure

    limits as per NHMRC guideline or ARPANSAstandard whichever is current

    3.13.2 50Hz Electric Fields

    The National Health and Medical Research Council

    (NHMRC) interim guidelines for occupational

    exposure limits for electric fields are as follows:

    Whole working day 10 kV/m

    Short term 30 kV/m

    Short term exposure to fields between 10 kV/m and

    30 kV/m is permitted provided the field strength (in

    kV/m) times the duration of exposure (in hours)

    does not exceed 80 for the whole day. For example,exposure to an electric field of 20 kV/m would be

    permitted for 4 hours under IRPA guidelines.

    For work situations with field strengths greater than

    30 kV/m, appropriate measures shall be taken.

    Such measures may include wearing of

    appropriately earthed or bonded conducting suits,the screening and earthing of vehicles, the

    screening of work platforms and access ways, and

    de-energising adjacent electrical apparatus.

  • 8/4/2019 BlueBook 2008

    39/151

    General Safety Requirements

    Blue Book December 2005 Page 37 of 148

    The person responsible for planning the work shall

    include in the work instructions details of any

    appropriate measures to be taken.3.13.3 Magnetic Fields

    The NHMRCs guidelines for limits of occupational

    exposure to magnetic fields are as follows

    (a) 50 Hz Magnetic Fields

    Whole working day 0.5 milliTesla(5 000 milliGauss)

    Short term 5 milliTesla

    (2 hours per day) (50 000 milliGauss)

    Limit for limbs 25 milliTesla

    (eg extended arm) (250 000 milliGauss)(b) Static or Direct Current (DC) Magnetic Fields

    The International Commission on Non-Ionizing

    Radiation Protection (ICNIRP) guidelines for

    Limitsab of occupational exposure to static or

    DC magnetic fields are as follows:

    Whole working day 200 milliTesla

    Ceiling Value 2000 milliTesla

    Limbs 5000 milliTesla

  • 8/4/2019 BlueBook 2008

    40/151

    General Safety Requirements

    Page 38 of 148 Blue Book December 2005

    Notes:

    (a) Caution: People with cardiac pacemakers and

    other implanted electrically activated devices,or with ferromagnetic implants, may not be

    adequately protected by the limits given here.

    The majority of cardiac pacemakers are

    unlikely to be affected from exposure to fields

    below 0.5 milliTesla. (Static or D.C. magnetic

    fields)People with some ferromagnetic implants or

    electrically activated devices (other than

    cardiac pacemakers) may be affected by

    fields above a few milliTesla.

    (b) When magnetic flux densities exceed 3

    milliTesla (Static or D.C. magnetic fields),precautions should be taken to prevent

    hazards from flying metallic objects.

    Areas in which higher levels of exposure can

    occur outside safe approach distances (see

    Clauses 6.1 and 6.2) shall be fenced off to

    exclude access whilst electrical apparatus isenergised.

  • 8/4/2019 BlueBook 2008

    41/151

    4 TRAINING AND AUTHORISATION

    PRINCIPLE - Persons working on or near highvoltage electrical apparatus shall haveappropriate training, and authorisation for theduty to be performed.

    4.1 GENERAL

    An organisationssafe system of work shall include

    reference to appropriate training and authorisation

    for all persons working on or near high voltage

    electrical apparatus.

    All authorisations shall be reviewed annually by theorganisation to ensure the relevance of the authority

    to the holder's duties.

    Persons holding authorisations shall be

    competency assessed at no more than 3-yearly

    intervals and where appropriate training given to

    restore competency.

    Training and Authorisation

    Blue Book December 2005 Page 39 of 148

  • 8/4/2019 BlueBook 2008

    42/151

    Training and Authorisation

    Page 40 of 148 Blue Book December 2005

    4.2 APPROVED TRAINING STANDARD

    4.2.1 Introduction

    Training courses will consist of identified learning

    outcomes which will be knowledge, skill (task), and

    attitude based and where appropriate, reflect

    National Electricity Supply Industry Competency

    Standards.

    There shall be assessment criteria establishedand documented for each learning outcome.

    Details of assessment method shall bedocumented.

    There shall be a documented process forrecognition of prior learning.

    Persons undergoing training must beassessed for competency against all learningoutcomes relevant to the course, and suchassessment must be documented.

    4.2.2 Learning Outcomes

    Learning outcomes shall include, but not be limitedto, the following:

    Working knowledge of the relevant sections ofthis Code of Practice.

  • 8/4/2019 BlueBook 2008

    43/151

    Training and Authorisation

    Blue Book December 2005 Page 41 of 148

    Knowledge of communication processesrequired.

    Knowledge of the relevant Organisationalprocedures.

    A knowledge of the consequences of anyphysical tasks performed.

    A working knowledge and skill associated withthe relevant: Forms and documentation Risk assessment Work practices Equipment and plant

    Demonstration of acquired knowledge throughpractical exercises.

    A clear understanding of the responsibilitiesassociated with relevant authorisations, eg therange of responsibilities associated with aRecipient in Charge.

    Other training requirements as specifiedherein.

  • 8/4/2019 BlueBook 2008

    44/151

    Training and Authorisation

    Page 42 of 148 Blue Book December 2005

    4.2.3 Approved Training Courses and Processes

    Organisations shall approve course descriptors

    and service providers as meeting their recognisedneeds. The descriptors of each course shall

    include learning outcomes, assessment criteria

    and assessment methods.

    4.3 RECORDS

    Organisations shall develop and maintain anappropriate management system for recording of

    all training and authorisations.

  • 8/4/2019 BlueBook 2008

    45/151

    Work in the Vicinity of Electrical Apparatus

    Blue Book December 2005 Page 43 of 148

    5 WORK IN THE VICINITY OFELECTRICAL APPARATUS

    PRINCIPLE Work in the vicinity of electricalapparatusshall be carried out in a safe manner.Control measures taken shall be consistent withthe risk and work performed.

    5.1 GENERAL

    For all works in the vicinityof electrical apparatus

    either specific written work instructions shall be

    used or organisational procedures shall apply in

    conjunction with the use of instructed or authorised

    persons.

    Where the risk assessment requires a record of the

    control measures then instructions shall be issued

    to the work party in accordance with Organisational

    procedure.

    The control measures implemented shall minimisethe risks involved and may include:

    defining the work area;

    isolating and earthing the electrical apparatus;

  • 8/4/2019 BlueBook 2008

    46/151

    Work in the Vicinity of Electrical Apparatus

    Page 44 of 148 Blue Book December 2005

    the use of barriersand signs;

    the use of approvedcovering;

    the use of safety observers;

    the issue of the appropriate access authorityor authority to work in the vicinity of electricalapparatus; and

    defining access routes.

    5.2 HANDLING OBJECTS/LOADS

    When objects are being handled manually or by

    mechanical equipment, care shall be exercised to

    prevent the objects or the mechanical equipment

    infringing safe approach distances.

    For manual handling, appropriate work methodsand an appropriate number of persons shall be

    used to maintain safe approach distances.

    For mechanical handling where there is a risk of

    infringing the safe approach distances (refer

    section 6) to electrical conductors, the movement

    of loads shall be controlled by means of approvednon-conducting ropes or other approved means.

    No person outside the cabin shall contact the load,

    mobile plant or any attached conducting objects

    (Refer to clause 5.4 for protection of other persons).

  • 8/4/2019 BlueBook 2008

    47/151

    Work in the Vicinity of Electrical Apparatus

    Blue Book December 2005 Page 45 of 148

    5.3 ERECTION OR DISMANTLING OF

    OVERHEAD CONDUCTORS

    When overhead lines (other than insulated lowvoltage service lines) are being erected,

    dismantled, or replaced and there is any possibility

    of contact with, or induction from, adjacent live

    conductors of any description, such conductors

    being moved shall be earthed by an approved

    device before work is commenced and shall remaineartheduntil the work is completed. A conductor

    being so erected shall be earthedbefore it is lifted

    from the ground.

    Consideration shall be given to the use of

    appropriate restraining devices to control such

    conductorswhen they are being moved.5.4 USE OF MOBILE PLANT

    Mobile plantshall only be used in the vicinityof live

    conductors and/or electrical apparatus after

    precautions appropriate to the particular

    circumstances have been considered and action

    taken to control the associated hazards and risks.

    The control measures to be considered within a risk

    assessment shouldinclude:

  • 8/4/2019 BlueBook 2008

    48/151

    Work in the Vicinity of Electrical Apparatus

    Page 46 of 148 Blue Book December 2005

    isolating and earthing electrical apparatus;

    positioning the mobile plantsuch that the safe

    approach distance can be maintained in allcircumstances;

    the use of safety observersand barriersand

    signs;

    the use of other precautions such as physical

    restrictions or control devices in conjunctionwith barriers;

    the suppression of Auto-Reclose;

    the alteration of protection and control

    settings; and

    de-energising the electrical apparatus.Mobile plant, and where appropriate, vehicles, shall

    be fitted with a trailing earthing conductorto protect

    against the hazards presented by induced

    voltages.

    When mobile plantmay come near (refer section 6)

    live electrical apparatus, the mobile plantshall beearthed. This shall be achieved by an approved

    earthing system.

    When mobile plant is operated from outside the

  • 8/4/2019 BlueBook 2008

    49/151

    Work in the Vicinity of Electrical Apparatus

    Blue Book December 2005 Page 47 of 148

    mobile plant, precautions shall be taken to protect

    the operator from hazardous step and touch

    potentials. No person other than the mobile plantoperator shall touch the mobile plant whilst in

    operation.

    Where mobile plant e.g. EWP is only partially

    insulated, the following permanent sign shall be

    fixed at each operators station:

    DANGER BEWARE OF POWER LINES

    This appliance is not fully insulated. Do notpermit any uninsulated part of this appliance tobe in close proximity to live conductors.

    Insulated mobile plant shall be tested at specific

    intervals as per organisational procedures andmarked to show the date of the next routine test.

    5.5 WORK BY ORDINARY PERSONS

    Where ordinary personsare required to work in the

    vicinity of electrical apparatus, the ordinary person

    performing the work, the person in charge of the

    work and the person in charge of the electricalapparatus shall all cooperate to ensure that the

    work is performed safely, and that specific

    precautions are taken.

  • 8/4/2019 BlueBook 2008

    50/151

    Work in the Vicinity of Electrical Apparatus

    Page 48 of 148 Blue Book December 2005

    5.6 WORK WITHIN STATIONS OR ON MULTI-

    CIRCUIT OVERHEAD LINES WITH

    MULTIPLE ASSET OWNERSHIPFor work within stations or on Multi-Circuit

    Overhead Lines where electrical apparatus is

    owned by more than one Organisation and work is

    adjacent to another Organisation's exposed

    electrical apparatus, there shall be joint

    consideration and agreement reached to carry outthe work in a safe manner. (See also 6.10 and

    9.2.4)

  • 8/4/2019 BlueBook 2008

    51/151

    Approach To Electrical Apparatus

    Blue Book December 2005 Page 49 of 148

    6 APPROACH TO ELECTRICAL

    APPARATUS

    6.1 GENERAL

    The safe approach distances are based on an

    exclusion zone principle. This principle defines

    an area around the electrical apparatusinto which

    no part of the person, mobile plantor object (other

    than approved insulated objects) may encroachunless in accordance with Section 9. Refer figures

    2 & 3.

    When working at these distances work practices

    shall be established to ensure persons, mobile

    plantand unapprovedobjects do not encroach on

    the safe approach distances.Unnecessary approach to electrical apparatus or

    unnecessary contact with parts not regarded as

    live shall be avoided.

    PRINCIPLE Persons shall observeappropriate safe approach distance whenworking, or operating vehicles or mobileplant, on or near electrical apparatus

  • 8/4/2019 BlueBook 2008

    52/151

    Approach To Electrical Apparatus

    Page 50 of 148 Blue Book December 2005

    Necessary approach to electrical apparatus shall

    be kept to a minimum and shall be restricted to the

    period required to perform the work.

    Figure 2: Safe Approach Distance Application

  • 8/4/2019 BlueBook 2008

    53/151

    Approach To Electrical Apparatus

    Blue Book December 2005 Page 51 of 148

    Figu

    re3:IllustrationofDiffer

    encesbetweenSafeApp

    roachDistance,Nearand

    Vicinity

    Vicinitymeansasituationwhereitisunlikely

    thatapersonwill,eitherdirectlyorthroughanyconduct

    ing

    medium(egmobileplant)comewithintherelevant

    safeapproachdistances.

    Nearmeansasituationwhere

    there

    isareasonablepossibilityofaperson,

    eitherdirectlyorthroughany

    conductingmedium(eg:viamo

    bileplant)

    comingwithintherelevant

    safeapproachdistances.

    Safe

    ApproachDistancemeanstheminimum

    distanc

    ethatshallbemaintaine

    dbyaperson

    vehicle

    ormobileplant(includin

    gitsload-controlling

    ropesandotheraccessories)w

    henapproaching

    electric

    alapparatusotherthanforwork

    inacco

    rdancewithanaccessauthority.

    Conductorm

    eansawire,

    cableorformof

    metaldesigned

    forcarryingelec

    tricalcurrent.

  • 8/4/2019 BlueBook 2008

    54/151

    Approach To Electrical Apparatus

    Page 52 of 148 Blue Book December 2005

    6.2 SAFE APPROACH DISTANCE PERSONS

    6.2.1 Safe Approach Distance

    The safe approach distances for persons

    conducting general work are as shown in Table 1.

    Instructed persons safe approach distances apply

    whilst undertaking duties under supervision or as

    instructed by an authorised person.

  • 8/4/2019 BlueBook 2008

    55/151

    Nominal Phase toPhase AC Voltage

    Ordinary Persons Instructed Persons orAuthorised Persons

    kV Millimetres Millimetres

    LV Aerial Lines 1500 Instructed Persons -

    No contactAuthorised Persons -

    insulated contact only

    Nominal Pole to Earth

    DC Voltage (kV)

    1.5 or less 1500

    Instructed Persons-

    No contactAuthorised Persons-

    insulated contact only

    6.6 2000 70011 2000 70022 2000 700

    33 2000 70050 2000 75066 2000 900

    110 3000 1000132 3000 1200220 4000 1700275 5000 2300330 6000 2700400 6000 3300500 6000 3600

    +/- 25 2000 700+/- 85 3000 1000+/- 150 3000 1200+/- 270 4500 1800

    +/- 350 5000 2500+/- 400 6000 2900

    Notes:(1) Deliberately avoid movements that could result in distances being

    infringed.(2) These distances specified are based on work from a stable surface.

    Appropriate allowance shall be made for conductorsag and sway.

    Table 1 - Safe Approach Distancesfor Persons to Exposed Conductors

    Approach To Electrical Apparatus

    Blue Book December 2005 Page 53 of 142

  • 8/4/2019 BlueBook 2008

    56/151

    6.2.2 SAFE APPROACH DISTANCE

    SPECIAL

    The safe approach distance(given in table 2) whichmay be used for authorised persons conducting

    general work has been determined using risk

    analysis methodology and consideration of power

    frequency and switching surge distances plus a

    safety margin.

    Approach To Electrical Apparatus

    Blue Book December 2005 Page 54 of 142

    Figure 4 Safe Approach Distance - Special

  • 8/4/2019 BlueBook 2008

    57/151

    Blue Book December 2005 Page 55 of 148

    Approach To Electrical Apparatus

    These safe approach distancesmay only be used

    in conjunction with the following control measures:

    The safe approach distancesshall bemaintained from any part of the persons body

    or any conducting or unapprovedobject

    touching any part of the persons body by using

    controlled movement;

    Positioning of the worker to minimise the risk of

    the specified distance being infringed. Thisincludes any unapprovedobject or tool being

    held by the worker;

    A person specifically trained and authorised to

    perform the work at the safe approach

    distance;

    Workcrew on site risk assessments are

    conducted;

    Safety observersare used to monitor the work

    activities;

    Minimise the exposure at the safe approach

    distance;

    Addressing adverse Impact of external

    influences on plant and equipment, e.g. traffic,

    boom movement, footing.

  • 8/4/2019 BlueBook 2008

    58/151

    Approach to Electrical Apparatus

    Page 56 of 148 Blue Book December 2005

    Addressing adverse impact of weather and

    environmental conditions (e.g. rain, lightning,

    wind, light, sag or sway of conductors).If these controls are not achieved either access

    authoritiesshall be issued or live work techniques

    shall be applied or alternative special safe

    approach distances and procedures developed in

    accordance with Clause 6.2.3

  • 8/4/2019 BlueBook 2008

    59/151

    Approach to Electrical Apparatus

    Blue Book December 2005 Page 57 of 148

    Table 2 - Safe Approach Distance - Special

    Nominal Phase to PhaseAC Voltage

    Authorised Persons

    KV Millimetres

    LV Insulated contact only

    6.6 300

    11 30022 300

    33 500

    50 700

    66 700

  • 8/4/2019 BlueBook 2008

    60/151

    Page 58 of 148 Blue Book December 2005

    Approach To Electrical Apparatus

    6.2.3 Guidelines for the Development anduse of Alternative Safe Approach

    Distances - SpecialWhen determining the safe approach distance -special and performing the task the followingcontrols shall be considered:

    Determining special safe approach distancesfrom:

    ENA NENS 04-2006 NationalGuidelines for Safe Approach Distancesto Electrical and Mechanical Apparatusand/or IEEE 516 and related guidelinesas may be appropriate; and

    Clause 9.6 Live Work High Voltage.

    When developing organisational proceduresspecial consideration shall be given to:

    Flashover;

    Possibility of inadvertent movement;

    Minimising the duration of work at thespecial safe approach distance; and

    Work techniques which providemaximum practical distance from liveconductors.

  • 8/4/2019 BlueBook 2008

    61/151

    Blue Book December 2005 Page 59 of 148

    Workcrew on site risk assessment shallconsider:

    Control of inadvertent movement by theuse of insulating barriers, insulated plantand appliances and controlled bodymovements; and

    Environmental conditions.

    6.3 SAFE APPROACH DISTANCES -VEHICLES

    6.3.1 Ordinary Persons

    An ordinary person in charge of any vehicle,excepting mobile plant when in working mode,

    shall ensure that no part of the vehicleor its load isplaced or moved within the distances shown inTable 3.

    6.3.2 Authorised and Instructed Persons

    Authorised and instructed personsin charge of anyvehicle, excepting mobile plant when in workingmode, shall ensure that no part of the vehicleor its

    load is placed or moved within the distances shown inTable 3.working mode)

    Approach To Electrical Apparatus

  • 8/4/2019 BlueBook 2008

    62/151

    Page 60 of 148 Blue Book December 2005

    Approach To Electrical Apparatus

    (1) All distances specified are based on work from a stable surface. Appropriateallowance shall be made for conductor sag and sway and for uncontrolled movement ofvehicle or plant due to any reason.

    Nominal Phase toPhase Voltage (AC)

    Safe ApproachDistance- for VehiclesUnder the Control of

    Ordinary Persons(note 1)

    Safe ApproachDistance- for Vehicles

    under the control of

    Instructed PersonsorAuthorised Persons

    (note 1)

    kV Millimetres Millimetres

    Table 3 - Safe Approach Distance for Vehicle to exposed

    live conductors (excepting Mobile Plant when in the

    working mode)

    Low Voltage 600 600

    HV up to/including 33 1000 700

    50 1000 750

    66 1000 1000

    110 1500 1000

    132 1500 1200

    220 4600 1800

    275 4600 2300

    330 5500 2300400 6400 3300

    500 6400 3900

    Nominal Pole to Earth

    DC Voltage

    +/- 25+/- 25 10001000 700700

    +/- 85+/- 85 15001500 10001000

    +/- 150+/- 150 15001500 12001200

    +/- 270+/- 270 46004600 18001800+/- 350+/- 350 55005500 25002500

    +/- 400+/- 400 64006400 29002900

  • 8/4/2019 BlueBook 2008

    63/151

    Approach To Electrical Apparatus

    Blue Book December 2005 Page 61 of 148

    (1) All distancesspecified arebased on workfrom a stablesurface.

    Appropriateallowance shall bemade forconductor sag andsway and foruncontrolledmovement ofvehicle or plantdue to any reason.(2) A safetyobserver is

    required unlessthe mobile plant isincapable ofinfringing the safeapproach distance.

    Table 4 Safe Approach Distance for Mobile Plant to

    exposed live conductors when in the working mode

    Nominal Phase to

    Phase Voltage(AC)

    Safe Approach

    Distance- forMobile Plant

    Under theControl of

    Ordinary Persons(Notes 1 & 4)

    Safe Approach

    Distance- forMobile Plant Under

    the Control of

    Instructed Persons

    or Authorised

    Persons(for

    Insulated Mobile

    Plantrefer table 5)

    (Notes 1 & 2)

    Safe Approach

    Distance- forMobile Plant Under

    the Control of Glove

    and Barrier Live-

    Line Work

    Authorised Persons

    (for Insulated Mobile

    Plantrefer Table 5)

    (Notes 1, 2 &3)

    kV Millimetres Millimetres Millimetres

    Low Voltage 2000 1000 380

    HV up

    to/including 33

    2000 1200 1000

    50 2000 130066 2000 1400110 4000 1800132 4000 1800220 4600 2400

    275 4600 3000330 5500 3700400 6400 4000500 6400 4600

    Nominal Pole toEarth DC Voltage

    +/- 25 2000 1200+/- 85 4000 1800+/- 150 4000 1800

    +/- 270 4600 2400+/- 350 5500 3200+/- 400 6400 3600

    (3) When lifting a load the conductors are suitably insulated in accordance withorganisational procedures.

    (4) Including Insulated Elevating Work Platforms.

  • 8/4/2019 BlueBook 2008

    64/151

    Approach To Electrical Apparatus

    Page 62 of 148 Blue Book December 2005

    6.4 SAFE APPROACH DISTANCES

    UNINSULATED MOBILE PLANT

    6.4.1 General

    Because of the physical capabilities of, and

    potential hazard with mobile plantworking adjacent

    to live conductors and/or electrical apparatus,

    specific consideration (including earthing) shall be

    given to its use during planning of the work. (Refer

    5.4)

    6.4.2 Ordinary Persons

    An ordinary person in charge of the work shall,

    ensure that the mobile plant, its equipment and

    load is not placed or moved within the distances

    shown in Table 4.6.4.3 Instructed Persons or Authorised Persons

    An instructed person or authorised person in

    charge of the work shall ensure that the mobile

    plant, its gear and load shall not approach live

    conductorsand/or electrical apparatus within the

    distances as shown in Table 4.

    When working under glove and barrier procedures,

    and where the conductors and load are suitably

    insulated, the load should remain a minimum of 380

  • 8/4/2019 BlueBook 2008

    65/151

    Blue Book December 2005 Page 63 of 148

    mm (at 22 kV) from the conductor(allowing for sag

    and sway of the conductor). Every effort should be

    made for the load to avoid accidental contact withthe conductors.

    When the work requires a closer approach to live

    conductors than the normal safe approach

    distancesgiven in Table 4 special safe approach

    distancesfor mobile plantmay be developed and

    applied with consideration of the requirements setout in 6.2.3

    The use of helicopters for bare hand live line work

    is excluded from the requirements of this clause.

    6.5 SAFE APPROACH DISTANCE

    INSULATED MOBILE PLANT

    Only instructed personsor authorised personsmay

    operate insulated mobile plantin accordance with

    Table 5 and organisational procedures.

    The insulated portion of mobile plantmay contact

    or encroach at distances less than the safe

    approach distanceto a live conductorspecified inTable 5 provided it is rated for the purpose for which

    it is intended to be used.

    Approach To Electrical Apparatus

  • 8/4/2019 BlueBook 2008

    66/151

    Approach To Electrical Apparatus

    (1) These distances specified are based on work from a stable surface.Appropriate allowance shall be made for conductor sag and sway, andfor uncontrolled movement of the Mobile plant for any reason.(2) For ordinary persons refer to Table 4.(3) For safe approach distance where contact is allowed, careshall be exercised to prevent movement of conductors.(4) For live work in accordance with Organisational Procedures.

    Table 5 - Safe Approach Distances to Exposed Live Conductors for

    Insulated mobile plant operated by persons who are instructed or

    authorised to work on or near exposed conductors.

    Safe Approach

    Distances

    (Note 1, 2 and 3)

    Working Within Safe

    Approach Distance

    (Note 1, 3 and 4)

    kV Millimetres MillimetresInsulated

    portions

    Uninsulated

    portions

    Insulated

    portions

    Uninsulated

    portions

    ContactAllowable

    1000 ContactAllowable

    1000

    700 1200 Contact 1000

    1000 1400 Contact 1000

    1800 2400 Contact

    Allowable

    1800

    2300 3000 Contact

    Allowable

    2300

    3000 3700 ContactAllowable

    3000

    3900 4600 ContactAllowance

    3900

    HV up to andincluding 33

    66

    220

    275

    330

    500

    Nominal Pole to

    earth DC Voltage kV

    +/- 25

    +/- 85

    700 1200 Contact

    Allowable

    1000

    1000 1800 Contact

    Allowable

    1000

    Nominal Phase toPhase AC Voltage

    Page 64 of 148 Blue Book December 2005

    Low Voltage

  • 8/4/2019 BlueBook 2008

    67/151

    Approach To Electrical Apparatus

    Blue Book December 2005 Page 65 of 148

    6.6 EMERGENCY APPROACH

    In emergency situations where there is likely risk of

    electric shock to persons from electricalconductors or electrical apparatus, e.g. fallen

    conductor, prompt action shall be taken to ensure

    people are kept well clear of the hazard at a greater

    than safe approach distances in accordance with

    organisational procedures.

    Safe Approach Distances shall apply only after theoperating authority has established that these

    requirements can be safely applied.

    6.7 CONTACT WITH LIVE HIGH VOLTAGECONDUCTORS BY MEANS OF

    APPLIANCES

    Only approved and tested appliances shall be

    permitted to be brought within the safe approach

    distance, or into direct contact with live high voltage

    conductors.

    6.8 APPROACH TO LIVE HIGH VOLTAGE

    INSULATED CABLES6.8.1 General

    When work is performed near live high voltage

    insulated cables, appropriate precautions shall be

  • 8/4/2019 BlueBook 2008

    68/151

    Page 66 of 148 Blue Book December 2005

    Approach To Electrical Apparatus

    taken to ensure that the insulation of the cables is

    not damaged.

    Cables, which are specifically designed formovement whilst live, may be moved in accordance

    with organisational procedures.

    Slight movement of other types of live cablesmay

    be permitted, but only after detailed consideration

    of all related circumstances by a person with a

    detailed knowledge of the cablesconcerned, whoshall fully detail all precautions to be taken.

    6.8.2 Earthed Metallic Sheathed or Screened

    High Voltage Cables

    Contact by persons may be made to external

    surfaces of live high voltage cables with earthedmetallic sheaths or screens.

    6.8.3 Non-Metallic Screened High Voltage AerialBundled Cable

    No body contact shall be made to external surfaces

    of live non-metallic screened high voltage aerial

    bundled cable or exposed support conductors.Suitable liveline techniques only shall be used for

    this purpose.

    Access to de-energised but not earthed non-

  • 8/4/2019 BlueBook 2008

    69/151

    Blue Book December 2005 Page 67 of 148

    Approach To Electrical Apparatus

    metallic screened high voltage aerial bundled

    cable may be permitted in accordance with

    organisational procedures.For the purposes of Insulated Mobile Plant work in

    the vicinity of live non-metallic screened high

    voltage aerial bundled cable the safe approach

    distance shall be the same as exposed high

    voltage conductors. (Refer Table 5)

    6.9 WORK IN STATIONS

    6.9.1 A person shall not perform work in any stationor allow mobile plant to enter any station without

    first obtaining the permission of the person in

    charge of the station and accepting all the

    conditions imposed by that person.

    6.9.2 An access authorityand or authority to workin the vicinity of live apparatus (refer Clause 5.1)

    shall be issued where

    mobile plantor elevating platform or other

    large vehicleswill be used; or

    the work involves excavation or the use ofexplosives.

  • 8/4/2019 BlueBook 2008

    70/151

    Page 68 of 148 Blue Book December 2005

    Approach To Electrical Apparatus

    6.10 WORK OUTSIDE OF STATIONS

    Work on or near electrical apparatus outside of

    stations shall be performed after obtaining thepermission and direction of the Network Operator.

  • 8/4/2019 BlueBook 2008

    71/151

    Blue Book December 2005 Page 69 of 148

    Operation of High Voltage Electrical Apparatus

    7 OPERATION OF HIGH VOLTAGEELECTRICAL APPARATUS

    7.1 PERSONS AUTHORISED TO OPERATEHIGH VOLTAGE ELECTRICAL APPARATUS

    Switching and associated duties on high voltage

    electrical apparatus should be performed by

    authorised electrical operators whose training,

    duties and instructions cover the particular

    electrical apparatus. However, any person may

    perform operations in the following circumstances:

    When specifically instructed by, or authorised

    by, the appropriate operating authority;

    In an emergency involving serious risk to

    persons or property; or

    Where they operate high voltage electrical

    apparatusas part of process control.

    PRINCIPLE Only authorised persons shallundertake switching and associated duties onhigh voltage electrical apparatus

  • 8/4/2019 BlueBook 2008

    72/151

    Page 70 of 148 Blue Book December 2005

    7.2 HIGH VOLTAGE SWITCHING

    Prior to a high voltage switching operation, the

    available information regarding circuit conditionsshall be taken into account and no electrical

    apparatusshall be operated if it is inappropriate for

    the duty to be performed. After switching, correct

    operation of the electrical apparatus should be

    confirmed whenever possible.

    When high voltage electrical apparatus isoperated, the person undertaking the task shall be

    protected in an approved manner from electric

    shock, flash or other hazards. (also refer 3.9)

    Operation of High Voltage Electrical Apparatus

  • 8/4/2019 BlueBook 2008

    73/151

    Blue Book December 2005 Page 71 of 148

    8 EARTHING OF HIGH VOLTAGEELECTRICAL APPARATUS

    8.1 GENERAL8.1.1 Only approved earthing devices shall be

    used and only authorised personsshall apply them

    after the circuit or electrical apparatus is isolated

    and after confirmation by tests, visual inspection or

    inquiry that the conductorsare de-energised.

    8.1.2 In applying an earthing device, it shall beconnected to earth before it is applied to the

    conductors, and it shall be removed from the

    conductorsbefore it is disconnected from earth.

    8.1.3 Wherever practicable, an earth shall be

    applied and removed by an approveddevice.

    When hand application or removal is unavoidable:

    All phases shall be discharged, and

    Another earth shall be held in contact with the

    PRINCIPLE Earthing devices shall be appliedby an authorised person following a safe to earth

    confirmation and placed to ensure the safety of

    the work party.

    Earthing of High Voltage Electrical Apparatus

  • 8/4/2019 BlueBook 2008

    74/151

    Page 72 of 148 Blue Book December 2005

    Earthing of High Voltage Electrical Apparatus

    conductor using an approveddevice while

    the hand applied earth is being attached or

    removed.8.1.4 When applying a portable earthing device

    that is not connected to a permanently installed

    station earthing system it shall be regarded as

    being liable to become live until the circuit earthing

    is complete.

    8.1.5 There are some situations where anauthorised electrical operatorcannot comply with

    the clearances specified as safe approach

    distances, when applying earths to electrical

    apparatusduring the preparation for access, eg.,

    discharging capacitor banks. In these situations,

    organisational procedures may permit suchapproach only to that part of the electrical

    apparatus which already has local isolation and

    earthing.

    8.2 EARTHING FOR ACCESS TO HIGHVOLTAGE ELECTRICAL APPARATUS

    Earths shall be applied at locations such thatconductors within the work area are effectively

    earthed in the event of energisation from any

    source of supply or hazardous occurrences and be

  • 8/4/2019 BlueBook 2008

    75/151

    Blue Book December 2005 Page 73 of 148

    so placed as to remain effective if adjoining

    conductors are disconnected.

    Wherever practicableearths shall be placed at thesite of the work.

    8.3 REMOVAL OF EARTH WHEN WORKING

    UNDER AN ACCESS AUTHORITY

    During work under an access authority, the

    recipient in chargemay authorise the removal of anearth for meggering, reconductoring, or other

    purposes, only if such action is considered

    necessary and safe, and provided

    the operating authoritythat has operational

    control of the earth and the operating

    authority who applied the earth agrees; in cases where the earth is listed on the

    access authority, the operating authoritywho

    issued the access authority is consulted, to

    confirm that the removal of the earth will not

    affect any other access authoritieson issue;

    persons likely to be affected by the removalof the earth are notified; and

    consideration is given to induced voltages.

    Earthing of High Voltage Electrical Apparatus

  • 8/4/2019 BlueBook 2008

    76/151

    Page 74 of 148 Blue Book December 2005

    The earth removed shall be replaced in the same,or other equally effective position, as soon as

    possible.8.4 EARTHING OF OVERHEAD LINES

    Where an overhead line can only be earthed usingtemporarily driven earth spikes the work planningshall consider protection from the hazards resultingfrom energisation and step and touch potentials

    (Refer to Clause 8.7 for priority earthing)

    8.5 HIGH VOLTAGE METAL-CLAD SWITCHUNITS

    For metal-clad switch units and circuits connectedthereto, the method of earthing shall be speciallyconsidered by the organisation responsible for the

    earthing and the person in charge of the work,particularly in regard to the number and location ofearths. The application of earthing devices toisolating contacts in the spouts of metal-cladswitchgear shall be supervised by an authorisedperson, unless the devices are specificallyapproved by the organisation which owns theelectrical apparatusfor application by one person.

    Earthing of High Voltage Electrical Apparatus

  • 8/4/2019 BlueBook 2008

    77/151

    Blue Book December 2005 Page 75 of 148

    8.6 HIGH VOLTAGE CAPACITORS

    To declare high voltage capacitors safe for the

    issue of an electrical access permit, the neutral aswell as the actives shall be earthedand, in addition,

    each individual capacitor shall be discharged

    before it is touched. The same precautions shall be

    taken for work on electrical apparatus which

    incorporates high voltage capacitors (e.g.

    capacitor voltage transformers, carrier couplingcapacitors).

    8.7 OVERHEAD LINES PRIORITY EARTHINGSYSTEM

    The choice of connection for an earthing device

    should where practicablebe made on the basis of

    the following order of preference:

    1. Permanently installed earthing system at the

    worksite, including the neutral conductor of a

    Common Multiple Earthed Neutral (CMEN)

    System [Not to be confused with a Multiple

    Earthed Neutral (MEN) System];

    2. Permanently installed earthing system as

    close as possible to the worksite (within 2

    kilometres);

    Earthing of High Voltage Electrical Apparatus

  • 8/4/2019 BlueBook 2008

    78/151

    Page 76 of 148 Blue Book December 2005

    3. Earthing ferrule in a concrete pole at theworksite;

    4. Earthing ferrule in a concrete pole as closeas possible to the work site (within 2

    kilometres);

    5. A permanently installed earthing system orconcrete pole earthing ferrule within the

    isolation area;

    6. The ground rod of an installed pole stay or

    permanently driven pole stakes;

    7. A temporarily driven spike.

    Earthing of High Voltage Electrical Apparatus

  • 8/4/2019 BlueBook 2008

    79/151

    Blue Book December 2005 Page 77 of 148

    9 ACCESS FOR WORK ON OR NEARHIGH VOLTAGE ELECTRICAL

    APPARATUS

    9.1 GENERAL

    No person shall touch or work near the high voltage

    conductorsof any electrical apparatusunless

    the person is a recipientof an electrical

    access permitcovering that electrical

    apparatusand the high voltage

    conductorshave been dischargedand/orearthedat the work site, and the electrical

    access permitis availablefor reference at the

    site of the work;

    the person is a recipientof an electrical

    access permitcovering the conductors of a

    high voltage cable and the de-energisedstate of the cable at the work site is confirmed

    in accordance with clause 9.8 and the

    electrical access permitis available for

    reference at the site of the work;

    PRINCIPLE An appropriate safe access systemshall be applied before any work on or near highvoltage electrical apparatus

    Access for Work on or Near High Voltage ElectricalApparatus

  • 8/4/2019 BlueBook 2008

    80/151

    Page 78 of 148 Blue Book December 2005

    in the case of a rackable circuit breakeror

    rackable voltage transformer, the electrical

    apparatusis removed from its rack or cubicleposition and placed in a designated

    maintenance position;

    the person is working under the terms of a

    sanction for testingon that electrical

    apparatus;

    the person is changing high voltageclamp-on type fuse links at single wire earth return

    distribution substations in accordance with

    Organisational procedures;

    the electrical apparatushas been declared

    as out-of-commission in accordance with

    clause 9.4;

    the person is performing livework in

    accordance with Organisational procedures;

    the person is working in accordance with the

    requirements of a person who has received

    an appropriate permit to work adjacent tonetwork assets, authority (Refer to Section

    12); or

    the person is working near high voltage

    Access for Work on or Near High Voltage ElectricalApparatus

  • 8/4/2019 BlueBook 2008

    81/151

    Blue Book December 2005 Page 79 of 148

    conductors under the requirements of safeapproach distance special as determined

    by Organisational procedures in accordancewith clause 6.2.2.

    9.2 ELECTRICAL ACCESS PERMITPROCEDURE

    9.2.1 Application for an Electrical Access Permit

    Before making application for an electrical accesspermit, the authorised applicantshall establish thatthe proposed work has been properly planned andcan be carried out safely.

    The electrical apparatus to be covered and itslocation shall be accurately defined and the work tobe undertaken adequately described.

    9.2.2 Testing Under an Electrical Access Permit

    Testing under an electrical access permitmay beundertaken in accordance with organisationalprocedures which include:

    a risk assessment to ensure that no

    hazardous voltages and currents will bepresent as a result of the testing; and

    that the provisions of clause 8.3 are met.

    Access for Work on or Near High Voltage ElectricalApparatus

  • 8/4/2019 BlueBook 2008

    82/151

    Page 80 of 148 Blue Book December 2005

    9.2.3 Multiple Working Parties

    When more than one electrical access permit is

    issued on the same electrical apparatus, or whereseparate parties are working under the terms of oneelectrical access permit, there shall be co-ordination in planning and performing the work toensure that the actions of one party shall notendanger the safety of others.

    9.2.4 Multiple Ownership

    Where the scope of electrical apparatus to becovered is owned by more than one organisation, aprotocol shall be established between theseorganisations for processing the application andoutage requirements.

    9.2.5 Issue and Receipt of Electrical AccessPermits

    9.2.5.1 An electrical access permitmust be eithercancelled or suspended prior to the issue of asanction for testing on the same electricalapparatus.

    9.2.5.2 An electrical access permitshall be issuedand cancelled only by an authorised electricaloperator. Electrical access permitsmay be issuedor relinquished by telephone or radio subject to the

    Access for Work on or Near High Voltage ElectricalApparatus

  • 8/4/2019 BlueBook 2008

    83/151

    Blue Book December 2005 Page 81 of 148

    statements between the authorised electricaloperator and the recipient in charge being

    confirmed by a witness at each end.9.2.5.3 At the time of issue the authorised electricaloperator shall describe and, where practicable,show the electrical apparatus covered by theelectrical access permitand the precautions taken,to the recipient in charge and all the initial

    recipients.The authorised electrical operator shall alsodescribe or point out the nearest points of supplyand adjacent live electrical apparatus. In the caseof an electrical access permitissued by telephoneor radio the recipient in chargeshall assume theseresponsibilities.

    9.2.5.4 Each electrical access permit shall beissued to a recipient in charge. The recipient inchargeshall ensure that all members of the workparty who will approach the electrical apparatussign on the electrical access permit.

    9.2.5.5 The issuer and authorised recipients allhave a responsibility to ensure that the condition ofthe electrical apparatus, covered by the electricalaccess permit, is such that it shall be safe for theproposed work to be undertaken.

    Access for Work on or Near High Voltage ElectricalApparatus

  • 8/4/2019 BlueBook 2008

    84/151

    Page 82 of 148 Blue Book December 2005

    9.2.5.6 All recipients shall be satisfied with theprecautions taken, the location of the points of

    supply, and the proximity of any adjacent liveelectrical apparatus.

    9.2.5.7 Any person involved in the issue or receiptof an electrical access permitwho is not satisfiedwith the conditions, may apply to have additionalprecautions taken, either before the electrical

    access permit is issued or during the currency ofthe work.

    9.2.5.8 Subsequent to the issue of an electricalaccess permitadditional recipientsmay sign on theelectrical access permit, after appropriateinstruction by the recipient in charge or by anauthorised electrical operator acting with theknowledge of the recipient in charge.

    9.2.6 Persons Permitted to Sign ontoElectrical Access Permits

    Recipientsof an electrical access permitshall beauthorised recipients or instructed persons

    approved to work under that specific electricalaccess permit. In the latter case it shall be theresponsibility of the recipient in charge to ensurethat such persons are placed in the charge of anauthorised recipient.

    Access for Work on or Near High Voltage ElectricalApparatus

  • 8/4/2019 BlueBook 2008

    85/151

    Blue Book December 2005 Page 83 of 148

    The conditions under which authorised recipientsshall sign onto an electrical access permit is that

    the recipient: Understands the electrical apparatus

    covered and the limits of the electricalaccess permit;

    Is satisfied with the precautions taken; and

    Is aware of the nearest adjacent live electricalapparatus.

    The conditions under which an instructed personshall sign onto an electrical access permit is thatperson:

    Understands instructions given on what

    approach is permitted to the electricalapparatus;

    Understands instructions given on whatactivity is permitted to be taken in relation tothe electrical apparatus; and

    Agrees to the continuous and close

    supervision by a nominated authorisedrecipient.

    Access for Work on or Near High Voltage ElectricalApparatus

  • 8/4/2019 BlueBook 2008

    86/151

    Page 84 of 148 Blue Book December 2005

    9.2.7 Rejection of a Recipient

    A person shall recommend the exclusion from an

    electrical access permitof any other person who atanytime is considered unsafe as a recipient. Suchinstances shall be reported promptly to the personin charge of the work.

    9.2.8 Absence of an Earth on ElectricalApparatus Under Electrical Access Permit

    Wherever practicable electrical apparatusshall beearthed before the issue of an electrical accesspermit.

    Where an earth has not been applied to electricalapparatusprior to the issue of an electrical accesspermit the recipient in charge shall arrange fordischarging and/or earthing of the electricalapparatus before any recipient touches the highvoltage conductors.

    9.2.9 Recipient Working Alone

    An electrical access permitmay be issued to one

    authorised recipient, or a recipientmay work aloneunder the terms of an electrical access permit, onlyin accordance with Organisational procedures.

    Access for Work on or Near High Voltage ElectricalApparatus

  • 8/4/2019 BlueBook 2008

    87/151

    Blue Book December 2005 Page 85 of 148

    9.2.10 Issuer also a Recipient

    An issuer of an electrical access permitshall not be

    the recipient in charge, but may sign on theelectrical access permit form as an authorisedrecipient.

    9.2.11 Temporary Cessation of Work or Absenceof Recipients

    Following a cessation of work or when recipientshave been temporarily absent from the work site,upon return each recipient, shall report to therecipient in charge to re-confirm the conditions ofthe electrical access permit.

    9.2.12 Working on Multi-Circuit Overhead Lines

    Where more than one high voltagecircuit is carriedon a pole or line structure and work is to beperformed on circuits under an electrical accesspermit whilst others remain live, the recipient inchargeshall ensure that each member of the workparty who approaches near any circuits correctlyidentify the circuit/s under electrical access permit

    and all other circuits.

    Access for Work on or Near High Voltage ElectricalApparatus

  • 8/4/2019 BlueBook 2008

    88/151

    Page 86 of 148 Blue Book December 2005

    9.2.13 Change of Electrical Access PermitConditions

    The conditions specified and the precautions listedon the electrical access permit shall not bechanged unless mutually agreed upon by both theoperating authority and the recipient in charge andthen only when a check has been made with theappropriate operating authority regarding the

    requirements of other electrical access permits andall recipients working under the electrical accesspermit have been notified of the change.

    9.2.14 Cancellation of an Electrical AccessPermit

    9.2.14.1 Recipients signing off an Electrical

    Access PermitIt shall be the duty of each recipientof an electricalaccess permit to sign off before the electricalaccess permitis relinquished.

    9.2.14.2 Responsibilities of the Recipient-inCharge when relinquishing an

    Electrical Access Permit for cancellation.

    When an electrical access permit is to berelinquished for cancellation, the recipient-in-chargeshall:

    Access for Work on or Near High Voltage ElectricalApparatus

  • 8/4/2019 BlueBook 2008

    89/151

    Blue Book December 2005 Page 87 of 148

    ensure that all recipients signed on theelectrical access permithave ceased work

    covered by the electrical access permitandhave signed off;

    ensure that all recipientsand equipment areclear and will remain clear of the electricalapparatus;

    sign off the electrical access permitas the

    recipient-in-chargeto indicate that theelectrical access permitcan be cancelled; and

    Advise the operating authorityof any conditionof the electrical apparatuswhich couldaffect its operation.

    9.2.14.3 Absence of a Recipient at

    Relinquishment

    The practice of signing off an electrical accesspermiton behalf of another person is undesirableand should be avoided.

    Appropriate organisation procedures should beimplemented with instructions for signing offrecipients where the recipients could not belocated.

    Access for Work on or Near High Voltage ElectricalApparatus

  • 8/4/2019 BlueBook 2008

    90/151

    Page 88 of 148 Blue Book December 2005

    9.3 SANCTION FOR TESTING PROCEDURE

    9.3.1 General

    9.3.1.1 A sanction for testingshall be used if thetesting of high voltage electrical apparatushas thepotential to produce currents hazardous to thehuman body.

    9.3.1.2 A sanction for testing must be eithercancelled or suspended prior to the issue of aelectrical access permit on the same electricalapparatus.

    9.3.1.3 A Tester Responsible at Remote Locationis an authorised tester at a remote location to whoman authorised electrical operator has issued aComplementary Sanction for Testing.

    9.3.1.4 Only one sanction for testing shall be onissue on the same electrical apparatusat any time.However, where the testing requires work at remotelocations, as well as the nominated main location,a Complementary Sanction for Testing covering thesame electrical apparatusshall be issued at eachremote location.

    A Complementary Sanction for Testing shall bestructured to agree with that on the parent sanctionfor testing applicable at the nominated mainlocation. It shall be issued to an authorised testerateach remote location, who shall sign it as the Tester

    Access for Work on or Near High Voltage ElectricalApparatus

  • 8/4/2019 BlueBook 2008

    91/151

    Blue Book December 2005 Page 89 of 148

    Responsible at the Remote Location.

    A Complementary Sanction for Testing shall