CODE OF PRACTICE
OF ELECTRICAL SAFETYFOR
WORK ON OR NEARHIGH VOLTAGE
ELECTRICAL APPARATUS
(THE BLUE BOOK)
2005
VICTORIA
-
8/4/2019 BlueBook 2008
2/151
ISSUE SHEET
Copy Number . . . . . . . . . . . . . . . . . . . . . .
CONTROLLED COPY
UNCONTROLLED COPY
(Note: Uncontrolled copies will NOT be subject
to automatic revision servicing)
ISSUED TO: . . . . . . . . . . . . . . . . . . . . . . .
COMPANY: . . . . . . . . . . . . . . . . . . . . . . .
DATE: . . . . . . . . . . . . . . . . . . . . . . . . . . . .
This book to be returned to the issuer onrequest or on termination of employment.
ISSUED BY: . . . . . . . . . . . . . . . . . . . . . . .
-
8/4/2019 BlueBook 2008
3/151
Blue Book December 2005 Page 1 of 148
NOTE TO USERS
The Electrical Safety Committee (ESC) calls to the
attention of users of this publication that the
following important matters are applicable to its
use:
DISCLAIMER
No person should act or rely on the contents of this
publication before considering and, if appropriate,
taking professional advice upon that persons own
particular circumstances. The ESC believes that, to
the best of its knowledge, the information in this
publication is correct but no person gives any
warranty of completeness, accuracy or reliability inrespect of the information or publication. This
publication is sold or otherwise made available on
the basis that the ESC and its respective
representatives, members, employees and agents,
the authors and the publishers:
(1) are not responsible for any error in oromission from this publication, and
(2) except for liability under statute which cannot
be excluded, expressly disclaim all and any
-
8/4/2019 BlueBook 2008
4/151
Page 2 of 148 Blue Book December 2005
liability, including without limitation for
negligence, to any person, whether a
purchaser of this publication or not, in respectof anything and of the consequences of
anything done or omitted to be done by any
person in reliance, whether whole or partial,
upon the whole or any part of the contents of
this publication.
This Code of Practice is regularly reviewed by theESC to ensure that it reflects current work
requirements and evolving technologies.
Suggestions or comments regarding possible
amendments should be addressed to:
Energy Safe Victoria
P.O. Box 262,Collins St West,
Melbourne, 8007
Telephone: (03) 9203 9700
Facsimile: (03) 9686 2197
E mail address: [email protected] web site: http://www.esv.vic.gov.au
Victorian Government web site:http://www.dms.dpc.vic.gov.au
-
8/4/2019 BlueBook 2008
5/151
Blue Book December 2005 Page 3 of 148
ELECTRICAL SAFETY COMMITTEEMEMBERSHIP
Dennis Mason BlueScope Steel Limited
(Chairperson)
Greg Hollett ALCOA World Alumina Australia
Jim Lean Agility Management Pty Ltd
Garry Reeves Powercor Australia LtdDavid Just SP AusNet
David Le Lievre ALCOA World Alumina Australia
Peter Billsdon Southern Hydro
Peter den Brinker Victorian WorkCover Authority
Graeme Watson Electrical Trades Union
Allan Driver Energy Safe Victoria
Loc Vuong Energy Safe Victoria
Paul Madden National Electrical andCommunications Association
Mark Fowler Utility Asset Management
SECRETARIAT
John Batten Secretary
-
8/4/2019 BlueBook 2008
6/151
Page 4 of 148 Blue Book December 2005
STATEMENT FROM THE DIRECTOR OFENERGY SAFETY
Energy Safe Victoria (ESV) is the regulator for
Electrical and Gas Safety in Victoria, Australia. As
part of its role, ESV sets the minimum standards for
the design, construction, operation and
maintenance of electricity network assets.
The Code of Practice On Electrical Safety For Work
on or Near High Voltage Electrical Apparatus (the
2005 Blue Book) has been prepared by the
Electrical Safety Committee established under
Section 10 of the Electricity Safety Act 1998.
The Electricity Safety (Network Assets) Regulations
1999, and The Electricity Safety (Installations)
Regulations 1999, invoke the Code as amended
from time to time. The 2005 Blue Book will therefore
supersede the Code of Practice On Electrical
Safety For Work on or Near High Voltage Electrical
Apparatus published in 1998 (the 1998 Blue Book).
ESV has decided that the 2005 Blue Book will come
into operation on 31 December 2005
ESV recognises that the Victorian Electricity Supply
Industry and high voltage customers need time to
train and make workers under their control aware of
-
8/4/2019 BlueBook 2008
7/151
Blue Book December 2005 Page 5 of 148
the requirements of the 2005 Blue Book, It is
therefore not necessary for a network operator or a
person who owns or operates a high voltageelectrical installation to comply with the 2005 Blue
Book before 31 December 2006 provided that the
1998 Blue Book continues to be complied with up
to that time.
I endorse the 2005 Blue Book and commend the
Committee members and those industryorganisations involved with the development of the
2005 Blue Book.
Ken Gardner
Director of Energy Safety
31 December 2005
-
8/4/2019 BlueBook 2008
8/151
Page 6 of 148 Blue Book December 2005
PREFACEVictorian legislation such as the Occupational
Health & Safety Act, 2004 requires, in part, that:
Sec. 21 Duties of employers to employees
(1) An employer must, so far as is reasonablypracticable, provide and maintain for
employees of the employer a working
environment that is safe and without risks to
health
For the purposes of sub-section (1)
(a) a reference to an employee includes a
reference to an independent contractor
engaged by an employer and any
employees of the independent contractor:and
(b) the duties of an employer under this sub-
section extends to an independent
contractor, engaged by the employer, and
any employees of the independent
contractor, in relation to matters overwhich the employer has control or would
have control if not for any agreement
purporting to limit or remove that control.
-
8/4/2019 BlueBook 2008
9/151
Blue Book December 2005 Page 7 of 148
Employers outside the scope of this document
requiring additional information on HV safety
should seek assistance from: Energy Safe Victoria;
Local Distribution, Transmission or Generating
Company; or
Victorian WorkCover Authority.
-
8/4/2019 BlueBook 2008
10/151Blue Book December 2005 Page 8 of 142
Contents
CONTENTS PAGE
Definitions 141 PURPOSE 26
2 SCOPE 26
3 GENERAL SAFETY REQUIREMENTS 28
3.1 Hazard Identification, Risk Assessment
And Control 28
3.2 First Aid 293.3 Communications 29
3.4 Forms 29
3.5 Use And Testing Of Operating And
Live-line Equipment 29
3.6 Insulating Sticks 30
3.7 Labelling Of Electrical Apparatus 31
3.8 Ladders 31
3.9 Personal Protective Equipment 31
3.10 Tapes And Other Measuring Devices 33
3.11 Use Of Safety Observers 33
3.12 Fit State For Work 343.13 Work Within Electric And
Magnetic Fields 35
-
8/4/2019 BlueBook 2008
11/151
Contents
Blue Book December 2005 Page 9 of 148
PAGE
4 TRAINING AND AUTHORISATION 39
4.1 General 39
4.2 Approved Training Standard 40
4.3 Records 42
5 WORK IN THE VICINITY OF ELECTRICAL
APPARATUS 43
5.1 General 43
5.2 Handling Objects/loads 44
5.3 Erection Or Dismantling Of Overhead Conductors 45
5.4 Use Of Mobile Plant 45
5.5 Work By Ordinary Persons 47
5.6 Work Within Stations Or On Multi-circuit
Overhead Lines With Multiple Asset 486 APPROACH TO ELECTRICAL APPARATUS 49
6.1 General 49
6.2 Safe Approach Distance Persons 52
6.3 Safe Approach Distances - Vehicles 59
6.4 Safe Approach Distances Uninsulated
Mobile Plant 62
6.5 Safe Approach Distance Insulated
Mobile Plant 63
-
8/4/2019 BlueBook 2008
12/151
Contents
Page 10 of 148 Blue Book December 2005
PAGE
6.6 Emergency Approach 65
6.7 Contact With Live High Voltage Conductors By
Means Of Appliances 65
6.8 Approach To Live High Voltage
Insulated Cables 65
6.9 Work In Stations 67
6.10 Work Outside Of Stations 68
7 OPERATION OF HIGH VOLTAGE ELECTRICAL
APPARATUS 69
7.1 Persons Authorised To Operate High Voltage
Electrical Apparatus 69
7.2 High Voltage Switching 708 EARTHING OF HIGH VOLTAGE
ELECTRICAL APPARATUS 71
8.1 General 71
8.2 Earthing For Access To High Voltage Electrical
Apparatus 72
8.3 Removal Of Earth When Working
Under An Access Authority 73
8.4 Earthing Of Overhead Lines 74
-
8/4/2019 BlueBook 2008
13/151
Contents
Blue Book December 2005 Page 11 of 148
PAGE
8.5 High Voltage Metal-clad Switch Units 74
8.6 High Voltage Capacitors 758.7 Overhead Lines Priority Earthing
System 75
9 ACCESS FOR WORK ON OR NEAR HIGH VOLTAGE
ELECTRICAL APPARATUS 77
9.1 General 77
9.2 Electrical Access Permit Procedure 79
9.3 Sanction For Testing Procedure 88
9.4 Out Of Commission Electrical
Apparatus 94
9.5 Suspension Of An Access Authority 94
9.6 Live Work - High Voltage 969.7 Preparing High Voltage Electrical Apparatus For
Access 99
9.8 Working On Insulated Power Or Supervisory
Cables 108
10 PLACING HIGH VOLTAGE ELECTRICAL
APPARATUS IN SERVICE 111
10.1 Clearance For Service 111
10.2 Connections To New Or Out Of
Commission Electrical Apparatus 111
-
8/4/2019 BlueBook 2008
14/151
Contents
Page 12 of 148 Blue Book December 2005
PAGE
11 LOW VOLTAGE NETWORK ASSETS 113
11.1 General 113
11.2 Work On Or Near Live Low Voltage
Conductors 113
11.3 Work On Or Near De-energised Low
Voltage Exposed Conductors 114
12 WORK BY PERSONS NOT UNDER THE CONTROL
OF THE ASSET OWNER 116
12.1 General 116
12.2 Permits To Work Adjacent To Network
Assets 117
12.3 Work On Abandoned Underground
Cables 118APPENDIX A INFORMATION TO BE
CONTAINED IN FORMS 119
Application for an Access Authority 119
Application for Authority to Work in the Vicinity
of Electrical Apparatus 120
Personal Authorisations 121
Authority to Work in the Vicinity of Electrical
Apparatus 122
-
8/4/2019 BlueBook 2008
15/151
Contents
Blue Book December 2005 Page 13 of 148
PAGE
Clearance to Place Electrical Apparatus into
Service (May also be Overhead Line Clearance and
Underground Cable Clearance) 122
Electrical Access Permit & Sanction For Testing 124
Statement of Condition of Apparatus/Plant (SCAP) 125
-
8/4/2019 BlueBook 2008
16/151
Definitions
Page 14 of 148 Blue Book December 2005
DEFINITIONS
For the purpose of this Code of Practice, thefollowing definitions shall apply:
Note: For definitions of barriers and signs referClause 9.7.2.4
1 Access Authority means any form ofauthorisation which allows access to, work on
or near, or testing of electrical apparatus.Examples used in this Code are:
Electrical Access Permit means a formof authorisation which allows access to,and work upon, electrical apparatus.
Sanction for Testing means a form ofauthorisation to allow energisation ofelectrical apparatusfor testing purposes.
Permit to Work Adjacent to Network
Assets means a document providingwritten permission to persons, other thanemployees or contractors of the networkoperator, to work within safe approachdistancesor nearor in the vicinityof thenetwork operators electrical apparatus.
2 Alive see Live
-
8/4/2019 BlueBook 2008
17/151
Definitions
Blue Book December 2005 Page 15 of 148
3 Appliance means any instrument or devicedesigned for the use nearor in direct contact
with live high voltage conductors. 4 Approvedmeans having appropriate
organisation endorsement in writing for aspecific function.
5 Authorised Personmeans a person withtechnical knowledge or sufficient experience
who has been approved, or has the delegatedauthority to act on behalf of the organisation, toperform the duty concerned
Examples used in this Code are:
Authorised Applicant means anapproved person who has been assessedas competent against an approvedtraining standard to make application forspecified types of access authorities.
Authorised Electrical Operator(Electrical Operator) means anapproved person who has been assessed
as competent against an approvedtraining standard to carry out switchingoperations on high voltage electricalapparatus.
Authorised Live HV Workermeans an
-
8/4/2019 BlueBook 2008
18/151
Definitions
Page 16 of 148 Blue Book December 2005
approved person who has beenassessed as competent against an
approved training standard to carry outparticular work on or near exposed livehigh voltage conductors.
Authorised Recipient means anapproved person who has been assessedas competent against an approved
training standard to receive an electricalaccess permit.
Authorised Testermeans an AuthorisedRecipient who has been assessed ascompetent against an approved trainingstandard, and is approved to receive asanction for testing.
6 Authority to Receive Electrical Access
Permitsmeans a form of authorisation held byan authorisedrecipient.
7 Authority to Receive Sanctions for Testing
means a form of authorisation held by an
authorisedtester.8 Authority to Work in the Vicinity of
Electrical Apparatusmeans a form ofauthorisation to be used where applicable to
-
8/4/2019 BlueBook 2008
19/151
Definitions
Blue Book December 2005 Page 17 of 148
allow work in the vicinityof electricalapparatus.
9 Bonded means connected together in such amanner as to ensure that all connected partsare maintained at the same potential
10 Cablemeans an insulated conductoror twoor more such conductorslaid together,whether with or without fillings, reinforcements
or protective coverings.
11 Circuit Breakermeans a device capable ofmaking, carrying and breaking currents undernormal and abnormal circuit conditions, suchas short circuit.
12 Competentmeans having the skills,knowledge and attributes a person needs tocomplete a task.
13 Conductormeans a wire, cable or form ofmetal designed for carrying electric current.
14 Connectedmeans joined together by a
conductor capable of carrying electricalcurrent for its required function or purpose byeither physically clamping or boltingconductors together or closing a circuitbreaker, switch or similar device.
-
8/4/2019 BlueBook 2008
20/151
Definitions
Page 18 of 148 Blue Book December 2005
15 De-energisedmeans not connected to anysource of electrical supply but not necessarily
isolated.16 Discharged means having been connected
to the general mass of earth in such a manneras to remove any residual electrical energy ina conductor.
17 Earthed means directly electrically
connected to the general mass of earth so asto ensure and maintain the effective dissipationof electrical energy.
18 Earthing Devicemeans an approveddeviceused for the earthing of conductors.
19 Electrical Apparatus means any electricalequipment, including overhead lines andunderground cables, the conductors of whichare liveor can be made live.
20 Energisedmeans connected to a source ofelectrical supply.
21 Exposed conductormeans an electricalconductor, approach to which is not preventedby a barrier of rigid material or by insulationwhich is adequate under a relevant AustralianStandard specification for the voltage
-
8/4/2019 BlueBook 2008
21/151
Definitions
Blue Book December 2005 Page 19 of 148
concerned.
22 High voltage or HVmeans a nominal voltage
exceeding 1000 volts a.c. or exceeding 1500 voltsd.c.
23 High Voltage Customermeans any user ofelectricity (excluding the VESI) directlyconnected at high voltageto the Transmissionor Distribution Networks.
24 Instructed personmeans a personadequately advised or supervised by anauthorised person to enable them to avoid thedangers which electricity may create.
25 Insulated Mobile Plantmeans mobile plantapprovedand tested for carrying out work onor near electrical apparatus.
26 Insulatedmeans separated from adjoiningconducting material by a non-conductingsubstance which provides resistance to thepassage of current, or to disruptive dischargesthrough or over the surface of the substance atthe operating voltage, and to mitigate thedanger of shock or injurious leakage of current.
27 Insulating Stickmeans a stick approvedandtested for carrying out operating and livework
-
8/4/2019 BlueBook 2008
22/151
Definitions
Page 20 of 148 Blue Book December 2005
on live electrical apparatus.
28 Isolatedmeans not connected to any
possible sources of electricity supply bymeans which will prevent unintentional re-energisation of the electrical apparatusandwhich is assessed as a suitable step in theprocess of making safe for access purposes.
29 Livemeans energised or subject to
hazardous induced or capacitive voltages
30 Live workmeans all work performed oncomponents of electrical apparatusnotisolated, proved de-energisedand earthed.
31 Low voltage or LVmeans nominal voltageexceeding 50 V a.c./120 V d.c. but notexceeding 1000 V a.c./1500 V d.c.
32 Mobile Plantmeans cranes, elevating workplatforms, tip trucks or similar plant, anyequipment fitted with a jib or boom and anydevice capable of raising or lowering a load.
Mobile plant can only be considered as avehiclewhen in the normal travelling mode andnot in the working mode when determiningsafe approach distances.
-
8/4/2019 BlueBook 2008
23/151
Definitions
Blue Book December 2005 Page 21 of 148
Helicopters used for bare hand live-line workare excluded from this definition of mobile
plant.33 Near means a situation where there is a
reasonable possibility of a person, eitherdirectly or through any conducting medium,coming within the relevant safe approachdistances.
34 Network Assetmeans any asset that isowned or operated by a network operatorforthe purposes of generating, transmitting,distributing or supplying electricity of thenetwork operator.
35 Network Operatormeans the owner,
controller or operator of an electricity network.
36 Nominal voltagemeans the AC (phase tophase RMS) or DC voltage by which a systemof supply is designated.
37 Not Electrically Connectedmeansdisconnected from all sources of supply by theremoval or absence of conductors,appropriate to the voltage and insulatingmedium and not able to be made live bynormal operating means and identified in
-
8/4/2019 BlueBook 2008
24/151
Definitions
Page 22 of 148 Blue Book December 2005
accordance with approvedprocedures.
38 Operating Authoritymeans an appropriate
representative of an organisation, who isresponsible for the control of electricalapparatusconcerned.
39 Ordinary Personmeans a person withoutsufficient training or experience to enable themto avoid the dangers which electrical
apparatusmay create.
Note: Ordinary Person in this Code refers to aperson under the control of a Network Operatoror HV Customer.
40 Organisationmeans a business, enterprise,company, or corporation.
41 Out of Commissionmeans the condition ofelectrical apparatuswhich is not electricallyconnectedand declared to be so in writing tothe operating authorityresponsible for theelectrical apparatus.
42 Personal Protective Equipmentmeansclothing, equipment and/or substances, whichwhen worn or correctly used, protect parts orall of the body from foreseeable risk of injury ordisease at work or in the workplace.
-
8/4/2019 BlueBook 2008
25/151
Definitions
Blue Book December 2005 Page 23 of 148
43 Practicable means having regard to (a) the severity of the hazard or risk in
question;(b) the state of knowledge about that hazard
or risk and any ways of removing ormitigating that hazard or risk;
(c) the availability and suitability of ways toremove or mitigate that hazard or risk; and
(d) the cost of removing or mitigating thathazard or risk.
44 Proceduremeans the documentation of asystematic series of actions (or activities)directed to achieve a desired result.
45 Recipientmeans a person who has signed
on an access authority.
46 Recipient in Chargemeans an authorisedrecipientto whom an access authorityhasbeen issued and who is in charge of allrecipientssigned on that access authority.
47 Resumption of (Resume) an Access
Authoritymeans the re-commencement of allwork under an access authoritythat had beensuspended.
48 Safe Approach Distancemeans the
-
8/4/2019 BlueBook 2008
26/151
Definitions
Page 24 of 148 Blue Book December 2005
minimum distance that shall be maintained bya person, vehicleor mobile plant(including its
load, controlling ropes and any otheraccessories) when approaching electricalapparatusother than for work in accordancewith an access authority.
49 Safety Observermeans a person withsufficient knowledge of the task being
performed and competent for the duty ofobserving and warning against unsafeapproach to electrical apparatus.
50 Shall is to be interpreted as mandatory.
51 Should- is to be interpreted as advisory ordiscretionary.
52 Stationmeans any enclosed or fencedlocation in which high voltagesupply isgenerated, converted, controlled ortransformed.
53 Suspension of an Access Authoritymeansthe cessation of all work under an issuedaccess authoritywhere all persons workingunder that authority have signed off.
-
8/4/2019 BlueBook 2008
27/151
Definitions
Blue Book December 2005 Page 25 of 148
54 Tester in Chargemeans an authorised testerto whom a sanction for testinghas been issued
and who is in charge of all members of thework party signed on that sanction for testing.
55 Vehiclemeans a truck (non tipping), car,utility, or other general purpose conveyanceused for the carriage of persons or goods. (seealso mobile plant).
56 Vicinitymeans a situation where it is unlikelythat a person will, either directly or through anyconducting medium (e.g. via mobile plant),come within the relevant safe approachdistances.
57 Victorian Electricity Supply Industry(VESI)
means the Organisations which are licensedunder the Electricity Industry Act 2000 toparticipate in the generation, transmission,distribution, and supply of electricity in Victoria.
58 Written (in Writing)means recorded onpaper or in electronic form.
-
8/4/2019 BlueBook 2008
28/151
Purpose and Scope
Page 26 of 148 Blue Book December 2005
1 PURPOSE
The purpose of this Code of Practice is to provide
practical guidance in maintaining safe systems of
work in relation to control of risks associated with
work on or near or in the vicinity of high voltage
electrical apparatusin Victoria.
2 SCOPEThis Code of Practice defines:
Principles; and
Electrical Safety Procedures
The Principles apply to all persons working on, near
or in the vicinityof high voltage electrical apparatuswhich is capable of being energised.
The Electrical Safety Procedures defined in this
Code apply within the VESI. HV Customers shall
apply those procedures required by regulations
and may use the remaining procedures.
This Code is also applicable to not electricallyconnected apparatus in situations where the
required level of isolation, as defined, cannot be
confirmed prior to work commencing, for example,
on abandoned underground cables.
-
8/4/2019 BlueBook 2008
29/151
Scope
Blue Book December 2005 Page 27 of 148
Organisationsshall follow the principles contained
within this Code.
In order to comply with the electrical safety
procedure requirements of this Code a VESIorganisation shall either:
(a) Apply the procedures contained within thisCode; or
(b) Vary the procedures by:
completing a hazard identification and risk
assessment documenting the process
advising the Electrical Safety Committee in
writing
Figure 1 - Hierarchy of documentation for electrical safety
This Code sets a minimum standard and may be
enhanced by Organisational procedures. These
procedures may utilise other industry standards.
-
8/4/2019 BlueBook 2008
30/151
General Safety Requirements
Page 28 of 148 Blue Book December 2005
3 GENERAL SAFETYREQUIREMENTS
PRINCIPLE - Consideration shall be given toprovide additional procedures covering mattersidentified relevant to providing a comprehensivesafe working environment.
3.1 HAZARD IDENTIFICATION, RISKASSESSMENT AND CONTROL
An organisations safe system of work shall includeappropriate risk management processes to ensurehazards associated with work within safe approachdistances or near electrical apparatus areidentified, assessed and controlled.
Prior to working within safe approach distancesornear any electrical apparatus, the personsconducting the work shall identify, assess andcontrol the associated hazards and risks.
The hazard identification and risk assessmentprocess shall be regularly reviewed and audited toensure compliance.
-
8/4/2019 BlueBook 2008
31/151
General Safety Requirements
Blue Book December 2005 Page 29 of 148
3.2 FIRST AID
Persons who are required to work where there is a
risk of inadvertent contact with live electricalconductors shall be given appropriate first aidtraining on commencement, and thereafter subjectto annual competency assessment. Training shallcover skills in expired air resuscitation, externalcardiac compressions, shock, burns and incidentassessment and management.
3.3 COMMUNICATIONS
All communications relating to the operation of, oraccess to, electrical apparatus shall be clear anddefinite. Electrical apparatusshall be referred to byname and sufficient detail to give positiveidentification. Verbal instructions and statements
shall be confirmed by repeating back to avoidmisunderstanding.
3.4 FORMS
Guidance for minimum requirement on forms isgiven in Appendix A.
3.5 USE AND TESTING OF OPERATING ANDLIVE-LINE EQUIPMENT
All sticks, gloves, sleeves, mats, protective barriersor covers, earthing trucks, portable earthing
-
8/4/2019 BlueBook 2008
32/151
General Safety Requirements
Page 30 of 148 Blue Book December 2005
devices, insulating platforms, insulated elevatingwork platforms or other equipment used for
operating high voltage electrical apparatus orperforming live-line work shall be specificallyapproved for the particular application. Visualinspection shall be made for physical damage orcontamination immediately prior to use.
All equipment including protective equipment usedon high voltage electrical apparatus and whichrequires regular testing to prove the effectivenessof insulation shall be tested at specific intervals asper Organisational procedures and marked to showthe date of the next routine test.
Gloves, sleeves, mats and protective barriers orcovers used for operating high voltage electrical
apparatusor for performing Glove and Barrier Live-Line Work shall not be relied upon as the solemeans of insulation.
Equipment shall not be used after the marked dateuntil retested.
3.6 INSULATING STICKS
3.6.1 Insulating sticks shall have a length whichprovides appropriate insulation from live parts andenables a person using the stick to maintain theapplicable safe approach distance(refer 6.2) at all
-
8/4/2019 BlueBook 2008
33/151
General Safety Requirements
Blue Book December 2005 Page 31 of 148
times.
3.6.2 When an insulating stickis to be used in wet
conditions consideration shall be given to thepotential for hazardous surface leakage currents.
3.7 LABELLING OF ELECTRICALAPPARATUS
For the purposes of identification and description,electrical apparatus shall, wherever practicable, beclearly labelled.
3.8 LADDERS
Metallic or wire-reinforced ladders, shall not beused on, or near exposed live electrical apparatus;unless approved for use in accordance with
organisational procedures.3.9 PERSONAL PROTECTIVE EQUIPMENT
All persons who may be exposed to possibleelectric shock, flash or other injury from electricalapparatusshall use approved personal protectiveequipment. Personal protective equipment shall
include clothing with wrist to ankle cover and fullyenclosed footwear.
Additional personal protective equipmentshall beused in accordance with the type of work and therisks involved.
-
8/4/2019 BlueBook 2008
34/151
General Safety Requirements
Page 32 of 148 Blue Book December 2005
GENERAL PPE REQUIREMENTS
1 Working on, near or in the vicinity ofelectrical apparatus approved safety:
headwear
natural fibre clothing
footwear
2 Operating electrical apparatus approvedsafety:
headwear
footwear
natural fibre clothing
hand protection
face/eye protection
3 Supervised visit to a station with no
involvement in any work at that station and
movements confined to normal access ways,
e.g. roads, paths and stairs:
The person responsible for organising or
supervising such visitors to ensure that they
are suitably clothed or covered, and
supplied with approved safety headwear.
-
8/4/2019 BlueBook 2008
35/151
General Safety Requirements
Blue Book December 2005 Page 33 of 148
3.10 TAPES AND OTHER MEASURING
DEVICES
Only approved non-conducting tapes and rulesshould be used in the vicinity of live electrical
apparatus. Conductive tapes shall not be used
near exposed live electrical apparatus unless
approvedfor use in accordance with organisational
procedures.
3.11 USE OF SAFETY OBSERVERS
Where it is considered after a risk assessment that
a person, equipment or mobile plant might
inadvertently infringe Safe Approach Distances, a
safety observershall be posted.
For work near electrical apparatus, use of a safetyobserverto warn against inadvertent infringement
of safe approach distancesmay be required under
this code, under organisational procedures or
under precautions determined appropriate under
the hazard identification, risk assessment and
control procedures used by the persons
conducting the work.
-
8/4/2019 BlueBook 2008
36/151
General Safety Requirements
Page 34 of 148 Blue Book December 2005
A safety observer shall:
monitor the work and warn against potential
infringement of safe approach distances;
be positioned to effectively observe andimmediately communicate with personsperforming the work;
have the authority to temporarily suspend therelevant work at any time;
not perform any other work while acting assafety observer; and
be specifically instructed in the duties andworkplace hazards applicable.
3.12 FIT STATE FOR WORK
Alcohol, drugs, mental alertness and physicalcondition of a person may impede their ability to
work safely in an electrical environment.
Persons who are required to work on, nearor in the
vicinityof electrical apparatusshall not consume or
be under the influence of alcohol or drugs that
diminish work skills during work hours. This shall betaken to include meal or rest breaks.
Appropriate policies shall be implemented by
organisations.
-
8/4/2019 BlueBook 2008
37/151
General Safety Requirements
Blue Book December 2005 Page 35 of 148
3.13 WORK WITHIN ELECTRIC AND
MAGNETIC FIELDS
3.13.1 General
Persons working within electric and magnetic fields
shall be appropriately protected from the
annoyance due to electric discharge effects of
strong electric fields and the possible biological
effects associated with extremely strong electric
and magnetic fields.
Persons using medical implantable devices
including cardiac pacemakers should consult their
doctors and the relevant organisation Health &
Safety Officer for information on possible
electromagnetic interferences with the medical
devices prior to entering areas of strong electricand magnetic fields.
The electric fields and magnetic field exposure
limits given below are based upon National Health
and Medical Research Council (NHMRC)
Guidelines. An ongoing review of these guidelines
is presently being carried out by the AustralianRadiation Protection and Nuclear Safety Agency
(ARPANSA), and information on the activity is
available from ARPANSA. Expected publication
-
8/4/2019 BlueBook 2008
38/151
General Safety Requirements
Page 36 of 148 Blue Book December 2005
date for the new ARPANSA Standard is 2006.
Organisations should apply appropriate exposure
limits as per NHMRC guideline or ARPANSAstandard whichever is current
3.13.2 50Hz Electric Fields
The National Health and Medical Research Council
(NHMRC) interim guidelines for occupational
exposure limits for electric fields are as follows:
Whole working day 10 kV/m
Short term 30 kV/m
Short term exposure to fields between 10 kV/m and
30 kV/m is permitted provided the field strength (in
kV/m) times the duration of exposure (in hours)
does not exceed 80 for the whole day. For example,exposure to an electric field of 20 kV/m would be
permitted for 4 hours under IRPA guidelines.
For work situations with field strengths greater than
30 kV/m, appropriate measures shall be taken.
Such measures may include wearing of
appropriately earthed or bonded conducting suits,the screening and earthing of vehicles, the
screening of work platforms and access ways, and
de-energising adjacent electrical apparatus.
-
8/4/2019 BlueBook 2008
39/151
General Safety Requirements
Blue Book December 2005 Page 37 of 148
The person responsible for planning the work shall
include in the work instructions details of any
appropriate measures to be taken.3.13.3 Magnetic Fields
The NHMRCs guidelines for limits of occupational
exposure to magnetic fields are as follows
(a) 50 Hz Magnetic Fields
Whole working day 0.5 milliTesla(5 000 milliGauss)
Short term 5 milliTesla
(2 hours per day) (50 000 milliGauss)
Limit for limbs 25 milliTesla
(eg extended arm) (250 000 milliGauss)(b) Static or Direct Current (DC) Magnetic Fields
The International Commission on Non-Ionizing
Radiation Protection (ICNIRP) guidelines for
Limitsab of occupational exposure to static or
DC magnetic fields are as follows:
Whole working day 200 milliTesla
Ceiling Value 2000 milliTesla
Limbs 5000 milliTesla
-
8/4/2019 BlueBook 2008
40/151
General Safety Requirements
Page 38 of 148 Blue Book December 2005
Notes:
(a) Caution: People with cardiac pacemakers and
other implanted electrically activated devices,or with ferromagnetic implants, may not be
adequately protected by the limits given here.
The majority of cardiac pacemakers are
unlikely to be affected from exposure to fields
below 0.5 milliTesla. (Static or D.C. magnetic
fields)People with some ferromagnetic implants or
electrically activated devices (other than
cardiac pacemakers) may be affected by
fields above a few milliTesla.
(b) When magnetic flux densities exceed 3
milliTesla (Static or D.C. magnetic fields),precautions should be taken to prevent
hazards from flying metallic objects.
Areas in which higher levels of exposure can
occur outside safe approach distances (see
Clauses 6.1 and 6.2) shall be fenced off to
exclude access whilst electrical apparatus isenergised.
-
8/4/2019 BlueBook 2008
41/151
4 TRAINING AND AUTHORISATION
PRINCIPLE - Persons working on or near highvoltage electrical apparatus shall haveappropriate training, and authorisation for theduty to be performed.
4.1 GENERAL
An organisationssafe system of work shall include
reference to appropriate training and authorisation
for all persons working on or near high voltage
electrical apparatus.
All authorisations shall be reviewed annually by theorganisation to ensure the relevance of the authority
to the holder's duties.
Persons holding authorisations shall be
competency assessed at no more than 3-yearly
intervals and where appropriate training given to
restore competency.
Training and Authorisation
Blue Book December 2005 Page 39 of 148
-
8/4/2019 BlueBook 2008
42/151
Training and Authorisation
Page 40 of 148 Blue Book December 2005
4.2 APPROVED TRAINING STANDARD
4.2.1 Introduction
Training courses will consist of identified learning
outcomes which will be knowledge, skill (task), and
attitude based and where appropriate, reflect
National Electricity Supply Industry Competency
Standards.
There shall be assessment criteria establishedand documented for each learning outcome.
Details of assessment method shall bedocumented.
There shall be a documented process forrecognition of prior learning.
Persons undergoing training must beassessed for competency against all learningoutcomes relevant to the course, and suchassessment must be documented.
4.2.2 Learning Outcomes
Learning outcomes shall include, but not be limitedto, the following:
Working knowledge of the relevant sections ofthis Code of Practice.
-
8/4/2019 BlueBook 2008
43/151
Training and Authorisation
Blue Book December 2005 Page 41 of 148
Knowledge of communication processesrequired.
Knowledge of the relevant Organisationalprocedures.
A knowledge of the consequences of anyphysical tasks performed.
A working knowledge and skill associated withthe relevant: Forms and documentation Risk assessment Work practices Equipment and plant
Demonstration of acquired knowledge throughpractical exercises.
A clear understanding of the responsibilitiesassociated with relevant authorisations, eg therange of responsibilities associated with aRecipient in Charge.
Other training requirements as specifiedherein.
-
8/4/2019 BlueBook 2008
44/151
Training and Authorisation
Page 42 of 148 Blue Book December 2005
4.2.3 Approved Training Courses and Processes
Organisations shall approve course descriptors
and service providers as meeting their recognisedneeds. The descriptors of each course shall
include learning outcomes, assessment criteria
and assessment methods.
4.3 RECORDS
Organisations shall develop and maintain anappropriate management system for recording of
all training and authorisations.
-
8/4/2019 BlueBook 2008
45/151
Work in the Vicinity of Electrical Apparatus
Blue Book December 2005 Page 43 of 148
5 WORK IN THE VICINITY OFELECTRICAL APPARATUS
PRINCIPLE Work in the vicinity of electricalapparatusshall be carried out in a safe manner.Control measures taken shall be consistent withthe risk and work performed.
5.1 GENERAL
For all works in the vicinityof electrical apparatus
either specific written work instructions shall be
used or organisational procedures shall apply in
conjunction with the use of instructed or authorised
persons.
Where the risk assessment requires a record of the
control measures then instructions shall be issued
to the work party in accordance with Organisational
procedure.
The control measures implemented shall minimisethe risks involved and may include:
defining the work area;
isolating and earthing the electrical apparatus;
-
8/4/2019 BlueBook 2008
46/151
Work in the Vicinity of Electrical Apparatus
Page 44 of 148 Blue Book December 2005
the use of barriersand signs;
the use of approvedcovering;
the use of safety observers;
the issue of the appropriate access authorityor authority to work in the vicinity of electricalapparatus; and
defining access routes.
5.2 HANDLING OBJECTS/LOADS
When objects are being handled manually or by
mechanical equipment, care shall be exercised to
prevent the objects or the mechanical equipment
infringing safe approach distances.
For manual handling, appropriate work methodsand an appropriate number of persons shall be
used to maintain safe approach distances.
For mechanical handling where there is a risk of
infringing the safe approach distances (refer
section 6) to electrical conductors, the movement
of loads shall be controlled by means of approvednon-conducting ropes or other approved means.
No person outside the cabin shall contact the load,
mobile plant or any attached conducting objects
(Refer to clause 5.4 for protection of other persons).
-
8/4/2019 BlueBook 2008
47/151
Work in the Vicinity of Electrical Apparatus
Blue Book December 2005 Page 45 of 148
5.3 ERECTION OR DISMANTLING OF
OVERHEAD CONDUCTORS
When overhead lines (other than insulated lowvoltage service lines) are being erected,
dismantled, or replaced and there is any possibility
of contact with, or induction from, adjacent live
conductors of any description, such conductors
being moved shall be earthed by an approved
device before work is commenced and shall remaineartheduntil the work is completed. A conductor
being so erected shall be earthedbefore it is lifted
from the ground.
Consideration shall be given to the use of
appropriate restraining devices to control such
conductorswhen they are being moved.5.4 USE OF MOBILE PLANT
Mobile plantshall only be used in the vicinityof live
conductors and/or electrical apparatus after
precautions appropriate to the particular
circumstances have been considered and action
taken to control the associated hazards and risks.
The control measures to be considered within a risk
assessment shouldinclude:
-
8/4/2019 BlueBook 2008
48/151
Work in the Vicinity of Electrical Apparatus
Page 46 of 148 Blue Book December 2005
isolating and earthing electrical apparatus;
positioning the mobile plantsuch that the safe
approach distance can be maintained in allcircumstances;
the use of safety observersand barriersand
signs;
the use of other precautions such as physical
restrictions or control devices in conjunctionwith barriers;
the suppression of Auto-Reclose;
the alteration of protection and control
settings; and
de-energising the electrical apparatus.Mobile plant, and where appropriate, vehicles, shall
be fitted with a trailing earthing conductorto protect
against the hazards presented by induced
voltages.
When mobile plantmay come near (refer section 6)
live electrical apparatus, the mobile plantshall beearthed. This shall be achieved by an approved
earthing system.
When mobile plant is operated from outside the
-
8/4/2019 BlueBook 2008
49/151
Work in the Vicinity of Electrical Apparatus
Blue Book December 2005 Page 47 of 148
mobile plant, precautions shall be taken to protect
the operator from hazardous step and touch
potentials. No person other than the mobile plantoperator shall touch the mobile plant whilst in
operation.
Where mobile plant e.g. EWP is only partially
insulated, the following permanent sign shall be
fixed at each operators station:
DANGER BEWARE OF POWER LINES
This appliance is not fully insulated. Do notpermit any uninsulated part of this appliance tobe in close proximity to live conductors.
Insulated mobile plant shall be tested at specific
intervals as per organisational procedures andmarked to show the date of the next routine test.
5.5 WORK BY ORDINARY PERSONS
Where ordinary personsare required to work in the
vicinity of electrical apparatus, the ordinary person
performing the work, the person in charge of the
work and the person in charge of the electricalapparatus shall all cooperate to ensure that the
work is performed safely, and that specific
precautions are taken.
-
8/4/2019 BlueBook 2008
50/151
Work in the Vicinity of Electrical Apparatus
Page 48 of 148 Blue Book December 2005
5.6 WORK WITHIN STATIONS OR ON MULTI-
CIRCUIT OVERHEAD LINES WITH
MULTIPLE ASSET OWNERSHIPFor work within stations or on Multi-Circuit
Overhead Lines where electrical apparatus is
owned by more than one Organisation and work is
adjacent to another Organisation's exposed
electrical apparatus, there shall be joint
consideration and agreement reached to carry outthe work in a safe manner. (See also 6.10 and
9.2.4)
-
8/4/2019 BlueBook 2008
51/151
Approach To Electrical Apparatus
Blue Book December 2005 Page 49 of 148
6 APPROACH TO ELECTRICAL
APPARATUS
6.1 GENERAL
The safe approach distances are based on an
exclusion zone principle. This principle defines
an area around the electrical apparatusinto which
no part of the person, mobile plantor object (other
than approved insulated objects) may encroachunless in accordance with Section 9. Refer figures
2 & 3.
When working at these distances work practices
shall be established to ensure persons, mobile
plantand unapprovedobjects do not encroach on
the safe approach distances.Unnecessary approach to electrical apparatus or
unnecessary contact with parts not regarded as
live shall be avoided.
PRINCIPLE Persons shall observeappropriate safe approach distance whenworking, or operating vehicles or mobileplant, on or near electrical apparatus
-
8/4/2019 BlueBook 2008
52/151
Approach To Electrical Apparatus
Page 50 of 148 Blue Book December 2005
Necessary approach to electrical apparatus shall
be kept to a minimum and shall be restricted to the
period required to perform the work.
Figure 2: Safe Approach Distance Application
-
8/4/2019 BlueBook 2008
53/151
Approach To Electrical Apparatus
Blue Book December 2005 Page 51 of 148
Figu
re3:IllustrationofDiffer
encesbetweenSafeApp
roachDistance,Nearand
Vicinity
Vicinitymeansasituationwhereitisunlikely
thatapersonwill,eitherdirectlyorthroughanyconduct
ing
medium(egmobileplant)comewithintherelevant
safeapproachdistances.
Nearmeansasituationwhere
there
isareasonablepossibilityofaperson,
eitherdirectlyorthroughany
conductingmedium(eg:viamo
bileplant)
comingwithintherelevant
safeapproachdistances.
Safe
ApproachDistancemeanstheminimum
distanc
ethatshallbemaintaine
dbyaperson
vehicle
ormobileplant(includin
gitsload-controlling
ropesandotheraccessories)w
henapproaching
electric
alapparatusotherthanforwork
inacco
rdancewithanaccessauthority.
Conductorm
eansawire,
cableorformof
metaldesigned
forcarryingelec
tricalcurrent.
-
8/4/2019 BlueBook 2008
54/151
Approach To Electrical Apparatus
Page 52 of 148 Blue Book December 2005
6.2 SAFE APPROACH DISTANCE PERSONS
6.2.1 Safe Approach Distance
The safe approach distances for persons
conducting general work are as shown in Table 1.
Instructed persons safe approach distances apply
whilst undertaking duties under supervision or as
instructed by an authorised person.
-
8/4/2019 BlueBook 2008
55/151
Nominal Phase toPhase AC Voltage
Ordinary Persons Instructed Persons orAuthorised Persons
kV Millimetres Millimetres
LV Aerial Lines 1500 Instructed Persons -
No contactAuthorised Persons -
insulated contact only
Nominal Pole to Earth
DC Voltage (kV)
1.5 or less 1500
Instructed Persons-
No contactAuthorised Persons-
insulated contact only
6.6 2000 70011 2000 70022 2000 700
33 2000 70050 2000 75066 2000 900
110 3000 1000132 3000 1200220 4000 1700275 5000 2300330 6000 2700400 6000 3300500 6000 3600
+/- 25 2000 700+/- 85 3000 1000+/- 150 3000 1200+/- 270 4500 1800
+/- 350 5000 2500+/- 400 6000 2900
Notes:(1) Deliberately avoid movements that could result in distances being
infringed.(2) These distances specified are based on work from a stable surface.
Appropriate allowance shall be made for conductorsag and sway.
Table 1 - Safe Approach Distancesfor Persons to Exposed Conductors
Approach To Electrical Apparatus
Blue Book December 2005 Page 53 of 142
-
8/4/2019 BlueBook 2008
56/151
6.2.2 SAFE APPROACH DISTANCE
SPECIAL
The safe approach distance(given in table 2) whichmay be used for authorised persons conducting
general work has been determined using risk
analysis methodology and consideration of power
frequency and switching surge distances plus a
safety margin.
Approach To Electrical Apparatus
Blue Book December 2005 Page 54 of 142
Figure 4 Safe Approach Distance - Special
-
8/4/2019 BlueBook 2008
57/151
Blue Book December 2005 Page 55 of 148
Approach To Electrical Apparatus
These safe approach distancesmay only be used
in conjunction with the following control measures:
The safe approach distancesshall bemaintained from any part of the persons body
or any conducting or unapprovedobject
touching any part of the persons body by using
controlled movement;
Positioning of the worker to minimise the risk of
the specified distance being infringed. Thisincludes any unapprovedobject or tool being
held by the worker;
A person specifically trained and authorised to
perform the work at the safe approach
distance;
Workcrew on site risk assessments are
conducted;
Safety observersare used to monitor the work
activities;
Minimise the exposure at the safe approach
distance;
Addressing adverse Impact of external
influences on plant and equipment, e.g. traffic,
boom movement, footing.
-
8/4/2019 BlueBook 2008
58/151
Approach to Electrical Apparatus
Page 56 of 148 Blue Book December 2005
Addressing adverse impact of weather and
environmental conditions (e.g. rain, lightning,
wind, light, sag or sway of conductors).If these controls are not achieved either access
authoritiesshall be issued or live work techniques
shall be applied or alternative special safe
approach distances and procedures developed in
accordance with Clause 6.2.3
-
8/4/2019 BlueBook 2008
59/151
Approach to Electrical Apparatus
Blue Book December 2005 Page 57 of 148
Table 2 - Safe Approach Distance - Special
Nominal Phase to PhaseAC Voltage
Authorised Persons
KV Millimetres
LV Insulated contact only
6.6 300
11 30022 300
33 500
50 700
66 700
-
8/4/2019 BlueBook 2008
60/151
Page 58 of 148 Blue Book December 2005
Approach To Electrical Apparatus
6.2.3 Guidelines for the Development anduse of Alternative Safe Approach
Distances - SpecialWhen determining the safe approach distance -special and performing the task the followingcontrols shall be considered:
Determining special safe approach distancesfrom:
ENA NENS 04-2006 NationalGuidelines for Safe Approach Distancesto Electrical and Mechanical Apparatusand/or IEEE 516 and related guidelinesas may be appropriate; and
Clause 9.6 Live Work High Voltage.
When developing organisational proceduresspecial consideration shall be given to:
Flashover;
Possibility of inadvertent movement;
Minimising the duration of work at thespecial safe approach distance; and
Work techniques which providemaximum practical distance from liveconductors.
-
8/4/2019 BlueBook 2008
61/151
Blue Book December 2005 Page 59 of 148
Workcrew on site risk assessment shallconsider:
Control of inadvertent movement by theuse of insulating barriers, insulated plantand appliances and controlled bodymovements; and
Environmental conditions.
6.3 SAFE APPROACH DISTANCES -VEHICLES
6.3.1 Ordinary Persons
An ordinary person in charge of any vehicle,excepting mobile plant when in working mode,
shall ensure that no part of the vehicleor its load isplaced or moved within the distances shown inTable 3.
6.3.2 Authorised and Instructed Persons
Authorised and instructed personsin charge of anyvehicle, excepting mobile plant when in workingmode, shall ensure that no part of the vehicleor its
load is placed or moved within the distances shown inTable 3.working mode)
Approach To Electrical Apparatus
-
8/4/2019 BlueBook 2008
62/151
Page 60 of 148 Blue Book December 2005
Approach To Electrical Apparatus
(1) All distances specified are based on work from a stable surface. Appropriateallowance shall be made for conductor sag and sway and for uncontrolled movement ofvehicle or plant due to any reason.
Nominal Phase toPhase Voltage (AC)
Safe ApproachDistance- for VehiclesUnder the Control of
Ordinary Persons(note 1)
Safe ApproachDistance- for Vehicles
under the control of
Instructed PersonsorAuthorised Persons
(note 1)
kV Millimetres Millimetres
Table 3 - Safe Approach Distance for Vehicle to exposed
live conductors (excepting Mobile Plant when in the
working mode)
Low Voltage 600 600
HV up to/including 33 1000 700
50 1000 750
66 1000 1000
110 1500 1000
132 1500 1200
220 4600 1800
275 4600 2300
330 5500 2300400 6400 3300
500 6400 3900
Nominal Pole to Earth
DC Voltage
+/- 25+/- 25 10001000 700700
+/- 85+/- 85 15001500 10001000
+/- 150+/- 150 15001500 12001200
+/- 270+/- 270 46004600 18001800+/- 350+/- 350 55005500 25002500
+/- 400+/- 400 64006400 29002900
-
8/4/2019 BlueBook 2008
63/151
Approach To Electrical Apparatus
Blue Book December 2005 Page 61 of 148
(1) All distancesspecified arebased on workfrom a stablesurface.
Appropriateallowance shall bemade forconductor sag andsway and foruncontrolledmovement ofvehicle or plantdue to any reason.(2) A safetyobserver is
required unlessthe mobile plant isincapable ofinfringing the safeapproach distance.
Table 4 Safe Approach Distance for Mobile Plant to
exposed live conductors when in the working mode
Nominal Phase to
Phase Voltage(AC)
Safe Approach
Distance- forMobile Plant
Under theControl of
Ordinary Persons(Notes 1 & 4)
Safe Approach
Distance- forMobile Plant Under
the Control of
Instructed Persons
or Authorised
Persons(for
Insulated Mobile
Plantrefer table 5)
(Notes 1 & 2)
Safe Approach
Distance- forMobile Plant Under
the Control of Glove
and Barrier Live-
Line Work
Authorised Persons
(for Insulated Mobile
Plantrefer Table 5)
(Notes 1, 2 &3)
kV Millimetres Millimetres Millimetres
Low Voltage 2000 1000 380
HV up
to/including 33
2000 1200 1000
50 2000 130066 2000 1400110 4000 1800132 4000 1800220 4600 2400
275 4600 3000330 5500 3700400 6400 4000500 6400 4600
Nominal Pole toEarth DC Voltage
+/- 25 2000 1200+/- 85 4000 1800+/- 150 4000 1800
+/- 270 4600 2400+/- 350 5500 3200+/- 400 6400 3600
(3) When lifting a load the conductors are suitably insulated in accordance withorganisational procedures.
(4) Including Insulated Elevating Work Platforms.
-
8/4/2019 BlueBook 2008
64/151
Approach To Electrical Apparatus
Page 62 of 148 Blue Book December 2005
6.4 SAFE APPROACH DISTANCES
UNINSULATED MOBILE PLANT
6.4.1 General
Because of the physical capabilities of, and
potential hazard with mobile plantworking adjacent
to live conductors and/or electrical apparatus,
specific consideration (including earthing) shall be
given to its use during planning of the work. (Refer
5.4)
6.4.2 Ordinary Persons
An ordinary person in charge of the work shall,
ensure that the mobile plant, its equipment and
load is not placed or moved within the distances
shown in Table 4.6.4.3 Instructed Persons or Authorised Persons
An instructed person or authorised person in
charge of the work shall ensure that the mobile
plant, its gear and load shall not approach live
conductorsand/or electrical apparatus within the
distances as shown in Table 4.
When working under glove and barrier procedures,
and where the conductors and load are suitably
insulated, the load should remain a minimum of 380
-
8/4/2019 BlueBook 2008
65/151
Blue Book December 2005 Page 63 of 148
mm (at 22 kV) from the conductor(allowing for sag
and sway of the conductor). Every effort should be
made for the load to avoid accidental contact withthe conductors.
When the work requires a closer approach to live
conductors than the normal safe approach
distancesgiven in Table 4 special safe approach
distancesfor mobile plantmay be developed and
applied with consideration of the requirements setout in 6.2.3
The use of helicopters for bare hand live line work
is excluded from the requirements of this clause.
6.5 SAFE APPROACH DISTANCE
INSULATED MOBILE PLANT
Only instructed personsor authorised personsmay
operate insulated mobile plantin accordance with
Table 5 and organisational procedures.
The insulated portion of mobile plantmay contact
or encroach at distances less than the safe
approach distanceto a live conductorspecified inTable 5 provided it is rated for the purpose for which
it is intended to be used.
Approach To Electrical Apparatus
-
8/4/2019 BlueBook 2008
66/151
Approach To Electrical Apparatus
(1) These distances specified are based on work from a stable surface.Appropriate allowance shall be made for conductor sag and sway, andfor uncontrolled movement of the Mobile plant for any reason.(2) For ordinary persons refer to Table 4.(3) For safe approach distance where contact is allowed, careshall be exercised to prevent movement of conductors.(4) For live work in accordance with Organisational Procedures.
Table 5 - Safe Approach Distances to Exposed Live Conductors for
Insulated mobile plant operated by persons who are instructed or
authorised to work on or near exposed conductors.
Safe Approach
Distances
(Note 1, 2 and 3)
Working Within Safe
Approach Distance
(Note 1, 3 and 4)
kV Millimetres MillimetresInsulated
portions
Uninsulated
portions
Insulated
portions
Uninsulated
portions
ContactAllowable
1000 ContactAllowable
1000
700 1200 Contact 1000
1000 1400 Contact 1000
1800 2400 Contact
Allowable
1800
2300 3000 Contact
Allowable
2300
3000 3700 ContactAllowable
3000
3900 4600 ContactAllowance
3900
HV up to andincluding 33
66
220
275
330
500
Nominal Pole to
earth DC Voltage kV
+/- 25
+/- 85
700 1200 Contact
Allowable
1000
1000 1800 Contact
Allowable
1000
Nominal Phase toPhase AC Voltage
Page 64 of 148 Blue Book December 2005
Low Voltage
-
8/4/2019 BlueBook 2008
67/151
Approach To Electrical Apparatus
Blue Book December 2005 Page 65 of 148
6.6 EMERGENCY APPROACH
In emergency situations where there is likely risk of
electric shock to persons from electricalconductors or electrical apparatus, e.g. fallen
conductor, prompt action shall be taken to ensure
people are kept well clear of the hazard at a greater
than safe approach distances in accordance with
organisational procedures.
Safe Approach Distances shall apply only after theoperating authority has established that these
requirements can be safely applied.
6.7 CONTACT WITH LIVE HIGH VOLTAGECONDUCTORS BY MEANS OF
APPLIANCES
Only approved and tested appliances shall be
permitted to be brought within the safe approach
distance, or into direct contact with live high voltage
conductors.
6.8 APPROACH TO LIVE HIGH VOLTAGE
INSULATED CABLES6.8.1 General
When work is performed near live high voltage
insulated cables, appropriate precautions shall be
-
8/4/2019 BlueBook 2008
68/151
Page 66 of 148 Blue Book December 2005
Approach To Electrical Apparatus
taken to ensure that the insulation of the cables is
not damaged.
Cables, which are specifically designed formovement whilst live, may be moved in accordance
with organisational procedures.
Slight movement of other types of live cablesmay
be permitted, but only after detailed consideration
of all related circumstances by a person with a
detailed knowledge of the cablesconcerned, whoshall fully detail all precautions to be taken.
6.8.2 Earthed Metallic Sheathed or Screened
High Voltage Cables
Contact by persons may be made to external
surfaces of live high voltage cables with earthedmetallic sheaths or screens.
6.8.3 Non-Metallic Screened High Voltage AerialBundled Cable
No body contact shall be made to external surfaces
of live non-metallic screened high voltage aerial
bundled cable or exposed support conductors.Suitable liveline techniques only shall be used for
this purpose.
Access to de-energised but not earthed non-
-
8/4/2019 BlueBook 2008
69/151
Blue Book December 2005 Page 67 of 148
Approach To Electrical Apparatus
metallic screened high voltage aerial bundled
cable may be permitted in accordance with
organisational procedures.For the purposes of Insulated Mobile Plant work in
the vicinity of live non-metallic screened high
voltage aerial bundled cable the safe approach
distance shall be the same as exposed high
voltage conductors. (Refer Table 5)
6.9 WORK IN STATIONS
6.9.1 A person shall not perform work in any stationor allow mobile plant to enter any station without
first obtaining the permission of the person in
charge of the station and accepting all the
conditions imposed by that person.
6.9.2 An access authorityand or authority to workin the vicinity of live apparatus (refer Clause 5.1)
shall be issued where
mobile plantor elevating platform or other
large vehicleswill be used; or
the work involves excavation or the use ofexplosives.
-
8/4/2019 BlueBook 2008
70/151
Page 68 of 148 Blue Book December 2005
Approach To Electrical Apparatus
6.10 WORK OUTSIDE OF STATIONS
Work on or near electrical apparatus outside of
stations shall be performed after obtaining thepermission and direction of the Network Operator.
-
8/4/2019 BlueBook 2008
71/151
Blue Book December 2005 Page 69 of 148
Operation of High Voltage Electrical Apparatus
7 OPERATION OF HIGH VOLTAGEELECTRICAL APPARATUS
7.1 PERSONS AUTHORISED TO OPERATEHIGH VOLTAGE ELECTRICAL APPARATUS
Switching and associated duties on high voltage
electrical apparatus should be performed by
authorised electrical operators whose training,
duties and instructions cover the particular
electrical apparatus. However, any person may
perform operations in the following circumstances:
When specifically instructed by, or authorised
by, the appropriate operating authority;
In an emergency involving serious risk to
persons or property; or
Where they operate high voltage electrical
apparatusas part of process control.
PRINCIPLE Only authorised persons shallundertake switching and associated duties onhigh voltage electrical apparatus
-
8/4/2019 BlueBook 2008
72/151
Page 70 of 148 Blue Book December 2005
7.2 HIGH VOLTAGE SWITCHING
Prior to a high voltage switching operation, the
available information regarding circuit conditionsshall be taken into account and no electrical
apparatusshall be operated if it is inappropriate for
the duty to be performed. After switching, correct
operation of the electrical apparatus should be
confirmed whenever possible.
When high voltage electrical apparatus isoperated, the person undertaking the task shall be
protected in an approved manner from electric
shock, flash or other hazards. (also refer 3.9)
Operation of High Voltage Electrical Apparatus
-
8/4/2019 BlueBook 2008
73/151
Blue Book December 2005 Page 71 of 148
8 EARTHING OF HIGH VOLTAGEELECTRICAL APPARATUS
8.1 GENERAL8.1.1 Only approved earthing devices shall be
used and only authorised personsshall apply them
after the circuit or electrical apparatus is isolated
and after confirmation by tests, visual inspection or
inquiry that the conductorsare de-energised.
8.1.2 In applying an earthing device, it shall beconnected to earth before it is applied to the
conductors, and it shall be removed from the
conductorsbefore it is disconnected from earth.
8.1.3 Wherever practicable, an earth shall be
applied and removed by an approveddevice.
When hand application or removal is unavoidable:
All phases shall be discharged, and
Another earth shall be held in contact with the
PRINCIPLE Earthing devices shall be appliedby an authorised person following a safe to earth
confirmation and placed to ensure the safety of
the work party.
Earthing of High Voltage Electrical Apparatus
-
8/4/2019 BlueBook 2008
74/151
Page 72 of 148 Blue Book December 2005
Earthing of High Voltage Electrical Apparatus
conductor using an approveddevice while
the hand applied earth is being attached or
removed.8.1.4 When applying a portable earthing device
that is not connected to a permanently installed
station earthing system it shall be regarded as
being liable to become live until the circuit earthing
is complete.
8.1.5 There are some situations where anauthorised electrical operatorcannot comply with
the clearances specified as safe approach
distances, when applying earths to electrical
apparatusduring the preparation for access, eg.,
discharging capacitor banks. In these situations,
organisational procedures may permit suchapproach only to that part of the electrical
apparatus which already has local isolation and
earthing.
8.2 EARTHING FOR ACCESS TO HIGHVOLTAGE ELECTRICAL APPARATUS
Earths shall be applied at locations such thatconductors within the work area are effectively
earthed in the event of energisation from any
source of supply or hazardous occurrences and be
-
8/4/2019 BlueBook 2008
75/151
Blue Book December 2005 Page 73 of 148
so placed as to remain effective if adjoining
conductors are disconnected.
Wherever practicableearths shall be placed at thesite of the work.
8.3 REMOVAL OF EARTH WHEN WORKING
UNDER AN ACCESS AUTHORITY
During work under an access authority, the
recipient in chargemay authorise the removal of anearth for meggering, reconductoring, or other
purposes, only if such action is considered
necessary and safe, and provided
the operating authoritythat has operational
control of the earth and the operating
authority who applied the earth agrees; in cases where the earth is listed on the
access authority, the operating authoritywho
issued the access authority is consulted, to
confirm that the removal of the earth will not
affect any other access authoritieson issue;
persons likely to be affected by the removalof the earth are notified; and
consideration is given to induced voltages.
Earthing of High Voltage Electrical Apparatus
-
8/4/2019 BlueBook 2008
76/151
Page 74 of 148 Blue Book December 2005
The earth removed shall be replaced in the same,or other equally effective position, as soon as
possible.8.4 EARTHING OF OVERHEAD LINES
Where an overhead line can only be earthed usingtemporarily driven earth spikes the work planningshall consider protection from the hazards resultingfrom energisation and step and touch potentials
(Refer to Clause 8.7 for priority earthing)
8.5 HIGH VOLTAGE METAL-CLAD SWITCHUNITS
For metal-clad switch units and circuits connectedthereto, the method of earthing shall be speciallyconsidered by the organisation responsible for the
earthing and the person in charge of the work,particularly in regard to the number and location ofearths. The application of earthing devices toisolating contacts in the spouts of metal-cladswitchgear shall be supervised by an authorisedperson, unless the devices are specificallyapproved by the organisation which owns theelectrical apparatusfor application by one person.
Earthing of High Voltage Electrical Apparatus
-
8/4/2019 BlueBook 2008
77/151
Blue Book December 2005 Page 75 of 148
8.6 HIGH VOLTAGE CAPACITORS
To declare high voltage capacitors safe for the
issue of an electrical access permit, the neutral aswell as the actives shall be earthedand, in addition,
each individual capacitor shall be discharged
before it is touched. The same precautions shall be
taken for work on electrical apparatus which
incorporates high voltage capacitors (e.g.
capacitor voltage transformers, carrier couplingcapacitors).
8.7 OVERHEAD LINES PRIORITY EARTHINGSYSTEM
The choice of connection for an earthing device
should where practicablebe made on the basis of
the following order of preference:
1. Permanently installed earthing system at the
worksite, including the neutral conductor of a
Common Multiple Earthed Neutral (CMEN)
System [Not to be confused with a Multiple
Earthed Neutral (MEN) System];
2. Permanently installed earthing system as
close as possible to the worksite (within 2
kilometres);
Earthing of High Voltage Electrical Apparatus
-
8/4/2019 BlueBook 2008
78/151
Page 76 of 148 Blue Book December 2005
3. Earthing ferrule in a concrete pole at theworksite;
4. Earthing ferrule in a concrete pole as closeas possible to the work site (within 2
kilometres);
5. A permanently installed earthing system orconcrete pole earthing ferrule within the
isolation area;
6. The ground rod of an installed pole stay or
permanently driven pole stakes;
7. A temporarily driven spike.
Earthing of High Voltage Electrical Apparatus
-
8/4/2019 BlueBook 2008
79/151
Blue Book December 2005 Page 77 of 148
9 ACCESS FOR WORK ON OR NEARHIGH VOLTAGE ELECTRICAL
APPARATUS
9.1 GENERAL
No person shall touch or work near the high voltage
conductorsof any electrical apparatusunless
the person is a recipientof an electrical
access permitcovering that electrical
apparatusand the high voltage
conductorshave been dischargedand/orearthedat the work site, and the electrical
access permitis availablefor reference at the
site of the work;
the person is a recipientof an electrical
access permitcovering the conductors of a
high voltage cable and the de-energisedstate of the cable at the work site is confirmed
in accordance with clause 9.8 and the
electrical access permitis available for
reference at the site of the work;
PRINCIPLE An appropriate safe access systemshall be applied before any work on or near highvoltage electrical apparatus
Access for Work on or Near High Voltage ElectricalApparatus
-
8/4/2019 BlueBook 2008
80/151
Page 78 of 148 Blue Book December 2005
in the case of a rackable circuit breakeror
rackable voltage transformer, the electrical
apparatusis removed from its rack or cubicleposition and placed in a designated
maintenance position;
the person is working under the terms of a
sanction for testingon that electrical
apparatus;
the person is changing high voltageclamp-on type fuse links at single wire earth return
distribution substations in accordance with
Organisational procedures;
the electrical apparatushas been declared
as out-of-commission in accordance with
clause 9.4;
the person is performing livework in
accordance with Organisational procedures;
the person is working in accordance with the
requirements of a person who has received
an appropriate permit to work adjacent tonetwork assets, authority (Refer to Section
12); or
the person is working near high voltage
Access for Work on or Near High Voltage ElectricalApparatus
-
8/4/2019 BlueBook 2008
81/151
Blue Book December 2005 Page 79 of 148
conductors under the requirements of safeapproach distance special as determined
by Organisational procedures in accordancewith clause 6.2.2.
9.2 ELECTRICAL ACCESS PERMITPROCEDURE
9.2.1 Application for an Electrical Access Permit
Before making application for an electrical accesspermit, the authorised applicantshall establish thatthe proposed work has been properly planned andcan be carried out safely.
The electrical apparatus to be covered and itslocation shall be accurately defined and the work tobe undertaken adequately described.
9.2.2 Testing Under an Electrical Access Permit
Testing under an electrical access permitmay beundertaken in accordance with organisationalprocedures which include:
a risk assessment to ensure that no
hazardous voltages and currents will bepresent as a result of the testing; and
that the provisions of clause 8.3 are met.
Access for Work on or Near High Voltage ElectricalApparatus
-
8/4/2019 BlueBook 2008
82/151
Page 80 of 148 Blue Book December 2005
9.2.3 Multiple Working Parties
When more than one electrical access permit is
issued on the same electrical apparatus, or whereseparate parties are working under the terms of oneelectrical access permit, there shall be co-ordination in planning and performing the work toensure that the actions of one party shall notendanger the safety of others.
9.2.4 Multiple Ownership
Where the scope of electrical apparatus to becovered is owned by more than one organisation, aprotocol shall be established between theseorganisations for processing the application andoutage requirements.
9.2.5 Issue and Receipt of Electrical AccessPermits
9.2.5.1 An electrical access permitmust be eithercancelled or suspended prior to the issue of asanction for testing on the same electricalapparatus.
9.2.5.2 An electrical access permitshall be issuedand cancelled only by an authorised electricaloperator. Electrical access permitsmay be issuedor relinquished by telephone or radio subject to the
Access for Work on or Near High Voltage ElectricalApparatus
-
8/4/2019 BlueBook 2008
83/151
Blue Book December 2005 Page 81 of 148
statements between the authorised electricaloperator and the recipient in charge being
confirmed by a witness at each end.9.2.5.3 At the time of issue the authorised electricaloperator shall describe and, where practicable,show the electrical apparatus covered by theelectrical access permitand the precautions taken,to the recipient in charge and all the initial
recipients.The authorised electrical operator shall alsodescribe or point out the nearest points of supplyand adjacent live electrical apparatus. In the caseof an electrical access permitissued by telephoneor radio the recipient in chargeshall assume theseresponsibilities.
9.2.5.4 Each electrical access permit shall beissued to a recipient in charge. The recipient inchargeshall ensure that all members of the workparty who will approach the electrical apparatussign on the electrical access permit.
9.2.5.5 The issuer and authorised recipients allhave a responsibility to ensure that the condition ofthe electrical apparatus, covered by the electricalaccess permit, is such that it shall be safe for theproposed work to be undertaken.
Access for Work on or Near High Voltage ElectricalApparatus
-
8/4/2019 BlueBook 2008
84/151
Page 82 of 148 Blue Book December 2005
9.2.5.6 All recipients shall be satisfied with theprecautions taken, the location of the points of
supply, and the proximity of any adjacent liveelectrical apparatus.
9.2.5.7 Any person involved in the issue or receiptof an electrical access permitwho is not satisfiedwith the conditions, may apply to have additionalprecautions taken, either before the electrical
access permit is issued or during the currency ofthe work.
9.2.5.8 Subsequent to the issue of an electricalaccess permitadditional recipientsmay sign on theelectrical access permit, after appropriateinstruction by the recipient in charge or by anauthorised electrical operator acting with theknowledge of the recipient in charge.
9.2.6 Persons Permitted to Sign ontoElectrical Access Permits
Recipientsof an electrical access permitshall beauthorised recipients or instructed persons
approved to work under that specific electricalaccess permit. In the latter case it shall be theresponsibility of the recipient in charge to ensurethat such persons are placed in the charge of anauthorised recipient.
Access for Work on or Near High Voltage ElectricalApparatus
-
8/4/2019 BlueBook 2008
85/151
Blue Book December 2005 Page 83 of 148
The conditions under which authorised recipientsshall sign onto an electrical access permit is that
the recipient: Understands the electrical apparatus
covered and the limits of the electricalaccess permit;
Is satisfied with the precautions taken; and
Is aware of the nearest adjacent live electricalapparatus.
The conditions under which an instructed personshall sign onto an electrical access permit is thatperson:
Understands instructions given on what
approach is permitted to the electricalapparatus;
Understands instructions given on whatactivity is permitted to be taken in relation tothe electrical apparatus; and
Agrees to the continuous and close
supervision by a nominated authorisedrecipient.
Access for Work on or Near High Voltage ElectricalApparatus
-
8/4/2019 BlueBook 2008
86/151
Page 84 of 148 Blue Book December 2005
9.2.7 Rejection of a Recipient
A person shall recommend the exclusion from an
electrical access permitof any other person who atanytime is considered unsafe as a recipient. Suchinstances shall be reported promptly to the personin charge of the work.
9.2.8 Absence of an Earth on ElectricalApparatus Under Electrical Access Permit
Wherever practicable electrical apparatusshall beearthed before the issue of an electrical accesspermit.
Where an earth has not been applied to electricalapparatusprior to the issue of an electrical accesspermit the recipient in charge shall arrange fordischarging and/or earthing of the electricalapparatus before any recipient touches the highvoltage conductors.
9.2.9 Recipient Working Alone
An electrical access permitmay be issued to one
authorised recipient, or a recipientmay work aloneunder the terms of an electrical access permit, onlyin accordance with Organisational procedures.
Access for Work on or Near High Voltage ElectricalApparatus
-
8/4/2019 BlueBook 2008
87/151
Blue Book December 2005 Page 85 of 148
9.2.10 Issuer also a Recipient
An issuer of an electrical access permitshall not be
the recipient in charge, but may sign on theelectrical access permit form as an authorisedrecipient.
9.2.11 Temporary Cessation of Work or Absenceof Recipients
Following a cessation of work or when recipientshave been temporarily absent from the work site,upon return each recipient, shall report to therecipient in charge to re-confirm the conditions ofthe electrical access permit.
9.2.12 Working on Multi-Circuit Overhead Lines
Where more than one high voltagecircuit is carriedon a pole or line structure and work is to beperformed on circuits under an electrical accesspermit whilst others remain live, the recipient inchargeshall ensure that each member of the workparty who approaches near any circuits correctlyidentify the circuit/s under electrical access permit
and all other circuits.
Access for Work on or Near High Voltage ElectricalApparatus
-
8/4/2019 BlueBook 2008
88/151
Page 86 of 148 Blue Book December 2005
9.2.13 Change of Electrical Access PermitConditions
The conditions specified and the precautions listedon the electrical access permit shall not bechanged unless mutually agreed upon by both theoperating authority and the recipient in charge andthen only when a check has been made with theappropriate operating authority regarding the
requirements of other electrical access permits andall recipients working under the electrical accesspermit have been notified of the change.
9.2.14 Cancellation of an Electrical AccessPermit
9.2.14.1 Recipients signing off an Electrical
Access PermitIt shall be the duty of each recipientof an electricalaccess permit to sign off before the electricalaccess permitis relinquished.
9.2.14.2 Responsibilities of the Recipient-inCharge when relinquishing an
Electrical Access Permit for cancellation.
When an electrical access permit is to berelinquished for cancellation, the recipient-in-chargeshall:
Access for Work on or Near High Voltage ElectricalApparatus
-
8/4/2019 BlueBook 2008
89/151
Blue Book December 2005 Page 87 of 148
ensure that all recipients signed on theelectrical access permithave ceased work
covered by the electrical access permitandhave signed off;
ensure that all recipientsand equipment areclear and will remain clear of the electricalapparatus;
sign off the electrical access permitas the
recipient-in-chargeto indicate that theelectrical access permitcan be cancelled; and
Advise the operating authorityof any conditionof the electrical apparatuswhich couldaffect its operation.
9.2.14.3 Absence of a Recipient at
Relinquishment
The practice of signing off an electrical accesspermiton behalf of another person is undesirableand should be avoided.
Appropriate organisation procedures should beimplemented with instructions for signing offrecipients where the recipients could not belocated.
Access for Work on or Near High Voltage ElectricalApparatus
-
8/4/2019 BlueBook 2008
90/151
Page 88 of 148 Blue Book December 2005
9.3 SANCTION FOR TESTING PROCEDURE
9.3.1 General
9.3.1.1 A sanction for testingshall be used if thetesting of high voltage electrical apparatushas thepotential to produce currents hazardous to thehuman body.
9.3.1.2 A sanction for testing must be eithercancelled or suspended prior to the issue of aelectrical access permit on the same electricalapparatus.
9.3.1.3 A Tester Responsible at Remote Locationis an authorised tester at a remote location to whoman authorised electrical operator has issued aComplementary Sanction for Testing.
9.3.1.4 Only one sanction for testing shall be onissue on the same electrical apparatusat any time.However, where the testing requires work at remotelocations, as well as the nominated main location,a Complementary Sanction for Testing covering thesame electrical apparatusshall be issued at eachremote location.
A Complementary Sanction for Testing shall bestructured to agree with that on the parent sanctionfor testing applicable at the nominated mainlocation. It shall be issued to an authorised testerateach remote location, who shall sign it as the Tester
Access for Work on or Near High Voltage ElectricalApparatus
-
8/4/2019 BlueBook 2008
91/151
Blue Book December 2005 Page 89 of 148
Responsible at the Remote Location.
A Complementary Sanction for Testing shall