    Application of VFD in

    Power Plants.........AN OVERVIEW

    by

    Amit KulshreshthaAGM(PE-Mech.)

  • 8/10/2019 Best presentation on VFD

    2/68

    Why to Use VFD

    1. Energy savings on most pump and fanapplications.

    2. Better process control and regulation.3. Speeding up or slowing down a machine or

    process.4. Inherent power-factor correction5. Protection from high in-rush currents6. Safe Acceleration and braking

  • 8/10/2019 Best presentation on VFD

    3/68

    Electric & Power Basics

    All VFDs must:

    Run a machine or process at adesired speed.

    Produce adequate torque tohandle the load.

    Use power efficiently to producethe necessary torque at a givenspeed.

  • 8/10/2019 Best presentation on VFD

    4/68

    Electric & Power Basics

    The typical waveform consists of thefrequency portion (time based) ofthe wave and the amplitude portion

    (the magnitude). This wave isactually in sine-wave form,commonly referred to as the

    fundamental.

  • 8/10/2019 Best presentation on VFD

    5/68

    Electric & Power Basics

    Sinusoidal Waveform With Frequency& Amplitude Components

  • 8/10/2019 Best presentation on VFD

    6/68

    AC-Induction-Motor Theory

  • 8/10/2019 Best presentation on VFD

    7/68

    AC Induction Motor Theory

    AC Induction Motor Squirrel Cage Design

  • 8/10/2019 Best presentation on VFD

    8/68

    AC Induction Motor Theory

    Three-phasemotor operation.

  • 8/10/2019 Best presentation on VFD

    9/68

    AC Induction Motor Theory

    How a motor shaft rotates?

    Torque is produced as the induction motorgenerates flux in its rotating field.

    As shaft torque load increases, the slip

    increases and more flux lines cut the rotorwindings, which in turn increases rotorcurrent, which increases the rotormagnetic field and consequently the rotortorque.

  • 8/10/2019 Best presentation on VFD

    10/68

    AC Induction Motor Theory

    Typical speedversus torquecurve for aNEMA design Bmotor.

    % Synchronous Speed

  • 8/10/2019 Best presentation on VFD

    11/68

    AC Induction Motor Issues

    Starting Induction Motors The starting current is very high, between 3 to 8

    times the full load current. Depending on the sizeof the motor, this can result in voltage sags inthe power system.

    The full torque is applied instantly at starting andthe mechanical shock can eventually damage thedrive system, particularly with materials handlingequipment, such as conveyors.

    In spite of the high starting current, for some

    applications the starting torque may be relativelylow, only 1.0 to 2.5 times full load torque.

  • 8/10/2019 Best presentation on VFD

    12/68

    AC Induction Motor Theory

    The speed of the rotating electric fieldwithin the induction motor.

    Synchronous Speed = 120 x frequencyNo. of motor poles

  • 8/10/2019 Best presentation on VFD

    13/68

    AC Induction Motor Theory

    AC motor speed change can beaccomplished in three ways:

    1. Change the number of poles in the motor; thismeans separate windings

    2. Change the slip characteristics of the motor;this is done with varying resistors, such as isdone with a wound-rotor motor or by varyingthe stator voltage; or

    3. Change the frequency of the power supplied tothe motor. This can be achieved by VFD .

  • 8/10/2019 Best presentation on VFD

    14/68

    VFD Basics

    The main objective of the VFD is to vary the speedof the motor while providing the closest

    approximation to a sine wave for current (whilepulsing DC voltage to the motor).

  • 8/10/2019 Best presentation on VFD

    15/68

    Components of VFD System1.Operator Interface2.Variable Frequency Controller

    3.AC Motor

    http://localhost/var/www/apps/conversion/tmp/scratch_6//upload.wikimedia.org/wikipedia/commons/e/e5/VFD_System.png
  • 8/10/2019 Best presentation on VFD

    16/68

    VFD Controller

    The variable frequency drive controlleris a solid state power electronicsconversion system consisting of threedistinct sub-systems

    1. A rectifier bridge converter

    2. A direct current (DC) link and

    3. An inverter

  • 8/10/2019 Best presentation on VFD

    17/68

    Rectifier bridge converter

    All VFDs need a power section that converts ACpower into DC power.

    This is called the Rectifier bridge.

    The Rectifieris commonly a three-phase, full-wave-diode bridge.

  • 8/10/2019 Best presentation on VFD

    18/68

    Direct current (DC) link

    The DC link may consist of a capacitor/inductorwhich smoothes out the converter's DC outputripple and provides a stiff input to the inverter. Ifnot, this distortion will show up in the output tothe motor.

  • 8/10/2019 Best presentation on VFD

    19/68

    Inverter

    The inverter section is made up of modules that consist of atransistor and diode in combination with each other whichinverts the DC energy back to AC.

    The power semi-conductors in the inverter section act asswitches, switches of the DC bus, and therefore, arepulsingthe motor with some voltage.

    By switching the inverter-transistor devices on and offmany times per half cycle, a

    pseudo - sinusoidal currentwaveform is approximated.

  • 8/10/2019 Best presentation on VFD

    20/68

    VFD Types

    Voltage-source inverter (VSI) drive The DC output of the diode-bridge converter stores energy in

    the capacitor bus to supply stiff voltage input to the inverter.The vast majority of drives are VSI type with PWM voltageoutput.

    Current-source inverter (CSI) drive

    The DC output of the SCR-bridge converter stores energy inseries-reactor connection to supply stiff current input to theinverter. CSI drives can be operated with either PWM or six-step waveform output.

    20

    http://localhost/var/www/apps/conversion/tmp/scratch_6//upload.wikimedia.org/wikipedia/commons/0/0d/CS_Inverter_Topology.jpghttp://localhost/var/www/apps/conversion/tmp/scratch_6//upload.wikimedia.org/wikipedia/commons/3/30/VSI_Topology.jpg
  • 8/10/2019 Best presentation on VFD

    21/68

    VFD Types Cont.. Six-step inverter drive

    The DC output of the SCR-bridge converter is smoothed viacapacitor bus and series-reactor connection to supply viaDarlington Pair or IGBT inverter quasi-sinusoidal, six-stepvoltage or current input to an induction motor.

    Load commutated inverter (LCI) drive The DC output of the SCR-bridge converter stores energy via

    DC link inductor circuit to supply stiff quasi-sinusoidal six-stepcurrent output of a second SCR-bridge's inverter and an over-excited synchronous machine.

    Cycloconverter or matrix converter (MC) Cyclo converters and MCs are AC-AC converters that have no

    intermediate DC link for energy storage.

    Doubly fed slip recovery system A doubly fed slip recovery system feeds rectified slip power to

    a smoothing reactor to supply power to the AC supply networkvia an inverter, the speed of the motor being controlled byadjusting the DC current.

    21

  • 8/10/2019 Best presentation on VFD

    22/68

    Pulse Width Modulation

    Pulse-width modulation (PWM), or pulse-durationmodulation (PDM), is a commonly used technique forcontrolling power to electrical devices.

    22

    Pulse-width-modulated voltage and

    current waveforms.

  • 8/10/2019 Best presentation on VFD

    23/68

    VFD Motor Selection issues

    The switching of insulated-gate bipolar transistors(IGBTs) to accomplish PWM on the output of aVFD creates voltage spikes on the line out to themotor.

    These spikes are amplified over distance and, intime, break down the insulation of a motor,shortening the motors life.

    For VFD applications, Class F or higher insulation

    should be selected when possible.

    23

  • 8/10/2019 Best presentation on VFD

    24/68

    VFD Motor Selection issues Cont..

    In constant power applications, for higher torque,the speed would be low.

    Reduced speed may affect the cooling of the

    motor windings for high torque applications. When a VFD applies high-frequency pulses to a

    motor, the parasitic capacitance between statorand rotor generates voltage on the motor shaft.

    This creates discharge arcing and shaft current,which may damage the shaft and bearingsurfaces.

    24

  • 8/10/2019 Best presentation on VFD

    25/68

    Sample PWM-Equivalent Circuit

  • 8/10/2019 Best presentation on VFD

    26/68

    26

    Application in Power

    Plants

  • 8/10/2019 Best presentation on VFD

    27/68

    27

    VFD APPLICATION TO CEP/ID fan(for Energy Savings)

  • 8/10/2019 Best presentation on VFD

    28/68

    28

    Variable speed control is the most energy efficient control method

  • 8/10/2019 Best presentation on VFD

    29/68

    29

    7 10

    7

    10

    12

    H

    Q

    Flow

    HeadHow VFD Saves Energy ?

  • 8/10/2019 Best presentation on VFD

    30/68

    30

    VFD for CEP

    P saving= 161.7 KW

  • 8/10/2019 Best presentation on VFD

    31/68

    31

    CEP/ID Fan

    There is a gap between design pointand the rated operating point.

    Design margins are to take care of

    extreme operating conditions. VFD ensures energy savings by

    reducing speed at the operating

    point. Margin to take care of operation at

    47.5Hz. is not needed.

  • 8/10/2019 Best presentation on VFD

    32/68

    32

    VFD APPLICATION TO COMPRESSOR

  • 8/10/2019 Best presentation on VFD

    33/68

    33

    VFD in Compressors

    Instead of loading and unloading in a cyclicmanner, the compressor is start/stop as perdesired duty requirement to maintain the setpressure.

    System saves energy as the motor does not runin idle mode.

    VFD in compressor allows frequent start/stop of

    motor as per duty requirement. Lower maintenance of the system due to smooth

    start.

  • 8/10/2019 Best presentation on VFD

    34/68

    34

    Coal Conveyors

    Coal conveyors are subjected to frequentstart/stop.

    Idle running of motor during stop bydisengaging the hydraulic coupling causes

    energy loss. Only 2 starts/hour are permissible. Conveyors have to be designed to start

    while fully loaded, i.e. high torque.

    Generally motors are run at part load. VFD can provide ideal solution for

    Conveyors.

  • 8/10/2019 Best presentation on VFD

    35/68

    35

    REELING DRUM APPLICATIONcont. The present scheme

    Cables reeling drum provided with brake motor The brake motor stops and holds the drum, as

    and when the paddle-feeder or stacker-re-claimer stops moving

    It protects the cable from slackness. The brake is released on restart and motor

    rotates the drum to maintain safe tension inthe cable.

    The motor with conical rotor with spring loaded

    brake and brake-shoe arrangement are proneto high maintenance. Many times causes unreeling of cable resulting

    in snapping or damage of it.

  • 8/10/2019 Best presentation on VFD

    36/68

    36

    REELING DRUM APPLICATION

    VFD Alternative Scheme The arrangement is an innovative solution

    of brake motor. The VFD maintains constant torque on the

    cable reeling drum continuously even atzero speed (i.e. stop condition).

    This constant torque maintains safetension on the cable.

    Power consumption at zero speed is equalto no load and part consumption duringmovements, as and when the drumrotates.

  • 8/10/2019 Best presentation on VFD

    37/68

    37

    VFD APPLICATION TO BOILER AREA

  • 8/10/2019 Best presentation on VFD

    38/68

    38

    VFD APPLICATION TO BOILER AREA

    Axial blade pitch control and VFD control give thesame level of efficiency in power consumption atpart load operations

    VFD control for PA fan, ID fan, Coal Feeder andFuel Oil motors can be implemented for old210MW units.

    VFD control for ID fans, Coal Feeder and Fuel Oilmotors can be implemented for old 500 MW units

    New units should have VFD for coal feeder speedcontrol as against eddy current clutch control

    Sipat-I coal feeder motors already have VFD

    controls.

  • 8/10/2019 Best presentation on VFD

    39/68

    39

    VFD APPLICATION TO BFP(for smooth start)

  • 8/10/2019 Best presentation on VFD

    40/68

    40

    Advantages of Using VFD

    Increased motor life due to the lowerthermal and mechanical stressed inview of the absence of starting inrushcurrents and reduced speed operation

    No limitation on the number of starts No contribution to fault current.

    One VFD can be used to start all the

    MDBFPs One more VFD can be kept as standby

  • 8/10/2019 Best presentation on VFD

    41/68

    41

    OPTION-A OPTION-B OPTION-C

    2 x50% TD+1x50%MD(hydrauliccoupling)

    2 x50% TD+1x50%MD (VFD)

    3x50% MDBFP (VFD)

    VFDs 0 2 ( 1+1standby) 9 (8+1standby)

    Turbines 8 8 0Motor 4 4 12

    Hydraulic couplings 4 0 0

    Flexibility of layout Negative Negative Positive

    Space requirement Negative Negative Positive

    Maintenance Negative Negative PositiveStartup time Negative Positive Positive

    Motor startup Negative Positive Positive

    Supply side Harmonics Neutral Neutral Neutral

    System Cost Low High Neutral

    VFD solution may be cheaper than the conventional one with other advantages as bonus

    VFD APPLICATION TO BFP4 UNITS

  • 8/10/2019 Best presentation on VFD

    42/68

    42

    BFP for 660MW Units- OPTION-B

    The BFP motor rating for 660MW (2x50%

    TDBFP+1x50% MDBFP) unit is 18MW andthus causes high electrical and mechanicalstress on the system during starting.

    Instead of 1x50%, it was proposed to use2x30% rating BFP for 660 & 800 MW units.However with VFD it can be retained as

    1x50%. The size of each VFD for 18MW motor shall

    be approximately 5MVA equal to no loadMVA rating.

    Ad t f U i VFD ith OPTION C

  • 8/10/2019 Best presentation on VFD

    43/68

    43

    Advantages of Using VFD with OPTION-C

    BFPs can be placed at 0.0 M El. Saving in Plant Cost due to lowering of

    De-aerator Elevation Absence of Associated Steam and

    Condensate piping

    Flexibility of Layout and Space Saving Absence of voltage dip problems This option is ruled out now because new

    CERC regulation permits only 2%

    additional aux. power on account of BFP,whereas BFP power consumption will be4% in supercritical unit.

  • 8/10/2019 Best presentation on VFD

    44/68

    44

    PRICE OF VFDfor BFP Motors cont.

    Siemens quote for VFD of 300kW Air Compressormotor: Rs. 4 million

    Siemens quote for VFD of 4000kW ID Fan

    induction motor: Rs. 45 million

    ABB quote for VFD of 4000kW ID Fan inductionmotor: Rs. 28.8 million

    Expected Price of VFD of 10MW rating along withmotor Rs. 80 millions

  • 8/10/2019 Best presentation on VFD

    45/68

    VFD WITH REMOTE RF CONTROLFOR

    EOT CRANES

    INTRODUCTION

  • 8/10/2019 Best presentation on VFD

    46/68

    INTRODUCTION

    USE :

    LIFTING / LOWERINGLOADS

    CARRYING LOADSALONG /ACROSS THERAILS

    MOTORS : MAIN HOIST/ CREEP MOTOR AUXILIARY HOIST / CREEP

    MOTOR

    CROSS TRAVEL / CREEPMOTOR

    LONG TRAVEL / CREEPMOTOR

    RANGE OF EOT CRANESIN NTPC:

    ( 7.5 T 105 T )

  • 8/10/2019 Best presentation on VFD

    47/68

    CONVENTIONAL PRACTICE

    SLIP-RING INDUCTIONMOTOR EMPLOYINGRESISTANCE CUT-IN/

    CUT-OUT FOR SPEEDCONTROL

    CABIN /PENDENTCONTROL

    http://images.google.co.in/imgres?imgurl=http://www.torqhoist.com/images/products/abal.gif&imgrefurl=http://www.torqhoist.com/product_detail.php%3FProductID%3D10%26CatID%3D37%26s_Name%3D%26&h=688&w=300&sz=37&hl=en&start=287&tbnid=nAzYnEVo3lfcrM:&tbnh=139&tbnw=61&prev=/images%3Fq%3Dpendant%2Bcontrol%2B%26start%3D280%26ndsp%3D20%26svnum%3D10%26hl%3Den%26lr%3D%26sa%3DN
  • 8/10/2019 Best presentation on VFD

    48/68

    VFD SYSTEM

    SQUIRREL CAGEINDUCTION MOTOR INPLACE OF SLIP RING IM

    SPEED CONTROL BYVARIABLE VOLTAGEVARIABLE REQUENCYDRIVE

    RADIO REMOTEFREQUENCY CONTROL

    UNIT

    http://en.wikipedia.org/wiki/Image:VFD_System.png
  • 8/10/2019 Best presentation on VFD

    49/68

    COMPONENTS & WORKINGPHILOSOPHY

    A) VARIABLE FREQUENCY DRIVE

    B) RADIO FREQUENCY REMOTE

    CONTROLLERTransmitter unitEncoderReceiverDecoderInterface panelCoupling systemControl gearBattery

    FEATURES

  • 8/10/2019 Best presentation on VFD

    50/68

    SALIENTFEATURES

    A) VFD SYSTEM

    SQ.CAGE INDUCTION MOTOR WITH VPI INSULATION AND INSULATEDNDE BEARING

    CHOICE OF MOTION CONTROL FROM OPERATORS CABIN OR REMOTE

    CONTROLLER

    STARTING TORQUE UPTO 400% WITH STARTING CURRENT LIMITEDTO 150%

    VFD CAPABLE OF WITHSTANDING UPTO 50C

    HARMONIC REDUCTION DEVICES

    SPEED CONTROL WITH 6 PULSE DESIGN

    PROTECTIONS: O/L , O/V , E/F , O/ S Ckt., I/P LOSS , LOAD LOSS, I/PTRANSIENT PROTECTION

    SALIENT FEATURES CONTINUED..

  • 8/10/2019 Best presentation on VFD

    51/68

    B)RADIO FREQUENCY REMOTE UNIT

    WIRELESS CONTROL WITH DOUBLE JOYSTIC MOVEMENTTYPE STEPPED CONTROL WITH SPRING RETURN

    TRANSMITTER & RECEIVER HAVE A UNIQUE FREQUENCY &

    ADDRESS CODE TO AVOID INTERFERENCE

    CAN COMMUNICATE UPTO 100 m DISTANCE

    CRANE OPERATION IS LOCKED IN CASE OFCOMMUNICATION FAILURE

    CHOICE OF TANDEM/SLAVE/SINGLE OPERATION

  • 8/10/2019 Best presentation on VFD

    52/68

    TECHNICAL ADVANTAGES

    VFD SYSTEM

    No slip ring related maintenance

    Creep motor not required

    Gear box not required

    Electrical braking before mechanical breaking-break life is more

    On line fault display- hence less down time

    Starting current is less than dol starting

    Smooth starting and stopping offers jerk less operation longer life due

    to less mechanical fatigue

    Wide speed range- step less speed control

    100% holding torque available at standstill

    More energy efficient

  • 8/10/2019 Best presentation on VFD

    53/68

    TECHNICAL ADVANTAGES

    RF CONTROL

    EASE IN HANDLING

    UNRESTRICTED OPERATOR MOBILITY

    NO ROUTINE MAINTENANCE REQUIRED

    WIRELESS OPERATION

  • 8/10/2019 Best presentation on VFD

    54/68

    COST ANALYSIS

    A) VFD SYSTEM IN 105T EOT CRANE IS COSTLIER BY Rs 1,39,750ie 0.7% OF COST OF ONE EOT CRANE (Approx. 2 crore)

    B) RF REMOTE CONTROLLER COSTS 1.15 Lacs WHICH IS 0.57% OFCOST OF ONE EOT CRANE

    BOTTOM LINE:

    A) + B) COMBINED TOGETHER SUMS UP TO BE 1.27%

    COSTLIER THAN THE PRESENT SYSTEM

    The 1.27% extra cost is insignificant, in lieu ofbenefits on energy savings, reduction in man powerand low maintenance.

  • 8/10/2019 Best presentation on VFD

    55/68

    AIR CONDITIONING

    55

  • 8/10/2019 Best presentation on VFD

    56/68

    Limitations of Centralized AC

    Higher space requirement for installation ofequipment. AC plant room is required.

    Not suitable for frequent load variation.

    Not efficient at part load operation. Difficult to retrofit.

    Operators intervention is required to control/vary inside conditions.

    Water Cooled systems although are veryefficient, require large quantity of make-upwater.

  • 8/10/2019 Best presentation on VFD

    57/68

    Limitations of Localized AC system

    Envisaged normally for small buildings.

    Available upto 15 TR capacity as a single unit.

    No humidity control.

    No arrangement for fresh air supply. Distance of out door unit can not be more

    than 10M.

    Part load operation is not possible.

    Noise in operation

    VRV (Variable Refrigerant

  • 8/10/2019 Best presentation on VFD

    58/68

    VRV (Variable Refrigerant

    Volume) Based on limitation of the above two

    systems a need was felt for anintermediate of the above two

    systems. VRV system has beendeveloped to overcome thelimitations imposed by centralisedand localised systems.

    The Variable Refrigerant Volume(VRV) system is also Known asVariable refrigerant Flow (VRF)

    system.

  • 8/10/2019 Best presentation on VFD

    59/68

    Schematic diagram of VRVsystem

  • 8/10/2019 Best presentation on VFD

    60/68

    VRV (Variable Refrigerant Volume) System

    Similar to split type of air conditioning. VRV comprises of no. of indoor units which share a common

    refrigerant circuit, served from a common outdoor unitcomprises of multiple compressors of varying capacity.

    The refrigerant flow is varied by using inverter controlledvariable speed compressor to respond to changes in thecooling or heating requirement.

    By the combination with the inverter compressor and theconstant speed compressor, the comfortable room conditionwill be obtained by changing the compressor operationcondition.

    VRV conditions air for each room individually as per loadrequirement.

  • 8/10/2019 Best presentation on VFD

    61/68

    Layout of VRV system

  • 8/10/2019 Best presentation on VFD

    62/68

    Freely Selectable Operation of

    Indoor UnitsUnitsOthers System VRF

    ON ONOFF OFF

    Partial Load implies 40 to 70%less energy consumption

    Not Possible

  • 8/10/2019 Best presentation on VFD

    63/68

    VRV/VRF

    VRV system can work as centralisedsystem.

    VRV system can work as localised system.

    Operating cost of the system is minimisedby use of varaible refrigerant flowconcept.

    Make up water is not required.

    VRV system can operate at part load. Total Piping length from outdoor to indoor

    unit can be as maximum as 150M.

    VRV/VRF

  • 8/10/2019 Best presentation on VFD

    64/68

    VRV/VRF

    (Comparison with chillers)

    S.No. Features VRV System Water cooled Chiller

    system

    Benefits of

    VRF System

    1. Type of System Completely Air-

    cooled system

    with three basic

    parts- Outdoor,indoor units &

    controllers

    Water cooled

    system with many

    component chilling

    machines, AHUs,Cooling tower,

    Chilled Water

    pumps, Condensate

    water pumps, many

    types valves,

    Electricals &controls etc.

    Minimum partsthus very

    simple VRF

    systems

    2. Energy

    Consumption

    Overall 25%-

    35% power

    saving on

    average basis

    Only efficient at

    certain load

    conditions

    Constant

    saving by

    optimal

    running

    VRV/VRF

  • 8/10/2019 Best presentation on VFD

    65/68

    VRV/VRF

    (Comparison with chillers)

    S.No. Features VRV System Water cooled

    Chiller system

    Benefits of

    VRV System

    3. Distribution

    Piping

    Network

    Smaller

    copper piping

    Bigger MS piping Shaft/ floor

    space not

    required

    4. Interiors,

    Ceiling height

    Different type

    of Indoor

    options to fit

    into different

    construction,interiors

    Only Ducted

    Systems possible.

    Flexibility in

    layout.

    5. Standby

    Function

    Inbuilt

    Standby -

    Multi tier

    To be added at

    extra cost

    Ensured

    Operation all

    Times

    C l i

  • 8/10/2019 Best presentation on VFD

    66/68

    66

    Conclusion VFD Can be used in CEP for future projects for

    energy saving.

    For All old stations, VFD can be installed in CEPbased on techno-economics.

    For Large size units, VFD in BFP Motor offers anumber of advantages and can be considered infuture.

    VFD can be useful for conveyor motors, compressorand reeling drum motors.

    Boiler Auxiliaries such as PA fan , ID fan ,Coal Feederand Fuel Oil motors can be upgraded with VFDcontrol, for old 210 MW and 500MW units.

    New units of all sizes should have VFD for coal feederspeed control.

    VFD is becoming popular for VRV air-conditioning ,Hoists, Lifts and EOT Cranes

  • 8/10/2019 Best presentation on VFD

    67/68

    67

    THANK YOU

    Speed & Motor Ratings - Major SG Auxiliaries

  • 8/10/2019 Best presentation on VFD

    68/68

    Aux\MW 210 500 660

    FD fan575 KW

    1480 RPM1225 KW900 RPM

    1950 KW990 RPM

    PA fan1600 KW1480 RPM

    2850 KW1490 RPM

    3350 KW1490 RPM

    ID fan1650 KW

    120-580 RPM3895 KW

    AT 545 RPM5250 KW590 RPM

    Coal Feeder5.5 KW

    1500 RPM5.5 KW

    1500 RPM5.5 KW

    VFD

    Coal Mill

    425 KW

    589 RPM

    525 KW

    985 RPM

    690 KW

    986 RPM

    BCW pump NA365 KW

    1455 RPM545 KW

    2930 RPM

    37 KW 90 KW 75 KW