water chemistry controls provide continuous monitoring and control of sanitizers (standard ORP probe or optional Cl/Br amperometric probe), oxidizers, pH and total system flow rate. The controller is reliable, flexible, expandable, easy to install and even easier to operate. The can be configured for functions such as dual pH feeds, heater control, a primary Cl/Br sanitation feed, up to two Cl/Br booster feeds, a reducer feed (dechlor), an ozone generator and an alarm relay. Every controller comes with a comprehensive installation, operation and service manual with field start-up and service support provided by local distribution.
All controllers come with a PVC machined flow cell, which includes proprietary potentiometric pH & ORP probes, reed flow switch (rotary flow switch is an optional upgrade), temperature sensor, optional amperometric probe and optional flow meter & saddle. controllers are suitable for gas chlorine, sodium & calcium hypochlorite, bromine and ozone in a variety of installations such as pools, spas, fountains, zoos, aquariums and cooling towers. With an interactive information system that provides remote control and data acquisition, the is the most advanced water chemistry control and monitoring system available today. With over 30,000 controls manufactured over a span of 14 years, is a proven leader in the design and manufacture of commercial recreational water chemistry controls.
BECSys5
BECSys5
BECSys5
BECSys5
BECSys5
July 06
FLOW SWITCH· Reed (standard)· Rotary w/in-line check valve
(upgrade)
Alliance Partner
Warranty - 5 year electronics and 2 year sensorsProduct Certifications - UL 508, (CSA) C22.2 Number 205 - M1983, FCC part 15 sub part B
EMATO CORP.
1605 McEwen Dr., Whitby, Ont., Can. L1N 7L4 Www.nemato.com [email protected]
Head Office1 (800) 361-5025Tel: (905) 571-5305Fax: (905) 571-3935
Rhode Island Office
Tel: (401) 667-7171Fax: (401) 667-7171
FEED MODEAuto/Off/Manual, On/Off or
Proportional·
BECSys5 WATER CHEMISTRY CONTROL
Distributor
BECS BECSTECHNOLOGY
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
DATA LOGGING Readings· Data logging of pH, ORP, Cl/Br ppm,
temperature, flow rate, chemical inventories Events· Alarms, menu changes, operational cycles· pH, ORP & ppm Hi/Low/interlocked
failsafe· Temperature Hi/Low/heater failsafe· System Low flow & sample stream No flow· Chemical inventory level· Battery Low Feed Mode· Auto/Off/Manual, On/Off or
Proportional
PHYSICAL SPECIFICATIONS CONTROLLER
· <1A 120 VAC fused input· Four outputs 3A powered solid
state relays for master alarm and pump control
· NEMA 4X polycarbonate (IP66) enclosure
ALARM INDICATORS· Flashing alarm LED· All specific alarms indicated with
auto scrolling on LCD· Hi/Low out of range, over feed and low or no flow
SAFETY SYSTEMS· Security passwords
o 3 levels: 6 Op, 2 Mgr, 1 Rep· Programmable alarms (some disabling
chemical feed)o pH, ORP, Cl/Br ppm, temp,
low flow & no flow, chemical overfeed, chemical inventory
CONTROL DISPLAYS· LCD display backlit 12X40 character
alpha/numeric, graphical· pH: 0.0 to 14.0, 0.1 or 0.01 resolution
(programmable)· ORP: -1000 to 1000 mV, 1 mV resolution· PPM: 0 to 20 ppm 0.1 or 0.01 resolution
(programmable)O· Temperature: 32-212 F, 1 F resolution; 0-
O O100 C, 1 C resolution· Flow rate: 0-8800 gpm, 0.1 gpm
resolution; 0-33265 liter/min, 0.1 liter resolution
· Flow volume: 999 trillion gallons, 1 gallon resolution; 999 trillion liters, 1 liter resolution
· Chemical Inventory: programmable range 0.1 ft.; 0.1 m
· Heater set point & alternate heater set point (4 Event 28 day timer)
· Alternate ORP control set point (4 Event 28 day timer)
· Cl/Br booster ORP and or ppm feed points with a separate trigger set points
· Ozone ORP and/or ppm set points· Dechlorination ORP or ppm set point· Superchlorination ORP or ppm set point· Display of Ca hardness & alkalinity· Langelier & Ryznar index calculated· Smart menus w/ integrated help
O
SENSORS· Potentiometric pH &
ORP; inorganic electrolyte
· Temperature· Pressure gauge· Amperometric Free
Chlorine w/replaceable PTFE membrane & electrolyte (optional)
· Flow meter & saddle (optional)
· Chemical Inventory; proprietary level & weight sensor (optional) or 4 to 20 mA sensor (optional) or digital sensor (optional)
PHYSICAL SPECIFICATIONS FLOWCELL
· PVC flowcell body· Threaded ports for sensors and sample
stream fittings· Clear acrylic viewing face· PVC ½” isolation ball valves· PVC ¼” wet test valve
July 06
REMOTE OPERATIONS
· PC direct connect· Data Modem· BECSys for Windows
with graphical display· BECSysRF Wireless
Communication Module monitor and control BECSys5 from remote location without phone lines or cables.