battery testing manual new logo

Upload: mukund-chaudhary

Post on 02-Jun-2018

240 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/10/2019 Battery Testing Manual New Logo

    1/15

    BATTERY TESTING, MONITORING

    AND

    RESTORATION MANUAL

    E-Mail:

    Submitted By

    MTekPRO Technologies Private Limited

    B-229, LGF, Greater Kailash- I, New Delhi, PIN- 110048

    [email protected],Website:www.mtekpro.com

    Phone: +91 11 46173333, Fax: +91 11 41825662

    mailto:[email protected]:[email protected]:[email protected]://www.mtekpro.com/http://www.mtekpro.com/http://www.mtekpro.com/http://www.mtekpro.com/mailto:[email protected]
  • 8/10/2019 Battery Testing Manual New Logo

    2/15

    Electric generating stations and substations for protection and control of switches

    and relays

    Why battery backup is needed?

    Batteries are used to ensure that critical electrical equipment is always on. There are so

    many places where batteries are used and it is nearly impossible to list them all. Some of

    the applications for batteries include:

    Telephone systems to support phone service, especially emergency services

    Industrial applications for protection and control

    Back up of computers, especially financial data and information

    Less critical business information systems.

    Without battery back-up hospitals would have to close their doors until power is restored.

    But even so, there are patients on life support systems that require absolute 100% electric

    power. For those patients, as it was once said, failure is not an option.

    Just look around and see how much electricity we use and then to see how important

    batteries have become in our everyday lives. The many blackouts of 2003 and 2012 aroundthe world show how critical electrical systems have become to sustain our basic needs.

    Batteries are used extensively and without them many of the services that we take for

    granted would fail and cause innumerable problems.

    to insure the supported equipment is adequately backed-up

    Why to test battery systems?

    There are three main reasons to test battery systems:

    to prevent unexpected failures by tracking the batterys health

    to forewarn/predict death

  • 8/10/2019 Battery Testing Manual New Logo

    3/15

    Primary Battery Failure Modes:

    Electrolyte Water Loss:

    Dry out, vapor diffusion through container (

  • 8/10/2019 Battery Testing Manual New Logo

    4/15

    Battery Life Cycle and Replacement Zone:

    1. Impedance

    IEEE Recommendations:

    2. Voltage

    3. Specific Gravity

    4. Loud Test

    5. Visual Inspection

    1. Impedance

    Lagging Indicators:

    2. Voltage

    3. Specific Gravity

    1. Sulfation

    Leading Indicators:

    2.

    Dry out3. Chemical Properties

  • 8/10/2019 Battery Testing Manual New Logo

    5/15

    In Old UPS Battery Systems - The DC filtering capacitors usually had much lower

    impedances than the batteries. Designs have changed.

    Improved Battery Diagnostics- The Truth About Noise:

    Because the DC capacitors and battery are in parallel, they will share the AC Ripple

    (Noise).

    Many UPS Manufacturers have lowered the amount of filtering capacitors.

    More DC current is flowing into the battery and less into the filtering capacitors.

    The majority of the AC ripple current comes from the inverter as it converts the DC

    power to AC power.

    Most battery manufacturers specify a maximum acceptable ripple voltage- typically1 to 2% of the DC float voltage.

    AC ripple voltages will induce AC ripple currents.

    High ripple currents cause Excess Heat, Reduced Battery Life and thermal

    runaway.

    Conclusions:

  • 8/10/2019 Battery Testing Manual New Logo

    6/15

    Discharge (Load) testing remains the most reliable method to monitor the state of

    health of a battery.

    Discharge testing is time consuming, expensive, must be done offline and is

    detrimental to the batteries.

    Reduced life due to discharge testing.

    Routine discharge testing is also required for accurate results.

    Load testing is still considered to be required.

    Cannot rely on any one test method.

    New test and measurement equipment is available for testing both the electrical

    and chemical properties. This will catch the chemical failure modes and is the best,

    rapid-test solution.

    Continuous monitoring is an excellent alternative when cost is not an issue.

  • 8/10/2019 Battery Testing Manual New Logo

    7/15

    Lead Acid

    Types of Batteries:

    There are several main types of battery technologies with subtypes:

    Flooded (Wet): Lead- Calcium, Lead- Antimony

    Valve regulated Lead-acid, VRLA (sealed): Lead- Calcium, Lead- Antimony-

    Selenium

    o Absorbed Glass Matte (AGM)

    o

    Gel Flat plate

    Tubular plate

    Nickel-Cadmium

    Flooded

    Sealed

    Pocket plate Flat plate

    PbO2 + Pb + 2H2SO4 2PbSO4+ 2H2O

    Lead- Acid Overview:

    The basic lead- acid chemical reaction in a sulfuric acid electrolyte, where the sulfate of the

    acid is the part of the reaction, is:

    The acid is depleted upon discharge and regenerated upon recharge. Hydrogen and

    oxygen form during discharge and float charging (because float charging is counter acting

    self-discharge). In flooded batteries, they escape and water must be periodically added. In

    valve-regulated, lead-acid (sealed) batteries, the hydrogen and oxygen gases recombine to

  • 8/10/2019 Battery Testing Manual New Logo

    8/15

    form water. Additionally, in VRLA batteries, the acid is immobilized by an absorbed glass

    matte (AGM) or in a gel.

    The matte is much like the fiberglass insulation used in houses. It traps the hydrogen and

    oxygen formed during discharge and allows them to migrate so that they react back to

    form water. This is why VRLA never need water added compared to flooded (wet, vented)

    lead-acid batteries.

    A battery has alternating positive and negative plates separated by micro-porous rubber in

    flooded lead-acid, absorbed glass matte in VRLA, gelled acid in VRLA gel batteries or plastic

    sheeting in NiCd. All of the like-polarity plates are welded together and to the appropriate

    post. In the case of VRLA cells, some compression of the plate-matte-plate sandwich isexerted to maintain good contact between them. There is also a self-resealing, pressure

    relief valve (PRV) to vent gases when over-pressurization occurs.

    2 NiO(OH) + Cd + 2 H2O 2Ni(OH)2 + Cd(OH)2

    However, in NiCd batteries the potassium hydroxide (KOH) does not enter the reaction like

    sulfuric acid does in lead-acid batteries. The construction is similar to lead-acid in that

    there are alternating positive and negative plates submerged in an electrolyte. Rarely

    seen, but available, are sealed NiCd batteries.

    Nickel- Cadmium Overview:

    Nickel-Cadmium chemistry is similar in some respects to lead-acid in that there are two

    dissimilar metals in an electrolyte. The basic reaction in a potassium hydroxide (alkaline)electrolyte is:

  • 8/10/2019 Battery Testing Manual New Logo

    9/15

    Failure Modes:

    Positive grid corrosion

    Lead-acid (flooded) failure modes:

    Sediment (shedding) build-up

    top lead corrosion

    Plate sulfation

    Hard shorts (paste lumps)

    Dry-out (Loss-of-Compression)

    Lead-acid (VRLA) failure modes:

    Plate Sulfation

    Soft and Hard Short

    Post leakage

    Thermal run-away

    Positive grid corrosion

    Gradual loss of capacity

    Nickel-Cadmium failure modes:

    NiCd batteries seem to be more robust than lead-acid. They are more expensive to

    purchase but the cost of ownership is similar to lead-acid, especially if maintenance costs

    are used in the cost equation. Also, the risks of catastrophic failure are considerably lower

    than for VRLAs.

    The failure modes of NiCd are much more limited than lead-acid. Some of the more

    important modes are:

    Carbonation

    Floating effects

    Cycling

    Iron poisoning of positive plates

  • 8/10/2019 Battery Testing Manual New Logo

    10/15

    Best way to test and evaluate your battery:

    1. Make a test and benchmark its values when the battery is new as part of the

    acceptance testing.

    Test intervals:

    2. Make an impedance test at the same time to establish baseline values for the

    battery.

    3. Repeat the above within 2 years for warranty purpose.

    4. Make an impedance test every year on flooded cells and quarterly on VRLA cells.

    5.

    Make capacity tests at least for every 25% of expected service life.6. Make capacity test annually when the battery has reached 85% of expected service

    life or if the capacity has dropped more than 10% since the previous test or is below

    90% of the manufacturers rating.

    7. Make a capacity test if the Impedance value has changed significantly.

    1. Replace cell if the impedance is more than 50% above baseline. Make a capacity test

    if 20-50% of baseline.

    Evaluation:

    2. Replace battery if capacity test shows less than 80% of rated capacity.

    Practical Battery Testing:

    The battery testing matrix below may help guide even the most skilled battery testing

    technician and will help simplify the recommended practices.

    The following is a description of some of the tests or maintenance parameters.

    Impedance, an internal ohmic test, is resistance in AC terms. With regard to DC battery

    systems, impedance indicates the condition of batteries. Since it tests the condition of the

    Impedance Test:

  • 8/10/2019 Battery Testing Manual New Logo

    11/15

    entire electrical path of a battery from terminal plate to terminal plate, impedance can

    find weaknesses in cells and inter cell connectors easily and reliably.

    Basically, impedance test is determined by applying an AC current signal, measuring the AC

    voltage drop across the cell or inter cell connector and calculating the impedance using

    Ohms Law. In practice, not only is the AC voltage drop measured but so is the AC current.

    The AC current is measured because of other AC currents in a battery that are additive

    (subtractive). Other AC currents are present from the charger system. The test is

    performed by applying an AC test signal to the terminal plates. Then measure both the

    total AC current in the string and the voltage drop of each unit in the string by measuring

    each cell and inter cell connector consecutively until the entire string is measured. The

    impedance is calculated, displayed and stored. As the cells age, the internal impedanceincreases as depicted in figure 1. By measuring impedance, the condition of each cell in the

    string can be measured and trended to determine when to replace a cell or the string

    which helps in planning for budgetary needs.

    Figure 1: Impedance V/S Discharge Current

  • 8/10/2019 Battery Testing Manual New Logo

    12/15

    The impedance test is a true four-wire, Kelvin-type measurement that provides excellent

    reliability and highly reproducible data on which to base sound decisions with regard to

    battery maintenance and replacement. Impedance is able to find weak cells so that

    proactive maintenance can be performed. After all, the battery is a cost but it is supporting

    a critical load or revenue stream. If a single cell goes open then the entire string goes off

    line and the load is no longer supported.

    Therefore, it is important to find the weak cells before they cause a major failure. The

    graph in figure 2 shows the effect of decreasing capacity on impedance. There is a strong

    correlation between impedance and capacity so that weak cells are ably and reliably found

    in sufficient time to take remedial action.

    The graph shows the reorganized impedance data in ascending order with each cells

    corresponding load test end voltage. (Impedance in milliohms coincidentally is the same

    scale as the voltage, 0 to 2.5). This view, that is ascending impedance/descending voltage,

    groups the weak cells on the right side of the graph to find them easily.

    Figure 2:- Ascending impedance with corresponding end voltage

  • 8/10/2019 Battery Testing Manual New Logo

    13/15

    High power battery capacity test system

    Battery testing using BTS 200 MKII and ELU 200 MKII

    Electrical power plants are normally equipped with batteries of different types and regular

    test according to international standard are requested in order to assure the standby

    power for relays, circuit breakers, measuring equipment and telephone exchanges.

    Discharging current up to 1300A with external loads (up to 9)

    Graphical display showing test parameters, curve and results

    Internal memory

    Light and easy to carry, with handles and wheels Shunt or clamp metering of an additional current

    Suitable for all battery types

    Application:

    The most reliable method for the determination of battery capacity is to perform a

    discharging cycle periodically. BTS 200 MKII allows performing such test combining

    efficiency with portability. It can test any type of battery with a discharging current op to1300A with external loads.

    Battery Nominal Voltage (in Volts)

    Specification:

    Maximum discharging current with BTS 200 MKII

    Maximum Current Discharged (in Amperes)

    240 70

    220 70140 130

    110 130

    48 130

    24 130

  • 8/10/2019 Battery Testing Manual New Logo

    14/15

    It is possible to parallel up to 9 external loads ELU 200 MKII. The test set shows on the

    large back-lighted LCD display the following parameters:

    Battery voltage;

    Minimum voltage threshold (adjustable),with automatic stop;

    Discharging current, power or profile;

    Ah (ampere-hour) discharged;

    Test time duration with automatic stop at time out;

    Test conditions are all displayed;

    Discharging curve is displayed;

    Test parameters are entered via the functional pushbutton and the graphical displayon the front panel.

    Constant discharge current

    Load patterns:

    Constant power

    Current profile (up to 20 steps)

    Power profile Manual control

    Range: 0 - 130 A;

    Measurement of the discharging current:

    Display: 0 - 130 A (0 - 1300 A with external loads);

    Accuracy: 1 % of the value, 0.2 % of the range.

    The discharging activity can be stopped and started again later from the same level.

  • 8/10/2019 Battery Testing Manual New Logo

    15/15

    External Load ELU 200 MKII (OPTIONAL):

    When higher load current is necessary, it is possible to use the BTS 200 MKII in connection

    with external load ELU 200 MKII.ELU 200 MKII is an active programmable burden as BTS

    200MKII. BTS 200 MKII allows the connection up to 9 external loads ELU 200 MKII.

    Nominal

    Battery

    Voltage (V)

    BTS 200 MKII: Discharging Examples:

    Nominal

    Capacity (Ah)

    Constant

    Current (A)

    Constant

    Power (kW)

    Test

    Duration (in

    Hours)

    Discharging

    Capacity (Ah)

    End of Test

    Voltage (V)

    24 500 50 1 10 500 20

    48 500 50 2 10 500 40

    110 500 50 4.7 10 500 94

    120 500 50 5.1 10 500 102

    220 500 50 9.4 10 500 188

    240 500 50 10.2 10 500 204

    Battery

    Voltage

    Maximum discharging current with BTS 200 MKII with external loads ELU 200

    MKII:

    Maximum Discharge Currents of BTS 200 MKII with ELU 200 MKII External Loads

    No. of

    ELU 200

    MKII

    1 2 3 4 5 6 7 8 9

    24 VDC 260 A 390 A 520 A 650 A 780 A 910 A 1040 A 1170 A 1300 A

    48 VDC 260 A 390 A 520 A 650 A 780 A 910 A 1040 A 1170 A 1300 A

    110 VDC 260 A 390 A 520 A 650 A 780 A 910 A 1040 A 1170 A 1300 A

    120 VDC 260 A 390 A 520 A 650 A 780 A 910 A 1040 A 1170 A 1300 A220 VDC 140 A 210 A 280 A 350 A 420 A 490 A 560 A 630 A 700 A

    240 VDC 140 A 210 A 280 A 350 A 420 A 490 A 530 A 630 A 700 A