auto transformer energy conversion 6

Upload: katari-sreenu

Post on 10-Feb-2018

235 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/22/2019 Auto Transformer Energy Conversion 6

    1/38

    ENERGY CONVERSION ONE

    (Course25741)

    Chapter Two

    TRANSFORMERScontinued

  • 7/22/2019 Auto Transformer Energy Conversion 6

    2/38

    Transformer Voltage Regulation

    and Efficiency Output Voltage of Transformer Varies with Load

    Due to Voltage Drop on Series Impedance of TransformerEquivalent Model

    Full Load Regulation Parameter, compares output no-load

    Voltage with its Full Load Voltage:V.R. =

    At no load VS= VP / a thus :

    V.R.=

    in per unit: V.R. =

    For Ideal Transformer V.R.=0

    %100..,

    ..,..,

    LFS

    LFSLNS

    V

    VV

    %100)/(

    ..

    ..

    LF

    LFP

    V

    VaV

    %100,,

    ,,,

    puFLS

    puFLSpuP

    V

    VV

  • 7/22/2019 Auto Transformer Energy Conversion 6

    3/38

    Transformer Voltage Regulation and

    Efficiency

    The transformer phasor diagram

    To determine the voltage regulation of a transformer:

    The voltage drops should be determined

    In below a Transformer equivalent circuit referred to

    the secondary side shown:

  • 7/22/2019 Auto Transformer Energy Conversion 6

    4/38

    Transformer Voltage Regulation

    and Efficiency

    since current which flow in magnetizing branch is small

    can be ignored

    Assuming secondary phasor voltage as reference VS with

    an angle of 0

    Writing the KVL equation:

    From this equation the phasor diagram can be shown: At lagging power factor:

    SeqSeqSP IjXIRVa

    V

  • 7/22/2019 Auto Transformer Energy Conversion 6

    5/38

    Transformer Voltage Regulation and

    Efficiency

    If power factor is unity, VS is lower than VP soV.R. > 0

    V.R. is smaller for lagging P.F.

    With a leading P.F., VS is larger VP V.R.

  • 7/22/2019 Auto Transformer Energy Conversion 6

    6/38

    Transformer Voltage Regulation

    and Efficiency

    Table Summarize possible Value for V.R. vs Load P.F.:

    Since transformer usually operate at lagging P.F., asimplified method is introduced

    Lagging P.F. VP/ a > VS V.R. > 0

    Unity P.F. VP / a > VS V.R. >0 (smaller)

    Leading P.F. VS > VP/ a V.R. < 0

  • 7/22/2019 Auto Transformer Energy Conversion 6

    7/38

    Transformer Voltage Regulation and

    Efficiency

    Simplified Voltage Regulation Calculation

    For lagging loads: the vertical components

    related to voltage drop on Req & Xeq partially

    cancel each otherangle of VP/a very small

  • 7/22/2019 Auto Transformer Energy Conversion 6

    8/38

    Transformer Voltage Regulation

    and Efficiency

    Transformer Efficiency (as applied to motors, generators and motors)

    Losses in Transformer:

    1- Copper IR losses

    2- Core Hysteresis losses

    3- Core Eddy current losses

    Transformer efficiency may be determined as follows:

    %100xP

    P

    in

    out %100x

    PP

    P

    lossout

    out

    %100cos

    cos

    xIVPP

    IV

    SScoreCu

    SS

  • 7/22/2019 Auto Transformer Energy Conversion 6

    9/38

    Transformer Voltage Regulation

    and Efficiency

    Example:

    A 15kVA, 2300/230 V transformer tested to determine

    1- its excitation branch components, 2- its series

    impedances, and 3- its voltage regulation Following data taken from the primary side of the transformer:

    Open Circuit Test Short Circuit Test

    VOC=2300 V VSC=47 V

    IOC=0.21A ISC=6 A

    POC= 50 W PSC= 160 W

  • 7/22/2019 Auto Transformer Energy Conversion 6

    10/38

    Transformer Voltage Regulation

    and Efficiency

    (a) Find the equivalent circuit referred to H.V. side

    (b) Find the equivalent circuit referred to L. V. side

    (c) Calculate the full-load voltage regulation at 0.8 lagging PF,

    1.0 PF, and at 0.8 leading PF(d) Find the efficiency at full load with PF 0.8 lagging

    SOLUTION:

    Open circuit impedance angle is:

    Excitation admittance is:

    8421.02300

    50coscos 11

    OCOC

    OC

    OC

    IVP

    0000908.00000095.0

    841013.9842300

    21.084

    5

    j

    V

    IY

    OC

    OC

    E

  • 7/22/2019 Auto Transformer Energy Conversion 6

    11/38

    Transformer Voltage Regulation

    and Efficiency

    Impedance of excitation branch referred to primary:

    Short Circuit Impedance angle:

    Equivalent series Impedance:

    Req=4.45 , Xeq=6.45

    kX

    kR

    M

    C

    110000908.0

    1

    1050000095.0

    1

    4.55647

    160coscos 11

    SCSC

    SCSC

    IV

    P

    45.645.4

    4.55833.74.556

    47

    j

    I

    VZ SC

    SC

    SCSE

  • 7/22/2019 Auto Transformer Energy Conversion 6

    12/38

    Transformer Voltage Regulation and

    Efficiency

    The equivalent circuits shown below:

  • 7/22/2019 Auto Transformer Energy Conversion 6

    13/38

    Transformer Voltage Regulation and

    Efficiency

    (b) To find eq. cct. Referred to L.V. side,

    impedances divided by a=NP/NS=10

    RC=1050 , XM=110 Req=0.0445 , Xeq=0.0645

    (c) full load current on secondary side:

    IS,rated=Srated/ VS,rated=15000/230 =65.2 ATo determine V.R., VP/ a is needed

    VP/a = VS + Req IS + j Xeq IS , and:

    IS=65.2/_-36.9 A , at PF=0.8 lagging

  • 7/22/2019 Auto Transformer Energy Conversion 6

    14/38

    Transformer Voltage Regulation

    and Efficiency

    Therefore:

    VP / a =

    V.R.=(234.85-230)/230 x 100 %=2.1 % for 0.8 lagging

    At PF=0.8 leading IS=65.2/_36.9 A

    VP / a =

    Vj

    jj

    j

    4.085.23462.184.234

    36.352.274.132.2230

    1.5321.49.369.20230

    9.362.650645.0)9.362.65)(0445.0(0230

    Vj

    jj

    j

    27.185.22910.58.229

    36.352.274.132.2230

    9.12621.49.369.20230

    9.362.650645.0)9.362.65)(0445.0(0230

  • 7/22/2019 Auto Transformer Energy Conversion 6

    15/38

    Transformer Voltage Regulation

    and Efficiency

    V.R. = (229.85-230)/230 x 100%= -0.062%

    At PF=1.0 , IS= 65.2 /_0 A

    VP/a=

    V.R. = (232.94-230)/230 x 100% = 1.28 % for PF=1

    Vj

    j

    j

    04.194.23221.49.232

    21.49.22309021.409.20230

    )02.65)(0645.0()02.65)(0445.0(0230

  • 7/22/2019 Auto Transformer Energy Conversion 6

    16/38

    Transformer Voltage Regulation and

    Efficiency

    Example: Phasor Diagrams

  • 7/22/2019 Auto Transformer Energy Conversion 6

    17/38

    Transformer Voltage Regulation and

    Efficiency

    (d) to plot V.R. as a function of load is by

    repeating the calculations of part c for many

    different loads using MATLAB

  • 7/22/2019 Auto Transformer Energy Conversion 6

    18/38

    Transformer Voltage Regulation and

    Efficiency

    (e) Efficiency of Transformer:

    - Copper losses:

    PCu=(IS)Req =(65.2) (0.0445)=189 W- Core losses:

    PCore= (VP/a) / RC= (234.85) / 1050=52.5 W

    output power:Pout=VSIS cos=230x65.2xcos36.9=12000 W

    = VSIS cos / [PCu+PCore+VSIS cos] x 100%=

    12000/ [189+52.5+12000] = 98.03 %

  • 7/22/2019 Auto Transformer Energy Conversion 6

    19/38

    Efficiency of Distribution Transformers

  • 7/22/2019 Auto Transformer Energy Conversion 6

    20/38

    Energy Losses in Electrical Energy

    Systems

    The total electrical energy use per annum of the worldis estimated as 13,934

    TeraWatthours [TWh] (1 TWh = 10^9 kWh)

    it is further estimated [2] that the losses in all of theworlds electrical distribution systemstotal about1215 TWh or

    about 8.8% of the total electrical energy consumed.

    About 30-35% of these losses are generated in theTransformersin the Distribution systems.

    Studies estimate that some 40-80% of thesetransformer losses are potentially saveable by

    increasing transformer efficiencies, i.e. 145-290 TWh.

  • 7/22/2019 Auto Transformer Energy Conversion 6

    21/38

    Electrical Energy Losses in Distribution

    Networks

  • 7/22/2019 Auto Transformer Energy Conversion 6

    22/38

    Transformer Taps & Voltage Regulation

    Distribution Transformers have a series taps in

    windings which permit small changes in turn

    ratio of transformer after leaving factory

    A typical distribution transformer has four taps

    in addition to nominal setting, each has a 2.5%

    of full load voltage with the adjacent tap

    This provides possibility for voltage adjustment

    below or above nominal setting by 5%

  • 7/22/2019 Auto Transformer Energy Conversion 6

    23/38

    Transformer Taps & Voltage

    Regulation

    Example: A 500 kVA, 13200/480 V distribution

    transformer has 4, 2.5 % taps on primary

    winding. What are voltage ratios?

    Five possible voltage ratings are:

    +5% tap 13860/480 V

    +2.5% tap 13530/480 V

    Nominal rating 13200/480 V

    -2.5% tap 12870/480 V

    -5% tap 12540/480 V

  • 7/22/2019 Auto Transformer Energy Conversion 6

    24/38

    Transformer Taps & Voltage Regulation

    Taps on transformer permit transformer to be adjustedin field to accommodate variations in tap voltages

    While this tap can not be changed when power isapplied to transformer

    Some times voltage varies widely with load, i.e. whenhigh line impedance exist between generators &particular load;while normal loads should be suppliedby an essentially constant voltage

    One solutionis using special transformer called: tapchanging under load transformer

    A voltage regulatoris a tap changing under loadtransformer with built-in voltage sensing circuitry thatautomatically changes taps to preserve systemvoltage constant

  • 7/22/2019 Auto Transformer Energy Conversion 6

    25/38

    AUTO TRANSFORMER

    some occasions it is desirable to changevoltage level only by a small amount

    i.e. may need to increase voltage from 110 to

    120 V or from 13.2 to 13.8 kV This may be due to small increase in voltage

    drop that occur in a power system with long

    lines In such cases it is very expensive to hire a two

    full winding transformer, however a specialtransformer called: auto-transformer can be

    used

  • 7/22/2019 Auto Transformer Energy Conversion 6

    26/38

    AUTO TRANSFORMER

    Diagram of a step-up auto-transformer shown in

    figure below:

    C: common, SE: series

  • 7/22/2019 Auto Transformer Energy Conversion 6

    27/38

    AUTO TRANSFORMER

    A step-down auto-transformer :

    IH=ISE IL=ISE+IC

  • 7/22/2019 Auto Transformer Energy Conversion 6

    28/38

    AUTO TRANSFORMER

    In step-up autotransformer:

    VC / VSE = NC / NSE (1)

    NC IC = NSE ISE (2)

    voltages in coils are related to terminal voltagesas follows:

    VL=VC (3)

    VH=VC+VSE (4)

    current in coils are related to terminal currents:

    IL=IC+ISE (5)

    IH=ISE (6)

  • 7/22/2019 Auto Transformer Energy Conversion 6

    29/38

    AUTO TRANSFORMER

    Voltage & Current Relations in Autotransformer

    VH=VC+VSE

    since VC/VSE=NC/NSE VH=VC+ NSE/NC . VC

    Noting that: VL=VC VH=VL+ NSE/NC . VL= (NSE+NC)/NC . VL

    VL/ VH = NC/ (NSE+NC) (7)

    Current relations:

    IL=IC+ISE employing Eq.(2) IC=(NSE / NC)ISE

    IL= (NSE / NC)ISE + ISE, since ISE=IH

    IL= (NSE / NC)IH +IH = (NSE + NC)/NC . IHIL/IH = (NSE + NC)/NC (8)

  • 7/22/2019 Auto Transformer Energy Conversion 6

    30/38

    AUTO TRANSFORMER

    Apparent Power Rating Advantage of Autotransformer

    Note :not all power transferring from primary to

    secondary in autotransformer pass through windings

    Therefore if a conventional transformer bereconnected as an autotransformer, it can handle

    much more power than its original rating

    The input apparent power to the step-up

    autotransformer is : Sin=VLIL

    And the output apparent power is:

    Sout=VH IH

  • 7/22/2019 Auto Transformer Energy Conversion 6

    31/38

    AUTO TRANSFORMER

    And :

    Sin=Sout=SIO

    Apparent power of transformer windings:

    SW= VCIC=VSE ISE This apparent power can be reformulated:

    SW= VCIC=VL(IL-IH) =VLIL-VLIH

    employing Eq.(8) SW= VLIL-VLIL NC/(NSE+NC)

    =VLIL [(NSE+NC)-NC]/(NSE+NC)=SIO NSE /(NSE+NC)

    SIO / SW = (NSE+NC) / NSE (9)

  • 7/22/2019 Auto Transformer Energy Conversion 6

    32/38

    AUTO TRANSFORMER

    Eq.(9); describes apparent power rating advantage of

    autotransformer over a conventional transformer

    smaller the series winding the greater the advantage

    Example one: A 5000 kVA autotransformer connectinga 110 kV system to a 138 kV system has an NC/NSE of

    110/28

    for this autotransformer actual winding rating is:

    SW=SIO NSE/(NSE+NC)=5000 x 28/ (28+110)=1015 kVA

    Example Two: A 100 VA 120/12 V transformer is

    connected as a step-up autotransformer, and primary

    voltage of 120 applied to transformer.

  • 7/22/2019 Auto Transformer Energy Conversion 6

    33/38

    AUTO TRANSFORMER

    (a) what is the secondary voltage of transformer

    (b) what is its maximum voltampere rating in this

    mode of operation

    (c) determine the rating advantage of this

    autotransformer connection over transformers

    rating of conventional 120/12 V operation

    Solution: NC/NSE= 120/12 (or 10:1)

    (a) using Eq.(7),VH= (12+120)/120 x 120 = 132 V

    (b)maximum VA rating 100 VA

    ISE,max=100/12=8.33 A

  • 7/22/2019 Auto Transformer Energy Conversion 6

    34/38

    AUTO TRANSFORMER

    Sout=VSIS=VHIH= 132 x 8.33 = 1100 VA = Sin(c) rating advantage:

    SIO/SW=(NSE+NC)/NSE=(12+120)/12=11 or:

    SIO/SW= 1100/100 = 11

    It is not normally possible to reconnect an ordinary transformeras an autotransformer due to the fact that insulation of L.V. sidemay not withstand full output voltage of autotransformerconnection

    Common practice: to use autotransformer when two voltages

    fairly close Also used as variable transformers, where L.V. tap moves up &

    down the winding

    Disadvantage:direct physical connection between primary &secondary circuits, and electrical isolation of two sides is lost

  • 7/22/2019 Auto Transformer Energy Conversion 6

    35/38

    AUTO TRANSFORMER

    Internal Impedance of an Autotransformer

    Another disadvantage: effective per unit

    impedance of an autotransformer w.r.t. the

    related conventional transformer is the

    reciprocal of power advantage

    This is a disadvantage where the series

    impedance is required to limit current flowsduring power system faults (S.C.)

  • 7/22/2019 Auto Transformer Energy Conversion 6

    36/38

    AUTO TRANSFORMER

    Example three:

    A transformer rated 1000 kVA, 12/1.2 kV, 60 Hz

    when used as a two winding conventionaltransformer and its series resistance &

    reactance are 1 and 8 percent per unit

    It is used as a 13.2/12 kV autotransformer

    (a) what is now the transformers rating ?

    (b) what is the transformers series impedance

    in per unit?

  • 7/22/2019 Auto Transformer Energy Conversion 6

    37/38

    AUTO TRANSFORMER

    Solution:

    (a) NC/NSE= 12/1.2 (or 10:1) the voltage ratio ofautotransformer is 13.2/12 kV & VA rating :

    SIO=(1+10)/1 x 1000 kVA=11000 kVA(b) transformers impedance in per-unit whenconnected as conventional transformer:

    Zeq=0.01 + j 0.08 puPower advantage of autotransformer is 11, soits per unit impedance would be:

    Zeq

    =(0.01+j0.08)/11=0.00091+j0.00727 pu

  • 7/22/2019 Auto Transformer Energy Conversion 6

    38/38

    Example of Variable Auto-Transformer