ashrae yea 091012

59
7/29/2019 Ashrae Yea 091012 http://slidepdf.com/reader/full/ashrae-yea-091012 1/59 Introduction To VRF: System Overview, Applications, & Savings Opportunities

Upload: motasem-nammora

Post on 03-Apr-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 1/59

IntroductionTo VRF:

SystemOverview,

Applications,

& Savings

Opportunities

Page 2: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 2/59

System System 

Overview Overview 

Page 3: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 3/59

What is VRF?

• Zoning System

• Two-Pipe / Three Pipe System

• Packaged DDC Control

• Operates as a Heat Pump

• Simultaneous Cooling & Heating

• Inverter Technology / Variable Speed

Compressor

• Multiple Indoor Units – Up to 50 Indoor

Units Per System

• Connected Diversity – Up to 150%

• Variable Capacity Indoor Units

• EMS / BMS Compatibility

• High Turn Down Ratios – Below 10% In

Many Cases

Variable

Refrigerant

Flow

Page 4: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 4/59

INVERTER Technology

Changes electrical frequency from 60 Hz (line Power) to a varyingrange (10 Hertz to 110 Hertz – depending on the system)

Page 5: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 5/59

INVERTER Technology

Time

   R  o  o  m    T  e  m  p  e  r  a   t  u

  r  e

Automatically adjusts compressor speed to meet load

Sizing flexibility with variable capacity Strives to run long periods at lower speeds.

• Reduced / eliminated cyclic losses

Improved temperature control

• No more minimum cycle timers – no temperature

overshoot.

VRFVRF

     V     R     F

SETPOINT

CONVENTIONALCONVENTIONAL

Page 6: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 6/59

AHRI Standard 1230 – VRF HAS ARRIVED !

3.27 VRF Multi-Split System . A split system air-conditioner or heat

pump incorporating a single refrigerant circuit, with one or

more outdoor units, at least one variable speed compressor or

an alternative compressor combination for varying the capacityof the system by three or more steps, multiple indoor fan coil

units, each of which is individually metered and individually

controlled by a proprietary control device and common

communications network. The system shall be capable ofoperating either as an air conditioner or a heat pump. Variable

refrigerant flow implies three or more steps of control on

common, inter-connecting piping.

Page 7: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 7/59

The Evolution VRF

Example (Mitsubishi City Multi):

Japan 20+ Years, Tried and Proven! Europe 15+ Years, depending on the country

Latin America 10+ Years, from Mitsubishi US

Bermuda 10+ Years

USA since 2002!

Page 8: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 8/59

Simultaneous Systems Components

OUTDOORUNIT

RemoteControllers+

BC / BranchCONTROLLER +

INDOORUNITS+

or 

WATER-SOURCE UNIT

Page 9: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 9/59

Typical Simultaneous 2-Pipe VRF System Layout

Page 10: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 10/59

Changeover Systems Components

OUTDOORUNIT

CONTROLS+INDOORUNITS+

or 

WATER-SOURCE UNIT

Page 11: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 11/59

Typical Changeover VRF Systems Layout

COOLING

HEATING

Page 12: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 12/59

Power Supply

Controls Example

Central Controllers

Power Supply

TG-2000LAN

Hub

TG-2000

PCControl

Remote Controllers

Page 13: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 13/59

Building Management System (BMS)

Hub

Ethernet

LonTalk

Central Controller

BACnet

Building Management Systems

May Be AHardwareInterface

Page 14: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 14/59

Applications Applications & System & System 

Capabilities Capabilities 

Page 15: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 15/59

Target Commercial Applications

Buildings wherezoning is required

Applications where sound is important

HistoricRenovations

Multi-Story Office Buildings

Hotels

Banks

Universities

Churches

Page 16: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 16/59

SEACOAST PROTECTION

Hospital Admin Areas /MOB – Non Procedure

RESIDENTIAL

BANKS

Additional Applications

Page 17: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 17/59

Building UseOccupant LoadSolar Load

Cooling Diversity – 3 Types

Page 18: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 18/59

VRF Excels at Heat Recovery Applications !

Typical Winter Loads

Heat

CHILLER,COOLINGTOWER, &PUMPS

H  e a  t   BOILER& PUMPS

$

$

Why SpendMoney On

Both?

   H  e

  a   t

Page 19: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 19/59

BTU/$ - VRF Makes Good Sense !

Page 20: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 20/59

Diversity - Heating

Minimal Diversity Available ! 

Ambient Modification Charts• Available capacity decreases

• Both outdoor and indoor units de-rated• Defrost Operation

Evaluation of De-ratings Important!• Use tools available from VRF manufacturer to

accurately access de-ratings.

Auxiliary Heating Changeover Point• Try and maximize heat pump hours – depends on

climate.Columbus Ohio:

90% of heating hours above 25 Deg F based onHourly Average Weather Data.

Evaluation of De-ratings Important !• Use tools available from VRF manufacturer to

accurately access de-ratings.

Page 21: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 21/59

Typical Range Of Available VRF Systems

Air Cooled6 – 24 Ton (Simultaneous)

6 – 30 Ton (Change Over)

208/230, 460 Volt – 3 Phase

62 dB(A) Operating Sound Level

Water Cooled6 – 20 Ton (Simultaneous)

6 – 30 Ton (Change Over)

208/230, 460 Volt – 3 Phase

Single Phase3, 4 Ton (Change Over)

208/230, 1 - Phase

Page 22: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 22/59

Partial Backup capability with multiple / twinned units.

The remaining one or two units will perform backup operation

Twinned Units Typically Required above 12 Tons

Partial Back-up Operation

Page 23: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 23/59

Typical Outdoor Temperature Operating Range

Cooling – Can be extended with low ambient options (as low as -10 F) 

-20

-4

-15

5

-10

14

-5

23

0

32

5

41

10

50

15

59

20

68

25

77

30

86

35

95

40

104

45

113

50

122

oCDB

oFDB

Heating 

-24

-13

-13

-10

-20

-4

-15

5

-10

14

-5

23

0

32

5

41

10

50

15

59

20

68

25

77

30

86

35

95

40

104

oCWB

oFWB

Outdoor Temperature

Outdoor Temperature

115 F23 F Single Phase – Air Cooled

23 F Simultaneous & Changeover – Air Cooled 115 F

23 F 115 FExtended Heat Capacity – Air Cooled

Single Phase – Air Cooled0 F 60 F

Simultaneous & Changeover – Air Cooled-4 F 60 F

Extended Heat Capacity – Air Cooled 60 F-13 F

NOT your typical Heat Pump Technology !

Page 24: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 24/59

Extended Range Heat Pump Technology

70 o F 

entering 

air temp 

Not Your Typical Heat Pump ! 

20 

40 

60 

80 

100 

120 

-13 -4 5 17 25 30 35 40 47  

Outdoor Temperature o FWB 

   %   H  e  a   t   i  n  g   C  a  p  a  c   i   t  y

Extended Rang VRF  Standard VRF 

100% 

87% 

75% 

50% 

Page 25: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 25/59

Water-source VRF Units - Changeover Systems

Heat Recovery In Water Loop Only Heat Recovery In Water Loop Only 

Water Circuit 

System System “ “ AA” ”  in in 

COOLING Mode COOLING Mode (refrigerant (refrigerant 

absorbing heat) absorbing heat) 

Heat is 

recovered 

between the 

units within 

the water loop 

System System “ “ B B ” ”  in in 

HEATING Mode HEATING Mode 

(refrigerant (refrigerant 

discharging heat) discharging heat) 

PQHY Unit “A” 

PQHY 

Unit “B” 

Cooling

Cooling

Cooling

Cooling

Heating

Heating

Heating

Heating

Page 26: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 26/59

Water-source VRF Units – Simultaneous Systems

Heat Recovery In Two Locations

Indoor unitsIndoor units

Water circuit 

Indoor unitsIndoor unitsHeat recovery

Heat recovery

Cooling

Cooling

Cooling

Cooling

Heating

Heating

Heating

Heating

PQRY 

PQRY 

Heat is recovered 

between the units within 

the water 

loop 

Page 27: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 27/59

Directly Coupled to a 

Lake or Pond Open Loop 

NO

NO

Directly Coupled to 

Ground water Open Loop 

Water-source VRF Units

Installations not allowed! NO

Page 28: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 28/59

Heat ExchangerIsolation

Coupled to a Lake or Pond 

Closed Loop 

HX

YES Heat ExchangerIsolation

Coupled to Ground Water 

Closed Loop 

HX

YES

Water-source VRF Units

Installations allowed YES

Page 29: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 29/59

Closed Piping

Loop

Coupled to Earth 

Vertical Closed Loop 

YES

Closed Piping Loop

Coupled to Earth 

Horizontal Closed Loop 

YES

Water-source VRF Units

Installations allowed YES

Page 30: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 30/59

Indoor Indoor Equipment Equipment 

Flexibility Flexibility 

Page 31: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 31/59

Indoor Unit Flexibility

Multiple styles ranging from 6,000 to 96,000 Btu/h

Typically single phase below 6 Nominal Tons

Linear Expansion Valve

Variable Capacity Operation

Mode: Fan,Fan, Cool,Cool, Dry,Dry, AutoAuto, HeatHeat

Built in or accessory condensate removal options from factory.

Typical Ventilation Air options – most models

Average operating sound levels around 35 dB(A) +/-

Page 32: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 32/59

Wall Mounted6 - 30 MBtu/h

Ceiling Suspended15 - 36 MBtu/h

Floor Standing6 – 24 MBtu/h

Product Review CITY MULTI VRF

Indoor Unit Flexibility

Page 33: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 33/59

4 – Way Large Cassette

12 - 36 MBtu/h

4 - Way Small Cassette

8 – 15 Mbtu/h

One Way Cassette6 – 15 Mbtu/h

Product Review CITY MULTI VRF

Indoor Unit Flexibility

Page 34: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 34/59

Enhanced air distribution by

independent vane settings

Independent Vane Control 

Vanes can be independently adjustedby a remote controller

Fixed

Horizontal

Air Vanes – 4 Way Cassettes

Page 35: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 35/59

Medium Static6 – 54 Mbth/h

High Static

15 – 96 Mbtu/h

Low Profile

15 – 24 Mbtu/h

Vertical Ducted12 – 54 Mbtu/h

Product Review CITY MULTI VRF

Indoor Unit Flexibility – Ducted Units

Page 36: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 36/59

Recessed Unit – St. Xavier Cathedral

Page 37: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 37/59

Refrigerant Refrigerant 

Piping & Piping & Refrigerant Refrigerant 

Leakage Leakage 

Page 38: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 38/59

Refrigerant Piping Flexibility – 2 Pipe Example

393 ft.984 ft.-

1640 ft.3,280 ft.1,804 ft.-2,460 ft.1,804 ft.-2,625 ft.Total Piping Length

PIPING LENGTH`

SimultaneousAir Cooled

2-Pipe

SimultaneousWater Cooled

2-Pipe

Changeover

Air Cooled

2-Pipe

Changeover

Water Cooled

2-Pipe

SinglePhase Air

Cooled

Farthest Indoor unit 541 ft. 541 ft. 541 ft. 541 ft. 262 ft.

PIPING HEIGHT

Simultaneous Air& Water Cooled

2-Pipe

Changeover Air &Water Cooled

2-Pipe

SinglePhase Air

cooled

Outdoor Unit HIGHER than Indoor Unit 164 ft.* 98 ft.

Outdoor Unit LOWER than Indoor Unit 131 ft. 65 ft.

Indoor Unit to Any BC Controller 49 ft. n/a n/a

Page 39: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 39/59

Two Pipe Example

• Soft Copper BC to IU

• Reducers possible at BC

• Soft Copper BC to IU

• Reducers possible at BC

12 indoor-unit system – Heat Recovery12 indoor-unit system – Heat Recovery

Page 40: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 40/59

Three Pipe Example

• Hard copper from OU toBS

• Reducer fittings

• Hard copper from OU toBS

• Reducer fittings

12 indoor-unit system – Heat Recovery12 indoor-unit system – Heat Recovery

Page 41: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 41/59

Refrigerant Leakage Concentration Levels

What is RCL?

Refrigerant Concentration Limit (RCL): “the refrigerant concentration limit, in air, determined in accordance with this 

standard and intended to reduce the risks of acute toxicity asphyxiation and flammability hazards in normally occupied,enclosed spaces” 

RCL typically expressed as lbs/1000 ft3

D t i ti f RCL

Page 42: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 42/59

Determination of RCL

Referenced Codes/Standards International Mechanical Code

• Previously set RCL for R-410A at 10 lbs/MCF• 2009 Revisions raises RCL to 25 lbs/MCF

ISO-5149

• ISO-5149 sets R-410A RCL as 18.7 lbs/MCF

ASHRAE 15-2007• ASHRAE 15-2007 establishes the R-410A RCL as 25lbs/MCF

through reference to ASHRAE 34.

Page 43: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 43/59

Critical Concentration Calculation

RCL (R410A) = 25 lb./McfRefrigerant Charge (Rc) of a P72 = 23 lbs 3 oz = 23.1875 lbs

MAV = Minimum Applied Volume (cubic feet)MAV = Rc/RCL

MAV = (23.1875 lbs)/(25 lbs/1000 cu ft)MAV = 927.5 cu ft

Page 44: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 44/59

Appropriate Solutions

Option 1-Locate Equipment within larger space

•Ducted communicating spaces w/ no closure devices that restrictairflow below 10% of peak airflow.

Option 2-Do not use equipment with refrigerant

Option 3-Increase room volume through the use of openings

•Door Undercuts, transfer ducts or grilles.

Option 1Option 2

Option 3

Page 45: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 45/59

• Inverter-driven compressors / part load 

performance ! 

• Variable 

capacity indoor units ! 

• Extended Heat Pump (Air to Air) 

Capability ! 

• Simultaneous cooling and 

heating ! 

The Efficiencies from “VRF System Effect” 

S f R f i t M t

Page 46: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 46/59

Summary of Refrigerant Management

Refrigerant Concentration Limit is a tool to protectthe public

Informed and educated engineers can incorporatenecessary measures to meet the RCL.

R410A is of lowest toxicity and is NOT combustible.

Page 47: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 47/59

Energy Standards Energy Standards 

& Savings & Savings 

AHRI 1230 & IEER

Page 48: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 48/59

AHRI 1230 & IEER

AHRI Standard 1230 created a testing standard for VRF equipment above 65,000Btu/h (below 65,000 Btu/h continues to be rated in accordance with AHRI Standard210/240-2008)

On January 1st, 2010, IEER superseded IPLV as the testing standard for VRFequipment above 65,000 Btu/h

Unlike testing VRF for IPLV (according to AHRI Standard 210/240), testing for IEERinvolves actual testing at part load conditions and assigning weighted values to eachtest point

Testing VRF for IEER involves testing at four fixed conditions: 100%, 75%,50%, & 25% load. The equipment is still not allowed to vary compressor speedand indoor unit capacity to meet a varying load as it was designed to do

Simultaneous Heating and Cooling Efficiency (Not Yet Tested)

SCHE = (Heating Capacity (Btu/h) + Cooling Capacity (Btu/h)) / Total System PowerInput (Watts)

ASHRAE 90 1 2010 VRF B h k

Page 49: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 49/59

ASHRAE 90.1-2010 VRF Benchmarks

ASHRAE 90 1 2010 VRF B h k

Page 50: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 50/59

ASHRAE 90.1-2010 VRF Benchmarks

Energy Star Requirements

Page 51: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 51/59

Energy Star Requirements

Energy Modeling

Page 52: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 52/59

Energy Modeling

EnergyPro Version 5.0

Accepted by the USGBC forCompliance with Energy and

Atmosphere Credit 1

What Makes Energy Pro Different

Page 53: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 53/59

Sample Building in Part Load: OA Temp 50oF

Simultaneous Load:

Cooling: 27000 BTU

Heating: 21000 BTU

3000 BTU

6000 BTU

3000 BTU

3000 BTU

3000 BTU

Elect

Janitor

Break RoomLobby/ 

Waiting Room

Conference

Room

Office #1 Office #2

Cubicle Area

Open Work 

Room

6000 BTU

12000 BTU

6000 BTU

3000 BTU

3000 BTU

WomenMen

PURY-P72

What Makes Energy Pro Different

What Makes Energy Pro Different

Page 54: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 54/59

What Makes Energy Pro Different

Cooling Power Input PURY-P72

0.00

1.00

2.00

3.00

4.00

5.00

6.00

7.00

0 12000 24000 36000 48000 60000 72000 84000

System Load BTUH

   P  o  w  e  r   I  n  p

  u   t   K   W

72,000 BTUH6.48 KW

27,000 BTUH2.38 KW

What Makes Energy Pro Different

Page 55: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 55/59

What Makes Energy Pro Different

Outdoor Temperature Power Input Correction

(For a 68 Indoor WB Temperature)

1.5000

1.6000

1.7000

1.8000

1.9000

2.0000

2.1000

2.2000

2.3000

2.4000

0 10 20 30 40 50 60 70 80 90 100

OA Temperature FDB

   P   o   w   e   r   I   n   p   u   t   K   W

2.38 KW at 95oF

1.87 KW at 50oF

What does this mean

Page 56: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 56/59

What does this mean

Getting 27,000 BTUH of cooling and 21,000 BTUH ofheating, while providing only 1.87 KW to the outdoorunit.

This savings cannot be realized without the ability tomodel simultaneous heating and cooling.

For this scenario,Calculated Efficiency of 25.7 EER

School Energy Modeling Results

Page 57: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 57/59

School Energy Modeling Results

School--Percentage Energy Cost Savings V/S Comparable Systems

0% 4% 7% 11% 14% 18% 21% 25% 28% 32%

Atlanta

Miami

Boston

NYC

Chicago

Dallas

LA

Seattle

   L  o  c  a   t   i  o  n

Energy Savings

CM v/s VAV

CM v/s 4 Pipe

CM v/s WSHP

Office Building Energy Modeling Results

Page 58: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 58/59

Office Building Energy Modeling Results

Percentage Energy Savings V/S Comparable Systems

0% 4% 7% 11% 14% 18% 21% 25%

Atlanta

Miami

Boston

NYC

Chicago

Dallas

LA

Seattle

   L  o  c  a   t   i  o  n

Energy Savings

CM v/s 4 Pipe

CM v/s VAVCM v/s WSHP

Questions & Answers

Page 59: Ashrae Yea 091012

7/29/2019 Ashrae Yea 091012

http://slidepdf.com/reader/full/ashrae-yea-091012 59/59

Questions & Answers

Thank You For Having UsToday!

We Are Here To Help Make Your VRFProjects Successful !