ASHRAEStandard189.1,“StandardfortheDesignofHighPerformanceGreen
BuildingsExceptLow-RiseResidentialBuildings”
DouglasFZentzAssociateProfessorHVACRProgramChairFerrisStateUniversity
![Page 2: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/2.jpg)
Reminders
• Cellphones– pleasesilence
• Commercialism– ASHRAEobservance!
• Pleasefilloutthesurveys
• MyviewsandnotASHRAE’s
![Page 3: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/3.jpg)
PresentationOverview
•Whyhaveit?
•Whatisit?
• Suggestions
![Page 4: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/4.jpg)
TotalEnergyConsumption
![Page 5: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/5.jpg)
BuildingsRepresent
• 17%offreshwaterconsumption• 25%ofwoodconsumption• 33%ofCO2 emissions• 30%ofwastegeneration• 55%ofnaturalgasuse• 72%ofelectricalenergyuse
![Page 6: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/6.jpg)
BuildingEnergyUseGrowth
![Page 7: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/7.jpg)
ProjectedWorldEnergySupply
![Page 8: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/8.jpg)
IPCCData
![Page 9: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/9.jpg)
![Page 10: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/10.jpg)
Austria
England & Wales
Greece
Italy
RelationshiptoOtherPrograms• Europe
– StandardEN15217Energyperformanceofbuildings—methodsforexpressingenergyperformanceandforenergycertificationofbuildings(2007)
– ExplicitefforttolearnfromEUexperience
![Page 11: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/11.jpg)
![Page 12: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/12.jpg)
Standard189.1
![Page 13: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/13.jpg)
Standard189.1RelationshiptoOtherStandards
• ASHRAE
• BuiltontheLEEDFoundation
![Page 14: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/14.jpg)
Whatisit?
• Standard189.1PublishedJanuary2009
• Updatedin2011&2014&2017
![Page 15: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/15.jpg)
Sponsors• USGBCwithitsaffiliatedmembershipincluding6,000corporations,federalagencies,stateandlocalgovernment,etc
• IESastheauthorityonilluminationwithover100yearsofexperience,publicationandservice
• ASHRAEwithitsglobalresources,publications,continuingeducationthatcontinuetoservethepublic
• ICC–agreementtomergewithIGCC
![Page 16: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/16.jpg)
Standard189.1Intent
• Whatitis;– Astandard– Appliestoallbuildingsexceptlow-riseresidential(sameasStandard90.1)
– Intendedforadoptionintomodelbuildingcodes
• Whatisnot;– Notadesignguide– Notaratingsystem
• Note:evenifnotadoptedbylocalauthoritiesthisstandardservesasindicationoffuturetrends
![Page 17: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/17.jpg)
Purpose• Thepurposeofthisstandardistoprovideminimumrequirementsforthesite,design,construction,andplansforoperation ofhighperformance,greenbuildingsto:– Balance environmentalresponsibility,resourceefficiency,occupantcomfortandwellbeingandcommunitysensitivity,and
– Supportthegoalofdevelopmentthatmeetstheneedofthepresentwithoutcompromising theabilityoffuturegenerationstomeettheirownneeds
![Page 18: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/18.jpg)
Scope
• ProvidesMinimumCriteriathat:–Applyto:• Newbuildingsandtheirneeds• Newportionsofbuildingsandtheirsystems• Newsystemsandequipmentinexistingbuildings
–Addressessitesustainability,wateruseefficiency,IEQ,andthebuilding’simpactonatmosphere,materialsandresources
![Page 19: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/19.jpg)
WhatitCovers
![Page 20: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/20.jpg)
BasicStructure(foreachsection)
• X.1– Scope• X.2– Compliance• X.3– Mandatory– (requiredforallprojects)
• X.4– Prescriptive(option1)– Simpleoption,fewchoices,andveryfewcalculations
• X.5– Performance(option2)–Moresophisticated,flexible,butmoreeffort
![Page 21: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/21.jpg)
Chapter5SustainableSites
• MandatoryProvisions– SiteHardscape(minimumsrequirements– someexceptions)
–Wallstobeshadedupto20feet(6meters)abovegrade
– Roofs(minimumrequirementsforsloping– someexceptions)
![Page 22: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/22.jpg)
Chapter5SustainableSites
• Mandatoryprovisions– Reductionoflightpollution
• Totalsitelumenlimit
• MaxBUGlimit(Backlight,UplightandGlare)ratings
• ModificationstoStandard90.1exteriorlighting
![Page 23: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/23.jpg)
Chapter6– WaterUse
• MandatoryProvisionsofsitewateruse– Bio-diverseplantings,hydro-zoningandsmartirrigationcontrol
![Page 24: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/24.jpg)
Chapter6– WaterUse• Mandatoryprovisionsforbuildingwateruse– PlumbingfittingsandfixturesperU.S.EPAWaterSenseorASMEStandards
– AppliancesperU.S.EPAEnergyStar–Watermetering(must)• >1,000gal(3,785Liters)/day
![Page 25: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/25.jpg)
Chapter6– WaterUse
• MandatoryprovisionsforHVACsystems– Subsystemmeteringabovethresholds
– Coolingtowerlimitationsondriftwaterlose
– Condensationcollectionforunits>19kW(65,000Btu/h)for≥72F(22C)meanwetbulb
![Page 26: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/26.jpg)
Chapter6– WaterUse• Metering
![Page 27: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/27.jpg)
Chapter7Energy
• Generalhighlights– Goalis30%betterthanASHRAE90.1-2016(includingprocessloads)
– AppendixGfromStandard90.1isincorporatedasNormativeAppendix
–Meteringforverification– Peakloadreduction– OtherareasareincreasedstringencybeyondStandard90.1
![Page 28: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/28.jpg)
Chapter7Energy• MandatoryRequirementsforon-siterenewablepower– Provisionsforfutureinstallationwithminimumratingof6.0Btu/ft2 xroofareainft2 (singlestory)&10.0Btu/ft2 xroofareainft2 (multi-story)
– Exceptions(lowincidentsolarorpurchaseGreenPower)
![Page 29: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/29.jpg)
Chapter7Energy• MandatoryRequirementsforMeters
– Remoteorautomaticreading(basedoncriteriaofsize,energysource&system)
–Meterscommunicatetocentralrecordingsystem
– Datastoragefor36months
![Page 30: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/30.jpg)
Chapter7Energy
![Page 31: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/31.jpg)
Chapter7Energy
• PrescriptivePath– Setofitemsclearlylaidout
–MustcomplywithALL
• PerformancePath–Mustproveperformance
![Page 32: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/32.jpg)
Chapter7Energy
• PrescriptivePath– RenewableEnergy
• Onsitesystemsminimumequaltomandatorylevels
• Exceptions
– Lowincidentsolarregions
– PurchaseofGreenpowerintermsof7kWh/ft2-yr(ofconditionedspace)untilatotalof70kWh/ft2 isobtained
![Page 33: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/33.jpg)
Chapter7Energy• PrescriptiveOptionforBuildingEnvelope– Section7.4.2generallyhasstringentrequirements– ReplacesTables5.5-1thru8inStandard90.1
![Page 34: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/34.jpg)
Chapter7Energy• PrescriptiveOptionforBuildingEnvelope– FenestrationOverhangPF>0.5
– Orientationtominimizesolar• East/West<North/South
– PermanentprojectionsinClimateZones1- 5
![Page 35: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/35.jpg)
Chapter7Energy• PrescriptiveOptionforBuildingEnvelope– SHGCmultipliers(differentthenStandard90.1)
![Page 36: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/36.jpg)
Chapter7Energy
• PrescriptiveOptionforHVAC– DemandControlledVentilationrequirements
• SpaceCO2 sensing– oneevery10,000ft2 (1,000m2)
• Sensingaccurateto50ppm(plusorminus)forevery1,000ppm
• Determinedby;
– OutdoorAirreferencebenchmarking
– Designassumptionsforoccupants
![Page 37: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/37.jpg)
Chapter7Energy• PrescriptiveOptionforHVAC– DuctSealinglevelAeverywhere
– ExpandedEconomizerUsage
– Newforrooftops<5tons(economizerthenmechanicalcooling)
– VAVsupplyairtempresetbyatleast5F
![Page 38: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/38.jpg)
Chapter7Energy
• PrescriptiveOptionforHVAC– Zonecontrolsforlimitonreheat
• Reheated,re-cooledorremixednottoexceedDesignOAairflowrateor
– FanPowerLimits– 10%lessthanStd90.1
![Page 39: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/39.jpg)
Chapter7Energy
• PrescriptiveOptionforHVAC– Expandedheatrecovery
– 60%energyrecoveryeffectiveness(enthalpy)
![Page 40: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/40.jpg)
Chapter7Energy
• PrescriptiveOptionforPower
– Peakfactor/peakloadreduction
– Reducepeakcapacityofthebuildingthroughdemandlimitingorloadshiftingmeasures(10%)
![Page 41: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/41.jpg)
Chapter7Energy
• PrescriptiveOptionforLighting– InteriorlightingtouseStandard90.1andapply“LightingPowerAllowance”
– Areafactorsavailableforcustomizedapproach
![Page 42: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/42.jpg)
Chapter7Energy
• PrescriptiveOptionforLighting– Occupancysensorcontroltoreducepowertolessthan50%for:• Hotel/Motelhallways• Storageaisles• Librarystacks
– Egresslightingcontrol• <0.1w/ft2continuouswithautoshut-offcontrol
– AutoControlwithNaturalLightingIntegration
![Page 43: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/43.jpg)
Chapter7Energy
• PerformanceBasedOption– DemonstrateequivalentperformanceinBothenergycostandCO2 equivalentcomparedtousingtheprescriptivepath
![Page 44: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/44.jpg)
Chapter7Energy
• PerformanceBasedOption– CO2 EquivalentComparedtoBuildingDesignwithPrescriptivePath
– Uselocalutilityinformation
– Takesiteenergytogetsourceemissions
![Page 45: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/45.jpg)
Chapter8- IEQ
• MandatoryitemsforIndoorEnvironmentalQuality– OutdoorAirflow– TobaccoSmokeControl– OutdoorAirMonitoring– FiltrationandAirCleaning
![Page 46: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/46.jpg)
Chapter8- IEQ
• Section8.3.1.4– TobaccoSmokeControl– Nosmokinginside
– Nosmokingwith25feetofentrances,outdoorairintakesoroperablewindows
![Page 47: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/47.jpg)
Chapter8- IEQ
• MandatoryRequirementonThermalComfort
– ComplywithStandard55
![Page 48: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/48.jpg)
Chapter8- IEQ
• Mandatory- BuildingEntrancesmustemployaMatSystemtocontrolcontaminants(someexceptions)
– Scraperarea
– Absorptionsurface
– Finishedsurface
![Page 49: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/49.jpg)
Chapter8- IEQ
• OtherMandatory– Daylightingbytoplightingforlargeopenofficeareas>20,000ft2 &ceiling>15ft&minimumlightingpowerof0.5watts/ft2
![Page 50: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/50.jpg)
Chapter8- IEQ
• PrescriptiveOption– Sidedaylighting(8.4)• Officesandclassrooms• Effectiveaperture• Visiblereflectanceofinteriorsurfaces• Someexceptions
![Page 51: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/51.jpg)
Chapter8- IEQ
• PrescriptiveOption– Officespaceshadingwithprojectionsorothertechniques
– LowEmittingMaterials• Adhesives&sealants• Paints&coatings• Floorcovering• Compositewoodandotherproducts
![Page 52: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/52.jpg)
Chapter9– Building’sImpactonAtmosphere,Materials&Resources
• MandatoryKeystoASHRAE– ConstructionWaste• Maxof5%oftotalprojectmaterials• Minimum50%ofnon-hazardousmaterialstoberecycledorreused• Limitontotalwasteperfloorarea• Off-sitestorageandsortingisallowed
![Page 53: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/53.jpg)
Chapter9– Building’sImpactonAtmosphere,Materials&Resources
• OtherMandatoryItems
– Storageandcollectionofrecyclablematerials
– Discardedfluorescentlampsandballasts
![Page 54: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/54.jpg)
Chapter10– Construction&OperationPlans
• Section10.3.1.1– BuildingAcceptanceTesting– Activitiespriortopermitandpriortooccupancy
– Designaterepresentativetooversee
– Constructiondocumentsindicatewhodoeswhat
– Includesmechanicalsystems,lighting,renewableenergy,energyandwatermeteringdevices
![Page 55: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/55.jpg)
Chapter10– Construction&OperationPlans
• Section10.3.1.2– BuildingProjectCommissioning– Fullcommissioningfor>5,000ft2
– IncludeHVAC,buildingenvelope,lighting,irrigation,plumbing,domesticwater,renewableenergy
– DesignReviewsat50%andFinal– Verifyinstallation,operationandtraining
![Page 56: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/56.jpg)
Chapter10– Construction&OperationPlans
• Section10.3.1.3ErosionControl– DevelopandimplementanErosionandSedimentcontrolplanforallconstructionactivities
![Page 57: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/57.jpg)
Chapter10– Construction&OperationPlans
• Section10.3.1.4– IAQConstructionManagement– DevelopandmanageanIAQConstructionManagementprogramplantoinclude:• Airconveyancematerialsshallnotbeusedduringconstruction• PermanentHVACnotusedduringconstruction,exceptforstart-uptesting• Flush-outorbaselineIAQmonitoring
![Page 58: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/58.jpg)
Chapter10– Construction&OperationPlans
![Page 59: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/59.jpg)
Chapter10– Construction&OperationPlans
• Section10.3.2.1.1– SiteSustainability– Includemaintenanceproceduresneededtomaintainhealthyvegetationgrowthforvegetationusedforshadingcompliance
![Page 60: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/60.jpg)
Chapter10– Construction&OperationPlans
• WaterUseEfficiency– Initialmeasurementandverification(M&V)– Procedurestotrackuse– Assesswateruseefficiency,document
![Page 61: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/61.jpg)
Chapter10– Construction&OperationPlans
• EnergyEfficiency– Initialmeasurementandverification(M&V)– Procedurestotrackandassessenergy• Hourlyloadprofile
• Monthlyaveragedailyload
• Monthlyandannualenergyuse
• Monthlyandannualpeakdemand
![Page 62: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/62.jpg)
Chapter10– Construction&OperationPlans
• IndoorEnvironmentalQuality– Outdoorairflowmeasurement,schedulinganddocumentation
– Indoorairqualityassessment– Greencleaning
• MaintenancePlan–Mechanical,electricalperStandard180– Documentation
![Page 63: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/63.jpg)
Chapter10– Construction&OperationPlans
• BuildingServiceLifePlan
![Page 64: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/64.jpg)
MyThoughts
• Suggestions
• UsingStandard189toyouradvantage
• ThinkingaboutthePyramid
![Page 65: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/65.jpg)
Mysuggestions
• GetTeam“Buy-in”and“OwnerSupport”
• Earlydecisionsinfluenceeveryone
• LookatBuildingOrientation,BuildingExteriorFeatures,andBuildingSiterequirements
• CreatetheRoadmapfortheBuildingOwnerCreatetheBOP(BuildingOperationalPlan)
![Page 66: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/66.jpg)
UsingStandard189
• Useallofthetools(criteria)toanalyzethe“BestHVACSystem”forthebuilding– Sitedevelopment–Watermanagement– EnergyManagement– IndoorEnvironmentalQuality– SustainablePractices– AndTrueLifeCycleCost(useinputfromowner)
![Page 67: ASHRAE Standard 189.1, “Standard for the Design of High ... · •Section 10.3.1.2 –Building Project Commissioning –Full commissioning for >5,000 ft2 –Include HVAC, building](https://reader035.vdocuments.us/reader035/viewer/2022062402/5fbd852bb8eae221096ea248/html5/thumbnails/67.jpg)
UpsideDownPyramid