Ascotherm ® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 29 Ascotherm eco KRN81 Tender specification, range available and sizes Operating principle Cooled air is drawn in and trans- ported through the heat exchanger. Heated air rises. Installation in front of window areas provides a specific shielding against cold air. For more information, see chapter "General information". Tender specification Version KRN81 forced convection with cross-flow fan Ready-to-install floor pans for the floor area. Operating princi- ple: Forced convection with cross-flow fan. Sturdy floor pan made of galvanised sheet steel, coloured in anthracite grey (RAL 7016), external, adjustable and acoustically decoupled height adjustments (pre-installed). Heat register of copper pipes and aluminium fins, anthracite grey (RAL7016) coated and mounted in transversal steel girder of galvanised sheet steel, acoustically decoupled. Standard to the face or room-side euro taper connection with union nut ( 3 / 4 “ internal thread) and air vent. Suitable for a max. operating pressure of 10 bar (optionally 16 bar) and a max. operating temperature of 90 °C. Cross-flow fan already installed in the floor pan parallel to the heat register to boost the convection effect (cross-flow fan on room side). Protective cover over the cross-flow fan. Cross-flow fan with energy-saving EC motors 24 V, wired ready for connection. Low-noise fan operation, infinitely variable via analogue interface (0 – 10 V). Actuator control pulse 24 V DC, infinitely variable via analogue interface (0 – 10 V). Synchronised control of fan speed and water flow for a hydraulically balanced pipe system and especially energy-efficient operation while maintai- ning a minimum spread between flow and return temperature. Factory configuration of appropriate control algorithm. Aluminium linear grille as standard. Acoustic decoupling through placement of the aluminium linear grille on rubber elements in the floor pan. Consisting of sturdy longitudinal profiles, natural colour anodised, with profile bar dimensions of 16 x 6 mm. Grille with a total height of 20 mm and an open cross-section of 60%. Including installation cover and edge bar protection for protec- tion of the trench convectors during the construction phase. QA system certified to DIN EN ISO 9001:2008. Environmental management system to DIN EN ISO 14001:2004. Operating conditions: Hot water up to 90 °C Operating pressure: Max. 10 bar (optionally 16 bar high-pres- sure-version) Test pressure: 13 bar (21 bar) General Trench convectors find application in private residential areas, in conservatories, in offices and administration buildings, in show- rooms as well as in business areas. Version KRN81 forced convection with cross-flow fan Connections: 2 x euro taper with union nut ( 3 / 4 “ internal thread), suitable for use with all fittings that comply with DIN V 3838 Air vent: installed Range available 5 depths: 185, 210, 260, 310 and 360 mm 1 height: 110 mm 12 lengths: – 1250 mm to 4000 mm – Grading 250 mm Standard: Aluminium linear grille Surface finishes Standard colour of floor pan, powder-coated: Anthracite grey (RAL7016 matt finish) Standard colour of linear grille: Aluminium anodised in natural colour Standard colour of edge bar corresponding to colour of cover grille Accessories Programmable room thermostat Thermoelectric actuator 24 V DC Connection set, consisting of valve base with factory preset k V valve and return fitting with shut-off Air-intake filter For additional accessories and information about accessories, see "Accessories".

Upload: others

Post on 15-Mar-2020

9 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® eco KRN81Forced convection with cross-flow fan

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 29

Asc

othe

rm e

co

KRN

81

Tender specification, range available and sizes

Operating principle

Cooled air is drawn in and trans-ported through the heat exchanger. Heated air rises.

Installation in front of window areas provides a specific shielding against cold air.

For more information, see chapter "General information".

Tender specification

Version KRN81 forced convection with cross-flow fan

Ready-to-install floor pans for the floor area. Operating princi-ple: Forced convection with cross-flow fan.

Sturdy floor pan made of galvanised sheet steel, coloured in anthracite grey (RAL 7016), external, adjustable and acoustically decoupled height adjustments (pre-installed).

Heat register of copper pipes and aluminium fins, anthracite grey (RAL7016) coated and mounted in transversal steel girder of galvanised sheet steel, acoustically decoupled.

Standard to the face or room-side euro taper connection with union nut (3/4“ internal thread) and air vent. Suitable for a max. operating pressure of 10 bar (optionally 16 bar) and a max. operating temperature of 90 °C.

Cross-flow fan already installed in the floor pan parallel to the heat register to boost the convection effect (cross-flow fan on room side).

Protective cover over the cross-flow fan. Cross-flow fan with energy-saving EC motors 24 V, wired ready for connection.

Low-noise fan operation, infinitely variable via analogue interface (0 – 10 V). Actuator control pulse 24 V DC, infinitely variable via analogue interface (0 – 10 V). Synchronised control of fan speed and water flow for a hydraulically balanced pipe system and especially energy-efficient operation while maintai-ning a minimum spread between flow and return temperature. Factory configuration of appropriate control algorithm.

Aluminium linear grille as standard. Acoustic decoupling through placement of the aluminium linear grille on rubber elements in the floor pan. Consisting of sturdy longitudinal profiles, natural colour anodised, with profile bar dimensions of 16 x 6 mm. Grille with a total height of 20 mm and an open cross-section of 60%.

Including installation cover and edge bar protection for protec-tion of the trench convectors during the construction phase.

QA system certified to DIN EN ISO 9001:2008.

Environmental management system to DIN EN ISO 14001:2004.

Operating conditions: Hot water up to 90 °C

Operating pressure: Max. 10 bar (optionally 16 bar high-pres-

sure-version)

Test pressure: 13 bar (21 bar)

GeneralTrench convectors find application in private residential areas, in conservatories, in offices and administration buildings, in show-rooms as well as in business areas.

Version KRN81 forced convection with cross-flow fan

• Connections: 2 x euro taper with union nut (3/4“ internal thread), suitable for use with all fittings that comply with DIN V 3838

• Air vent: installed

Range available• 5 depths: 185, 210, 260, 310 and 360 mm• 1 height: 110 mm• 12 lengths:

– 1250 mm to 4000 mm– Grading 250 mm

• Standard: Aluminium linear grille

Surface finishes• Standard colour of floor pan, powder-coated:

Anthracite grey (RAL7016 matt finish)• Standard colour of linear grille:

Aluminium anodised in natural colour• Standard colour of edge bar corresponding to colour of cover

grille

Accessories• Programmable room thermostat• Thermoelectric actuator 24 V DC• Connection set, consisting of valve base with factory preset kV

valve and return fitting with shut-off• Air-intake filter

For additional accessories and information about accessories, see "Accessories".

Page 2: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® eco KRN81Forced convection with cross-flow fan

30 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Asc

othe

rm e

co

KRN

81

Technical data per metre

Floor pan dimensions and register

TypeHfloor pan

[mm]Hreg.

[mm]Tfloor pan

[mm]Treg.

[mm]Lfloor pan [mm]

Lribb. [mm]

KRN81 110 50

185 210 260 310 360

5075 125 175 225

1250 - 3000

>3000

LFloor pan - 473

LFloor pan - 555

Technical data per metreHeight 110 mm

HeightH

[mm]

DepthT

[mm]

Controlvoltage

EC motor [V]

Heat output

Exponentn[ ]

Spec.standard

waterflow rate

qms[kg/h m]

Massper

metre(average)

M[kg/m]

ΦL ∆T 50K75/65/20°C[watts/m

ribbedconvector

length]

Φ ∆T 42K70/55/20°C[watts/mribbed

convectorlength]

Φ ∆T 30K55/45/20°C[watts/mribbed

convectorlength]

Φ ∆T 25K50/40/20°C[watts/mribbed

convectorlength]

110

185

035810

19068994512561412

13857478810451175

71405556739830

49337462613689

1,93 1,00 1,00 1,00 1,00

16,459,481,5108,3121,7

10,07

210

035810

250744104713891584

19462287311571319

116439616817932

89364511678773

1,48 1,00 1,00 1,00 1,00

21,664,190,2108,3136,5

10,83

260

035810

340902132317201982

268754110314321651

16553377910131167

127441646840968

1,40 1,00 1,00 1,00 1,00

29,377,8114,1108,3170,9

12,28

310

0358

10

3801076142620122247

297898118816741870

17963483911841322

136526696982

1097

1,45 1,00 1,00 1,00 1,00

32,892,7122,9108,3193,7

13,84

360

035810

4201271174722112589

3281060145618402154

199749102813011523

15262285310801264

1,44 1,00 1,00 1,00 1,00

36,2109,6150,6108,3223,2

15,59

The heat outputs of the KRN81 versions are not linear to the length.

The specific heat outputs (watts/m ribbed convector length) and the specific standard water flows in the above table result by conver-ting the average length of 2000 mm. The data are intended for approximate dimensioning.

For individual calculations of heat outputs, see "General information"

Page 3: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® eco KRN81Forced convection with cross-flow fan

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 31

Asc

othe

rm e

co

KRN

81

Dimensional drawings and connection images

2-pipe connections without integrated valve

Connection system

Orde-ring code IVTI

ArrangementOrdering code

|ANB|Connection

size

Ordering code

Addi-tional price per

radiator[EUR]|VG| |RG|

2-pipe, room side, side by side

2 BB DD

Euro taper with union

nut internal

thread 3/4“

64 64 –

2-pipe, to the face, side by side

2 11 33

2-pipe, facing down, side by side

2

Special connection 66 / 88

The accessories range does not contain any connection sets with preset valves for the connection arrangements 66 and 88; however, these can be installed at the factory with appropriate notification when ordering.

Valve base with factory preset kv valve = Outflow 3/4“ external thread with euro taper, inlet 1/2“ inter-nal thread; return fitting with shut-off: both sides 3/4“ external thread with euro taper

On re-quest

Connection 11/33 and 66/88 are not possible with a depth of 185 mm.

Dimensional drawings KRN81

Connection BB/DD

Side view from left Front view Side view from right

H1

T-33

T

61 H

105 50L

Ø33 Ø

19

100 44

48

Top view

L

Dimensional drawings for connection BB, connection DD mirrored

ribb.

Page 4: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® eco KRN81Forced convection with cross-flow fan

32 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Asc

othe

rm e

co

KRN

81

Dimensional drawings and connection images

Dimensional drawings KRN81

Connection 11/33

Side view from left Front view Side view from rightH

161

T-33

T

T1 NA

Ø33

H

L

4828

32

Ø19

Top view

L

Dimensional drawings for connection 11, connection 33 mirrored

Applies to all connection optionsApplies only to connection arrangement 11/33

T [mm]

H [mm]

H1 [mm]

L [mm]

Lribb. [mm]

185

210

260

310

360

1103 - 30

(3 - 40)*

up to 3000

L - 473

over 3000 L - 555

* When installing extended headless screws (available as accessory, product code: ZB02960001)

T [mm]

T1 [mm]

Boss spacing [mm]

210 37 112,5

260 37 112,5

310 87 112,5

360 110 140

Connection 11/33 not possible with a depth of 185 mm

ribb.

Page 5: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® eco KRN81Forced convection with cross-flow fan

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 33

Asc

othe

rm e

co

KRN

81

Dimensional drawings and connection images

Number and version of cross-flow fans depending on the length

Cross-flow fan technical data, incl. thermoelectric actuator 24 V DC

L = 1250 L = 1500 L = 1750

Length 1250 1500 1750

Number of EC motors 1 1 2

Number of fan wheels 2 2 3

max. power consumption [W] 9,2 9,2 14,2

max. current consumption [mA] 40 40 62

max. inrush current for max. 2 min [mA] 381 381 403

max. volume flow rate [m³/h] 252 252 378

Cross-flow fan technical data, incl. thermoelectric actuator 24 V DC

L = 2000 L = 2250 L = 2500

Length 2000 2250 2500

Number of EC motors 2 2 3

Number of fan wheels 4 4 5

max. power consumption [W] 16,4 16,4 21,4

max. current consumption [mA] 71 71 93

max. inrush current for max. 2 min [mA] 413 413 434

max. volume flow rate [m³/h] 504 504 630

Cross-flow fan technical data, incl. thermoelectric actuator 24 V DC

L = 2750 L = 3000

Length 2750 3000

Number of EC motors 3 3

Number of fan wheels 6 6

max. power consumption [W] 23,6 23,6

max. current consumption [mA] 103 103

max. inrush current for max. 2 min [mA] 444 444

max. volume flow rate [m³/h] 756 756

Cross-flow fan technical data, incl. thermoelectric actuator 24 V DC

L = 3250 L = 3500

Length 3250 3500

Number of EC motors 3 4

Number of fan wheels 6 7

max. power consumption [W] 23,6 28,6

max. current consumption [mA] 103 124

max. inrush current for max. 2 min [mA] 444 466

max. volume flow rate [m³/h] 756 882

Cross-flow fan technical data, incl. thermoelectric actuator 24 V DC

L =3750 L = 4000

Length 3750 4000

Number of EC motors 4 4

Number of fan wheels 7 8

max. power consumption [W] 28,6 30,8

max. current consumption [mA] 124 134

max. inrush current for max. 2 min [mA] 466 475

max. volume flow rate [m³/h] 882 1008

For general information about "Control system", see corresponding chapter.Detailed data (e.g. circuit diagrams) can be found in the installation instructions included with the trench convector and also requested, if necessary.

Page 6: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® eco KRN81Forced convection with cross-flow fan

34 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Asc

othe

rm e

co

KRN

81

Pressure loss diagram

Pressure loss diagram

Pres

sure

dro

p p

[m

bar

/m r

ibb

ed c

on

vect

or

len

gth

]

T 185, T 210

T 260T 310

T 360

1

10

100

10 100 1000

Water flow qm [kg/h]

Page 7: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Prices without value-added tax. Technical specifications subject to change. Prices and Technology 2015-N 35

Ascotherm® eco KRN81Forced convection with cross-flow fan

Asc

othe

rm e

co

KRN

81

Prices and heat outputs

Ribbed convector length = length floor pan - 473 mm, for length > 3000 mm: length floor pan - 555 mm

LR: Aluminium linear grille, natural colour anodised (standard)

Standard heat output at 75 / 65 / 20 °C (∆T 50 K)

Height 110 mm (depth 185–260 mm)Length 1250 – 2500 mm

Version KRN81 KRN81 KRN81

Depth T [mm] 185 210 260

Price per piece [EUR/pc.] 203,16 224,35 236,09

Price per metre [EUR/m]without linear

grille 392,27

with linear grille

483,19

without linear grille

437,20

with lineat grille

532,85

without linear grille

440,44

with linear grille

549,07

LengthL

[mm]

Ribbedcon-

vector lengthLribb. [mm]

Controlvoltage

EC motor[V]

Soundpres-surelevel

LP[dB/A]

AcousticpowerlevelLW

[dB/A]ΦS

[watts]Price[EUR]

Price[EUR]

ΦS[watts]

Price[EUR]

Price[EUR]

ΦS[watts]

Price[EUR]

Price[EUR]

1250 777

035810

24273743

32354551

148529725962

1082

693,50 807,15

19457280310651214

770,85 890,41

264694101513191520

786,64 922,43

1500 1027

0358

10

24273743

32354551

19558278210251152

791,57 927,95

25764287811451301

880,15 1023,63

349784111014191632

896,75 1059,69

1750 1277

0358

10

25293945

33374753

243817111314711654

889,63 1048,74

319889123816331860

989,45 1156,84

4341081156520232330

1006,86 1196,96

2000 1527

035810

26304046

34384854

2901053144319182156

987,70 1169,54

3821136159821212418

1098,75 1290,05

5191378202026273027

1116,97 1334,23

2250 1777

035810

26304046

34384854

3381105150119802226

1085,77 1290,34

4441206167322012506

1208,05 1423,26

6041468211527273140

1227,08 1471,50

2500 2027

035810

27314147

35394955

3851341183124272728

1183,84 1411,14

5071453203326893064

1317,35 1556,47

6891765257033313837

1337,19 1608,77

Notes regarding acoustic power and sound pressure level valuesThe acoustic power levels were measured following the DIN 45635-1. According to E DIN EN 16430-1 (Fan-assisted radiators, convectors and trench convectors - Part 1: Technical specifications and requirements), the sound pressure level can be established with a room absorption of 8 dB(A). This corresponds to a distance of 2 m from the unit being tested, a room volume of 100 m3 and a reverberation time of 0.5 s.

Page 8: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

36 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Ascotherm® eco KRN81Forced convection with cross-flow fan

Asc

othe

rm e

co

KRN

81

Prices and heat outputs

Ribbed convector length = length floor pan - 473 mm, for length > 3000 mm: length floor pan - 555 mm

LR: Aluminium linear grille, natural colour anodised (standard)

Standard heat output at 75 / 65 / 20 °C (∆T 50 K)

Height 110 mm (depth 310–360 mm)Length 1250 – 2500 mm

Version KRN81 KRN81

Depth T [mm] 310 360

Price per piece [EUR/pc.] 352,06 441,39

Price per metre [EUR/m]without linear grille

469,93

with linear grille

602,18

without linear grille 562,96

with linear grille

709,38

LengthL

[mm]

Ribbedcon-

vector lengthLribb. [mm]

Controlvoltage

EC motor[V]

Soundpres-surelevel

LP[dB/A]

AcousticpowerlevelLW

[dB/A]ΦS

[watts]Price[EUR]

Price[EUR]

ΦS[watts]

Price[EUR]

Price[EUR]

1250 777

035810

24273743

32354551

295827109415421722

939,47 1104,79

326976134016951984

1145,09 1328,12

1500 1027

035810

24273743

32354551

390927119916521850

1056,95 1255,33

4311084145218172116

1285,83 1505,46

1750 1277

035810

25293945

33374753

4851285168823622640

1174,44 1405,88

5361512206025973035

1426,57 1682,81

2000 1527

035810

26304046

34384854

5801643217730723431

1291,92 1556,42

6411941266733763953

1567,31 1860,15

2250 1777

035810

26304046

34384854

6751743228231823558

1409,40 1706,96

7462048278034994086

1708,05 2037,49

2500 2027

035810

27314147

35394955

7702101277138924349

1526,89 1857,51

8512477338742785004

1848,79 2214,84

Notes regarding acoustic power and sound pressure level valuesThe acoustic power levels were measured following the DIN 45635-1. According to E DIN EN 16430-1 (Fan-assisted radiators, convectors and trench convectors - Part 1: Technical specifications and requirements), the sound pressure level can be established with a room absorption of 8 dB(A). This corresponds to a distance of 2 m from the unit being tested, a room volume of 100 m3 and a reverberation time of 0.5 s.

Page 9: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Prices without value-added tax. Technical specifications subject to change. Prices and Technology 2015-N 37

Ascotherm® eco KRN81Forced convection with cross-flow fan

Asc

othe

rm e

co

KRN

81

Prices and heat outputs

Ribbed convector length = length floor pan - 473 mm, for length > 3000 mm: length floor pan - 555 mm

LR: Aluminium linear grille, natural colour anodised (standard)

Standard heat output at 75 / 65 / 20 °C (∆T 50 K)

Height 110 mm (depth 185–260 mm)Length 2750 – 4000 mm

Version KRN81 KRN81 KRN81

Depth T [mm] 185 210 260

Price per piece [EUR/pc.] 203,16 224,35 236,09

Price per metre [EUR/m]without linear

grille 392,27

with linear grille

483,19

without linear grille

437,20

with lineat grille

532,85

without linear grille

440,44

with linear grille

549,07

LengthL

[mm]

Ribbedcon-

vector lengthLribb. [mm]

Controlvoltage

EC motor[V]

Soundpres-surelevel

LP[dB/A]

AcousticpowerlevelLW

[dB/A]ΦS

[watts]Price[EUR]

Price[EUR]

ΦS[watts]

Price[EUR]

Price[EUR]

ΦS[watts]

Price[EUR]

Price[EUR]

2750 2277

035810

28324248

36405056

4331576216228733230

1281,90 1531,93

5691700239331773623

1426,65 1689,69

7742062302539354535

1447,30 1746,03

3000 2527

035810

28324248

36405056

4801629221929363300

1379,97 1652,73

6321770246832573710

1535,95 1822,90

8592152312040354647

1557,41 1883,30

3250 2695

035810

28324248

36405056

5121664225829783347

1478,04 1773,53

6741817251933103769

1645,25 1956,11

9162212318441024723

1667,52 2020,57

3500 2945

035810

29334349

37415157

5601899258834243849

1576,11 1894,33

7362064287937984328

1754,55 2089,32

10012509363947065420

1777,63 2157,84

3750 3195

035810

29334349

37415157

6071952264634873919

1674,17 2015,12

7992134295438784415

1863,85 2222,54

10862599373448065533

1887,74 2295,10

4000 3445

035810

30344450

38425258

6552187297639334421

1772,24 2135,92

8612381331443664974

1973,15 2355,75

11712896418954106230

1997,85 2432,37

Notes regarding acoustic power and sound pressure level valuesThe acoustic power levels were measured following the DIN 45635-1. According to E DIN EN 16430-1 (Fan-assisted radiators, convectors and trench convectors - Part 1: Technical specifications and requirements), the sound pressure level can be established with a room absorption of 8 dB(A). This corresponds to a distance of 2 m from the unit being tested, a room volume of 100 m3 and a reverberation time of 0.5 s.

Page 10: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

38 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Ascotherm® eco KRN81Forced convection with cross-flow fan

Asc

othe

rm e

co

KRN

81

Prices and heat outputs

Ribbed convector length = length floor pan - 473 mm, for length > 3000 mm: length floor pan - 555 mm

LR: Aluminium linear grille, natural colour anodised (standard)

Standard heat output at 75 / 65 / 20 °C (∆T 50 K)

Height 110 mm (depth 310–360 mm)Length 2750 – 4000 mm

Version KRN81 KRN81

Depth T [mm] 310 360

Price per piece [EUR/pc.] 352,06 441,39

Price per metre [EUR/m]without linear grille

469,93

with linear grille

602,18

without linear grille 562,96

with linear grille

709,38

LengthL

[mm]

Ribbedcon-

vector lengthLribb. [mm]

Controlvoltage

EC motor[V]

Soundpres-surelevel

LP[dB/A]

AcousticpowerlevelLW

[dB/A]ΦS

[watts]Price[EUR]

Price[EUR]

ΦS[watts]

Price[EUR]

Price[EUR]

2750 2277

035810

28324248

36405056

8652459326046025139

1644,37 2008,06

9562905399550585923

1989,53 2392,18

3000 2527

035810

28324248

36405056

9602559336547125267

1761,85 2158,60

10613013410751806055

2130,27 2569,53

3250 2695

035810

28324248

36405056

10242626343647865352

1879,33 2309,15

11323085418352636144

2271,01 2746,88

3500 2945

035810

29334349

37415157

11192984392554966143

1996,82 2459,69

12373513479060427063

2411,75 2924,22

3750 3195

035810

29334349

37415157

12143084403056066270

2114,30 2610,24

13423621490361657195

2552,49 3101,57

4000 3445

035810

30344450

38425258

13093442451963167061

2231,78 2760,78

14474049551069448114

2693,23 3278,91

Notes regarding acoustic power and sound pressure level valuesThe acoustic power levels were measured following the DIN 45635-1. According to E DIN EN 16430-1 (Fan-assisted radiators, convectors and trench convectors - Part 1: Technical specifications and requirements), the sound pressure level can be established with a room absorption of 8 dB(A). This corresponds to a distance of 2 m from the unit being tested, a room volume of 100 m3 and a reverberation time of 0.5 s.

Page 11: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® ecoProduct details

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 65

Prod

uct

deta

ils

The new connection sets with factory preset kV valves

Control curves for valve inserts

Standard valve insert V5K S

Presetting 1 1,5 2 2,5 3 3,5 4 4,5 5 5,5 6 6,5 7 7,56 8

kvs value up to 0,16 0,21 0,24 0,30 0,34 0,41 0,44 0,54 0,65 0,82 0,98 1,11 1,23 1,33 1,43

Pres

sure

loss

in m

bar

321 4 5 6

87

1,5 2,5 3,5 4,5 5,5

7,56,5

100

1000

10 1002 3 4 5 6 7 8 9 2 3 4 5 6 7 8 9

1000

10

2

345

6 78 9

2

345

6 78 9

Water flow in kg/h

Connection sets for the Ascotherm ecoIt is recommended that the Ascotherm eco be fitted with preset kv connection sets (see accessories range). On request, the instal-lation can be done at the factory.

The Ascotherm eco units are fitted with preset connection sets depending on the heating or cooling capacity.

Ascotherm eco units can also be fitted with the fine-adjusting valve. The adjustable valve insert permits reproducible settings of low water flow rates. The setting values can be taken from the diagram.

Page 12: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® ecoProduct details

66 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Prod

uct

deta

ils

The new connection sets with factory preset kV valves

Valve performance limits of valve inserts for the Ascotherm eco connection setsPlease note the valve performance limits in relation to the system parameters

Standard valve insert V5K S

Presetting kvs value Δp [mbar]

Temperature difference ΔT [K]

2 4 6 8 10 12 15 20

1 0,16

60 92 183 275 366 458 549 686 91580 106 211 317 423 528 634 793 1057

100 118 236 354 473 591 709 886 1182120 129 259 388 518 647 777 971 1294140 140 280 419 559 699 839 1049 1398

1,5 0,21

60 120 240 360 480 601 721 901 120180 139 277 416 555 694 832 1040 1387

100 155 310 465 620 775 930 1163 1551120 170 340 510 680 849 1019 1274 1699140 183 367 550 734 917 1101 1376 1835

2 0,24

60 137 275 412 549 686 824 1030 137380 159 317 476 634 793 951 1189 1585

100 177 354 532 709 886 1063 1329 1772120 194 388 582 777 971 1165 1456 1941140 210 419 629 839 1049 1258 1573 2097

2,5 0,30

60 169 337 506 675 844 1012 1266 168780 195 390 585 779 974 1169 1461 1948

100 218 436 654 871 1089 1307 1634 2178120 239 477 716 955 1193 1432 1790 2386140 258 516 773 1031 1289 1547 1933 2578

3 0,34

60 194 389 583 778 972 1167 1459 194580 225 449 674 898 1123 1347 1684 2246

100 251 502 753 1004 1255 1506 1883 2511120 275 550 825 1100 1375 1650 2063 2750140 297 594 891 1188 1485 1782 2228 2971

3,5 0,41

60 235 469 704 938 1173 1407 1759 234580 271 542 812 1083 1354 1625 2031 2708

100 303 606 908 1211 1514 1817 2271 3028120 332 663 995 1327 1658 1990 2487 3317140 358 716 1075 1433 1791 2149 2687 3582

4 0,44

60 252 503 755 1007 1258 1510 1888 251780 291 581 872 1162 1453 1744 2180 2906

100 325 650 975 1300 1625 1950 2437 3249120 356 712 1068 1424 1780 2136 2669 3559140 384 769 1153 1538 1922 2307 2883 3845

4,5 0,54

60 309 618 927 1236 1544 1853 2317 308980 357 713 1070 1427 1783 2140 2675 3567

100 399 798 1196 1595 1994 2393 2991 3988120 437 874 1310 1747 2184 2621 3276 4368140 472 944 1415 1887 2359 2831 3539 4718

5 0,65

60 372 744 1115 1487 1859 2231 2789 371880 429 859 1288 1717 2147 2576 3220 4293

100 480 960 1440 1920 2400 2880 3600 4800120 526 1052 1577 2103 2629 3155 3944 5258140 568 1136 1704 2272 2840 3408 4260 5679

5,5 0,82

60 469 938 1407 1876 2345 2814 3518 469080 542 1083 1625 2166 2708 3250 4062 5416

100 606 1211 1817 2422 3028 3633 4541 6055120 663 1327 1990 2653 3317 3980 4975 6633140 716 1433 2149 2866 3582 4299 5374 7165

6 0,98

60 561 1121 1682 2242 2803 3363 4204 560680 647 1295 1942 2589 3236 3884 4855 6473

100 724 1447 2171 2895 3618 4342 5428 7237120 793 1586 2378 3171 3964 4757 5946 7928140 856 1713 2569 3425 4281 5138 6422 8563

6,5 1,11

60 635 1270 1905 2540 3175 3810 4762 634980 733 1466 2199 2933 3666 4399 5499 7331

100 820 1639 2459 3279 4098 4918 6148 8197120 898 1796 2694 3592 4490 5388 6734 8979140 970 1940 2910 3879 4849 5819 7274 9699

7 1,23

60 704 1407 2111 2814 3518 4221 5277 703680 812 1625 2437 3250 4062 4874 6093 8124

100 908 1817 2725 3633 4541 5450 6812 9083120 995 1990 2985 3980 4975 5970 7462 9950140 1075 2149 3224 4299 5374 6448 8060 10747

7,5 1,33

60 761 1522 2282 3043 3804 4565 5706 760880 878 1757 2635 3514 4392 5271 6588 8785

100 982 1964 2946 3929 4911 5893 7366 9821120 1076 2152 3228 4304 5379 6455 8069 10759140 1162 2324 3486 4648 5810 6973 8716 11621

8 1,43

60 818 1636 2454 3272 4090 4908 6135 818080 945 1889 2834 3778 4723 5667 7084 9445

100 1056 2112 3168 4224 5280 6336 7920 10560120 1157 2314 3470 4627 5784 6941 8676 11568140 1249 2499 3748 4998 6247 7497 9371 12495

Page 13: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® ecoProduct details

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 67

Prod

uct

deta

ils

The new connection sets with factory preset kV valves

Fine-adjusting valve insert V5K F

Presetting 1 1,5 2 2,5 3 3,5 4 4,5 5 5,5 6 6,5 7 7,56 8

kvs value up to 0,06 0,06 0,07 0,07 0,08 0,09 0,1 0,11 0,12 0,15 0,17 0,21 0,25 0,37 0,5

Pres

sure

loss

in m

bar

22,5

11,5

3 4 5 6 7 83,5 4,5 5,5 6,5 7,5

100

1000

10 1002 3 4 5 6 7 8 9 2 3 4 5 6 7 8 9

1000

10

2

345

6 78 9

2

345

6 78 9

Water flow in kg/h

Page 14: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® ecoProduct details

68 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Prod

uct

deta

ils

The new connection sets with factory preset kV valves

Valve performance limits of valve inserts for the Ascotherm eco connection setsPlease note the valve performance limits in relation to the system parameters

Fine-adjusting valve insert V5K F

Presetting kvs value Δp [mbar]

Temperature difference ΔT [K]

2 4 6 8 10 12 15 20

1 0,06

60 34 69 103 137 172 206 257 34380 40 79 119 159 198 238 297 396

100 44 89 133 177 222 266 332 443120 49 97 146 194 243 291 364 485140 52 105 157 210 262 315 393 524

1,5 0,06

60 34 69 103 137 172 206 257 34380 40 79 119 159 198 238 297 396

100 44 89 133 177 222 266 332 443120 49 97 146 194 243 291 364 485140 52 105 157 210 262 315 393 524

2 0,07

60 40 80 120 160 200 240 300 40080 46 92 139 185 231 277 347 462

100 52 103 155 207 258 310 388 517120 57 113 170 227 283 340 425 566140 61 122 183 245 306 367 459 612

2,5 0,07

60 40 80 120 160 200 240 300 40080 46 92 139 185 231 277 347 462

100 52 103 155 207 258 310 388 517120 57 113 170 227 283 340 425 566140 61 122 183 245 306 367 459 612

3 0,08

60 46 92 137 183 229 275 343 45880 53 106 159 211 264 317 396 528

100 59 118 177 236 295 354 443 591120 65 129 194 259 324 388 485 647140 70 140 210 280 350 419 524 699

3,5 0,09

60 51 103 154 206 257 309 386 51580 59 119 178 238 297 357 446 594

100 66 133 199 266 332 399 498 665120 73 146 218 291 364 437 546 728140 79 157 236 315 393 472 590 786

4 0,10

60 57 114 172 229 286 343 429 57280 66 132 198 264 330 396 495 660

100 74 148 222 295 369 443 554 738120 81 162 243 324 404 485 607 809140 87 175 262 350 437 524 655 874

4,5 0,11

60 63 126 189 252 315 378 472 62980 73 145 218 291 363 436 545 727

100 81 162 244 325 406 487 609 812120 89 178 267 356 445 534 667 890140 96 192 288 384 481 577 721 961

5 0,12

60 69 137 206 275 343 412 515 68680 79 159 238 317 396 476 594 793

100 89 177 266 354 443 532 665 886120 97 194 291 388 485 582 728 971140 105 210 315 419 524 629 786 1049

5,5 0,15

60 86 172 257 343 429 515 644 85880 99 198 297 396 495 594 743 991

100 111 222 332 443 554 665 831 1108120 121 243 364 485 607 728 910 1213140 131 262 393 524 655 786 983 1311

6 0,17

60 97 194 292 389 486 583 729 97280 112 225 337 449 561 674 842 1123

100 126 251 377 502 628 753 942 1255120 138 275 413 550 688 825 1031 1375140 149 297 446 594 743 891 1114 1485

6,5 0,21

60 120 240 360 480 601 721 901 120180 139 277 416 555 694 832 1040 1387

100 155 310 465 620 775 930 1163 1551120 170 340 510 680 849 1019 1274 1699140 183 367 550 734 917 1101 1376 1835

7 0,25

60 143 286 429 572 715 858 1073 143080 165 330 495 660 826 991 1238 1651

100 185 369 554 738 923 1108 1385 1846120 202 404 607 809 1011 1213 1517 2022140 218 437 655 874 1092 1311 1638 2184

7,5 0,37

60 212 423 635 847 1058 1270 1587 211680 244 489 733 978 1222 1466 1833 2444

100 273 546 820 1093 1366 1639 2049 2732120 299 599 898 1197 1497 1796 2245 2993140 323 647 970 1293 1616 1940 2425 3233

8 0,50

60 286 572 858 1144 1430 1716 2145 286080 330 660 991 1321 1651 1981 2477 3302

100 369 738 1108 1477 1846 2215 2769 3692120 404 809 1213 1618 2022 2427 3034 4045140 437 874 1311 1748 2184 2621 3277 4369

Page 15: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® ecoProduct details

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 69

Prod

uct

deta

ils

The new connection sets with factory preset kV valves

Factory kV presetting of the valves

KRP91

H [mm] 92 120 150 200

T [mm] 185 210 260 310 360 400 185 210 260 310 360 400 185 210 260 310 360 400 185 210 260 310 360 400

L [mm] Preset kV values

1000 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5*

1250 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 2,5 2,5

1500 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5 5,5* 5,5* 2,5 5,5* 5,5* 5,5* 2,5 2,5 2,5

1750 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5 5,5* 5,5* 2,5 5,5* 5,5* 2,5 2,5 2,5 2,5

2000 5,5* 5,5* 5,5* 5,5* 5,5* 2,5 5,5* 5,5* 5,5* 2,5 2,5 2,5 5,5* 5,5* 2,5 2,5 2,5 2,5 5,5* 5,5* 2,5 2,5 2,5 4,5

2250 5,5* 5,5* 5,5* 5,5* 5,5* 2,5 5,5* 5,5* 5,5* 2,5 2,5 2,5 5,5* 2,5 2,5 2,5 2,5 2,5 5,5* 2,5 2,5 2,5 4,5 4,5

2500 5,5* 5,5* 5,5* 2,5 2,5 2,5 5,5* 5,5* 5,5* 2,5 2,5 2,5 5,5* 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 4,5 4,5

2750 5,5* 5,5* 5,5* 2,5 2,5 2,5 5,5* 5,5* 2,5 2,5 2,5 2,5 5,5* 2,5 2,5 2,5 4,5 4,5 2,5 2,5 2,5 4,5 4,5 4,5

3000 5,5* 5,5* 5,5* 2,5 2,5 2,5 5,5* 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 4,5 4,5 2,5 2,5 2,5 4,5 4,5 4,5

3250 5,5* 5,5* 2,5 2,5 2,5 2,5 5,5* 2,5 2,5 2,5 2,5 4,5 2,5 2,5 2,5 4,5 4,5 4,5 2,5 2,5 4,5 4,5 4,5 4,5

3500 5,5* 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 4,5 2,5 2,5 2,5 4,5 4,5 4,5 2,5 2,5 4,5 4,5 4,5 6,0

3750 5,5* 2,5 2,5 2,5 2,5 4,5 2,5 2,5 2,5 4,5 4,5 4,5 2,5 2,5 4,5 4,5 4,5 4,5 2,5 2,5 4,5 4,5 4,5 6,0

4000 2,5 2,5 2,5 2,5 4,5 4,5 2,5 2,5 2,5 4,5 4,5 4,5 2,5 2,5 4,5 4,5 4,5 4,5 2,5 4,5 4,5 4,5 6,0 6,0

4250 2,5 2,5 2,5 2,5 4,5 4,5 2,5 2,5 2,5 4,5 4,5 4,5 2,5 4,5 4,5 4,5 4,5 4,5 2,5 4,5 4,5 4,5 6,0 6,0

4500 2,5 2,5 2,5 2,5 4,5 4,5 2,5 2,5 2,5 4,5 4,5 4,5 2,5 4,5 4,5 4,5 4,5 6,0 2,5 4,5 4,5 4,5 6,0 6,0

4750 2,5 2,5 2,5 4,5 4,5 4,5 2,5 2,5 2,5 4,5 4,5 4,5 2,5 4,5 4,5 4,5 4,5 6,0 4,5 4,5 4,5 4,5 6,0 6,0

5000 2,5 2,5 2,5 4,5 4,5 4,5 2,5 2,5 4,5 4,5 4,5 4,5 2,5 4,5 4,5 4,5 6,0 6,0 4,5 4,5 4,5 6,0 6,0 6,0

* Fine-adjusting valve

Dimensioning:

Heat outputs at 70 / 55 / 20°C,

Pressure loss across the valve 100 mbar

Page 16: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® ecoProduct details

70 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Prod

uct

deta

ils

The new connection sets with factory preset kV valves

Factory kV presetting of the valves

KRN92

H [mm] 110 150 200

T [mm] 185 210 260 310 360 400 185 210 260 310 360 400 185 210 260 310 360 400

L [mm] Preset kV values

1000 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5*

1250 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5*

1500 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5*

1750 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 5,5* 2,5 2,5

2000 5,5* 5,5* 5,5* 5,5 5,5 5,5 5,5* 5,5* 5,5* 5,5* 2,5 2,5 5,5* 5,5* 5,5* 2,5 2,5 2,5

2250 5,5* 5,5* 5,5* 2,5 2,5 2,5 5,5* 5,5* 5,5* 2,5 2,5 2,5 5,5* 5,5* 5,5* 2,5 2,5 2,5

2500 5,5* 5,5* 5,5* 2,5 2,5 2,5 5,5* 5,5* 5,5* 2,5 2,5 2,5 5,5* 5,5* 5,5* 2,5 2,5 2,5

2750 5,5* 5,5* 5,5* 2,5 2,5 2,5 5,5* 5,5* 5,5* 2,5 2,5 2,5 5,5* 5,5* 2,5 2,5 2,5 2,5

3000 5,5* 5,5* 5,5* 2,5 2,5 2,5 5,5* 5,5* 2,5 2,5 2,5 2,5 5,5* 5,5* 2,5 2,5 2,5 2,5

3250 5,5* 5,5* 5,5* 2,5 2,5 2,5 5,5* 5,5* 2,5 2,5 2,5 2,5 5,5* 5,5* 2,5 2,5 4,5 4,5

3500 5,5* 5,5* 2,5 2,5 2,5 2,5 5,5* 5,5* 2,5 2,5 2,5 4,5 5,5* 5,5* 2,5 2,5 4,5 4,5

3750 5,5* 5,5* 2,5 2,5 2,5 2,5 5,5* 5,5* 2,5 2,5 4,5 4,5 5,5* 5,5* 2,5 4,5 4,5 4,5

4000 5,5* 5,5* 2,5 2,5 2,5 4,5 5,5* 5,5* 2,5 2,5 4,5 4,5 5,5* 5,5* 2,5 4,5 4,5 4,5

4250 5,5* 5,5* 2,5 4,5 4,5 4,5 5,5* 5,5* 2,5 4,5 4,5 4,5 5,5* 5,5* 2,5 4,5 4,5 4,5

4500 5,5* 5,5* 2,5 4,5 4,5 4,5 5,5* 5,5* 2,5 4,5 4,5 4,5 5,5* 2,5 2,5 4,5 4,5 4,5

4750 5,5* 5,5* 2,5 4,5 4,5 4,5 5,5* 5,5* 2,5 4,5 4,5 4,5 2,5 2,5 2,5 4,5 4,5 4,5

5000 5,5* 5,5* 2,5 4,5 4,5 4,5 5,5* 2,5 2,5 4,5 4,5 4,5 2,5 2,5 4,5 4,5 4,5 4,5

* Fine-adjusting valve

Dimensioning:

Heat outputs at 70 / 55 / 20°C,

Pressure loss across the valve 100 mbar

Page 17: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® ecoProduct details

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 71

Prod

uct

deta

ils

The new connection sets with factory preset kV valves

Factory kV presetting of the valves

KRN81

H [mm] 110

T [mm] 185 210 260 310 360

L [mm] Preset kV values

1250 2,5 2,5 2,5 2,5 4,5

1500 2,5 2,5 2,5 2,5 4,5

1750 2,5 2,5 4,5 4,5 4,5

2000 4,5 4,5 4,5 4,5 6

2250 4,5 4,5 4,5 4,5 6

2500 4,5 4,5 6 6 6

2750 4,5 6 6 6 6

3000 4,5 6 6 6 6

3250 4,5 6 6 6 6

3500 6 6 6 6 8

3750 6 6 6 6 8

4000 6 6 6 8 8

Dimensioning:

Heat outputs at 70 / 55 / 20°C,

Pressure loss across the valve 100 mbar

Page 18: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® ecoProduct details

72 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Prod

uct

deta

ils

The new connection sets with factory preset kV valves

Factory kV presetting of the valves

KC 281

H [mm] 130 155

T [mm] 310 360 310 360

L [mm] Preset kV values

1250 6 6 6 8

2000 0* 0* 0* 0*

2750 0* 0* 0* 0*

Note:

On the KC2 81, the valve inserts are preset in relation to the cooling capacity, since the water flow rate required for cooling is usually higher than for heating.

Dimensioning:

Cooling capacities at 16 / 18 / 27°C,

Pressure loss across the valve 100 mbar

KC 481

H [mm] 130 155

T [mm] 330 360 330 360

L [mm] Preset kV values

1250 6 6 6 6

2000 0* 0* 0* 0*

2750 0* 0* 0* 0*

Dimensioning:

Cooling capacities at 16 / 18 / 27°C,

Pressure loss across the valve 100 mbar

KC 481

H [mm] 130 155

T [mm] 330 360 330 360

L [mm] Preset kV values

1250 4,5 4,5 4,5 4,5

2000 6 8 6 8

2750 8 0* 8 0*

Dimensioning:

Heat outputs at 70 / 55 / 20°C,

Pressure loss across the valve 100 mbar

* Wherever kv preset values are stated as 0, the maximum convector outputs are above the valve performance limits for the indicated system parameters. In this case, it is necessary to check whether the dimensioned output is within the valve performance limits. See data under valve performance limits.

Page 19: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® ecoArbonia Individual

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 73

Asc

othe

rm e

co

Indi

vidu

al

Special versions

Angled version

• Available for all versions and for empty pan• Angle can be between 50° and 320° Please provide a dimensional drawing or template with the

order.• Feasibility depends on engineering review• Radiator must still be transportable

Dimensional drawing

Orde-ring code |BES|

Additional price / bevel cut

[EUR]

Floor pan

Linear grille

Roll-up grille

Single bevel

90°

L2

L1

TWA

W A T

L1

L2

270°

76

771)49,00 46,00 164,00

WA

T

L1

L2

αL1

L2

α

WA

T

1) Characteristic 77 for bevel cut at both ends

L1, L2: Length of the limbs, measured on the wallα: AngleT: Depth floor panWA: Wall spacing

Page 20: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® ecoArbonia Individual

74 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Asc

othe

rm e

co

Indi

vidu

al

Special versions

Curved version

• Available for KRP91 (other versions on request)• Bending radius R: at least 1000 mm Please provide a dimensional drawing or template with the

order.• Feasibility depends on engineering review• Radiator must still be transportable

Dimensional drawing

Orde-ring code |BES|

Additional price per radiator

[EUR]

L

R T

W A

Inside radius

70 On requestW A

T

R

L

Outside radius

L: Streched lengthR: Bending radius (wall radius)T: Depth floor panWA: Wall spacing

Page 21: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® ecoArbonia Individual

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 75

Asc

othe

rm e

co

Indi

vidu

al

Special versions

Column section version

• Available for all versions and for empty pan Please provide a dimensional drawing or template with the

order.• Feasibility depends on engineering review• Radiator must still be transportable

Dimensional drawing

Orde-ring codeIBESI

Additional price per column section

[EUR]

Floor pan

Linear grille

Roll-up grille

Column section according to drawing

75On

requestOn

requestOn

request

column section in floor pan column section in linear grille column section in roll-up grille

A

Ød C

A

Ød C

A

Ød C

A B

C

A B

C

A B

C

d: DiameterA: Inset dimension for lengthB: Edge dimensionC: Inset dimension for depth

Page 22: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® ecoArbonia Individual

76 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Asc

othe

rm e

co

Indi

vidu

al

Special versions

Version with impact sound insulation

Description

Orde-ring codeIEBTI

Additional price per

metre [EUR]

Without impact sound insulation

• Standard version wit-hout

With impact sound insulation

TS1 39,00

Coupled Ascotherm• radiators are supplied individually• Connection material (flexible connection hoses etc. available as accessory)• Only for versions KRP91 (not for H 150 and H 200), KRN92, KRN81• On version KRN81 (max. up to 4 motors)

Con-nection system Description

Sequence of coupled radiatorsΔ(enter in column "Special characteri-stics")

Ordering code|KHP|

Additio-nal price per radi-

ator [EUR]

Connec-tion on the same side from the left

• Radiator position 2 re-peats when coupling more than 3 radiators

• Please provide a draw-ing with the order

Initial radiator1

Middle radiator2

Final radiator3

75 67,00Connec-tion on the same side from the right

• Radiator position 2 re-peats when coupling more than 3 radiators

• Please provide a draw-ing with the order

Final radiator3

Middle radiator2

Initial radiator1

Impact sound insulation 4 mm

Page 23: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® ecoArbonia Individual

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 77

Asc

othe

rm e

co

Indi

vidu

al

Special versions

Air connection with air connection valve

Number of air connec-tions|LAZ| Length [mm] Description and dimensional drawings

Air connection arrangement

|LAP|1)

Height H

[mm]

Connec-tion size

|LAG|

Additional price per

additional connec-

tion [EUR]

1 ≤ 3000 mm • Standard: 1 air connection, incl. air valve • Additional air connections possible (max.

number and location on request) • Air connections are distributed evenly (to the

extent technically possible)• The exact positioning of the air connections

can be seen in the drawing

– 110, 150, 200 63 39,00

150, 200 80 41,00

200 100 44,00

200 125 46,00

2 > 3000 mm • Standard: 2 air connections, incl. air valves • Additional air connections possible (max.

number and location on request) • Air connections are distributed evenly (to the

extent technically possible)• The exact positioning of the air connections

can be seen in the drawing

• No clear assignment of positions, since floor pan joined at the factory

110, 150, 200 63 39,00

150, 200 80 41,00

200 100 44,00

200 125 46,00

Special connections - Version per drawing - Ordering code LAP = SON On re-quest

1) The positioning of the air connections is affected slightly by the arrangement of the cross bracing in the floor pan, example: connec-tion F (room side, centred) = "approx. centred" The exact dimensions/positions can be seen in the drawing and need to be approved by the customer.

Number and positions of the air connections

L/2 ±75L/2 ±75L ≤ 3000

L/4 ±150 L/4 ±150L > 3000

Page 24: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® ecoArbonia Individual

78 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Asc

othe

rm e

co

Indi

vidu

al

Special versions

Additional special versions

Description

Cha-racteri-

stic

Orde-ring code

Additional price per radiator

[EUR]

Pressure version High-pressure version16 bar (1600 kPa) |DRU| 16 + 5 %

Special versions Special length for heating 1)

• > 1000 mm (KRP91 and KRN92)• > 1250 mm possible (KRN81)

|BES| SBL Next-larger standard length

Special length for heating and cooling 1)

• > 1250 mm possible |BES| SBL On request

Extra-short length (smaller than smallest standard length)

• 600 mm - < 1000 mm possible (KRP91 and KRN92)• 1000 mm - < 1250 possible (KRN81)• 850 mm - < 1250 mm possible (KC281)• 1050 mm - < 1250 mm possible (KC481)

|BES| SBL On request

Special depth acc. to drawing 2) |BES| SBT On request

Special height according to drawing 3) |BES| SBH On request

Fixing Fixing with special bracket (in case of high soil structure) On request

Special finish Finished in special colour (no RAL colour)

Aluminium linear grille / aluminium roll-up grille |AUS| SF On request

Floor pan and register |FAR1| 99 On request

Finished in other RAL colour (standard is RAL 7016)

Floor pan and register |FAR1| SF + 30 %

1) Provide exact length2) Provide exact depth3) Provide exact height

Page 25: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® ecoAscotherm® eco Individual

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 79

Asc

othe

rm e

co

Indi

vidu

al

On request, accessory components, available factory-installed

Available on request

Description

Cha-racteri-

stic

Orde-ring code

Additional price per

metre [EUR]

Edge bar

Anodised in natural colour ELO = Anodised in natural colour |RDL| ELO –

Colour anodised BRO = Anodised in bronze finish MES = Anodised in brass finish DKS = Anodised in dark silver finish SWZ = Anodised in black finish EDS = Anodised in stainless steel finish

|RDL| BROMESDKSSWZEDS

11,0011,0011,0011,0011,00

Paint finish FAR1 = Edge bar finished as floor pan/register |RDL| FAR1 –

FAR2 = Edge bar finished as top grille |RDL| FAR2 49,00

Air-intake filter • For KRN81 air-intake filter PPI 30 dark 90 x 3 mm |FVL| FV 8,00

• For KC281 and KC481 air -ntake filter PPI 30 dark 140 x 3 mm |FVL| FV 9,00

Accessory components, factory-installed

Description

Cha-racteri-

stic

Orde-ring code

Additional price per radiator

[EUR]

Installation Connection set, straight form with pre-set kv valve

Consisting of:

• Valve base with factory preset kv valve– DN 15, both sides 3/4“ external thread

with euro taper– M30 x 1,5– nickel-plated, protective cap

• Return fitting with shut-off– DN 15, both sides 3/4“ external thread

with euro taper– nickel-plated

• Threaded fitting attached only hand-tight

• For all KRN, KRP91 and KC281 with connection 11 or 33

|VRS| VRS 44,00

• For KC481 with connec-tion 11 or 33

|VRS| VRS 88,00

Connection set, angled version with preset kv valve

Consisting of:

• Valve base with factory preset kv valve– DN 15, both sides 3/4“ external thread

with euro taper– M30 x 1,5– nickel-plated, protective cap

• Return fitting with shut-off– DN 15, both sides 3/4“ external thread

with euro taper– nickel-plated

• Threaded fitting attached only hand-tight

• For KC281 with connec-tion BB or DD

|VRS| VRS 44,00

• For KC481 with connec-tion BB or DD

|VRS| VRS 88,00

Connection set, angled version with preset kv val-ve, connection arrangement 66/88

Consisting of:

• Valve base with factory preset kv valve– DN 15, outlet 3/4“ external thread with

euro taper, inlet 1/2“ internal thread– M30 x 1,5– nickel-plated, protective cap

• Return fitting with shut-off– DN 15, both sides 3/4“ external thread

with euro taper– nickel-plated

• Threaded fitting attached only hand-tight

• For KRP91, KRN92 and KRN81

|VRS| VRS 44,00

Thermoelec-tric actuator 230 V AC

• Factory-installed • Only in conjunction with VRS

• For KRP91 and KRN92

|STT| STT 29,00

Thermoelec-tric actuator 24 V DC

• Factory-installed and with controller board wired

• Only in conjunction with VRS

• For KRN81 and KC281

|STT| STT 92,00

• For KC481 |STT| STT 184,00

KNX plug-in card (for KRN81, KC281 and KC481)

• for installation in the Ascotherm eco control board to connect to KNX networks, only 1 per convector group is needed (up to 6 convectors)

• For KRN81, KC281 and KC481

|GLT| KNX 146,00

Page 26: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® ecoAccessories

80 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Acc

esso

ries

Empty floor pan

1) Dimensions |HOE| and |MT| need to be stated with the order (for description, see chapter "General information")

Prices for other colours, see chapter "Ascotherm top grilles" and "Special versions".

Ascotherm eco empty floor panFor the ... Arbonia offers an Ascotherm empty floor pan in its accessories range.

The range available (H / B / T) and the special or extra-short empty floor pan lengths are listed at the individual versions.

Description Product code Characteristic

Dimensi-ons

Ordering code

ProductVersion

Ordering code

|3|

Priceper

piece[EUR/pc.]

Priceper

metrewithout grille

[EUR/m]

Priceper

metrewith grille[EUR/m]

Priceper

metrewithout grille

[EUR/m]|3.1| |3.4|

Empty floor panZA0108

Dimensions

• Heights:– 92, 110, 120, 130,

150, 155, 200 mm• Depths:

– 185, 210, 260, 310, 330, 360, 400 mm

• Lengths variable:– 200–3000 mm

Finish

• Standard in anthraci-te grey (RAL 7016 matt finish)

Top grille version

• Standard in alumi-nium, anodised in natural colour

Material

• Galvanised sheet steel, colour-coated

92 185 ZA0108 1)

111,30 89,04 179,96 179,96

210 111,30 100,17 195,82 195,82

260 111,30 111,30 219,93 219,93

310 111,30 122,43 254,68 254,68

360 111,30 133,56 279,98 279,98

400 111,30 144,69 302,03 302,03

110 185 ZA0108 1)

111,30 100,17 191,09 191,09

210 111,30 111,30 206,95 206,95

260 111,30 122,43 231,06 231,06

310 111,30 133,56 265,81 265,81

360 111,30 144,69 291,11 291,11

400 111,30 155,82 313,16 313,16

120 185 ZA0108 1) 111,30 100,17 271,38 271,38

210 111,30 111,30 282,62 282,62

260 111,30 122,43 296,68 296,68

310 111,30 133,56 191,09 191,09

360 111,30 144,69 206,95 206,95

400 111,30 155,82 231,06 231,06

130 310 ZA0108 1) 111,30 139,13 265,81 265,81

330 111,30 144,70 291,11 291,11

360 111,30 150,26 313,16 313,16

150 185 ZA0108 1)

111,30 111,30 202,22 202,22

210 111,30 122,43 218,08 218,08

260 111,30 133,56 242,19 242,19

310 111,30 144,69 276,94 276,94

360 111,30 155,82 302,24 302,24

400 111,30 166,95 324,29 324,29

155 310 ZA0108 1)

111,30 150,26 282,51 282,51

330 111,30 155,83 293,75 293,75

360 111,30 161,40 307,82 307,82

200 185 ZA0108 1)

111,30 122,43 213,35 213,35

210 111,30 133,56 229,21 229,21

260 111,30 144,69 253,32 253,32

310 111,30 155,82 288,07 288,07

360 111,30 166,95 313,37 313,37

400 111,30 178,08 335,42 335,42

Page 27: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® eco Accessories

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 81

Acc

esso

ries

1) Dimensions characteristic |MT| and ordering code need to be stated when ordering (for description, see chapter "General informati-on" and colour chart)

Top grilles

are attractively shaped, solid and robust. There are practically no limits to how they can be integrated into the architectural design of the room, thanks to the choice of various profile forms,

materials and

Surface finishes. The grilles can easily be removed for cleaning and then returned to their original positions.

Ascotherm eco top grilles

Description Product code Characteristic

Dimen-sions

Ordering code|MT|

Version

ProductVersion

Price per

metre [EUR/m]]Description

Orde-ring code

Alumini-um linear grille

ZA0109

Dimensions• Length up to 5000 mm

– up to 3000 mm in one piece

– as of 3001 mm in two pieces

• Height 20 mm• Bar width 6 mm• Bar spacing 10 mm• Open cross-section 60 %

Finish

• Anodised in natural or co-lour, powder-coated in RAL colours

• Anodised colours– Natural (ELO)– Bronze (BRO)– Dark silver (DKS)– Brass (MES)– Black (SWZ)

• Cut surfaces in aluminium colour if linear grille is in two pieces

Version

• Longitudinal profile bars are fixedly connected to aluminium angle profiles by means of a pressure process every 200-300 mm

Material

• Aluminium profiles

T = 185 Natural anodised ELO ZA0109 1) 90,92

Colour anodised BROMESDKSSWZ

ZA0109 1) 161,76

Finished in colour of choice

LAC ZA0109 1) 118,20

T = 210 Natural anodised ELO ZA0109 1) 95,65

Colour anodised BROMESDKSSWZ

ZA0109 1) 166,50

Finished in colour of choice

LAC ZA0109 1) 124,33

T = 260 Natural anodised ELO ZA0109 1) 108,63

Colour anodised BROMESDKSSWZ

ZA0109 1) 179,49

Finished in colour of choice

LAC ZA0109 1) 141,22

T = 310 Natural anodised ELO ZA0109 1) 132,25

Colour anodised BROMESDKSSWZ

ZA0109 1) 203,10

Finished in colour of choice

LAC ZA0109 1) 171,93

T = 330 Natural anodised ELO ZA0109 1) 137,92

Colour anodised BROMESDKSSWZ

ZA0109 1) 208,77

Finished in colour of choice

LAC ZA0109 1) 179,30

T = 360 Natural anodised ELO ZA0109 1) 146,42

Colour anodised BROMESDKSSWZ

ZA0109 1) 217,28

Finished in colour of choice

LAC ZA0109 1) 190,35

T = 400 Natural anodised ELO ZA0109 1) 157,34

Colour anodised BROMESDKSSWZ

ZA0109 1) 228,62

Finished in colour of choice

LAC ZA0109 1) 205,09

Natural anodised

Bronze

Dark silver

Brass

black

Page 28: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® ecoAccessories

82 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Acc

esso

ries

1) Dimensions characteristic |MT| and ordering code need to be stated when ordering (for description, see chapter "General informati-on" and colour chart)

Top grilles

Ascotherm eco top grilles

Description Product code Characteristic

Dimen-sions

Ordering code|MT|

Version

ProductVersion

Price per

metre [EUR/m]Description

Orde-ring code

Flexible aluminium roll-up grille

ZA0110

Dimensions• Length up to 5000 mm

– up to 3000 mm in one piece

– as of 3001 mm in two pieces

• Height 20 mm• Bar width 6 mm• Bar spacing 14 mm

– other spacings on request• Open cross-section 70 %

Finish

• Anodised in natural or co-lour, powder-coated in RAL colours

• Anodised colours– Natural (ELO)– Bronze (BRO)– Dark silver (DKS)– Brass (MES)– Black (SWZ)

• Cut surfaces in aluminium colour if linear grille is in two pieces

Version

• Anodised in natural colour– Cross connections with

chrome steel springs and PVC spacers in grey

• Anodised in colour– Cross connections with

chrome steel springs and PVC spacers in black

• Finished in colour of choice– Cross connections with

chrome steel springs and PVC spacers in black

Material

• Aluminium profiles

T = 185 Natural anodised ELO ZA0110 1) 90,92

Colour anodised BROMESDKSSWZ

ZA0110 1) 161,76

Finished in colour of choice

LAC ZA0110 1) 118,20

T = 210 Natural anodised ELO ZA0110 1) 95,65

Colour anodised BROMESDKSSWZ

ZA0110 1) 166,50

Finished in colour of choice

LAC ZA0110 1) 124,33

T = 260 Natural anodised ELO ZA0110 1) 108,63

Colour anodised BROMESDKSSWZ

ZA0110 1) 179,49

Finished in colour of choice

LAC ZA0110 1) 141,22

T = 310 Natural anodised ELO ZA0110 1) 132,25

Colour anodised BROMESDKSSWZ

ZA0110 1) 203,10

Finished in colour of choice

LAC ZA0110 1) 171,93

T = 330 Natural anodised ELO ZA0110 1) 137,92

Colour anodised BROMESDKSSWZ

ZA0110 1) 208,77

Finished in colour of choice

LAC ZA0110 1) 179,30

T = 360 Natural anodised ELO ZA0110 1) 146,42

Colour anodised BROMESDKSSWZ

ZA0110 1) 217,28

Finished in colour of choice

LAC ZA0110 1) 190,35

T = 400 Natural anodised ELO ZA0110 1) 157,34

Colour anodised BROMESDKSSWZ

ZA0110 1) 228,62

Finished in colour of choice

LAC ZA0110 1) 205,09

Natural anodised

Brass

Dark silver

black

Bronze

Page 29: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® eco Accessories

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 83

Acc

esso

ries

1) Dimensions characteristic |MT| and ordering code need to be stated when ordering (for description, see chapter "General informati-on" and colour chart)

Top grilles

Ascotherm eco top grilles

Description Product code Characteristic

Dimen-sions

Ordering code|MT|

Version

ProductVersion

Price per

metre [EUR/m]]Description

Orde-ring code

Stainless steel roll-up grille

ZA0111

Dimensions• Length up to 5000 mm

– up to 3000 mm in one piece

– as of 3001 mm in two pieces

• Height 20 mm• Profile width 10 mm• Profile spacing 16 mm• Open cross-section 60 %

Version

• Cross connections with chrome steel springs and PVC spacers in grey

• Aluminium edge bar in stain-less steel optic

Material

• Stainless steel• Not to be used at tempe-

ratures below dew point (danger of slipping)

T = 185 Stainless steel EDS ZA0111 1) 413,29

T = 210 Stainless steel EDS ZA0111 1) 448,70

T = 260 Stainless steel EDS ZA0111 1) 495,94

T = 310 Stainless steel EDS ZA0111 1) 543,17

T = 330 Stainless steel EDS ZA0111 1) 562,06

T = 360 Stainless steel EDS ZA0111 1) 590,40

T = 400 Stainless steel EDS ZA0111 1) 628,18

Wooden roll-up grille

ZA0112

Dimensions• Length up to 5000 mm

– up to 3000 mm in one piece

– as of 3001 mm in two pieces

• Height 20 mm• Profile width 12 mm• Profile spacing 16 mm• Open cross-section 55 %

Version

• Light oak, ash and beech, oiled

• Aluminium edge bar, natural

Material

• Cross connections with chrome steel springs and PVC spacers in white

• not to be used at tempe-ratures below dew point (material deformation)

T = 185 OakAshBeech

HEIHESHBU

ZA0112 1) 271,49

T = 210 OakAshBeech

HEIHESHBU

ZA0112 1) 307,01

T = 260 OakAshBeech

HEIHESHBU

ZA0112 1) 354,24

T = 310 OakAshBeech

HEIHESHBU

ZA0112 1) 401,48

T = 330 OakAshBeech

HEIHESHBU

ZA0112 1) 420,37

T = 360 OakAshBeech

HEIHESHBU

ZA0112 1) 448,70

T = 400 OakAshBeech

HEIHESHBU

ZA0112 1) 486,48

Beech

Stainless steel

Page 30: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® ecoAccessories

84 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Acc

esso

ries

Accessories and miscellaneous

Accessories–fittings

Description Product code Characteristic Dimensions

ProductVersion

Price [EUR]

Connection set, straight form

ZV0110

• VE 5,5 (yellow), kv value 0,15• Only for KRP91 / KRN92Consisting of:• Valve base with factory preset kv valve

– DN 15, both sides 3/4“ external thread with euro taper

– M30 x 1,5– nickel-plated, protective cap

• Return fitting with shut-off– DN 15, both sides 3/4“ external thread with euro

taper– nickel-plated

– ZV0110 0001 41,16

• VE 2,5 (white), kv value 0,30• Only for KRP91 / KRN92 / KRN81Consisting of:• Valve base with factory preset kv valve

– DN 15, both sides 3/4“ external thread with euro taper

– M30 x 1,5– nickel-plated, protective cap

• Return fitting with shut-off– DN 15, both sides 3/4“ external thread with euro

taper– nickel-plated

– ZV0110 0002 41,16

• VE 4,5 (red), kv value 0,54 • Only for KRP91 / KRN92 / KRN81 Consisting of:• Valve base with factory preset kv valve

– DN 15, both sides 3/4“ external thread with euro taper

– M30 x 1,5– nickel-plated, protective cap

• Return fitting with shut-off– DN 15, both sides 3/4“ external thread with euro

taper– nickel-plated

– ZV0110 0003 41,16

• VE 6 (black), kv value 0,98 • Only for KRP91 / KRN 81 / KC2 81 / KC4 81 Consisting of:• Valve base with factory preset kv valve

– DN 15, both sides 3/4“ external thread with euro taper

– M30 x 1,5– nickel-plated, protective cap

• Return fitting with shut-off– DN 15, both sides 3/4“ external thread with euro

taper– nickel-plated

– ZV0110 0004 41,16

• VE 8 (blue), kv value 1,43 • Only for KRN 81 / KC2 81 / KC4 81Consisting of:• Valve base with factory preset kv valve

– DN 15, both sides 3/4“ external thread with euro taper

– M30 x 1,5– nickel-plated, protective cap

• Return fitting with shut-off– DN 15, both sides 3/4“ external thread with euro

taper– nickel-plated

– ZV0110 0005 41,16

Page 31: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® eco Accessories

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 85

Acc

esso

ries

Accessories and miscellaneous

Connection set, angled form

ZV0109

• VE 6 (black), kvs value 0,98 • Only for KC2 81 / KC4 81Consisting of:• Valve base with factory preset kv valve

– DN 15, both sides 3/4“ external thread with euro taper

– M30 x 1,5– nickel-plated, protective cap

• Return fitting with shut-off– DN 15, both sides 3/4“ external thread with euro

taper– nickel-plated

– ZV0109 0001 41,16

• VE 8 (blue), kvs value 1,43 • Only for KC2 81 / KC4 81Consisting of:• Valve base with factory preset kv valve

– DN 15, both sides 3/4“ external thread with euro taper

– M30 x 1,5– nickel-plated, protective cap

• Return fitting with shut-off– DN 15, both sides 3/4“ external thread with euro

taper– nickel-plated

– ZV0109 0002 41,16

Flexible connection

ZT0110

• Incl. 2 double nipples and seals for euro taper• Corrugated hose , stainless steel, DN 16• Operating pressure 10 bar• Temperature resistance up to +90°C (briefly up to

+110°C)• Nuts: brass, internal thread 3/4“, spanner opening 30

mm• Seals: AFM 34• Oxygen diffusion-proof

L = 300 mm ZT0110 0001 28,81

L = 500 mm ZT0110 0002 31,90

Double nipple set

ZT0111 0001

• 2 pcs.• 3/4“ external thread to 3/4“ external thread

– ZT0111 0001 5,66

Air-intake filter

ZK0077

• For KRN 81• 1 roll (5 m)• PPI 30 dark 90x3 mm, with hook & loop strips (1,5 m)

for installation

– ZK0077 0001 22,64

• For KC2 81 / KC4 81• 1 roll (5 m)• PPI 30 dark 140x3 mm, with hook & loop strips (2 m)

for installation

– ZK0077 0002 26,75

Plastic fitting set

ZK0072

• Pipe penetration • For installation in the pipe penetration of the floor

pan (suitable for pipe diameter up to 20 mm)• 10 pcs.

– ZK0072 0001 14,41

• Cable penetration • For installation in the cable penetration of the floor

pan• 5 pcs.

– ZK0072 0002 10,29

Accessories–fittings

Description Product code Characteristic

DimensionsOrdering

code|LAE|

ProductVersion

Price [EUR]

Page 32: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® ecoAccessories

86 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Acc

esso

ries

Accessories and miscellaneous

Accessories-Control technique

Description Product code Characteristic

DimensionsOrdering

code|4|

ProductVersion

Ordering code

|3|Price[EUR]

Room thermo-stat

ZE0077

• Programmable room thermostat, incl. fan control• Only for KRN81 / KC281 / KC481• Temperature control unit, incl. fan control with large

liquid crystal display (LCD) for controlling up to 6 trench convectors

• Energy-saving, automatic blue backlighting• Programmable timer programs• Temperature range 9°C to 32°C• Settings 0,5°C• Frost protection temperature 8°C• Adjustable temperature offset +/5°C• Control of heating/cooling• Voltage supply via BUS cable<• Output relay 5 A• Protection type / protection class: IP30 / II• Plastic casing 81x135x22 for wall mounting (with and

without in-wall pattress box)• Colour similar to RAL9010

– ZE 0077 0003 125,54

• Digital room thermostat• Only for KRP91 / KRN92• Temperature control unit with digital temperature

display• 3 operating modes• Comfort and setback temperature adjustable from

5°C to 30°C• Frost protection temperature adjustable from 5°C to

15°C• Settings 0,5°C• Adjustable temperature offset +/5°C• Voltage supply via AAA batteries (2*1,5V)• Battery charge display, battery change from the front• Output relay 2 A• Protection type / protection class: IP30 / II• Plastic casing 80x80x23 for wall mounting (with and

without in-wall pattress box)• Colour similar to RAL9010

– ZE 0077 0001 68,94

• Programmable room thermostat• Only for KRP91 / KRN92• Temperature control unit with large liquid crystal

display (LCD)• Energy-saving, automatic blue backlighting• Programmable timer programs• 5 operating modes (comfort, set-back, frost protec-

tion, AUTO, Off)• Week or day programming• Voltage supply via AAA batteries (2*1,5V)• Battery charge display, battery change from the front

without loss of program• Output relay 2 A• Protection type / protection class: IP30 / II• Plastic casing 81x135x33 for wall mounting (with and

without in-wall pattress box)• Colour similar to RAL9010

– ZE 0077 0002 107,02

KNX plug-in card

ZE 0078 0001

• Only for KRN81 / KC281 / KC481• For installation on the ASCOTHERM eco control board

to connect to KNX networks, only 1 card needed per convector group (up to 6 convectors)

– ZE 0078 0001 139,94

Page 33: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® eco Accessories

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 87

Acc

esso

ries

Accessories and miscellaneous

Actuator

ZE 0087 0001

• Thermoelectric actuator 24 V DC• Only for KRN 81 / KC2 81 / KC4 81• Operating voltage 24 V DC• Control voltage 0-10 V DC• Power consumption 2 W• Current draw 80 mA• Inrush current max. 350 mA (max 2 min)• Protection type / protection class: IP 54 / III• Operating displacement 4 mm• Incl. VA80 valve adapter and 5 m connecting line• Currentless closed

– ZE 0087 0001 87,47

Actuator

ZE 0023 0001

• Thermoelectric actuator 230 V AC• Only for KRP91 / KRN 92• Operating voltage 230 V AC, 50/60 Hz• Power consumption 1 W• Inrush current max. 320 mA• Protection type / protection class: IP54 / II• Humidity max 80% non-condensing• Currentless closed

– ZE 0023 0001 29,84

Thermostat with fine adjustment

ZV0081 0001

• Only for KRP91 / KRN 92• Threaded connection M30 x 1,5• Capillary pipe 5 m long• casing, white• Temperature range 7 °C to 28 °C• Scaled cap

– 0 Frost protection– 1 - 5

• When a thermostat with remote control is used, other kv settings are needed for the valves; the valve inserts are preset for use with actuators as standard

– ZV0081 0001 94,67

External room temperature sensor

ZE 0080 0001

• Room temperature sensor NTC 10 K with plastic cap, incl. 3-m cable + installation material

– ZE 0080 0001 31,90

Pipe surface sensor

ZE0081

• For sensing the flow temperatures, incl. 2-m cable + installation material, for lengths up to 2000 mm

– ZE 0081 0001 36,02

• For sensing the flow temperatures, incl. 4-m cable + installation material, for lengths over 2000 mm

– ZE 0081 0002 39,10

Dew point monitor

ZE 0082 0001

• Supply voltage 24 V DC• Current draw max. 3 mA• Range 10% to 100% relative humidity• Switching point at 20°C: 90 +/ 3% relative humidity• Reaction time on change of pipe temperature:

t90 < 3 min.• Reaction time on change of room humidity: t90 < 25

sec.• Incl. cable penetration and circuit board plug

– ZE 0082 0001 143,03

Window contact sensor

ZE00830001

• Voltage supply 1 lithium battery 3 V, type CR2032, service life up to 2 years

• Transmission type X2D protocol• Radio frequency 868 MHz• Transmission range up to 300 m (in open area)• Protection type IP 40• Casing ABS/PC

– ZE 0083 0001 81,29

Accessories-Control technique

Description Product code Characteristic

DimensionsOrdering

code|4|

ProductVersion

Ordering code

|3|Price[EUR]

Page 34: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® ecoAccessories

88 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Acc

esso

ries

Accessories and miscellaneous

Assembling aids

Description

Product code Characteristic

DimensionsOrdering

code|4|

Surface / Finish

Ordering code|17|

ProductVersion

Ordering code

|3|Price[EUR]

Spray paint

ZK0002 0007

• RAL 7016 (matt) – Anthracite ZK0002 0007 16,98

Presence detector

ZE00840001

• Voltage supply 230 V with phase and neutral conduc-tor

• Radio frequency 868 MHz• 1 to 2 control channels, depending on function• 3 pre-installed cable for connection to the local

switch, button for up/down• 1 wired phase input from sensor or button• Up to 16 bidirectional RF receivers and any number of

unidirectional RF receivers• Operating temperature -5°C to 40°C• Dimensions: H 50 x B 47 x T 23 mm

– ZE 0084 0001 121,42

RF receiver

ZE 0085 0001

• For use with window contact sensor and presence detector

• Voltage supply via control board• Up to 2x20 transmitters applicable• Transmission range up to 100 m (open area)• Incl. 1-m cable + installation material

– ZE 0085 0001 183,16

Cable

ZE 0086 0001

• For use with RF receiver (ZE00850001)• Length 2 m

– ZE 0086 0001 12,35

Accessories-Control technique

Description Product code Characteristic

DimensionsOrdering

code|4|

ProductVersion

Ordering code

|3|Price[EUR]

Page 35: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® ecoFurther information

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 89

Furt

her

info

rmat

ion

Size and units of measurement

Size and units of measurement

Description Code Units

metre [m]

Millimetre [mm]

Kilogramme [kg]

Degree Celsius [°C]

Kelvin [K]

Joule [J]

Second [s]

Hour [h]

Pascal, kilopascal [Pa, kPa]

Length, height, depth L, H, T [mm]

Floor pan length Lfloor pan [mm]

Ribbed convector length Lribb. [mm]

floor pan height Hfloor pan [mm]

Register height Hreg. [mm]

floor pan depth Tfloor pan [mm]

Register depth Treg. [mm]

Mass M [kg]

Flow-, return temperature t1, t2 [°C]

Room temperature tr [°C]

Mean hot water temperature tm [°C]

Volume flow rate V [m3/h]

Velocity v [m/s]

Pressure loss ∆p [mbar]

Valve coefficient kV –

Adjustable valve coefficient kVS –

Operating pressure, test pressure, air pressure p [bar/Pa]

Sound pressure level Lp [dB/A]

Acoustic power level LW [dB/A]

Internal thread IG –

External thread AG –1) Maximum length: greatest possible length of a delivery unit

Page 36: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® ecoFurther information

90 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Furt

her

info

r-m

atio

n

Size and units of measurement

Size and units of measurement for heating

Description Code Units

Average heat transfer medium temperature EN 442 tm = t1 + t2

2[°C]

Over temperature ∆T [K]

Standard over temperature ΔTn = 49,83 K [K]

Heat output (Phi) Φ [W]

Standard heat output at 75 / 65 / 20 °C (∆T 50 K) (EN 442) Φs [W]

Specific standard heat output ΦL [W/m]

Specific heat capacity cp [J/kgK]

Radiator classification, exponent n –

Correction factor CK –

Water flow rate, standard water flow rate in accordance with EN 442

qm [kg/h]

spec. standard water flow rate according to EN 442 qms [kg/h m]

Size and units of measurement for cooling

Description Code Units

Mean cooling water temperature tm = t1 + t2

2[°C]

Under temperature difference ∆T [K]

Standard under temperature ∆Tn = 9,97 K [K]

Total cooling capacity PK [W]

Total standard cooling capacity PKN [W]

Sensible cooling capacity PS [W]

Sensible standard cooling capacity PSN [W]

Specific heat capacity cp [J/kgK]

Classification, exponent n –

Correction factor CK –

Water flow rate, standard water flow rate in accordance with EN 442

qm [kg/h]

spec. water flow, spec. standard water flow rate according to EN 442

qms [kg/h m]

Relative humidity ϕ [%]

Page 37: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® eco Further information

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 91

Furt

her

info

rmat

ion

Planning, assembly and installation information

Preliminary notes

General

Goods and services are provided exclusively on the basis of our General Terms of Sale, Delivery and Payment.

Technical data

The respective technical data refer to the standard version. Subject to changes and tolerances customary in the industry or necessary for production reasons.

Operating conditions

• For closed hot water heating systems in accordance with DIN 18380 and water quality in accordance with VDI 2035.

• Ascotherm eco trench convectors are not suitable for steam heating systems.

KRP91, KRN92

Company relevant characteristics

Standard version

High-pressure version

Operating pressure [bar (kPa)]

10,0 (1000) 16,0 (1600)

Test pressure [bar (kPa)] 13,0 (1300) 20,8 (2080)

Max. temperature [°C] 110 110

KRN81, KC281, KC481

Company relevant characteristics

Standard version

High-pressure version

Operating pressure [bar (kPa)]

10,0 (1000) 16,0 (1600)

Test pressure [bar (kPa)] 13,0 (1300) 20,8 (2080)

Max. temperature [°C] 90 90

Unless an operating pressure is specified, the standard version will be provided.

Water quality

Operating conditions for water quality in accordance with VDI 2035 must be maintained just as the industry-standard installati-on rules.

Warranty claims according to our General Terms of Sale, Delivery and Payment shall be invalid in the event of:

• periodic or extended draining of the system• operation with steam• addition of substances (e.g. chemicals, antifreeze) to the

heating water that can have a corrosive effect on copper or sealing materials

• excessive sludge deposition in the trench convector• occasional or constant drag-in of oxygen into the system (e.g.

lines and pipes that are not sealed against diffusion) • leaks in the heating system

Special versions according to drawings

If necessary, the customer receives a dimensional drawing for review and approval; the order will be produced after this is returned. In the event that the order is cancelled, the customer must pay compensation for the services and costs incurred up to that point.

Paint finishes

Stoved enamel powder coating (packaged) in all RAL colours according to customer specifications; colour deviations customary in the industry are possible.

Use only original RAL colour samples for colour matching.

For production reasons, paint finishes are subject to slight colour deviations, caused in part by specific light conditions. There may also be differences when comparing painted surfaces with painted ceramic products. Because of limitations in the printing process, the illustrated colours are not binding.

The floor pans and possibly aluminium grilles are finished in accordance with DIN 55900. They must be transported with care and protected against damage at the construction site.

Noises

Noise emission depends on the design, size and fan speed. The acoustic power levels were measured using DIN 45635-1 as a reference.

According to E DIN EN 16430-1 (Fan-assisted radiators, convectors and trench convectors - Part 1: Technical specifications and requi-rements), the sound pressure level can be defined with a room absorption of 8 dB(A). This corresponds to a distance of 2 m from the tested unit, a room volume of 100 m3 and a reverberation time of 0,5 s.

The acoustic characteristics of the room influence the noise level. Accordingly, the actual values may differ. It is recommended that the Ascotherm eco be designed for operation at a moderate speed.

Page 38: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® ecoFurther information

92 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Furt

her

info

r-m

atio

n

Planning, assembly and installation information

Acoustic

Sources of noise cause the air to oscillate; it compresses and expands alternately.

These pressure changes dither the existing air pressure and pro-pagated through the air in sinusoidal form. When these pressure fluctuations reach our ear, the air pressure waves are transfor-med into mechanical vibrations by the eardrum.

The process of hearing is begun.

The human ear only senses the airborne sound; the following two factors are decisive:

a: Sound pressure

b: Frequency

1. Sound pressure

The sound pressure is the change in pressure of the air caused by a sound source. These pressure fluctuations are measured in N/m², and are designated with the letter p.

The sound pressure is a measure of the sound level. It depends on the distance between the sound source and the measurement location as well as the properties of the room.

The sound pressure is unsuitable for calculating the expansion of sound on the sound propagation paths. For this it is necessary to determine the acoustic power of the sound source.

2. Acoustic power

The energy converted into sound by a component (sound source) is called acoustic power. This acoustic power is transmitted to the air in the form of pressure fluctuations.

The acoustic power is a value that cannot be measured directly. It is determined by integrating the acoustic pressure over a hemis-pherical or spherical surface about the sound source.

The acoustic power is thus a value that is independent of space and distance.

It will be used for all of the following calculations.

The acoustic power is stated in watt [W].

For practical use, dimensionless figures have been introduced based on the work of A. G. Bell.

3. Sound pressure level

The logarithmic relationship of a sound pressure p to the refe-rence value p0 is designated acoustic pressure level LP; the unit used to specify it is the decibel [dB].

Lp = 10 lg ( p )2

p0

p = Effective value of the sound pressure at a certain spot in the room

p0 = Reference sound pressure, specified internationally at 2 x 10-5 N/m²

4. Acoustic power level

The acoustic power level LW is defined by:

LW = 10 lg ( P ) in dBP0

P = Acoustic power in watts

P0 = Reference power, specify internationally at 1 x 10-12 watts

The sound pressure level is the sound generated at the sound source (the energy transmitted to the air), while the acoustic pressure level is the sound registered at a certain distance from the sound source.

Thus generally the acoustic power level is larger than the acoustic pressure level.

5. Frequency assessment

Humans perceive the same sound pressure level differently at dif-ferent frequencies. A sound pressure level is generally perceived as quieter and less annoying at low frequencies than at higher frequencies.

In order to take this subjective perception into account, the objectively measured sound pressure levels are adapted to the perception of sound levels. This is called assessment of the sound pressure level.

This assessment is done by subtracting a certain amount from the measured sound pressure level for frequencies that humans are less sensitive to, while adding a certain amount in the other frequency ranges.

Of the various assessments, the A-weighting has become virtually the only one used.

This provides information in the form of a single figure that is designated as an A-weighted acoustic pressure level or an A-weighted sound pressure power.

The unit is called db[A].

6. Sound level additions

If several sound sources are present, then the corresponding levels have to be added to form a total sound level.

The same principles apply here for both the sound pressure level and the acoustic power level.

When there is more than one sound source with the same level, the following relationship applies:

Ltot = L1 + 10 x log n [dB]

Page 39: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 93

Furt

her

info

rmat

ion

Planning, assembly and installation information

Ascotherm® eco Further information

Calculation: General informationCalculation of the heating requirements of buildings is perfor-med according to the standard DIN EN 12831.

Basic principles heat outputsThe heat outputs of Ascotherm eco trench convectors were measured and established in accordance with E DIN EN 16430 "Fan-assisted radiators, convectors and trench convectors" Part 1: "Technical specifications and requirements" and Part 2 "Test method and rating for thermal output".

Standard heat output ΦS (∆T = 50 K)

The standard heat output ΦS in watts of a radiator indicates the heat flow that is emitted under the following conditions:

- Flow temperature t1 = 75 °C

- Return temperature t2 = 65 °C

- Room temperature tr = 20 °C

- Air pressure p = 1013 hPa

From this follows the average heating water temperature tm in °C.

tr

t1 t2

tm

tm =t1 + t2

=75 + 65

= 70 °C2 2

Calculation

Heat output Φ (deviation from ∆T = 50 K)

For over temperature ∆T deviating from ∆T = 50 K, the heat out-put is calculated as follows:

Φ = ΦS x∆T

n

or Φ = ΦS x CK∆Tn

where n = exponent and CK = correction factor of the heat output characteristic curve (see technical data of the radiators). The over temperature ∆T should be calculated logarithmically as follows:

∆T =(t1 - tr) - (t2 - tr)

=(t1 - t2)

ln(t1 - tr)

ln(t1 - tr)

(t2 - tr) (t2 - tr)

The over temperature ∆T for normal conditions (75 / 65 / 20 °C) is the following as a logarithmic over temperature :

∆Tn =75- 65

= 49.83 K

ln75 - 2065 - 20

Calculation example

KRP91 with L = 3000 mm; H = 120 mm; T = 260 mm

Ascotherm eco:

- Standard heat output ΦS = 1288 watts- Exponent n = 1,43

Operating conditions:

- Flow temperature t1 = 65 °C

- Return temperature t2 = 50 °C

- Room temperature tr = 20 °C

∆T =65 - 50

=15

=15

=15

= 36,99 K

ln65 - 20

ln45 ln1,5 0,4055

50 - 20 30

Φ = ΦS x CK = 1089 x36,99

1,43

= 1288 x 0,653 = 841 W49,83

Page 40: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

94 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Furt

her

info

r-m

atio

n

Planning, assembly and installation information

Ascotherm® ecoFurther information

Water flow

Minimum water flow rate

In order to guarantee even temperature distribution in the radi-ator and thus proper heat emission, a minimum water flow must be assured.

For each version, the specific standard water flow rate qms is stated in the performance tables.

The water flow is calculated as follows:

qm [kg/h] =Φ

1,16 x (t1 - t2)

Calculation example

KRP91 with L = 3000 mm; H = 110 mm; T = 260 mm

Φs = 1288 W t1 = 75 °C t2 = 65 °C tr = 20 °C

qm =1288 W

= 111,0 kg/h 1,16 x (75-65)

Calculation example

Φ = 841 W t1 = 65 °C t2 = 50 °C tr = 20 °C

qm =841 W

= 48,3 kg/h 1.16 x (65-50)

Simplified dimensioning

Calculation:

1) Take exponent from table

2) Determine over temperature

3) Determine factor CK from the correction factor table

4) Calculate standard heat output as follows:

Φs =Φ desired

CK

5) Compare calculated value ΦS with table value Φ ∆T 50 K and select corresponding version

Example:

- Flow temperature t1 = 65 °C

- Return temperature t2 = 55 °C

- Room temperature tr = 20 °C

- Desired heat output Φ = 1800 W- Maximum dimensions L = 4500 mm

H = 200 mm T = 360 m

1) n = 1,37

2) Over temperature at 65/55/20 °C = 39,8 K ∼ 40 K3) Factor CK 65/55/20 = 0,7400

4)Φs =

Φ desired=

1800 W= 2432 W

Ck 0,7400

5) KRP91 with L = 4250 mm, H = 150 mm, T = 260 mm, ΦS = 2575 W ≥ 2432 W

or

KRP91 with

L = 3250 mm, H = 200 mm, T = 310 mm, ΦS = 2520 W ≥ 2432 W

Page 41: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 95

Furt

her

info

rmat

ion

Planning, assembly and installation information, cooling outputs

Ascotherm® eco Further information

Calculation: General informationThe cooling load of buildings is calculated on the basis of VDI 2078.

Basic principles, cooling outputsThe cooling outputs of Ascotherm eco trench convectors were measured and established in accordance with E DIN EN 16430 "Fan-assisted radiators, convectors and trench convectors" Part 1: "Technical specifications and requirements" and Part 3 "Test method and rating for cooling outputs".

Standard cooling output PKN (∆T = 10 K)

The cold air flow generated under the following conditions is designated the total standard cooling output PKN in watts of an Ascotherm eco:

t1 [°C] = Cool water inflow t1 = 16 °C

t2 [°C] = Cool water outflow t2 = 18 °C

tr [°C] = Room temperature tr = 27 °C

Air pressure p = 1013 hPa

Relative humidity ϕ = 50 %

This produces the average cooling water temperature tm in °C.

tm =t1 + t2

=16 + 18

= 17 °C2 2

Calculation

Cooling output PK (when deviating from ∆T = 10 K)

For temperature loss ∆T that deviate from ∆T = 10 K, the cooling output is calculated as follows:

PK = PKN x∆T

n

or PK = PKN x CK∆Tn

where n = exponent and CK = correction factor of the heat out-put characteristic (see technical data). The temperature diffe-rence ∆T should be calculated logarithmically as follows:

∆T =(t1 - tr) - (t2 - tr)

=(t1 - t2)

ln(t1 - tr)

ln(t1 - tr)

(t2 - tr) (t2 - tr)

The under temperature ∆T under standard conditions (16 / 18 / 27 °C) corresponds to the following logarithmic under temperature :

∆Tn =16- 18

= 9,97 K

ln16 - 2718 - 27

Calculation example

KC281 with L = 2000 mm; H = 130 mm; T = 310 mm

Ascotherm eco:

- Total standard cooling output

PKN = 882 watts

- Exponent n = 1,00

- Control voltage 5 V

Operating conditions:

- Flow temperature t1 = 17 °C

- Return temperature t2 = 19 °C

- Room temperature tr = 26 °C

∆T =17 - 19

=2

=2

=2

= 7,96 K

ln17 - 26

ln9 ln1,29 0,2513

19 - 26 7

PK = PKN x CK = 882 x7,96

1,00

= 882 x 0,7984 = 704 W9,97

Page 42: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

96 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Furt

her

info

r-m

atio

n

Planning, assembly and installation information, cooling outputs

Ascotherm® ecoFurther information

Water flowFormula for calculating the water flow qm.

qm [kg/h] = PK [W]

1,16 (t2 - t1)

For each version<, the specific standard water flow rate qms is stated in the performance tables.

Calculation example

KC281 with L = 2000 mm, H = 130 mm, T = 310 mm

PKN = 882 W t1 = 16 °C<t2 = 18

°Ctr = 27 °C

qm =882 W

= 380 kg/h 1,16 x (18-16)

Calculation example

PK = 704 W t1 = 17 °C t2 = 19 °C tr = 26 °C

qm =704 W

= 303,45 kg/h 1,16 x (19-17)

Simplified dimensioning

Calculation:

1) Take exponent from table For approximate calculation n = 1,00

2) Determine under temperature

3) Determine factor CK from the correction factor table

4) Calculate standard cooling output as follows:

PKN =Pdesired

CK

5) Compare calculated value PKN with table value and select appropriate version

Example:

- Flow temperature t1 = 17 °C

- Return temperature t2 = 19 °C

- Room temperature tr = 26 °C

- Desired cooling output Pdesired = 1000 W

- Desired version KC 281

- Maximum dimensions L = 2000 mm H = 155 mm T = 360 m

1) n = 1,00

2) Under temperature at 17/19/26 °C = 7,96 K ∼ 8 K3) Factor CK 17/19/26 = 0,8024

4)PKN=

Pdesired=

1000 W= 1246 W

Ck 0,8024

5) KC281 with L = 2000 mm, H = 155 mm, T = 360 mm,

Dimensioning with control voltage of 5 V PKN = 1256 W ≥ 1246 W

or

KC281 with L = 2000 mm, H = 130 mm, T = 310 mm,

Dimensioning with control voltage of 7 V PKN = 1336 W ≥ 1246 W

Note regarding "Basics of cooling outputs":

The calculations above are for a dimensioning with dry cooling. If system parameters that result in condensation on the cooling register are intentionally selected during planning, the sensible cooling output needs to be considered in addition to the total cooling output. In this case, the sensible cooling output is the determining factor for performance the cooling load.

Page 43: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 97

Furt

her

info

rmat

ion

Planning, assembly and installation information, cooling outputs

Ascotherm® eco Further information

Air tempera-ture

[°C]

Dew point temperature in °C at a relative humidity of

10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

5 -24,0 -15,9 -11,2 -7,6 -4,6 -2,2 -0,1 +1,8 +3,5 +5,0

6 -23,1 -15,0 -10,3 -6,6 -3,7 -1,3 +0,8 +2,8 +4,5 +6,0

7 -22,3 -14,2 -9,4 -5,7 -2,8 -0,4 +1,8 +3,8 +5,5 +7,0

8 -21,6 -13,5 -8,5 -4,8 -1,8 +0,6 +2,8 +4,8 +6,5 +8,0

9 -21,0 -12,8 -7,6 -3,8 -0,8 +1,6 +3,8 +5,8 +7,4 +9,0

10 -20,2 -12,0 -6,7 -2,9 +0,1 +2,5 +4,8 +6,8 +8,4 +10,0

11 -19,5 -11,1 -5,9 -2,0 +0,9 +3,5 +5,7 +7,8 +9,4 +11,0

12 -18,7 -10,2 -5,0 -1,2 +1,7 +4,4 +6,6 +8,7 +10,4 +12,0

13 -17,9 -9,4 -4,2 -0,3 +2,6 +5,3 +7,5 +9,7 +11,4 +13,0

14 -17,2 -8,6 -3,3 +0,6 +3,5 +6,2 +8,5 +10,6 +12,3 +14,0

15 -16,5 -7,8 -2,4 +1,5 +4,5 +7,2 +9,5 +11,6 +13,3 +15,0

16 -15,7 -6,9 -1,5 +2,4 +5,5 +8,1 +10,5 +12,6 +14,3 +16,0

17 -14,9 -6,0 -0,7 +3,3 +6,5 +9,1 +11,5 +13,5 +15,3 +17,0

18 -14,1 -5,2 +0,2 +4,2 +7,4 +10,1 +12,4 +14,5 +16,3 +18,0

19 -13,2 -4,5 +1,0 +5,1 +8,3 +11,0 +13,4 +15,4 +17,3 +19,0

20 -12,5 -3,6 +1,9 +6,0 +9,3 +12,0 +14,3 +16,4 +18,3 +20,0

21 -11,7 -2,8 +2,7 +6,8 +10,2 +12,9 +15,3 +17,4 +19,3 +21,0

22 -11,0 -2,0 +3,6 +7,7 +11,1 +13,9 +16,3 +18,3 +20,3 +22,0

23 -10,3 -1,2 +4,5 +8,6 +12,1 +14,7 +17,2 +19,3 +21,2 +23,0

24 -9,6 -0,3 +5,4 +9,5 +12,9 +15,7 +18,2 +20,3 +22,2 +24,0

25 -8,8 +0,5 +6,3 +10,4 +13,8 +16,7 +19,2 +21,3 +23,2 +25,0

26 -8,0 +1,3 +7,1 +11,3 +14,8 +17,7 +20,2 +22,3 +24,2 +26,0

27 -7,3 +2,1 +7,9 +12,2 +15,8 +18,5 +21,0 +23,2 +25,2 +27,0

28 -6,5 +3,0 +8,7 +13,1 +16,7 +19,5 +22,0 +24,2 +26,2 +28,0

29 -5,7 +3,8 +9,6 +14,0 +17,5 +20,4 +23,0 +25,2 +27,2 +29,0

30 -5,0 +4,6 +10,5 +14,9 +18,4 +21,4 +24,0 +26,2 +28,2 +30,0

Example of system dimensioning under normal conditions

Dew point tableFor a correct dry cooling dimensioning without condensation, the flow temperature of the cool water needs to be taken into account. The flow temperature of the cooling water can be taken as the lowest possible surface temperature of fin compon-ents. Assuming normal conditions (room air temperature 27 °C, relative humidity 50%), the

dew point will be 15.8 °C. This means that condensation can be expected if the flow temperature of the cool water drops below 15.8 °C. Beneficial drying effects associated with fan operation are not taken into account, since this effect depends largely on the fan speed.

Page 44: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

98 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Furt

her

info

r-m

atio

n

Planning, assembly and installation information

Ascotherm® ecoFurther information

Over temperatures ∆T (logarithmic calculation)

Flow temperature

t1 °C

Room temperature

tr °C

Return temperature t2 °C

30 35 40 45 50 55 60 65 70 75

90 24 30,7 35,3 39,3 42,9 46,3 49,5 52,5 55,4 58,2

22 33,2 37,6 41,5 45,1 48,4 51,6 54,5 57,4 60,2

20 30,8 35,7 39,9 43,7 47,2 50,5 53,6 56,6 59,4 62,2

18 33,5 38,1 42,2 45,9 49,3 52,6 55,7 58,6 61,5 64,2

15 37,3 41,6 45,5 49,1 52,5 55,7 58,7 61,7 64,5 67,2

85 24 29,2 33,6 37,5 41,0 44,3 47,4 50,3 53,1 55,9

22 31,7 35,9 39,7 43,2 46,4 49,5 52,4 55,2 57,9

20 29,4 34,1 38,2 41,9 45,3 48,5 51,5 54,4 57,2 59,9

18 32,0 36,5 40,4 44,0 47,4 50,5 53,5 56,4 59,2 61,9

15 35,7 39,9 43,7 47,2 50,5 53,6 56,6 59,4 62,2 64,9

80 24 27,7 31,9 35,7 39,1 42,3 45,3 48,1 50,8 53,5

22 30,1 34,2 37,8 41,2 44,3 47,3 50,1 52,8 55,5

20 27,9 32,5 36,4 40,0 43,3 46,4 49,3 52,1 54,8 57,5

18 30,4 34,8 38,6 42,1 45,4 48,4 51,4 54,2 56,9 59,5

15 34,1 38,2 41,9 45,3 48,5 51,5 54,4 57,2 59,9 62,5

75 24 26,1 30,2 33,8 37,1 40,2 43,1 45,8 48,5

22 28,5 32,4 35,9 39,2 42,2 45,1 47,8 50,5

20 26,4 30,8 34,6 38,0 41,2 44,2 47,1 49,8 52,5

18 28,9 33,1 36,8 40,1 43,3 46,3 49,1 51,8 54,5

15 32,5 36,4 40,0 43,3 46,4 49,3 52,1 54,8 57,5

70 24 24,5 28,4 31,9 35,1 38,0 40,8 43,5

22 26,8 30,6 34,0 37,1 40,0 42,8 45,5

20 24,9 29,1 32,7 36,1 39,2 42,1 44,8 47,5

18 27,3 31,3 34,9 38,1 41,2 44,1 46,8 49,5

15 30,8 34,6 38,0 41,2 44,2 47,1 49,8 52,5

65 24 22,8 26,6 29,9 32,9 35,8 38,4

22 25,1 28,7 32,0 35,0 37,8 40,4

20 23,3 27,3 30,8 34,0 37,0 39,8 42,5

18 25,6 29,5 32,9 36,1 39,0 41,8 44,5

15 29,1 32,7 36,1 39,2 42,1 44,8 47,5

60 24 21,1 24,7 27,8 30,7 33,4

22 23,3 26,8 29,9 32,7 35,4

20 21,6 25,5 28,9 31,9 34,8 37,4

18 23,9 27,6 30,9 33,9 36,8 39,4

15 27,3 30,8 34,0 37,0 39,8 42,5

55 24 19,3 22,7 25,7 28,4

22 21,5 24,7 27,7 30,4

20 20,0 23,6 26,8 29,7 32,4

18 22,2 25,7 28,9 31,7 34,4

15 25,5 28,9 31,9 34,8 37,4

50 24 17,4 20,6 23,4

22 19,6 22,6 25,4

20 18,2 21,6 24,7 27,4

18 20,4 23,7 26,7 29,4

15 23,6 26,8 29,7 32,4

45 24 15,5 18,4

22 17,5 20,4

20 16,4 19,6 22,4

18 18,5 21,6 24,4

15 21,6 24,7 27,4

Page 45: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 99

Furt

her

info

rmat

ion

Planning, assembly and installation information, heat output correction factors

Ascotherm® eco Further information

Correction factors CK (logarithmic calculation)

∆T [K]Exponent n

∆T [K]1,00 1,28 1,29 1,30 1,31 1,32 1,33 1,34 1,35 1,36 1,37 1,38 1,39

10 0,2007 0,1280 0,1260 0,1239 0,1220 0,1200 0,1181 0,1162 0,1144 0,1126 0,1108 0,1090 0,1073 1011 0,2207 0,1446 0,1424 0,1403 0,1382 0,1361 0,1341 0,1321 0,1301 0,1281 0,1262 0,1243 0,1225 1112 0,2408 0,1616 0,1593 0,1571 0,1549 0,1527 0,1505 0,1484 0,1463 0,1442 0,1422 0,1402 0,1382 1213 0,2609 0,1791 0,1767 0,1743 0,1720 0,1697 0,1674 0,1652 0,1630 0,1608 0,1587 0,1566 0,1545 1314 0,2809 0,1969 0,1944 0,1920 0,1895 0,1871 0,1848 0,1824 0,1801 0,1779 0,1756 0,1734 0,1712 1415 0,3010 0,2151 0,2125 0,2100 0,2075 0,2050 0,2025 0,2001 0,1977 0,1954 0,1930 0,1907 0,1885 1516 0,3211 0,2336 0,2310 0,2283 0,2258 0,2232 0,2207 0,2182 0,2157 0,2133 0,2109 0,2085 0,2061 1617 0,3411 0,2524 0,2497 0,2471 0,2444 0,2418 0,2392 0,2367 0,2341 0,2316 0,2291 0,2267 0,2243 1718 0,3612 0,2716 0,2688 0,2661 0,2634 0,2608 0,2581 0,2555 0,2529 0,2504 0,2478 0,2453 0,2428 1819 0,3813 0,2911 0,2883 0,2855 0,2828 0,2800 0,2774 0,2747 0,2721 0,2695 0,2669 0,2643 0,2618 19

20 0,4013 0,3108 0,3080 0,3052 0,3024 0,2997 0,2969 0,2942 0,2916 0,2889 0,2863 0,2837 0,2811 2021 0,4214 0,3308 0,3280 0,3252 0,3224 0,3196 0,3169 0,3141 0,3114 0,3087 0,3061 0,3035 0,3008 2122 0,4415 0,3511 0,3483 0,3454 0,3426 0,3398 0,3371 0,3343 0,3316 0,3289 0,3262 0,3236 0,3209 2223 0,4615 0,3717 0,3688 0,3660 0,3632 0,3604 0,3576 0,3548 0,3521 0,3494 0,3467 0,3440 0,3414 2324 0,4816 0,3925 0,3897 0,3868 0,3840 0,3812 0,3784 0,3757 0,3729 0,3702 0,3675 0,3649 0,3622 2425 0,5017 0,4136 0,4107 0,4079 0,4051 0,4023 0,3995 0,3968 0,3941 0,3914 0,3887 0,3860 0,3833 2526 0,5217 0,4349 0,4320 0,4292 0,4265 0,4237 0,4209 0,4182 0,4155 0,4128 0,4101 0,4075 0,4048 2627 0,5418 0,4564 0,4536 0,4508 0,4481 0,4453 0,4426 0,4399 0,4372 0,4345 0,4319 0,4292 0,4266 2728 0,5619 0,4781 0,4754 0,4726 0,4699 0,4672 0,4645 0,4619 0,4592 0,4566 0,4540 0,4513 0,4487 2829 0,5819 0,5001 0,4974 0,4947 0,4920 0,4894 0,4867 0,4841 0,4815 0,4789 0,4763 0,4737 0,4712 2930 0,6020 0,5223 0,5196 0,5170 0,5144 0,5118 0,5092 0,5066 0,5040 0,5015 0,4990 0,4964 0,4939 3031 0,6221 0,5447 0,5421 0,5395 0,5370 0,5344 0,5319 0,5294 0,5269 0,5244 0,5219 0,5194 0,5169 3132 0,6421 0,5672 0,5647 0,5622 0,5598 0,5573 0,5548 0,5524 0,5499 0,5475 0,5451 0,5427 0,5403 3233 0,6622 0,5900 0,5876 0,5852 0,5828 0,5804 0,5780 0,5756 0,5733 0,5709 0,5685 0,5662 0,5639 3334 0,6823 0,6130 0,6107 0,6083 0,6060 0,6037 0,6014 0,5991 0,5968 0,5946 0,5923 0,5900 0,5878 3435 0,7023 0,6362 0,6339 0,6317 0,6295 0,6273 0,6250 0,6228 0,6206 0,6185 0,6163 0,6141 0,6119 3536 0,7224 0,6595 0,6574 0,6553 0,6531 0,6510 0,6489 0,6468 0,6447 0,6426 0,6405 0,6384 0,6364 3637 0,7425 0,6831 0,6811 0,6790 0,6770 0,6750 0,6730 0,6710 0,6690 0,6670 0,6650 0,6630 0,6611 3738 0,7625 0,7068 0,7049 0,7030 0,7011 0,6992 0,6973 0,6954 0,6935 0,6916 0,6898 0,6879 0,6860 3839 0,7826 0,7307 0,7289 0,7271 0,7254 0,7236 0,7218 0,7200 0,7183 0,7165 0,7148 0,7130 0,7113 3940 0,8027 0,7548 0,7531 0,7515 0,7498 0,7482 0,7465 0,7449 0,7432 0,7416 0,7400 0,7384 0,7367 4041 0,8227 0,7790 0,7775 0,7760 0,7745 0,7730 0,7714 0,7699 0,7684 0,7669 0,7655 0,7640 0,7625 4142 0,8428 0,8034 0,8020 0,8007 0,7993 0,7979 0,7966 0,7952 0,7939 0,7925 0,7911 0,7898 0,7884 4243 0,8629 0,8280 0,8268 0,8255 0,8243 0,8231 0,8219 0,8207 0,8195 0,8183 0,8171 0,8159 0,8147 4344 0,8830 0,8527 0,8516 0,8506 0,8495 0,8485 0,8474 0,8464 0,8453 0,8443 0,8432 0,8422 0,8411 4445 0,9030 0,8776 0,8767 0,8758 0,8749 0,8740 0,8731 0,8722 0,8713 0,8705 0,8696 0,8687 0,8678 4546 0,9231 0,9026 0,9019 0,9012 0,9005 0,8997 0,8990 0,8983 0,8976 0,8969 0,8962 0,8954 0,8947 4647 0,9432 0,9278 0,9273 0,9267 0,9262 0,9257 0,9251 0,9246 0,9240 0,9235 0,9229 0,9224 0,9219 4748 0,9632 0,9532 0,9528 0,9525 0,9521 0,9517 0,9514 0,9510 0,9507 0,9503 0,9500 0,9496 0,9492 4849 0,9833 0,9787 0,9785 0,9783 0,9782 0,9780 0,9778 0,9777 0,9775 0,9773 0,9772 0,9770 0,9768 4950 1,0034 1,0043 1,0043 1,0044 1,0044 1,0044 1,0045 1,0045 1,0045 1,0046 1,0046 1,0046 1,0047 5051 1,0234 1,0301 1,0303 1,0306 1,0308 1,0310 1,0313 1,0315 1,0317 1,0320 1,0322 1,0325 1,0327 5152 1,0435 1,0560 1,0564 1,0569 1,0573 1,0578 1,0582 1,0587 1,0592 1,0596 1,0601 1,0605 1,0610 5253 1,0636 1,0821 1,0827 1,0834 1,0841 1,0847 1,0854 1,0861 1,0867 1,0874 1,0881 1,0888 1,0894 5354 1,0836 1,1083 1,1092 1,1100 1,1109 1,1118 1,1127 1,1136 1,1145 1,1154 1,1163 1,1172 1,1181 5455 1,1037 1,1346 1,1357 1,1368 1,1380 1,1391 1,1402 1,1413 1,1425 1,1436 1,1447 1,1459 1,1470 5556 1,1238 1,1611 1,1624 1,1638 1,1651 1,1665 1,1679 1,1692 1,1706 1,1720 1,1733 1,1747 1,1761 5657 1,1438 1,1877 1,1893 1,1909 1,1925 1,1941 1,1957 1,1973 1,1989 1,2005 1,2021 1,2037 1,2054 5758 1,1639 1,2144 1,2163 1,2181 1,2200 1,2218 1,2237 1,2255 1,2274 1,2293 1,2311 1,2330 1,2349 5859 1,1840 1,2413 1,2434 1,2455 1,2476 1,2497 1,2518 1,2539 1,2560 1,2582 1,2603 1,2624 1,2646 5960 1,2040 1,2683 1,2706 1,2730 1,2754 1,2777 1,2801 1,2825 1,2849 1,2873 1,2896 1,2920 1,2944 6061 1,2241 1,2954 1,2980 1,3006 1,3033 1,3059 1,3086 1,3112 1,3139 1,3165 1,3192 1,3219 1,3245 6162 1,2442 1,3226 1,3255 1,3284 1,3313 1,3342 1,3372 1,3401 1,3430 1,3460 1,3489 1,3518 1,3548 6263 1,2642 1,3500 1,3532 1,3564 1,3595 1,3627 1,3659 1,3691 1,3723 1,3756 1,3788 1,3820 1,3853 6364 1,2843 1,3775 1,3809 1,3844 1,3879 1,3913 1,3948 1,3983 1,4018 1,4053 1,4089 1,4124 1,4159 6465 1,3044 1,4051 1,4088 1,4126 1,4163 1,4201 1,4239 1,4277 1,4315 1,4353 1,4391 1,4429 1,4468 6566 1,3244 1,4328 1,4369 1,4409 1,4450 1,4490 1,4531 1,4572 1,4613 1,4654 1,4695 1,4737 1,4778 6667 1,3445 1,4607 1,4650 1,4694 1,4737 1,4781 1,4825 1,4869 1,4913 1,4957 1,5001 1,5046 1,5090 6768 1,3646 1,4886 1,4933 1,4979 1,5026 1,5073 1,5120 1,5167 1,5214 1,5261 1,5309 1,5356 1,5404 6869 1,3846 1,5167 1,5217 1,5266 1,5316 1,5366 1,5416 1,5466 1,5517 1,5567 1,5618 1,5669 1,5720 69

Page 46: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

100 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Furt

her

info

r-m

atio

n

Planning, assembly and installation information, heat output correction factors

Ascotherm® ecoFurther information

Correction factors CK (logarithmic calculation)

∆T [K]Exponent n

∆T [K]1,40 1,41 1,42 1,43 1,44 1,45 1,47 1,48 1,49 1,65 1,70 1,72 1,93

10 0,1056 0,1039 0,1022 0,1006 0,0990 0,0974 0,0943 0,0928 0,0913 0,0706 0,0652 0,0631 0,0451 1011 0,1206 0,1188 0,1170 0,1153 0,1135 0,1118 0,1085 0,1069 0,1053 0,0827 0,0767 0,0744 0,0542 1112 0,1362 0,1343 0,1324 0,1306 0,1287 0,1269 0,1233 0,1216 0,1199 0,0954 0,0889 0,0864 0,0641 1213 0,1524 0,1504 0,1484 0,1464 0,1444 0,1425 0,1387 0,1369 0,1350 0,1089 0,1018 0,0991 0,0748 1314 0,1691 0,1669 0,1648 0,1627 0,1607 0,1587 0,1547 0,1527 0,1508 0,1231 0,1155 0,1126 0,0863 1415 0,1862 0,1840 0,1818 0,1796 0,1775 0,1754 0,1712 0,1692 0,1671 0,1379 0,1299 0,1268 0,0985 1516 0,2038 0,2015 0,1992 0,1970 0,1948 0,1926 0,1882 0,1861 0,1840 0,1534 0,1450 0,1417 0,1116 1617 0,2219 0,2195 0,2172 0,2148 0,2125 0,2103 0,2058 0,2036 0,2014 0,1696 0,1607 0,1573 0,1255 1718 0,2404 0,2379 0,2355 0,2331 0,2308 0,2284 0,2238 0,2216 0,2193 0,1863 0,1771 0,1735 0,1401 1819 0,2593 0,2568 0,2543 0,2519 0,2494 0,2471 0,2423 0,2400 0,2377 0,2037 0,1941 0,1904 0,1555 19

20 0,2786 0,2760 0,2735 0,2710 0,2686 0,2661 0,2613 0,2589 0,2566 0,2217 0,2118 0,2080 0,1717 2021 0,2983 0,2957 0,2931 0,2906 0,2881 0,2856 0,2807 0,2783 0,2759 0,2403 0,2301 0,2262 0,1887 2122 0,3183 0,3157 0,3132 0,3106 0,3081 0,3056 0,3006 0,2982 0,2957 0,2595 0,2491 0,2450 0,2064 2223 0,3388 0,3362 0,3336 0,3310 0,3284 0,3259 0,3209 0,3184 0,3160 0,2792 0,2686 0,2645 0,2249 2324 0,3596 0,3569 0,3543 0,3518 0,3492 0,3467 0,3416 0,3391 0,3367 0,2995 0,2888 0,2846 0,2441 2425 0,3807 0,3781 0,3755 0,3729 0,3703 0,3678 0,3628 0,3603 0,3578 0,3204 0,3095 0,3053 0,2641 2526 0,4022 0,3996 0,3970 0,3944 0,3919 0,3893 0,3843 0,3818 0,3793 0,3418 0,3309 0,3266 0,2849 2627 0,4240 0,4214 0,4189 0,4163 0,4138 0,4112 0,4062 0,4037 0,4013 0,3638 0,3528 0,3485 0,3064 2728 0,4462 0,4436 0,4411 0,4385 0,4360 0,4335 0,4285 0,4261 0,4236 0,3863 0,3753 0,3710 0,3287 2829 0,4686 0,4661 0,4636 0,4611 0,4586 0,4561 0,4512 0,4488 0,4463 0,4093 0,3984 0,3941 0,3517 2930 0,4914 0,4889 0,4865 0,4840 0,4815 0,4791 0,4743 0,4719 0,4695 0,4329 0,4220 0,4178 0,3755 3031 0,5145 0,5121 0,5096 0,5072 0,5048 0,5024 0,4977 0,4953 0,4930 0,4569 0,4462 0,4420 0,4001 3132 0,5379 0,5355 0,5331 0,5308 0,5284 0,5261 0,5215 0,5192 0,5169 0,4815 0,4710 0,4668 0,4253 3233 0,5616 0,5593 0,5570 0,5547 0,5524 0,5501 0,5456 0,5433 0,5411 0,5066 0,4962 0,4922 0,4514 3334 0,5855 0,5833 0,5811 0,5789 0,5766 0,5744 0,5701 0,5679 0,5657 0,5322 0,5221 0,5181 0,4781 3435 0,6098 0,6076 0,6055 0,6034 0,6012 0,5991 0,5949 0,5928 0,5907 0,5582 0,5485 0,5446 0,5056 3536 0,6343 0,6323 0,6302 0,6282 0,6261 0,6241 0,6200 0,6180 0,6160 0,5848 0,5754 0,5716 0,5339 3637 0,6591 0,6572 0,6552 0,6533 0,6513 0,6494 0,6455 0,6436 0,6417 0,6118 0,6028 0,5992 0,5629 3738 0,6842 0,6823 0,6805 0,6786 0,6768 0,6750 0,6713 0,6695 0,6677 0,6394 0,6307 0,6273 0,5926 3839 0,7095 0,7078 0,7061 0,7043 0,7026 0,7009 0,6975 0,6957 0,6940 0,6674 0,6592 0,6560 0,6231 3940 0,7351 0,7335 0,7319 0,7303 0,7287 0,7271 0,7239 0,7223 0,7207 0,6958 0,6882 0,6852 0,6543 4041 0,7610 0,7595 0,7580 0,7565 0,7551 0,7536 0,7507 0,7492 0,7477 0,7248 0,7177 0,7149 0,6862 4142 0,7871 0,7857 0,7844 0,7831 0,7817 0,7804 0,7777 0,7764 0,7751 0,7542 0,7477 0,7452 0,7189 4243 0,8135 0,8123 0,8111 0,8099 0,8087 0,8075 0,8051 0,8039 0,8027 0,7840 0,7782 0,7760 0,7523 4344 0,8401 0,8390 0,8380 0,8369 0,8359 0,8348 0,8328 0,8317 0,8307 0,8143 0,8093 0,8073 0,7864 4445 0,8669 0,8660 0,8651 0,8643 0,8634 0,8625 0,8607 0,8599 0,8590 0,8451 0,8408 0,8391 0,8213 4546 0,8940 0,8933 0,8926 0,8919 0,8911 0,8904 0,8890 0,8883 0,8876 0,8763 0,8728 0,8714 0,8569 4647 0,9213 0,9208 0,9203 0,9197 0,9192 0,9186 0,9176 0,9170 0,9165 0,9079 0,9053 0,9042 0,8932 4748 0,9489 0,9485 0,9482 0,9478 0,9475 0,9471 0,9464 0,9460 0,9457 0,9400 0,9383 0,9376 0,9302 4849 0,9767 0,9765 0,9764 0,9762 0,9760 0,9759 0,9755 0,9754 0,9752 0,9726 0,9718 0,9714 0,9680 4950 1,0047 1,0047 1,0048 1,0048 1,0048 1,0049 1,0049 1,0050 1,0050 1,0055 1,0057 1,0058 1,0065 5051 1,0329 1,0332 1,0334 1,0337 1,0339 1,0341 1,0346 1,0349 1,0351 1,0389 1,0401 1,0406 1,0457 5152 1,0614 1,0619 1,0623 1,0628 1,0632 1,0637 1,0646 1,0650 1,0655 1,0728 1,0750 1,0760 1,0856 5253 1,0901 1,0908 1,0914 1,0921 1,0928 1,0935 1,0948 1,0955 1,0962 1,1070 1,1104 1,1118 1,1263 5354 1,1190 1,1199 1,1208 1,1217 1,1226 1,1235 1,1253 1,1262 1,1271 1,1417 1,1463 1,1481 1,1677 5455 1,1481 1,1492 1,1504 1,1515 1,1527 1,1538 1,1561 1,1572 1,1584 1,1768 1,1826 1,1849 1,2097 5556 1,1774 1,1788 1,1802 1,1816 1,1830 1,1843 1,1871 1,1885 1,1899 1,2123 1,2194 1,2222 1,2526 5657 1,2070 1,2086 1,2102 1,2119 1,2135 1,2151 1,2184 1,2200 1,2217 1,2482 1,2566 1,2600 1,2961 5758 1,2367 1,2386 1,2405 1,2424 1,2443 1,2462 1,2499 1,2518 1,2537 1,2846 1,2943 1,2983 1,3403 5859 1,2667 1,2688 1,2710 1,2731 1,2753 1,2774 1,2818 1,2839 1,2861 1,3213 1,3325 1,3370 1,3853 5960 1,2968 1,2993 1,3017 1,3041 1,3065 1,3089 1,3138 1,3163 1,3187 1,3585 1,3711 1,3762 1,4310 6061 1,3272 1,3299 1,3326 1,3353 1,3380 1,3407 1,3461 1,3489 1,3516 1,3960 1,4102 1,4159 1,4773 6162 1,3578 1,3607 1,3637 1,3667 1,3697 1,3727 1,3787 1,3817 1,3847 1,4340 1,4497 1,4561 1,5244 6263 1,3885 1,3918 1,3951 1,3983 1,4016 1,4049 1,4115 1,4148 1,4181 1,4723 1,4897 1,4967 1,5722 6364 1,4195 1,4230 1,4266 1,4302 1,4338 1,4374 1,4446 1,4482 1,4518 1,5111 1,5301 1,5378 1,6208 6465 1,4506 1,4545 1,4584 1,4622 1,4661 1,4700 1,4779 1,4818 1,4857 1,5503 1,5710 1,5794 1,6700 6566 1,4820 1,4861 1,4903 1,4945 1,4987 1,5029 1,5114 1,5157 1,5199 1,5898 1,6123 1,6214 1,7199 6667 1,5135 1,5180 1,5225 1,5270 1,5315 1,5361 1,5452 1,5498 1,5544 1,6298 1,6541 1,6639 1,7706 6768 1,5452 1,5500 1,5549 1,5597 1,5646 1,5694 1,5792 1,5841 1,5891 1,6701 1,6962 1,7068 1,8219 6869 1,5771 1,5823 1,5874 1,5926 1,5978 1,6030 1,6135 1,6187 1,6240 1,7108 1,7389 1,7502 1,8740 69

Page 47: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 101

Furt

her

info

rmat

ion

Planning, assembly and installation information, cooling capacity correction factors

Ascotherm® eco Further information

Correction factors CK (logarithmic calculation)

∆T [K]Exponent n

∆T [K]0,68 0,72 0,74 0,76 0,78 0,79 0,83 0,90 0,91 0,92 0,93

8 0,8610 0,8534 0,8497 0,8459 0,8422 0,8404 0,8330 0,8203 0,8185 0,8167 0,8149 89 0,9328 0,9290 0,9271 0,9252 0,9233 0,9223 0,9186 0,9120 0,9111 0,9101 0,9092 910 1,0020 1,0022 1,0022 1,0023 1,0023 1,0024 1,0025 1,0027 1,0027 1,0028 1,0028 1011 1,0691 1,0734 1,0755 1,0776 1,0797 1,0808 1,0850 1,0925 1,0936 1,0947 1,0957 1112 1,1343 1,1427 1,1470 1,1512 1,1555 1,1577 1,1663 1,1815 1,1837 1,1859 1,1881 1213 1,1978 1,2105 1,2170 1,2235 1,2300 1,2332 1,2464 1,2698 1,2731 1,2765 1,2799 1314 1,2597 1,2769 1,2856 1,2943 1,3032 1,3076 1,3255 1,3573 1,3620 1,3666 1,3712 1415 1,3202 1,3419 1,3529 1,3640 1,3752 1,3808 1,4036 1,4443 1,4502 1,4561 1,4621 1516 1,3794 1,4057 1,4191 1,4326 1,4462 1,4531 1,4808 1,5307 1,5379 1,5452 1,5525 1617 1,4374 1,4685 1,4842 1,5001 1,5162 1,5244 1,5572 1,6165 1,6252 1,6339 1,6426 1718 1,4944 1,5302 1,5483 1,5667 1,5854 1,5948 1,6329 1,7018 1,7119 1,7221 1,7323 1819 1,5504 1,5909 1,6115 1,6325 1,6537 1,6644 1,7078 1,7867 1,7983 1,8099 1,8216 1920 1,6054 1,6507 1,6739 1,6974 1,7212 1,7332 1,7821 1,8711 1,8842 1,8974 1,9106 2021 1,6596 1,7098 1,7354 1,7615 1,7879 1,8013 1,8558 1,9551 1,9697 1,9845 1,9993 2122 1,7129 1,7680 1,7962 1,8249 1,8540 1,8687 1,9288 2,0387 2,0549 2,0712 2,0877 2223 1,7655 1,8255 1,8563 1,8876 1,9194 1,9355 2,0013 2,1219 2,1397 2,1577 2,1758 2324 1,8173 1,8823 1,9157 1,9496 1,9842 2,0017 2,0733 2,2048 2,2242 2,2439 2,2637 2425 1,8685 1,9385 1,9744 2,0111 2,0484 2,0673 2,1447 2,2873 2,3084 2,3297 2,3512 2526 1,9190 1,9940 2,0326 2,0719 2,1120 2,1324 2,2157 2,3695 2,3923 2,4153 2,4386 2627 1,9689 2,0489 2,0901 2,1322 2,1751 2,1969 2,2862 2,4513 2,4759 2,5007 2,5257 27

∆T [K]Exponent n

∆T [K]0,94 0,95 0,97 1,00 1,02 1,04 1,05 1,06 1,10 1,12 1,19

8 0,8131 0,8113 0,8077 0,8024 0,7989 0,7954 0,7936 0,7919 0,7849 0,7815 0,7695 89 0,9083 0,9073 0,9055 0,9027 0,9009 0,8990 0,8981 0,8972 0,8935 0,8917 0,8853 910 1,0028 1,0029 1,0029 1,0030 1,0031 1,0031 1,0032 1,0032 1,0033 1,0034 1,0036 1011 1,0968 1,0979 1,1001 1,1033 1,1055 1,1077 1,1087 1,1098 1,1142 1,1164 1,1241 1112 1,1903 1,1925 1,1969 1,2036 1,2081 1,2126 1,2148 1,2171 1,2261 1,2307 1,2467 1213 1,2833 1,2867 1,2936 1,3039 1,3109 1,3178 1,3213 1,3248 1,3390 1,3461 1,3713 1314 1,3759 1,3806 1,3900 1,4042 1,4138 1,4234 1,4283 1,4331 1,4527 1,4626 1,4978 1415 1,4681 1,4741 1,4862 1,5045 1,5169 1,5293 1,5356 1,5418 1,5672 1,5801 1,6259 1516 1,5599 1,5673 1,5822 1,6048 1,6201 1,6355 1,6432 1,6510 1,6825 1,6985 1,7557 1617 1,6514 1,6602 1,6780 1,7051 1,7234 1,7419 1,7512 1,7606 1,7986 1,8179 1,8871 1718 1,7425 1,7529 1,7737 1,8054 1,8269 1,8486 1,8595 1,8706 1,9153 1,9381 2,0199 1819 1,8334 1,8453 1,8692 1,9057 1,9305 1,9555 1,9682 1,9809 2,0327 2,0590 2,1541 1920 1,9240 1,9374 1,9646 2,0060 2,0341 2,0627 2,0771 2,0916 2,1506 2,1808 2,2897 2021 2,0142 2,0293 2,0598 2,1063 2,1379 2,1700 2,1863 2,2026 2,2692 2,3033 2,4266 2122 2,1043 2,1210 2,1548 2,2066 2,2418 2,2776 2,2957 2,3139 2,3884 2,4265 2,5647 2223 2,1941 2,2125 2,2498 2,3069 2,3458 2,3854 2,4054 2,4256 2,5080 2,5503 2,7040 2324 2,2836 2,3038 2,3446 2,4072 2,4499 2,4933 2,5153 2,5375 2,6283 2,6748 2,8445 2425 2,3730 2,3949 2,4393 2,5075 2,5541 2,6014 2,6255 2,6497 2,7490 2,8000 2,9861 2526 2,4621 2,4858 2,5339 2,6078 2,6583 2,7098 2,7358 2,7622 2,8702 2,9257 3,1288 2627 2,5510 2,5765 2,6284 2,7081 2,7626 2,8182 2,8464 2,8749 2,9918 3,0520 3,2725 27

Page 48: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® ecoFurther information

102 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Furt

her

info

r-m

atio

n

Planning, assembly and installation instructions

Scope of delivery• External, adjustable and acoustically decoupled height adjust-

ments (pre-installed)• For KRP91, KRN92 and KRN81 aluminium linear grille (on

request, delivery can be postponed until the end of the construction phase)

• For KC281 and KC481 aluminium roll-up grille (on request, delivery can be postponed until the end of the construction phase)

• Plastic elements for acoustic decoupling• Installation cover and edge bar protection (for protection

during the construction phase)

Planning advices• To compensate for cold air that occurs on large window areas,

the trench convectors must be dimensioned to extend along the entire length of the window.

• The thermal behaviour of screeds and floors can compress the floor pans of trench convectors. To prevent this, expansion joints must be provided.

• When electrical cables or a thermostatic sensor head with a remote sensor will be used, it is necessary to install an empty conduit.

• The installation cover supplied serves to protect the convec-tor during the construction phase and should be replaced with the supplied linear grille or roll-up grille only after all construction work has been completed. The installation cover has only limited loading capability and is not suitable for use as a surface to support scaffolds, ladders etc.

• The convector must be accessible for maintenance work at any time.

Installation instructions

Positioning and arrangement

• Remove the packaging film and packaging cardboard from the trench convector before installation. If the top grille has already been delivered, store it in a safe location until construction work has been completed.

• Place the trench convector in position and use the external height adjustments to align it. The height adjustments can be placed in the correct position with the aid of a screwdriver.

• Use the mounting brackets to secure the floor pan to the floor.

• If necessary, use insulation underneath and on the sides of the floor pan as well.

• Note the acoustic decoupling

Connecting of the trench convector

• Water connection to the face (as standard) or room sided with openings already provided for pipe entry (on request, other connection arrangements also possible).

• Attach fittings and connect convector to pipework.• To prevent entry of screed into the floor pan, seal the provi-

ded openings with suitable material. (e. g. plastic plugs from the accessory range)

• Perform a pressure test.• Cover the convector with the supplied installation cover for

protection• When components from other manufacturers are used (e.g.

connection set, actuator,…) that are not in the accessory range for the Ascotherm eco, pay attention to the installation dimensions.

Intended use

The Ascotherm KRN81, KC281 and KC481 are intended exclusi-vely for use in indoor areas (e.g. conservatories, residential and commercial areas, showrooms, etc. The Ascotherm KRN81, KC281 and KC481 cannot be used in swimming pools, damp locations and outdoor areas. In case of doubt, always consult the manufac-turer. Any other or additional use shall be considered as impro-per use.

Safety instructions

• Electrical work may be carried out only by authorised electri-cians. Connection must comply with valid VDE regulations and the EVU directives.

• When installing Ascotherm KRN81, KC281 and KC481, a suita-ble residual current-operated protective device (RCD) / earth leakage circuit breaker (less than or equal to 30 mA) must be installed.

• In case of failure to comply with the regulations and directives malfunctions with consequential damage and endangerment of individuals can occur. Mixing up wires or connecting impro-perly can result in MORTAL DANGER!

• Note additional safety information in the installation instruc-tions.

Page 49: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® eco KRP91Further information

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 103

Ordering process

Furt

her

info

rmat

ion

Product Flow/return Floor pan Grille

Pos

Ro

om

Nu

mb

er

Pro

du

ct /

vers

ion

Hei

gh

t in

mm

Dep

th in

mm

Len

gth

in m

m

Co

nn

ecti

on

sys

tem

Co

up

ling

of

rad

iato

r p

osi

tio

n

Des

ign

(in

terc

on

nec

ted

)

Arr

ang

emen

t

Co

nn

ecti

on

siz

e

Pres

sure

ver

sio

n

Top

gri

lle

Fitt

ing

s

Act

uat

or

Fitt

ing

Pan

co

lou

r

Pan

co

lou

r co

de

Edg

e b

ar c

olo

ur

Top

gri

lle v

ersi

on

Spec

ials

|HOE| |MT| |LAE| |VT| |KHP| |BF| |ANB| |VG| |RG| |DRU| |ABD| |EBT| |STT| |VRS| |FAR1| |FNR1| |RDL| |AUS| |BES|

1 WG 1 KRP91 150 185 1000 2 BB 64 64 10 LR RAL 7016 ELO ELO

2 WG 1 KRP91 92 260 2050 2 33 64 64 10 RR TS1 STT VRS RAL 7016 DKS DKS SBL

RoomInformation on the room in which the radiator will be installed

Ordering information Ordering code

Conservatory WG

Entrance Entrance

Administrative building VG

... ...

NumberNumber of radiators

Ordering informationOrdering code for example

1 radiator 1

2 radiators 2

Product / version

Ordering information Ordering code

Ascotherm KRP91 Natural Convection KRP91

|HOE| - Height BH in mm

Ordering information Ordering code

92 mm 92

120 mm 120

150 mm 150

200 mm 200

|MT| - Depth in mm

Ordering information Ordering code

185 mm 185

210 mm 210

260 mm 260

310 mm 310

360 mm 360

400 mm 400

|LAE| - Length in mm

Ordering information Ordering code

from 1000 mm to 5000 mm 1000 - 5000

|VT| - Flow / return: Connection system

Ordering information Ordering code

2-pipe system (flow and return are separate)

2

Other connection arrangements

Ordering information Ordering code

Coupled on same side in series 75

Special connections 99

|KHP| - Coupling of radiator position

Ordering information Ordering code

Without coupling –

Initial radiator 1

Centred radiator 2

Final radiator 3

|BF| - radiator design

Ordering information Ordering code

Without –

Connected at right end 1

Connected at both ends 2

Connected at left end 3

|ANB| - Flow / return: Arrangement

Ordering information Ordering code

1st digit: pos. flow 2nd digit: pos. return

DB

8 361

|VG| - Flow connection size

Ordering information Ordering code

G 3/4’’ 64

|RG| - Return connection size

Ordering information Ordering code

G 3/4’’ 64

|DRU| - Pressure version in bar (Pa)

Ordering information Ordering code

Standard version: 10 bar (1000 kPa) 10

High-pressure version: 16 bar (1600 kPa) 16

Page 50: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® eco KRP91Further information

104 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Ordering process

Furt

her

info

r-m

atio

n

|ABD| - Top grille

Ordering information Ordering code

Without –

Standard version: Aluminium linear grille LR

Aluminium roll-up grille RR

|EBT| - Fittings

Ordering information Ordering code

Without impact sound insulation –

With impact sound insulation TS1

|STT| - Actuator

Ordering information Ordering code

Without actuator –

With actuator STT

|VRS| - Fitting

Ordering information Ordering code

Without Fitting –

With Fitting VRS

Floor pan |FAR1| - Surface: Colour

Ordering information Ordering code

RAL RAL

|FNR1| - Surface: Colour code

Ordering information Ordering code

Anthracite grey 7016

Edge bar |RDL| - Edge bar colour

Ordering information Ordering code

Anodised ELO

Bronze BRO

Brass MES

Dark silver DKS

black SWZ

Stainless steel EDS

Pan colour FAR1

Grille colour FAR2

Top grilles |AUS| - Top grille version Ordering information Ordering code

Anodised ELO

Bronze BRO

Brass MES

Dark silver DKS

black SWZ

Finished LAC

Stainless steel 1) EDS

Type of wood: beech 1) HBU

Type of wood: oak 1) HEI

Type of wood: ash 1) HES1) This version is only possible with roll-up grille.

|BES| - Specials

Ordering information Ordering code

Mitre / column 75

Single mitre 76

Double mitre 77

Special height SBH

Special length SBL

Special depth SBT

= Standard version, instead of value, it is also possible to insert "-"

Page 51: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® eco KRN92Further information

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 105

Ordering process

Furt

her

info

rmat

ion

Product Flow/return Floor pan Grile

Pos

Ro

om

Nu

mb

er

Pro

du

ct /

vers

ion

Hei

gh

t in

mm

Dep

th in

mm

Len

gth

in m

m

Co

nn

ecti

on

sys

tem

Co

up

ling

of

rad

iato

r p

osi

tio

n

Des

ign

(in

terc

on

nec

ted

)

Arr

ang

emen

t

Nu

mb

er o

f ai

r co

nn

ec-

tio

ns

Air

co

nn

ecti

on

arr

an-

gem

ent

Air

co

nn

ecti

on

siz

e

Co

nn

ecti

on

siz

e

Pres

sure

ver

sio

n

Top

gri

lle

Fitt

ing

s

Act

uat

or

Fitt

ing

Pan

co

lou

r

Pan

co

lou

r co

de

Edg

e b

ar c

olo

ur

Top

gri

lle v

ersi

on

Spec

ials

|HOE| |MT| |LAE| |VT| |KHP| |BF| |ANB| |LAZ| |LAP| |LAG| |VG| |RG| |DRU| |ABD| |EBT| |STT| |VRS| |FAR1| |FNR1| |RDL| |AUS| |BES|

1 HK2 2 KRN92 110 310 2750 2 11 1 F 63 64 64 10 LR RAL 7016 ELO ELO

2 HK2 1 KRN92 200 185 2000 2 BB 1 F 100 64 64 10 RR STT VRS RAL 7016 SWZ SWZ

RoomInformation on the room in which the radiator will be installed

Ordering information Ordering code

Conservatory WG

Administrative building VG

... ...

NumberNumber of radiators

Ordering information Ordering code

1 radiator 1

2 radiators 2

Product / version

Ordering information Ordering code

Ascotherm KRN92 Natural convection with additional air connection

KRN92

|HOE| - Height BH in mm

Ordering information Ordering code

110 mm 110

150 mm 150

200 mm 200

|MT| - Depth in mm

Ordering information Ordering code

185 mm 185

210 mm 210

260 mm 260

310 mm 310

360 mm 360

400 mm 400

|LAE| - Length in mm

Ordering information Ordering code

from 1000 mm to 5000 mm 1000 - 5000

|VT| - Flow / return: Connection system

Ordering information Ordering code

2-pipe system (flow and return are separate)

2

Other connection arrangements

Ordering information Ordering code

Coupled on same side in series 75

Special connections 99

|KHP| - Coupling of radiator position

Ordering information Ordering code

Without coupling –

Initial radiator 1

Centred radiator 2

Final radiator 3

|BF| - radiator design

Ordering information Ordering code

Without –

Connected at right end 1

Connected at both ends 2

Connected at left end 3

|ANB| - Flow / return: Arrangement

Ordering information Ordering code

1st digit: pos. flow 2nd digit: pos. return

DB

8 361

|LAZ| - Number of air connections

Ordering information Ordering code

One 1

Select 2 - 10 2 - 10

|LAP| - Air connection arrangement

Ordering information Ordering code

Air connection F

Special connection according to drawing SON

Page 52: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® eco KRN92Further information

106 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Ordering process

Furt

her

info

r-m

atio

n

|LAG| - Air connection size

Ordering information Ordering code

Connection 63 mm 63

Connection 80 mm 80

Connection 100 mm 100

Connection 125 mm 125

• Connection size depends on height

|VG| - Flow connection size

Ordering information Ordering code

G 3/4’’ 64

|RG| - Return connection size

Ordering information Ordering code

G 3/4’’ 64

|DRU| - Pressure version in bar (Pa)

Ordering information Ordering code

Standard version: 10 bar (1000 kPa) 10

High-pressure version: 16 bar (1600 kPa) 16

|ABD| - Top grille

Ordering information Ordering code

Without –

Standard version: Aluminium linear grille LR

Aluminium roll-up grille RR

|EBT| - Fittings

Ordering information Ordering code

Without impact sound insulation –

With impact sound insulation TS1

|STT| - Actuator

Ordering information Ordering code

Without actuator –

With actuator STT

|VRS| - Fitting

Ordering information Ordering code

Without Fitting –

With Fitting VRS

Floor pan |FAR1| - Surface: Colour

Ordering information Ordering code

RAL RAL

|FNR1| - Surface: Colour code

Ordering information Ordering code

Anthracite grey 7016

Edge bar |RDL| - Edge bar colour

Ordering information Ordering code

Anodised ELO

Bronze BRO

Brass MES

Dark silver DKS

black SWZ

Stainless steel EDS

Pan colour FAR1

Grille colour FAR2

Top grilles |AUS| - Top grille version Ordering information Ordering code

Anodised ELO

Bronze BRO

Brass MES

Dark silver DKS

black SWZ

Finished LAC

Stainless steel 1) EDS

Type of wood: beech 1) HBU

Type of wood: oak 1) HEI

Type of wood: ash 1) HES1) This version is only possible with roll-up grille.

|BES| - Specials

Ordering information Ordering code

Mitre / column 75

Single mitre 76

Double mitre 77

Special height SBH

Special length SBL

Special depth SBT

= Standard version, instead of value, it is also possible to insert "-"

Page 53: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® eco KRN81Further information

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 107

Ordering process

Furt

her

info

rmat

ion

Product Flow/return Floor pan Grille

Pos

Ro

om

Nu

mb

er

Pro

du

ct /

vers

ion

Hei

gh

t in

mm

Dep

th in

mm

Len

gth

in m

m

Co

nn

ecti

on

sys

tem

Co

up

ling

of

rad

iato

r p

osi

tio

n

Des

ign

(in

terc

on

nec

ted

)

Arr

ang

emen

t

Co

nn

ecti

on

siz

e

Pres

sure

ver

sio

n

Top

gri

lle

Fitt

ing

s

Filt

er f

leec

e

Act

uat

or

Fitt

ing

Co

ntr

ol s

yste

m

Bu

ildin

g m

anag

emen

t sy

stem

Pan

co

lou

r

Pan

co

lou

r co

de

Top

gri

lle v

ersi

on

Edg

e b

ar c

olo

ur

Spec

ials

|HOE| |MT| |LAE| |VT| |KHP| |BF| |ANB| |VG| |RG| |DRU| |ABD| |EBT| |FVL| |STT| |VRS| |RLT| |GLT| |FAR1| |FNR1| |AUS| |RDL| |BES|

1 R01 1 KRN81 110 310 1250 2 BB 64 64 10 RR TS1 FV RLT RAL 7016 HEI ELO

2 R01 1 KRN81 110 260 3000 2 33 64 64 10 LR STT VRS RLT RAL 7016 ELO ELO

RoomInformation on the room in which the radiator will be installed

Ordering information Ordering code

Conservatory WG

Administrative building VG

... ...

NumberNumber of radiators

Ordering information Ordering code

1 radiator 1

2 radiators 2

Product / version

Ordering information Ordering code

Ascotherm KRN81 Forced convection with cross-flow fan

KRN81

|HOE| - Height BH in mm

Ordering information Ordering code

110 mm 110

|MT| - Depth in mm

Ordering information Ordering code

185 mm 185

210 mm 210

260 mm 260

310 mm 310

360 mm 360

|LAE| - Length in mm

Ordering information Ordering code

from 1250 mm to 4000 mm 1250 - 4000

|VT| - Flow / return: Connection system

Ordering information Ordering code

2-pipe system (flow and return are separate)

2

Other connection arrangements

Ordering information Ordering code

Coupled on same side in series 75

Special connections 99

|KHP| - Coupling of radiator position

Ordering information Ordering code

Without coupling –

Initial radiator 1

Centred radiator 2

Final radiator 3

|BF| - radiator design

Ordering information Ordering code

Without –

Connected at right end 1

Connected at both ends 2

Connected at left end 3

|ANB| - Flow / return: Arrangement

Ordering information Ordering code

1st digit: pos. flow 2nd digit: pos. return

DB

8 361

|VG| - Flow connection size

Ordering information Ordering code

G 3/4’’ 64

|RG| - Return connection size

Ordering information Ordering code

G 3/4’’ 64

|DRU| - Pressure version in bar (Pa)

Ordering information Ordering code

Standard version: 10 bar (1000 kPa) 10

High-pressure version: 16 bar (1600 kPa) 16

Page 54: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® eco KRN81Further information

108 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Ordering process

Furt

her

info

r-m

atio

n

|ABD| - Top grille

Ordering information Ordering code

Without –

Standard version: Aluminium linear grille LR

Aluminium roll-up grille RR

|EBT| - Fittings

Ordering information Ordering code

Without impact sound insulation –

With impact sound insulation TS1

|FVL| - Filter fleece

Ordering information Ordering code

Without filter fleece –

With filter fleece FV

|STT| - Actuator

Ordering information Ordering code

Without actuator –

With actuator STT

|VRS| - Fitting

Ordering information Ordering code

Without Fitting –

With Fitting VRS

|RLT| - Control system

Ordering information Ordering code

Without control system –

With control system RLT

|GLT| - Building management system

Ordering information Ordering code

Without –

KNX card KNX

LON card LON

Floor pan |FAR1| - Surface: Colour

Ordering information Ordering code

RAL RAL

|FNR1| - Surface: Colour code

Ordering information Ordering code

Anthracite grey 7016

Edge bar |RDL| - Edge bar colour

Ordering information Ordering code

Anodised ELO

Bronze BRO

Brass MES

Dark silver DKS

black SWZ

Stainless steel EDS

Pan colour FAR1

Grille colour FAR2

Top grilles |AUS| - Top grille version Ordering information Ordering code

Anodised ELO

Bronze BRO

Brass MES

Dark silver DKS

black SWZ

Finished LAC

Stainless steel 1) EDS

Type of wood: beech 1) HBU

Type of wood: oak 1) HEI

Type of wood: ash 1) HES1) This version is only possible with roll-up grille.

|BES| - Specials

Ordering information Ordering code

Mitre / column 75

Single mitre 76

Double mitre 77

Special height SBH

Special length SBL

Special depth SBT

= Standard version, instead of value, it is also possible to insert "-"

Page 55: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® eco KC281Further information

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 109

Ordering process

Furt

her

info

rmat

ion

Product Flow/return Floor pan Grille

Pos

Ro

om

Nu

mb

er

Pro

du

ct /

vers

ion

Hei

gh

t in

mm

Dep

th in

mm

Len

gth

in m

m

Co

nn

ecti

on

sys

tem

Co

up

ling

of

rad

iato

r p

osi

tio

n

Des

ign

(in

terc

on

nec

ted

)

Hea

tin

g /

coo

ling

arr

an-

gem

ent

Co

nn

ecti

on

siz

e

Pres

sure

ver

sio

n

Top

gri

lle

Fitt

ing

s

Filt

er f

leec

e

Co

nd

ensa

te p

um

p

Act

uat

or

Fitt

ing

Co

ntr

ol s

yste

m

Bu

ildin

g m

anag

emen

t sy

stem

Pan

co

lou

r

Pan

co

lou

r co

de

Edg

e b

ar c

olo

ur

Top

gri

lle v

ersi

on

Spec

ials

|HOE| |MT| |LAE| |VT| |KHP| |BF| |ANB| |VG| |RG| |DRU| |ABD| |EBT| |FVL| |PUM| |STT| |VRS| |RLT| |GLT| |FAR1| |FNR1| |RDL| |AUS| |BES|

1 R02 2KC

281130 310 1250 2 BB 64 64 10 RR TS1 RAL 7016 ELO ELO

RoomInformation on the room in which the radiator will be installed

Ordering information Ordering code

Conservatory WG

Entrance Entrance

Administrative building VG

... ...

NumberNumber of radiators

Ordering information Ordering code

1 radiator 1

2 radiators 2

Product / version

Ordering information Ordering code

Ascotherm KC281 heating and cooling in 2-pipe system

KC 281

|HOE| - Height BH in mm

Ordering information Ordering code

130 mm 130

155 mm 155

|MT| - Depth in mm

Ordering information Ordering code

310 mm 310

360 mm 360

|LAE| - Length in mm

Ordering information Ordering code

1250 mm 1250

2000 mm 2000

2750 mm 2750

|VT| - Flow / return: Connection system

Ordering information Ordering code

2-pipe system (flow and return are separate)

2

Other connection arrangements

Ordering information Ordering code

Coupled on same side in series 75

Special connections 99

|KHP| - Coupling of radiator position

Ordering information Ordering code

Without coupling –

Initial radiator 1

Centred radiator 2

Final radiator 3

|BF| - radiator design

Ordering information Ordering code

Without –

Connected at right end 1

Connected at both ends 2

Connected at left end 3

|ANB| - Flow / return: Arrangement

Ordering information Ordering code

1st digit: pos. flow 2nd digit: pos. return

DB

8 361

|VG| - Flow connection size

Ordering information Ordering code

G 3/4’’ 64

|RG| - Return connection size

Ordering information Ordering code

G 3/4’’ 64

|DRU| - Pressure version in bar (Pa)

Ordering information Ordering code

Standard version: 10 bar (1000 kPa) 10

High-pressure version: 16 bar (1600 kPa) 16

Page 56: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® eco KC281Further information

110 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Ordering process

Furt

her

info

r-m

atio

n

|ABD| - Top grille

Ordering information Ordering code

Without –

Aluminium linear grille LR

Standard version: Aluminium roll-up grille RR

|EBT| - Fittings

Ordering information Ordering code

Without impact sound insulation –

With impact sound insulation TS1

|FVL| - Filter fleece

Ordering information Ordering code

Without filter fleece –

With filter fleece FV

|PUM| - Condensate pump

Ordering information Ordering code

Without condensate pump –

With condensate pump PUM

|STT| - Actuator

Ordering information Ordering code

Without actuator –

With actuator STT

|VRS| - Fitting

Ordering information Ordering code

Without Fitting –

With Fitting VRS

|RLT| - Control system

Ordering information Ordering code

Without control system –

With control system RLT

|GLT| - Building management system

Ordering information Ordering code

Without –

KNX card KNX

LON card LON

Floor pan |FAR1| - Surface: Colour

Ordering information Ordering code

RAL RAL

|FNR1| - Surface: Colour code

Ordering information Ordering code

Anthracite grey 7016

Edge bar |RDL| - Edge bar colour

Ordering information Ordering code

Anodised ELO

Bronze BRO

Brass MES

Dark silver DKS

black SWZ

Stainless steel EDS

Pan colour FAR1

Grille colour FAR2

Top grilles |AUS| - Top grille version Ordering information Ordering code

Anodised ELO

Bronze BRO

Brass MES

Dark silver DKS

black SWZ

Finished LAC

Stainless steel 1) EDS

Type of wood: beech 1) HBU

Type of wood: oak 1) HEI

Type of wood: ash 1) HES1) This version is only possible with roll-up grille.

|BES| - Specials

Ordering information Ordering code

Mitre / column 75

Single mitre 76

Double mitre 77

Special height SBH

Special length SBL

Special depth SBT

= Standard version, instead of value, it is also possible to insert "-"

Page 57: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® eco KC481Further information

Prices without value-added tax. Technical specifications subject to change.Prices and Technology 2015-N 111

Ordering process

Furt

her

info

rmat

ion

Product Flow/return Floor pan Grille

Pos

Ro

om

Nu

mb

er

Pro

du

ct /

vers

ion

Hei

gh

t in

mm

Dep

th in

mm

Len

gth

in m

m

Co

nn

ecti

on

sys

tem

Co

up

ling

of

rad

iato

r p

osi

tio

n

Des

ign

(in

terc

on

nec

ted

)

Arr

ang

emen

t h

eati

ng

Arr

ang

emen

t co

olin

g

Co

nn

ecti

on

siz

e h

eati

ng

Co

nn

ecti

on

siz

e co

olin

g

Pres

sure

ver

sio

n

Top

gri

lle

Fitt

ing

s

Filt

er f

leec

e

Co

nd

ensa

te p

um

p

Act

uat

or

Fitt

ing

Co

ntr

ol s

yste

m

Bu

ildin

g m

anag

emen

t sy

stem

Pan

co

lou

r

Pan

co

lou

r co

de

Edg

e b

ar c

olo

ur

Top

gri

lle v

ersi

on

Spec

ials

|HOE| |MT| |LAE| |VT| |KHP| |BF| |ANB| |ANK| |VG| |RG| |VGK| |RGK| |DRU| |ABD| |EBT| |FVL| |PUM| |STT| |VRS| |RLT| |GLT| |FAR1| |FNR1| |RDL| |AUS| |BES|

1 LW 2 KC 481 155 330 2750 4 11 33 64 64 64 64 10 RR TS1 FV STT VRS RLT RAL 7016 EDS EDS

RoomInformation on the room in which the radiator will be installed

Ordering information Ordering code

Conservatory WG

Entrance Entrance

Administrative building VG

... ...

NumberNumber of radiators

Ordering information Ordering code

1 radiator 1

2 radiators 2

Product / version

Ordering information Ordering code

Ascotherm KC481 heating and cooling in 4-conductor system

KC 481

|HOE| - Height BH in mm

Ordering information Ordering code

130 mm 130

155 mm 155

|MT| - Depth in mm

Ordering information Ordering code

330 mm 330

360 mm 360

|LAE| - Length in mm

Ordering information Ordering code

1250 mm 1250

2000 mm 2000

2750 mm 2750

|VT| - Flow / return: Connection system

Ordering information Ordering code

4-pipe system (heating flow and return, cooling flow and return are separate)

4

Other connection arrangements

Ordering information Ordering code

Coupled on same side in series 75

Special connections 99

|KHP| - Coupling of radiator position

Ordering information Ordering code

Without coupling –

Initial radiator 1

Centred radiator 2

Final radiator 3

|BF| - radiator design

Ordering information Ordering code

Without –

Connected at right end 1

Connected at both ends 2

Connected at left end 3

|ANB| - Flow / return: Heating arrangement

Ordering information Ordering code

1st digit: pos. flow 2nd digit: pos. return

DB

8 361

|ANK| - Flow / return: Cooling arrangement

Ordering information Ordering code

1st digit: pos. flow 2nd digit: pos. return

DB

8 361

|VG| - Flow connection size

Ordering information Ordering code

G 3/4’’ 64

|RG| - Return connection size

Ordering information Ordering code

G 3/4’’ 64

Page 58: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Ascotherm® eco KC481Further information

112 Prices and Technology 2015-N Prices without value-added tax. Technical specifications subject to change.

Ordering process

Furt

her

info

r-m

atio

n

|VGK| - Flow connection size

Ordering information Ordering code

G 3/4’’ 64

|RGK| - Return connection size

Ordering information Ordering code

G 3/4’’ 64

|DRU| - Pressure version in bar (Pa)

Ordering information Ordering code

Standard version: 10 bar (1000 kPa) 10

High-pressure version: 16 bar (1600 kPa) 16

|ABD| - Top grille

Ordering information Ordering code

Without –

Aluminium linear grille LR

Standard version: Aluminium roll-up grille RR

|EBT| - Fittings

Ordering information Ordering code

Without impact sound insulation –

With impact sound insulation TS1

|FVL| - Filter fleece

Ordering information Ordering code

Without filter fleece –

With filter fleece FV

|PUM| - Condensate pump

Ordering information Ordering code

Without condensate pump –

With condensate pump PUM

|STT| - Actuator

Ordering information Ordering code

Without actuator –

With actuator STT

|VRS| - Fitting

Ordering information Ordering code

Without Fitting –

With Fitting VRS

|RLT| - Control system

Ordering information Ordering code

Without control system –

With control system RLT

|GLT| - Building management system

Ordering information Ordering code

Without –

KNX card KNX

LON card LON

Floor pan |FAR1| - Surface: Colour

Ordering information Ordering code

RAL RAL

|FNR1| - Surface: Colour code

Ordering information Ordering code

Anthracite grey 7016

Edge bar |RDL| - Edge bar colour

Ordering information Ordering code

Anodised ELO

Bronze BRO

Brass MES

Dark silver DKS

black SWZ

Stainless steel EDS

Pan colour FAR1

Grille colour FAR2

Top grilles |AUS| - Top grille version Ordering information Ordering code

Anodised ELO

Bronze BRO

Brass MES

Dark silver DKS

black SWZ

Finished LAC

Stainless steel 1) EDS

Type of wood: beech 1) HBU

Type of wood: oak 1) HEI

Type of wood: ash 1) HES1) This version is only possible with roll-up grille.

|BES| - Specials

Ordering information Ordering code

Mitre / column 75

Single mitre 76

Double mitre 77

Special height SBH

Special length SBL

Special depth SBT

= Standard version, instead of value, it is also possible to insert "-"

Page 59: Ascotherm eco KRN81 Forced convection with cross-flow fan · Ascotherm® eco KRN81 Forced convection with cross-flow fan Prices without value-added tax. Technical specifications subject

Prodcut Flow/return Floor pan Grille

Pos

Ro

om

Nu

mb

er

Pro

du

ct /

vers

ion

Hei

gh

t in

mm

Dep

th in

mm

Len

gth

in m

m

Co

nn

ecti

on

sys

tem

Co

up

ling

of

rad

ia-

tor

po

siti

on

Des

ign

(in

terc

on

-n

ecte

d)

Arr

ang

emen

t h

eati

ng

Arr

ang

emen

t co

olin

g

Nu

mb

er o

f ai

r

con

nec

tio

ns

Air

co

nn

ecti

on

ar

ran

gem

ent

Air

co

nn

ecti

on

siz

e

Pres

sure

ver

sio

n

Top

gri

lle

Fitt

ing

s

Filt

er f

leec

e

Co

nd

ensa

te p

um

p

Act

uat

or

Fitt

ing

Co

ntr

ol s

yste

m

Bu

ildin

g m

anag

e-m

ent

syst

em

Pan

co

lou

r

Pan

co

lou

r co

de

Edg

e b

ar c

olo

ur

Top

gri

lle v

ersi

on

Spec

ials

|HOE| |MT| |LAE| |VT| |KHP| |BF| |ANB| |ANK| |LAZ| |LAP| |LAG| |DRU| |ABD| |EBT| |FVL| |PUM| |STT| |VRS| |RLT| |GLT| |FAR1| |FNR1| |RDL| |AUS| |BES|

1

2

3

4

5

6

7

8

9

10

Ascotherm® ecoOrder Form

Ordering process

Customer Ordered by

Object Desired delivery date

Address Address Address

Postcode / city

Postcode / city

Postcode / city

Tel. / Fax Tel. / Fax Tel. / Fax

Comments