asbestos reinspection report - sodexo... · 2020-01-13 · insulation residue to pipework (post...

73
Asbestos Reinspection Report (with Priority Assessments) Raynes Park High School Bushey Road London SW20 0JL Project Number: B-87863 Issue Date: 7 th November 2019 Issue No: 1 Client Contact: Barry Pratt Life Environmental Services Ltd Contact: Phil James 47a Leopold Road Wimbledon, London, SW19 7JG 4 Duckett’s Wharf South Street Bishop’s Stortford Hertfordshire CM23 3AR Tel: Tel: 01279 503117 Fax: Fax: 01279 503162

Upload: others

Post on 15-Jul-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

Asbestos Reinspection Report

(with Priority Assessments)

Raynes Park High School

Bushey Road

London

SW20 0JL

Project Number: B-87863

Issue Date: 7th November 2019

Issue No: 1

Client Contact:Barry Pratt

Life Environmental Services Ltd Contact: Phil James

47a Leopold Road Wimbledon, London, SW19 7JG

4 Duckett’s Wharf South Street Bishop’s Stortford Hertfordshire CM23 3AR

Tel: Tel: 01279 503117 Fax: Fax: 01279 503162

Page 2: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

Life Environmental - Survey Report Guide

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 2 of 60

This guide explains the Section content of the survey report. Failure to use the information provided in the report correctly may result in incorrect information or assumptions being obtained.

Section 1.0 Executive Summary

The Executive Summary contains details of the scope and extent of the works. The reader must ensure that the scope covers the required areas and that any variations do not impact on any proposed works or management of the site. All areas of no access should be considered as containing asbestos until proven otherwise.

Recommended Actions provides a summary of all identified and presumed asbestos containing materials (ACMs). ACMs are listed by recommendation with those requiring urgent attention listed first.

The Asbestos Register presents ACMs by building, floor & location. It provides a detailed list of all locations included within the survey where positive samples have been taken or items are presumed to contain asbestos. Items physically sampled will show the asbestos type within the analysis column.

Items cross referenced (strong presumption) have their asbestos type determined by the sample result of materials of similar appearance and use that have been sampled elsewhere on site. These will show the analysis proceeded by X.

Strongly Presumed samples are items that the surveyor was unable to sample but the materials are similar in appearance and use to known asbestos-containing materials and hence they are confirmed as containing asbestos.

Presumed items are those that the surveyor was unable to sample or inspect adequately to confirm the presence of asbestos, as such there is a potential for asbestos being present and the item is presumed to contain asbestos.

A Material Assessment algorithm has been completed for all positive samples. It should be noted that to enable an accurate Priority Assessment to be undertaken this requires a detailed knowledge of the property. The responsibility for this lies with the dutyholder, although Life Environmental can assist with the provision of information or generic assessments where agreed.

Recommendations within this report are based on the condition of the asbestos and the Material Assessment. Prior to carrying out these recommendations consideration should be given to the Priority Assessment Algorithm.

Section 2.0 Introduction

The Introduction provides a general overview of the purpose, aims and type of survey undertaken. It also presents Project particulars and Quality Assurance.

Section 3.0 Survey Findings – Survey Reinspection Data Sheets

Survey Data Sheets contains detailed information on all suspect items with a photographic record of each item.

Section 4.0 – Survey Findings – Certificate & Schedule of Additional Bulk Samples This section provides analysis information and results of any additional samples taken.

Appendix 1 - Definitions & Recommended Guidance

These contain a general guidance relating to Samples, Assessments and Recommendations and a detailed Risk Assessment explanation.

Appendix 2 - Material & Priority Assessment algorithms

These contain a general guidance relating to detailed Risk Assessment explanation.

Appendix 3 - Survey Drawings

All locations will be given a unique reference number which corresponds to the location detailed within the Asbestos Register. The drawings highlight areas containing positive information and areas of no access. In the case of planned works, a check should always be made of adjacent areas.

Page 3: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

1. Introduction

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 3 of 60

1. Introduction

a. Purpose & Aim of Survey

b. Quality Assurance

2. Executive Summary

a. Revisions

b. Recommended Actions

c. Asbestos Register

3. Reinspection Data Sheets

4. Additional Bulk Samples

Appendices:

• Appendix 1 - Definitions & Recommended Guidance

• Appendix 2 - Material & Priority Assessment algorithms

• Appendix 3 - Survey Drawings

Page 4: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

1. Introduction

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 4 of 60

Life Environmental Services Ltd received an order of confirmation to undertake a Reinspection Survey from Sodexo (UK) Ltd. This order has been accepted on the basis of the original Quotation and our terms and conditions of business. This reinspection is subject to copyright and protected by copyright law.

The brief for these works was to carry out a reinspection of the Asbestos Containing Materials (ACMs) within the Raynes Park High School. The reinspection is based upon the previous report ref 408469.

This reinspection considered any damage and disturbance to items identified in the above survey. Every effort has been made to access any areas that were previously not accessible in the original survey. Where such locations have still not been accessed, asbestos should be presumed to be present within these areas.

Each section of this report focuses on one or two aspects; no section should be taken and read as a stand-alone document. It is imperative that each section is read in conjunction with each other.

This reinspection report forms an addendum to the original survey. The original survey report should be referred to for the following items of information:

• Information on the original survey methodology/caveats

• Original laboratory bulk analysis certificate of analysed samples

• Original drawings

It should be noted that this report is not intended as a Scope of Works for asbestos removal and that a detailed technical document could be provided upon request.

If any maintenance works are to be undertaken within the areas not accessed then a further survey and assessment should be carried out prior to these works.

Client Details: Sodexo (UK) Ltd

Date(s) of Survey: 23-October-2019

Surveyor(s): Lead Surveyor(s): Colin Platt

Report Prepared by: Matthew Richards 7th November 2019

Quality Control by: Colin Platt 7th November 2019

Life Environmental Project Manager:

Phil James

root
Pencil
Page 5: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

2. Executive Summary

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 5 of 60

a. Revisions

The following table summarises the items removed between the most recent re-inspection and its predecessor.

Removal Summary

ACMs removed during the period between previous site inspection visits. For removal details please liaise with the dutyholder.

Building Floor Location Number

and Name Item Material

Level of Identification

Risk Assessment

Block B 0 2/056 - Boiler Room

Bitumen Wrap To Live Electrical Cable

No Suspect Materials Seen

IA 0

b. Recommended Actions

Detailed below is guidance on actions to be taken to prevent potential exposure to ACMs. There follows a summary of all reinspected asbestos items that require further action in order that they can be managed safely

Please note that if additional samples or suspect items have been identified during the reinspection these will be detailed in Section 3 (Reinspection Data Sheets) of this report only and will not be detailed below or within any part of Section 2 of the report.

Please note the colour coding is based on the recommendation only and is not determined by the Material Assessment scores, these are explained within the original asbestos survey report. Some lower risk items may be recommended for removal based on its location or usage rather than the score only.

Please contact Life Environmental Services Ltd for advice in dealing with any asbestos in poor, unsealed or damaged condition or for assistance in developing your management plan and scheduling reinspections.

Remove

Asbestos that is redundant, in a poor condition or has the potential to be easily damaged, has been identified. It is recommended that these items are removed by an Approved or Licensed Asbestos Removal Contractor.

Building Floor Location Number

and Name Item Material

Level of Identification

Risk Assessment

Block A External

Tank Room - Tank Room

Insulation Residue To Walls

Thermal Insulation

SP 8

Encapsulate/Repair and Manage

ACMs which are damaged or unsealed have been identified within the following areas. It is recommended that remedial work to repair & seal these materials is undertaken.

Building Floor Location Number

and Name Item Material

Level of Identification

Risk Assessment

Block A 0 1/0130 - Boiler Room

Insulation Residue To South Wall

Thermal Insulation

SP 8

Block A 0 1/0130 - Boiler Room

Insulation Residue To East Wall

Thermal Insulation

SP 8

Page 6: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

2. Executive Summary

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 6 of 60

Encapsulate/Repair and Manage

ACMs which are damaged or unsealed have been identified within the following areas. It is recommended that remedial work to repair & seal these materials is undertaken.

Building Floor Location Number

and Name Item Material

Level of Identification

Risk Assessment

Block A 0 1/0130 - Boiler Room

Insulation Residue To South Wall

Thermal Insulation

SP 8

Block A 0 1/0130 - Boiler Room

Insulation Residue To North Wall

Thermal Insulation

SP 8

Block A 0 1/0130 - Boiler Room

Insulation Residue To West Wall

Thermal Insulation

SP 8

Block A 0 1/040A - Stores Insulation Residue To Pipework

Thermal Insulation

SP 8

Manage and Re-inspect

ACMs have been identified which are in good condition. A management policy and plan need to be implemented to manage these materials safely.

Building Floor Location Number

and Name Item Material

Level of Identification

Risk Assessment

Block A 0 1/006 - Meeting Room

Stair Nosing Strip

Reinforced Composites

SP 2

Block A 0 1/007 - Risers

Insulation Residue To Wall (post Removal)

Thermal Insulation

SP 7

Block A 0 1/007 - Risers

Insulation Residue To Pipework (post Removal)

Thermal Insulation

SP 7

Block A 0 1/007 - Risers

Insulation Residue To Residue (post Removal)

Thermal Insulation

SP 7

Block A 0 1/008 - Electrical Cupboard

Flashguards Textile Rope & Yarn

P 4

Block A 0 1/0101 - Lift Motor Room

Flashguards Textile Rope & Yarn

P 4

Block A 0 1/0116 - Classroom G17

Bitumen Below Parquet Floor

Bitumen Products

P 3

Block A 0 1/0117 - Classroom G18

Bitumen Below Parquet Floor

Bitumen Products

P 3

Block A 0 1/0130 - Boiler Room

Rope Seal To Skylight

Textile Rope & Yarn

P 4

Block A 0 1/0131 - Tank Room Gaskets To Pipework

Thermal Insulation

SP 3

Block A 0 1/0132 - Electrical Cupboard

Bitumen Wrap To Live Cable

Bitumen Products

P 2

Block A 0 1/0132 - Electrical Cupboard

Flashguards Textile Rope & Yarn

P 4

Block A 0 1/0137 - Bathroom Floor Tiles Vinyl SP 3

Page 7: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

2. Executive Summary

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 7 of 60

Manage and Re-inspect

ACMs have been identified which are in good condition. A management policy and plan need to be implemented to manage these materials safely.

Building Floor Location Number

and Name Item Material

Level of Identification

Risk Assessment

Block A 0 1/026 - Kitchen Rope Seal To Skylight

Textile Rope & Yarn

P 4

Block A 0 1/071 - Classroom G3

Floor Floor Tiles SP 2

Block A 0 1/073 - Classroom G2

Floor Floor Tiles SP 2

Block A 1 1/115 - Roof void above Classroom F8

Insulation Residue To Floor Duct

Thermal Insulation

SP 10

Block A 1 1/136 - Classroom F1

Stair Nosing Strip

Reinforced Composites

SP 2

Block A 1 1/137 - Roof Void above Classroom F1

Insulation Residue To Pipework (post Removal Findings)

Thermal Insulation

SP 9

Block A External

Tank Room - Tank Room

Gaskets To Pipework

Thermal Insulation

P 3

Block A External

Outside Main Hall 1/097 - External (low Level)

Damp Proof Membrane

Bitumen Products

SP 3

Block A External

Water Room - Tank Room

Gaskets To Pipework

Thermal Insulation

P 3

Block B 0 2/002 - Office

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 0 2/002 - Stores Floor Tiles Vinyl SP 2

Block B 0 2/003 - Office

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 0 2/004 - Office

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 0 2/006 - Classroom BG1

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 0 2/007 - Classroom BG2

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 0 2/009 - Classroom BG3

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 0 2/012 - Classroom BG5

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 0 2/045 - Canteen

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 0 2/056 - Boiler Room Gaskets To Pipework

Gasket P 3

Page 8: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

2. Executive Summary

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 8 of 60

Manage and Re-inspect

ACMs have been identified which are in good condition. A management policy and plan need to be implemented to manage these materials safely.

Building Floor Location Number

and Name Item Material

Level of Identification

Risk Assessment

Block B 1 2/103 - Sixth Form Maths Classroom

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 1 2/105 - Classroom B11

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 1 2/106 - Staff Room

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 1 2/107 - Classroom B12

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 1 2/109 - Classroom B13

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 1 2/110 - Classroom B14

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 1 2/111 - Classroom B15

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 1 2/114 - Office

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 1 2/115 - Staff Room

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 1 2/122 - Classroom B17

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 1 2/123 - Classroom B16

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block C 0 3/002 - Classroom DG4

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block C 0 3/003 - Classroom DG4 Cupboard

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block C 0 3/033 - Classroom DG1

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block C 0 3/044 - Electrical Cupboard

Flashguards Textile Rope & Yarn

P 4

Block C 0 3/048 - Stores S47

Bitumen Wrap To Live Electrical Cable

Bitumen Products

P 3

Block C 0 3/054 - Classroom Bitumen Below

Bitumen Products

P 2

Page 9: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

2. Executive Summary

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 9 of 60

Manage and Re-inspect

ACMs have been identified which are in good condition. A management policy and plan need to be implemented to manage these materials safely.

Building Floor Location Number

and Name Item Material

Level of Identification

Risk Assessment

Parquet Floor

Block C External

Design Block Roof - External (high Level)

Flue Pipe Cement Products

P 3

Block C External

Design Block Roof - External (high Level)

Cowl Cement Products

P 3

Presumed Items

The following items have been presumed to contain asbestos where it was not possible to access the item in order to sample. These items must be treated as containing asbestos until access can be arranged in order to inspect or sample to confirm or refute the presence of asbestos.

Building Floor Location Number

and Name Item Material

Level of Identification

Risk Assessment

Block A 0 1/008 - Electrical Cupboard

Flashguards Textile Rope & Yarn

P 4

Block A 0 1/0101 - Lift Motor Room

Flashguards Textile Rope & Yarn

P 4

Block A 0 1/0116 - Classroom G17

Bitumen Below Parquet Floor

Bitumen Products

P 3

Block A 0 1/0117 - Classroom G18

Bitumen Below Parquet Floor

Bitumen Products

P 3

Block A 0 1/0130 - Boiler Room

Rope Seal To Skylight

Textile Rope & Yarn

P 4

Block A 0 1/0132 - Electrical Cupboard

Flashguards Textile Rope & Yarn

P 4

Block A 0 1/0132 - Electrical Cupboard

Bitumen Wrap To Live Cable

Bitumen Products

P 2

Block A 0 1/023 - Canteen Life Wall Heaters

Unspecified Material

P 6

Block A 0 1/026 - Kitchen Rope Seal To Skylight

Textile Rope & Yarn

P 4

Block A 0 1/075 - Corridor Insulation Residue To Floor Duct

Thermal Insulation

P 10

Block A 0 1/093 - Stores Sash Window Cord

Textile Rope & Yarn

P 4

Block A 0 1/099 - Stores Insulation Residue To Floor Duct

Thermal Insulation

P 10

Block A 0 1/099 - Stores Board Lining To Sealed Safe

Insulating Board

P 5

Block A External

Tank Room - Tank Room

Gaskets To Pipework

Thermal Insulation

P 3

Block A External

Water Room - Tank Room

Gaskets To Pipework

Thermal Insulation

P 3

Block B 0 2/002 - Office Bitumen Below Parquet

Bitumen Products

P 2

Page 10: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

2. Executive Summary

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 10 of 60

Presumed Items

The following items have been presumed to contain asbestos where it was not possible to access the item in order to sample. These items must be treated as containing asbestos until access can be arranged in order to inspect or sample to confirm or refute the presence of asbestos.

Building Floor Location Number

and Name Item Material

Level of Identification

Risk Assessment

Floor

Block B 0 2/003 - Office

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 0 2/004 - Office

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 0 2/006 - Classroom BG1

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 0 2/007 - Classroom BG2

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 0 2/009 - Classroom BG3

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 0 2/012 - Classroom BG5

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 0 2/045 - Canteen

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 0 2/056 - Boiler Room Gaskets To Pipework

Gasket P 3

Block B 1 2/103 - Sixth Form Maths Classroom

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 1 2/105 - Classroom B11

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 1 2/106 - Staff Room

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 1 2/107 - Classroom B12

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 1 2/109 - Classroom B13

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 1 2/110 - Classroom B14

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 1 2/111 - Classroom B15

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 1 2/114 - Office Bitumen Below Parquet

Bitumen Products

P 2

Page 11: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

2. Executive Summary

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 11 of 60

Presumed Items

The following items have been presumed to contain asbestos where it was not possible to access the item in order to sample. These items must be treated as containing asbestos until access can be arranged in order to inspect or sample to confirm or refute the presence of asbestos.

Building Floor Location Number

and Name Item Material

Level of Identification

Risk Assessment

Floor

Block B 1 2/115 - Staff Room

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 1 2/122 - Classroom B17

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block B 1 2/123 - Classroom B16

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block C 0 3/002 - Classroom DG4

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block C 0 3/003 - Classroom DG4 Cupboard

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block C 0 3/033 - Classroom DG1

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block C 0 3/044 - Electrical Cupboard

Flashguards Textile Rope & Yarn

P 4

Block C 0 3/048 - Stores S47

Bitumen Wrap To Live Electrical Cable

Bitumen Products

P 3

Block C 0 3/054 - Classroom

Bitumen Below Parquet Floor

Bitumen Products

P 2

Block C External

Design Block Roof - External (high Level)

Flue Pipe Cement Products

P 3

Block C External

Design Block Roof - External (high Level)

Cowl Cement Products

P 3

All locations were accessible at the time of this survey.

Page 12: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

2. Executive Summary

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 12 of 60

c. Asbestos Register

Building

Flo

or

Location

Leve

l o

f Id

en

tifi

cati

on

Item

Exte

nt

Material Assessment

Acces

sib

ilit

y

Pri

ori

ty

As

se

ssm

en

t

Recommendation N

ext

Insp

ecti

on

Product Type Condition Surface

Treatment Asbestos

Type

To

tal

Sc

ore

Block A 0 1/006 - Meeting Room

SP Stair Nosing Strip

4Lm Reinforced Composites

Good Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Routinely Disturbed

8 Manage & Re-inspect

23 October 2020

Block A 0 1/007 - Risers SP

Insulation Residue To Wall (post Removal)

6m² Thermal

Insulation Good

Condition Sealed AIB,

spray, textile etc. Crocidolite 7 Easily Disturbed 3

Manage & Re-inspect

23 October 2020

Block A 0 1/007 - Risers SP

Insulation Residue To Pipework (post Removal)

10m² Thermal

Insulation Good

Condition Sealed AIB,

spray, textile etc. Crocidolite 7 Easily Disturbed 3

Manage & Re-inspect

23 October 2020

Block A 0 1/007 - Risers SP

Insulation Residue To Residue (post Removal)

1m² Thermal

Insulation Good

Condition Sealed AIB,

spray, textile etc. Crocidolite 7 Easily Disturbed 2

Manage & Re-inspect

23 October 2020

Block A 0 1/008 - Electrical Cupboard

P Flashguards 1Lm Textile Rope &

Yarn Good

Condition Sealed AIB,

spray, textile etc. Chrysotile 4

Occasional Disturbance

3 Manage & Re-inspect

23 October 2020

Block A 0 1/0101 - Lift Motor Room

P Flashguards 1Lm Textile Rope &

Yarn Good

Condition Sealed AIB,

spray, textile etc. Chrysotile 4

Occasional Disturbance

5 Manage & Re-inspect

23 October 2020

Block A 0 1/0116 - Classroom G17

P

Bitumen Below Parquet Floor

60m² Bitumen Products

Good Condition

Sealed AIB, spray, textile etc.

Chrysotile 3 Usually

inaccessible 5

Manage & Re-inspect

23 October 2020

Block A 0 1/0117 - Classroom G18

P

Bitumen Below Parquet Floor

70m² Bitumen Products

Good Condition

Sealed AIB, spray, textile etc.

Chrysotile 3 Usually

inaccessible 5

Manage & Re-inspect

23 October 2020

Block A 0 1/0130 - Boiler Room

SP Insulation Residue To South Wall

40m² Thermal

Insulation Medium Damage

Sealed AIB, spray, textile etc.

Amosite 8 Easily Disturbed 8 Encapsulate / Repair and Manage

23 October 2020

Page 13: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

2. Executive Summary

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 13 of 60

Building

Flo

or

Location

Le

vel o

f Id

en

tifi

cati

on

Item

Ex

ten

t

Material Assessment

Acces

sib

ilit

y

Pri

ori

ty

As

se

ssm

en

t

Recommendation N

ext

Insp

ecti

on

Product Type Condition Surface

Treatment Asbestos

Type

To

tal S

co

re

Block A 0 1/0130 - Boiler Room

SP Insulation Residue To East Wall

20m² Thermal

Insulation Medium Damage

Sealed AIB, spray, textile etc.

Amosite 8 Easily Disturbed 8 Encapsulate / Repair and Manage

23 October 2020

Block A 0 1/0130 - Boiler Room

SP Insulation Residue To South Wall

40m² Thermal

Insulation Medium Damage

Sealed AIB, spray, textile etc.

Amosite 8 Easily Disturbed 8 Encapsulate / Repair and Manage

23 October 2020

Block A 0 1/0130 - Boiler Room

SP Insulation Residue To North Wall

40m² Thermal

Insulation Medium Damage

Sealed AIB, spray, textile etc.

Amosite 8 Easily Disturbed 8 Encapsulate / Repair and Manage

23 October 2020

Block A 0 1/0130 - Boiler Room

P Rope Seal To Skylight

8Lm Textile Rope &

Yarn Good

Condition Sealed AIB,

spray, textile etc. Chrysotile 4

Usually inaccessible

3 Manage & Re-inspect

23 October 2020

Block A 0 1/0130 - Boiler Room

SP Insulation Residue To West Wall

40m² Thermal

Insulation Medium Damage

Sealed AIB, spray, textile etc.

Amosite 8 Easily Disturbed 8 Encapsulate / Repair and Manage

23 October 2020

Block A 0 1/0131 - Tank Room

SP Gaskets To Pipework

1m² Thermal

Insulation Low

Damage

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 3 Usually

inaccessible 3

Manage & Re-inspect

23 October 2020

Block A 0 1/0132 - Electrical Cupboard

P Flashguards 1Lm Textile Rope &

Yarn Good

Condition Sealed AIB,

spray, textile etc. Chrysotile 4

Occasional Disturbance

3 Manage & Re-inspect

23 October 2020

Block A 0 1/0132 - Electrical Cupboard

P Bitumen Wrap To Live Cable

1Lm Bitumen Products

Good Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Usually

inaccessible 1

Manage & Re-inspect

23 October 2020

Block A 0 1/0137 - Bathroom SP Floor Tiles 6m² Vinyl Low

Damage

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 3 Occasional Disturbance

5 Manage & Re-inspect

23 October 2020

Page 14: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

2. Executive Summary

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 14 of 60

Building

Flo

or

Location

Le

vel o

f Id

en

tifi

cati

on

Item

Ex

ten

t

Material Assessment

Acces

sib

ilit

y

Pri

ori

ty

As

se

ssm

en

t

Recommendation N

ext

Insp

ecti

on

Product Type Condition Surface

Treatment Asbestos

Type

To

tal S

co

re

Block A 0 1/023 - Canteen P Life Wall Heaters

1Lm Unspecified

Material Low

Damage

Composite materials containing asbestos,

plastics, resins etc.

Crocidolite 6 Occasional Disturbance

0 No Access - Inspection Required

23 October 2020

Block A 0 1/026 - Kitchen P Rope Seal To Skylight

8Lm Textile Rope &

Yarn Good

Condition Sealed AIB,

spray, textile etc. Chrysotile 4

Usually inaccessible

5 Manage & Re-inspect

23 October 2020

Block A 0 1/040A - Stores SP Insulation Residue To Pipework

6m² Thermal

Insulation Medium Damage

Sealed AIB, spray, textile etc.

Amosite 8 Easily Disturbed 6 Encapsulate / Repair and Manage

23 October 2020

Block A 0 1/071 - Classroom G3

SP Floor 40m² Floor Tiles Good

Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Easily Disturbed 8 Manage & Re-inspect

23 October 2020

Block A 0 1/073 - Classroom G2

SP Floor 40m² Floor Tiles Good

Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Easily Disturbed 8 Manage & Re-inspect

23 October 2020

Block A 0 1/075 - Corridor P Insulation Residue To Floor Duct

15m² Thermal

Insulation High

Damage Sealed AIB,

spray, textile etc. Crocidolite 10

Usually inaccessible

4 No Access - Inspection Required

23 October 2020

Block A 0 1/093 - Stores P Sash Window Cord

8Lm Textile Rope &

Yarn Good

Condition Sealed AIB,

spray, textile etc. Chrysotile 4

Occasional Disturbance

2 No Access - Inspection Required

23 October 2020

Block A 0 1/099 - Stores P Board Lining To Sealed Safe

1m² Insulating Board Good

Condition Sealed AIB,

spray, textile etc. Amosite 5

Occasional Disturbance

3 No Access - Inspection Required

23 October 2020

Block A 0 1/099 - Stores P Insulation Residue To Floor Duct

5m² Thermal

Insulation High

Damage Sealed AIB,

spray, textile etc. Crocidolite 10

Usually inaccessible

3 No Access - Inspection Required

23 October 2020

Block A 1 1/115 - Roof void above Classroom F8

SP Insulation Residue To Floor Duct

32m² Thermal

Insulation High

Damage Sealed AIB,

spray, textile etc. Crocidolite 10

Usually inaccessible

3 Manage & Re-inspect

23 October 2020

Page 15: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

2. Executive Summary

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 15 of 60

Building

Flo

or

Location

Le

vel o

f Id

en

tifi

cati

on

Item

Ex

ten

t

Material Assessment

Acces

sib

ilit

y

Pri

ori

ty

As

se

ssm

en

t

Recommendation N

ext

Insp

ecti

on

Product Type Condition Surface

Treatment Asbestos

Type

To

tal S

co

re

Block A 1 1/136 - Classroom F1

SP Stair Nosing Strip

4Lm Reinforced Composites

Good Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Routinely Disturbed

9 Manage & Re-inspect

23 October 2020

Block A 1 1/137 - Roof Void above Classroom F1

SP

Insulation Residue To Pipework (post Removal Findings)

2m² Thermal

Insulation Medium Damage

Sealed AIB, spray, textile etc.

Crocidolite 9 Occasional Disturbance

3 Manage & Re-inspect

23 October 2020

Block A Extern

al Tank Room - Tank Room

SP Insulation Residue To Walls

30m² Thermal

Insulation Low

Damage Sealed AIB,

spray, textile etc. Crocidolite 8

Occasional Disturbance

4 Remove by Licensed Asbestos Contractor

23 October 2020

Block A Extern

al Tank Room - Tank Room

P Gaskets To Pipework

2m² Thermal

Insulation Low

Damage

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 3 Usually

inaccessible 3

Manage & Re-inspect

23 October 2020

Block A Extern

al

Outside Main Hall 1/097 - External (low Level)

SP Damp Proof Membrane

50Lm Bitumen Products

Low Damage

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 3 Usually

inaccessible 3

Manage & Re-inspect

23 October 2020

Block A Extern

al Water Room - Tank Room

P Gaskets To Pipework

1m² Thermal

Insulation Low

Damage

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 3 Usually

inaccessible 3

Manage & Re-inspect

23 October 2020

Block B 0 2/002 - Office P

Bitumen Below Parquet Floor

15m² Bitumen Products

Good Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Usually

inaccessible 4

Manage & Re-inspect

23 October 2020

Page 16: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

2. Executive Summary

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 16 of 60

Building

Flo

or

Location

Le

vel o

f Id

en

tifi

cati

on

Item

Ex

ten

t

Material Assessment

Acces

sib

ilit

y

Pri

ori

ty

As

se

ssm

en

t

Recommendation N

ext

Insp

ecti

on

Product Type Condition Surface

Treatment Asbestos

Type

To

tal S

co

re

Block B 0 2/002 - Stores SP Floor Tiles 1m² Vinyl Good

Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Easily Disturbed 3 Manage & Re-inspect

23 October 2020

Block B 0 2/003 - Office P

Bitumen Below Parquet Floor

15m² Bitumen Products

Good Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Usually

inaccessible 4

Manage & Re-inspect

23 October 2020

Block B 0 2/004 - Office P

Bitumen Below Parquet Floor

15m² Bitumen Products

Good Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Usually

inaccessible 4

Manage & Re-inspect

23 October 2020

Block B 0 2/006 - Classroom BG1

P

Bitumen Below Parquet Floor

48m² Bitumen Products

Good Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Usually

inaccessible 4

Manage & Re-inspect

23 October 2020

Block B 0 2/007 - Classroom BG2

P

Bitumen Below Parquet Floor

48m² Bitumen Products

Good Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Usually

inaccessible 4

Manage & Re-inspect

23 October 2020

Block B 0 2/009 - Classroom BG3

P

Bitumen Below Parquet Floor

48m² Bitumen Products

Good Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Usually

inaccessible 4

Manage & Re-inspect

23 October 2020

Page 17: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

2. Executive Summary

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 17 of 60

Building

Flo

or

Location

Le

vel o

f Id

en

tifi

cati

on

Item

Ex

ten

t

Material Assessment

Acces

sib

ilit

y

Pri

ori

ty

As

se

ssm

en

t

Recommendation N

ext

Insp

ecti

on

Product Type Condition Surface

Treatment Asbestos

Type

To

tal S

co

re

Block B 0 2/012 - Classroom BG5

P

Bitumen Below Parquet Floor

50m² Bitumen Products

Good Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Usually

inaccessible 5

Manage & Re-inspect

23 October 2020

Block B 0 2/045 - Canteen P

Bitumen Below Parquet Floor

140m² Bitumen Products

Good Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Usually

inaccessible 7

Manage & Re-inspect

23 October 2020

Block B 0 2/056 - Boiler Room

P Gaskets To Pipework

2m² Gasket Low

Damage

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 3 Usually

inaccessible 5

Manage & Re-inspect

23 October 2020

Block B 1 2/103 - Sixth Form Maths Classroom

P

Bitumen Below Parquet Floor

20m² Bitumen Products

Good Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Usually

inaccessible 4

Manage & Re-inspect

23 October 2020

Block B 1 2/105 - Classroom B11

P

Bitumen Below Parquet Floor

54m² Bitumen Products

Good Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Usually

inaccessible 5

Manage & Re-inspect

23 October 2020

Block B 1 2/106 - Staff Room P

Bitumen Below Parquet Floor

25m² Bitumen Products

Good Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Usually

inaccessible 5

Manage & Re-inspect

23 October 2020

Page 18: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

2. Executive Summary

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 18 of 60

Building

Flo

or

Location

Le

vel o

f Id

en

tifi

cati

on

Item

Ex

ten

t

Material Assessment

Acces

sib

ilit

y

Pri

ori

ty

As

se

ssm

en

t

Recommendation N

ext

Insp

ecti

on

Product Type Condition Surface

Treatment Asbestos

Type

To

tal S

co

re

Block B 1 2/107 - Classroom B12

P

Bitumen Below Parquet Floor

54m² Bitumen Products

Good Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Usually

inaccessible 6

Manage & Re-inspect

23 October 2020

Block B 1 2/109 - Classroom B13

P

Bitumen Below Parquet Floor

45m² Bitumen Products

Good Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Usually

inaccessible 7

Manage & Re-inspect

23 October 2020

Block B 1 2/110 - Classroom B14

P

Bitumen Below Parquet Floor

40m² Bitumen Products

Good Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Usually

inaccessible 7

Manage & Re-inspect

23 October 2020

Block B 1 2/111 - Classroom B15

P

Bitumen Below Parquet Floor

40m² Bitumen Products

Good Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Usually

inaccessible 7

Manage & Re-inspect

23 October 2020

Block B 1 2/114 - Office P

Bitumen Below Parquet Floor

15m² Bitumen Products

Good Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Usually

inaccessible 5

Manage & Re-inspect

23 October 2020

Block B 1 2/115 - Staff Room P

Bitumen Below Parquet Floor

15m² Bitumen Products

Good Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Usually

inaccessible 5

Manage & Re-inspect

23 October 2020

Page 19: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

2. Executive Summary

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 19 of 60

Building

Flo

or

Location

Le

vel o

f Id

en

tifi

cati

on

Item

Ex

ten

t

Material Assessment

Acces

sib

ilit

y

Pri

ori

ty

As

se

ssm

en

t

Recommendation N

ext

Insp

ecti

on

Product Type Condition Surface

Treatment Asbestos

Type

To

tal S

co

re

Block B 1 2/122 - Classroom B17

P

Bitumen Below Parquet Floor

35m² Bitumen Products

Good Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Usually

inaccessible 7

Manage & Re-inspect

23 October 2020

Block B 1 2/123 - Classroom B16

P

Bitumen Below Parquet Floor

40m² Bitumen Products

Good Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Usually

inaccessible 7

Manage & Re-inspect

23 October 2020

Block C 0 3/002 - Classroom DG4

P

Bitumen Below Parquet Floor

66m² Bitumen Products

Good Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Usually

inaccessible 8

Manage & Re-inspect

23 October 2020

Block C 0 3/003 - Classroom DG4 Cupboard

P

Bitumen Below Parquet Floor

1m² Bitumen Products

Good Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Usually

inaccessible 5

Manage & Re-inspect

23 October 2020

Block C 0 3/033 - Classroom DG1

P

Bitumen Below Parquet Floor

90m² Bitumen Products

Good Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Usually

inaccessible 8

Manage & Re-inspect

23 October 2020

Block C 0 3/044 - Electrical Cupboard

P Flashguards 1Lm Textile Rope &

Yarn Good

Condition Sealed AIB,

spray, textile etc. Chrysotile 4

Occasional Disturbance

3 Manage & Re-inspect

23 October 2020

Block C 0 3/048 - Stores S47 P

Bitumen Wrap To Live Electrical Cable

1Lm Bitumen Products

Good Condition

Sealed AIB, spray, textile etc.

Chrysotile 3 Occasional Disturbance

2 Manage & Re-inspect

23 October 2020

Page 20: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

2. Executive Summary

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 20 of 60

Building

Flo

or

Location

Le

vel o

f Id

en

tifi

cati

on

Item

Ex

ten

t

Material Assessment

Acces

sib

ilit

y

Pri

ori

ty

As

se

ssm

en

t

Recommendation N

ext

Insp

ecti

on

Product Type Condition Surface

Treatment Asbestos

Type

To

tal S

co

re

Block C 0 3/054 - Classroom P

Bitumen Below Parquet Floor

50m² Bitumen Products

Good Condition

Composite materials containing asbestos,

plastics, resins etc.

Chrysotile 2 Usually

inaccessible 7

Manage & Re-inspect

23 October 2020

Block C Extern

al

Design Block Roof - External (high Level)

P Flue Pipe 3Lm Cement Products

Good Condition

Sealed AIB, spray, textile etc.

Chrysotile 3 Usually

inaccessible 1

Manage & Re-inspect

23 October 2020

Block C Extern

al

Design Block Roof - External (high Level)

P Cowl 1No. Cement Products

Good Condition

Sealed AIB, spray, textile etc.

Chrysotile 3 Usually

inaccessible 1

Manage & Re-inspect

23 October 2020

Page 21: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 21 of 60

Surveyor Colin Platt Room/Area 1/006 - Meeting Room

Survey Date 23 October 2019 Level of Identification

Strongly Presumed (SP)

Building Block A Sample No SP

Floor Ground Floor Item Stair Nosing Strip

Item Accessibility Easy Amount 4Lm

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Reinforced Composites 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 2 E – Main type of activity 2 Total Priority Score (P.A.) = (1+2+3+4):

8 Total Risk Ass’ Score (P.A. + M.A)

10 Risk Coding LOW

2 = Disturbance = (F+G+H)/3 2 F – Location 2 G – Accessibility 3 H – Extent 0

3 = Exposure potential = (I+J+K)/3 3 I – Number of occupants 2 J – Frequency of use 3 K – Average time in use 3

4 = Maintenance activity = (L+M)/21

L – Type of maintenance0

M – Frequency of maintenance 1

Recommendation:

Manage & Re-inspect

Further Information: Brown stair nosing strips, previously sampled by Safer Spaces as sample 024/182 in report 408469 found to contain chrysotile.

Surveyor Colin Platt Room/Area 1/007 - Risers

Survey Date 23 October 2019 Level of Identification

Strongly Presumed (SP)

Building Block A Sample No SP

Floor Ground Floor Item Insulation Residue To Wall (post Removal)

Item Accessibility Easy Amount 6m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Thermal Insulation 3 Good Condition 0

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Crocidolite 3 7

1 = Normal Occupant Activity = (E) 1 E – Main type of activity 1 Total Priority Score (P.A.) = (1+2+3+4):

3 Total Risk Ass’ Score (P.A. + M.A)

10 Risk Coding LOW

2 = Disturbance = (F+G+H)/3 2 F – Location 2 G – Accessibility 2 H – Extent 1

3 = Exposure potential = (I+J+K)/3 0 I – Number of occupants 0 J – Frequency of use 0 K – Average time in use 0

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Thermal Insulation residue to walls previously sampled by Safer Spaces as sample 024/166 in report 408469 found to contain crocidolite. Residues remain below painted surfaces not removed from area. Unsealed areas of wall have been encapsulated with ET150 during asbestos remedial works undertaken on 05/01/2019. See Life Environmental air certificate B-80385.

Page 22: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 22 of 60

Surveyor Colin Platt Room/Area 1/007 - Risers

Survey Date 23 October 2019 Level of Identification

Strongly Presumed (SP)

Building Block A Sample No SP

Floor Ground Floor Item Insulation Residue To Pipework (post Removal)

Item Accessibility Easy Amount 10m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Thermal Insulation 3 Good Condition 0

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Crocidolite 3 7

1 = Normal Occupant Activity = (E) 1 E – Main type of activity 1 Total Priority Score (P.A.) = (1+2+3+4):

3 Total Risk Ass’ Score (P.A. + M.A)

10 Risk Coding LOW

2 = Disturbance = (F+G+H)/3 2 F – Location 2 G – Accessibility 2 H – Extent 2

3 = Exposure potential = (I+J+K)/3 0 I – Number of occupants 0 J – Frequency of use 0 K – Average time in use 0

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Visually consistent with sample number 024/166 Thermal Insulation residue to pipework previously x ref by Safer Spaces as sample 024/166 in report 408469 found to contain crocidolite. Pipework have been encapsulated in previous asbestos remedial works undertaken on 05/01/2019. See Life Environmental air certificate B-80385.

Surveyor Colin Platt Room/Area 1/007 - Risers

Survey Date 23 October 2019 Level of Identification

Strongly Presumed (SP)

Building Block A Sample No SP

Floor Ground Floor Item Insulation Residue To Residue (post Removal)

Item Accessibility Easy Amount 1m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Thermal Insulation 3 Good Condition 0

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Crocidolite 3 7

1 = Normal Occupant Activity = (E) 1 E – Main type of activity 1 Total Priority Score (P.A.) = (1+2+3+4):

2 Total Risk Ass’ Score (P.A. + M.A)

9 Risk Coding LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 2 H – Extent 0

3 = Exposure potential = (I+J+K)/3 0 I – Number of occupants 0 J – Frequency of use 0 K – Average time in use 0

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Visually consistent with sample number 024/166 Thermal Insulation residue to pipework previously x ref by Safer Spaces as sample 024/166 in report 408469 found to contain crocidolite. Pipework have been encapsulated in previous asbestos remedial works undertaken on 05/01/2019. See Life Environmental air certificate B-80385.

Page 23: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 23 of 60

Surveyor Colin Platt Room/Area 1/008 - Electrical Cupboard

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block A Sample No P

Floor Ground Floor Item Flashguards

Item Accessibility Medium Amount 1Lm

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Textile Rope & Yarn 2 Good Condition 0

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Chrysotile 1 4

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

3 Total Risk Ass’ Score (P.A. + M.A)

7 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 1 H – Extent 0

3 = Exposure potential = (I+J+K)/3 0 I – Number of occupants 0 J – Frequency of use 0 K – Average time in use 0

4 = Maintenance activity = (L+M)/22

L – Type of maintenance2

M – Frequency of maintenance 1

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM flashguards within electrical box, previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed.

Surveyor Colin Platt Room/Area 1/0101 - Lift Motor Room

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block A Sample No P

Floor Ground Floor Item Flashguards

Item Accessibility Medium Amount 1Lm

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Textile Rope & Yarn 2 Good Condition 0

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Chrysotile 1 4

1 = Normal Occupant Activity = (E) 1 E – Main type of activity 1 Total Priority Score (P.A.) = (1+2+3+4):

5 Total Risk Ass’ Score (P.A. + M.A)

9 Risk Coding LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 1 H – Extent 0

3 = Exposure potential = (I+J+K)/3 1 I – Number of occupants 1 J – Frequency of use 1 K – Average time in use 0

4 = Maintenance activity = (L+M)/22

L – Type of maintenance1

M – Frequency of maintenance 2

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM flashguards within electrical box, previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed.

Page 24: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 24 of 60

Surveyor Colin Platt Room/Area 1/0116 - Classroom G17

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block A Sample No P

Floor Ground Floor Item Bitumen Below Parquet Floor

Item Accessibility Difficult Amount 60m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Chrysotile 1 3

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

5 Total Risk Ass’ Score (P.A. + M.A)

8 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 2 F – Location 2 G – Accessibility 0 H – Extent 3

3 = Exposure potential = (I+J+K)/3 3 I – Number of occupants 3 J – Frequency of use 3 K – Average time in use 3

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM bitumen below parquet floor previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Surveyor Colin Platt Room/Area 1/0117 - Classroom G18

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block A Sample No P

Floor Ground Floor Item Bitumen Below Parquet Floor

Item Accessibility Difficult Amount 70m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Chrysotile 1 3

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

5 Total Risk Ass’ Score (P.A. + M.A)

8 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 2 F – Location 2 G – Accessibility 0 H – Extent 3

3 = Exposure potential = (I+J+K)/3 3 I – Number of occupants 3 J – Frequency of use 3 K – Average time in use 3

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM bitumen below parquet floor previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Page 25: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 25 of 60

Surveyor Colin Platt Room/Area 1/0130 - Boiler Room

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block A Sample No P

Floor Ground Floor Item Rope Seal To Skylight

Item Accessibility Difficult Amount 8Lm

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Textile Rope & Yarn 2 Good Condition 0

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Chrysotile 1 4

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

3 Total Risk Ass’ Score (P.A. + M.A)

7 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 0 H – Extent 1

3 = Exposure potential = (I+J+K)/3 1 I – Number of occupants 0 J – Frequency of use 3 K – Average time in use 1

4 = Maintenance activity = (L+M)/21

L – Type of maintenance2

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM role seal to skylights previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Surveyor Colin Platt Room/Area 1/0130 - Boiler Room

Survey Date 23 October 2019 Level of Identification

Strongly Presumed (SP)

Building Block A Sample No SP

Floor Ground Floor Item Insulation Residue To West Wall

Item Accessibility Easy Amount 40m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Thermal Insulation 3 Medium Damage 2

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Amosite 2 8

1 = Normal Occupant Activity = (E) 2 E – Main type of activity 2 Total Priority Score (P.A.) = (1+2+3+4):

8 Total Risk Ass’ Score (P.A. + M.A)

16 Risk Coding MEDIUM

2 = Disturbance = (F+G+H)/3 2 F – Location 2 G – Accessibility 2 H – Extent 2

3 = Exposure potential = (I+J+K)/3 2 I – Number of occupants 1 J – Frequency of use 3 K – Average time in use 1

4 = Maintenance activity = (L+M)/22

L – Type of maintenance2

M – Frequency of maintenance 1

Recommendation:

Encapsulate / Repair and Manage

Further Information: Insulation Residue to West wall previously sampled by Safer Spaces as sample 024/194 in report 408469 to contain amosite. Wall poorly encapsulated with paint, large asbestos insulation shots remain. Lumps to be removed and walls encapsulated or all paint to be removed.

Page 26: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 26 of 60

Surveyor Colin Platt Room/Area 1/0130 - Boiler Room

Survey Date 23 October 2019 Level of Identification

Strongly Presumed (SP)

Building Block A Sample No SP

Floor Ground Floor Item Insulation Residue To North Wall

Item Accessibility Easy Amount 40m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Thermal Insulation 3 Medium Damage 2

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Amosite 2 8

1 = Normal Occupant Activity = (E) 2 E – Main type of activity 2 Total Priority Score (P.A.) = (1+2+3+4):

8 Total Risk Ass’ Score (P.A. + M.A)

16 Risk Coding MEDIUM

2 = Disturbance = (F+G+H)/3 2 F – Location 2 G – Accessibility 2 H – Extent 2

3 = Exposure potential = (I+J+K)/3 2 I – Number of occupants 1 J – Frequency of use 3 K – Average time in use 1

4 = Maintenance activity = (L+M)/22

L – Type of maintenance2

M – Frequency of maintenance 1

Recommendation:

Encapsulate / Repair and Manage

Further Information: Visually consistent with sample number 024/194 Insulation Residue to north wall previously cross referenced by Safer Spaces as sample 024/194 in report 408469 to contain amosite. Wall poorly encapsulated with paint, large asbestos insulation shots remain. Lumps to be removed and walls encapsulated or all paint to be removed.

Surveyor Colin Platt Room/Area 1/0130 - Boiler Room

Survey Date 23 October 2019 Level of Identification

Strongly Presumed (SP)

Building Block A Sample No SP

Floor Ground Floor Item Insulation Residue To South Wall

Item Accessibility Easy Amount 40m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Thermal Insulation 3 Medium Damage 2

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Amosite 2 8

1 = Normal Occupant Activity = (E) 2 E – Main type of activity 2 Total Priority Score (P.A.) = (1+2+3+4):

8 Total Risk Ass’ Score (P.A. + M.A)

16 Risk Coding MEDIUM

2 = Disturbance = (F+G+H)/3 2 F – Location 2 G – Accessibility 2 H – Extent 2

3 = Exposure potential = (I+J+K)/3 2 I – Number of occupants 1 J – Frequency of use 3 K – Average time in use 1

4 = Maintenance activity = (L+M)/22

L – Type of maintenance2

M – Frequency of maintenance 1

Recommendation:

Encapsulate / Repair and Manage

Further Information: Visually consistent with sample number 024/194 Insulation Residue to south wall previously cross referenced by Safer Spaces as sample 024/194 in report 408469 to contain amosite. Wall poorly encapsulated with paint, large asbestos insulation shots remain. Lumps to be removed and walls encapsulated or all paint to be removed.

Page 27: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 27 of 60

Surveyor Colin Platt Room/Area 1/0130 - Boiler Room

Survey Date 23 October 2019 Level of Identification

Strongly Presumed (SP)

Building Block A Sample No SP

Floor Ground Floor Item Insulation Residue To East Wall

Item Accessibility Easy Amount 20m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Thermal Insulation 3 Medium Damage 2

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Amosite 2 8

1 = Normal Occupant Activity = (E) 2 E – Main type of activity 2 Total Priority Score (P.A.) = (1+2+3+4):

8 Total Risk Ass’ Score (P.A. + M.A)

16 Risk Coding MEDIUM

2 = Disturbance = (F+G+H)/3 2 F – Location 2 G – Accessibility 2 H – Extent 2

3 = Exposure potential = (I+J+K)/3 2 I – Number of occupants 1 J – Frequency of use 3 K – Average time in use 1

4 = Maintenance activity = (L+M)/22

L – Type of maintenance2

M – Frequency of maintenance 1

Recommendation:

Encapsulate / Repair and Manage

Further Information: Visually consistent with sample number 024/194 Insulation Residue to east wall previously cross referenced by Safer Spaces as sample 024/194 in report 408469 to contain amosite. Wall poorly encapsulated with paint, large asbestos insulation shots remain. Lumps to be removed and walls encapsulated or all paint to be removed.

Surveyor Colin Platt Room/Area 1/0130 - Boiler Room

Survey Date 23 October 2019 Level of Identification

Strongly Presumed (SP)

Building Block A Sample No SP

Floor Ground Floor Item Insulation Residue To South Wall

Item Accessibility Easy Amount 40m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Thermal Insulation 3 Medium Damage 2

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Amosite 2 8

1 = Normal Occupant Activity = (E) 2 E – Main type of activity 2 Total Priority Score (P.A.) = (1+2+3+4):

8 Total Risk Ass’ Score (P.A. + M.A)

16 Risk Coding MEDIUM

2 = Disturbance = (F+G+H)/3 2 F – Location 2 G – Accessibility 2 H – Extent 2

3 = Exposure potential = (I+J+K)/3 2 I – Number of occupants 1 J – Frequency of use 3 K – Average time in use 1

4 = Maintenance activity = (L+M)/22

L – Type of maintenance2

M – Frequency of maintenance 1

Recommendation:

Encapsulate / Repair and Manage

Further Information: Visually consistent with sample number 024/194 Insulation Residue to south wall previously cross referenced by Safer Spaces as sample 024/194 in report 408469 to contain amosite. Wall poorly encapsulated with paint, large asbestos insulation shots remain. Lumps to be removed and walls encapsulated or all paint to be removed.

Page 28: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 28 of 60

Surveyor Colin Platt Room/Area 1/0131 - Tank Room

Survey Date 23 October 2019 Level of Identification

Strongly Presumed (SP)

Building Block A Sample No SP

Floor Ground Floor Item Gaskets To Pipework

Item Accessibility Difficult Amount 1m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Thermal Insulation 1 Low Damage 1 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 3

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

3 Total Risk Ass’ Score (P.A. + M.A)

6 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 0 H – Extent 0

3 = Exposure potential = (I+J+K)/3 0 I – Number of occupants 0 J – Frequency of use 1 K – Average time in use 0

4 = Maintenance activity = (L+M)/22

L – Type of maintenance1

M – Frequency of maintenance 2

Recommendation:

Manage & Re-inspect

Further Information: Gaskets to pipework, previously sampled by Safer Spaces as sample 024/200 in report 408469 found to contain chrysotile.

Surveyor Colin Platt Room/Area 1/0132 - Electrical Cupboard

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block A Sample No P

Floor Ground Floor Item Flashguards

Item Accessibility Medium Amount 1Lm

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Textile Rope & Yarn 2 Good Condition 0

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Chrysotile 1 4

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

3 Total Risk Ass’ Score (P.A. + M.A)

7 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 1 H – Extent 0

3 = Exposure potential = (I+J+K)/3 0 I – Number of occupants 0 J – Frequency of use 0 K – Average time in use 0

4 = Maintenance activity = (L+M)/22

L – Type of maintenance2

M – Frequency of maintenance 1

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM flashguards within electrical box, previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed.

Page 29: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 29 of 60

Surveyor Colin Platt Room/Area 1/0132 - Electrical Cupboard

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block A Sample No P

Floor Ground Floor Item Bitumen Wrap To Live Cable

Item Accessibility Difficult Amount 1Lm

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

1 Total Risk Ass’ Score (P.A. + M.A)

3 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 0 H – Extent 0

3 = Exposure potential = (I+J+K)/3 0 I – Number of occupants 0 J – Frequency of use 0 K – Average time in use 0

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM bitumen wrap to live electrical cable, previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed.

Surveyor Colin Platt Room/Area 1/0137 - Bathroom

Survey Date 23 October 2019 Level of Identification

Strongly Presumed (SP)

Building Block A Sample No SP

Floor Ground Floor Item Floor Tiles

Item Accessibility Medium Amount 6m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Vinyl 1 Low Damage 1 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 3

1 = Normal Occupant Activity = (E) 2 E – Main type of activity 2 Total Priority Score (P.A.) = (1+2+3+4):

5 Total Risk Ass’ Score (P.A. + M.A)

8 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 1 H – Extent 1

3 = Exposure potential = (I+J+K)/3 1 I – Number of occupants 1 J – Frequency of use 3 K – Average time in use 0

4 = Maintenance activity = (L+M)/21

L – Type of maintenance0

M – Frequency of maintenance 1

Recommendation:

Manage & Re-inspect

Further Information: Floor Tiles and adhesive, previously sampled by Safer Spaces as sample 024/165 in report 408469 found to contain chrysotile.

Page 30: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 30 of 60

Surveyor Colin Platt Room/Area 1/023 - Canteen

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block A Sample No P

Floor Ground Floor Item Life Wall Heaters

Item Accessibility Medium Amount 1Lm

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Unspecified Material 2 Low Damage 1 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Crocidolite 3 6

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

0 Total Risk Ass’ Score (P.A. + M.A)

6 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 0 F – Location 0 G – Accessibility 1 H – Extent 0

3 = Exposure potential = (I+J+K)/3 0 I – Number of occupants 0 J – Frequency of use 0 K – Average time in use 0

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

No Access - Inspection Required

Further Information: This location was not accessed and as such should be presumed to contain asbestos until proven otherwise. No access into live wall heaters previously presumed by Safer Spaces in report 408469 to contain crocodile until accessed. No access due to damage limitations.

Surveyor Colin Platt Room/Area 1/026 - Kitchen

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block A Sample No P

Floor Ground Floor Item Rope Seal To Skylight

Item Accessibility Difficult Amount 8Lm

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Textile Rope & Yarn 2 Good Condition 0

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Chrysotile 1 4

1 = Normal Occupant Activity = (E) 1 E – Main type of activity 1 Total Priority Score (P.A.) = (1+2+3+4):

5 Total Risk Ass’ Score (P.A. + M.A)

9 Risk Coding LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 0 H – Extent 1

3 = Exposure potential = (I+J+K)/3 2 I – Number of occupants 1 J – Frequency of use 3 K – Average time in use 2

4 = Maintenance activity = (L+M)/21

L – Type of maintenance1

M – Frequency of maintenance 1

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM role seal to skylights previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Page 31: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 31 of 60

Surveyor Colin Platt Room/Area 1/040A - Stores

Survey Date 23 October 2019 Level of Identification

Strongly Presumed (SP)

Building Block A Sample No SP

Floor Ground Floor Item Insulation Residue To Pipework

Item Accessibility Easy Amount 6m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Thermal Insulation 3 Medium Damage 2

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Amosite 2 8

1 = Normal Occupant Activity = (E) 1 E – Main type of activity 1 Total Priority Score (P.A.) = (1+2+3+4):

6 Total Risk Ass’ Score (P.A. + M.A)

14 Risk Coding MEDIUM

2 = Disturbance = (F+G+H)/3 2 F – Location 2 G – Accessibility 2 H – Extent 1

3 = Exposure potential = (I+J+K)/3 2 I – Number of occupants 1 J – Frequency of use 3 K – Average time in use 1

4 = Maintenance activity = (L+M)/21

L – Type of maintenance1

M – Frequency of maintenance 1

Recommendation:

Encapsulate / Repair and Manage

Further Information: Insulation Residue to pipework Previously sampled by Safer Spaces as sample 024/203 in report 408469 found to contain Amosite. Upon re-election further than encapsulation is required.

Surveyor Colin Platt Room/Area 1/071 - Classroom G3

Survey Date 23 October 2019 Level of Identification

Strongly Presumed (SP)

Building Block A Sample No SP

Floor Ground Floor Item Floor

Item Accessibility Easy Amount 40m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Floor Tiles 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 2 E – Main type of activity 2 Total Priority Score (P.A.) = (1+2+3+4):

8 Total Risk Ass’ Score (P.A. + M.A)

10 Risk Coding LOW

2 = Disturbance = (F+G+H)/3 2 F – Location 2 G – Accessibility 2 H – Extent 2

3 = Exposure potential = (I+J+K)/3 3 I – Number of occupants 3 J – Frequency of use 3 K – Average time in use 3

4 = Maintenance activity = (L+M)/21

L – Type of maintenance0

M – Frequency of maintenance 1

Recommendation:

Manage & Re-inspect

Further Information: Floor Tiles and adhesive below carpet, previously sampled by Safer Spaces as sample 024/179 in report 408469 found to contain chrysotile.

Page 32: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 32 of 60

Surveyor Colin Platt Room/Area 1/073 - Classroom G2

Survey Date 23 October 2019 Level of Identification

Strongly Presumed (SP)

Building Block A Sample No SP

Floor Ground Floor Item Floor

Item Accessibility Easy Amount 40m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Floor Tiles 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 2 E – Main type of activity 2 Total Priority Score (P.A.) = (1+2+3+4):

8 Total Risk Ass’ Score (P.A. + M.A)

10 Risk Coding LOW

2 = Disturbance = (F+G+H)/3 2 F – Location 2 G – Accessibility 2 H – Extent 2

3 = Exposure potential = (I+J+K)/3 3 I – Number of occupants 3 J – Frequency of use 3 K – Average time in use 3

4 = Maintenance activity = (L+M)/21

L – Type of maintenance0

M – Frequency of maintenance 1

Recommendation:

Manage & Re-inspect

Further Information: Visually consistent with sample number 024/179 Floor Tiles and adhesive below carpet, previously cross referenced by Safer Spaces as sample 024/179 in report 408469 found to contain chrysotile.

Surveyor Colin Platt Room/Area 1/075 - Corridor

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block A Sample No P

Floor Ground Floor Item Insulation Residue To Floor Duct

Item Accessibility Difficult Amount 15m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Thermal Insulation 3 High Damage 3

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Crocidolite 3 10

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

4 Total Risk Ass’ Score (P.A. + M.A)

14 Risk Coding MEDIUM

2 = Disturbance = (F+G+H)/3 2 F – Location 3 G – Accessibility 0 H – Extent 2

3 = Exposure potential = (I+J+K)/3 0 I – Number of occupants 0 J – Frequency of use 0 K – Average time in use 0

4 = Maintenance activity = (L+M)/22

L – Type of maintenance3

M – Frequency of maintenance 1

Recommendation:

No Access - Inspection Required

Further Information: Presumed ACM Thermal Insulation Residue to floor duct previously presumed by Safer Spaces in report 408469 to contain crocidolite until accessed. No access into duct due to damage limitations.

Page 33: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 33 of 60

Surveyor Colin Platt Room/Area 1/093 - Stores

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block A Sample No P

Floor Ground Floor Item Sash Window Cord

Item Accessibility Medium Amount 8Lm

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Textile Rope & Yarn 2 Good Condition 0

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Chrysotile 1 4

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

2 Total Risk Ass’ Score (P.A. + M.A)

6 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 1 H – Extent 1

3 = Exposure potential = (I+J+K)/3 0 I – Number of occupants 0 J – Frequency of use 0 K – Average time in use 0

4 = Maintenance activity = (L+M)/21

L – Type of maintenance1

M – Frequency of maintenance 1

Recommendation:

No Access - Inspection Required

Further Information: Presumed ACM sash window cords previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access into duct due to damage limitations.

Surveyor Colin Platt Room/Area 1/099 - Stores

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block A Sample No P

Floor Ground Floor Item Board Lining To Sealed Safe

Item Accessibility Medium Amount 1m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Insulating Board 2 Good Condition 0

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Amosite 2 5

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

3 Total Risk Ass’ Score (P.A. + M.A)

8 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 1 H – Extent 0

3 = Exposure potential = (I+J+K)/3 0 I – Number of occupants 0 J – Frequency of use 0 K – Average time in use 0

4 = Maintenance activity = (L+M)/22

L – Type of maintenance2

M – Frequency of maintenance 1

Recommendation:

No Access - Inspection Required

Further Information: Presumed ACM board lining to Sealed safe previously presumed by Safer Spaces in report 408469 to contain amosite until accessed. No access due to damage limitations. No access for purposes of reinspection.

Page 34: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 34 of 60

Surveyor Colin Platt Room/Area 1/099 - Stores

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block A Sample No P

Floor Ground Floor Item Insulation Residue To Floor Duct

Item Accessibility Difficult Amount 5m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Thermal Insulation 3 High Damage 3

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Crocidolite 3 10

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

3 Total Risk Ass’ Score (P.A. + M.A)

13 Risk Coding LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 3 G – Accessibility 0 H – Extent 1

3 = Exposure potential = (I+J+K)/3 0 I – Number of occupants 0 J – Frequency of use 0 K – Average time in use 0

4 = Maintenance activity = (L+M)/22

L – Type of maintenance3

M – Frequency of maintenance 1

Recommendation:

No Access - Inspection Required

Further Information: Presumed ACM Thermal Insulation Residue to floor duct previously presumed by Safer Spaces in report 408469 to contain crocidolite until accessed. No access into duct due to damage limitations. No access for purposes of reinspection.

Surveyor Colin Platt Room/Area 1/115 - Roof void above Classroom F8

Survey Date 23 October 2019 Level of Identification

Strongly Presumed (SP)

Building Block A Sample No SP

Floor 1st Floor Item Insulation Residue To Floor Duct

Item Accessibility Difficult Amount 32m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Thermal Insulation 3 High Damage 3

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Crocidolite 3 10

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

3 Total Risk Ass’ Score (P.A. + M.A)

13 Risk Coding LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 0 H – Extent 2

3 = Exposure potential = (I+J+K)/3 0 I – Number of occupants 0 J – Frequency of use 0 K – Average time in use 0

4 = Maintenance activity = (L+M)/22

L – Type of maintenance3

M – Frequency of maintenance 1

Recommendation:

Manage & Re-inspect

Further Information: Visually consistent with sample number 024/193 insulation residue to pipework Previously S ref by Safer Spaces to sample 25/193 in report 408469. Roof void inspected as part of the remedial works undertaken on the 05 01/2019. Sectional areas Previously sheets to create clean area for maintenance access had been visually inspected and no visible asbestos containing materials identified. Areas beyond the sheeted area are still deemed to be contaminated.

Page 35: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 35 of 60

Surveyor Colin Platt Room/Area 1/136 - Classroom F1

Survey Date 23 October 2019 Level of Identification

Strongly Presumed (SP)

Building Block A Sample No SP

Floor 1st Floor Item Stair Nosing Strip

Item Accessibility Easy Amount 4Lm

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Reinforced Composites 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 3 E – Main type of activity 3 Total Priority Score (P.A.) = (1+2+3+4):

9 Total Risk Ass’ Score (P.A. + M.A)

11 Risk Coding LOW

2 = Disturbance = (F+G+H)/3 2 F – Location 2 G – Accessibility 3 H – Extent 0

3 = Exposure potential = (I+J+K)/3 3 I – Number of occupants 3 J – Frequency of use 3 K – Average time in use 3

4 = Maintenance activity = (L+M)/21

L – Type of maintenance0

M – Frequency of maintenance 1

Recommendation:

Manage & Re-inspect

Further Information: Brown stair nosing strips, previously sampled by Safer Spaces as sample 024/190 in report 408469 found to contain chrysotile.

Surveyor Colin Platt Room/Area 1/137 - Roof Void above Classroom F1

Survey Date 23 October 2019 Level of Identification

Strongly Presumed (SP)

Building Block A Sample No SP

Floor 1st Floor Item Insulation Residue To Pipework (post Removal Findings)

Item Accessibility Medium Amount 2m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Thermal Insulation 3 Medium Damage 2

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Crocidolite 3 9

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

3 Total Risk Ass’ Score (P.A. + M.A)

12 Risk Coding LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 1 H – Extent 0

3 = Exposure potential = (I+J+K)/3 0 I – Number of occupants 0 J – Frequency of use 0 K – Average time in use 0

4 = Maintenance activity = (L+M)/22

L – Type of maintenance3

M – Frequency of maintenance 1

Recommendation:

Manage & Re-inspect

Further Information: Previously sampled by Safer Spaces as sample 024/193 Pipework sealed as part of previous asbestos remedial works. Thermal residue identified to Wall behind pipework, within pipe flashing to Floor penetration point and adjacent surfaces had been removed as far as reasonably practicable during asbestos remedial works undertaken on 05/01/2018. See Life Environmental Services air test certificate B-80385.

Page 36: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 36 of 60

Surveyor Colin Platt Room/Area Tank Room - Tank Room

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block A Sample No P

Floor External Item Gaskets To Pipework

Item Accessibility Difficult Amount 2m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Thermal Insulation 1 Low Damage 1 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 3

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

3 Total Risk Ass’ Score (P.A. + M.A)

6 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 0 H – Extent 0

3 = Exposure potential = (I+J+K)/3 0 I – Number of occupants 0 J – Frequency of use 1 K – Average time in use 0

4 = Maintenance activity = (L+M)/22

L – Type of maintenance1

M – Frequency of maintenance 2

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM Gaskets to pipework, previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access into room at time of survey, item presumed to remain I. Situ.

Surveyor Colin Platt Room/Area Tank Room - Tank Room

Survey Date 23 October 2019 Level of Identification

Strongly Presumed (SP)

Building Block A Sample No SP

Floor External Item Insulation Residue To Walls

Item Accessibility Medium Amount 30m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Thermal Insulation 3 Low Damage 1

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Crocidolite 3 8

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

4 Total Risk Ass’ Score (P.A. + M.A)

12 Risk Coding LOW

2 = Disturbance = (F+G+H)/3 2 F – Location 2 G – Accessibility 1 H – Extent 2

3 = Exposure potential = (I+J+K)/3 0 I – Number of occupants 0 J – Frequency of use 0 K – Average time in use 0

4 = Maintenance activity = (L+M)/22

L – Type of maintenance3

M – Frequency of maintenance 1

Recommendation:

Remove by Licensed Asbestos Contractor

Further Information: Insulation Residue to walls, previously sampled by Safer Spaces as sample 024/198 in report 408469 to contain crocidolite. No access into room at time of survey, item presumed to remain in Situ.

Page 37: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 37 of 60

Surveyor Colin Platt Room/Area Outside Main Hall 1/097 - External (low Level)

Survey Date 23 October 2019 Level of Identification

Strongly Presumed (SP)

Building Block A Sample No SP

Floor External Item Damp Proof Membrane

Item Accessibility Difficult Amount 50Lm

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Low Damage 1 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 3

1 = Normal Occupant Activity = (E) 1 E – Main type of activity 1 Total Priority Score (P.A.) = (1+2+3+4):

3 Total Risk Ass’ Score (P.A. + M.A)

6 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 0 G – Accessibility 0 H – Extent 3

3 = Exposure potential = (I+J+K)/3 0 I – Number of occupants 0 J – Frequency of use 0 K – Average time in use 0

4 = Maintenance activity = (L+M)/21

L – Type of maintenance1

M – Frequency of maintenance 1

Recommendation:

Manage & Re-inspect

Further Information: Bitumen camp proof course to perimeter of building, previously sampled by Safer Spaces as sample 024/197 in report 408469 to contain chrysotile.

Surveyor Colin Platt Room/Area Water Room - Tank Room

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block A Sample No P

Floor External Item Gaskets To Pipework

Item Accessibility Difficult Amount 1m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Thermal Insulation 1 Low Damage 1 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 3

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

3 Total Risk Ass’ Score (P.A. + M.A)

6 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 0 H – Extent 0

3 = Exposure potential = (I+J+K)/3 0 I – Number of occupants 0 J – Frequency of use 1 K – Average time in use 0

4 = Maintenance activity = (L+M)/22

L – Type of maintenance1

M – Frequency of maintenance 2

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM Gaskets to pipework, previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to height restrictions.

Page 38: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 38 of 60

Surveyor Colin Platt Room/Area 2/002 - Office

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block B Sample No P

Floor Ground Floor Item Bitumen Below Parquet Floor

Item Accessibility Difficult Amount 15m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 1 E – Main type of activity 1 Total Priority Score (P.A.) = (1+2+3+4):

4 Total Risk Ass’ Score (P.A. + M.A)

6 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 0 H – Extent 2

3 = Exposure potential = (I+J+K)/3 2 I – Number of occupants 1 J – Frequency of use 3 K – Average time in use 3

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM bitumen below parquet floor previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Surveyor Colin Platt Room/Area 2/002 - Stores

Survey Date 23 October 2019 Level of Identification

Strongly Presumed (SP)

Building Block B Sample No SP

Floor Ground Floor Item Floor Tiles

Item Accessibility Easy Amount 1m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Vinyl 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

3 Total Risk Ass’ Score (P.A. + M.A)

5 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 2 H – Extent 0

3 = Exposure potential = (I+J+K)/3 1 I – Number of occupants 1 J – Frequency of use 3 K – Average time in use 0

4 = Maintenance activity = (L+M)/21

L – Type of maintenance0

M – Frequency of maintenance 1

Recommendation:

Manage & Re-inspect

Further Information: Floor Tiles and adhesive previously sampled by Safer Spaces as sample 024/209 in report 408469 found to contain chrysotile

Page 39: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 39 of 60

Surveyor Colin Platt Room/Area 2/003 - Office

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block B Sample No P

Floor Ground Floor Item Bitumen Below Parquet Floor

Item Accessibility Difficult Amount 15m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 1 E – Main type of activity 1 Total Priority Score (P.A.) = (1+2+3+4):

4 Total Risk Ass’ Score (P.A. + M.A)

6 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 0 H – Extent 2

3 = Exposure potential = (I+J+K)/3 2 I – Number of occupants 1 J – Frequency of use 3 K – Average time in use 3

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM bitumen below parquet floor previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Surveyor Colin Platt Room/Area 2/004 - Office

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block B Sample No P

Floor Ground Floor Item Bitumen Below Parquet Floor

Item Accessibility Difficult Amount 15m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 1 E – Main type of activity 1 Total Priority Score (P.A.) = (1+2+3+4):

4 Total Risk Ass’ Score (P.A. + M.A)

6 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 0 H – Extent 2

3 = Exposure potential = (I+J+K)/3 2 I – Number of occupants 1 J – Frequency of use 3 K – Average time in use 3

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM bitumen below parquet floor previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Page 40: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 40 of 60

Surveyor Colin Platt Room/Area 2/006 - Classroom BG1

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block B Sample No P

Floor Ground Floor Item Bitumen Below Parquet Floor

Item Accessibility Difficult Amount 48m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

4 Total Risk Ass’ Score (P.A. + M.A)

6 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 0 H – Extent 2

3 = Exposure potential = (I+J+K)/3 3 I – Number of occupants 3 J – Frequency of use 3 K – Average time in use 3

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM bitumen below parquet floor previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Surveyor Colin Platt Room/Area 2/007 - Classroom BG2

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block B Sample No P

Floor Ground Floor Item Bitumen Below Parquet Floor

Item Accessibility Difficult Amount 48m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

4 Total Risk Ass’ Score (P.A. + M.A)

6 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 0 H – Extent 2

3 = Exposure potential = (I+J+K)/3 3 I – Number of occupants 3 J – Frequency of use 3 K – Average time in use 3

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM bitumen below parquet floor previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Page 41: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 41 of 60

Surveyor Colin Platt Room/Area 2/009 - Classroom BG3

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block B Sample No P

Floor Ground Floor Item Bitumen Below Parquet Floor

Item Accessibility Difficult Amount 48m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

4 Total Risk Ass’ Score (P.A. + M.A)

6 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 0 H – Extent 2

3 = Exposure potential = (I+J+K)/3 3 I – Number of occupants 3 J – Frequency of use 3 K – Average time in use 3

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM bitumen below parquet floor previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Surveyor Colin Platt Room/Area 2/012 - Classroom BG5

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block B Sample No P

Floor Ground Floor Item Bitumen Below Parquet Floor

Item Accessibility Difficult Amount 50m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

5 Total Risk Ass’ Score (P.A. + M.A)

7 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 2 F – Location 2 G – Accessibility 0 H – Extent 3

3 = Exposure potential = (I+J+K)/3 3 I – Number of occupants 3 J – Frequency of use 3 K – Average time in use 3

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM bitumen below parquet floor previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Page 42: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 42 of 60

Surveyor Colin Platt Room/Area 2/045 - Canteen

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block B Sample No P

Floor Ground Floor Item Bitumen Below Parquet Floor

Item Accessibility Difficult Amount 140m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 3 E – Main type of activity 3 Total Priority Score (P.A.) = (1+2+3+4):

7 Total Risk Ass’ Score (P.A. + M.A)

9 Risk Coding LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 1 G – Accessibility 0 H – Extent 3

3 = Exposure potential = (I+J+K)/3 3 I – Number of occupants 3 J – Frequency of use 3 K – Average time in use 3

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM bitumen below parquet floor previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Surveyor Colin Platt Room/Area 2/056 - Boiler Room

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block B Sample No P

Floor Ground Floor Item Gaskets To Pipework

Item Accessibility Difficult Amount 2m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Gasket 1 Low Damage 1 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 3

1 = Normal Occupant Activity = (E) 1 E – Main type of activity 1 Total Priority Score (P.A.) = (1+2+3+4):

5 Total Risk Ass’ Score (P.A. + M.A)

8 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 0 H – Extent 0

3 = Exposure potential = (I+J+K)/3 1 I – Number of occupants 1 J – Frequency of use 2 K – Average time in use 1

4 = Maintenance activity = (L+M)/22

L – Type of maintenance1

M – Frequency of maintenance 2

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM Gaskets to pipework, previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed.

Page 43: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 43 of 60

Surveyor Colin Platt Room/Area 2/056 - Boiler Room

Survey Date 23 October 2019 Level of Identification

Inspected Area (IA)

Building Block B Sample No IA

Floor Ground Floor Item Bitumen Wrap To Live Electrical Cable

Item Accessibility Amount

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

No Suspect Materials Seen

Asbestos Removed 0

1 = Normal Occupant Activity = (E) E – Main type of activity Total Priority Score (P.A.) = (1+2+3+4):

Total Risk Ass’ Score (P.A. + M.A)

0 Risk Coding

2 = Disturbance = (F+G+H)/3 F – Location G – Accessibility H – Extent

3 = Exposure potential = (I+J+K)/3 I – Number of occupants J – Frequency of use K – Average time in use

4 = Maintenance activity = (L+M)/2 L – Type of maintenance M – Frequency of maintenance

Recommendation:

No recommendation required

Further Information: Area visually inspected. No suspect materials seen. Presumed ACM bitumen wrap to live electrical cable, previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. Asbestos Removed

Surveyor Colin Platt Room/Area 2/103 - Sixth Form Maths Classroom

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block B Sample No P

Floor 1st Floor Item Bitumen Below Parquet Floor

Item Accessibility Difficult Amount 20m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

4 Total Risk Ass’ Score (P.A. + M.A)

6 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 0 H – Extent 2

3 = Exposure potential = (I+J+K)/3 3 I – Number of occupants 3 J – Frequency of use 3 K – Average time in use 3

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM bitumen below parquet floor previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Page 44: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 44 of 60

Surveyor Colin Platt Room/Area 2/105 - Classroom B11

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block B Sample No P

Floor 1st Floor Item Bitumen Below Parquet Floor

Item Accessibility Difficult Amount 54m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

5 Total Risk Ass’ Score (P.A. + M.A)

7 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 2 F – Location 2 G – Accessibility 0 H – Extent 3

3 = Exposure potential = (I+J+K)/3 3 I – Number of occupants 3 J – Frequency of use 3 K – Average time in use 3

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM bitumen below parquet floor previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Surveyor Colin Platt Room/Area 2/106 - Staff Room

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block B Sample No P

Floor 1st Floor Item Bitumen Below Parquet Floor

Item Accessibility Difficult Amount 25m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 1 E – Main type of activity 1 Total Priority Score (P.A.) = (1+2+3+4):

5 Total Risk Ass’ Score (P.A. + M.A)

7 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 0 H – Extent 2

3 = Exposure potential = (I+J+K)/3 2 I – Number of occupants 2 J – Frequency of use 3 K – Average time in use 2

4 = Maintenance activity = (L+M)/21

L – Type of maintenance0

M – Frequency of maintenance 1

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM bitumen below parquet floor previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Page 45: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 45 of 60

Surveyor Colin Platt Room/Area 2/107 - Classroom B12

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block B Sample No P

Floor 1st Floor Item Bitumen Below Parquet Floor

Item Accessibility Difficult Amount 54m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 2 E – Main type of activity 2 Total Priority Score (P.A.) = (1+2+3+4):

6 Total Risk Ass’ Score (P.A. + M.A)

8 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 2 F – Location 2 G – Accessibility 0 H – Extent 3

3 = Exposure potential = (I+J+K)/3 2 I – Number of occupants 2 J – Frequency of use 3 K – Average time in use 1

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM bitumen below parquet floor previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Surveyor Colin Platt Room/Area 2/109 - Classroom B13

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block B Sample No P

Floor 1st Floor Item Bitumen Below Parquet Floor

Item Accessibility Difficult Amount 45m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 3 E – Main type of activity 3 Total Priority Score (P.A.) = (1+2+3+4):

7 Total Risk Ass’ Score (P.A. + M.A)

9 Risk Coding LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 0 H – Extent 2

3 = Exposure potential = (I+J+K)/3 3 I – Number of occupants 3 J – Frequency of use 3 K – Average time in use 3

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM bitumen below parquet floor previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Page 46: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 46 of 60

Surveyor Colin Platt Room/Area 2/110 - Classroom B14

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block B Sample No P

Floor 1st Floor Item Bitumen Below Parquet Floor

Item Accessibility Difficult Amount 40m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 3 E – Main type of activity 3 Total Priority Score (P.A.) = (1+2+3+4):

7 Total Risk Ass’ Score (P.A. + M.A)

9 Risk Coding LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 0 H – Extent 2

3 = Exposure potential = (I+J+K)/3 3 I – Number of occupants 3 J – Frequency of use 3 K – Average time in use 3

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM bitumen below parquet floor previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Surveyor Colin Platt Room/Area 2/111 - Classroom B15

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block B Sample No P

Floor 1st Floor Item Bitumen Below Parquet Floor

Item Accessibility Difficult Amount 40m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 3 E – Main type of activity 3 Total Priority Score (P.A.) = (1+2+3+4):

7 Total Risk Ass’ Score (P.A. + M.A)

9 Risk Coding LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 0 H – Extent 2

3 = Exposure potential = (I+J+K)/3 3 I – Number of occupants 3 J – Frequency of use 3 K – Average time in use 3

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM bitumen below parquet floor previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Page 47: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 47 of 60

Surveyor Colin Platt Room/Area 2/114 - Office

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block B Sample No P

Floor 1st Floor Item Bitumen Below Parquet Floor

Item Accessibility Difficult Amount 15m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 1 E – Main type of activity 1 Total Priority Score (P.A.) = (1+2+3+4):

5 Total Risk Ass’ Score (P.A. + M.A)

7 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 0 H – Extent 2

3 = Exposure potential = (I+J+K)/3 2 I – Number of occupants 1 J – Frequency of use 3 K – Average time in use 3

4 = Maintenance activity = (L+M)/21

L – Type of maintenance1

M – Frequency of maintenance 1

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM bitumen below parquet floor previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Surveyor Colin Platt Room/Area 2/115 - Staff Room

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block B Sample No P

Floor 1st Floor Item Bitumen Below Parquet Floor

Item Accessibility Difficult Amount 15m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 1 E – Main type of activity 1 Total Priority Score (P.A.) = (1+2+3+4):

5 Total Risk Ass’ Score (P.A. + M.A)

7 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 0 H – Extent 2

3 = Exposure potential = (I+J+K)/3 2 I – Number of occupants 2 J – Frequency of use 3 K – Average time in use 2

4 = Maintenance activity = (L+M)/21

L – Type of maintenance0

M – Frequency of maintenance 1

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM bitumen below parquet floor previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Page 48: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 48 of 60

Surveyor Colin Platt Room/Area 2/122 - Classroom B17

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block B Sample No P

Floor 1st Floor Item Bitumen Below Parquet Floor

Item Accessibility Difficult Amount 35m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 3 E – Main type of activity 3 Total Priority Score (P.A.) = (1+2+3+4):

7 Total Risk Ass’ Score (P.A. + M.A)

9 Risk Coding LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 0 H – Extent 2

3 = Exposure potential = (I+J+K)/3 3 I – Number of occupants 3 J – Frequency of use 3 K – Average time in use 3

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM bitumen below parquet floor previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Surveyor Colin Platt Room/Area 2/123 - Classroom B16

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block B Sample No P

Floor 1st Floor Item Bitumen Below Parquet Floor

Item Accessibility Difficult Amount 40m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 3 E – Main type of activity 3 Total Priority Score (P.A.) = (1+2+3+4):

7 Total Risk Ass’ Score (P.A. + M.A)

9 Risk Coding LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 0 H – Extent 2

3 = Exposure potential = (I+J+K)/3 3 I – Number of occupants 3 J – Frequency of use 3 K – Average time in use 3

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM bitumen below parquet floor previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Page 49: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 49 of 60

Surveyor Colin Platt Room/Area 3/002 - Classroom DG4

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block C Sample No P

Floor Ground Floor Item Bitumen Below Parquet Floor

Item Accessibility Difficult Amount 66m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 3 E – Main type of activity 3 Total Priority Score (P.A.) = (1+2+3+4):

8 Total Risk Ass’ Score (P.A. + M.A)

10 Risk Coding LOW

2 = Disturbance = (F+G+H)/3 2 F – Location 2 G – Accessibility 0 H – Extent 3

3 = Exposure potential = (I+J+K)/3 3 I – Number of occupants 3 J – Frequency of use 3 K – Average time in use 3

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM bitumen below parquet floor previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Surveyor Colin Platt Room/Area 3/003 - Classroom DG4 Cupboard

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block C Sample No P

Floor Ground Floor Item Bitumen Below Parquet Floor

Item Accessibility Difficult Amount 1m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 3 E – Main type of activity 3 Total Priority Score (P.A.) = (1+2+3+4):

5 Total Risk Ass’ Score (P.A. + M.A)

7 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 0 H – Extent 0

3 = Exposure potential = (I+J+K)/3 1 I – Number of occupants 0 J – Frequency of use 3 K – Average time in use 0

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM bitumen below parquet floor previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Page 50: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 50 of 60

Surveyor Colin Platt Room/Area 3/033 - Classroom DG1

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block C Sample No P

Floor Ground Floor Item Bitumen Below Parquet Floor

Item Accessibility Difficult Amount 90m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 3 E – Main type of activity 3 Total Priority Score (P.A.) = (1+2+3+4):

8 Total Risk Ass’ Score (P.A. + M.A)

10 Risk Coding LOW

2 = Disturbance = (F+G+H)/3 2 F – Location 2 G – Accessibility 0 H – Extent 3

3 = Exposure potential = (I+J+K)/3 3 I – Number of occupants 3 J – Frequency of use 3 K – Average time in use 3

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM bitumen below parquet floor previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Surveyor Colin Platt Room/Area 3/044 - Electrical Cupboard

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block C Sample No P

Floor Ground Floor Item Flashguards

Item Accessibility Medium Amount 1Lm

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Textile Rope & Yarn 2 Good Condition 0

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Chrysotile 1 4

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

3 Total Risk Ass’ Score (P.A. + M.A)

7 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 1 H – Extent 0

3 = Exposure potential = (I+J+K)/3 0 I – Number of occupants 0 J – Frequency of use 0 K – Average time in use 0

4 = Maintenance activity = (L+M)/22

L – Type of maintenance2

M – Frequency of maintenance 1

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM flashguards within electrical box, previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed.

Page 51: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 51 of 60

Surveyor Colin Platt Room/Area 3/048 - Stores S47

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block C Sample No P

Floor Ground Floor Item Bitumen Wrap To Live Electrical Cable

Item Accessibility Medium Amount 1Lm

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Chrysotile 1 3

1 = Normal Occupant Activity = (E) 1 E – Main type of activity 1 Total Priority Score (P.A.) = (1+2+3+4):

2 Total Risk Ass’ Score (P.A. + M.A)

5 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 1 F – Location 2 G – Accessibility 1 H – Extent 0

3 = Exposure potential = (I+J+K)/3 0 I – Number of occupants 0 J – Frequency of use 0 K – Average time in use 0

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM Bitumen Wrap to Live Electrical cable, previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed.

Surveyor Colin Platt Room/Area 3/054 - Classroom

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block C Sample No P

Floor Ground Floor Item Bitumen Below Parquet Floor

Item Accessibility Difficult Amount 50m²

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Bitumen Products 1 Good Condition 0 Composite materials; reinforced plastics, resins, vinyl tiles, sealed decorative finishes, etc.

0 Chrysotile 1 2

1 = Normal Occupant Activity = (E) 3 E – Main type of activity 3 Total Priority Score (P.A.) = (1+2+3+4):

7 Total Risk Ass’ Score (P.A. + M.A)

9 Risk Coding LOW

2 = Disturbance = (F+G+H)/3 2 F – Location 2 G – Accessibility 0 H – Extent 3

3 = Exposure potential = (I+J+K)/3 2 I – Number of occupants 2 J – Frequency of use 3 K – Average time in use 1

4 = Maintenance activity = (L+M)/20

L – Type of maintenance0

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM bitumen below parquet floor previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed. No access due to damage limitations.

Page 52: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

3. Reinspection Data Sheets

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 52 of 60

Surveyor Colin Platt Room/Area Design Block Roof - External (high Level)

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block C Sample No P

Floor External Item Cowl

Item Accessibility Difficult Amount 1No.

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Cement Products 1 Good Condition 0

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Chrysotile 1 3

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

1 Total Risk Ass’ Score (P.A. + M.A)

4 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 0 F – Location 0 G – Accessibility 0 H – Extent 0

3 = Exposure potential = (I+J+K)/3 0 I – Number of occupants 0 J – Frequency of use 0 K – Average time in use 0

4 = Maintenance activity = (L+M)/21

L – Type of maintenance1

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM cement cowl previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed.

Surveyor Colin Platt Room/Area Design Block Roof - External (high Level)

Survey Date 23 October 2019 Level of Identification

Presumed (P)

Building Block C Sample No P

Floor External Item Flue Pipe

Item Accessibility Difficult Amount 3Lm

A - Product Type: B - Extent of Damage: C – Surface Treatment D – Asbestos Type Material Ass (M.A) (A+B+C+D):

Cement Products 1 Good Condition 0

Enclosed sprays, lagging and textiles, AIB (encapsulated), asbestos cement and unsealed decorative finishes

1 Chrysotile 1 3

1 = Normal Occupant Activity = (E) 0 E – Main type of activity 0 Total Priority Score (P.A.) = (1+2+3+4):

1 Total Risk Ass’ Score (P.A. + M.A)

4 Risk Coding VERY LOW

2 = Disturbance = (F+G+H)/3 0 F – Location 0 G – Accessibility 0 H – Extent 0

3 = Exposure potential = (I+J+K)/3 0 I – Number of occupants 0 J – Frequency of use 0 K – Average time in use 0

4 = Maintenance activity = (L+M)/21

L – Type of maintenance1

M – Frequency of maintenance 0

Recommendation:

Manage & Re-inspect

Further Information: Presumed ACM cement flue pipe previously presumed by Safer Spaces in report 408469 to contain chrysotile until accessed.

Page 53: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

4. Additional Bulk Samples

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 53 of 60

No further Bulk samples taken

Page 54: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

Appendix 1 – Definitions & Recommended Guidance

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 54 of 60

Level of Identification

Sample (S) A physical sample was taken on site by the Surveyor and analysed by the laboratory.

Cross reference (X) No sample was taken but the material is visually similar to a sample that has been analysed from

the survey. This is a form of Strong Presumption as defined in HSG264.

Strongly Presumed (SP) No sample was taken but due to the appearance of the material and with the surveyor’s

knowledge and experience the material has been identified as containing asbestos.

Presumed (P) No sample was taken and therefore due to this lack of information the material or item must be

presumed to contain asbestos. This will often be because the item could not be sampled due to excessive height (such

as soffits) or an item could not be inspected (or sampled) as this may have presented a risk to the Surveyor (e.g.

opening up live plant and electrics).

No access areas are also treated as a presumption.

Recommendations

The various recommendations given within this report are explained below:-

Manage & Re-inspect

Where asbestos is left in situ there is a duty to formulate and implement a Management Plan to help prevent accidental

damage and exposure.

The basic requirements of this policy are (from HSG 264):

• Keep and maintain an up-to-date record of the location, condition, maintenance and removal of all asbestos-

containing materials

• Maintain it in a good state of repair and regularly monitor the condition

• Inform anyone who will potentially come into contact with or disturb the material as to its location and condition

• Have arrangements and procedures in place, so that work which may disturb the materials complies with the Control

of Asbestos Regulations 2012

• Review the plan at regular intervals

Label

A decision should be taken as to whether to label ACMs. The decision will depend on the confidence in the

administration of the asbestos management system and whether communication with workers and contractors coming

to work on site can be effective.

Labelling ACMs should not be solely relied on as a control measure; however it is an effective method of preventing

exposure to building occupants (and, in particular, maintenance workers). If, for any reason, management procedures

fail, it may act as an effective last barrier to uncontrolled damage to the ACM.

It may not always be prudent or practical to label all installations of asbestos; for example high level items such as roof

sheets, flue cowls and soffits or items such as gaskets to pipe flanges, textured coating and floor tiles.

Encapsulate

When this recommendation has been given, the ACM is raw and requires encapsulating with a suitable sealant or the

existing sealant or covering has deteriorated and the installation requires either a complete or partial re-encapsulation.

Page 55: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

Appendix 1 – Definitions & Recommended Guidance

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 55 of 60

We recommend that sealing or painting of insulating board, insulation or spray coatings should be undertaken by a

licensed contractor and is likely to be subject to a 14 day notification to the HSE, (as per the Control of Asbestos

Regulations 2012).

Repair

The material has sustained damage to some area or areas and requires attention to make good the material so that it

can be managed safely. This will often involve some element of decontamination if debris is associated with the

damage.

Remove

If an item is recommended for removal it has either sustained damage and is posing an increased risk in its current

condition; or due to its location it is considered high risk as it could easily be disturbed in the future. Materials

recommended for removal will be given one of the following recommendations:-

Removal by Licensed Contractor. This will include removal of AIB, Insulation, and Spray Coatings and is likely to be

subject to a 14 day notification to the HSE, (as per the Control of Asbestos Regulations 2012).

Removal by Approved Contractor. This will include removal of lower risk materials such as Asbestos Cement,

Bitumen Products, Reinforced Composites, and Floor Tiles etc. Some such works may be considered Notifiable Non-

Licensed Works.

The Control of Asbestos Regulations 2012 does not necessarily require such removal works to be undertaken by a

licensed contractor. However it is good practice, and we would strongly recommended that all removal works are

undertaken by a licensed contractor.

Restrict Access

Materials have been identified that are in a damaged condition often with associated debris that can be easily

disturbed. As such access to the area should be prevented to all persons until such a time when the area has been

deemed safe for reoccupation. This will usually be once removal works have been completed.

No Access – Inspection Required

Access to the given location was either not possible at all or only limited access was possible. In both instances there

is the potential for unidentified asbestos being present and as such the area must be treated as containing asbestos

until full access is possible.

Arrangements should be made at the earliest opportunity to revisit locations where access was not possible or access

was limited in order that such areas can be inspected fully.

Items and materials that are presumed to contain asbestos will also be given the recommendation of ‘No Access –

Inspection required’. In these instances the item or material should be treated as containing asbestos until

arrangements can be made to access such items or materials in order to carry out an inspection or sample to confirm

or otherwise the presence of asbestos.

No Recommendation Required

Asbestos has not been identified and as such no further action is required.

Recommended Guidance

To comply with and ensure that the requirements of section 2 & 3 of the Health and Safety at Work Act (as amended)

1974, the Management of Health and Safety at Work Regulations 1999, the Control of Asbestos Regulations 2012 and

the Control of Substances Hazardous to Health 2002 are met, the following recommendations should be implemented:

Page 56: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

Appendix 1 – Definitions & Recommended Guidance

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 56 of 60

Undertake suitable and sufficient Risk Assessments of identified ACMs against normal occupation and maintenance

operations, in compliance with Regulations 3 of the Management of Health & Safety at Work Regulations 1999 and

Regulation 6 of the Control of Asbestos Regulations 2012.

The findings of the survey be brought to the attention of those persons who are likely to come in contact with asbestos, in

compliance with Section 2 and 3 of the Health and Safety at Work Act (as amended) 1974 and Regulation 9 of the Control

of Asbestos Regulations 2012.

Implement an Asbestos Management Policy, Plan and review process in compliance Regulation 4 of the Control of

Asbestos Regulations 2012.

During the course of the survey it may not have been possible to access all areas of the site. Details of areas requiring

further access is identified within the Data Sheets and Executive Summary of this report. In accordance with HSG 264,

asbestos is presumed to be present within these areas and should be treated accordingly until further inspection and

analysis of building fabric and services proves otherwise.

It is recommended that air monitoring is carried out within any areas where ACMs have been identified in order to assess

airborne fibre levels within adjacent occupied areas in relation to the clearance indicator, as documented by HSG 248 The

Analyst Guide.

Where asbestos debris or asbestos in poor condition has been found it is recommended that access is restricted to these

areas in accordance with Regulation 11 of the Control of Asbestos Regulations 2012 and that air monitoring is carried out

within adjacent areas in order to assess airborne fibre levels.

All identified asbestos to be appropriately identified and subject to Risk Assessment, management, and re-inspection.

Site specific recommendations in respect to the location and condition of asbestos materials identified during the

course of this inspection are detailed in the Survey Data Sheets and Asbestos register. In considering the management

of asbestos materials identified to date, these recommendations should be referred to and complied with.

It is recommended that work on, or removal of, both licensed and non-licensed ACMs is undertaken by a licensed

asbestos removal contractor so that the Duty Holder / Client can have confidence that the contractor has provided the

correct level of training and has the experience and knowledge necessary to deal with these products safely.

It is a requirement of CAR 2012 that further intrusive investigations and sampling be carried out where any refurbishment,

maintenance, or similar activity is planned that may expose asbestos materials. This should be a refurbishment/demolition

survey as documented by HSG 264.

The findings of this report should not be solely relied upon in obtaining costs for proposed asbestos abatement work. Any

proposed abatement/removal of the asbestos should be undertaken against a detailed specification.

Page 57: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

Appendix 2 – Material & Priority Assessment Algorithms

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 57 of 60

Where ACMs have been identified or presumed to be present a Material Assessment Algorithm has been calculated as detailed in HSG 264 and reproduced in line with the table overleaf.

The Material Assessment is an assessment of the condition of the ACM, or the presumed ACM, and the likelihood of it releasing fibres in the event of it being disturbed in some way. This Material Assessment will give a good initial guide to the priority for management as it will identify the materials which will most readily release airborne fibres if disturbed. However, there are other factors to take into account when prioritising action. These are considered in the Priority Assessment which is described later.

For each of the four variables given by the table a score is allocated. The four scores are added together to give a Material Assessment score of between 2 and 12.

HIGH RISK 10-12 Materials with scores of 10 or more should be regarded as high risk with a significant potential to release fibres if disturbed;

MEDIUM RISK 7- 9 Those materials with a score between 7 and 9 are regarded as medium risk to release fibres.

LOW RISK 5-6 Materials with a score between 5 and 6 are low risk to release fibres.

VERY LOW RISK 4 or less Scores of 4 or less are very low risk.

Section Sample Variable

Score Examples of Score

A Product type (or debris from product).

1 Asbestos reinforced composites (plastics, resins, mastics, roofing felts, vinyl floor tiles, semi rigid paint or decorative finishes, asbestos cement, etc).

2 Asbestos insulating board, mill boards, other low-density insulation boards, asbestos textiles, gaskets, ropes and woven textiles, asbestos paper and felt.

3 Thermal insulation (e.g.: pipe and boiler lagging), sprayed asbestos, loose asbestos, asbestos mattresses and packing.

BExtent of damage/ deterioration.

0 Good condition: no visible damage.

1 Low damage: a few scratches or surface marks; broken edges on boards, tiles, etc.

2 Medium damage: significant breakage of materials or several small areas where material has been damaged revealing loose asbestos fibres.

3 High damage or delamination of materials, sprays and thermal insulation. Visible asbestos debris.

C Surface Treatment

0 Composite materials containing asbestos: reinforced plastics, resins, vinyl tiles.

1 Enclosed sprays and lagging, AIB (with exposed face painted or encapsulated), unsealed cement sheets, etc.

2 Unsealed AIB, or encapsulated lagging and sprays.

3 Unsealed lagging and sprays.

D Asbestos type

1 Chrysotile.

2 Amphibole asbestos excluding Crocidolite.

3 Crocidolite.

Material Assessment Score = A + B + C + D

Page 58: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

Appendix 2 – Material & Priority Assessment Algorithms

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 58 of 60

The Material Assessment identifies the high risk materials, that is, those which will most readily release airborne fibres if disturbed. It does not automatically follow that those materials assigned the highest score in the Material Assessment will be the materials that should be given priority for remedial action. Management priority must be determined by carrying out a Risk Assessment which will also take into account the likely maintenance activity; occupant activity; likelihood of disturbance; and human exposure potential.

The Priority Assessment Algorithm looks at the likelihood of someone disturbing the ACM. Please note Priority Assessments have not been undertaken as part of this survey.

A legal requirement to carry out a Risk Assessment for all work activities exists under the Management of Health and Safety at Work Regulations 1999. The requirement to assess the risk posed by asbestos is further enforced by the Control of Asbestos Regulations 2012. These regulations require that asbestos present in the workplace must not present a hazard to health

The risks from asbestos should be assessed and managed for all identified or presumed ACMs. The Risk Assessment or priority rating will establish the likelihood of people being exposed to the hazard and identify the measures to be taken that will either eliminate the hazard or adequately control it.

The Priority Assessment Score is calculated on the average scores for each of the four human exposure factors given by the table on the following page.

It is the responsibility of the Duty Holder to complete the Priority Risk Assessment, and ensure it remains up to date and accurate.

Section Factor Score Examples of Score

Normal Occupant Activity Score = E

E Main Type of Activity

0 Rare Disturbance activity (e.g. Store Room) 1 Low Disturbance Activity (e.g. Office) 2 Periodic Disturbance (May contact ACMs) 3 High Level of disturbance (e.g. panel on door)

Likelihood of Disturbance Score = Average of F + G + H

F Location

0 Outdoors 1 Large Rooms or well ventilated Areas 2 Rooms up to 100sqm 3 Confined Spaces

G Accessibility

0 Usually Inaccessible or unlikely to be disturbed 1 Occasional Disturbance 2 Easily Disturbed 3 Routinely Disturbed

H Extent

0 Very Small Amounts 1 <10sqm or <10lm 2 >10sqm to <50sqm or >10lm to <50lm 3 <50sqm or >50lm

Human Exposure Potential Score = Average of I + J + K

I No of Occupants

0 None 1 1-3 2 4-10 3 >10

J Frequency of Use

0 Infrequent 1 Monthly 2 Weekly 3 Daily

K Average Time in Use

0 <1 Hour 1 >1 hour and <3 hours 2 >3 hours to <6 hours 3 >6 Hours

Maintenance Activity Score = Average of L + M

L Type of Activity

0 Minor disturbance e.g. possible contact 1 Low disturbance e.g. removing light bulb 2 Medium Disturbance 3 High levels of disturbance

Page 59: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

Appendix 2 – Material & Priority Assessment Algorithms

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 59 of 60

MFrequency of Maintenance

0 ACM unlikely to be disturbed 1 1 per Year 2 >1 per year 3 >1 per Month

Risk Assessment

The Risk Assessment Priority Algorithm is calculated by adding the Material Assessment Score obtained during the survey to the Priority Assessment Score.

HIGH RISK - 18 POINTS OR MORE

The potential hazard arising from this category warrants urgent action. Immediate plans should be made for the removal/containment of the ACM. If delay in remedial action is likely to occur the affected area should initially be sealed-off and appropriate warning signs posted.

MEDIUM RISK - 14-17 POINTS

This category indicates that deterioration in any of the contributory factors may result in fibre release. Therefore all asbestos should be contained/sealed/encapsulated.

LOW RISK - 9-13 Points

This category indicates the need for regular monitoring. Although the current risk of fibre release is low, this material may suffer deterioration through age/local accidental damage.

VERY LOW RISK 8 or less

Similarly this category requires regular monitoring. Although the current risk of fibre release is low, this material may suffer deterioration through age/local accidental damage.

Page 60: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

Appendix 3 – Survey Drawings

Version 08, May 2018 Life Environmental Services Issue No. 1

Reinspection Survey & PA B-87863 - Raynes Park High School Page 60 of 60

Page 61: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

COURTYARD

UP

void

UP

UP

UP

UP

UP

UP

UP

UP

UP

GIA: 3 779.3 m²

Raynes Park High School - Ground FloorBlock A

A-E5

A-E3A-E4

A-E6

A-E8A-E7

A-E9

A-E12 A-E11

A-E10

A-E1

A-E2

1/076Corridor54.52 m²

1/095Store6.37 m²

1/096Store6.33 m²

1/097Hall227.08 m²

1/075Corridor38.58 m²

1/0111Corridor51.03 m²

1/009Corridor40.61 m²

1/002Reception45.91 m²

1/094Store (Tables)16.55 m²

1/093Store24.77 m²

1/081Corridor8.62 m²

1/091Corridor1.25 m²

1/086Corridor1.85 m²

1/080Store13.22 m²

1/082Lobby1.84 m²

1/082Lockers (Sodexo Staff)8.59 m²

1/085Toilet (Sodexo Staff)3.79 m²

1/087Staff Room (Sodexo Staff)16.43 m²

1/092Workshop9.54 m²

1/090Office5.09 m²

1/0129Store2.01 m²

1/0128Entrance to the flat6.60 m²

1/088Lobby2.72 m²

1/089Store2.28 m²

1/083Corridor3.04 m²

1/084Toilet (Sodexo Staff)2.01 m²

1/098Store2.74 m²

1/079Drama Studio82.67 m²

1/078Drama Studio82.88 m² 1/077

Office17.11 m²

1/074Classroom58.30 m² 1/073

Classroom50.24 m²

1/071Classroom44.34 m²

1/072Store12.78 m²

1/070Classroom45.71 m²

COURTYARD

1/0115Office4.87 m²

1/0114MFL Base Room22.85 m²

1/0116Classroom44.90 m²

1/069Corridor159.17 m²

1/0117Classroom44.92 m²

1/0118Classroom44.79 m²

1/0119Classroom44.67 m²

1/0112Classroom56.17 m²

1/0113Classroom53.27 m²

1/040Classroom45.43 m²

1/039AST Base29.61 m²

1/037AST Base13.79 m²

1/036Deputy Head's Office14.95 m²

1/035PA to Deputy Head's Office9.23 m²

1/0121Assistant Head's Office9.91 m²

1/0120Data Man's Office10.02 m²

1/034Lobby5.54 m²

1/038Lobby0.93 m²

1/0122Cleaning Store2.34 m²

1/0123Toilet (Girls)11.81 m²

1/0125Toilet (Boys)10.04 m²

1/0124Toilet (Accessible)3.50 m²

1/0126Assistant Head's Office10.39 m²

1/0127Office9.54 m²

1/025Corridor21.79 m² 1/033

Stairwell16.97 m²

1/029Store5.10 m²

1/028Store10.50 m²

1/027Office9.15 m²

1/0133Gas Meter3.08 m²

1/0132Elect Room5.50 m²

1/0131Tank Room17.63 m²

1/0130Boiler Room41.85 m²

1/026Kitchen105.81 m²

1/032Chemical Store0.87 m²

1/031Toilet (Staff)1.60 m²

1/030Changing (Staff)3.26 m²

1/023Dining Hall188.66 m²

1/024Store4.40 m²

1/021Corridor21.11 m²

1/0110Store1.05 m²

1/022Classroom43.64 m²

1/020Meeting Room43.81 m²

1/017Reprographics28.08 m²

1/019Corridor4.74 m²

1/018Lobby9.62 m²

1/016Help Desk Office29.04 m²

1/015Support Team Office56.97 m²

1/014Store2.53 m²

1/013Exam Store7.21 m²

1/010Waiting Room8.58 m²

1/011PA to Head's Office9.34 m²

1/012Head's Office26.12 m²

1/008Archive Store9.41 m²

1/0137Toilet6.17 m²

1/006Conference Room31.65 m²

1/005Office9.28 m²

1/004Finance Office13.03 m²

1/001Entrance Lobby5.35 m²

1/003Waiting Room7.18 m²

1/007Riser0.54 m²

1/099Store7.29 m²

1/0100Stairwell9.64 m²

1/0101Lift Motor Room2.65 m²

1/0102Lift 1.42 m²

1/0103Medical Room8.69 m²

1/0104Toilet1.64 m²

1/0105PA to Deputy Head's Office8.66 m²

1/0106Exam Office9.66 m²

1/017Deputy Head's Office8.90 m²

1/0108Toilet (Staff/Female)12.87 m²

1/0109Toilet (Staff/Male)11.30 m²

1/043Stairwell15.88 m²

1/041The Base43.93 m²

1/042Office11.81 m²

1/044Corridor52.66 m²

1/046Classroom56.49 m²

1/064Staff Room61.78 m²

1/063Staff Room67.84 m²

1/062Meeting Room28.79 m² 1/061

Lift 2.56 m²

1/045Corridor37.15 m²

1/051Corridor67.63 m²

1/054Corridor13.24 m²

1/058Server Room20.95 m²

1/059ICT 72.16 m²

1/057Classroom72.14 m²

1/060Resource Centre122.75 m²

1/056Toilet (Girls)22.21 m²

1/049Toilet (Staff/Female)10.19 m²

1/052Store5.19 m²

1/053Cleaning Store2.14 m²

1/055Lobby1.88 m²

1/050Toilet (Accessible)2.87 m²

1/048Toilet (Staff/Male)6.69 m²

1/047Lobby3.61 m²

1/065The Hub64.50 m²

1/066The Hub19.09 m²

1/068Chill Out Room4.85 m²

1/067Intervention Room10.85 m²

1/0136Store11.32 m²

1/1035Stairwell21.23 m²

1/0134Plant Room29.01 m²

1/040A

Drawing Not to Scale Drawing should not be viewed in isolation. Please refer to Report Asbestos Register.

Drawn By:

Surveyor Initials:Survey Date:Revision No.:

Date:

Page:2.4 Oct 2016

Life Environmental Services Ltd.4 Ducketts Wharf

South StreetBishop’s Stortford CM23 3AR

Telephone: 0844 335 1281Email: [email protected]

www.lifeenvironmental.co.ukRegistered in England No. 3053057

Key

- Location Number

- Asbestos Present (Please refer to register)

- No Access

- Limited Access

- Outside Scope of Survey

- Asbestos Removed

- Positive Sample

- Cross Referenced Sample

- Strongly Presumed Asbestos

- Presumed Asbestos

- Negative Sample

- Negative Cross Referenced Sample

SP

S0001

Survey Plan

001

S0001

X0001

P

S0001

X0001

Job No.:

23/10/2019CP07/11/2019MR

1 of 13

Reinspection

B-87863

Sodexo

Raynes Park High SchoolBushey Road

LondonSW20 0JL

P

P

024/197

P

024/166

024/182 024/165 024/169 024/171 P P P P 024/200 P

024/194

024/204

P P P

P

P

P

024/179PP

X024/166

X024/166

X024/194

NO ACCESS WITHINHEATERS

X024/179

Page 62: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

UP

UP

UP

void

UP

GIA: 3 070.0 m²

Raynes Park High School - First FloorBlock A

UP

UP

UP

UP

UP

UP

UP

1/112Corridor90.13 m²

1/113Corridor46.13 m²

1/109Corridor80.34 m²

1/118Corridor11.85 m²

1/120Stairwell21.70 m²

1/123Corridor53.06 m²

1/126Corridor45.09 m²

1/133Corridor6.15 m²

1/130IT Room9.89 m²

1/132Stairwell17.85 m²

1/131Lift1.42 m²

1/129Toilet (Girls)13.36 m²

1/128Toilet (Boys)14.13 m²

1/136Classroom82.32 m²

1/138Classroom83.60 m²

1/140Classroom89.67 m²

1/141Classroom88.53 m²

1/143Classroom90.93 m²

1/121Classroom84.40 m²

1/144Classroom75.61 m²

1/145Intervention Room14.67 m²1/122

Store7.10 m²

1/125Boiler Room1.39 m²

1/124Science Teachers Work Room65.58 m²

1/142Store (Science)7.09 m²

1/139Prep Room (Science)18.34 m²

1/137Store14.22 m²

1/135Store (Sound)8.12 m²

1/134Sound/Light Room32.91 m²

1/176Living Room15.58 m²

1/177Kitchen7.80 m²

1/175Bedroom12.49 m²

1/174Bedroom10.72 m²

1/172Bedroom7.89 m²

1/173Store0.79 m²

1/183Store1.58 m²

1/171Corridor9.27 m²

1/178Store1.97 m²

1/180Store1.75 m²1/179Store1.75 m²

1/119Classroom91.97 m²

1/115Classroom69.17 m²

1/114Classroom75.92 m²

1/158Stairwell14.39 m²

1/150Classroom61.49 m²

1/148Classroom61.95 m²

1/147Stairwell14.03 m²

1/146Corridor55.35 m²

1/149Studio14.57 m²

1/151Store (Music)12.04 m²

1/153Practice Room16.24 m²

1/152Corridor15.18 m²

1/154Practice Room5.55 m²

1/155Practice Room5.36 m²

1/156Practice Room5.36 m²

1/157Practice Room5.62 m²

1/159Classroom74.34 m²

1/111Classroom56.70 m²

1/110Classroom56.73 m²

1/161Stairwell29.78 m²

1/116Store4.45 m²

1/117Cleaning Store4.83 m²

1/160Store10.49 m²

1/107Office17.16 m²

1/108Lift2.56 m²

1/106Library93.94 m²

1/105Classroom86.94 m²

1/104Classroom56.05 m²

1/103Classroom55.63 m²

1/101Stairwell35.45 m²

1/167Classroom56.18 m²

1/102Corridor63.18 m²

1/168Classroom56.31 m²

1/169Classroom58.21 m²

1/170Store4.07 m²

1/164Toilet (Boys)16.84 m²

1/162Toilet (Accessible)3.10 m²

1/163Lobby2.64 m²

1/165Cleaning Store2.45 m²

1/166Group Room27.70 m²

1/182Toilet1.85 m²

1/181Toilet3.91 m²

1/127Office8.71 m²

Drawing Not to Scale Drawing should not be viewed in isolation. Please refer to Report Asbestos Register.

Drawn By:

Surveyor Initials:Survey Date:Revision No.:

Date:

Page:2.4 Oct 2016

Life Environmental Services Ltd.4 Ducketts Wharf

South StreetBishop’s Stortford CM23 3AR

Telephone: 0844 335 1281Email: [email protected]

www.lifeenvironmental.co.ukRegistered in England No. 3053057

Key

- Location Number

- Asbestos Present (Please refer to register)

- No Access

- Limited Access

- Outside Scope of Survey

- Asbestos Removed

- Positive Sample

- Cross Referenced Sample

- Strongly Presumed Asbestos

- Presumed Asbestos

- Negative Sample

- Negative Cross Referenced Sample

SP

S0001

Survey Plan

001

S0001

X0001

P

S0001

X0001

Job No.:

23/10/2019CP07/11/2019MR

2 of 13

Reinspection

B-87863

Sodexo

Raynes Park High SchoolBushey Road

LondonSW20 0JL

024/193024/190 P

X024/193

Page 63: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

UP

UP

GIA: 520.7 m²

Raynes Park High School - Second FloorBlock A

1/202Stairwell29.83 m²

1/203Corridor38.13 m²

1/208Lift2.56 m² 1/209

Office8.91 m²

1/207Store11.04 m²

1/206Store2.58 m²

1/210Cleaning Store3.72 m²

1/212Store11.66 m²

1/215Store6.01 m²

1/216Store2.68 m²

1/205Store10.46 m²

1/204Classroom110.16 m²

1/211Classroom106.20 m²

1/214Classroom102.23 m²

1/213Kiln Room10.19 m²

1/217Toilet (Staff)2.90 m²

1/201Stairwell39.80 m²

External Tank Room

Drawing Not to Scale Drawing should not be viewed in isolation. Please refer to Report Asbestos Register.

Drawn By:

Surveyor Initials:Survey Date:Revision No.:

Date:

Page:2.4 Oct 2016

Life Environmental Services Ltd.4 Ducketts Wharf

South StreetBishop’s Stortford CM23 3AR

Telephone: 0844 335 1281Email: [email protected]

www.lifeenvironmental.co.ukRegistered in England No. 3053057

Key

- Location Number

- Asbestos Present (Please refer to register)

- No Access

- Limited Access

- Outside Scope of Survey

- Asbestos Removed

- Positive Sample

- Cross Referenced Sample

- Strongly Presumed Asbestos

- Presumed Asbestos

- Negative Sample

- Negative Cross Referenced Sample

SP

S0001

Survey Plan

001

S0001

X0001

P

S0001

X0001

Job No.:

23/10/2019CP07/11/2019MR

3 of 13

Reinspection

B-87863

Sodexo

Raynes Park High SchoolBushey Road

LondonSW20 0JL

024/198

P

Page 64: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

UP

UP

UPUP

GIA 1 204.6 m²

Raynes Park High School - Ground FloorBlock B

UP

B-E7

B-E6

B-E5

B-E8

B-E9

B-E10

B-E1

B-E2

B-E3

B-E4

2/013Corridor22.34 m²

2/032Corridor14.47 m²

2/011Corridor5.66 m²

2/008Corridor41.46 m²

2/005Corridor40.88 m²

2/001Corridor15.67 m²

2/048Corridor15.78 m²

2/051Stairwell8.98 m²

2/052Store3.06 m²

2/053Lobby3.79 m²

2/054Office13.73 m²

2/055Toilet (Staff)5.16 m²

2/002Store10.68 m²

2/003Store13.27 m²

2/004Store15.29 m²

2/006Classroom59.54 m²

2/007Classroom59.73 m²

2/009Classroom59.36 m²

2/010Classroom59.43 m²

2/012Classroom55.29 m²

2/021Meeting Room14.30 m²

2/014Plant Room2.43 m²2/022

Office14.96 m²

2/023Changing Room12.25 m²

2/020Lobby12.78 m²

2/024Intervention Room10.81 m²

2/015Corridor56.14 m²

2/017Cloaks6.18 m²

2/016Kitchen15.36 m²

2/018Toilet (Staff/Accessible)3.43 m²

2/019Toilet (Accessible)3.34 m²

2/025Lobby12.55 m²

2/026Group Room12.41 m²

2/027Group Room15.09 m²

2/028Group Room13.96 m²

2/029Classroom48.27 m²

2/030Common Room7.67 m²

2/031SENCO Office14.91 m²

2/033Stairwell8.38 m²

2/034Store3.06 m²

2/037Toilet (Accessible)2.54 m²

2/035Lobby2.80 m²

2/036Toilet (Girls)8.04 m²

2/038Toilet (Boys)15.11 m²

2/040Toilet (Staff)8.55 m²

2/041Cleaning Store1.33 m²

2/042Cleaning Store2.72 m²

2/043Store1.40 m²

2/044Lift1.54 m²2/039

Corridor2.58 m²

2/045Hall171.88 m²

2/046Kitchen25.09 m²

2/047Plant Room1.39 m²

2/056Boiler Room11.72 m²

2/049Group Room7.77 m²

2/050Office7.77 m²

Drawing Not to Scale Drawing should not be viewed in isolation. Please refer to Report Asbestos Register.

Drawn By:

Surveyor Initials:Survey Date:Revision No.:

Date:

Page:2.4 Oct 2016

Life Environmental Services Ltd.4 Ducketts Wharf

South StreetBishop’s Stortford CM23 3AR

Telephone: 0844 335 1281Email: [email protected]

www.lifeenvironmental.co.ukRegistered in England No. 3053057

Key

- Location Number

- Asbestos Present (Please refer to register)

- No Access

- Limited Access

- Outside Scope of Survey

- Asbestos Removed

- Positive Sample

- Cross Referenced Sample

- Strongly Presumed Asbestos

- Presumed Asbestos

- Negative Sample

- Negative Cross Referenced Sample

SP

S0001

Survey Plan

001

S0001

X0001

P

S0001

X0001

Job No.:

23/10/2019CP07/11/2019MR

4 of 13

Reinspection

B-87863

Sodexo

Raynes Park High SchoolBushey Road

LondonSW20 0JL

P P P P P P P

024/209

P

P P

Page 65: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

GIA: 741.9 m²

Raynes Park High School - First FloorBlock B

UP

UP

UP

2/102Corridor57.69 m²

2/125Office15.44 m²

2/101Stairwell14.38 m²

2/124Toilet (Boys)15.45 m²

2/103Group Room24.08 m²

2/104Store11.06 m²2/105

Classroom60.13 m²

2/107Classroom60.08 m²

2/109Classroom59.58 m²

2/110Classroom60.05 m²

2/111Classroom55.09 m²

2/108Corridor49.64 m²

2/106Staff Room29.06 m²

2/123Classroom46.74 m²

2/122Classroom46.67 m²

2/113Stairwell14.28 m²

2/112Toilet (Girls)14.49 m²

2/114Office15.83 m²

2/115Staff Work Room16.62 m²

2/117Toilet (Staff)4.61 m²

2/116Toilet (Staff)3.66 m²

2/118Cleaning Store1.37 m²

2/119Cleaning Store2.23 m²

2/120Plant Room2.13 m²

2/121Lift1.54 m²

Drawing Not to Scale Drawing should not be viewed in isolation. Please refer to Report Asbestos Register.

Drawn By:

Surveyor Initials:Survey Date:Revision No.:

Date:

Page:2.4 Oct 2016

Life Environmental Services Ltd.4 Ducketts Wharf

South StreetBishop’s Stortford CM23 3AR

Telephone: 0844 335 1281Email: [email protected]

www.lifeenvironmental.co.ukRegistered in England No. 3053057

Key

- Location Number

- Asbestos Present (Please refer to register)

- No Access

- Limited Access

- Outside Scope of Survey

- Asbestos Removed

- Positive Sample

- Cross Referenced Sample

- Strongly Presumed Asbestos

- Presumed Asbestos

- Negative Sample

- Negative Cross Referenced Sample

SP

S0001

Survey Plan

001

S0001

X0001

P

S0001

X0001

Job No.:

23/10/2019CP07/112019MR

5 of 13

Reinspection

B-87863

Sodexo

Raynes Park High SchoolBushey Road

LondonSW20 0JL

P

P

P P P P P

PP

PP

Page 66: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

UP

courtyard

UP

UP

GIA: 1 272.2 m²

Raynes Park High School - Ground FloorBlock C

C-E1

C-E2

C-E3

C-E4

3/001Corridor10.05 m²

3/045Corridor29.35 m²

3/004Corridor41.71 m²

3/007Corridor20.82 m²

3/010Corridor12.15 m²

3/011Corridor28.43 m²

3/019Corridor17.05 m²

3/054Staff Room57.52 m²

3/022Changing (Girls)19.85 m²

3/024Changing (Girls)16.38 m²

3/026Changing (Boys)16.62 m²

3/023Showers8.37 m²

3/025Showers8.07 m²

3/027Showers8.48 m²

3/017Store8.80 m²

3/020Changing (Girls)17.34 m²

3/021Showers8.12 m²

3/053Boiler Room10.47 m²

3/018Showers2.95 m²

3/014Toilet (Girls)17.41 m²

3/028Toilet (Boys)13.20 m²

3/016Toilet (Accessible)4.33 m²

3/015Store1.32 m²

3/013Store0.95 m²

3/012Office11.82 m²

3/055Office7.84 m²

3/032Corridor8.99 m²

3/034Store7.24 m²

3/035Store3.22 m²

3/037Store3.71 m² 3/031

Toilet (Staff/Male)2.12 m²

3/030Toilet (Staff/Female)6.76 m²

3/029Cleaning Store3.73 m²

3/008Classroom77.43 m²

3/005Classroom77.37 m²

3/002Classroom77.08 m²

3/052Boiler Room27.51 m²

3/003Store4.40 m²

3/006Store4.65 m²

3/009Store4.78 m²

courtyard

3/039Store9.64 m²

3/038Corridor13.13 m²

3/040Store7.60 m²

3/036Store9.55 m²

3/033Classroom114.73 m²

3/041Classroom117.63 m²

3/046Classroom95.88 m²

3/048Store10.66 m²

3/047Store7.22 m²

3/049Store8.62 m²

3/051Store10.21 m²

3/050Store9.75 m²

3/043Lift1.56 m²

3/044Elect Store5.23 m²

3/042Work Prep Room29.53 m²

Drawing Not to Scale Drawing should not be viewed in isolation. Please refer to Report Asbestos Register.

Drawn By:

Surveyor Initials:Survey Date:Revision No.:

Date:

Page:2.4 Oct 2016

Life Environmental Services Ltd.4 Ducketts Wharf

South StreetBishop’s Stortford CM23 3AR

Telephone: 0844 335 1281Email: [email protected]

www.lifeenvironmental.co.ukRegistered in England No. 3053057

Key

- Location Number

- Asbestos Present (Please refer to register)

- No Access

- Limited Access

- Outside Scope of Survey

- Asbestos Removed

- Positive Sample

- Cross Referenced Sample

- Strongly Presumed Asbestos

- Presumed Asbestos

- Negative Sample

- Negative Cross Referenced Sample

SP

S0001

Survey Plan

001

S0001

X0001

P

S0001

X0001

Job No.:

23/10/2019CP07/11/2019MR

6 of 13

Reinspection

B-87863

Sodexo

Raynes Park High SchoolBushey Road

LondonSW20 0JL

P P P

P

P P

Page 67: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

GIA: 394.3 m²

Raynes Park High School - First FloorBlock C

UP

UP

UP

3/101Corridor37.24 m²

3/107Corridor21.45 m²

3/110Teacher's Work Room29.57 m²

3/109Store14.60 m²

3/108Store5.61 m²

3/102Lift1.56 m²

3/103Store5.61 m²

3/104Classroom (Food Techlonogy)111.74 m²

3/106Classroom (Food Techlonogy)113.74 m²

3/105Prep Room (Food Techlonogy)22.35 m²

Drawing Not to Scale Drawing should not be viewed in isolation. Please refer to Report Asbestos Register.

Drawn By:

Surveyor Initials:Survey Date:Revision No.:

Date:

Page:2.4 Oct 2016

Life Environmental Services Ltd.4 Ducketts Wharf

South StreetBishop’s Stortford CM23 3AR

Telephone: 0844 335 1281Email: [email protected]

www.lifeenvironmental.co.ukRegistered in England No. 3053057

Key

- Location Number

- Asbestos Present (Please refer to register)

- No Access

- Limited Access

- Outside Scope of Survey

- Asbestos Removed

- Positive Sample

- Cross Referenced Sample

- Strongly Presumed Asbestos

- Presumed Asbestos

- Negative Sample

- Negative Cross Referenced Sample

SP

S0001

Survey Plan

001

S0001

X0001

P

S0001

X0001

Job No.:

23/10/2019CP07/11/2019MR

7 of 13

Reinspection

B-87863

Sodexo

Raynes Park High SchoolBushey Road

LondonSW20 0JL

P P

Page 68: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

UP

GIA: 827.8 m²

Raynes Park High School - Ground FloorBlock D

D-E4

D-E3

D-E2

D-E1

4/007Corridor10.61 m²

4/003Corridor27.90 m²

4/001Corridor29.17 m²

4/002Lift1.54 m²

4/015Reception4.43 m²

4/004Lobby5.32 m²

4/014Store18.52 m²

4/011PE Store58.01 m²

4/010Sports Hall522.96 m²

4/016Boiler Room25.69 m²

4/009Toilet (Boys)15.81 m²

4/008Changing (Boys)29.88 m²

4/005Changing (Boys)28.64 m²

4/006Toilet (Girls)10.35 m²

4/013Toilet (Accessible)4.84 m²

4/012Cleaning Store2.19 m²

Drawing Not to Scale Drawing should not be viewed in isolation. Please refer to Report Asbestos Register.

Drawn By:

Surveyor Initials:Survey Date:Revision No.:

Date:

Page:2.4 Oct 2016

Life Environmental Services Ltd.4 Ducketts Wharf

South StreetBishop’s Stortford CM23 3AR

Telephone: 0844 335 1281Email: [email protected]

www.lifeenvironmental.co.ukRegistered in England No. 3053057

Key

- Location Number

- Asbestos Present (Please refer to register)

- No Access

- Limited Access

- Outside Scope of Survey

- Asbestos Removed

- Positive Sample

- Cross Referenced Sample

- Strongly Presumed Asbestos

- Presumed Asbestos

- Negative Sample

- Negative Cross Referenced Sample

SP

S0001

Survey Plan

001

S0001

X0001

P

S0001

X0001

Job No.:

23/10/2019CP07/11/2019MR

8 of 13

Reinspection

B-87863

Sodexo

Raynes Park High SchoolBushey Road

LondonSW20 0JL

Page 69: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

UP

void

GIA: 734.6 m²

Raynes Park High School - First FloorBlock D

4/106Lift1.54 m²

4/105Office22.85 m²

4/101Stairwell32.74 m²

4/102Store3.98 m²

4/104Store7.11 m²

4/103Multipurpose Room130.01 m²

Drawing Not to Scale Drawing should not be viewed in isolation. Please refer to Report Asbestos Register.

Drawn By:

Surveyor Initials:Survey Date:Revision No.:

Date:

Page:2.4 Oct 2016

Life Environmental Services Ltd.4 Ducketts Wharf

South StreetBishop’s Stortford CM23 3AR

Telephone: 0844 335 1281Email: [email protected]

www.lifeenvironmental.co.ukRegistered in England No. 3053057

Key

- Location Number

- Asbestos Present (Please refer to register)

- No Access

- Limited Access

- Outside Scope of Survey

- Asbestos Removed

- Positive Sample

- Cross Referenced Sample

- Strongly Presumed Asbestos

- Presumed Asbestos

- Negative Sample

- Negative Cross Referenced Sample

SP

S0001

Survey Plan

001

S0001

X0001

P

S0001

X0001

Job No.:

23/10/2019CP07/11/2019MR

9 of 13

Reinspection

B-87863

Sodexo

Raynes Park High SchoolBushey Road

LondonSW20 0JL

Page 70: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

GIA: 784.4 m²

Raynes Park High School - Ground FloorBlock E

UP

UP

E-E2

E-E1

E-E3

5/006Corridor57.58 m²

5/012Corridor33.93 m²

5/022Corridor30.54 m²

5/021Store3.26 m²

5/016Store7.51 m²

5/018Store7.70 m²

5/015Cleaning Store2.89 m²

5/011Store6.25 m²

5/014Store6.17 m²

5/027Boiler Room17.51 m²

5/017Toilet (Staff/Female/Accessible)3.21 m²

5/019Toilet (Staff/Male/Accessible)3.36 m²

5/024Toilet (Accessible)3.45 m²

5/020Classroom70.62 m²

5/026Common Room142.69 m²

5/013Classroom63.00 m²

5/010Study Room122.93 m²

5/008Head of 6th Form Office19.94 m²

5/0096th Form Office19.92 m²

5/007Corridor10.36 m²

5/003Kitchen (Staff)9.73 m²

5/002Intervention Room8.80 m²

5/004Corridor27.27 m²

5/005Lift1.51 m²

5/001Lobby17.96 m²

5/025Toilet (Girls)25.55 m²5/023

Toilet (Boys)22.90 m²

Drawing Not to Scale Drawing should not be viewed in isolation. Please refer to Report Asbestos Register.

Drawn By:

Surveyor Initials:Survey Date:Revision No.:

Date:

Page:2.4 Oct 2016

Life Environmental Services Ltd.4 Ducketts Wharf

South StreetBishop’s Stortford CM23 3AR

Telephone: 0844 335 1281Email: [email protected]

www.lifeenvironmental.co.ukRegistered in England No. 3053057

Key

- Location Number

- Asbestos Present (Please refer to register)

- No Access

- Limited Access

- Outside Scope of Survey

- Asbestos Removed

- Positive Sample

- Cross Referenced Sample

- Strongly Presumed Asbestos

- Presumed Asbestos

- Negative Sample

- Negative Cross Referenced Sample

SP

S0001

Survey Plan

001

S0001

X0001

P

S0001

X0001

Job No.:

23/10/2019CP07/11/2019MR

10 of 13

Reinspection

B-87863

Sodexo

Raynes Park High SchoolBushey Road

LondonSW20 0JL

Page 71: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

GIA: 782.9 m²

Raynes Park High School - First FloorBlock E

accessible toilet

UP

UP

UP

no access

5/110Corridor65.25 m²

5/101Stairwell18.48 m²

5/111Corridor51.98 m²

5/103Lift1.51 m²

5/102Unknown1.77 m² 5/105

Elect Store4.26 m²

5/106Media Suite23.01 m²

5/104Drama Studio104.84 m²

5/107Store (Drama) 23.18 m²

5/108Classroom55.19 m²

5/112Stairwell13.73 m²

5/113Cleaning Store6.18 m²

5/114Creche21.40 m²

5/109Store4.39 m²

5/115Classroom42.39 m²

5/116Store6.48 m²

5/117Teacher's Work Room14.56 m²

5/118Group Room16.13 m²

5/119Classroom61.95 m²

5/122Classroom51.36 m²

5/124Classroom51.34 m²

5/127Classroom63.69 m²

5/128Store5.98 m²

5/125Store5.98 m²

5/121Store3.39 m²

5/120Server Room2.72 m²

5/126Store13.59 m²

5/123Store6.13 m²

Drawing Not to Scale Drawing should not be viewed in isolation. Please refer to Report Asbestos Register.

Drawn By:

Surveyor Initials:Survey Date:Revision No.:

Date:

Page:2.4 Oct 2016

Life Environmental Services Ltd.4 Ducketts Wharf

South StreetBishop’s Stortford CM23 3AR

Telephone: 0844 335 1281Email: [email protected]

www.lifeenvironmental.co.ukRegistered in England No. 3053057

Key

- Location Number

- Asbestos Present (Please refer to register)

- No Access

- Limited Access

- Outside Scope of Survey

- Asbestos Removed

- Positive Sample

- Cross Referenced Sample

- Strongly Presumed Asbestos

- Presumed Asbestos

- Negative Sample

- Negative Cross Referenced Sample

SP

S0001

Survey Plan

001

S0001

X0001

P

S0001

X0001

Job No.:

23/10/2019CP07/11/2019MR

11 of 13

Reinspection

B-87863

Sodexo

Raynes Park High SchoolBushey Road

LondonSW20 0JL

Page 72: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

GIA: 342.9 m²

Raynes Park High School - Ground FloorBlock F

F-E2F-E4

F-E3

F-E1

6/001Corridor18.67 m²

6/011Corridor9.40 m²

6/016Store0.83 m²

6/015Store0.85 m²

6/009Store2.55 m²

6/010Office3.32 m²

6/012Officials Room8.29 m²

6/008Store4.54 m²

6/017First Aid Room11.30 m²

6/018Toilet/Shower (Accessible)7.36 m²

6/014Shower Room2.08 m²

6/013Toilet1.34 m²

6/004Toilet4.06 m²

6/003Toilet (Accessible)3.58 m²

6/002Toilet (Unisex)13.08 m²

6/005Hall47.70 m²

6/007Kitchen10.77 m²

6/006Store4.74 m²

6/036Store9.78 m²

6/035Cleaning Store2.40 m²

6/032Changing Room10.29 m²

6/033Changing Room16.18 m²

6/030Changing Room16.08 m²

6/034Showers7.76 m²

6/031Showers7.85 m²

6/027Plant Room15.14 m² 6/025

Changing Room16.27 m²

6/021Changing Room15.93 m²

6/026Showers7.74 m²

6/022Showers7.84 m²

6/023Changing Room4.45 m²

6/029Toilet5.55 m²

6/028Changing Room4.70 m²

6/024Toilet5.32 m²

6/019Changing Room4.67 m²

6/020Toilet5.53 m²

Drawing Not to Scale Drawing should not be viewed in isolation. Please refer to Report Asbestos Register.

Drawn By:

Surveyor Initials:Survey Date:Revision No.:

Date:

Page:2.4 Oct 2016

Life Environmental Services Ltd.4 Ducketts Wharf

South StreetBishop’s Stortford CM23 3AR

Telephone: 0844 335 1281Email: [email protected]

www.lifeenvironmental.co.ukRegistered in England No. 3053057

Key

- Location Number

- Asbestos Present (Please refer to register)

- No Access

- Limited Access

- Outside Scope of Survey

- Asbestos Removed

- Positive Sample

- Cross Referenced Sample

- Strongly Presumed Asbestos

- Presumed Asbestos

- Negative Sample

- Negative Cross Referenced Sample

SP

S0001

Survey Plan

001

S0001

X0001

P

S0001

X0001

Job No.:

23/10/2019CP07/11/2019MR

12 of 13

Reinspection

B-87863

Sodexo

Raynes Park High SchoolBushey Road

LondonSW20 0JL

Page 73: Asbestos Reinspection Report - SODEXO... · 2020-01-13 · Insulation Residue To Pipework (post Removal Findings) Thermal Insulation SP 9 Block A Extern al Tank Room - Tank Room Gaskets

GIA: 37.2 m²

Raynes Park High School - Ground FloorBlock G

G-E3

G-E1

G-E2 G-E4

7/002Store10.33 m²

7/001Garage26.34 m²

Drawing Not to Scale Drawing should not be viewed in isolation. Please refer to Report Asbestos Register.

Drawn By:

Surveyor Initials:Survey Date:Revision No.:

Date:

Page:2.4 Oct 2016

Life Environmental Services Ltd.4 Ducketts Wharf

South StreetBishop’s Stortford CM23 3AR

Telephone: 0844 335 1281Email: [email protected]

www.lifeenvironmental.co.ukRegistered in England No. 3053057

Key

- Location Number

- Asbestos Present (Please refer to register)

- No Access

- Limited Access

- Outside Scope of Survey

- Asbestos Removed

- Positive Sample

- Cross Referenced Sample

- Strongly Presumed Asbestos

- Presumed Asbestos

- Negative Sample

- Negative Cross Referenced Sample

SP

S0001

Survey Plan

001

S0001

X0001

P

S0001

X0001

Job No.:

23/10/2019CP07/11/2019MR

13 of 13

Reinspection

B-87863

Sodexo

Raynes Park High SchoolBushey Road

LondonSW20 0JL