aravind mamidi cii national award for excellence in · aravind mamidi sholapur vijay kumar....
TRANSCRIPT
Aravind Mamidi29, 30 & 31Aug 2018
Honeywell Internal
CII NATIONAL AWARD FOR EXCELLENCE IN
ENERGY MANAGEMENT
Hyderabad
Honeywell Confidential - © 2017 by Honeywell International Inc. All rights reserved.
Honeywell Technology Solutions - Global Presence
2
ChinaShanghai
Beijing
Other locations
IndiaBengaluru
Hyderabad
Madurai
Guru gram
Czech
RepublicPrague
Brno
MexicoMexico City
Chihuahua
Juarez
Tijuana
1994Established in India
+9,000Employees globally
50%+Engineers focused on software
100%CMMI Maturity Level 5 certified
Businesses We Serve
Aerospace Home and Building Technologies
Performance Materials and Technologies
Safety and Productivity Solutions
PRESENTATION ON
CII NATIONAL AWARD FOR EXCELLENCE IN ENERGY MANAGEMENT
30th to 31st Aug 2018
BYReshmi Shankar Aravind Mamidi
Sholapur Vijay Kumar
Building 1 Building 2 Remarks
No of Floors G+4 G+2
Area 125733 Sq. ft. 28000 Sq. ft.
Year of operation 2008 2016
Contracted demand 1550 kva
MAX Demand 1163 kva
DG capacity 1055 X2 Kva ,380 Kva 1 no's
Occupancy 99% ( 1250 )
Operating Hours 9 hours 5 days week 9 Hours 5 days week Labs(12000 sq ft area), Go Direct Flight services and server rooms operates 24X7
Annual energy use is around 34 lakh KWH with the spend of 2.75 crores , Including Diesel cost
Site profile -- HTS Hyderabad, Telangana
Installation of solar water heater
Investment –Rs 70000
Savings – 14151 KWh -INR 1,20,280
ROI - 0.6 years
Timer for street lights
Investment – INR 45000
Savings -4908 Kwh –INR 41,788
ROI – 0.9 years
LED street lights , cove lighting parkinglighting
Investment –Rs 685000
Savings – 61762 kwh , INR 5,24,927
ROI – 1.1 years
Installation of adiabatic system
Investment : INR 6 lakhs
Savings : 43334 Kwh INR 3,68,333
ROI 2.5 years
Installation new aerators for TapsInvestment – Rs 22 000Savings – 1141 Kwh Rs 9,700 ROI – 2.5 years
5
Energy Projects completed Years 2014-15
EC Fan installation for AHU
Investment – 25 lakhs
Saving Kwh - 70588 KWh INR 6,00.000
ROI -4.5 years
Installation of PAC unit for server room
Investment :INR 16 lakhs
Savings : 84902 Kwh INR 5,15,000
ROI -3.1 years
Replacement of UPS 60 kva to 10 kva
Investment : INR 5.4 lakhs
Savings : 14227 Kwh INR 1,28,000
ROI : 3.4 years
Solar thermal system Investment : INR 2.6 croresSavings 1.33 lakh units INR 11,96,000ROI 12 years
Energy Projects completed Years 2014-17 contd
Total energy saving achieved 6,73,312 kwh INR 57.23 lacs6
Occupancy control for conference room AC units.
Investment : INR 1.2 lacs
Savings : App 4500 kwh INR 38250
ROI : 4 years
Energy Projects Planned in the years 2018-19
Solar PV 100 kW
Investment :INR 55 lacs
Savings : 155000 Kwh INR 13.17 lacs
ROI -4.2 years - On Hold due to Phase III construction on Hold .
7
Wheeling energy PPA Investment TBDROI – TBDPrincipally got clearance from management
170072
254508
145000
103732
0
50000
100000
150000
200000
250000
300000
Kwh Saved
KWH saving Trend
2014 2015 2016 2017
THE
GREEN
METRICS
538.7 tons
57.23 lakhsINR
$85.42K
Co2 Mitigation
Monetary Saving
673312kWh
Power Saving
Energy Saving Trend
Specific Energy Consumption overview in 2014 - 2017
198
222
213
229
180
185
190
195
200
205
210
215
220
225
230
235
2014 2015 2016 2017
ENERGY PERFORMANCE INDICATOR (KWH/SQ.MT)
ENERGY SAVINGS TREND
2014 compared to 2013 – Saving 170,072 kWh
9
Baseline-2013 KWH 2,481,349
2014 Actual Consumption in KWH 2,875,177
2014 Normalized consumption in KWH 2,311,277
Savings Achieved in KWH 170,072
% of savings achieved in 2014 compared to 2013 7%
2,481,3492,311,277
2,875,177
2,000,000
1,500,000
1,000,000
500,000
-
3,000,000
2,500,000
3,500,000
Baseline-2013 KWH 2014 Normalized 2014 Actual Consumption consumption in KWH in KWH
Weather Impact
Increase in working days
Increase in Occupancy
Increase in Operational hours
Load Addition
© 2015 by Honeywell International Inc. All rights reserved.
Additional Disclaimers As Needed (Consult Legal)
ENERGY SAVINGS TREND
2015 compared to 2014 – 254,508 kWh
10
Baseline-2014 KWH 2,875,177
2015 Actual Consumption in KWH 3,200,945
2015 Normalized consumption in KWH 2,605,673
Savings Achieved in KWH 254,508
% of savings achieved in 2015 compared to 2014 9.37%
2,875,177
2,605,673
3,200,945
2,500,000
2,000,000
1,500,000
1,000,000
500,000
-
3,000,000
3,500,000
Baseline-2014 KWH 2015 Normalized consumption in KWH
2015 Actual Consumption in KWH
Increase in
Occupancy
Increase in operational hours
Load Addition
Weather Impact
© 2015 by Honeywell International Inc. All rights reserved.
Additional Disclaimers As Needed (Consult Legal)
ENERGY SAVINGS TREND
2016 compared to 2015 145,308 KWH
kWh
11
Baseline-2015 KWH 3,200,945
2016 Actual Consumption in KWH 3,384,374
2016 Normalized consumption in KWH 3,055,637
Savings Achieved in KWH 145,308
% of savings achieved in 2016 compared to 2015 4.54%
3150000
3100000
3050000
3200000
3250000
3300000
3350000
3400000
2015 Actual 2016 Normalized 2016 Actual
Increase in operational hours
Increase in
Occupancy
Load Addition
Weather Impact
3,200,945
© 2015 by Honeywell International Inc. All rights reserved.
Additional Disclaimers As Needed (Consult Legal)
3,055,637
3,384,374
ENERGY SAVINGS TREND
2017 compared to 2016 103,732 KWH
kWh
11
Baseline-2016 KWH 3,384,374
2017 Actual Consumption in KWH 3,660,856
2017 Normalized consumption in KWH 3,280,642
Savings Achieved in KWH 103,732
% of savings achieved in 2016 compared to 2015 3.07%
3200000
3100000
3000000
3300000
3400000
3500000
3600000
3700000
2016 Actual 2017 Normalized 2017 Actual
Increase in operational hours
Increase in
Occupancy
Load Addition
Weather Impact
3,384,374
© 2015 by Honeywell International Inc. All rights reserved.
Additional Disclaimers As Needed (Consult Legal)
3,280,642
3,660,856
Total Cumulative savings for last 4 years 23.98%
Energy Distribution- Year 2016 HTS Hyderabad
Highest power consumption in HAVC and UPS loads
14
HVAC39%
UPS28%
Utility5%
Lighting10%
Raw power6%
café& EMC lab12%
KWH
HVAC UPS Utility Lighting Raw power café& EMC lab
HVAC
BMSintegration
Ambientair supplyin winter
Adiabatic system
Solar VAM
system
EC Fans for AHU
Energy saving projects In HVAC area
THE
GREEN
METRICS
191.1 tons
20.30 Lakh
INR
$30.3
Co2 Mitigation
Monetary Saving
238885kWh
Power Saving
15
Monitoring , Command Control & Data reporting
Energy Meters online monitoring
UPS Online monitoring DG Online monitoring
Chiller online monitoring
17
Monitoring , Command Control & Data reporting
Scope 1 Diesel consumed for electricity 0.47 Mt CO2e
Year Fuel consumed in litersEmission factor
(CO2e/unit)Total GHG emission in Mt CO2e
2013 31000 0.00268963 0.08
2014 33583 0.00268963 0.09
2015 39520 0.00268963 0.11
2016 35604 0.00268963 0.10
2017 33236 0.00268963 0.09
18
Scope 2 Indirect Emissions from Electricity 13.03 Mt CO2e
Year Energy consumption in KWHEmission factor
(CO2e/unit)Total GHG emission in Mt CO2e
2013 2542745 0.00082839 2.11
2014 2943785 0.00082839 2.44
2015 3305427 0.00082839 2.74
2016 3384112 0.00082839 2.80
2017 3546190 0.00082839 2.94
Scope 3 Fleet Vehicle Emissions 0.6 Mt CO2e
Year Fuel consumed in litersEmission factor
(CO2e/unit)GHG emission CO2 (M t CO2e)
2013 44400 0.00269 0.119
2014 44489 0.00269 0.120
2015 46713 0.00269 0.126
2016 49049 0.00269 0.132
2017 47216 0.00269 0.127
GHG Inventorisation
Apr-18 May-18 Jun-18
STP oulet 681 656 673
Garden usage fressh water 345 459 311
Total Garden usage 1026 1115 984
0
200
400
600
800
1000
1200
Wat
er C
on
sum
pti
on
in
KL
water usage for garden/landscape
Water usage & its control
Planned drip irrigation project in 2018 with investment of Rs22 lakhs ROI 3.2 years
Organic waste composting2840 2765 2843 2652
2465
19582123
0
500
1000
1500
2000
2500
3000
Jan-18 Feb-18 Mar-18 Apr-18 May-18 Jun-18 Jul-18
Total waste conversion 1.7 tons
Employee Engagement – Appreciation form leadership
Safety and Energy conversation pledge
Car/Bike pool app introduced to reduce carbon foot print
Awards and Recognition- HTS India - Hyderabad
28
Best Development Centre for HTS,
Hyderabad by Hyderabad Software
Enterprises Association, India
Solar Thermal System Installation
recognition for best
demonstration project HTS,
Hyderabad campus
Energy Efficient Unit
Certification By CII for HTS,
Hyderabad campus in the year
2017
Honeywell HYD Wins Best
CSR award at 25th HYSEA
Awards;
HTS HYD wins The golden Peacock
Award in the Event of 19th July 2017
World Congress Environmental.
Honeywell Confidential - © 2017 by Honeywell International Inc. All rights reserved.
Winner of the ROSPA Safety award 2018
29
Honeywell is building a smarter, safer,
and more sustainable world.
THAT’S THE POWER OF CONNECTED.
THAT’S THE POWER OF HONEYWELL.
ConnectedAircraft | ConnectedAutomobile | Connected Home | Connected Building
Connected Plant | Connected Supply Chain | Connected Worker
This document contains certain statements that may be deemed “forward-looking statements” within the meaning of Section 21E of the Securities Exchange Act of 1934. All statements, other than statements of historical fact, that address activities, events or developments that we or our management intends, expects, projects, believes or anticipates will
or may occur in the future are forward-looking statements. Such statements are based upon certain assumptions and assessments made by our management in light of their experience and their perception of historical trends, current economic and industry conditions, expected future developments and other factors they believe to be appropriate. The
forward-looking statements included in this release are also subject to a number of material risks and uncertainties, including but not limited to economic, competitive, governmental, and technological factors affecting our operations, markets, products, services and prices. Such forward-looking statements are not guarantees of future performance, and
actual results, developmentsand business decisions may differ from those envisaged by such forward-lookingstatements.We identify the principal risks and uncertainties that affect our performancein our Form 10-K and other filingswith the Securities and Exchange Commission.
Honeywell Confidential - © 2017 by Honeywell International Inc. All rights reserved.