‘r’ rated motor fuses - fusetek - 1-800-479-3875...5r 6r 9r 12r 18r 24r 36r 100 1000 10000...

12
2.75kV, 5.5kV & 8.3kV ‘R’ Rated Motor Fuses ‘R’ Rated Motor Fuses

Upload: others

Post on 31-Jan-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

  • 2.75kV, 5.5kV & 8.3kV ‘R’ Rated Motor Fuses

    ‘R’ Rated Motor Fuses

  • MVR ‘R’ Rated Motor FusesMVR ‘R’ Rated Motor Fuses

    ‘R’ Rated Motor Fuses

    MVR fuses are current and energy limiting fuses intended for the backup protection of medium voltage motor control. They are non-venting.

    MVR fuses have integral striker/indicators and have standardized dimensions compatible with today’s 5.5kV motor control gear. They are fully interchangeable with other manufacturers’ fuses of the same type and rating.

    They feature a ‘field toughened’ element design which makes them less susceptible to mechanical damage during shipping and instal-lation while also providing superior cycling characteristics.

    Features

    • Integral indicating pin

    • Standard “R” Ratings

    • Toughened element design

    • Fully plated parts

    Standard Hook-eye Bolt-in Extended

    1B

    GE 1B-Bolt-in

    1iB

    GE 1iB-bolt-inInverted

    MVR Series General Specifications

    Series Vac I.R Clip Diam Clip centers Ratings Options

    MVR2 2.75kV

    50kA rms symm 3”

    7” (178mm) 25A, 30A, 2R, 3R, 4R, 5R, 6R, 9R, 12R, 18R,

    24R, 36R

    B,Y,S

    MVR5 5.5kV 12” (305mm) B,Y,S,X,1B,1iB

    MVR8 8.3kV 12” (305mm) B,Y,S

    Options

    Standard fuses are clip-in design with 3” diameter barrels (18R - 36R are double barrel designs) and have an integral striker/in-dicator pin. Several options are available to make them compatible with other manufacturers’ specialized designs. Add suffixes to the part number as required. More than one option can be specified.

    All options are not available in some voltages.

  • MVR ‘R’ Rated Motor FusesMVR ‘R’ Rated Motor Fuses

    Medium voltage LED line Indicators

    Bolt these line indicators onto any convenient live part and the high brightness LED cluster will flash to indicate pres-ence of voltage. Rated for 2.5kV - 38kV

    Epoxy Resin Insulators

    We carry a range of epoxy resin insulators from 7.2kV to 38kV. Tapped brass inserts can accomodate a wide range of equipment.

    HV Accessories

    600 Amp clip for 3” diameter barrels

    Steel backup spring for high pressure contact.Compatible with any 3” diameter fuse.

    p/n. FC3R

    Hookeye Add on

    Hookeye kit is compatible with any 3” diameter fuse. May be ordered separately.

    p/n. Hookeye

    p/n. KF22-12

    p/n. refer to Fusetek

    Medium Voltage Microswitch

    Need more than visual indication? Our remote mount mi-croswitch is good for all systems up to 38kV. The insulated Bowden cable is actuated by the fuse striker which then actuates the microswitch at the other end.

    p/n. 3100110

    Medium voltage bases

    Fusetek can supply single or 3 pole bases for most of the medium voltage fuses we supply.

    p/n. refer to Fusetek

  • MVR ‘R’ Rated Motor FusesMVR ‘R’ Rated Motor Fuses

    RMS Amperes

    1000.01

    0.1

    10

    100

    1

    1000 10000 100000

    8.3kV Total Clearing Time Current Characteristics

    2R3R4R5R6R9R12R18R24R36R

    Tim

    e in

    Sec

    onds

  • MVR ‘R’ Rated Motor FusesMVR ‘R’ Rated Motor Fuses

    Part Number System

    MV R 5 / 09R - DI XYS

    Installation Notes:

    1. When replacing ‘R’ fuses, always replace with the same ‘R’ rating to maintain coordination and motor starting capability.

    2. These fuses can replace any manufacturers’ fuse of same ‘R’ rating.

    3. Ensure that fuse clips have good tension. (if you can spin the fuse in the clips easily, clips should be replaced.)

    4. Clean all contact surfaces before installation.

    5. Install with striker pin facing up.

    6. Unless the cause of fuse failure is known to have been confined to 1 phase, fuses should be replaced in sets of 3 to ensure ‘As new’ performance.

    R Rating Defined

    The ‘R’ rating of a fuse is established by dividing the 20-35s melt cur-rent of the fuse by 100.

    Fuses of the same ‘R’ rating will have the same time current character-istics and ensure identical motor starting performance and coordination with the overload relays.

    Technical data presented.

    Amp Rating

    Each fuse has both an assigned ‘R’ and amp rating. It is the ‘R’ rating of the fuse that governs the motor starting capability and coordi-nation with the overload relays. To maintain the same capabilities, fuses should be replaced with matching ‘R’ ratings.

    On direct across the line starts, the necessity of passing the motor starting current results in a fuse selection with an assigned amp rating well above the nominal motor full load amps.

    However, applications using reduced voltage starts, variable frequency drives or other methods to reduce the motor starting current, can result in a fuse rating with an amp rating too close to the motor F.L.A. As a check, the fuse’s assigned full load amp rating should be a minimum of 140% of the nominal full load amps of the motor.

    MV Series 5 09R DI XYS

    Medium Voltage R Motor Fuse Voltage Class Rating Body Size Option Modifier

    2 = 2.75kV 25A, 30A2R, 3R4R, 5R6R, 9R

    12R, 18R24R, 36R

    D = Single 3” I = Striker (standard)X = 2” extensionB = Bolt-inS = Div. 1, class llY = Hookeye1B = GE Tags1iB = GE inverted tags

    5 = 5.5kV DD = Double 3”

    8 = 8.3kV

    9R200A

  • MVR ‘R’ Rated Motor FusesMVR ‘R’ Rated Motor Fuses

    Peak Let-thru Characteristics

    Use these characteristics to evaluate busbar bracing requirements and withstand capability of down-the-line components.

    Read RMS fault value on lower scale and read up to where it intersects the line for the fuse you are evaluating. From this intersec-tion point, read across to the left hand scale to obtain the peak current let-thru. Note: this value is in peak asymmetrical amperes. To convert to RMS symmetrical, divide by 2.3. Peak let-thru graph is valid for all voltage classes.

    Time current Characteristic curves.

    Time current curves shown on pages 4-6 are minimum melting curves. For total clearing, please refer to the curves on pages 7-9.

    Characteristic curves are generated with the fuse at an ambient temperature of 24-26 C. Ambient temperatures higher than 30 C may require fuse de-rating. Please contact Fusetek in this instance.

    24R (450A)

    18R (390A)12R (230A)

    9R (200A)

    6R (170A)5R (150A)4R (130A)3R (100A)

    2R (700A)

    25A/30A

    RMS Symmetrical Amperes

    Peak

    Let

    -Thr

    u - A

    ssym

    met

    rical

    Am

    pere

    s X

    1000

    5 6 7 8 9 10 20.01

    .02

    .03

    .04

    .05

    .06

    .07

    .08

    .09

    1

    2

    3

    4

    56789

    1

    .2

    .3

    .4

    .5

    .6

    .7

    .8

    .9

    10

    20

    30

    40

    5060708090

    100

    30 40 50 60 70 80 90 100

    200

    300

    400

    500

    600

    700

    800

    900

    1000

    2000

    3000

    4000

    5000

    6000

    8000

    9000

    1000

    0

    2000

    0

    3000

    0

    4000

    0

    5000

    060

    000

    7000

    080

    000

    9000

    010

    0000

    7000

    Motor Application Tables.

    Standard duty is defined as: 2 evenly spaced starts per hour, 25o

    C ambient temperature, 10 second run-up time and a starting current of no more than 6X the nominal full load amp of the motor.

    If any of these parameters are exceeded - use the heavy duty (HD) column.

    • Select the appropriate HP rating in the left column

    • Read across to the appropriate voltage and duty column (Std or HD)

    • Use the ‘R’ rating of fuse specified

    • 5.5kV fuses may be used on 2.3kV control.

    The graphic on the right is a screen shot from our free Fusesoft 5.0 fuse selection software and shows the ideal coordination between the fuse, overload relay and motor starting current. The motor starting tables were generated using this software. Fusesoft 5.0 can be downloaded at no charge by visiting www.fusetek.com

    o o

  • MVR ‘R’ Rated Motor FusesMVR ‘R’ Rated Motor Fuses

    Total Clearing time current characteristics

    0.01

    0.1

    10

    100

    1

    Tim

    e in

    Sec

    onds

    100 1000 10000 100000

    30A2R3R4R5R6R9R

    12R18R24R36R

    5.5kV Total Clearing Time Current Characteristics

    RMS Amperes

    5.5kV Total Clearing Time Current Characteristic

  • MVR ‘R’ Rated Motor FusesMVR ‘R’ Rated Motor Fuses

    Total Clearing time current characteristics

    These time current curves have been plotted to maximum test points so any variations should be negative. Curves are based on tests at an ambient of 25 C with fuses starting from cold with no initial load.

    Tim

    e in

    Sec

    onds

    25A2R3R4R5R6R9R

    12R18R24R

    2.75kV Total Clearing Time Current Characteristics

    0.01

    0.1

    10

    100

    1

    100 1000 10000 100000RMS Amperes

    2.75kV Total Clearing Time Current Characteristic

    o

  • MVR ‘R’ Rated Motor FusesMVR ‘R’ Rated Motor Fuses

    2.75kV Peak Current Let-through

    Available Current in Amperes

    Peak

    inst

    anta

    neou

    s Le

    t Thr

    ough

    cur

    rent

    in K

    ilo A

    mpe

    res

    24R

    25A

    18R

    9R/12R6R5R4R3R2R

    .2

    .3

    .4

    .5

    .6

    .7

    .8

    .91

    2

    345678910

    20

    30

    405060708090

    100

    100

    200

    300

    400

    500

    600

    700

    800

    900

    1000

    2000

    3000

    4000

    5000

    6000

    7000

    8000

    9000

    1000

    0

    3000

    0

    2000

    0

    4000

    050

    000

    6000

    070

    000

    8000

    090

    000

    1000

    00

    2.75kV Motor Fuses - 7” clip center

    General Specifications

    PartNumber

    A F.L.A.D x L

    (inches)I.RkA

    Avail.Options

    MVR2/025A-DI 25A 25A 3 10.8

    50kArms

    B,Y,S

    MVR2/02R-DI 2R 70 3 10.8

    MVR2/03R-DI 3R 100 3 10.8

    MVR2/04R-DI 4R 130 3 10.8

    MVR2/05R-DI 5R 150 3 10.8

    MVR2/06R-DI 6R 170 3 10.8

    MVR2/09R-DI 9R 200 3 10.8

    MVR2/12R-DI 12R 230 3 10.8

    MVR2/18R-DDI 18R 390 2X3 10.8

    MVR2/24R-DDI 24R 450 2X3 10.8

    2.75kV Minimum Melt Time Current Characteristics

    Fuse selection for Motors rated at 2.75kV or less

    Motor HPFuse ‘R’ rating

    Standard Duty Heavy Duty

    100 2R 2R

    150 3R 3R

    200 4R 5R

    250 4R 5R

    300 5R 6R

    350 6R 6R

    400 9R 9R

    450 9R 9R

    500 9R 12R

    600 12R 12R

    700 12R 18R

    800 18R 18R

    900 18R 18R

    1000 18R 24R

    1250 24R 24R

    25A2R3R4R5R6R9R12R18R24R

    RMS Amperes

    Tim

    e in

    sec

    onds

    100 1000 10000 1000000.01

    0.1

    1

    10

    100

    2.75 kVPeak Current Let-through

    10.88”276.35mm

    10.88”276.35mm

    3”76.2mm

    3”76.2mm

    .63” max16mm

    3”76.2mm

    .63” max16mm

    6.31” 160mm

    3”76.2mm

    D

    DD

  • MVR ‘R’ Rated Motor FusesMVR ‘R’ Rated Motor Fuses

    5.5kV Motor Fuses - 12” clip center

    General Specifications

    PartNumber

    A F.L.A.D x L

    (inches)I.RkA

    Avail.Options

    MVR5/030A-DI 30A 30A 3 15.8

    50kArms

    B.Y.S,X

    MVR5/02R-DI 2R 70 3 15.8

    MVR5/03R-DI 3R 100 3 15.8

    MVR5/04R-DI 4R 130 3 15.8

    MVR5/05R-DI 5R 150 3 15.8

    MVR5/06R-DI 6R 170 3 15.8

    MVR5/09R-DI 9R 200 3 15.8

    MVR5/12R-DI 12R 230 3 15.8

    MVR5/18R-DDI 18R 390 2X3 15.8

    MVR5/24R-DDI 24R 450 2X3 15.8

    MVR5/36R-DDI 36R 650 2X3 15.8

    Fuse selection for Motors rated at 5.5kV or less

    Motor HPFuse ‘R’ rating

    Standard Duty Heavy Duty

    100 30A 30A

    150 2R 2R

    200 2R 2R

    250 3R 3R

    300 3R 3R

    350 3R 4R

    400 4R 5R

    450 4R 5R

    500 5R 6R

    600 5R 6R

    700 6R 9R

    800 9R 9R

    900 9R 12R

    1000 9R 12R

    1250 12R 18R

    1500 18R 18R

    30A2R3R4R5R6R9R12R18R24R36R

    100 1000 10000 1000000.01

    0.1

    1

    10

    100

    RMS Amperes

    Tim

    e in

    sec

    on

    ds

    5.5kV Minimum Melt Time Current Characteristics

    5.5 kV Peak Current Let-through

    15.88”403mm

    15.88”403mm

    3”76.2mm

    3”76.2mm

    .63” max16mm

    3”76.2mm

    .63” max16mm

    6.31” 160mm

    3”76.2mm

    D

    DD

    2.75kV Peak Current Let-through

    Available Current in Amperes

    Peak

    inst

    anta

    neou

    s Le

    t Thr

    ough

    cur

    rent

    in K

    ilo A

    mpe

    res 36R

    24R

    30A

    18R

    9R/12R6R5R4R3R2R

    .2

    .3

    .4

    .5

    .6

    .7

    .8

    .91

    2

    345678910

    20

    30

    405060708090

    100

    100

    200

    300

    400

    500

    600

    700

    800

    900

    1000

    2000

    3000

    4000

    5000

    6000

    7000

    8000

    9000

    1000

    0

    3000

    0

    2000

    0

    4000

    050

    000

    6000

    070

    000

    8000

    090

    000

    1000

    00

  • 8.3kV Motor Fuses - 12” clip center

    General Specifications

    PartNumber

    A F.L.A.D x L

    (inches)I.RkA

    Avail.Options

    MVR8/02R-DI 2R 70 3 15.8

    50kArms

    B.Y.S

    MVR8/03R-DI 3R 100 3 15.8

    MVR8/04R-DI 4R 130 3 15.8

    MVR8/05R-DI 5R 150 3 15.8

    MVR8/06R-DI 6R 170 3 15.8

    MVR8/09R-DI 9R 200 3 15.8

    MVR8/12R-DI 12R 230 3 15.8

    MVR8/18R-DDI 18R 390 2X3 15.8

    MVR8/24R-DDI 24R 450 2X3 15.8

    MVR8/36R-DDI 36R 650 2X3 15.8

    Fuse selection for Motors rated at 8.3kV or less

    Motor HPFuse ‘R’ rating

    Standard Duty Heavy Duty

    250 2R 2R

    300 2R 2R

    350 2R 2R

    400 2R 3R

    450 3R 3R

    500 3R 4R

    600 3R 4R

    700 4R 5R

    800 4R 5R

    900 5R 6R

    1000 5R 6R

    1250 6R 9R

    1500 9R 12R

    1000.01

    0.1

    1

    10

    100

    1000 10000 100000

    2R3R4R5R6R9R

    12R18R24R36R

    RMS AMPERES

    Tim

    e in

    sec

    on

    ds

    8.3 kVPeak Current Let-through

    8.3kV Minimum Melt Time Current Characteristics

    8.3kV Peak Current Let-through

    Available Current in Amperes

    Peak

    inst

    anta

    neou

    s Le

    t Thr

    ough

    cur

    rent

    in K

    ilo A

    mpe

    res 36R

    24R18R

    9R/12R6R5R4R3R2R

    .2

    .3

    .4

    .5

    .6

    .7

    .8

    .91

    2

    345678910

    20

    30

    405060708090

    100

    100

    200

    300

    400

    500

    600

    700

    800

    900

    1000

    2000

    3000

    4000

    5000

    6000

    7000

    8000

    9000

    1000

    0

    3000

    0

    2000

    0

    4000

    050

    000

    6000

    070

    000

    8000

    090

    000

    1000

    00

    15.88”403mm

    15.88”403mm

    3”76.2mm

    3”76.2mm

    .63” max16mm

    3”76.2mm

    .63” max16mm

    6.31” 160mm

    3”76.2mm

    D

    DD

    MVR ‘R’ Rated Motor FusesMVR ‘R’ Rated Motor Fuses

  • Head Office

    599 Norris CourtKingston, On. K7P2R9

    Toll Free T: 800-479-3875Toll free F: 800-866-7690

    Intl T: 613-384-4144Intl F: 613-384-0167

    E: [email protected]: www.fusetek.compub: MVR09-1 Printed in Canada

    Other Medium Voltage Products

    - ‘E’ Rated Distribution Fuse to 28.8kV

    - DIN Distribution Fuses to 38kV

    - Load Break Switches to 38kV

    - Capacitor Fuses

    - Adapter Kits & Live Parts

    - Remote Indicator Kits

    - Clips & Insulators

    - PT Fuses to 38kV

    Dimensions - Standard

    15.88”403mm

    17.8”457mm

    19.3”490mm

    3”76.2mm

    3”76.2mm

    .44” X .91” Slots(1.53” c.t.c.)

    3”76.2mm

    .63” max16mm

    .63” max16mm

    3”76.2mm

    3.6”91.4mm

    7.6”193mm

    Front view

    Dimensions - ‘B’ bolt-in

    Dimensions - GE TagsDimensions for GE tags are dictated by the GE starters they fit into.

    15.88”403mm

    15.88”403mm

    3”76.2mm

    3”76.2mm

    .63” max16mm

    3”76.2mm

    .63” max16mm

    6.31” 160mm

    3”76.2mm

    D

    DD