d ‘r’ rated motor fuses - fusetek - 1-800-479-3875....63” max 16mm.63” max 16mm 3” 76.2mm...
TRANSCRIPT
Head Office
599 Norris CourtKingston, On. K7P2R9
Toll Free T: 800-479-3875Toll free F: 800-866-7690
Intl T: 613-384-4144Intl F: 613-384-0167
E: [email protected]: www.fusetek.com
2.75kV, 5.5kV & 8.3kV ‘R’ Rated Motor Fuses
pub: MVR09-1 Printed in Canada
Other Medium Voltage Products
- ‘E’ Rated Distribution Fuse to 28.8kV
- DIN Distribution Fuses to 38kV
- Load Break Switches to 38kV
- Capacitor Fuses
- Adapter Kits & Live Parts
- Remote Indicator Kits
- Clips & Insulators
- PT Fuses to 38kV
Dimensions - Standard
15.88”403mm
17.8”457mm
19.3”490mm
3”76.2mm
3”76.2mm
.44” X .91” Slots(1.53” c.t.c.)
3”76.2mm
.63” max16mm
.63” max16mm
3”76.2mm
3.6”91.4mm
7.6”193mm
Front view
Dimensions - ‘B’ bolt-in
Dimensions - GE TagsDimensions for GE tags are dictated by the GE starters they fi t into.
15.88”403mm
15.88”403mm
3”76.2mm
3”76.2mm
.63” max16mm
3”76.2mm
.63” max16mm
6.31” 160mm
3”76.2mm
D
DD
‘R’ Rated Motor Fuses
KNOWLEDGE, SERVICE, SOLUTIONSMVR ‘R’ Rated Motor Fuses MVR ‘R’ Rated Motor FusesMVR ‘R’ Rated Motor Fuses MVR ‘R’ Rated Motor Fuses
‘R’ Rated Motor Fuses
MVR fuses are current and energy limiting fuses intended for the backup protection of medium voltage motor control. They are non-venting.
MVR fuses have integral striker/indicators and have standardized dimensions compatible with today’s 5.5kV motor control gear. They are fully interchangeable with other manufacturers’ fuses of the same type and rating.
They feature a ‘fi eld toughened’ element design which makes them less susceptible to mechanical damage during shipping and installation while also providing superior cycling characteristics.
Features
• Integral indicating pin
• Standard “R” Ratings
• Toughened element design
• Fully plated parts
Standard Hook-eye Bolt-in Extended
1B
GE 1B-Bolt-in
1iB
GE 1iB-bolt-inInverted
MVR Series General Specifi cationsSeries Vac I.R Clip Diam Clip centers Ratings OptionsMVR2 2.75kV
50kA rms symm 3”
7” (178mm) 25A, 30A, 2R, 3R, 4R, 5R, 6R, 9R, 12R, 18R,
24R, 36R
B,Y,SMVR5 5.5kV 12” (305mm) B,Y,S,X,1B,1iBMVR8 8.3kV 12” (305mm) B,Y,S
Options
Standard fuses are clip-in design with 3” diameter barrels (18R - 36R are double barrel designs) and have an integral striker/in-dicator pin. Several options are available to make them compatible with other manufacturers’ specialized designs. Add suffi xes to the part number as required. More than one option can be specifi ed.
All options are not available in some voltages.
Medium voltage LED line Indicators
Bolt these line indicators onto any convenient live part and the high brightness LED cluster will fl ash to indicate presence of voltage. Rated for 2.5kV - 38kV
Epoxy Resin Insulators
We carry a range of epoxy resin insulators from 7.2kV to 38kV. Tapped brass inserts can accomodate a wide range of equipment.
HV Accessories600 Amp clip for 3” diameter barrels
Steel backup spring for high pressure contact.Compatible with any 3” diameter fuse.
p/n. FC3R
Hookeye Add on
Hookeye kit is compatible with any 3” diameter fuse. May be ordered separately.
p/n. Hookeye
p/n. KF22-12
p/n. refer to Fusetek
Medium Voltage Microswitch
Need more than visual indication? Our remote mount microswitch is good for all systems up to 38kV. The insulated Bowden cable is actu-ated by the fuse striker which then actuates the microswitch at the other end.
p/n. 3100110
Medium voltage bases
Fusetek can supply single or 3 pole bases for most of the medium voltage fuses we supply.
p/n. refer to Fusetek
KNOWLEDGE, SERVICE, SOLUTIONSMVR ‘R’ Rated Motor Fuses MVR ‘R’ Rated Motor FusesMVR ‘R’ Rated Motor Fuses MVR ‘R’ Rated Motor Fuses
Part Number System
MV R 5 / 09R - DI XYS
Installation Notes:
1. When replacing ‘R’ fuses, always replace with the same ‘R’ rating to maintain coordination and motor starting capability.
2. These fuses can replace any manufacturers’ fuse of same ‘R’ rating.
3. Ensure that fuse clips have good tension. (if you can spin the fuse in the clips easily, clips should be replaced.)
4. Clean all contact surfaces before installation.
5. Install with striker pin facing up.
6. Unless the cause of fuse failure is known to have been confi ned to 1 phase, fuses should be replaced in sets of 3 to ensure ‘As new’ performance.
R Rating Defi ned
The ‘R’ rating of a fuse is established by dividing the 20-35s melt current of the fuse by 100.
Fuses of the same ‘R’ rating will have the same time current characteristics and ensure identical motor start-ing performance and coordination with the overload relays.
Technical data presented.
Amp Rating
Each fuse has both an assigned ‘R’ and amp rating. It is the ‘R’ rating of the fuse that governs the motor starting capability and coordination with the overload relays. To maintain the same capabilities, fuses should be replaced with matching ‘R’ ratings.
On direct across the line starts, the necessity of passing the motor starting current results in a fuse selection with an assigned amp rating well above the nominal motor full load amps.
However, applications using reduced voltage starts, variable frequency drives or other methods to reduce the motor starting current, can result in a fuse rating with an amp rating too close to the motor F.L.A. As a check, the fuse’s as-signed full load amp rating should be a minimum of 140% of the nominal full load amps of the motor.
MV Series 5 09R DI XYSMedium Voltage R Motor Fuse Voltage Class Rating Body Size Option Modifi er
2 = 2.75kV 25A, 30A2R, 3R4R, 5R6R, 9R
12R, 18R24R, 36R
D = Single 3” I = Striker (standard)X = 2” extensionB = Bolt-inS = Div. 1, class llY = Hookeye1B = GE Tags1iB = GE inverted tags
5 = 5.5kV DD = Double 3”8 = 8.3kV
9R200A
RMS Amperes
1000.01
0.1
10
100
1
1000 10000 100000
8.3kV Total Clearing Time Current Characteristics
2R3R4R5R6R9R12R18R24R36R
Tim
e in
Sec
onds
KNOWLEDGE, SERVICE, SOLUTIONSMVR ‘R’ Rated Motor Fuses MVR ‘R’ Rated Motor FusesMVR ‘R’ Rated Motor Fuses MVR ‘R’ Rated Motor Fuses
Total Clearing time current characteristics
0.01
0.1
10
100
1
Tim
e in
Sec
onds
100 1000 10000 100000
30A2R3R4R5R6R9R12R18R24R36R
5.5kV Total Clearing Time Current Characteristics
RMS Amperes
5.5kV Total Clearing Time Current Characteristic
Peak Let-thru Characteristics
Use these characteristics to evaluate busbar bracing requirements and withstand capability of down-the-line components.
Read RMS fault value on lower scale and read up to where it intersects the line for the fuse you are evaluating. From this intersec-tion point, read across to the left hand scale to obtain the peak current let-thru. Note: this value is in peak asymmetrical amperes. To convert to RMS symmetrical, divide by 2.3. Peak let-thru graph is valid for all voltage classes.
Time current Characteristic curves.
Time current curves shown on pages 4-6 are minimum melting curves. For total clearing, please refer to the curves on pages 7-9.
Characteristic curves are generated with the fuse at an ambient temperature of 24-26 C. Ambient temperatures higher than 30 C may require fuse de-rating. Please contact Fusetek in this instance.
24R (450A)
18R (390A)12R (230A)
9R (200A)
6R (170A)5R (150A)4R (130A)3R (100A)
2R (700A)
25A/30A
RMS Symmetrical Amperes
Peak
Let
-Thr
u - A
ssym
met
rical
Am
pere
s X
1000
5 6 7 8 9 10 20.01
.02
.03
.04
.05
.06
.07
.08
.09
1
2
3
4
56789
1
.2
.3
.4
.5
.6
.7
.8
.9
10
20
30
40
5060708090
100
30 40 50 60 70 80 90 100
200
300
400
500
600
700
800
900
1000
2000
3000
4000
5000
6000
8000
9000
1000
0
2000
0
3000
0
4000
0
5000
060
000
7000
080
000
9000
010
0000
7000
Motor Application Tables.
Standard duty is defined as: 2 evenly spaced starts per hour, 25o C ambient temperature, 10 second run-up time and a starting current of no more than 6X the nominal full load amp of the motor.
If any of these parameters are exceeded - use the heavy duty (HD) column.
• Select the appropriate HP rating in the left column
• Read across to the appropriate voltage and duty column (Std or HD)
• Use the ‘R’ rating of fuse specified
• 5.5kV fuses may be used on 2.3kV control.
The graphic on the right is a screen shot from our free Fusesoft 5.0 fuse selection software and shows the ideal coordination between the fuse, overload relay and motor starting current. The motor starting tables were generated using this software. Fusesoft 5.0 can be downloaded at no charge by visiting www.fusetek.com
o o
KNOWLEDGE, SERVICE, SOLUTIONSMVR ‘R’ Rated Motor Fuses MVR ‘R’ Rated Motor FusesMVR ‘R’ Rated Motor Fuses MVR ‘R’ Rated Motor Fuses
Total Clearing time current characteristics
These time current curves have been plotted to maximum test points so any variations should be negative. Curves are based on tests at an ambient of 25 C with fuses starting from cold with no initial load.
Tim
e in
Sec
onds
25A2R3R4R5R6R9R
12R18R24R
2.75kV Total Clearing Time Current Characteristics
0.01
0.1
10
100
1
100 1000 10000 100000RMS Amperes
2.75kV Total Clearing Time Current Characteristic
o
2.75kV Peak Current Let-through
Available Current in Amperes
Peak
inst
anta
neou
s Le
t Thr
ough
cur
rent
in K
ilo A
mpe
res
24R
25A
18R
9R/12R6R5R4R3R2R
.2
.3
.4
.5
.6
.7
.8
.91
2
345678910
20
30
405060708090
100
100
200
300
400
500
600
700
800
900
1000
2000
3000
4000
5000
6000
7000
8000
9000
1000
0
3000
0
2000
0
4000
050
000
6000
070
000
8000
090
000
1000
00
2.75kV Motor Fuses - 7” clip center
General Specifi cationsPart
Number A F.L.A. D x L(inches)
I.RkA
Avail.Options
MVR2/025A-DI 25A 25A 3 10.8
50kArms B,Y,S
MVR2/02R-DI 2R 70 3 10.8MVR2/03R-DI 3R 100 3 10.8MVR2/04R-DI 4R 130 3 10.8MVR2/05R-DI 5R 150 3 10.8MVR2/06R-DI 6R 170 3 10.8MVR2/09R-DI 9R 200 3 10.8MVR2/12R-DI 12R 230 3 10.8
MVR2/18R-DDI 18R 390 2X3 10.8MVR2/24R-DDI 24R 450 2X3 10.8
2.75kV Minimum Melt Time Current Characteristics
Fuse selection for Motors rated at 2.75kV or less
Motor HPFuse ‘R’ rating
Standard Duty Heavy Duty100 2R 2R150 3R 3R200 4R 5R250 4R 5R300 5R 6R350 6R 6R400 9R 9R450 9R 9R500 9R 12R600 12R 12R700 12R 18R800 18R 18R900 18R 18R1000 18R 24R1250 24R 24R
25A2R3R4R5R6R9R12R18R24R
RMS Amperes
Tim
e in
sec
onds
100 1000 10000 1000000.01
0.1
1
10
100
2.75 kVPeak Current Let-through
10.88”276.35mm
10.88”276.35mm
3”76.2mm
3”76.2mm
.63” max16mm
3”76.2mm
.63” max16mm
6.31” 160mm
3”76.2mm
D
DD
KNOWLEDGE, SERVICE, SOLUTIONSMVR ‘R’ Rated Motor Fuses MVR ‘R’ Rated Motor FusesMVR ‘R’ Rated Motor Fuses MVR ‘R’ Rated Motor Fuses
5.5kV Motor Fuses - 12” clip center
General Specifi cationsPart
Number A F.L.A. D x L(inches)
I.RkA
Avail.Options
MVR5/030A-DI 30A 30A 3 15.8
50kArms
B.Y.S,X
MVR5/02R-DI 2R 70 3 15.8MVR5/03R-DI 3R 100 3 15.8MVR5/04R-DI 4R 130 3 15.8MVR5/05R-DI 5R 150 3 15.8MVR5/06R-DI 6R 170 3 15.8MVR5/09R-DI 9R 200 3 15.8MVR5/12R-DI 12R 230 3 15.8
MVR5/18R-DDI 18R 390 2X3 15.8MVR5/24R-DDI 24R 450 2X3 15.8MVR5/36R-DDI 36R 650 2X3 15.8
Fuse selection for Motors rated at 5.5kV or less
Motor HPFuse ‘R’ rating
Standard Duty Heavy Duty
100 30A 30A
150 2R 2R200 2R 2R250 3R 3R300 3R 3R350 3R 4R400 4R 5R450 4R 5R500 5R 6R600 5R 6R700 6R 9R800 9R 9R900 9R 12R1000 9R 12R1250 12R 18R1500 18R 18R
30A2R3R4R5R6R9R12R18R24R36R
100 1000 10000 1000000.01
0.1
1
10
100
RMS Amperes
Tim
e in
sec
on
ds
5.5kV Minimum Melt Time Current Characteristics
5.5 kV Peak Current Let-through
15.88”403mm
15.88”403mm
3”76.2mm
3”76.2mm
.63” max16mm
3”76.2mm
.63” max16mm
6.31” 160mm
3”76.2mm
D
DD
2.75kV Peak Current Let-through
Available Current in Amperes
Peak
inst
anta
neou
s Le
t Thr
ough
cur
rent
in K
ilo A
mpe
res 36R
24R
30A
18R
9R/12R6R5R4R3R2R
.2
.3
.4
.5
.6
.7
.8
.91
2
345678910
20
30
405060708090
100
100
200
300
400
500
600
700
800
900
1000
2000
3000
4000
5000
6000
7000
8000
9000
1000
0
3000
0
2000
0
4000
050
000
6000
070
000
8000
090
000
1000
00
8.3kV Motor Fuses - 12” clip center
General Specifi cationsPart
Number A F.L.A. D x L(inches)
I.RkA
Avail.Options
MVR8/02R-DI 2R 70 3 15.8
50kArms B.Y.S
MVR8/03R-DI 3R 100 3 15.8MVR8/04R-DI 4R 130 3 15.8MVR8/05R-DI 5R 150 3 15.8MVR8/06R-DI 6R 170 3 15.8MVR8/09R-DI 9R 200 3 15.8MVR8/12R-DI 12R 230 3 15.8
MVR8/18R-DDI 18R 390 2X3 15.8MVR8/24R-DDI 24R 450 2X3 15.8MVR8/36R-DDI 36R 650 2X3 15.8
Fuse selection for Motors rated at 8.3kV or less
Motor HPFuse ‘R’ rating
Standard Duty Heavy Duty
250 2R 2R
300 2R 2R350 2R 2R400 2R 3R450 3R 3R500 3R 4R600 3R 4R700 4R 5R800 4R 5R900 5R 6R1000 5R 6R1250 6R 9R1500 9R 12R
1000.01
0.1
1
10
100
1000 10000 100000
2R3R4R5R6R9R
12R18R24R36R
RMS AMPERES
Tim
e in
sec
on
ds
8.3 kVPeak Current Let-through
8.3kV Minimum Melt Time Current Characteristics
8.3kV Peak Current Let-through
Available Current in Amperes
Peak
inst
anta
neou
s Le
t Thr
ough
cur
rent
in K
ilo A
mpe
res 36R
24R18R
9R/12R6R5R4R3R2R
.2
.3
.4
.5
.6
.7
.8
.91
2
345678910
20
30
405060708090
100
100
200
300
400
500
600
700
800
900
1000
2000
3000
4000
5000
6000
7000
8000
9000
1000
0
3000
0
2000
0
4000
050
000
6000
070
000
8000
090
000
1000
00
15.88”403mm
15.88”403mm
3”76.2mm
3”76.2mm
.63” max16mm
3”76.2mm
.63” max16mm
6.31” 160mm
3”76.2mm
D
DD