Appendix G Redlands & Cottonwood Booster Electrical Replacement Emergency Standby Generator Sizing Report

Upload: others

Post on 16-Oct-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Appendix G - emwd.org

Appendix G

Redlands & Cottonwood Booster

Electrical Replacement

Emergency Standby Generator Sizing Report

Page 2: Appendix G - emwd.org

[PAGE LEFT INTENTIONALLY BLANK]

Page 3: Appendix G - emwd.org

Eastern Municipal Water District (EMWD)

Redlands and Cottonwood Booster Electrical

Replacement

Emergency Standby Generator Sizing Report

October 14, 2020

Prepared by:

5 Hutton Centre Drive, Suite 500

Santa Ana, CA 92707

949.472.3505 Telephone

949.472.8373 Fax

Page 4: Appendix G - emwd.org

Eastern Municipal Water District (EMWD)

Redlands and Cottonwood Booster Electrical Replacement

Generator Sizing Report

PAGE | 2

Generator Sizing Report

The generator sizing criteria for Redlands and Cottonwood Booster Pump station are based on the

following:

Design criteria:

Maximum Voltage Dip: 20%

Maximum Frequency Dip: 20%

Generator loads:

1. 125HP motor with VFD and 110% current limit

2. 100HP motor with VFD and 110% current limit

3. 15KVA transformer loads

Generator Steps:

Step 1 loads: 125HP motor and 15KVA transformer loads

Step 2 loads: 100HP motor

The generator sizing software used for this project is Caterpillar’s Specsizer. See Appendix A for details

calculation report.

Conclusion:

To provide backup power for 125HP motor, 100HP motor and 15KVA transformer loads, a minimum of

250KW rated generator will be needed. See Appendix B for generator cutsheet, dimensions, integral fuel

tank and sound attenuation enclosure information.

Page 5: Appendix G - emwd.org

Eastern Municipal Water District (EMWD) Redlands and Cottonwood Booster Pump Station Generator Sizing Report

APPENDIX A

Page 6: Appendix G - emwd.org

Pro

ject

Siz

ing

Rep

ort

Pro

ject

Nam

eR

edla

nd B

oost

er P

S Im

prov

emen

tsE

lect

ricity

Sup

ply

60 H

z 48

0/27

7 V

Cus

tom

er N

ame

EM

WD

Con

nect

ion

STA

R

Reg

ion

U.S

.M

ax. A

mbi

ent T

empe

ratu

re77

.0 F

Pre

pare

d B

yY

ee P

ing

See

Alti

tude

500.

0 Ft

. A.S

.L

Mod

ified

Dat

e12

-Aug

-202

0H

umid

ity30

%

Load

Ana

lysi

s S

umm

ary

Max

Tra

nsie

nt L

oad

Ste

p26

.6 S

kVA

/ 24

.0 S

kW

Pea

k Tr

ansi

ent L

oad

Ste

p23

5.3

SkV

A /

211.

8 S

kW

Fina

l Run

ning

Loa

d22

6.2

kVA

/ 20

3.3

kW /

0.90

PF

Max

Run

ning

Non

Lin

ear L

oad

225.

5 R

kVA

Max

imum

Run

ning

Loa

d22

6.2

kVA

/ 20

3.3

kW

Sel

ectio

n C

riter

iaS

tep

2 N

on-li

near

load

requ

irem

ents

Gen

erat

or S

et

Gen

erat

or S

et M

odel

(1) o

f C9

Nam

epla

te R

atin

g25

0.0

ekW

/ 31

2.5

kVA

/ 0.

8 P

F

Vol

tage

Reg

ulat

or a

nd S

lope

IVR

2:1

slo

pe;

Site

Out

put R

atin

g25

0 ek

W /

312.

5 kV

A

Feat

ure

Cod

eC

09D

E47

Rat

ing

Type

Sta

ndby

Fuel

Die

sel

Ope

n / E

nclo

sure

Ope

n

Siz

ing

Met

hodo

logy

Con

vent

iona

lU

L Li

sted

Yes

Cap

acity

Use

d81

.3%

Eng

ine

Mak

e/M

odel

C9

Em

issi

ons

/ Cer

tific

atio

nsE

PA

ES

E

Asp

iratio

nTA

Gov

erno

rE

LEC

Cyl

inde

r Con

figur

atio

nIN

LIN

E -

6A

fterc

oole

r Typ

eA

TAA

C

Spe

ed18

00 R

PM

Dis

plac

emen

t53

7 C

ubic

Inch

/ 9

Lite

r

Page 7: Appendix G - emwd.org

Eng

ine

Per

form

ance

Num

ber

DM

8501

Bor

e11

2

Fuel

Con

sum

ptio

n at

100

% L

oad

19.1

gph

Stro

ke14

9

Alte

rnat

or

Alte

rnat

or T

ype/

Fram

e S

ize

LC /

LC50

14J

Insu

latio

n C

lass

H

Alte

rnat

or W

indi

ng P

itch

0.66

67Te

mpe

ratu

re R

ise

105

C

Exc

itatio

n/W

indi

ng T

ype

SE

/ R

AN

DO

MN

umbe

r Of P

oles

4

Alte

rnat

or A

rran

gem

ent N

umbe

r44

9057

5N

umbe

r of L

eads

12

Sub

trans

ient

Rea

ctan

ce X

''d0.

0749

Rat

ed A

mps

375.

9

****

See

you

r Cat

erpi

llar d

eale

r and

/or S

pec

She

et fo

r tec

hnic

al in

form

atio

n.

****

* P

acka

ge P

ower

Tol

eran

ce: +

/- 5%

Blo

ck L

oad(

Onl

y) T

rans

ient

Res

pons

e *

Load

Cha

nge

%FD

ip %

VD

ip %

Rec

over

y Ti

me

(sec

)

0 - 2

5<5

%5.

4<

3

0 - 5

06.

612

.4<

3

0 - 7

59.

217

.6<

3

0 - 1

0013

.526

.2<

3

0 - 1

00 L

oad

Cha

nge

%

0

< 3

Rec

over

y Ti

me

(sec

)

Tran

sien

t Per

form

ance

Blo

ck L

oad

(onl

y) T

rans

ient

Res

pons

e va

lues

are

at f

acto

ry c

ondi

tions

with

a re

sist

ive

load

. Thi

s in

form

atio

n is

repr

esen

tativ

e of

a ty

pica

l Cat

gen

erat

or s

et, b

ut is

not

gua

rant

eed.

Gen

erat

or s

et b

lock

load

ca

pabi

litie

s at

site

con

ditio

ns m

ay v

ary

from

fact

ory

trans

ient

resp

onse

test

resu

lts d

ue to

site

alti

tude

, site

am

bien

t, an

d en

gine

to e

ngin

e va

riatio

n.

Page 8: Appendix G - emwd.org

Load

Rep

ort

Pro

ject

Nam

eR

edla

nd B

oost

er P

S Im

prov

emen

tsE

lect

ricity

Sup

ply

60 H

z 48

0/27

7 V

Cus

tom

er N

ame

EM

WD

Rat

ing

Type

Sta

ndby

Reg

ion

U.S

.M

ax. A

mbi

ent T

empe

ratu

re77

.0 F

Pre

pare

d B

yY

ee P

ing

See

Alti

tude

500.

0 Ft

. A.S

.L

Mod

ified

Dat

e12

-Aug

-202

0H

umid

ity30

%

Gen

erat

or S

et M

odel

(1) o

f C9

Nam

epla

te R

atin

g25

0.0

ekW

/ 31

2.5

kVA

/ 0.

8 P

F

Load

Det

ails

Per

mitt

edP

redi

cted

Tran

sien

t Inr

ush

Run

ning

Res

ulta

nt P

eak

Cum

ulat

ive

Run

ning

Load

Ste

pLo

ad D

escr

iptio

nFD

ipV

Dip

FDip

VD

ipS

kVA

SkW

kVA

kWS

kVA

SkW

kVA

kW

Ste

p 1

1.1

1x12

5.00

HP

- P

ump

2: N

EM

A, 3

-Pha

se M

otor

, V

FD, 1

10%

Cur

rent

Lim

it, S

ingl

e O

pera

ting

Poi

nt, 6

20

%20

%11

.610

.511

6.4

104.

7

1.2

1x15

.00

kVA

- Tr

ansf

orm

er L

oad:

Ste

ady

Sta

te

Mag

netiz

atio

n, 9

8% E

ffici

ency

, 208

V S

econ

dary

-

-0.

00.

00.

80.

1

1.3

1x15

.00

kVA

- E

quip

men

t Loa

d: O

ffice

Equ

ipm

ent,

Dis

tr. 3

-Pha

se20

%20

%15

.013

.515

.013

.5

Ste

p 1

Tota

l20

%20

%<5

%<5

%26

.624

.013

2.1

118.

6

Tota

l Thr

ough

Ste

p 1

143.

012

8.7

132.

111

8.6

Ste

p 2

2.1

1x10

0.00

HP

- P

ump

3: N

EM

A, 3

-Pha

se M

otor

, V

FD, 1

10%

Cur

rent

Lim

it, S

ingl

e O

pera

ting

Poi

nt, 6

20

%20

%9.

48.

594

.284

.7

Ste

p 2

Tota

l20

%20

%<5

%<5

%9.

48.

594

.284

.7

Tota

l Thr

ough

Ste

p 2

235.

321

1.8

226.

220

3.3

Load

Ana

lysi

s S

umm

ary

: Gen

erat

or s

et m

eets

site

requ

irem

ents

Max

imum

Ste

pM

axim

um P

eak

Fina

l Run

ning

SkV

AS

kWS

kVA

SkW

kVA

kW

26.6

24.0

235.

321

1.8

226.

220

3.3

Page 9: Appendix G - emwd.org

Eastern Municipal Water District (EMWD) Redlands and Cottonwood Booster Pump Station Generator Sizing Report

APPENDIX B

Page 10: Appendix G - emwd.org

CATERPILLAR ENGINE DIVISION TECHNICAL COMMUNICATIONS GROUP Installation Drawing Index AutoCAD 2013 Format

Installation Drawing No. 4557122 chg 05

Overall Dimensions:

C9 SA L2 ENCLOSURE W/660 GALLON TANK

Length =

Width =

Height =

4515.30 mm

2055.90 mm

2831.00 mm

Engine pricing arrangements found on drawing:

Attachment pricing arrangements found on drawing:

LS0249 chg 01

LS1838 chg 00 LS1843 chg 00 4490661 chg 00

LS1839 chg 00 LS1845 chg 00 4490662 chg 00

LS1840 chg 00 LS1869 chg 00 4529865 chg 00

LS1841 chg 00 3745706 chg 00

4557122A.dwg = Summary of LS-0249 CHG 01 shown. (sheet1)

LS0249

4557122B.dwg = Right side view, top view, and rear view of LS-0249 CHG 01 shown. (sheet2)

View A-A

Page 11: Appendix G - emwd.org
Page 12: Appendix G - emwd.org
Page 13: Appendix G - emwd.org

LEHE1567-00

.

CAT® GENERATOR SET PACKAGE

Cat generator set packages have been fully prototype tested and certified torsional vibration analysis reports are available. The packages are designed to meet the NFPA 110 requirement for loading, conform to the ISO 8528-5 steady state and fill transient response requirements.

CAT DIESEL ENGINES The four-cycle Cat diesel engine combines consistent performance with excellent fuel economy and transient response that meets or exceeds ISO 8528-5. The engines feature a reliable, rugged, and durable design that has been field proven in thousands of applications worldwide in emergency standby installations.

ENGINE SPECIFICATIONS

Engine Model Cat® C9 ACERT In-line 6, 4-cycle diesel

Bore x Stroke 112mm x 149mm (4.4in x 5.9in)

Displacement 8.8 L (538 in³)

Compression Ratio 16.1:1

Aspiration Turbocharged Air-to-Air Aftercooled

Fuel Injection System MEUI

Governor Electronic ADEM™ A4

Emission Certifications

EPA Tier 3 - EPA Stationary Emergency

GENERATOR SET SPECIFICATIONS

Alternator Design Brushless Single Bearing, 4 Pole

Stator 2/3 Pitch

No. of Leads 12

Available Voltage Options 600V/480V/240V/208V

Frequency 60Hz

Alternator Voltage 24V

Alternator Insulation & IP Class H; IP23

Standard Temperature Rise 150 Deg C

Available Excitation Options

Self-Excited, AR

Voltage Regulation, Steady State +/- ≤0.5%

COOLING SYSTEM The cooling system has been designed and tested to ensure proper generator set cooling, and includes the radiator, fan, belts, and all guarding installed as standard. Contact your Cat dealer for specific ambient and altitude capabilities.

GENERATORS The generators used on Cat packages have been designed and tested to work with the Cat engine. The generators are built with robust Class H insulation and provide industry-leading motor starting capability and altitude capabilities.

EMCP CONTROL PANELS The EMCP controller features the reliability and durability you have to come to expect from your Cat equipment. The EMCP 4 is a scalable control platform designed to ensure reliable generator set operation, providing extensive information about power output and engine operation. EMCP 4 systems can be further customized to meet your needs through programming and expansion modules.

200ekW 180ekW

Standby Prime

Cat® C9 DIESEL GENERATOR SETS

250ekW 225ekW

300ekW 275ekW

1/10

Page 14: Appendix G - emwd.org

LEHE1567-00

STANDARD EQUIPMENT

Air inlet system Aftercooler core, Turbocharger.

Control panels EMCP4.2 control panel.

Cooling system

Coolant drain line with valve; terminated on edge of base.

Fan and belt guards.

Coolant Level Sensor

Thermostats and housing, full open temperature 92 deg C (198 deg F). Coolant level sight gauge. Jacket water pump, gear driven, centrifugal.

Exhaust system Exhaust manifold; dry.

Fuel system

Primary fuel filter w/integral water separator & secondary filter.

Fuel cooler.

Fuel priming pump.

Flexible fuel lines.

Engine fuel transfer pump.

Generators and generator attachments

Brushless, self-excited 2/3 pitch, random wound.

IP23 Protection.

Insulation Class H and temperature rise

Power center, IP22 bottom cable entry

Segregated low voltage wiring panel

Governing system Cat Electronic Governor (ADEM A4).

Lube system

Oil cooler.

Lubricating oil.

Oil filter and dipstick.

Oil drain lines with valve; piped to edge of base. - Fumes disposal; piped to front of radiator.

Starting/charging system

24-volt electric starting motor.

24V, 45 amp charging alternator.

General Paint, Caterpillar Yellow.

Vibration damper.

OPTIONAL EQUIPMENT

Air inlet system

STD AIR CLEANER

Single Element Air Cleaner

Dual Element Air Cleaner

Control panels

EMCP 4.4

Local & Remote Annunciator

Discrete I/O Module

Circuit Breakers

Power terminal strips- 800A & 600A

3-Pole 100% Rated- Single (Manual & Motorised)

3-Pole 100% Rated- Dual (Manual)

3-Pole 100% Rated- Third (Manual)

External Paralleling

Enclosures

Weather Protective

Sound Attenuated

Aluminium Enclosures

Cooling system Stone guards.

Exhaust system

Industrial grade (10 dBA)

Residential and Critical grade (25 dBA)

Industrial grade (10 dBA)

Fuel storage Sub Tank & Integral tank Bases

Generators and generator attachments

Space heater control

Permanent magnet generator

Mounting system Captive linear vibration isolators

Starting/charging system

Battery Chargers

Jacket Water Heater

General Tool Set.

2/10

Cat® C9 DIESEL GENERATOR SETS

Page 15: Appendix G - emwd.org

LEHE1567-00

Genset Package Dim “A” mm (in)

Dim “B” mm (in)

Dim “C” mm (in)

Open Generator Set Weight (Dry)1

kg (lb)

Maximum Weight (Dry)2

kg (lb) Standby Prime

200 ekW 180 ekW 3091 (122) 1622 (64) 2066 (82) 2157 (4755) 2692 (5935)

250 ekW 225 ekW 3091 (122) 1622 (64) 2066 (82) 2248 (4956) 2692 (5935)

300 ekW 275 ekW 3091 (122) 1622 (64) 2066 (82) 2313 (5100) 2908 (6411)

1Estimated weight includes standard generator, narrow skid base and heaviest mechanically operated standard single circuit breaker. 2Estimated weight includes oversize generator, wide skid base and heaviest circuit breaker configuration.

WEIGHTS & DIMENSIONS

3/10

A B

C

Cat® C9 DIESEL GENERATOR SETS

Page 16: Appendix G - emwd.org

LEHE1567-00

• UL Listed for United States (UL 142) and Canada (CAN/ULC S601)

• Facilitate compliance with NFPA 30 code, NFPA 37 and 110 standards and CSA C282 code.

• Dual wall • Lockable fuel fill cap, 4” (101.6mm) NPT • Low fuel level warning standard, customer configurable

warning or shutdown Primary tank leak detection switch in containment basin.

• Tank design provides capacity for thermal expansion of fuel

• Fuel supply dip tube is positioned so as not to pick up fuel sediment

• Fuel return and supply dip tube is separated by an internal baffle to prevent immediate re-supply of heated return fuel

• Pressure washed with an iron phosphate solution • Interior tank surfaces coated with a solvent-based thin-

film rust preventative • Heavy guage steel gussets with internal lifting rings • Primary and secondary tanks are leak tested at 20.7 kPa

(3 psi) minimum • Compatible with open packages and enclosures • Gloss black polyester alkyd enamel exterior paint • Welded steel containment basin (minimum of 110% of

primary tank capacity) • Direct reading fuel gauge with variable electrical output • Emergency vents on primary and secondary tanks are

sized in accordance with NFPA 30

Cat® C9 INTEGRAL & SUB BASE FUEL TANKS

FEATURES

Sub Base • The sub-base fuel tank mounts below the

generator set wide base

Image shown might not reflect actual configuration

Options • Audio/visual fuel level alarm panel • 5gal (18.9 L) spill containment • 5gal (18.9 L) spill containment with fuel fill drop

tube with in 6” (152mm) from bottom of tank. • 5gal (18.9 L) spill containment with overfill

prevention valve and fuel fill drop tube with in 6” (152mm) from bottom of tank

• ULC Listed 7.5gal (28.4 L) spill containment with vent extensions, vent whistle, and drop tube facilitating compliance with CSA B139-09.

• ULC Listed 7.5gal (28.4 L) spill containment with overfill prevention valve, vent extensions, vent whistle and drop tube facilitating compliance with CSA B139-09

Integral Base • Integral diesel fuel tank is incorporated into the

generator set base frame. • Robust base design includes linear vibration

isolators between tank base and engine generator.

3/10

WEATHER PROTECTIVE & SOUND ATTENUATED FUEL TANKS

Page 17: Appendix G - emwd.org

LEHE1567-00

Integral & Sub-Base Fuel Tank Base Capacities with Fuel Tank Dimensions & Weights Integral – Width (W) 2014 mm (79.3 in); Sub-base – Width (W) 2056 mm (81.0 in)

Open Set, Weather Protective Enclosure & Sound Attenuated

Cat® C9 INTEGRAL & SUB BASE FUEL TANKS

C9 Tank

Design

Feature Code

Total Capacity

Useable Capacity

Tank Only Overall Package Height with Tank

Dry Weight

Height ‘H’ Length ‘L’ Open Weather

Protective Sound

Attenuated

Litre

Gallon

Litre

Gallon kg lb m

m in mm in mm in mm in mm in

Integral FTDW010 784 207 770 203 891 1964 635 25.0 3810 150.0 2360 90.0 2438 96.0 2492 98.1

Sub-Base FTDW008 2476 654 2435 643 1468 3236 635 25.0 3810 150.0 2699 106.3 2777 109.4 2831 111.5

Sub-Base FTDW009 3941 1041 3876 1024 1832 4039 635 25.0 5550 219.0 2699 106.3 2777 109.4 2831 111.5

Sub-Base FTDW012 4285 1132 4221 1115 1542 3399 686 27.0 5550 219.0 5550 219.0 2750 108.3 2828 111.4

C9 Tank Design

Feature Code

Standby Ratings (ekW) Prime Ratings (ekW)

300 250 200 275 225 180

Integral FTDW010 9 11 13 10 11 14

Sub-Base FTDW008 28 33 42 30 35 46

Sub-Base FTDW009 45 53 67 48 56 73

Sub-Base FTDW012 48 57 72 52 60 79

Estimated Run Times (hours) at 100% Load

Width

Length

Height,

STUB UP AREA

4/10

Page 18: Appendix G - emwd.org

LEHE1567-00

5/10

Notes:

The heights listed above do not include lumber used during manufacturing and shipping.

Tanks with full electrical stub-up area include removable end channel. Tanks with RH/LH stub-up include stub-up area directly below the circuit breaker or power terminal strips. Dimensions include weather-protective enclosure exhaust system.

Dual wall sub-base tanks are UL Listed and constructed in accordance with UL Standard for Safety UL 142, Steel Aboveground Tanks for Flammable and Combustible Liquids and Canada CAN/ULC S601, Standard for Shop Fabricated Steel Aboveground Horizontal Tanks for Flammable and Combustible Liquids.

Fuel tanks and applicable options facilitate compliance with the following United States NFPA Code and Standards: NFPA 30: Flammable and Combustible Liquids Code NFPA 37: Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines NFPA 110: Standard for Emergency and Standby Power Systems

Fuel tanks and applicable options facilitate compliance with the following Canadian Standard and Code: CSA C282 – Emergency Electrical Power Supply for Buildings CSA B139-09 – Installation Code for Oil-Burning Equipment The following sub-base fuel tanks meet Chicago code for containment and labelling: FTDW008 FTDW009 FTDW012

Cat® C9 INTEGRAL & SUB BASE FUEL TANKS

Page 19: Appendix G - emwd.org

LEHE1567-00

Cat® C9 ENCLOSURES

Robust/Highly Corrosion Resistant Construction • Factory-installed on skid base

• Environmentally friendly, polyester powder baked paint

• Zinc plated or stainless steel fasteners.

• Internally mounted-critical exhaust silencing system (sound attenuated only)

• Externally front-mounted enclosed exhaust

• silencing system (weather protective only)

• Designed and tested to comply with UL 2200 listed generator set package.

• Compression door latches providing solid door seal Excellent Access • Large cable entry area for installation ease.

• Accommodates side-mounted single or multiple breakers

• Two doors on both sides

• Vertically hinged allow 180° opening rotation and retention with door stays.

• Lube oil and coolant drains routed to the exterior of the enclosure base.

Transportability • These enclosures are of extremely rugged construction to

withstand outdoor exposure and rough handling common on many construction sites.

• Security and Safety

• Lockable access doors which give full access to control panel and breaker.

• Cooling fan and battery charging alternator fully guarded

• Fuel fill, oil fill, and battery can only be reached via lockable access.

• Externally mounted emergency stop button

• Designed for spreader bar lifting to ensure safety

• Stub-up area is rodent proof.

FEATURES

SOUND ATTENUATED & HIGH AMBIENT ENCLOSURES

60 Hz

Options • Caterpillar yellow* or white paint

• Weather protective enclosure constructed with14-gauge steel

• Sound attenuated Level 1 constructed with 14-gauge steel

• Sound attenuated Level 2 constructed with 14-gauge steel

• Sound attenuated enclosure constructed with 12-gauge aluminum (5052 grade)

• UL Listed 203 gallon integral fuel tank

• UL Listed 660 or 1002 gallon sub base fuel tanks

• Seismic certification per applicable building codes:

• IBC 2000, IBC 2003, IBC 2006,

• IBC 2009, IBC 2012, CBC 2007, CBC 2010

• IBC certification for 150 mph wind loading

• Anchoring details are site specific and are dependent on many factors such as generator set size, weight and concrete strength.

• IBC certification requires that the anchoring system used is reviewed and approved by a professional engineer.

• Control panel viewing window**

• Cold weather bundle. Available with SA Level 2 and Aluminum SA enclosures only.

These Sound Attenuated & High Ambient, factory installed enclosures incorporate internally mounted super critical level silencers

and residential level silencers respectively, designed for safety and aesthetic value on integral fuel tank base or optional dual wall

integral fuel tank base for total fluid containment. These enclosures are of extremely rugged construction to withstand exposure to

the elements and provide weather protection.

7/10

**Not available with aluminum enclosures **Steel sound attenuated only

Page 20: Appendix G - emwd.org

LEHE1567-00

Cat® C9 ENCLOSURES

Enclosure Package Operating Characteristics

*Cooling system performance at sea level. Consult your Caterpillar dealer for site specific ambient and altitude capabilities. The sound pressure level data shown in the tables above is quoted as free field and is for guidance only. Actual levels produced may vary according to site conditions.

ENCLOSURE TYPE

STANDBY ekW

PRIME ekW

COOLING AIR FLOW RATE

AMBIENT CAPABILITY* (DBA) @ 7M (23 FT)

AT 100% LOAD Standby Prime

m3/min cfm ˚C ˚F ˚C ˚F

SOUND ATTENUATED

LEVEL 2

300 275 351 12395 46 115 50 122 71

250 225 351 12395 53 127 56 133 71

200 180 351 12395 59 138 60 140 71

SOUND ATTENUATED

LEVEL 1

300 275 351 12395 46 115 50 122 75

250 225 351 12395 53 127 56 133 74

200 180 351 12395 59 138 60 140 73

300 275 516 18222 49 120 52 126 82

WEATHER PROTECTIVE

250 225 516 18222 55 131 59 138 82

200 180 516 18222 60 140 60 140 82

ALUMINUM SOUND

ATTENUATED

300 275 351 12395 46 115 46 115 72

250 225 351 12395 53 127 56 133 72

200 180 351 12395 59 138 60 140 72

Component Weights to Calculate Package Weight

Narrow Skid Wide Skid

Steel Enclosure Aluminum Enclosure

Weather Protective

Sound Attenuated Level 1

Sound Attenuated Level 2

Sound Attenuated

kg lb kg lb kg lb kg lb kg lb kg lb

219 483 468 1032 660 1455 1062 2341 1062 2341 629 1387

8/10

Page 21: Appendix G - emwd.org

LEHE1567-00

9/10

Enclosure Type

Length “L” Width “W” Height “H”

mm in mm in mm in

Sound Attenuated

4515 177.8 2037 80.2 2196 86.5

Weather Protective

4035 158.9 2037 80.2 2142 84.3

Enclosure Weights and Dimensions

A. Enclosure on Skid Base

C. Enclosure on UL Listed 203 Gallon Integral Fuel Tank Base

Enclosure Type

Length “L” Width “W” Height “H”

mm in mm in mm in

Sound Attenuated

4515 177.8 2014 79.3 2492 98.1

Weather Protective

4035 158.9 2014 79.3 2438 96.0

B. Enclosure on UL Listed 660 Gallon Sub Base Fuel Tank Base

Enclosure Type

Length “L” Width “W” Height “H”

mm in mm in mm in

Sound Attenuated

4515 177.8 2056 80.9 2831 111.5

Weather Protective

4035 158.9 2056 80.9 2777 109.3

Cat® C9 ENCLOSURES

D. Enclosure on UL Listed 1002 Gallon Sub Base Fuel Tank Base

Enclosure Type

Length “L” Width “W” Height “H”

mm in mm in mm in

Sound Attenuated

5739 225.9 2056 80.9 2831 111.5

Weather Protective

5739 225.9 2056 80.9 2777 109.3

Page 22: Appendix G - emwd.org

EMCP 4 control features • Run / Auto / Stop Control • Speed and Voltage Adjust • Engine Cycle Crank • 24-volt DC operation • Environmental sealed front face • Text alarm/event descriptions

Digital indication for: • RPM • DC volts • Operating hours • Oil pressure (psi, kPa or bar) • Coolant temperature • Volts (L-L & L-N), frequency (Hz) • Amps (per phase & average) • ekW, kVA, kVAR, kW-hr, %kW, PF (4.2 only)

Warning/shutdown with common LED indication of: • Low oil pressure • High coolant temperature • Overspeed • Emergency Stop • Failure to start (overcrank) • Low coolant temperature • Low coolant level

Cat® C9 DIESEL GENERATOR SETS

Programmable protective relaying functions: • Generator phase sequence • Over/Under voltage (27/59) • Over/Under Frequency (81 o/u) • Reverse Power (kW) (32) (4.2 only) • Reverse reactive power (kVAr) (32RV) • Overcurrent (50/51)

Communications:

• 4 digital inputs & 4 relay outputs (4.1) • 6 digital inputs & 8 relay outputs (4.2) • 12 digital inputs & 8 relay outputs (4.4) • Customer data link (Modbus RTU) (4.2 only) • Accessory module data link (4.2 only) • Serial annunciator module data link (4.2 only) • Emergency stop pushbutton

Compatible with the following:

• Digital I/O module • Local Annunciator • Remote CAN annunciator • Remote serial annunciator

www.Cat.com/electricpower ©2018 Caterpillar All rights reserved. Materials and specifications are subject to change without notice. The International System of Units (SI) is used in this publication. CAT, CATERPILLAR, their respective logos, ADEM, S•O•S, BUILT FOR IT, “Caterpillar Yellow”, the “Power Edge” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used

FINANCING Caterpillar offers an array of financial products to help you succeed through financial service excellence. Options include loans, finance lease, operating lease, working capital, and revolving line of credit. Contact your local Cat dealer for availability in your region.

EMCP 4 CONTROL KEY FEATURES

WORLDWIDE PRODUCT SUPPORT

Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Caterpillar® SOSSM program effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products.

LEHE1567-00 10/10